Telect Data Center Rack
description
Transcript of Telect Data Center Rack
data center rack
we simplify networks.TM
Ordering & Installation Guide
we simplify networks
racks
tough
secure
cool
Applies to : DR750-84430 :: DR750-84424 :: DR-84830 :: DR-84824 :: DR-84442 :: DR-84436 :: DR-84430 :: DR-84424 DR2000-84442 :: DR2000-84436 :: DR2000-84430 :: DR2000-84424 :: DR-84842 :: DR-84836 :: DR1250-84430 DR1250-84424 :: DR2000-84842 :: DR2000-84836 :: DR2000-84830 :: DR2000-84824 :: DR1250-84842 :: DR750-84830 DR1250-84836 :: DR1250-84830 :: DR1250-84824 :: DR1250-84442 :: DR1250-84436 :: DR750-84842 :: DR750-84824 DR750-84442 :: DR750-84436 DR750-84430 :: DR750-84842
Patents Pending
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
data center rack
we’re toughTelect’s new Earthquake-Safe Data Center Rack is a product to take pride in. Through its strength, seismic security and sheer good looks, you’ll be sure to demonstrate to the world that you do excellent work.
Imagine walking into a data center and seeing your namedisplayed proudly and prominently amongst rows and rowsof blank, no name racks. Telect wants you to serve thecloud in style. Through its rack-customizing program, you’llbe able to get private labels, custom color accents andunique configurations.
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
data center rack
we’re securePrimary Benefits
• Zone 4 certified• 2,000 lbs., 1,250 lbs. and 750 lbs.• Industry leading airflow doors above 80%• Compatible with OEM cooling solutions• Highly versatile and configurable• Ensuring safety of core equipment• Adjustable front and rear rails• Flexible equipment mounting• Robust design ensures reliable, long-term performance• Compatible with: - standard rack-mount equipment - a wide range of cable management solutions - Telect’s energy management strip
Panel Base Slot
Pull Latch Keeper
REV ECO DESCRIPTION DATE BY
NTSB1 of 1
drawing no designed by sheetrev sheet sizecustomer drawing dateunits
drawn by dateinch
scale project projection
copy
right
201
2te
lect
.com
::
1.50
9.92
6.60
00
.X
.XX
.XXX
tolerances (unless otherwise speci�ed)
CON
FID
ENTI
AL N
OT
FOR
REPR
OD
UCT
ION
±.060 ±.020 ±.010
±.005 ±1°
hole size:angularity:End Panel Assem A0
6/2/2011R118
G. HILBERT
B. Fuller
3/20/2012
USER MANUAL VIEWS
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
data center rack
we’re coolThe new rack offers earthquake protection accompaniedby more options for cable management, more workingroom than other deployed cabinets, and industry leadingairflow. The Telect team worked to ensure that the newcabinet would exceed current specifications and projectedfuture requirements.
Tested in switch offices and by stringent independent labs.This highly durable and versatile platform is sure not todisappoint the most veteran telecom engineers. Designedto accommodate servers, routers, batteries, and othercrucial network components, each cabinet is independentlyZone 4 seismic certified to hold up to 2,000 lbs., 1,250 lbs.and 750 lbs. of network equipment.
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
1
Data Center RacksRacks :: tough. secure. cool.
Panel Base Slot
Pull Latch Keeper
REV ECO DESCRIPTION DATE BY
NTSB1 of 1
drawing no designed by sheetrev sheet sizecustomer drawing dateunits
drawn by dateinch
scale project projection
copy
right
201
2te
lect
.com
::
1.50
9.92
6.60
00
.X
.XX
.XXX
tolerances (unless otherwise speci�ed)
CON
FID
ENTI
AL N
OT
FOR
REPR
OD
UCT
ION
±.060 ±.020 ±.010
±.005 ±1°
hole size:angularity:End Panel Assem A0
6/2/2011R118
G. HILBERT
B. Fuller
3/20/2012
USER MANUAL VIEWS
The ultimate equipment rack solution for core data center equipment, Telect’s Data Center Racks provide a seismic certified, highly durable and versatile platform for mounting equipment such as servers, routers, batteries and other crucial network components.
The Data Center Rack features enhanced durability and the ability to hold a broad range of network equipment. Each rack is independently Zone 4 seismic certified to hold up to 2,000 lbs,1250 lbs and 750 lbs of network equipment. Battery shelves are also compatible, making the rack ideal for core equipment or as a heavy duty battery rack.
1.1 Introduction
Ordering Guide
‣
‣
‣
‣
Design the perfect rack
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
2
Data Center RacksRacks ::
1.3 750 Data Center Rack Rack
• 84ʺ fixed height• 24ʺ & 28ʺ width (supporting 19ʺ & 23ʺ rack, respectively)• 24ʺ, 30ʺ, 36ʺ, 42ʺ depth
Panels
• Removable side panels• Six-post design, seismic Zone 4 rating, 750 lb certified• Multiple side entry points• Compatible with all standard rack-mount equipment
Options
• Adjustable cable management panels −6ʺ W x 24ʺ- 42ʺ D panel −10ʺ W x 24ʺ- 42ʺ D panel
• Power accessories: −Grounding package—wiring, buss bar, vertical power lacing bar −Vertical lacing bar for power cables −PDU mounting
Mounting
• Optional, adjustable front and rear mounting rails• Isolation pad
750 lb Rack with cable management
750 lb earthquake safe
NEBS tested Zone 4. Earthquake tested and ready if Seismic Anchor Kit is installed properly
Item SpecificationSeismic certification 750 lbs (340 kg)Physical specs, rack for 23" equipment mtg. 28ʺ W x 42" D x 84ʺ H (711 mm x 1067 mm x 2134 mm)
98 lbs (44kg)- 380 lbs (172 kg) *Additional Depths availablePhysical specs, rack for 19" equipment mtg. 24ʺ W x 42ʺ D x 84ʺ H (610 mm x 2134 mm)
90 lbs (41 kg) - 340 lbs (154 kg) *Additional Depths availableHole spacing EIA Wide RMU=1-¾ʺ (1/2ʺ, 1-¼ʺ), 44 RU
EIA Narrow RMU=1-¾ʺ (1/2ʺ, 5/8ʺ, 5/8ʺ), 44 RUUniversal RMU=1/2ʺ, 1/2ʺ, 1/2ʺ, 44 RU
Color Standard black, others availableCompliance GR-63-CORE, NEBS compliant, Zone 4 certified.
1.4 Specifications
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
3
Data Center RacksRacks :: tough. secure. cool.
Figure 1 - 19"Dimensions for 750 lb and part number DR750-84442, Front and Side View
Diagram Weight Part Number DimensionsA 750 lb DR750-84842 23.500B 750 lb DR750-84842 28.000
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
4
Data Center RacksRacks ::
Design the perfect rack
750 lb earthquake safe
Data Rack Mounting Rail EIA D Models DimensionsDR-MRGCTZ All Models CN/12-24DR-MRGTTZ All Models 12-24/12-24DR-MRGCTZP All Models CN/12-24 PlatedDR-MRGTTZP All Models 12-24/12-24 Plated
Adustable Cable Manager Models DimensionsACCE-DR6 All Models 6" Front and Rear OnlyACCE-DR10 All Models 10" Front and Rear OnlyACCE-DR6TS C, D, G, H 6" Through 24"-30" W/ HW (Qty2)ACCE-DR10TS C, D, G, H 10" Through 24"-30" W/ HW (Qty2)ACCE-DR6TD A, B, E, F 6" Through 36"-42" W/ HW (Qty2)ACCE-DR10TD A, B, E, F 10" Through 36"-42" W/ HW (Qty2)
Data Rack Model DimensionsDR750 Width Depth84842 A 28" 42"84836 B 28" 36"84830 C 28" 30"84824 D 28" 24"84442 E 24" 42"84436 F 24" 36"84430 G 24" 30"84424 H 24" 24"
End Panel Models DepthDREP-42 A, E 42"DREP-36 B, F 36"DREP-30 C, G 30"DREP-24 D, H 24"
Pick Model
Data Rack Mounting Rails 44RU Models DimensionsDR-MRCGP All Models Cage Nut Zinc Plated EIA-D (Qty 2)DR-MRGP-A All Models 12-24 Tapped Zinc Plated EIA-D (Qty 2) 23"-19"DR-MRCG-A A, B, C, D Cage Nut EIA-D (Qty 2) 23"-19"DR-MRCGP-A A, B, C, D Cage Nut Zinc Plated EIA-D (Qty 2) 23"-19"DR-MRGP-A A, B, C, D 12-24 Tapped Zinc Plated EIA-D (Qty 2) 23"-19"DR-MRCG-A A, B, C, D Cage Nut EIA-D (Qty 2) 23"-19"DR-MRG-A A, B, C, D 12-24 EIA-D (Qty 2) 23"-19"
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
5
Data Center RacksRacks :: tough. secure. cool.
Part Numbers Model ProductDR-TC28 A, B, C, D Data Rack Top Cap 28"DR-HGB-23 A, B, C, D Horizontal Ground Bar 23"DR-TC24 E, F, G, H Data Rack Top Cap 24"DR-TCC All Models Data Rack Top Cap Center Label HolderDR-TCB All Models Data Rack Top Cap Border Qty 2DRMR-AC All Models Data Rack AC Power BracketDRMR-ACD All Models Data Rack AC Power Bracket DualDR-GANG All Models Data Rack Ganging HardwareDR-HGB-19 All Models Horizontal Ground Bar 19"DR-ANCS All Models Seismic Anchor Data Center RackDR-CN50 All Models Data Rack Cage Nut Qty 50DR-CN100 All Models Data Rack Cage Nut Qty 10004500-50 All Models 12-24 Mounting Screws Qty 5004500-100 All Models 12-24 Mounting ScrewsDR-CDS All Models Cabinet Duct Spacer
Isolation Pad Model Width DepthDRISO-2842 A 28ʺ 42ʺDRISO-2836 B 28ʺ 36ʺDRISO-2830 C 28ʺ 30ʺDRISO-2824 D 28ʺ 24ʺDRISO-2442 E 24" 42"DRISO-2436 F 24" 36"DRISO-2430 G 24" 30"DRISO-2424 H 24" 24"ACCE-DR6ISO All Models 6" 6" for ACC-DR6ACCE-DR10ISO All Models 10" 6" for ACC-DR10
Part Number Model Width DoorsDRDP-28 A, B, C, D 28" Chrome Perforated DoorDRDBP-28 A, B, C, D 28" Black Perforated DoorDRDDP-28 A, B, C, D 28" Chrome Perforated Dual DoorDRDDBP-28 A, B, C, D 28" Black Perforated Dual DoorDRDP-24 E, F, G, H 24" Chrome Perforated DoorDRDBP-24 E, F, G, H 24" Black Perforated DoorDRDDP-24 E, F, G, H 24" Chrome Perforated Dual DoorDRDDBP-24 E, F, G, H 24" Black Perforated Dual Door
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
6
Data Center RacksRacks ::
1.5 1250 Data Center Rack
Rear View, Seismic Data CenterRack
1.6 Specifications
Item SpecificationSeismic certification 1,250 lbs (567 kg) Physical specs, rack for 23" equipment mtg.
28ʺ W x 42ʺ D x 84ʺ H (711 mm x 1067 mm x 2134 mm) 98 lbs (44kg) - 380 lbs (172 kg)*Additional Depths available
Physical specs, rack for 19" equipment mtg.
24" W x 42" D x 84" H (610 mm x 2134 mm) 90 lbs (41 kg) - 340 lbs (154 kg)*Additional Depths available
Hole spacing EIA Wide RMU=1-¾ʺ (1/2ʺ, 1-¼ʺ), 44 RUEIA Narrow RMU=1-¾ʺ (1/2ʺ, 5/8ʺ, 5/8ʺ), 44 RUUniversal RMU=1/2ʺ, 1/2ʺ, 1/2ʺ, 44 RU
Color Standard black, others availableCompliance GR-63-CORE, NEBS compliant, Zone 4 certified.
NEBS tested Zone 4. Earthquake tested and ready if Seismic Anchor Kit is installed properly
1250 lb earthquake safe
Rack
• 84ʺ fixed height• 24ʺ & 28ʺ width (supporting 19ʺ & 23ʺ rack, respectively)• 24ʺ, 30ʺ, 36ʺ, 42ʺ depth
Panels
• Removable side panels• Six-post design, seismic Zone 4 rating, 1250 lb certified• Multiple side entry points• Compatible with all standard rack-mount equipment
Options
• Adjustable cable management panels −6ʺ W x 24ʺ- 42ʺ D panel −10ʺ W x 24ʺ- 42ʺ D panel
• Power accessories: −Grounding package—wiring, buss bar, vertical power lacing bar −Vertical lacing bar for power cables −PDU mounting
Mounting
• Optional, adjustable front and rear mounting rails• Isolation pad
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
7
Data Center RacksRacks :: tough. secure. cool.
Diagram Weight Part Number DimensionsA 1250 lb DR1250-84842 23.500B 1250 lb DR1250-84842 28.000
Figure 2 - 19ʺ Dimensions for 1250 lb and part number DR1250-84442, Front and Side View
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
8
Data Center RacksRacks :: 1250 lb earthquake safe
Design the perfect rack
Data Rack Mounting Rail EIA D Models DimensionsDR-MRGCTZ All Models CN/12-24DR-MRGTTZ All Models 12-24/12-24DR-MRGCTZP All Models CN/12-24 PlatedDR-MRGTTZP All Models 12-24/12-24 Plated
Adustable Cable Manager Models DimensionsACCE-DR6 All Models 6" Front and Rear OnlyACCE-DR10 All Models 10" Front and Rear OnlyACCE-DR6TS C, D, G, H 6" Through 24"-30" W/ HW (Qty2)ACCE-DR10TS C, D, G, H 10" Through 24"-30" W/ HW (Qty2)ACCE-DR6TD A, B, E, F 6" Through 36"-42" W/ HW (Qty2)ACCE-DR10TD A, B, E, F 10" Through 36"-42" W/ HW (Qty2)
Data Rack Model DimensionsDR1250 Width Depth84842 A 28" 42"84836 B 28" 36"84830 C 28" 30"84824 D 28" 24"84442 E 24" 42"84436 F 24" 36"84430 G 24" 30"84424 H 24" 24"
End Panel Models DepthDREP-42 A, E 42"DREP-36 B, F 36"DREP-30 C, G 30"DREP-24 D, H 24"
Pick Model
Data Rack Mounting Rails 44RU Models DimensionsDR-MRCGP All Models Cage Nut Zinc Plated EIA-D (Qty 2)DR-MRGP-A All Models 12-24 Tapped Zinc Plated EIA-D (Qty 2) 23"-19"DR-MRCG-A A, B, C, D Cage Nut EIA-D (Qty 2) 23"-19"DR-MRCGP-A A, B, C, D Cage Nut Zinc Plated EIA-D (Qty 2) 23"-19"DR-MRGP-A A, B, C, D 12-24 Tapped Zinc Plated EIA-D (Qty 2) 23"-19"DR-MRCG-A A, B, C, D Cage Nut EIA-D (Qty 2) 23"-19"DR-MRG-A A, B, C, D 12-24 EIA-D (Qty 2) 23"-19"
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
9
Data Center RacksRacks :: tough. secure. cool.
Part Numbers Model ProductDR-TC28 A, B, C, D Data Rack Top Cap 28"DR-HGB-23 A, B, C, D Horizontal Ground Bar 23"DR-TC24 E, F, G, H Data Rack Top Cap 24"DR-TCC All Models Data Rack Top Cap Center Label HolderDR-TCB All Models Data Rack Top Cap Border Qty 2DRMR-AC All Models Data Rack AC Power BracketDRMR-ACD All Models Data Rack AC Power Bracket DualDR-GANG All Models Data Rack Ganging HardwareDR-HGB-19 All Models Horizontal Ground Bar 19"DR-ANCS All Models Seismic Anchor Data Center RackDR-CN50 All Models Data Rack Cage Nut Qty 50DR-CN100 All Models Data Rack Cage Nut Qty 10004500-50 All Models 12-24 Mounting Screws Qty 5004500-100 All Models 12-24 Mounting ScrewsDR-CDS All Models Cabinet Duct Spacer
Part Number Model Width DoorsDRDP-28 A, B, C, D 28" Chrome Perforated DoorDRDBP-28 A, B, C, D 28" Black Perforated DoorDRDDP-28 A, B, C, D 28" Chrome Perforated Dual DoorDRDDBP-28 A, B, C, D 28" Black Perforated Dual DoorDRDP-24 E, F, G, H 24" Chrome Perforated DoorDRDBP-24 E, F, G, H 24" Black Perforated DoorDRDDP-24 E, F, G, H 24" Chrome Perforated Dual DoorDRDDBP-24 E, F, G, H 24" Black Perforated Dual Door
Isolation Pad Model Width DepthDRISO-2842 A 28ʺ 42ʺDRISO-2836 B 28ʺ 36ʺDRISO-2830 C 28ʺ 30ʺDRISO-2824 D 28ʺ 24ʺDRISO-2442 E 24" 42"DRISO-2436 F 24" 36"DRISO-2430 G 24" 30"DRISO-2424 H 24" 24"ACCE-DR6ISO All Models 6" 6" for ACC-DR6ACCE-DR10ISO All Models 10" 6" for ACC-DR10
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
10
Data Center RacksRacks ::
1.7 2000 Data Center Rack
Data Center Rack with cable management
1.8 Specifications
Item SpecificationSeismic certification 2,000 lbs (907 kg) Physical specs, rack for 23" equipment mtg.
28" W x 42" D x 84" H (711 mm x 1067 mm x 2134 mm) 98 lbs (44kg) - 380 lbs (172 kg)*Additional Depths available
Physical specs, rack for 19" equipment mtg.
24" W x 42" D x 84" H (610 mm x 2134 mm) 90 lbs (41 kg) - 340 lbs (154 kg)*Additional Depths available
Hole spacing EIA Wide RMU=1-¾ʺ (1/2ʺ, 1-¼ʺ), 44 RUEIA Narrow RMU=1-¾ʺ (1/2ʺ, 5/8ʺ, 5/8ʺ), 44 RUUniversal RMU=1/2ʺ, 1/2ʺ, 1/2ʺ, 44 RU
Color Standard black, others availableCompliance GR-63-CORE, NEBS compliant, Zone 4 certified.
2000 lb earthquake safe
NEBS tested Zone 4. Earthquake tested and ready if Seismic Anchor Kit is installed properly
Rack
• 84ʺ fixed height• 24ʺ & 28ʺ width (supporting 19ʺ & 23ʺ rack, respectively)• 24ʺ, 30ʺ, 36ʺ, 42ʺ depth
Panels
• Removable side panels• Six-post design, seismic Zone 4 rating, 2000 lb certified• Multiple side entry points• Compatible with all standard rack-mount equipment
Options
• Adjustable cable management panels −6ʺ W x 24ʺ- 42ʺ D panel −10ʺ W x 24ʺ- 42ʺ D panel
• Power accessories: −Grounding package—wiring, buss bar, vertical power lacing bar −Vertical lacing bar for power cables −PDU mounting
Mounting
• Optional, adjustable front and rear mounting rails• Isolation pad
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
11
Data Center RacksRacks :: tough. secure. cool.
Figure 3 - 19ʺ Dimensions for 2000 lb and part number DR2000-84442, Front and Side View
84.000 79.656
19.500
24.000
Front View
4.739
16.000
4.739
42.000
Side View
5.709TYP
10.791TYP
2.000TYP
18.000TYP
4.906
4.906
1.00 X 8.00 SLOTTYP
Top View
TYP(6.200)
9.000TYP
5.000TYP
36.732
19.500
2.250TYP
2.634TYP
2.634TYP
2.250TYP
Bottom View
REV ECO DESCRIPTION DATE BY
NTSB1 of 1
drawing no designed by sheetrev sheet sizecustomer drawing dateunits
drawn by dateinch
scale project projection
copy
right
201
2te
lect
.com
::
1.50
9.92
6.60
00.X .XX .XXX
tolerances (unless otherwise specified)
CO
NFI
DEN
TIAL
NO
T FO
R R
EPR
OD
UC
TIO
N±.060 ±.020 ±.010
±.005 ±1°
hole size:angularity:DR2000-84442 A0
2/21/2012R118
G. HILBERT
S. SITTON
3/20/2012
USER MANUAL VIEWSDiagram Weight Part Number DimensionsA 2000 lb DR2000-84842 23.500B 2000 lb DR2000-84842 28.000
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
12
Data Center RacksRacks :: 2000 lb earthquake safe
Design the perfect rack
Data Rack Mounting Rail EIA D Models DimensionsDR-MRGCTZ All Models CN/12-24DR-MRGTTZ All Models 12-24/12-24DR-MRGCTZP All Models CN/12-24 PlatedDR-MRGTTZP All Models 12-24/12-24 Plated
Adustable Cable Manager Models DimensionsACCE-DR6 All Models 6" Front and Rear OnlyACCE-DR10 All Models 10" Front and Rear OnlyACCE-DR6TS C, D, G, H 6" Through 24"-30" W/ HW (Qty2)ACCE-DR10TS C, D, G, H 10" Through 24"-30" W/ HW (Qty2)ACCE-DR6TD A, B, E, F 6" Through 36"-42" W/ HW (Qty2)ACCE-DR10TD A, B, E, F 10" Through 36"-42" W/ HW (Qty2)
Data Rack Model DimensionsDR2000 Width Depth84842 A 28" 42"84836 B 28" 36"84830 C 28" 30"84824 D 28" 24"84442 E 24" 42"84436 F 24" 36"84430 G 24" 30"84424 H 24" 24"
End Panel Models DepthDREP-42 A, E 42"DREP-36 B, F 36"DREP-30 C, G 30"DREP-24 D, H 24"
Pick Model
Data Rack Mounting Rails 44RU Models DimensionsDR-MRCGP All Models Cage Nut Zinc Plated EIA-D (Qty 2)DR-MRGP-A All Models 12-24 Tapped Zinc Plated EIA-D (Qty 2) 23"-19"DR-MRCG-A A, B, C, D Cage Nut EIA-D (Qty 2) 23"-19"DR-MRCGP-A A, B, C, D Cage Nut Zinc Plated EIA-D (Qty 2) 23"-19"DR-MRGP-A A, B, C, D 12-24 Tapped Zinc Plated EIA-D (Qty 2) 23"-19"DR-MRCG-A A, B, C, D Cage Nut EIA-D (Qty 2) 23"-19"DR-MRG-A A, B, C, D 12-24 EIA-D (Qty 2) 23"-19"
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
13
Data Center RacksRacks :: tough. secure. cool.
Part Numbers Model ProductDR-TC28 A, B, C, D Data Rack Top Cap 28"DR-HGB-23 A, B, C, D Horizontal Ground Bar 23"DR-TC24 E, F, G, H Data Rack Top Cap 24"DR-TCC All Models Data Rack Top Cap Center Label HolderDR-TCB All Models Data Rack Top Cap Border Qty 2DRMR-AC All Models Data Rack AC Power BracketDRMR-ACD All Models Data Rack AC Power Bracket DualDR-GANG All Models Data Rack Ganging HardwareDR-HGB-19 All Models Horizontal Ground Bar 19"DR-ANCS All Models Seismic Anchor Data Center RackDR-CN50 All Models Data Rack Cage Nut Qty 50DR-CN100 All Models Data Rack Cage Nut Qty 10004500-50 All Models 12-24 Mounting Screws Qty 5004500-100 All Models 12-24 Mounting ScrewsDR-CDS All Models Cabinet Duct Spacer
Part Number Model Width DoorsDRDP-28 A, B, C, D 28" Chrome Perforated DoorDRDBP-28 A, B, C, D 28" Black Perforated DoorDRDDP-28 A, B, C, D 28" Chrome Perforated Dual DoorDRDDBP-28 A, B, C, D 28" Black Perforated Dual DoorDRDP-24 E, F, G, H 24" Chrome Perforated DoorDRDBP-24 E, F, G, H 24" Black Perforated DoorDRDDP-24 E, F, G, H 24" Chrome Perforated Dual DoorDRDDBP-24 E, F, G, H 24" Black Perforated Dual Door
Isolation Pad Model Width DepthDRISO-2842 A 28ʺ 42ʺDRISO-2836 B 28ʺ 36ʺDRISO-2830 C 28ʺ 30ʺDRISO-2824 D 28ʺ 24ʺDRISO-2442 E 24" 42"DRISO-2436 F 24" 36"DRISO-2430 G 24" 30"DRISO-2424 H 24" 24"ACCE-DR6ISO All Models 6" 6" for ACC-DR6ACCE-DR10ISO All Models 10" 6" for ACC-DR10
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
14
Data Center RacksRacks ::
1.9 Non-Seismic Data Rack
Data Center Rack with no cable management
Item SpecificationNon-Seismic Physical specs, rack for 23" equipment mtg. 28" W x 42" D x 84" H (711 mm x 1067 mm x 2134 mm)
98 lbs (44kg)- 380 lbs (172 kg) *Additional Depths availablePhysical specs, rack for 19" equipment mtg. 24" W x 42" D x 84" H (610 mm x 2134 mm)
90 lbs (41 kg) - 340 lbs (154 kg) *Additional Depths availableHole spacing EIA Wide RMU=1-¾" (1/2", 1-¼"), 44 RU
EIA Narrow RMU=1-¾" (1/2", 5/8", 5/8"), 44 RUUniversal RMU=1/2", 1/2", 1/2", 44 RU
Color Standard black, others availableCompliance GR-63-CORE, NEBS compliant, Zone 4 certified.
1.10 Specifications
Non-Seismic
Rack
• 84ʺ fixed height• 24ʺ & 28ʺ width (supporting 19ʺ & 23ʺ rack, respectively)• 24ʺ, 30ʺ, 36ʺ, 42ʺ depth
Panels
• Removable side panels• Six-post design, seismic Zone 4 rating, 2000 lb certified• Multiple side entry points• Compatible with all standard rack-mount equipment
Options
• Adjustable cable management panels −6ʺ W x 24ʺ- 42ʺ D panel −10ʺ W x 24ʺ- 42ʺ D panel
• Power accessories: −Grounding package—wiring, buss bar, vertical power lacing bar −Vertical lacing bar for power cables −PDU mounting
Mounting
• Optional, adjustable front and rear mounting rails• Isolation pad
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
15
Data Center RacksRacks :: tough. secure. cool.
Figure 4 - 19" Non-Seismic Dimensions for DR-84442, Front and Side Views
Diagram Part Number DimensionsA DR-84842 23.500B DR-84842 28.000
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
16
Data Center RacksRacks :: Non-Seismic
Design the perfect rack
Data Rack Mounting Rail EIA D Models DimensionsDR-MRGCTZ All Models CN/12-24DR-MRGTTZ All Models 12-24/12-24DR-MRGCTZP All Models CN/12-24 PlatedDR-MRGTTZP All Models 12-24/12-24 Plated
Adustable Cable Manager Models DimensionsACCE-DR6 All Models 6" Front and Rear OnlyACCE-DR10 All Models 10" Front and Rear OnlyACCE-DR6TS C, D, G, H 6" Through 24"-30" W/ HW (Qty2)ACCE-DR10TS C, D, G, H 10" Through 24"-30" W/ HW (Qty2)ACCE-DR6TD A, B, E, F 6" Through 36"-42" W/ HW (Qty2)ACCE-DR10TD A, B, E, F 10" Through 36"-42" W/ HW (Qty2)
Data Rack Model DimensionsDR Width Depth84842 A 28" 42"84836 B 28" 36"84830 C 28" 30"84824 D 28" 24"84442 E 24" 42"84436 F 24" 36"84430 G 24" 30"84424 H 24" 24"
End Panel Models DepthDREP-42 A, E 42"DREP-36 B, F 36"DREP-30 C, G 30"DREP-24 D, H 24"
Pick Model
Data Rack Mounting Rails 44RU Models DimensionsDR-MRCGP All Models Cage Nut Zinc Plated EIA-D (Qty 2)DR-MRGP-A All Models 12-24 Tapped Zinc Plated EIA-D (Qty 2) 23"-19"DR-MRCG-A A, B, C, D Cage Nut EIA-D (Qty 2) 23"-19"DR-MRCGP-A A, B, C, D Cage Nut Zinc Plated EIA-D (Qty 2) 23"-19"DR-MRGP-A A, B, C, D 12-24 Tapped Zinc Plated EIA-D (Qty 2) 23"-19"DR-MRCG-A A, B, C, D Cage Nut EIA-D (Qty 2) 23"-19"DR-MRG-A A, B, C, D 12-24 EIA-D (Qty 2) 23"-19"
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
17
Data Center RacksRacks :: tough. secure. cool.
Part Numbers Model ProductDR-TC28 A, B, C, D Data Rack Top Cap 28"DR-HGB-23 A, B, C, D Horizontal Ground Bar 23"DR-TC24 E, F, G, H Data Rack Top Cap 24"DR-TCC All Models Data Rack Top Cap Center Label HolderDR-TCB All Models Data Rack Top Cap Border Qty 2DRMR-AC All Models Data Rack AC Power BracketDRMR-ACD All Models Data Rack AC Power Bracket DualDR-GANG All Models Data Rack Ganging HardwareDR-HGB-19 All Models Horizontal Ground Bar 19"DR-ANCS All Models Seismic Anchor Data Center RackDR-CN50 All Models Data Rack Cage Nut Qty 50DR-CN100 All Models Data Rack Cage Nut Qty 10004500-50 All Models 12-24 Mounting Screws Qty 5004500-100 All Models 12-24 Mounting ScrewsDR-CDS All Models Cabinet Duct Spacer
Part Number Model Width DoorsDRDP-28 A, B, C, D 28" Chrome Perforated DoorDRDBP-28 A, B, C, D 28" Black Perforated DoorDRDDP-28 A, B, C, D 28" Chrome Perforated Dual DoorDRDDBP-28 A, B, C, D 28" Black Perforated Dual DoorDRDP-24 E, F, G, H 24" Chrome Perforated DoorDRDBP-24 E, F, G, H 24" Black Perforated DoorDRDDP-24 E, F, G, H 24" Chrome Perforated Dual DoorDRDDBP-24 E, F, G, H 24" Black Perforated Dual Door
Isolation Pad Model Width DepthDRISO-2842 A 28ʺ 42ʺDRISO-2836 B 28ʺ 36ʺDRISO-2830 C 28ʺ 30ʺDRISO-2824 D 28ʺ 24ʺDRISO-2442 E 24ʺ 42ʺDRISO-2436 F 24ʺ 36ʺDRISO-2430 G 24ʺ 30ʺDRISO-2424 H 24ʺ 24ʺACCE-DR6ISO All Models 6ʺ 6ʺ for ACC-DR6ACCE-DR10ISO All Models 10ʺ 6ʺ for ACC-DR10
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
18
Data Center RacksRacks ::
Figure 5 - 23ʺ Data Center Dimensions for DR-ISO2847, Top and Bottom Views
tough. secure. cool.
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
19
Data Center RacksRacks :: tough. secure. cool.
Figure 6 - 19ʺ Data Center Dimensions for DR-ISO2442, Top and Bottom Views
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
20
Data Center RacksRacks ::
BYDATEDESCRIPTIONECOREV
SS1/31/12ORIGINAL PRINTA0
36.00
28.008.50 23.25
2.00
30.482.76
2.38
23.25 10.00
.06
NOTES: (UNLESS OTHERWISE SPECIFIED)
1. PART TO BE FABRICATED IN ACCORDANCE WITH ALL TELECT WORKMANSHIP STANDARDS
2. BREAK SHARP EDGES & REMOVE BURRS D
C
B
AA
B
C
D
12345678
8 7 6 5 4 3 2 1
R118 1:8
B
1
142158
ISOLATION PAD 28x36
FABRICATION DRAWING2012
1/11/2012S. SITTON
1
1/31/2012S. SITTON
INCHSCALE
OF
DRAWING NO
COPYRIGHT:
DATEDESIGNED BY
This document contains proprietary information that is property of TELECT, INC., Spokane, Washington. It is intended for the exclusive use of our customer for information, installation, and/or service. The recipient agrees not to reproduce or copy this document or its contents in whole or in part without prior written permission from TELECT, INC. This document must be returned promptly if no longer needed or upon written request from TELECT, INC.
PROJECT
UNITS
SHEET REV
SHEET SIZE
TITLE
(509) 926-6000Liberty Lake, Washington 99019
N. 1730 Madson Street, PO Box 665
NOT FOR REPRODUCTION
DRAWN BY DATE
Finish:
Material:
THE 3D MODEL IS THE MASTER FILE. THE GEOMETRY WITHIN THE MASTER FILE MUST BE USED TO FABRICATE THIS PART. DIMENSIONS SHOWN ARE DEEMED CRITICAL AND WILL BE USED AS INSPECTION/PROCESS DIMENSIONS. APPLY THE FOLLOWING TOLERANCES TO THE 3D CAD FILE GEOMETRY TO FABRICATE THIS PART.
Tolerances Unless Otherwise Specified
.X ±.060 HOLE SIZE: ±.005
.XX ±.020 ANGULARITY: ±1°
.XXX ±.010
GP03-RED FIBERGLASS
Figure 7 - Data Center Isolation Pad 28ʺW 36ʺD, part number DRISO-2836
Product Dimensions Part NumberData Center Rack Isolation Pad 28"W 42"D DRISO-2442Data Center Rack Isolation Pad 24"W 42"D DRISO-2842Data Center Rack Isolation Pad 24"W 36"D DRISO-2436Data Center Rack Isolation Pad 28"W 36"D DRISO-2836Data Center Rack Isolation Pad 24"W 30"D DRISO-2430Data Center Rack Isolation Pad 28"W 30"D DRISO-2830Data Center Rack Isolation Pad 24"W 24"D DRISO-2424Data Center Rack Isolation Pad 28"W 24"D DRISO-2824
tough. secure. cool.
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
21
Data Center RacksRacks :: tough. secure. cool.
2.1 Inspecting the shipment
Telect, Inc., is not liable for shipping damage. Telect is not responsible for any equipment damage or poor operating performance when you do not follow these guidelines or when you use non-certified installers.
Keep the container until you have checked equipment operation. If you experience any kind of problem, call Telect’s Customer Service Department at 1-509-926-6000. Use the original, undamaged container if you are instructed to return the enclosure to Telect.
If a shipping container is damaged, keep it for the carrier’s inspection. Notify the carrier and call Telect’s Customer Service Department at 1-509-926-6000.
Other than this installation guide, the cabinet ships with no other components. Optional concrete and raised floor anchoring kits discussed in this guide are shown on page 18.
2.1 Installation
Please read these instructions carefully and completely before beginning installation. For assistance, contact Technical Support at 1.509.926.6000, www.telect.com, or [email protected].
These instructions presume you have verified that the Telect equipment being installed is compatible with the rest of the system, including power, ground, circuit protection, signal characteristics, equipment from other vendors, and local codes or ordinances.
Installation Guide
Design the perfect rack
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
22
Data Center RacksRacks ::
2.1.1 Important Installation Guidelines
• Elevated Operating Ambient Temperature - If installed in a closed or multi-unit rack assembly, the operat-ing ambient temperature of the rack environment may be greater than room ambient. Therefore, consideration should be given to installing the equipment in an environment compatible with the maximum ambient temper-ature (Tma) specified by the manufacturer.
• Reduced Air Flow - Installation of the equipment in a rack should be such that the amount of air flow required for safe operation of the equipment is not compromised.
• Mechanical Loading - Mounting of the equipment in the rack should be such that a hazardous condition is not achieved due to uneven mechanical loading.
• Circuit Overloading - Consideration should be given to the connection of the equipment to the supply circuit and the effect that overloading of the circuits might have on overcurrent protection and supply wiring. Appropriate consideration of equipment nameplate ratings should be used when addressing this concern.
• Reliable Earthing - Reliable earthing of rack-mounted equipment should be maintained. Particular attention should be given to supply connections other than direct connections to the branch circuit (e.g. use of power strips).
ALERT!ALERT! Only qualified technicians may install and maintain this product. Verify all connections meet requirements specified in local electric codes or operating company guidelines.
Only use components and crimping tools approved by agencies or certifying bodies recognized in your country or region, such as Underwriter’s Laboratories (UL), TUV, etc.
2.1.2 Installation Considerations
2.1.3 Location & Space
The indoor cabinet requires 28" (71 cm) door clearance at the front and rear. Leave as much side clearance for panel removal and worker access as required by your application or local regulations. If you don’t require side access, you can install the cabinets with zero side clearance, and you can leave off any adjacent panels for side-by-side cabinets needing cross-access.
Choose a location in compliance with your local operating company requirements.
2.1.4 Tools & EquipmentYou will need the following tools to install the rack:
• 18-mm (or 23/32-in.) masonry bit• 40 N•m torque wrench with a 19-mm box or open end. (A 19-mm socket at least 54-mm deep will also work.)• broadblade screwdriver (~8-mm or 5/16-in. blade width)• horizontal or plumb level (optional)• isolation pad (if required at base of cabinet)• hammer• support strut mounting hardware
tough. secure. cool.
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
23
Data Center RacksRacks :: tough. secure. cool.
ALERT!
Figure 8 - Mounting Hardware
2.2 Mounting
ALERT! The cabinet weighs approximately 445 lbs. (202 kg) for the 19" Data Center Rack, and 475 lbs. (216 kg) for the 23", without additional equipment or shipping materials. Use the appropriate lifting equipment.
2.2.1 Concrete Floor (51005-ANCS Anchor Kit)Each Telect Anchoring Kit (sold separately) contains an isolation pad, concrete anchors, threaded studs, and fastening hardware to anchor and secure the base of one cabinet to a concrete floor.
• Using the isolation pad as a template, mark the hole patterns, then move the pad aside.• Drill a 5/8" (18 mm) diameter hole, 4" (100 mm) deep, at each of the four anchor locations. Use a HEPA filter
shop vacuum while drilling to prevent concrete dust contamination of adjacent equipment.
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
24
Data Center RacksRacks ::
ALERT!ALERT! If you drill past a reinforcing bar, you MUST use an isolation pad to isolate the cabinet from the rebar ground. Telect recommends the use of isolation pads on all cabinet and rack installations to protect against inadvertent rebar grounds.
1. Clean out the holes using a HEPA filter shop vacuum and carefully clean away all debris.
THREADED STUD
TORQUE NUT
RED PLASTIC RING ON A TORQUE NUT
FLAT WASHER
METAL SLEEVE
NYLON SPACER SLEEVE
EXPANDABLE ANCHOR SLEEVE
ANCHOR CONE
2. Thread the torque nut and washer onto the rod. The washer should touch the top of the metal sleeve.
3. Insert the anchor into the hole. Tap the anchor rod down with a hammer until the washer touches the concrete.
Figure 9 - Isolation Pad for the Data Center Rack
Figure 10 - 51005-ANCS Anchor Kit
tough. secure. cool.
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
25
Data Center RacksRacks :: tough. secure. cool.
4. Pre-torque the anchor to approximately 30 ft-lbs.5. Loosen the nut several turns, then remove the rod, torque nut, and washer (the rod assembly can be backed out
by using the screwdriver slot; the sleeves and anchor cone remain in the hole).6. Place the isolation pad on the mounting surface.7. Position the cabinet over the holes; do not let debris fall into the holes.8. Install the insulating washers that accompany the isolation pad.9. Place the rods through the holes in the cabinet base and thread them into the anchor bodies until they are fully
engaged in the threads of the bottom cones.10. Add the steel washer and the torque nut assembly and retorque to 30 ft-lbs. Make sure the washer and torque
nut are securing the diagonal corner strut and not the end cap.
CABINET FRAME
END CAP
CORNER STRUT
CONCRETE FLOORANCHOR ASSEMBLY
Figure 11 - Securing the Anchor
ISO PAD INSERT
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
26
Data Center RacksRacks ::
2.2.2 Raised Computer Floor (DR-ANCRF Anchor Kit)
Each Telect Anchoring Kit (sold separately) contains an isolation pad, concrete anchors, threaded rods, and fastening hardware to anchor and secure the base of one cabinet to a raised floor and the concrete below it. See “Isolation Pad for the Data Center Rack" on page 10 for a view of the isolation pad.
1. Locate the isolation pad over one raised floor panel.2. Using the isolation pad as a template, mark the hole pattern, then move the pad aside.3. Drill a 5/8" (18 mm) diameter hole at each of the four anchor locations.4. Remove the floor panel, transfer the panel holes to the concrete, and drill a 5/8" (18 mm) diameter hole, 4"
(100 mm) deep at each of the four marks. Use a HEPA filter shop vacuum while drilling to prevent concrete dust contamination of adjacent equipment.
ALERT!ALERT! If you drill past a reinforcing bar, you MUST use an isolation pad between the floor plate and cabinet to isolate the cabinet from the rebar ground. Telect recommends the use of isolation pads on all cabinet and rack installations to protect against inadvertent rebar grounds.
5. Clean out the holes using a HEPA filter shop vacuum and carefully clean away all debris.
6. Thread the torque nut and washer onto the rod. (See “Securing the Anchor" on page 11.) The washer should touch the top of the metal sleeve.
7. Insert the anchor into the hole. Tap the anchor rod down with a hammer until the washer touches the concrete.
8. Torque the anchor to approximately 30 ft-lbs.9. Thread a nut, lock washer, flat washer, and square plate onto each rod so the square
plate sits at the level required to fully support the floor panel at the proper height.10. Cut any wire access holes required in the floor plate, then place it over the anchor rods.11. Install the isolation pad.12. Locate the cabinet over the anchor rods.13. Install the insulating washers that accompany the isolation pad.14. Add the Delrin® shoulder washer, flat washer, pressure washer, and nut and torque
to 30 ft-lbs. Make sure the washer and torque nut are securing the diagonal corner strut and not the end cap.
12 mm x 1.75 Nut (12)
½ in. Spring Lockwasher (12)
½ in. Flat Washer (12)
12 mm x 1.75 x 1 m All Thread Rod (4)
Delrin ® Shoulder Washer (4)
2 in. x 2 in. x ¼ in. Square Washer (4)
M12/25, Heavy Duty Expansion Anchor (4)
tough. secure. cool.
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
27
Data Center RacksRacks :: tough. secure. cool.
2.2.3 Grounding
WARNING!
WARNING!
WARNING! To maintain proper grounding protocol, always ground this cabinet to the site master ground return that facilitates the earth ground for the site.
WARNING! Failure to properly ground this equipment can create hazardous conditions to installation personnel and to the equipment.
1. Route the 14 AWG (min.) ground wire in from the isolated chassis ground (use appropriate fittings) to the ground in the cabinet (ground lug locations vary).
2. In the cabinet, crimp a single-hole compression lug for a ¼-20 stud onto the ground wire.3. Thread a ¼-20 KEPS nuts (not provided) on the stud and tighten to ~45 in.lb (~5 N•m).4. Place the compression grounding lug over the stud.5. If desired or required, place a washer on top of the lug.6. Thread another KEPS nut onto the stud and also tighten to ~45 in.lb (~5 N•m).
2.2.4 Installing the Cable Managment Panel
1. Using two people, hold the cable management panel up against the side of the Data Center Rack
2. From the inside of the Data Center Rack, attach six 3/8" bolts, flatwashers, and lockwashers through the vertical support frame and into the panel at the mounting holes indicated in Figure 11.
3. To install a second Data Center Rack to the same cable manager, repeat steps 1 and 2 on the other side of the cable management panel. See figure 12.
Figure 12 - Attaching the Cable Management PanelREV ECO DESCRIPTION DATE BY
NTSB1 of 1
drawing no designed by sheetrev sheet sizecustomer drawing dateunits
drawn by dateinch
scale project projectionco
pyrig
ht 2
012
tele
ct.c
om :
: 1.
509.
926.
6000
.X
.XX
.XXX
tolerances (unless otherwise specified)C
ON
FID
EN
TIA
L N
OT
FO
R R
EP
RO
DU
CT
ION
±.060 ±.020 ±.010
±.005 ±1°
hole size:angularity:ACCE-DR6 A0
6/2/2011R118
G. HILBERT
B. Fuller
2/8/2012
CABLE MNGR USER MANUAL VIEWS
ASSEMBLE IN ACCORDANCE WITH ALL APPLICABLE 1.TELECT WORKMANSHIP STANDARDS.
DIMENSIONS ARE FOR REFERENCE ONLY. 2.
BYNOTES: (UNLESS OTHERWISE SPECIFIED)
REV ECO DESCRIPTION DATE
ITEM NO. PART NUMBER DESCRIPTION QTY.
1 141922 DUCT:CMS,HORIZ,4X4,ADJ,OUTER,19.75",10"-14" SPAN 2
2 141921 DUCT:CMS,HORIZ,4X4,ADJ,INNER,19.75",10"-14" SPAN 2
3 116786 SCREW:6-32x.250,FHPUC GROUNDING NIBS,STL,ZN,TFS,ROHS 16
1
2
3
24"-30"
6/2/2011DATE
D
C
B
AA
B
C
D
12345678
8 7 6 5 4 3
DRAWN BY
2
A0NTS
1
R118
B
NOT FOR REPRODUCTION
1
ADJUSTABLE CABLE MANAGER 6" TROUGH 24"-30" W/ HW
2/8/2012CUSTOMER DRAWING
B. Fuller
1
2012
QTY 2
G. Hilbert
INCHSCALE
OF
DRAWING NO
COPYRIGHT:
DATE
ACCE-DR6TS
CONNECTING THE FUTURE
Liberty Lake, Washington 99019(509) 926-6000
TITLE
SHEET SIZE
REVSHEET
DESIGNED BY
TELECT, INC.
PROJECT
UNITS
This document contains proprietary information that is property of TELECT, INC., Spokane, Washington. It is intended for the exclusive use of our customer for information, installation, and/or service. The recipient agrees not to reproduce or copy this document or its contents in whole or in part without prior written permission from TELECT, INC. This document must be returned promptly if no longer needed or upon written request from
23321 East Knox Avenue, PO Box 665
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
28
Data Center RacksRacks ::
2.2.5 Installing the End Panels
You can install the end panel to the Data Center Rack with or without the cable management panel. The side panels are 79.7 inches high and 35.67 inches wide, with handles at the positions shown.
1. Hold the panel up against the side of the rack.2. Using six 3/8" bolts, flatwashers, and lockwashers
at the bolt holes indicated in figure 13, secure the panels to the side.
Figure 14 - End Panel Assembly
Locking Pull Latches
Panel Base Slot
Pull Latch Keeper
REV ECO DESCRIPTION DATE BY
NTSB1 of 1
drawing no designed by sheetrev sheet sizecustomer drawing dateunits
drawn by dateinch
scale project projection
copy
right
201
2te
lect
.com
::
1.50
9.92
6.60
00
.X
.XX
.XXX
tolerances (unless otherwise specified)
CO
NF
IDE
NT
IAL
NO
T F
OR
RE
PR
OD
UC
TIO
N
±.060 ±.020 ±.010
±.005 ±1°
hole size:angularity:End Panel Assem A0
6/2/2011R118
G. HILBERT
B. Fuller
3/20/2012
USER MANUAL VIEWS
Figure 13 - Two Data Center Racks with Single Cable Management Panel
tough. secure. cool.
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
29
Data Center RacksRacks :: tough. secure. cool.
2.2.6 Installing the Ground Bar
To install the ground bar, mount it to the top of the verti-cal frame rail at hole 1 down from the top, using 12-24 mounting hardware, as shown.
Figure 15 - Mounting the Ground Bar
2.2.7 Installing Doors
Two door options are available: single doors with the latch on the side, or double doors with the latch in the center. The double doors allow you to open one side of the door in a narrow corridor. See “1.6 Accessories" on page 18 for details.
Door hinges are partially installed at the factory. To install a door, first locate the M6x10m Phillips panhead hinge mount screws, the bracket mount screws, the hinge, and the bracket.
Figure 16 - Installing the Door Hinges
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
30
Data Center RacksRacks ::
Procedure steps:1. Install the hinge to the rack, using the screws provided.2. Install the other side of the hinge to the bracket, using the other two screws.3. Repeat steps 1 & 2 to install the bottom hinge.4. With an assistant holding the door up against the frame, align the door hinge components and lower the door
onto the hinge.This procedure is complete.
2.2.8 Replacing DoorsFigure
If it is necessary to replace the cabinet doors, follow these steps:1. Lift the door straight up and out to remove it
from the hinge pin.2. To replace the door, have an assistant help
align the door hinge components with those on the cabinet and lower the door onto the hinge.
Figure 17 - Door Hinge
NTS B 1 of 1
drawing nodesigned bysheet revsheet size customer drawingdate units
drawn bydateinch
scaleprojectprojection
copyright 2012
telect.com :: 1.509.926.6000
.X
.XX
.XXX
tolerances (unless otherwise speci�ed)
CONFIDENTIAL NOT FOR REPRODUCTION
±.060 ±.020 ±.010
±.005 ±1°
hole size:angularity: Rear Door hinge viewA0
8/9/2011R118
G. HILBERT
G. HILBERT
3/26/2012
USER MANUAL DUAL DOOR HINGE VIEW
Factory-installedhinge section
Hinge
Frame bracketmounting hardware
Figure 18 - Back Door Hinge
tough. secure. cool.
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
31
Data Center RacksRacks :: tough. secure. cool.
2.3 Maintenance
Telect’s indoor cabinets require no preventive maintenance
2.4 Service
Technical supportEmail: [email protected]: 1-509-926-6000
2.4.1 In-warranty service
Contact your Telect equipment distributor, or call a Telect Customer Service Representative: 1-509-926-6000
Telect will repair or replace defective products within the limits of the warranty.
NOTE: Call a Customer Service Representative for a Return Material Authorization (RMA) before returning any equipment.
2.4.2 Out-of-warranty service
Contact a Telect Customer Service Representative as detailed above. Telect will provide a Purchase Order form along with a Return Material Authorization (RMA) to be included with the enclosure when it is shipped for repair. A processing fee will be charged to guarantee a repair estimate. The charge is credited against actual material and labor costs.
2.4.3 Repacking for shipment
1. Tag the equipment showing owner’s name, address, and telephone number, together with a detailed descrip-tion of the problem.
2. Use the original shipping container if possible. If you do not have it, package the equipment in a way to pre-vent shipping damage. Include the RMA inside the container and legibly print the RMA number on the outside of the package, near the shipping address.
3. Insure the package.
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
32
Data Center RacksRacks :: tough. secure. cool.
Table of Contents
Chapter 1 ..............................................................................................................................11.1 Introduction .....................................................................................................................11.3 750 Data Center Rack ..................................................................................................21.4 Specifications ..................................................................................................................21.5 1250 Data Center Rack ................................................................................................61.6 Specifications .................................................................................................................61.7 2000 Data Center Rack ..............................................................................................101.8 Specifications ...............................................................................................................101.9 Non-Seismic Data Rack ..............................................................................................141.10 Specifications ..............................................................................................................14Chapter 2 ............................................................................................................................212.1 Installation .....................................................................................................................212.1 Inspecting the shipment ................................................................................................21
2.1.1 Important Installation Guidelines ...........................................................................222.1.2 Installation Considerations ....................................................................................222.1.3 Location & Space ..................................................................................................222.1.4 Tools & Equipment ................................................................................................22
2.2 Mounting .......................................................................................................................232.2.1 Concrete Floor (51005-ANCS Anchor Kit) ............................................................232.2.2 Raised Computer Floor (DR-ANCRF Anchor Kit) .................................................262.2.3 Grounding .............................................................................................................272.2.4 Installing the Cable Managment Panel .................................................................272.2.5 Installing the End Panels.......................................................................................282.2.6 Installing the Ground Bar ......................................................................................292.2.7 Installing Doors .....................................................................................................292.2.8 Replacing DoorsFigure .........................................................................................30
2.3 Maintenance .................................................................................................................312.4 Service ..........................................................................................................................31
2.4.1 In-warranty service ................................................................................................312.4.2 Out-of-warranty service .........................................................................................312.4.3 Repacking for shipment ........................................................................................31
© Telect, Inc., All Rights Reserved, 142359 A01.509.926.6000 :: telect.com
33
Data Center RacksRacks :: tough. secure. cool.
List of Figures
Figure 1 - 19" Dimensions for 1250 lb and part number DR1250-84442 .............................7Figure 2 - 2,000 lb Rack with cable management ..............................................................10Figure 3 - 19" Dimensions for 2000 lb and part number DR2000-84442 ........................... 11Figure 4 - Non-Seismic Data Rack with no cable management .........................................14Figure 5 - 19" Non-Seismic Dimensions for DR-84442, Front and Side Views ................15Figure 6 - 23" Data Center Dimensions for DR-ISO2847, Top and Bottom Views .............18Figure 7 - 19" Data Center Dimensions for DR-ISO2442, Top and Bottom Views .............19Figure 8 - Data Center Isolation Pad 28"W 36"D, part number DRISO-2824 ....................20Figure 9 - Mounting Hardware ............................................................................................23Figure 10 - Isolation Pad for the Data Center Rack ............................................................24Figure 11 - 51005-ANCS Anchor Kit ...................................................................................24Figure 12 - Securing the Anchor .........................................................................................25Figure 13 - Attaching the Cable Management Panel ..........................................................27Figure 14 - Two Data Center Racks with Single Cable Management Panel ......................28Figure 15 - End Panel Assembly .......................................................................................28Figure 16 - Mounting the Ground Bar ................................................................................29Figure 17 - Installing the Door Hinges ...............................................................................29Figure 18 - Door Hinge .......................................................................................................30Figure 19 - Back Door Hinge ..............................................................................................30
1.509.926.6000 :: telect.com