Technical YN
-
Upload
nairam2003 -
Category
Documents
-
view
20 -
download
0
description
Transcript of Technical YN
-
ROTARY SCREW LIQUID CHILLER
Product Catalogue
REFRIGERANT TYPE : R134a
GB
YN.01 TME 09.03
-
Page 1FORM YN.01 TME 09.03
CONTENTSSpecification
Controls
Accessories and Options
Application Data
Operating Limitations
Identification
Electrical Data
Refrigerant Flow Diagram
Dimensions
Condenser Water Box NozzleArrangement
Evaporator Water Box NozzleArrangement
Nozzle Types and Dimensions
Unit Weights
Motor Weights
Technical Data
Solid State Starter (Optional)
FEATURESManufactured to ISO 9001 EN 29001.
High full load and part load efficiency.
Operates at low condenser water temperatures. Cooling towerbypass not required.
Open drive motor.
Mixed-matched components.
High efficiency industrial type open drive twin helical screwcompressor.
Microprocessor control with visual display of temperatures,pressures, motor currents, operating hours and number ofstarts.
Unit remote alarm contacts.
Optional remote water temperature and current limit reset.
Building management system interface.
The YN range of chillers are designedfor water or water/glycol cooling. Thetwin screw compressor is open driveand close coupled to the motor. Heatexchangers are the flooded type withrefrigerant passing through the coolerand condenser shells and water in thetubes.
Capacity selection is computerised sothat chil ler components can becustomed matched to meet individualbuilding load energy requirements.
A Cooling Tower or Dry Cooler isrequired for heat rejection.
All units are designed for plant roominstallation
BENEFITSHigh standard of quality control.
Low operating costs at all load conditions.
Reduced energy costs during winter. Reducedcapital cost savings.
More efficient than refrigerant cooled motor.
Satisfies exact capacity/energy requirements.
Energy efficient, long life reliable compressor.
System data logging and temperature resetcapability.Fault diagnostics.Energy management.
Warning notification.
Improve operating efficiency.
For central data logging and single point fullsystem monitoring and control.
YNWATER COOLEDCHILLER WITHROTARY SCREWCOMPRESSORR134a REFRIGERANT
COOLING CAPACITIES570kW to 1298kW
AVAILABLE MODELS & NOMINAL COOLING CAPACITIES
Compressor Code S2 S3 S4 S5
Evaporator/Condenser RB/RB RB/RB RB/RB RD/RBCode Range to RD/RD to RD/RD to SD/SD to SD/SD
Cooling Capacity Range (kW) 570 to 581 743 to 762 958 to 1042 1223 to 1298
SPECIFICATIONThe YORK Rotary Screw Chiller is completely factory packaged includingevaporator, condenser, subcooler, oil separator, compressor, motor, lubricationsystem, Control panel, and all interconnecting unit piping and wiring. The unitcontains the full charge of R134a and oil.
CompressorThe rotary twin screw compressor has been engineered and constructed to meetthe exacting requirements of the industrial refrigeration market. It utilizes state-of-the-art technology to provide the most reliable and energy efficient compressoravailable at all operating conditions. The compressor operates at 2975 rpm. Thecompressor housing is made of cast iron, precision machined to provide minimalclearance for the rotors. The compressor housing has a design working pressureof 2413 kPa and is hydro-tested to 3751 kPa.
The rotors are manufactured from forged steel and use asymmetric profiles. Thecompressor incorporates a complete anti-friction bearing design for reduced powerand increased reliability. Four separate cylindrical roller bearings handle radialloads. Two 4-point angular contact ball bearings handle axial loads. Together theymaintain accurate rotor positioning at all pressure ratios thereby minimizing blow-by and maintaining efficiency.
A non return valve is installed in the compressor discharge housing (suction forS4 and S5 compressor) to prevent compressor rotor backspin due to systemrefrigerant pressure gradients during shutdown.
TABLE 1
-
FORM YN.01 TME 09.03Page 2
SPECIFICATION (CONTINUED)The open-drive compressor has a doubleshaft seal and consists of a bellows type,spring-loaded precision lapped ceramicring, PTFE static seal and a precisionlapped ceramic rotating collar. The entireshaft seal cavity is at low pressure, beingvented to the oil drain from thecompressor. Combining low pressurewith direct oil cooling provides long seallife.
Capacity ControlCapacity control is achieved by use of aslide valve which provides fullymodulating control from 100% to 15%of full load, depending upon unitselection. The slide valve is actuated byoil pressure controlled by externalsolenoid valves via the control panel.
Motor Driveline
The compressor motor is an open drip-proof, squirrel cage, type constructed toYORK design specifications andoperates at 2975 rpm. The open motoris provided with a D-flange, factorymounted to a cast iron adaptor mountedon the compressor. This unique designallows the motor to be rigidly coupled tothe compressor to provide factoryalignment of motor and compressorshafts.
The motor drive shaft is directlyconnected to the compressor shaft witha flexible disc coupling. The coupling isof all metal construction with no wearingparts to assure long life, and nolubrication requirements to provide lowmaintenance.
For units util izing remote electro-mechanical starters, a steel terminal boxwith gasketed front access cover isprovided for field connected conduit.There are six or three terminals(depending of motor) brought throughthe motor casing into the terminal box.Jumpers are supplied for three-leadtypes of starting. Motor terminal lugs arenot supplied. Overload/overcurrenttransformers are supplied with all units.For units supplied with factory packagedSolid State Starters, refer to theAccessories and Options Section.
Oil Separator
The combined oil separator/reservoir witha design working pressure of 20 bar shallbe the high efficiency, augmented gasimpingement type to maximise oilextraction without fragile media to breakdown.
LubricationThe main oil reservoir is located in theoil separator. The compressor also hasan oil reservoir located at the rotorbearings to provide lubrication duringstartup, coastdown and in the event of apower failure. During operation, systempressure differential provides proper oilflow without the need of an oil pump.This minimizes system energyconsumption.
The chiller is shipped with a 3 micronabsolute oil filter, ensuring a clean oilsystem and superior compressor life. Anoptional dual oil filter housing withisolation valves is available on all units.This allows immediate switching fromone filter to the other, eliminatingdowntime during filter changes. The off-line filter can be changed during chilleroperation.
A 500 watt (115 volt - 1 phase - 50Hz)immersion oil heater is located in the oilseparator reservoir, temperatureactuated to effectively remove refrigerantfrom the oil. Power wiring is provided tothe control panel. A refrigerant cooledoil cooler is provided, factory piped tothe system. An external, replaceablecartridge, 15 micron oil filter is providedwith manual isolation stop valves forease of servicing. An oil eductorautomatically removes oil which mayhave migrated to the evaporator andreturns it to the compressor.
Heat ExchangersShells - Evaporator and condensershells are fabricated from rolled carbonsteel plates with fusion welded seams.Carbon steel tube sheets, drilled andreamed to accommodate the tubes, arewelded to the end of each shell.Intermediate tube supports arefabricated of 12 mm carbon steel plates.The refrigerant side of each shell isdesigned for 16.2 bar g design workingpressure, tested at 23.2 bar g. With"High Condensing Pressure" option therefrigerant side of the condenser isdesigned for 20 bar g design workingpressure and tested at 28.6 bar g.
Tubes - Tubes are state-of-the-art, highefficiency, internally enhanced type toprovide optimum performance. Eachtube is roller expanded into the tubesheets providing a leak-proof seal, andare individually replaceable. Tubes are19 mm OD copper alloy.
Evaporator - Evaporator is a shell andtube, flooded type heat exchanger. Adistributor trough provides uniformdistribution of refrigerant over the entireshell length to yield optimum heattransfer. A suction baffle is located abovethe tube bundle to prevent liquidrefrigerant carryover into the compressor.A liquid level sight glass is convenientlylocated on the side of the shell to aid indetermining proper refrigerant charge. Arefrigerant charging valve is provided.
Condenser - The condenser is a shelland tube type, with a discharge gasbaffle to prevent direct high velocityimpingement on the tubes. This baffle isalso used to distribute the refrigerant gasflow properly for most efficient heattransfer. The subcooler is located in thebottom of the condenser sectionproviding highly effective liquidrefrigerant subcooling to improve cycleefficiency.
Compact Water Boxes - Removablewater boxes are fabricated of steel. Thedesign working pressure is 10 bar g.Integral steel water baffles are locatedand welded within the water box toprovide required pass arrangements.Stub-out water nozzle connections withvictaulic grooves are welded to the waterboxes. These nozzle connections aresuitable for Victaulic couplings, weldingor flanges, are capped for shipment.Plugged drain and vent connections areprovided in each evaporator andcondenser water box.
Refrigerant Flow ControlThe chiller is equipped with a refrigerantmetering device consisting of a fixedorifice and modulating valve controlledvia the chiller micro panel. This controlensures proper refrigerant flow to theevaporator over a wide range ofoperating conditions, including thermalstorage applications with chilled waterreset. Valve operation is programmableand can be customized for a specificapplication via the micro panel keypad.
Isolation MountingThe unit is provided with four vibrationisolation mounts consisting of 25mmthick neoprene isolation pads for fieldmounting under the steel mounting padslocated on the tube sheets. Suitable forground floor installations.
PaintExterior surfaces are coated with durablealkyd-modified, vinyl enamel, machinerypaint.
ShipmentProtective covering is supplied on themotor, control panel, and unit-mountedcontrols. water nozzles are capped withfitted plastic enclosures.
-
Page 3FORM YN.01 TME 09.03
CONTROLSThe control panel, supplied as standardon each chiller, provides the ultimate inefficiency and chiller protection. State-of-the-art microelectronics assureprecise, reliable chiller control logic andsafety annunciations. The control centreallows direct interfacing with the YORKIntegrated Systems Network (ISN)building automation system, allowingcomplete integration of chiller, airside,and building automation controls.
Information DisplayVital chiller operating information can beshown on the 40-character alphanumericdisplay. All information is in the Englishlanguage with numeric data provided inimperial or metric units.
Information provided on all units asstandard includes:
Chilled liquid temperatures - enteringand leaving
Condenser l iquid temperatures -entering and leaving
Refrigerant pressures - evaporator andcondenser
Oil pressure - at compressor and oilfilter differential
Oil temperature
% motor current
% slide valve position
Operating hours
Number of compressor starts
Saturation temperatures - evaporatorand condenser
Discharge temperature
Information provided as an option:
Three phase motor current with SolidState Starter option
Three phase motor voltage with SolidState Starter option
In addition, all operating and setpointinformation can be transmitted to anoptional remote printer through theRS-232 port to obtain data logs:
At any time by pressing PRINT button
At set time intervals by programmingthe panel
Record of time and cause of safety andcycling shutdowns with all operatinginformation just prior to shutdown
History printout of last four shutdowns
Precise Leaving Chilled WaterTemperature Control Digital keypad entry of setpoint to
0.05C.
Verify actual vs. setpoint temperaturevia alphanumeric display.
Remote reset capability standard withYORK ISN Building AutomationSystem, optional for other analog ordiscreet remote signals.
Adjustable remote reset range (up to11C) provides flexible, efficient use ofremote signal depending on resetneeds.
Thermal (Ice) Storage Control ModeThermal ice storage systems are basedon the concept of using off-peak, lowercost electricity to build ice for handlingthe cooling load during peak hours. Themost efficient way to build ice is tomaximize chiller load and minimize runtime. Standard chiller control systemsare not designed for this operating mode.In a typical application, chillers will loadand unload to maintain a leaving chilledliquid setpoint.
When the YORK YN Chiller operates inthe thermal storage control mode, theunit will remain at 100% load until thesetpoint shutdown temperature isreached. To add greater operatingflexibility and eliminate unnecessarychiller cycling, two different Low Water(Liquid) Temperature Restart Thresholdscan be programmed, one for the icemode and one for the standard coolingmode.
This control enhancement is standardon all YN chillers. The chiller can alsobe left in the standard control mode fortemperatures between 6.7 to 0C, forapplications involving a process coolingduty that requires leaving chilled liquidtemperature setpoint control.
Motor Current Limiting Controls Programmable pull-down demand to
automatically limit motor loading forminimizing building demand charges.
Pull-down time period control up to fourhours.
Verify time remaining in pull-down cyclefrom display readout.
Separate digital setpoint for currentlimiting between 40 and 100%.
Remote reset capability standard withYORK ISN Building AutomationSystem, optional for other analog ordiscreet remote signals.
System Cycling Controls Programmable seven-day time clock for
automatic start/stop of chiller, coolerand condenser water pumps, andcooling tower.
Separate schedule input strictly forholidays.
Remote cycling contacts available forother field-supplied signals.
System Shutdown ControlsThe following safeties responsible forsystem shutdown are shown in Englishon the alphanumeric display. Eachannunciation details the day, time,reason for shutdown and type of restartrequired. All shutdowns are sequencedby the micro board except as noted.
Cycling those controls whichautomatically reset and permit autorestart of the system (as allowed by anti-recycle timers).
Low water temperature as sensedthrough the LWT sensor. If a drop inwater temperature occurs, the unit isstopped at 2.2C below the chilledliquid temperature setpoint. On a risein water temperature, the unit restartsautomatically.
Chilled water pump interlock or flowswitch. Flow must be interrupted for aminimum of two seconds beforeshutdown will occur.
Remote/local cycling devices (fieldsupplied).
Automatic restart after power failure(a jumper plug is furnished if automaticrestart is desired).
Multi-unit sequencing.
Power fault relay.
High and low line voltage with SolidState Starter option.
Safety those controls which (whenemployed) require a manual operationto depress the STOP-RESET switch andthen COMPRESSOR START to restartthe system.
High Compressor DischargeTemperaturefixed cutout provided by thermistorsensor.
High Oil Temperaturefixed cutout provided by thermistorsensor.
Manual Restart after Power Failure(jumper plug furnished if automaticrestart is desired).
High Oil Pressure or Low Oil Pressurefixed cutout provided by differentialbetween separate transducer readingsfrom the compressor sump and bearingfeed line.
Low Evaporator Pressure or HighCondenser Pressureto avoid nuisance cycling, thecompressor capacity is held at cutoutthreshold for a safe period of time; ifcondition persists, a fixed cutout isprovided by dedicated transducers.
Clogged oil filter.
Low oil level switch in oil separator.
Remote stop (field-supplied signal).
Differential between Leaving ChilledWater and Evaporator SaturationTemperaturesfixed cutout when value falls outsidespecified range to detect faulty sensors.
Motor Controllerfixed cutout provided by motoroverloads (manual reset required ofspecific controller depending on startertype).
-
FORM YN.01 TME 09.03Page 4
CONTROLS (CONTINUED)
ACCESSORIES AND OPTIONS
Control Mode SelectionThere are three keys for the selection ofthe control centre modes:
ACCESS CODE permits access to themicrocomputer PROGRAM and MODEbuttons.
PROGRAM permits the operator toprogram the setpoints.
MODE permits the operator to selectthe following control modes:
LOCAL allows manual compressor startfrom the compressor switch located onthe control centre.
REMOTE allows remote start and stopof the compressor and remote reset ofthe chilled water temperature andcurrent limit.
SERVICE allows manual operation ofthe screw compressor slide valve,includes LOAD, UNLOAD HOLD andAUTO keys.
Field Interlocks Chiller Status
Remote mode ready to start - contactclosure indicates that the panel is inREMOTE mode and that the unit willstart (all safeties and cycling devices
satisfied) when a remote start signal isreceived.
Cycling shutdown - contact closureindicates that a cycling shutdown hasoccurred and that the unit will restartwhen the cycling control re-closes.
Safety shutdown - contact closureindicates that a safety shutdown hasoccurred and that a manual reset isrequired to restart.
Run contact - closure indicates that thepanel is providing a run signal to thecompressor motor starter.
Solid State StarterThe solid state starter is a reducedvoltage starter that controls andmaintains a constant current flow to themotor during start-up. It is compact andmounted on the unit adjacent to themotor terminals. Power and controlwiring is factory supplied. The starterenclosure is IP33 rated with a hingedaccess door with lock and key.
Standard features include: digital readoutat the control panel of 3-phase voltageand current; high and low line voltageprotection; 115 V control transformer;three-leg sensing overloads; phaserotation and single-phase failureprotection; and momentary powerinterruption protection. An integral doorinterlocked and pad-lockable fuseddisconnect switch is also available.
Factory Insulation of EvaporatorFactory-applied 19 mm thick anti-sweatinsulation (flexible, closed-cell plastictype) is attached with vapour-proofcement to the evaporator shell, flowchamber, evaporator tube sheets,suction connection, and (as necessary)to the auxiliary tubing. This insulationwill normally prevent sweating inenvironments with relative humidity upto 75% and dry bulb temperaturesranging from 10C to 32C. 38 mm thickinsulation is also available forenvironments with relative humidity upto 90% and dry bulb temperaturesranging from 10C to 32C. Insulation ofwater boxes and nozzles is not included.
Note: It is difficult to insulate theunderside of the chiller when installed.
Water FlangesFour BS4504/ ISO7005 - NP10 raised-face flanges can be supplied factorywelded or for site welding to thecondenser and evaporator water nozzles(companion flanges, bolts, nuts andgaskets are not included).
Water Flow SwitchesPaddle-type, vapour-proof water flowswitches can be supplied suitable for 10bar DWP chilled and condenser watercircuits. This or an equivalent switchmust be fitted in the chilled water circuitto protect against loss of water flow. Acondenser water flow switch is optional.
Isolation Valves
Factory installed valves in compressordischarge line and refrigerant liquid lineto enable refrigerant isolation/storage inunit condenser during servicing.
Hot Gas Bypass SystemA hot gas bypass system can be factoryinstalled to allow unit operation down tovirtually zero load if required.
Low Pressure Cut Out Kit/Brine
The Option Low Pressure Cut-out Kit /Brine is for units with possible conditionof Chilled Leaving Temperature between3,3C and 0C. The Brine Jumper in themicropanel is cut in the factory to allowextending the leaving brine temperaturesensor below 38F(3.3C). An extra lowevaporator pressure cut out is factoryinstalled and connected to themicropanel for the required safetyprotection.
Spring Isolation MountsSpring Isolation mounting isrecommended instead of standardisolation mounting pads for all upper floorlocations. Four level adjusting spring-type vibration isolator assemblies withnon-skid pads are provided withmounting brackets for field installation.Isolators are designed for 25 mmdeflection.
Sequence Control KitsSequence control kits for two, three orfour units with series or parallel chilledwater arrangement. Kits provide controland switching based on return watertemperature and enable centralised start/stop.
Gauge Kit3 pressures gauge (BP, HP, Oil) addedto the control system.
Marine Water BoxesMarine water boxes in lieu of standardcompact water boxes.
Fabricated steel construction, bolted-on(removable), suitable for 10 Barg DWP.All 2-pass arrangements have a marinewater box, in lieu of standard compactboxes, at nozzle end only. Return boxwill be a standard compact water box.All 1-pass and 3-pass arrangements arefurnished with a marine water box, inlieu of standard compact box, at eachend. Box has removable, bolted-on coverplate. In addition, the entire box is boltedon to the tube sheet for easy removaland direct access. Water connectionsare pipe stubs with Victaulic grooves topermit optional welded, flanged orVictaulic-coupled connections. Theconnections are capped for shipment. Acoupling, with well, is provided in thecooler outlet nozzle for the sensorelement of the temperature controlmodule. Integral steel baffles provide forthe same pass arrangements asstandard compact water boxes. Pluggedcouplings are provided for vent and drainconnections.
Form 3 Shipment -Motor/Compressor separate fromShellsShipped as three major assemblies:Compressor/motor assembly removedfrom shells and skidded. Evaporator/condenser is not skidded. Oil separatoris skidded. All wiring integral withcompressor is left on it, and all conduitis left on shells. All openings oncompressor, oil separator, and shell areclosed and charged with dry nitrogen(0.5 barg). Miscellaneous packaging ofcontrol panel, tubing, water temperaturecontrols, wiring, oil isolators, solid statestarter (option), etc; R134a charge notincluded.
-
Page 5FORM YN.01 TME 09.03
ACCESSORIES AND OPTIONS (CONTINUED)Form 7 Shipment - Split ShellsShipped as four major assemblies:Compressor/motor assembly removedfrom shells and skidded. Oil separatoris skidded. Evaporator and condensershells are separated at tube sheets andare not skidded. Refrigerant linesbetween shells are flanged and capped,requiring no welding. Tube sheets willrequire welding in field.All wiring integralwith compressor is left on it. All wiringharnesses on shells are removed. Allopenings on compressor, oil separatorand shells are closed and charged withdry nitrogen (0.5 barg). Miscellaneous
packaging of control panel, tubing, watertemperature controls, wiring, oil isolators,solid state starter (option), etc; R134acharge not included.
Factory Witness TestTo perform a customer functional witnesstest at full load.
High Condensing Pressure
If Leaving Chilled Fluid Temperature(LCFT) > 50C, oil separator andcondenser have a design workingpressure of 20 bar .
Dual High Pressure Switch (VBG20)
APPLICATION DATAThe following information on theapplication and installation of YN chillerswill ensure the reliability and trouble-freelife for which this equipment wasdesigned. While this guide is directedtowards normal, water-chillingapplications, the YORK salesrepresentative can provide completerecommendations on other types ofapplications.
LocationYN chillers are virtually vibration-free andmay generally be located at any level ina building where the construction willsupport the total system operatingweight.
The unit site must be a floor, mountingpad or foundation which is level within8mm and capable of supporting theoperating weight of the chiller.
Sufficient clearance to permit normalservice and maintenance work shouldbe provided all around and above theunit. Additional space should be providedat one end of the unit to permit cleaningof cooler and condenser tubes asrequired. A doorway or other properlylocated opening may be used.
The chiller should be installed in anindoor location where temperaturesrange from 4.5C to 43C.
Water CircuitsFlow Rate For normal water chillingduty, cooler and condenser flow ratesare permitted to any velocity levelbetween 1.0 m/s and 3.65 m/s). Flowshould be maintained constant at allloads. Refer to Table 3 for flow limits.
Pressure Drop For normal waterchilling duty, evaporator and condenserflow rates are permitted to any pressuredrop until 100 kPa. However, notably forbrine applications, pressure drops until150 kPa are acceptable. Refer to Table3 for flow limits.
Temperature Ranges For normalwater chilling duty, leaving chilled watertemperatures may be selected between3.3C and 18.9C for water temperaturedifferential between 1.6C and 11C.
Water Quality The practical andeconomical application of liquid chillersrequires that the quality of the watersupply for the condenser and cooler beanalysed by a water treatment specialist.Water quality may affect the performanceof any chil ler through corrosion,deposition of heat-resistant scale, orsedimentation or organic growth. Thesewill hurt chiller performance and increaseoperating and maintenance costs.Normally, performance may bemaintained by corrective water treatmentand periodic cleaning of tubes. If waterconditions exist which cannot becorrected by proper water treatment, itmay be necessary to provide a largerallowance for fouling, and/or to specifyspecial materials of construction.
General Piping All chilled water andcondenser water piping should bedesigned and installed in accordancewith accepted piping practice.
Chilled water and condenser waterpumps should be located to dischargethrough the chiller to assure positivepressure and flow through the unit.Piping should include offsets to provideflexibility and should be arranged toprevent drainage of water from the coolerand condenser when the pumps are shutdown. Piping should be adequatelysupported and braced independent ofthe chiller to avoid the imposition ofstrain on chiller components. Hangersmust allow for alignment of the pipe.Isolators in the piping and in the hangersare highly desirable in achieving soundand vibration control.
Convenience Considerations Toperform routine maintenance work, someor all of the following steps may be takenby the purchaser. Cooler and condenserwater boxes are equipped with pluggedvent and drain connections. If desired,vent and drain valves may be installedwith or without piping to an open drain.Pressure gauges with stop cocks, andstop valves, may be installed in the inletsand outlets of the condenser and chilledwater line as close as possible to thechiller. An overhead monorail or beammay be used to facilitate servicing.
Connections The standard chiller isdesigned for 1034 KPa design workingpressure in both the chilled water andcondenser water circuits. Theconnections (water nozzles) to thesecircuits are supplied with grooves forVictaulic couplings. Piping should bearranged for ease of disassembly at theunit for performance of such routinemaintenance as tube cleaning. All waterpiping should be thoroughly cleaned ofall dirt and debris before finalconnections are made to the chiller.
Chilled Water The chilled water circuitshould be designed for constant flow. Aflow switch must be installed in thechilled water line of every unit. Theswitch must be located in the horizontalpiping close to the unit, where thestraight horizontal runs on each side ofthe flow switch are at least five pipediameters in length. The switch must beelectrically connected to the chilled waterinterlock position in the unit controlcentre. A water strainer of maximum3.18mm mesh must be field-installed inthe chilled water inlet line as close aspossible to the chiller. If located closeenough to the chiller, the chilled waterpump may be protected by the samestrainer. The flow switch and strainerassure chilled water flow during unitoperation. The loss or severe reductionof water flow could seriously impair thechiller performance or even result in tubefreeze up.
Solid State Starter (SSS) coolingChilled water cooling of the SSS isrequired when entering condenser watertemperature exceeds 37,5C.
MODBUS (RTU) CommunicationProtocol Option.- Microgateway Board- for Standard ISN Panel
The Microgateway board is fitted on thechiller by the factory. The setting is madeby the factory.
With this option the chillers may becontrolled or monitored locally orremotely by any device that can processModbus (RTU) requests.
-
FORM YN.01 TME 09.03Page 6
APPLICATION DATA (CONTINUED)Condenser Water The chiller isengineered for maximum efficiency atboth design and part-load operation bytaking advantage of the colder coolingtower water temperatures which naturallyoccur during the winter months.
Appreciable power savings are realizedfrom these reduced head conditions.Exacting control of condenser watertemperature, requiring an expensivecooling tower bypass, may not benecessary in all applications.
The minimum entering condenser watertemperature (C) is defined by thefollowing equation:
Min ECWT = LCHWT + 9 + [(% load/100)x (5.5 - full load condenser water T)]Where: ECWT = entering condenserwater temperature
LCHWT = leaving chilled watertemperature
At initial startup, entering condensingwater temperature may be as much as14C colder than the standby chilledwater temperature. Cooling tower fancycling will normally provide adequatecontrol of entering condenser watertemperature on most installations.
Multiple UnitsSelection Many applications requiremultiple units to meet the total capacityrequirements as well as to provideflexibility and some degree of protectionagainst equipment shutdown. There areseveral common unit arrangements forthis type of application. The MillenniumChiller has been designed to be readilyadapted to the requirements of thesevarious arrangements.
Parallel Arrangement
Chillers may be applied in multiples withchilled and condenser water circuitsconnected in parallel between the units.Assuming two units of equal size, eachwill reduce in capacity, as the loaddecreases to about 40% of the totalcapacity, at which point one of the unitswill be shut down by a sequence control.
Assuming chilled water flow to theinoperative unit is stopped by pumpshutdown and/or a closed valve, theremaining unit will pick up the totalremaining load and continue to reducein capacity as the load decreases. Theunit will cycle off on the low chilled watertemperature control when the loadreduces below minimum unit capacity.
The controls can maintain constant(0.28C) leaving chil led watertemperature at all loads.
If chilled water continues to flow throughthe non-operating unit, the chilled waterflowing through the operating unit willmix with the water leaving the non-operating unit to produce a commonwater supply to the load. Since controlof the operating unit is from its ownleaving chiller water temperature, thecommon temperature to the load will riseabove the full-load design temperature.This higher chilled water temperatureoccurs below 40% load when thedehumidification load in normal airconditioning applications is usually quitelow. In such instances, this temperaturerise will save additional energy.
The running time may be apportionedbetween both units by alternating theshut off sequence.
Series Arrangement
The chillers may be applied in pairs withchilled water circuits connected in seriesand condenser water circuits connectedin parallel. All of the chilled water flowsthrough both coolers with each unithandling approximately one-half of thetotal load. When the load decreases toabout 40% of the total capacity, one ofthe units will be shut down by asequence control. Since all water isflowing through the operating unit, thatunit will cool the water to the desiredtemperature.
Brine ApplicationsThe YN Screw Chiller, utilizing theindustrial screw compressor, is a goodmatch for the high head requirements oflow temperature brine applications. Thisis particularly true of thermal ice storagesystems, typically requiring 5.6C to 4.4C leaving brine temperatures. Thisperformance is enhanced with thestandard thermal storage control mode.
Particular attention must be paid to theapplication of two or more chillers withevaporators in parallel or series whenthe brine temperature is below 0C. Thebrine must not flow through theevaporator of the idle chiller, because itcan cause the condenser water tofreeze. A bypass or other type ofarrangement is required that shuts offflow to the idle evaporator. When unitsare applied in series with lead/lagcapability, the units should be identical.
Refrigerant Relief PipingEach chiller is equipped with pressurerelief devices. The purpose of the reliefdevices is to quickly relieve excesspressure of the refrigerant charge toatmosphere, as a safety precaution inthe event of an emergency such as afire.
They are set to relieve at an internalpressure of 2069 KPa and are locatedon the condenser, evaporator and oilseparator.
Each unit is also equipped with a rupturedisk which relieves the entire pumpingcapacity of the compressor if electronicsafeties fail, providing protection forproperty and personnel.
Sized to the requirements of applicablecodes, a vent line must run from therelief device to the outside of thebuilding. This refrigerant relief pipingmust include a cleanable, vertical-leg dirttrap to catch vent-stack condensation.Vent piping must be arranged to avoidimposing a strain on the chil lerconnections and should include oneflexible connection.
Sound and Vibration ConsiderationsA Millennium chiller is not a source ofobjectionable sound and vibration innormal air conditioning applications.Neoprene isolation mounts, supplied asstandard with each chiller, are perfectlyadequate for ground-floor installations.For upper-floor installation standard,level-adjusting spring isolator assembliesdesigned for 25mm static deflectionshould be used (available from York asan option).
YN chiller sound pressure level ratingswill be supplied on request.
Control of sound and vibrationtransmission must be taken into accountin the equipment room construction aswell as in the selection and installationof the equipment.
TEMPERATURE SENSOR FORCHILLER CAPACITY CONTROL
_
S1
COND. 1
COND. 2
EVAP. 1
EVAP. 2
T
S
T THERMOSTAT FOR CHILLERSEQUENCING CONTROL
_
S2
S1
COND. 1 COND. 2
EVAP. 1 EVAP. 2
T S2
-
Page 7FORM YN.01 TME 09.03
Chiller type
Cooler code
Condenser code
Compressor code
Motor code (5 for 50 Hz)
Design Level
YN RB RB S3 5CE A
IDENTIFICATION
COMPRESSOR EVAPORATOR CONDENSER MOTORCODE CODE CODE CODE
S2 RB, RD RB, RD 5CB, 5CC, 5CD, 5CE, 5CF, 5CG, 5CH
S3 RB, RD RB, RD 5CC, 5CD, 5CE, 5CF, 5CG, 5CH, 5CI, 5CJ, 5CK
S4RB, RD RB, RD 5CE, 5CF, 5CG, 5CH,
SA, SD SA, SD 5CI, 5CJ, 5CK, 5CL, 5CM, 5CN
S5RD RB, RD 5CE, 5CF, 5CG, 5CH, 5CI, 5CJ,
SA, SD SA, SD 5CK, 5CL, 5CM, 5CN, 5CO, 5CP, 5CQ
ShellPass
Condenser Evaporator
Code Min. Max. Min. Max.
1 38.6 139.1 26.7 96.2
RB 2 19.4 69.5 13.3 48.13 12.9 39.1* 8.9 25.8*
1 48.6 174.9 39.9 143.6
RD 2 24.3 87.5 20.0 71.83 - - 13.3 38.6*
ShellPass
Condenser Evaporator
Code Min. Max. Min. Max.
1 49.2 177.1 43.2 155.4
SA 2 24.7 85.5* 21.6 71.9*3 16.6 45.2* 14.4 37.7*
1 88.2 317.6 69.1 248.7
SD 2 44.2 153.0* 34.5 114.7*3 - - 23.0 59.7*
WATER FLOW LIMITS (L/S) TABLE 3
All Models Min. Max.
Leaving Chilled Water Temperature C 3.3 18.9
Leaving Water/Glycol Temperature C -6.7 -
Leaving Condenser Water Temperature C - 58.0
Entering Condenser Water Temperature above Leaving Chilled Liquid Temperature C 6.0 -
Evaporator Water Velocity LWT 5.5C and above m/s 1.0 3.65
Evaporator Water Velocity LWT less than 5.5C m/s 1.5 3.6
Condenser Water Velocity m/s 1.0 3.6
OPERATING LIMITATIONS TABLE 2
APPLICATION DATA (CONTINUED)Thermal InsulationNo appreciable operating economy canbe achieved by thermally insulating thechiller. However, the chillers coldsurfaces should be insulated with avapour barrier insulation sufficient toprevent sweating. A chiller can be factoryinsulated with 19mm or 38mm thickinsulation, as an option. This insulationwill normally prevent sweating inenvironments with dry bulb temperaturesof 10C to 32C and relative humidities
up to 75% (19mm thickness) or 90%(38mm thickness). The insulation ispainted and the surface is flexible andreasonably resistant to wear. It isintended for a chiller to be installedindoors and, therefore, no protectivecovering of the insulation is usuallyrequired. If insulation is applied to thewater boxes at the job site, it must beremovable to permit access to the tubesfor routine maintenance.
VentilationLocal and other related codes shouldbe reviewed for specific requirements.Since the chiller motor is air-cooled,ventilation should allow for the removalof heat from the motor.
The maximum flows have been calculated the 2 following limiting conditions: a maximum velocity of 3.65 m/s in the exchangepipes; a maximum pressure drop of 150 kPa in the circuit. When the maximum pressure drop is the limiting condition, thevalues are indicated with an asterisk.
-
FORM YN.01 TME 09.03Page 8
Rated Operating Voltage
Voltage Min. Max.
400 360 423
415 374 440
MOTOR VOLTAGE FACTORS TABLE 4
Electrical ConsiderationsMotor Voltage Low voltage motors (upto and including 600 volts) are furnishedwith six leads.
Motor circuit conductor size must be inaccordance with National ElectricalCodes, for the motor full-load amperes(FLA). Flexible conduit should be usedfor the last several feet to the chiller inorder to provide vibration isolation. Table4 lists the allowable variation in voltagesupplied to the chiller motor. The unitnameplate is stamped with the specificmotor voltage and frequency for theappropriate motor.
Starters The chiller is available with afactory-mounted and wired YORK SolidState Starter for voltages up to 600 volts.Other types of remote mounted startersmay be used, supplied by others. Theseelectro-mechanical starters must besupplied in accordance with YORKStandard Specifications. This will ensurethat starter components, controls,circuits, and terminal markings will beapplicable for required overall systemperformance.
Controls A 115 volt, single phase, 50Hertz power supply must be supplied tothe chiller from a separate, fuseddisconnect or from a control transformerincluded as an option with electro-mechanical starters. No field controlwiring is required, when the YORK SolidState Starter is supplied.
Copper Conductors Only copperconductors should be connected tocompressor motors and starters.Aluminum conductors have proven to beunsatisfactory when connected to copperlugs. Aluminum oxide and the differencein thermal conductivity between copperand aluminum cannot guarantee therequired tight connection over a longperiod of time.
Capacitors Capacitors can be appliedto a chiller for the purpose of powerfactor correction. For Star-Delta Closed-Transition and Across-the-Line starters,the capacitors should be located on theload side of the starter. For YORK SolidState Starters, the capacitors must belocated on the line side of the starter.Capacitors are not recommended for usewith Star-Delta Open-Transition starters.The capacitors must be sized andinstalled to meet National ElectricalCodes and be verified by York.
Compressor Motor Power Supply Electrical power wire size to the chilleris based on the minimum unit ampacity.For Solid State Starters, this wiring isdone at the factory. For remote starters,National Electrical Codes defines thecalculation of ampacity, as summarizedbelow. More specific information onactual amperage ratings will be suppliedwith the submittal drawings.
Six-lead type of starting (Star-Delta)
Minimum circuit ampacity per conductor(1 of 6):
Ampacity = .721 x compressor motoramps.
ELECTRICAL DATAThree-lead type of starting
(Across-the-Line, Autotransformer andPrimary Reactor)
Minimum circuit ampacity per conductor(1 of 3):
Ampacity = 1.25 x compressor motoramps.
Fused Disconnect Switch The fuseddisconnect switch for the compressormotor starter must be sized inaccordance with National ElectricalCodes. Below 600 volts, the formulagenerally is:
Amp rating = 115% x amps of all loadson the circuit
This would include compressor motor,and may include control transformer.Refer to submittal drawings for specificcalculations for each application.
Ampacity on Line Side of Starter Min. Circuit Ampacity =
125% of Compressor. motor amps FLA+ of all other loads on the circuit
The only additional load on the circuitfor the chiller would be the controltransformer, unless they are supplied bya separate source.
Branch Circuit OvercurrentProtectionThe branch circuit overcurrent protectiondevice(s) should be a time-delay type,with a minimum rating equal to the nextstandard fuse/breaker rating above thecalculated value. It is calculated takinginto account the compressor motor ampsand may also include controltransformer. Refer to submittal drawingsfor the specific calculations for eachapplication.
-
Page 9FORM YN.01 TME 09.03
Starter Type SOLID STATE STAR DELTA ACROSS THE LINE
Transition NONE CLOSED OPEN -
Inrush amperage (% of LRA) 45 33 33 100
MOTOR CODE 5CB 5CC 5CD 5CE 5CF 5CG 5CH 5CI 5CJ 5CK 5CL 5CM 5CN 5CO 5CP 5CQ
ELECTRICAL 102 119 134 159 180 201 217 232 255 280 308 330 363 398 428 450POWER (kW)
SHAFT POWER 95 110 125 148 168 188 203 218 240 263 291 313 345 378 407 429(kW)
AMPERES (MAX)
400 VFLA 165 190 219 259 295 324 350 369 406 452 496 530 589 645 703 737
LRA 1185 1327 1383 1490 1797 2201 2716 2718 2943 3495 3705 3491 3758 4211 4843 5216
415 VFLA - 183 211 249 278 313 344 364 391 441 478 510 561 619 668 700
LRA - 1150 1170 1280 1500 1830 2100 2300 2300 2750 3000 3000 3300 3660 4100 4200
MOTOR ELECTRICAL DATA TABLE 5
Motor must be selected with 8% margin over rated shaft power.
FLA : Full Load Amps - LRA : Locked Rotor Amps
For brine cooling applications, higher margin is advisable to achieve higher capacities during the start-up conditions.
MOTOR STARTER DATA TABLE 6
ELECTRICAL DATA (CONTINUED)
-
FORM YN.01 TME 09.03Page 10
REFRIGERANT FLOW DIAGRAM
1 COMPRESSOR
2 MOTOR
3 CONDENSER
4 SUB-COOLER
5 EVAPORATOR
6 OIL COOLER (optional)
7 OIL SEPARATOR
8 FILTER
9 ORIFICE
10 FILTER DRIER
LEGEND
BP PRESSURE TRANSDUCER
BSVP POSITION POTENTIOMETER
BT TEMPERATURE TRANSDUCER
EOH OIL HEATER
FHP HIGH PRESSURE SAFETY
LG LEVEL GAUGE
PSV PRESSURE RELIEF VALVE
PW PRESSURE TAPPING
RD BURSTING DISC
SG SIGHT GLASS
SSOL LOW LEVEL SAFETY
TSH HIGH TEMPERATURE SAFETY
YSV SOLENOID VALVE
YSVL COMP. LOAD SOLENOID VALVE
YSVUL COMP. UNLOAD SOLENOID VALVE
S2 & S3 COMPRESSORS
S4 & S5 COMPRESSORS
S4 & S5 COMPRESSORS
S2 & S3 COMPRESSORS
BP10
2M1
7
8
10
3-4 5
6
9
PA B
Tb(+) a(-)SM1
SC8 SC12
SC1 SC2
SB2
SC5 SC11SB3
17 bar
17 bar
SC6- +
FHPFHP
PW
TSHBPYSV BSVP
YSVL
YSVUL
LG
16,2 bar 16,2 bar
BPPW
EOH
BT
PSV PSV16,2 bar 16,2 bar
PSV PSV
BT
BT
SG BT
BT
SG
YSV
BP BT
RD
RD
PW
SSOL
CUSTOMERYORK
CUSTOMERYORK
DRAINDRAIN
TRANSFER
YORKATMOSPHERE
CUSTOMER
OILCHARGE
AND DRAIN
YORK YORK
CUSTOMER YORK
WAT
ER
WAT
ER
ATMOSPHERE
-
Page 11FORM YN.01 TME 09.03
CompressorShell Code
B C D E M(5) Y(2) P(Evap - Cond)
S2, S3 R - R 2400 1549 394 775 3050 52 3048
S4R - R 2400 1549 394 775 3050 245 3048
S - S 2500 1676 445 838 3650 50 3657
S5R - R 2410 1585 394 775 3050 494 3048
S - S 2500 1700 445 838 3650 300 3657
Dimensions in mm
DIMENSIONS
TYPE COMPACT WATER BOXEVAPORATOR CODE CONDENSER CODE
DIM. R S DIM. R S1-Pass 2-Pass 3-Pass 1-Pass 2-Pass 3-Pass 1-Pass 2-Pass 3-Pass 1-Pass 2-Pass 3-Pass
J1 - 171 - - 187 - K1 - 156 - - 172 -J2 361 361 361 367 367 367 K2 356 356 356 367 367 367
B
CP
D K2
M
J2K1J1
Y
E
Overall Dimensions
Notes
1. Unit height includes steel mounting plates under tube sheets. To determine overall installed height, add 25mm for neopreneisolators (40 mm for optional spring isolators).
2. Dimension with largest motor.
3. Determine overall unit length by adding:- tube sheet length (P),- compressor side water box depth (from table below),- greater dimension between motor side water box depth (from table below) and "Y" dimension.
5. Tube pulling space (either end).
6. All dimensions are approximate. Certified dimensions are available on request.
MOTOR
COMPRESSOROIL SEPARATOR SOLID STATESTARTER(Optional)
MICROCOMPUTERCONTROLCENTER
EVAPORATORCONDENSER
Dimensions in mm
Dimensions based on Victaulic connection. Add 15 mm to each compact water box with optional flanged nozzles.
SE
E N
OT
E 1
SEENOTE 2
SEE NOTE 5
-
FORM YN.01 TME 09.03Page 12
CompressorShell Code
P Q R S T U V W X(Evap - Cond)
S2, S3 R - R 3048 1549 11 26 115 170 155 83 197
S4R - R 3048 1549 11 26 115 170 155 83 197
S - S 3657 1676 48 63 152 170 155 86 242
S5R - R 3048 1549 11 26 115 170 155 86 242
S - S 3657 1676 48 63 152 170 155 86 242
Dimensions in mm
Floor Layout with Neoprene Isolators
Floor Layout with Spring Isolators (Optional)
Q
R = P = R
T
115
SS
EVAPORATOR CENTERLINE
CONDENSER CENTERLINE
SH
ELL
SC
EN
TE
RLI
NE
Q
= P =U
5757
57
V
57
W
=X=
EVAPORATOR CENTERLINE
CONDENSER CENTERLINE
SHEL
LSCE
NTER
LINE
DIMENSIONS (CONTINUED)
-
Page 13FORM YN.01 TME 09.03
C3
C1
W
C3C1
V
Y
X
MOTOR END COMPRESSOR END
CONDENSER CONDENSER
C3C1
S
R
U
TC3
C1
MOTOR END COMPRESSOR END
CONDENSERCONDENSER
C2 C2
QP
MOTOR END COMPRESSOR END
CONDENSER CONDENSER
Nozzle Arrangements
No. Of Condenser
Passes In Out
1P Q
Q P
CONDENSER NOZZLE POSITIONS (See Note 2)
Shell 1-Pass 2-Pass 3-Pass
Code C2 C1 C3 C1 C3
RB 727 562 892 549 905
RD 727 562 892 - -
SA 778 588 968 588 968
SD 778 588 968 - -
CONDENSER NOZZLE DIMENSIONS
Shell No. of Passes
Code 1 2 3
RB DN 250 DN 150 DN 150
RD DN 250 DN 150 -
SA DN 300 DN 200 DN 150
SD DN 300 DN 200 -
NOTES:
1.Standard water nozzles are furnished as welding stub-outs with Victaulic grooves, allowing the option of welding, flanges, or useof Victaulic couplings. Factory installed PN10 or PN20 round slip-on water flanged nozzles are optional (add 15 mm to nozzlelenght). Companion flanges, nuts, bolts and gaskets are not furnished.
2.Add 25 mm for neoprene isolators
3.One, two and three pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of evaporatornozzles may be used in combination with any pair of condenser nozzles. Compact water boxes on one heat exchanger may beused with marine water boxes on the other heat exchanger.
4.Condenser water must enter the water box through the bottom connection for proper operation of the subcooler to achieve ratedperformance.
5.Connected piping should allow for removal of compact water box for tube access and cleaning.
6.All dimensions are approximate. Certified dimensions are available on request.
1-PASSFRONTOF UNIT
FRONTOF UNIT
2-PASS
Nozzle Arrangements
No. Of Condenser
Passes In Out
2R S
T U
FRONTOF UNIT
FRONTOF UNIT
3-PASS
Nozzle Arrangements
No. Of Condenser
Passes In Out
3V Y
X W
FRONTOF UNIT
FRONTOF UNIT
CONDENSER WATER BOX NOZZLE ARRANGEMENT
-
FORM YN.01 TME 09.03Page 14
N
P
E1
E3
F
G
MOTOR END COMPRESSOR END
EVAPORATOR EVAPORATOR
J
K
E1
E3
B
C
MOTOR END COMPRESSOR END
EVAPORATOR EVAPORATOR
HE2
A
MOTOR END COMPRESSOR END
EVAPORATOR EVAPORATOR
Nozzle Arrangements
No. Of Evaporator
Passes In Out
1A H
H A
EVAPORATOR NOZZLE POSITIONS (See Note 2)
Shell 1-Pass 2-Pass 3-Pass
Code E2 E1 E3 E1 E3
RB 574 371 777 371 777
RD 574 371 777 371 777
SA 626 404 848 404 848
SD 626 404 848 404 848
EVAPORATOR NOZZLE DIMENSIONS
Shell No. of Passes
Code 1 2 3
RB DN 200 DN 150 DN 100
RD DN 200 DN 150 DN 100
SA DN 250 DN 200 DN 150
SD DN 250 DN 200 DN 150
NOTES:
1.Standard water nozzles are furnished as welding stub-outs with Victaulic grooves, allowing the option of welding, flanges, or useof Victaulic couplings. Factory installed PN10 or PN20 round slip-on water flanged nozzles are optional (add 15 mm to nozzlelenght). Companion flanges, nuts, bolts and gaskets are not furnished.
2.Add 25 mm for neoprene isolators
3.One, two and three pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of evaporatornozzles may be used in combination with any pair of condenser nozzles. Compact water boxes on one heat exchanger may beused with marine water boxes on the other heat exchanger.
4.Water must enter the water box through the bottom connection for proper operation of the subcooler to achieve rated performance.
5.Connected piping should allow for removal of compact water box for tube access and cleaning.
6.All dimensions are approximate. Certified dimensions are available on request.
1-PASSREAR
OF UNIT
2-PASS
Nozzle Arrangements
No. Of Evaporator
Passes In Out
2C B
K J
3-PASS
Nozzle Arrangements
No. Of Evaporator
Passes In Out
3G N
P F
REAROF UNIT
REAROF UNIT
EVAPORATOR WATER BOX NOZZLE ARRANGEMENT
-
Page 15FORM YN.01 TME 09.03
1.6
T
D R
S
PN 20 WELD FLANGE
Dimensions in mm
Nom. Size D R S T Boltsmini
DN 100 190.5 157.2 33 23.9 8 x M16
DN 150 241.3 215.9 40 25.4 8 x M20
DN 200 298.4 269.9 44 28.6 8 x M20
DN 250 362.0 323.8 49 30.2 12 x M24
DN 300 431.8 381.0 56 31.8 12 x M24
Optional PN 10 Flanges
PN 10 WELD FLANGE
For nominal connection sizes for individual models of chiller,see condenser or evaporator water box nozzle arrangementSection.
ConnectionsStandard chilled liquid connections on all coolers andcondensers are of the Victaulic Groove type. Optionally,flanges may be fitted. Dimensions are as follows :
Standard Victaulic :
Dimensions in mm
ACD
T
B
Nom. Size D T A B C
DN 100 114.3 6.3 15.9 9.5 109.9
DN 150 168.3 7.1 15.9 9.5 163.7
DN 200 219.1 8.0 19.0 11.1 214.1
DN 250 273.0 8.0 19.0 12.7 268.0
DN 300 323.9 8.0 19.0 12.7 317.9
Dimensions in mm
Nom. Size D T Bolts
DN 100 180 22 8 x M16
DN 150 240 24 8 x M20
DN 200 295 24 8 x M20
DN 250 350 26 12 x M20
DN 300 400 26 12 x M20
T
D
NOZZLE TYPES AND DIMENSIONS
Optional PN 20 Flanges
-
FORM YN.01 TME 09.03Page 16
Shell CodeShipping Operating Refrigerant
Evaporator-CondenserCompressor Weight Weight Charge
(kg) (kg) (kg)
RB-RB S2 4682 5017 295
RB-RD S2 4762 5127 295
RD-RB S2 4782 5157 295
RD-RD S2 4862 5267 295
RB-RB S3 4762 5097 295
RB-RD S3 4842 5207 295
RD-RB S3 4862 5237 295
RD-RD S3 4942 5347 295
RB-RB S4 5141 5476 295
RB-RD S4 5221 5586 295
RD-RB S4 5241 5616 295
RD-RD S4 5321 5726 295
SA-SA S4 6289 6919 567
SA-SD S4 6644 7408 567
SD-SA S4 6495 7160 567
SD-SD S4 6850 7649 567
RB-RB S5 5312 5647 295
RB-RD S5 5392 5757 295
RD-RB S5 5412 5787 295
RD-RD S5 5492 5897 295
SA-SA S5 6460 7090 567
SA-SD S5 6815 7579 567
SD-SA S5 6666 7331 567
SD-SD S5 7021 7820 567
NOTE:Calculate total chiller weight by adding motor weight and solid state starter weight, if applicable.Shipping weight includes refrigerant and oil charge.Operating weight includes water in tubes and water boxes.Weights based on standard tubes in evaporators and condensers.
Motor Code Weight50 Hz (kg)
5 CB 454
5 CC 486
5 CD 490
5 CE 490
5 CF 654
5 CG 699
5 CH 740
5 CI 785
Motor Code Weight50 Hz (kg)
5 CJ 810
5 CK 854
5 CL 990
5 CM 1120
5 CN 1200
5 CO 1200
5 CP 1430
5 CQ 1430
UNIT WEIGHTS
MOTOR WEIGHTS
TABLE 7
TABLE 8
-
Page 17FORM YN.01 TME 09.03
TABLE 9
Compressor Code CHARGE(liters)
S2,S3 & S4 57
S5 76
Recommended Evaporator/CondenserPipework Arrangement
TECHNICAL DATA
Refrigerant
Isolating Valve
Flow Switch
Regulating Valve
Flow Measurement Device
Strainer
Pressure Tapping
Flanged Connection
Water
Water
Shell Evaporator Condenser
Code liters liters
RB 165 170
RD 205 200
SA 360 270
SD 395 404
SHELL WATER CAPACITIES TABLE 10
SOLID STATE STARTER (OPTIONAL)SELECTION TABLE
MOTOR CODE 5CB to 5CD 5CE to 5CJ 5CK to 5CQ
STARTER MODEL SSS-7LCE-50A SSS-14LCE-50A SSS-26LCE-50A
OIL CHARGE
-
FORM YN.01 TME 09.03Page 18
BG
F D
EC
A
SOLIDSTATE
STARTER
POWER WIRING ENTRANCE COVER WITH 22 mm KNOCKOUTS USED AS LEAD HOLES FOR POWERWIRING CONDUIT CONNECTORS
CL OF POWERCONNECTIONLOCATION
Solid State Starter with R Shell Code
Compressor S2, S3 S4, S5 S4, S5
SSS Size 7L, 14L 7L, 14L 26L
A mm 864 864 889
B mm 543 543 645
C mm 279 279 305
D mm 50 37 62
E mm 280 262 262
F mm 140 140 152
G mm 1172 1208 1106
Weight kg 91 91 136B
G
F D
EC
A
SOLIDSTATE
STARTER
POWER WIRING ENTRANCE COVER WITH 22 mm KNOCKOUTS USED AS LEAD HOLES FOR POWERWIRING CONDUIT CONNECTORS
CL OF POWERCONNECTIONLOCATION
SOLID STATE STARTER (CONTINUED)
Compressor S4, S5 S4, S5
SSS Size 7L, 14L 26L
A mm 864 889
B mm 543 645
C mm 279 305
D mm 157 133
E mm 338 338
F mm 140 152
G mm 1309 1207
Weight kg 91 136
Solid State Starter with S Shell Code
-
Page 19FORM YN.01 TME 09.03
NOTES
-
FORM YN.01 TME 09.03Page 20
NOTES
-
This manual has been prepared withthe greatest care.
Should you nevertheless encountererrors or omissions, or should you feeladditions would be useful, do nothesitate to contact the TechnicalLiterature Department (see below).
Any suggestions for improvement aremost welcome.
-
EuropeFORM YN.01 TME 09.03
Supersedes : NothingSubject to change without notice
ALL RIGHTS RESERVED
CONTENTSSpecificationControlsAccessories and OptionsApplication DataOperating LimitationsIdentificationElectrical DataRefrigerant Flow DiagramDimensionsCondenser Water Box Nozzle ArrangementEvaporator Water Box Nozzle ArrangementNozzle Types and DimensionsUnit WeightsMotor WeightsTechnical DataSolid State Starter (Optional)