Mini Chiller Panel Controller

V2.0

Technical Training 2008Technical Training 2008

Content

1. Mini Chiller Panel Controller V2.0

2. Inverter Parameter

3. Inverter Display

4. Other Information

Technical Training 2008Technical Training 2008

Mini Chiller Panel Controller V2.0

Main Board

Control Module, MC01 1 CP

Control Module, Inverter

Control Module, MC01 2 CPHandset, CH_XX2.0

WCCH

Chiller Panel V2.0

Control Module, MC01 HP TC2CP

Double Comp.

Tandem Comp.

Inverter

Single Comp.

Chiller Panel vs Main Board

Technical Training 2008Technical Training 2008

Mini Chiller Panel Controller V2.0

OutlineMAIN MENU

OPERATING MENU

TIMERS MENU

ALARM MENU

DISPLAY MENU

SETTING MENU SET PANEL ID

CHANGE PASSWORD

PANEL OPTION

SET PARAMETER GENERAL

SENSOR (OMITTED)

REGULATOR

COMPRESSOR

CONDENSER DEFROST

COOL MODE ANTIFREEZE

ALARM & CONTACT (P4~P19 OMITTED)

INVERTER

V2 EXV OPENING

V3 COMPRESSOR MANUAL SETTING

V4 EXV MANUAL SETTING

V5 DEFROST MODE

V1 COMPRESSOR FREQUENCY

Technical Training 2008Technical Training 2008

Mini Chiller Panel Controller V2.0

OutlineMAIN MENU

OPERATING MENU

SETTIGN MENU

TIMERS MENU

ALARM MENU

DISPLAY MENU DEFROST SENSOR

DISCHARGE SENSOR

COMP. RUN TIME

INVERTER CHILLER EXV OPENING

CURRENT

DC VOLTAGE

SUCTION SENSOR

BPHE IN SENSOR

BPHE OUT SENSOR

CONDENSER IN SENSOR

COMPRESSOR FREQUENCY

Technical Training 2008Technical Training 2008

Condenser Coil 1

Acc

Acc

Liq Rvr

Liq Rvr

BPHE FS

Condenser Coil 2

DischTemp 2

(Disch Comp 2)

DischTemp 1

(Disch Comp 1)

InvComp

StdComp

SuctTemp

(Suction)

HP1

HP2

LP2

LP1

Cond InTemp 1

(Condenser)

Cond OutTemp 1

(Def Comp 1)

BPHE OutTemp

(BPHE Out)

BPHE InTemp

(BPHE In)

EWT (Water In)

LWT (Water Out)

Pump

Cond OutTemp 2

(Def Comp 2)

FilterDrier

Heating Cap Tube

Check valve

Cooling Cap Tube

Check valve

FilterDrier

EXV

O/A Temp(Outdoor Air)

Summary Pages-Screen 3

Display Menu-Defrost Sensor

Display Menu-Inverter Chiller

Display Menu-Discharge Sensor

5ACV100CR

4WV

4WV

Schematic diagram

Inverter chiller schematic diagram

Technical Training 2008Technical Training 2008

Inverter Parameter

Technical Training 2008Technical Training 2008

Inverter Parameter

These parameter are only available when the Chiller Panel Controller V2.0 is connected to an Inverter Mini Chiller Model

V1 Cp Freq : 0Hz

V2 EXV : 0

V3 Cp Manual : Disable

V4 EXV Manual : Disable

V5 Def Mode : Disable

V1 : Compressor FrequencyIt allows to set the inverter compressor frequency (max frequency varies according to models)

V2 : EXV It allows to set the EXV opening (0~480 pulsation)

Technical Training 2008Technical Training 2008

Inverter Parameter

V1 Cp Freq : 0Hz

V2 EXV : 0

V3 Cp Manual : Disable

V4 EXV Manual : Disable

V5 Def Mode : Disable

V3 : Cp ManualThis parameter enables automatic or manual setting for compressor frequencyEnable : Manual setting is possibleDisable: Compressor frequency auto-run

V4 : EXV Manual This parameter enables automatic or manual setting for EXV openingEnable : Manual setting is possibleDisable: EXV opening auto-run

Technical Training 2008Technical Training 2008

Inverter Parameter

V1 Cp Freq : 0Hz

V2 EXV : 0

V3 Cp Manual : Disable

V4 EXV Manual : Disable

V5 Def Mode : Disable

V5 : Def ModeThis parameter enables automatic intelligent or standard defrosting settingEnable : Manual setting for defrosting is possible in Parameter D1~D6Disable: Intelligent defrosting (auto-run)

Technical Training 2008Technical Training 2008

Inverter Display

Technical Training 2008Technical Training 2008

Inverter Display

These parameter are only available when the Chiller Panel Controller V2.0 is connected to an Inverter Mini Chiller Model

Inverter Chiller

Comp : 45Hz

EXV : 500

Comp Amp : 9.7A

DC Bus : 385V

Compressor FrequencyIt shows the operating inverter compressor frequency (Hz)

EXV It shows the operating EXV opening (pulse)

Comp AmpIt shows the operating inverter compressor running current (A)

Screen 1

Technical Training 2008Technical Training 2008

Inverter Display

DC BusIt shows the operating DC voltage in the inverter system (V)

Inverter Chiller

Comp : 45Hz

EXV : 500

Comp Amp : 9.7A

DC Bus : 385V Screen 1

Technical Training 2008Technical Training 2008

Inverter Display

SuctionIt shows the inverter compressor suction temperature (°C)

BPHE InIt shows the refrigerant inlet temperature at the BPHE during Cooling Mode. During Heating Mode, the value shows refrigerant outlet temperature at BPHE (°C)

Inverter Chiller

Suction : 15.5°C

BPHE In : 45.9°C

BPHE Out : 18.3°C

Condenser : 28.4°C Screen 2

Technical Training 2008Technical Training 2008

Inverter Display

BPHE OutIt shows the refrigerant outlet temperature at the BPHE during Cooling Mode. During Heating Mode, the value shows refrigerant inlet temperature at the BPHE (°C)

CondenserIt shows the inverter condenser coil inlet temperature (°C)

Inverter Chiller

Suction : 15.5°C

BPHE In : 45.9°C

BPHE Out : 18.3°C

Condenser : 28.4°C Screen 2

Technical Training 2008Technical Training 2008

Other Information

Technical Training 2008Technical Training 2008

Other Information

If the Chiller Panel V2.0 is connected to a Non Inverter Mini Chiller, the following information will display “--”

V1 Cp Freq : --

V2 EXV : --

V3 Cp Manual : --

V4 EXV Manual : --

V5 Def Mode : --

Inverter Parameter V1~V5

Inverter Chiller

Comp : --

EXV : --

Comp Amp : --

DC Bus : --

Inverter Chiller

Suction : --

BPHE In : --

BPHE Out : --

Condenser : --

Display Menu for Inverter Chiller

Screen 1 Screen 2

Technical Training 2008Technical Training 2008

Other Information

Alarm & Contact Parameter P1~P3 will display

P1 FS Confirm : 5s

P2 FS Delay : 180s

P3 LP Delay : 30s

P4 CO Reset : ManualP5 HP Reset : AutoP6 LP Reset : AutoP7 FO Reset : ManualP8 PO Reset : ManualP9 FS Reset : ManualP10 Aux Reset : ManualP11 A/F Reset : ManualP12 CO Contact : NormalP13 HP Contact : NormalP14 LP Contact : NormalP15 FO Contact : NormalP16 PO Contact : NormalP17 FS Contact : NormalP18 EA Contact : NormalP19 DE Contact : Normal

Parameter P4~P19 and Sensor Parameter had been omittedS1 Water Enter : 0.0°CS2 Water Leave : 0.0°CS3 Air Sensor : 0.0°CS4 Defrost 1 : 0.0°CS5 Defrost 2 : 0.0°CS6 Defrost 3 : 0.0°CS7 Defrost 4 : 0.0°CS8 Cp Dish 1 : 0.0°CS9 Cp Dish 2 : 0.0°CS10 Cp Dish 3 : 0.0°CS11 Cp Dish 4 : 0.0°C

Technical Training 2008Technical Training 2008

Other Information

If the Chiller Panel V1.0 is connected to an inverter mini chiller, there shall be no Inverter features.

Alarm & Contact P4~P19 and Sensor Parameter will display “00”

Technical Training 2008Technical Training 2008