Technical specification / installation
Transcript of Technical specification / installation
6 PANELFIXING 76.1 General 76.2 FastenerDurability 76.3 Fastener—Type,SizeandLayout 76.4 PanelLayout 8
7 JOINTING 87.1 General 87.2 VerticalJoint 87.3 HorizontalJoint 97.4 ExternalCorner 97.5 InternalCorner 97.6 FlashingMaterialDurability 9
8 FINISHING 98.1 Preparation 98.2 FlexibleSealants 9
9 STORAGEANDHANDLING 9
10 MAINTENANCE 10
11 PRODUCTINFORMATION 1011.1 ManufacturingandClassification 1011.2 ProductMass 1011.3 Durability 10
12 SAFEWORKINGPRACTICES 11
13 PRODUCTSIZESANDACCESSORIES 13
14 DETAILS 15
PRODUCTWARRANTY 47
1 APPLICATIONANDSCOPE 31.1 Application 31.2 Scope 31.3 Details 31.4 SpecificDesign 3
2 DESIGN 32.1 Compliance 32.2 Responsibility 32.3 SiteandFoundation 32.4 SurfaceClearances 42.5 MoistureManagement 42.6 Structure 42.7 Bracing 42.8 FireRatedWalls 42.9 EnergyEfficiency 4
3 FRAMING 53.1 General 53.2 TimberFraming 53.3 SteelFraming 53.4 ConstructionMethods 53.5 Tolerances 5
4 PREPARATION 54.1 BuildingUnderlayorHomeRABPre-Cladding 54.2 RigidAirBarrier 54.3 VentStrip 54.4 Flashings 64.5 JunctionsandPenetrations 6
5 BATTENINSTALLATION 65.1 CLDStructuralCavityBattens 65.2 BattenLayout 65.3 IntermediateSupport 65.4 BattenFasteners 6
Contents
THISTECHNICALSPECIFICATIONISFORAXON®PANELDIRECT
FIXEDANDFIXEDTOCLD®STRUCTURALCAVITYBATTEN.
WEVALUEYOURFEEDBACKTocontinuewiththedevelopmentofourproductsandsystems,wevalueyourinput.Pleasesendanysuggestions,includingyourname,contactdetails,andrelevantsketchesto:
Ask James HardieTM [email protected]
Axon®PanelTechnical Specification July 2015NewZealand3
1.3 DETAILSVariousAxonPanelfiguresareprovidedintheDetailssectionofthisdocument.Alldimensionsshownareinmillimetresunlessnotedotherwise.ThisspecificationanddetailsinCADfilearealsoavailablefordownloadatwww.jameshardie.co.nz.
1.4 SPECIFIC DESIGNForuseofAxonPaneloutsidethispublishedscope,thearchitect,designerorengineermustundertakespecificdesign.
Foradviceondesignsoutsidethescopeofthisspecification,AskJamesHardieon0800808868.
2 Design2.1 COMPLIANCEAxonPanelcomplieswithE2oftheNZBCasanalternatesolution.
AxonPanelcladdinghasbeentestedasperE2/VM1oftheNZBCanditpassesthetestperformancerequirements.AxonPanelalsocomplieswithdurabilityrequirementsof‘B2’clauseoftheNZBC.
2.2 RESPONSIBILITYThespecifierorotherpartyresponsiblefortheprojectmustrunthroughariskmatrixanalysistodeterminewhichconstructionmethodistobeused.Thedesignermustalsoensurethatthefigurespublishedinthisspecificationareappropriatefortheintendedapplicationandthatadditionaldetailingisperformedforspecificdesignoranyareasthatfalloutsidethescopeofthisspecification.ThedesignersshouldensurethattheintentoftheirdesignmeetstherequirementsoftheNZBC.
AllNewZealandStandardsreferencedinthismanualarecurrenteditionandmustbecompliedwith.
JamesHardieconductsstringentqualitycheckstoensurethatanyproductmanufacturedfallswithinourqualityspectrum.Itistheresponsibilityofthebuildertoensurethattheproductmeetsaestheticrequirementsbeforeinstallation.JamesHardiewillnotberesponsibleforrectifyingobviousaestheticsurfacevariationsfollowinginstallation.
2.3 SITE AND FOUNDATIONThesiteonwhichthebuildingissituatedmustcomplywiththeNZBCAcceptableSolutionE1/AS1‘SurfaceWater’.
FoundationsdesignmustcomplywiththerequirementsofNZS3604‘Timber-framedBuildings’orbeasperspecificengineeringdesign.
ThegradeofadjacentfinishedgroundmustslopeawayfromthebuildingtoavoidanypossibilityofwateraccumulationinaccordancewiththeNZBCrequirements.
1 Application and scope
1.1 APPLICATIONAxon®PanelismanufacturedinNewZealandbyJamesHardieusinganadvancedlightweightcementcomposite.Basecompositionisportlandcement,groundsand,cellulosefibreandwater.AxonPanelhasverticalgroovesalongthepanel.Itisclassifiedaslightweightwallcladdingsuitableforresidentialandlightcommercialbuildingsusingtimberframing.
•AxonPanelisidealforachievingfeaturewallsinareassuchasgableendsandentranceways.
•AxonPanelisprimedonthefacetotakeasuitablepaintfinishinanycolour.
•AxonPanel133Smooth-thegroovesonthefacepanelarenominal10mmwidex2.25mmdeepandspacedat133mmcentres.
•AxonPanel133Grained-thegroovesonthefacepanelarenominal10mmwidex2.25mmdeepandspacedat133mmcentres.Betweenthegroovesisalookoftraditionalwood-graintexture.
•AxonPanel400Smooth-thegroovesonthefacepanelarenominal10mmwidex2.25mmdeepandspacedat400mmcentres.
If you are a specifier Orotherresponsiblepartyforaproject,ensurethattheinformationinthisdocumentisappropriatefortheapplicationyouareplanningandthatyouundertakespecificdesignanddetailingforareaswhichfalloutsidethescopeofthesespecifications.
If you are an installer Ensurethatyoufollowthedesign,moisturemanagementprinciples,associateddetailsandmaterialselectionprovidedbythedesigner.Allofthedetailsprovidedinthisdocumentmustbereadinconjunctionwiththisspecification.
Make sure your information is up to dateWhenspecifyingorinstallingJamesHardieproducts,ensureyouhavethecurrentmanual.Ifyou’renotsureyoudo,oryouneedmoreinformation,visitwww.jameshardie.co.nzorAskJamesHardie™on0800808868.
1.2 SCOPEThescopeofthisspecificationfortheuseofAxonPanelislimitedtobuildingswhichfallwithinthescopelimitationsof‘AcceptableSolutionE2/AS1paragraph1.1’oftheNewZealandBuildingCode(NZBC).
Thisdocumentisintendedforusebyarchitects,designersandspecifierswhomaybeinvolvedwiththespecificationofAxonPanel.
ThismanualcoverstheuseofAxonPanelforbothconstructionmethodsi.e.directfixedtoframingorcavityconstruction,usedinexternalwallsoftimberframedbuildingsupto2.5kPa.
PleaserefertoE2/AS1forfurtherinformationregardingtheselectionofconstructionmethodstobeusedforfixingcladdings.
4Axon®PanelTechnical Specification July 2015NewZealand
2.4 SURFACE CLEARANCESTheclearancebetweenthebottomedgeofcladdingandpaved/unpavedgroundmustcomplywithsection9.1.3ofE2/AS1.ThefinishedfloorlevelmustalsocomplywiththeserequirementsTheseclearancesmustbemaintainedthroughoutthelifeofthebuilding.
AxonPanelmustoverhangthebottomplateonaconcreteslabbyaminimumof50mmasrequiredbyNZS3604.
AxonPanelmusthaveaminimumclearanceof100mmfrompavedground,and175mmfromunpavedground.Ontheroofsanddecks,theminimumclearancemustbe50mm.
Donotinstallexternalcladdingsuchthatitmayremainincontactwithwaterorground.ReferFigures3and18.
2.5 MOISTURE MANAGEMENTItistheresponsibilityofthespecifiertoidentifymoisturerelatedrisksassociatedwithanyparticularbuildingdesign.
Wallconstructiondesignmusteffectivelymanagemoisture,consideringboththeinteriorandexteriorenvironmentsofthebuilding,particularlyinbuildingsthathaveahigherriskofwinddrivenrainpenetrationorthatareartificiallyheatedorcooled.
WallsshallincludethoseprovisionsasrequiredbytheNZBCAcceptableSolutionE2/AS1‘ExternalMoisture’.Inadditionallwallopenings,penetrations,junctions,connections,windowsills,headsandjambsmustincorporateappropriateflashingsforwaterproofing.Theothermaterials,componentsandinstallationmethodsusedtomanagemoistureinexternalwalls,mustcomplywiththerequirementsofrelevantstandardsandtheNZBC.
2.6 STRUCTURE2.6.1 Timber framingTimber-framedbuildingsmustbedesignedinaccordancewithNZS3604(Timber-framedBuildings).Whentheframingisprovidedasperthespecificengineeringdesign,theframingstiffnessmustbeeitherequivalenttoormorethanthestiffnessrequirementsofNZS3604.
Fortimberframewallslongerthan12mitisbestpraticetoallowforconstructionjointstoaccommodatemovementsgeneratedduetotimbershrinkageordeflectionsetc.
2.6.2 Wind loadingAxonPanelissuitableforuseinallwindzonesinNewZealanduptoandincludingEHasdefinedinNZS3604.
AspecificdesignisrequiredforallsituationswherethebuildingsfallsoutsidethescopeofNZS3604andE2/AS1.
2.7 BRACINGAxonPaneldirectfixedcanbeusedtoachievestructuralbracingwhenfixedwithstainlesssteelHardieFlex™nails.ForfurtherinformationrefertotheJamesHardieBracingDesignManual.
AxonPanelinstalledtoCLDStructuralCavityBattensasperthisspecificationhasnotbeentestedandthereforecannotbeused
toachievestructuralbracing.However,bracingcanbeachievedbyusingJamesHardierigidairbarrierboardinstalleddirecttoframinginsteadofabuildingunderlayorbyusingVillaboard®Liningbracingsystemontheinternalface.
2.8 FIRE RATED WALLSAxonPanelwhendirectfixedwithHardieFlexnailstoexternalwallscanachievefireratingsupto60/60/60tocomplywithC/AS1oftheNZBCwhenthewallsareconstructedinaccordancewiththecurrentJamesHardie‘FireandAcousticDesignManual’.
WhenusingAxonPanelfixedtoCLDStructuralCavityBattens,afireratingofupto60minutescanbeachievedusingRAB®BoardinconjunctionwiththefireratedsystemrequirementsasspecifiedintheJamesHardie‘FireandAcousticDesignManual’.AskJamesHardieon0800808868forfurtherinformation.
AxonPanelisclassifiedasanon-combustiblematerialsuitableforuseonwallsclosetoboundary.
2.9 ENERGY EFFICIENCY ExternalwallsconstructedusingAxonPanel,bulkinsulation,wheretheareaofglazingis30%orlessofthetotalwallareaandconstructedasperthistechnicalspecificationcomplywiththerequirementsforwallsintheNZBCAcceptableSolutionH1/AS1(NZBCClauseH1EnergyEfficiency),ReplacementTable1.Tomeetthermalinsulationrequirementsfortheconstruction,thebulkinsulationasspecifiedinTable-1mustbeused.ThisinsulationmaybesubstitutedwithinsulationshavinghigherR-values.Thethermalinsulationofawallgetsaffectedwhenthedepthofthetimberframingisincreasedordecreased.ThecalculationusedinTable1isbasedonatimberframingsize90x45mmandusinganinternalliningmaterialsuchasJamesHardieVillaboard®Liningora10mmplasterboard.
Table1Insulationcapability
Climate Zone
Construction R‑Value Requirement
Minimum R‑Value of Insulation Required
1and2 1.9m2ºC/W #R2.0
3 2.0m2ºC/W #R2.2
TotalconstructionR-Valuedependsontheinsulationmaterialusedandtheframingratio.TheinsulationmaterialR-Valuesspecifiedinthistableareforstudsspacedat600mmc/candnogsspacedat800mmc/c.
#ToachievehigherR-ValuesofconstructionthewallinsulationmaterialmustbereplacedwithaninsulationmaterialhavinghigherR-Valuestosuittherequirements.
Forfurtherguidanceoninsulationrequirementsrefertothecurrenteditionof‘HouseInsulationGuide’publishedbyBRANZ.
Axon®PanelTechnical Specification July 2015NewZealand5
3.4 CONSTRUCTION METHODS3.4.1 Direct fixed Fordirectfixedconstructionmethodthefollowingframingisrequired:
•Studsat600mmc/cmaximum
•Aminimum45mmstudwidthisrequiredatverticalpaneljoints
•Nogs/dwangsarerequiredat1200mmc/cmaximum.
3.4.2 CLD Structural Cavity BattenForcavityconstructionmethodthefollowingframingisrequired:
•Whenstudsarespacedat600mmcentresmaximum,thenogs/dwangsmustbeprovidedat800mmcentresmaximum
•Whenstudsarespacedat400mmcentresthenthenogs/dwangsmaybeprovidedat1200mmcentres
•Anextrastudisrequiredininternalcorners.RefertoFigure21.
3.5 TOLERANCESInordertoachievetherequiredperformanceandanacceptablewallfinish,itisimperativethatframingisstraightandtrue.
FramingtolerancesmustcomplywiththerequirementsofNZS3604.Allframingshallbemadeflush.
4 Preparation4.1 BUILDING UNDERLAY OR
HOMERAB PRE-CLADDINGBuildingunderlayorHomeRAB®Pre-CladdingmustbeprovidedaspertherequirementsoftheNZBCAcceptableSolutionE2/AS1‘ExternalMoisture’andNZS3604.ThebuildingunderlaymustcomplywithTable23ofE2/AS1andAS/NZS4200.1.ThebuildingunderlaymustbefixedinaccordancewithE2/AS1,NZS3604andAS/NZS4200.2andtheunderlaymanufacturer’srecommendations.
Wallswhicharenotlinedontheinsidefacee.g.garagewallsorgableendsmustincludearigidsheathingoranairbarrierbehindthecladdingwhichcomplieswiththerequirementsoftheNZBCAcceptableSolutionE2/AS1Table23.HomeRABPre-Claddingissuitableforuseintheseapplications.ItmustbeinstalledinaccordancewiththeJamesHardieRigidAirBarriersinstallationmanual.
4.2 RIGID AIR BARRIERForEHwindzoneorSpecificEngineeringDesignprojectswherethewindpressuresarehigherthan1.5kPa(ULS),RABBoard(6mm)mustbeused.RefertotheJamesHardierigidairbarriersinstallationmanualforinformationregardingitsinstallation.ForbuildingswithinthescopeNZS3604HomeRABPre-CladdingLining(4.5mm)orbuildingunderlayscanbeused.
3 Framing
3.1 GENERALThisAxonPaneltechnicalspecificationisonlysuitablefortimber-framedbuildings.Otherframingmaterialsaresubjecttoaspecificengineeringdesign.
3.2 TIMBER FRAMING3.2.1 DimensionsAminimum45mmwidestudisrequired.
3.2.2 Structural gradeMinimumtimbergraderequirementisNo.1framinggradeorMSG6asperNZS3604.ThegradingoftimbermustcomplywiththeAS/NZS1748andNZS3631requirements.
3.2.3 DurabilityTheexternalframingmustbetreatedtoaminimumH1.2treatment.RefertotheNZBCAcceptableSolutionB2/AS1‘Durability’forfurtherinformationaboutthedurabilityrequirements.
FortimbertreatmentandallowablemoisturecontentinformationrefertoNZS3602(TimberandWood-BasedProductsforuseinBuildings)andNZS3640(ChemicalPreservationofRoundSawnTimber)forminimumtimbertreatmentselectionandtreatmentrequirements.
Alsorefertotheframingmanufacturer’sliteratureforfurtherguidanceontimberselection.Framingmustbeprotectedfrommoistureatsiteinaccordancewiththerecommendationoftheframingmanufacturers.
3.2.4 Frame constructionTheframingmustfullysupportallpaneledges.Theframingmustberigidandnotrelyonthecladdingpanelforstability.
Timberframingsizesanditsset-outmustcomplywithNZS3604andasspecifiedinthisspecification.
Incaseofgableendtrussessittingontopplatesoftheexternalwallframe,theframesizemustcomplywiththeminimumtimbersizesstipulatedforwallframesinSection8oftheNZS3604.
3.3 STEEL FRAMING3.3.1 Dimensions and gaugeA38mmminimumstudwidthisrequired.Framingmembersmustbe0.55mmminimumto1.6mmmaximumBMT(BaseMetalThickness).
3.3.2 DurabilityThesteelframingmusthavetheappropriatelevelofcoatingtopreventcorrosionandtocomplywiththedurabilityrequirementsoftheNZBC.
3.3.3 Frame constructionSteelframingmustcomplywithNASHhandbook/guidelinesStudandbattenspacingmustnotbemorethanwhathasbeenspecifiedinthisspecification.Refertoframingmanufacturer’sspecificationsandalsotoNASHforfurtherguidanceonsteelframeinstallation.
ForfurtherinformationregardingtheinstallationofJamesHardieCladdings,referto‘SteelFrameTechnicalSupplement’publishedbyJamesHardie.
6Axon®PanelTechnical Specification July 2015NewZealand
4.3 VENT STRIPTheJamesHardieuPVCcavityventstripmustbeinstalledatthebottomofallwallsconstructedusingthedrainedandventilatedcavityconstructionmethod.Itisimportantthattheopeningsintheventstriparekeptclearandunobstructedtoallowfreedrainageandventilationofcavities.JamesHardieuPVCventstriphasanopeningareaof1000mm²/mlength.
4.4 FLASHINGAllwallopenings,penetrations,intersections,connections,windowsills,headsandjambsmustbeflashedpriortopanelinstallation.PleaserefertomoisturemanagementrequirementsinClause2.5.ThebuildingunderlayorRABBoardmustbeappropriatelytapedaroundthepenetrationsandlapped/tapedtoflashings.Materialsmustbelappedinsuchawaythatwatertracksdowntotheexteriorofabuilding.JamesHardiewillassumenoresponsibilityforwaterinfiltrationwithinthewallduetopoorinstallationofflashingsorbuildingunderlays.TheselectedflashingmaterialsmustcomplywiththedurabilityrequirementsoftheNZBC.ForinformationrefertoTable20ofclauseE2oftheNZBC.
WhenusingaJamesHardierigidairbarrierboardtheentireframingaroundwindowopeningmustbesealedwithaflashingtape.ThetapemustbefinishedoverthefaceofJamesHariderigidairbarrierboard.TheflashingtapeslikeSUPER-STICKBuildingTape®byMarshallInnovationsor3M™AllWeatherFlashingTape8067by3M™arerecommendedforusewithJamesHardierigidairbarrierboard.Refertothetapemanufacturer’sliteratureforfurtherinformationregardingtheirinstallation.
4.5 JUNCTIONS AND PENETRATIONSRefertoClause2.5ofthisspecificationformoisturemanagementrequirements.Allwindowsanddoorsmustbedetailedaspertherequirementsofthisspecification.JamesHardiehasdevelopedthewindowdetailsforAxonPanelwhichmeettherequirementsofE2‘ExternalMoisture’,anapproveddocumentoftheNZBC.RefertoFigures8to10and24to26.
5 Batten installation
Note:Thisspecificationisnotfortimbercavitybattens.RefertoseparatetechnicalspecificationfromJamesHardie.
5.1 CLD STRUCTURAL CAVITY BATTENSBuildingswithariskscoreof7-20calculatedinaccordancewithTable2ofAcceptableSolutionE2/AS1oftheNZBC,requireAxonPaneltobeinstalledonacavity.CLDStructuralCavityBattensprovideairspacebetweentheframeandthepanelandareusedtofixcladdingintothem.
CLDStructuralCavityBattensaremadeofalowdensityfibrecementformulationwhichenablesthemtohaveextrastrengthanddurability.CLDStructuralCavityBattenissealedonallsidesandissuitabletofixAxonPanelinstalledasperthistechnicalspecification,anditcanwithstandthedesignwindpressuresexertedonacladdingwithinthescopeofNZS3604.
TheCLDStructuralCavityBattensaremade2450mmlongand19mmthick.Thebattensarefullysealedonallsides.
5.2 BATTEN LAYOUTCLDStructuralCavityBattensmustbefixedtothewallframingoverbuildingunderlayorJamesHardierigidairbarrier.Thesmootherfaceofbattenshouldfacetowardsthecladding.
CLDStructuralCavityBattensaresuitabletowithstandwindpressuresupto2.5kPa(ULS).Forbattenfixing,refertosection5.4.EnsurethebattensarestraightandprovideaflatsurfacetofixAxonPanelto.SitecutendsofbattensmustbesealedonsitewithDulux®Acraprime501/1sealerorReseneQuickDry.
Thebattensareruncontinuouslyoverthestudsbuttheymustnotberuncontinuouslyoverthefloorjoists.Theremustbea15mmgapbetweenthebattensatfloorjoistleveltoallowforstructuralshrinkagesanddeflections.RefertoFigure27.
CLDStructuralCavityBattenscanbebuttjointedoverthestudswithinthefloorheight.Thebattenendsmustbecutbetween20ºto45ºandbeinstalledinawaythatthebuttjointdeflectsthemoisturetotheexterior.Theendsmustbesealedandjointedwiththeadhesivesealantbeforebuttingthemtogether.RefertoFigure23.
ThedesignermustensurethattheCLDStructuralCavityBattensarenotusedinsituationswheredesignwindpressuresareabove2.5kPa(ULS).
CLDStructuralCavityBattensmustalwaysbeatleast300mminlength.
5.3 INTERMEDIATE SUPPORTWherestudsareat600mmcentresanintermediatemeansofrestrainingthebuildingunderlayandinsulationfrombulgingintothecavityshallbeinstalled.Anacceptablemethodtoachievethisisusinga:
•75mmgalvanisedmesh
•polypropylenetapeat300mmcentresfixedhorizontallyanddrawntaut.
Nointermediatesupportsarerequired:
•whenstudsarespacedat400mmcentres
•whenRABBoardinsteadofbuildingunderlaysareused.
5.4 BATTEN FASTENERSTheCLDStructuralCavityBattenmustbefixedtotheframingasspecifiedinTable2.Thefastenersmustbedrivenataminimumdistanceof50mmfromthebattenends.
Axon®PanelTechnical Specification July 2015NewZealand7
Table2Battenfixing
Fixing Type
Framing Basic Wind Pressure kPa (ULS)
Batten centres max. (mm)
Fixings centres max. (mm)
65mmx2.8mmRounDriveringshanknailhotdipgalv./s.steel
Timber Upto1.5(UptoandincludingVHwindzone)
600 250
Upto2.5(>VHwindzone)
400 200
50mmx9-10gCountersunkheadsteelscrewclass3/4
*Steel0.55to1.6mmBMT
Upto1.5(UptoandincludingVHwindzone)
600 250
Upto2.5(>VHwindzone)
400 200
*WhenfixingCLDStructuralCavityBattensoversteelframe,providea10mmthickHDPbattenunderthewraporRABBoardtoachieveathermalbreak.
*Ensureaminimum15mmpenetrationofscrewintosteelframe.
Whenusingarigidairbarrierboardthebattenfixingmustbeincreasedbyminimumthicknessofrigidairbarrierboard.
Forfastenerdurabilityinformation,refertoClause6.2ofthisdocument.
CLDStructuralCavityBattenslessthan400mminheightmusthavefixingsatmaximum150mmcentres.
Battensmustbefixedoverstuds.
6 Panel fixing6.1 GENERALAxonPanelmustbekeptdryandundercoverwhilstinstorageorduringtheinstallation.Everyendeavourmustbemadetokeepframingdryoncepanelfixingcommences.Allsite-cutpaneledgesmustbesealedpriortoinstallation.
•Theshiplapjointingofpanelsisonlysuitableforverticalfixingofpanels.
•DonotfixinthegrooveofAxonPanel.
•Ensurethesheetsarefromthesamebatch.
•Itisrecommendedtofixfromthecentreofthepanelandworkoutwards.
•Donotoverdrivefasteners.
•Fixingsmustbefinishedflushwiththepanelsurface.
6.2 FASTENER DURABILITYFastenersmustmeettheminimumdurabilityrequirementsoftheNZBC.NZS3604specifiestherequirementsforfixingmaterialtobeusedinrelationtoexposureconditionsandaresummarisedinTable3.
Table3ExposureconditionsandnailselectionprescribedbyNZS3604
NAIL MATERIAL
ZoneD* ZoneC*outsideseasprayzone,ZoneBandGeothermalhotspots
Bracing—AllZones
Grade316Stainless
Hot-dippedgalvanisedorGrade316stainless
Grade316Stainless
*(ZoneCareaswherelocalknowledgedictatesthatincreaseddurabilityisrequired,appropriateselectionshallbemade).MicroclimateconditionsasdetailedinNZS3604,paragraph4.2.4requireSED.
AlsorefertotheNZBCAcceptableSolutionE2/AS1Table20and21forinformationregardingtheselectionofsuitablefixingmaterialsandtheircompatibilitywithothermaterials.
6.3 FASTENER — TYPE, SIZE AND LAYOUT
6.3.1 Direct fixAxonPanelmustbefixedtoframingusingthefixingsasspecifiedinTable4belowandfollowtheedgedistancerequiredfornailsasshowninthedetails.RefertoFigures2and4.
Table4Panelfixing
DIRECT FIXED TO FRAME USING HARDIEFLEX NAILS
40x2.8mmHardieFlexnails.
Fix@200mmcentrestoallframing.Studwidth45mmmin.requiredatverticaljoint.
DIRECT FIXED TO FRAME USING BRAD NAIL
ND50stainlesssteelstraightbradnail
Upto1.5kPa(UptoandincludingVHwindzone)
Fix150mmc/conpaneledgesandintermediateframing
Notes:
1.Bradnailfixingmethodisonlysuitableuptoveryhighwindspeedzones.DonotusethismethodforEHwindzonesdescribedinNZS3604orSEDprojects.
2.Nailsmustbefinishedflushwithpanelsurface.
3.Specialfixingarrangementsarerequiredforbracingandfire-resistanceratedwallsystems.
FormoreinformationAskJamesHardieon0800808868.
Whenfixingthepanelsusingnailguns,refertothenailgunmanufacturerforinformationaboutnailsandthetypeofnailguntobeused.
Note:Donotuse‘D’headnails.
8Axon®PanelTechnical Specification July 2015NewZealand
6.3.2 CLD Structural Cavity Batten MethodThispanelfixingmethodcanbeusedupto2.5kPawindpressure.AxonPanelisonlyfixedintotheCLDStructuralCavityBattenasperthismethod.
Adhesive sealantApolyurethaneadhesivesealantSealNFlex-1manufacturedbyBostikorSikaFlex11FCbySikaarerecommendedforuseintheinstallationoftheseproducts.Applya6mmcontinuousbeadofthisadhesivesealantoverthefaceoftheCLDStructuralCavityBattenbeforefixingtheAxonPanel.RefertoFigure19,20and21.
Whenusingexternalboxcornerflashing,usea10mmthickbeadofadhesiveoverthealuminiumboxcornerflanges.RefertoFigure22.
Note:Donotuseexcessiveadhesive.
6.3.3 Cavity construction using timber cavity battensWhenfixingAxonPanelusingtimbercavitybattens,thesedetailsareavailableatwww.jameshardie.co.nzorAskJamesHardieon0800808868.
6.4 PANEL LAYOUTAllpaneledgesmustbesupportedbytheframing.Theshiplapjointmustbeformedvertically.Theframingcentersmustbecheckedbeforethepanelinstallation.
FixAxonPaneltoCLDStructuralCavityBattensusingoneofthefollowingfixingsspecifiedinTable5.Theedgedistanceatpanelcornermustbeminimum75mmverticallyfrompanelcorners.ReferFigure17.
Table5AxonPanelFixing
Types of fixings to be used with adhesive sealants
Suitable up to Basic Wind Pressure kPa (ULS)
Fixing to CLD Structural Cavity Battens c/c (mm)
C-25straight‘T’-Headstainlesssteelbradnail
1.5(UptoandincludingVHwindzone)
150
25x2.5mmannularthreadedfibrecementnail
2.5(>VHwindzone)
200
25mmx10gcountersunkscrewclass3/4orstainlesssteel
2.5(>VHwindzone)
200
Notes:
1.Bradnailfixingmethodisonlysuitableupto1.5kPa.
2.Nailsmustbefinishedflushwithpanelsurface.
7 Jointing7.1 GENERALAxonPanelsarefixedtoformashiplapjointatverticaledges.Thepanelshavefactory-madeedgestosuitthisjointing.
7.2 VERTICAL JOINTDirect fixedAxonPanelsareshiplapjointedkeepingagapof1-2mmbetweenthepanels.A50mmwide3259Insealsealingtapeisusedunderthejointoverthefaceofthetimberstudwheredirectfixedconstructionmethodisused.Aflexiblesealantmustbeappliedtothefulllengthoftheshiplapjointbeforethepanelsarejointed.TheedgedistanceforaHardieFlexnailmustbe18mmmin.RefertoFigure4.
Cavity constructionFixtheCLDStructuralCavityBattenoverthestudsanditrunsbehindtheentirelengthoftheshiplapjointwitha50mmoverhangbelowthebottomplateandfinishesflushwiththebottomedgeofpanel.RefertoFigures16and17.Theverticalshiplapjointisformedalongthecentrelineofthebatten.AbeadofsealantisappliedtotheverticaledgeoftheAxonPaneltosealtheshiplapjointbeforefixingthepanels.RefertoFigure19.Theedgedistanceforabradnailmustbe16mmand18mm.ReferFigures14and19.
Brad nail
www.jameshardie.co.nz
James HardieAxon™ Panel and CLD® Structural Cavity BattenFIGURE 15: BRAD NAIL FIXING5 March 2008
1:2
n_zl-axoncld-015.dwg
Bradnail
Brad nail
www.jameshardie.co.nz
James Hardie Axon™ Panel and CLD® Structural Cavity BattenFIGURE 15: BRAD NAIL FIXING 5 March 2008
1:2
n_zl-axoncld-015.dwg
Brad nail
www.jameshardie.co.nz
James HardieAxon™ Panel and CLD® Structural Cavity BattenFIGURE 15: BRAD NAIL FIXING5 March 2008
1:2
n_zl-axoncld-015.dwgBradnail
Brad nail
www.jameshardie.co.nz
James Hardie Axon™ Panel and CLD® Structural Cavity BattenFIGURE 15: BRAD NAIL FIXING 5 March 2008
1:2
n_zl-axoncld-015.dwg
Brad nail
www.jameshardie.co.nz
James HardieAxon™ Panel and CLD® Structural Cavity BattenFIGURE 15: BRAD NAIL FIXING5 March 2008
1:2
n_zl-axoncld-015.dwg
Bradnail
Brad nail
www.jameshardie.co.nz
James Hardie Axon™ Panel and CLD® Structural Cavity BattenFIGURE 15: BRAD NAIL FIXING 5 March 2008
1:2
n_zl-axoncld-015.dwg
Axon®PanelTechnical Specification July 2015NewZealand9
8 Finishing
7.3 HORIZONTAL JOINTAtfloorjoistlevelsahorizontaljointmustbeprovidedtoaccommodatethemovementresultingfromtimberjoistshrinkageandsettlement.AJH9mmpanelaluminiumhorizontal‘h’mouldisusedtoformahorizontaljoint.Usethealuminium‘h’mouldjointertocoveroverthebuttjointof‘h’mould.Apurposemademetal‘Z’flashingoraJamesHardieuPVCflashingcouldalsobeusedtoflashthehorizontaljoint.RefertoFigures11,12and27.
7.4 EXTERNAL CORNERAJH9mmpanelaluminiumboxcornermouldisusedtoformtheexternalboxcorner.Thesite-cutsheetedgesmustbesealedbeforebuttingthemintotheboxcorner.RefertoFigure7.
Donotruntheboxcornerflashingcontinuouslyoverthefloorjoist.Onatwostoreyconstructionthealuminiumboxcornerisfinishedunderthealuminium‘h’mould.AuPVCcornerunderflashingmustbeusedundertheboxcornerwheninthissituation.RefertoFigure12.
ForCLDStructuralCavityBattenexternalcornerrefertoFigure22.
Thebeadofadhesivemustbe10mmthicktoaccommodateforthethicknessofthealuminium.
7.5 INTERNAL CORNERDirectfixedinternalcornerisformedusingauPVCcornerunderflashingoran80mmwideInsealsealingstripbehindthepaneledges.Thejointisfilledwiththeflexiblesealant.RefertoFigure6.
ForCLDStructuralCavityBatteninternalcornerjointdetailrefertoFigure21.
7.6 FLASHING MATERIAL DURABILITYPleaserefertoTable20ofE2/AS1oftheNZBCregardingthedurabilityrequirementsofvariousflashingmaterials.
8.1 PREPARATIONPaintingofAxonPanelismandatorytomeetthedurabilityrequirementsoftheNZBCand15yearJamesHardieproductwarranties.AxonPanelmustbedryandfreeofanydustorgrimebeforepainting.Thepanelsmustbepaintedwithin90daysoftheirinstallation.ThereisnorestrictionontheLRVofpainttobeappliedontheAxonPanel.
WhenusinguPVCflashings,darkcoloursshouldbeavoidedasitwillaffectthedurabilityofuPVCflashing.TheLRVofpaintmustbeabove40%whenusinguPVCflashings.
Darkpaintscanbeusedwhenusingthealuminiumflashings.
Panelsarepre-primedandaresuitableforsiteappliedacrylicpaints.Pre-finishedpanelscanalsobeinstalledusingexposedheadfasteners.
Inordertosealcutedgesorsandedpatches,DuluxPrimacryl,Resenequickdryorasimilarproductshouldbeapplied.Theprimershouldbecompatiblewiththepainttobeused.
Wherepanelsarefixedwithbradnails,thenailheadsmustbefinishedflushwithpanelsurface.Thenailgunshouldbesettonail“proud”ofthepanelsurfaceandnailheadstobemanuallyfinishedflushwithsurface.Thenailheadscanbeskimmedoverwithanexteriorgrade2partbuildersfillifrequired.Theskimmedareamustbeprimedpriortosite-appliedfinishing.
Forsite-appliedfinisheswherebradnailsareused.JamesHardierecommendsanundercoatandaminimumoftwocoatsofacrylicpaint.Followthepaintmanufacturer’srecommendationstopreparethesurfaceandtoadequatelycoverandconcealthepanelfixings.
8.2 FLEXIBLE SEALANTAllsealantsusedmustcomplywiththerelevantrequirementsoftheNZBC.Theirapplicationandusagemustbeinaccordancewithmanufacturer’sinstructions.Checkwithsealantmanufacturerpriortocoatingoversealants.Somesealantmanufacturersdonotrecommendcoatingovertheirproducts.
9 Storage and handling
WhenstoringAxonPanel,boardsmustbelaidflatonasmoothlevelsurface.Edgesandcornersmustbeprotectedfromchipping.
Toensureoptimumperformance,storepanelsundercoverandkeepdrypriortofixing.Ifthepanelsbecomewet,allowthemtodrythoroughlybeforefixing.
Donotcarrypanelsontheflat,carryintheverticalpositiontoavoidexcessivebending.
10Axon®PanelTechnical Specification July 2015NewZealand
10 Maintenance 11 Product information
11.1 MANUFACTURING AND CLASSIFICATION
AxonPanelisanadvancedlightweightcementcompositebuildingproduct.Thebasiccompositionisportlandcement,groundsand,cellulosefibreandwater.Thepanelsareeasilyidentifiedbythename‘AxonPanel’printedatregularintervalsonthebackfaceofpanel.
CLDStructuralCavityBattensaremanufacturedusingalowdensityfibrecementformulation.ThebasiccompositionisPortlandcement,groundsand,cellulosefibreandwaterandproprietaryadditives.Thebattensaresealedonallsides.
AxonPanelismanufacturedtoAS/NZS2908.2‘Cellulose-CementProductsPart2:FlatSheets’(ISO8336’FibreCementFlatPanels’)standardsinNewZealand.JamesHardieNewZealandisanISO9001‘Telarc’certifiedmanufacturer.
AxonPanelisclassifiedTypeA,Category3inaccordancewithAS/NZS2908.2“Cellulose-CementProducts”.
ForSafetyDataSheets(SDS)visitwww.jameshardie.co.nzorAskJamesHardieon0800808868.
11.2 PRODUCT MASSAxonPanelismanufacturedin9.0mmthicknessandhasamassof12.1kg/m2atEMC.
AxonPanelcladdingisdefinedasaLightWeightWallCladding(notexceeding30kg/m2)asperNZS3604.
11.3 DURABILITY11.3.1 GeneralAxonPanelinstalledasperthistechnicalspecificationwillmeetthedurabilityrequirementsforcladdingsasrequiredunderclause‘B2-Durability’oftheNZBC.
11.3.2 Resistance to moisture/rottingAxonPanelhasdemonstratedresistancetopermanentmoistureinduceddeterioration(rotting)andhaspassedthefollowingtestsinaccordancewithAS/NZS2908.2:
•WaterPermeability(Clause8.2.2).•WarmWater(Clause8.2.4).•HeatRain(Clause6.5).•SoakDry(Clause8.2.5).
11.3.3 Control of External Fire SpreadAxon Panel is tested as per Appendix C C7.1.1 and is classified as ‘Non-Combustible Material’ which is suitable for use as external wall cladding and complies with requirements of Paragraph 5.4 of the NZBC Acceptable Solution C/AS1 and Paragraph 5.8.1 of Acceptable Soluations C/AS2 to C/AS6 of the NZBC.
11.3.4 Alpine regionsInregionssubjecttofreeze/thawconditions,AxonPanelmustnotbeindirectcontactwithsnoworicebuildupforextendedperiods,e.g.externalwallsinalpineregionsmustbeprotectedwheresnowdriftsoverwinterareexpected.
TheAxonPanelhasbeentestedinaccordancewithAS/NZS2908.2Clause8.2.3.
Theextentandnatureofmaintenancewilldependonthegeographicallocationandexposureofthebuilding.Asaguide,itisrecommendedthatbasicnormalmaintenancetasksshallincludebutnotbelimitedto:
•Washingdownexteriorsurfacesevery6-12months*
•Re-applyingofexteriorprotectivefinishesifnecessary**
•Maintainingtheexteriorenvelopeandconnectionsincludingjoints,penetrations,flashingsandsealantsthatmayprovideameansofmoistureentrybeyondtheexteriorcladding.
•Cleaningoutgutters,blockedpipesandoverflowsasrequired
•Pruningbackvegetationthatisclosetoortouchingthebuilding
•TheclearancebetweenthebottomedgeofAxonPanelandthefinishedgroundmustalwaysbemaintained.
*Donotuseawaterblastertowashdownthecladding.
*In extreme coastal conditions or sea spray zones, wash every 3-4 months.
**Refertoyourpaintmanufacturerforwashingdownandrecoatingrequirementsrelatedtopaintperformance.
Axon®PanelTechnical Specification July 2015NewZealand11
12 Safe working practices
WARNING — AVOID BREATHING SILICA DUSTJamesHardieproductscontainsand,asourceofrespirablecrystallinesilicawhichisconsideredbyrelevantgovernmentauthoritiestobeacauseofcancerfromsomeoccupationalsources.Breathingexcessiveamountsofrespirablesilicadustcanalsocauseadisablingandpotentiallyfatallungdiseasecalledsilicosis,andhasbeenlinkedwithotherdiseases.Somestudiessuggestsmokingmayincreasetheserisks.Duringinstallationorhandling:(1)workinoutdoorareaswithampleventilation;(2)minimisedustwhencuttingbyusingeither‘ScoreandSnap’knife,fibrecementshearsor,wherenotfeasible,useaHardieBlade™SawBladeanddust-reducingcircularsawattachedtoaHEPAvacuum;(3)warnothersintheimmediateareatoavoidbreathingdust;(4)wearaproperly-fitted,approveddustmaskorrespirator(e.g.P1orP2)inaccordancewithapplicablegovernmentregulationsandmanufacturer’sinstructionstofurtherlimitrespirablesilicaexposures.Duringclean-up,useHEPAvacuumsorwetcleanupmethods—neverdrysweep.Forfurtherinformation,refertoourinstallationinstructionsandSafetyDataSheetavailableatwww.jameshardie.co.nz
FAILURE TO ADHERE TO OUR WARNINGS, SAFETY DATA SHEETS, AND INSTALLATION INSTRUCTIONS MAY LEAD TO SERIOUS PERSONAL INJURY OR DEATH.
JamesHardierecommendedsafeworkingpractices
CUTTING OUTDOORS
1. Positioncuttingstationsowindwillblowdustawayfromtheuserorothersinworkingarea.
2. Useoneofthefollowingmethodsbasedontherequiredcuttingrate:
BEST
• DustreducingcircularsawequippedwithHardieBlade™SawBladeandHEPAvacuumextraction.
GOOD
•DustreducingcircularsawwithHardieBlade™SawBlade.
SANDING/REBATING/DRILLING/OTHER MACHINING
Whensanding,rebating,drillingormachiningyoushouldalwayswearaP1orP2dustmaskandwarnothersintheimmediatearea.
IMPORTANT NOTES
1. Formaximumprotection(lowestrespirabledustproduction),JamesHardierecommendsalwaysusing“Best”—levelcuttingmethodswherefeasible.
2. NEVERuseapowersawindoors.
3. NEVERuseacircularsawbladethatdoesnotcarrytheHardieBlade™logo.
4. NEVERdrysweep—UsewetsuppressionorHEPAvacuum.
5. NEVERusegrinders.
6. ALWAYSfollowtoolmanufacturers’safetyrecommendations.
P1orP2respiratorsshouldbeusedinconjunctionwithabovecuttingpracticestofurtherreducedustexposures.Additionalexposureinformationisavailableatwww.jameshardie.co.nztohelpyoudeterminethemostappropriatecuttingmethodforyourjobrequirements.Ifconcernstillexistsaboutexposurelevelsoryoudonotcomplywiththeabovepractices,youshouldalwaysconsultaqualifiedindustrialhygienistorcontactJamesHardieforfurtherinformation.
12Axon®PanelTechnical Specification July 2015NewZealand
Working instructionsRefertorecommendedSafeWorkingPracticesbeforestartinganycuttingormachiningofproduct.
HardieBlade™ Saw BladeTheHardieBlade™SawBladeusedwithadust-reducingsawconnectedtoaHEPAvacuumisidealforfast,cleancuttingofJamesHardiefibrecementproducts.Adust-reducingsawusesadustdeflectororadustcollectorconnectedtoavacuumsystem.Whensawing,clampastraight-edgetothesheetasaguideandrunthesawbaseplatealongthestraightedgewhenmakingthecut.
Hole‑formingFor smooth clean cut circular holes:Markthecentreoftheholeonthesheet.
Pre-drillapilothole.
Usingthepilotholeasaguide,cuttheholetotheappropriatediameterwithaholesawfittedtoaheavydutyelectricdrill.
For irregular holes:Smallrectangularorcircularholescanbecutbydrillingaseriesofsmallholesaroundtheperimeteroftheholethentappingoutthewastepiecefromthesheetface.
Tapcarefullytoavoiddamagetosheets,ensuringthatthesheetedgesareproperlysupported.
Storage and handlingAllJamesHardiebuildingproductsshouldbestoredtoavoiddamage,withedgesandcornersofthesheetsprotectedfromchipping.
JamesHardiebuildingproductsmustbeinstalledinadrystateandbeprotectedfromrainduringtransportandstorage.Theproductmustbelaidflatundercoveronasmoothlevelsurfaceclearofthegroundtoavoidexposuretowaterormoisture,etc.
QualityJamesHardieconductsstringentqualitycheckstoensurethatanyproductmanufacturedfallswithinourqualityspectrum.Itistheresponsibilityofthebuildertoensurethattheproductmeetsaestheticrequirementsbeforeinstallation.JamesHardiewillnotberesponsibleforrectifyingobviousaestheticsurfacevariationsfollowinginstallation.
Axon®PanelTechnical Specification July 2015NewZealand13
13 Product sizes and accessories
Table7AxonPanelinformation
Product Description Thickness SizeProduct CodeAxon Panel 133 Smooth
Isashiplapjointedpaneltohidethepaneljoints.Thepanelisfaceprimed.Thepanelhasgroovesat133mmcentres.Thepanelmustbeinstalledvertically.Nom.PanelMass:12.1kg/m2
9
Length Width
2450 1200 403780
2750 1200 403781
3000 1200 403782Axon Panel 133 GrainedIsashiplapjointedpaneltohidethepaneljoints.Thepanelisfaceprimed.Thepanelhasgroovesat133mmcentres.Thepanelmustbeinstalledvertically.Nom.PanelMass:12.1kg/m2
9
2450 1200 404510
2750 1200 404511
3000 1200 404512
Axon Panel 400 SmoothIsashiplapjointedpaneltohidethepaneljoints.Thepanelisfaceprimed.Thepanelhasgroovesat400mmcentres.Thepanelmustbeinstalledvertically.Nom.PanelMass:12.1kg/m2
9
2450 1200 404414
2750 1200 404415
3000 1200 404416
Table8Accessories/toolssuppliedbyJamesHardie
Note:Theactualwidthofthepanelis1203mm.Alldimensionsandmassesprovidedareapproximateonlyandsubjecttomanufacturingtolerances.
Accessories Description Quantity/Size (approx) Code
CLD Structural Cavity Batten19mmthickfibrecementcavitybatteninstalledoverRABBoardorabuildingunderlay.AxonPanelsarefixedtothebattens.
19x70mm,2450mmlong 403870
JH 9mm Panel Aluminium External Box CornerAboxcornermouldtoformtheexternaljoints.9mmetchprimed.
2450mmlong
2750mmlong
3000mmlong
4000mmlong
304509
304510
305150
305808
JH 9mm Panel Aluminium Horizontal ‘h’ MouldAhorizontalflashingtoflashthehorizontaljoints.9mmetchprimed.
3000mmlong 304508
Aluminium ‘h’ Mould JointerAjointertocoverthebuttjointof‘h’mould.
100mmlong 304512
uPVC Corner Under Flashing A50x50mmcornerunderflashingforinternalandexternaljoints.
3000mmlong 303745
uPVC Vent StripUsedtoprovideprotectionfromverminenteringcavityspace.
3000mmlong 302490
Annular Threaded Nail 25x2.5mmnail.
500gm 300390
INSEAL® 3259 TapeBlack50mmtapetobeusedundertheverticalshiplapjoint.Black80mmtapetobeusedatcorners.
50mroll
300767
300769
CLD Batten Corner Flashing AluminiumUsedatinternalcornersealantjointsatfloorjoistlevel.
304652
Tools
HardieBlade™ Saw BladeDiamondtip184mmdiameterfibrecementcircularsawblade.Spacersnotincluded.
Each 300660
NOTE:uPVC‘h’mouldandjointeraccessoriesarealsoavailablefromJamesHardie.
14Axon®PanelTechnical Specification July 2015NewZealand
Table9Accessories/toolsnotsuppliedbyJamesHardie
JamesHardierecommendsthefollowingproductsforuseinconjunctionwithAxonPanel.JamesHardiedoesnotsupplytheseproductsanddoesnotprovideawarrantyfortheiruse.Pleasecontactcomponentmanufacturerforinformationontheirwarrantiesandfurtherinformationontheirproducts.
Accessories Description
Building UnderlayTocomplywithTable23ofE2/AS1.
Flexible TapeAflexibleself-adhesivetapeusedinpreparationofawindow.RefertotheWindowinstallationsectioninthismanualformoreinformation.e.g.Tyvek®,ProtectoorThermakraftorsimilar.
Joint SealantPaintableflexiblesealantsarerecommendedforfillingthejoints.RefertoSection7.2forinformation.e.g.SikaSilaflexMS,SikaATFaçade,BostikSealNFlex-1orsimilar
Head FlashingRequiredoverwindowheadstobesuppliedbywindowinstaller.MaterialmustcomplywithTable20and21ofE2/AS1.
Flashing Material as per Table 20, ‘E2/AS1’
HardieFlex™ Hot Dip Galv and Stainless Steel 316 nailsForfixingpanelsdirecttoframing.40x2.8mm
C‑25 Stainless Steel Brad Nails304SSbradnailsusedtoinstallAxonPanelstotheCLDStructuralCavityBattensusedinastraightbradder.Paslode:(09)4773000
ND 50 Stainless Steel Brad NailsUsedtoinstallAxonPaneldirectfixtotimberframing.Usedinastraightbradder.
65 x 2.87mm RounDrive Ring Shank Nail
For fixing CLD Structural Cavity Battens to the framing.
Paslode: (09) 477 3000
Bostik Seal N Flex‑1‘SealNFlex-1’PolyurethaneadhesivesealantmanufacturedbyBOSTIKforapplyingbetweenthepanelsandbattens,Refertosection5formoreinformation.BOSTIK:ALK:(09)5796253,WGTN:(04)5675119,CHCH:(03)3662583.
Sika Sikaflex 11FCSika:0800SIKANZ(0800745269)
200mm wide Polypropylene DPCProductusedoverbuildingunderlayatexternalandinternalcorners.ie.SuperCourse500
Sealant
Adhesive
Adhesive
Axon®PanelTechnical Specification July 2015NewZealand15
14 Details
Thefollowinggenericdetailshavebeenprovidedinthisdocumentforbothdirectfixedandcavityconstructionmethods.
Table10
Details
DescriptionDirect Fixed
CLD Structural Cavity Batten Construction
Figure No. Page No. Figure No. Page No.
Typical framing setout Figure1 16 Figure15 25
Typical panel nail fixing setoutFigure2 17
Figure17 27Figure13 24
Foundation detail Figure3 18 Figure18 28
Vertical shiplap jointFigure4 18
Figure19 29Figure14 25
Soffit detail Figure5 19 Figure29 37
Internal corner detail Figure6 19 Figure21 30
External corner detail Figure7 20 Figure22 31
Section at sill Figure8 20 Figure24 33
Window jamb Figure9 21 Figure25 34
Window head Figure10 21 Figure26 34
Horizontal joint detail Figure11 22Figure27 35
Figure28 36
Corner at ‘h’ mould joint detail Figure12 23
Battenfixingsetout Figure16 26
Intermediate stud fixing Figure20 30
Jointing of CLD Structural Cavity Batten Figure23 32
Externalcorner Figure30 38
Cavitypipepenetration Figure31 38
Internalcorner Figure32 39
Aluminium‘h’mouldjoiner Figure33 40
Onepieceapronflashingjoint Figure34 41
Drained flashing joint at floor joist Figure35 42
Meterboxatsill Figure36 43
Meterboxatjamb Figure37 43
Meterboxathead Figure38 44
JunctionbetweenAxonPanelandfasciaboard Figure39 45
Enclosedrooftowallintersection Figure40 46
Axon®PanelTechnical Specification July 2015NewZealand17
Figure2:DirectfixedtypicalpanelHardieFlexnailfixingsetout
18Axon®PanelTechnical Specification July 2015NewZealand
Figure3:Directfixedfoundationdetail
Figure4:Verticalshiplapjoint—HardieFlexnail
Axon®PanelTechnical Specification July 2015NewZealand19
Figure5:Soffitdetail
Figure6:Internalcornerdetail
20Axon®PanelTechnical Specification July 2015NewZealand
Figure7:Externalcornerdetail
Figure8:Sectionatsill
24Axon®PanelTechnical Specification July 2015NewZealand
Figure13:Directfixedtypicalpanelbradnailfixingsetout
Axon®PanelTechnical Specification July 2015NewZealand25
Figure15:Framingsetout
Figure14:Shiplapjoint—bradnail
30Axon®PanelTechnical Specification July 2015NewZealand
Figure20:Intermediatestudfixing
Figure21:Internalcorner
32Axon®PanelTechnical Specification July 2015NewZealand
Figure23:JointingofCLDStructuralCavityBatten
38Axon®PanelTechnical Specification July 2015NewZealand
Figure30:Externalcornerat‘h’mouldjointdetail
Figure31:Cavitypipepenetration
Axon®PanelTechnical Specification July 2015NewZealand39
Figure32:Internalcornerat‘h’mouldjointdetail
Axon®PanelTechnical Specification July 2015NewZealand43
Figure36:Meterboxatsill
Figure37:Meterboxatjamb
Axon®PanelTechnical Specification July 2015NewZealand45
Figure39:JunctionbetweenAxonPanelandfasciaboard
Ask James HardieTM I Call 0800 808 868 I jameshardie.co.nz
July 2015JamesHardieNewZealand(“JamesHardie”)warrantsforaperiodof15yearsfromthedateofpurchasethattheAxon®PanelandCLDStructuralCavityBattens(the“Product”),willbefreefromdefectsduetodefectivefactoryworkmanshipormaterialsand,subjecttocompliancewiththeconditionsbelow,willberesistanttocracking,rotting,fireanddamagefromtermiteattackstotheextentsetoutinJamesHardie’srelevantpublishedliteraturecurrentatthetimeofinstallation.JamesHardiewarrantsforaperiodof15yearsfromthedateofpurchasethattheaccessoriessuppliedbyJamesHardiewillbefreefromdefectsduetodefectivefactoryworkmanshipormaterials.
NothinginthisdocumentshallexcludeormodifyanylegalrightsacustomermayhaveundertheConsumerGuaranteesActorotherwisewhichcannotbeexcludedormodifiedatlaw.
CONDITIONS OF WARRANTY: Thewarrantyisstrictlysubjecttothefollowingconditions:
a) JamesHardiewillnotbeliableforbreachofwarrantyunlesstheclaimantprovidesproofofpurchaseandmakesawrittenclaimeitherwithin30daysafterthedefectwouldhavebecomereasonablyapparentor,ifthedefectwasreasonablyapparentpriortoinstallation,thentheclaimmustbemadepriortoinstallation.
b) Thiswarrantyisnottransferable.
c) TheProductmustbeinstalledandmaintainedstrictlyinaccordancewiththerelevantJamesHardieliteraturecurrentatthetimeofinstallationandmustbeinstalledinconjunctionwiththecomponentsorproductsspecifiedintheliterature.Further,allotherproducts,includingcoatingandjointingsystems,appliedtoorusedinconjunctionwiththeProductmustbeappliedorinstalledandmaintainedstrictlyinaccordancewiththerelevantmanufacturer’sinstructionsandgoodtradepractice.
d) TheprojectmustbedesignedandconstructedinstrictcompliancewithallrelevantprovisionsofthecurrentNewZealandBuildingCode(“NZBC”),regulationsandstandards.
e) Theclaimant’ssoleremedyforbreachofwarrantyis(atJamesHardie’soption)thatJamesHardiewilleithersupplyreplacementproduct,rectifytheaffectedproductorpayforthecostofthereplacementorrectificationoftheaffectedproduct.
f) JamesHardiewillnotbeliableforanylossesordamages(whetherdirectorindirect)includingpropertydamageorpersonalinjury,consequentialloss,economiclossorlossofprofits,arisingincontractornegligenceorhowsoeverarising.WithoutlimitingtheforegoingJamesHardiewillnotbeliableforanyclaims,damagesordefectsarisingfromorinanywayattributabletopoorworkmanship,poordesignordetailing,settlementorstructuralmovementand/ormovementofmaterialstowhichtheProductisattached,incorrectdesignofthestructure,actsofGodincludingbutnotlimitedtoearthquakes,cyclones,floodsorothersevereweatherconditionsorunusualclimaticconditions,efflorescenceorperformanceofpaint/coatingsappliedtotheProduct,normalwearandtear,growthofmould,mildew,fungi,bacteria,oranyorganismonanyProductsurfaceorProduct(whetherontheexposedorunexposedsurfaces).
g) Allwarranties,conditions,liabilitiesandobligationsotherthanthosespecifiedinthiswarrantyareexcludedtothefullestextentallowedbylaw.
h) Ifmeetingaclaimunderthiswarrantyinvolvesre-coatingofProducts,theremaybeslightcolourdifferencesbetweentheoriginalandreplacementProductsduetotheeffectsofweatheringandvariationsinmaterialsovertime.
Disclaimer: The recommendations in James Hardie’s literature are based on good building practice, but are not an exhaustive statement of all relevant information and are subject to conditions (c), (d), (f) and (g) above. James Hardie has tested the performance of the Axon® Panel when installed in accordance with the Axon® Panel technical specification, in accordance with the standards and verification methods required by the NZBC and those test results demonstrate the product complies with the performance criteria established by the NZBC. However, as the successful performance of the relevant system depends on numerous factors outside the control of James Hardie (e.g. quality of workmanship and design) James Hardie shall not be liable for the recommendations made in its literature and the performance of the relevant system, including its suitability for any purpose or ability to satisfy the relevant provisions of the NZBC, regulations and standards, as it is the responsibility of the building designer to ensure that the details and recommendations provided in the relevant James Hardie installation manual are suitable for the intended project and that specific design is conducted where appropriate.
Copyright July 2015. © James Hardie New Zealand. TM and ® denotes a Trademark or Registered Mark owned by James Hardie Technology Limited.
Except for Tyvek ® and Inseal ® which are Registered Marks owned by their registered owners.
Product Warranty