TECHNICAL FILE Cintramax CE - Skylux · 2018. 8. 21. · E_TD_TECHNICAL_FILE_SKYLUX_CINTRAMAX_CE...

4
05-04-2017 Cintramax ® CE TECHNICAL FILE BARREL VAULTS CE approved according to EN 12101-2:2003 and in conformity with NBN S21-208

Transcript of TECHNICAL FILE Cintramax CE - Skylux · 2018. 8. 21. · E_TD_TECHNICAL_FILE_SKYLUX_CINTRAMAX_CE...

Page 1: TECHNICAL FILE Cintramax CE - Skylux · 2018. 8. 21. · E_TD_TECHNICAL_FILE_SKYLUX_CINTRAMAX_CE 05fi04fi2017 2/4 General product description The Cintramax® CE consists of two galvanised

05-04-2017

Cintramax® CETECHNICAL FILE

BARREL VAULTS

CE approved according to EN 12101-2:2003

and in conformity with NBN S21-208

Page 2: TECHNICAL FILE Cintramax CE - Skylux · 2018. 8. 21. · E_TD_TECHNICAL_FILE_SKYLUX_CINTRAMAX_CE 05fi04fi2017 2/4 General product description The Cintramax® CE consists of two galvanised

E_TD_TECHNICAL_FILE_SKYLUX_CINTRAMAX_CE 05-04-20172/4

General product descriptionThe Cintramax® CE consists of two galvanised scissors systems, mounted on the inside of the curb. The mechanical parts are protected through a galvanised covering piece. The system functions according to the principle of natural ven-tilation by convection of hot air. It also provides protection against the sun and the rain thanks to the umbrella system. This is an appliance, which permits to combine the aesthetical aspect and the characteristics of light transmission, sound and thermal insulation, smoke and heat extraction and daily ventilation of the barrel vault. The Cintramax® CE meets the European norm EN12101-2:2003 and is CE certified.

The Cintramax® CE opening part can be used with a length auf 2 running meter in Cintralux® GRP and Cintralux® Alu barrel vaults with a daylight size of 1,5 to 4m width, and with a length of 3 running meter up to a daylight size of 1,5 to 3m width. It is opened and closed by two 24V actuators, operated by a Skycom® CE control unit OR two double opera-ting pneumatic cylinders operated by a pneumatic control cabin. By the use of the Skycom® master CE detection unit combined with a Skycom® slave CE OR by the use of a CO2-cartridge with fusible link, the positive safety is guaranteed and the Cintramax® CE meets the NBN S21-208.1-3 norm. For daily ventilation, the Cintramax® CE can be opened and closed continuously. Smoke hatches must be closed when the wind load exceeds 6 m/s (this can be detected with a wind detector).

Advantages

Specific characteristics opening system

- A combination of aesthetical aspect and light transmission, sound and thermal insulation

- The actuator is not hung lower than a curb of 30 cm- Continuous light transmission on full length assured- Execution with thermal break possible- Insulation value up to Ug 0,9 W/m².K- Broof t1 combination possible

Type Cintramax® CE electric Cintramax® CE pneumatic Scissors system ...........................................................System height ........................................................System height actuator included : 30 cm cylinder included : 30 cmFunctioning .....................................................................24 V ..................................................................................minimum 9 bar and maximum 10 barAerodynamic coefficient .................................0,5 to 0,6 ....................................................................0,5 to 0,6 In function of the sizes In function of the sizes U-value ..................................................................................Same execution Cintralux® .....................Same execution Cintralux®

barrel vault of your choice barrel vault of your choiceNominal power ............................................................4 A (per actuator) ..............................................-Density ................................................................................IP54 ..................................................................................-

Page 3: TECHNICAL FILE Cintramax CE - Skylux · 2018. 8. 21. · E_TD_TECHNICAL_FILE_SKYLUX_CINTRAMAX_CE 05fi04fi2017 2/4 General product description The Cintramax® CE consists of two galvanised

01-03-20173/4

E_TD_TECHNICAL_FILE_SKYLUX_CINTRAMAX_CE

Specific characteristics detection unit

Cintramax® CE electric Cintramax® CE pneumatic

Skycom® CE master Metal cabin lacquered in RAL 7032

Operating temperature ............... -15 °C to + 60°C .........................................-20 °C to + 50 °C

Outgoing current / ......................... 8 A ............................................................................dry air, filtered, oilfree Operating pressure operating pressure: 9 à 10 bar

Characteristics ..................................... - power supply 230 V AC .................- reverse valve with automatic - SHE & comfort operation ventilation, provided with an electro- - battery back-up 72h magnet on 24 V (impulse on the ‘open’

- weight 7,5 kg valve) - colour RAL 9003 - pressure regulator with filter and

condensation catcher - 3 transit screws 4/6 - all necessary cables and wiring in the cabin - the cabin is ready for connection - 3x open/close after power failure

Positive safety ....................................... Skycom® CE slave CE with ..............- Fusible link 68°C by CO2 cartridge in-built detection 75°C

Options ......................................................... - fire push button .....................................- wind and/or rain detection - priority switch - compressor - smoke detector - pressure vessel - temperature detector - ventilation push button - wind and rain detection

Sizes ................................................................. WxHxD 286x238x113mm ..................for 1 to 2 zones: WxHxD 380x300x155mm for 3 to 4 zones: WxHxD 500x500x210mm for 5 zones: WxHxD 600x600x210mm

Page 4: TECHNICAL FILE Cintramax CE - Skylux · 2018. 8. 21. · E_TD_TECHNICAL_FILE_SKYLUX_CINTRAMAX_CE 05fi04fi2017 2/4 General product description The Cintramax® CE consists of two galvanised

E_TD_TECHNICAL_FILE_SKYLUX_CINTRAMAX_CE 01-03-20174/4

CINTRAMAX IS A REGISTERED BRAND OF AG.PLASTICSSPINNERIJSTRAAT 100 - B-8530 STASEGEMT +32 (0)56 20 00 00 - F +32 (0)56 21 95 [email protected]

Attention: the CE certification is only valid if the composition, execution and the installation regulations are respected.AG.Plastics guarantees the CE conformity as described in the documentation and according the plant regulations of the appliances. Every variance, cancels the CE conformity.

ONLY USE ORIGINAL PARTS DELIVERED BY AG.PLASTICS. EVERY GUARANTEE IS CANCELLED IF NON-ORIGINAL PARTS ARE USED. THE SHE DETECTION UNIT MUST BE USED WITH THE RIGHT SHE OPENING SYSTEM. THE USE OF NON-ORIGINAL SHE PARTS CAN LEAD TO DEFECTS OF THE SYSTEM.

Image- electric

- pneumatic

Attestations, certificates and documentation• CE according to the SHE norm EN12101-2:2003• CE of the Skycom® master CE and Skycom® slave CE detection unit according to EN 12.101-(9)/10• NBN S21-208-1-3• DoP through www.cintramax.be• Installation instructions through www.cintramax.be

closed

opening height

19001820

1900

1904

upst

and

min

. 300

160

160182

300

800

9618

5

closed

opening height

19001820

1904

185

1900

300

800

160

upst

and

min

. 300

160

96

182