• Split Sky Air • Indoor Units 1
• Indoor Units • R-410A • FBQ-C7VEB
TABLE OF CONTENTSFBQ-C7VEB
1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3For indoor units only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3 Safety device settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . 7Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6 Piping diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7 Wiring diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
8 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Sound power spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
9 Fan characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
10 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Installation method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Filter installation method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Switch box connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
• Indoor Units • R-410A • FBQ-C7VEB
11
• Split Sky Air • Indoor Units2
1 Features
Indoor Unit Split Sky FBQ-C7VEB R-410a • Reduction in power consumption thanks to DC inverter fans
• Improved comfort thanks to 3-step airflow control
• Maximum external static pressure (ESP) is 100Pa
• Possibility to change ESP through wired remote control allows optimisation of the supply air volume
• Blends unobtrusively with any interior décor: only the suction and discharge grilles are visible
• Energy efficient: up to class A energy labels
• Home leave operation saves energy during absence
• Whisper quiet operation: down to 26 dBA sound pressure level
• Standard air filter: removes airborne dust particles to ensure a steady supply of clean air
• Easy installation thanks to automatic air flow adjustment towards nominal air flow rate
• Built-in drain pump as standard increases reliability of the drain system
optional standard 3 steps
via wired remote control
optional
3
12
• Split Sky Air • Indoor Units 3
• Indoor Units • R-410A • FBQ-C7VEB
2 Specifications
2-1 For indoor units only FBQ35C7VEB FBQ50C7VEB FBQ60C7VEB FBQ71C7VEB FBQ100C7VEB FBQ125C7VEB FBQ140C7VEB
Nominal input (Indoor only)
Cooling kW 0.14 0.14 0.35 0.35 0.35 0.35 0.35Heating kW 0.14 0.14 0.35 0.35 0.35 0.35 0.35
2-2 Technical Specifications FBQ35C7VEB FBQ50C7VEB FBQ60C7VEB FBQ71C7VEB FBQ100C7VEB FBQ125C7VEB FBQ140C7VEB
Casing Colour Non paintedMaterial Galvanised steel
Dimensions Packing Height mm 355 355 355 355 355 355 355Width mm 920 920 1,220 1,220 1,620 1,620 1,620Depth mm 900 900 900 900 900 900 900
Unit Height mm 300 300 300 300 300 300 300Width mm 700 700 1,000 1,000 1,400 1,400 1,400Depth mm 700 700 700 700 700 700 700
Weight Unit kg 25 25 34 34 45 45 45Packed Unit kg 28 28 41 41 53 53 53
Required Ceiling Void mm >350Heat Exchanger Dimensions Length mm 440 440 740 740 1,140 1,140 1,140
Nr of Rows 3 3 3 3 3 3 3Fin Pitch mm 1.75 1.75 1.75 1.75 1.75 1.75 1.75Nr of Passes 4 4 7 7 11 11 11Face Area m² 0.148 0.148 0.249 0.249 0.383 0.383 0.383Nr of Stages 16 16 16 16 16 16 16
Tube type Hi-XSS (7)Fin Type Symmetric waffle louvre
Treatment HydrophilicFan Type Sirocco fan
Quantity 1 1 2 2 3 3 3Air Flow Rate Cooling High m³/min 16 16 18 18 32 39 39
Low m³/min 11 11 15 15 23 28 28Heating High m³/min 16 16 18 18 32 39 41
Low m³/min 11 11 15 15 23 28 29Fan Max High Pa 100 100 100 100 100 100 100
Standard Pa 30 30 30 30 40 50 50Motor Quantity 1 1 1 1 1 1 1
Model Brushless DCNumber of steps 10 10 8 8 9 9 9
Motor Speed (cooling) High rpm 1,186 1,186 942 942 1,060 1,218 1,218Low rpm 875 875 823 823 813 920 920
Speed (heating) High rpm 1,186 1,186 942 942 1,060 1,218 1,280Low rpm 875 875 823 823 813 920 967
Fan Motor Output (high) W 140 140 350 350 350 350 350Drive Direct drive
Cooling Sound Power High dBA 63 63 57 57 61 66 66Sound Pressure High dBA 37 37 37 37 38 40 40
Low dBA 29 29 29 29 32 33 33Heating Sound Pressure High dBA 37 37 37 37 38 40 41
Low dBA 29 29 29 29 32 33 34Refrigerant Type R-410APiping connections Liquid (OD) Type Flare connection
Diameter (OD) mm 6.35 6.35 6.35 9.52 9.52 9.52 9.52Gas Type Flare connection
Diameter (OD) mm 9.52 12.7 12.7 15.9 15.9 15.9 15.9Drain Diameter (OD) mm VP25 (O.D. 32 / I.D. 25)Heat Insulation Both liquid and gas pipes
Drain-up Height mm 625 625 625 625 625 625 625
• Indoor Units • R-410A • FBQ-C7VEB
12
• Split Sky Air • Indoor Units4
2 Specifications
Decoration Panel Model BYBS45DJW1 BYBS45DJW1 BYBS71DJW1 BYBS71DJW1 BYBS125DJW1 BYBS125DJW1 BYBS125DJW1Colour White (10Y9/0,5)Dimensions H mm 55 55 55 55 55 55 55
W mm 800 800 1,100 1,100 1,500 1,500 1,500D mm 500 500 500 500 500 500 500
Weight kg 3.5 3.5 4.5 4.5 6.5 6.5 6.5Air Filter Resin net with mold resistanceSafety Devices PC board fuse
PC board fuse (fan driver)Drain pump fuse
Notes Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m, level difference : 0m
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.The sound pressure values are mentioned for a unit installed with rear suction
Remote Control Wired BRC1D528
2-2 Technical Specifications FBQ35C7VEB FBQ50C7VEB FBQ60C7VEB FBQ71C7VEB FBQ100C7VEB FBQ125C7VEB FBQ140C7VEB
3
13
• Split Sky Air • Indoor Units 5
• Indoor Units • R-410A • FBQ-C7VEB
3 Safety device settings
4 Options
Safety devices 35 50 60 71 100 125 140
FBQ
PC Board Fuse 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A
PC Board Fuse (Fan Driver) 250V 5A 250V 5A 250V 6.3A 250V 6.3A 250V 6.3A 250V 6.3A 250V 6.3A
Fan Motor Thermal Protector °C — — — — — — —
Drain Pump Fuse °C 145 145 145 145 145 145 145
FBQ35-140C
3TW31279-3A
Options
Operation Control
(*1): Electrical heater and humidifier are field supply. These parts should not be installed inside the equipment (refer to installation manual EKRP1B2A)
(*2): If installing an electrical heater, an option PCB for external heater (EKRP1B2) for each indoor unit is required.
(*3): Mounting plate KRP4A96 is required for these options. Maximum 2 option PCB’s can be mounted.
Contents of accessory bag
Item Type FBQ35 FBQ50 FBQ60,71 FBQ100,125,140
Panel related Decoration panel BYBS45D BYBS71D BYBS125D
Air inlet and air discharge outlet related Air discharge adapter for round duct KDAJ25K56A KDAJ25KA71A KDAJ25KA140A
Item Type FBQ35 FBQ50 FBQ60,71 FBQ100,125,140
Remote Control Wired Type BRC1D528
Option BCB for external el. heater, humidifier and/or hour meter (*1), (*3) EKRP1B2A
Adapter for wiring (interlock for fresh air intake fan) (*3) KRP1BA54
Wiring adapter for electrical appendices (*3) KRP4A51
Central remote control DCS302CA51
Unified ON/OFF control DCS301BA51
Schedule timer DST301BA51
Interface adapter for sky air series DTA112BA51
Remote ON/OFF and FORCED OFF kit EKRORO3
Mounting plate for adapter PCB KRP4A96
DescriptionQuantity
FBQ35,50,60,71,100,125,140
Hexagon tapping screw (M5x16) 16
Round plain washer for wood 8
Installation and operation manual 1
Hose band 1
Insulation for joint (GAS) 1
Insulation for joint (LIQUID) 1
Drain hose 1
Drain hose sealing material 1
Sealing material 2
NOTES
• Indoor Units • R-410A • FBQ-C7VEB
14
• Split Sky Air • Indoor Units6
4 Options
3TW31601-1
EKRORO3
Standardsetting:
’forced off’
Selection of ’FORCED OFF’ and ’ON/OFF’ operation
Input ’ON’ = closed contact.
Remotecontroller
T1,T2Switch
Alternativesetting:’on/off’
Terminal X2M
Connector (White)
connect to indoorPCB (X30A)
On
Off
On
Off
On
Off
On
Off
unit
INPU
T
Operating methodWire specifications
Forced off On/off operationInput ’on’ stops operation + disables control Input off→on: starts operation, remote control is still enabled.Input ’off’ enables control Input on→off: stops operation, remote control is still enabled.
Setting Mode No. First code NO Second code NOForced off
12 (22) 1 01On/off operation 02
Screw to control boxreplacing the originalterminal
3
15
• Split Sky Air • Indoor Units 7
• Indoor Units • R-410A • FBQ-C7VEB
5 Dimensional drawing & centre of gravity5 - 1 Dimensional drawing
FBQ35C
3TW31274-1
(sus
pens
ion
posi
tion)
(suspension position)
suspension bolt
or more(service space)
(ser
vice
spa
ce)
or m
ore
View A-A Detail B
Detail B
Item Name Description
1 Liquid pipe connection Ø6.35 flare connection
2 Gas pipe connection Ø9.52 flare connection
3 Drain pipe connection VP25 (OD Ø32, ID Ø25)
4 Remote control wiring connection -
5 Power supply connection -
6 Drain hole VP25 (OD Ø32, ID Ø25)
7 Air filter -
8 Air suction side -
9 Air discharge side -
10 Nameplate -
NOTES
1 Refer to ‘outlook drawing for installing optional
accessories’ when installing optional accessories.
2 The required ceiling depth varies according to the
configuration of the specific system.
3 For maintenance of the air filter, it is necessary to
provide a service access panel.
Refer to the ‘filter installation method’ drawing
FBQ50C
3TW31214-1
NOTE
1 Refer to ‘outlook drawing for installing optional
accessories’ when installing optional accessories.
2 The required ceiling depth varies according to the
configuration of the specific system.
3 For maintenance of the air filter, it is necessary to
provide a service access panel.
Refer to the ‘filter installation method’ drawing.
Nr Name Description
1 Liquid pipe connection ø 6.35 flare (connection)
2 Gas pipe connection ø 12.70 (flare connection)
3 Drain pipe connection VP25 (O.D. ø 32 /I.D. ø 25)
4 Remote control wiring connection
5 Power supply connection
6 Drain hole VP25 (OD ø 32 /I.D. ø 25)
7 Air filter
8 Air suction side
9 Air discharge side
10 Nameplate
View A-A Detail B
Suspension bolt
(Service space) Detail B
350
or m
ore
(Ser
vice
spa
ce)
(Suspension position)
(Sus
pens
ion
posi
tion)
or more
• Indoor Units • R-410A • FBQ-C7VEB
15
• Split Sky Air • Indoor Units8
5 Dimensional drawing & centre of gravity5 - 1 Dimensional drawing
FBQ60C
3TW31294-1
NOTE
1 Refer to ‘outlook drawing for installing optional
accessories’ when installing optional accessories.
2 The required ceiling depth varies according to the
configuration of the specific system.
3 For maintenance of the air filter, it is necessary to
provide a service access panel.
Refer to the ‘filter installation method’ drawing.
Nr Name Description
1 Liquid pipe connection ø 6.35 flare (connection)
2 Gas pipe connection ø 12.70 (flare connection)
3 Drain pipe connection VP25 (O.D. ø 32 /I.D. ø 25)
4 Remote control wiring connection
5 Power supply connection
6 Drain hole VP25 (OD ø 32 /I.D. ø 25)
7 Air filter
8 Air suction side
9 Air discharge side
10 Nameplate
View A-A
Detail B
Suspension bolt
(Service space)
Detail B
350
or m
ore
(Ser
vice
spa
ce)
(Suspension position)
(Sus
pens
ion
posi
tion)
or more
FBQ71C
3TW31234-1
NOTE
1 Refer to ‘outlook drawing for installing optional
accessories’ when installing optional accessories.
2 The required ceiling depth varies according to the
configuration of the specific system.
3 For maintenance of the air filter, it is necessary to
provide a service access panel.
Refer to the ‘filter installation method’ drawing.
Nr Name Description
1 Liquid pipe connection ø 9.52 flare (connection)
2 Gas pipe connection ø 15.90 (flare connection)
3 Drain pipe connection VP25 (O.D. ø 32 /I.D. ø 25)
4 Remote control wiring connection
5 Power supply connection
6 Drain hole VP25 (OD ø 32 /I.D. ø 25)
7 Air filter
8 Air suction side
9 Air discharge side
10 Nameplate
View A-A
Detail B
Suspension bolt
(Service space)
Detail B
350
or m
ore
(Ser
vice
spa
ce)
(Suspension position)
(Sus
pens
ion
posi
tion)
or more
3
15
• Split Sky Air • Indoor Units 9
• Indoor Units • R-410A • FBQ-C7VEB
5 Dimensional drawing & centre of gravity5 - 1 Dimensional drawing
FBQ100-140C
3TW31254-1
NOTE
1 Refer to ‘outlook drawing for installing optional
accessories’ when installing optional accessories.
2 The required ceiling depth varies according to the
configuration of the specific system.
3 For maintenance of the air filter, it is necessary to
provide a service access panel.
Refer to the ‘filter installation method’ drawing.
Nr Name Description
1 Liquid pipe connection ø 9.52 flare (connection)
2 Gas pipe connection ø 15.90 (flare connection)
3 Drain pipe connection VP25 (O.D. ø 32 /I.D. ø 25)
4 Remote control wiring connection
5 Power supply connection
6 Drain hole VP25 (OD ø 32 /I.D. ø 25)
7 Air filter
8 Air suction side
9 Air discharge side
10 Nameplate
View A-A
Detail B
Suspension bolt
(Service space)
Detail B
350
or m
ore
(Ser
vice
spa
ce)
(Suspension position)
(Sus
pens
ion
posi
tion)
or more
• Indoor Units • R-410A • FBQ-C7VEB
15
• Split Sky Air • Indoor Units10
5 Dimensional drawing & centre of gravity5 - 2 Centre of gravity
FBQ35-140C
4TW31189-1A
MODEL A B
FBQ35,50 283 700
FBQ60,71 441 1000FBQ100~140 619 1400
3
16
• Split Sky Air • Indoor Units 11
• Indoor Units • R-410A • FBQ-C7VEB
6 Piping diagram
FBQ35-140C
3TW31275-1
Heat exchanger
Liquid pipe connection port
Gas pipe connection port
Refrigerant flow
Cooling
Heating
Refrigerant pipe connection port diameters
Model Gas Liquid
FBQ35C 9.52 6.35
FBQ50C 12.70 6.35
FBQ60C 12.70 6.35
FBQ71C 15.90 9.52
FBQ100C 15.90 9.52
FBQ125C 15.90 9.52
FBQ140C 15.90 9.52
• Indoor Units • R-410A • FBQ-C7VEB
17
• Split Sky Air • Indoor Units12
7 Wiring diagram7 - 1 Wiring diagram
2TW31276-1A
NOTES
1 Use copper conductors only.
2 When using the central remote controller, see manual for connection to the unit.
3 The remote control model varies according to the combination system.
See technical materials and catalogues, etc. before connecting.
4 Refer to installation manual.
Indoor unit M1F Motor (fan) SS1 Selector switch (emergency) TC Signal transmission circuit
A1P Printed circuit board M1P Motor (drain pump) S1L Float switch Connector optional accessoryA2P Printed circuit board (fan) PS Switching power supply V1R Diode bridge X28A Connector (Power supply for wiring)
C1 Capacitor Q1DI Earth leak detector V2R Power module X33A Connector (for wiring)
F1U, F2U Fuse (T, 5A, 250V) R1 Resistor (current limiting) X1M Terminal strip (power supply) X35A Connector (adapter)
F4U Fuse (T, 6.3A, 250V) R2 Current sensing device X2M Terminal strip (control) X85A Connector (for multi zoning)
HAP Light emitting diode (Service monitor green) R1T Thermistor (suction air) Z1C Noise filter (ferrite core) X33A Connector (for wiring)
KPR, K1R Magnetic relay R2T Thermistor (liquid) Z1F Noise filter Wired remote controlL1R Reactor R3T Thermistor (gas) RC Signal receiver circuit SS1 Selector switch (emergency)
1N~220-240V 50Hz1N~220V 60Hz
indoor
Common power supply
note 4
Transmission wiring central remote controlnote 2
wired remote control(optional accessory)
Switch box (indoor)
norm.emg
ColorsBLK : BlackBLU : BlueBRN : BrownGRY : GrayORG : OrangePNK : PinkRED : RedWHT : WhiteYLW : YellowGRN : Green
: Field wiringL : LiveN : Neutral
: Connector
: Wire clamp: Protective earth (screw)
,
FBQ35-50C7VEB
FBQ60-140C7VEB
2TW31296-1A
NOTES
1 Use copper conductors only.
2 When using the central remote controller, see manual for connection to the unit.
3 The remote control model varies according to the combination system. See technical materials and catalogues, etc. before connecting.
4 Refer to installation manual.
Indoor unit L1R Reactor R3T Thermistor (gas) TC Terminal strip (control)
A1P Printed circuit board M1F Motor (fan) R5T Thermistor NTC (Current limiting) Y1E Electronic expansion valve
A2P Printed circuit board (fan) M1P Motor (drain pump) SS1 Selector switch (emergency) Connector optional accessory
A3P Printed circuit board (capacitor) PS Switching power supply S1L Float switch X33A Connector (for wiring)
C1, C2, C3 Capacitor Q1DI Earth leak detector V1R Diode bridge X35A Connector (adapter)
F1U Fuse (T, 5A, 250V) R2 Current sensing device V2R Power module X38A Connector (for wiring)
F3U Fuse (T, 6.3A, 250V) R3, R4 Resistor (electric discharge) Z1C Noise filter (ferrite core) Wired remote control
HAP Light emitting diode (service monitor green) R1T Thermistor (suction air) Z1F Noise filter R1T Thermistor (air)
KPR, K1R Magnetic relay R2T Thermistor (liquid) RC Terminal strip (power supply) SS1 Selector switch (main/sub)
1N~220-240V 50Hz1N~220V 60Hz
only for 60 class
Common power supply
note 4
Transmission wiring central remote controlnote 2
Wired remote control(optional accessory)
Switch box (indoor)
NORM. EMG
only for 60 class
ColorsBLK : BlackBLU : BlueBRN : BrownGRY : GrayORG : OrangePNK : PinkRED : RedWHT : WhiteYLW : YellowGRN : Green
: Field wiringL : LiveN : Neutral
: Connector
: Wire clamp: Protective earth (screw)
,
3
18
• Split Sky Air • Indoor Units 13
• Indoor Units • R-410A • FBQ-C7VEB
8 Sound data8 - 1 Sound pressure spectrum
3TW31217-2
NOTES
1 Data is valid at free field condition
2 Data is valid at nominal operation condition
3 dBA= A-weighted sound pressure level. (A-scale according to IEC)
4 Reference acoustic pressures 0dB = 20μPa
5 Location of microphone
Sou
nd p
ress
ure
leve
l [dB
]
FBQ35-50C
Octave band center frequency (Hz)
High-tap
Medium-tap
Low-tap
Unit
Microphone
DischargeSuction
3TW31297-2
NOTES
1 Data is valid at free field condition
2 Data is valid at nominal operation condition
3 dBA= A-weighted sound pressure level. (A-scale according to IEC)
4 Reference acoustic pressures 0dB = 20μPa
5 Location of microphone
Sou
nd p
ress
ure
leve
l [dB
]
FBQ60C
Octave band center frequency (Hz)
High-tap
Medium-tap
Low-tap
Unit
Microphone
DischargeSuction
FBQ71C
3TW31297-2
Notes
1 Data is valid at free field condition
2 Data is valid at nominal operation condition
3 dBA = A-weighted sound power level. (A-scale according to IEC)
4 Reference acoustic pressures 0dB = 20μPa
5 Location of microphine
Sou
nd p
ress
ure
leve
l [dB
]
Octave band center frequency [dB]
1.5m
Microphone
Unit2m 2m
1.5m
1m
High-tap
Medium-tap
Low-tap
DischargeSuction
FBQ100C
3TW31257-2
Notes
1 Data is valid at free field condition
2 Data is valid at nominal operation condition
3 dBA = A-weighted sound power level. (A-scale according to IEC)
4 Reference acoustic pressures 0dB = 20μPa
5 Location of microphine
Sou
nd p
ress
ure
leve
l [dB
]
Octave band center frequency [dB]
1.5m
Microphone
Unit2m 2m
1.5m
1m
High-tap
Medium-tap
Low-tap
DischargeSuction
• Indoor Units • R-410A • FBQ-C7VEB
18
• Split Sky Air • Indoor Units14
8 Sound data8 - 1 Sound pressure spectrum
FBQ125C
3TW31267-2
Notes
1 Data is valid at free field condition
2 Data is valid at nominal operation condition
3 dBA = A-weighted sound power level. (A-scale according to IEC)
4 Reference acoustic pressures 0dB = 20μPa
5 Location of microphine
Sou
nd p
ress
ure
leve
l [dB
]
Octave band center frequency [dB]
1.5m
Microphone
Unit2m 2m
1.5m
1m
High-tap
Medium-tap
Low-tap
DischargeSuction
FBQ140C
3TW31337-2
Notes
1 Data is valid at free field condition
2 Data is valid at nominal operation condition
3 dBA = A-weighted sound power level. (A-scale according to IEC)
4 Reference acoustic pressures 0dB = 20μPa
5 Location of microphine
Sou
nd p
ress
ure
leve
l [dB
]
Octave band center frequency [dB]
1.5m
Microphone
Unit2m 2m
1.5m
1m
High-tap
Medium-tap
Low-tap
DischargeSuction
3
18
• Split Sky Air • Indoor Units 15
• Indoor Units • R-410A • FBQ-C7VEB
8 Sound data8 - 2 Sound power spectrum
3TW31217-1
NOTES
1 dBA= A-weighted sound power level. (A-scale according to IEC)
2 Reference acoustic intensity 0dB = 10E-6μW/m2
3 Measured according to ISO 3744
Sou
nd p
ower
leve
l [dB
]
FBQ35-50C
Octave band center frequency (Hz)
High-tap
Medium-tap
Low-tap
3TW31297-1
NOTES
1 dBA= A-weighted sound power level. (A-scale according to IEC)
2 Reference acoustic intensity 0dB = 10E-6μW/m2
3 Measured according to ISO 3744
Sou
nd p
ower
leve
l [dB
]
FBQ60C
Octave band center frequency (Hz)
High-tap
Medium-tap
Low-tap
FBQ71C
3TW31297-1
Notes
1 dBA = A-weighted sound power level. (A-scale according to IEC)
2 Reference acoustic intensity 0dB = 10E-6μW/m2
3 Measured according to ISO 3744
Sou
nd p
ress
ure
leve
l [dB
]
Octave band center frequency [dB]
High-tap
Medium-tap
Low-tap
FBQ100C
3TW31257-1
Notes
1 dBA = A-weighted sound power level. (A-scale according to IEC)
2 Reference acoustic intensity 0dB = 10E-6μW/m2
3 Measured according to ISO 3744
Sou
nd p
ress
ure
leve
l [dB
]
Octave band center frequency [dB]
High-tap
Medium-tap
Low-tap
• Indoor Units • R-410A • FBQ-C7VEB
18
• Split Sky Air • Indoor Units16
8 Sound data8 - 2 Sound power spectrum
FBQ125-140C
3TW31267-1
Notes
1 dBA = A-weighted sound power level. (A-scale according to IEC)
2 Reference acoustic intensity 0dB = 10E-6μW/m2
3 Measured according to ISO 3744
Sou
nd p
ress
ure
leve
l [dB
]
Octave band center frequency [dB]
High-tap
Medium-tap
Low-tap
3
19
• Split Sky Air • Indoor Units 17
• Indoor Units • R-410A • FBQ-C7VEB
9 Fan characteristics
FBQ35-50C
3TW31218-1
Fan characteristics (1)Fan characteristics (3)
(airflow auto adjustment)
Fan characteristics (2)(Field setting with remote control)
Ext
erna
l sta
tic p
ress
ure
[Pa]
Ext
erna
l sta
tic p
ress
ure
[Pa]
Ext
erna
l sta
tic p
ress
ure
[Pa]
Airflow [m3/min]Airflow [m3/min]
Airflow [m3/min]
Range of available air flow rate (H)
L
M
H
Upper limint of ESP by airflow auto adjustment
Upper limint of ESP by airflow auto adjustment
Upper limint of ESP
Lower limit of ESP
Upper limint of ESP(max ESP )
Lower limit of ESP(std ESP)
Lower limit of ESP(max ESP)
Upper limint of ESP(std ESP )
L (max ESP)
M (max ESP)
H (max ESP)
L (std ESP)
H (std ESP)
M (std ESP)
NOTES
1 Fan characteristics as shown are in “fan only” mode.
2 ESP: External static pressure
FBQ60C
3TW31298-1
Fan characteristics (1) Fan characteristics (3)(airflow auto adjustment)
Fan characteristics (2)(Field setting with remote control)
Ext
erna
l sta
tic p
ress
ure
[Pa]
Ext
erna
l sta
tic p
ress
ure
[Pa]
Ext
erna
l sta
tic p
ress
ure
[Pa]
Airflow [m3/min]Airflow [m3/min]
Airflow [m3/min]
Range of available air flow rate (H)
L
M
H
Upper limint of ESP by airflow auto adjustment
Upper limint of ESP by airflow auto adjustment
Upper limint of ESP
Lower limit of ESP
Upper limint of ESP(max ESP )
Lower limit of ESP(std ESP)
Lower limit of ESP(max ESP)
Upper limint of ESP(std ESP )
L (max ESP)
M (max ESP)
H (max ESP)
L (std ESP)
H (std ESP)M (std ESP)
NOTES
1 Fan characteristics as shown are in “fan only” mode.
2 ESP: External static pressure
• Indoor Units • R-410A • FBQ-C7VEB
19
• Split Sky Air • Indoor Units18
9 Fan characteristics
FBQ71C
3TW31298-1
Fan characteristics (1) Fan characteristics (3)(Airflow auto adjustment)
Airflow [m³/min] Airflow [m³/min]
Fan characteristics (2)(Field setting with remote control)
Range of available air flow rate (H)
Airflow [m³/min]
NOTES
1 Fan characteristics as shown ar in “fan only” mode.
2 ESP: External static pressure
Upper limit of ESP(max. ESP)
H (max. ESP)
M (max. ESP)
L (max. ESP)
Lower limit of ESP(max. ESP)
H (std ESP)M (std ESP)
L (std ESP) Lower limit of ESP(std. ESP)
Upper limit of ESP(std. ESP)
Upper limit of ESP Upper limit of ESP by airflow auto adjustment
Lower limit of ESP by airflow auto adjustment
Lower limit of ESP
Ext
erna
l sta
tic p
ress
ure
[Pa]
Ext
erna
l sta
tic p
ress
ure
[Pa]
H
M
L
Ext
erna
l sta
tic p
ress
ure
[Pa]
FBQ100C
3TW31258-1
Fan characteristics (1) Fan characteristics (3)(Airflow auto adjustment)
Airflow [m³/min] Airflow [m³/min]
Fan characteristics (2)(Field setting with remote control)
Range of available air flow rate (H)
Airflow [m³/min]
NOTES
1 Fan characteristics as shown ar in “fan only” mode.
2 ESP: External static pressure
Upper limit of ESP(max. ESP)
H (max. ESP)
M (max. ESP)
L (max. ESP)
Lower limit of ESP(max. ESP)
H (std ESP)
M (std ESP)
L (std ESP)
Lower limit of ESP(std. ESP)
Upper limit of ESP(std. ESP)
Upper limit of ESPUpper limit of ESP by airflow auto adjustment
Lower limit of ESP by airflow auto adjustment
Lower limit of ESP
Ext
erna
l sta
tic p
ress
ure
[Pa]
Ext
erna
l sta
tic p
ress
ure
[Pa]
H
M
L
Ext
erna
l sta
tic p
ress
ure
[Pa]
3
19
• Split Sky Air • Indoor Units 19
• Indoor Units • R-410A • FBQ-C7VEB
9 Fan characteristics
FBQ140C
3TW31268-1
Fan characteristics (1)Fan characteristics (3)
(airflow auto adjustment)
Fan characteristics (2)(Field setting with remote control)
Ext
erna
l sta
tic p
ress
ure
[Pa]
Ext
erna
l sta
tic p
ress
ure
[Pa]
Ext
erna
l sta
tic p
ress
ure
[Pa]
Airflow [m3/min]Airflow [m3/min]
Airflow [m3/min]
Range of available air flow rate (H)
L
M
H
Upper limint of ESP by airflow auto adjustment
Upper limint of ESP by airflow auto adjustment
Upper limint of ESP
Lower limit of ESP
Upper limint of ESP(max ESP )
Lower limit of ESP(std ESP)
Lower limit of ESP(max ESP)
Upper limint of ESP(std ESP )
L (max ESP)
M (max ESP)
H (max ESP)
L (std ESP)
H (std ESP)
M (std ESP)
NOTES
1 Fan characteristics as shown are in “fan only” mode.
2 ESP: External static pressure
FBQ125C
3TW31268-1
Fan characteristics (1) Fan characteristics (3)(Airflow auto adjustment)
Airflow [m³/min]Airflow [m³/min]
Fan characteristics (2)(Field setting with remote control)
Range of available air flow rate (H)
Airflow [m³/min]
NOTES
1 Fan characteristics as shown ar in “fan only” mode.
2 ESP: External static pressure
Upper limit of ESP(max. ESP)
H (max. ESP)
M (max. ESP)
L (max. ESP)
Lower limit of ESP(max. ESP)
H (std ESP)
M (std ESP)
L (std ESP)Lower limit of ESP(std. ESP)
Upper limit of ESP(std. ESP)
Upper limit of ESP
Upper limit of ESP by airflow auto adjustment
Lower limit of ESP by airflow auto adjustment
Lower limit of ESP
Ext
erna
l sta
tic p
ress
ure
[Pa]
Ext
erna
l sta
tic p
ress
ure
[Pa]
H
M
L
Ext
erna
l sta
tic p
ress
ure
[Pa]
• Indoor Units • R-410A • FBQ-C7VEB
110
• Split Sky Air • Indoor Units20
10 Installation10 - 1 Installation method
FBQ35-140C
3TW31183-1
Rear Suction Bottom Suction
Ceiling return Ceiling return
Installation with duct
Direct installation of inlet panel
Wide variety of installation methods
Easy modification from rear to bottom suction
Drain pump up height
Number Description
1 Main body
2 Air outlet duct Field supply
3 Inlet panel Optional accessory
4 Acces panel optional accessory
5 Air inlet duct Field supply
3
110
• Split Sky Air • Indoor Units 21
• Indoor Units • R-410A • FBQ-C7VEB
10 Installation10 - 2 Filter installation method
FBQ35-140C
3TW31184-4
Installation without air inlet duct Installation with air inlet duct
(or less)
NOTES
Nr. Description 1 When installing the unit with rear
suction, a service opening is
necessary for the maintenance of
the air filters.
2 When installing the unit with a
suction duct. A service opening
must be provided in the duct.
1 Suspended Ceiling2 Ceiling opening3 Service access panel (optimal)4 Air filter5 Air inlet duct6 Duct service opening
• Indoor Units • R-410A • FBQ-C7VEB
110
• Split Sky Air • Indoor Units22
10 Installation10 - 3 Switch box connection
FBQ35-140C
3TW31184-5
Emerg.
Common power supply
Norm.
Daikin Europe N.V. is approved by LRQA for its QualityManagement System in accordance with the ISO9001standard. ISO9001 pertains to quality assurance regardingdesign, development, manufacturing as well as to servicesrelated to the product.
Daikin units comply with the European regulations thatguarantee the safety of the product.
Prep
ared
in B
elgium
by La
nnoo
(ww
w.lan
noop
rint.b
e), a
comp
any w
hose
conc
ern f
or
the en
viron
mont
is se
t in th
e EMA
S an
d ISO
1400
1 sys
tems.
Resp
onsib
le Ed
itor:
Daiki
n Eur
ope N
.V., Z
andv
oord
estra
at 30
0, B-
8400
Oos
tende
The present publication is drawn up by way of information only and does notconstitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. hascompiled the content of this publication to the best of its knowledge. Noexpress or implied warranty is given for the completeness, accuracy,reliability or fitness for particular purpose of its content and the products andservices presented therein. Specifications are subject to change withoutprior notice. Daikin Europe N.V. explicitly rejects any liability for any direct orindirect damage, in the broadest sense, arising from or related to the useand/or interpretation of this publication. All content is copyrighted by DaikinEurope N.V..
Naamloze VennootschapZandvoordestraat 300B-8400 Oostende, Belgiumwww.daikin.euBTW: BE 0412 120 336RPR Oostende
Daikin’s unique position as a manufacturer of airconditioning equipment, compressors andrefrigerants has led to its close involvement inenvironmental issues. For several years Daikin hashad the intension to become a leader in the provisionof products that have limited impact on theenvironment. This challenge demands the eco designand development of a wide range of products and anenergy management system, resulting in energyconservation and a reduction of waste.