Technical Concepts - Fault Analysis Methods (Continued) · 1) How AC and DC decay ... the ANSI...
Transcript of Technical Concepts - Fault Analysis Methods (Continued) · 1) How AC and DC decay ... the ANSI...
"What is the difference between a traditional fault calculation and an ANSI-based fault calculation" is acommon question. While a thorough review of the ANSI C37 standards is required for complete understand-ing, the following summary highlights the primary conceptual differences.
The primary differences include:1) How AC and DC decay are handled for interrupting calculations.2) How the X/R ratios are calculated.3) How the X/R ratios are used in the calculations.4) Whether the calculated currents are adjusted to account for differences in application versus breakertesting conditions.
A traditional fault calculation reports the initial symmetrical fault current and initial asymmetrical faultcurrent (the difference being the DC offset) as shown in the following figure. It is also possible to report theasymmetrical fault current at any time using the DC decay, which is based on the system X/R. The DCcomponent is calculated by equation from the system impedance and decays more slowly at higher X/Rvalues.
Notice that for traditional fault calculations, the only differencebetween the Asymmetrical current and the Symmetrical currentis the DC offset and decay. This assumes that there is no ACdecay from rotating equipment. The initial symmetrical andmomentary asymmetrical values are not affected by the ACdecay, however interrupting values will be affected dependingon the amount of motor and local generator contribution.
Rather than calculate the DC decay by equation, the ANSIstandard adjusts the motor and local generator contributionsin an effort to account for both the AC and DC decay. Thefollowing adjustment factors are used in the ANSI C37.010and C37.5 standards for the interrupting calculations.
Type of Contribution X"d MultiplierUtility 1.0 (no adjustment)Synchronous Motors 1.5Induction Motors>1000 HP <= 1800 RPM 1.5> 250 HP <= 3600 RPM 1.550>1000 HP <= 1800 RPM 3.050<250 HP <= 3600 RPM 3.0<50 HP Excluded from Calculation
Further AC/DC or DC only adjustments are made usingmultiplying factors published in the standard. These factorsare multiplied times the calculated fault current and serve toaccount for variations in X/R ratios and to compare totalasymmetrical values to equivalent symmetrical values.
Sample AC/DC or DC only factors are shown below. The applicable curves change depending on whether you arecalculating fault currents to compare with Total Rated Breakers (pre-1962) or Symmetrical Rated Breakers. They alsovary for generator contributions depending on whether they are considered local or remote.
Another subtle difference between traditional fault calculation methods and ANSI C37 fault calculations is that theANSI method calculates X/R ratios from separate X and R network calculations, whereas the traditional methodscalculate the X/R ratio using complex impedance values. Since the decrement value adjustments are based on X/Rratios, the differences between complex network calculations and separate R and X calculations can affect the calcu-lated fault currents.
This simplified description of the differences between traditional fault calculations methods and the ANSI C37 calcula-tion methods is intended to provide a general overview and is not intended as an application guide. There are severaldetails left out of this discussion for simplicity. Refer to the appropriate ANSI standards and NEMA publications fordetailed application instructions.
The A_FAULT module rigorously follows the ANSI C37 standards. The DAPPER Comprehensive fault modulefollows the traditional complex calculation method.
Similarly, a low voltage factor is applied to calculated fault currents used to select low voltage breakers when thecalculated system X/R is larger than the X/R used to test the circuit breaker.
Technical Concepts - Fault Analysis Methods
MULTIPLYING FACTORS FOR E/X AMPERES
UTILITY
LOCALGENERATORS
MOTORS
Synchronous
Induction
RATIOX/R
Total Asymmetrical CurrentAC Component
DC Component
DCOffset
Technical Concepts - Fault Analysis Methods (Continued)