Technical Committee on Piping Systems (HEA-PIP) - NFPA · Technical Committee on Piping Systems...

52
Technical Committee on Piping Systems (HEA-PIP) M E M O R A N D U M DATE: May 10, 2013 TO: Principal and Alternate Members of the Technical Committee on Piping Systems (HEA-PIP) FROM: Jon Hart, Fire Protection Engineer/NFPA Staff Liaison SUBJECT: AGENDA PACKAGE– NFPA 99 Second Draft Meeting (A2014) ________________________________________________________________________ Enclosed is the agenda for the NFPA 99 Second Draft meeting of the Technical Committee on Piping Systems, which will be held on Tuesday, June 4, 2013 through Wednesday, June 5, 2013 at the Embassy Suites Fort Lauderdale, in Ft. Lauderdale, FL. Please review the attached comments in advance, and if you have alternate suggestions, please come prepared with proposed language and respective substantiation. If you have any questions prior to the meeting, please do not hesitate to contact me at: Office: (617) 984-7470 Email: [email protected] For administrative questions, please contact Elena Carroll at (617) 984-7952. I look forward to working with everyone.

Transcript of Technical Committee on Piping Systems (HEA-PIP) - NFPA · Technical Committee on Piping Systems...

Technical Committee on Piping Systems (HEA-PIP)

M E M O R A N D U M

DATE: May 10, 2013 TO: Principal and Alternate Members of the Technical Committee on Piping Systems

(HEA-PIP) FROM: Jon Hart, Fire Protection Engineer/NFPA Staff Liaison SUBJECT: AGENDA PACKAGE– NFPA 99 Second Draft Meeting (A2014) ________________________________________________________________________

Enclosed is the agenda for the NFPA 99 Second Draft meeting of the Technical Committee on

Piping Systems, which will be held on Tuesday, June 4, 2013 through Wednesday, June 5,

2013 at the Embassy Suites Fort Lauderdale, in Ft. Lauderdale, FL. Please review the

attached comments in advance, and if you have alternate suggestions, please come prepared with

proposed language and respective substantiation.

If you have any questions prior to the meeting, please do not hesitate to contact me at:

Office: (617) 984-7470 Email: [email protected]

For administrative questions, please contact Elena Carroll at (617) 984-7952.

I look forward to working with everyone.

Technical Committee on Piping Systems

(HEA-PIP) NFPA 99 Second Draft Meeting (Annual 2014) Tuesday, June 4, and Wednesday, June 5, 2013

Embassy Suites Fort Lauderdale 1100 SE 17th Street, Ft. Lauderdale, FL 33316

AGENDA

1. Call to Order – 8:00 am (6/4)

2. Introductions and Attendance

3. Chairman Comments

4. Approval of Previous Meeting Minutes

5. Staff Liaison Presentation

6. Preparation of the Second Draft

• Review Public Comments • Review Correlating Notes • Create Second Revisions

7. New Business

8. Adjournment

Please submit requests for additional agenda items to the chair and staff liaison at least seven days prior to the meeting. Please notify the chair and staff liaison as soon as possible if you plan to introduce any second revisions at the meeting.

Technical Committee on Piping Systems

(HEA-PIP) NFPA 99 Second Draft Meeting (Annual 2014) Tuesday, June 4, and Wednesday, June 5, 2013

Embassy Suites Fort Lauderdale 1100 SE 17th Street, Ft. Lauderdale, FL 33316

Key Dates for the Annual 2014 Revision Cycle

Public Comment Closing Date May 3, 2013 Final Date for Second Draft Meeting July 12, 2013 Final Date for Ballot Return September 20, 2013 Correlating Committee Second Draft Meeting October 16, 2013 Final Second Draft Posted January 3, 2014 Closing Date for Notice of Intent to Make a Motion (NITMAM) February 7, 2014 Issuance of Consent Document (No NITMAMs) May 9, 2014 NFPA Annual Meeting (Las Vegas) June 2014 Issuance of Document with NITMAM August 12-14, 2014

Technical Committee deadlines are in bold.

Technical Committee on Piping Systems

(HEA-PIP) NFPA 99 Second Draft Meeting (Annual 2014) Tuesday, June 4, and Wednesday, June 5, 2013

Embassy Suites Fort Lauderdale 1100 SE 17th Street, Ft. Lauderdale, FL 33316

Staff Liaison Notice Note from the Staff Liaison Dear Technical Committee Members: We are very pleased that you will be participating in the processing of the 2015 Edition of NFPA 99, Health Care Facilities Code. Development of this document would not be possible without the participation of volunteers like you. Meeting Preparation Committee members should review the published comments prior to the meeting and to be prepared to act on each item. Handout materials should be submitted to the chair and staff liaison at least seven days prior to the meeting. Only one posting of the Public Comments will be made; it will be arranged in section/order and will be pre-numbered. This will be posted to the NFPA 99 Document Information page (www.nfpa.org/99) under the “Next Edition” tab. If you have trouble accessing the website please contact Elena Carroll at [email protected].

Mandatory Materials: • Last edition of the standard • Meeting agenda • Public Comments • Committee Officers' Guide (Chairs) • Roberts’ Rules of Order (Chairs; An abbreviated version may be found in the

Committee Officer’s Guide) Optional Materials:

• NFPA Annual Directory • NFPA Manual of Style

Technical Committee on Piping Systems

(HEA-PIP) NFPA 99 Second Draft Meeting (Annual 2014) Tuesday, June 4, and Wednesday, June 5, 2013

Embassy Suites Fort Lauderdale 1100 SE 17th Street, Ft. Lauderdale, FL 33316

Regulations and Guiding Documents All committee members are expected to behave in accordance with the Guide for the Conduct of Participants in the NFPA Codes and Standards Development Process. All actions during and following the committee meetings will be governed in accordance with the Regulations Governing the Development of NFPA Standards. Failure to comply with these could result in challenges to the standards-making process. A successful challenge on procedural grounds could prevent or delay publication of the document. The style of the document must comply with the Manual of Style for NFPA Technical Committee Documents.

Technical Committee on Piping Systems

(HEA-PIP) NFPA 99 Second Draft Meeting (Annual 2014) Tuesday, June 4, and Wednesday, June 5, 2013

Embassy Suites Fort Lauderdale 1100 SE 17th Street, Ft. Lauderdale, FL 33316

General Procedures for Meetings

• Use of tape recorders or other means capable of producing verbatim transcriptions of any NFPA Committee Meeting is not permitted.

• Attendance at all NFPA Committee Meetings is open. All guests must sign in and identify their affiliation.

• Participation in NFPA Committee Meetings is generally limited to committee members and NFPA staff. Participation by guests is limited to individuals, who have received prior approval from the chair to address the committee on a particular item, or who wish to speak regarding public proposals or comments that they submitted.

• The chairman reserves the right to limit the amount of time available for any presentation.

• No interviews will be allowed in the meeting room at any time, including breaks.

• All attendees are reminded that formal votes of committee members will be secured by letter ballot. Voting at this meeting is used to establish a sense of agreement, but only the results of the formal letter ballot will determine the official action of the committee.

• Note to Special Experts: Particular attention is called to Section 3.3(e) of the NFPA Guide for the Conduct of Participants in the NFPA Codes and Standards Development Process in the NFPA Directory. This section requires committee members to declare any interest they may represent, other than their official designation as shown on the committee roster. This typically occurs when a special expert is retained by and represents another interest category on a particular subject. If such a situation exists on a specific issue or issues, the committee member shall declare those interests to the committee and refrain from voting on any action relating to those issues.

• Smoking is not permitted at NFPA Committee Meetings.

Address List No PhonePiping Systems HEA-PIP

Health Care Facilities

Jonathan Hart05/03/2013

HEA-PIP

James K. Lathrop

ChairKoffel Associates, Inc.81 Pennsylvania AvenueNiantic, CT 06357

SE 03/05/2012HEA-PIP

Mark W. Allen

PrincipalBeacon Medaes1800 Overview DriveRock hill, SC 29730-7463Alternate: Mark T. Franklin

M 1/1/1986

HEA-PIP

Grant A. Anderson

PrincipalBard, Rao & Athanas Consulting Engineers, LLC9 Stagecoach RoadBoxford, MA 01921

SE 7/14/2004HEA-PIP

Steven J. Barker

PrincipalUniversity of ArizonaCOM/Department of Anesthesiology1501 North Campbell AvenuePO Box 245114Tucson, AZ 85724-5114American Society of AnesthesiologistsAlternate: Robert G. Loeb

C 8/9/2011

HEA-PIP

Chad E. Beebe

PrincipalASHE - AHAPO Box 5756Lacey, WA 98509-5756American Society for Healthcare Engineering

U 10/20/2010HEA-PIP

David L. Brittain

PrincipalProVac8012 Glendevan Street, NWMassillon, OH 44646-9017

M 1/1/1988

HEA-PIP

Dana A. Colombo

PrincipalPIPE/National ITC Corporation2540 Severn AvenueMetairie, LA 70002Alternate: Michael T. Massey

L 03/05/2012HEA-PIP

Keith Ferrari

PrincipalPraxair, Inc.2807 Gresham Lake RoadRaleigh, NC 27615Compressed Gas AssociationAlternate: Gary L. Bean

M 1/16/2003

HEA-PIP

William C. Fettes

PrincipalAirgas, Inc.11523 Knox StreetOverland Park, KS 66210Alternate: Barry E. Brown

IM 7/23/2008HEA-PIP

Michael Frankel

PrincipalUtility Systems Consultants10860 Royal Caribbean CircleBoynton Beach, FL 33437-4219American Society of Plumbing Engineers

SE 7/1/1995

HEA-PIP

Ed Golla

PrincipalTRI/Air Testing1607 North Cuernavaca Drive, Suite 500Austin, TX 78733-1600

RT 4/3/2003HEA-PIP

John C. Gregory

PrincipalHDR Architecture Inc.3200 East Camelback Road, Suite 250Phoenix, AZ 85018Alternate: Marc Dodson

SE 3/1/2011

1

Address List No PhonePiping Systems HEA-PIP

Health Care Facilities

Jonathan Hart05/03/2013

HEA-PIP

Daniel Patrick Kelly

PrincipalThe Cleveland Clinic9500 Euclid AvenueCleveland, OH 44195Alternate: Edward J. Lyczko

U 10/29/2012HEA-PIP

Anthony Lowe

PrincipalAllied Hospital SystemsAllied Air Compressor, Inc.512-A Crain Highway NorthGlen Burnie, MD 21061Alternate: Gary Currence

IM 03/05/2012

HEA-PIP

James L. Lucas

PrincipalTri-Tech Medical Inc.35401 Avon Commerce ParkwayAvon, OH 44011-1374

M 7/14/2004HEA-PIP

Jeffery F. McBride

PrincipalRed Lion Medgas Consultants, Inc.123A Sandy DriveNewark, DE 19713

SE 10/27/2009

HEA-PIP

Donald R. McIlroy

PrincipalProvidence Health System9205 SW Barnes RoadPortland, OR 97225

U 10/4/2007HEA-PIP

David B. Mohile

PrincipalMedical Engineering Services, Inc.40836 Oak Bucket LaneLeesburg, VA 20175-8814

SE 1/1/1989

HEA-PIP

Thomas J. Mraulak

PrincipalPlumbing Industry Training Center1911 Ring DriveTroy, MI 48083-4229American Society of Sanitary EngineeringAlternate: David D. Eastman

L 10/1/1999HEA-PIP

Ronald J. Schwipps

PrincipalHill-Rom, Inc.1069 State Route 46 EastMail Code M19Batesville, IN 47006-1252

M 08/09/2012

HEA-PIP

E. Daniel Shoemaker

PrincipalAccutron Inc.607 West Camino CircleMesa, AZ 85201

M 7/1/1994HEA-PIP

Matt Sigler

PrincipalInternational Association of Plumbing & Mechanical Officials4755 East Philadelphia StreetOntario, CA 91761

E 08/09/2012

HEA-PIP

Ronald M. Smidt

PrincipalCarolinas HealthCare SystemPO Box 901Troutman, NC 28166NFPA Health Care Section

U 11/14/1997HEA-PIP

Russell C. Thomason

PrincipalUS Army Corps of EngineersMedical Facilities Center of Expertise221 North William StreetMt. Prospect, IL 60056

U 3/4/2009

HEA-PIP

J. Richard Wagner

PrincipalJ. Richard Wagner, PE, LLC207 Locknell RoadTimonium, MD 21093-3323Mechanical Contractors Association of America, Inc.

IM 1/1/1986HEA-PIP

Jonathan C. Willard

PrincipalCertified Medical Gas Services532 Bedford RoadNew Boston, NH 03070

SE 7/23/2008

2

Address List No PhonePiping Systems HEA-PIP

Health Care Facilities

Jonathan Hart05/03/2013

HEA-PIP

Wayne T. Wozniak

PrincipalAmerican Dental Association211 East Chicago AvenueChicago, IL 60103American Dental AssociationAlternate: P. L. Fan

U 10/28/2008HEA-PIP

Gary L. Bean

AlternateAir Products & Chemicals, Inc.2920-A Horizon Park DriveSuwanee, GA 30024Compressed Gas AssociationPrincipal: Keith Ferrari

M 7/23/2008

HEA-PIP

Barry E. Brown

AlternateAirgas, Inc.3426 Starwood TrailLilburn, GA 30047Principal: William C. Fettes

IM 8/2/2010HEA-PIP

Laurence T. Coleman

AlternatePipe Fitters Local Union 597-Chicago10850 West 187th StreetMokena, IL 60448American Society of Sanitary EngineeringPrincipal: Thomas J. Mraulak

L 10/29/2012

HEA-PIP

Gary Currence

AlternateAllied Hospital Systems512 Crain Highway North, Suite AGlen Burnie, MD 21061Principal: Anthony Lowe

IM 10/29/2012HEA-PIP

Marc Dodson

AlternateC-Scan Technologies, Inc.PO Box 87239Phoenix, AZ 85080Principal: John C. Gregory

SE 03/07/2013

HEA-PIP

David D. Eastman

AlternateMetro Detroit Plumbing Industry Training Center1911 Ring DriveTroy, MI 48083American Society of Sanitary EngineeringPrincipal: Thomas J. Mraulak

L 7/20/2000HEA-PIP

P. L. Fan

Alternate2829 Plaza VerdeSanta Fe, NM 87507American Dental AssociationPrincipal: Wayne T. Wozniak

U 1/1/1994

HEA-PIP

Mark T. Franklin

AlternateSherman Engineering Company3679 Old Easton RoadDoylestown, PA 18902Principal: Mark W. Allen

M 03/05/2012HEA-PIP

Robert G. Loeb

AlternateUniversity of ArizonaDepartment of Anesthesiology1501 North Campbell Ave., Room 5301PO Box 245114Tucson, AZ 85724-5114American Society of AnesthesiologistsPrincipal: Steven J. Barker

C 8/9/2011

HEA-PIP

Edward J. Lyczko

AlternateThe Cleveland Clinic19680 Puritas Avenue, #252Cleveland, OH 44135Principal: Daniel Patrick Kelly

U 07/26/2007HEA-PIP

Michael T. Massey

AlternatePIPE/National ITC Corporation501 Shatto Place, Suite 200Los Angeles, CA 90020-1713Principal: Dana A. Colombo

L 4/17/2002

3

Address List No PhonePiping Systems HEA-PIP

Health Care Facilities

Jonathan Hart05/03/2013

HEA-PIP

Jonathan Hart

Staff LiaisonNational Fire Protection Association1 Batterymarch ParkQuincy, MA 02169-7471

3/1/2012

4

Friday 5 3, Friday

Piping SystemsHEA-PIPName Representation Class Office

Distribution by %

Company

Steven J. Barker University of Arizona ASA C Principal

1Voting Number Percent 4%

Matt Sigler International Association of Plumbing& Mechanical Officials

IAPMO E Principal

1Voting Number Percent 4%

William C. Fettes Airgas, Inc. IM Principal

Anthony Lowe Allied Hospital Systems IM Principal

J. Richard Wagner J. Richard Wagner, PE, LLC MCAA IM Principal

3Voting Number Percent 11%

Dana A. Colombo PIPE/National ITC Corporation L Principal

Thomas J. Mraulak Plumbing Industry Training Center ASoSE L Principal

2Voting Number Percent 7%

Mark W. Allen Beacon Medaes M Principal

David L. Brittain ProVac M Principal

Keith Ferrari Praxair, Inc. CGA M Principal

James L. Lucas Tri-Tech Medical Inc. M Principal

Ronald J. Schwipps Hill-Rom, Inc. M Principal

E. Daniel Shoemaker Accutron Inc. M Principal

6Voting Number Percent 22%

Ed Golla TRI/Air Testing RT Principal

1Voting Number Percent 4%

James K. Lathrop Koffel Associates, Inc. SE Chair

Grant A. Anderson Bard, Rao & Athanas ConsultingEngineers, LLC

SE Principal

Michael Frankel Utility Systems Consultants ASPE SE Principal

John C. Gregory HDR Architecture Inc. SE Principal

Jeffery F. McBride Red Lion Medgas Consultants, Inc. SE Principal

David B. Mohile Medical Engineering Services, Inc. SE Principal

Friday 5 3, Friday

Piping SystemsHEA-PIPName Representation Class Office

Distribution by %

Company

Jonathan C. Willard Certified Medical Gas Services SE Principal

7Voting Number Percent 26%

Chad E. Beebe ASHE - AHA ASHE U Principal

Daniel Patrick Kelly The Cleveland Clinic U Principal

Donald R. McIlroy Providence Health System U Principal

Ronald M. Smidt Carolinas HealthCare System NFPA/HCS U Principal

Russell C. Thomason US Army Corps of Engineers U Principal

Wayne T. Wozniak American Dental Association ADA U Principal

6Voting Number Percent 22%

27Total Voting Number

MINUTES NFPA Technical Committee on Piping Systems (HEA-PIP)

August 22 + 23, 2012 First Draft Meeting

Sheraton Suites at Symphony Hall – San Diego, CA

1. Call to Order. Committee Chair, James Lathrop, called the meeting to order at 8:05 am on Wednesday, August 22, 2012.

2. Attendance and Introductions: Attendance was taken and those present at the meeting introduced themselves and stated who they represent on the committee. Those who were present at the meeting are listed below:

Name  Representing 

Lathrop , James – Chair  Koffel Associates, Inc.

Allen, Mark – Principal   Beacon Medaes

Barker, Steven ‐ Principal   American Society of Anesthesiologists

Beebe, Chad – Principal   American Society for Healthcare Engineers

Brittain, David – Principal  ProVac

Colombo, Dana – Principal  PIPE/National ITC Corporation 

Ferrari, Keith –Principal   Compressed Gas Association 

Fettes, William – Principal  Airgas, Inc.

Frankel, Michael – Principal  American Society of Plumbing Engineers

Golla, Ed – Principal  TRI/Air Testing

Gregory, John ‐ Principal  HDR Architecture Inc.

Lowe, Anthony – Principal  Allied Hospital Systems

Lucas, James – Principal   Tri‐Tech Medical Inc.

McBride, Jeffery – Principal  Red Lion Medgas Consultants, Inc. 

McIlroy, Donald – Principal  Providence Health & Services 

Mohile, David – Principal  Medical Engineering Services, Inc. 

Thomas, Mraulak – Principal   American Society of Sanitary Engineering

Smidt, Ronald – Principal (web) NFPA Health Care Section

Thomason, Russell – Principal   US Army Corps of Engineers 

Wagner, J. Richard – Principal  Mechanical Contractors Association of America, Inc. 

Willard, Jonathan – Principal  Certified Medical Gas Services 

Bean, Gary – Alternate  Compressed Gas Association 

Brown, Barry – Alternate  Airgas, Inc.

Franklin, Mark – Alternate  Sherman Engineering Company 

Hart, Jonathan – Staff Liaison  NFPA

Bielen, Richard – NFPA Staff  NFPA

Currence, Gary – Guest  Allied Hospital Systems

Dodson, Mark – Guest  C‐Sean Technologies

Kelly, Patrick – Guest  Cleveland Clinic

Shoemaker, Daniel – Guest  Accutron

3. Chairman Comments: Jim Lathrop spoke to the agenda for the meeting and provided opening comments.

4. Minutes Approval: The minutes of the HEA-PIP September 28 + 29, 2010 ROC Meeting were approved as distributed in the Agenda Package with one amendment.

5. Staff Liaison Presentation: Jon Hart introduced himself and proceeded to give the staff presentation for the meeting which included general meeting procedures, a review of the Annual 2014 revision cycle, and an introduction to NFPA’s new revision process.

6. Development of First Draft: The committee reviewed all public input (PI) and resolved it by either providing a committee statement or by creating a first revision (FR) based on the PI. Other First Revisions were also created. See the First Draft and First Draft report for the official committee actions.

7. Old Business: There was no old business.

8. New Business: There was no new business.

9. Next Meeting: TBD in the late May or June 2013 timeframe.

10. Meeting Adjourned: The meeting was adjourned at 5:30 pm on August 23, 2012.

Public

Comments

Public Comment No. 99-NFPA 99-2013 [ New Section after 3.3.103 ]

3.3.XX Mcro Bulk Cryogenic SystemAn assembly of equipment, a container that is permanently installed through anchoring to a foundation,pressure regulators, pressure relief devices, vaporizers, manifolds, and interconnecting piping is designedto be filled at the health care facility with a cryogenic gas, that has a storage capacity of more than less orequal to 566 m3 (20,000 ft3 (scf)) of oxygen, including unconnected reserves on hand at the site, and thatterminates at the source valve.

Additional Proposed Changes

File Name Description Approved3.3.x.pdf Cover Sheet (email sent by Phillip Mariscal)

Statement of Problem and Substantiation for Public Comment

Editorial revision to CI 305. The original intent about small bulk or microbulk is related to gas supplies at 20,000 cu ft or less. (Bulk Gas is defined as over 20,000 cu ft).

Submitter Information Verification

Submitter Full Name: JERROLD SAMETHOrganization: CGASubmittal Date: Thu May 09 12:41:28 EDT 2013

Copyright Assignment

I, JERROLD SAMETH, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyrightin this Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intendthat I acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or anothersimilar or derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority toenter into this copyright assignment.

By checking this box I affirm that I am JERROLD SAMETH, and I agree to be legally bound by the above Copyright Assignment and theterms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will,upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 97 5/10/2013 9:14 AM

Public Comment No. 37-NFPA 99-2013 [ Section No. 5.1.3.2.13 ]

5.1.3.2.13 Central supply systems for nitrous oxide and carbon dioxide using cylinders or portable containers shallbe prevented from reaching temperatures lower than the recommendations of the central supply system'smanufacturer, but shall never be lower than -7°C (20°F) or greater than 51.6°C (125°F).

Statement of Problem and Substantiation for Public Comment

I agree with the temperatures stated in this paragraph and endorse the change from the 2012 edition. This matches the requirements in chapter 9.

Submitter Information Verification

Submitter Full Name: CORKY BISHOPOrganization: AIRGAS MEDICAL SERVICESSubmittal Date: Fri Apr 26 18:23:19 EDT 2013

Copyright Assignment

I, CORKY BISHOP, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright inthis Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend thatI acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similaror derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter intothis copyright assignment.

By checking this box I affirm that I am CORKY BISHOP, and I agree to be legally bound by the above Copyright Assignment and theterms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will,upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 97 5/10/2013 9:14 AM

Public Comment No. 75-NFPA 99-2013 [ Section No. 5.1.3.2.13 ]

5.1.3.2.13 Central supply systems for nitrous oxide and carbon dioxide using cylinders or portablecontainers shall be prevented from reaching temperatures lower than the recommendationsof the central supply system's manufacturer , but shall never be lower than -7°C (20°F) orgreater than 51 . 6°C (125°F).

Additional Proposed Changes

File Name Description Approved

Figure_1_Carbon_Dioxide_Vapor_Pressure_Curve_CGA_Handbook_of_Compressed_Gases.pdf

CGA Handbook of Compressed Gases. Carbon Dioxide Vapor Pressure Curve Figure 1 (CGA Public Comment responding to Public Input #383). From 5th edition.

Table_1B_Thermodynamic_Properties.pdf

Table 1B. Thermodynamic properties of saturated carbon dioxide solid, liquid, and vapor phases. CGA Handbook of Compressed Gases 5th edition.

Nitrous_Oxide_Vapor_Pressure_Curve.pdf

Nitrous Oxide Vapor Pressure Curve from CGA Handbook of Compressed Gases, 5th edition.

Statement of Problem and Substantiation for Public Comment

No empirical data was given to change the min. temp from -20F to +20F. CGA G-8.1 (2007) Standard for Nitrous Oxide Systems at Consumer Sites: "8.2 Requirements: These storage vessels shall be designed, constructed, and tested in accordance with the appropriate requirements of the ASME Boiler & Pressure Vessel Code, Section VIII, Division 1, Unfired Pressure Vessels [14]. Special construction is required for operating temperatures below –20 °F (–29 °C). In Canada, the design and installation of these vessels must be approved by the Pressure Vessels Department of the appropriate provincial government."

The Code of Federal Regulations (29 CFR 1910.101), states, "the in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tank cars or motor vehicle cargo tanks shall be in accordance with Compressed Gas Association Pamphlet P-1."

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 97 5/10/2013 9:14 AM

A temperature of - 20° F will provide an adequate cylinder pressure for a medical supply system (188.3 psig and 200.3 psig for nitrous oxide and carbon dioxide, respectively). Leaving the current plus + 20 F would prohibit outside systems on most of the USA (without additional heating devices or additional structures with additional unnecessary costs).

In 2002: the explanation given was: The minimum temperature for nitrous oxide and carbon dioxide results from the fact that these gases are actually above their triple point in a standard cylinder and are thus in liquid form inside the cylinder. Their pressure-temperature curves are steep, so they lose pressure rapidly as temperature falls, reaching a point where the liquid simply cannot vaporize, and the gas cannot draw off. A temperature of - 20° F will provide an adequate cylinder pressure for a medical supply system (188.3 psig and 200.3 psig for nitrous oxide and carbon dioxide, respectively). Leaving the current plus 10 (or plus 20) would prohibit outside systems on most of the USA (without additional construction utilizing heating devices or additional structures that will add unnecessary costs).

The high pressure cylinders, either steel or aluminum, are manufactured and tested for temperatures at or below - 20 degrees Fahrenheit.There are control modules/manifolds (AMKO, ACME, Chart) installed, at hospitals, in areas of the USA where temperatures reach - 20 degrees Fahrenheit or below. These modules operate and meet the delivery line pressure requirements of NFPA 99. CGA G 8.1 (2007) Standard for Nitrous Oxide Systems at Customer Sites. Scope: This standard covers the general principles recommended for the installation of Nitrous Oxide systems on medical or industrial customer premises. Such systems consist of a central supply, which can be either cylinders connected to a common manifold, liquid containers, or bulk liquid, and the associated equipment and piping required for connecting the central supply to the line supplying the nitrous oxide to the point of use.

Section 8.2 RequirementsStorage vessels shall be designed, constructed, and tested in accordance with the appropriate requirements of the ASME Boiler & Pressure Vessel Code, Section VIII, Division 1, and Unfired Pressure Vessels. Special construction is required for operating temperatures below - 20 degrees Fahrenheit (- 29 degrees Celsius).

Submitter Information Verification

Submitter Full Name: Phillip MariscalOrganization: Compressed Gas AssociationSubmittal Date: Fri May 03 11:37:43 EDT 2013

Copyright Assignment

I, Phillip Mariscal, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright inthis Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend thatI acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similaror derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter intothis copyright assignment.

By checking this box I affirm that I am Phillip Mariscal, and I agree to be legally bound by the above Copyright Assignment and theterms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will,upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 97 5/10/2013 9:14 AM

Public Comment No. 10-NFPA 99-2013 [ Section No. 5.1.3.3.3 ]

5.1.3.3.3 Ventilation. ( Please see 9.3.6 Medical gas storage and transfilling for room ventilationrequirements.)5.1.3.3.3.1 Venting of Relief Valves.

Indoor supply systems shall have all relief valves vented per 5.1.3.5.6.1 (4) through (9).5.1.3.3.3.2 Ventilation for Motor-Driven Equipment.

The following source locations shall be adequately ventilated to prevent accumulation of heat:

(1) Medical air sources (see 5.1.3.6 )

(2) Medical–surgical vacuum sources (see 5.1.3.7 )

(3) Waste anesthetic gas disposal (WAGD) sources (see 5.1.3.8.1 )

(4)

5.1.3.3.3.3 Ventilation for Outdoor Locations.(A)

Outdoor locations surrounded by impermeable walls, except fire barrier walls, shall haveprotected ventilation openings located at the base of each wall to allow free circulation of airwithin the enclosure.(B)

Walls that are shared with other enclosures or with buildings shall be permitted to not haveopenings.(C)

The fire barrier wall shall not have openings or penetrations, except conduit or piping shall bepermitted provided that the penetration is protected with a firestop system in accordance withthe building code.

Statement of Problem and Substantiation for Public Comment

I think one of the biggest concerns I had with 2012 was no reference to room ventilation requirements guiding the installer/designer to look to 9.3.7 (2012) for these requirements. I would like to see the complete ventilation section reinstated in chapter 5 under venting for ease of use to the installer and designer. If this is not possible a simple reference to 9.3.6 (2015) would be sufficient.

Submitter Information Verification

Submitter Full Name: Scott StarkweatherOrganization: Emcor New England Mechanical ServicesSubmittal Date: Fri Mar 15 05:15:24 EDT 2013

Copyright Assignment

I, Scott Starkweather, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyrightin this Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intendthat I acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or anothersimilar or derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority toenter into this copyright assignment.

By checking this box I affirm that I am Scott Starkweather, and I agree to be legally bound by the above Copyright Assignment and theterms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will,upon my submission of this form, have the same legal force and effect as a handwritten signature

* Instrument air sources (see 5.1.3.9 )

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 97 5/10/2013 9:14 AM

Public Comment No. 68-NFPA 99-2013 [ Section No. 5.1.3.5.7 ]

5.1.3.5.7 Auxiliary Source Connection.All source systems shall be provided with an auxiliary source connection point of the same size asthe main line, which shall be located immediately on the patient side of the source valve. 5.1.3.5.7.1 The connection shall consist of a tee, a valve, and a removable plug or cap.5.1.3.5.7.2 The auxiliary source connection valve shall be normally closed and secured.5.1.3.5.7.3 On oxygen systems furnished with an emergency oxygen supply connection (EOSC), the EOSCshall be considered to fulfill this requirement.

Statement of Problem and Substantiation for Public Comment

The EOSC is used for backing up a facility in the case of a bulk supply shutdown for emergency, major repair, and major maintenance. The auxiliary source connection is used for normal maintenance (minor repairs, normal preventative maintenance) around the bulk supply.

Submitter Information Verification

Submitter Full Name: Phillip MariscalOrganization: Compressed Gas AssociationSubmittal Date: Thu May 02 14:49:53 EDT 2013

Copyright Assignment

I, Phillip Mariscal, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright inthis Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend thatI acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similaror derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter intothis copyright assignment.

By checking this box I affirm that I am Phillip Mariscal, and I agree to be legally bound by the above Copyright Assignment and theterms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will,upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 97 5/10/2013 9:14 AM

Public Comment No. 74-NFPA 99-2013 [ New Section after 5.1.3.6.3.9(C) ]

TITLE OF NEW CONTENT(7) Control circuits utilizing fuses for overcurrent protection shall be provided with means to replace the fusewithout interuption to the control circuit.

Statement of Problem and Substantiation for Public Comment

Currently some medical air compressor manufacturers are utilizing fuses to protect the compressor PLC. The compressor PLC also control the air treatment equipment, dryers, co & dp monitors, condensate drains, etc. If the fuse blows the PLC no longer received power and the aforesaid equipment will not operate.

NFPA 70 requires a control panels to have means to disconnect without flipping a main breaker - In the field there are numerous medical air compressor that comply with NFPA 99 but not NFPA 70. Electrical Inspectors do not find the problem due to the medical air compressor system have control panel mounted disconnects that appear at a glance to disconnect the complete panel but the panel is still HOT.

Submitter Information Verification

Submitter Full Name: Anthony LoweOrganization: Allied Hospital SystemsSubmittal Date: Fri May 03 08:47:03 EDT 2013

Copyright Assignment

I, Anthony Lowe, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright inthis Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend thatI acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similaror derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter intothis copyright assignment.

By checking this box I affirm that I am Anthony Lowe, and I agree to be legally bound by the above Copyright Assignment and the termsand conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will, upon mysubmission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 97 5/10/2013 9:14 AM

Public Comment No. 78-NFPA 99-2013 [ Section No. 5.1.3.6.3.9(C) ]

(C) Each compressor motor shall be provided with electrical components including, but not limited to,the following:

(1) Dedicated disconnect switch installed in the electrical circuit ahead of each motor starter

(2) Motor starting device

(3) Overload protection

(4) Where compressor systems having two or more compressors employ a control transformer orother voltage control power device, installation of at least two such devices.

(5) Control circuits arranged in such a manner that the shutdown of one compressor does notinterrupt the operation of another compressor

(6) Automatic restart function, such that the compressor(s) will restart after power interruptionwithout manual intervention

(7) Electrical devices not directing controlling the operation of the compressors shall be poweredfrom a separate EESS power feed.

Statement of Problem and Substantiation for Public Comment

We had a single feed coming in to a fuse block that fed the entire air treatment center. When a 2 amp control fuse blew, the entire air treatment center was shut down. This created a hazrard to the care of our patients and for the tech who came to serve the unit being that the panel was still live.

Submitter Information Verification

Submitter Full Name: DAVID MCGUNIGALEOrganization: BALTIMORE WA MED CENTERSubmittal Date: Fri May 03 12:53:02 EDT 2013

Copyright Assignment

I, DAVID MCGUNIGALE, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights incopyright in this Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understandand intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this oranother similar or derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power andauthority to enter into this copyright assignment.

By checking this box I affirm that I am DAVID MCGUNIGALE, and I agree to be legally bound by the above Copyright Assignment andthe terms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature thatwill, upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 97 5/10/2013 9:14 AM

Public Comment No. 79-NFPA 99-2013 [ Section No. 5.1.3.8.1.6 ]

5.1.3.8.1.6 The WAGD source shall consist of the following:

(1) Two or more WAGD producers sufficient to serve the peak calculated demand with thelargest single WAGD producer out of service

(2) Automatic means to prevent backflow from any on-cycle WAGD producers through anyoff-cycle WAGD producers

(3) Shutoff valve to isolate each WAGD producer from the centrally piped system and otherWAGD producers for maintenance or repair without loss of medical–surgical vacuumWAGD in the system

(4) Piping between the WAGD producers and the source shutoff valve compliant with 5.1.10.2 ,as recommended by the manufacturer

(5) Antivibration mountings installed for WAGD producers as required by equipment dynamics orlocation and in accordance with the manufacturer's recommendations

(6) Flexible connectors interconnecting the producers with their intake and outlet piping asrequired by equipment dynamics or location and in accordance with the WAGD producermanufacturer's recommendations

Statement of Problem and Substantiation for Public Comment

Replace medical surgical vacuum in subparagraph (3) with WAGD since this section deals with dedicated WAGD sources.

Submitter Information Verification

Submitter Full Name: CORKY BISHOPOrganization: AIRGAS MEDICAL SERVICESSubmittal Date: Fri May 03 14:55:06 EDT 2013

Copyright Assignment

I, CORKY BISHOP, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright inthis Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend thatI acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similaror derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter intothis copyright assignment.

By checking this box I affirm that I am CORKY BISHOP, and I agree to be legally bound by the above Copyright Assignment and theterms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will,upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 97 5/10/2013 9:14 AM

Public Comment No. 17-NFPA 99-2013 [ Section No. 5.1.4.3 [Excluding any

Sub-Sections] ]

New or replacement

shutoff

valves shall be

as follows:

They shall be of the quarter turn, full ported, ball type.

They shall be of brass or bronze construction.

They shall have extensions for brazing.

They shall have a handle indicating open or closed.They shall consist of three pieces permitting in-line serviceability

permitted to be of any type meeting the following conditions:

(1) with a maximum pressure drop at intended maximum flow of 0.2 psig in pressure service and0.15 inHg in vacuum service*,

(1) quarter turn to on to off,

(2) constructed of materials suitable to the service,

(3) provided with copper tube extensions for brazing,

(4) clearly indicating to the operator if they are open or closed,

(5) permit in-line serviceability,

(6) cleaned for oxygen service by the manufacturer if used for any positive pressure service .

Statement of Problem and Substantiation for Public Comment

Substantiation

The Draft 1 proposal from Jim Lucas on this clause has substantial merit in four specific respects:1. there is not particular reason that a ball valve is necessarily better or worse than any other valve type in medical gas service.2. the standard already permits butterfly valves in vacuum (5.1.4.3.2), which is demonstrably a far worse restriction in absolute terms than many other valve types and has been permitted in a far more pressure-loss sensitive application (vacuum) with no known issues.3. the current standard already permits three way valves (5.1.3.6.3.10) which are also far more flow restrictive than standard balls valves. 3. the current wording is unnecessarily design restrictive.

It is therefore the intent of this submission to revise the wording of the standard to reflect the genuine concerns underlying this paragraph and thereby move to a performance rather than prescriptive clause.

In researching valve types, the standard for expressing valve "resistance to flow" is the Cv value which is readily available for all valves. However, standard medical gas design practice is to design based on pressure drop across the pipeline.

It is thus necessary to convert from Cv to pressure drop, and a formula exists to perform this calculation:

5.4X10-7 * SpGr * T * Q2 SpGr = Specific Gravity referenced to Air (1)�P = ––––––––––––––––––––– T = Temperature °Rankine

Cv2 * Pout Q = flow in SCFH Pout = Pressure absolute

It is standard design practice to allow a 5 psi pressure drop across a pressure gas pipeline and 4 or 5inHg across

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

14 of 97 5/10/2013 9:14 AM

a vacuum pipeline (ref: BeaconMedaes Medical Gas Design Guide, Chapter 4; ASPE Databook Vol. 3 page 68-69)

The standard requires a typical 5 valves between source and outlet (source, main, riser, service and zone). It seems reasonable to allot to these five a worst case 20% of the total loss, or 1 psi for pressure and 0.75 inHgV for vacuum.

Thus, in a workable design each of these 5 valves could be permitted 0.2 psi drop for pressure and 0.15 inHgV, and the proposal is based on these values.

This will require an engineer to utilize the formula (having obtained from the manufacturer the Cv value of the valve under consideration) to determine the loss expected from that valve under their specific design conditions. However, given that calculation, the designer would be free to use any valve which meets the other criteria in the clause. If the valve seemed to be overly restrictive, they would also be at liberty to use a larger (and higher Cv) valve, which is not an option implied in the present standard. **To see the impact of this, the following table will allow some comparisons:

Flow Needed to Attain Allowed Pressure Drop across a Valve at a Typical Commercial Cv Value(using the specific gravity for N2O, 1.53 for worst case)size Cv 55 psiFlow (scfm) 15 inHgFlow (scfm)1/2 26 77 263/4 51 151 501 68 202 671 1/4 120 356 1191 1/2 (ball) 170 505 1681 1/2 (butterfly) 131 390 1292 (ball) 376 1115 3712 (butterfly) 224 667 2222 1/2 (ball) 510 1516 5082 1/2 (butterfly) 366 1088 3623 (ball) 996 2959 9843 (butterfly) 494 1470 4924 (ball) 1893 5626 18744 (butterfly) 840 2503 8345 (butterfly) 1445 4299 14316 (butterfly) 2161 6418 2142

Note: Please also see proposal for Annex Material A-5.1.5.3

Cv Values for ball valves from ApolloCv values for butterfly valves from Flowserve.

Submitter Information Verification

Submitter Full Name: Mark AllenOrganization: Beacon MedaesSubmittal Date: Mon Apr 01 16:45:54 EDT 2013

Copyright Assignment

I, Mark Allen, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in thisPublic Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that Iacquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similar orderivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter intothis copyright assignment.

By checking this box I affirm that I am Mark Allen, and I agree to be legally bound by the above Copyright Assignment and the termsand conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will, upon mysubmission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

15 of 97 5/10/2013 9:14 AM

Public Comment No. 22-NFPA 99-2013 [ Sections 5.1.4.3.1, 5.1.4.3.2 ]

Sections 5.1.4.3.1, 5.1.4.3.25.1.4.3.1

Valves for positive pressure gases shall be cleaned for oxygen service by the manufacturer.5.1.4.3.2

Valves for vacuum or WAGD service shall be permitted to be in accordance with 5.1.4.3 or butterflytype and shall not be required to be cleaned for oxygen service.

Statement of Problem and Substantiation for Public Comment

Please see proposal for 5.4.1.3

Submitter Information Verification

Submitter Full Name: Mark AllenOrganization: Beacon MedaesSubmittal Date: Tue Apr 09 15:11:36 EDT 2013

Copyright Assignment

I, Mark Allen, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in thisPublic Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that Iacquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similar orderivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter intothis copyright assignment.

By checking this box I affirm that I am Mark Allen, and I agree to be legally bound by the above Copyright Assignment and the termsand conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will, upon mysubmission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

16 of 97 5/10/2013 9:14 AM

Public Comment No. 12-NFPA 99-2013 [ Section No. 5.1.4.7 ]

5.1.4.7 Service Valves.(Branch valves)Service valves (Branch valves) shall be installed to allow servicing or modification of lateralbranch piping from a main or riser without shutting down the entire main, riser, or facility.5.1.4.7.1

Only one service valve (Branch valve) shall be required for each branch off of a riser, regardlessof how many zone valve boxes are installed on that lateral.5.1.4.7.2

Service valves (Branch valves) shall be placed in the branch piping prior to any zone valve boxassembly on that branch.5.1.4.7.3

Service valves (Branch valves) shall be located in any one of the following areas:

(1) Behind a locked access door

(2) Locked open above a ceiling

(3) Locked open in a secure area

5.1.4.7.4 Service valves (Branch valves) shall be labeled in accordance with 5.1.11.2 .

Statement of Problem and Substantiation for Public Comment

Most installers I know refer to service valves as branch valves. Adding branch valves in () next to the service valve section eliminates any confusion or someone specifically looking for the words "branch valves" in the standard/code.

Submitter Information Verification

Submitter Full Name: Scott StarkweatherOrganization: Emcor New England Mechanical ServicesSubmittal Date: Fri Mar 15 05:37:33 EDT 2013

Copyright Assignment

I, Scott Starkweather, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyrightin this Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intendthat I acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or anothersimilar or derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority toenter into this copyright assignment.

By checking this box I affirm that I am Scott Starkweather, and I agree to be legally bound by the above Copyright Assignment and theterms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will,upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

17 of 97 5/10/2013 9:14 AM

Public Comment No. 29-NFPA 99-2013 [ Section No. 5.1.9.2.3 [Excluding any

Sub-Sections] ]

The master alarm panels required in 5.1.9.2.1 shall communicate directly to the alarm-initiatingdevices that they monitor.

If wired, paragraphs 5.1.9.2.3.1 thru 5.1.9.2.3.6 should be followed.

Statement of Problem and Substantiation for Public Comment

Paragraph 5.1.9.2.3 provides the installer with option of using other methods of communication which do not limit technology. The subordinate paragraphs 5.1.9.2.3.1 thru 5.1.9.2.3.6 provide the required installation detail for when the installer chooses to wire but without this clarification, may create confusion as to whether other technologies for methods of communication are acceptable.

Submitter Information Verification

Submitter Full Name: James LucasOrganization: Tri-Tech Medical Inc.Submittal Date: Mon Apr 22 11:51:12 EDT 2013

Copyright Assignment

I, James Lucas, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in thisPublic Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that Iacquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similar orderivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter intothis copyright assignment.

By checking this box I affirm that I am James Lucas, and I agree to be legally bound by the above Copyright Assignment and the termsand conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will, upon mysubmission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

18 of 97 5/10/2013 9:14 AM

Public Comment No. 2-NFPA 99-2013 [ Section No. 5.1.10.8 ]

5.1.10.8 Threaded Fittings.Threaded fittings shall meet the following criteria:

(1) They shall be limited to connections for pressure and vacuum indicators, alarm devices,gas-specific demand , check valves fittings , and source equipment on the source side of thesource valve.

(2) They shall be tapered pipe threads complying with ASME B1.20.1, Pipe Threads, GeneralPurpose, Inch.

(3)

Statement of Problem and Substantiation for Public Comment

Please delete the comma to state "gas-specific demand check fittings". These are not check valves as they do not restrict direction of flow. The term used throughout the document is gas-specific demand check fittings.

Related Items from the Public Input Stage for This Document

Related ItemFirst Revision No. 276-NFPA 99-2012 [Section No. 5.1.10.8]

Submitter Information Verification

Submitter Full Name: CORKY BISHOPOrganization: AIRGAS MEDICAL SERVICESSubmittal Date: Thu Mar 07 10:41:29 EST 2013

Copyright Assignment

I, CORKY BISHOP, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright inthis Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend thatI acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similaror derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter intothis copyright assignment.

By checking this box I affirm that I am CORKY BISHOP, and I agree to be legally bound by the above Copyright Assignment and theterms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will,upon my submission of this form, have the same legal force and effect as a handwritten signature

* They shall be made up with polytetrafluroethylene tape or other thread sealantrecommended for oxygen service, with sealant applied to the male threads only and care takento ensure sealant does not enter the pipe.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

19 of 97 5/10/2013 9:14 AM

Public Comment No. 76-NFPA 99-2013 [ Section No. 5.1.10.8 ]

5.1.10.8 Threaded Fittings.Threaded fittings shall meet the following criteria:

(1) They shall be limited to connections for pressure and vacuum indicators, alarm devices,gas-specific demand,check valves, and source equipment on the source side of the sourcevalve.

(2) They shall be tapered pipe threads complying with ASME B1.20.1, Pipe Threads, GeneralPurpose, Inch.

(1)

The annexed section A.5.1.10.8(3) referrences Teflon as a type of sealant tape. Teflon is a registered tradename owned by DuPont and DuPont does not make Teflon tape according to DuPont. The referencedsealant tape is P.F.T.E. as spelled in the above code.

Statement of Problem and Substantiation for Public Comment

A registered trade name is being used incorrectly.

Submitter Information Verification

Submitter Full Name: Anthony LoweOrganization: Allied Hospital SystemsSubmittal Date: Fri May 03 12:19:56 EDT 2013

Copyright Assignment

I, Anthony Lowe, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright inthis Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend thatI acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similaror derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter intothis copyright assignment.

By checking this box I affirm that I am Anthony Lowe, and I agree to be legally bound by the above Copyright Assignment and the termsand conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will, upon mysubmission of this form, have the same legal force and effect as a handwritten signature

*

They shall be made up with polytetrafluroethylene tape or other thread sealantrecommended for oxygen service, with sealant applied to the male threads only and caretaken to ensure sealant does not enter the pipe.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

20 of 97 5/10/2013 9:14 AM

Public Comment No. 80-NFPA 99-2013 [ Section No. 5.1.12.3.14.3(H) ]

(H) A demand of approximately 25 percent of the rated compressor capacity shall be created tocause the compressors to cycle on and off continuously and the dryers to operate for the24 12 -hour period.

Statement of Problem and Substantiation for Public Comment

Replace 24 hours with 12 hours to match paragraph (E) which was changed in 2012.

Submitter Information Verification

Submitter Full Name: CORKY BISHOPOrganization: AIRGAS MEDICAL SERVICESSubmittal Date: Fri May 03 15:03:13 EDT 2013

Copyright Assignment

I, CORKY BISHOP, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright inthis Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend thatI acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similaror derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter intothis copyright assignment.

By checking this box I affirm that I am CORKY BISHOP, and I agree to be legally bound by the above Copyright Assignment and theterms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will,upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

21 of 97 5/10/2013 9:14 AM

Public Comment No. 32-NFPA 99-2013 [ Sections 5.3.6.1.1, 5.3.6.1.2 ]

Sections 5.3.6.1.1, 5.3.6.1.25.3.6.1.1

Installers of Category 3 medical gas sources (i.e., oxygen and nitrous oxide) where the total of allgases in cylinders or containers, except nitrogen, connected and in storage at one time does not

exceed 85 m 3 (3000 ft 3 ) at standard temperature and pressure (STP), or 142 m 3 (5000 ft 3 )(STP) if oxygen is stored in a DOT Specification 4L (cryogenic liquid) container shall be certified inaccordance with ASSE 6010, Professional Qualification Standard for Medical Gas SystemsInstallers.

5.3.6.1.2 Installers of Category 3 medical gas sources (i.e., oxygen and nitrous oxide) where the total of allgases exceeds the limits specified in 5.3.6.1.1 , shall be qualified in accordance with CGA M-1,Guide for Medical Gas Installations at Consumer Sites.

Statement of Problem and Substantiation for Public Comment

Delete both paragraphs. Category 3 systems are limited in size by definition in section 5.3.6.20.1.

Related Items from the Public Input Stage for This Document

Related ItemCommittee Input No. 298-NFPA 99-2012 [Section No. 5.3]

Submitter Information Verification

Submitter Full Name: CORKY BISHOPOrganization: AIRGAS MEDICAL SERVICESSubmittal Date: Fri Apr 26 17:33:50 EDT 2013

Copyright Assignment

I, CORKY BISHOP, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright inthis Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend thatI acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similaror derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter intothis copyright assignment.

By checking this box I affirm that I am CORKY BISHOP, and I agree to be legally bound by the above Copyright Assignment and theterms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will,upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

22 of 97 5/10/2013 9:14 AM

Public Comment No. 33-NFPA 99-2013 [ New Section after 5.3.6.20.12 ]

TITLE OF NEW CONTENT5.3.6.20.13 Cylinders in service and in storage shall be individually secured and located to prevent fallingor being knocked over.

Statement of Problem and Substantiation for Public Comment

Securement of cylinders is not addressed in the 2012 edition for category 3. Individual securement is needed since each cylinder has a regulator attached. This prevents knocking over the adjacent cylinder while attaching the regulator. This wording is the same as 5.3.3.3 in the 2005 edition.

Related Items from the Public Input Stage for This Document

Related ItemCommittee Input No. 298-NFPA 99-2012 [Section No. 5.3]

Submitter Information Verification

Submitter Full Name: CORKY BISHOPOrganization: AIRGAS MEDICAL SERVICESSubmittal Date: Fri Apr 26 17:48:50 EDT 2013

Copyright Assignment

I, CORKY BISHOP, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright inthis Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend thatI acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similaror derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter intothis copyright assignment.

By checking this box I affirm that I am CORKY BISHOP, and I agree to be legally bound by the above Copyright Assignment and theterms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will,upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

23 of 97 5/10/2013 9:14 AM

Public Comment No. 34-NFPA 99-2013 [ Section No. 5.3.6.21.10 ]

5.3.6.21.10 Medical gas source equipment that serves one or two treatment facilities shall include twobanks of one or more cylinders of oxygen and (if used) two banks of one or more cylindersof nitrous oxygen oxide , each bank containing at least an average day's supply.

Statement of Problem and Substantiation for Public Comment

Corrected typo.

Submitter Information Verification

Submitter Full Name: CORKY BISHOPOrganization: AIRGAS MEDICAL SERVICESSubmittal Date: Fri Apr 26 17:57:19 EDT 2013

Copyright Assignment

I, CORKY BISHOP, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright inthis Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend thatI acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similaror derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter intothis copyright assignment.

By checking this box I affirm that I am CORKY BISHOP, and I agree to be legally bound by the above Copyright Assignment and theterms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will,upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

24 of 97 5/10/2013 9:14 AM

Public Comment No. 31-NFPA 99-2013 [ Section No. 5.3.7.6.1 ]

5.3.7.6.1 General.Category 3 compressed air compressor supply systems shall include the following:

(1) Disconnect switch(es)

(2) Motor-starting device(s)

(3) Motor overload protection device(s)

(4) One or more compressors

(5) For single, duplex, or multiple compressor systems, means for activation/de-activation of eachindividual compressor

(6) When multiple compressors are used, manual or automatic means to alternate individualcompressors

(7) When multiple compressors are used, manual or automatic means to activate the additionalunit(s) should the in-service unit(s) be incapable of maintaining adequate pressure

(8) Intake filter–muffler(s) of the dry type

(9) Receiver(s) with a manual or automatic drain

(10) Shutoff valves

(11) Compressor discharge check valve(s) (for multiple compressors)

(12) Air dryer(s) that maintains a minimum of 40 percent relative humidity at operating pressure andtemperature

(13) In-line final particulate/coalescing filters rated at 0.01 micron 5 microns , with filter statusindicator to ensure the delivery of compressed air with a maximum allowable 0.05 ppm liquidoil

(14) Pressure regulator(s)

(15) Pressure relief valve

(16) Pressure indicator

(17) Moisture indicator

Additional Proposed Changes

File Name Description Approved5_micron_filter.jpg Air Techniques literature

Statement of Problem and Substantiation for Public Comment

Change the dental air filtration back to the 2005 requirement as that is what is typically provided in the dental industry.

The 2012 requirement was 500 times finer filtration but still had a moisture content of 40% relative humidity which is equal to a pressure dewpoint of 89 degrees F @ 50 psig.

Related Items from the Public Input Stage for This Document

Related ItemCommittee Input No. 298-NFPA 99-2012 [Section No. 5.3]

Submitter Information Verification

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

25 of 97 5/10/2013 9:14 AM

Submitter Full Name: CORKY BISHOPOrganization: AIRGAS MEDICAL SERVICESSubmittal Date: Fri Apr 26 17:08:40 EDT 2013

Copyright Assignment

I, CORKY BISHOP, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright inthis Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend thatI acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similaror derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter intothis copyright assignment.

By checking this box I affirm that I am CORKY BISHOP, and I agree to be legally bound by the above Copyright Assignment and theterms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will,upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

26 of 97 5/10/2013 9:14 AM

Public Comment No. 36-NFPA 99-2013 [ New Section after 5.3.8.3.7.4 ]

5.3.8.3.8 Special Requirements for Category 3 Vacuum Piping.5.3.8.3.8.1 Horizontal piping in Category 3 vacuum systems shall be sloped a minimum of 7 mm per 3.05m (1/4 in. per 10 ft) toward the vacuum source equipment.5.3.8.3.8.2 Horizontal piping shall include no sags or low points that will permit fluids or debris toaccumulate.

Statement of Problem and Substantiation for Public Comment

This is a wet vacuum system. Sloped piping toward the pump will help to avoid clogs and debris left in the piping. This section should be reinserted before the valve paragraph.

Related Items from the Public Input Stage for This Document

Related ItemCommittee Input No. 298-NFPA 99-2012 [Section No. 5.3]

Submitter Information Verification

Submitter Full Name: CORKY BISHOPOrganization: AIRGAS MEDICAL SERVICESSubmittal Date: Fri Apr 26 18:09:34 EDT 2013

Copyright Assignment

I, CORKY BISHOP, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright inthis Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend thatI acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similaror derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter intothis copyright assignment.

By checking this box I affirm that I am CORKY BISHOP, and I agree to be legally bound by the above Copyright Assignment and theterms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will,upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

27 of 97 5/10/2013 9:14 AM

Public Comment No. 84-NFPA 99-2013 [ Section No. 5.3.9.2.4.4 ]

5.3.9.2.4.4 The test vacuum shall be maintained until each joint has been examined for leakage bymeans of a leak detectant that is safe for use with oxygen and does not contain ammonia . Anultrasonic leak detector may be used .

Statement of Problem and Substantiation for Public Comment

A soap solution will not help much when looking for vacuum leaks. An ultrasonic leak detector is one suggested solution. Maybe it should be mentioned in the annex.

Related Items from the Public Input Stage for This Document

Related ItemCommittee Input No. 298-NFPA 99-2012 [Section No. 5.3]

Submitter Information Verification

Submitter Full Name: CORKY BISHOPOrganization: AIRGAS MEDICAL SERVICESSubmittal Date: Fri May 03 15:25:19 EDT 2013

Copyright Assignment

I, CORKY BISHOP, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright inthis Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend thatI acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similaror derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter intothis copyright assignment.

By checking this box I affirm that I am CORKY BISHOP, and I agree to be legally bound by the above Copyright Assignment and theterms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will,upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

28 of 97 5/10/2013 9:14 AM

Public Comment No. 23-NFPA 99-2013 [ New Section after A.5.1.4 ]

A-5.1.4.3In order to evaluate the size and appropriateness of valves under part (1), a formula is available to convertfrom Cv (a commonly published value) to a flow rate or a pressure drop.

5.4X10^-7 * SpGr * T * Q^2 SpGr = Specific Gravity referenced to Air (1)?P = ––––––––––––––––––––– T = Temperature °Rankine Cv^2 * Pout Q = flow in SCFH Pout = Pressure absolute

Statement of Problem and Substantiation for Public Comment

Please see comment on 5.1.4.3

Submitter Information Verification

Submitter Full Name: Mark AllenOrganization: Beacon MedaesSubmittal Date: Tue Apr 09 15:15:02 EDT 2013

Copyright Assignment

I, Mark Allen, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in thisPublic Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that Iacquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similar orderivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter intothis copyright assignment.

By checking this box I affirm that I am Mark Allen, and I agree to be legally bound by the above Copyright Assignment and the termsand conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will, upon mysubmission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

89 of 97 5/10/2013 9:14 AM

Correlating Notes

Correlating Committee Note No. 20-NFPA 99-2012 [ Section No. 1.3.2 [Excluding any

Sub-Sections] ]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Tue Dec 11 15:02:23 EST 2012

Committee Statement and Meeting Notes

CommitteeStatement:

The Correlating Committee on Health Care Facilities directs each technical committee toevaluate their applicability clause to clarify what sections apply to existing facilities withoutcreating a circular argument to Section 1.3.

Ballot Results

This item has passed ballot

18 Eligible Voters1 Not Returned

17 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not Returned, Jensen, Michael S.

Affirmative All,,,,,,,,,,,,,,,,,

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 28 5/2/2013 5:03 PM

Correlating Committee Note No. 12-NFPA 99-2012 [ Section No. 2.3.9 ]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Tue Dec 11 11:55:54 EST 2012

Committee Statement and Meeting Notes

CommitteeStatement:

The Correlating Committee on Health Care Facilities directs the technical committees onFundamentals, Medical Equipment, and Piping Systems, to review requirements includingreferences to CGA documents and specifically list the requirements that apply. Non-mandatoryrequirements cannot be referenced in the body of the code.

Ballot Results

This item has passed ballot

18 Eligible Voters1 Not Returned

17 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not Returned, Jensen, Michael S.

Affirmative All,,,,,,,,,,,,,,,,,

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 28 5/2/2013 5:03 PM

Correlating Committee Note No. 1-NFPA 99-2012 [ Section No. 3.3.9 ]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Tue Dec 11 08:39:04 EST 2012

Committee Statement and Meeting Notes

CommitteeStatement:

The Correlating Committee on Health Care Facilities directs that each technical committeeevaluate where the term "anesthetizing location" is used within their Chapter(s) and remove theterm and replace it with whichever levels as defined in 3.3.63 are applicable.

Ballot Results

This item has passed ballot

18 Eligible Voters1 Not Returned

17 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not Returned, Jensen, Michael S.

Affirmative All,,,,,,,,,,,,,,,,,

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 28 5/2/2013 5:03 PM

Correlating Committee Note No. 3-NFPA 99-2012 [ Section No. 3.3.135.7 ]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Tue Dec 11 08:56:01 EST 2012

Committee Statement and Meeting Notes

CommitteeStatement:

The Correlating Committee on Health Care Facilities directs the technical committees on PipingSystems,Medical Equipment, and Hyperbaric and Hypobaric Facilities to re-assess where the term"working pressure" is used and determine where it is still applicable rather than the new definitionfor "operating pressure." Understand that the 200 lb limit has removed from working pressure.

Ballot Results

This item has passed ballot

18 Eligible Voters1 Not Returned

17 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not Returned, Jensen, Michael S.

Affirmative All,,,,,,,,,,,,,,,,,

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 28 5/2/2013 5:03 PM

Correlating Committee Note No. 4-NFPA 99-2012 [ Section No. 3.3.155 ]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Tue Dec 11 09:04:27 EST 2012

Committee Statement and Meeting Notes

CommitteeStatement:

The Correlating Committee on Health Care Facilities directs each of the technical committees toassess text, both in the Chapters and in definitions, where "room," "space," or "vicinity," are usedand determine the applicability based on the definitions of each. See FR 92.

Ballot Results

This item has passed ballot

18 Eligible Voters1 Not Returned

17 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not Returned, Jensen, Michael S.

Affirmative All,,,,,,,,,,,,,,,,,

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 28 5/2/2013 5:03 PM

Correlating Committee Note No. 5-NFPA 99-2012 [ Section No. 5.1.1.1 ]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Tue Dec 11 11:03:59 EST 2012

Committee Statement and Meeting Notes

CommitteeStatement:

In regards to CI 297, if the technical committee intends to go with such an approach, then theCorrelating Committee on Health Care Facilities suggests simply adding this as a code sectionrather than a table. For example in 5.3, say if either A, B, or C, is being provided, then therequirements of Section 5.2 shall be applied.

Ballot Results

This item has passed ballot

18 Eligible Voters1 Not Returned

17 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not Returned, Jensen, Michael S.

Affirmative All,,,,,,,,,,,,,,,,,

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 28 5/2/2013 5:03 PM

Correlating Committee Note No. 13-NFPA 99-2012 [ Section No. 5.1.1.3 ]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Tue Dec 11 13:43:31 EST 2012

Committee Statement and Meeting Notes

CommitteeStatement:

The Correlating Committee on Health Care Facilities directs the technical committee on PipingSystems to review FR 251, 252, and 253, to ensure that the language is clearly meant to apply toboth new and existing facilities.

Ballot Results

This item has passed ballot

18 Eligible Voters1 Not Returned

17 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not Returned, Jensen, Michael S.

Affirmative All,,,,,,,,,,,,,,,,,

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 28 5/2/2013 5:03 PM

Correlating Committee Note No. 26-NFPA 99-2012 [ Section No. 5.1.3.3.3 ]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Tue Dec 11 15:32:01 EST 2012

Committee Statement and Meeting Notes

CommitteeStatement:

The Correlating Committee on Health Care Facilities directs the technical committee on PipingSystems to address the issue of ventilation for gas storage. If needed, a reference to Chapter 9for those requirements should be made.

Ballot Results

This item has passed ballot

18 Eligible Voters1 Not Returned

17 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not Returned, Jensen, Michael S.

Affirmative All,,,,,,,,,,,,,,,,,

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 28 5/2/2013 5:03 PM

Correlating Committee Note No. 22-NFPA 99-2012 [ Section No. 5.1.3.6.3.6 ]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Submittal Date: Tue Dec 11 15:13:48 EST 2012

Committee Statement and Meeting Notes

CommitteeStatement:

The Correlating Committee on Health Care Facilities directs the technical committee on PipingSystems to review FR-259 for parallel construction of the listed requirements

Ballot Results

This item has passed ballot

18 Eligible Voters1 Not Returned

17 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not Returned, Jensen, Michael S.

Affirmative All,,,,,,,,,,,,,,,,,

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 28 5/2/2013 5:03 PM

Correlating Committee Note No. 31-NFPA 99-2012 [ Section No. A.5.1.14.2.3 ]

Submitter Information Verification

Submitter Full Name: Jonathan HartOrganization: National Fire Protection AssocSubmittal Date: Wed Dec 19 10:49:10 EST 2012

Committee Statement and Meeting Notes

CommitteeStatement:

The Correlating Committee on Health Care Facilities directs the technical committee on PipingSystems to evaluate the new annex material and to incorporate the language that had previouslybeen annex material to that section when it was located in the body of the code.

Ballot Results

This item has passed ballot

18 Eligible Voters1 Not Returned

17 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not Returned, Jensen, Michael S.

Affirmative All,,,,,,,,,,,,,,,,,

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

26 of 28 5/2/2013 5:03 PM