Technical 1554 cables specifications

56
TECHNICAL SPECIFICATIONS PAGODA CABLES PVT. LTD. 1/58, STREET NO: 3, VISHWAS NAGAR, SHAHDARA, DELHI 110 032. (INDIA) TEL/FAX : 91-11-22392801, 22385391. Email : pagoda @del2.vsnl.net.in

description

detailed specification for cables data

Transcript of Technical 1554 cables specifications

Page 1: Technical 1554 cables specifications

TECHNICAL SPECIFICATIONS

PAGODA CABLES PVT. LTD.1/58, STREET NO: 3, VISHWAS NAGAR,

SHAHDARA, DELHI 110 032. (INDIA)TEL/FAX : 91-11-22392801, 22385391.

Email : pagoda @del2.vsnl.net.in

Page 2: Technical 1554 cables specifications

CONTENTS:

1. ABOUT PAGODA

2. PRODUCT RANGE

3. SELECTION OF CABLES

4. QUALITY ASSURANCE PLAN

5. DESIGN & CONSTRUCTION

6. FRLS SHEATHED CABLES.

7. TABLES ON TECHNICAL DATA:

TABLE 1 CONDUCTOR RESISTANCE

TABLE 2 REACTANCE.

TABLE 3 CAPACITANCE

TABLE 4 1.5 SQ.MM. UPTO 61 CORES, ARMOURED/UNARMOURED CONTROL CABLES.

TABLE 5 2.5 SQ.MM. UPTO 61 CORES, ARMOURED/UNARMOURED CONTROL CABLES.

TABLE 6 SINGLE CORE COPPER CONDUCTOR UNARMOURED CABLES.

TABLE 7 TWO CORE COPPER CONDUCTOR UNARMOURED CABLES.

TABLE 8 THREE CORE COPPER CONDUCTOR UNARMOURED CABLES.

TABLE 9 THREE & HALF CORE COPPER CONDUCTOR UNARMOURED CABLES.

TABLE 10 FOUR CORE COPPER CONDUCTOR UNARMOURED CABLES.

TABLE 11 TWO CORE COPPER CONDUCTOR ARMOURED CABLES.

TABLE 12 THREE CORE COPPER CONDUCTOR ARMOURED CABLES.

TABLE 13 THREE & HALF CORE COPPER CONDUCTOR ARMOURED CABLES.

TABLE 14 FOUR CORE COPPER CONDUCTOR ARMOURED CABLES.

TABLE 15 SINGLE CORE ALUMINIUM CONDUCTOR UNARMOURED CABLES.

TABLE 16 TWO CORE ALUMINIUM CONDUCTOR UNARMOURED CABLES.

TABLE 17 THREE CORE ALUMINIUM CONDUCTOR UNARMOURED CABLES.

TABLE 18 THREE & HALF CORE ALUMINIUM CONDUCTOR UNARMOURED CABLES.

TABLE 19 FOUR CORE ALUMINIUM CONDUCTOR UNARMOURED CABLES.

TABLE 20 TWO CORE ALUMINIUM CONDUCTOR ARMOURED CABLES.

TABLE 21 THREE CORE ALUMINIUM CONDUCTOR ARMOURED CABLES.

TABLE 22 THREE & HALF CORE ALUMINIUM CONDUCTOR ARMOURED CABLES.

TABLE 23 FOUR CORE ALUMINIUM CONDUCTOR ARMOURED CABLES.

8. RATING FACTORS.

9. OVERLOAD & SHORT CIRCUIT CAPACITY

10. FORMULA FOR CALCULATING VOLTAGE DROP.

11. RECOMMENDATION FOR INSTALLATION.

12. RECOMMENDED "PAGODA" CABLE FOR MO TORS.

13. CURRENT FOR AC MOTORS.

14. CONVERSION TABLE.

15. GLOSSARY OF TERMS

1.

Page 3: Technical 1554 cables specifications

ABOUT PAGODA.

Pagoda Cables Pvt. Ltd. is one of the renowned manufacturers of cables in

the Cable Industry in India. Our range encompasses a large variety of wires &

cables including Flexible Cables, Control & Power Cables (Unarmoured &

Armoured), Telephone Cables (Unarmoured & Armoured), Submersible

Cables, Data Flow Cables, Instrumentation Cables, Coaxial Cables,

Compensating cables and FRLS cables.

Our Quality Assurance department performs regular checks on quality of

cables online & offline to deliver high quality of cables. Pagoda Cables has

established a favorable image in the eyes of people for reliability and

commitment.

2.

Page 4: Technical 1554 cables specifications

OUR PRODUCT RANGE

SELECTION OF CABLE

*Single Core Unarmoured/Armoured Cables upto 630 Sq.mm conforming to IS:1554 [Pt-I]:88.

*Two Core, Three Core, Three & Half Core and Four Core Unarmoured/Armoured Power Cables

upto 400 Sq.mm. conforming toIS:1554[Pt-I]:88.

*Multicore Unarmoured/Armoured Control Cables upto 61 cores in 1.5

conforming to IS: 1554 [PT-I] : 88.

* FRLS PVC / FRHF Compound Sheathed Unarmoured/Armoured Cables

The following points should be taken into consideration before selecting any

[1] The System of Power & Voltage Source where the cable are being used.

[2] Conditions of Installation at site.

[3] Current Carrying Capacity of the cable.

[4] Voltage Drop of the cable.

[5] Short Circuit Capacity of the cable.

Sq.mm. & 2.5 Sq.mm.

particular size and

type of cable.

3.

Page 5: Technical 1554 cables specifications

QUALITY ASSURANCE PLAN.

We have a vigorous Quality Manual Plan comprising testing of incoming material , in line checks

during production and final testing. The quality manual program is regularly reviewed to upgrade it.

Our laboratory is equipped with all the instruments to ensure that the various tests required under different

specification are conducted before cables are cleared for despatch. Each consignment of cables

is despatched to the customer with test report results of tests conducted in our laboratory. The details of

tests conducted on raw material, in process and on final stage are given below:-

Raw materials are procured from approved vendors. Testing on raw material starts from vendor's end. The

raw material are received along with the vendor's test report. The following tests conducted to test the raw

material/verify the vendor's test report.

TEST ON RAW MATERIALS

1.Conductor:-

2. P.V.C. Compound.

Tests are conducted on conductor as per IS:8130:1984. Apart from these tests, if customers requires any other

additional test. Those tests are also conducted.

i) Conductor Resistance : 100% with the help of Kelvin Double Bridge for wire up to

0.4mm. diameter. Finer wires by sampling of 10% on lot basis.

ii) Conductor Elongation : 100% on Tensile Testing machine for wires upto 0.4mm Diameter.

Finer wires by sampling of 10% on lot basis.

iii) Solder Bath/Persulphate : 100% for wires up to 0.4mm. Diameter Finer wires by sampling of

For Tinned conductors only) 10% on lot basis

iv) Wrapping Test : 100% Wrapping is done manually.

(For Aluminium Conductor Only)

v) Tensile Strength : 100% on Tensile Testing Machine.

(For Aluminium Conductor Only)

Tests are conducted on PVC Compound are as per IS:5831:1984. Apart from these tests, if customers requires any

other additional tests. Those tests are also conducted.

Sample of every consignment is first run on trial basis and following tests are conducted: -

( .

4.

Page 6: Technical 1554 cables specifications

i) Insulation Resistance : With Mega Ohms Meter.

ii) Elongation : With Tensile Testing Machine.

iii) Tensile Strength : With Tensile Testing Machine.

iv) Spark Testing : With on line Spark Testers.

v) High Voltage Test : With High Voltage Tester.

vi) Thermal Stability Test : With Oven & PH Paper.

vii) Oxygen & Temperature Index : With Oxygen Test Appartus Specification - ASTM -D 2863.

[For FRLS PVC / FRHF Compound]

viii) Smoke Density Test : With Smoke Density Test Appartus Specification -ASTM - D

ix) HCL Gas Generation Test : With HCL Gas Emission Test Appartus Specification IEC-754-1.

[For FRLS PVC Compound]

i) Bleeding & Blooming : With Bleeding & Blooming tape and HST Oven.

ii) Ageing : With Ageing Oven.

iii) Hot Deformation : With Hot Deformation Apparatus.

iv) Loss of Mass : With Electronic Balance & Additional Ageing Oven with

Air Flow.

We procure ISI marked G.I. wire & Strips conforming to IS:3975. However, the following Tests are conducted

TYPE TESTS :-

3. STEEL STRIP/WIRE:-

2843

[For FRLS PVC / FRHF Compound].

/ FRHF

5.

Page 7: Technical 1554 cables specifications

i) Dimension : 100% with Micrometer and Vernier Callipers.

ii) Tensile Strength : 100% with Tensile Testing Machine.

iii) Dip Test : with Dip Tester.

IN PROCESS TESTING

PROCESS TESTSa) CONDUCTOR STRANDING 1. Dimension of Conductor.

2. Lay Length & Direction of Lay.

3. Surface and Shape of Conductor

4. D.C. Resistance.

b) INSULATION 1. Dimension of Core.

[PVC EXTRUSION] 2. Insulation Thickness.

3. Eccentricity of Insulation Wall.

4. Spark Test.

c) LAYING OF CORES. 1. Sequence of Cores.

2. Lay Length & Direction of Lay.

3. Laid Up Diameter.

4. Circularity of Cable.

5. High Voltage Test.

6. Conductor Resistance Test.

d) INNER SHEATH 1. Surface.

[PVC EXTRUSION] 2. Concentricity.

3. Thickness.

4. Diameter Over Inner Sheath.

5. High Voltage Test.

6. Conductor Resistance Test.

e) ARMOURING 1. Number & Size of Wire/Strip.

2. Lay Length & Direction of Lay.

3. Dia. Over Armouring.

4. Uniformity & Circularity of Cable.

5. High Voltage Test.

6. Conductor Resistance Test.

f) OUTER SHEATH 1. Surface.

[PVC EXTRUSION] 2. Concentricity.

3. Thickness.

4. Overall Diameter.

5 Embossing with requisite Information on outer sheath.

6.

Page 8: Technical 1554 cables specifications

All the cables drums leaving "Pagoda" works undergo the following tests at final stage of manufacturer:

i) Conductor Resistance Test

ii) High Voltage Test.

iii) Armour Resistance Test (For Mining Cable)

i) Conductor Resistance Test

ii) Annealing Test [For Copper]

iii) Tensile strength Test [For Aluminium]

iv) Wrapping Test [For Aluminium]

v) Thickness of Insulation, Inner sheath & Outer Sheath.

vi) Tensile Strength & Elongation Test of Insulation & Outer Sheath.

vii) Insulation Resistance Test.

viii) High Voltage Test at Room Temperature Test.

ix) Oxygen & Temperature Index test [For FRLS PVC / FRHF Compound Insulation & Sheath.]

x) Smoke Density Test[For FRLS PVC

xi) HCL Gas Generation Test[For FRLS PVC

i) Conductor Resistance Test

ii) Annealing Test [For Copper]

iii) Tensile strength Test [For Aluminium]

iv) Wrapping Test [For Aluminium]

v) Thickness of Insulation, Inner sheath & Outer Sheath.

vi) Tensile Strength & Elongation Test of Insulation & Outer Sheath.

vii) Ageing in air Oven of Insulation & Outer Sheath.

viii) Shrinkage Test of Insulation & Outer Sheath.

ix) Thermal Stability Test of Insulation & Outer Sheath.

x) Hot Deformation Test of Insulation & Outer Sheath.

xi) Heat shock Test of Insulation & Outer Sheath.

xii) Loss of Mass Test of Insulation & Outer Sheath.

xiii) Oxygen & Temperature Index [For FRLS PVC

xiv) Smoke Density Test[For FRLS PVC

xv) HCL Gas Generation Test[For FRLS PVC

xvi) Test for Armouring Wires/strips.

xvii) Insulation Resistance Test.

xviii) High Voltage Test [Water Immersion & at Room temperature]

xix) Flammability Test.

i) Cold Bend Test.

ii) Cold Impact Test.

Iii) Armour Resistance Test [for other than Mining Cable]

ROUTINE TESTS

ACCEPTANCE TESTS

TYPE TESTS

OPTIONAL TESTS

/ FRHF Compound Insulation & Sheath.]

/ FRHF Compound Insulation & Sheath.]

/ FRHF Compound Insulation & Sheath.]

/ FRHF Compound Insulation & Sheath.]

/ FRHF Compound Insulation & Sheath.]

7.

Page 9: Technical 1554 cables specifications

Cable Design & Construction

IS:1554(Pt-I) : 88

Conductor:

Insulation:

Armoured and Unarmoured Single Core, Twin Core, Three Core and Multicore Copper orAluminium conductor PVC Insulated & Sheathed cables for Electric supply and control purposesfor use on AC voltage upto & including 1100 V or DC upto & including 1500 V to earth.

The most acceptable metals for conductors are Copper or Aluminium due to their high conductivityand ductility. Therefore, Conductor material normally employed in PVC Cables are O, H2, or H4 ECgrade Aluminium or high conductivity annealed copper or annealed tinned copper conforming inall respect to IS: 8130:84.

As Copper gets higher affinity with Sulphur, it corrodes in the atmostphere where Sulphur fumes arepresent. In these conditions, tinned copper shall be used. Power Cables are mostly manufacturedwith Aluminium .Use of Copper has been restricted to Control Cables, Signalling Cables andMining Cables as per Govt. Directives.

The most economic construction for conductor is solid conductor. As area of conductor increases,solid conductor becomes more stiff and hence difficult to handle. In this connection StrandedConstruction is adopted i.e.made of number of strands, arranged in spiral layers in1+6+12+18+24......formations.

Shaping of conductor is necessary in making Multicore Cables sizes above 10.0 Sq.mm. Inaluminium & 6.0 mm in copper conductor to obtain compact and economic design. Here,Stranded Conductors are shaped into a segment of a circle so that when all cores are laid , theyform a complete circle.

The PVC covering over conductor is called "INSULATION". It is a specially formulated best quality,high grade of Poly Vinyl Chloride conforming to IS 5831:84 and is applied by Extrusion processonly. It is resistant to moisure, oils, alkalies, good dielectric and having high Insulation Resistancevalues, Fire Retarding, Permanent Colours .

S.No. Properties Values

1. Specific Gravity 1.3 - 1.45

2. Tensile Strength(N/mm ) 16.0to18.5

Properties of General Purpose PVC Compound:

2

8.

Page 10: Technical 1554 cables specifications

3. CompressionStrength 0.75-1.254. Elongation % 220-3005. HardnessRockwell(ShoreA) 50-100

6. ThermalConductivity10 3-4

Cal/Sec/Sq.Cm./1( C/Cm.)

7. SpecificHeat,Cal/ C/gm. 0.3-0.5

8. ThermalResistitvity, C.Cm./W 600-6509. DielectricConstant,50-60Cycle 5-610. DielectricStrengthKV/mm. 20-40

11. VolumeResistivity10 Ohm-Cm. 10-100012. DissipationFactor,50-60Cycle 0.10-0.15

___________________________________________________________________________

PVCCompoundismadeofPVCresin,blendedwithPlastisizers,Stablizers, fillers,Lubricants,Antioxidantandcertain special purpose additives to improve processability Electrical, Mechanical, Thermal andChemical Propertiesandalsootherspecial requirements.

We also provide Heat Resistance (H.R.) PVC Compound Flame Retardent low smoke (FRLS) PVCCompound & Flame Retardent Halogen Free (FRHF) Compund insulation on special requirement.

TheInsulatedcoresareidentifiedwithacolourscheme as per IS:1554[Pt-I]-1988as follows:

NoOfCores CoreColour

1 Red,Black,Yellow Blue or natural (non-pigmented)2 Red&Black3 Red,Yellow&Blue.4 Red,Yellow,Blue&Black.5 Red,Yellow,Blue,Black&Grey.

In case of cable exceeding five cores, two adjacent [Counting and direction core] in each layer shall becolored Blue, Yellow and remaining cores grey or Cores can also be identified by numbers printed onthat of same colour.

Incaseoffourcorescableswithreducedneutralconductor[Usually termedas3 CoreCable] threemain

coresarecolouredRed,YellowandBlueandthereducedneutralcoreshallbeblack.

4

0

0

0

12

IdentificationofCores:

½

LayingupofCores:

Thecoresarelaidupwithasuitablelay.Thefinal layerhasalwaysarighthandlay.

9.

Page 11: Technical 1554 cables specifications

InnerSheath:

Armouring:

Outer Sheath :

Innersheath isprovidedover laidupofcores. It isprovidedtogiveCircularShapeof thecableanditprovidesbeddingfor the armouring.

IS:1554(Pt-I) - 88 permits following two methods of applying the Inner Sheath of thermoplastic material i.e.PVC,Polyethyleneetc., Whichisnotharder than insulation.

a) Here the innersheath is provided by extrusion of thermoplastic

overthelaidupofcores

(b) Here theinnersheathis provided by wrapping at hermoplastic tape.

Armouringmaterial isconformingtoIS:3975. In order to protect thecable against MechanicalDamages,armouring of steel wire/strip is provided. It provides mechanical protection to inside of cores and it carries earthReturnCurrent incaseofshortcircuitofacorewitharmour.Asper IS:1554(Pt-I) -88, RoundWirearmouringisprovidedincablewherecalculateddiameterunderarmourisupto13mm.Abovethisthearmouriseithersteelwireorsteelstripof size 4.00X0.80 mm. As strip construction is economical, the manufacture always provides steel strip armouringunlesswirearmouringisspecified.

In long runofcableand incaseofMines, the roundwirearmour ismustas stripconstructionprovides,higherresistance to Earthfault Current and some times this current may not be sufficient to operate the circuit breaker incaseofearthfault.

In case of cables for use in mines, theresistanceofarmour shall not exceed that of the conductor of mainby more than 33 percent for safety reasons. To achieve this, sometimes tinned hard drawn copper is used alongwith the galvanised steel Wires/Strips.Sometimes two layers of steel wires are provided to give extra protection.

In case of Single core armoured cables used in A.C. System, the material has to be non magnetic forarmouring as in this case of return current is not passing through the same cable. Hence it will not cancel themagneticlines producedbycurrent.Thesemagneticlines whichareoscillatingincaseofA.C.systemswillgiverisetoeddy currents in magnetic armouring and hence armouring will become hot, and this may lead to failure of thecable. Generally hard drawn aluminium wires/ strips are used for armouring in this case . In D.C. System, Steelwires/strips armouringisused.

In order to protect the cable frommoisureandotherchemicalerosions,a finalcoveringofPVCcompoundisappliedoverarmouring incaseofarmouredcableandover inner sheath incaseofunarmouredcable called as"Outer Sheath". Sometimes this outer sheath is required to be special compound to resist from termites, acids,fungis,rodentetc.,weprovidethesame.

IS:1554(Pt-I)-88specifiesnominalthickness and minimum thickness ofoutersheath for Unarmoured cablesand minimum thickness ofoutersheath for Armoured Cables.

It permits the following types of PVCcompound for sheathing.

[i] Outer Sheath with type ST1 PVC Compound as per IS:5831-84 which is suitable for 70 C continuousoperation.

[ii] Outer Sheath with type ST2 PVC Compound as per IS:5831-84 which is suitable for 85 C continuousoperation.

0

ExtrudedInnersheath :

TappedInnersheath :

0

10.

Page 12: Technical 1554 cables specifications

Instead of above two, we also provide flame Retardent Low Smoke (FRLS) PVC compound

sheathed cable on special requirement.

PVC Cables aredesigned as per the requirement of relevant IS specification. Following is thescheme ofnomenclature.A - Aluminium Conductor when first letter of typedesignation. When type designation does not

begin with A the cablehas copperconductor.Y - When at first or second place in typedesignation, it stands for PVCW - Round Steel Wire Armouring.

WW - Steel Double Round Wire Armouring.FF - Steel FlatDouble StripArmouring.

CodesforCableDesignation:

- Flat Steel StripArmouring.

PAGODAFLAMERETARDANTLOWSMOKECABLES

&Flame Retardent Halogen Free (FRHF) Compound

F

YWY means CopperConductor, PVC insulated, Round Wire Armoured and PVC SheathedCable.

AYFYmeansAluminiumConductor, PVCInsulated,SteelStripArmouredandPVCOuterSheathed.

TYPICAL EXAMPLES OF DESIGN & CONSTRUCTION

AS PER IS:1554

IS Specification

8130

5831

5831

3975

5831

Conductor :

Insulation :

Inner Sheath :

Armour :

Outer Sheath :

EC grade

Aluminium

PVC type

A or C

PVC type

ST1 nor ST2

Galvanised

Steel strip

PVC type

ST1 or St2

Conductor :

Insulation :

Inner Sheath :

Armour :

Outer Sheath :

High conductivity

Grade copper

PVC type

A or C

PVC type

ST1 nor ST2

Galvanised

Steel strip

PVC type

ST1 or ST2

Power CableSteel Strip, armoured

Control CableSteel Strip, armoured

CLASSIFICATION OF PVC COMPOUNDType Application Max.Conductor

A Insulation 70 C

C Insulation 85 C

ST1 Sheath 70 C

ST2 Sheath 85 C

0

0

0

0

11.

Page 13: Technical 1554 cables specifications

InmodernPower,Chemical,Fertilizers,CementsPlantsetc.andPublicPlacessuchas Hospitals,RailwayStation,HighRise

CommercialComplexes, Theatres,Airportsetc.manyPVCcablesarebunchedinacableshaftoronacabletrays. Incaseoffirein

thesecables, thefirebecomesselfsustaining.MoreverduetoburningofPVC,adensecorrosivesmokeisemittedwhichmakesfire

fighting very difficult, due to poor visibility and toxic nature of gas. HCL contents of the smoke, not only damages other costly

equipmentlyingnearby,butalsopenetratestheRCCandcorrodesthesteelreinforcement.Duetothis, thereisextensivedamage

totheproperty.Therefore,phenomenonoffirehasalwaysbeenamatterofseriousconcernandbehaviourofcableunderthefire.

The phenomenon of fire has always been a matter of serious concern and the performance of electric cables in fire

situation is becoming increasingly important, because every year innumberable persons die in fire and causing disasters to

human life and property. Investigations have proved that under fire situations PVC emits large quantities of smoke and corrosive

fumesmakingvirtually impossibleforfirefightingandrescueoperations.

FRLScablesincorporatesthefollowingfeatures:

1. No fire propogation.

2. Flame Retardancy.

3. LowAcidEmission-Normalcablessmokewhencombineswithairmoistureproduces largeamountofhighlycorrosive

acids imposing threat to life and property while FRLS cables produces less smoke reducing the threat to life and

property.

4. Lowsmokeemission.

To overcome these problems, "PAGODA" has also successfully developed, tested and manufactured new generation

FRLS[FlameRetardentLowSmoke]Cables.ThesecableswithspecialPVCformulationmaterialprevents thepropagationofflame

along the length when exposed to fire. In addition, these cables emit low smoke and halogen emission is also reduced under fire

conditions. These properties help immense fire fighting operation and prevention of further loss to costly equipment to which

cablesareconnected.

i) Increasedresistancetoignitionrelativeofhigheroxygenindexandtemperatureindex.

ii) Volumeofsmokeandcorrosivefumesisminimisedbecauseofspecialcompositionofprotectiveinsulationmaterial,having

lowestrateofdecompositionandthuspreventsdamagetoproperty.

iii) Duetoemissionof less smoke, lowacidemissionand lowtoxicgasemission,damagetopropertyand lossof life isminimised

makingfirefightingeasy.

SPECIFICATION TEST AIM TYPICALVALUES

FRLS CABLES

ASTM-D 2863 ygen To determine at room temp, the %

Index of oxygen needed to burn More than 29 %

the insulating material

ASTM-D 2863 Temperature To determine temp. At which 21%

&BICC Index Oxygen in the air will burn

Handbook the insulating material. More than 250 C

Chp. No. 6

ASTM-D 2843 Smoke To determine the visibility in case More than 40%

Density the Insulating Material ever

catches fire. (Transmission of Light)

IEC 754-1 Acid Gas To determine the amount of Less than 20%

Generation Hydro Chloric, Hydro-Flouric and

Halogen Acid Gases produced from

burning of Insulating Material.

0

FRLS PVC SHEATHEDCABLES

Advantagesof"PAGODAFRLS PVC SHEATHED CABLES" CABLES UnderFireConditions:

Ox

Index

12.

Page 14: Technical 1554 cables specifications

TABLE - 1

COMPOSITION & MAX RESISTANCE OF CONDUCTOR, CLASS I (SOLID)& CLASS 2 (STRANDED) FOR SINGLE CORE & MULTICORE CABLES.

AS PER IS - 8130/1984

Class 2 (Stranded)

Circular ConductorNon-Compacted

Sq. mm.

1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

185

240

300

400

500

630

Cu/AI

1

1

1

1

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

Cu

3

3

7

7

7

7

7

7

19

19

19

37

37

37

61

61

61

61

91

Cu

---

---

---

---

6

6

6

6

6

12

15

18

18

30

34

34

53

53

53

AI

---

---

---

6

6

6

6

6

12

15

18

18

30

34

34

53

53

53

---

Plain wires

12.1

7.41

4.61

3.08

1.83

1.15

0.727

0.524

0.387

0.268

0.193

0.153

0.124

0.0991

0.0754

0.0601

0.0470

0.0366

0.0283

Tinned wires

12.2

7.56

4.70

3.11

1.84

1.16

0.734

0.529

0.391

0.270

0.195

0.154

0.126

0.100

0.0762

0.0607

0.0475

0.0369

0.0286

18.1

12.1

7.41

4.61

3.08

1.91

1.20

0.868

0.641

0.443

0.320

0.253

0.206

0.164

0.125

0.100

0.0778

0.0605

0.0469

AI

3

3

7

7

7

7

7

7

19

19

19

37

37

37

61

61

61

61

91

Circular Compactedor shaped

Copper Conductor AluminiumConductor

MINIMUM NO. OF WIRES IN THE CONDUCTORMax. D.C. Resistance at 20 C

Ohms/Km.

0

13

Page 15: Technical 1554 cables specifications

APPROXIMATE REACTANCE AT 50 HZ. (Ohm/Km.) 1.1 KV PVC & HR PVC CABLES

REACTANCE

NOMINAL AREA

OF

CONDUCTOR

(SQ. MM.)

SINGLE CORE MULTI CORE

UNARMOURED

1.5

2.5

4.0

6.0

10.0

16.0

25.0

35.0

50.0

70.0

95.0

120.0

150.0

185.0

240.0

300.0

400.0

0.167

0.156

0.147

0.137

0.126

0.116

0.111

0.105

0.0984

0.0934

0.0914

0.0878

0.0866

0.0852

0.0834

0.0830

0.0815

----------

----------

0.163

0.152

0.139

0.130

0.122

0.116

0.108

0.105

0.100

0.0962

0.0945

0.0924

0.0908

0.0902

0.0879

0.109

0.105

0.101

0.0949

0.0890

0.0859

0.0842

0.0824

0.0794

0.0764

0.0761

0.0738

0.0738

0.0737

0.0732

0.0729

0.0725

ARMOURED

TABLE - 2

14

Page 16: Technical 1554 cables specifications

APPROXIMATE CAPACITANCE (MICRO FARADS/KM.) 1.1 KV PVC & HR PVC CABLES.

NOMINAL AREA

OF

CONDUCTOR

(SQ. MM.)

SINGLE CORE TWO CORETHREE & HALF

& FOUR COREUNARMOURED

1.5

2.5

4.0

6.0

10.0

16.0

25.0

35.0

50.0

70.0

95.0

120.0

150.0

185.0

240.0

300.0

400.0

0.43

0.52

0.57

0.67

0.83

0.97

1.00

1.15

1.26

1.32

1.36

1.49

1.52

1.53

1.54

1.60

1.70

----------

----------

----------

----------

----------

----------

0.83

0.95.

0.95

1.12

1.17

1.28

1.32

1.30

1.37

1.40

1.50

0.35

0.41

0.46

0.52

0.63

0.82

0.86

0.98

1.00

1.16

1.18

1.31

1.28

1.30

1.34

1.37

1.43

0.12

0.13

0.14

0.16

0.18

0.19

0.22

0.24

0.24

0.26

0.26

0.28

0.28

0.28

0.28

0.29

0.29

ARMOURED

TABLE - 3

CAPACITANCE

15

Page 17: Technical 1554 cables specifications

TYPE - 1.5 SQ.MM. MULTI CORE, VOLTAGE - 1100 VOLTS

CONSTRUCTION: COPPER CONDUCTOR, PVC INSULATION, PVC INNER

SHEATHED, ARMOURED/UNARMOURED & OVERALL PVC SHEATHED

CABLE CODE - YY/YWY/YFY

Nominal

Thickness

of

Insulation

mm

Min.

Thickness

of

Inner

Sheath

mm

ARMOUR Nominal

Sheath

Thickness

for

Unarm-

oured

mm

Minimum

Sheath

Thickness

for

Armoured

mm

Galvanised

Round

Steel

Wire

Nominal

Diameter

mm

Galvanised

Flat

Steel

Strip

Nominal

Thickness

mm

Approx. Over

All Diameter

Unarmoured

mm

Unarm

oured

Kg/Km

Armoured

mm

Armou

red

Kg/Km

Direct

in

ground

Amps.

In

Ducts

Amps.

Approx. Weight

of CablesMax.

DC

Conductor

Resistance

at

20 C

Ohm/Km

0

Current Ratings

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.4

0.4

1.4

1.4

1.4

1.4

1.4

1.4

1.4

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

1.8

1.8

1.8

1.8

1.8

1.8

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.2

1.24

1.24

1.24

1.24

1.24

1.24

1.40

1.40

1.40

1.40

1.40

1.40

1.40

1.40

1.56

10.4

10.9

11.7

12.6

13.4

13.4

16.5

17.0

17.7

19.0

19.9

23.0

24.2

26.0

32.7

12.0

12.7

13.3

14.2

15.0

15.0

18.2

17.3

18.3

19.1

20.0

23.0

24.3

26.6

33.0

170

195

225

275

325

345

460

520

580

680

780

950

1150

1350

2100

390

430

480

560

625

645

810

815

885

980

1100

1300

1540

1800

2670

12.1

12.1

12.1

12.1

12.1

12.1

12.1

12.1

12.1

12.1

12.1

12.1

12.1

12.1

12.1

23

21

21

21

15

14

13

12

11

11

10

9

9

8

7

Number

of

cores

No.

In

Air

Amps.

2

3

4

5

6

7

10

12

14

16

19

24

30

37

61

20

17

17

17

13

13

11

10

10

9

9

8

7

7

6

20

17

17

17

13

13

11

10

10

9

9

8

7

7

6

TABLE - 4

PART - I

IS: 1554

16

Page 18: Technical 1554 cables specifications

TABLE - 5

TYPE - 2.5 sq.mm. MULTI CORE, VOLTAGE - 1100 VOLTS

CONSTRUCTION: COPPER CONDUCTOR, PVC INSULATION, PVC INNER

SHEATHED, ARMOURED/UNARMOURED & OVERALL PVC SHEATHED

CABLE CODE - YY/YWY/YFY

Number

oif

cores

No.

Nominal

Thickness

of

Insulation

mm

Min.

Thickness

of

Inner

Sheath

mm

ARMOUR Nominal

Sheath

Thickness

for

Unarm-

oured

cables

mm

Minimum

sheath

Thickness

for

Armoured

mm

cables

Galvanised

Round

Steel

Wire

Nominal

Diameter

mm

Galvanised

Flat

Steel

Strip

Nominal

mm

thickness

Approx. Over

All Diameter

Unarm

oured

mm

Unarm

oured

Kg/Km

Armou

red

mm

Armou

red

Kg/Km

Direct

in

ground

Amps.

In

Ducts

Amps.

In

Air

Amps.

Approx. Weight

of CablesMax.

DC

Condu-

ctor

Resistance

at 20 C

Ohm/Km

Current Ratings

2

3

4

5

6

7

10

12

14

16

19

24

30

37

61

0.9

0.9

0.9

0.9

0.9

0.9

0.9

0.9

0.9

0.9

0.9

0.9

0.9

0.9

0.9

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.4

0.4

1.4

1.4

1.4

1.4

1.4

1.4

1.4

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

1.8

1.8

1.8

1.8

1.8

1.8

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.2

2.2

1.24

1.24

1.24

1.24

1.24

1.24

1.40

1.40

1.40

1.40

1.40

1.40

1.56

1.56

1.56

11.6

12.2

13.1

14.2

15.2

15.2

19.3

19.8

20.8

21.9

22.9

26.6

28.1

30.8

38.1

13.2

13.8

14.7

15.8

16.8

16.8

19.4

20.0

20.9

21.9

23.0

26.6

28.6

30.8

38.0

210

254

305

356

415

445

615

710

790

900

1025

1275

1520

1850

2910

460

515

590

665

740

755

940

1014

1130

1240

1380

1730

2000

2350

3600

7.41

7.41

7.41

7.41

7.41

7.41

7.41

7.41

7.41

7.41

7.41

7.41

7.41

7.41

7.41

32

27

27

27

20

20

18

17

16

15

14

13

12

11

9

27

24

24

24

18

17

15

14

13

13

12

11

10

10

8

27

24

24

24

18

17

15

14

13

13

12

11

10

10

8

PART - I

IS: 1554

17

Page 19: Technical 1554 cables specifications

TABLE - 6

TYPE - SINGLE CORE, VOLTAGE - 1100 VOLTS

CONSTRUCTION: COPPER CONDUCTOR, PVC INSULATION & OVERALL PVC SHEATHED

CABLE CODE - YY

Nominal

Cross

Sectional

Area

Sq. mm

Nominal

Thickness

of

Insulation

mm

Nominal

Thickness

of Outer

Sheath

mm

Approx.

Overall

Diameter

mm

Approx.

Weight

of

Cables

Kg/Km

Max. DC

Conductor

Resistance

AT 20 C

Ohm/Km

�Direct in ground

2 Cables

Amps.

3 Cables

Amps.

2 Cables

Amps.

3 Cables

Amps.

2 Cables

Amps.

3 Cables

Amps.

In Duct In Air

Current Ratings

1.5*

2.5*

4.0*

6.0*

10.0

16.0

25.0

35.0

50.0

70.0

95.0

120.0

150.0

185.0

240.0

300.0

400.0

500.0

630.0

800.0

1000.0

0.8

0.9

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.6

3.0

3.4

3.4

3.4

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

2.0

2.0

2.0

2.0

2.0

2.2

2.2

2.4

2.4

2.4

2.8

6.70

7.40

8.00

8.50

9.30

10.80

12.50

13.70

15.80

17.80

19.70

21.80

23.40

25.50

28.60

32.00

36.50

40.20

43.50

50.00

55.00

55

80

100

130

170

240

260

440

610

840

1090

1300

1600

2000

2550

3200

4200

5250

6400

8200

10200

12.10

7.41

4.61

3.08

1.83

1.15

0.727

0.525

0.384

0.268

0.193

0.153

0.124

0.0991

0.0754

0.0601

0.0470

0.0366

0.0283

0.0221

0.0176

22

35

46

57

75

94

125

150

180

220

265

300

340

380

420

465

500

540

590

668

733

22

30

39

49

65

85

110

130

155

190

220

250

280

305

345

375

400

425

470

533

585

23

31

42

54

72

92

120

140

165

200

230

255

280

305

340

370

405

430

465

527

579

21

29

38

48

64

83

110

125

150

175

200

220

245

260

285

310

335

355

375

425

467

24

32

43

54

72

92

125

155

190

235

275

310

345

390

445

500

570

610

680

832

879

20

27

35

44

60

82

110

130

165

205

245

280

320

370

425

475

550

590

660

808

853

* If required, Cables can be made with stranded conductor also.

PART - I

IS: 1554

18

Page 20: Technical 1554 cables specifications

TABLE - 7

TYPE - TWO CORE, VOLTAGE - 1100 VOLTS

CONSTRUCTION: COPPER CONDUCTOR, PVC INSULATION, PVC INNER

SHEATHED & OVERALL PVC SHEATHED

CABLE CODE - YY

* If required, Cables can be made with stranded conductor also.

1.5

2.5

4.0

6.0

10.0

16.0

25.0

35.0

50.0

70.0

95.0

120.0

150.0

185.0

240.0

300.0

400.0

PART - I

IS: 1554

NominalCross

SectionalArea

Sq. mm

4*

6*

10

16

25

35

50

70

95

120

150

185

240

300

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.4

0.4

0.4

0.4

0.5

0.5

1.8

1.8

1.8

1.8

2.0

2.0

2.0

2.0

2.2

2.2

2.2

2.2

2.4

2.6

13.0

14.5

15.6

16.5

19.4

21.0

23.7

26.3

30.4

32.8

35.8

39.3

44.5

49.1

297

375

475

562

790

1033

1370

1766

2375

2985

3470

4328

5465

6786

4.61

3.08

1.83

1.15

0.727

0.524

0.387

0.268

0.193

0.153

0.124

0.0991

0.0754

0.0601

41

50

70

90

115

140

165

205

245

285

320

360

425

480

35

45

58

75

97

120

145

180

215

235

270

300

345

385

35

45

60

78

105

125

155

195

230

265

305

350

410

465

NominalThickness

ofInsulation

mm

MinimumThicknessof InnerSheath

mm

NominalThicknessof OuterSheath

mm

Approx.Overall

Diameter

mm

Approx.Weight

ofCables

Kg/Km

Max DCConductorResistance

At 20 C

Ohm/Km

� Direct inGround

Amps.

In Duct

Amps.

In Air

Amps.

Current Ratings

19

Page 21: Technical 1554 cables specifications

TABLE - 8

TYPE - THREE CORE, VOLTAGE - 1100 VOLTS

CONSTRUCTION: COPPER CONDUCTOR, PVC INSULATION, PVC INNER

SHEATHED & OVERALL PVC SHEATHED

CABLE CODE - YY

* If required, Cables can be made with stranded conductor also.

1.5

2.5

4.0

6.0

10.0

16.0

25.0

35.0

50.0

70.0

95.0

120.0

150.0

185.0

240.0

300.0

400.0

PART - I

IS: 1554

NominalCross

SectionalArea

Sq. mm

4*

6*

10

16

25

35

50

70

95

120

150

185

240

300

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.4

0.4

0.4

0.4

0.5

0.6

1.8

1.8

1.8

1.8

2.0

2.0

2.0

2.2

2.2

2.2

2.4

2.4

2.8

3.0

13.7

14.8

16.5

17.8

21.2

21.3

26.1

29.7

33.7

36.7

40.6

44.9

51.0

56.5

393

510

620

735

1095

1355

1850

2500

3400

4200

5200

6200

8000

9900

4.61

3.08

1.83

1.15

0.727

0.524

0.384

0.268

0.193

0.153

0.124

0.0991

0.0754

0.0601

36

45

60

77

99

120

145

175

210

240

270

300

345

385

30

38

50

64

81

99

125

150

175

195

225

255

295

335

30

39

52

60

90

110

135

165

200

230

265

305

355

400

NominalThickness

ofInsulation

mm

MinimumThicknessof InnerSheath

mm

NominalThicknessof OuterSheath

mm

Approx.Overall

Diameter

mm

Approx.Weight

ofCables

Kg/Km

Max DCConductorResistance

At 20 C

Ohm/Km

� Direct inGround

Amps.

In Duct

Amps.

In Air

Amps.

Current Ratings

20

Page 22: Technical 1554 cables specifications

TABLE - 9

TYPE - THREE & HALF CORE, VOLTAGE - 1100 VOLTS

CONSTRUCTION : COPPER CONDUCTOR, PVC INSULATION, PVC INNER SHEATHED,

OVERALL PVC SHEATHED CABLE CODE - YY

Nominal Cross

Sectional Area

Main Neutral

Sq. mm. Sq. mm

Nominal

Thickness

Minimum

Thickness

of Inner

Sheath

mm

Nominal

Thickness

of Outer

Sheath

mm

Approx

Overall

Diameter

mm

Approx

Weight

of Cables

Kg/Km

Main

Ohm/km

Neutral

Ohm/km

Direct in

Ground

Amps

In

Ducts

Amps

In

Air

Amps

of Insulation

Main Neurtral

mm mm

25

35

50

70

95

120

150

185

240

300

16

16

25

35

50

70

70

95

120

150

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

1.0

1.0

1.2

1.2

1.4

1.4

1.4

1.6

1.6

1.8

0.3

0.3

0.3

0.4

0.4

0.5

0.5

0.5

0.6

0.6

2.00

2.00

2.20

2.20

2.20

2.40

2.40

2.60

3.00

3.20

23.90

26.20

29.50

33.50

37.50

41.20

43.80

47.70

56.60

62.50

1313

1600

2230

3020

3975

4960

6020

7420

9440

11670

0.727

0.524

0.387

0.268

0.193

0.153

0.124

0.0991

0.0754

0.0601

1.150

1.150

0.727

0.524

0.387

0.268

0.268

0.193

0.153

0.124

99

120

145

175

210

240

270

300

345

385

81

99

125

150

175

195

225

255

295

335

90

110

135

165

200

230

265

305

355

400

PART - I

IS: 1554

Max. DC Conductor

Resistance at 20 C0 Current Ratings

21

Page 23: Technical 1554 cables specifications

TABLE - 10

TYPE - FOUR CORE, VOLTAGE - 1100 VOLTS

CONSTRUCTION: COPPER CONDUCTOR, PVC INSULATION, PVC INNER

SHEATHED OVERALL PVC SHEATHED

CABLE CODE - YY

Nominal

Cross

Sectional

Area

Sq. mm

Nominal

Thickness

of

Insulation

mm

Minimum

Thickness

of Inner

Sheath

mm

Nominal

Thickness

of Outer

Sheath

mm

Approx.

Overall

Diameter

mm

Approx.

Weight

of Cables

Kg./Km

Direct

in ground

Amps.

Max. DC

Conductor

Resistance

AT 20 C

Ohm/Km

0In

Duct

Amps.

Current Ratings

In

Air

Amps.

* If required, Cables can be made with stranded conductor also.

PART - I

IS: 1554

4*

6*

10

16

25

35

50

70

95

120

150

185

240

300

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.4

0.5

0.5

0.6

0.6

0.7

1.8

1.8

1.8

2.0

2.0

2.0

2.2

2.2

2.2

2.4

2.6

2.8

3.0

3.2

14.8

16.0

17.9

20.3

23.9

26.0

30.1

33.9

38.6

42.5

47.0

52.2

58.9

65.3

368

488

707

945

1418

1850

2540

3430

4450

5570

6910

7612

10840

13425

4.61

3.08

1.83

1.15

0.727

0.524

0.387

0.268

0.193

0.153

0.124

0.0991

0.0754

0.0470

36

45

60

77

99

120

145

175

210

240

270

300

345

385

30

38

50

64

81

99

125

150

175

195

225

255

295

335

30

39

52

66

90

110

135

165

200

230

265

305

355

400

22

Page 24: Technical 1554 cables specifications

TABLE - 11

TYPE - TWO CORE, VOLTAGE - 1100 VOLTS

CONSTRUCTION: COPPER CONDUCTOR, PVC INSULATION, PVC INNER SHEATHED

GI WIRE/STRIP ARMOURED & OVERALL PVC SHEATHED.

CABLE CODE - YWY/YFY

Nominal

Cross

Sectional

Area

Sq. mm

Nominal

Thickness

of

Insulation

mm

Minimum

Thickness

of Inner

Sheath

mm

Minimum

Thickness

of Outer

Sheath

mm

Galvanised

Round

Steel Wire

Nominal

Diameter

mm

Galvanised

at

Steel Strip

Nominal

Thickness

mm

Approx.

Overall

Diameter

mm

Approx.

Weight

of Cables

Kg./Km

Direct

in ground

Amps.

Max. DC

Conductor

Resistance

AT 20 C

Ohm/Km

0In

Duct

Amps.

Current RatingsARMOUR

In

Air

Amps.

* If required, Cables can be made with stranded conductor also.

PART - I

IS: 1554

4*

6*

10

16

25

35

50

70

95

120

150

185

240

300

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.4

0.4

0.4

0.4

0.5

0.5

1.40

1.40

1.40

1.40

-----

-----

-----

-----

-----

-----

-----

-----

-----

-----

-----

-----

-----

-----

0.80

0.80

0.80

0.80

0.80

0.80

0.80

0.80

0.80

0.80

1.24

1.24

1.24

1.24

1.40

1.40

1.40

1.40

1.40

1.56

1.56

1.56

1.72

1.88

14.50

15.60

17.10

16.50

17.80

19.30

22.00

24.00

27.00

29.00

32.40

35.60

39.60

43.70

585

655

824

918

1070

1333

1660

2121

2770

3320

3996

4930

6170

7562

4.61

3.08

1.83

1.15

0.727

0.524

0.387

0.268

0.193

0.153

0.124

0.0991

0.0754

0.0601

41

50

70

90

115

140

165

205

240

275

310

350

405

450

35

44

58

75

97

120

145

180

215

235

270

300

345

385

35

45

60

78

105

125

155

195

230

265

305

350

410

465

23

Page 25: Technical 1554 cables specifications

TABLE - 12

TYPE - THREE CORE, VOLTAGE - 1100 VOLTS

CONSTRUCTION: COPPER CONDUCTOR, PVC INSULATION, PVC INNER SHEATHED

GI WIRE/STRIP ARMOURED & OVERALL PVC SHEATHED.

CABLE CODE - YWY/YFY

Nominal

Cross

Sectional

Area

Sq. mm

Nominal

Thickness

of

Insulation

mm

Minimum

Thickness

of Inner

Sheath

mm

Minimum

Thickness

of Outer

Sheath

mm

Galvanised

Round

Steel Wire

Nominal

Diameter

mm

Galvanised

Flat

Steel Strip

Nominal

Thickness

mm

Approx.

Overall

Diameter

mm

Approx.

Weight

of Cables

Kg./Km

Direct

in ground

Amps.

Max. DC

Conductor

Resistance

AT 20 C

Ohm/Km

0In

Duct

Amps.

Current RatingsARMOUR

In

Air

Amps.

* If required, Cables can be made with stranded conductor also.

PART - I

IS: 1554

4*

6*

10

16

25

35

50

70

95

120

150

185

240

300

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.4

0.5

0.5

0.6

0.6

0.6

1.40

1.40

1.40

-----

-----

-----

-----

-----

-----

-----

-----

-----

-----

-----

-----

-----

-----

0.80

0.80

0.80

0.80

0.80

0.80

0.80

0.80

0.80

0.80

0.80

1.24

1.24

1.40

1.40

1.40

1.40

1.40

1.56

1.56

1.56

1.72

1.72

1.88

2.04

15.2

16.4

18.2

17.8

20.8

22.8

26.0

29.2

33.2

35.7

39.6

43.5

48.7

54.0

660

740

970

1080

1390

1700

2250

3000

3900

4700

5700

6900

8700

10700

4.61

3.08

1.83

1.15

0.727

0.524

0.387

0.268

0.193

0.153

0.124

0.0991

0.0754

0.0601

36

45

60

77

99

120

145

175

210

240

270

300

345

385

30

38

50

64

81

99

125

150

175

195

225

255

295

335

30

39

52

66

90

110

135

165

200

230

265

305

355

400

24

Page 26: Technical 1554 cables specifications

TABLE - 13

TYPE - THREE & HALF CORE, VOLTAGE - 1100 VOLTS

CONSTRUCTION: COPPER CONDUCTOR, PVC INSULATION, PVC INNER SHEATHED,

GI STRIP ARMOURED & OVERALL PVC SHEATHED CABLE CODE - YFY

Nominal Cross

Sectional Area

Main Neutral

Sq. mm. Sq. mm

Minimum

Thickness

of Inner

Sheath

mm

Minimum

Thickness

of Outer

Sheath

mm

Approx

Overall

Diameter

mm

Approx

Weight

of Cables

kg/km

Main

Ohm/km

Neutral

Ohm/km

Direct in

Ground

Amps

In

Ducts

Amps

In

Air

Amps

Nominal

Thickness

of Insulation

Main Neutral

mm mm

25

35

50

70

95

120

150

185

240

300

16

16

25

35

50

70

70

95

120

150

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

1.0

1.0

1.2

1.2

1.4

1.4

1.4

1.6

1.6

1.8

0.3

0.3

0.3

0.4

0.4

0.5

0.5

0.5

0.6

0.6

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

1.4

1.4

1.56

1.56

1.56

1.72

1.88

2.04

2.20

2.36

23.0

25.3

29.5

32.8

37.2

40.5

45.0

49.5

55.6

61.5

0.727

0.524

0.387

0.268

0.193

0.153

0.124

0.0991

0.0754

0.0601

1610

1970

2680

3520

4425

5540

6570

8020

10200

12500

1.150

1.150

0.727

0.524

0.387

0.268

0.268

0.193

0.153

0.124

99

120

145

175

210

240

270

300

345

385

81

99

125

150

175

195

225

255

295

335

90

110

135

165

200

230

265

305

355

400

PART - I

IS: 1554

Max. DC Conductor

Resistance at 20 C0ARMOUR Current Ratings

Galv.

Flat

Steel Strip

Nominal

Thickness

mm

25

Page 27: Technical 1554 cables specifications

TABLE - 14

TYPE - FOUR CORE, VOLTAGE - 1100 VOLTS

CONSTRUCTION: COPPER CONDUCTOR, PVC INSULATION, PVC INNER SHEATHED

GI WIRE/STRIP ARMOURED & OVERALL PVC SHEATHED.

CABLE CODE - YWY/YFY

Nominal

Cross

Sectional

Area

Sq. mm

Nominal

Thickness

of

Insulation

mm

Minimum

Thickness

of Inner

Sheath

mm

Minimum

Thickness

of Outer

Sheath

mm

Galvanised

Round

Steel Wire

Nominal

Diameter

mm

Galvanised

Flat

Steel Strip

Nominal

Thickness

mm

Approx.

Overall

Diameter

mm

Approx.

Weight

of Cables

Kg./Km

Direct

in ground

Amps.

Max. DC

Conductor

Resistance

AT 20 C

Ohm/Km

0In

Duct

Amps.

Current RatingsARMOUR

In

Air

Amps.

* If required, Cables can be made with stranded conductor also.

PART - I

IS: 1554

4*

6*

10

16

25

35

50

70

95

120

150

185

240

300

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.4

0.5

0.5

0.6

0.6

0.7

1.40

1.40

-----

-----

-----

-----

-----

-----

-----

-----

-----

-----

-----

-----

-----

-----

0.80

0.80

0.80

0.80

0.80

0.80

0.80

0.80

0.80

0.80

0.80

0.80

1.24

1.24

1.40

1.40

1.40

1.40

1.56

1.56

1.72

1.88

1.88

2.04

2.36

2.52

16.3

17.6

18.4

20.8

24.5

27.0

31.8

35.4

40.0

44.0

48.5

53.9

60.6

2.52

749

878

1050

1275

1748

2350

3040

3930

5050

6240

7363

8122

11424

16680

4.61

3.08

1.83

1.15

0.727

0.524

0.387

0.268

0.193

0.153

0.124

0.0991

0.0754

0.0470

36

45

60

77

99

120

145

175

210

240

270

300

345

385

30

38

50

64

81

99

125

150

175

195

225

255

295

335

30

39

52

60

90

110

135

165

200

230

265

305

355

400

26

Page 28: Technical 1554 cables specifications

TABLE - 15

TYPE - SINGLE CORE, VOLTAGE - 1100 VOLTS

CONSTRUCTION: ALUMINIUM CONDUCTOR, PVC INSULATION & OVERALL PVC SHEATHED

CABLE CODE - AYY

Nominal

Cross

Sectional

Area

Sq. mm

Nominal

Thickness

of

Insulation

mm

Nominal

Thickness

of Outer

Sheath

mm

Approx.

Overall

Diameter

mm

Approx.

Weight

of

Cables

mm

Max. DC

Conductor

Resistance

AT 20 C

Ohm/Km

Direct in ground

2 Cables

Amps.

Cables

Amps.

2 Cables

Amps.

3 Cables

Amps.

2 Cables

Amps.

3 Cables

Amps.

Direct in Duct Direct in Air

Current Ratings

1.5*

2.5*

4.0*

6.0*

10.0*

16.0

25.0

35.0

50.0

70.0

95.0

120.0

150.0

185.0

240.0

300.0

400.0

500.0

630.0

800.0

1000.0

0.8

0.9

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.6

3.0

3.4

3.4

3.4

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

2.0

2.0

2.0

2.0

2.0

2.2

2.2

2.4

2.4

2.4

2.8

6.70

7.40

8.00

8.50

9.30

10.80

12.50

13.70

15.80

17.80

19.70

21.80

23.40

25.50

28.60

32.00

36.50

40.20

43.50

50.00

55.00

55

65

75

90

105

140

190

225

300

400

500

560

665

855

1070

1345

1710

2150

2564

3270

4060

18.10

12.10

7.41

4.61

3.08

1.91

1.20

0.868

0.641

0.443

0.320

0.253

0.206

0.164

0.125

0.100

0.0778

0.0605

0.0469

0.0367

0.0291

21

28

36

44

54

75

97

120

145

170

205

230

265

300

335

370

410

435

485

525

570

17

24

31

39

51

66

86

100

120

140

175

195

220

240

270

295

325

345

390

440

490

19

25

33

42

56

71

93

110

130

155

180

200

220

240

270

295

335

355

395

420

445

17

24

30

37

51

65

84

100

115

135

155

170

190

210

225

245

275

295

320

380

380

18

25

32

41

56

72

99

120

150

185

215

240

270

305

350

395

455

490

560

650

735

15

21

27

35

47

64

84

105

130

155

190

220

250

290

335

380

435

480

550

640

720

* If required, Cables can be made with stranded conductor also.

PART - I

IS: 1554

27

Page 29: Technical 1554 cables specifications

TABLE - 16

TYPE - TWO CORE, VOLTAGE - 1100 VOLTS

CONSTRUCTION: ALUMINIUM CONDUCTOR, PVC INSULATION, PVC INNER

SHEATHED, OVERALL PVC SHEATHED

CABLE CODE - AYY

Nominal

Cross

Sectional

Area

Sq. mm

Nominal

Thickness

of

Insulation

mm

Minimum

Thickness

of Inner

Sheath

mm

Nominal

Thickness

of Outer

Sheath

mm

Approx.

Overall

Diameter

mm

Approx.

Weight

of Cables

Kg./Km

Max. DC

Conductor

Resistance

AT 20 C

Ohm/Km

Direct

in ground

Amps.

In

Duct

Amps.

Current Ratings

In

Air

Amps.

1.5*

2.5*

4.0*

6.0*

10.0*

16.0

25.0

35.0

50.0

70.0

95.0

120.0

150.0

185.0

240.0

300.0

400.0

0.8

0.9

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.6

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.4

0.4

0.4

0.4

0.5

0.5

0.6

1.8

1.8

1.8

1.8

1.8

1.8

2.0

2.0

2.0

2.2

2.2

2.2

2.2

2.4

2.4

2.6

2.8

10.4

11.6

13.0

14.0

15.6

16.5

19.4

21.0

23.7

26.3

30.4

32.8

35.8

39.3

44.5

49.1

54.8

140

200

250

300

350

370

480

600

750

900

1200

1500

1620

2040

2500

3100

3900

18.10

12.10

7.41

4.61

3.08

1.91

1.20

0.868

0.641

0.443

0.320

0.253

0.206

0.164

0.125

0.100

0.0778

* If required, Cables can be made with stranded conductor also.

18

25

32

40

55

70

90

110

135

160

190

210

240

275

320

355

385

16

21

27

34

45

58

76

92

115

140

170

190

210

240

275

305

345

16

21

27

35

47

59

78

99

125

150

185

210

240

275

325

365

420

PART - I

IS: 1554

28

Page 30: Technical 1554 cables specifications

TABLE - 17

TYPE - THREE CORE, VOLTAGE - 1100 VOLTS

CONSTRUCTION: ALUMINIUM CONDUCTOR, PVC INSULATION, PVC INNER

SHEATHED, OVERALL PVC SHEATHED

CABLE CODE - AYY

Nominal

Cross

Sectional

Area

Sq. mm

Nominal

Thickness

of

Insulation

mm

Minimum

Thickness

of Inner

Sheath

mm

Nominal

Thickness

of Outer

Sheath

mm

Approx.

Overall

Diameter

mm

Approx.

Weight

of Cables

Kg./Km

Max. DC

Conductor

Resistance

AT 20 C

Ohm/Km

Direct

in ground

Amps.

In

Duct

Amps.

Current Ratings

In

Air

Amps.

1.5*

2.5*

4.0*

6.0*

10.0*

16.0

25.0

35.0

50.0

70.0

95.0

120.0

150.0

185.0

240.0

300.0

400.0

0.8

0.9

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.6

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.4

0.4

0.4

0.5

0.5

0.6

0.7

1.8

1.8

1.8

1.8

1.8

1.8

2.0

2.0

2.0

2.2

2.2

2.2

2.4

2.4

2.8

3.0

3.2

10.9

12.2

13.7

14.8

16.5

17.8

21.2

23.1

26.1

29.7

33.7

36.7

40.6

44.9

51.0

56.5

63.1

160

221

320

400

420

440

630

710

900

1200

1650

1950

2400

2750

3500

4350

5500

18.10

12.10

7.41

4.61

3.08

1.91

1.20

0.868

0.641

0.443

0.320

0.253

0.206

0.164

0.125

0.100

0.0778

16

21

28

35

46

60

76

92

110

135

165

185

210

235

275

305

335

14

18

23

30

39

50

63

77

95

115

140

155

175

200

235

260

290

13

18

23

30

40

51

70

86

105

130

155

180

205

240

280

315

375

* If required, Cables can be made with stranded conductor also.

PART - I

IS: 1554

29

Page 31: Technical 1554 cables specifications

TABLE - 18

TYPE - THREE & HALF CORE, VOLTAGE - 1100 VOLTS

CONSTRUCTION: ALUMINIUM CONDUCTOR, PVC INSULATION, PVC INNER SHEATHED,

& OVERALL PVC SHEATHED CABLE CODE - AYY PART - I

IS: 1554

Nominal Cross

Sectional Area

Main Neutral

Sq. mm. Sq. mm

Nominal

Thickness

Nominal

Thickness

of Inner

Sheath

mm

Nominal

Thickness

of Outer

Sheath

mm

Approx

Overall

Diameter

mm

Approx

Weight

of Cables

kg/km

Main

Ohm/km

Neutral

Ohm/km

Direct in

Ground

Amps

In

Ducts

Amps

In

Air

Amps

of Insulation

Main Neutral

mm mm

25

35

50

70

95

120

150

185

240

300

400

16

16

25

35

50

70

70

95

120

150

185

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.6

1.0

1.0

1.2

1.2

1.4

1.4

1.4

1.6

1.6

1.8

2.0

0.3

0.3

0.3

0.4

0.4

0.5

0.5

0.5

0.6

0.6

0.7

2.00

2.00

2.20

2.20

2.20

2.40

2.40

2.60

3.00

3.20

3.40

23.90

26.20

29.50

33.50

37.20

41.20

43.80

47.70

56.60

62.50

69.80

750

850

1150

1500

1900

2300

2800

3400

4244

5176

6700

1.200

0.868

0.641

0.443

0.320

0.253

0.206

0.164

0.125

0.100

0.0778

1.91

1.91

1.20

0.868

0.641

0.443

0.443

0.320

0.253

0.206

0.164

76

92

110

135

165

185

210

235

275

305

335

63

77

95

115

140

155

175

200

235

260

290

70

86

105

130

155

180

205

240

280

315

375

Max. DC Conductor

Resistance at 20 C0 Current Ratings

30

Page 32: Technical 1554 cables specifications

Nominal

Cross

Sectional

Area

Sq. mm

Nominal

Thickness

of

Insulation

mm

Minimum

Thickness

of Inner

Sheath

mm

Nominal

Thickness

of Outer

Sheath

mm

Approx.

Overall

Diameter

mm

Approx.

Weight

of Cables

Kg./Km

Direct

in ground

Amps.

Max. DC

Conductor

Resistance

AT 20 C

Ohm/Km

0In

Duct

Amps.

Current Ratings

In

Air

Amps.

* If required, Cables can be made with stranded conductor also.

1.5*

2.5*

4*

6*

10*

16

25

35

50

70

95

120

150

185

240

300

400

0.8

0.9

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.6

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.4

0.4

0.5

0.5

0.6

0.6

0.7

0.7

1.8

1.8

1.8

1.8

1.8

2.0

2.0

2.0

2.2

2.2

2.2

2.4

2.6

2.8

3.0

3.2

3.6

11.7

13.1

14.8

16.0

17.9

20.3

23.9

26.0

30.1

33.9

38.6

42.5

47.0

52.2

58.9

65.3

72.9

180

225

269

340

460

550

800

980

1300

1700

2100

2600

3200

3900

4900

6000

8000

16

21

28

35

46

60

76

92

110

135

165

185

210

235

275

305

335

14

18

23

30

39

50

63

77

95

115

140

155

175

200

235

260

290

13

18

23

30

40

51

70

86

105

130

155

180

205

240

280

315

375

TABLE - 19

TYPE - FOUR CORE, VOLTAGE - 1100 VOLTS

CONSTRUCTION: ALUMINIUM CONDUCTOR, PVC INSULATION, PVC INNER SHEATHED,

& OVERALL PVC SHEATHED CABLE CODE - AYY PART - I

IS: 1554

18.10

12.10

7.41

4.61

3.08

1.91

1.20

0.868

0.641

0.443

0.320

0.253

0.206

0.164

0.125

0.100

0.0778

31

Page 33: Technical 1554 cables specifications

TABLE - 20

TYPE - TWO CORE, VOLTAGE - 1100 VOLTS

CONSTRUCTION: ALUMINIUM CONDUCTOR, PVC INSULATION, PVC INNER

SHEATHED, GI WIRE/STRIP ARMOURED & OVERALL PVC SHEATHED

CABLE CODE - AYWY/AYFY.

Nominal

Cross

Sectional

Area

Sq. mm

Nominal

Thickness

of

Insulation

mm

Minimum

Thickness

of Inner

Sheath

mm

Galvanised

Rond

Steel Wire

Nominal

Diameter

mm

ARMOUR

Galvanised

Flat

Steel Strip

Nominal

Thickness

mm

Minimum

Thickness

of Outer

Sheath

mm

Approx.

Overall

Diameter

mm

Approx.

Weight

of Cables

Kg/Km

Max. DC

Conductor

Resistance

AT 20 C

Ohm/Km

0

Direct

in ground

Amps.

In

Duct

Amps.

Current Ratings

In

Air

Amps.

1.5*

2.5*

4.0*

6.0*

10.0*

16.0

25.0

35.0

50.0

70.0

95.0

120.0

150.0

185.0

240.0

300.0

400.0

0.8

0.9

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.6

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.4

0.4

0.4

0.4

0.4

0.5

0.5

1.4

1.4

1.4

1.4

1.4

1.4

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

1.24

1.24

1.24

1.24

1.24

1.24

1.40

1.40

1.40

1.40

1.40

1.56

1.56

1.56

1.72

1.88

2.00

12.00

13.50

14.50

15.60

17.10

16.50

17.80

19.30

22.00

24.00

27.00

29.00

32.40

35.60

39.60

43.70

49.00

400

425

535

580

700

720

760

900

1040

1255

1595

1835

2140

2640

3200

3850

4700

18.10

12.10

7.41

4.61

3.08

1.91

1.20

0.868

0.641

0.443

0.320

0.253

0.206

0.164

0.125

0.100

0.0778

18

25

32

40

55

70

90

110

135

160

190

210

240

275

320

355

385

16

21

27

34

45

58

76

92

115

140

170

190

210

240

275

305

345

16

21

27

35

47

59

78

99

125

150

185

210

240

275

325

365

420

* If required, Cables can be made with stranded conductor also.

PART - I

IS: 1554

32

Page 34: Technical 1554 cables specifications

TABLE - 21

TYPE - THREE CORE, VOLTAGE - 1100 VOLTS

CONSTRUCTION: ALUMINIUM CONDUCTOR, PVC INSULATION, PVC INNER

SHEATHED, GI WIRE/STRIP ARMOURED & OVERALL PVC SHEATHED

CABLE CODE - AYWY/AYFY.

Nominal

Cross

Sectional

Area

Sq. mm

Nominal

Thickness

of

Insulation

mm

Minimum

Thickness

of Inner

Sheath

mm

Galvanised

Rond

Steel Wire

Nominal

Diameter

mm

ARMOUR

Galvanised

Flat

Steel Strip

Nominal

Thickness

mm

Minimum

Thickness

of Outer

Sheath

mm

Approx.

Overall

Diameter

mm

Approx.

Weight

of Cables

Kg./Km

Max. DC

Conductor

Resistance

AT 20 C

Ohm/Km

Direct

in ground

Amps.

In

Duct

Amps.

Current Ratings

In

Air

Amps.

1.5

2.5

4.0

6.0

10.0

16.0

25.0

35.0

50.0

70.0

95.0

120.0

150.0

185.0

240.0

300.0

400.0

0.8

0.9

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.6

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.4

0.4

0.4

0.5

0.5

0.6

0.6

1.4

1.4

1.4

1.4

1.4

1.4

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

1.24

1.24

1.24

1.24

1.40

1.40

1.40

1.40

1.40

1.56

1.56

1.56

1.72

1.88

1.88

2.04

2.36

12.5

13.5

15.2

16.4

18.2

17..8

20.8

22.8

26.0

29.2

33.2

35.7

39.6

43.5

48.7

54.0

61.0

440

500

580

620

750

780

920

1050

1300

1700

2100

2500

2900

3450

4250

5150

6600

18.10

12.10

7.41

4.61

3.08

1.91

1.20

0.868

0.641

0.443

0.320

0.253

0.206

0.164

0.125

0.100

0.0778

16

21

28

35

6

60

76

92

110

135

165

185

210

235

275

305

335

14

18

23

30

39

50

63

77

95

115

140

155

175

200

235

260

290

13

18

23

30

40

51

70

86

105

130

155

180

2105

240

280

315

375

PART - I

IS: 1554

* If required, Cables can be made with stranded conductor also.

33

Page 35: Technical 1554 cables specifications

TABLE - 22

TYPE - THREE & HALF CORE, VOLTAGE - 1100 VOLTS

CONSTRUCTION: ALUMINIUM CONDUCTOR, PVC INSULATION, PVC INNER

SHEATHED, GI STRIP ARMOURED & OVERALL PVC SHEATHED

CABLE CODE - AYFY.

Nominal Cross

Sectional Area

Main

Sq. mm.

Main

Ohm/Km

Main

Sq. mm.

Neutral

Sq. mm.

Neutral

Ohm./Km

Neutral

Sq. mm.

Nominal Thickness

of Insulation

Minimum

Thickness

of Inner

Sheath

mm

ARMOUR

Galvanised

Flat

Steel Strip

Nominal

Thickness

mm

Minimum

Thickness

of Outer

Sheath

mm

Approx.

Overall

Diameter

mm

Approx.

Weight

of Cables

Kg./Km

Max. DC Conductor

Resistance AT 20 C� Direct

in ground

Amps.

In

Duct

Amps.

Current Ratings

In

Air

Amps.

25.0

35.0

50.0

70.0

95.0

120.0

150.0

185.0

240.0

300.0

400.0

16

16

25

35

50

70

70

95

120

150

185

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.6

1.0

1.0

1.2

1.2

1.4

1.4

1.4

1.6

1.6

1.8

2.0

0.3

0.3

0.3

0.4

0.4

0.4

0.5

0.5

0.6

0.6

0.7

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

1.4

1.4

1.56

1.56

1.56

1.72

1.88

2.04

2.20

2.36

2.52

23.0

25.3

29.5

32.8

37.2

40.5

45.0

49.5

55.6

61.5

69.5

1050

1220

1600

2000

2350

2900

3350

4000

5100

6060

7900

1.200

0.868

0.641

0.443

0.320

0.253

0.206

0.164

0.125

0.100

0.0778

1.91

1.91

1.20

.868

0.641

0.443

0.443

0.320

0.253

0.206

0.164

76

92

100

135

165

185

210

235

275

305

335

63

77

95

115

10

155

175

200

235

260

290

70

86

105

130

155

180

205

240

280

315

375

PART - I

IS: 1554

34

Page 36: Technical 1554 cables specifications

TABLE - 23

TYPE - FOUR CORE, VOLTAGE - 1100 VOLTS

CONSTRUCTION: ALUMINIUM CONDUCTOR, PVC INSULATION, PVC INNER

SHEATHED, GI WIRE/STRIP ARMOURED & OVERALL PVC SHEATHED

CABLE CODE - AYWY/AYFY.

Nominal

Cross

Sectional

Area

Sq. mm

Nominal

Thickness

of

Insulation

mm

Minimum

Thickness

of Inner

Sheath

mm

Galvanised

Rond

Steel Wire

Nominal

Diameter

mm

ARMOUR

Galvanised

Flat

Steel Strip

Nominal

Thickness

mm

Minimum

Thickness

of Outer

Sheath

mm

Approx.

Overall

Diameter

mm

Approx.

Weight

of Cables

Kg./Km

Max. DC

Conductor

Resistance

AT 20 C

Ohm/Km

Direct

in ground

Amps.

In Duct

Amps.

Current Ratings

In Air

Amps.

1.5

2.5

4.0

6.0

10.0

16.0

25.0

35.0

50.0

70.0

95.0

120.0

150.0

185.0

240.0

300.0

400.0

0.8

0.9

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.6

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.4

0.4

0.4

0.5

0.5

0.6

0.6

0.7

0.7

1.4

1.4

1.4

1.4

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

1.24

1.24

1.24

1.24

1.40

1.40

1.40

1.40

1.56

1.56

1.72

1.88

1.88

2.04

2.36

2.52

2.68

13.3

14.7

16.3

17.6

18.4

20.8

24.5

27.0

31.8

35.4

40.0

44.0

48.5

53.9

60.6

64.0

72.0

478

568

650

730

750

880

1130

1480

1800

2200

2700

3070

3653

4410

5484

6780

8340

18.10

12.10

7.41

4.61

3.08

1.91

1.20

0.868

0.641

0.443

0.320

0.253

0.206

0.164

0.125

0.100

0.0778

16

21

28

35

46

60

76

92

110

135

165

185

210

235

275

305

335

14

18

23

30

39

50

63

77

95

115

140

155

175

200

235

260

290

13

18

23

30

40

51

70

86

105

130

155

180

210

240

280

315

375

PART - I

IS: 1554

* If required, Cables can be made with stranded conductor also. 35

Page 37: Technical 1554 cables specifications

CURRENT RATING in PVC Cable:

Current Rating e.g. Current Carrying Capacity of the cable is determined by the maximum permissible conductor

temperature and the ambient conditions as far as they are for the dissipation of the heat. Current Rating in various types

and size of cable are given in various tables, have been derived IS:3961 (Pt-II) 1967. The values are dependent on so

many conditions like method of laying, ground and ambient temperature, Soil conditions extra.One or all conditions may

vary from installation to installation. It is necessary to define all these parameters and to know their effects on current

rating quantitatively to work out current rating to any set of conditions:

The current ratings given in relevant table are based on the following assumptions:

1. Max. Conductor Temperature - 70 C

2. Ground temperature - 30 C.

3. AmbientTemperature - 40 C.

4. ThermalResistivityofSoil - 150 C.Cm/W.

5. ThermalResistivityofPVCCompound - 650 C.Cm/W.

6. Depth ofLaying[To highest point of - 75 C

cable laid direct in ground or to top surface of ducts]

Cable Type Typeof Installation Method of Installation.

Single Core Cable I] Laid direct in ground 1. Three cables in closed

trefoil formation, or

2. Two touching in

horizontal formation

Ii] In ducts 1. Three in trefoil formation, or

2. Two in horizontal formation.

Iii] In air 1. Three Single Core Cables are installed

in trefoil formation touching.

2. Two installed one above the other fixed

to avertical wall.

Twin &Multi core Cables Installed Singly.

InnerDiameterofduct 100mm/125mm.

-Whenmore thanonecablecircuitare run simutaneously, there isno

effect on current rating upto cable size of 70.0 Sq.mm., provided the minimum clearance between two circuits is 75 mm.

The same will apply for higher than 70.0 Sq.mm. cable size if minimum clearance is kept at 150 mm and provided that

numberofcircuitsexceedsfour,theyareinstalledinahorizentalplane.

The current rating gives in various tables are based on certain assumed condition described above. In actual practice,

these conditions may be defferent. Therefore, to determine the current rating at different installation conditions,, the

tabulated rating should be multiplied with appropriate 'rating' factors. These rating factors are as follows:

0

0

0

0

0

0

6. MethodOfInstallation:

7. SIZEOFDUCT

8.EFFECTOFGROUPINGOFTHECABLES INAIR

36.

Page 38: Technical 1554 cables specifications

1.0

0.9

0.8

0.7

0.6

0.5

0.4

1 2 3 4 5 6 7 8 9 10 11 12NUMBER OF CABLES IN GROUP

GR

OU

PR

AT

ING

FA

CT

OR

RATING FACTORS

A) CABLE LAID DIRECT IN GROUND :-

i) DEPTH OFLAYING

ii) FORVARIATIONINGROUNDTEMPERATURE (FOR CABLES LAID DIRECT IN GROUND)

iii) FORGROUPRATINGFACTORS.

DEPTHOF LAYING SIZE

CMS. UPTO 25.0 ABOVE 25 ABOVE 300

SQ.MM. SQ.MM. SQ.MM. SQ.MM.

UPTO 300 SQ. MM.

75 1.00 1.00 1.00

90 0.99 0.98 0.97

105 0.98 0.97 0.96

120 0.97 0.96 0.95

150 0.96 0.94 0.92

180 OR MORE 0.95 0.94 0.91

GROUND TEMPERATURE IN DEGREE C 15 20 25 30 35 40 45

RATING FACTOR 1.17 1.12 1.06 1.00 0.94 0.87 0.79

a) GROUPRATINGFACTORSFORTWINANDMULTICORECABLESIN

HORIZENTALFORMATION,LAIDDIRECTIN THE GROUND

Numbers SPACING OF CABLES [ CENTRE TO CENTRE]

OF CABLE TOUCHING 15CM. 30CMS. 45CMS. 60CMS.

2 0.80 0.84 0.87 0.90 0.91

3 0.68 0.74 0.79 0.83 0.86

4 0.62 0.69 0.75 0.80 0.83

5 0.58 0.65 0.72 0.77 0.80

6 0.55 0.62 0.69 0.75 0.78

7 0.52 0.59 0.67 0.73 0.77

8 0.50 0.57 0.66 0.72 0.75

9 0.48 0.55 0.65 0.71 0.75

10 0.46 0.54 0.64 0.70 0.74

11 0.45 0.53 0.63 0.70 0.74

12 0.44 0.52 0.62 0.69 0.73

37.

Page 39: Technical 1554 cables specifications

No. of

CABLES

No. of

TIERSTOUCHING 15 CM. 30 CMS. 45 CMS. 60 CMS.

SPACING OF CABLES (CENTE TO CENTRE)

2

3

4

5

6

7

8

9

10

11

12

1

1

2

2

2

3

3

3

4

4

4

0.80

0.68

0.60

0.55

0.51

0.48

0.46

0.44

0.42

0.41

0.40

0.84

0.74

0.66

0.61

0.57

0.54

0.51

0.48

0.47

0.46

0.45

0.87

0.79

0.73

0.68

0.63

0.59

0.56

0.53

0.52

0.50

0.49

0.90

0.83

0.77

0.71

0.67

0.63

0.60

0.57

0.55

0.54

0.53

0.91

0.86

0.79

0.83

0.69

0.64

0.61

0.58

0.56

0.55

0.54

No. of

CABLESTOUCHING 15 CM. 30 CMS. 45 CMS. 60 CMS.

SPACING OF GROUPS OF CABLES (CENTRE TO CENTRE)

2

3

4

5

6

7

8

9

10

11

12

0.80

0.70

0.64

0.59

0.55

0.53

0.51

0.49

0.48

0.47

0.46

0.85

0.78

0.73

0.70

0.67

0.65

0.64

0.63

0.63

0.62

0.61

0.90

0.85

0.81

0.79

0.77

0.76

0.75

0.74

0.74

0.73

0.73

0.92

0.88

0.86

0.84

0.83

0.82

0.82

0.81

0.81

0.80

0.80

0.95

0.91

0.89

0.88

0.87

0.86

0.86

0.85

0.85

0.84

0.84

No. of

CABLESTOUCHING 15 CM. 30 CMS. 45 CMS. 60 CMS.

SPACING OF GROUPS OF CABLES (CENTRE TO CENTRE)

2

3

4

5

6

7

8

9

10

11

12

0.77

0.67

0.61

0.57

0.53

0.51

0.49

0.47

0.45

0.44

0.43

0.81

0.74

0.64

0.60

0.57

0.55

0.53

0.52

0.51

0.50

0.49

0.86

0.78

0.72

0.69

0.669

0.64

0.63

0.62

0.61

0.60

0.59

0.88

0.81

0.76

0.74

0.72

0.70

0.59

0.68

0.67

0.66

0.65

0.89

0.83

0.80

0.77

0.75

0.74

0.73

0.73

0.72

0.72

0.71

B) GROUPRATINGFACTORSFORTWINANDMULTICORECABLESIN

TIERFORMATION,LAIDDIRECTIN THE GROUND

c) GROUPRATINGFACTORSFOR CIRCUIT OF TWOSINGLECORECABLES

SIDEBYSIDE TOUCHING,HORIZENTALFORMATION,LAIDDIRECTIN THE GROUND

D) GROUPRATINGFACTORSFORCIRCUITOFTHREESINGLECORE

CABLESINTREFOILANDTOUCHING,HORIZENTALFORMATION,

LAIDDIRECTINGROUND

1.0

0.9

0.8

0.7

0.6

0.5

0.4

1.0

0.9

0.8

0.7

0.6

0.5

0.4

1.0

0.9

0.8

0.7

0.6

0.5

0.4

NUMBER OF CIRCUITS (OF THO CABLES) IN GROUP

NUMBER OF CIRCUITS IN GROUP

1 2 3 4 5 6 7 8 9 10 11 12

1 2 3 4 5 6 7 8 9 10 11 12

GR

OU

PR

AT

ING

FA

CT

OR

GR

OU

PR

AT

ING

FA

CT

OR

GR

OU

PR

AT

ING

FA

CT

OR

NUMBER OF CABLES IN GROUP(OF THREE CABLES)

1 2 3 4 5 6 7 8 9 10 11 12

38.

Page 40: Technical 1554 cables specifications

b) RATING FACTOR FOR VARIATION INTHERMAL RESISTIVITY OF SOIL

[TWO & THREE CORE SIGNLE CABLES LAID DIRECT IN GROUND]

Nominal

Area

of

Conductor

in Sq. mm.

100 120 150 200 250 300

FOR VALUE OF THERMAL RESISTIVITY OF SOIL IN C m/W0

1.5

2.5

4.0

6.0

10.0

16.0

25.0

35.0

50.0

70.0

95.0

120.0

150.0

185.0

240.0

300.0

400.0

1.1

1.1

1.1

1.1

1.1

1.12

1.14

1.15

1.15

1.15

1.15

1.17

1.17

1.18

1.18

1.18

1.19

1.05

1.05

1.05

1.05

1.06

1.06

1.08

1.08

1.08

1.08

1.08

1.09

1.09

1.09

1.09

1.09

1.10

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

0.92

0.92

0.92

0.92

0.92

0.91

0.91

0.91

0.91

0.90

0.90

0.90

0.10

0.89

0.89

0.89

0.89

0.86

0.86

0.86

0.86

0.85

0.84

0.84

0.84

0.84

0.83

0.83

0.82

0.82

0.81

0.81

0.81

0.81

0.81

0.81

0.81

0.81

0.80

0.79

0.78

0.77

0.77

0.76

0.76

0.76

0.76

0.75

0.75

0.75

0.75

Nominal

Area of

Conductor

Two Cables Touching, For Value of

Thermal Resistivity of Soil C cm/W0

Three Cables in Trefoil Touching, for

Value of Thermal Resistivity of Soil Soil C cm/W0

In Sq. mm.

1.5

2.5

4.0

6.0

10.0

16.0

25.0

35.0

50.0

70.0

95.0

120.0

150.0

185.0

240.0

300.0

400.0

100

1.15

1.15

1.15

1.15

1.15

1.17

1.18

1.18

1.18

1.19

1.19

1.21

1.21

1.21

1.21

1.21

1.21

120

1.08

1.08

1.08

1.08

1.08

1.09

1.09

1.09

1.09

1.09

1.09

1.10

1.10

1.10

1.10

1.10

1.10

120

1.09

1.09

1.09

1.09

1.09

1.09

1.09

1.09

1.09

1.10

1.10

1.10

1.10

1.10

1.10

1.10

1.11

150

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

150

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

200

0.91

0.91

0.91

0.91

0.90

0.90

0.90

0.90

0.90

0.89

0.89

0.89

0.89

0.89

0.89

0.89

0.88

200

0.90

0.90

0.90

0.90

0.89

0.89

0.88

0.88

0.88

0.88

0.88

0.88

0.88

0.88

0.88

0.88

0.88

250

0.84

0.84

0.84

0.84

0.83

0.83

0.82

0.82

0.82

0.81

0.81

0.80

0.80

0.80

0.80

0.80

0.80

250

0.82

0.82

0.82

0.82

0.82

0.81

0.80

0.80

0.80

0.80

0.80

0.79

0.79

0.79

0.79

0.79

0.79

300

0.78

0.78

0.78

0.78

0.77

0.77

0.76

0.75

0.75

0.74

0.74

0.74

0.74

0.74

0.74

0.74

0.74

300

0.76

0.76

0.76

0.76

0.75

0.74

0.74

0.74

0.74

0.74

0.74

0.74

0.73

0.73

0.73

0.72

0.72

100

1.18

1.18

1.18

1.18

1.18

1.19

1.19

1.20

1.20

1.21

1.22

1.22

1.22

1.22

1.22

1.22

1.24

iv) FORVARIATIONINTHERMALRESISTIVITYOFSOIL

a) RATING FACTOR FOR VARIATION IN THERMAL RESISTIVITY OF SOIL

[TWIN&MULTICORECABLESLAIDDIRECTINGROUND]

39.

Page 41: Technical 1554 cables specifications

B)

i) RATING FACTOR FOR DEPTH OF LAYING

CABLE INSTALLED IN DUCT :-

(TWIN & MULTICORE CABLES IN SINGLE WAY DUCTS)

ii) FOR VARIATION IN GROUND TEMPERATURE[FOR CABLES IN DUCTS]

iii) FOR VARIATION IN THERMAL RESISTIVITY OF SOIL

a) RATING FACTOR FOR VARIATION IN THERMAL RESISTIVITY OF SOIL(TWIN & MULTICORE CABLES SINGLE WAY DUCT)

NominalArea

ofConductorin Sq. mm.

100 150 250 200 250 300

FOR VALUE OF THERMAL RESISTIVITY OF SOIL IN C cm/W0

1.5

2.5

4.0

6.0

10.0

16.0

25.0

35.0

50.0

70.0

95.0

120.0

150.0

185.0

240.0

300.0

400.0

1.05

1.05

1.05

1.05

1.05

1.06

1.07

1.08

1.08

1.08

1.08

1.09

1.09

1.10

1.10

1.10

1.11

1.03

1.03

1.03

1.03

1.03

1.03

1.04

1.04

1.04

1.04

1.04

1.05

1.05

1.05

1.05

1.05

1.06

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

0.96

0.96

0.96

0.96

0.95

0.95

0.95

0.94

0.94

0.94

0.94

0.94

0.93

0.93

0.92

0.92

0.92

0.91

0.91

0.91

0.91

0.90

0.90

0.90

0.89

0.89

0.88

0.87

0.87

0.86

0.86

0.86

0.86

0.86

0.88

0.88

0.88

0.88

0.87

0.86

0.85

0.84

0.84

0.83

0.83

0.82

0.82

0.81

0.81

0.81

0.81

DEPTH OF LAYING

[CM.]

GROUND TEMPERATURE

IN DEGREE C

RATING FACTOR

15

1.17

20

1.12

25

1.06

30

1.00

35

0.94

40

0.87

45

0.79

75

90

105

120

150

180

270

360

450

540 or more

1.00

0.99

0.98

0.97

0.96

0.95

0.92

0.91

0.90

0.89

RATING FACTOR

40.

Page 42: Technical 1554 cables specifications

0.85

0.80

0.75

0.70

0.65

0.60

0.55

0.50

SIZE OF CONDUCTOR IN SQ mm.

0 100 200 300 400 500 600

GR

OU

PR

AT

ING

FA

CT

OR

b) RATING FACTOR FOR VARIATION IN THERMAL RESISTIVITY OF SOIL

[TWO & THREE SINGLE CORE CABLES LAID DIRECT IN DUCTS]

v) RATING FACTORS FOR MULTIWAY DUCTS

Nominal Two Cables in two way ducts, For Value of Three Cables in Trefoil Ducts, For

Area of Thermal Resistivity of Soil C cm/W Value of Thermal Resistivity of Soil C cm/W

In Sq.mm.

i

(i) [FOR USE WHEN A MULTI WAY DUCT DOES NOT CONTAIN THE FULL NUMBER

OF LOADED ARMOURED CABLES]

3 WAY DUCT 6 WAY DUCT 9 WAY DUCT

NUMBER OF 1 2 4 5 7 8

LOADED CABLES

RATING FACTOR 1.15 1.07 1.10 1.04 1.10 1.05

O O

In Sq. mm.

1.5

2.5

4.0

6.0

10.0

16.0

25.0

35.0

50.0

70.0

95.0

120.0

150.0

185.0

240.0

300.0

400.0

(ii) RATING FACTORS FOR WIRE

ARMOURED CABLES IN MULTIWAY DUCTS

(To Be Applied rating of Corresponding

cables in single way duct to obtain

rating for cables in multiway duct)

100

1.07

1.07

1.07

1.07

1.07

1.08

1.08

1.09

1.09

1.09

1.10

1.10

1.10

1.10

1.11

1.12

1.12

120

1.04

1.04

1.04

1.04

1.04

1.04

1.04

1.05

1.05

1.05

1.05

1.05

1.05

1.05

1.06

1.06

1.06

150

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

200

0.96

0.96

0.96

0.96

0.95

0.94

0.94

0.94

0.94

0.94

0.93

0.92

0.92

0.92

0.92

0.92

0.91

200

0.94

0.94

0.94

0.94

0.93

0.92

0.92

0.92

0.92

0.91

0.91

0.91

0.91

0.91

0.91

0.90

0.90

250

0.91

0.91

0.91

0.91

0.90

0.89

0.88

0.87

0.87

0.82

0.86

0.85

0.85

0.85

0.85

0.85

0.85

250

0.87

0.87

0.87

0.87

0.86

0.86

0.85

0.85

0.85

0.85

0.84

0.84

0.84

0.84

0.83

0.83

0.83

300

0.83

0.83

0.83

0.83

0.82

0.81

0.80

0.80

0.80

0.79

0.79

0.78

0.78

0.77

0.77

0.76

0.76

300

0.86

0.86

0.86

0.86

0.85

0.84

0.83

0.83

0.83

0.83

0.82

0.81

0.81

0.80

0.80

0.80

0.79

100

1.10

1.10

1.10

1.10

1.10

1.10

1.10

1.11

1.12

1.12

1.13

1.13

1.14

1.15

1.15

1.15

1.16

120

1.05

1.05

1.05

1.05

1.05

1.05

1.05

1.06

1.06

1.06

1.06

1.06

1.07

1.08

1.08

1.08

1.08

150

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

41.41.

Page 43: Technical 1554 cables specifications

SP

AC

ING

SPACING

0.76

0.790.81

0.67

0.710.74

Ducts (Pipes)approximatelytouching30 cm45 cm

Spacing ofDucts (Pipes)

0.58

0.610.63

0.54

0.570.60

SP

AC

ING

SPACING

0.76

0.78

0.70

0.75

0.64

0.67

0.61

0.64

Ducts (Pipes)approximately

touching45 cm

Spacingof

Ducts

a) GROUP RATING FACTORS FOR TWIN & MULTICORE CABLES IN

SINGLEWAY STONEWARE DUCTS AND IRON PIPES IN TIER

FORMATION [Formation of Ducts (Pipes)]

b) GROUP RATING FACTORS FOR SINGLE CORE CABLES IN TREFOIL

STONEWARE DUCTS IN TIER FORMATION

[Formation of Ducts]

i) RATING FACTOR FOR VARIATION IN AMBIENT AIR TEMPERATURE :

AIR TEMPERATURE 25 30 35 40 45

IN DEGREE C

ii) RATING FACTOR FOR THREE SINGLE CORE CABLES (AC) IN FLAT FORMATION IN AIR

(To be applied to the corresponding rating for trefoil groups in air)

NOMINAL AREA OF CONDUCTOR MM RATING FACTOR

UPTO & INCLUDING 185 1.07

240 1.10

300 1.08

400 1.04

500 1.00

v) RATING FACTOR FOR DUCTS IN TIER FORMATION

C) CABLES INSTALLED IN AIR

2

RATING FACTOR 1.25 1.16 1.09 1.00 0.90

Page 44: Technical 1554 cables specifications

ARRANGEMENT NO. OF

RACKS

1

2

3

6

NO. OF CABLES PER RACK

25 mm d d

1 2 3 6 9

1.00 0.98 0.96 0.93 0.92

1.00 0.95 0.93 0.90 0.89

1.00 0.94 0.92 0.89 0.88

1.00 0.93 0.90 0.87 0.86

ARRANGEMENT NO. OF

RACKS

1

2

3

6

NO. OF CABLES PER RACK

25 mm

30 cm.1 2 3 6 9

1.00 0.84 0.80 0.75 0.73

1.00 0.80 0.76 0.71 0.69

1.00 0.78 0.74 0.70 0.68

1.00 0.76 0.72 0.68 0.66

iii) RATING FACTOR FOR MULTICORE LAID ON RACK IN AIR

a) WITH SPACING BETWEEN CABLES EQUAL TO DIAMETER OF CABLE.

b) WITH CABLE TOUCHING

43.

Page 45: Technical 1554 cables specifications

"PAGODA" OVERLOAD & SHORT CIRCUIT RATING

PVC Insulated Cables should not been operated even for comparatively short duration, at a temperature appreciably higher

than that permissible for continuous operation, since the PVC insulation is liable to soften at higher temperature and sustain

serious damage.

It is therefore essential that such cables should be continuously operated at the rated currents given in the tables only if they

are suitably protected against excess currents arising out of fault conditions. It is assumed that duration of such faults does not

exceed four hours and protection is considered to be adequate if minimum current at which the protective device is

designed to operate does not exceed 1.5 times the tabulated rating for cables laid in air and 1.3times the tabulated rating

for cables laid direct in ground.

If by the nature of the circuit protection, It is not possible to operate the cables at the rated current under the foergoing

provisions, the cable required for a given continuous load current should be so chosen as to have that rating of the tables,

which will not less than :-

a) The given continuous current, and

b) for cables in air and in ducts, 67% of the minimum current at which the excess current protection is designed to

operate. or

For cables laid direct in ground, 77% of the minimum current at which excess protection is designed to operate.

The Conductor Size in a cable for an installation is also governed by its abilities to carry short circuit current of the system. Short

Circuit Rating are based on the assumption that duration of the short circuit is to small and apparently that there is no

transmission of heat, produced during short circuit, through the insulation and the whole of it is absorbed by the conductor.

With a high increase in KVA, capacity in power distribution system, cables are expected to carry short circuit to carry short

circuit current of high magnitude. Normally rated at 70 C,Ourinsulationmaterial permitashort circuit temperature of160 C.

With high interrupting capacity expected of a cable under short circuit , it is essential that protective fuses in the system are

designedtominimisethedurationasfaraspossible.

TheShortCircuitRatingcanbecalculatedasunder:-

Ish = K X A

T

Ish: ShortCircuitCurrentinr.m.s.KiloAmps. T : DurationofShortCircuit inseconds.

A ; AreaofConductor inSq.mm.

K ; aConstant ForAluminiumwithgeneralpurposePVCInsulation- 0.0760

ForCopperwithgeneralpurposePVCInsulation- 0.115

ForAluminiumwithHeatResistingPVCInsulation- 0.0686

ForCopperwithHeatResistingPVCInsulation- 0.104

Short Circuit Rating

0 0

44.

Page 46: Technical 1554 cables specifications

CONDUCTOR

SIZE

ALUMINIUM CONDUCTOR COPPER CONDUCTOR

WITH

GENERAL

PURPOSE

INSULATION

WITH

GENERAL

PURPOSE

INSULATION

WITH

HEAT

RESISTING

INSULATION

WITH

HEAT

RESISTING

INSULATION

SHORT CIRCUIT RATING FOR ONE SECOND.

SHORTCIRCUITRATING

SQ.MM. K. AMPS. K. AMPS. K. AMPS. K. AMPS.

1.5 0.114 0.103 0.173 0.156

2.5 0.190 0.172 0.288 0.260

4.0 0.304 0.274 0.460 0.416

6.0 0.456 0.412 0.690 0.624

10.0 0.760 0.686 1.150 1.040

16.0 1.220 1.100 1.840 1.66

25.0 1.900 1.720 2.880 2.60

35.0 2.660 2.400 4.030 3.64

50.0 3.800 3.430 5.750 5.20

70.0 5.320 4.800 8.050 7.28

95.0 7.220 6.520 10.90 9.88

120.0 9.120 8.230 13.80 12.50

150.0 11.40 10.30 17.30 15.60

185.0 14.10 12.70 21.30 19.20

240.0 18.20 16.50 27.60 25.00

300.0 22.80 20.60 34.50 31.20

400.0 30.40 27.40 46.00 41.60

500.0 38.00 34.30 57.50 52.00

630.0 47.90 43.20 72.50 65.50

800.0 60.80 54.90 92.00 83.20

1000.0 76.00 68.60 115.0 104.00

45.

Page 47: Technical 1554 cables specifications

FORMULA FOR CALCULATING VOLTAGE DROP IN A BALANCED

3 PHASEAC DISTRIBUTION SYSTEM:-

VoltageDrop[rms]PerKm.PerPhase[volts]

= 3 x x X [Max. Continuous Current Rating]

X [D.C. Resistance Per phase Per Km.(Ohm/Km.)]

Where K = 1+a[T To]

a = 0.00393 for Copper

a = 0.004 for Aluminium

T = Max. Conductor Resistance [Degree C]

To = 20 Degree C Standard Temperature.

K = Factor For Converting DC Resistance to AC Resistance.

NOMINAL COPPER ALUMINIUM

CONDUCTOR AREA CONDUCTOR CONDUCTOR

IN SQ.MM.

1.5 to 95.0 1.000 1.000

120 1.010 1.003

150 1.015 1.005

185 1.022 1.008

240 1.038 1.014

300 1.062 1.020

400 1.100 1.038

500 1.150 1.060

C

T C

AC

-

APPROXIMATE VALUES OF K FOR 1100 VOLTS CABLES ARE GIVEN BELOW:-AC

K KT AC

46.

Page 48: Technical 1554 cables specifications

Recommendations For Storage & Installation Of Cables

i) No drum should be stored one above the other.

ii) Drum should be stored in perfectly ground without having any projected hard stones on the ground

surface. The drums should be stored preferably in the shed.

iii) Drums should be stored and kept in such a way that bottom cable does not get

iv) Drum should be always rotated in the "Direction Arrow Of Rotation"mark on the drum. In the absence of any

such mark, the drum should be rolled in the direction in the direction same as inside the cable end and

opposite that of outside end.

v) Loading and Unloading should be done with material handling equipment Only.

vi) While laying the cable in a trench the cable ends should be pulled with pulling eye only after mounting of

the drum on the jacks.

vii) 100% drums should be checked for continuity and cross continuity tests to ensure that there is no internal

damage to the cable during transportation.

viii) Insulation Resistance should be measured with 500 V Meggar between cores and all the cores to earth

[Armour].

ix) After the cables are installed, before commissioning, it should be test for high DC Voltage test. The

recommended volts and duration of the test between each core mettalic armour [Earth] at 3KV DC is for 5

minutes. During high voltage test all electrical equipments related to the cable installation must be earthed

and adequate clearance should be maintained from the other equipment and from work to prevent flash

over.

x) Where the cable to be joined with an existing cable, the sequence of cores at two ends to be joined should

be in opposite direction i.e. if at one ends it is clockwise direction, at the other end it should be in

anticlockwise direction . This is necessary to avoid the crossing of cores during jointing. This will also decide

the direction in which the cable is to be pulled.

xi) Avoid excessively high temperature when sealing of the cable joint of cable. Cool the sealing to avoid 100 C

beforepuring.

xii) Thecableshouldbe paidoff fromthe topof the cable drum,held inthenormalposition.Sufficientcareshould

betakentoprevent twists,accutebendsetc.whilelaying.

xiii) Thedispositionofcablesupport itsspacingshouldbesuch,astopreventunduestrainordamagetothecable.

xiv) TheminimumBendingRadiusforCablesshouldnotbelessthanthevaluesshown.

Wherererpossible25%highervalueshouldbeadopted.

i) 8XDiamerterforSingleCoreCable. ii) 12XDiameterformultiCoreCable

xv) MaximumPullingTensionduringInstallation: -

CablehavingAluminiumConductor -30N.Sq.mm.Max.

CablehavingCopperConductor -50N.Sq.mm.Max.

For easy and convenient installation conditions and desired performance, following

recommendation are made:

0

damaged.

47.

Page 49: Technical 1554 cables specifications

RECOMMENDED "PAGODA" CABLE SIZES

FOR MOTORS WITH START-DELTA STARTER

RECOMMENDED " CABLE SIZES

FOR MOTORS WITH DOL STARTERS

PAGODA"

415 V

50Hz

KW

Approx.

full load

current in

Amps

Phase

Current

in AmpsSupply

Side

Motor

Side

Supply

Side

Motor

Side

3 Phase

415 v

50Hz

HP

415 V,

50Hz

KW

Approx

full load

current in

AmpsAluminium

(sq. mm.)

2.2

3.75

5.50

7.50

9.30

11.0

15.0

18.50

22.0

26.0

30.0

33.5

37.0

44.0

48.5

52

55

67.5

75.0

90

110

132

150

175

187.5

204

225

300

5

7.5

11

14

18

21

28

35

40

47

55

60

66

80

87

94

100

120

135

165

200

230

275

320

323

360

385

500

2.88

4.32

6.34

8.10

10.02

12.10

16.0

20.20

23.0

27.0

30.30

34.6

35.0

45.0

50

54

57.5

69

78

95

115

133

159

184.50

185

206

222

300

1.5/2.5

1.5/2.5

2.5/4

4

4

6

10

16

16

25

25

35

35

50

70

70

70

95

95

120

185

240

300/400

300/400

400

500

500

630

1.5/2.5

1.5/2.5

1.5/2.5

1.5/2.5

2.5

2.5

4

6

6

10

16

16

16

25

35

35

35

50

50

70

70

120

150

185

185

185

240

300/400

1.5/1.5

1.5/1.5

1.5/1.5

2.5

2.5

4

6

10

10

16

16

25

25

35

50

50

50

70

70

95

120

185

240/300

240/300

240/300

300/400

300/400

400/500

1.5/1.5

1.5/1.5

1.5/1.5

1.5/1.5

1.5

1.5

2.5

4

4

6

10

10

10

16

25

25

25

35

35

50

50

95

120

150

150

150

185

240/300

0.50

0.75

1.0

1.5

2.0

3.0

4.0

5.0

6.0

7.5

10

12.5

15

17.5

20

25

30

35

40

45

50

60

75

90

100

150

200

225

0.40

0.55

0.75

1.1

1.5

2.2

3.0

3.75

4.5

5.5

7.5

9.3

11

13

15

18.5

22

26

30

33.50

37

44

55

67.5

75

110

150

168

1.2

1.6

1.8

2.6

3.5

5

6.2

7.5

9

11

14

18

21

24

28

35

40

47

55

60

66

80

100

120

135

150

175

200

1.5/2.5

1.5/2.5

1.5/2.5

1.5/2.5

1.5/2.5

1.5/2.5

1.5/2.5

2.5

2.5

4

4

6

6

10

10

16

25

25

25

35

35

50

70

95

95

185

300/400

300/400

Typical Cable Size Aluminium Typical Cable Size Copper Typical Cable Size

3 Phase

415 V

HP Copper

(sq. mm.)

3

5

7.5

10

12.5

15

20

25

30

35

40

45

50

60

65

70

75

90

100

125

150

175

200

240

250

275

300

400

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

2.5

2.5

4

4

6

6

10

16

16

16

25

25

35

50

70

70

150

240/300

240/300

Page 50: Technical 1554 cables specifications

49.

CURRENT FOR A/C MOTORSApprox. Amps per phase taken by modern induction motors, allowing reasonable efficiencies and power factors

B.H.P.

of

Motor

1/8

1/4

1/2

3/4

1

1

1

1

2

2

3

4

5

7

10

12

15

20

30

40

50

1.0

1.8

3.5

4.8

6.2

7.4

8.7

10.0

11.8

14.0

17.5

20.0

24.0

36.0

47.0

59.0

70.0

91.0

135.0

183.0

227.

0.6

1.1

2.0

3.0

4.0

4.8

5.7

6.3

7.0

8.2

9.5

12.0

14.0

21.0

27.0

34.0

40.0

53.0

78.0

105.0

130.0

0.6

1.3

2.5

3.3

4.0

4.8

5.5

6.8

7.0

8.5

10.0

12.0

14.0

21.0

26.0

32.0

38.0

51.0

75.0

100.0

120.0

0.3

0.7

1.2

1.5

2.0

2.5

3.0

3.2

3.5

4.3

5.0

6.5

7.0

10.0

13.0

15.0

19.0

25.0

38.0

50.0

60.0

0.3

0.7

1.2

1.7

2.0

2.5

2.8

3.2

3.5

4.3

5.0

6.5

8.0

12.0

15.0

19.0

22.0

29.0

42.0

56.0

71.0

0.3

0.6

1.0

1.3

1.5

1.9

2.2

2.5

2.8

3.6

4.2

5.5

7.0

10.0

13.0

16.0

19.0

25.0

36.0

47.0

58.0

0.4

0.8

1.5

1.9

2.2

2.7

3.0

3.5

4.0

5.0

6.0

7.5

9.0

13.0

17.0

21.0

25.0

33.0

48.0

63.0

79.0

0

0.6

1.0

1.7

2.2

2.5

2.8

3.2

4.0

4.5

6.0

7.0

11.0

14.0

18.0

21.0

28.0

39.0

53.0

66.0

Single Phase Two Phase Three Phase

230 Volts 230 Volts 346 Volts400 Volts 400 Volts 400 Volts 440 Volts 500 Volts

Page 51: Technical 1554 cables specifications

CONVERSION TABLEMultiplier

Constant

Miles to Millimeters (1000 Miles - 1 inch)

Inches to Centimetres

Yards to Metres

Miles to Kilometres

Sq. Inches to Sq. Millimetres

Circ. Miles to Sq. Millimetres

Circ. Miles to Sq. Inches

Sq. Yards to Sq. Metres

Pounds to Kilogrammes

Tons (2240 lbs.) to Kilogrammes

Cwt. to Kilogrammes

Ounces (Avolr) to Grammes

Gallons (Imp.) to Litres

Gallons (Imp.) to Cubic Inches

lbs./1000 Yards to lbs./Mile

Ohms/1000 Yards to Ohms/Mile

OHms/1000 Yards to Ohms/Km

Horse Power to Ft. Lb./Min...

Horse Power to Ft. Kilowatts..

Horse Power to Kg.m./Sec..

Watts Ft. lb./Min.

Watts to Kg.m./Sec.

Miles/Hour to Ft./Min.

Meters/Sec. to Ft./Min.

Land Miles to Nautical Miles

Temperature : F to C : Subtract 32 and Multiply by 5/9; C to F : Multiply by 9/5 and add 32.0 0 0 0

lbs./1000 Yards to-gm./Km.

lbs./Sq. Inch to-gm./mm2

0.0254

2.54

0.9144

1.6093

645.16

5.06.7 x 10

0.7854 x 10

0.08361

0.4536

1016.02

50.8

28.35

4.546

277.42

1.76

0.4961

703 x 10

1.76

1.0936

33000

0.746

76.0

44.24

0.1

88.0

197.0

0.868

-6

-6

-6

39.37

0.3937

1.0936

0.6214

0.00155

1937.5

1.273 x 10

1.196

2.2910

0.00098

0.01968

0.0353

0.22

0.003604

0.568

2.016

1422.33

0.568

0.9144

30.10

1.34

0.01316

0.022

10.0

0.01134

0.00508

1.151

6

-6

Reciprocal

of Constant

50.

Page 52: Technical 1554 cables specifications

GLOSSARY OF TERMS

A :

AC :

ABRASION :

RESISTANCE

ALLOY :

ACCELERATED :

AGEING

AMBIENT :

ALTERNATING :

CURRENT[A.C.]

AMPERE :

ANNEAL :

BENDING RADIUS :

BREAKDOWN :

VOLTAGE

BUNCH STRAND :

CAPACITIVE :

REACTANCE

CAPACITANCE :

COLOR CODE :

CONCENTRIC :

STRANDING

CONDUCTIVITY :

CONDUIT :

Ampere

Alternating Current

Ability of a Wire or Cable to resist surface wear.

A Combination of two or more different polymers or metal. Usually combined tomake use of different properties of each polymer or metal.

A test that simulates long time environmental condition in a relatively short time.

Condition existing at a test or operating location prior to to energizingequipments.

Electric Current that alternates or reverses polarity continuously. The numbers

of alternations per seconds are called as "Cycles" [Hertz or Hz.]

A standard unit of current and is defined as the amount of current that flows whenOne volt of emf is applied across one ohm of resistance. An Ampere of current is

produced by one coulomb of charge passing a point in one second.

To soften and relieve strains in any solid material such as metal by heating tojust below its melting point and then slowly cooling it . Annealing generallylowers the tensile strength of the material, while improving its elongation andflexibility.

Radius of curvature that a cable can bend without any adverse effect.

The Voltage at which the insulation between two conductor or one conductor &

the earth will fail and allow the electricity to conduct energy from one point toanother.

Conductors twisted together with same lay and direction.

The opposition of alternating current due to capacitance of a capacitor or cable. It

is measured in Ohms.

The ability of dielectric or insulation material between the conductors to storeenergy when a difference of potential exists between conductors. The unit ofCapacitance is Farads. Cable Capacitance is usually measured in Picofarads [pF]Per Mtr.

A system of different colours used to identify the components of cables such asConductor or group of conductors.

A group of uninsulated wired twisted together and containing a center core with

the subsequent layers spirally wrapped around the core with alternating laydirection to form a single conductor.

The ability of a material to allow electrons to flow, measured by current per unitof voltage applied. It is the reciprocal of resistivity.

A tube of metal or Plastic through which wire or cable can be run, used to protect

51.

Page 53: Technical 1554 cables specifications

the wire or cable from surroundings.

A Substance, usually metal Copper or Aluminium, used to transfer electricalenergy from point to point.

A very flexible insulated Cable.

A two wire transmit/receive interface.

Direct Current.

Electric Current that flows in one direction only.

An Insulating [ non conducting] medium when used in signal carrying design.

The Power dissipation in a dielectric as the result of friction produced bymolecular motion when an alternating field is applied.

The voltage which an insulation can withstand before it break down.

A number which indicates the quality of a material to resist holding an electricalcharge when placed between two conductors. It is based on a vacuum, which hasdielectric constant of 1.

: motion when an alternating field is applied.

Pertaining to static electricity, or electricity at rest.

Electromotive Force [Voltage]

The Capacity of doing work.

Loss of energy from a system due to conversion of work energy into undesirable

form usually heat. Dissipation of Electric Energy occurs when current flowsthrough a resistance.

The increase in length of a wire or cable caused by longitudinal tension.

A unit of capacity that will store one coulomb of electrical charge when one voltof electrical pressure is applied.

Composed of and/or containg iron. A ferrous metal exhibits magneticcharacterstics.

The ability of a material not to fuel a flame once the source of heat is removed.

The ability of a cable to bend in a short radius.

Flame Retardent Low Smoke.

The number of times a periodic actions occurs in one second.

An electrical connection between the circuit and earth.

Symbol used to designate current.

CONDUCTOR :

CORD :

CURRENT LOOP :

D C :

DIRECT CURRENT :

DIELECTRIC :

DIELECTRIC LOSS :

DIELECTRIC :

STRENGTH

DIELECTRIC :

CONSTANT

ELECTROSTATIC :

EMF :

ENERGY :

ENERGY :

DISSIPATION

ELONGATION :

FARADS :

FERROUS :

FLAME RESISTANCE :

FLEXIBILITY :

FRLS :

FREQUENCY :

GROUND :

I :

52.

Page 54: Technical 1554 cables specifications

IMPEDANCE :

INDUCTANCE :

INSULATION :

IR DROP :

LAY :

LAY DIRECTION :

LEAKAGE :

KILO :

KV :

KVA :

KW :

mA :

MEGA :

MHO :

MICRO :

MICRON :

MIL :

MILLI :

mV :

mW :

NANO :

NOISE :

PEAK :

The total opposition that a circuit offers to flow the alternating current or anyother varying current at a particular frequency.

The property of a wire which store electrical current in a magnetic field aroundthe wire. It is measured in Henrys.

A material having good dielectric properties which is used to separate theconductor from surroundings.

The designation of voltage drop in term of current and resistance.

The length measured along the axis of wire required for a single strand to makeone complete turn about the axis of conductor or cable. In a twisted pair cable,the lay length is the distance it takes for two wires to completely twist aroundeach other.

The direction of progreesive spiral twist in a cable while looking along the axis ofthe cable away from the observer. The lay direction can be left or right.

The undesirable passage of current over the surface of or through an insulator.

One Thousand [ 10 ]

Kilo Volts [ 1000 Volts.]

Kilo Volt Ampere.

Kilo Watt.

Milli Ampere.

Prefix Meaning Million.

Unit of Conductance equal to reciprocal of unit of resistance [Ohm].

Prefix meaning of One - millionth [ 10 ]

Millionth of a Meter.

A unit of length equal to one thousand of an Inch.

Prefix meaning One-thousandth [ 10 ].

Milli Volt.

Milli Watt.

One Billionth.

In a Cable or circuit, any extraneous signal which tends to interfere with thesignal normally present in or passing through the system.

The maximum instantaneous value of a vaying current or voltage.

3

-6

-3

53.

Page 55: Technical 1554 cables specifications

POWER :

POWER LOSS :

RATED :

TEMPERATURE

RATED VOLTAGE :

REACTANCE :

RESISTANCE [DC] :

RESISTANCE [AC] :

RMS :

PVC :

STRAND :

STRANDED :

CONDUCTOR

SHEATH :

THERMAL RATING :

TENSILE STENGTH :

TRANSMISSION LINE :

V :

VOLTAGE :

VOLTAGE DROP :

VOLTAGE RATING :

VSWR :

WALL THICKNESS :

WATT :

The amount of work per unit of time. It is expressed in Watts.

The difference between the total power delivered to a circuit or cable and powerdelivered by the circuit or cable.

The maximum temperature at which an electric component can operate for

extended period without loss of its basic properties.

The maximum voltage at which an electric component can operate for extendedperiod without undue degration or safety hazards.

A measure of combined effect of capacitance and inductance on an alternatingcurrent. The amount of such opposition varies with the frequency of current.

The opposition offered by a material to flow of current. It is expressed in Ohms.

The total opposition that a circuit offers to the flow of alternating current. It is thetotal effect of resistance, Inductance & Capacitance. It is expressed in Ohms.

Root Mean Square.

Poly Vinyl Chloride.

A Single Uninsulated Wire.

A Conductor composed of groups of uninsulated wires.

Pertaining to Twisted Insulated Conductors , the outer protection covering.

The Temperature in which a material will perform its function without undueDegration.

The pull stress required to break a bare wire or insulation.

An arrangement of two or more conductors used to transfer signal energy fromone location to another.

Volts.

Electrical Potential or electromotive force expressed in volts.

A Voltage loss occurring between any two points in a power transmission line.Such drop, Resistance, Reactance & leakage of the line.

The highest rating that may be continuously applied to a cable construction inconformance with the standard or specification.

Abbreviation for voltage standing wave ratio. It is the ratio of transferred signalvoltage as compared to reflected signal voltage measured along with the length oftransmission line.

The Thickness of Insulation or Sheath.

The unit of electrical Power.

54.

Page 56: Technical 1554 cables specifications