200
Tubular Centrifugal Fans
Model TCB
Inline - Horizontal or Vertical
Roof Upblast and Roof Supply
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 232
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 332
3
All TCB inline and roof mounted fans are available in two levels of construction to provide the most efficient and
economical selections Construction differences between level 1 and 2 selections include the impeller the inlet c
the shaft size and the bearings The housings for both levels are identical in material gauge and overall design
Model TCBRU mdashRoof Upblast Fanbull Sizes from 09 to 36
bull Performance Range 425 to 24000 c
(722 - 40750 msup3hr)
bull Static Pressure Up to 4 in wg (100
bull Max Operating Temperature 200degF
bull Options mdash Easy Access
mdash All Aluminum Construct
Easy Access Feature All models are available with an optional
oversized access door for serviceability o
components without removing the fan or See page 8 for details
Level 1 Constructionbull Maximum pressure capabilities of 2 in wg (500 Pa)
bull Highest efficiencies at static pressures below 15 in wg (375 Pa)bull Aluminum wheel construction
bull Most economical selections
Level 2 Constructionbull Maximum pressure capabilities of 45 in wg (1125 Pa)
bull Highest efficiencies at static pressures above 15 in wg (375 Pa)
bull Completely welded aluminum wheel
bull Increased shaft and bearing diameter
bull Increased horsepower and motor frame size capability
Two Levels of Construction
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 432
4
WindbandHood Panels
HousingCurb Cap
Housing
Model TCB Model TCBRUModel TCBRS
Steel Construction (gauge)
Aluminum Construction (thickness in inches)
Size Housing Curb Cap WindbandHood
Panels
Shaft Diameter (in)
Level 1 Level 2
09 12 12 20 22 3 frasl 4 1
10 12 12 20 22 3 frasl 4 1
12 12 12 20 22 3 frasl 4 1
13 12 12 20 22 3 frasl 4 1
16 12 12 20 22 1 13 frasl 16
18 12 12 20 22 1 13 frasl 16
22 10 12 20 22 1 17
frasl 16
24 10 12 20 22 1 111 frasl 16
30 10 12 20 22 11 frasl 4 115 frasl 16
36 10 12 20 22 11 frasl 2 115 frasl 16
Size Housing Curb Cap WindbandHood
Panels
Shaft Diameter (in)
Level 1 Level 2
09 0125 0125 0051 0051 3 frasl 4 1
10 0125 0125 0051 0051 3 frasl 4 1
12 0125 0125 0051 0051 3 frasl 4 1
13 0125 0125 0051 0051 3 frasl 4 1
16 0125 0125 0051 0051 1 13 frasl 16
18 0125 0125 0051 0051 1 13 frasl 16
22 0125 0125 0051 0051 1 17 frasl 16
24 0125 0125 0051 0051 1 111 frasl 16
30 019 0125 0051 0051 11 frasl 4 115 frasl 16
36 019 0125 0051 0051 11 frasl 2 115 frasl 16
Construction Specifications
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 532
5
Horizontal Base Mount
Fig 1
Horizontal Base MountMotor at 3 or 9 oclock position
Fig 2
OptionalMounting Rail
Horizontal Ceiling HungMotor at 3 or 9 oclock position
Fig 4
OptionaMounting R
Horizontal Ceiling Hung
Fig 3
Vertical Base Mount
Fig 5
Easy AccessOption
Easy AccessOption
Vertical Ceiling Hung
The Model TCB inline fan is the ideal choice for
ducted systems Greenheckrsquos standard fan can be
mounted in any position from horizontal to vertical
allowing installation in the smallest possible space
at the lowest installation cost The centrifugal wheels
used in this design provide higher efficiencies and
lower sound levels than propeller type inline fanswhen used in medium pressure ducted systems TCB
fans are available in either painted steel or aluminum
construction
Typical applications include
bull General exhaust or supply
bull Industrial space ventilation
bull Fume hood exhaust (special coatings are available)
bull Combustion air
bull Roof exhaust or supply (with weatherhood)
bull Restaurant grease exhaust
Universal Mounting
All TCB fans can be mounted horizontally or vertically For
ease of installation eight mounting brackets are welded
on each fan These eight brackets along with standard
mounting supports provide for Greenheckrsquos Universal
Mounting System
Fig 1 Horizontal Base Mount
Each fan is shipped as standard in this arrangement
Motor at 12 orsquoclock is standard
Fig 2 Horizontal Base Mount with Motor at
3 or 9 orsquoclock
A set of optional mounting rails are required for this
installation This is the base mounting position required with
the easy access option
Fig 3 Horizontal Ceiling Hung
In this installation the supports can be positioned for
mounting the motor at either 6 or 12 orsquoclock
Fig 4 Horizontal Ceiling Hung with Motor at3 or 9 orsquoclock
A set of optional mounting rails are required for this
installation
Fig 5 Vertical Mount
All TCB fans can be mounted vertically (ceiling hung or base
mount) for either upward or downward airflow Optional
mounting rails are recommended
NOTE
All fans are shown with optional vibration isolators See the
appropriate submittal drawings or installation manual for
complete dimensional data
TCB Inline Fan - Belt Drive
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 632
6 A
B
C
D
E
21 2
CBRU fans do
ot incorporate
rovisions for
nternal wiring
xternal wiring from
he roof to unit must
e provided by
thers
0 4 8 12 16 20 24
CFM x 1000
18
16
14
12
10
08
06
04
02
00
P r e s s u r e
L o s s ( i n
c h e s )
1 6
1 8
2 2
2 4
3 0 3 6
0 1 2 3 4
CFM x 1000
08
07
06
05
04
03
02
01
00
(
)
0 9
1 0
1 2
1 3
System Effect Curves
Sizes 9-13 Sizes 16-36
Dimensional Data
The TCBRU is ideal for roof upblast exhaust systems
with moderate system static pressures and for
applications where quiet operation is essential
Standard features include a necked-down windband
section which creates the high outlet velocities
necessary to carry contaminated exhausts away from
the roof deck All TCBRU fans include motor coversfor weather protection of the motor and drives gravity
operated dampers to prevent backflow into the
building and a welded curb cap for ease in mounting
to a roof curb TCBRU fans are available in either
painted steel or aluminum construction
Typical applications include
bull Low cfmhigh velocity exhaust
bull General exhaust
bull Fume hood exhaust
bull Industrial process exhaust
When selecting TCBRU fans use the TCB inline performance data
(pgs 12 to 31) along with the following system effect curves The
pressure loss determined below must be added to the extended
system static pressure to assure accurate selections Greenheckrsquos
Computer Aided Product Selection (CAPS) software will add these
system effects automatically
Size A B C D E Minimum CFMRequired to Open Dampers
09 22 211 frasl 2 23 45 20 425
10 22 211 frasl 2 23 45 20 425
12 22 211 frasl 2 23 45 20 1250
13 4 231 frasl 2 241 frasl 2 50 1 frasl 2 24 1800
16 28 25 1 frasl 2 28 1 frasl 2 53 28 2030
18 34 28 1 frasl 2 31 571 frasl 2 30 2570
22 40 34 35 1 frasl 2 64 34 2740
24 46 36 1 frasl 2 42 74 1 frasl 2 40 4760
30 52 42 1 frasl 4 481 frasl 2 84 46 6600
36 58 451 frasl 2 54 94 1 frasl 2 52 8700
All dimensions shown in inches
TCBRU Roof Upblast Fan
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 732
7
A B
C
D
W
21 2 in
L
Hood End View Hood Side View
TCBRS fans donot incorporateprovisions for internal wiring
External wiring fromthe roof to unit mustbe provided byothers
0 4 8 12 16 20 24
CFM x 1000
0 9
1 0
1 2
1 3
1 6
1 8
2 2 2
4
3 0
3 6
018
016
014
012
010
008
006
004
002
000
P r e s s u r e
L o s s ( i n c h e s )
System Effect Curves
Dimensional Data
The TCBRS roof mounted supply fan is designed
for intake air systems with pressures up to 4 inches
of wg and where low sound is required The TCBRS
hood intake is located at a sufficient height above
the roof to limit entry of roof debris and snow In
addition the hood has sufficient intake area to keep
velocities low Filters are available to collect dustand moisture before entering the building Motor
and drive protection is provided with a weatherproof
motor cover For ease of installation TCBRS fans are
shipped assembled and have curb caps for attaching
to roof curbs TCBRS fans are available in either
painted steel or aluminum construction
Typical applications include
bull Ducted supply systems
bull Industrial space supply
bull Filtered supply
TCBRS fan selections can be made using the TCB inline
performance data (pgs 12 to 31) along with the following
system effect curves The pressure loss determined to the
left must be added to the external system static pressure
to assure accurate selections Greenheckrsquos Computer
Aided Product Selection (CAPS) software will add thesesystem effects automatically
Size A B C D L W
09 22 211 frasl 2 251 frasl 2 391 frasl 2 39 46
10 22 211 frasl 2 251 frasl 2 391 frasl 2 39 46
12 22 211 frasl 2 251 frasl 2 391 frasl 2 39 4613 24 231 frasl 2 27 431 frasl 2 39 54
16 28 25 1 frasl 2 31 471 frasl 2 51 55
18 34 28 1 frasl 2 331 frasl 2 50 63 64
22 40 34 38 1 frasl 2 59 75 73
24 46 36 1 frasl 2 45 67 1 frasl 2 87 82
30 52 42 1 frasl 4 52 1 frasl 2 76 99 88
36 58 45 1 frasl 2 58 851 frasl 2 111 88
All dimensions shown in inches
TCBRS Roof Supply Fan
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 832
8
Optional Construction Features
Aluminum Construction
Aluminum construction is available on the TCB TCBRU and TCBRS Aluminum fans are an excellent choice for
applications involving moisture or coastal installations
Easy Access Construction
The Easy Access option is highly recommended to allow forinspection cleaning and service of internal fan components
By removing one access panel service to the wheel shaft
and bearing assembly is possible without removing duct
connections In addition all internal fan components can be
removed from the fan through the easy access panel
Easy Access construction is available on all levels and sizes
of TCB TCBRU and TCBRS Easy Access is also available
with aluminum fan construction
The Easy Access panel is located 180deg from the motor
position
Standard Construction Features
Inlet amp Outlet Flanges
Flanged inlets and outlets with mounting holes are
provided for duct connections (TCB only)
Housing
Housings are continuously welded steel and coated
with Permatector trade
Protective Coating
All steel constructed units are coated with
Permatectortrade a thermosetting polyester urethane
Aluminum units are uncoated
Type B Spark Resistance
All fans have aluminum wheels and a nonferrous
(aluminum) rub ring which surrounds the fanshaft where it passes through the drive cover
This construction meets Type B spark resistant
requirements
Bearings
Standard bearings are grease lubricated self-aligning
ball type in pillow block mounts Bearings are selected
for a minimum L10 life in excess of 80000 hours (L50 average life of 400000 hours) at maximum cataloged
operating speeds
Belt amp Bearing Tube
Belts bearings and drives are protected from the
airstream by heavy gauge belt tubes and bolted
bearing covers with shaft seals
Extended
Lube Lines
Lubrication lines with grease
fittings allow bearing lubricationwithout disassembling the fan
TCB - 1 - 24 - 30Tubular CentrifugalBelt Drive
TCB - Inline FanTCBRU - Roof Upblast FanTCBRS - Roof Supply Fan
Level of Construction1 or 2
Motor Horsepower
4 = 1 4 30=3 3 = 1 3 50=5
5 = 1 2 75=7 1 2
7 = 3 4 100=10
10=1 150=15
15=11 2 200=20 20=2
Fan Size09-36
Model Number CodeThe model number system is designed to completely identify
the fan A detailed explanation of the model number code for
TCB fans is shown below
Construction Features
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 932
9
Inline grease exhaust fans are excellent alternative for kitchen applications when roof or wall mounted ventilators
are not practical The TCB with UL 762 grease option is designed to withstand the demands of high temperature
kitchen grease exhaust and high-pressure duct washes
Continuously welded housing and integral duct flanges
provide air and water tight design
Bearing cover gasketed and includes a labyrinth shaft seal
to prevent moisture leakage during normal operation and
while cleaning with high pressure solvents
Continuously welded belt tube keeps the belts and
bearings clean
Two threaded drain connections are located 90deg from the
motor location to allow for removal of grease and moisture
UL 762 is concerned with fans
designed for removal of smoke and
grease laden vapors with airstream
temperatures up to 300degF
bull Meets all UL 705 Requirements
bull Bolted Access Door
bull Drain Connectionbull Meets requirements of NFPA 96
Ventilation Control and Fire
Protection of Commercial
Cooking Operations
Listed Power
Ventilation for
Restaurant
Exhaust Appliances
13G3
Maximum
Operating
Temperature
300degF
The TCB inline grease fan is tough to beat when
packaged with our full line of kitchen hoods and grease
extraction options Take advantage of Greenheckrsquos
expertise in providing a total solution in kitchen
ventilation equipment
A Tough Package to Beat
Leak Resistant Construction Features
bull Inline grease exhaust fans should be installed near the end of the duct run to reduce sound at the hood
bull Inline fan must be securely bolted to the exhaust duct per NFPA-96 guidelines Greenheckrsquos companion flange
are recommended for ease of installation
bull Grease exhaust fans and ductwork must maintain 18 inches (46 cm) minimum clearance to combustible
material If the ductwork and fan are insulated the inspection door must be accessible for maintenancebull A minimum of 10 ft (30 m) of clearance must be kept from the fan outlet to adjacent buildings property lines
or the closest point of any air intake or operable window at or below the plane of the exhaust termination
bull Greenheck recommends that all inline grease applications be reviewed by your local code official to ensure
compliance with NFPA IMC and other local codes
System Design Guidelines
1
2
3
4
5
6
7
Mounting and Serviceability Features
4 6
7
5 14
Optional Construction forUL 762 Restaurant Exhaust
Universal mounting brackets allow for rotation of the motor to
the 3 or 9 orsquoclock position at the jobsiteDuct flanges and access door bolt locations are no more
than 4 inches (100 mm) on center per NFPA 96
ldquoEasy Access Doorrdquo provides access for duct cleaning and allows removal of the wheel
shaft and bearings for maintenance Gasket is rated for 400degF (200degC) and prevents
leakage during operation [Fan is rated for 300degF (149degC) continous operation]
Air1047298ow
Duct to heat source
Ambient temperaturenot to exceed 120ordmF
Wall andor ceiling should enclosefan when used for emergency heatand smoke exhaust Enclosure shallbe per NFPA 96 or local building codes
Roof
Cooling air fordrives andbearings
Minimum ductat discharge
To buildingexterior
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1032
10
Electrical Accessories
Belt Guard (TCB only) Belt guards are totally enclosed to provide protection
from rotating pulleys and belts Belt guards meet
OSHA guidelines
Motor Cover (Weatherhood) Weatherproof motor covers shield the motor and
drive components from dust dirt and moisture when
used in outdoor applications Motor covers also
provide protection from rotating pulleys and belts and
meet OSHA guidelines Motor covers are standard on
TCBRU and TCBRS models
Inlet and Outlet Companion Flanges
(TCB only) Companion inlet flanges and outlet flanges with
prepunched holes are available for all fan sizes in
painted steel construction
Inlet and Outlet Guards (TCB TCBRU)
Removable inlet and outlet guards provide protectionfor personnel and equipment in non-ducted
installations These guards meet OSHA guidelines
TCBRU fans are available with outlet screens to
shield the fan discharge and damper from debris
Inspection Door Bolted or hinged doors provide access for cleaning or
inspection
Inspection Section (TCB only) Inspection sections serve as a length of duct that can
be easily removed to provide for complete access to
the fan for servicing Each section includes a bolted
inspection door
Isolators (TCB only) Both base mount or hanging isolators are available in
either neoprene or spring mounts The isolators are
furnished in sets of four and are sized to match the
weight of each fan
Mounting Rails (TCB only) Mounting rails are required for horizontal mounting
of TCB fans when the motor is to be located in
the 3 or 9 orsquoclock position Mounting rails are also
recommended for all vertically mounted inline fans
See page 5 for additional details
Protective Coatings Greenheck has a wide offering of protective coatings
Consult Greenheckrsquos Product Application Guide
FA110-04R4 Performance Coatings for Ventilation
Products for a complete listing of coatings and a
relative resistance chart
Inlet Vane Dampers (TCB only) Nested inlet vane dampers for controlling air volume
are available on model TCB inline fans with Level 2
steel construction in fan sizes 12 through 36
Birdscreen Insect Screen (TCBRS only)
TCBRS fans are available with either aluminum insectscreen or birdscreen at the hood intake (Birdscreen is
standard)
Roof Curbs (TCBRU TCBRS) Prefabricated roof curbs are available to reduce
installation time and costs by ensuring compatibility
between the fan the curb and the roof opening
All curbs are lined with fiberglass insulation to
prevent condensation and reduce sound levels See
Greenheckrsquos Roof Curb Extensions and Equipment
Supports catalog for complete details
Washable Aluminum Filters (TCBRS only)
Helps trap dust and dirt before it enters the fanFilters can be removed for cleaning
Enclosure Application Toggle Heavy Duty
NEMA-1 Indoor General Purpose Yes Yes
NEMA-12 Indoor DustDrip Tight Yes YesNEMA-3R IndoorOutdoor Rainproof Yes Yes
NEMA-4 IndoorOutdoor Watertight Yes Yes
NEMA-4X IndoorOutdoor Watertight
(Corrosion Resistant) Yes Yes
NEMA-7 amp 9 Indoor Hazardous Locations Yes No
Toggle type and heavy duty disconnect switches are available for positive
electrical shut-off and safety in servicing fans The following switches are
available to meet individual electrical requirements
Accessories
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1132
11
Inspection
Section
Outlet Guard
Belt Guard
Motor Cover
Companion Flange
(Outlet)NeopreneIsolator
Spring Base
Isolator
Inspection
Door
Easy Access
Inlet Guard
CompanionFlange (Inlet)
Mounting Rails
Spring HangingIsolator
Isolator Neoprene Hanging
Accessories (Model TCB shown)
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
12
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
360 195846 002 999 003 1260 006
53 60 75
420 228941 003 1071 004 1314 007 1526 011
57 63 77 92
480 2601040 004 1155 005 1380 009 1576 012 1758 017
63 68 80 93 106
540 2931144 005 1245 006 1449 010 1635 014 1807 019 1968 023 2115 028
71 74 84 95 107 120 133
600 326
1250 006 1341 008 1523 012 1704 016 1865 021 2017 026 2163 031 2298 036
78 81 88 99 110 122 135 147
660 3581357 007 1439 009 1606 014 1774 018 1930 023 2074 029 2212 034 2346 040 2472 046
86 88 93 104 114 126 137 149 162
720 3911465 009 1542 011 1692 016 1845 021 1999 026 2137 032 2270 038 2395 043 2520 050
94 96 100 109 120 131 140 150 163
780 4231576 012 1647 014 1786 018 1928 024 2069 029 2206 035 2331 041 2454 047 2570 054
102 104 108 115 127 136 145 154 165
840 4561688 014 1752 016 1882 021 2012 027 2142 033 2276 039 2400 045 2515 052 2629 059
110 112 117 123 133 142 150 160 170
900 4891801 017 1859 019 1980 025 2100 030 2225 036 2347 043 2469 050 2584 056
120 122 127 133 139 148 157 166
960 5211914 020 1966 023 2081 028 2195 034 2310 040 2424 047 2540 054
130 132 140 142 147 154 164
1020 5542028 024 2075 026 2184 032 2292 038 2395 044 2507 052 2612 059
144 149 150 151 155 163 172
1080 5862141 028 2186 031 2288 037 2389 043 2490 050 2592 057
159 159 160 162 166 172
1140 6192255 033 2298 036 2394 042 2487 049 2585 055
169 169 171 174 178
1200 6522370 038 2410 041 2500 047 2590 054
179 180 183 186
TCB-1-09 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2645
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm3114)3
Max Motor Frame Size - 56
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
13
TCB-2-09 Level 2 Construction
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3330)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg
025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
400 2171198 005 1460 008 1893 018
73 87 119
480 2601332 006 1566 010 1971 020 2309 032
82 96 127 157
560 3041480 009 1686 013 2059 024 2386 036 2671 049
92 106 135 165 191
640 3471635 011 1818 016 2158 027 2469 041 2749 055 3000 070 3228 086
106 117 146 174 20 23 25
720 3911799 015 1958 020 2275 032 2562 045 2830 061 3078 077 3305 094 3514 112
120 130 158 183 21 23 25 28
800 4341966 020 2108 025 2397 037 2666 051 2921 067 3158 085 3383 103 3591 121 3786 141
134 145 169 183 22 24 26 28 31
880 4782135 025 2262 030 2528 043 2784 058 3015 074 3250 093 3464 112 3669 132 3863 152
151 162 182 21 23 25 27 29 32
960 5212308 032 2425 037 2665 050 2905 066 3132 083 3343 101 3555 121 3752 142 3942 164
168 176 196 22 24 26 28 31 33
1040 5652482 039 2590 045 2810 059 3033 075 3251 093 3453 111 3648 131 3844 153 4027 176
184 193 21 23 25 27 29 32 34
1120 6082658 048 2757 054 2960 068 3168 085 3372 103 3571 123 3754 143 3937 165
20 21 23 25 27 29 31 33
1200 6522835 058 2925 065 3113 079 3306 096 3501 115 3691 135 3872 157 4041 179
22 23 24 26 28 30 32 35
1280 6953012 070 3095 076 3271 091 3453 109 3636 128 3813 149 3991 171
24 25 26 28 29 32 34
1360 7393190 083 3269 090 3434 105 3603 123 3773 143 3945 164
26 26 28 29 31 34
1440 7823368 097 3444 105 3599 121 3756 139 3917 159
28 28 30 31 33
1520 8263547 114 3619 121 3765 138 3909 156
30 30 32 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
14
TCB-1-10 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2555
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm2760)3
Max Motor Frame Size - 143T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
480 260858 003 1011 005 1253 009
49 57 73
560 304947 004 1089 006 1321 011 1511 015
55 63 77 93
640 3471042 005 1171 008 1394 013 1578 018 1740 023 1892 029
63 70 82 96 112 133
720 3911141 007 1259 009 1470 015 1649 021 1806 027 1949 033 2079 039
72 76 89 100 115 132 150
800 4341239 009 1349 012 1548 018 1723 024 1876 031 2015 037 2144 044 2263 051
80 84 96 107 119 135 148 161
880 4781340 011 1444 014 1630 021 1798 027 1949 034 2084 042 2211 049 2329 057 2440 064
88 92 102 113 125 137 150 162 176
960 5211441 014 1541 017 1716 024 1876 031 2023 039 2157 047 2280 055 2396 063 2506 071
97 101 109 121 133 141 152 165 179
1040 5651544 017 1640 021 1805 028 1957 035 2099 044 2231 052 2352 060 2465 069
105 109 117 129 139 148 157 169
1120 6081648 021 1739 025 1895 032 2042 040 2178 049 2306 058 2426 067 2538 076
113 117 127 138 146 155 165 177
1200 6521752 025 1839 029 1989 037 2129 046 2259 055 2383 064 2501 073
122 126 137 145 153 163 175
1280 6951858 030 1940 034 2085 043 2218 052 2343 061 2464 071
132 137 145 152 162 173
1360 7391964 035 2041 040 2183 049 2308 058 2430 068 2545 078
145 149 154 162 172 183
1440 7822071 041 2144 046 2282 056 2401 066 2519 076
156 158 164 173 183
1520 8262177 048 2247 053 2380 064 2497 074
164 167 175 184
1600 8692285 056 2351 061 2479 072
173 177 185
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
15
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-10 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3120)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 3261300 007 1504 011 1875 021 2213 032
73 82 105 132
700 3801453 010 1630 014 1966 024 2273 036 2560 049
84 91 110 133 156
800 4341611 013 1768 018 2070 029 2355 042 2619 055 2872 070 3102 086
100 101 118 137 158 182 20
900 4891773 017 1917 023 2188 034 2448 048 2698 062 2932 078 3160 094 3371 111 3568 129
112 113 127 143 162 185 20 22 25
1000 543
1937 023 2071 029 2319 041 2559 055 2790 070 3011 086 3220 103 3430 122 3626 140
124 127 136 152 170 190 21 23 25
1100 5972104 029 2228 035 2457 048 2677 063 2892 079 3103 096 3303 114 3490 132 3685 152
138 143 146 161 179 195 21 23 25
1200 6522276 036 2389 043 2601 057 2807 073 3009 089 3199 107 3394 125 3578 145 3751 165
154 154 159 172 189 20 21 23 25
1300 7062449 045 2552 052 2753 067 2944 083 3128 101 3315 119 3488 138 3670 159 3841 180
164 166 172 183 195 21 22 24 25
1400 7602623 055 2717 062 2907 079 3083 095 3261 114 3433 133 3603 153 3763 173 3933 196
175 177 185 193 20 21 23 24 26
1500 8152797 066 2883 074 3063 092 3231 109 3398 128 3557 148 3721 169 3878 191 4026 212
186 189 197 20 21 22 23 25 26
1600 8692973 079 3052 087 3223 106 3384 125 3537 144 3693 165 3840 186 3995 209
198 20 21 21 22 23 24 25
1700 9233149 094 3224 103 3384 122 3538 142 3683 162 3831 184 3974 206
21 21 22 22 23 23 25
1800 9783325 110 3396 119 3546 140 3693 161 3834 182 3970 204
22 22 23 23 24 24
1900 10323502 129 3570 138 3710 159 3852 182 3988 204
23 24 24 25 25
2000 10863679 149 3744 159 3875 181 4012 204
25 25 25 26
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
16
TCB-1-12 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2490
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 3436
Maximum bhp at a given rpm mdash (rpm2202)3
Max Motor Frame Size - 145T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 0075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
700 380853 006 958 008 1158 014 1345 021 1518 028
62 66 79 94 110
800 434943 008 1042 011 1218 017 1386 024 1551 031 1703 040
66 70 83 96 111 125
900 4891037 010 1128 013 1287 020 1442 027 1587 035 1736 044 1873 053 2000 063
71 76 87 99 112 126 142 155
1000 5431132 013 1216 017 1363 024 1506 031 1643 040 1771 049 1906 059 2033 069 2151 079
78 83 91 103 115 128 143 156 170
1100 597
1229 016 1305 020 1447 028 1574 036 1702 045 1827 055 1943 065 2066 075 2183 086
86 89 96 108 120 133 144 157 171
1200 6521326 020 1398 025 1532 034 1649 042 1769 051 1884 061 1999 071 2105 082 2216 094
92 95 103 113 126 139 149 159 173
1300 7061426 025 1492 030 1619 039 1732 049 1839 058 1950 068 2055 079 2161 090 2260 102
98 102 112 121 134 145 154 164 176
1400 7601526 031 1588 036 1707 046 1817 056 1916 066 2019 076 2120 088 2217 099 2316 111
106 112 122 132 142 151 160 170 181
1500 8151627 037 1684 042 1796 053 1903 064 1999 075 2089 085 2188 097 2281 109 2372 121
119 125 135 144 149 157 167 176 187
1600 8691729 044 1781 050 1886 061 1990 073 2084 085 2170 096 2258 107 2350 120 2436 133
134 139 150 153 157 165 174 183 194
1700 9231830 053 1879 058 1980 070 2077 083 2170 095 2254 107 2334 119 2419 132
151 157 159 162 167 173 181 191
1800 9781932 062 1978 068 2074 080 2166 093 2256 107 2339 120 2417 132
166 166 168 171 176 182 190
1900 10322034 072 2078 078 2169 091 2256 105 2343 119 2425 133
173 173 176 180 185 192
2000 10862137 083 2179 090 2265 103 2348 118 2432 133
180 181 184 189 195
2100 11412240 096 2280 102 2361 117 2442 132
187 188 192 198
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
17
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-12 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 3274
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 321
Maximum bhp at a given rpm mdash (rpm2315)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
750 4071009 008 1226 014 1587 027
55 67 98
900 4891119 011 1315 018 1648 032 1936 049 2182 067
63 76 102 131 159
1050 5701238 015 1419 023 1728 039 1995 056 2240 076 2456 096
75 85 110 136 164 190
1200 6521363 020 1529 029 1813 046 2070 065 2299 085 2514 108 2710 131 2890 155
89 96 120 142 169 195 22 24
1350 733
1495 027 1643 036 1911 055 2151 076 2372 097 2574 120 2768 145 2948 171 3115 197
104 111 132 152 176 20 22 25 28
1500 8151630 034 1764 044 2018 066 2240 088 2452 111 2647 135 2828 160 3007 187 3174 216
120 129 145 166 186 21 23 26 29
1650 8961767 044 1887 054 2127 077 2338 101 2534 126 2727 151 2903 178 3067 205 3233 235
139 144 159 184 199 22 24 27 30
1800 9781908 055 2018 066 2239 090 2445 117 2630 143 2808 170 2983 198 3145 227
159 165 180 199 22 23 25 28
1950 10592053 068 2151 079 2356 105 2554 134 2731 162 2900 190 3064 220 3225 250
182 188 20 22 23 25 27 29
2100 11412198 083 2286 095 2477 122 2664 152 2839 183 2997 213 3154 244
21 22 22 23 25 27 29
2250 12222344 100 2423 113 2599 141 2777 173 2948 205 3104 238 3250 271
24 24 25 26 27 29 32
2400 13042490 119 2560 133 2726 163 2896 196 3058 230 3212 265
26 26 27 28 30 32
2550 13852637 141 2703 156 2858 187 3016 221 3169 257
28 29 29 31 32
2700 14672785 166 2847 181 2991 214 3138 248
31 31 32 34
2850 15482933 193 2992 209 3126 243 3262 279
34 34 35 37
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
18
TCB-1-13 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2355
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 3435
Maximum bhp at a given rpm mdash (rpm2119)3
Max Motor Frame Size - 145T
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 265660 003 792 005 1019 010
41 51 69
750 331760 005 874 007 1073 013 1254 019
48 58 71 84
900 398864 007 967 010 1146 016 1305 023 1459 030
58 64 75 86 102
1050 464973 009 1067 013 1230 020 1378 027 1512 036 1646 044 1770 053
66 70 80 91 103 120 140
1200 530
1085 013 1171 017 1321 024 1457 032 1585 041 1703 051 1820 061 1933 071 2039 081
72 77 86 96 108 120 136 153 172
1350 5971199 017 1277 022 1419 030 1545 039 1662 048 1777 058 1883 069 1984 080 2089 091
81 85 94 103 114 125 136 151 167
1500 6631316 023 1387 027 1520 037 1637 046 1749 059 1853 067 1957 078 2054 090 2146 102
90 94 102 112 122 132 143 155 169
1650 7301434 029 1499 034 1623 044 1736 055 1839 065 1940 077 2034 088 2128 100 2219 113
100 104 113 123 132 143 153 165 178
1800 7961552 037 1613 042 1729 054 1836 065 1935 076 2029 088 2121 100 2207 113 2293 126
112 115 125 134 144 154 165 177 190
1950 8621672 045 1728 052 1836 064 1939 076 2034 088 2123 100 2209 113 2294 127
124 129 138 147 156 167 178 190
2100 9291792 056 1844 062 1947 076 2044 089 2135 102 2221 115 2302 128
138 142 151 161 170 181 192
2250 9951913 067 1962 075 2058 089 2150 103 2238 117 2321 131
152 157 167 177 186 196
2400 10612034 081 2080 088 2171 104 2258 119 2342 133
169 174 184 194 20
2550 11282155 095 2199 104 2285 120
187 192 20
2700 11942277 112 2319 121
21 21
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
19
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
TCB-2-13 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2971
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 353
Maximum bhp at a given rpm mdash (rpm1933)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
800 353828 008 1026 014 1379 030
38 56 104
1000 442934 011 1108 018 1418 035 1692 055
44 60 101 135
1200 5301048 016 1206 024 1479 042 1731 064 1961 087
58 72 101 130 165
1400 6191171 022 1313 031 1562 051 1784 073 2002 099 2201 126 2391 155
75 87 106 128 160 189 22
1600 707
1300 030 1424 040 1657 062 1865 086 2053 112 2247 141 2425 171 2596 203 2759 237
97 100 115 133 156 184 21 24 27
1800 7961431 039 1545 051 1759 075 1950 101 2134 129 2300 157 2472 189 2636 223 2790 258
114 113 125 144 160 181 21 24 26
2000 8841565 051 1669 063 1868 090 2050 118 2217 148 2381 178 2531 210 2683 244 2836 282
127 127 137 157 170 186 21 23 26
2200 9731700 064 1797 078 1979 107 2152 138 2312 169 2464 202 2612 236 2750 270 2883 306
142 145 156 169 183 198 21 23 26
2400 10611836 081 1928 096 2097 127 2260 160 2413 194 2556 228 2695 264 2831 301 2959 338
164 169 174 182 197 21 23 24 26
2600 11501975 100 2060 116 2219 150 2371 185 2517 221 2656 257 2785 295 2914 334
190 192 193 196 21 23 24 26
2800 12382115 122 2194 140 2343 175 2484 212 2626 251 2758 290 2885 330
21 21 21 22 23 24 26
3000 13272256 148 2329 166 2470 204 2605 243 2737 284 2864 325
24 24 24 24 25 26
3200 14152397 177 2464 196 2600 236 2728 278 2849 320
26 26 26 27 27
3400 15042539 210 2601 230 2731 272 2852 316 2969 361
29 29 30 30 30
3600 15922681 247 2739 267 2863 312
33 33 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
20
TCB-1-16 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2000
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 4384
Maximum bhp at a given rpm mdash (rpm1378)3
Max Motor Frame Size - 182T
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1000 308507 005 612 009 802 017
37 43 59
1250 385584 008 671 012 833 021 985 032
45 49 62 81
1500 462668 011 743 016 884 026 1016 038 1145 052
54 58 69 84 103
1750 540755 016 821 021 944 032 1065 045 1176 059 1289 075 1392 091
64 68 79 93 105 120 136
2000 617
844 022 904 028 1014 040 1119 054 1225 069 1322 085 1422 102 1517 120 1605 139
76 81 92 104 113 124 140 157 175
2250 694934 030 989 036 1090 049 1185 064 1278 080 1373 097 1460 115 1547 134 1635 154
89 94 107 114 123 133 146 161 179
2500 7711026 039 1077 047 1169 061 1257 076 1342 092 1425 110 1511 130 1591 149 1666 170
104 110 119 126 134 144 156 169 184
2750 8481118 051 1166 059 1252 074 1334 091 1411 107 1489 126 1564 146 1643 167 1717 188
121 124 131 138 147 157 168 181 194
3000 9251210 064 1256 073 1337 090 1412 107 1486 125 1556 144 1627 165 1695 186 1769 209
134 138 145 152 161 171 183 194 21
3250 10031303 080 1347 090 1423 108 1494 127 1563 146 1630 166 1695 186 1760 209 1823 232
149 153 161 169 177 187 199 21 22
3500 10801397 098 1438 109 1511 128 1578 148 1642 169 1706 190 1768 211 1828 233 1889 258
166 170 179 187 195 21 22 23 24
3750 11571491 119 1530 130 1599 152 1663 173 1725 194 1784 216 1844 239 1900 262 1956 286
185 189 197 21 22 23 24 25 27
4000 12341585 143 1622 155 1689 178 1750 200 1809 223 1865 246 1921 270 1976 295
20 21 22 23 24 25 26 28
4250 13111680 170 1714 183 1779 207 1838 231 1893 255 1948 280 1999 304
23 23 24 25 26 28 29
4500 13881775 200 1807 214 1869 240 1926 265 1979 291
25 26 27 28 30
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
21
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
TCB-2-16 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2431
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 432
Maximum bhp at a given rpm mdash (rpm1406)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1200 370668 011 842 020 1137 041
46 61 104
1500 462749 015 899 025 1166 049 1395 077
55 68 102 138
1800 555843 021 969 033 1208 059 1424 089 1616 121
71 77 104 135 168
2100 648944 030 1053 042 1268 071 1461 103 1647 138 1813 175 1972 215
83 88 111 134 166 196 22
2400 740
1047 040 1144 054 1336 085 1518 120 1684 157 1847 197 1996 238 2140 283 2275 329
99 105 120 140 166 195 22 25 27
2700 8331152 053 1243 068 1412 101 1579 139 1739 179 1885 221 2033 266 2169 312 2297 359
116 122 132 150 171 195 22 25 28
3000 9251260 069 1345 086 1498 121 1651 161 1799 204 1941 248 2070 295 2206 344 2333 394
132 136 144 162 182 20 23 25 28
3300 10181373 089 1448 107 1588 144 1727 186 1866 231 2001 279 2129 328 2247 379 2370 432
147 151 161 177 195 22 24 26 29
3600 11111486 112 1553 131 1686 171 1813 215 1939 262 2065 312 2188 365 2306 418 2416 473
166 171 182 193 21 23 25 28 30
3900 12031600 140 1658 159 1786 202 1900 247 2020 297 2138 349 2252 404 2366 461
189 194 20 21 23 25 27 29
4200 12961715 172 1766 191 1888 238 1996 285 2106 336 2213 390 2324 448 2430 508
21 21 22 23 24 26 29 31
4500 13881831 208 1878 228 1990 277 2095 328 2193 380 2298 437 2398 496
23 23 24 25 27 28 31
4800 14811946 250 1992 271 2094 322 2196 376 2289 430 2385 488
25 26 27 28 29 31
5100 15742062 296 2105 319 2199 371 2297 429 2388 486
28 28 29 30 32
5400 16662179 349 2219 373 2305 426 2399 487
30 31 32 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
22
TCB-1-18 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1645
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 4843
Maximum bhp at a given rpm mdash (rpm1147)3
Max Motor Frame Size - 182T
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg
0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1500 298486 008 568 012 724 023
43 49 62
1800 357552 011 623 016 755 028 883 042
54 57 67 81
2100 417622 016 683 021 799 034 911 048 1022 065 1123 082
67 68 77 85 99 116
2400 477693 021 749 028 852 041 950 056 1048 073 1147 092 1238 112 1322 133
80 81 90 95 103 120 135 148
2700 536
765 029 817 036 911 050 1001 066 1088 084 1174 103 1262 124 1346 146 1424 169
91 94 103 105 113 125 138 150 164
3000 596838 037 887 045 972 061 1056 078 1136 097 1214 117 1292 138 1369 161 1448 185
102 106 111 115 122 133 142 153 166
3300 656912 048 957 057 1038 074 1115 092 1187 111 1261 132 1331 154 1403 177 1472 202
112 114 120 126 133 141 149 158 168
3600 715987 061 1029 070 1105 089 1176 108 1246 128 1312 149 1379 172 1443 196 1510 222
121 125 131 138 145 152 160 168 178
3900 7751063 075 1102 085 1174 106 1239 126 1305 147 1368 170 1430 193 1491 218 1549 244
133 137 143 149 157 165 173 181 189
4200 8341139 092 1175 103 1244 125 1307 147 1366 169 1428 193 1485 217 1542 243 1599 269
146 149 155 163 171 179 187 195 20
4500 8941215 112 1249 124 1315 147 1375 170 1430 193 1488 218 1544 244 1597 270
160 162 169 176 185 194 20 21
4800 9541292 134 1323 147 1386 172 1444 197 1498 221 1549 246 1604 273
171 174 181 190 199 21 22
5100 10131369 159 1399 172 1458 199 1513 226 1565 252 1615 278
184 187 195 20 21 23
5400 10731446 188 1474 201 1530 229 1584 258 1634 285
197 20 21 22 23
5700 11331523 219 1550 233 1603 263
21 22 22
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 232
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 332
3
All TCB inline and roof mounted fans are available in two levels of construction to provide the most efficient and
economical selections Construction differences between level 1 and 2 selections include the impeller the inlet c
the shaft size and the bearings The housings for both levels are identical in material gauge and overall design
Model TCBRU mdashRoof Upblast Fanbull Sizes from 09 to 36
bull Performance Range 425 to 24000 c
(722 - 40750 msup3hr)
bull Static Pressure Up to 4 in wg (100
bull Max Operating Temperature 200degF
bull Options mdash Easy Access
mdash All Aluminum Construct
Easy Access Feature All models are available with an optional
oversized access door for serviceability o
components without removing the fan or See page 8 for details
Level 1 Constructionbull Maximum pressure capabilities of 2 in wg (500 Pa)
bull Highest efficiencies at static pressures below 15 in wg (375 Pa)bull Aluminum wheel construction
bull Most economical selections
Level 2 Constructionbull Maximum pressure capabilities of 45 in wg (1125 Pa)
bull Highest efficiencies at static pressures above 15 in wg (375 Pa)
bull Completely welded aluminum wheel
bull Increased shaft and bearing diameter
bull Increased horsepower and motor frame size capability
Two Levels of Construction
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 432
4
WindbandHood Panels
HousingCurb Cap
Housing
Model TCB Model TCBRUModel TCBRS
Steel Construction (gauge)
Aluminum Construction (thickness in inches)
Size Housing Curb Cap WindbandHood
Panels
Shaft Diameter (in)
Level 1 Level 2
09 12 12 20 22 3 frasl 4 1
10 12 12 20 22 3 frasl 4 1
12 12 12 20 22 3 frasl 4 1
13 12 12 20 22 3 frasl 4 1
16 12 12 20 22 1 13 frasl 16
18 12 12 20 22 1 13 frasl 16
22 10 12 20 22 1 17
frasl 16
24 10 12 20 22 1 111 frasl 16
30 10 12 20 22 11 frasl 4 115 frasl 16
36 10 12 20 22 11 frasl 2 115 frasl 16
Size Housing Curb Cap WindbandHood
Panels
Shaft Diameter (in)
Level 1 Level 2
09 0125 0125 0051 0051 3 frasl 4 1
10 0125 0125 0051 0051 3 frasl 4 1
12 0125 0125 0051 0051 3 frasl 4 1
13 0125 0125 0051 0051 3 frasl 4 1
16 0125 0125 0051 0051 1 13 frasl 16
18 0125 0125 0051 0051 1 13 frasl 16
22 0125 0125 0051 0051 1 17 frasl 16
24 0125 0125 0051 0051 1 111 frasl 16
30 019 0125 0051 0051 11 frasl 4 115 frasl 16
36 019 0125 0051 0051 11 frasl 2 115 frasl 16
Construction Specifications
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 532
5
Horizontal Base Mount
Fig 1
Horizontal Base MountMotor at 3 or 9 oclock position
Fig 2
OptionalMounting Rail
Horizontal Ceiling HungMotor at 3 or 9 oclock position
Fig 4
OptionaMounting R
Horizontal Ceiling Hung
Fig 3
Vertical Base Mount
Fig 5
Easy AccessOption
Easy AccessOption
Vertical Ceiling Hung
The Model TCB inline fan is the ideal choice for
ducted systems Greenheckrsquos standard fan can be
mounted in any position from horizontal to vertical
allowing installation in the smallest possible space
at the lowest installation cost The centrifugal wheels
used in this design provide higher efficiencies and
lower sound levels than propeller type inline fanswhen used in medium pressure ducted systems TCB
fans are available in either painted steel or aluminum
construction
Typical applications include
bull General exhaust or supply
bull Industrial space ventilation
bull Fume hood exhaust (special coatings are available)
bull Combustion air
bull Roof exhaust or supply (with weatherhood)
bull Restaurant grease exhaust
Universal Mounting
All TCB fans can be mounted horizontally or vertically For
ease of installation eight mounting brackets are welded
on each fan These eight brackets along with standard
mounting supports provide for Greenheckrsquos Universal
Mounting System
Fig 1 Horizontal Base Mount
Each fan is shipped as standard in this arrangement
Motor at 12 orsquoclock is standard
Fig 2 Horizontal Base Mount with Motor at
3 or 9 orsquoclock
A set of optional mounting rails are required for this
installation This is the base mounting position required with
the easy access option
Fig 3 Horizontal Ceiling Hung
In this installation the supports can be positioned for
mounting the motor at either 6 or 12 orsquoclock
Fig 4 Horizontal Ceiling Hung with Motor at3 or 9 orsquoclock
A set of optional mounting rails are required for this
installation
Fig 5 Vertical Mount
All TCB fans can be mounted vertically (ceiling hung or base
mount) for either upward or downward airflow Optional
mounting rails are recommended
NOTE
All fans are shown with optional vibration isolators See the
appropriate submittal drawings or installation manual for
complete dimensional data
TCB Inline Fan - Belt Drive
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 632
6 A
B
C
D
E
21 2
CBRU fans do
ot incorporate
rovisions for
nternal wiring
xternal wiring from
he roof to unit must
e provided by
thers
0 4 8 12 16 20 24
CFM x 1000
18
16
14
12
10
08
06
04
02
00
P r e s s u r e
L o s s ( i n
c h e s )
1 6
1 8
2 2
2 4
3 0 3 6
0 1 2 3 4
CFM x 1000
08
07
06
05
04
03
02
01
00
(
)
0 9
1 0
1 2
1 3
System Effect Curves
Sizes 9-13 Sizes 16-36
Dimensional Data
The TCBRU is ideal for roof upblast exhaust systems
with moderate system static pressures and for
applications where quiet operation is essential
Standard features include a necked-down windband
section which creates the high outlet velocities
necessary to carry contaminated exhausts away from
the roof deck All TCBRU fans include motor coversfor weather protection of the motor and drives gravity
operated dampers to prevent backflow into the
building and a welded curb cap for ease in mounting
to a roof curb TCBRU fans are available in either
painted steel or aluminum construction
Typical applications include
bull Low cfmhigh velocity exhaust
bull General exhaust
bull Fume hood exhaust
bull Industrial process exhaust
When selecting TCBRU fans use the TCB inline performance data
(pgs 12 to 31) along with the following system effect curves The
pressure loss determined below must be added to the extended
system static pressure to assure accurate selections Greenheckrsquos
Computer Aided Product Selection (CAPS) software will add these
system effects automatically
Size A B C D E Minimum CFMRequired to Open Dampers
09 22 211 frasl 2 23 45 20 425
10 22 211 frasl 2 23 45 20 425
12 22 211 frasl 2 23 45 20 1250
13 4 231 frasl 2 241 frasl 2 50 1 frasl 2 24 1800
16 28 25 1 frasl 2 28 1 frasl 2 53 28 2030
18 34 28 1 frasl 2 31 571 frasl 2 30 2570
22 40 34 35 1 frasl 2 64 34 2740
24 46 36 1 frasl 2 42 74 1 frasl 2 40 4760
30 52 42 1 frasl 4 481 frasl 2 84 46 6600
36 58 451 frasl 2 54 94 1 frasl 2 52 8700
All dimensions shown in inches
TCBRU Roof Upblast Fan
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 732
7
A B
C
D
W
21 2 in
L
Hood End View Hood Side View
TCBRS fans donot incorporateprovisions for internal wiring
External wiring fromthe roof to unit mustbe provided byothers
0 4 8 12 16 20 24
CFM x 1000
0 9
1 0
1 2
1 3
1 6
1 8
2 2 2
4
3 0
3 6
018
016
014
012
010
008
006
004
002
000
P r e s s u r e
L o s s ( i n c h e s )
System Effect Curves
Dimensional Data
The TCBRS roof mounted supply fan is designed
for intake air systems with pressures up to 4 inches
of wg and where low sound is required The TCBRS
hood intake is located at a sufficient height above
the roof to limit entry of roof debris and snow In
addition the hood has sufficient intake area to keep
velocities low Filters are available to collect dustand moisture before entering the building Motor
and drive protection is provided with a weatherproof
motor cover For ease of installation TCBRS fans are
shipped assembled and have curb caps for attaching
to roof curbs TCBRS fans are available in either
painted steel or aluminum construction
Typical applications include
bull Ducted supply systems
bull Industrial space supply
bull Filtered supply
TCBRS fan selections can be made using the TCB inline
performance data (pgs 12 to 31) along with the following
system effect curves The pressure loss determined to the
left must be added to the external system static pressure
to assure accurate selections Greenheckrsquos Computer
Aided Product Selection (CAPS) software will add thesesystem effects automatically
Size A B C D L W
09 22 211 frasl 2 251 frasl 2 391 frasl 2 39 46
10 22 211 frasl 2 251 frasl 2 391 frasl 2 39 46
12 22 211 frasl 2 251 frasl 2 391 frasl 2 39 4613 24 231 frasl 2 27 431 frasl 2 39 54
16 28 25 1 frasl 2 31 471 frasl 2 51 55
18 34 28 1 frasl 2 331 frasl 2 50 63 64
22 40 34 38 1 frasl 2 59 75 73
24 46 36 1 frasl 2 45 67 1 frasl 2 87 82
30 52 42 1 frasl 4 52 1 frasl 2 76 99 88
36 58 45 1 frasl 2 58 851 frasl 2 111 88
All dimensions shown in inches
TCBRS Roof Supply Fan
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 832
8
Optional Construction Features
Aluminum Construction
Aluminum construction is available on the TCB TCBRU and TCBRS Aluminum fans are an excellent choice for
applications involving moisture or coastal installations
Easy Access Construction
The Easy Access option is highly recommended to allow forinspection cleaning and service of internal fan components
By removing one access panel service to the wheel shaft
and bearing assembly is possible without removing duct
connections In addition all internal fan components can be
removed from the fan through the easy access panel
Easy Access construction is available on all levels and sizes
of TCB TCBRU and TCBRS Easy Access is also available
with aluminum fan construction
The Easy Access panel is located 180deg from the motor
position
Standard Construction Features
Inlet amp Outlet Flanges
Flanged inlets and outlets with mounting holes are
provided for duct connections (TCB only)
Housing
Housings are continuously welded steel and coated
with Permatector trade
Protective Coating
All steel constructed units are coated with
Permatectortrade a thermosetting polyester urethane
Aluminum units are uncoated
Type B Spark Resistance
All fans have aluminum wheels and a nonferrous
(aluminum) rub ring which surrounds the fanshaft where it passes through the drive cover
This construction meets Type B spark resistant
requirements
Bearings
Standard bearings are grease lubricated self-aligning
ball type in pillow block mounts Bearings are selected
for a minimum L10 life in excess of 80000 hours (L50 average life of 400000 hours) at maximum cataloged
operating speeds
Belt amp Bearing Tube
Belts bearings and drives are protected from the
airstream by heavy gauge belt tubes and bolted
bearing covers with shaft seals
Extended
Lube Lines
Lubrication lines with grease
fittings allow bearing lubricationwithout disassembling the fan
TCB - 1 - 24 - 30Tubular CentrifugalBelt Drive
TCB - Inline FanTCBRU - Roof Upblast FanTCBRS - Roof Supply Fan
Level of Construction1 or 2
Motor Horsepower
4 = 1 4 30=3 3 = 1 3 50=5
5 = 1 2 75=7 1 2
7 = 3 4 100=10
10=1 150=15
15=11 2 200=20 20=2
Fan Size09-36
Model Number CodeThe model number system is designed to completely identify
the fan A detailed explanation of the model number code for
TCB fans is shown below
Construction Features
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 932
9
Inline grease exhaust fans are excellent alternative for kitchen applications when roof or wall mounted ventilators
are not practical The TCB with UL 762 grease option is designed to withstand the demands of high temperature
kitchen grease exhaust and high-pressure duct washes
Continuously welded housing and integral duct flanges
provide air and water tight design
Bearing cover gasketed and includes a labyrinth shaft seal
to prevent moisture leakage during normal operation and
while cleaning with high pressure solvents
Continuously welded belt tube keeps the belts and
bearings clean
Two threaded drain connections are located 90deg from the
motor location to allow for removal of grease and moisture
UL 762 is concerned with fans
designed for removal of smoke and
grease laden vapors with airstream
temperatures up to 300degF
bull Meets all UL 705 Requirements
bull Bolted Access Door
bull Drain Connectionbull Meets requirements of NFPA 96
Ventilation Control and Fire
Protection of Commercial
Cooking Operations
Listed Power
Ventilation for
Restaurant
Exhaust Appliances
13G3
Maximum
Operating
Temperature
300degF
The TCB inline grease fan is tough to beat when
packaged with our full line of kitchen hoods and grease
extraction options Take advantage of Greenheckrsquos
expertise in providing a total solution in kitchen
ventilation equipment
A Tough Package to Beat
Leak Resistant Construction Features
bull Inline grease exhaust fans should be installed near the end of the duct run to reduce sound at the hood
bull Inline fan must be securely bolted to the exhaust duct per NFPA-96 guidelines Greenheckrsquos companion flange
are recommended for ease of installation
bull Grease exhaust fans and ductwork must maintain 18 inches (46 cm) minimum clearance to combustible
material If the ductwork and fan are insulated the inspection door must be accessible for maintenancebull A minimum of 10 ft (30 m) of clearance must be kept from the fan outlet to adjacent buildings property lines
or the closest point of any air intake or operable window at or below the plane of the exhaust termination
bull Greenheck recommends that all inline grease applications be reviewed by your local code official to ensure
compliance with NFPA IMC and other local codes
System Design Guidelines
1
2
3
4
5
6
7
Mounting and Serviceability Features
4 6
7
5 14
Optional Construction forUL 762 Restaurant Exhaust
Universal mounting brackets allow for rotation of the motor to
the 3 or 9 orsquoclock position at the jobsiteDuct flanges and access door bolt locations are no more
than 4 inches (100 mm) on center per NFPA 96
ldquoEasy Access Doorrdquo provides access for duct cleaning and allows removal of the wheel
shaft and bearings for maintenance Gasket is rated for 400degF (200degC) and prevents
leakage during operation [Fan is rated for 300degF (149degC) continous operation]
Air1047298ow
Duct to heat source
Ambient temperaturenot to exceed 120ordmF
Wall andor ceiling should enclosefan when used for emergency heatand smoke exhaust Enclosure shallbe per NFPA 96 or local building codes
Roof
Cooling air fordrives andbearings
Minimum ductat discharge
To buildingexterior
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1032
10
Electrical Accessories
Belt Guard (TCB only) Belt guards are totally enclosed to provide protection
from rotating pulleys and belts Belt guards meet
OSHA guidelines
Motor Cover (Weatherhood) Weatherproof motor covers shield the motor and
drive components from dust dirt and moisture when
used in outdoor applications Motor covers also
provide protection from rotating pulleys and belts and
meet OSHA guidelines Motor covers are standard on
TCBRU and TCBRS models
Inlet and Outlet Companion Flanges
(TCB only) Companion inlet flanges and outlet flanges with
prepunched holes are available for all fan sizes in
painted steel construction
Inlet and Outlet Guards (TCB TCBRU)
Removable inlet and outlet guards provide protectionfor personnel and equipment in non-ducted
installations These guards meet OSHA guidelines
TCBRU fans are available with outlet screens to
shield the fan discharge and damper from debris
Inspection Door Bolted or hinged doors provide access for cleaning or
inspection
Inspection Section (TCB only) Inspection sections serve as a length of duct that can
be easily removed to provide for complete access to
the fan for servicing Each section includes a bolted
inspection door
Isolators (TCB only) Both base mount or hanging isolators are available in
either neoprene or spring mounts The isolators are
furnished in sets of four and are sized to match the
weight of each fan
Mounting Rails (TCB only) Mounting rails are required for horizontal mounting
of TCB fans when the motor is to be located in
the 3 or 9 orsquoclock position Mounting rails are also
recommended for all vertically mounted inline fans
See page 5 for additional details
Protective Coatings Greenheck has a wide offering of protective coatings
Consult Greenheckrsquos Product Application Guide
FA110-04R4 Performance Coatings for Ventilation
Products for a complete listing of coatings and a
relative resistance chart
Inlet Vane Dampers (TCB only) Nested inlet vane dampers for controlling air volume
are available on model TCB inline fans with Level 2
steel construction in fan sizes 12 through 36
Birdscreen Insect Screen (TCBRS only)
TCBRS fans are available with either aluminum insectscreen or birdscreen at the hood intake (Birdscreen is
standard)
Roof Curbs (TCBRU TCBRS) Prefabricated roof curbs are available to reduce
installation time and costs by ensuring compatibility
between the fan the curb and the roof opening
All curbs are lined with fiberglass insulation to
prevent condensation and reduce sound levels See
Greenheckrsquos Roof Curb Extensions and Equipment
Supports catalog for complete details
Washable Aluminum Filters (TCBRS only)
Helps trap dust and dirt before it enters the fanFilters can be removed for cleaning
Enclosure Application Toggle Heavy Duty
NEMA-1 Indoor General Purpose Yes Yes
NEMA-12 Indoor DustDrip Tight Yes YesNEMA-3R IndoorOutdoor Rainproof Yes Yes
NEMA-4 IndoorOutdoor Watertight Yes Yes
NEMA-4X IndoorOutdoor Watertight
(Corrosion Resistant) Yes Yes
NEMA-7 amp 9 Indoor Hazardous Locations Yes No
Toggle type and heavy duty disconnect switches are available for positive
electrical shut-off and safety in servicing fans The following switches are
available to meet individual electrical requirements
Accessories
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1132
11
Inspection
Section
Outlet Guard
Belt Guard
Motor Cover
Companion Flange
(Outlet)NeopreneIsolator
Spring Base
Isolator
Inspection
Door
Easy Access
Inlet Guard
CompanionFlange (Inlet)
Mounting Rails
Spring HangingIsolator
Isolator Neoprene Hanging
Accessories (Model TCB shown)
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
12
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
360 195846 002 999 003 1260 006
53 60 75
420 228941 003 1071 004 1314 007 1526 011
57 63 77 92
480 2601040 004 1155 005 1380 009 1576 012 1758 017
63 68 80 93 106
540 2931144 005 1245 006 1449 010 1635 014 1807 019 1968 023 2115 028
71 74 84 95 107 120 133
600 326
1250 006 1341 008 1523 012 1704 016 1865 021 2017 026 2163 031 2298 036
78 81 88 99 110 122 135 147
660 3581357 007 1439 009 1606 014 1774 018 1930 023 2074 029 2212 034 2346 040 2472 046
86 88 93 104 114 126 137 149 162
720 3911465 009 1542 011 1692 016 1845 021 1999 026 2137 032 2270 038 2395 043 2520 050
94 96 100 109 120 131 140 150 163
780 4231576 012 1647 014 1786 018 1928 024 2069 029 2206 035 2331 041 2454 047 2570 054
102 104 108 115 127 136 145 154 165
840 4561688 014 1752 016 1882 021 2012 027 2142 033 2276 039 2400 045 2515 052 2629 059
110 112 117 123 133 142 150 160 170
900 4891801 017 1859 019 1980 025 2100 030 2225 036 2347 043 2469 050 2584 056
120 122 127 133 139 148 157 166
960 5211914 020 1966 023 2081 028 2195 034 2310 040 2424 047 2540 054
130 132 140 142 147 154 164
1020 5542028 024 2075 026 2184 032 2292 038 2395 044 2507 052 2612 059
144 149 150 151 155 163 172
1080 5862141 028 2186 031 2288 037 2389 043 2490 050 2592 057
159 159 160 162 166 172
1140 6192255 033 2298 036 2394 042 2487 049 2585 055
169 169 171 174 178
1200 6522370 038 2410 041 2500 047 2590 054
179 180 183 186
TCB-1-09 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2645
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm3114)3
Max Motor Frame Size - 56
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
13
TCB-2-09 Level 2 Construction
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3330)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg
025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
400 2171198 005 1460 008 1893 018
73 87 119
480 2601332 006 1566 010 1971 020 2309 032
82 96 127 157
560 3041480 009 1686 013 2059 024 2386 036 2671 049
92 106 135 165 191
640 3471635 011 1818 016 2158 027 2469 041 2749 055 3000 070 3228 086
106 117 146 174 20 23 25
720 3911799 015 1958 020 2275 032 2562 045 2830 061 3078 077 3305 094 3514 112
120 130 158 183 21 23 25 28
800 4341966 020 2108 025 2397 037 2666 051 2921 067 3158 085 3383 103 3591 121 3786 141
134 145 169 183 22 24 26 28 31
880 4782135 025 2262 030 2528 043 2784 058 3015 074 3250 093 3464 112 3669 132 3863 152
151 162 182 21 23 25 27 29 32
960 5212308 032 2425 037 2665 050 2905 066 3132 083 3343 101 3555 121 3752 142 3942 164
168 176 196 22 24 26 28 31 33
1040 5652482 039 2590 045 2810 059 3033 075 3251 093 3453 111 3648 131 3844 153 4027 176
184 193 21 23 25 27 29 32 34
1120 6082658 048 2757 054 2960 068 3168 085 3372 103 3571 123 3754 143 3937 165
20 21 23 25 27 29 31 33
1200 6522835 058 2925 065 3113 079 3306 096 3501 115 3691 135 3872 157 4041 179
22 23 24 26 28 30 32 35
1280 6953012 070 3095 076 3271 091 3453 109 3636 128 3813 149 3991 171
24 25 26 28 29 32 34
1360 7393190 083 3269 090 3434 105 3603 123 3773 143 3945 164
26 26 28 29 31 34
1440 7823368 097 3444 105 3599 121 3756 139 3917 159
28 28 30 31 33
1520 8263547 114 3619 121 3765 138 3909 156
30 30 32 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
14
TCB-1-10 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2555
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm2760)3
Max Motor Frame Size - 143T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
480 260858 003 1011 005 1253 009
49 57 73
560 304947 004 1089 006 1321 011 1511 015
55 63 77 93
640 3471042 005 1171 008 1394 013 1578 018 1740 023 1892 029
63 70 82 96 112 133
720 3911141 007 1259 009 1470 015 1649 021 1806 027 1949 033 2079 039
72 76 89 100 115 132 150
800 4341239 009 1349 012 1548 018 1723 024 1876 031 2015 037 2144 044 2263 051
80 84 96 107 119 135 148 161
880 4781340 011 1444 014 1630 021 1798 027 1949 034 2084 042 2211 049 2329 057 2440 064
88 92 102 113 125 137 150 162 176
960 5211441 014 1541 017 1716 024 1876 031 2023 039 2157 047 2280 055 2396 063 2506 071
97 101 109 121 133 141 152 165 179
1040 5651544 017 1640 021 1805 028 1957 035 2099 044 2231 052 2352 060 2465 069
105 109 117 129 139 148 157 169
1120 6081648 021 1739 025 1895 032 2042 040 2178 049 2306 058 2426 067 2538 076
113 117 127 138 146 155 165 177
1200 6521752 025 1839 029 1989 037 2129 046 2259 055 2383 064 2501 073
122 126 137 145 153 163 175
1280 6951858 030 1940 034 2085 043 2218 052 2343 061 2464 071
132 137 145 152 162 173
1360 7391964 035 2041 040 2183 049 2308 058 2430 068 2545 078
145 149 154 162 172 183
1440 7822071 041 2144 046 2282 056 2401 066 2519 076
156 158 164 173 183
1520 8262177 048 2247 053 2380 064 2497 074
164 167 175 184
1600 8692285 056 2351 061 2479 072
173 177 185
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
15
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-10 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3120)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 3261300 007 1504 011 1875 021 2213 032
73 82 105 132
700 3801453 010 1630 014 1966 024 2273 036 2560 049
84 91 110 133 156
800 4341611 013 1768 018 2070 029 2355 042 2619 055 2872 070 3102 086
100 101 118 137 158 182 20
900 4891773 017 1917 023 2188 034 2448 048 2698 062 2932 078 3160 094 3371 111 3568 129
112 113 127 143 162 185 20 22 25
1000 543
1937 023 2071 029 2319 041 2559 055 2790 070 3011 086 3220 103 3430 122 3626 140
124 127 136 152 170 190 21 23 25
1100 5972104 029 2228 035 2457 048 2677 063 2892 079 3103 096 3303 114 3490 132 3685 152
138 143 146 161 179 195 21 23 25
1200 6522276 036 2389 043 2601 057 2807 073 3009 089 3199 107 3394 125 3578 145 3751 165
154 154 159 172 189 20 21 23 25
1300 7062449 045 2552 052 2753 067 2944 083 3128 101 3315 119 3488 138 3670 159 3841 180
164 166 172 183 195 21 22 24 25
1400 7602623 055 2717 062 2907 079 3083 095 3261 114 3433 133 3603 153 3763 173 3933 196
175 177 185 193 20 21 23 24 26
1500 8152797 066 2883 074 3063 092 3231 109 3398 128 3557 148 3721 169 3878 191 4026 212
186 189 197 20 21 22 23 25 26
1600 8692973 079 3052 087 3223 106 3384 125 3537 144 3693 165 3840 186 3995 209
198 20 21 21 22 23 24 25
1700 9233149 094 3224 103 3384 122 3538 142 3683 162 3831 184 3974 206
21 21 22 22 23 23 25
1800 9783325 110 3396 119 3546 140 3693 161 3834 182 3970 204
22 22 23 23 24 24
1900 10323502 129 3570 138 3710 159 3852 182 3988 204
23 24 24 25 25
2000 10863679 149 3744 159 3875 181 4012 204
25 25 25 26
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
16
TCB-1-12 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2490
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 3436
Maximum bhp at a given rpm mdash (rpm2202)3
Max Motor Frame Size - 145T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 0075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
700 380853 006 958 008 1158 014 1345 021 1518 028
62 66 79 94 110
800 434943 008 1042 011 1218 017 1386 024 1551 031 1703 040
66 70 83 96 111 125
900 4891037 010 1128 013 1287 020 1442 027 1587 035 1736 044 1873 053 2000 063
71 76 87 99 112 126 142 155
1000 5431132 013 1216 017 1363 024 1506 031 1643 040 1771 049 1906 059 2033 069 2151 079
78 83 91 103 115 128 143 156 170
1100 597
1229 016 1305 020 1447 028 1574 036 1702 045 1827 055 1943 065 2066 075 2183 086
86 89 96 108 120 133 144 157 171
1200 6521326 020 1398 025 1532 034 1649 042 1769 051 1884 061 1999 071 2105 082 2216 094
92 95 103 113 126 139 149 159 173
1300 7061426 025 1492 030 1619 039 1732 049 1839 058 1950 068 2055 079 2161 090 2260 102
98 102 112 121 134 145 154 164 176
1400 7601526 031 1588 036 1707 046 1817 056 1916 066 2019 076 2120 088 2217 099 2316 111
106 112 122 132 142 151 160 170 181
1500 8151627 037 1684 042 1796 053 1903 064 1999 075 2089 085 2188 097 2281 109 2372 121
119 125 135 144 149 157 167 176 187
1600 8691729 044 1781 050 1886 061 1990 073 2084 085 2170 096 2258 107 2350 120 2436 133
134 139 150 153 157 165 174 183 194
1700 9231830 053 1879 058 1980 070 2077 083 2170 095 2254 107 2334 119 2419 132
151 157 159 162 167 173 181 191
1800 9781932 062 1978 068 2074 080 2166 093 2256 107 2339 120 2417 132
166 166 168 171 176 182 190
1900 10322034 072 2078 078 2169 091 2256 105 2343 119 2425 133
173 173 176 180 185 192
2000 10862137 083 2179 090 2265 103 2348 118 2432 133
180 181 184 189 195
2100 11412240 096 2280 102 2361 117 2442 132
187 188 192 198
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
17
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-12 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 3274
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 321
Maximum bhp at a given rpm mdash (rpm2315)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
750 4071009 008 1226 014 1587 027
55 67 98
900 4891119 011 1315 018 1648 032 1936 049 2182 067
63 76 102 131 159
1050 5701238 015 1419 023 1728 039 1995 056 2240 076 2456 096
75 85 110 136 164 190
1200 6521363 020 1529 029 1813 046 2070 065 2299 085 2514 108 2710 131 2890 155
89 96 120 142 169 195 22 24
1350 733
1495 027 1643 036 1911 055 2151 076 2372 097 2574 120 2768 145 2948 171 3115 197
104 111 132 152 176 20 22 25 28
1500 8151630 034 1764 044 2018 066 2240 088 2452 111 2647 135 2828 160 3007 187 3174 216
120 129 145 166 186 21 23 26 29
1650 8961767 044 1887 054 2127 077 2338 101 2534 126 2727 151 2903 178 3067 205 3233 235
139 144 159 184 199 22 24 27 30
1800 9781908 055 2018 066 2239 090 2445 117 2630 143 2808 170 2983 198 3145 227
159 165 180 199 22 23 25 28
1950 10592053 068 2151 079 2356 105 2554 134 2731 162 2900 190 3064 220 3225 250
182 188 20 22 23 25 27 29
2100 11412198 083 2286 095 2477 122 2664 152 2839 183 2997 213 3154 244
21 22 22 23 25 27 29
2250 12222344 100 2423 113 2599 141 2777 173 2948 205 3104 238 3250 271
24 24 25 26 27 29 32
2400 13042490 119 2560 133 2726 163 2896 196 3058 230 3212 265
26 26 27 28 30 32
2550 13852637 141 2703 156 2858 187 3016 221 3169 257
28 29 29 31 32
2700 14672785 166 2847 181 2991 214 3138 248
31 31 32 34
2850 15482933 193 2992 209 3126 243 3262 279
34 34 35 37
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
18
TCB-1-13 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2355
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 3435
Maximum bhp at a given rpm mdash (rpm2119)3
Max Motor Frame Size - 145T
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 265660 003 792 005 1019 010
41 51 69
750 331760 005 874 007 1073 013 1254 019
48 58 71 84
900 398864 007 967 010 1146 016 1305 023 1459 030
58 64 75 86 102
1050 464973 009 1067 013 1230 020 1378 027 1512 036 1646 044 1770 053
66 70 80 91 103 120 140
1200 530
1085 013 1171 017 1321 024 1457 032 1585 041 1703 051 1820 061 1933 071 2039 081
72 77 86 96 108 120 136 153 172
1350 5971199 017 1277 022 1419 030 1545 039 1662 048 1777 058 1883 069 1984 080 2089 091
81 85 94 103 114 125 136 151 167
1500 6631316 023 1387 027 1520 037 1637 046 1749 059 1853 067 1957 078 2054 090 2146 102
90 94 102 112 122 132 143 155 169
1650 7301434 029 1499 034 1623 044 1736 055 1839 065 1940 077 2034 088 2128 100 2219 113
100 104 113 123 132 143 153 165 178
1800 7961552 037 1613 042 1729 054 1836 065 1935 076 2029 088 2121 100 2207 113 2293 126
112 115 125 134 144 154 165 177 190
1950 8621672 045 1728 052 1836 064 1939 076 2034 088 2123 100 2209 113 2294 127
124 129 138 147 156 167 178 190
2100 9291792 056 1844 062 1947 076 2044 089 2135 102 2221 115 2302 128
138 142 151 161 170 181 192
2250 9951913 067 1962 075 2058 089 2150 103 2238 117 2321 131
152 157 167 177 186 196
2400 10612034 081 2080 088 2171 104 2258 119 2342 133
169 174 184 194 20
2550 11282155 095 2199 104 2285 120
187 192 20
2700 11942277 112 2319 121
21 21
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
19
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
TCB-2-13 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2971
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 353
Maximum bhp at a given rpm mdash (rpm1933)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
800 353828 008 1026 014 1379 030
38 56 104
1000 442934 011 1108 018 1418 035 1692 055
44 60 101 135
1200 5301048 016 1206 024 1479 042 1731 064 1961 087
58 72 101 130 165
1400 6191171 022 1313 031 1562 051 1784 073 2002 099 2201 126 2391 155
75 87 106 128 160 189 22
1600 707
1300 030 1424 040 1657 062 1865 086 2053 112 2247 141 2425 171 2596 203 2759 237
97 100 115 133 156 184 21 24 27
1800 7961431 039 1545 051 1759 075 1950 101 2134 129 2300 157 2472 189 2636 223 2790 258
114 113 125 144 160 181 21 24 26
2000 8841565 051 1669 063 1868 090 2050 118 2217 148 2381 178 2531 210 2683 244 2836 282
127 127 137 157 170 186 21 23 26
2200 9731700 064 1797 078 1979 107 2152 138 2312 169 2464 202 2612 236 2750 270 2883 306
142 145 156 169 183 198 21 23 26
2400 10611836 081 1928 096 2097 127 2260 160 2413 194 2556 228 2695 264 2831 301 2959 338
164 169 174 182 197 21 23 24 26
2600 11501975 100 2060 116 2219 150 2371 185 2517 221 2656 257 2785 295 2914 334
190 192 193 196 21 23 24 26
2800 12382115 122 2194 140 2343 175 2484 212 2626 251 2758 290 2885 330
21 21 21 22 23 24 26
3000 13272256 148 2329 166 2470 204 2605 243 2737 284 2864 325
24 24 24 24 25 26
3200 14152397 177 2464 196 2600 236 2728 278 2849 320
26 26 26 27 27
3400 15042539 210 2601 230 2731 272 2852 316 2969 361
29 29 30 30 30
3600 15922681 247 2739 267 2863 312
33 33 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
20
TCB-1-16 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2000
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 4384
Maximum bhp at a given rpm mdash (rpm1378)3
Max Motor Frame Size - 182T
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1000 308507 005 612 009 802 017
37 43 59
1250 385584 008 671 012 833 021 985 032
45 49 62 81
1500 462668 011 743 016 884 026 1016 038 1145 052
54 58 69 84 103
1750 540755 016 821 021 944 032 1065 045 1176 059 1289 075 1392 091
64 68 79 93 105 120 136
2000 617
844 022 904 028 1014 040 1119 054 1225 069 1322 085 1422 102 1517 120 1605 139
76 81 92 104 113 124 140 157 175
2250 694934 030 989 036 1090 049 1185 064 1278 080 1373 097 1460 115 1547 134 1635 154
89 94 107 114 123 133 146 161 179
2500 7711026 039 1077 047 1169 061 1257 076 1342 092 1425 110 1511 130 1591 149 1666 170
104 110 119 126 134 144 156 169 184
2750 8481118 051 1166 059 1252 074 1334 091 1411 107 1489 126 1564 146 1643 167 1717 188
121 124 131 138 147 157 168 181 194
3000 9251210 064 1256 073 1337 090 1412 107 1486 125 1556 144 1627 165 1695 186 1769 209
134 138 145 152 161 171 183 194 21
3250 10031303 080 1347 090 1423 108 1494 127 1563 146 1630 166 1695 186 1760 209 1823 232
149 153 161 169 177 187 199 21 22
3500 10801397 098 1438 109 1511 128 1578 148 1642 169 1706 190 1768 211 1828 233 1889 258
166 170 179 187 195 21 22 23 24
3750 11571491 119 1530 130 1599 152 1663 173 1725 194 1784 216 1844 239 1900 262 1956 286
185 189 197 21 22 23 24 25 27
4000 12341585 143 1622 155 1689 178 1750 200 1809 223 1865 246 1921 270 1976 295
20 21 22 23 24 25 26 28
4250 13111680 170 1714 183 1779 207 1838 231 1893 255 1948 280 1999 304
23 23 24 25 26 28 29
4500 13881775 200 1807 214 1869 240 1926 265 1979 291
25 26 27 28 30
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
21
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
TCB-2-16 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2431
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 432
Maximum bhp at a given rpm mdash (rpm1406)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1200 370668 011 842 020 1137 041
46 61 104
1500 462749 015 899 025 1166 049 1395 077
55 68 102 138
1800 555843 021 969 033 1208 059 1424 089 1616 121
71 77 104 135 168
2100 648944 030 1053 042 1268 071 1461 103 1647 138 1813 175 1972 215
83 88 111 134 166 196 22
2400 740
1047 040 1144 054 1336 085 1518 120 1684 157 1847 197 1996 238 2140 283 2275 329
99 105 120 140 166 195 22 25 27
2700 8331152 053 1243 068 1412 101 1579 139 1739 179 1885 221 2033 266 2169 312 2297 359
116 122 132 150 171 195 22 25 28
3000 9251260 069 1345 086 1498 121 1651 161 1799 204 1941 248 2070 295 2206 344 2333 394
132 136 144 162 182 20 23 25 28
3300 10181373 089 1448 107 1588 144 1727 186 1866 231 2001 279 2129 328 2247 379 2370 432
147 151 161 177 195 22 24 26 29
3600 11111486 112 1553 131 1686 171 1813 215 1939 262 2065 312 2188 365 2306 418 2416 473
166 171 182 193 21 23 25 28 30
3900 12031600 140 1658 159 1786 202 1900 247 2020 297 2138 349 2252 404 2366 461
189 194 20 21 23 25 27 29
4200 12961715 172 1766 191 1888 238 1996 285 2106 336 2213 390 2324 448 2430 508
21 21 22 23 24 26 29 31
4500 13881831 208 1878 228 1990 277 2095 328 2193 380 2298 437 2398 496
23 23 24 25 27 28 31
4800 14811946 250 1992 271 2094 322 2196 376 2289 430 2385 488
25 26 27 28 29 31
5100 15742062 296 2105 319 2199 371 2297 429 2388 486
28 28 29 30 32
5400 16662179 349 2219 373 2305 426 2399 487
30 31 32 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
22
TCB-1-18 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1645
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 4843
Maximum bhp at a given rpm mdash (rpm1147)3
Max Motor Frame Size - 182T
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg
0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1500 298486 008 568 012 724 023
43 49 62
1800 357552 011 623 016 755 028 883 042
54 57 67 81
2100 417622 016 683 021 799 034 911 048 1022 065 1123 082
67 68 77 85 99 116
2400 477693 021 749 028 852 041 950 056 1048 073 1147 092 1238 112 1322 133
80 81 90 95 103 120 135 148
2700 536
765 029 817 036 911 050 1001 066 1088 084 1174 103 1262 124 1346 146 1424 169
91 94 103 105 113 125 138 150 164
3000 596838 037 887 045 972 061 1056 078 1136 097 1214 117 1292 138 1369 161 1448 185
102 106 111 115 122 133 142 153 166
3300 656912 048 957 057 1038 074 1115 092 1187 111 1261 132 1331 154 1403 177 1472 202
112 114 120 126 133 141 149 158 168
3600 715987 061 1029 070 1105 089 1176 108 1246 128 1312 149 1379 172 1443 196 1510 222
121 125 131 138 145 152 160 168 178
3900 7751063 075 1102 085 1174 106 1239 126 1305 147 1368 170 1430 193 1491 218 1549 244
133 137 143 149 157 165 173 181 189
4200 8341139 092 1175 103 1244 125 1307 147 1366 169 1428 193 1485 217 1542 243 1599 269
146 149 155 163 171 179 187 195 20
4500 8941215 112 1249 124 1315 147 1375 170 1430 193 1488 218 1544 244 1597 270
160 162 169 176 185 194 20 21
4800 9541292 134 1323 147 1386 172 1444 197 1498 221 1549 246 1604 273
171 174 181 190 199 21 22
5100 10131369 159 1399 172 1458 199 1513 226 1565 252 1615 278
184 187 195 20 21 23
5400 10731446 188 1474 201 1530 229 1584 258 1634 285
197 20 21 22 23
5700 11331523 219 1550 233 1603 263
21 22 22
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 332
3
All TCB inline and roof mounted fans are available in two levels of construction to provide the most efficient and
economical selections Construction differences between level 1 and 2 selections include the impeller the inlet c
the shaft size and the bearings The housings for both levels are identical in material gauge and overall design
Model TCBRU mdashRoof Upblast Fanbull Sizes from 09 to 36
bull Performance Range 425 to 24000 c
(722 - 40750 msup3hr)
bull Static Pressure Up to 4 in wg (100
bull Max Operating Temperature 200degF
bull Options mdash Easy Access
mdash All Aluminum Construct
Easy Access Feature All models are available with an optional
oversized access door for serviceability o
components without removing the fan or See page 8 for details
Level 1 Constructionbull Maximum pressure capabilities of 2 in wg (500 Pa)
bull Highest efficiencies at static pressures below 15 in wg (375 Pa)bull Aluminum wheel construction
bull Most economical selections
Level 2 Constructionbull Maximum pressure capabilities of 45 in wg (1125 Pa)
bull Highest efficiencies at static pressures above 15 in wg (375 Pa)
bull Completely welded aluminum wheel
bull Increased shaft and bearing diameter
bull Increased horsepower and motor frame size capability
Two Levels of Construction
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 432
4
WindbandHood Panels
HousingCurb Cap
Housing
Model TCB Model TCBRUModel TCBRS
Steel Construction (gauge)
Aluminum Construction (thickness in inches)
Size Housing Curb Cap WindbandHood
Panels
Shaft Diameter (in)
Level 1 Level 2
09 12 12 20 22 3 frasl 4 1
10 12 12 20 22 3 frasl 4 1
12 12 12 20 22 3 frasl 4 1
13 12 12 20 22 3 frasl 4 1
16 12 12 20 22 1 13 frasl 16
18 12 12 20 22 1 13 frasl 16
22 10 12 20 22 1 17
frasl 16
24 10 12 20 22 1 111 frasl 16
30 10 12 20 22 11 frasl 4 115 frasl 16
36 10 12 20 22 11 frasl 2 115 frasl 16
Size Housing Curb Cap WindbandHood
Panels
Shaft Diameter (in)
Level 1 Level 2
09 0125 0125 0051 0051 3 frasl 4 1
10 0125 0125 0051 0051 3 frasl 4 1
12 0125 0125 0051 0051 3 frasl 4 1
13 0125 0125 0051 0051 3 frasl 4 1
16 0125 0125 0051 0051 1 13 frasl 16
18 0125 0125 0051 0051 1 13 frasl 16
22 0125 0125 0051 0051 1 17 frasl 16
24 0125 0125 0051 0051 1 111 frasl 16
30 019 0125 0051 0051 11 frasl 4 115 frasl 16
36 019 0125 0051 0051 11 frasl 2 115 frasl 16
Construction Specifications
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 532
5
Horizontal Base Mount
Fig 1
Horizontal Base MountMotor at 3 or 9 oclock position
Fig 2
OptionalMounting Rail
Horizontal Ceiling HungMotor at 3 or 9 oclock position
Fig 4
OptionaMounting R
Horizontal Ceiling Hung
Fig 3
Vertical Base Mount
Fig 5
Easy AccessOption
Easy AccessOption
Vertical Ceiling Hung
The Model TCB inline fan is the ideal choice for
ducted systems Greenheckrsquos standard fan can be
mounted in any position from horizontal to vertical
allowing installation in the smallest possible space
at the lowest installation cost The centrifugal wheels
used in this design provide higher efficiencies and
lower sound levels than propeller type inline fanswhen used in medium pressure ducted systems TCB
fans are available in either painted steel or aluminum
construction
Typical applications include
bull General exhaust or supply
bull Industrial space ventilation
bull Fume hood exhaust (special coatings are available)
bull Combustion air
bull Roof exhaust or supply (with weatherhood)
bull Restaurant grease exhaust
Universal Mounting
All TCB fans can be mounted horizontally or vertically For
ease of installation eight mounting brackets are welded
on each fan These eight brackets along with standard
mounting supports provide for Greenheckrsquos Universal
Mounting System
Fig 1 Horizontal Base Mount
Each fan is shipped as standard in this arrangement
Motor at 12 orsquoclock is standard
Fig 2 Horizontal Base Mount with Motor at
3 or 9 orsquoclock
A set of optional mounting rails are required for this
installation This is the base mounting position required with
the easy access option
Fig 3 Horizontal Ceiling Hung
In this installation the supports can be positioned for
mounting the motor at either 6 or 12 orsquoclock
Fig 4 Horizontal Ceiling Hung with Motor at3 or 9 orsquoclock
A set of optional mounting rails are required for this
installation
Fig 5 Vertical Mount
All TCB fans can be mounted vertically (ceiling hung or base
mount) for either upward or downward airflow Optional
mounting rails are recommended
NOTE
All fans are shown with optional vibration isolators See the
appropriate submittal drawings or installation manual for
complete dimensional data
TCB Inline Fan - Belt Drive
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 632
6 A
B
C
D
E
21 2
CBRU fans do
ot incorporate
rovisions for
nternal wiring
xternal wiring from
he roof to unit must
e provided by
thers
0 4 8 12 16 20 24
CFM x 1000
18
16
14
12
10
08
06
04
02
00
P r e s s u r e
L o s s ( i n
c h e s )
1 6
1 8
2 2
2 4
3 0 3 6
0 1 2 3 4
CFM x 1000
08
07
06
05
04
03
02
01
00
(
)
0 9
1 0
1 2
1 3
System Effect Curves
Sizes 9-13 Sizes 16-36
Dimensional Data
The TCBRU is ideal for roof upblast exhaust systems
with moderate system static pressures and for
applications where quiet operation is essential
Standard features include a necked-down windband
section which creates the high outlet velocities
necessary to carry contaminated exhausts away from
the roof deck All TCBRU fans include motor coversfor weather protection of the motor and drives gravity
operated dampers to prevent backflow into the
building and a welded curb cap for ease in mounting
to a roof curb TCBRU fans are available in either
painted steel or aluminum construction
Typical applications include
bull Low cfmhigh velocity exhaust
bull General exhaust
bull Fume hood exhaust
bull Industrial process exhaust
When selecting TCBRU fans use the TCB inline performance data
(pgs 12 to 31) along with the following system effect curves The
pressure loss determined below must be added to the extended
system static pressure to assure accurate selections Greenheckrsquos
Computer Aided Product Selection (CAPS) software will add these
system effects automatically
Size A B C D E Minimum CFMRequired to Open Dampers
09 22 211 frasl 2 23 45 20 425
10 22 211 frasl 2 23 45 20 425
12 22 211 frasl 2 23 45 20 1250
13 4 231 frasl 2 241 frasl 2 50 1 frasl 2 24 1800
16 28 25 1 frasl 2 28 1 frasl 2 53 28 2030
18 34 28 1 frasl 2 31 571 frasl 2 30 2570
22 40 34 35 1 frasl 2 64 34 2740
24 46 36 1 frasl 2 42 74 1 frasl 2 40 4760
30 52 42 1 frasl 4 481 frasl 2 84 46 6600
36 58 451 frasl 2 54 94 1 frasl 2 52 8700
All dimensions shown in inches
TCBRU Roof Upblast Fan
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 732
7
A B
C
D
W
21 2 in
L
Hood End View Hood Side View
TCBRS fans donot incorporateprovisions for internal wiring
External wiring fromthe roof to unit mustbe provided byothers
0 4 8 12 16 20 24
CFM x 1000
0 9
1 0
1 2
1 3
1 6
1 8
2 2 2
4
3 0
3 6
018
016
014
012
010
008
006
004
002
000
P r e s s u r e
L o s s ( i n c h e s )
System Effect Curves
Dimensional Data
The TCBRS roof mounted supply fan is designed
for intake air systems with pressures up to 4 inches
of wg and where low sound is required The TCBRS
hood intake is located at a sufficient height above
the roof to limit entry of roof debris and snow In
addition the hood has sufficient intake area to keep
velocities low Filters are available to collect dustand moisture before entering the building Motor
and drive protection is provided with a weatherproof
motor cover For ease of installation TCBRS fans are
shipped assembled and have curb caps for attaching
to roof curbs TCBRS fans are available in either
painted steel or aluminum construction
Typical applications include
bull Ducted supply systems
bull Industrial space supply
bull Filtered supply
TCBRS fan selections can be made using the TCB inline
performance data (pgs 12 to 31) along with the following
system effect curves The pressure loss determined to the
left must be added to the external system static pressure
to assure accurate selections Greenheckrsquos Computer
Aided Product Selection (CAPS) software will add thesesystem effects automatically
Size A B C D L W
09 22 211 frasl 2 251 frasl 2 391 frasl 2 39 46
10 22 211 frasl 2 251 frasl 2 391 frasl 2 39 46
12 22 211 frasl 2 251 frasl 2 391 frasl 2 39 4613 24 231 frasl 2 27 431 frasl 2 39 54
16 28 25 1 frasl 2 31 471 frasl 2 51 55
18 34 28 1 frasl 2 331 frasl 2 50 63 64
22 40 34 38 1 frasl 2 59 75 73
24 46 36 1 frasl 2 45 67 1 frasl 2 87 82
30 52 42 1 frasl 4 52 1 frasl 2 76 99 88
36 58 45 1 frasl 2 58 851 frasl 2 111 88
All dimensions shown in inches
TCBRS Roof Supply Fan
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 832
8
Optional Construction Features
Aluminum Construction
Aluminum construction is available on the TCB TCBRU and TCBRS Aluminum fans are an excellent choice for
applications involving moisture or coastal installations
Easy Access Construction
The Easy Access option is highly recommended to allow forinspection cleaning and service of internal fan components
By removing one access panel service to the wheel shaft
and bearing assembly is possible without removing duct
connections In addition all internal fan components can be
removed from the fan through the easy access panel
Easy Access construction is available on all levels and sizes
of TCB TCBRU and TCBRS Easy Access is also available
with aluminum fan construction
The Easy Access panel is located 180deg from the motor
position
Standard Construction Features
Inlet amp Outlet Flanges
Flanged inlets and outlets with mounting holes are
provided for duct connections (TCB only)
Housing
Housings are continuously welded steel and coated
with Permatector trade
Protective Coating
All steel constructed units are coated with
Permatectortrade a thermosetting polyester urethane
Aluminum units are uncoated
Type B Spark Resistance
All fans have aluminum wheels and a nonferrous
(aluminum) rub ring which surrounds the fanshaft where it passes through the drive cover
This construction meets Type B spark resistant
requirements
Bearings
Standard bearings are grease lubricated self-aligning
ball type in pillow block mounts Bearings are selected
for a minimum L10 life in excess of 80000 hours (L50 average life of 400000 hours) at maximum cataloged
operating speeds
Belt amp Bearing Tube
Belts bearings and drives are protected from the
airstream by heavy gauge belt tubes and bolted
bearing covers with shaft seals
Extended
Lube Lines
Lubrication lines with grease
fittings allow bearing lubricationwithout disassembling the fan
TCB - 1 - 24 - 30Tubular CentrifugalBelt Drive
TCB - Inline FanTCBRU - Roof Upblast FanTCBRS - Roof Supply Fan
Level of Construction1 or 2
Motor Horsepower
4 = 1 4 30=3 3 = 1 3 50=5
5 = 1 2 75=7 1 2
7 = 3 4 100=10
10=1 150=15
15=11 2 200=20 20=2
Fan Size09-36
Model Number CodeThe model number system is designed to completely identify
the fan A detailed explanation of the model number code for
TCB fans is shown below
Construction Features
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 932
9
Inline grease exhaust fans are excellent alternative for kitchen applications when roof or wall mounted ventilators
are not practical The TCB with UL 762 grease option is designed to withstand the demands of high temperature
kitchen grease exhaust and high-pressure duct washes
Continuously welded housing and integral duct flanges
provide air and water tight design
Bearing cover gasketed and includes a labyrinth shaft seal
to prevent moisture leakage during normal operation and
while cleaning with high pressure solvents
Continuously welded belt tube keeps the belts and
bearings clean
Two threaded drain connections are located 90deg from the
motor location to allow for removal of grease and moisture
UL 762 is concerned with fans
designed for removal of smoke and
grease laden vapors with airstream
temperatures up to 300degF
bull Meets all UL 705 Requirements
bull Bolted Access Door
bull Drain Connectionbull Meets requirements of NFPA 96
Ventilation Control and Fire
Protection of Commercial
Cooking Operations
Listed Power
Ventilation for
Restaurant
Exhaust Appliances
13G3
Maximum
Operating
Temperature
300degF
The TCB inline grease fan is tough to beat when
packaged with our full line of kitchen hoods and grease
extraction options Take advantage of Greenheckrsquos
expertise in providing a total solution in kitchen
ventilation equipment
A Tough Package to Beat
Leak Resistant Construction Features
bull Inline grease exhaust fans should be installed near the end of the duct run to reduce sound at the hood
bull Inline fan must be securely bolted to the exhaust duct per NFPA-96 guidelines Greenheckrsquos companion flange
are recommended for ease of installation
bull Grease exhaust fans and ductwork must maintain 18 inches (46 cm) minimum clearance to combustible
material If the ductwork and fan are insulated the inspection door must be accessible for maintenancebull A minimum of 10 ft (30 m) of clearance must be kept from the fan outlet to adjacent buildings property lines
or the closest point of any air intake or operable window at or below the plane of the exhaust termination
bull Greenheck recommends that all inline grease applications be reviewed by your local code official to ensure
compliance with NFPA IMC and other local codes
System Design Guidelines
1
2
3
4
5
6
7
Mounting and Serviceability Features
4 6
7
5 14
Optional Construction forUL 762 Restaurant Exhaust
Universal mounting brackets allow for rotation of the motor to
the 3 or 9 orsquoclock position at the jobsiteDuct flanges and access door bolt locations are no more
than 4 inches (100 mm) on center per NFPA 96
ldquoEasy Access Doorrdquo provides access for duct cleaning and allows removal of the wheel
shaft and bearings for maintenance Gasket is rated for 400degF (200degC) and prevents
leakage during operation [Fan is rated for 300degF (149degC) continous operation]
Air1047298ow
Duct to heat source
Ambient temperaturenot to exceed 120ordmF
Wall andor ceiling should enclosefan when used for emergency heatand smoke exhaust Enclosure shallbe per NFPA 96 or local building codes
Roof
Cooling air fordrives andbearings
Minimum ductat discharge
To buildingexterior
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1032
10
Electrical Accessories
Belt Guard (TCB only) Belt guards are totally enclosed to provide protection
from rotating pulleys and belts Belt guards meet
OSHA guidelines
Motor Cover (Weatherhood) Weatherproof motor covers shield the motor and
drive components from dust dirt and moisture when
used in outdoor applications Motor covers also
provide protection from rotating pulleys and belts and
meet OSHA guidelines Motor covers are standard on
TCBRU and TCBRS models
Inlet and Outlet Companion Flanges
(TCB only) Companion inlet flanges and outlet flanges with
prepunched holes are available for all fan sizes in
painted steel construction
Inlet and Outlet Guards (TCB TCBRU)
Removable inlet and outlet guards provide protectionfor personnel and equipment in non-ducted
installations These guards meet OSHA guidelines
TCBRU fans are available with outlet screens to
shield the fan discharge and damper from debris
Inspection Door Bolted or hinged doors provide access for cleaning or
inspection
Inspection Section (TCB only) Inspection sections serve as a length of duct that can
be easily removed to provide for complete access to
the fan for servicing Each section includes a bolted
inspection door
Isolators (TCB only) Both base mount or hanging isolators are available in
either neoprene or spring mounts The isolators are
furnished in sets of four and are sized to match the
weight of each fan
Mounting Rails (TCB only) Mounting rails are required for horizontal mounting
of TCB fans when the motor is to be located in
the 3 or 9 orsquoclock position Mounting rails are also
recommended for all vertically mounted inline fans
See page 5 for additional details
Protective Coatings Greenheck has a wide offering of protective coatings
Consult Greenheckrsquos Product Application Guide
FA110-04R4 Performance Coatings for Ventilation
Products for a complete listing of coatings and a
relative resistance chart
Inlet Vane Dampers (TCB only) Nested inlet vane dampers for controlling air volume
are available on model TCB inline fans with Level 2
steel construction in fan sizes 12 through 36
Birdscreen Insect Screen (TCBRS only)
TCBRS fans are available with either aluminum insectscreen or birdscreen at the hood intake (Birdscreen is
standard)
Roof Curbs (TCBRU TCBRS) Prefabricated roof curbs are available to reduce
installation time and costs by ensuring compatibility
between the fan the curb and the roof opening
All curbs are lined with fiberglass insulation to
prevent condensation and reduce sound levels See
Greenheckrsquos Roof Curb Extensions and Equipment
Supports catalog for complete details
Washable Aluminum Filters (TCBRS only)
Helps trap dust and dirt before it enters the fanFilters can be removed for cleaning
Enclosure Application Toggle Heavy Duty
NEMA-1 Indoor General Purpose Yes Yes
NEMA-12 Indoor DustDrip Tight Yes YesNEMA-3R IndoorOutdoor Rainproof Yes Yes
NEMA-4 IndoorOutdoor Watertight Yes Yes
NEMA-4X IndoorOutdoor Watertight
(Corrosion Resistant) Yes Yes
NEMA-7 amp 9 Indoor Hazardous Locations Yes No
Toggle type and heavy duty disconnect switches are available for positive
electrical shut-off and safety in servicing fans The following switches are
available to meet individual electrical requirements
Accessories
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1132
11
Inspection
Section
Outlet Guard
Belt Guard
Motor Cover
Companion Flange
(Outlet)NeopreneIsolator
Spring Base
Isolator
Inspection
Door
Easy Access
Inlet Guard
CompanionFlange (Inlet)
Mounting Rails
Spring HangingIsolator
Isolator Neoprene Hanging
Accessories (Model TCB shown)
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
12
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
360 195846 002 999 003 1260 006
53 60 75
420 228941 003 1071 004 1314 007 1526 011
57 63 77 92
480 2601040 004 1155 005 1380 009 1576 012 1758 017
63 68 80 93 106
540 2931144 005 1245 006 1449 010 1635 014 1807 019 1968 023 2115 028
71 74 84 95 107 120 133
600 326
1250 006 1341 008 1523 012 1704 016 1865 021 2017 026 2163 031 2298 036
78 81 88 99 110 122 135 147
660 3581357 007 1439 009 1606 014 1774 018 1930 023 2074 029 2212 034 2346 040 2472 046
86 88 93 104 114 126 137 149 162
720 3911465 009 1542 011 1692 016 1845 021 1999 026 2137 032 2270 038 2395 043 2520 050
94 96 100 109 120 131 140 150 163
780 4231576 012 1647 014 1786 018 1928 024 2069 029 2206 035 2331 041 2454 047 2570 054
102 104 108 115 127 136 145 154 165
840 4561688 014 1752 016 1882 021 2012 027 2142 033 2276 039 2400 045 2515 052 2629 059
110 112 117 123 133 142 150 160 170
900 4891801 017 1859 019 1980 025 2100 030 2225 036 2347 043 2469 050 2584 056
120 122 127 133 139 148 157 166
960 5211914 020 1966 023 2081 028 2195 034 2310 040 2424 047 2540 054
130 132 140 142 147 154 164
1020 5542028 024 2075 026 2184 032 2292 038 2395 044 2507 052 2612 059
144 149 150 151 155 163 172
1080 5862141 028 2186 031 2288 037 2389 043 2490 050 2592 057
159 159 160 162 166 172
1140 6192255 033 2298 036 2394 042 2487 049 2585 055
169 169 171 174 178
1200 6522370 038 2410 041 2500 047 2590 054
179 180 183 186
TCB-1-09 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2645
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm3114)3
Max Motor Frame Size - 56
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
13
TCB-2-09 Level 2 Construction
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3330)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg
025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
400 2171198 005 1460 008 1893 018
73 87 119
480 2601332 006 1566 010 1971 020 2309 032
82 96 127 157
560 3041480 009 1686 013 2059 024 2386 036 2671 049
92 106 135 165 191
640 3471635 011 1818 016 2158 027 2469 041 2749 055 3000 070 3228 086
106 117 146 174 20 23 25
720 3911799 015 1958 020 2275 032 2562 045 2830 061 3078 077 3305 094 3514 112
120 130 158 183 21 23 25 28
800 4341966 020 2108 025 2397 037 2666 051 2921 067 3158 085 3383 103 3591 121 3786 141
134 145 169 183 22 24 26 28 31
880 4782135 025 2262 030 2528 043 2784 058 3015 074 3250 093 3464 112 3669 132 3863 152
151 162 182 21 23 25 27 29 32
960 5212308 032 2425 037 2665 050 2905 066 3132 083 3343 101 3555 121 3752 142 3942 164
168 176 196 22 24 26 28 31 33
1040 5652482 039 2590 045 2810 059 3033 075 3251 093 3453 111 3648 131 3844 153 4027 176
184 193 21 23 25 27 29 32 34
1120 6082658 048 2757 054 2960 068 3168 085 3372 103 3571 123 3754 143 3937 165
20 21 23 25 27 29 31 33
1200 6522835 058 2925 065 3113 079 3306 096 3501 115 3691 135 3872 157 4041 179
22 23 24 26 28 30 32 35
1280 6953012 070 3095 076 3271 091 3453 109 3636 128 3813 149 3991 171
24 25 26 28 29 32 34
1360 7393190 083 3269 090 3434 105 3603 123 3773 143 3945 164
26 26 28 29 31 34
1440 7823368 097 3444 105 3599 121 3756 139 3917 159
28 28 30 31 33
1520 8263547 114 3619 121 3765 138 3909 156
30 30 32 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
14
TCB-1-10 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2555
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm2760)3
Max Motor Frame Size - 143T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
480 260858 003 1011 005 1253 009
49 57 73
560 304947 004 1089 006 1321 011 1511 015
55 63 77 93
640 3471042 005 1171 008 1394 013 1578 018 1740 023 1892 029
63 70 82 96 112 133
720 3911141 007 1259 009 1470 015 1649 021 1806 027 1949 033 2079 039
72 76 89 100 115 132 150
800 4341239 009 1349 012 1548 018 1723 024 1876 031 2015 037 2144 044 2263 051
80 84 96 107 119 135 148 161
880 4781340 011 1444 014 1630 021 1798 027 1949 034 2084 042 2211 049 2329 057 2440 064
88 92 102 113 125 137 150 162 176
960 5211441 014 1541 017 1716 024 1876 031 2023 039 2157 047 2280 055 2396 063 2506 071
97 101 109 121 133 141 152 165 179
1040 5651544 017 1640 021 1805 028 1957 035 2099 044 2231 052 2352 060 2465 069
105 109 117 129 139 148 157 169
1120 6081648 021 1739 025 1895 032 2042 040 2178 049 2306 058 2426 067 2538 076
113 117 127 138 146 155 165 177
1200 6521752 025 1839 029 1989 037 2129 046 2259 055 2383 064 2501 073
122 126 137 145 153 163 175
1280 6951858 030 1940 034 2085 043 2218 052 2343 061 2464 071
132 137 145 152 162 173
1360 7391964 035 2041 040 2183 049 2308 058 2430 068 2545 078
145 149 154 162 172 183
1440 7822071 041 2144 046 2282 056 2401 066 2519 076
156 158 164 173 183
1520 8262177 048 2247 053 2380 064 2497 074
164 167 175 184
1600 8692285 056 2351 061 2479 072
173 177 185
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
15
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-10 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3120)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 3261300 007 1504 011 1875 021 2213 032
73 82 105 132
700 3801453 010 1630 014 1966 024 2273 036 2560 049
84 91 110 133 156
800 4341611 013 1768 018 2070 029 2355 042 2619 055 2872 070 3102 086
100 101 118 137 158 182 20
900 4891773 017 1917 023 2188 034 2448 048 2698 062 2932 078 3160 094 3371 111 3568 129
112 113 127 143 162 185 20 22 25
1000 543
1937 023 2071 029 2319 041 2559 055 2790 070 3011 086 3220 103 3430 122 3626 140
124 127 136 152 170 190 21 23 25
1100 5972104 029 2228 035 2457 048 2677 063 2892 079 3103 096 3303 114 3490 132 3685 152
138 143 146 161 179 195 21 23 25
1200 6522276 036 2389 043 2601 057 2807 073 3009 089 3199 107 3394 125 3578 145 3751 165
154 154 159 172 189 20 21 23 25
1300 7062449 045 2552 052 2753 067 2944 083 3128 101 3315 119 3488 138 3670 159 3841 180
164 166 172 183 195 21 22 24 25
1400 7602623 055 2717 062 2907 079 3083 095 3261 114 3433 133 3603 153 3763 173 3933 196
175 177 185 193 20 21 23 24 26
1500 8152797 066 2883 074 3063 092 3231 109 3398 128 3557 148 3721 169 3878 191 4026 212
186 189 197 20 21 22 23 25 26
1600 8692973 079 3052 087 3223 106 3384 125 3537 144 3693 165 3840 186 3995 209
198 20 21 21 22 23 24 25
1700 9233149 094 3224 103 3384 122 3538 142 3683 162 3831 184 3974 206
21 21 22 22 23 23 25
1800 9783325 110 3396 119 3546 140 3693 161 3834 182 3970 204
22 22 23 23 24 24
1900 10323502 129 3570 138 3710 159 3852 182 3988 204
23 24 24 25 25
2000 10863679 149 3744 159 3875 181 4012 204
25 25 25 26
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
16
TCB-1-12 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2490
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 3436
Maximum bhp at a given rpm mdash (rpm2202)3
Max Motor Frame Size - 145T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 0075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
700 380853 006 958 008 1158 014 1345 021 1518 028
62 66 79 94 110
800 434943 008 1042 011 1218 017 1386 024 1551 031 1703 040
66 70 83 96 111 125
900 4891037 010 1128 013 1287 020 1442 027 1587 035 1736 044 1873 053 2000 063
71 76 87 99 112 126 142 155
1000 5431132 013 1216 017 1363 024 1506 031 1643 040 1771 049 1906 059 2033 069 2151 079
78 83 91 103 115 128 143 156 170
1100 597
1229 016 1305 020 1447 028 1574 036 1702 045 1827 055 1943 065 2066 075 2183 086
86 89 96 108 120 133 144 157 171
1200 6521326 020 1398 025 1532 034 1649 042 1769 051 1884 061 1999 071 2105 082 2216 094
92 95 103 113 126 139 149 159 173
1300 7061426 025 1492 030 1619 039 1732 049 1839 058 1950 068 2055 079 2161 090 2260 102
98 102 112 121 134 145 154 164 176
1400 7601526 031 1588 036 1707 046 1817 056 1916 066 2019 076 2120 088 2217 099 2316 111
106 112 122 132 142 151 160 170 181
1500 8151627 037 1684 042 1796 053 1903 064 1999 075 2089 085 2188 097 2281 109 2372 121
119 125 135 144 149 157 167 176 187
1600 8691729 044 1781 050 1886 061 1990 073 2084 085 2170 096 2258 107 2350 120 2436 133
134 139 150 153 157 165 174 183 194
1700 9231830 053 1879 058 1980 070 2077 083 2170 095 2254 107 2334 119 2419 132
151 157 159 162 167 173 181 191
1800 9781932 062 1978 068 2074 080 2166 093 2256 107 2339 120 2417 132
166 166 168 171 176 182 190
1900 10322034 072 2078 078 2169 091 2256 105 2343 119 2425 133
173 173 176 180 185 192
2000 10862137 083 2179 090 2265 103 2348 118 2432 133
180 181 184 189 195
2100 11412240 096 2280 102 2361 117 2442 132
187 188 192 198
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
17
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-12 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 3274
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 321
Maximum bhp at a given rpm mdash (rpm2315)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
750 4071009 008 1226 014 1587 027
55 67 98
900 4891119 011 1315 018 1648 032 1936 049 2182 067
63 76 102 131 159
1050 5701238 015 1419 023 1728 039 1995 056 2240 076 2456 096
75 85 110 136 164 190
1200 6521363 020 1529 029 1813 046 2070 065 2299 085 2514 108 2710 131 2890 155
89 96 120 142 169 195 22 24
1350 733
1495 027 1643 036 1911 055 2151 076 2372 097 2574 120 2768 145 2948 171 3115 197
104 111 132 152 176 20 22 25 28
1500 8151630 034 1764 044 2018 066 2240 088 2452 111 2647 135 2828 160 3007 187 3174 216
120 129 145 166 186 21 23 26 29
1650 8961767 044 1887 054 2127 077 2338 101 2534 126 2727 151 2903 178 3067 205 3233 235
139 144 159 184 199 22 24 27 30
1800 9781908 055 2018 066 2239 090 2445 117 2630 143 2808 170 2983 198 3145 227
159 165 180 199 22 23 25 28
1950 10592053 068 2151 079 2356 105 2554 134 2731 162 2900 190 3064 220 3225 250
182 188 20 22 23 25 27 29
2100 11412198 083 2286 095 2477 122 2664 152 2839 183 2997 213 3154 244
21 22 22 23 25 27 29
2250 12222344 100 2423 113 2599 141 2777 173 2948 205 3104 238 3250 271
24 24 25 26 27 29 32
2400 13042490 119 2560 133 2726 163 2896 196 3058 230 3212 265
26 26 27 28 30 32
2550 13852637 141 2703 156 2858 187 3016 221 3169 257
28 29 29 31 32
2700 14672785 166 2847 181 2991 214 3138 248
31 31 32 34
2850 15482933 193 2992 209 3126 243 3262 279
34 34 35 37
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
18
TCB-1-13 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2355
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 3435
Maximum bhp at a given rpm mdash (rpm2119)3
Max Motor Frame Size - 145T
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 265660 003 792 005 1019 010
41 51 69
750 331760 005 874 007 1073 013 1254 019
48 58 71 84
900 398864 007 967 010 1146 016 1305 023 1459 030
58 64 75 86 102
1050 464973 009 1067 013 1230 020 1378 027 1512 036 1646 044 1770 053
66 70 80 91 103 120 140
1200 530
1085 013 1171 017 1321 024 1457 032 1585 041 1703 051 1820 061 1933 071 2039 081
72 77 86 96 108 120 136 153 172
1350 5971199 017 1277 022 1419 030 1545 039 1662 048 1777 058 1883 069 1984 080 2089 091
81 85 94 103 114 125 136 151 167
1500 6631316 023 1387 027 1520 037 1637 046 1749 059 1853 067 1957 078 2054 090 2146 102
90 94 102 112 122 132 143 155 169
1650 7301434 029 1499 034 1623 044 1736 055 1839 065 1940 077 2034 088 2128 100 2219 113
100 104 113 123 132 143 153 165 178
1800 7961552 037 1613 042 1729 054 1836 065 1935 076 2029 088 2121 100 2207 113 2293 126
112 115 125 134 144 154 165 177 190
1950 8621672 045 1728 052 1836 064 1939 076 2034 088 2123 100 2209 113 2294 127
124 129 138 147 156 167 178 190
2100 9291792 056 1844 062 1947 076 2044 089 2135 102 2221 115 2302 128
138 142 151 161 170 181 192
2250 9951913 067 1962 075 2058 089 2150 103 2238 117 2321 131
152 157 167 177 186 196
2400 10612034 081 2080 088 2171 104 2258 119 2342 133
169 174 184 194 20
2550 11282155 095 2199 104 2285 120
187 192 20
2700 11942277 112 2319 121
21 21
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
19
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
TCB-2-13 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2971
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 353
Maximum bhp at a given rpm mdash (rpm1933)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
800 353828 008 1026 014 1379 030
38 56 104
1000 442934 011 1108 018 1418 035 1692 055
44 60 101 135
1200 5301048 016 1206 024 1479 042 1731 064 1961 087
58 72 101 130 165
1400 6191171 022 1313 031 1562 051 1784 073 2002 099 2201 126 2391 155
75 87 106 128 160 189 22
1600 707
1300 030 1424 040 1657 062 1865 086 2053 112 2247 141 2425 171 2596 203 2759 237
97 100 115 133 156 184 21 24 27
1800 7961431 039 1545 051 1759 075 1950 101 2134 129 2300 157 2472 189 2636 223 2790 258
114 113 125 144 160 181 21 24 26
2000 8841565 051 1669 063 1868 090 2050 118 2217 148 2381 178 2531 210 2683 244 2836 282
127 127 137 157 170 186 21 23 26
2200 9731700 064 1797 078 1979 107 2152 138 2312 169 2464 202 2612 236 2750 270 2883 306
142 145 156 169 183 198 21 23 26
2400 10611836 081 1928 096 2097 127 2260 160 2413 194 2556 228 2695 264 2831 301 2959 338
164 169 174 182 197 21 23 24 26
2600 11501975 100 2060 116 2219 150 2371 185 2517 221 2656 257 2785 295 2914 334
190 192 193 196 21 23 24 26
2800 12382115 122 2194 140 2343 175 2484 212 2626 251 2758 290 2885 330
21 21 21 22 23 24 26
3000 13272256 148 2329 166 2470 204 2605 243 2737 284 2864 325
24 24 24 24 25 26
3200 14152397 177 2464 196 2600 236 2728 278 2849 320
26 26 26 27 27
3400 15042539 210 2601 230 2731 272 2852 316 2969 361
29 29 30 30 30
3600 15922681 247 2739 267 2863 312
33 33 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
20
TCB-1-16 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2000
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 4384
Maximum bhp at a given rpm mdash (rpm1378)3
Max Motor Frame Size - 182T
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1000 308507 005 612 009 802 017
37 43 59
1250 385584 008 671 012 833 021 985 032
45 49 62 81
1500 462668 011 743 016 884 026 1016 038 1145 052
54 58 69 84 103
1750 540755 016 821 021 944 032 1065 045 1176 059 1289 075 1392 091
64 68 79 93 105 120 136
2000 617
844 022 904 028 1014 040 1119 054 1225 069 1322 085 1422 102 1517 120 1605 139
76 81 92 104 113 124 140 157 175
2250 694934 030 989 036 1090 049 1185 064 1278 080 1373 097 1460 115 1547 134 1635 154
89 94 107 114 123 133 146 161 179
2500 7711026 039 1077 047 1169 061 1257 076 1342 092 1425 110 1511 130 1591 149 1666 170
104 110 119 126 134 144 156 169 184
2750 8481118 051 1166 059 1252 074 1334 091 1411 107 1489 126 1564 146 1643 167 1717 188
121 124 131 138 147 157 168 181 194
3000 9251210 064 1256 073 1337 090 1412 107 1486 125 1556 144 1627 165 1695 186 1769 209
134 138 145 152 161 171 183 194 21
3250 10031303 080 1347 090 1423 108 1494 127 1563 146 1630 166 1695 186 1760 209 1823 232
149 153 161 169 177 187 199 21 22
3500 10801397 098 1438 109 1511 128 1578 148 1642 169 1706 190 1768 211 1828 233 1889 258
166 170 179 187 195 21 22 23 24
3750 11571491 119 1530 130 1599 152 1663 173 1725 194 1784 216 1844 239 1900 262 1956 286
185 189 197 21 22 23 24 25 27
4000 12341585 143 1622 155 1689 178 1750 200 1809 223 1865 246 1921 270 1976 295
20 21 22 23 24 25 26 28
4250 13111680 170 1714 183 1779 207 1838 231 1893 255 1948 280 1999 304
23 23 24 25 26 28 29
4500 13881775 200 1807 214 1869 240 1926 265 1979 291
25 26 27 28 30
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
21
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
TCB-2-16 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2431
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 432
Maximum bhp at a given rpm mdash (rpm1406)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1200 370668 011 842 020 1137 041
46 61 104
1500 462749 015 899 025 1166 049 1395 077
55 68 102 138
1800 555843 021 969 033 1208 059 1424 089 1616 121
71 77 104 135 168
2100 648944 030 1053 042 1268 071 1461 103 1647 138 1813 175 1972 215
83 88 111 134 166 196 22
2400 740
1047 040 1144 054 1336 085 1518 120 1684 157 1847 197 1996 238 2140 283 2275 329
99 105 120 140 166 195 22 25 27
2700 8331152 053 1243 068 1412 101 1579 139 1739 179 1885 221 2033 266 2169 312 2297 359
116 122 132 150 171 195 22 25 28
3000 9251260 069 1345 086 1498 121 1651 161 1799 204 1941 248 2070 295 2206 344 2333 394
132 136 144 162 182 20 23 25 28
3300 10181373 089 1448 107 1588 144 1727 186 1866 231 2001 279 2129 328 2247 379 2370 432
147 151 161 177 195 22 24 26 29
3600 11111486 112 1553 131 1686 171 1813 215 1939 262 2065 312 2188 365 2306 418 2416 473
166 171 182 193 21 23 25 28 30
3900 12031600 140 1658 159 1786 202 1900 247 2020 297 2138 349 2252 404 2366 461
189 194 20 21 23 25 27 29
4200 12961715 172 1766 191 1888 238 1996 285 2106 336 2213 390 2324 448 2430 508
21 21 22 23 24 26 29 31
4500 13881831 208 1878 228 1990 277 2095 328 2193 380 2298 437 2398 496
23 23 24 25 27 28 31
4800 14811946 250 1992 271 2094 322 2196 376 2289 430 2385 488
25 26 27 28 29 31
5100 15742062 296 2105 319 2199 371 2297 429 2388 486
28 28 29 30 32
5400 16662179 349 2219 373 2305 426 2399 487
30 31 32 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
22
TCB-1-18 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1645
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 4843
Maximum bhp at a given rpm mdash (rpm1147)3
Max Motor Frame Size - 182T
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg
0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1500 298486 008 568 012 724 023
43 49 62
1800 357552 011 623 016 755 028 883 042
54 57 67 81
2100 417622 016 683 021 799 034 911 048 1022 065 1123 082
67 68 77 85 99 116
2400 477693 021 749 028 852 041 950 056 1048 073 1147 092 1238 112 1322 133
80 81 90 95 103 120 135 148
2700 536
765 029 817 036 911 050 1001 066 1088 084 1174 103 1262 124 1346 146 1424 169
91 94 103 105 113 125 138 150 164
3000 596838 037 887 045 972 061 1056 078 1136 097 1214 117 1292 138 1369 161 1448 185
102 106 111 115 122 133 142 153 166
3300 656912 048 957 057 1038 074 1115 092 1187 111 1261 132 1331 154 1403 177 1472 202
112 114 120 126 133 141 149 158 168
3600 715987 061 1029 070 1105 089 1176 108 1246 128 1312 149 1379 172 1443 196 1510 222
121 125 131 138 145 152 160 168 178
3900 7751063 075 1102 085 1174 106 1239 126 1305 147 1368 170 1430 193 1491 218 1549 244
133 137 143 149 157 165 173 181 189
4200 8341139 092 1175 103 1244 125 1307 147 1366 169 1428 193 1485 217 1542 243 1599 269
146 149 155 163 171 179 187 195 20
4500 8941215 112 1249 124 1315 147 1375 170 1430 193 1488 218 1544 244 1597 270
160 162 169 176 185 194 20 21
4800 9541292 134 1323 147 1386 172 1444 197 1498 221 1549 246 1604 273
171 174 181 190 199 21 22
5100 10131369 159 1399 172 1458 199 1513 226 1565 252 1615 278
184 187 195 20 21 23
5400 10731446 188 1474 201 1530 229 1584 258 1634 285
197 20 21 22 23
5700 11331523 219 1550 233 1603 263
21 22 22
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 432
4
WindbandHood Panels
HousingCurb Cap
Housing
Model TCB Model TCBRUModel TCBRS
Steel Construction (gauge)
Aluminum Construction (thickness in inches)
Size Housing Curb Cap WindbandHood
Panels
Shaft Diameter (in)
Level 1 Level 2
09 12 12 20 22 3 frasl 4 1
10 12 12 20 22 3 frasl 4 1
12 12 12 20 22 3 frasl 4 1
13 12 12 20 22 3 frasl 4 1
16 12 12 20 22 1 13 frasl 16
18 12 12 20 22 1 13 frasl 16
22 10 12 20 22 1 17
frasl 16
24 10 12 20 22 1 111 frasl 16
30 10 12 20 22 11 frasl 4 115 frasl 16
36 10 12 20 22 11 frasl 2 115 frasl 16
Size Housing Curb Cap WindbandHood
Panels
Shaft Diameter (in)
Level 1 Level 2
09 0125 0125 0051 0051 3 frasl 4 1
10 0125 0125 0051 0051 3 frasl 4 1
12 0125 0125 0051 0051 3 frasl 4 1
13 0125 0125 0051 0051 3 frasl 4 1
16 0125 0125 0051 0051 1 13 frasl 16
18 0125 0125 0051 0051 1 13 frasl 16
22 0125 0125 0051 0051 1 17 frasl 16
24 0125 0125 0051 0051 1 111 frasl 16
30 019 0125 0051 0051 11 frasl 4 115 frasl 16
36 019 0125 0051 0051 11 frasl 2 115 frasl 16
Construction Specifications
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 532
5
Horizontal Base Mount
Fig 1
Horizontal Base MountMotor at 3 or 9 oclock position
Fig 2
OptionalMounting Rail
Horizontal Ceiling HungMotor at 3 or 9 oclock position
Fig 4
OptionaMounting R
Horizontal Ceiling Hung
Fig 3
Vertical Base Mount
Fig 5
Easy AccessOption
Easy AccessOption
Vertical Ceiling Hung
The Model TCB inline fan is the ideal choice for
ducted systems Greenheckrsquos standard fan can be
mounted in any position from horizontal to vertical
allowing installation in the smallest possible space
at the lowest installation cost The centrifugal wheels
used in this design provide higher efficiencies and
lower sound levels than propeller type inline fanswhen used in medium pressure ducted systems TCB
fans are available in either painted steel or aluminum
construction
Typical applications include
bull General exhaust or supply
bull Industrial space ventilation
bull Fume hood exhaust (special coatings are available)
bull Combustion air
bull Roof exhaust or supply (with weatherhood)
bull Restaurant grease exhaust
Universal Mounting
All TCB fans can be mounted horizontally or vertically For
ease of installation eight mounting brackets are welded
on each fan These eight brackets along with standard
mounting supports provide for Greenheckrsquos Universal
Mounting System
Fig 1 Horizontal Base Mount
Each fan is shipped as standard in this arrangement
Motor at 12 orsquoclock is standard
Fig 2 Horizontal Base Mount with Motor at
3 or 9 orsquoclock
A set of optional mounting rails are required for this
installation This is the base mounting position required with
the easy access option
Fig 3 Horizontal Ceiling Hung
In this installation the supports can be positioned for
mounting the motor at either 6 or 12 orsquoclock
Fig 4 Horizontal Ceiling Hung with Motor at3 or 9 orsquoclock
A set of optional mounting rails are required for this
installation
Fig 5 Vertical Mount
All TCB fans can be mounted vertically (ceiling hung or base
mount) for either upward or downward airflow Optional
mounting rails are recommended
NOTE
All fans are shown with optional vibration isolators See the
appropriate submittal drawings or installation manual for
complete dimensional data
TCB Inline Fan - Belt Drive
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 632
6 A
B
C
D
E
21 2
CBRU fans do
ot incorporate
rovisions for
nternal wiring
xternal wiring from
he roof to unit must
e provided by
thers
0 4 8 12 16 20 24
CFM x 1000
18
16
14
12
10
08
06
04
02
00
P r e s s u r e
L o s s ( i n
c h e s )
1 6
1 8
2 2
2 4
3 0 3 6
0 1 2 3 4
CFM x 1000
08
07
06
05
04
03
02
01
00
(
)
0 9
1 0
1 2
1 3
System Effect Curves
Sizes 9-13 Sizes 16-36
Dimensional Data
The TCBRU is ideal for roof upblast exhaust systems
with moderate system static pressures and for
applications where quiet operation is essential
Standard features include a necked-down windband
section which creates the high outlet velocities
necessary to carry contaminated exhausts away from
the roof deck All TCBRU fans include motor coversfor weather protection of the motor and drives gravity
operated dampers to prevent backflow into the
building and a welded curb cap for ease in mounting
to a roof curb TCBRU fans are available in either
painted steel or aluminum construction
Typical applications include
bull Low cfmhigh velocity exhaust
bull General exhaust
bull Fume hood exhaust
bull Industrial process exhaust
When selecting TCBRU fans use the TCB inline performance data
(pgs 12 to 31) along with the following system effect curves The
pressure loss determined below must be added to the extended
system static pressure to assure accurate selections Greenheckrsquos
Computer Aided Product Selection (CAPS) software will add these
system effects automatically
Size A B C D E Minimum CFMRequired to Open Dampers
09 22 211 frasl 2 23 45 20 425
10 22 211 frasl 2 23 45 20 425
12 22 211 frasl 2 23 45 20 1250
13 4 231 frasl 2 241 frasl 2 50 1 frasl 2 24 1800
16 28 25 1 frasl 2 28 1 frasl 2 53 28 2030
18 34 28 1 frasl 2 31 571 frasl 2 30 2570
22 40 34 35 1 frasl 2 64 34 2740
24 46 36 1 frasl 2 42 74 1 frasl 2 40 4760
30 52 42 1 frasl 4 481 frasl 2 84 46 6600
36 58 451 frasl 2 54 94 1 frasl 2 52 8700
All dimensions shown in inches
TCBRU Roof Upblast Fan
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 732
7
A B
C
D
W
21 2 in
L
Hood End View Hood Side View
TCBRS fans donot incorporateprovisions for internal wiring
External wiring fromthe roof to unit mustbe provided byothers
0 4 8 12 16 20 24
CFM x 1000
0 9
1 0
1 2
1 3
1 6
1 8
2 2 2
4
3 0
3 6
018
016
014
012
010
008
006
004
002
000
P r e s s u r e
L o s s ( i n c h e s )
System Effect Curves
Dimensional Data
The TCBRS roof mounted supply fan is designed
for intake air systems with pressures up to 4 inches
of wg and where low sound is required The TCBRS
hood intake is located at a sufficient height above
the roof to limit entry of roof debris and snow In
addition the hood has sufficient intake area to keep
velocities low Filters are available to collect dustand moisture before entering the building Motor
and drive protection is provided with a weatherproof
motor cover For ease of installation TCBRS fans are
shipped assembled and have curb caps for attaching
to roof curbs TCBRS fans are available in either
painted steel or aluminum construction
Typical applications include
bull Ducted supply systems
bull Industrial space supply
bull Filtered supply
TCBRS fan selections can be made using the TCB inline
performance data (pgs 12 to 31) along with the following
system effect curves The pressure loss determined to the
left must be added to the external system static pressure
to assure accurate selections Greenheckrsquos Computer
Aided Product Selection (CAPS) software will add thesesystem effects automatically
Size A B C D L W
09 22 211 frasl 2 251 frasl 2 391 frasl 2 39 46
10 22 211 frasl 2 251 frasl 2 391 frasl 2 39 46
12 22 211 frasl 2 251 frasl 2 391 frasl 2 39 4613 24 231 frasl 2 27 431 frasl 2 39 54
16 28 25 1 frasl 2 31 471 frasl 2 51 55
18 34 28 1 frasl 2 331 frasl 2 50 63 64
22 40 34 38 1 frasl 2 59 75 73
24 46 36 1 frasl 2 45 67 1 frasl 2 87 82
30 52 42 1 frasl 4 52 1 frasl 2 76 99 88
36 58 45 1 frasl 2 58 851 frasl 2 111 88
All dimensions shown in inches
TCBRS Roof Supply Fan
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 832
8
Optional Construction Features
Aluminum Construction
Aluminum construction is available on the TCB TCBRU and TCBRS Aluminum fans are an excellent choice for
applications involving moisture or coastal installations
Easy Access Construction
The Easy Access option is highly recommended to allow forinspection cleaning and service of internal fan components
By removing one access panel service to the wheel shaft
and bearing assembly is possible without removing duct
connections In addition all internal fan components can be
removed from the fan through the easy access panel
Easy Access construction is available on all levels and sizes
of TCB TCBRU and TCBRS Easy Access is also available
with aluminum fan construction
The Easy Access panel is located 180deg from the motor
position
Standard Construction Features
Inlet amp Outlet Flanges
Flanged inlets and outlets with mounting holes are
provided for duct connections (TCB only)
Housing
Housings are continuously welded steel and coated
with Permatector trade
Protective Coating
All steel constructed units are coated with
Permatectortrade a thermosetting polyester urethane
Aluminum units are uncoated
Type B Spark Resistance
All fans have aluminum wheels and a nonferrous
(aluminum) rub ring which surrounds the fanshaft where it passes through the drive cover
This construction meets Type B spark resistant
requirements
Bearings
Standard bearings are grease lubricated self-aligning
ball type in pillow block mounts Bearings are selected
for a minimum L10 life in excess of 80000 hours (L50 average life of 400000 hours) at maximum cataloged
operating speeds
Belt amp Bearing Tube
Belts bearings and drives are protected from the
airstream by heavy gauge belt tubes and bolted
bearing covers with shaft seals
Extended
Lube Lines
Lubrication lines with grease
fittings allow bearing lubricationwithout disassembling the fan
TCB - 1 - 24 - 30Tubular CentrifugalBelt Drive
TCB - Inline FanTCBRU - Roof Upblast FanTCBRS - Roof Supply Fan
Level of Construction1 or 2
Motor Horsepower
4 = 1 4 30=3 3 = 1 3 50=5
5 = 1 2 75=7 1 2
7 = 3 4 100=10
10=1 150=15
15=11 2 200=20 20=2
Fan Size09-36
Model Number CodeThe model number system is designed to completely identify
the fan A detailed explanation of the model number code for
TCB fans is shown below
Construction Features
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 932
9
Inline grease exhaust fans are excellent alternative for kitchen applications when roof or wall mounted ventilators
are not practical The TCB with UL 762 grease option is designed to withstand the demands of high temperature
kitchen grease exhaust and high-pressure duct washes
Continuously welded housing and integral duct flanges
provide air and water tight design
Bearing cover gasketed and includes a labyrinth shaft seal
to prevent moisture leakage during normal operation and
while cleaning with high pressure solvents
Continuously welded belt tube keeps the belts and
bearings clean
Two threaded drain connections are located 90deg from the
motor location to allow for removal of grease and moisture
UL 762 is concerned with fans
designed for removal of smoke and
grease laden vapors with airstream
temperatures up to 300degF
bull Meets all UL 705 Requirements
bull Bolted Access Door
bull Drain Connectionbull Meets requirements of NFPA 96
Ventilation Control and Fire
Protection of Commercial
Cooking Operations
Listed Power
Ventilation for
Restaurant
Exhaust Appliances
13G3
Maximum
Operating
Temperature
300degF
The TCB inline grease fan is tough to beat when
packaged with our full line of kitchen hoods and grease
extraction options Take advantage of Greenheckrsquos
expertise in providing a total solution in kitchen
ventilation equipment
A Tough Package to Beat
Leak Resistant Construction Features
bull Inline grease exhaust fans should be installed near the end of the duct run to reduce sound at the hood
bull Inline fan must be securely bolted to the exhaust duct per NFPA-96 guidelines Greenheckrsquos companion flange
are recommended for ease of installation
bull Grease exhaust fans and ductwork must maintain 18 inches (46 cm) minimum clearance to combustible
material If the ductwork and fan are insulated the inspection door must be accessible for maintenancebull A minimum of 10 ft (30 m) of clearance must be kept from the fan outlet to adjacent buildings property lines
or the closest point of any air intake or operable window at or below the plane of the exhaust termination
bull Greenheck recommends that all inline grease applications be reviewed by your local code official to ensure
compliance with NFPA IMC and other local codes
System Design Guidelines
1
2
3
4
5
6
7
Mounting and Serviceability Features
4 6
7
5 14
Optional Construction forUL 762 Restaurant Exhaust
Universal mounting brackets allow for rotation of the motor to
the 3 or 9 orsquoclock position at the jobsiteDuct flanges and access door bolt locations are no more
than 4 inches (100 mm) on center per NFPA 96
ldquoEasy Access Doorrdquo provides access for duct cleaning and allows removal of the wheel
shaft and bearings for maintenance Gasket is rated for 400degF (200degC) and prevents
leakage during operation [Fan is rated for 300degF (149degC) continous operation]
Air1047298ow
Duct to heat source
Ambient temperaturenot to exceed 120ordmF
Wall andor ceiling should enclosefan when used for emergency heatand smoke exhaust Enclosure shallbe per NFPA 96 or local building codes
Roof
Cooling air fordrives andbearings
Minimum ductat discharge
To buildingexterior
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1032
10
Electrical Accessories
Belt Guard (TCB only) Belt guards are totally enclosed to provide protection
from rotating pulleys and belts Belt guards meet
OSHA guidelines
Motor Cover (Weatherhood) Weatherproof motor covers shield the motor and
drive components from dust dirt and moisture when
used in outdoor applications Motor covers also
provide protection from rotating pulleys and belts and
meet OSHA guidelines Motor covers are standard on
TCBRU and TCBRS models
Inlet and Outlet Companion Flanges
(TCB only) Companion inlet flanges and outlet flanges with
prepunched holes are available for all fan sizes in
painted steel construction
Inlet and Outlet Guards (TCB TCBRU)
Removable inlet and outlet guards provide protectionfor personnel and equipment in non-ducted
installations These guards meet OSHA guidelines
TCBRU fans are available with outlet screens to
shield the fan discharge and damper from debris
Inspection Door Bolted or hinged doors provide access for cleaning or
inspection
Inspection Section (TCB only) Inspection sections serve as a length of duct that can
be easily removed to provide for complete access to
the fan for servicing Each section includes a bolted
inspection door
Isolators (TCB only) Both base mount or hanging isolators are available in
either neoprene or spring mounts The isolators are
furnished in sets of four and are sized to match the
weight of each fan
Mounting Rails (TCB only) Mounting rails are required for horizontal mounting
of TCB fans when the motor is to be located in
the 3 or 9 orsquoclock position Mounting rails are also
recommended for all vertically mounted inline fans
See page 5 for additional details
Protective Coatings Greenheck has a wide offering of protective coatings
Consult Greenheckrsquos Product Application Guide
FA110-04R4 Performance Coatings for Ventilation
Products for a complete listing of coatings and a
relative resistance chart
Inlet Vane Dampers (TCB only) Nested inlet vane dampers for controlling air volume
are available on model TCB inline fans with Level 2
steel construction in fan sizes 12 through 36
Birdscreen Insect Screen (TCBRS only)
TCBRS fans are available with either aluminum insectscreen or birdscreen at the hood intake (Birdscreen is
standard)
Roof Curbs (TCBRU TCBRS) Prefabricated roof curbs are available to reduce
installation time and costs by ensuring compatibility
between the fan the curb and the roof opening
All curbs are lined with fiberglass insulation to
prevent condensation and reduce sound levels See
Greenheckrsquos Roof Curb Extensions and Equipment
Supports catalog for complete details
Washable Aluminum Filters (TCBRS only)
Helps trap dust and dirt before it enters the fanFilters can be removed for cleaning
Enclosure Application Toggle Heavy Duty
NEMA-1 Indoor General Purpose Yes Yes
NEMA-12 Indoor DustDrip Tight Yes YesNEMA-3R IndoorOutdoor Rainproof Yes Yes
NEMA-4 IndoorOutdoor Watertight Yes Yes
NEMA-4X IndoorOutdoor Watertight
(Corrosion Resistant) Yes Yes
NEMA-7 amp 9 Indoor Hazardous Locations Yes No
Toggle type and heavy duty disconnect switches are available for positive
electrical shut-off and safety in servicing fans The following switches are
available to meet individual electrical requirements
Accessories
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1132
11
Inspection
Section
Outlet Guard
Belt Guard
Motor Cover
Companion Flange
(Outlet)NeopreneIsolator
Spring Base
Isolator
Inspection
Door
Easy Access
Inlet Guard
CompanionFlange (Inlet)
Mounting Rails
Spring HangingIsolator
Isolator Neoprene Hanging
Accessories (Model TCB shown)
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
12
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
360 195846 002 999 003 1260 006
53 60 75
420 228941 003 1071 004 1314 007 1526 011
57 63 77 92
480 2601040 004 1155 005 1380 009 1576 012 1758 017
63 68 80 93 106
540 2931144 005 1245 006 1449 010 1635 014 1807 019 1968 023 2115 028
71 74 84 95 107 120 133
600 326
1250 006 1341 008 1523 012 1704 016 1865 021 2017 026 2163 031 2298 036
78 81 88 99 110 122 135 147
660 3581357 007 1439 009 1606 014 1774 018 1930 023 2074 029 2212 034 2346 040 2472 046
86 88 93 104 114 126 137 149 162
720 3911465 009 1542 011 1692 016 1845 021 1999 026 2137 032 2270 038 2395 043 2520 050
94 96 100 109 120 131 140 150 163
780 4231576 012 1647 014 1786 018 1928 024 2069 029 2206 035 2331 041 2454 047 2570 054
102 104 108 115 127 136 145 154 165
840 4561688 014 1752 016 1882 021 2012 027 2142 033 2276 039 2400 045 2515 052 2629 059
110 112 117 123 133 142 150 160 170
900 4891801 017 1859 019 1980 025 2100 030 2225 036 2347 043 2469 050 2584 056
120 122 127 133 139 148 157 166
960 5211914 020 1966 023 2081 028 2195 034 2310 040 2424 047 2540 054
130 132 140 142 147 154 164
1020 5542028 024 2075 026 2184 032 2292 038 2395 044 2507 052 2612 059
144 149 150 151 155 163 172
1080 5862141 028 2186 031 2288 037 2389 043 2490 050 2592 057
159 159 160 162 166 172
1140 6192255 033 2298 036 2394 042 2487 049 2585 055
169 169 171 174 178
1200 6522370 038 2410 041 2500 047 2590 054
179 180 183 186
TCB-1-09 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2645
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm3114)3
Max Motor Frame Size - 56
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
13
TCB-2-09 Level 2 Construction
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3330)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg
025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
400 2171198 005 1460 008 1893 018
73 87 119
480 2601332 006 1566 010 1971 020 2309 032
82 96 127 157
560 3041480 009 1686 013 2059 024 2386 036 2671 049
92 106 135 165 191
640 3471635 011 1818 016 2158 027 2469 041 2749 055 3000 070 3228 086
106 117 146 174 20 23 25
720 3911799 015 1958 020 2275 032 2562 045 2830 061 3078 077 3305 094 3514 112
120 130 158 183 21 23 25 28
800 4341966 020 2108 025 2397 037 2666 051 2921 067 3158 085 3383 103 3591 121 3786 141
134 145 169 183 22 24 26 28 31
880 4782135 025 2262 030 2528 043 2784 058 3015 074 3250 093 3464 112 3669 132 3863 152
151 162 182 21 23 25 27 29 32
960 5212308 032 2425 037 2665 050 2905 066 3132 083 3343 101 3555 121 3752 142 3942 164
168 176 196 22 24 26 28 31 33
1040 5652482 039 2590 045 2810 059 3033 075 3251 093 3453 111 3648 131 3844 153 4027 176
184 193 21 23 25 27 29 32 34
1120 6082658 048 2757 054 2960 068 3168 085 3372 103 3571 123 3754 143 3937 165
20 21 23 25 27 29 31 33
1200 6522835 058 2925 065 3113 079 3306 096 3501 115 3691 135 3872 157 4041 179
22 23 24 26 28 30 32 35
1280 6953012 070 3095 076 3271 091 3453 109 3636 128 3813 149 3991 171
24 25 26 28 29 32 34
1360 7393190 083 3269 090 3434 105 3603 123 3773 143 3945 164
26 26 28 29 31 34
1440 7823368 097 3444 105 3599 121 3756 139 3917 159
28 28 30 31 33
1520 8263547 114 3619 121 3765 138 3909 156
30 30 32 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
14
TCB-1-10 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2555
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm2760)3
Max Motor Frame Size - 143T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
480 260858 003 1011 005 1253 009
49 57 73
560 304947 004 1089 006 1321 011 1511 015
55 63 77 93
640 3471042 005 1171 008 1394 013 1578 018 1740 023 1892 029
63 70 82 96 112 133
720 3911141 007 1259 009 1470 015 1649 021 1806 027 1949 033 2079 039
72 76 89 100 115 132 150
800 4341239 009 1349 012 1548 018 1723 024 1876 031 2015 037 2144 044 2263 051
80 84 96 107 119 135 148 161
880 4781340 011 1444 014 1630 021 1798 027 1949 034 2084 042 2211 049 2329 057 2440 064
88 92 102 113 125 137 150 162 176
960 5211441 014 1541 017 1716 024 1876 031 2023 039 2157 047 2280 055 2396 063 2506 071
97 101 109 121 133 141 152 165 179
1040 5651544 017 1640 021 1805 028 1957 035 2099 044 2231 052 2352 060 2465 069
105 109 117 129 139 148 157 169
1120 6081648 021 1739 025 1895 032 2042 040 2178 049 2306 058 2426 067 2538 076
113 117 127 138 146 155 165 177
1200 6521752 025 1839 029 1989 037 2129 046 2259 055 2383 064 2501 073
122 126 137 145 153 163 175
1280 6951858 030 1940 034 2085 043 2218 052 2343 061 2464 071
132 137 145 152 162 173
1360 7391964 035 2041 040 2183 049 2308 058 2430 068 2545 078
145 149 154 162 172 183
1440 7822071 041 2144 046 2282 056 2401 066 2519 076
156 158 164 173 183
1520 8262177 048 2247 053 2380 064 2497 074
164 167 175 184
1600 8692285 056 2351 061 2479 072
173 177 185
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
15
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-10 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3120)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 3261300 007 1504 011 1875 021 2213 032
73 82 105 132
700 3801453 010 1630 014 1966 024 2273 036 2560 049
84 91 110 133 156
800 4341611 013 1768 018 2070 029 2355 042 2619 055 2872 070 3102 086
100 101 118 137 158 182 20
900 4891773 017 1917 023 2188 034 2448 048 2698 062 2932 078 3160 094 3371 111 3568 129
112 113 127 143 162 185 20 22 25
1000 543
1937 023 2071 029 2319 041 2559 055 2790 070 3011 086 3220 103 3430 122 3626 140
124 127 136 152 170 190 21 23 25
1100 5972104 029 2228 035 2457 048 2677 063 2892 079 3103 096 3303 114 3490 132 3685 152
138 143 146 161 179 195 21 23 25
1200 6522276 036 2389 043 2601 057 2807 073 3009 089 3199 107 3394 125 3578 145 3751 165
154 154 159 172 189 20 21 23 25
1300 7062449 045 2552 052 2753 067 2944 083 3128 101 3315 119 3488 138 3670 159 3841 180
164 166 172 183 195 21 22 24 25
1400 7602623 055 2717 062 2907 079 3083 095 3261 114 3433 133 3603 153 3763 173 3933 196
175 177 185 193 20 21 23 24 26
1500 8152797 066 2883 074 3063 092 3231 109 3398 128 3557 148 3721 169 3878 191 4026 212
186 189 197 20 21 22 23 25 26
1600 8692973 079 3052 087 3223 106 3384 125 3537 144 3693 165 3840 186 3995 209
198 20 21 21 22 23 24 25
1700 9233149 094 3224 103 3384 122 3538 142 3683 162 3831 184 3974 206
21 21 22 22 23 23 25
1800 9783325 110 3396 119 3546 140 3693 161 3834 182 3970 204
22 22 23 23 24 24
1900 10323502 129 3570 138 3710 159 3852 182 3988 204
23 24 24 25 25
2000 10863679 149 3744 159 3875 181 4012 204
25 25 25 26
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
16
TCB-1-12 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2490
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 3436
Maximum bhp at a given rpm mdash (rpm2202)3
Max Motor Frame Size - 145T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 0075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
700 380853 006 958 008 1158 014 1345 021 1518 028
62 66 79 94 110
800 434943 008 1042 011 1218 017 1386 024 1551 031 1703 040
66 70 83 96 111 125
900 4891037 010 1128 013 1287 020 1442 027 1587 035 1736 044 1873 053 2000 063
71 76 87 99 112 126 142 155
1000 5431132 013 1216 017 1363 024 1506 031 1643 040 1771 049 1906 059 2033 069 2151 079
78 83 91 103 115 128 143 156 170
1100 597
1229 016 1305 020 1447 028 1574 036 1702 045 1827 055 1943 065 2066 075 2183 086
86 89 96 108 120 133 144 157 171
1200 6521326 020 1398 025 1532 034 1649 042 1769 051 1884 061 1999 071 2105 082 2216 094
92 95 103 113 126 139 149 159 173
1300 7061426 025 1492 030 1619 039 1732 049 1839 058 1950 068 2055 079 2161 090 2260 102
98 102 112 121 134 145 154 164 176
1400 7601526 031 1588 036 1707 046 1817 056 1916 066 2019 076 2120 088 2217 099 2316 111
106 112 122 132 142 151 160 170 181
1500 8151627 037 1684 042 1796 053 1903 064 1999 075 2089 085 2188 097 2281 109 2372 121
119 125 135 144 149 157 167 176 187
1600 8691729 044 1781 050 1886 061 1990 073 2084 085 2170 096 2258 107 2350 120 2436 133
134 139 150 153 157 165 174 183 194
1700 9231830 053 1879 058 1980 070 2077 083 2170 095 2254 107 2334 119 2419 132
151 157 159 162 167 173 181 191
1800 9781932 062 1978 068 2074 080 2166 093 2256 107 2339 120 2417 132
166 166 168 171 176 182 190
1900 10322034 072 2078 078 2169 091 2256 105 2343 119 2425 133
173 173 176 180 185 192
2000 10862137 083 2179 090 2265 103 2348 118 2432 133
180 181 184 189 195
2100 11412240 096 2280 102 2361 117 2442 132
187 188 192 198
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
17
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-12 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 3274
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 321
Maximum bhp at a given rpm mdash (rpm2315)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
750 4071009 008 1226 014 1587 027
55 67 98
900 4891119 011 1315 018 1648 032 1936 049 2182 067
63 76 102 131 159
1050 5701238 015 1419 023 1728 039 1995 056 2240 076 2456 096
75 85 110 136 164 190
1200 6521363 020 1529 029 1813 046 2070 065 2299 085 2514 108 2710 131 2890 155
89 96 120 142 169 195 22 24
1350 733
1495 027 1643 036 1911 055 2151 076 2372 097 2574 120 2768 145 2948 171 3115 197
104 111 132 152 176 20 22 25 28
1500 8151630 034 1764 044 2018 066 2240 088 2452 111 2647 135 2828 160 3007 187 3174 216
120 129 145 166 186 21 23 26 29
1650 8961767 044 1887 054 2127 077 2338 101 2534 126 2727 151 2903 178 3067 205 3233 235
139 144 159 184 199 22 24 27 30
1800 9781908 055 2018 066 2239 090 2445 117 2630 143 2808 170 2983 198 3145 227
159 165 180 199 22 23 25 28
1950 10592053 068 2151 079 2356 105 2554 134 2731 162 2900 190 3064 220 3225 250
182 188 20 22 23 25 27 29
2100 11412198 083 2286 095 2477 122 2664 152 2839 183 2997 213 3154 244
21 22 22 23 25 27 29
2250 12222344 100 2423 113 2599 141 2777 173 2948 205 3104 238 3250 271
24 24 25 26 27 29 32
2400 13042490 119 2560 133 2726 163 2896 196 3058 230 3212 265
26 26 27 28 30 32
2550 13852637 141 2703 156 2858 187 3016 221 3169 257
28 29 29 31 32
2700 14672785 166 2847 181 2991 214 3138 248
31 31 32 34
2850 15482933 193 2992 209 3126 243 3262 279
34 34 35 37
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
18
TCB-1-13 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2355
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 3435
Maximum bhp at a given rpm mdash (rpm2119)3
Max Motor Frame Size - 145T
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 265660 003 792 005 1019 010
41 51 69
750 331760 005 874 007 1073 013 1254 019
48 58 71 84
900 398864 007 967 010 1146 016 1305 023 1459 030
58 64 75 86 102
1050 464973 009 1067 013 1230 020 1378 027 1512 036 1646 044 1770 053
66 70 80 91 103 120 140
1200 530
1085 013 1171 017 1321 024 1457 032 1585 041 1703 051 1820 061 1933 071 2039 081
72 77 86 96 108 120 136 153 172
1350 5971199 017 1277 022 1419 030 1545 039 1662 048 1777 058 1883 069 1984 080 2089 091
81 85 94 103 114 125 136 151 167
1500 6631316 023 1387 027 1520 037 1637 046 1749 059 1853 067 1957 078 2054 090 2146 102
90 94 102 112 122 132 143 155 169
1650 7301434 029 1499 034 1623 044 1736 055 1839 065 1940 077 2034 088 2128 100 2219 113
100 104 113 123 132 143 153 165 178
1800 7961552 037 1613 042 1729 054 1836 065 1935 076 2029 088 2121 100 2207 113 2293 126
112 115 125 134 144 154 165 177 190
1950 8621672 045 1728 052 1836 064 1939 076 2034 088 2123 100 2209 113 2294 127
124 129 138 147 156 167 178 190
2100 9291792 056 1844 062 1947 076 2044 089 2135 102 2221 115 2302 128
138 142 151 161 170 181 192
2250 9951913 067 1962 075 2058 089 2150 103 2238 117 2321 131
152 157 167 177 186 196
2400 10612034 081 2080 088 2171 104 2258 119 2342 133
169 174 184 194 20
2550 11282155 095 2199 104 2285 120
187 192 20
2700 11942277 112 2319 121
21 21
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
19
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
TCB-2-13 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2971
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 353
Maximum bhp at a given rpm mdash (rpm1933)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
800 353828 008 1026 014 1379 030
38 56 104
1000 442934 011 1108 018 1418 035 1692 055
44 60 101 135
1200 5301048 016 1206 024 1479 042 1731 064 1961 087
58 72 101 130 165
1400 6191171 022 1313 031 1562 051 1784 073 2002 099 2201 126 2391 155
75 87 106 128 160 189 22
1600 707
1300 030 1424 040 1657 062 1865 086 2053 112 2247 141 2425 171 2596 203 2759 237
97 100 115 133 156 184 21 24 27
1800 7961431 039 1545 051 1759 075 1950 101 2134 129 2300 157 2472 189 2636 223 2790 258
114 113 125 144 160 181 21 24 26
2000 8841565 051 1669 063 1868 090 2050 118 2217 148 2381 178 2531 210 2683 244 2836 282
127 127 137 157 170 186 21 23 26
2200 9731700 064 1797 078 1979 107 2152 138 2312 169 2464 202 2612 236 2750 270 2883 306
142 145 156 169 183 198 21 23 26
2400 10611836 081 1928 096 2097 127 2260 160 2413 194 2556 228 2695 264 2831 301 2959 338
164 169 174 182 197 21 23 24 26
2600 11501975 100 2060 116 2219 150 2371 185 2517 221 2656 257 2785 295 2914 334
190 192 193 196 21 23 24 26
2800 12382115 122 2194 140 2343 175 2484 212 2626 251 2758 290 2885 330
21 21 21 22 23 24 26
3000 13272256 148 2329 166 2470 204 2605 243 2737 284 2864 325
24 24 24 24 25 26
3200 14152397 177 2464 196 2600 236 2728 278 2849 320
26 26 26 27 27
3400 15042539 210 2601 230 2731 272 2852 316 2969 361
29 29 30 30 30
3600 15922681 247 2739 267 2863 312
33 33 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
20
TCB-1-16 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2000
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 4384
Maximum bhp at a given rpm mdash (rpm1378)3
Max Motor Frame Size - 182T
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1000 308507 005 612 009 802 017
37 43 59
1250 385584 008 671 012 833 021 985 032
45 49 62 81
1500 462668 011 743 016 884 026 1016 038 1145 052
54 58 69 84 103
1750 540755 016 821 021 944 032 1065 045 1176 059 1289 075 1392 091
64 68 79 93 105 120 136
2000 617
844 022 904 028 1014 040 1119 054 1225 069 1322 085 1422 102 1517 120 1605 139
76 81 92 104 113 124 140 157 175
2250 694934 030 989 036 1090 049 1185 064 1278 080 1373 097 1460 115 1547 134 1635 154
89 94 107 114 123 133 146 161 179
2500 7711026 039 1077 047 1169 061 1257 076 1342 092 1425 110 1511 130 1591 149 1666 170
104 110 119 126 134 144 156 169 184
2750 8481118 051 1166 059 1252 074 1334 091 1411 107 1489 126 1564 146 1643 167 1717 188
121 124 131 138 147 157 168 181 194
3000 9251210 064 1256 073 1337 090 1412 107 1486 125 1556 144 1627 165 1695 186 1769 209
134 138 145 152 161 171 183 194 21
3250 10031303 080 1347 090 1423 108 1494 127 1563 146 1630 166 1695 186 1760 209 1823 232
149 153 161 169 177 187 199 21 22
3500 10801397 098 1438 109 1511 128 1578 148 1642 169 1706 190 1768 211 1828 233 1889 258
166 170 179 187 195 21 22 23 24
3750 11571491 119 1530 130 1599 152 1663 173 1725 194 1784 216 1844 239 1900 262 1956 286
185 189 197 21 22 23 24 25 27
4000 12341585 143 1622 155 1689 178 1750 200 1809 223 1865 246 1921 270 1976 295
20 21 22 23 24 25 26 28
4250 13111680 170 1714 183 1779 207 1838 231 1893 255 1948 280 1999 304
23 23 24 25 26 28 29
4500 13881775 200 1807 214 1869 240 1926 265 1979 291
25 26 27 28 30
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
21
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
TCB-2-16 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2431
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 432
Maximum bhp at a given rpm mdash (rpm1406)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1200 370668 011 842 020 1137 041
46 61 104
1500 462749 015 899 025 1166 049 1395 077
55 68 102 138
1800 555843 021 969 033 1208 059 1424 089 1616 121
71 77 104 135 168
2100 648944 030 1053 042 1268 071 1461 103 1647 138 1813 175 1972 215
83 88 111 134 166 196 22
2400 740
1047 040 1144 054 1336 085 1518 120 1684 157 1847 197 1996 238 2140 283 2275 329
99 105 120 140 166 195 22 25 27
2700 8331152 053 1243 068 1412 101 1579 139 1739 179 1885 221 2033 266 2169 312 2297 359
116 122 132 150 171 195 22 25 28
3000 9251260 069 1345 086 1498 121 1651 161 1799 204 1941 248 2070 295 2206 344 2333 394
132 136 144 162 182 20 23 25 28
3300 10181373 089 1448 107 1588 144 1727 186 1866 231 2001 279 2129 328 2247 379 2370 432
147 151 161 177 195 22 24 26 29
3600 11111486 112 1553 131 1686 171 1813 215 1939 262 2065 312 2188 365 2306 418 2416 473
166 171 182 193 21 23 25 28 30
3900 12031600 140 1658 159 1786 202 1900 247 2020 297 2138 349 2252 404 2366 461
189 194 20 21 23 25 27 29
4200 12961715 172 1766 191 1888 238 1996 285 2106 336 2213 390 2324 448 2430 508
21 21 22 23 24 26 29 31
4500 13881831 208 1878 228 1990 277 2095 328 2193 380 2298 437 2398 496
23 23 24 25 27 28 31
4800 14811946 250 1992 271 2094 322 2196 376 2289 430 2385 488
25 26 27 28 29 31
5100 15742062 296 2105 319 2199 371 2297 429 2388 486
28 28 29 30 32
5400 16662179 349 2219 373 2305 426 2399 487
30 31 32 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
22
TCB-1-18 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1645
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 4843
Maximum bhp at a given rpm mdash (rpm1147)3
Max Motor Frame Size - 182T
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg
0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1500 298486 008 568 012 724 023
43 49 62
1800 357552 011 623 016 755 028 883 042
54 57 67 81
2100 417622 016 683 021 799 034 911 048 1022 065 1123 082
67 68 77 85 99 116
2400 477693 021 749 028 852 041 950 056 1048 073 1147 092 1238 112 1322 133
80 81 90 95 103 120 135 148
2700 536
765 029 817 036 911 050 1001 066 1088 084 1174 103 1262 124 1346 146 1424 169
91 94 103 105 113 125 138 150 164
3000 596838 037 887 045 972 061 1056 078 1136 097 1214 117 1292 138 1369 161 1448 185
102 106 111 115 122 133 142 153 166
3300 656912 048 957 057 1038 074 1115 092 1187 111 1261 132 1331 154 1403 177 1472 202
112 114 120 126 133 141 149 158 168
3600 715987 061 1029 070 1105 089 1176 108 1246 128 1312 149 1379 172 1443 196 1510 222
121 125 131 138 145 152 160 168 178
3900 7751063 075 1102 085 1174 106 1239 126 1305 147 1368 170 1430 193 1491 218 1549 244
133 137 143 149 157 165 173 181 189
4200 8341139 092 1175 103 1244 125 1307 147 1366 169 1428 193 1485 217 1542 243 1599 269
146 149 155 163 171 179 187 195 20
4500 8941215 112 1249 124 1315 147 1375 170 1430 193 1488 218 1544 244 1597 270
160 162 169 176 185 194 20 21
4800 9541292 134 1323 147 1386 172 1444 197 1498 221 1549 246 1604 273
171 174 181 190 199 21 22
5100 10131369 159 1399 172 1458 199 1513 226 1565 252 1615 278
184 187 195 20 21 23
5400 10731446 188 1474 201 1530 229 1584 258 1634 285
197 20 21 22 23
5700 11331523 219 1550 233 1603 263
21 22 22
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 532
5
Horizontal Base Mount
Fig 1
Horizontal Base MountMotor at 3 or 9 oclock position
Fig 2
OptionalMounting Rail
Horizontal Ceiling HungMotor at 3 or 9 oclock position
Fig 4
OptionaMounting R
Horizontal Ceiling Hung
Fig 3
Vertical Base Mount
Fig 5
Easy AccessOption
Easy AccessOption
Vertical Ceiling Hung
The Model TCB inline fan is the ideal choice for
ducted systems Greenheckrsquos standard fan can be
mounted in any position from horizontal to vertical
allowing installation in the smallest possible space
at the lowest installation cost The centrifugal wheels
used in this design provide higher efficiencies and
lower sound levels than propeller type inline fanswhen used in medium pressure ducted systems TCB
fans are available in either painted steel or aluminum
construction
Typical applications include
bull General exhaust or supply
bull Industrial space ventilation
bull Fume hood exhaust (special coatings are available)
bull Combustion air
bull Roof exhaust or supply (with weatherhood)
bull Restaurant grease exhaust
Universal Mounting
All TCB fans can be mounted horizontally or vertically For
ease of installation eight mounting brackets are welded
on each fan These eight brackets along with standard
mounting supports provide for Greenheckrsquos Universal
Mounting System
Fig 1 Horizontal Base Mount
Each fan is shipped as standard in this arrangement
Motor at 12 orsquoclock is standard
Fig 2 Horizontal Base Mount with Motor at
3 or 9 orsquoclock
A set of optional mounting rails are required for this
installation This is the base mounting position required with
the easy access option
Fig 3 Horizontal Ceiling Hung
In this installation the supports can be positioned for
mounting the motor at either 6 or 12 orsquoclock
Fig 4 Horizontal Ceiling Hung with Motor at3 or 9 orsquoclock
A set of optional mounting rails are required for this
installation
Fig 5 Vertical Mount
All TCB fans can be mounted vertically (ceiling hung or base
mount) for either upward or downward airflow Optional
mounting rails are recommended
NOTE
All fans are shown with optional vibration isolators See the
appropriate submittal drawings or installation manual for
complete dimensional data
TCB Inline Fan - Belt Drive
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 632
6 A
B
C
D
E
21 2
CBRU fans do
ot incorporate
rovisions for
nternal wiring
xternal wiring from
he roof to unit must
e provided by
thers
0 4 8 12 16 20 24
CFM x 1000
18
16
14
12
10
08
06
04
02
00
P r e s s u r e
L o s s ( i n
c h e s )
1 6
1 8
2 2
2 4
3 0 3 6
0 1 2 3 4
CFM x 1000
08
07
06
05
04
03
02
01
00
(
)
0 9
1 0
1 2
1 3
System Effect Curves
Sizes 9-13 Sizes 16-36
Dimensional Data
The TCBRU is ideal for roof upblast exhaust systems
with moderate system static pressures and for
applications where quiet operation is essential
Standard features include a necked-down windband
section which creates the high outlet velocities
necessary to carry contaminated exhausts away from
the roof deck All TCBRU fans include motor coversfor weather protection of the motor and drives gravity
operated dampers to prevent backflow into the
building and a welded curb cap for ease in mounting
to a roof curb TCBRU fans are available in either
painted steel or aluminum construction
Typical applications include
bull Low cfmhigh velocity exhaust
bull General exhaust
bull Fume hood exhaust
bull Industrial process exhaust
When selecting TCBRU fans use the TCB inline performance data
(pgs 12 to 31) along with the following system effect curves The
pressure loss determined below must be added to the extended
system static pressure to assure accurate selections Greenheckrsquos
Computer Aided Product Selection (CAPS) software will add these
system effects automatically
Size A B C D E Minimum CFMRequired to Open Dampers
09 22 211 frasl 2 23 45 20 425
10 22 211 frasl 2 23 45 20 425
12 22 211 frasl 2 23 45 20 1250
13 4 231 frasl 2 241 frasl 2 50 1 frasl 2 24 1800
16 28 25 1 frasl 2 28 1 frasl 2 53 28 2030
18 34 28 1 frasl 2 31 571 frasl 2 30 2570
22 40 34 35 1 frasl 2 64 34 2740
24 46 36 1 frasl 2 42 74 1 frasl 2 40 4760
30 52 42 1 frasl 4 481 frasl 2 84 46 6600
36 58 451 frasl 2 54 94 1 frasl 2 52 8700
All dimensions shown in inches
TCBRU Roof Upblast Fan
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 732
7
A B
C
D
W
21 2 in
L
Hood End View Hood Side View
TCBRS fans donot incorporateprovisions for internal wiring
External wiring fromthe roof to unit mustbe provided byothers
0 4 8 12 16 20 24
CFM x 1000
0 9
1 0
1 2
1 3
1 6
1 8
2 2 2
4
3 0
3 6
018
016
014
012
010
008
006
004
002
000
P r e s s u r e
L o s s ( i n c h e s )
System Effect Curves
Dimensional Data
The TCBRS roof mounted supply fan is designed
for intake air systems with pressures up to 4 inches
of wg and where low sound is required The TCBRS
hood intake is located at a sufficient height above
the roof to limit entry of roof debris and snow In
addition the hood has sufficient intake area to keep
velocities low Filters are available to collect dustand moisture before entering the building Motor
and drive protection is provided with a weatherproof
motor cover For ease of installation TCBRS fans are
shipped assembled and have curb caps for attaching
to roof curbs TCBRS fans are available in either
painted steel or aluminum construction
Typical applications include
bull Ducted supply systems
bull Industrial space supply
bull Filtered supply
TCBRS fan selections can be made using the TCB inline
performance data (pgs 12 to 31) along with the following
system effect curves The pressure loss determined to the
left must be added to the external system static pressure
to assure accurate selections Greenheckrsquos Computer
Aided Product Selection (CAPS) software will add thesesystem effects automatically
Size A B C D L W
09 22 211 frasl 2 251 frasl 2 391 frasl 2 39 46
10 22 211 frasl 2 251 frasl 2 391 frasl 2 39 46
12 22 211 frasl 2 251 frasl 2 391 frasl 2 39 4613 24 231 frasl 2 27 431 frasl 2 39 54
16 28 25 1 frasl 2 31 471 frasl 2 51 55
18 34 28 1 frasl 2 331 frasl 2 50 63 64
22 40 34 38 1 frasl 2 59 75 73
24 46 36 1 frasl 2 45 67 1 frasl 2 87 82
30 52 42 1 frasl 4 52 1 frasl 2 76 99 88
36 58 45 1 frasl 2 58 851 frasl 2 111 88
All dimensions shown in inches
TCBRS Roof Supply Fan
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 832
8
Optional Construction Features
Aluminum Construction
Aluminum construction is available on the TCB TCBRU and TCBRS Aluminum fans are an excellent choice for
applications involving moisture or coastal installations
Easy Access Construction
The Easy Access option is highly recommended to allow forinspection cleaning and service of internal fan components
By removing one access panel service to the wheel shaft
and bearing assembly is possible without removing duct
connections In addition all internal fan components can be
removed from the fan through the easy access panel
Easy Access construction is available on all levels and sizes
of TCB TCBRU and TCBRS Easy Access is also available
with aluminum fan construction
The Easy Access panel is located 180deg from the motor
position
Standard Construction Features
Inlet amp Outlet Flanges
Flanged inlets and outlets with mounting holes are
provided for duct connections (TCB only)
Housing
Housings are continuously welded steel and coated
with Permatector trade
Protective Coating
All steel constructed units are coated with
Permatectortrade a thermosetting polyester urethane
Aluminum units are uncoated
Type B Spark Resistance
All fans have aluminum wheels and a nonferrous
(aluminum) rub ring which surrounds the fanshaft where it passes through the drive cover
This construction meets Type B spark resistant
requirements
Bearings
Standard bearings are grease lubricated self-aligning
ball type in pillow block mounts Bearings are selected
for a minimum L10 life in excess of 80000 hours (L50 average life of 400000 hours) at maximum cataloged
operating speeds
Belt amp Bearing Tube
Belts bearings and drives are protected from the
airstream by heavy gauge belt tubes and bolted
bearing covers with shaft seals
Extended
Lube Lines
Lubrication lines with grease
fittings allow bearing lubricationwithout disassembling the fan
TCB - 1 - 24 - 30Tubular CentrifugalBelt Drive
TCB - Inline FanTCBRU - Roof Upblast FanTCBRS - Roof Supply Fan
Level of Construction1 or 2
Motor Horsepower
4 = 1 4 30=3 3 = 1 3 50=5
5 = 1 2 75=7 1 2
7 = 3 4 100=10
10=1 150=15
15=11 2 200=20 20=2
Fan Size09-36
Model Number CodeThe model number system is designed to completely identify
the fan A detailed explanation of the model number code for
TCB fans is shown below
Construction Features
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 932
9
Inline grease exhaust fans are excellent alternative for kitchen applications when roof or wall mounted ventilators
are not practical The TCB with UL 762 grease option is designed to withstand the demands of high temperature
kitchen grease exhaust and high-pressure duct washes
Continuously welded housing and integral duct flanges
provide air and water tight design
Bearing cover gasketed and includes a labyrinth shaft seal
to prevent moisture leakage during normal operation and
while cleaning with high pressure solvents
Continuously welded belt tube keeps the belts and
bearings clean
Two threaded drain connections are located 90deg from the
motor location to allow for removal of grease and moisture
UL 762 is concerned with fans
designed for removal of smoke and
grease laden vapors with airstream
temperatures up to 300degF
bull Meets all UL 705 Requirements
bull Bolted Access Door
bull Drain Connectionbull Meets requirements of NFPA 96
Ventilation Control and Fire
Protection of Commercial
Cooking Operations
Listed Power
Ventilation for
Restaurant
Exhaust Appliances
13G3
Maximum
Operating
Temperature
300degF
The TCB inline grease fan is tough to beat when
packaged with our full line of kitchen hoods and grease
extraction options Take advantage of Greenheckrsquos
expertise in providing a total solution in kitchen
ventilation equipment
A Tough Package to Beat
Leak Resistant Construction Features
bull Inline grease exhaust fans should be installed near the end of the duct run to reduce sound at the hood
bull Inline fan must be securely bolted to the exhaust duct per NFPA-96 guidelines Greenheckrsquos companion flange
are recommended for ease of installation
bull Grease exhaust fans and ductwork must maintain 18 inches (46 cm) minimum clearance to combustible
material If the ductwork and fan are insulated the inspection door must be accessible for maintenancebull A minimum of 10 ft (30 m) of clearance must be kept from the fan outlet to adjacent buildings property lines
or the closest point of any air intake or operable window at or below the plane of the exhaust termination
bull Greenheck recommends that all inline grease applications be reviewed by your local code official to ensure
compliance with NFPA IMC and other local codes
System Design Guidelines
1
2
3
4
5
6
7
Mounting and Serviceability Features
4 6
7
5 14
Optional Construction forUL 762 Restaurant Exhaust
Universal mounting brackets allow for rotation of the motor to
the 3 or 9 orsquoclock position at the jobsiteDuct flanges and access door bolt locations are no more
than 4 inches (100 mm) on center per NFPA 96
ldquoEasy Access Doorrdquo provides access for duct cleaning and allows removal of the wheel
shaft and bearings for maintenance Gasket is rated for 400degF (200degC) and prevents
leakage during operation [Fan is rated for 300degF (149degC) continous operation]
Air1047298ow
Duct to heat source
Ambient temperaturenot to exceed 120ordmF
Wall andor ceiling should enclosefan when used for emergency heatand smoke exhaust Enclosure shallbe per NFPA 96 or local building codes
Roof
Cooling air fordrives andbearings
Minimum ductat discharge
To buildingexterior
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1032
10
Electrical Accessories
Belt Guard (TCB only) Belt guards are totally enclosed to provide protection
from rotating pulleys and belts Belt guards meet
OSHA guidelines
Motor Cover (Weatherhood) Weatherproof motor covers shield the motor and
drive components from dust dirt and moisture when
used in outdoor applications Motor covers also
provide protection from rotating pulleys and belts and
meet OSHA guidelines Motor covers are standard on
TCBRU and TCBRS models
Inlet and Outlet Companion Flanges
(TCB only) Companion inlet flanges and outlet flanges with
prepunched holes are available for all fan sizes in
painted steel construction
Inlet and Outlet Guards (TCB TCBRU)
Removable inlet and outlet guards provide protectionfor personnel and equipment in non-ducted
installations These guards meet OSHA guidelines
TCBRU fans are available with outlet screens to
shield the fan discharge and damper from debris
Inspection Door Bolted or hinged doors provide access for cleaning or
inspection
Inspection Section (TCB only) Inspection sections serve as a length of duct that can
be easily removed to provide for complete access to
the fan for servicing Each section includes a bolted
inspection door
Isolators (TCB only) Both base mount or hanging isolators are available in
either neoprene or spring mounts The isolators are
furnished in sets of four and are sized to match the
weight of each fan
Mounting Rails (TCB only) Mounting rails are required for horizontal mounting
of TCB fans when the motor is to be located in
the 3 or 9 orsquoclock position Mounting rails are also
recommended for all vertically mounted inline fans
See page 5 for additional details
Protective Coatings Greenheck has a wide offering of protective coatings
Consult Greenheckrsquos Product Application Guide
FA110-04R4 Performance Coatings for Ventilation
Products for a complete listing of coatings and a
relative resistance chart
Inlet Vane Dampers (TCB only) Nested inlet vane dampers for controlling air volume
are available on model TCB inline fans with Level 2
steel construction in fan sizes 12 through 36
Birdscreen Insect Screen (TCBRS only)
TCBRS fans are available with either aluminum insectscreen or birdscreen at the hood intake (Birdscreen is
standard)
Roof Curbs (TCBRU TCBRS) Prefabricated roof curbs are available to reduce
installation time and costs by ensuring compatibility
between the fan the curb and the roof opening
All curbs are lined with fiberglass insulation to
prevent condensation and reduce sound levels See
Greenheckrsquos Roof Curb Extensions and Equipment
Supports catalog for complete details
Washable Aluminum Filters (TCBRS only)
Helps trap dust and dirt before it enters the fanFilters can be removed for cleaning
Enclosure Application Toggle Heavy Duty
NEMA-1 Indoor General Purpose Yes Yes
NEMA-12 Indoor DustDrip Tight Yes YesNEMA-3R IndoorOutdoor Rainproof Yes Yes
NEMA-4 IndoorOutdoor Watertight Yes Yes
NEMA-4X IndoorOutdoor Watertight
(Corrosion Resistant) Yes Yes
NEMA-7 amp 9 Indoor Hazardous Locations Yes No
Toggle type and heavy duty disconnect switches are available for positive
electrical shut-off and safety in servicing fans The following switches are
available to meet individual electrical requirements
Accessories
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1132
11
Inspection
Section
Outlet Guard
Belt Guard
Motor Cover
Companion Flange
(Outlet)NeopreneIsolator
Spring Base
Isolator
Inspection
Door
Easy Access
Inlet Guard
CompanionFlange (Inlet)
Mounting Rails
Spring HangingIsolator
Isolator Neoprene Hanging
Accessories (Model TCB shown)
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
12
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
360 195846 002 999 003 1260 006
53 60 75
420 228941 003 1071 004 1314 007 1526 011
57 63 77 92
480 2601040 004 1155 005 1380 009 1576 012 1758 017
63 68 80 93 106
540 2931144 005 1245 006 1449 010 1635 014 1807 019 1968 023 2115 028
71 74 84 95 107 120 133
600 326
1250 006 1341 008 1523 012 1704 016 1865 021 2017 026 2163 031 2298 036
78 81 88 99 110 122 135 147
660 3581357 007 1439 009 1606 014 1774 018 1930 023 2074 029 2212 034 2346 040 2472 046
86 88 93 104 114 126 137 149 162
720 3911465 009 1542 011 1692 016 1845 021 1999 026 2137 032 2270 038 2395 043 2520 050
94 96 100 109 120 131 140 150 163
780 4231576 012 1647 014 1786 018 1928 024 2069 029 2206 035 2331 041 2454 047 2570 054
102 104 108 115 127 136 145 154 165
840 4561688 014 1752 016 1882 021 2012 027 2142 033 2276 039 2400 045 2515 052 2629 059
110 112 117 123 133 142 150 160 170
900 4891801 017 1859 019 1980 025 2100 030 2225 036 2347 043 2469 050 2584 056
120 122 127 133 139 148 157 166
960 5211914 020 1966 023 2081 028 2195 034 2310 040 2424 047 2540 054
130 132 140 142 147 154 164
1020 5542028 024 2075 026 2184 032 2292 038 2395 044 2507 052 2612 059
144 149 150 151 155 163 172
1080 5862141 028 2186 031 2288 037 2389 043 2490 050 2592 057
159 159 160 162 166 172
1140 6192255 033 2298 036 2394 042 2487 049 2585 055
169 169 171 174 178
1200 6522370 038 2410 041 2500 047 2590 054
179 180 183 186
TCB-1-09 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2645
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm3114)3
Max Motor Frame Size - 56
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
13
TCB-2-09 Level 2 Construction
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3330)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg
025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
400 2171198 005 1460 008 1893 018
73 87 119
480 2601332 006 1566 010 1971 020 2309 032
82 96 127 157
560 3041480 009 1686 013 2059 024 2386 036 2671 049
92 106 135 165 191
640 3471635 011 1818 016 2158 027 2469 041 2749 055 3000 070 3228 086
106 117 146 174 20 23 25
720 3911799 015 1958 020 2275 032 2562 045 2830 061 3078 077 3305 094 3514 112
120 130 158 183 21 23 25 28
800 4341966 020 2108 025 2397 037 2666 051 2921 067 3158 085 3383 103 3591 121 3786 141
134 145 169 183 22 24 26 28 31
880 4782135 025 2262 030 2528 043 2784 058 3015 074 3250 093 3464 112 3669 132 3863 152
151 162 182 21 23 25 27 29 32
960 5212308 032 2425 037 2665 050 2905 066 3132 083 3343 101 3555 121 3752 142 3942 164
168 176 196 22 24 26 28 31 33
1040 5652482 039 2590 045 2810 059 3033 075 3251 093 3453 111 3648 131 3844 153 4027 176
184 193 21 23 25 27 29 32 34
1120 6082658 048 2757 054 2960 068 3168 085 3372 103 3571 123 3754 143 3937 165
20 21 23 25 27 29 31 33
1200 6522835 058 2925 065 3113 079 3306 096 3501 115 3691 135 3872 157 4041 179
22 23 24 26 28 30 32 35
1280 6953012 070 3095 076 3271 091 3453 109 3636 128 3813 149 3991 171
24 25 26 28 29 32 34
1360 7393190 083 3269 090 3434 105 3603 123 3773 143 3945 164
26 26 28 29 31 34
1440 7823368 097 3444 105 3599 121 3756 139 3917 159
28 28 30 31 33
1520 8263547 114 3619 121 3765 138 3909 156
30 30 32 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
14
TCB-1-10 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2555
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm2760)3
Max Motor Frame Size - 143T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
480 260858 003 1011 005 1253 009
49 57 73
560 304947 004 1089 006 1321 011 1511 015
55 63 77 93
640 3471042 005 1171 008 1394 013 1578 018 1740 023 1892 029
63 70 82 96 112 133
720 3911141 007 1259 009 1470 015 1649 021 1806 027 1949 033 2079 039
72 76 89 100 115 132 150
800 4341239 009 1349 012 1548 018 1723 024 1876 031 2015 037 2144 044 2263 051
80 84 96 107 119 135 148 161
880 4781340 011 1444 014 1630 021 1798 027 1949 034 2084 042 2211 049 2329 057 2440 064
88 92 102 113 125 137 150 162 176
960 5211441 014 1541 017 1716 024 1876 031 2023 039 2157 047 2280 055 2396 063 2506 071
97 101 109 121 133 141 152 165 179
1040 5651544 017 1640 021 1805 028 1957 035 2099 044 2231 052 2352 060 2465 069
105 109 117 129 139 148 157 169
1120 6081648 021 1739 025 1895 032 2042 040 2178 049 2306 058 2426 067 2538 076
113 117 127 138 146 155 165 177
1200 6521752 025 1839 029 1989 037 2129 046 2259 055 2383 064 2501 073
122 126 137 145 153 163 175
1280 6951858 030 1940 034 2085 043 2218 052 2343 061 2464 071
132 137 145 152 162 173
1360 7391964 035 2041 040 2183 049 2308 058 2430 068 2545 078
145 149 154 162 172 183
1440 7822071 041 2144 046 2282 056 2401 066 2519 076
156 158 164 173 183
1520 8262177 048 2247 053 2380 064 2497 074
164 167 175 184
1600 8692285 056 2351 061 2479 072
173 177 185
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
15
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-10 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3120)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 3261300 007 1504 011 1875 021 2213 032
73 82 105 132
700 3801453 010 1630 014 1966 024 2273 036 2560 049
84 91 110 133 156
800 4341611 013 1768 018 2070 029 2355 042 2619 055 2872 070 3102 086
100 101 118 137 158 182 20
900 4891773 017 1917 023 2188 034 2448 048 2698 062 2932 078 3160 094 3371 111 3568 129
112 113 127 143 162 185 20 22 25
1000 543
1937 023 2071 029 2319 041 2559 055 2790 070 3011 086 3220 103 3430 122 3626 140
124 127 136 152 170 190 21 23 25
1100 5972104 029 2228 035 2457 048 2677 063 2892 079 3103 096 3303 114 3490 132 3685 152
138 143 146 161 179 195 21 23 25
1200 6522276 036 2389 043 2601 057 2807 073 3009 089 3199 107 3394 125 3578 145 3751 165
154 154 159 172 189 20 21 23 25
1300 7062449 045 2552 052 2753 067 2944 083 3128 101 3315 119 3488 138 3670 159 3841 180
164 166 172 183 195 21 22 24 25
1400 7602623 055 2717 062 2907 079 3083 095 3261 114 3433 133 3603 153 3763 173 3933 196
175 177 185 193 20 21 23 24 26
1500 8152797 066 2883 074 3063 092 3231 109 3398 128 3557 148 3721 169 3878 191 4026 212
186 189 197 20 21 22 23 25 26
1600 8692973 079 3052 087 3223 106 3384 125 3537 144 3693 165 3840 186 3995 209
198 20 21 21 22 23 24 25
1700 9233149 094 3224 103 3384 122 3538 142 3683 162 3831 184 3974 206
21 21 22 22 23 23 25
1800 9783325 110 3396 119 3546 140 3693 161 3834 182 3970 204
22 22 23 23 24 24
1900 10323502 129 3570 138 3710 159 3852 182 3988 204
23 24 24 25 25
2000 10863679 149 3744 159 3875 181 4012 204
25 25 25 26
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
16
TCB-1-12 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2490
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 3436
Maximum bhp at a given rpm mdash (rpm2202)3
Max Motor Frame Size - 145T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 0075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
700 380853 006 958 008 1158 014 1345 021 1518 028
62 66 79 94 110
800 434943 008 1042 011 1218 017 1386 024 1551 031 1703 040
66 70 83 96 111 125
900 4891037 010 1128 013 1287 020 1442 027 1587 035 1736 044 1873 053 2000 063
71 76 87 99 112 126 142 155
1000 5431132 013 1216 017 1363 024 1506 031 1643 040 1771 049 1906 059 2033 069 2151 079
78 83 91 103 115 128 143 156 170
1100 597
1229 016 1305 020 1447 028 1574 036 1702 045 1827 055 1943 065 2066 075 2183 086
86 89 96 108 120 133 144 157 171
1200 6521326 020 1398 025 1532 034 1649 042 1769 051 1884 061 1999 071 2105 082 2216 094
92 95 103 113 126 139 149 159 173
1300 7061426 025 1492 030 1619 039 1732 049 1839 058 1950 068 2055 079 2161 090 2260 102
98 102 112 121 134 145 154 164 176
1400 7601526 031 1588 036 1707 046 1817 056 1916 066 2019 076 2120 088 2217 099 2316 111
106 112 122 132 142 151 160 170 181
1500 8151627 037 1684 042 1796 053 1903 064 1999 075 2089 085 2188 097 2281 109 2372 121
119 125 135 144 149 157 167 176 187
1600 8691729 044 1781 050 1886 061 1990 073 2084 085 2170 096 2258 107 2350 120 2436 133
134 139 150 153 157 165 174 183 194
1700 9231830 053 1879 058 1980 070 2077 083 2170 095 2254 107 2334 119 2419 132
151 157 159 162 167 173 181 191
1800 9781932 062 1978 068 2074 080 2166 093 2256 107 2339 120 2417 132
166 166 168 171 176 182 190
1900 10322034 072 2078 078 2169 091 2256 105 2343 119 2425 133
173 173 176 180 185 192
2000 10862137 083 2179 090 2265 103 2348 118 2432 133
180 181 184 189 195
2100 11412240 096 2280 102 2361 117 2442 132
187 188 192 198
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
17
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-12 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 3274
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 321
Maximum bhp at a given rpm mdash (rpm2315)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
750 4071009 008 1226 014 1587 027
55 67 98
900 4891119 011 1315 018 1648 032 1936 049 2182 067
63 76 102 131 159
1050 5701238 015 1419 023 1728 039 1995 056 2240 076 2456 096
75 85 110 136 164 190
1200 6521363 020 1529 029 1813 046 2070 065 2299 085 2514 108 2710 131 2890 155
89 96 120 142 169 195 22 24
1350 733
1495 027 1643 036 1911 055 2151 076 2372 097 2574 120 2768 145 2948 171 3115 197
104 111 132 152 176 20 22 25 28
1500 8151630 034 1764 044 2018 066 2240 088 2452 111 2647 135 2828 160 3007 187 3174 216
120 129 145 166 186 21 23 26 29
1650 8961767 044 1887 054 2127 077 2338 101 2534 126 2727 151 2903 178 3067 205 3233 235
139 144 159 184 199 22 24 27 30
1800 9781908 055 2018 066 2239 090 2445 117 2630 143 2808 170 2983 198 3145 227
159 165 180 199 22 23 25 28
1950 10592053 068 2151 079 2356 105 2554 134 2731 162 2900 190 3064 220 3225 250
182 188 20 22 23 25 27 29
2100 11412198 083 2286 095 2477 122 2664 152 2839 183 2997 213 3154 244
21 22 22 23 25 27 29
2250 12222344 100 2423 113 2599 141 2777 173 2948 205 3104 238 3250 271
24 24 25 26 27 29 32
2400 13042490 119 2560 133 2726 163 2896 196 3058 230 3212 265
26 26 27 28 30 32
2550 13852637 141 2703 156 2858 187 3016 221 3169 257
28 29 29 31 32
2700 14672785 166 2847 181 2991 214 3138 248
31 31 32 34
2850 15482933 193 2992 209 3126 243 3262 279
34 34 35 37
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
18
TCB-1-13 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2355
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 3435
Maximum bhp at a given rpm mdash (rpm2119)3
Max Motor Frame Size - 145T
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 265660 003 792 005 1019 010
41 51 69
750 331760 005 874 007 1073 013 1254 019
48 58 71 84
900 398864 007 967 010 1146 016 1305 023 1459 030
58 64 75 86 102
1050 464973 009 1067 013 1230 020 1378 027 1512 036 1646 044 1770 053
66 70 80 91 103 120 140
1200 530
1085 013 1171 017 1321 024 1457 032 1585 041 1703 051 1820 061 1933 071 2039 081
72 77 86 96 108 120 136 153 172
1350 5971199 017 1277 022 1419 030 1545 039 1662 048 1777 058 1883 069 1984 080 2089 091
81 85 94 103 114 125 136 151 167
1500 6631316 023 1387 027 1520 037 1637 046 1749 059 1853 067 1957 078 2054 090 2146 102
90 94 102 112 122 132 143 155 169
1650 7301434 029 1499 034 1623 044 1736 055 1839 065 1940 077 2034 088 2128 100 2219 113
100 104 113 123 132 143 153 165 178
1800 7961552 037 1613 042 1729 054 1836 065 1935 076 2029 088 2121 100 2207 113 2293 126
112 115 125 134 144 154 165 177 190
1950 8621672 045 1728 052 1836 064 1939 076 2034 088 2123 100 2209 113 2294 127
124 129 138 147 156 167 178 190
2100 9291792 056 1844 062 1947 076 2044 089 2135 102 2221 115 2302 128
138 142 151 161 170 181 192
2250 9951913 067 1962 075 2058 089 2150 103 2238 117 2321 131
152 157 167 177 186 196
2400 10612034 081 2080 088 2171 104 2258 119 2342 133
169 174 184 194 20
2550 11282155 095 2199 104 2285 120
187 192 20
2700 11942277 112 2319 121
21 21
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
19
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
TCB-2-13 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2971
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 353
Maximum bhp at a given rpm mdash (rpm1933)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
800 353828 008 1026 014 1379 030
38 56 104
1000 442934 011 1108 018 1418 035 1692 055
44 60 101 135
1200 5301048 016 1206 024 1479 042 1731 064 1961 087
58 72 101 130 165
1400 6191171 022 1313 031 1562 051 1784 073 2002 099 2201 126 2391 155
75 87 106 128 160 189 22
1600 707
1300 030 1424 040 1657 062 1865 086 2053 112 2247 141 2425 171 2596 203 2759 237
97 100 115 133 156 184 21 24 27
1800 7961431 039 1545 051 1759 075 1950 101 2134 129 2300 157 2472 189 2636 223 2790 258
114 113 125 144 160 181 21 24 26
2000 8841565 051 1669 063 1868 090 2050 118 2217 148 2381 178 2531 210 2683 244 2836 282
127 127 137 157 170 186 21 23 26
2200 9731700 064 1797 078 1979 107 2152 138 2312 169 2464 202 2612 236 2750 270 2883 306
142 145 156 169 183 198 21 23 26
2400 10611836 081 1928 096 2097 127 2260 160 2413 194 2556 228 2695 264 2831 301 2959 338
164 169 174 182 197 21 23 24 26
2600 11501975 100 2060 116 2219 150 2371 185 2517 221 2656 257 2785 295 2914 334
190 192 193 196 21 23 24 26
2800 12382115 122 2194 140 2343 175 2484 212 2626 251 2758 290 2885 330
21 21 21 22 23 24 26
3000 13272256 148 2329 166 2470 204 2605 243 2737 284 2864 325
24 24 24 24 25 26
3200 14152397 177 2464 196 2600 236 2728 278 2849 320
26 26 26 27 27
3400 15042539 210 2601 230 2731 272 2852 316 2969 361
29 29 30 30 30
3600 15922681 247 2739 267 2863 312
33 33 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
20
TCB-1-16 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2000
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 4384
Maximum bhp at a given rpm mdash (rpm1378)3
Max Motor Frame Size - 182T
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1000 308507 005 612 009 802 017
37 43 59
1250 385584 008 671 012 833 021 985 032
45 49 62 81
1500 462668 011 743 016 884 026 1016 038 1145 052
54 58 69 84 103
1750 540755 016 821 021 944 032 1065 045 1176 059 1289 075 1392 091
64 68 79 93 105 120 136
2000 617
844 022 904 028 1014 040 1119 054 1225 069 1322 085 1422 102 1517 120 1605 139
76 81 92 104 113 124 140 157 175
2250 694934 030 989 036 1090 049 1185 064 1278 080 1373 097 1460 115 1547 134 1635 154
89 94 107 114 123 133 146 161 179
2500 7711026 039 1077 047 1169 061 1257 076 1342 092 1425 110 1511 130 1591 149 1666 170
104 110 119 126 134 144 156 169 184
2750 8481118 051 1166 059 1252 074 1334 091 1411 107 1489 126 1564 146 1643 167 1717 188
121 124 131 138 147 157 168 181 194
3000 9251210 064 1256 073 1337 090 1412 107 1486 125 1556 144 1627 165 1695 186 1769 209
134 138 145 152 161 171 183 194 21
3250 10031303 080 1347 090 1423 108 1494 127 1563 146 1630 166 1695 186 1760 209 1823 232
149 153 161 169 177 187 199 21 22
3500 10801397 098 1438 109 1511 128 1578 148 1642 169 1706 190 1768 211 1828 233 1889 258
166 170 179 187 195 21 22 23 24
3750 11571491 119 1530 130 1599 152 1663 173 1725 194 1784 216 1844 239 1900 262 1956 286
185 189 197 21 22 23 24 25 27
4000 12341585 143 1622 155 1689 178 1750 200 1809 223 1865 246 1921 270 1976 295
20 21 22 23 24 25 26 28
4250 13111680 170 1714 183 1779 207 1838 231 1893 255 1948 280 1999 304
23 23 24 25 26 28 29
4500 13881775 200 1807 214 1869 240 1926 265 1979 291
25 26 27 28 30
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
21
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
TCB-2-16 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2431
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 432
Maximum bhp at a given rpm mdash (rpm1406)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1200 370668 011 842 020 1137 041
46 61 104
1500 462749 015 899 025 1166 049 1395 077
55 68 102 138
1800 555843 021 969 033 1208 059 1424 089 1616 121
71 77 104 135 168
2100 648944 030 1053 042 1268 071 1461 103 1647 138 1813 175 1972 215
83 88 111 134 166 196 22
2400 740
1047 040 1144 054 1336 085 1518 120 1684 157 1847 197 1996 238 2140 283 2275 329
99 105 120 140 166 195 22 25 27
2700 8331152 053 1243 068 1412 101 1579 139 1739 179 1885 221 2033 266 2169 312 2297 359
116 122 132 150 171 195 22 25 28
3000 9251260 069 1345 086 1498 121 1651 161 1799 204 1941 248 2070 295 2206 344 2333 394
132 136 144 162 182 20 23 25 28
3300 10181373 089 1448 107 1588 144 1727 186 1866 231 2001 279 2129 328 2247 379 2370 432
147 151 161 177 195 22 24 26 29
3600 11111486 112 1553 131 1686 171 1813 215 1939 262 2065 312 2188 365 2306 418 2416 473
166 171 182 193 21 23 25 28 30
3900 12031600 140 1658 159 1786 202 1900 247 2020 297 2138 349 2252 404 2366 461
189 194 20 21 23 25 27 29
4200 12961715 172 1766 191 1888 238 1996 285 2106 336 2213 390 2324 448 2430 508
21 21 22 23 24 26 29 31
4500 13881831 208 1878 228 1990 277 2095 328 2193 380 2298 437 2398 496
23 23 24 25 27 28 31
4800 14811946 250 1992 271 2094 322 2196 376 2289 430 2385 488
25 26 27 28 29 31
5100 15742062 296 2105 319 2199 371 2297 429 2388 486
28 28 29 30 32
5400 16662179 349 2219 373 2305 426 2399 487
30 31 32 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
22
TCB-1-18 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1645
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 4843
Maximum bhp at a given rpm mdash (rpm1147)3
Max Motor Frame Size - 182T
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg
0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1500 298486 008 568 012 724 023
43 49 62
1800 357552 011 623 016 755 028 883 042
54 57 67 81
2100 417622 016 683 021 799 034 911 048 1022 065 1123 082
67 68 77 85 99 116
2400 477693 021 749 028 852 041 950 056 1048 073 1147 092 1238 112 1322 133
80 81 90 95 103 120 135 148
2700 536
765 029 817 036 911 050 1001 066 1088 084 1174 103 1262 124 1346 146 1424 169
91 94 103 105 113 125 138 150 164
3000 596838 037 887 045 972 061 1056 078 1136 097 1214 117 1292 138 1369 161 1448 185
102 106 111 115 122 133 142 153 166
3300 656912 048 957 057 1038 074 1115 092 1187 111 1261 132 1331 154 1403 177 1472 202
112 114 120 126 133 141 149 158 168
3600 715987 061 1029 070 1105 089 1176 108 1246 128 1312 149 1379 172 1443 196 1510 222
121 125 131 138 145 152 160 168 178
3900 7751063 075 1102 085 1174 106 1239 126 1305 147 1368 170 1430 193 1491 218 1549 244
133 137 143 149 157 165 173 181 189
4200 8341139 092 1175 103 1244 125 1307 147 1366 169 1428 193 1485 217 1542 243 1599 269
146 149 155 163 171 179 187 195 20
4500 8941215 112 1249 124 1315 147 1375 170 1430 193 1488 218 1544 244 1597 270
160 162 169 176 185 194 20 21
4800 9541292 134 1323 147 1386 172 1444 197 1498 221 1549 246 1604 273
171 174 181 190 199 21 22
5100 10131369 159 1399 172 1458 199 1513 226 1565 252 1615 278
184 187 195 20 21 23
5400 10731446 188 1474 201 1530 229 1584 258 1634 285
197 20 21 22 23
5700 11331523 219 1550 233 1603 263
21 22 22
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 632
6 A
B
C
D
E
21 2
CBRU fans do
ot incorporate
rovisions for
nternal wiring
xternal wiring from
he roof to unit must
e provided by
thers
0 4 8 12 16 20 24
CFM x 1000
18
16
14
12
10
08
06
04
02
00
P r e s s u r e
L o s s ( i n
c h e s )
1 6
1 8
2 2
2 4
3 0 3 6
0 1 2 3 4
CFM x 1000
08
07
06
05
04
03
02
01
00
(
)
0 9
1 0
1 2
1 3
System Effect Curves
Sizes 9-13 Sizes 16-36
Dimensional Data
The TCBRU is ideal for roof upblast exhaust systems
with moderate system static pressures and for
applications where quiet operation is essential
Standard features include a necked-down windband
section which creates the high outlet velocities
necessary to carry contaminated exhausts away from
the roof deck All TCBRU fans include motor coversfor weather protection of the motor and drives gravity
operated dampers to prevent backflow into the
building and a welded curb cap for ease in mounting
to a roof curb TCBRU fans are available in either
painted steel or aluminum construction
Typical applications include
bull Low cfmhigh velocity exhaust
bull General exhaust
bull Fume hood exhaust
bull Industrial process exhaust
When selecting TCBRU fans use the TCB inline performance data
(pgs 12 to 31) along with the following system effect curves The
pressure loss determined below must be added to the extended
system static pressure to assure accurate selections Greenheckrsquos
Computer Aided Product Selection (CAPS) software will add these
system effects automatically
Size A B C D E Minimum CFMRequired to Open Dampers
09 22 211 frasl 2 23 45 20 425
10 22 211 frasl 2 23 45 20 425
12 22 211 frasl 2 23 45 20 1250
13 4 231 frasl 2 241 frasl 2 50 1 frasl 2 24 1800
16 28 25 1 frasl 2 28 1 frasl 2 53 28 2030
18 34 28 1 frasl 2 31 571 frasl 2 30 2570
22 40 34 35 1 frasl 2 64 34 2740
24 46 36 1 frasl 2 42 74 1 frasl 2 40 4760
30 52 42 1 frasl 4 481 frasl 2 84 46 6600
36 58 451 frasl 2 54 94 1 frasl 2 52 8700
All dimensions shown in inches
TCBRU Roof Upblast Fan
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 732
7
A B
C
D
W
21 2 in
L
Hood End View Hood Side View
TCBRS fans donot incorporateprovisions for internal wiring
External wiring fromthe roof to unit mustbe provided byothers
0 4 8 12 16 20 24
CFM x 1000
0 9
1 0
1 2
1 3
1 6
1 8
2 2 2
4
3 0
3 6
018
016
014
012
010
008
006
004
002
000
P r e s s u r e
L o s s ( i n c h e s )
System Effect Curves
Dimensional Data
The TCBRS roof mounted supply fan is designed
for intake air systems with pressures up to 4 inches
of wg and where low sound is required The TCBRS
hood intake is located at a sufficient height above
the roof to limit entry of roof debris and snow In
addition the hood has sufficient intake area to keep
velocities low Filters are available to collect dustand moisture before entering the building Motor
and drive protection is provided with a weatherproof
motor cover For ease of installation TCBRS fans are
shipped assembled and have curb caps for attaching
to roof curbs TCBRS fans are available in either
painted steel or aluminum construction
Typical applications include
bull Ducted supply systems
bull Industrial space supply
bull Filtered supply
TCBRS fan selections can be made using the TCB inline
performance data (pgs 12 to 31) along with the following
system effect curves The pressure loss determined to the
left must be added to the external system static pressure
to assure accurate selections Greenheckrsquos Computer
Aided Product Selection (CAPS) software will add thesesystem effects automatically
Size A B C D L W
09 22 211 frasl 2 251 frasl 2 391 frasl 2 39 46
10 22 211 frasl 2 251 frasl 2 391 frasl 2 39 46
12 22 211 frasl 2 251 frasl 2 391 frasl 2 39 4613 24 231 frasl 2 27 431 frasl 2 39 54
16 28 25 1 frasl 2 31 471 frasl 2 51 55
18 34 28 1 frasl 2 331 frasl 2 50 63 64
22 40 34 38 1 frasl 2 59 75 73
24 46 36 1 frasl 2 45 67 1 frasl 2 87 82
30 52 42 1 frasl 4 52 1 frasl 2 76 99 88
36 58 45 1 frasl 2 58 851 frasl 2 111 88
All dimensions shown in inches
TCBRS Roof Supply Fan
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 832
8
Optional Construction Features
Aluminum Construction
Aluminum construction is available on the TCB TCBRU and TCBRS Aluminum fans are an excellent choice for
applications involving moisture or coastal installations
Easy Access Construction
The Easy Access option is highly recommended to allow forinspection cleaning and service of internal fan components
By removing one access panel service to the wheel shaft
and bearing assembly is possible without removing duct
connections In addition all internal fan components can be
removed from the fan through the easy access panel
Easy Access construction is available on all levels and sizes
of TCB TCBRU and TCBRS Easy Access is also available
with aluminum fan construction
The Easy Access panel is located 180deg from the motor
position
Standard Construction Features
Inlet amp Outlet Flanges
Flanged inlets and outlets with mounting holes are
provided for duct connections (TCB only)
Housing
Housings are continuously welded steel and coated
with Permatector trade
Protective Coating
All steel constructed units are coated with
Permatectortrade a thermosetting polyester urethane
Aluminum units are uncoated
Type B Spark Resistance
All fans have aluminum wheels and a nonferrous
(aluminum) rub ring which surrounds the fanshaft where it passes through the drive cover
This construction meets Type B spark resistant
requirements
Bearings
Standard bearings are grease lubricated self-aligning
ball type in pillow block mounts Bearings are selected
for a minimum L10 life in excess of 80000 hours (L50 average life of 400000 hours) at maximum cataloged
operating speeds
Belt amp Bearing Tube
Belts bearings and drives are protected from the
airstream by heavy gauge belt tubes and bolted
bearing covers with shaft seals
Extended
Lube Lines
Lubrication lines with grease
fittings allow bearing lubricationwithout disassembling the fan
TCB - 1 - 24 - 30Tubular CentrifugalBelt Drive
TCB - Inline FanTCBRU - Roof Upblast FanTCBRS - Roof Supply Fan
Level of Construction1 or 2
Motor Horsepower
4 = 1 4 30=3 3 = 1 3 50=5
5 = 1 2 75=7 1 2
7 = 3 4 100=10
10=1 150=15
15=11 2 200=20 20=2
Fan Size09-36
Model Number CodeThe model number system is designed to completely identify
the fan A detailed explanation of the model number code for
TCB fans is shown below
Construction Features
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 932
9
Inline grease exhaust fans are excellent alternative for kitchen applications when roof or wall mounted ventilators
are not practical The TCB with UL 762 grease option is designed to withstand the demands of high temperature
kitchen grease exhaust and high-pressure duct washes
Continuously welded housing and integral duct flanges
provide air and water tight design
Bearing cover gasketed and includes a labyrinth shaft seal
to prevent moisture leakage during normal operation and
while cleaning with high pressure solvents
Continuously welded belt tube keeps the belts and
bearings clean
Two threaded drain connections are located 90deg from the
motor location to allow for removal of grease and moisture
UL 762 is concerned with fans
designed for removal of smoke and
grease laden vapors with airstream
temperatures up to 300degF
bull Meets all UL 705 Requirements
bull Bolted Access Door
bull Drain Connectionbull Meets requirements of NFPA 96
Ventilation Control and Fire
Protection of Commercial
Cooking Operations
Listed Power
Ventilation for
Restaurant
Exhaust Appliances
13G3
Maximum
Operating
Temperature
300degF
The TCB inline grease fan is tough to beat when
packaged with our full line of kitchen hoods and grease
extraction options Take advantage of Greenheckrsquos
expertise in providing a total solution in kitchen
ventilation equipment
A Tough Package to Beat
Leak Resistant Construction Features
bull Inline grease exhaust fans should be installed near the end of the duct run to reduce sound at the hood
bull Inline fan must be securely bolted to the exhaust duct per NFPA-96 guidelines Greenheckrsquos companion flange
are recommended for ease of installation
bull Grease exhaust fans and ductwork must maintain 18 inches (46 cm) minimum clearance to combustible
material If the ductwork and fan are insulated the inspection door must be accessible for maintenancebull A minimum of 10 ft (30 m) of clearance must be kept from the fan outlet to adjacent buildings property lines
or the closest point of any air intake or operable window at or below the plane of the exhaust termination
bull Greenheck recommends that all inline grease applications be reviewed by your local code official to ensure
compliance with NFPA IMC and other local codes
System Design Guidelines
1
2
3
4
5
6
7
Mounting and Serviceability Features
4 6
7
5 14
Optional Construction forUL 762 Restaurant Exhaust
Universal mounting brackets allow for rotation of the motor to
the 3 or 9 orsquoclock position at the jobsiteDuct flanges and access door bolt locations are no more
than 4 inches (100 mm) on center per NFPA 96
ldquoEasy Access Doorrdquo provides access for duct cleaning and allows removal of the wheel
shaft and bearings for maintenance Gasket is rated for 400degF (200degC) and prevents
leakage during operation [Fan is rated for 300degF (149degC) continous operation]
Air1047298ow
Duct to heat source
Ambient temperaturenot to exceed 120ordmF
Wall andor ceiling should enclosefan when used for emergency heatand smoke exhaust Enclosure shallbe per NFPA 96 or local building codes
Roof
Cooling air fordrives andbearings
Minimum ductat discharge
To buildingexterior
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1032
10
Electrical Accessories
Belt Guard (TCB only) Belt guards are totally enclosed to provide protection
from rotating pulleys and belts Belt guards meet
OSHA guidelines
Motor Cover (Weatherhood) Weatherproof motor covers shield the motor and
drive components from dust dirt and moisture when
used in outdoor applications Motor covers also
provide protection from rotating pulleys and belts and
meet OSHA guidelines Motor covers are standard on
TCBRU and TCBRS models
Inlet and Outlet Companion Flanges
(TCB only) Companion inlet flanges and outlet flanges with
prepunched holes are available for all fan sizes in
painted steel construction
Inlet and Outlet Guards (TCB TCBRU)
Removable inlet and outlet guards provide protectionfor personnel and equipment in non-ducted
installations These guards meet OSHA guidelines
TCBRU fans are available with outlet screens to
shield the fan discharge and damper from debris
Inspection Door Bolted or hinged doors provide access for cleaning or
inspection
Inspection Section (TCB only) Inspection sections serve as a length of duct that can
be easily removed to provide for complete access to
the fan for servicing Each section includes a bolted
inspection door
Isolators (TCB only) Both base mount or hanging isolators are available in
either neoprene or spring mounts The isolators are
furnished in sets of four and are sized to match the
weight of each fan
Mounting Rails (TCB only) Mounting rails are required for horizontal mounting
of TCB fans when the motor is to be located in
the 3 or 9 orsquoclock position Mounting rails are also
recommended for all vertically mounted inline fans
See page 5 for additional details
Protective Coatings Greenheck has a wide offering of protective coatings
Consult Greenheckrsquos Product Application Guide
FA110-04R4 Performance Coatings for Ventilation
Products for a complete listing of coatings and a
relative resistance chart
Inlet Vane Dampers (TCB only) Nested inlet vane dampers for controlling air volume
are available on model TCB inline fans with Level 2
steel construction in fan sizes 12 through 36
Birdscreen Insect Screen (TCBRS only)
TCBRS fans are available with either aluminum insectscreen or birdscreen at the hood intake (Birdscreen is
standard)
Roof Curbs (TCBRU TCBRS) Prefabricated roof curbs are available to reduce
installation time and costs by ensuring compatibility
between the fan the curb and the roof opening
All curbs are lined with fiberglass insulation to
prevent condensation and reduce sound levels See
Greenheckrsquos Roof Curb Extensions and Equipment
Supports catalog for complete details
Washable Aluminum Filters (TCBRS only)
Helps trap dust and dirt before it enters the fanFilters can be removed for cleaning
Enclosure Application Toggle Heavy Duty
NEMA-1 Indoor General Purpose Yes Yes
NEMA-12 Indoor DustDrip Tight Yes YesNEMA-3R IndoorOutdoor Rainproof Yes Yes
NEMA-4 IndoorOutdoor Watertight Yes Yes
NEMA-4X IndoorOutdoor Watertight
(Corrosion Resistant) Yes Yes
NEMA-7 amp 9 Indoor Hazardous Locations Yes No
Toggle type and heavy duty disconnect switches are available for positive
electrical shut-off and safety in servicing fans The following switches are
available to meet individual electrical requirements
Accessories
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1132
11
Inspection
Section
Outlet Guard
Belt Guard
Motor Cover
Companion Flange
(Outlet)NeopreneIsolator
Spring Base
Isolator
Inspection
Door
Easy Access
Inlet Guard
CompanionFlange (Inlet)
Mounting Rails
Spring HangingIsolator
Isolator Neoprene Hanging
Accessories (Model TCB shown)
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
12
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
360 195846 002 999 003 1260 006
53 60 75
420 228941 003 1071 004 1314 007 1526 011
57 63 77 92
480 2601040 004 1155 005 1380 009 1576 012 1758 017
63 68 80 93 106
540 2931144 005 1245 006 1449 010 1635 014 1807 019 1968 023 2115 028
71 74 84 95 107 120 133
600 326
1250 006 1341 008 1523 012 1704 016 1865 021 2017 026 2163 031 2298 036
78 81 88 99 110 122 135 147
660 3581357 007 1439 009 1606 014 1774 018 1930 023 2074 029 2212 034 2346 040 2472 046
86 88 93 104 114 126 137 149 162
720 3911465 009 1542 011 1692 016 1845 021 1999 026 2137 032 2270 038 2395 043 2520 050
94 96 100 109 120 131 140 150 163
780 4231576 012 1647 014 1786 018 1928 024 2069 029 2206 035 2331 041 2454 047 2570 054
102 104 108 115 127 136 145 154 165
840 4561688 014 1752 016 1882 021 2012 027 2142 033 2276 039 2400 045 2515 052 2629 059
110 112 117 123 133 142 150 160 170
900 4891801 017 1859 019 1980 025 2100 030 2225 036 2347 043 2469 050 2584 056
120 122 127 133 139 148 157 166
960 5211914 020 1966 023 2081 028 2195 034 2310 040 2424 047 2540 054
130 132 140 142 147 154 164
1020 5542028 024 2075 026 2184 032 2292 038 2395 044 2507 052 2612 059
144 149 150 151 155 163 172
1080 5862141 028 2186 031 2288 037 2389 043 2490 050 2592 057
159 159 160 162 166 172
1140 6192255 033 2298 036 2394 042 2487 049 2585 055
169 169 171 174 178
1200 6522370 038 2410 041 2500 047 2590 054
179 180 183 186
TCB-1-09 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2645
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm3114)3
Max Motor Frame Size - 56
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
13
TCB-2-09 Level 2 Construction
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3330)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg
025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
400 2171198 005 1460 008 1893 018
73 87 119
480 2601332 006 1566 010 1971 020 2309 032
82 96 127 157
560 3041480 009 1686 013 2059 024 2386 036 2671 049
92 106 135 165 191
640 3471635 011 1818 016 2158 027 2469 041 2749 055 3000 070 3228 086
106 117 146 174 20 23 25
720 3911799 015 1958 020 2275 032 2562 045 2830 061 3078 077 3305 094 3514 112
120 130 158 183 21 23 25 28
800 4341966 020 2108 025 2397 037 2666 051 2921 067 3158 085 3383 103 3591 121 3786 141
134 145 169 183 22 24 26 28 31
880 4782135 025 2262 030 2528 043 2784 058 3015 074 3250 093 3464 112 3669 132 3863 152
151 162 182 21 23 25 27 29 32
960 5212308 032 2425 037 2665 050 2905 066 3132 083 3343 101 3555 121 3752 142 3942 164
168 176 196 22 24 26 28 31 33
1040 5652482 039 2590 045 2810 059 3033 075 3251 093 3453 111 3648 131 3844 153 4027 176
184 193 21 23 25 27 29 32 34
1120 6082658 048 2757 054 2960 068 3168 085 3372 103 3571 123 3754 143 3937 165
20 21 23 25 27 29 31 33
1200 6522835 058 2925 065 3113 079 3306 096 3501 115 3691 135 3872 157 4041 179
22 23 24 26 28 30 32 35
1280 6953012 070 3095 076 3271 091 3453 109 3636 128 3813 149 3991 171
24 25 26 28 29 32 34
1360 7393190 083 3269 090 3434 105 3603 123 3773 143 3945 164
26 26 28 29 31 34
1440 7823368 097 3444 105 3599 121 3756 139 3917 159
28 28 30 31 33
1520 8263547 114 3619 121 3765 138 3909 156
30 30 32 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
14
TCB-1-10 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2555
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm2760)3
Max Motor Frame Size - 143T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
480 260858 003 1011 005 1253 009
49 57 73
560 304947 004 1089 006 1321 011 1511 015
55 63 77 93
640 3471042 005 1171 008 1394 013 1578 018 1740 023 1892 029
63 70 82 96 112 133
720 3911141 007 1259 009 1470 015 1649 021 1806 027 1949 033 2079 039
72 76 89 100 115 132 150
800 4341239 009 1349 012 1548 018 1723 024 1876 031 2015 037 2144 044 2263 051
80 84 96 107 119 135 148 161
880 4781340 011 1444 014 1630 021 1798 027 1949 034 2084 042 2211 049 2329 057 2440 064
88 92 102 113 125 137 150 162 176
960 5211441 014 1541 017 1716 024 1876 031 2023 039 2157 047 2280 055 2396 063 2506 071
97 101 109 121 133 141 152 165 179
1040 5651544 017 1640 021 1805 028 1957 035 2099 044 2231 052 2352 060 2465 069
105 109 117 129 139 148 157 169
1120 6081648 021 1739 025 1895 032 2042 040 2178 049 2306 058 2426 067 2538 076
113 117 127 138 146 155 165 177
1200 6521752 025 1839 029 1989 037 2129 046 2259 055 2383 064 2501 073
122 126 137 145 153 163 175
1280 6951858 030 1940 034 2085 043 2218 052 2343 061 2464 071
132 137 145 152 162 173
1360 7391964 035 2041 040 2183 049 2308 058 2430 068 2545 078
145 149 154 162 172 183
1440 7822071 041 2144 046 2282 056 2401 066 2519 076
156 158 164 173 183
1520 8262177 048 2247 053 2380 064 2497 074
164 167 175 184
1600 8692285 056 2351 061 2479 072
173 177 185
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
15
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-10 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3120)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 3261300 007 1504 011 1875 021 2213 032
73 82 105 132
700 3801453 010 1630 014 1966 024 2273 036 2560 049
84 91 110 133 156
800 4341611 013 1768 018 2070 029 2355 042 2619 055 2872 070 3102 086
100 101 118 137 158 182 20
900 4891773 017 1917 023 2188 034 2448 048 2698 062 2932 078 3160 094 3371 111 3568 129
112 113 127 143 162 185 20 22 25
1000 543
1937 023 2071 029 2319 041 2559 055 2790 070 3011 086 3220 103 3430 122 3626 140
124 127 136 152 170 190 21 23 25
1100 5972104 029 2228 035 2457 048 2677 063 2892 079 3103 096 3303 114 3490 132 3685 152
138 143 146 161 179 195 21 23 25
1200 6522276 036 2389 043 2601 057 2807 073 3009 089 3199 107 3394 125 3578 145 3751 165
154 154 159 172 189 20 21 23 25
1300 7062449 045 2552 052 2753 067 2944 083 3128 101 3315 119 3488 138 3670 159 3841 180
164 166 172 183 195 21 22 24 25
1400 7602623 055 2717 062 2907 079 3083 095 3261 114 3433 133 3603 153 3763 173 3933 196
175 177 185 193 20 21 23 24 26
1500 8152797 066 2883 074 3063 092 3231 109 3398 128 3557 148 3721 169 3878 191 4026 212
186 189 197 20 21 22 23 25 26
1600 8692973 079 3052 087 3223 106 3384 125 3537 144 3693 165 3840 186 3995 209
198 20 21 21 22 23 24 25
1700 9233149 094 3224 103 3384 122 3538 142 3683 162 3831 184 3974 206
21 21 22 22 23 23 25
1800 9783325 110 3396 119 3546 140 3693 161 3834 182 3970 204
22 22 23 23 24 24
1900 10323502 129 3570 138 3710 159 3852 182 3988 204
23 24 24 25 25
2000 10863679 149 3744 159 3875 181 4012 204
25 25 25 26
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
16
TCB-1-12 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2490
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 3436
Maximum bhp at a given rpm mdash (rpm2202)3
Max Motor Frame Size - 145T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 0075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
700 380853 006 958 008 1158 014 1345 021 1518 028
62 66 79 94 110
800 434943 008 1042 011 1218 017 1386 024 1551 031 1703 040
66 70 83 96 111 125
900 4891037 010 1128 013 1287 020 1442 027 1587 035 1736 044 1873 053 2000 063
71 76 87 99 112 126 142 155
1000 5431132 013 1216 017 1363 024 1506 031 1643 040 1771 049 1906 059 2033 069 2151 079
78 83 91 103 115 128 143 156 170
1100 597
1229 016 1305 020 1447 028 1574 036 1702 045 1827 055 1943 065 2066 075 2183 086
86 89 96 108 120 133 144 157 171
1200 6521326 020 1398 025 1532 034 1649 042 1769 051 1884 061 1999 071 2105 082 2216 094
92 95 103 113 126 139 149 159 173
1300 7061426 025 1492 030 1619 039 1732 049 1839 058 1950 068 2055 079 2161 090 2260 102
98 102 112 121 134 145 154 164 176
1400 7601526 031 1588 036 1707 046 1817 056 1916 066 2019 076 2120 088 2217 099 2316 111
106 112 122 132 142 151 160 170 181
1500 8151627 037 1684 042 1796 053 1903 064 1999 075 2089 085 2188 097 2281 109 2372 121
119 125 135 144 149 157 167 176 187
1600 8691729 044 1781 050 1886 061 1990 073 2084 085 2170 096 2258 107 2350 120 2436 133
134 139 150 153 157 165 174 183 194
1700 9231830 053 1879 058 1980 070 2077 083 2170 095 2254 107 2334 119 2419 132
151 157 159 162 167 173 181 191
1800 9781932 062 1978 068 2074 080 2166 093 2256 107 2339 120 2417 132
166 166 168 171 176 182 190
1900 10322034 072 2078 078 2169 091 2256 105 2343 119 2425 133
173 173 176 180 185 192
2000 10862137 083 2179 090 2265 103 2348 118 2432 133
180 181 184 189 195
2100 11412240 096 2280 102 2361 117 2442 132
187 188 192 198
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
17
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-12 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 3274
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 321
Maximum bhp at a given rpm mdash (rpm2315)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
750 4071009 008 1226 014 1587 027
55 67 98
900 4891119 011 1315 018 1648 032 1936 049 2182 067
63 76 102 131 159
1050 5701238 015 1419 023 1728 039 1995 056 2240 076 2456 096
75 85 110 136 164 190
1200 6521363 020 1529 029 1813 046 2070 065 2299 085 2514 108 2710 131 2890 155
89 96 120 142 169 195 22 24
1350 733
1495 027 1643 036 1911 055 2151 076 2372 097 2574 120 2768 145 2948 171 3115 197
104 111 132 152 176 20 22 25 28
1500 8151630 034 1764 044 2018 066 2240 088 2452 111 2647 135 2828 160 3007 187 3174 216
120 129 145 166 186 21 23 26 29
1650 8961767 044 1887 054 2127 077 2338 101 2534 126 2727 151 2903 178 3067 205 3233 235
139 144 159 184 199 22 24 27 30
1800 9781908 055 2018 066 2239 090 2445 117 2630 143 2808 170 2983 198 3145 227
159 165 180 199 22 23 25 28
1950 10592053 068 2151 079 2356 105 2554 134 2731 162 2900 190 3064 220 3225 250
182 188 20 22 23 25 27 29
2100 11412198 083 2286 095 2477 122 2664 152 2839 183 2997 213 3154 244
21 22 22 23 25 27 29
2250 12222344 100 2423 113 2599 141 2777 173 2948 205 3104 238 3250 271
24 24 25 26 27 29 32
2400 13042490 119 2560 133 2726 163 2896 196 3058 230 3212 265
26 26 27 28 30 32
2550 13852637 141 2703 156 2858 187 3016 221 3169 257
28 29 29 31 32
2700 14672785 166 2847 181 2991 214 3138 248
31 31 32 34
2850 15482933 193 2992 209 3126 243 3262 279
34 34 35 37
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
18
TCB-1-13 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2355
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 3435
Maximum bhp at a given rpm mdash (rpm2119)3
Max Motor Frame Size - 145T
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 265660 003 792 005 1019 010
41 51 69
750 331760 005 874 007 1073 013 1254 019
48 58 71 84
900 398864 007 967 010 1146 016 1305 023 1459 030
58 64 75 86 102
1050 464973 009 1067 013 1230 020 1378 027 1512 036 1646 044 1770 053
66 70 80 91 103 120 140
1200 530
1085 013 1171 017 1321 024 1457 032 1585 041 1703 051 1820 061 1933 071 2039 081
72 77 86 96 108 120 136 153 172
1350 5971199 017 1277 022 1419 030 1545 039 1662 048 1777 058 1883 069 1984 080 2089 091
81 85 94 103 114 125 136 151 167
1500 6631316 023 1387 027 1520 037 1637 046 1749 059 1853 067 1957 078 2054 090 2146 102
90 94 102 112 122 132 143 155 169
1650 7301434 029 1499 034 1623 044 1736 055 1839 065 1940 077 2034 088 2128 100 2219 113
100 104 113 123 132 143 153 165 178
1800 7961552 037 1613 042 1729 054 1836 065 1935 076 2029 088 2121 100 2207 113 2293 126
112 115 125 134 144 154 165 177 190
1950 8621672 045 1728 052 1836 064 1939 076 2034 088 2123 100 2209 113 2294 127
124 129 138 147 156 167 178 190
2100 9291792 056 1844 062 1947 076 2044 089 2135 102 2221 115 2302 128
138 142 151 161 170 181 192
2250 9951913 067 1962 075 2058 089 2150 103 2238 117 2321 131
152 157 167 177 186 196
2400 10612034 081 2080 088 2171 104 2258 119 2342 133
169 174 184 194 20
2550 11282155 095 2199 104 2285 120
187 192 20
2700 11942277 112 2319 121
21 21
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
19
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
TCB-2-13 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2971
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 353
Maximum bhp at a given rpm mdash (rpm1933)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
800 353828 008 1026 014 1379 030
38 56 104
1000 442934 011 1108 018 1418 035 1692 055
44 60 101 135
1200 5301048 016 1206 024 1479 042 1731 064 1961 087
58 72 101 130 165
1400 6191171 022 1313 031 1562 051 1784 073 2002 099 2201 126 2391 155
75 87 106 128 160 189 22
1600 707
1300 030 1424 040 1657 062 1865 086 2053 112 2247 141 2425 171 2596 203 2759 237
97 100 115 133 156 184 21 24 27
1800 7961431 039 1545 051 1759 075 1950 101 2134 129 2300 157 2472 189 2636 223 2790 258
114 113 125 144 160 181 21 24 26
2000 8841565 051 1669 063 1868 090 2050 118 2217 148 2381 178 2531 210 2683 244 2836 282
127 127 137 157 170 186 21 23 26
2200 9731700 064 1797 078 1979 107 2152 138 2312 169 2464 202 2612 236 2750 270 2883 306
142 145 156 169 183 198 21 23 26
2400 10611836 081 1928 096 2097 127 2260 160 2413 194 2556 228 2695 264 2831 301 2959 338
164 169 174 182 197 21 23 24 26
2600 11501975 100 2060 116 2219 150 2371 185 2517 221 2656 257 2785 295 2914 334
190 192 193 196 21 23 24 26
2800 12382115 122 2194 140 2343 175 2484 212 2626 251 2758 290 2885 330
21 21 21 22 23 24 26
3000 13272256 148 2329 166 2470 204 2605 243 2737 284 2864 325
24 24 24 24 25 26
3200 14152397 177 2464 196 2600 236 2728 278 2849 320
26 26 26 27 27
3400 15042539 210 2601 230 2731 272 2852 316 2969 361
29 29 30 30 30
3600 15922681 247 2739 267 2863 312
33 33 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
20
TCB-1-16 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2000
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 4384
Maximum bhp at a given rpm mdash (rpm1378)3
Max Motor Frame Size - 182T
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1000 308507 005 612 009 802 017
37 43 59
1250 385584 008 671 012 833 021 985 032
45 49 62 81
1500 462668 011 743 016 884 026 1016 038 1145 052
54 58 69 84 103
1750 540755 016 821 021 944 032 1065 045 1176 059 1289 075 1392 091
64 68 79 93 105 120 136
2000 617
844 022 904 028 1014 040 1119 054 1225 069 1322 085 1422 102 1517 120 1605 139
76 81 92 104 113 124 140 157 175
2250 694934 030 989 036 1090 049 1185 064 1278 080 1373 097 1460 115 1547 134 1635 154
89 94 107 114 123 133 146 161 179
2500 7711026 039 1077 047 1169 061 1257 076 1342 092 1425 110 1511 130 1591 149 1666 170
104 110 119 126 134 144 156 169 184
2750 8481118 051 1166 059 1252 074 1334 091 1411 107 1489 126 1564 146 1643 167 1717 188
121 124 131 138 147 157 168 181 194
3000 9251210 064 1256 073 1337 090 1412 107 1486 125 1556 144 1627 165 1695 186 1769 209
134 138 145 152 161 171 183 194 21
3250 10031303 080 1347 090 1423 108 1494 127 1563 146 1630 166 1695 186 1760 209 1823 232
149 153 161 169 177 187 199 21 22
3500 10801397 098 1438 109 1511 128 1578 148 1642 169 1706 190 1768 211 1828 233 1889 258
166 170 179 187 195 21 22 23 24
3750 11571491 119 1530 130 1599 152 1663 173 1725 194 1784 216 1844 239 1900 262 1956 286
185 189 197 21 22 23 24 25 27
4000 12341585 143 1622 155 1689 178 1750 200 1809 223 1865 246 1921 270 1976 295
20 21 22 23 24 25 26 28
4250 13111680 170 1714 183 1779 207 1838 231 1893 255 1948 280 1999 304
23 23 24 25 26 28 29
4500 13881775 200 1807 214 1869 240 1926 265 1979 291
25 26 27 28 30
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
21
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
TCB-2-16 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2431
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 432
Maximum bhp at a given rpm mdash (rpm1406)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1200 370668 011 842 020 1137 041
46 61 104
1500 462749 015 899 025 1166 049 1395 077
55 68 102 138
1800 555843 021 969 033 1208 059 1424 089 1616 121
71 77 104 135 168
2100 648944 030 1053 042 1268 071 1461 103 1647 138 1813 175 1972 215
83 88 111 134 166 196 22
2400 740
1047 040 1144 054 1336 085 1518 120 1684 157 1847 197 1996 238 2140 283 2275 329
99 105 120 140 166 195 22 25 27
2700 8331152 053 1243 068 1412 101 1579 139 1739 179 1885 221 2033 266 2169 312 2297 359
116 122 132 150 171 195 22 25 28
3000 9251260 069 1345 086 1498 121 1651 161 1799 204 1941 248 2070 295 2206 344 2333 394
132 136 144 162 182 20 23 25 28
3300 10181373 089 1448 107 1588 144 1727 186 1866 231 2001 279 2129 328 2247 379 2370 432
147 151 161 177 195 22 24 26 29
3600 11111486 112 1553 131 1686 171 1813 215 1939 262 2065 312 2188 365 2306 418 2416 473
166 171 182 193 21 23 25 28 30
3900 12031600 140 1658 159 1786 202 1900 247 2020 297 2138 349 2252 404 2366 461
189 194 20 21 23 25 27 29
4200 12961715 172 1766 191 1888 238 1996 285 2106 336 2213 390 2324 448 2430 508
21 21 22 23 24 26 29 31
4500 13881831 208 1878 228 1990 277 2095 328 2193 380 2298 437 2398 496
23 23 24 25 27 28 31
4800 14811946 250 1992 271 2094 322 2196 376 2289 430 2385 488
25 26 27 28 29 31
5100 15742062 296 2105 319 2199 371 2297 429 2388 486
28 28 29 30 32
5400 16662179 349 2219 373 2305 426 2399 487
30 31 32 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
22
TCB-1-18 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1645
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 4843
Maximum bhp at a given rpm mdash (rpm1147)3
Max Motor Frame Size - 182T
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg
0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1500 298486 008 568 012 724 023
43 49 62
1800 357552 011 623 016 755 028 883 042
54 57 67 81
2100 417622 016 683 021 799 034 911 048 1022 065 1123 082
67 68 77 85 99 116
2400 477693 021 749 028 852 041 950 056 1048 073 1147 092 1238 112 1322 133
80 81 90 95 103 120 135 148
2700 536
765 029 817 036 911 050 1001 066 1088 084 1174 103 1262 124 1346 146 1424 169
91 94 103 105 113 125 138 150 164
3000 596838 037 887 045 972 061 1056 078 1136 097 1214 117 1292 138 1369 161 1448 185
102 106 111 115 122 133 142 153 166
3300 656912 048 957 057 1038 074 1115 092 1187 111 1261 132 1331 154 1403 177 1472 202
112 114 120 126 133 141 149 158 168
3600 715987 061 1029 070 1105 089 1176 108 1246 128 1312 149 1379 172 1443 196 1510 222
121 125 131 138 145 152 160 168 178
3900 7751063 075 1102 085 1174 106 1239 126 1305 147 1368 170 1430 193 1491 218 1549 244
133 137 143 149 157 165 173 181 189
4200 8341139 092 1175 103 1244 125 1307 147 1366 169 1428 193 1485 217 1542 243 1599 269
146 149 155 163 171 179 187 195 20
4500 8941215 112 1249 124 1315 147 1375 170 1430 193 1488 218 1544 244 1597 270
160 162 169 176 185 194 20 21
4800 9541292 134 1323 147 1386 172 1444 197 1498 221 1549 246 1604 273
171 174 181 190 199 21 22
5100 10131369 159 1399 172 1458 199 1513 226 1565 252 1615 278
184 187 195 20 21 23
5400 10731446 188 1474 201 1530 229 1584 258 1634 285
197 20 21 22 23
5700 11331523 219 1550 233 1603 263
21 22 22
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 732
7
A B
C
D
W
21 2 in
L
Hood End View Hood Side View
TCBRS fans donot incorporateprovisions for internal wiring
External wiring fromthe roof to unit mustbe provided byothers
0 4 8 12 16 20 24
CFM x 1000
0 9
1 0
1 2
1 3
1 6
1 8
2 2 2
4
3 0
3 6
018
016
014
012
010
008
006
004
002
000
P r e s s u r e
L o s s ( i n c h e s )
System Effect Curves
Dimensional Data
The TCBRS roof mounted supply fan is designed
for intake air systems with pressures up to 4 inches
of wg and where low sound is required The TCBRS
hood intake is located at a sufficient height above
the roof to limit entry of roof debris and snow In
addition the hood has sufficient intake area to keep
velocities low Filters are available to collect dustand moisture before entering the building Motor
and drive protection is provided with a weatherproof
motor cover For ease of installation TCBRS fans are
shipped assembled and have curb caps for attaching
to roof curbs TCBRS fans are available in either
painted steel or aluminum construction
Typical applications include
bull Ducted supply systems
bull Industrial space supply
bull Filtered supply
TCBRS fan selections can be made using the TCB inline
performance data (pgs 12 to 31) along with the following
system effect curves The pressure loss determined to the
left must be added to the external system static pressure
to assure accurate selections Greenheckrsquos Computer
Aided Product Selection (CAPS) software will add thesesystem effects automatically
Size A B C D L W
09 22 211 frasl 2 251 frasl 2 391 frasl 2 39 46
10 22 211 frasl 2 251 frasl 2 391 frasl 2 39 46
12 22 211 frasl 2 251 frasl 2 391 frasl 2 39 4613 24 231 frasl 2 27 431 frasl 2 39 54
16 28 25 1 frasl 2 31 471 frasl 2 51 55
18 34 28 1 frasl 2 331 frasl 2 50 63 64
22 40 34 38 1 frasl 2 59 75 73
24 46 36 1 frasl 2 45 67 1 frasl 2 87 82
30 52 42 1 frasl 4 52 1 frasl 2 76 99 88
36 58 45 1 frasl 2 58 851 frasl 2 111 88
All dimensions shown in inches
TCBRS Roof Supply Fan
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 832
8
Optional Construction Features
Aluminum Construction
Aluminum construction is available on the TCB TCBRU and TCBRS Aluminum fans are an excellent choice for
applications involving moisture or coastal installations
Easy Access Construction
The Easy Access option is highly recommended to allow forinspection cleaning and service of internal fan components
By removing one access panel service to the wheel shaft
and bearing assembly is possible without removing duct
connections In addition all internal fan components can be
removed from the fan through the easy access panel
Easy Access construction is available on all levels and sizes
of TCB TCBRU and TCBRS Easy Access is also available
with aluminum fan construction
The Easy Access panel is located 180deg from the motor
position
Standard Construction Features
Inlet amp Outlet Flanges
Flanged inlets and outlets with mounting holes are
provided for duct connections (TCB only)
Housing
Housings are continuously welded steel and coated
with Permatector trade
Protective Coating
All steel constructed units are coated with
Permatectortrade a thermosetting polyester urethane
Aluminum units are uncoated
Type B Spark Resistance
All fans have aluminum wheels and a nonferrous
(aluminum) rub ring which surrounds the fanshaft where it passes through the drive cover
This construction meets Type B spark resistant
requirements
Bearings
Standard bearings are grease lubricated self-aligning
ball type in pillow block mounts Bearings are selected
for a minimum L10 life in excess of 80000 hours (L50 average life of 400000 hours) at maximum cataloged
operating speeds
Belt amp Bearing Tube
Belts bearings and drives are protected from the
airstream by heavy gauge belt tubes and bolted
bearing covers with shaft seals
Extended
Lube Lines
Lubrication lines with grease
fittings allow bearing lubricationwithout disassembling the fan
TCB - 1 - 24 - 30Tubular CentrifugalBelt Drive
TCB - Inline FanTCBRU - Roof Upblast FanTCBRS - Roof Supply Fan
Level of Construction1 or 2
Motor Horsepower
4 = 1 4 30=3 3 = 1 3 50=5
5 = 1 2 75=7 1 2
7 = 3 4 100=10
10=1 150=15
15=11 2 200=20 20=2
Fan Size09-36
Model Number CodeThe model number system is designed to completely identify
the fan A detailed explanation of the model number code for
TCB fans is shown below
Construction Features
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 932
9
Inline grease exhaust fans are excellent alternative for kitchen applications when roof or wall mounted ventilators
are not practical The TCB with UL 762 grease option is designed to withstand the demands of high temperature
kitchen grease exhaust and high-pressure duct washes
Continuously welded housing and integral duct flanges
provide air and water tight design
Bearing cover gasketed and includes a labyrinth shaft seal
to prevent moisture leakage during normal operation and
while cleaning with high pressure solvents
Continuously welded belt tube keeps the belts and
bearings clean
Two threaded drain connections are located 90deg from the
motor location to allow for removal of grease and moisture
UL 762 is concerned with fans
designed for removal of smoke and
grease laden vapors with airstream
temperatures up to 300degF
bull Meets all UL 705 Requirements
bull Bolted Access Door
bull Drain Connectionbull Meets requirements of NFPA 96
Ventilation Control and Fire
Protection of Commercial
Cooking Operations
Listed Power
Ventilation for
Restaurant
Exhaust Appliances
13G3
Maximum
Operating
Temperature
300degF
The TCB inline grease fan is tough to beat when
packaged with our full line of kitchen hoods and grease
extraction options Take advantage of Greenheckrsquos
expertise in providing a total solution in kitchen
ventilation equipment
A Tough Package to Beat
Leak Resistant Construction Features
bull Inline grease exhaust fans should be installed near the end of the duct run to reduce sound at the hood
bull Inline fan must be securely bolted to the exhaust duct per NFPA-96 guidelines Greenheckrsquos companion flange
are recommended for ease of installation
bull Grease exhaust fans and ductwork must maintain 18 inches (46 cm) minimum clearance to combustible
material If the ductwork and fan are insulated the inspection door must be accessible for maintenancebull A minimum of 10 ft (30 m) of clearance must be kept from the fan outlet to adjacent buildings property lines
or the closest point of any air intake or operable window at or below the plane of the exhaust termination
bull Greenheck recommends that all inline grease applications be reviewed by your local code official to ensure
compliance with NFPA IMC and other local codes
System Design Guidelines
1
2
3
4
5
6
7
Mounting and Serviceability Features
4 6
7
5 14
Optional Construction forUL 762 Restaurant Exhaust
Universal mounting brackets allow for rotation of the motor to
the 3 or 9 orsquoclock position at the jobsiteDuct flanges and access door bolt locations are no more
than 4 inches (100 mm) on center per NFPA 96
ldquoEasy Access Doorrdquo provides access for duct cleaning and allows removal of the wheel
shaft and bearings for maintenance Gasket is rated for 400degF (200degC) and prevents
leakage during operation [Fan is rated for 300degF (149degC) continous operation]
Air1047298ow
Duct to heat source
Ambient temperaturenot to exceed 120ordmF
Wall andor ceiling should enclosefan when used for emergency heatand smoke exhaust Enclosure shallbe per NFPA 96 or local building codes
Roof
Cooling air fordrives andbearings
Minimum ductat discharge
To buildingexterior
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1032
10
Electrical Accessories
Belt Guard (TCB only) Belt guards are totally enclosed to provide protection
from rotating pulleys and belts Belt guards meet
OSHA guidelines
Motor Cover (Weatherhood) Weatherproof motor covers shield the motor and
drive components from dust dirt and moisture when
used in outdoor applications Motor covers also
provide protection from rotating pulleys and belts and
meet OSHA guidelines Motor covers are standard on
TCBRU and TCBRS models
Inlet and Outlet Companion Flanges
(TCB only) Companion inlet flanges and outlet flanges with
prepunched holes are available for all fan sizes in
painted steel construction
Inlet and Outlet Guards (TCB TCBRU)
Removable inlet and outlet guards provide protectionfor personnel and equipment in non-ducted
installations These guards meet OSHA guidelines
TCBRU fans are available with outlet screens to
shield the fan discharge and damper from debris
Inspection Door Bolted or hinged doors provide access for cleaning or
inspection
Inspection Section (TCB only) Inspection sections serve as a length of duct that can
be easily removed to provide for complete access to
the fan for servicing Each section includes a bolted
inspection door
Isolators (TCB only) Both base mount or hanging isolators are available in
either neoprene or spring mounts The isolators are
furnished in sets of four and are sized to match the
weight of each fan
Mounting Rails (TCB only) Mounting rails are required for horizontal mounting
of TCB fans when the motor is to be located in
the 3 or 9 orsquoclock position Mounting rails are also
recommended for all vertically mounted inline fans
See page 5 for additional details
Protective Coatings Greenheck has a wide offering of protective coatings
Consult Greenheckrsquos Product Application Guide
FA110-04R4 Performance Coatings for Ventilation
Products for a complete listing of coatings and a
relative resistance chart
Inlet Vane Dampers (TCB only) Nested inlet vane dampers for controlling air volume
are available on model TCB inline fans with Level 2
steel construction in fan sizes 12 through 36
Birdscreen Insect Screen (TCBRS only)
TCBRS fans are available with either aluminum insectscreen or birdscreen at the hood intake (Birdscreen is
standard)
Roof Curbs (TCBRU TCBRS) Prefabricated roof curbs are available to reduce
installation time and costs by ensuring compatibility
between the fan the curb and the roof opening
All curbs are lined with fiberglass insulation to
prevent condensation and reduce sound levels See
Greenheckrsquos Roof Curb Extensions and Equipment
Supports catalog for complete details
Washable Aluminum Filters (TCBRS only)
Helps trap dust and dirt before it enters the fanFilters can be removed for cleaning
Enclosure Application Toggle Heavy Duty
NEMA-1 Indoor General Purpose Yes Yes
NEMA-12 Indoor DustDrip Tight Yes YesNEMA-3R IndoorOutdoor Rainproof Yes Yes
NEMA-4 IndoorOutdoor Watertight Yes Yes
NEMA-4X IndoorOutdoor Watertight
(Corrosion Resistant) Yes Yes
NEMA-7 amp 9 Indoor Hazardous Locations Yes No
Toggle type and heavy duty disconnect switches are available for positive
electrical shut-off and safety in servicing fans The following switches are
available to meet individual electrical requirements
Accessories
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1132
11
Inspection
Section
Outlet Guard
Belt Guard
Motor Cover
Companion Flange
(Outlet)NeopreneIsolator
Spring Base
Isolator
Inspection
Door
Easy Access
Inlet Guard
CompanionFlange (Inlet)
Mounting Rails
Spring HangingIsolator
Isolator Neoprene Hanging
Accessories (Model TCB shown)
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
12
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
360 195846 002 999 003 1260 006
53 60 75
420 228941 003 1071 004 1314 007 1526 011
57 63 77 92
480 2601040 004 1155 005 1380 009 1576 012 1758 017
63 68 80 93 106
540 2931144 005 1245 006 1449 010 1635 014 1807 019 1968 023 2115 028
71 74 84 95 107 120 133
600 326
1250 006 1341 008 1523 012 1704 016 1865 021 2017 026 2163 031 2298 036
78 81 88 99 110 122 135 147
660 3581357 007 1439 009 1606 014 1774 018 1930 023 2074 029 2212 034 2346 040 2472 046
86 88 93 104 114 126 137 149 162
720 3911465 009 1542 011 1692 016 1845 021 1999 026 2137 032 2270 038 2395 043 2520 050
94 96 100 109 120 131 140 150 163
780 4231576 012 1647 014 1786 018 1928 024 2069 029 2206 035 2331 041 2454 047 2570 054
102 104 108 115 127 136 145 154 165
840 4561688 014 1752 016 1882 021 2012 027 2142 033 2276 039 2400 045 2515 052 2629 059
110 112 117 123 133 142 150 160 170
900 4891801 017 1859 019 1980 025 2100 030 2225 036 2347 043 2469 050 2584 056
120 122 127 133 139 148 157 166
960 5211914 020 1966 023 2081 028 2195 034 2310 040 2424 047 2540 054
130 132 140 142 147 154 164
1020 5542028 024 2075 026 2184 032 2292 038 2395 044 2507 052 2612 059
144 149 150 151 155 163 172
1080 5862141 028 2186 031 2288 037 2389 043 2490 050 2592 057
159 159 160 162 166 172
1140 6192255 033 2298 036 2394 042 2487 049 2585 055
169 169 171 174 178
1200 6522370 038 2410 041 2500 047 2590 054
179 180 183 186
TCB-1-09 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2645
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm3114)3
Max Motor Frame Size - 56
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
13
TCB-2-09 Level 2 Construction
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3330)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg
025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
400 2171198 005 1460 008 1893 018
73 87 119
480 2601332 006 1566 010 1971 020 2309 032
82 96 127 157
560 3041480 009 1686 013 2059 024 2386 036 2671 049
92 106 135 165 191
640 3471635 011 1818 016 2158 027 2469 041 2749 055 3000 070 3228 086
106 117 146 174 20 23 25
720 3911799 015 1958 020 2275 032 2562 045 2830 061 3078 077 3305 094 3514 112
120 130 158 183 21 23 25 28
800 4341966 020 2108 025 2397 037 2666 051 2921 067 3158 085 3383 103 3591 121 3786 141
134 145 169 183 22 24 26 28 31
880 4782135 025 2262 030 2528 043 2784 058 3015 074 3250 093 3464 112 3669 132 3863 152
151 162 182 21 23 25 27 29 32
960 5212308 032 2425 037 2665 050 2905 066 3132 083 3343 101 3555 121 3752 142 3942 164
168 176 196 22 24 26 28 31 33
1040 5652482 039 2590 045 2810 059 3033 075 3251 093 3453 111 3648 131 3844 153 4027 176
184 193 21 23 25 27 29 32 34
1120 6082658 048 2757 054 2960 068 3168 085 3372 103 3571 123 3754 143 3937 165
20 21 23 25 27 29 31 33
1200 6522835 058 2925 065 3113 079 3306 096 3501 115 3691 135 3872 157 4041 179
22 23 24 26 28 30 32 35
1280 6953012 070 3095 076 3271 091 3453 109 3636 128 3813 149 3991 171
24 25 26 28 29 32 34
1360 7393190 083 3269 090 3434 105 3603 123 3773 143 3945 164
26 26 28 29 31 34
1440 7823368 097 3444 105 3599 121 3756 139 3917 159
28 28 30 31 33
1520 8263547 114 3619 121 3765 138 3909 156
30 30 32 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
14
TCB-1-10 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2555
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm2760)3
Max Motor Frame Size - 143T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
480 260858 003 1011 005 1253 009
49 57 73
560 304947 004 1089 006 1321 011 1511 015
55 63 77 93
640 3471042 005 1171 008 1394 013 1578 018 1740 023 1892 029
63 70 82 96 112 133
720 3911141 007 1259 009 1470 015 1649 021 1806 027 1949 033 2079 039
72 76 89 100 115 132 150
800 4341239 009 1349 012 1548 018 1723 024 1876 031 2015 037 2144 044 2263 051
80 84 96 107 119 135 148 161
880 4781340 011 1444 014 1630 021 1798 027 1949 034 2084 042 2211 049 2329 057 2440 064
88 92 102 113 125 137 150 162 176
960 5211441 014 1541 017 1716 024 1876 031 2023 039 2157 047 2280 055 2396 063 2506 071
97 101 109 121 133 141 152 165 179
1040 5651544 017 1640 021 1805 028 1957 035 2099 044 2231 052 2352 060 2465 069
105 109 117 129 139 148 157 169
1120 6081648 021 1739 025 1895 032 2042 040 2178 049 2306 058 2426 067 2538 076
113 117 127 138 146 155 165 177
1200 6521752 025 1839 029 1989 037 2129 046 2259 055 2383 064 2501 073
122 126 137 145 153 163 175
1280 6951858 030 1940 034 2085 043 2218 052 2343 061 2464 071
132 137 145 152 162 173
1360 7391964 035 2041 040 2183 049 2308 058 2430 068 2545 078
145 149 154 162 172 183
1440 7822071 041 2144 046 2282 056 2401 066 2519 076
156 158 164 173 183
1520 8262177 048 2247 053 2380 064 2497 074
164 167 175 184
1600 8692285 056 2351 061 2479 072
173 177 185
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
15
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-10 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3120)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 3261300 007 1504 011 1875 021 2213 032
73 82 105 132
700 3801453 010 1630 014 1966 024 2273 036 2560 049
84 91 110 133 156
800 4341611 013 1768 018 2070 029 2355 042 2619 055 2872 070 3102 086
100 101 118 137 158 182 20
900 4891773 017 1917 023 2188 034 2448 048 2698 062 2932 078 3160 094 3371 111 3568 129
112 113 127 143 162 185 20 22 25
1000 543
1937 023 2071 029 2319 041 2559 055 2790 070 3011 086 3220 103 3430 122 3626 140
124 127 136 152 170 190 21 23 25
1100 5972104 029 2228 035 2457 048 2677 063 2892 079 3103 096 3303 114 3490 132 3685 152
138 143 146 161 179 195 21 23 25
1200 6522276 036 2389 043 2601 057 2807 073 3009 089 3199 107 3394 125 3578 145 3751 165
154 154 159 172 189 20 21 23 25
1300 7062449 045 2552 052 2753 067 2944 083 3128 101 3315 119 3488 138 3670 159 3841 180
164 166 172 183 195 21 22 24 25
1400 7602623 055 2717 062 2907 079 3083 095 3261 114 3433 133 3603 153 3763 173 3933 196
175 177 185 193 20 21 23 24 26
1500 8152797 066 2883 074 3063 092 3231 109 3398 128 3557 148 3721 169 3878 191 4026 212
186 189 197 20 21 22 23 25 26
1600 8692973 079 3052 087 3223 106 3384 125 3537 144 3693 165 3840 186 3995 209
198 20 21 21 22 23 24 25
1700 9233149 094 3224 103 3384 122 3538 142 3683 162 3831 184 3974 206
21 21 22 22 23 23 25
1800 9783325 110 3396 119 3546 140 3693 161 3834 182 3970 204
22 22 23 23 24 24
1900 10323502 129 3570 138 3710 159 3852 182 3988 204
23 24 24 25 25
2000 10863679 149 3744 159 3875 181 4012 204
25 25 25 26
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
16
TCB-1-12 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2490
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 3436
Maximum bhp at a given rpm mdash (rpm2202)3
Max Motor Frame Size - 145T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 0075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
700 380853 006 958 008 1158 014 1345 021 1518 028
62 66 79 94 110
800 434943 008 1042 011 1218 017 1386 024 1551 031 1703 040
66 70 83 96 111 125
900 4891037 010 1128 013 1287 020 1442 027 1587 035 1736 044 1873 053 2000 063
71 76 87 99 112 126 142 155
1000 5431132 013 1216 017 1363 024 1506 031 1643 040 1771 049 1906 059 2033 069 2151 079
78 83 91 103 115 128 143 156 170
1100 597
1229 016 1305 020 1447 028 1574 036 1702 045 1827 055 1943 065 2066 075 2183 086
86 89 96 108 120 133 144 157 171
1200 6521326 020 1398 025 1532 034 1649 042 1769 051 1884 061 1999 071 2105 082 2216 094
92 95 103 113 126 139 149 159 173
1300 7061426 025 1492 030 1619 039 1732 049 1839 058 1950 068 2055 079 2161 090 2260 102
98 102 112 121 134 145 154 164 176
1400 7601526 031 1588 036 1707 046 1817 056 1916 066 2019 076 2120 088 2217 099 2316 111
106 112 122 132 142 151 160 170 181
1500 8151627 037 1684 042 1796 053 1903 064 1999 075 2089 085 2188 097 2281 109 2372 121
119 125 135 144 149 157 167 176 187
1600 8691729 044 1781 050 1886 061 1990 073 2084 085 2170 096 2258 107 2350 120 2436 133
134 139 150 153 157 165 174 183 194
1700 9231830 053 1879 058 1980 070 2077 083 2170 095 2254 107 2334 119 2419 132
151 157 159 162 167 173 181 191
1800 9781932 062 1978 068 2074 080 2166 093 2256 107 2339 120 2417 132
166 166 168 171 176 182 190
1900 10322034 072 2078 078 2169 091 2256 105 2343 119 2425 133
173 173 176 180 185 192
2000 10862137 083 2179 090 2265 103 2348 118 2432 133
180 181 184 189 195
2100 11412240 096 2280 102 2361 117 2442 132
187 188 192 198
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
17
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-12 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 3274
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 321
Maximum bhp at a given rpm mdash (rpm2315)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
750 4071009 008 1226 014 1587 027
55 67 98
900 4891119 011 1315 018 1648 032 1936 049 2182 067
63 76 102 131 159
1050 5701238 015 1419 023 1728 039 1995 056 2240 076 2456 096
75 85 110 136 164 190
1200 6521363 020 1529 029 1813 046 2070 065 2299 085 2514 108 2710 131 2890 155
89 96 120 142 169 195 22 24
1350 733
1495 027 1643 036 1911 055 2151 076 2372 097 2574 120 2768 145 2948 171 3115 197
104 111 132 152 176 20 22 25 28
1500 8151630 034 1764 044 2018 066 2240 088 2452 111 2647 135 2828 160 3007 187 3174 216
120 129 145 166 186 21 23 26 29
1650 8961767 044 1887 054 2127 077 2338 101 2534 126 2727 151 2903 178 3067 205 3233 235
139 144 159 184 199 22 24 27 30
1800 9781908 055 2018 066 2239 090 2445 117 2630 143 2808 170 2983 198 3145 227
159 165 180 199 22 23 25 28
1950 10592053 068 2151 079 2356 105 2554 134 2731 162 2900 190 3064 220 3225 250
182 188 20 22 23 25 27 29
2100 11412198 083 2286 095 2477 122 2664 152 2839 183 2997 213 3154 244
21 22 22 23 25 27 29
2250 12222344 100 2423 113 2599 141 2777 173 2948 205 3104 238 3250 271
24 24 25 26 27 29 32
2400 13042490 119 2560 133 2726 163 2896 196 3058 230 3212 265
26 26 27 28 30 32
2550 13852637 141 2703 156 2858 187 3016 221 3169 257
28 29 29 31 32
2700 14672785 166 2847 181 2991 214 3138 248
31 31 32 34
2850 15482933 193 2992 209 3126 243 3262 279
34 34 35 37
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
18
TCB-1-13 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2355
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 3435
Maximum bhp at a given rpm mdash (rpm2119)3
Max Motor Frame Size - 145T
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 265660 003 792 005 1019 010
41 51 69
750 331760 005 874 007 1073 013 1254 019
48 58 71 84
900 398864 007 967 010 1146 016 1305 023 1459 030
58 64 75 86 102
1050 464973 009 1067 013 1230 020 1378 027 1512 036 1646 044 1770 053
66 70 80 91 103 120 140
1200 530
1085 013 1171 017 1321 024 1457 032 1585 041 1703 051 1820 061 1933 071 2039 081
72 77 86 96 108 120 136 153 172
1350 5971199 017 1277 022 1419 030 1545 039 1662 048 1777 058 1883 069 1984 080 2089 091
81 85 94 103 114 125 136 151 167
1500 6631316 023 1387 027 1520 037 1637 046 1749 059 1853 067 1957 078 2054 090 2146 102
90 94 102 112 122 132 143 155 169
1650 7301434 029 1499 034 1623 044 1736 055 1839 065 1940 077 2034 088 2128 100 2219 113
100 104 113 123 132 143 153 165 178
1800 7961552 037 1613 042 1729 054 1836 065 1935 076 2029 088 2121 100 2207 113 2293 126
112 115 125 134 144 154 165 177 190
1950 8621672 045 1728 052 1836 064 1939 076 2034 088 2123 100 2209 113 2294 127
124 129 138 147 156 167 178 190
2100 9291792 056 1844 062 1947 076 2044 089 2135 102 2221 115 2302 128
138 142 151 161 170 181 192
2250 9951913 067 1962 075 2058 089 2150 103 2238 117 2321 131
152 157 167 177 186 196
2400 10612034 081 2080 088 2171 104 2258 119 2342 133
169 174 184 194 20
2550 11282155 095 2199 104 2285 120
187 192 20
2700 11942277 112 2319 121
21 21
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
19
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
TCB-2-13 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2971
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 353
Maximum bhp at a given rpm mdash (rpm1933)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
800 353828 008 1026 014 1379 030
38 56 104
1000 442934 011 1108 018 1418 035 1692 055
44 60 101 135
1200 5301048 016 1206 024 1479 042 1731 064 1961 087
58 72 101 130 165
1400 6191171 022 1313 031 1562 051 1784 073 2002 099 2201 126 2391 155
75 87 106 128 160 189 22
1600 707
1300 030 1424 040 1657 062 1865 086 2053 112 2247 141 2425 171 2596 203 2759 237
97 100 115 133 156 184 21 24 27
1800 7961431 039 1545 051 1759 075 1950 101 2134 129 2300 157 2472 189 2636 223 2790 258
114 113 125 144 160 181 21 24 26
2000 8841565 051 1669 063 1868 090 2050 118 2217 148 2381 178 2531 210 2683 244 2836 282
127 127 137 157 170 186 21 23 26
2200 9731700 064 1797 078 1979 107 2152 138 2312 169 2464 202 2612 236 2750 270 2883 306
142 145 156 169 183 198 21 23 26
2400 10611836 081 1928 096 2097 127 2260 160 2413 194 2556 228 2695 264 2831 301 2959 338
164 169 174 182 197 21 23 24 26
2600 11501975 100 2060 116 2219 150 2371 185 2517 221 2656 257 2785 295 2914 334
190 192 193 196 21 23 24 26
2800 12382115 122 2194 140 2343 175 2484 212 2626 251 2758 290 2885 330
21 21 21 22 23 24 26
3000 13272256 148 2329 166 2470 204 2605 243 2737 284 2864 325
24 24 24 24 25 26
3200 14152397 177 2464 196 2600 236 2728 278 2849 320
26 26 26 27 27
3400 15042539 210 2601 230 2731 272 2852 316 2969 361
29 29 30 30 30
3600 15922681 247 2739 267 2863 312
33 33 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
20
TCB-1-16 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2000
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 4384
Maximum bhp at a given rpm mdash (rpm1378)3
Max Motor Frame Size - 182T
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1000 308507 005 612 009 802 017
37 43 59
1250 385584 008 671 012 833 021 985 032
45 49 62 81
1500 462668 011 743 016 884 026 1016 038 1145 052
54 58 69 84 103
1750 540755 016 821 021 944 032 1065 045 1176 059 1289 075 1392 091
64 68 79 93 105 120 136
2000 617
844 022 904 028 1014 040 1119 054 1225 069 1322 085 1422 102 1517 120 1605 139
76 81 92 104 113 124 140 157 175
2250 694934 030 989 036 1090 049 1185 064 1278 080 1373 097 1460 115 1547 134 1635 154
89 94 107 114 123 133 146 161 179
2500 7711026 039 1077 047 1169 061 1257 076 1342 092 1425 110 1511 130 1591 149 1666 170
104 110 119 126 134 144 156 169 184
2750 8481118 051 1166 059 1252 074 1334 091 1411 107 1489 126 1564 146 1643 167 1717 188
121 124 131 138 147 157 168 181 194
3000 9251210 064 1256 073 1337 090 1412 107 1486 125 1556 144 1627 165 1695 186 1769 209
134 138 145 152 161 171 183 194 21
3250 10031303 080 1347 090 1423 108 1494 127 1563 146 1630 166 1695 186 1760 209 1823 232
149 153 161 169 177 187 199 21 22
3500 10801397 098 1438 109 1511 128 1578 148 1642 169 1706 190 1768 211 1828 233 1889 258
166 170 179 187 195 21 22 23 24
3750 11571491 119 1530 130 1599 152 1663 173 1725 194 1784 216 1844 239 1900 262 1956 286
185 189 197 21 22 23 24 25 27
4000 12341585 143 1622 155 1689 178 1750 200 1809 223 1865 246 1921 270 1976 295
20 21 22 23 24 25 26 28
4250 13111680 170 1714 183 1779 207 1838 231 1893 255 1948 280 1999 304
23 23 24 25 26 28 29
4500 13881775 200 1807 214 1869 240 1926 265 1979 291
25 26 27 28 30
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
21
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
TCB-2-16 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2431
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 432
Maximum bhp at a given rpm mdash (rpm1406)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1200 370668 011 842 020 1137 041
46 61 104
1500 462749 015 899 025 1166 049 1395 077
55 68 102 138
1800 555843 021 969 033 1208 059 1424 089 1616 121
71 77 104 135 168
2100 648944 030 1053 042 1268 071 1461 103 1647 138 1813 175 1972 215
83 88 111 134 166 196 22
2400 740
1047 040 1144 054 1336 085 1518 120 1684 157 1847 197 1996 238 2140 283 2275 329
99 105 120 140 166 195 22 25 27
2700 8331152 053 1243 068 1412 101 1579 139 1739 179 1885 221 2033 266 2169 312 2297 359
116 122 132 150 171 195 22 25 28
3000 9251260 069 1345 086 1498 121 1651 161 1799 204 1941 248 2070 295 2206 344 2333 394
132 136 144 162 182 20 23 25 28
3300 10181373 089 1448 107 1588 144 1727 186 1866 231 2001 279 2129 328 2247 379 2370 432
147 151 161 177 195 22 24 26 29
3600 11111486 112 1553 131 1686 171 1813 215 1939 262 2065 312 2188 365 2306 418 2416 473
166 171 182 193 21 23 25 28 30
3900 12031600 140 1658 159 1786 202 1900 247 2020 297 2138 349 2252 404 2366 461
189 194 20 21 23 25 27 29
4200 12961715 172 1766 191 1888 238 1996 285 2106 336 2213 390 2324 448 2430 508
21 21 22 23 24 26 29 31
4500 13881831 208 1878 228 1990 277 2095 328 2193 380 2298 437 2398 496
23 23 24 25 27 28 31
4800 14811946 250 1992 271 2094 322 2196 376 2289 430 2385 488
25 26 27 28 29 31
5100 15742062 296 2105 319 2199 371 2297 429 2388 486
28 28 29 30 32
5400 16662179 349 2219 373 2305 426 2399 487
30 31 32 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
22
TCB-1-18 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1645
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 4843
Maximum bhp at a given rpm mdash (rpm1147)3
Max Motor Frame Size - 182T
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg
0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1500 298486 008 568 012 724 023
43 49 62
1800 357552 011 623 016 755 028 883 042
54 57 67 81
2100 417622 016 683 021 799 034 911 048 1022 065 1123 082
67 68 77 85 99 116
2400 477693 021 749 028 852 041 950 056 1048 073 1147 092 1238 112 1322 133
80 81 90 95 103 120 135 148
2700 536
765 029 817 036 911 050 1001 066 1088 084 1174 103 1262 124 1346 146 1424 169
91 94 103 105 113 125 138 150 164
3000 596838 037 887 045 972 061 1056 078 1136 097 1214 117 1292 138 1369 161 1448 185
102 106 111 115 122 133 142 153 166
3300 656912 048 957 057 1038 074 1115 092 1187 111 1261 132 1331 154 1403 177 1472 202
112 114 120 126 133 141 149 158 168
3600 715987 061 1029 070 1105 089 1176 108 1246 128 1312 149 1379 172 1443 196 1510 222
121 125 131 138 145 152 160 168 178
3900 7751063 075 1102 085 1174 106 1239 126 1305 147 1368 170 1430 193 1491 218 1549 244
133 137 143 149 157 165 173 181 189
4200 8341139 092 1175 103 1244 125 1307 147 1366 169 1428 193 1485 217 1542 243 1599 269
146 149 155 163 171 179 187 195 20
4500 8941215 112 1249 124 1315 147 1375 170 1430 193 1488 218 1544 244 1597 270
160 162 169 176 185 194 20 21
4800 9541292 134 1323 147 1386 172 1444 197 1498 221 1549 246 1604 273
171 174 181 190 199 21 22
5100 10131369 159 1399 172 1458 199 1513 226 1565 252 1615 278
184 187 195 20 21 23
5400 10731446 188 1474 201 1530 229 1584 258 1634 285
197 20 21 22 23
5700 11331523 219 1550 233 1603 263
21 22 22
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 832
8
Optional Construction Features
Aluminum Construction
Aluminum construction is available on the TCB TCBRU and TCBRS Aluminum fans are an excellent choice for
applications involving moisture or coastal installations
Easy Access Construction
The Easy Access option is highly recommended to allow forinspection cleaning and service of internal fan components
By removing one access panel service to the wheel shaft
and bearing assembly is possible without removing duct
connections In addition all internal fan components can be
removed from the fan through the easy access panel
Easy Access construction is available on all levels and sizes
of TCB TCBRU and TCBRS Easy Access is also available
with aluminum fan construction
The Easy Access panel is located 180deg from the motor
position
Standard Construction Features
Inlet amp Outlet Flanges
Flanged inlets and outlets with mounting holes are
provided for duct connections (TCB only)
Housing
Housings are continuously welded steel and coated
with Permatector trade
Protective Coating
All steel constructed units are coated with
Permatectortrade a thermosetting polyester urethane
Aluminum units are uncoated
Type B Spark Resistance
All fans have aluminum wheels and a nonferrous
(aluminum) rub ring which surrounds the fanshaft where it passes through the drive cover
This construction meets Type B spark resistant
requirements
Bearings
Standard bearings are grease lubricated self-aligning
ball type in pillow block mounts Bearings are selected
for a minimum L10 life in excess of 80000 hours (L50 average life of 400000 hours) at maximum cataloged
operating speeds
Belt amp Bearing Tube
Belts bearings and drives are protected from the
airstream by heavy gauge belt tubes and bolted
bearing covers with shaft seals
Extended
Lube Lines
Lubrication lines with grease
fittings allow bearing lubricationwithout disassembling the fan
TCB - 1 - 24 - 30Tubular CentrifugalBelt Drive
TCB - Inline FanTCBRU - Roof Upblast FanTCBRS - Roof Supply Fan
Level of Construction1 or 2
Motor Horsepower
4 = 1 4 30=3 3 = 1 3 50=5
5 = 1 2 75=7 1 2
7 = 3 4 100=10
10=1 150=15
15=11 2 200=20 20=2
Fan Size09-36
Model Number CodeThe model number system is designed to completely identify
the fan A detailed explanation of the model number code for
TCB fans is shown below
Construction Features
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 932
9
Inline grease exhaust fans are excellent alternative for kitchen applications when roof or wall mounted ventilators
are not practical The TCB with UL 762 grease option is designed to withstand the demands of high temperature
kitchen grease exhaust and high-pressure duct washes
Continuously welded housing and integral duct flanges
provide air and water tight design
Bearing cover gasketed and includes a labyrinth shaft seal
to prevent moisture leakage during normal operation and
while cleaning with high pressure solvents
Continuously welded belt tube keeps the belts and
bearings clean
Two threaded drain connections are located 90deg from the
motor location to allow for removal of grease and moisture
UL 762 is concerned with fans
designed for removal of smoke and
grease laden vapors with airstream
temperatures up to 300degF
bull Meets all UL 705 Requirements
bull Bolted Access Door
bull Drain Connectionbull Meets requirements of NFPA 96
Ventilation Control and Fire
Protection of Commercial
Cooking Operations
Listed Power
Ventilation for
Restaurant
Exhaust Appliances
13G3
Maximum
Operating
Temperature
300degF
The TCB inline grease fan is tough to beat when
packaged with our full line of kitchen hoods and grease
extraction options Take advantage of Greenheckrsquos
expertise in providing a total solution in kitchen
ventilation equipment
A Tough Package to Beat
Leak Resistant Construction Features
bull Inline grease exhaust fans should be installed near the end of the duct run to reduce sound at the hood
bull Inline fan must be securely bolted to the exhaust duct per NFPA-96 guidelines Greenheckrsquos companion flange
are recommended for ease of installation
bull Grease exhaust fans and ductwork must maintain 18 inches (46 cm) minimum clearance to combustible
material If the ductwork and fan are insulated the inspection door must be accessible for maintenancebull A minimum of 10 ft (30 m) of clearance must be kept from the fan outlet to adjacent buildings property lines
or the closest point of any air intake or operable window at or below the plane of the exhaust termination
bull Greenheck recommends that all inline grease applications be reviewed by your local code official to ensure
compliance with NFPA IMC and other local codes
System Design Guidelines
1
2
3
4
5
6
7
Mounting and Serviceability Features
4 6
7
5 14
Optional Construction forUL 762 Restaurant Exhaust
Universal mounting brackets allow for rotation of the motor to
the 3 or 9 orsquoclock position at the jobsiteDuct flanges and access door bolt locations are no more
than 4 inches (100 mm) on center per NFPA 96
ldquoEasy Access Doorrdquo provides access for duct cleaning and allows removal of the wheel
shaft and bearings for maintenance Gasket is rated for 400degF (200degC) and prevents
leakage during operation [Fan is rated for 300degF (149degC) continous operation]
Air1047298ow
Duct to heat source
Ambient temperaturenot to exceed 120ordmF
Wall andor ceiling should enclosefan when used for emergency heatand smoke exhaust Enclosure shallbe per NFPA 96 or local building codes
Roof
Cooling air fordrives andbearings
Minimum ductat discharge
To buildingexterior
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1032
10
Electrical Accessories
Belt Guard (TCB only) Belt guards are totally enclosed to provide protection
from rotating pulleys and belts Belt guards meet
OSHA guidelines
Motor Cover (Weatherhood) Weatherproof motor covers shield the motor and
drive components from dust dirt and moisture when
used in outdoor applications Motor covers also
provide protection from rotating pulleys and belts and
meet OSHA guidelines Motor covers are standard on
TCBRU and TCBRS models
Inlet and Outlet Companion Flanges
(TCB only) Companion inlet flanges and outlet flanges with
prepunched holes are available for all fan sizes in
painted steel construction
Inlet and Outlet Guards (TCB TCBRU)
Removable inlet and outlet guards provide protectionfor personnel and equipment in non-ducted
installations These guards meet OSHA guidelines
TCBRU fans are available with outlet screens to
shield the fan discharge and damper from debris
Inspection Door Bolted or hinged doors provide access for cleaning or
inspection
Inspection Section (TCB only) Inspection sections serve as a length of duct that can
be easily removed to provide for complete access to
the fan for servicing Each section includes a bolted
inspection door
Isolators (TCB only) Both base mount or hanging isolators are available in
either neoprene or spring mounts The isolators are
furnished in sets of four and are sized to match the
weight of each fan
Mounting Rails (TCB only) Mounting rails are required for horizontal mounting
of TCB fans when the motor is to be located in
the 3 or 9 orsquoclock position Mounting rails are also
recommended for all vertically mounted inline fans
See page 5 for additional details
Protective Coatings Greenheck has a wide offering of protective coatings
Consult Greenheckrsquos Product Application Guide
FA110-04R4 Performance Coatings for Ventilation
Products for a complete listing of coatings and a
relative resistance chart
Inlet Vane Dampers (TCB only) Nested inlet vane dampers for controlling air volume
are available on model TCB inline fans with Level 2
steel construction in fan sizes 12 through 36
Birdscreen Insect Screen (TCBRS only)
TCBRS fans are available with either aluminum insectscreen or birdscreen at the hood intake (Birdscreen is
standard)
Roof Curbs (TCBRU TCBRS) Prefabricated roof curbs are available to reduce
installation time and costs by ensuring compatibility
between the fan the curb and the roof opening
All curbs are lined with fiberglass insulation to
prevent condensation and reduce sound levels See
Greenheckrsquos Roof Curb Extensions and Equipment
Supports catalog for complete details
Washable Aluminum Filters (TCBRS only)
Helps trap dust and dirt before it enters the fanFilters can be removed for cleaning
Enclosure Application Toggle Heavy Duty
NEMA-1 Indoor General Purpose Yes Yes
NEMA-12 Indoor DustDrip Tight Yes YesNEMA-3R IndoorOutdoor Rainproof Yes Yes
NEMA-4 IndoorOutdoor Watertight Yes Yes
NEMA-4X IndoorOutdoor Watertight
(Corrosion Resistant) Yes Yes
NEMA-7 amp 9 Indoor Hazardous Locations Yes No
Toggle type and heavy duty disconnect switches are available for positive
electrical shut-off and safety in servicing fans The following switches are
available to meet individual electrical requirements
Accessories
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1132
11
Inspection
Section
Outlet Guard
Belt Guard
Motor Cover
Companion Flange
(Outlet)NeopreneIsolator
Spring Base
Isolator
Inspection
Door
Easy Access
Inlet Guard
CompanionFlange (Inlet)
Mounting Rails
Spring HangingIsolator
Isolator Neoprene Hanging
Accessories (Model TCB shown)
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
12
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
360 195846 002 999 003 1260 006
53 60 75
420 228941 003 1071 004 1314 007 1526 011
57 63 77 92
480 2601040 004 1155 005 1380 009 1576 012 1758 017
63 68 80 93 106
540 2931144 005 1245 006 1449 010 1635 014 1807 019 1968 023 2115 028
71 74 84 95 107 120 133
600 326
1250 006 1341 008 1523 012 1704 016 1865 021 2017 026 2163 031 2298 036
78 81 88 99 110 122 135 147
660 3581357 007 1439 009 1606 014 1774 018 1930 023 2074 029 2212 034 2346 040 2472 046
86 88 93 104 114 126 137 149 162
720 3911465 009 1542 011 1692 016 1845 021 1999 026 2137 032 2270 038 2395 043 2520 050
94 96 100 109 120 131 140 150 163
780 4231576 012 1647 014 1786 018 1928 024 2069 029 2206 035 2331 041 2454 047 2570 054
102 104 108 115 127 136 145 154 165
840 4561688 014 1752 016 1882 021 2012 027 2142 033 2276 039 2400 045 2515 052 2629 059
110 112 117 123 133 142 150 160 170
900 4891801 017 1859 019 1980 025 2100 030 2225 036 2347 043 2469 050 2584 056
120 122 127 133 139 148 157 166
960 5211914 020 1966 023 2081 028 2195 034 2310 040 2424 047 2540 054
130 132 140 142 147 154 164
1020 5542028 024 2075 026 2184 032 2292 038 2395 044 2507 052 2612 059
144 149 150 151 155 163 172
1080 5862141 028 2186 031 2288 037 2389 043 2490 050 2592 057
159 159 160 162 166 172
1140 6192255 033 2298 036 2394 042 2487 049 2585 055
169 169 171 174 178
1200 6522370 038 2410 041 2500 047 2590 054
179 180 183 186
TCB-1-09 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2645
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm3114)3
Max Motor Frame Size - 56
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
13
TCB-2-09 Level 2 Construction
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3330)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg
025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
400 2171198 005 1460 008 1893 018
73 87 119
480 2601332 006 1566 010 1971 020 2309 032
82 96 127 157
560 3041480 009 1686 013 2059 024 2386 036 2671 049
92 106 135 165 191
640 3471635 011 1818 016 2158 027 2469 041 2749 055 3000 070 3228 086
106 117 146 174 20 23 25
720 3911799 015 1958 020 2275 032 2562 045 2830 061 3078 077 3305 094 3514 112
120 130 158 183 21 23 25 28
800 4341966 020 2108 025 2397 037 2666 051 2921 067 3158 085 3383 103 3591 121 3786 141
134 145 169 183 22 24 26 28 31
880 4782135 025 2262 030 2528 043 2784 058 3015 074 3250 093 3464 112 3669 132 3863 152
151 162 182 21 23 25 27 29 32
960 5212308 032 2425 037 2665 050 2905 066 3132 083 3343 101 3555 121 3752 142 3942 164
168 176 196 22 24 26 28 31 33
1040 5652482 039 2590 045 2810 059 3033 075 3251 093 3453 111 3648 131 3844 153 4027 176
184 193 21 23 25 27 29 32 34
1120 6082658 048 2757 054 2960 068 3168 085 3372 103 3571 123 3754 143 3937 165
20 21 23 25 27 29 31 33
1200 6522835 058 2925 065 3113 079 3306 096 3501 115 3691 135 3872 157 4041 179
22 23 24 26 28 30 32 35
1280 6953012 070 3095 076 3271 091 3453 109 3636 128 3813 149 3991 171
24 25 26 28 29 32 34
1360 7393190 083 3269 090 3434 105 3603 123 3773 143 3945 164
26 26 28 29 31 34
1440 7823368 097 3444 105 3599 121 3756 139 3917 159
28 28 30 31 33
1520 8263547 114 3619 121 3765 138 3909 156
30 30 32 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
14
TCB-1-10 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2555
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm2760)3
Max Motor Frame Size - 143T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
480 260858 003 1011 005 1253 009
49 57 73
560 304947 004 1089 006 1321 011 1511 015
55 63 77 93
640 3471042 005 1171 008 1394 013 1578 018 1740 023 1892 029
63 70 82 96 112 133
720 3911141 007 1259 009 1470 015 1649 021 1806 027 1949 033 2079 039
72 76 89 100 115 132 150
800 4341239 009 1349 012 1548 018 1723 024 1876 031 2015 037 2144 044 2263 051
80 84 96 107 119 135 148 161
880 4781340 011 1444 014 1630 021 1798 027 1949 034 2084 042 2211 049 2329 057 2440 064
88 92 102 113 125 137 150 162 176
960 5211441 014 1541 017 1716 024 1876 031 2023 039 2157 047 2280 055 2396 063 2506 071
97 101 109 121 133 141 152 165 179
1040 5651544 017 1640 021 1805 028 1957 035 2099 044 2231 052 2352 060 2465 069
105 109 117 129 139 148 157 169
1120 6081648 021 1739 025 1895 032 2042 040 2178 049 2306 058 2426 067 2538 076
113 117 127 138 146 155 165 177
1200 6521752 025 1839 029 1989 037 2129 046 2259 055 2383 064 2501 073
122 126 137 145 153 163 175
1280 6951858 030 1940 034 2085 043 2218 052 2343 061 2464 071
132 137 145 152 162 173
1360 7391964 035 2041 040 2183 049 2308 058 2430 068 2545 078
145 149 154 162 172 183
1440 7822071 041 2144 046 2282 056 2401 066 2519 076
156 158 164 173 183
1520 8262177 048 2247 053 2380 064 2497 074
164 167 175 184
1600 8692285 056 2351 061 2479 072
173 177 185
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
15
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-10 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3120)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 3261300 007 1504 011 1875 021 2213 032
73 82 105 132
700 3801453 010 1630 014 1966 024 2273 036 2560 049
84 91 110 133 156
800 4341611 013 1768 018 2070 029 2355 042 2619 055 2872 070 3102 086
100 101 118 137 158 182 20
900 4891773 017 1917 023 2188 034 2448 048 2698 062 2932 078 3160 094 3371 111 3568 129
112 113 127 143 162 185 20 22 25
1000 543
1937 023 2071 029 2319 041 2559 055 2790 070 3011 086 3220 103 3430 122 3626 140
124 127 136 152 170 190 21 23 25
1100 5972104 029 2228 035 2457 048 2677 063 2892 079 3103 096 3303 114 3490 132 3685 152
138 143 146 161 179 195 21 23 25
1200 6522276 036 2389 043 2601 057 2807 073 3009 089 3199 107 3394 125 3578 145 3751 165
154 154 159 172 189 20 21 23 25
1300 7062449 045 2552 052 2753 067 2944 083 3128 101 3315 119 3488 138 3670 159 3841 180
164 166 172 183 195 21 22 24 25
1400 7602623 055 2717 062 2907 079 3083 095 3261 114 3433 133 3603 153 3763 173 3933 196
175 177 185 193 20 21 23 24 26
1500 8152797 066 2883 074 3063 092 3231 109 3398 128 3557 148 3721 169 3878 191 4026 212
186 189 197 20 21 22 23 25 26
1600 8692973 079 3052 087 3223 106 3384 125 3537 144 3693 165 3840 186 3995 209
198 20 21 21 22 23 24 25
1700 9233149 094 3224 103 3384 122 3538 142 3683 162 3831 184 3974 206
21 21 22 22 23 23 25
1800 9783325 110 3396 119 3546 140 3693 161 3834 182 3970 204
22 22 23 23 24 24
1900 10323502 129 3570 138 3710 159 3852 182 3988 204
23 24 24 25 25
2000 10863679 149 3744 159 3875 181 4012 204
25 25 25 26
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
16
TCB-1-12 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2490
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 3436
Maximum bhp at a given rpm mdash (rpm2202)3
Max Motor Frame Size - 145T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 0075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
700 380853 006 958 008 1158 014 1345 021 1518 028
62 66 79 94 110
800 434943 008 1042 011 1218 017 1386 024 1551 031 1703 040
66 70 83 96 111 125
900 4891037 010 1128 013 1287 020 1442 027 1587 035 1736 044 1873 053 2000 063
71 76 87 99 112 126 142 155
1000 5431132 013 1216 017 1363 024 1506 031 1643 040 1771 049 1906 059 2033 069 2151 079
78 83 91 103 115 128 143 156 170
1100 597
1229 016 1305 020 1447 028 1574 036 1702 045 1827 055 1943 065 2066 075 2183 086
86 89 96 108 120 133 144 157 171
1200 6521326 020 1398 025 1532 034 1649 042 1769 051 1884 061 1999 071 2105 082 2216 094
92 95 103 113 126 139 149 159 173
1300 7061426 025 1492 030 1619 039 1732 049 1839 058 1950 068 2055 079 2161 090 2260 102
98 102 112 121 134 145 154 164 176
1400 7601526 031 1588 036 1707 046 1817 056 1916 066 2019 076 2120 088 2217 099 2316 111
106 112 122 132 142 151 160 170 181
1500 8151627 037 1684 042 1796 053 1903 064 1999 075 2089 085 2188 097 2281 109 2372 121
119 125 135 144 149 157 167 176 187
1600 8691729 044 1781 050 1886 061 1990 073 2084 085 2170 096 2258 107 2350 120 2436 133
134 139 150 153 157 165 174 183 194
1700 9231830 053 1879 058 1980 070 2077 083 2170 095 2254 107 2334 119 2419 132
151 157 159 162 167 173 181 191
1800 9781932 062 1978 068 2074 080 2166 093 2256 107 2339 120 2417 132
166 166 168 171 176 182 190
1900 10322034 072 2078 078 2169 091 2256 105 2343 119 2425 133
173 173 176 180 185 192
2000 10862137 083 2179 090 2265 103 2348 118 2432 133
180 181 184 189 195
2100 11412240 096 2280 102 2361 117 2442 132
187 188 192 198
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
17
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-12 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 3274
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 321
Maximum bhp at a given rpm mdash (rpm2315)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
750 4071009 008 1226 014 1587 027
55 67 98
900 4891119 011 1315 018 1648 032 1936 049 2182 067
63 76 102 131 159
1050 5701238 015 1419 023 1728 039 1995 056 2240 076 2456 096
75 85 110 136 164 190
1200 6521363 020 1529 029 1813 046 2070 065 2299 085 2514 108 2710 131 2890 155
89 96 120 142 169 195 22 24
1350 733
1495 027 1643 036 1911 055 2151 076 2372 097 2574 120 2768 145 2948 171 3115 197
104 111 132 152 176 20 22 25 28
1500 8151630 034 1764 044 2018 066 2240 088 2452 111 2647 135 2828 160 3007 187 3174 216
120 129 145 166 186 21 23 26 29
1650 8961767 044 1887 054 2127 077 2338 101 2534 126 2727 151 2903 178 3067 205 3233 235
139 144 159 184 199 22 24 27 30
1800 9781908 055 2018 066 2239 090 2445 117 2630 143 2808 170 2983 198 3145 227
159 165 180 199 22 23 25 28
1950 10592053 068 2151 079 2356 105 2554 134 2731 162 2900 190 3064 220 3225 250
182 188 20 22 23 25 27 29
2100 11412198 083 2286 095 2477 122 2664 152 2839 183 2997 213 3154 244
21 22 22 23 25 27 29
2250 12222344 100 2423 113 2599 141 2777 173 2948 205 3104 238 3250 271
24 24 25 26 27 29 32
2400 13042490 119 2560 133 2726 163 2896 196 3058 230 3212 265
26 26 27 28 30 32
2550 13852637 141 2703 156 2858 187 3016 221 3169 257
28 29 29 31 32
2700 14672785 166 2847 181 2991 214 3138 248
31 31 32 34
2850 15482933 193 2992 209 3126 243 3262 279
34 34 35 37
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
18
TCB-1-13 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2355
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 3435
Maximum bhp at a given rpm mdash (rpm2119)3
Max Motor Frame Size - 145T
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 265660 003 792 005 1019 010
41 51 69
750 331760 005 874 007 1073 013 1254 019
48 58 71 84
900 398864 007 967 010 1146 016 1305 023 1459 030
58 64 75 86 102
1050 464973 009 1067 013 1230 020 1378 027 1512 036 1646 044 1770 053
66 70 80 91 103 120 140
1200 530
1085 013 1171 017 1321 024 1457 032 1585 041 1703 051 1820 061 1933 071 2039 081
72 77 86 96 108 120 136 153 172
1350 5971199 017 1277 022 1419 030 1545 039 1662 048 1777 058 1883 069 1984 080 2089 091
81 85 94 103 114 125 136 151 167
1500 6631316 023 1387 027 1520 037 1637 046 1749 059 1853 067 1957 078 2054 090 2146 102
90 94 102 112 122 132 143 155 169
1650 7301434 029 1499 034 1623 044 1736 055 1839 065 1940 077 2034 088 2128 100 2219 113
100 104 113 123 132 143 153 165 178
1800 7961552 037 1613 042 1729 054 1836 065 1935 076 2029 088 2121 100 2207 113 2293 126
112 115 125 134 144 154 165 177 190
1950 8621672 045 1728 052 1836 064 1939 076 2034 088 2123 100 2209 113 2294 127
124 129 138 147 156 167 178 190
2100 9291792 056 1844 062 1947 076 2044 089 2135 102 2221 115 2302 128
138 142 151 161 170 181 192
2250 9951913 067 1962 075 2058 089 2150 103 2238 117 2321 131
152 157 167 177 186 196
2400 10612034 081 2080 088 2171 104 2258 119 2342 133
169 174 184 194 20
2550 11282155 095 2199 104 2285 120
187 192 20
2700 11942277 112 2319 121
21 21
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
19
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
TCB-2-13 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2971
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 353
Maximum bhp at a given rpm mdash (rpm1933)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
800 353828 008 1026 014 1379 030
38 56 104
1000 442934 011 1108 018 1418 035 1692 055
44 60 101 135
1200 5301048 016 1206 024 1479 042 1731 064 1961 087
58 72 101 130 165
1400 6191171 022 1313 031 1562 051 1784 073 2002 099 2201 126 2391 155
75 87 106 128 160 189 22
1600 707
1300 030 1424 040 1657 062 1865 086 2053 112 2247 141 2425 171 2596 203 2759 237
97 100 115 133 156 184 21 24 27
1800 7961431 039 1545 051 1759 075 1950 101 2134 129 2300 157 2472 189 2636 223 2790 258
114 113 125 144 160 181 21 24 26
2000 8841565 051 1669 063 1868 090 2050 118 2217 148 2381 178 2531 210 2683 244 2836 282
127 127 137 157 170 186 21 23 26
2200 9731700 064 1797 078 1979 107 2152 138 2312 169 2464 202 2612 236 2750 270 2883 306
142 145 156 169 183 198 21 23 26
2400 10611836 081 1928 096 2097 127 2260 160 2413 194 2556 228 2695 264 2831 301 2959 338
164 169 174 182 197 21 23 24 26
2600 11501975 100 2060 116 2219 150 2371 185 2517 221 2656 257 2785 295 2914 334
190 192 193 196 21 23 24 26
2800 12382115 122 2194 140 2343 175 2484 212 2626 251 2758 290 2885 330
21 21 21 22 23 24 26
3000 13272256 148 2329 166 2470 204 2605 243 2737 284 2864 325
24 24 24 24 25 26
3200 14152397 177 2464 196 2600 236 2728 278 2849 320
26 26 26 27 27
3400 15042539 210 2601 230 2731 272 2852 316 2969 361
29 29 30 30 30
3600 15922681 247 2739 267 2863 312
33 33 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
20
TCB-1-16 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2000
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 4384
Maximum bhp at a given rpm mdash (rpm1378)3
Max Motor Frame Size - 182T
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1000 308507 005 612 009 802 017
37 43 59
1250 385584 008 671 012 833 021 985 032
45 49 62 81
1500 462668 011 743 016 884 026 1016 038 1145 052
54 58 69 84 103
1750 540755 016 821 021 944 032 1065 045 1176 059 1289 075 1392 091
64 68 79 93 105 120 136
2000 617
844 022 904 028 1014 040 1119 054 1225 069 1322 085 1422 102 1517 120 1605 139
76 81 92 104 113 124 140 157 175
2250 694934 030 989 036 1090 049 1185 064 1278 080 1373 097 1460 115 1547 134 1635 154
89 94 107 114 123 133 146 161 179
2500 7711026 039 1077 047 1169 061 1257 076 1342 092 1425 110 1511 130 1591 149 1666 170
104 110 119 126 134 144 156 169 184
2750 8481118 051 1166 059 1252 074 1334 091 1411 107 1489 126 1564 146 1643 167 1717 188
121 124 131 138 147 157 168 181 194
3000 9251210 064 1256 073 1337 090 1412 107 1486 125 1556 144 1627 165 1695 186 1769 209
134 138 145 152 161 171 183 194 21
3250 10031303 080 1347 090 1423 108 1494 127 1563 146 1630 166 1695 186 1760 209 1823 232
149 153 161 169 177 187 199 21 22
3500 10801397 098 1438 109 1511 128 1578 148 1642 169 1706 190 1768 211 1828 233 1889 258
166 170 179 187 195 21 22 23 24
3750 11571491 119 1530 130 1599 152 1663 173 1725 194 1784 216 1844 239 1900 262 1956 286
185 189 197 21 22 23 24 25 27
4000 12341585 143 1622 155 1689 178 1750 200 1809 223 1865 246 1921 270 1976 295
20 21 22 23 24 25 26 28
4250 13111680 170 1714 183 1779 207 1838 231 1893 255 1948 280 1999 304
23 23 24 25 26 28 29
4500 13881775 200 1807 214 1869 240 1926 265 1979 291
25 26 27 28 30
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
21
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
TCB-2-16 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2431
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 432
Maximum bhp at a given rpm mdash (rpm1406)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1200 370668 011 842 020 1137 041
46 61 104
1500 462749 015 899 025 1166 049 1395 077
55 68 102 138
1800 555843 021 969 033 1208 059 1424 089 1616 121
71 77 104 135 168
2100 648944 030 1053 042 1268 071 1461 103 1647 138 1813 175 1972 215
83 88 111 134 166 196 22
2400 740
1047 040 1144 054 1336 085 1518 120 1684 157 1847 197 1996 238 2140 283 2275 329
99 105 120 140 166 195 22 25 27
2700 8331152 053 1243 068 1412 101 1579 139 1739 179 1885 221 2033 266 2169 312 2297 359
116 122 132 150 171 195 22 25 28
3000 9251260 069 1345 086 1498 121 1651 161 1799 204 1941 248 2070 295 2206 344 2333 394
132 136 144 162 182 20 23 25 28
3300 10181373 089 1448 107 1588 144 1727 186 1866 231 2001 279 2129 328 2247 379 2370 432
147 151 161 177 195 22 24 26 29
3600 11111486 112 1553 131 1686 171 1813 215 1939 262 2065 312 2188 365 2306 418 2416 473
166 171 182 193 21 23 25 28 30
3900 12031600 140 1658 159 1786 202 1900 247 2020 297 2138 349 2252 404 2366 461
189 194 20 21 23 25 27 29
4200 12961715 172 1766 191 1888 238 1996 285 2106 336 2213 390 2324 448 2430 508
21 21 22 23 24 26 29 31
4500 13881831 208 1878 228 1990 277 2095 328 2193 380 2298 437 2398 496
23 23 24 25 27 28 31
4800 14811946 250 1992 271 2094 322 2196 376 2289 430 2385 488
25 26 27 28 29 31
5100 15742062 296 2105 319 2199 371 2297 429 2388 486
28 28 29 30 32
5400 16662179 349 2219 373 2305 426 2399 487
30 31 32 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
22
TCB-1-18 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1645
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 4843
Maximum bhp at a given rpm mdash (rpm1147)3
Max Motor Frame Size - 182T
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg
0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1500 298486 008 568 012 724 023
43 49 62
1800 357552 011 623 016 755 028 883 042
54 57 67 81
2100 417622 016 683 021 799 034 911 048 1022 065 1123 082
67 68 77 85 99 116
2400 477693 021 749 028 852 041 950 056 1048 073 1147 092 1238 112 1322 133
80 81 90 95 103 120 135 148
2700 536
765 029 817 036 911 050 1001 066 1088 084 1174 103 1262 124 1346 146 1424 169
91 94 103 105 113 125 138 150 164
3000 596838 037 887 045 972 061 1056 078 1136 097 1214 117 1292 138 1369 161 1448 185
102 106 111 115 122 133 142 153 166
3300 656912 048 957 057 1038 074 1115 092 1187 111 1261 132 1331 154 1403 177 1472 202
112 114 120 126 133 141 149 158 168
3600 715987 061 1029 070 1105 089 1176 108 1246 128 1312 149 1379 172 1443 196 1510 222
121 125 131 138 145 152 160 168 178
3900 7751063 075 1102 085 1174 106 1239 126 1305 147 1368 170 1430 193 1491 218 1549 244
133 137 143 149 157 165 173 181 189
4200 8341139 092 1175 103 1244 125 1307 147 1366 169 1428 193 1485 217 1542 243 1599 269
146 149 155 163 171 179 187 195 20
4500 8941215 112 1249 124 1315 147 1375 170 1430 193 1488 218 1544 244 1597 270
160 162 169 176 185 194 20 21
4800 9541292 134 1323 147 1386 172 1444 197 1498 221 1549 246 1604 273
171 174 181 190 199 21 22
5100 10131369 159 1399 172 1458 199 1513 226 1565 252 1615 278
184 187 195 20 21 23
5400 10731446 188 1474 201 1530 229 1584 258 1634 285
197 20 21 22 23
5700 11331523 219 1550 233 1603 263
21 22 22
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 932
9
Inline grease exhaust fans are excellent alternative for kitchen applications when roof or wall mounted ventilators
are not practical The TCB with UL 762 grease option is designed to withstand the demands of high temperature
kitchen grease exhaust and high-pressure duct washes
Continuously welded housing and integral duct flanges
provide air and water tight design
Bearing cover gasketed and includes a labyrinth shaft seal
to prevent moisture leakage during normal operation and
while cleaning with high pressure solvents
Continuously welded belt tube keeps the belts and
bearings clean
Two threaded drain connections are located 90deg from the
motor location to allow for removal of grease and moisture
UL 762 is concerned with fans
designed for removal of smoke and
grease laden vapors with airstream
temperatures up to 300degF
bull Meets all UL 705 Requirements
bull Bolted Access Door
bull Drain Connectionbull Meets requirements of NFPA 96
Ventilation Control and Fire
Protection of Commercial
Cooking Operations
Listed Power
Ventilation for
Restaurant
Exhaust Appliances
13G3
Maximum
Operating
Temperature
300degF
The TCB inline grease fan is tough to beat when
packaged with our full line of kitchen hoods and grease
extraction options Take advantage of Greenheckrsquos
expertise in providing a total solution in kitchen
ventilation equipment
A Tough Package to Beat
Leak Resistant Construction Features
bull Inline grease exhaust fans should be installed near the end of the duct run to reduce sound at the hood
bull Inline fan must be securely bolted to the exhaust duct per NFPA-96 guidelines Greenheckrsquos companion flange
are recommended for ease of installation
bull Grease exhaust fans and ductwork must maintain 18 inches (46 cm) minimum clearance to combustible
material If the ductwork and fan are insulated the inspection door must be accessible for maintenancebull A minimum of 10 ft (30 m) of clearance must be kept from the fan outlet to adjacent buildings property lines
or the closest point of any air intake or operable window at or below the plane of the exhaust termination
bull Greenheck recommends that all inline grease applications be reviewed by your local code official to ensure
compliance with NFPA IMC and other local codes
System Design Guidelines
1
2
3
4
5
6
7
Mounting and Serviceability Features
4 6
7
5 14
Optional Construction forUL 762 Restaurant Exhaust
Universal mounting brackets allow for rotation of the motor to
the 3 or 9 orsquoclock position at the jobsiteDuct flanges and access door bolt locations are no more
than 4 inches (100 mm) on center per NFPA 96
ldquoEasy Access Doorrdquo provides access for duct cleaning and allows removal of the wheel
shaft and bearings for maintenance Gasket is rated for 400degF (200degC) and prevents
leakage during operation [Fan is rated for 300degF (149degC) continous operation]
Air1047298ow
Duct to heat source
Ambient temperaturenot to exceed 120ordmF
Wall andor ceiling should enclosefan when used for emergency heatand smoke exhaust Enclosure shallbe per NFPA 96 or local building codes
Roof
Cooling air fordrives andbearings
Minimum ductat discharge
To buildingexterior
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1032
10
Electrical Accessories
Belt Guard (TCB only) Belt guards are totally enclosed to provide protection
from rotating pulleys and belts Belt guards meet
OSHA guidelines
Motor Cover (Weatherhood) Weatherproof motor covers shield the motor and
drive components from dust dirt and moisture when
used in outdoor applications Motor covers also
provide protection from rotating pulleys and belts and
meet OSHA guidelines Motor covers are standard on
TCBRU and TCBRS models
Inlet and Outlet Companion Flanges
(TCB only) Companion inlet flanges and outlet flanges with
prepunched holes are available for all fan sizes in
painted steel construction
Inlet and Outlet Guards (TCB TCBRU)
Removable inlet and outlet guards provide protectionfor personnel and equipment in non-ducted
installations These guards meet OSHA guidelines
TCBRU fans are available with outlet screens to
shield the fan discharge and damper from debris
Inspection Door Bolted or hinged doors provide access for cleaning or
inspection
Inspection Section (TCB only) Inspection sections serve as a length of duct that can
be easily removed to provide for complete access to
the fan for servicing Each section includes a bolted
inspection door
Isolators (TCB only) Both base mount or hanging isolators are available in
either neoprene or spring mounts The isolators are
furnished in sets of four and are sized to match the
weight of each fan
Mounting Rails (TCB only) Mounting rails are required for horizontal mounting
of TCB fans when the motor is to be located in
the 3 or 9 orsquoclock position Mounting rails are also
recommended for all vertically mounted inline fans
See page 5 for additional details
Protective Coatings Greenheck has a wide offering of protective coatings
Consult Greenheckrsquos Product Application Guide
FA110-04R4 Performance Coatings for Ventilation
Products for a complete listing of coatings and a
relative resistance chart
Inlet Vane Dampers (TCB only) Nested inlet vane dampers for controlling air volume
are available on model TCB inline fans with Level 2
steel construction in fan sizes 12 through 36
Birdscreen Insect Screen (TCBRS only)
TCBRS fans are available with either aluminum insectscreen or birdscreen at the hood intake (Birdscreen is
standard)
Roof Curbs (TCBRU TCBRS) Prefabricated roof curbs are available to reduce
installation time and costs by ensuring compatibility
between the fan the curb and the roof opening
All curbs are lined with fiberglass insulation to
prevent condensation and reduce sound levels See
Greenheckrsquos Roof Curb Extensions and Equipment
Supports catalog for complete details
Washable Aluminum Filters (TCBRS only)
Helps trap dust and dirt before it enters the fanFilters can be removed for cleaning
Enclosure Application Toggle Heavy Duty
NEMA-1 Indoor General Purpose Yes Yes
NEMA-12 Indoor DustDrip Tight Yes YesNEMA-3R IndoorOutdoor Rainproof Yes Yes
NEMA-4 IndoorOutdoor Watertight Yes Yes
NEMA-4X IndoorOutdoor Watertight
(Corrosion Resistant) Yes Yes
NEMA-7 amp 9 Indoor Hazardous Locations Yes No
Toggle type and heavy duty disconnect switches are available for positive
electrical shut-off and safety in servicing fans The following switches are
available to meet individual electrical requirements
Accessories
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1132
11
Inspection
Section
Outlet Guard
Belt Guard
Motor Cover
Companion Flange
(Outlet)NeopreneIsolator
Spring Base
Isolator
Inspection
Door
Easy Access
Inlet Guard
CompanionFlange (Inlet)
Mounting Rails
Spring HangingIsolator
Isolator Neoprene Hanging
Accessories (Model TCB shown)
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
12
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
360 195846 002 999 003 1260 006
53 60 75
420 228941 003 1071 004 1314 007 1526 011
57 63 77 92
480 2601040 004 1155 005 1380 009 1576 012 1758 017
63 68 80 93 106
540 2931144 005 1245 006 1449 010 1635 014 1807 019 1968 023 2115 028
71 74 84 95 107 120 133
600 326
1250 006 1341 008 1523 012 1704 016 1865 021 2017 026 2163 031 2298 036
78 81 88 99 110 122 135 147
660 3581357 007 1439 009 1606 014 1774 018 1930 023 2074 029 2212 034 2346 040 2472 046
86 88 93 104 114 126 137 149 162
720 3911465 009 1542 011 1692 016 1845 021 1999 026 2137 032 2270 038 2395 043 2520 050
94 96 100 109 120 131 140 150 163
780 4231576 012 1647 014 1786 018 1928 024 2069 029 2206 035 2331 041 2454 047 2570 054
102 104 108 115 127 136 145 154 165
840 4561688 014 1752 016 1882 021 2012 027 2142 033 2276 039 2400 045 2515 052 2629 059
110 112 117 123 133 142 150 160 170
900 4891801 017 1859 019 1980 025 2100 030 2225 036 2347 043 2469 050 2584 056
120 122 127 133 139 148 157 166
960 5211914 020 1966 023 2081 028 2195 034 2310 040 2424 047 2540 054
130 132 140 142 147 154 164
1020 5542028 024 2075 026 2184 032 2292 038 2395 044 2507 052 2612 059
144 149 150 151 155 163 172
1080 5862141 028 2186 031 2288 037 2389 043 2490 050 2592 057
159 159 160 162 166 172
1140 6192255 033 2298 036 2394 042 2487 049 2585 055
169 169 171 174 178
1200 6522370 038 2410 041 2500 047 2590 054
179 180 183 186
TCB-1-09 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2645
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm3114)3
Max Motor Frame Size - 56
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
13
TCB-2-09 Level 2 Construction
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3330)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg
025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
400 2171198 005 1460 008 1893 018
73 87 119
480 2601332 006 1566 010 1971 020 2309 032
82 96 127 157
560 3041480 009 1686 013 2059 024 2386 036 2671 049
92 106 135 165 191
640 3471635 011 1818 016 2158 027 2469 041 2749 055 3000 070 3228 086
106 117 146 174 20 23 25
720 3911799 015 1958 020 2275 032 2562 045 2830 061 3078 077 3305 094 3514 112
120 130 158 183 21 23 25 28
800 4341966 020 2108 025 2397 037 2666 051 2921 067 3158 085 3383 103 3591 121 3786 141
134 145 169 183 22 24 26 28 31
880 4782135 025 2262 030 2528 043 2784 058 3015 074 3250 093 3464 112 3669 132 3863 152
151 162 182 21 23 25 27 29 32
960 5212308 032 2425 037 2665 050 2905 066 3132 083 3343 101 3555 121 3752 142 3942 164
168 176 196 22 24 26 28 31 33
1040 5652482 039 2590 045 2810 059 3033 075 3251 093 3453 111 3648 131 3844 153 4027 176
184 193 21 23 25 27 29 32 34
1120 6082658 048 2757 054 2960 068 3168 085 3372 103 3571 123 3754 143 3937 165
20 21 23 25 27 29 31 33
1200 6522835 058 2925 065 3113 079 3306 096 3501 115 3691 135 3872 157 4041 179
22 23 24 26 28 30 32 35
1280 6953012 070 3095 076 3271 091 3453 109 3636 128 3813 149 3991 171
24 25 26 28 29 32 34
1360 7393190 083 3269 090 3434 105 3603 123 3773 143 3945 164
26 26 28 29 31 34
1440 7823368 097 3444 105 3599 121 3756 139 3917 159
28 28 30 31 33
1520 8263547 114 3619 121 3765 138 3909 156
30 30 32 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
14
TCB-1-10 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2555
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm2760)3
Max Motor Frame Size - 143T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
480 260858 003 1011 005 1253 009
49 57 73
560 304947 004 1089 006 1321 011 1511 015
55 63 77 93
640 3471042 005 1171 008 1394 013 1578 018 1740 023 1892 029
63 70 82 96 112 133
720 3911141 007 1259 009 1470 015 1649 021 1806 027 1949 033 2079 039
72 76 89 100 115 132 150
800 4341239 009 1349 012 1548 018 1723 024 1876 031 2015 037 2144 044 2263 051
80 84 96 107 119 135 148 161
880 4781340 011 1444 014 1630 021 1798 027 1949 034 2084 042 2211 049 2329 057 2440 064
88 92 102 113 125 137 150 162 176
960 5211441 014 1541 017 1716 024 1876 031 2023 039 2157 047 2280 055 2396 063 2506 071
97 101 109 121 133 141 152 165 179
1040 5651544 017 1640 021 1805 028 1957 035 2099 044 2231 052 2352 060 2465 069
105 109 117 129 139 148 157 169
1120 6081648 021 1739 025 1895 032 2042 040 2178 049 2306 058 2426 067 2538 076
113 117 127 138 146 155 165 177
1200 6521752 025 1839 029 1989 037 2129 046 2259 055 2383 064 2501 073
122 126 137 145 153 163 175
1280 6951858 030 1940 034 2085 043 2218 052 2343 061 2464 071
132 137 145 152 162 173
1360 7391964 035 2041 040 2183 049 2308 058 2430 068 2545 078
145 149 154 162 172 183
1440 7822071 041 2144 046 2282 056 2401 066 2519 076
156 158 164 173 183
1520 8262177 048 2247 053 2380 064 2497 074
164 167 175 184
1600 8692285 056 2351 061 2479 072
173 177 185
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
15
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-10 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3120)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 3261300 007 1504 011 1875 021 2213 032
73 82 105 132
700 3801453 010 1630 014 1966 024 2273 036 2560 049
84 91 110 133 156
800 4341611 013 1768 018 2070 029 2355 042 2619 055 2872 070 3102 086
100 101 118 137 158 182 20
900 4891773 017 1917 023 2188 034 2448 048 2698 062 2932 078 3160 094 3371 111 3568 129
112 113 127 143 162 185 20 22 25
1000 543
1937 023 2071 029 2319 041 2559 055 2790 070 3011 086 3220 103 3430 122 3626 140
124 127 136 152 170 190 21 23 25
1100 5972104 029 2228 035 2457 048 2677 063 2892 079 3103 096 3303 114 3490 132 3685 152
138 143 146 161 179 195 21 23 25
1200 6522276 036 2389 043 2601 057 2807 073 3009 089 3199 107 3394 125 3578 145 3751 165
154 154 159 172 189 20 21 23 25
1300 7062449 045 2552 052 2753 067 2944 083 3128 101 3315 119 3488 138 3670 159 3841 180
164 166 172 183 195 21 22 24 25
1400 7602623 055 2717 062 2907 079 3083 095 3261 114 3433 133 3603 153 3763 173 3933 196
175 177 185 193 20 21 23 24 26
1500 8152797 066 2883 074 3063 092 3231 109 3398 128 3557 148 3721 169 3878 191 4026 212
186 189 197 20 21 22 23 25 26
1600 8692973 079 3052 087 3223 106 3384 125 3537 144 3693 165 3840 186 3995 209
198 20 21 21 22 23 24 25
1700 9233149 094 3224 103 3384 122 3538 142 3683 162 3831 184 3974 206
21 21 22 22 23 23 25
1800 9783325 110 3396 119 3546 140 3693 161 3834 182 3970 204
22 22 23 23 24 24
1900 10323502 129 3570 138 3710 159 3852 182 3988 204
23 24 24 25 25
2000 10863679 149 3744 159 3875 181 4012 204
25 25 25 26
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
16
TCB-1-12 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2490
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 3436
Maximum bhp at a given rpm mdash (rpm2202)3
Max Motor Frame Size - 145T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 0075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
700 380853 006 958 008 1158 014 1345 021 1518 028
62 66 79 94 110
800 434943 008 1042 011 1218 017 1386 024 1551 031 1703 040
66 70 83 96 111 125
900 4891037 010 1128 013 1287 020 1442 027 1587 035 1736 044 1873 053 2000 063
71 76 87 99 112 126 142 155
1000 5431132 013 1216 017 1363 024 1506 031 1643 040 1771 049 1906 059 2033 069 2151 079
78 83 91 103 115 128 143 156 170
1100 597
1229 016 1305 020 1447 028 1574 036 1702 045 1827 055 1943 065 2066 075 2183 086
86 89 96 108 120 133 144 157 171
1200 6521326 020 1398 025 1532 034 1649 042 1769 051 1884 061 1999 071 2105 082 2216 094
92 95 103 113 126 139 149 159 173
1300 7061426 025 1492 030 1619 039 1732 049 1839 058 1950 068 2055 079 2161 090 2260 102
98 102 112 121 134 145 154 164 176
1400 7601526 031 1588 036 1707 046 1817 056 1916 066 2019 076 2120 088 2217 099 2316 111
106 112 122 132 142 151 160 170 181
1500 8151627 037 1684 042 1796 053 1903 064 1999 075 2089 085 2188 097 2281 109 2372 121
119 125 135 144 149 157 167 176 187
1600 8691729 044 1781 050 1886 061 1990 073 2084 085 2170 096 2258 107 2350 120 2436 133
134 139 150 153 157 165 174 183 194
1700 9231830 053 1879 058 1980 070 2077 083 2170 095 2254 107 2334 119 2419 132
151 157 159 162 167 173 181 191
1800 9781932 062 1978 068 2074 080 2166 093 2256 107 2339 120 2417 132
166 166 168 171 176 182 190
1900 10322034 072 2078 078 2169 091 2256 105 2343 119 2425 133
173 173 176 180 185 192
2000 10862137 083 2179 090 2265 103 2348 118 2432 133
180 181 184 189 195
2100 11412240 096 2280 102 2361 117 2442 132
187 188 192 198
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
17
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-12 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 3274
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 321
Maximum bhp at a given rpm mdash (rpm2315)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
750 4071009 008 1226 014 1587 027
55 67 98
900 4891119 011 1315 018 1648 032 1936 049 2182 067
63 76 102 131 159
1050 5701238 015 1419 023 1728 039 1995 056 2240 076 2456 096
75 85 110 136 164 190
1200 6521363 020 1529 029 1813 046 2070 065 2299 085 2514 108 2710 131 2890 155
89 96 120 142 169 195 22 24
1350 733
1495 027 1643 036 1911 055 2151 076 2372 097 2574 120 2768 145 2948 171 3115 197
104 111 132 152 176 20 22 25 28
1500 8151630 034 1764 044 2018 066 2240 088 2452 111 2647 135 2828 160 3007 187 3174 216
120 129 145 166 186 21 23 26 29
1650 8961767 044 1887 054 2127 077 2338 101 2534 126 2727 151 2903 178 3067 205 3233 235
139 144 159 184 199 22 24 27 30
1800 9781908 055 2018 066 2239 090 2445 117 2630 143 2808 170 2983 198 3145 227
159 165 180 199 22 23 25 28
1950 10592053 068 2151 079 2356 105 2554 134 2731 162 2900 190 3064 220 3225 250
182 188 20 22 23 25 27 29
2100 11412198 083 2286 095 2477 122 2664 152 2839 183 2997 213 3154 244
21 22 22 23 25 27 29
2250 12222344 100 2423 113 2599 141 2777 173 2948 205 3104 238 3250 271
24 24 25 26 27 29 32
2400 13042490 119 2560 133 2726 163 2896 196 3058 230 3212 265
26 26 27 28 30 32
2550 13852637 141 2703 156 2858 187 3016 221 3169 257
28 29 29 31 32
2700 14672785 166 2847 181 2991 214 3138 248
31 31 32 34
2850 15482933 193 2992 209 3126 243 3262 279
34 34 35 37
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
18
TCB-1-13 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2355
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 3435
Maximum bhp at a given rpm mdash (rpm2119)3
Max Motor Frame Size - 145T
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 265660 003 792 005 1019 010
41 51 69
750 331760 005 874 007 1073 013 1254 019
48 58 71 84
900 398864 007 967 010 1146 016 1305 023 1459 030
58 64 75 86 102
1050 464973 009 1067 013 1230 020 1378 027 1512 036 1646 044 1770 053
66 70 80 91 103 120 140
1200 530
1085 013 1171 017 1321 024 1457 032 1585 041 1703 051 1820 061 1933 071 2039 081
72 77 86 96 108 120 136 153 172
1350 5971199 017 1277 022 1419 030 1545 039 1662 048 1777 058 1883 069 1984 080 2089 091
81 85 94 103 114 125 136 151 167
1500 6631316 023 1387 027 1520 037 1637 046 1749 059 1853 067 1957 078 2054 090 2146 102
90 94 102 112 122 132 143 155 169
1650 7301434 029 1499 034 1623 044 1736 055 1839 065 1940 077 2034 088 2128 100 2219 113
100 104 113 123 132 143 153 165 178
1800 7961552 037 1613 042 1729 054 1836 065 1935 076 2029 088 2121 100 2207 113 2293 126
112 115 125 134 144 154 165 177 190
1950 8621672 045 1728 052 1836 064 1939 076 2034 088 2123 100 2209 113 2294 127
124 129 138 147 156 167 178 190
2100 9291792 056 1844 062 1947 076 2044 089 2135 102 2221 115 2302 128
138 142 151 161 170 181 192
2250 9951913 067 1962 075 2058 089 2150 103 2238 117 2321 131
152 157 167 177 186 196
2400 10612034 081 2080 088 2171 104 2258 119 2342 133
169 174 184 194 20
2550 11282155 095 2199 104 2285 120
187 192 20
2700 11942277 112 2319 121
21 21
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
19
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
TCB-2-13 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2971
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 353
Maximum bhp at a given rpm mdash (rpm1933)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
800 353828 008 1026 014 1379 030
38 56 104
1000 442934 011 1108 018 1418 035 1692 055
44 60 101 135
1200 5301048 016 1206 024 1479 042 1731 064 1961 087
58 72 101 130 165
1400 6191171 022 1313 031 1562 051 1784 073 2002 099 2201 126 2391 155
75 87 106 128 160 189 22
1600 707
1300 030 1424 040 1657 062 1865 086 2053 112 2247 141 2425 171 2596 203 2759 237
97 100 115 133 156 184 21 24 27
1800 7961431 039 1545 051 1759 075 1950 101 2134 129 2300 157 2472 189 2636 223 2790 258
114 113 125 144 160 181 21 24 26
2000 8841565 051 1669 063 1868 090 2050 118 2217 148 2381 178 2531 210 2683 244 2836 282
127 127 137 157 170 186 21 23 26
2200 9731700 064 1797 078 1979 107 2152 138 2312 169 2464 202 2612 236 2750 270 2883 306
142 145 156 169 183 198 21 23 26
2400 10611836 081 1928 096 2097 127 2260 160 2413 194 2556 228 2695 264 2831 301 2959 338
164 169 174 182 197 21 23 24 26
2600 11501975 100 2060 116 2219 150 2371 185 2517 221 2656 257 2785 295 2914 334
190 192 193 196 21 23 24 26
2800 12382115 122 2194 140 2343 175 2484 212 2626 251 2758 290 2885 330
21 21 21 22 23 24 26
3000 13272256 148 2329 166 2470 204 2605 243 2737 284 2864 325
24 24 24 24 25 26
3200 14152397 177 2464 196 2600 236 2728 278 2849 320
26 26 26 27 27
3400 15042539 210 2601 230 2731 272 2852 316 2969 361
29 29 30 30 30
3600 15922681 247 2739 267 2863 312
33 33 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
20
TCB-1-16 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2000
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 4384
Maximum bhp at a given rpm mdash (rpm1378)3
Max Motor Frame Size - 182T
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1000 308507 005 612 009 802 017
37 43 59
1250 385584 008 671 012 833 021 985 032
45 49 62 81
1500 462668 011 743 016 884 026 1016 038 1145 052
54 58 69 84 103
1750 540755 016 821 021 944 032 1065 045 1176 059 1289 075 1392 091
64 68 79 93 105 120 136
2000 617
844 022 904 028 1014 040 1119 054 1225 069 1322 085 1422 102 1517 120 1605 139
76 81 92 104 113 124 140 157 175
2250 694934 030 989 036 1090 049 1185 064 1278 080 1373 097 1460 115 1547 134 1635 154
89 94 107 114 123 133 146 161 179
2500 7711026 039 1077 047 1169 061 1257 076 1342 092 1425 110 1511 130 1591 149 1666 170
104 110 119 126 134 144 156 169 184
2750 8481118 051 1166 059 1252 074 1334 091 1411 107 1489 126 1564 146 1643 167 1717 188
121 124 131 138 147 157 168 181 194
3000 9251210 064 1256 073 1337 090 1412 107 1486 125 1556 144 1627 165 1695 186 1769 209
134 138 145 152 161 171 183 194 21
3250 10031303 080 1347 090 1423 108 1494 127 1563 146 1630 166 1695 186 1760 209 1823 232
149 153 161 169 177 187 199 21 22
3500 10801397 098 1438 109 1511 128 1578 148 1642 169 1706 190 1768 211 1828 233 1889 258
166 170 179 187 195 21 22 23 24
3750 11571491 119 1530 130 1599 152 1663 173 1725 194 1784 216 1844 239 1900 262 1956 286
185 189 197 21 22 23 24 25 27
4000 12341585 143 1622 155 1689 178 1750 200 1809 223 1865 246 1921 270 1976 295
20 21 22 23 24 25 26 28
4250 13111680 170 1714 183 1779 207 1838 231 1893 255 1948 280 1999 304
23 23 24 25 26 28 29
4500 13881775 200 1807 214 1869 240 1926 265 1979 291
25 26 27 28 30
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
21
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
TCB-2-16 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2431
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 432
Maximum bhp at a given rpm mdash (rpm1406)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1200 370668 011 842 020 1137 041
46 61 104
1500 462749 015 899 025 1166 049 1395 077
55 68 102 138
1800 555843 021 969 033 1208 059 1424 089 1616 121
71 77 104 135 168
2100 648944 030 1053 042 1268 071 1461 103 1647 138 1813 175 1972 215
83 88 111 134 166 196 22
2400 740
1047 040 1144 054 1336 085 1518 120 1684 157 1847 197 1996 238 2140 283 2275 329
99 105 120 140 166 195 22 25 27
2700 8331152 053 1243 068 1412 101 1579 139 1739 179 1885 221 2033 266 2169 312 2297 359
116 122 132 150 171 195 22 25 28
3000 9251260 069 1345 086 1498 121 1651 161 1799 204 1941 248 2070 295 2206 344 2333 394
132 136 144 162 182 20 23 25 28
3300 10181373 089 1448 107 1588 144 1727 186 1866 231 2001 279 2129 328 2247 379 2370 432
147 151 161 177 195 22 24 26 29
3600 11111486 112 1553 131 1686 171 1813 215 1939 262 2065 312 2188 365 2306 418 2416 473
166 171 182 193 21 23 25 28 30
3900 12031600 140 1658 159 1786 202 1900 247 2020 297 2138 349 2252 404 2366 461
189 194 20 21 23 25 27 29
4200 12961715 172 1766 191 1888 238 1996 285 2106 336 2213 390 2324 448 2430 508
21 21 22 23 24 26 29 31
4500 13881831 208 1878 228 1990 277 2095 328 2193 380 2298 437 2398 496
23 23 24 25 27 28 31
4800 14811946 250 1992 271 2094 322 2196 376 2289 430 2385 488
25 26 27 28 29 31
5100 15742062 296 2105 319 2199 371 2297 429 2388 486
28 28 29 30 32
5400 16662179 349 2219 373 2305 426 2399 487
30 31 32 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
22
TCB-1-18 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1645
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 4843
Maximum bhp at a given rpm mdash (rpm1147)3
Max Motor Frame Size - 182T
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg
0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1500 298486 008 568 012 724 023
43 49 62
1800 357552 011 623 016 755 028 883 042
54 57 67 81
2100 417622 016 683 021 799 034 911 048 1022 065 1123 082
67 68 77 85 99 116
2400 477693 021 749 028 852 041 950 056 1048 073 1147 092 1238 112 1322 133
80 81 90 95 103 120 135 148
2700 536
765 029 817 036 911 050 1001 066 1088 084 1174 103 1262 124 1346 146 1424 169
91 94 103 105 113 125 138 150 164
3000 596838 037 887 045 972 061 1056 078 1136 097 1214 117 1292 138 1369 161 1448 185
102 106 111 115 122 133 142 153 166
3300 656912 048 957 057 1038 074 1115 092 1187 111 1261 132 1331 154 1403 177 1472 202
112 114 120 126 133 141 149 158 168
3600 715987 061 1029 070 1105 089 1176 108 1246 128 1312 149 1379 172 1443 196 1510 222
121 125 131 138 145 152 160 168 178
3900 7751063 075 1102 085 1174 106 1239 126 1305 147 1368 170 1430 193 1491 218 1549 244
133 137 143 149 157 165 173 181 189
4200 8341139 092 1175 103 1244 125 1307 147 1366 169 1428 193 1485 217 1542 243 1599 269
146 149 155 163 171 179 187 195 20
4500 8941215 112 1249 124 1315 147 1375 170 1430 193 1488 218 1544 244 1597 270
160 162 169 176 185 194 20 21
4800 9541292 134 1323 147 1386 172 1444 197 1498 221 1549 246 1604 273
171 174 181 190 199 21 22
5100 10131369 159 1399 172 1458 199 1513 226 1565 252 1615 278
184 187 195 20 21 23
5400 10731446 188 1474 201 1530 229 1584 258 1634 285
197 20 21 22 23
5700 11331523 219 1550 233 1603 263
21 22 22
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1032
10
Electrical Accessories
Belt Guard (TCB only) Belt guards are totally enclosed to provide protection
from rotating pulleys and belts Belt guards meet
OSHA guidelines
Motor Cover (Weatherhood) Weatherproof motor covers shield the motor and
drive components from dust dirt and moisture when
used in outdoor applications Motor covers also
provide protection from rotating pulleys and belts and
meet OSHA guidelines Motor covers are standard on
TCBRU and TCBRS models
Inlet and Outlet Companion Flanges
(TCB only) Companion inlet flanges and outlet flanges with
prepunched holes are available for all fan sizes in
painted steel construction
Inlet and Outlet Guards (TCB TCBRU)
Removable inlet and outlet guards provide protectionfor personnel and equipment in non-ducted
installations These guards meet OSHA guidelines
TCBRU fans are available with outlet screens to
shield the fan discharge and damper from debris
Inspection Door Bolted or hinged doors provide access for cleaning or
inspection
Inspection Section (TCB only) Inspection sections serve as a length of duct that can
be easily removed to provide for complete access to
the fan for servicing Each section includes a bolted
inspection door
Isolators (TCB only) Both base mount or hanging isolators are available in
either neoprene or spring mounts The isolators are
furnished in sets of four and are sized to match the
weight of each fan
Mounting Rails (TCB only) Mounting rails are required for horizontal mounting
of TCB fans when the motor is to be located in
the 3 or 9 orsquoclock position Mounting rails are also
recommended for all vertically mounted inline fans
See page 5 for additional details
Protective Coatings Greenheck has a wide offering of protective coatings
Consult Greenheckrsquos Product Application Guide
FA110-04R4 Performance Coatings for Ventilation
Products for a complete listing of coatings and a
relative resistance chart
Inlet Vane Dampers (TCB only) Nested inlet vane dampers for controlling air volume
are available on model TCB inline fans with Level 2
steel construction in fan sizes 12 through 36
Birdscreen Insect Screen (TCBRS only)
TCBRS fans are available with either aluminum insectscreen or birdscreen at the hood intake (Birdscreen is
standard)
Roof Curbs (TCBRU TCBRS) Prefabricated roof curbs are available to reduce
installation time and costs by ensuring compatibility
between the fan the curb and the roof opening
All curbs are lined with fiberglass insulation to
prevent condensation and reduce sound levels See
Greenheckrsquos Roof Curb Extensions and Equipment
Supports catalog for complete details
Washable Aluminum Filters (TCBRS only)
Helps trap dust and dirt before it enters the fanFilters can be removed for cleaning
Enclosure Application Toggle Heavy Duty
NEMA-1 Indoor General Purpose Yes Yes
NEMA-12 Indoor DustDrip Tight Yes YesNEMA-3R IndoorOutdoor Rainproof Yes Yes
NEMA-4 IndoorOutdoor Watertight Yes Yes
NEMA-4X IndoorOutdoor Watertight
(Corrosion Resistant) Yes Yes
NEMA-7 amp 9 Indoor Hazardous Locations Yes No
Toggle type and heavy duty disconnect switches are available for positive
electrical shut-off and safety in servicing fans The following switches are
available to meet individual electrical requirements
Accessories
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1132
11
Inspection
Section
Outlet Guard
Belt Guard
Motor Cover
Companion Flange
(Outlet)NeopreneIsolator
Spring Base
Isolator
Inspection
Door
Easy Access
Inlet Guard
CompanionFlange (Inlet)
Mounting Rails
Spring HangingIsolator
Isolator Neoprene Hanging
Accessories (Model TCB shown)
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
12
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
360 195846 002 999 003 1260 006
53 60 75
420 228941 003 1071 004 1314 007 1526 011
57 63 77 92
480 2601040 004 1155 005 1380 009 1576 012 1758 017
63 68 80 93 106
540 2931144 005 1245 006 1449 010 1635 014 1807 019 1968 023 2115 028
71 74 84 95 107 120 133
600 326
1250 006 1341 008 1523 012 1704 016 1865 021 2017 026 2163 031 2298 036
78 81 88 99 110 122 135 147
660 3581357 007 1439 009 1606 014 1774 018 1930 023 2074 029 2212 034 2346 040 2472 046
86 88 93 104 114 126 137 149 162
720 3911465 009 1542 011 1692 016 1845 021 1999 026 2137 032 2270 038 2395 043 2520 050
94 96 100 109 120 131 140 150 163
780 4231576 012 1647 014 1786 018 1928 024 2069 029 2206 035 2331 041 2454 047 2570 054
102 104 108 115 127 136 145 154 165
840 4561688 014 1752 016 1882 021 2012 027 2142 033 2276 039 2400 045 2515 052 2629 059
110 112 117 123 133 142 150 160 170
900 4891801 017 1859 019 1980 025 2100 030 2225 036 2347 043 2469 050 2584 056
120 122 127 133 139 148 157 166
960 5211914 020 1966 023 2081 028 2195 034 2310 040 2424 047 2540 054
130 132 140 142 147 154 164
1020 5542028 024 2075 026 2184 032 2292 038 2395 044 2507 052 2612 059
144 149 150 151 155 163 172
1080 5862141 028 2186 031 2288 037 2389 043 2490 050 2592 057
159 159 160 162 166 172
1140 6192255 033 2298 036 2394 042 2487 049 2585 055
169 169 171 174 178
1200 6522370 038 2410 041 2500 047 2590 054
179 180 183 186
TCB-1-09 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2645
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm3114)3
Max Motor Frame Size - 56
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
13
TCB-2-09 Level 2 Construction
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3330)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg
025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
400 2171198 005 1460 008 1893 018
73 87 119
480 2601332 006 1566 010 1971 020 2309 032
82 96 127 157
560 3041480 009 1686 013 2059 024 2386 036 2671 049
92 106 135 165 191
640 3471635 011 1818 016 2158 027 2469 041 2749 055 3000 070 3228 086
106 117 146 174 20 23 25
720 3911799 015 1958 020 2275 032 2562 045 2830 061 3078 077 3305 094 3514 112
120 130 158 183 21 23 25 28
800 4341966 020 2108 025 2397 037 2666 051 2921 067 3158 085 3383 103 3591 121 3786 141
134 145 169 183 22 24 26 28 31
880 4782135 025 2262 030 2528 043 2784 058 3015 074 3250 093 3464 112 3669 132 3863 152
151 162 182 21 23 25 27 29 32
960 5212308 032 2425 037 2665 050 2905 066 3132 083 3343 101 3555 121 3752 142 3942 164
168 176 196 22 24 26 28 31 33
1040 5652482 039 2590 045 2810 059 3033 075 3251 093 3453 111 3648 131 3844 153 4027 176
184 193 21 23 25 27 29 32 34
1120 6082658 048 2757 054 2960 068 3168 085 3372 103 3571 123 3754 143 3937 165
20 21 23 25 27 29 31 33
1200 6522835 058 2925 065 3113 079 3306 096 3501 115 3691 135 3872 157 4041 179
22 23 24 26 28 30 32 35
1280 6953012 070 3095 076 3271 091 3453 109 3636 128 3813 149 3991 171
24 25 26 28 29 32 34
1360 7393190 083 3269 090 3434 105 3603 123 3773 143 3945 164
26 26 28 29 31 34
1440 7823368 097 3444 105 3599 121 3756 139 3917 159
28 28 30 31 33
1520 8263547 114 3619 121 3765 138 3909 156
30 30 32 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
14
TCB-1-10 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2555
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm2760)3
Max Motor Frame Size - 143T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
480 260858 003 1011 005 1253 009
49 57 73
560 304947 004 1089 006 1321 011 1511 015
55 63 77 93
640 3471042 005 1171 008 1394 013 1578 018 1740 023 1892 029
63 70 82 96 112 133
720 3911141 007 1259 009 1470 015 1649 021 1806 027 1949 033 2079 039
72 76 89 100 115 132 150
800 4341239 009 1349 012 1548 018 1723 024 1876 031 2015 037 2144 044 2263 051
80 84 96 107 119 135 148 161
880 4781340 011 1444 014 1630 021 1798 027 1949 034 2084 042 2211 049 2329 057 2440 064
88 92 102 113 125 137 150 162 176
960 5211441 014 1541 017 1716 024 1876 031 2023 039 2157 047 2280 055 2396 063 2506 071
97 101 109 121 133 141 152 165 179
1040 5651544 017 1640 021 1805 028 1957 035 2099 044 2231 052 2352 060 2465 069
105 109 117 129 139 148 157 169
1120 6081648 021 1739 025 1895 032 2042 040 2178 049 2306 058 2426 067 2538 076
113 117 127 138 146 155 165 177
1200 6521752 025 1839 029 1989 037 2129 046 2259 055 2383 064 2501 073
122 126 137 145 153 163 175
1280 6951858 030 1940 034 2085 043 2218 052 2343 061 2464 071
132 137 145 152 162 173
1360 7391964 035 2041 040 2183 049 2308 058 2430 068 2545 078
145 149 154 162 172 183
1440 7822071 041 2144 046 2282 056 2401 066 2519 076
156 158 164 173 183
1520 8262177 048 2247 053 2380 064 2497 074
164 167 175 184
1600 8692285 056 2351 061 2479 072
173 177 185
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
15
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-10 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3120)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 3261300 007 1504 011 1875 021 2213 032
73 82 105 132
700 3801453 010 1630 014 1966 024 2273 036 2560 049
84 91 110 133 156
800 4341611 013 1768 018 2070 029 2355 042 2619 055 2872 070 3102 086
100 101 118 137 158 182 20
900 4891773 017 1917 023 2188 034 2448 048 2698 062 2932 078 3160 094 3371 111 3568 129
112 113 127 143 162 185 20 22 25
1000 543
1937 023 2071 029 2319 041 2559 055 2790 070 3011 086 3220 103 3430 122 3626 140
124 127 136 152 170 190 21 23 25
1100 5972104 029 2228 035 2457 048 2677 063 2892 079 3103 096 3303 114 3490 132 3685 152
138 143 146 161 179 195 21 23 25
1200 6522276 036 2389 043 2601 057 2807 073 3009 089 3199 107 3394 125 3578 145 3751 165
154 154 159 172 189 20 21 23 25
1300 7062449 045 2552 052 2753 067 2944 083 3128 101 3315 119 3488 138 3670 159 3841 180
164 166 172 183 195 21 22 24 25
1400 7602623 055 2717 062 2907 079 3083 095 3261 114 3433 133 3603 153 3763 173 3933 196
175 177 185 193 20 21 23 24 26
1500 8152797 066 2883 074 3063 092 3231 109 3398 128 3557 148 3721 169 3878 191 4026 212
186 189 197 20 21 22 23 25 26
1600 8692973 079 3052 087 3223 106 3384 125 3537 144 3693 165 3840 186 3995 209
198 20 21 21 22 23 24 25
1700 9233149 094 3224 103 3384 122 3538 142 3683 162 3831 184 3974 206
21 21 22 22 23 23 25
1800 9783325 110 3396 119 3546 140 3693 161 3834 182 3970 204
22 22 23 23 24 24
1900 10323502 129 3570 138 3710 159 3852 182 3988 204
23 24 24 25 25
2000 10863679 149 3744 159 3875 181 4012 204
25 25 25 26
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
16
TCB-1-12 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2490
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 3436
Maximum bhp at a given rpm mdash (rpm2202)3
Max Motor Frame Size - 145T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 0075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
700 380853 006 958 008 1158 014 1345 021 1518 028
62 66 79 94 110
800 434943 008 1042 011 1218 017 1386 024 1551 031 1703 040
66 70 83 96 111 125
900 4891037 010 1128 013 1287 020 1442 027 1587 035 1736 044 1873 053 2000 063
71 76 87 99 112 126 142 155
1000 5431132 013 1216 017 1363 024 1506 031 1643 040 1771 049 1906 059 2033 069 2151 079
78 83 91 103 115 128 143 156 170
1100 597
1229 016 1305 020 1447 028 1574 036 1702 045 1827 055 1943 065 2066 075 2183 086
86 89 96 108 120 133 144 157 171
1200 6521326 020 1398 025 1532 034 1649 042 1769 051 1884 061 1999 071 2105 082 2216 094
92 95 103 113 126 139 149 159 173
1300 7061426 025 1492 030 1619 039 1732 049 1839 058 1950 068 2055 079 2161 090 2260 102
98 102 112 121 134 145 154 164 176
1400 7601526 031 1588 036 1707 046 1817 056 1916 066 2019 076 2120 088 2217 099 2316 111
106 112 122 132 142 151 160 170 181
1500 8151627 037 1684 042 1796 053 1903 064 1999 075 2089 085 2188 097 2281 109 2372 121
119 125 135 144 149 157 167 176 187
1600 8691729 044 1781 050 1886 061 1990 073 2084 085 2170 096 2258 107 2350 120 2436 133
134 139 150 153 157 165 174 183 194
1700 9231830 053 1879 058 1980 070 2077 083 2170 095 2254 107 2334 119 2419 132
151 157 159 162 167 173 181 191
1800 9781932 062 1978 068 2074 080 2166 093 2256 107 2339 120 2417 132
166 166 168 171 176 182 190
1900 10322034 072 2078 078 2169 091 2256 105 2343 119 2425 133
173 173 176 180 185 192
2000 10862137 083 2179 090 2265 103 2348 118 2432 133
180 181 184 189 195
2100 11412240 096 2280 102 2361 117 2442 132
187 188 192 198
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
17
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-12 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 3274
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 321
Maximum bhp at a given rpm mdash (rpm2315)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
750 4071009 008 1226 014 1587 027
55 67 98
900 4891119 011 1315 018 1648 032 1936 049 2182 067
63 76 102 131 159
1050 5701238 015 1419 023 1728 039 1995 056 2240 076 2456 096
75 85 110 136 164 190
1200 6521363 020 1529 029 1813 046 2070 065 2299 085 2514 108 2710 131 2890 155
89 96 120 142 169 195 22 24
1350 733
1495 027 1643 036 1911 055 2151 076 2372 097 2574 120 2768 145 2948 171 3115 197
104 111 132 152 176 20 22 25 28
1500 8151630 034 1764 044 2018 066 2240 088 2452 111 2647 135 2828 160 3007 187 3174 216
120 129 145 166 186 21 23 26 29
1650 8961767 044 1887 054 2127 077 2338 101 2534 126 2727 151 2903 178 3067 205 3233 235
139 144 159 184 199 22 24 27 30
1800 9781908 055 2018 066 2239 090 2445 117 2630 143 2808 170 2983 198 3145 227
159 165 180 199 22 23 25 28
1950 10592053 068 2151 079 2356 105 2554 134 2731 162 2900 190 3064 220 3225 250
182 188 20 22 23 25 27 29
2100 11412198 083 2286 095 2477 122 2664 152 2839 183 2997 213 3154 244
21 22 22 23 25 27 29
2250 12222344 100 2423 113 2599 141 2777 173 2948 205 3104 238 3250 271
24 24 25 26 27 29 32
2400 13042490 119 2560 133 2726 163 2896 196 3058 230 3212 265
26 26 27 28 30 32
2550 13852637 141 2703 156 2858 187 3016 221 3169 257
28 29 29 31 32
2700 14672785 166 2847 181 2991 214 3138 248
31 31 32 34
2850 15482933 193 2992 209 3126 243 3262 279
34 34 35 37
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
18
TCB-1-13 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2355
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 3435
Maximum bhp at a given rpm mdash (rpm2119)3
Max Motor Frame Size - 145T
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 265660 003 792 005 1019 010
41 51 69
750 331760 005 874 007 1073 013 1254 019
48 58 71 84
900 398864 007 967 010 1146 016 1305 023 1459 030
58 64 75 86 102
1050 464973 009 1067 013 1230 020 1378 027 1512 036 1646 044 1770 053
66 70 80 91 103 120 140
1200 530
1085 013 1171 017 1321 024 1457 032 1585 041 1703 051 1820 061 1933 071 2039 081
72 77 86 96 108 120 136 153 172
1350 5971199 017 1277 022 1419 030 1545 039 1662 048 1777 058 1883 069 1984 080 2089 091
81 85 94 103 114 125 136 151 167
1500 6631316 023 1387 027 1520 037 1637 046 1749 059 1853 067 1957 078 2054 090 2146 102
90 94 102 112 122 132 143 155 169
1650 7301434 029 1499 034 1623 044 1736 055 1839 065 1940 077 2034 088 2128 100 2219 113
100 104 113 123 132 143 153 165 178
1800 7961552 037 1613 042 1729 054 1836 065 1935 076 2029 088 2121 100 2207 113 2293 126
112 115 125 134 144 154 165 177 190
1950 8621672 045 1728 052 1836 064 1939 076 2034 088 2123 100 2209 113 2294 127
124 129 138 147 156 167 178 190
2100 9291792 056 1844 062 1947 076 2044 089 2135 102 2221 115 2302 128
138 142 151 161 170 181 192
2250 9951913 067 1962 075 2058 089 2150 103 2238 117 2321 131
152 157 167 177 186 196
2400 10612034 081 2080 088 2171 104 2258 119 2342 133
169 174 184 194 20
2550 11282155 095 2199 104 2285 120
187 192 20
2700 11942277 112 2319 121
21 21
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
19
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
TCB-2-13 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2971
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 353
Maximum bhp at a given rpm mdash (rpm1933)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
800 353828 008 1026 014 1379 030
38 56 104
1000 442934 011 1108 018 1418 035 1692 055
44 60 101 135
1200 5301048 016 1206 024 1479 042 1731 064 1961 087
58 72 101 130 165
1400 6191171 022 1313 031 1562 051 1784 073 2002 099 2201 126 2391 155
75 87 106 128 160 189 22
1600 707
1300 030 1424 040 1657 062 1865 086 2053 112 2247 141 2425 171 2596 203 2759 237
97 100 115 133 156 184 21 24 27
1800 7961431 039 1545 051 1759 075 1950 101 2134 129 2300 157 2472 189 2636 223 2790 258
114 113 125 144 160 181 21 24 26
2000 8841565 051 1669 063 1868 090 2050 118 2217 148 2381 178 2531 210 2683 244 2836 282
127 127 137 157 170 186 21 23 26
2200 9731700 064 1797 078 1979 107 2152 138 2312 169 2464 202 2612 236 2750 270 2883 306
142 145 156 169 183 198 21 23 26
2400 10611836 081 1928 096 2097 127 2260 160 2413 194 2556 228 2695 264 2831 301 2959 338
164 169 174 182 197 21 23 24 26
2600 11501975 100 2060 116 2219 150 2371 185 2517 221 2656 257 2785 295 2914 334
190 192 193 196 21 23 24 26
2800 12382115 122 2194 140 2343 175 2484 212 2626 251 2758 290 2885 330
21 21 21 22 23 24 26
3000 13272256 148 2329 166 2470 204 2605 243 2737 284 2864 325
24 24 24 24 25 26
3200 14152397 177 2464 196 2600 236 2728 278 2849 320
26 26 26 27 27
3400 15042539 210 2601 230 2731 272 2852 316 2969 361
29 29 30 30 30
3600 15922681 247 2739 267 2863 312
33 33 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
20
TCB-1-16 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2000
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 4384
Maximum bhp at a given rpm mdash (rpm1378)3
Max Motor Frame Size - 182T
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1000 308507 005 612 009 802 017
37 43 59
1250 385584 008 671 012 833 021 985 032
45 49 62 81
1500 462668 011 743 016 884 026 1016 038 1145 052
54 58 69 84 103
1750 540755 016 821 021 944 032 1065 045 1176 059 1289 075 1392 091
64 68 79 93 105 120 136
2000 617
844 022 904 028 1014 040 1119 054 1225 069 1322 085 1422 102 1517 120 1605 139
76 81 92 104 113 124 140 157 175
2250 694934 030 989 036 1090 049 1185 064 1278 080 1373 097 1460 115 1547 134 1635 154
89 94 107 114 123 133 146 161 179
2500 7711026 039 1077 047 1169 061 1257 076 1342 092 1425 110 1511 130 1591 149 1666 170
104 110 119 126 134 144 156 169 184
2750 8481118 051 1166 059 1252 074 1334 091 1411 107 1489 126 1564 146 1643 167 1717 188
121 124 131 138 147 157 168 181 194
3000 9251210 064 1256 073 1337 090 1412 107 1486 125 1556 144 1627 165 1695 186 1769 209
134 138 145 152 161 171 183 194 21
3250 10031303 080 1347 090 1423 108 1494 127 1563 146 1630 166 1695 186 1760 209 1823 232
149 153 161 169 177 187 199 21 22
3500 10801397 098 1438 109 1511 128 1578 148 1642 169 1706 190 1768 211 1828 233 1889 258
166 170 179 187 195 21 22 23 24
3750 11571491 119 1530 130 1599 152 1663 173 1725 194 1784 216 1844 239 1900 262 1956 286
185 189 197 21 22 23 24 25 27
4000 12341585 143 1622 155 1689 178 1750 200 1809 223 1865 246 1921 270 1976 295
20 21 22 23 24 25 26 28
4250 13111680 170 1714 183 1779 207 1838 231 1893 255 1948 280 1999 304
23 23 24 25 26 28 29
4500 13881775 200 1807 214 1869 240 1926 265 1979 291
25 26 27 28 30
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
21
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
TCB-2-16 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2431
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 432
Maximum bhp at a given rpm mdash (rpm1406)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1200 370668 011 842 020 1137 041
46 61 104
1500 462749 015 899 025 1166 049 1395 077
55 68 102 138
1800 555843 021 969 033 1208 059 1424 089 1616 121
71 77 104 135 168
2100 648944 030 1053 042 1268 071 1461 103 1647 138 1813 175 1972 215
83 88 111 134 166 196 22
2400 740
1047 040 1144 054 1336 085 1518 120 1684 157 1847 197 1996 238 2140 283 2275 329
99 105 120 140 166 195 22 25 27
2700 8331152 053 1243 068 1412 101 1579 139 1739 179 1885 221 2033 266 2169 312 2297 359
116 122 132 150 171 195 22 25 28
3000 9251260 069 1345 086 1498 121 1651 161 1799 204 1941 248 2070 295 2206 344 2333 394
132 136 144 162 182 20 23 25 28
3300 10181373 089 1448 107 1588 144 1727 186 1866 231 2001 279 2129 328 2247 379 2370 432
147 151 161 177 195 22 24 26 29
3600 11111486 112 1553 131 1686 171 1813 215 1939 262 2065 312 2188 365 2306 418 2416 473
166 171 182 193 21 23 25 28 30
3900 12031600 140 1658 159 1786 202 1900 247 2020 297 2138 349 2252 404 2366 461
189 194 20 21 23 25 27 29
4200 12961715 172 1766 191 1888 238 1996 285 2106 336 2213 390 2324 448 2430 508
21 21 22 23 24 26 29 31
4500 13881831 208 1878 228 1990 277 2095 328 2193 380 2298 437 2398 496
23 23 24 25 27 28 31
4800 14811946 250 1992 271 2094 322 2196 376 2289 430 2385 488
25 26 27 28 29 31
5100 15742062 296 2105 319 2199 371 2297 429 2388 486
28 28 29 30 32
5400 16662179 349 2219 373 2305 426 2399 487
30 31 32 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
22
TCB-1-18 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1645
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 4843
Maximum bhp at a given rpm mdash (rpm1147)3
Max Motor Frame Size - 182T
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg
0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1500 298486 008 568 012 724 023
43 49 62
1800 357552 011 623 016 755 028 883 042
54 57 67 81
2100 417622 016 683 021 799 034 911 048 1022 065 1123 082
67 68 77 85 99 116
2400 477693 021 749 028 852 041 950 056 1048 073 1147 092 1238 112 1322 133
80 81 90 95 103 120 135 148
2700 536
765 029 817 036 911 050 1001 066 1088 084 1174 103 1262 124 1346 146 1424 169
91 94 103 105 113 125 138 150 164
3000 596838 037 887 045 972 061 1056 078 1136 097 1214 117 1292 138 1369 161 1448 185
102 106 111 115 122 133 142 153 166
3300 656912 048 957 057 1038 074 1115 092 1187 111 1261 132 1331 154 1403 177 1472 202
112 114 120 126 133 141 149 158 168
3600 715987 061 1029 070 1105 089 1176 108 1246 128 1312 149 1379 172 1443 196 1510 222
121 125 131 138 145 152 160 168 178
3900 7751063 075 1102 085 1174 106 1239 126 1305 147 1368 170 1430 193 1491 218 1549 244
133 137 143 149 157 165 173 181 189
4200 8341139 092 1175 103 1244 125 1307 147 1366 169 1428 193 1485 217 1542 243 1599 269
146 149 155 163 171 179 187 195 20
4500 8941215 112 1249 124 1315 147 1375 170 1430 193 1488 218 1544 244 1597 270
160 162 169 176 185 194 20 21
4800 9541292 134 1323 147 1386 172 1444 197 1498 221 1549 246 1604 273
171 174 181 190 199 21 22
5100 10131369 159 1399 172 1458 199 1513 226 1565 252 1615 278
184 187 195 20 21 23
5400 10731446 188 1474 201 1530 229 1584 258 1634 285
197 20 21 22 23
5700 11331523 219 1550 233 1603 263
21 22 22
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1132
11
Inspection
Section
Outlet Guard
Belt Guard
Motor Cover
Companion Flange
(Outlet)NeopreneIsolator
Spring Base
Isolator
Inspection
Door
Easy Access
Inlet Guard
CompanionFlange (Inlet)
Mounting Rails
Spring HangingIsolator
Isolator Neoprene Hanging
Accessories (Model TCB shown)
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
12
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
360 195846 002 999 003 1260 006
53 60 75
420 228941 003 1071 004 1314 007 1526 011
57 63 77 92
480 2601040 004 1155 005 1380 009 1576 012 1758 017
63 68 80 93 106
540 2931144 005 1245 006 1449 010 1635 014 1807 019 1968 023 2115 028
71 74 84 95 107 120 133
600 326
1250 006 1341 008 1523 012 1704 016 1865 021 2017 026 2163 031 2298 036
78 81 88 99 110 122 135 147
660 3581357 007 1439 009 1606 014 1774 018 1930 023 2074 029 2212 034 2346 040 2472 046
86 88 93 104 114 126 137 149 162
720 3911465 009 1542 011 1692 016 1845 021 1999 026 2137 032 2270 038 2395 043 2520 050
94 96 100 109 120 131 140 150 163
780 4231576 012 1647 014 1786 018 1928 024 2069 029 2206 035 2331 041 2454 047 2570 054
102 104 108 115 127 136 145 154 165
840 4561688 014 1752 016 1882 021 2012 027 2142 033 2276 039 2400 045 2515 052 2629 059
110 112 117 123 133 142 150 160 170
900 4891801 017 1859 019 1980 025 2100 030 2225 036 2347 043 2469 050 2584 056
120 122 127 133 139 148 157 166
960 5211914 020 1966 023 2081 028 2195 034 2310 040 2424 047 2540 054
130 132 140 142 147 154 164
1020 5542028 024 2075 026 2184 032 2292 038 2395 044 2507 052 2612 059
144 149 150 151 155 163 172
1080 5862141 028 2186 031 2288 037 2389 043 2490 050 2592 057
159 159 160 162 166 172
1140 6192255 033 2298 036 2394 042 2487 049 2585 055
169 169 171 174 178
1200 6522370 038 2410 041 2500 047 2590 054
179 180 183 186
TCB-1-09 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2645
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm3114)3
Max Motor Frame Size - 56
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
13
TCB-2-09 Level 2 Construction
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3330)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg
025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
400 2171198 005 1460 008 1893 018
73 87 119
480 2601332 006 1566 010 1971 020 2309 032
82 96 127 157
560 3041480 009 1686 013 2059 024 2386 036 2671 049
92 106 135 165 191
640 3471635 011 1818 016 2158 027 2469 041 2749 055 3000 070 3228 086
106 117 146 174 20 23 25
720 3911799 015 1958 020 2275 032 2562 045 2830 061 3078 077 3305 094 3514 112
120 130 158 183 21 23 25 28
800 4341966 020 2108 025 2397 037 2666 051 2921 067 3158 085 3383 103 3591 121 3786 141
134 145 169 183 22 24 26 28 31
880 4782135 025 2262 030 2528 043 2784 058 3015 074 3250 093 3464 112 3669 132 3863 152
151 162 182 21 23 25 27 29 32
960 5212308 032 2425 037 2665 050 2905 066 3132 083 3343 101 3555 121 3752 142 3942 164
168 176 196 22 24 26 28 31 33
1040 5652482 039 2590 045 2810 059 3033 075 3251 093 3453 111 3648 131 3844 153 4027 176
184 193 21 23 25 27 29 32 34
1120 6082658 048 2757 054 2960 068 3168 085 3372 103 3571 123 3754 143 3937 165
20 21 23 25 27 29 31 33
1200 6522835 058 2925 065 3113 079 3306 096 3501 115 3691 135 3872 157 4041 179
22 23 24 26 28 30 32 35
1280 6953012 070 3095 076 3271 091 3453 109 3636 128 3813 149 3991 171
24 25 26 28 29 32 34
1360 7393190 083 3269 090 3434 105 3603 123 3773 143 3945 164
26 26 28 29 31 34
1440 7823368 097 3444 105 3599 121 3756 139 3917 159
28 28 30 31 33
1520 8263547 114 3619 121 3765 138 3909 156
30 30 32 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
14
TCB-1-10 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2555
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm2760)3
Max Motor Frame Size - 143T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
480 260858 003 1011 005 1253 009
49 57 73
560 304947 004 1089 006 1321 011 1511 015
55 63 77 93
640 3471042 005 1171 008 1394 013 1578 018 1740 023 1892 029
63 70 82 96 112 133
720 3911141 007 1259 009 1470 015 1649 021 1806 027 1949 033 2079 039
72 76 89 100 115 132 150
800 4341239 009 1349 012 1548 018 1723 024 1876 031 2015 037 2144 044 2263 051
80 84 96 107 119 135 148 161
880 4781340 011 1444 014 1630 021 1798 027 1949 034 2084 042 2211 049 2329 057 2440 064
88 92 102 113 125 137 150 162 176
960 5211441 014 1541 017 1716 024 1876 031 2023 039 2157 047 2280 055 2396 063 2506 071
97 101 109 121 133 141 152 165 179
1040 5651544 017 1640 021 1805 028 1957 035 2099 044 2231 052 2352 060 2465 069
105 109 117 129 139 148 157 169
1120 6081648 021 1739 025 1895 032 2042 040 2178 049 2306 058 2426 067 2538 076
113 117 127 138 146 155 165 177
1200 6521752 025 1839 029 1989 037 2129 046 2259 055 2383 064 2501 073
122 126 137 145 153 163 175
1280 6951858 030 1940 034 2085 043 2218 052 2343 061 2464 071
132 137 145 152 162 173
1360 7391964 035 2041 040 2183 049 2308 058 2430 068 2545 078
145 149 154 162 172 183
1440 7822071 041 2144 046 2282 056 2401 066 2519 076
156 158 164 173 183
1520 8262177 048 2247 053 2380 064 2497 074
164 167 175 184
1600 8692285 056 2351 061 2479 072
173 177 185
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
15
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-10 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3120)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 3261300 007 1504 011 1875 021 2213 032
73 82 105 132
700 3801453 010 1630 014 1966 024 2273 036 2560 049
84 91 110 133 156
800 4341611 013 1768 018 2070 029 2355 042 2619 055 2872 070 3102 086
100 101 118 137 158 182 20
900 4891773 017 1917 023 2188 034 2448 048 2698 062 2932 078 3160 094 3371 111 3568 129
112 113 127 143 162 185 20 22 25
1000 543
1937 023 2071 029 2319 041 2559 055 2790 070 3011 086 3220 103 3430 122 3626 140
124 127 136 152 170 190 21 23 25
1100 5972104 029 2228 035 2457 048 2677 063 2892 079 3103 096 3303 114 3490 132 3685 152
138 143 146 161 179 195 21 23 25
1200 6522276 036 2389 043 2601 057 2807 073 3009 089 3199 107 3394 125 3578 145 3751 165
154 154 159 172 189 20 21 23 25
1300 7062449 045 2552 052 2753 067 2944 083 3128 101 3315 119 3488 138 3670 159 3841 180
164 166 172 183 195 21 22 24 25
1400 7602623 055 2717 062 2907 079 3083 095 3261 114 3433 133 3603 153 3763 173 3933 196
175 177 185 193 20 21 23 24 26
1500 8152797 066 2883 074 3063 092 3231 109 3398 128 3557 148 3721 169 3878 191 4026 212
186 189 197 20 21 22 23 25 26
1600 8692973 079 3052 087 3223 106 3384 125 3537 144 3693 165 3840 186 3995 209
198 20 21 21 22 23 24 25
1700 9233149 094 3224 103 3384 122 3538 142 3683 162 3831 184 3974 206
21 21 22 22 23 23 25
1800 9783325 110 3396 119 3546 140 3693 161 3834 182 3970 204
22 22 23 23 24 24
1900 10323502 129 3570 138 3710 159 3852 182 3988 204
23 24 24 25 25
2000 10863679 149 3744 159 3875 181 4012 204
25 25 25 26
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
16
TCB-1-12 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2490
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 3436
Maximum bhp at a given rpm mdash (rpm2202)3
Max Motor Frame Size - 145T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 0075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
700 380853 006 958 008 1158 014 1345 021 1518 028
62 66 79 94 110
800 434943 008 1042 011 1218 017 1386 024 1551 031 1703 040
66 70 83 96 111 125
900 4891037 010 1128 013 1287 020 1442 027 1587 035 1736 044 1873 053 2000 063
71 76 87 99 112 126 142 155
1000 5431132 013 1216 017 1363 024 1506 031 1643 040 1771 049 1906 059 2033 069 2151 079
78 83 91 103 115 128 143 156 170
1100 597
1229 016 1305 020 1447 028 1574 036 1702 045 1827 055 1943 065 2066 075 2183 086
86 89 96 108 120 133 144 157 171
1200 6521326 020 1398 025 1532 034 1649 042 1769 051 1884 061 1999 071 2105 082 2216 094
92 95 103 113 126 139 149 159 173
1300 7061426 025 1492 030 1619 039 1732 049 1839 058 1950 068 2055 079 2161 090 2260 102
98 102 112 121 134 145 154 164 176
1400 7601526 031 1588 036 1707 046 1817 056 1916 066 2019 076 2120 088 2217 099 2316 111
106 112 122 132 142 151 160 170 181
1500 8151627 037 1684 042 1796 053 1903 064 1999 075 2089 085 2188 097 2281 109 2372 121
119 125 135 144 149 157 167 176 187
1600 8691729 044 1781 050 1886 061 1990 073 2084 085 2170 096 2258 107 2350 120 2436 133
134 139 150 153 157 165 174 183 194
1700 9231830 053 1879 058 1980 070 2077 083 2170 095 2254 107 2334 119 2419 132
151 157 159 162 167 173 181 191
1800 9781932 062 1978 068 2074 080 2166 093 2256 107 2339 120 2417 132
166 166 168 171 176 182 190
1900 10322034 072 2078 078 2169 091 2256 105 2343 119 2425 133
173 173 176 180 185 192
2000 10862137 083 2179 090 2265 103 2348 118 2432 133
180 181 184 189 195
2100 11412240 096 2280 102 2361 117 2442 132
187 188 192 198
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
17
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-12 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 3274
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 321
Maximum bhp at a given rpm mdash (rpm2315)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
750 4071009 008 1226 014 1587 027
55 67 98
900 4891119 011 1315 018 1648 032 1936 049 2182 067
63 76 102 131 159
1050 5701238 015 1419 023 1728 039 1995 056 2240 076 2456 096
75 85 110 136 164 190
1200 6521363 020 1529 029 1813 046 2070 065 2299 085 2514 108 2710 131 2890 155
89 96 120 142 169 195 22 24
1350 733
1495 027 1643 036 1911 055 2151 076 2372 097 2574 120 2768 145 2948 171 3115 197
104 111 132 152 176 20 22 25 28
1500 8151630 034 1764 044 2018 066 2240 088 2452 111 2647 135 2828 160 3007 187 3174 216
120 129 145 166 186 21 23 26 29
1650 8961767 044 1887 054 2127 077 2338 101 2534 126 2727 151 2903 178 3067 205 3233 235
139 144 159 184 199 22 24 27 30
1800 9781908 055 2018 066 2239 090 2445 117 2630 143 2808 170 2983 198 3145 227
159 165 180 199 22 23 25 28
1950 10592053 068 2151 079 2356 105 2554 134 2731 162 2900 190 3064 220 3225 250
182 188 20 22 23 25 27 29
2100 11412198 083 2286 095 2477 122 2664 152 2839 183 2997 213 3154 244
21 22 22 23 25 27 29
2250 12222344 100 2423 113 2599 141 2777 173 2948 205 3104 238 3250 271
24 24 25 26 27 29 32
2400 13042490 119 2560 133 2726 163 2896 196 3058 230 3212 265
26 26 27 28 30 32
2550 13852637 141 2703 156 2858 187 3016 221 3169 257
28 29 29 31 32
2700 14672785 166 2847 181 2991 214 3138 248
31 31 32 34
2850 15482933 193 2992 209 3126 243 3262 279
34 34 35 37
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
18
TCB-1-13 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2355
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 3435
Maximum bhp at a given rpm mdash (rpm2119)3
Max Motor Frame Size - 145T
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 265660 003 792 005 1019 010
41 51 69
750 331760 005 874 007 1073 013 1254 019
48 58 71 84
900 398864 007 967 010 1146 016 1305 023 1459 030
58 64 75 86 102
1050 464973 009 1067 013 1230 020 1378 027 1512 036 1646 044 1770 053
66 70 80 91 103 120 140
1200 530
1085 013 1171 017 1321 024 1457 032 1585 041 1703 051 1820 061 1933 071 2039 081
72 77 86 96 108 120 136 153 172
1350 5971199 017 1277 022 1419 030 1545 039 1662 048 1777 058 1883 069 1984 080 2089 091
81 85 94 103 114 125 136 151 167
1500 6631316 023 1387 027 1520 037 1637 046 1749 059 1853 067 1957 078 2054 090 2146 102
90 94 102 112 122 132 143 155 169
1650 7301434 029 1499 034 1623 044 1736 055 1839 065 1940 077 2034 088 2128 100 2219 113
100 104 113 123 132 143 153 165 178
1800 7961552 037 1613 042 1729 054 1836 065 1935 076 2029 088 2121 100 2207 113 2293 126
112 115 125 134 144 154 165 177 190
1950 8621672 045 1728 052 1836 064 1939 076 2034 088 2123 100 2209 113 2294 127
124 129 138 147 156 167 178 190
2100 9291792 056 1844 062 1947 076 2044 089 2135 102 2221 115 2302 128
138 142 151 161 170 181 192
2250 9951913 067 1962 075 2058 089 2150 103 2238 117 2321 131
152 157 167 177 186 196
2400 10612034 081 2080 088 2171 104 2258 119 2342 133
169 174 184 194 20
2550 11282155 095 2199 104 2285 120
187 192 20
2700 11942277 112 2319 121
21 21
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
19
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
TCB-2-13 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2971
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 353
Maximum bhp at a given rpm mdash (rpm1933)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
800 353828 008 1026 014 1379 030
38 56 104
1000 442934 011 1108 018 1418 035 1692 055
44 60 101 135
1200 5301048 016 1206 024 1479 042 1731 064 1961 087
58 72 101 130 165
1400 6191171 022 1313 031 1562 051 1784 073 2002 099 2201 126 2391 155
75 87 106 128 160 189 22
1600 707
1300 030 1424 040 1657 062 1865 086 2053 112 2247 141 2425 171 2596 203 2759 237
97 100 115 133 156 184 21 24 27
1800 7961431 039 1545 051 1759 075 1950 101 2134 129 2300 157 2472 189 2636 223 2790 258
114 113 125 144 160 181 21 24 26
2000 8841565 051 1669 063 1868 090 2050 118 2217 148 2381 178 2531 210 2683 244 2836 282
127 127 137 157 170 186 21 23 26
2200 9731700 064 1797 078 1979 107 2152 138 2312 169 2464 202 2612 236 2750 270 2883 306
142 145 156 169 183 198 21 23 26
2400 10611836 081 1928 096 2097 127 2260 160 2413 194 2556 228 2695 264 2831 301 2959 338
164 169 174 182 197 21 23 24 26
2600 11501975 100 2060 116 2219 150 2371 185 2517 221 2656 257 2785 295 2914 334
190 192 193 196 21 23 24 26
2800 12382115 122 2194 140 2343 175 2484 212 2626 251 2758 290 2885 330
21 21 21 22 23 24 26
3000 13272256 148 2329 166 2470 204 2605 243 2737 284 2864 325
24 24 24 24 25 26
3200 14152397 177 2464 196 2600 236 2728 278 2849 320
26 26 26 27 27
3400 15042539 210 2601 230 2731 272 2852 316 2969 361
29 29 30 30 30
3600 15922681 247 2739 267 2863 312
33 33 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
20
TCB-1-16 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2000
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 4384
Maximum bhp at a given rpm mdash (rpm1378)3
Max Motor Frame Size - 182T
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1000 308507 005 612 009 802 017
37 43 59
1250 385584 008 671 012 833 021 985 032
45 49 62 81
1500 462668 011 743 016 884 026 1016 038 1145 052
54 58 69 84 103
1750 540755 016 821 021 944 032 1065 045 1176 059 1289 075 1392 091
64 68 79 93 105 120 136
2000 617
844 022 904 028 1014 040 1119 054 1225 069 1322 085 1422 102 1517 120 1605 139
76 81 92 104 113 124 140 157 175
2250 694934 030 989 036 1090 049 1185 064 1278 080 1373 097 1460 115 1547 134 1635 154
89 94 107 114 123 133 146 161 179
2500 7711026 039 1077 047 1169 061 1257 076 1342 092 1425 110 1511 130 1591 149 1666 170
104 110 119 126 134 144 156 169 184
2750 8481118 051 1166 059 1252 074 1334 091 1411 107 1489 126 1564 146 1643 167 1717 188
121 124 131 138 147 157 168 181 194
3000 9251210 064 1256 073 1337 090 1412 107 1486 125 1556 144 1627 165 1695 186 1769 209
134 138 145 152 161 171 183 194 21
3250 10031303 080 1347 090 1423 108 1494 127 1563 146 1630 166 1695 186 1760 209 1823 232
149 153 161 169 177 187 199 21 22
3500 10801397 098 1438 109 1511 128 1578 148 1642 169 1706 190 1768 211 1828 233 1889 258
166 170 179 187 195 21 22 23 24
3750 11571491 119 1530 130 1599 152 1663 173 1725 194 1784 216 1844 239 1900 262 1956 286
185 189 197 21 22 23 24 25 27
4000 12341585 143 1622 155 1689 178 1750 200 1809 223 1865 246 1921 270 1976 295
20 21 22 23 24 25 26 28
4250 13111680 170 1714 183 1779 207 1838 231 1893 255 1948 280 1999 304
23 23 24 25 26 28 29
4500 13881775 200 1807 214 1869 240 1926 265 1979 291
25 26 27 28 30
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
21
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
TCB-2-16 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2431
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 432
Maximum bhp at a given rpm mdash (rpm1406)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1200 370668 011 842 020 1137 041
46 61 104
1500 462749 015 899 025 1166 049 1395 077
55 68 102 138
1800 555843 021 969 033 1208 059 1424 089 1616 121
71 77 104 135 168
2100 648944 030 1053 042 1268 071 1461 103 1647 138 1813 175 1972 215
83 88 111 134 166 196 22
2400 740
1047 040 1144 054 1336 085 1518 120 1684 157 1847 197 1996 238 2140 283 2275 329
99 105 120 140 166 195 22 25 27
2700 8331152 053 1243 068 1412 101 1579 139 1739 179 1885 221 2033 266 2169 312 2297 359
116 122 132 150 171 195 22 25 28
3000 9251260 069 1345 086 1498 121 1651 161 1799 204 1941 248 2070 295 2206 344 2333 394
132 136 144 162 182 20 23 25 28
3300 10181373 089 1448 107 1588 144 1727 186 1866 231 2001 279 2129 328 2247 379 2370 432
147 151 161 177 195 22 24 26 29
3600 11111486 112 1553 131 1686 171 1813 215 1939 262 2065 312 2188 365 2306 418 2416 473
166 171 182 193 21 23 25 28 30
3900 12031600 140 1658 159 1786 202 1900 247 2020 297 2138 349 2252 404 2366 461
189 194 20 21 23 25 27 29
4200 12961715 172 1766 191 1888 238 1996 285 2106 336 2213 390 2324 448 2430 508
21 21 22 23 24 26 29 31
4500 13881831 208 1878 228 1990 277 2095 328 2193 380 2298 437 2398 496
23 23 24 25 27 28 31
4800 14811946 250 1992 271 2094 322 2196 376 2289 430 2385 488
25 26 27 28 29 31
5100 15742062 296 2105 319 2199 371 2297 429 2388 486
28 28 29 30 32
5400 16662179 349 2219 373 2305 426 2399 487
30 31 32 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
22
TCB-1-18 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1645
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 4843
Maximum bhp at a given rpm mdash (rpm1147)3
Max Motor Frame Size - 182T
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg
0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1500 298486 008 568 012 724 023
43 49 62
1800 357552 011 623 016 755 028 883 042
54 57 67 81
2100 417622 016 683 021 799 034 911 048 1022 065 1123 082
67 68 77 85 99 116
2400 477693 021 749 028 852 041 950 056 1048 073 1147 092 1238 112 1322 133
80 81 90 95 103 120 135 148
2700 536
765 029 817 036 911 050 1001 066 1088 084 1174 103 1262 124 1346 146 1424 169
91 94 103 105 113 125 138 150 164
3000 596838 037 887 045 972 061 1056 078 1136 097 1214 117 1292 138 1369 161 1448 185
102 106 111 115 122 133 142 153 166
3300 656912 048 957 057 1038 074 1115 092 1187 111 1261 132 1331 154 1403 177 1472 202
112 114 120 126 133 141 149 158 168
3600 715987 061 1029 070 1105 089 1176 108 1246 128 1312 149 1379 172 1443 196 1510 222
121 125 131 138 145 152 160 168 178
3900 7751063 075 1102 085 1174 106 1239 126 1305 147 1368 170 1430 193 1491 218 1549 244
133 137 143 149 157 165 173 181 189
4200 8341139 092 1175 103 1244 125 1307 147 1366 169 1428 193 1485 217 1542 243 1599 269
146 149 155 163 171 179 187 195 20
4500 8941215 112 1249 124 1315 147 1375 170 1430 193 1488 218 1544 244 1597 270
160 162 169 176 185 194 20 21
4800 9541292 134 1323 147 1386 172 1444 197 1498 221 1549 246 1604 273
171 174 181 190 199 21 22
5100 10131369 159 1399 172 1458 199 1513 226 1565 252 1615 278
184 187 195 20 21 23
5400 10731446 188 1474 201 1530 229 1584 258 1634 285
197 20 21 22 23
5700 11331523 219 1550 233 1603 263
21 22 22
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
12
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
360 195846 002 999 003 1260 006
53 60 75
420 228941 003 1071 004 1314 007 1526 011
57 63 77 92
480 2601040 004 1155 005 1380 009 1576 012 1758 017
63 68 80 93 106
540 2931144 005 1245 006 1449 010 1635 014 1807 019 1968 023 2115 028
71 74 84 95 107 120 133
600 326
1250 006 1341 008 1523 012 1704 016 1865 021 2017 026 2163 031 2298 036
78 81 88 99 110 122 135 147
660 3581357 007 1439 009 1606 014 1774 018 1930 023 2074 029 2212 034 2346 040 2472 046
86 88 93 104 114 126 137 149 162
720 3911465 009 1542 011 1692 016 1845 021 1999 026 2137 032 2270 038 2395 043 2520 050
94 96 100 109 120 131 140 150 163
780 4231576 012 1647 014 1786 018 1928 024 2069 029 2206 035 2331 041 2454 047 2570 054
102 104 108 115 127 136 145 154 165
840 4561688 014 1752 016 1882 021 2012 027 2142 033 2276 039 2400 045 2515 052 2629 059
110 112 117 123 133 142 150 160 170
900 4891801 017 1859 019 1980 025 2100 030 2225 036 2347 043 2469 050 2584 056
120 122 127 133 139 148 157 166
960 5211914 020 1966 023 2081 028 2195 034 2310 040 2424 047 2540 054
130 132 140 142 147 154 164
1020 5542028 024 2075 026 2184 032 2292 038 2395 044 2507 052 2612 059
144 149 150 151 155 163 172
1080 5862141 028 2186 031 2288 037 2389 043 2490 050 2592 057
159 159 160 162 166 172
1140 6192255 033 2298 036 2394 042 2487 049 2585 055
169 169 171 174 178
1200 6522370 038 2410 041 2500 047 2590 054
179 180 183 186
TCB-1-09 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2645
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm3114)3
Max Motor Frame Size - 56
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
13
TCB-2-09 Level 2 Construction
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3330)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg
025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
400 2171198 005 1460 008 1893 018
73 87 119
480 2601332 006 1566 010 1971 020 2309 032
82 96 127 157
560 3041480 009 1686 013 2059 024 2386 036 2671 049
92 106 135 165 191
640 3471635 011 1818 016 2158 027 2469 041 2749 055 3000 070 3228 086
106 117 146 174 20 23 25
720 3911799 015 1958 020 2275 032 2562 045 2830 061 3078 077 3305 094 3514 112
120 130 158 183 21 23 25 28
800 4341966 020 2108 025 2397 037 2666 051 2921 067 3158 085 3383 103 3591 121 3786 141
134 145 169 183 22 24 26 28 31
880 4782135 025 2262 030 2528 043 2784 058 3015 074 3250 093 3464 112 3669 132 3863 152
151 162 182 21 23 25 27 29 32
960 5212308 032 2425 037 2665 050 2905 066 3132 083 3343 101 3555 121 3752 142 3942 164
168 176 196 22 24 26 28 31 33
1040 5652482 039 2590 045 2810 059 3033 075 3251 093 3453 111 3648 131 3844 153 4027 176
184 193 21 23 25 27 29 32 34
1120 6082658 048 2757 054 2960 068 3168 085 3372 103 3571 123 3754 143 3937 165
20 21 23 25 27 29 31 33
1200 6522835 058 2925 065 3113 079 3306 096 3501 115 3691 135 3872 157 4041 179
22 23 24 26 28 30 32 35
1280 6953012 070 3095 076 3271 091 3453 109 3636 128 3813 149 3991 171
24 25 26 28 29 32 34
1360 7393190 083 3269 090 3434 105 3603 123 3773 143 3945 164
26 26 28 29 31 34
1440 7823368 097 3444 105 3599 121 3756 139 3917 159
28 28 30 31 33
1520 8263547 114 3619 121 3765 138 3909 156
30 30 32 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
14
TCB-1-10 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2555
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm2760)3
Max Motor Frame Size - 143T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
480 260858 003 1011 005 1253 009
49 57 73
560 304947 004 1089 006 1321 011 1511 015
55 63 77 93
640 3471042 005 1171 008 1394 013 1578 018 1740 023 1892 029
63 70 82 96 112 133
720 3911141 007 1259 009 1470 015 1649 021 1806 027 1949 033 2079 039
72 76 89 100 115 132 150
800 4341239 009 1349 012 1548 018 1723 024 1876 031 2015 037 2144 044 2263 051
80 84 96 107 119 135 148 161
880 4781340 011 1444 014 1630 021 1798 027 1949 034 2084 042 2211 049 2329 057 2440 064
88 92 102 113 125 137 150 162 176
960 5211441 014 1541 017 1716 024 1876 031 2023 039 2157 047 2280 055 2396 063 2506 071
97 101 109 121 133 141 152 165 179
1040 5651544 017 1640 021 1805 028 1957 035 2099 044 2231 052 2352 060 2465 069
105 109 117 129 139 148 157 169
1120 6081648 021 1739 025 1895 032 2042 040 2178 049 2306 058 2426 067 2538 076
113 117 127 138 146 155 165 177
1200 6521752 025 1839 029 1989 037 2129 046 2259 055 2383 064 2501 073
122 126 137 145 153 163 175
1280 6951858 030 1940 034 2085 043 2218 052 2343 061 2464 071
132 137 145 152 162 173
1360 7391964 035 2041 040 2183 049 2308 058 2430 068 2545 078
145 149 154 162 172 183
1440 7822071 041 2144 046 2282 056 2401 066 2519 076
156 158 164 173 183
1520 8262177 048 2247 053 2380 064 2497 074
164 167 175 184
1600 8692285 056 2351 061 2479 072
173 177 185
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
15
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-10 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3120)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 3261300 007 1504 011 1875 021 2213 032
73 82 105 132
700 3801453 010 1630 014 1966 024 2273 036 2560 049
84 91 110 133 156
800 4341611 013 1768 018 2070 029 2355 042 2619 055 2872 070 3102 086
100 101 118 137 158 182 20
900 4891773 017 1917 023 2188 034 2448 048 2698 062 2932 078 3160 094 3371 111 3568 129
112 113 127 143 162 185 20 22 25
1000 543
1937 023 2071 029 2319 041 2559 055 2790 070 3011 086 3220 103 3430 122 3626 140
124 127 136 152 170 190 21 23 25
1100 5972104 029 2228 035 2457 048 2677 063 2892 079 3103 096 3303 114 3490 132 3685 152
138 143 146 161 179 195 21 23 25
1200 6522276 036 2389 043 2601 057 2807 073 3009 089 3199 107 3394 125 3578 145 3751 165
154 154 159 172 189 20 21 23 25
1300 7062449 045 2552 052 2753 067 2944 083 3128 101 3315 119 3488 138 3670 159 3841 180
164 166 172 183 195 21 22 24 25
1400 7602623 055 2717 062 2907 079 3083 095 3261 114 3433 133 3603 153 3763 173 3933 196
175 177 185 193 20 21 23 24 26
1500 8152797 066 2883 074 3063 092 3231 109 3398 128 3557 148 3721 169 3878 191 4026 212
186 189 197 20 21 22 23 25 26
1600 8692973 079 3052 087 3223 106 3384 125 3537 144 3693 165 3840 186 3995 209
198 20 21 21 22 23 24 25
1700 9233149 094 3224 103 3384 122 3538 142 3683 162 3831 184 3974 206
21 21 22 22 23 23 25
1800 9783325 110 3396 119 3546 140 3693 161 3834 182 3970 204
22 22 23 23 24 24
1900 10323502 129 3570 138 3710 159 3852 182 3988 204
23 24 24 25 25
2000 10863679 149 3744 159 3875 181 4012 204
25 25 25 26
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
16
TCB-1-12 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2490
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 3436
Maximum bhp at a given rpm mdash (rpm2202)3
Max Motor Frame Size - 145T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 0075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
700 380853 006 958 008 1158 014 1345 021 1518 028
62 66 79 94 110
800 434943 008 1042 011 1218 017 1386 024 1551 031 1703 040
66 70 83 96 111 125
900 4891037 010 1128 013 1287 020 1442 027 1587 035 1736 044 1873 053 2000 063
71 76 87 99 112 126 142 155
1000 5431132 013 1216 017 1363 024 1506 031 1643 040 1771 049 1906 059 2033 069 2151 079
78 83 91 103 115 128 143 156 170
1100 597
1229 016 1305 020 1447 028 1574 036 1702 045 1827 055 1943 065 2066 075 2183 086
86 89 96 108 120 133 144 157 171
1200 6521326 020 1398 025 1532 034 1649 042 1769 051 1884 061 1999 071 2105 082 2216 094
92 95 103 113 126 139 149 159 173
1300 7061426 025 1492 030 1619 039 1732 049 1839 058 1950 068 2055 079 2161 090 2260 102
98 102 112 121 134 145 154 164 176
1400 7601526 031 1588 036 1707 046 1817 056 1916 066 2019 076 2120 088 2217 099 2316 111
106 112 122 132 142 151 160 170 181
1500 8151627 037 1684 042 1796 053 1903 064 1999 075 2089 085 2188 097 2281 109 2372 121
119 125 135 144 149 157 167 176 187
1600 8691729 044 1781 050 1886 061 1990 073 2084 085 2170 096 2258 107 2350 120 2436 133
134 139 150 153 157 165 174 183 194
1700 9231830 053 1879 058 1980 070 2077 083 2170 095 2254 107 2334 119 2419 132
151 157 159 162 167 173 181 191
1800 9781932 062 1978 068 2074 080 2166 093 2256 107 2339 120 2417 132
166 166 168 171 176 182 190
1900 10322034 072 2078 078 2169 091 2256 105 2343 119 2425 133
173 173 176 180 185 192
2000 10862137 083 2179 090 2265 103 2348 118 2432 133
180 181 184 189 195
2100 11412240 096 2280 102 2361 117 2442 132
187 188 192 198
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
17
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-12 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 3274
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 321
Maximum bhp at a given rpm mdash (rpm2315)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
750 4071009 008 1226 014 1587 027
55 67 98
900 4891119 011 1315 018 1648 032 1936 049 2182 067
63 76 102 131 159
1050 5701238 015 1419 023 1728 039 1995 056 2240 076 2456 096
75 85 110 136 164 190
1200 6521363 020 1529 029 1813 046 2070 065 2299 085 2514 108 2710 131 2890 155
89 96 120 142 169 195 22 24
1350 733
1495 027 1643 036 1911 055 2151 076 2372 097 2574 120 2768 145 2948 171 3115 197
104 111 132 152 176 20 22 25 28
1500 8151630 034 1764 044 2018 066 2240 088 2452 111 2647 135 2828 160 3007 187 3174 216
120 129 145 166 186 21 23 26 29
1650 8961767 044 1887 054 2127 077 2338 101 2534 126 2727 151 2903 178 3067 205 3233 235
139 144 159 184 199 22 24 27 30
1800 9781908 055 2018 066 2239 090 2445 117 2630 143 2808 170 2983 198 3145 227
159 165 180 199 22 23 25 28
1950 10592053 068 2151 079 2356 105 2554 134 2731 162 2900 190 3064 220 3225 250
182 188 20 22 23 25 27 29
2100 11412198 083 2286 095 2477 122 2664 152 2839 183 2997 213 3154 244
21 22 22 23 25 27 29
2250 12222344 100 2423 113 2599 141 2777 173 2948 205 3104 238 3250 271
24 24 25 26 27 29 32
2400 13042490 119 2560 133 2726 163 2896 196 3058 230 3212 265
26 26 27 28 30 32
2550 13852637 141 2703 156 2858 187 3016 221 3169 257
28 29 29 31 32
2700 14672785 166 2847 181 2991 214 3138 248
31 31 32 34
2850 15482933 193 2992 209 3126 243 3262 279
34 34 35 37
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
18
TCB-1-13 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2355
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 3435
Maximum bhp at a given rpm mdash (rpm2119)3
Max Motor Frame Size - 145T
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 265660 003 792 005 1019 010
41 51 69
750 331760 005 874 007 1073 013 1254 019
48 58 71 84
900 398864 007 967 010 1146 016 1305 023 1459 030
58 64 75 86 102
1050 464973 009 1067 013 1230 020 1378 027 1512 036 1646 044 1770 053
66 70 80 91 103 120 140
1200 530
1085 013 1171 017 1321 024 1457 032 1585 041 1703 051 1820 061 1933 071 2039 081
72 77 86 96 108 120 136 153 172
1350 5971199 017 1277 022 1419 030 1545 039 1662 048 1777 058 1883 069 1984 080 2089 091
81 85 94 103 114 125 136 151 167
1500 6631316 023 1387 027 1520 037 1637 046 1749 059 1853 067 1957 078 2054 090 2146 102
90 94 102 112 122 132 143 155 169
1650 7301434 029 1499 034 1623 044 1736 055 1839 065 1940 077 2034 088 2128 100 2219 113
100 104 113 123 132 143 153 165 178
1800 7961552 037 1613 042 1729 054 1836 065 1935 076 2029 088 2121 100 2207 113 2293 126
112 115 125 134 144 154 165 177 190
1950 8621672 045 1728 052 1836 064 1939 076 2034 088 2123 100 2209 113 2294 127
124 129 138 147 156 167 178 190
2100 9291792 056 1844 062 1947 076 2044 089 2135 102 2221 115 2302 128
138 142 151 161 170 181 192
2250 9951913 067 1962 075 2058 089 2150 103 2238 117 2321 131
152 157 167 177 186 196
2400 10612034 081 2080 088 2171 104 2258 119 2342 133
169 174 184 194 20
2550 11282155 095 2199 104 2285 120
187 192 20
2700 11942277 112 2319 121
21 21
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
19
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
TCB-2-13 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2971
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 353
Maximum bhp at a given rpm mdash (rpm1933)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
800 353828 008 1026 014 1379 030
38 56 104
1000 442934 011 1108 018 1418 035 1692 055
44 60 101 135
1200 5301048 016 1206 024 1479 042 1731 064 1961 087
58 72 101 130 165
1400 6191171 022 1313 031 1562 051 1784 073 2002 099 2201 126 2391 155
75 87 106 128 160 189 22
1600 707
1300 030 1424 040 1657 062 1865 086 2053 112 2247 141 2425 171 2596 203 2759 237
97 100 115 133 156 184 21 24 27
1800 7961431 039 1545 051 1759 075 1950 101 2134 129 2300 157 2472 189 2636 223 2790 258
114 113 125 144 160 181 21 24 26
2000 8841565 051 1669 063 1868 090 2050 118 2217 148 2381 178 2531 210 2683 244 2836 282
127 127 137 157 170 186 21 23 26
2200 9731700 064 1797 078 1979 107 2152 138 2312 169 2464 202 2612 236 2750 270 2883 306
142 145 156 169 183 198 21 23 26
2400 10611836 081 1928 096 2097 127 2260 160 2413 194 2556 228 2695 264 2831 301 2959 338
164 169 174 182 197 21 23 24 26
2600 11501975 100 2060 116 2219 150 2371 185 2517 221 2656 257 2785 295 2914 334
190 192 193 196 21 23 24 26
2800 12382115 122 2194 140 2343 175 2484 212 2626 251 2758 290 2885 330
21 21 21 22 23 24 26
3000 13272256 148 2329 166 2470 204 2605 243 2737 284 2864 325
24 24 24 24 25 26
3200 14152397 177 2464 196 2600 236 2728 278 2849 320
26 26 26 27 27
3400 15042539 210 2601 230 2731 272 2852 316 2969 361
29 29 30 30 30
3600 15922681 247 2739 267 2863 312
33 33 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
20
TCB-1-16 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2000
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 4384
Maximum bhp at a given rpm mdash (rpm1378)3
Max Motor Frame Size - 182T
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1000 308507 005 612 009 802 017
37 43 59
1250 385584 008 671 012 833 021 985 032
45 49 62 81
1500 462668 011 743 016 884 026 1016 038 1145 052
54 58 69 84 103
1750 540755 016 821 021 944 032 1065 045 1176 059 1289 075 1392 091
64 68 79 93 105 120 136
2000 617
844 022 904 028 1014 040 1119 054 1225 069 1322 085 1422 102 1517 120 1605 139
76 81 92 104 113 124 140 157 175
2250 694934 030 989 036 1090 049 1185 064 1278 080 1373 097 1460 115 1547 134 1635 154
89 94 107 114 123 133 146 161 179
2500 7711026 039 1077 047 1169 061 1257 076 1342 092 1425 110 1511 130 1591 149 1666 170
104 110 119 126 134 144 156 169 184
2750 8481118 051 1166 059 1252 074 1334 091 1411 107 1489 126 1564 146 1643 167 1717 188
121 124 131 138 147 157 168 181 194
3000 9251210 064 1256 073 1337 090 1412 107 1486 125 1556 144 1627 165 1695 186 1769 209
134 138 145 152 161 171 183 194 21
3250 10031303 080 1347 090 1423 108 1494 127 1563 146 1630 166 1695 186 1760 209 1823 232
149 153 161 169 177 187 199 21 22
3500 10801397 098 1438 109 1511 128 1578 148 1642 169 1706 190 1768 211 1828 233 1889 258
166 170 179 187 195 21 22 23 24
3750 11571491 119 1530 130 1599 152 1663 173 1725 194 1784 216 1844 239 1900 262 1956 286
185 189 197 21 22 23 24 25 27
4000 12341585 143 1622 155 1689 178 1750 200 1809 223 1865 246 1921 270 1976 295
20 21 22 23 24 25 26 28
4250 13111680 170 1714 183 1779 207 1838 231 1893 255 1948 280 1999 304
23 23 24 25 26 28 29
4500 13881775 200 1807 214 1869 240 1926 265 1979 291
25 26 27 28 30
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
21
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
TCB-2-16 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2431
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 432
Maximum bhp at a given rpm mdash (rpm1406)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1200 370668 011 842 020 1137 041
46 61 104
1500 462749 015 899 025 1166 049 1395 077
55 68 102 138
1800 555843 021 969 033 1208 059 1424 089 1616 121
71 77 104 135 168
2100 648944 030 1053 042 1268 071 1461 103 1647 138 1813 175 1972 215
83 88 111 134 166 196 22
2400 740
1047 040 1144 054 1336 085 1518 120 1684 157 1847 197 1996 238 2140 283 2275 329
99 105 120 140 166 195 22 25 27
2700 8331152 053 1243 068 1412 101 1579 139 1739 179 1885 221 2033 266 2169 312 2297 359
116 122 132 150 171 195 22 25 28
3000 9251260 069 1345 086 1498 121 1651 161 1799 204 1941 248 2070 295 2206 344 2333 394
132 136 144 162 182 20 23 25 28
3300 10181373 089 1448 107 1588 144 1727 186 1866 231 2001 279 2129 328 2247 379 2370 432
147 151 161 177 195 22 24 26 29
3600 11111486 112 1553 131 1686 171 1813 215 1939 262 2065 312 2188 365 2306 418 2416 473
166 171 182 193 21 23 25 28 30
3900 12031600 140 1658 159 1786 202 1900 247 2020 297 2138 349 2252 404 2366 461
189 194 20 21 23 25 27 29
4200 12961715 172 1766 191 1888 238 1996 285 2106 336 2213 390 2324 448 2430 508
21 21 22 23 24 26 29 31
4500 13881831 208 1878 228 1990 277 2095 328 2193 380 2298 437 2398 496
23 23 24 25 27 28 31
4800 14811946 250 1992 271 2094 322 2196 376 2289 430 2385 488
25 26 27 28 29 31
5100 15742062 296 2105 319 2199 371 2297 429 2388 486
28 28 29 30 32
5400 16662179 349 2219 373 2305 426 2399 487
30 31 32 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
22
TCB-1-18 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1645
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 4843
Maximum bhp at a given rpm mdash (rpm1147)3
Max Motor Frame Size - 182T
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg
0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1500 298486 008 568 012 724 023
43 49 62
1800 357552 011 623 016 755 028 883 042
54 57 67 81
2100 417622 016 683 021 799 034 911 048 1022 065 1123 082
67 68 77 85 99 116
2400 477693 021 749 028 852 041 950 056 1048 073 1147 092 1238 112 1322 133
80 81 90 95 103 120 135 148
2700 536
765 029 817 036 911 050 1001 066 1088 084 1174 103 1262 124 1346 146 1424 169
91 94 103 105 113 125 138 150 164
3000 596838 037 887 045 972 061 1056 078 1136 097 1214 117 1292 138 1369 161 1448 185
102 106 111 115 122 133 142 153 166
3300 656912 048 957 057 1038 074 1115 092 1187 111 1261 132 1331 154 1403 177 1472 202
112 114 120 126 133 141 149 158 168
3600 715987 061 1029 070 1105 089 1176 108 1246 128 1312 149 1379 172 1443 196 1510 222
121 125 131 138 145 152 160 168 178
3900 7751063 075 1102 085 1174 106 1239 126 1305 147 1368 170 1430 193 1491 218 1549 244
133 137 143 149 157 165 173 181 189
4200 8341139 092 1175 103 1244 125 1307 147 1366 169 1428 193 1485 217 1542 243 1599 269
146 149 155 163 171 179 187 195 20
4500 8941215 112 1249 124 1315 147 1375 170 1430 193 1488 218 1544 244 1597 270
160 162 169 176 185 194 20 21
4800 9541292 134 1323 147 1386 172 1444 197 1498 221 1549 246 1604 273
171 174 181 190 199 21 22
5100 10131369 159 1399 172 1458 199 1513 226 1565 252 1615 278
184 187 195 20 21 23
5400 10731446 188 1474 201 1530 229 1584 258 1634 285
197 20 21 22 23
5700 11331523 219 1550 233 1603 263
21 22 22
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
13
TCB-2-09 Level 2 Construction
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3330)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg
025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
400 2171198 005 1460 008 1893 018
73 87 119
480 2601332 006 1566 010 1971 020 2309 032
82 96 127 157
560 3041480 009 1686 013 2059 024 2386 036 2671 049
92 106 135 165 191
640 3471635 011 1818 016 2158 027 2469 041 2749 055 3000 070 3228 086
106 117 146 174 20 23 25
720 3911799 015 1958 020 2275 032 2562 045 2830 061 3078 077 3305 094 3514 112
120 130 158 183 21 23 25 28
800 4341966 020 2108 025 2397 037 2666 051 2921 067 3158 085 3383 103 3591 121 3786 141
134 145 169 183 22 24 26 28 31
880 4782135 025 2262 030 2528 043 2784 058 3015 074 3250 093 3464 112 3669 132 3863 152
151 162 182 21 23 25 27 29 32
960 5212308 032 2425 037 2665 050 2905 066 3132 083 3343 101 3555 121 3752 142 3942 164
168 176 196 22 24 26 28 31 33
1040 5652482 039 2590 045 2810 059 3033 075 3251 093 3453 111 3648 131 3844 153 4027 176
184 193 21 23 25 27 29 32 34
1120 6082658 048 2757 054 2960 068 3168 085 3372 103 3571 123 3754 143 3937 165
20 21 23 25 27 29 31 33
1200 6522835 058 2925 065 3113 079 3306 096 3501 115 3691 135 3872 157 4041 179
22 23 24 26 28 30 32 35
1280 6953012 070 3095 076 3271 091 3453 109 3636 128 3813 149 3991 171
24 25 26 28 29 32 34
1360 7393190 083 3269 090 3434 105 3603 123 3773 143 3945 164
26 26 28 29 31 34
1440 7823368 097 3444 105 3599 121 3756 139 3917 159
28 28 30 31 33
1520 8263547 114 3619 121 3765 138 3909 156
30 30 32 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
14
TCB-1-10 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2555
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm2760)3
Max Motor Frame Size - 143T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
480 260858 003 1011 005 1253 009
49 57 73
560 304947 004 1089 006 1321 011 1511 015
55 63 77 93
640 3471042 005 1171 008 1394 013 1578 018 1740 023 1892 029
63 70 82 96 112 133
720 3911141 007 1259 009 1470 015 1649 021 1806 027 1949 033 2079 039
72 76 89 100 115 132 150
800 4341239 009 1349 012 1548 018 1723 024 1876 031 2015 037 2144 044 2263 051
80 84 96 107 119 135 148 161
880 4781340 011 1444 014 1630 021 1798 027 1949 034 2084 042 2211 049 2329 057 2440 064
88 92 102 113 125 137 150 162 176
960 5211441 014 1541 017 1716 024 1876 031 2023 039 2157 047 2280 055 2396 063 2506 071
97 101 109 121 133 141 152 165 179
1040 5651544 017 1640 021 1805 028 1957 035 2099 044 2231 052 2352 060 2465 069
105 109 117 129 139 148 157 169
1120 6081648 021 1739 025 1895 032 2042 040 2178 049 2306 058 2426 067 2538 076
113 117 127 138 146 155 165 177
1200 6521752 025 1839 029 1989 037 2129 046 2259 055 2383 064 2501 073
122 126 137 145 153 163 175
1280 6951858 030 1940 034 2085 043 2218 052 2343 061 2464 071
132 137 145 152 162 173
1360 7391964 035 2041 040 2183 049 2308 058 2430 068 2545 078
145 149 154 162 172 183
1440 7822071 041 2144 046 2282 056 2401 066 2519 076
156 158 164 173 183
1520 8262177 048 2247 053 2380 064 2497 074
164 167 175 184
1600 8692285 056 2351 061 2479 072
173 177 185
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
15
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-10 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3120)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 3261300 007 1504 011 1875 021 2213 032
73 82 105 132
700 3801453 010 1630 014 1966 024 2273 036 2560 049
84 91 110 133 156
800 4341611 013 1768 018 2070 029 2355 042 2619 055 2872 070 3102 086
100 101 118 137 158 182 20
900 4891773 017 1917 023 2188 034 2448 048 2698 062 2932 078 3160 094 3371 111 3568 129
112 113 127 143 162 185 20 22 25
1000 543
1937 023 2071 029 2319 041 2559 055 2790 070 3011 086 3220 103 3430 122 3626 140
124 127 136 152 170 190 21 23 25
1100 5972104 029 2228 035 2457 048 2677 063 2892 079 3103 096 3303 114 3490 132 3685 152
138 143 146 161 179 195 21 23 25
1200 6522276 036 2389 043 2601 057 2807 073 3009 089 3199 107 3394 125 3578 145 3751 165
154 154 159 172 189 20 21 23 25
1300 7062449 045 2552 052 2753 067 2944 083 3128 101 3315 119 3488 138 3670 159 3841 180
164 166 172 183 195 21 22 24 25
1400 7602623 055 2717 062 2907 079 3083 095 3261 114 3433 133 3603 153 3763 173 3933 196
175 177 185 193 20 21 23 24 26
1500 8152797 066 2883 074 3063 092 3231 109 3398 128 3557 148 3721 169 3878 191 4026 212
186 189 197 20 21 22 23 25 26
1600 8692973 079 3052 087 3223 106 3384 125 3537 144 3693 165 3840 186 3995 209
198 20 21 21 22 23 24 25
1700 9233149 094 3224 103 3384 122 3538 142 3683 162 3831 184 3974 206
21 21 22 22 23 23 25
1800 9783325 110 3396 119 3546 140 3693 161 3834 182 3970 204
22 22 23 23 24 24
1900 10323502 129 3570 138 3710 159 3852 182 3988 204
23 24 24 25 25
2000 10863679 149 3744 159 3875 181 4012 204
25 25 25 26
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
16
TCB-1-12 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2490
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 3436
Maximum bhp at a given rpm mdash (rpm2202)3
Max Motor Frame Size - 145T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 0075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
700 380853 006 958 008 1158 014 1345 021 1518 028
62 66 79 94 110
800 434943 008 1042 011 1218 017 1386 024 1551 031 1703 040
66 70 83 96 111 125
900 4891037 010 1128 013 1287 020 1442 027 1587 035 1736 044 1873 053 2000 063
71 76 87 99 112 126 142 155
1000 5431132 013 1216 017 1363 024 1506 031 1643 040 1771 049 1906 059 2033 069 2151 079
78 83 91 103 115 128 143 156 170
1100 597
1229 016 1305 020 1447 028 1574 036 1702 045 1827 055 1943 065 2066 075 2183 086
86 89 96 108 120 133 144 157 171
1200 6521326 020 1398 025 1532 034 1649 042 1769 051 1884 061 1999 071 2105 082 2216 094
92 95 103 113 126 139 149 159 173
1300 7061426 025 1492 030 1619 039 1732 049 1839 058 1950 068 2055 079 2161 090 2260 102
98 102 112 121 134 145 154 164 176
1400 7601526 031 1588 036 1707 046 1817 056 1916 066 2019 076 2120 088 2217 099 2316 111
106 112 122 132 142 151 160 170 181
1500 8151627 037 1684 042 1796 053 1903 064 1999 075 2089 085 2188 097 2281 109 2372 121
119 125 135 144 149 157 167 176 187
1600 8691729 044 1781 050 1886 061 1990 073 2084 085 2170 096 2258 107 2350 120 2436 133
134 139 150 153 157 165 174 183 194
1700 9231830 053 1879 058 1980 070 2077 083 2170 095 2254 107 2334 119 2419 132
151 157 159 162 167 173 181 191
1800 9781932 062 1978 068 2074 080 2166 093 2256 107 2339 120 2417 132
166 166 168 171 176 182 190
1900 10322034 072 2078 078 2169 091 2256 105 2343 119 2425 133
173 173 176 180 185 192
2000 10862137 083 2179 090 2265 103 2348 118 2432 133
180 181 184 189 195
2100 11412240 096 2280 102 2361 117 2442 132
187 188 192 198
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
17
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-12 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 3274
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 321
Maximum bhp at a given rpm mdash (rpm2315)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
750 4071009 008 1226 014 1587 027
55 67 98
900 4891119 011 1315 018 1648 032 1936 049 2182 067
63 76 102 131 159
1050 5701238 015 1419 023 1728 039 1995 056 2240 076 2456 096
75 85 110 136 164 190
1200 6521363 020 1529 029 1813 046 2070 065 2299 085 2514 108 2710 131 2890 155
89 96 120 142 169 195 22 24
1350 733
1495 027 1643 036 1911 055 2151 076 2372 097 2574 120 2768 145 2948 171 3115 197
104 111 132 152 176 20 22 25 28
1500 8151630 034 1764 044 2018 066 2240 088 2452 111 2647 135 2828 160 3007 187 3174 216
120 129 145 166 186 21 23 26 29
1650 8961767 044 1887 054 2127 077 2338 101 2534 126 2727 151 2903 178 3067 205 3233 235
139 144 159 184 199 22 24 27 30
1800 9781908 055 2018 066 2239 090 2445 117 2630 143 2808 170 2983 198 3145 227
159 165 180 199 22 23 25 28
1950 10592053 068 2151 079 2356 105 2554 134 2731 162 2900 190 3064 220 3225 250
182 188 20 22 23 25 27 29
2100 11412198 083 2286 095 2477 122 2664 152 2839 183 2997 213 3154 244
21 22 22 23 25 27 29
2250 12222344 100 2423 113 2599 141 2777 173 2948 205 3104 238 3250 271
24 24 25 26 27 29 32
2400 13042490 119 2560 133 2726 163 2896 196 3058 230 3212 265
26 26 27 28 30 32
2550 13852637 141 2703 156 2858 187 3016 221 3169 257
28 29 29 31 32
2700 14672785 166 2847 181 2991 214 3138 248
31 31 32 34
2850 15482933 193 2992 209 3126 243 3262 279
34 34 35 37
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
18
TCB-1-13 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2355
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 3435
Maximum bhp at a given rpm mdash (rpm2119)3
Max Motor Frame Size - 145T
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 265660 003 792 005 1019 010
41 51 69
750 331760 005 874 007 1073 013 1254 019
48 58 71 84
900 398864 007 967 010 1146 016 1305 023 1459 030
58 64 75 86 102
1050 464973 009 1067 013 1230 020 1378 027 1512 036 1646 044 1770 053
66 70 80 91 103 120 140
1200 530
1085 013 1171 017 1321 024 1457 032 1585 041 1703 051 1820 061 1933 071 2039 081
72 77 86 96 108 120 136 153 172
1350 5971199 017 1277 022 1419 030 1545 039 1662 048 1777 058 1883 069 1984 080 2089 091
81 85 94 103 114 125 136 151 167
1500 6631316 023 1387 027 1520 037 1637 046 1749 059 1853 067 1957 078 2054 090 2146 102
90 94 102 112 122 132 143 155 169
1650 7301434 029 1499 034 1623 044 1736 055 1839 065 1940 077 2034 088 2128 100 2219 113
100 104 113 123 132 143 153 165 178
1800 7961552 037 1613 042 1729 054 1836 065 1935 076 2029 088 2121 100 2207 113 2293 126
112 115 125 134 144 154 165 177 190
1950 8621672 045 1728 052 1836 064 1939 076 2034 088 2123 100 2209 113 2294 127
124 129 138 147 156 167 178 190
2100 9291792 056 1844 062 1947 076 2044 089 2135 102 2221 115 2302 128
138 142 151 161 170 181 192
2250 9951913 067 1962 075 2058 089 2150 103 2238 117 2321 131
152 157 167 177 186 196
2400 10612034 081 2080 088 2171 104 2258 119 2342 133
169 174 184 194 20
2550 11282155 095 2199 104 2285 120
187 192 20
2700 11942277 112 2319 121
21 21
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
19
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
TCB-2-13 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2971
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 353
Maximum bhp at a given rpm mdash (rpm1933)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
800 353828 008 1026 014 1379 030
38 56 104
1000 442934 011 1108 018 1418 035 1692 055
44 60 101 135
1200 5301048 016 1206 024 1479 042 1731 064 1961 087
58 72 101 130 165
1400 6191171 022 1313 031 1562 051 1784 073 2002 099 2201 126 2391 155
75 87 106 128 160 189 22
1600 707
1300 030 1424 040 1657 062 1865 086 2053 112 2247 141 2425 171 2596 203 2759 237
97 100 115 133 156 184 21 24 27
1800 7961431 039 1545 051 1759 075 1950 101 2134 129 2300 157 2472 189 2636 223 2790 258
114 113 125 144 160 181 21 24 26
2000 8841565 051 1669 063 1868 090 2050 118 2217 148 2381 178 2531 210 2683 244 2836 282
127 127 137 157 170 186 21 23 26
2200 9731700 064 1797 078 1979 107 2152 138 2312 169 2464 202 2612 236 2750 270 2883 306
142 145 156 169 183 198 21 23 26
2400 10611836 081 1928 096 2097 127 2260 160 2413 194 2556 228 2695 264 2831 301 2959 338
164 169 174 182 197 21 23 24 26
2600 11501975 100 2060 116 2219 150 2371 185 2517 221 2656 257 2785 295 2914 334
190 192 193 196 21 23 24 26
2800 12382115 122 2194 140 2343 175 2484 212 2626 251 2758 290 2885 330
21 21 21 22 23 24 26
3000 13272256 148 2329 166 2470 204 2605 243 2737 284 2864 325
24 24 24 24 25 26
3200 14152397 177 2464 196 2600 236 2728 278 2849 320
26 26 26 27 27
3400 15042539 210 2601 230 2731 272 2852 316 2969 361
29 29 30 30 30
3600 15922681 247 2739 267 2863 312
33 33 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
20
TCB-1-16 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2000
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 4384
Maximum bhp at a given rpm mdash (rpm1378)3
Max Motor Frame Size - 182T
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1000 308507 005 612 009 802 017
37 43 59
1250 385584 008 671 012 833 021 985 032
45 49 62 81
1500 462668 011 743 016 884 026 1016 038 1145 052
54 58 69 84 103
1750 540755 016 821 021 944 032 1065 045 1176 059 1289 075 1392 091
64 68 79 93 105 120 136
2000 617
844 022 904 028 1014 040 1119 054 1225 069 1322 085 1422 102 1517 120 1605 139
76 81 92 104 113 124 140 157 175
2250 694934 030 989 036 1090 049 1185 064 1278 080 1373 097 1460 115 1547 134 1635 154
89 94 107 114 123 133 146 161 179
2500 7711026 039 1077 047 1169 061 1257 076 1342 092 1425 110 1511 130 1591 149 1666 170
104 110 119 126 134 144 156 169 184
2750 8481118 051 1166 059 1252 074 1334 091 1411 107 1489 126 1564 146 1643 167 1717 188
121 124 131 138 147 157 168 181 194
3000 9251210 064 1256 073 1337 090 1412 107 1486 125 1556 144 1627 165 1695 186 1769 209
134 138 145 152 161 171 183 194 21
3250 10031303 080 1347 090 1423 108 1494 127 1563 146 1630 166 1695 186 1760 209 1823 232
149 153 161 169 177 187 199 21 22
3500 10801397 098 1438 109 1511 128 1578 148 1642 169 1706 190 1768 211 1828 233 1889 258
166 170 179 187 195 21 22 23 24
3750 11571491 119 1530 130 1599 152 1663 173 1725 194 1784 216 1844 239 1900 262 1956 286
185 189 197 21 22 23 24 25 27
4000 12341585 143 1622 155 1689 178 1750 200 1809 223 1865 246 1921 270 1976 295
20 21 22 23 24 25 26 28
4250 13111680 170 1714 183 1779 207 1838 231 1893 255 1948 280 1999 304
23 23 24 25 26 28 29
4500 13881775 200 1807 214 1869 240 1926 265 1979 291
25 26 27 28 30
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
21
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
TCB-2-16 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2431
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 432
Maximum bhp at a given rpm mdash (rpm1406)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1200 370668 011 842 020 1137 041
46 61 104
1500 462749 015 899 025 1166 049 1395 077
55 68 102 138
1800 555843 021 969 033 1208 059 1424 089 1616 121
71 77 104 135 168
2100 648944 030 1053 042 1268 071 1461 103 1647 138 1813 175 1972 215
83 88 111 134 166 196 22
2400 740
1047 040 1144 054 1336 085 1518 120 1684 157 1847 197 1996 238 2140 283 2275 329
99 105 120 140 166 195 22 25 27
2700 8331152 053 1243 068 1412 101 1579 139 1739 179 1885 221 2033 266 2169 312 2297 359
116 122 132 150 171 195 22 25 28
3000 9251260 069 1345 086 1498 121 1651 161 1799 204 1941 248 2070 295 2206 344 2333 394
132 136 144 162 182 20 23 25 28
3300 10181373 089 1448 107 1588 144 1727 186 1866 231 2001 279 2129 328 2247 379 2370 432
147 151 161 177 195 22 24 26 29
3600 11111486 112 1553 131 1686 171 1813 215 1939 262 2065 312 2188 365 2306 418 2416 473
166 171 182 193 21 23 25 28 30
3900 12031600 140 1658 159 1786 202 1900 247 2020 297 2138 349 2252 404 2366 461
189 194 20 21 23 25 27 29
4200 12961715 172 1766 191 1888 238 1996 285 2106 336 2213 390 2324 448 2430 508
21 21 22 23 24 26 29 31
4500 13881831 208 1878 228 1990 277 2095 328 2193 380 2298 437 2398 496
23 23 24 25 27 28 31
4800 14811946 250 1992 271 2094 322 2196 376 2289 430 2385 488
25 26 27 28 29 31
5100 15742062 296 2105 319 2199 371 2297 429 2388 486
28 28 29 30 32
5400 16662179 349 2219 373 2305 426 2399 487
30 31 32 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
22
TCB-1-18 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1645
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 4843
Maximum bhp at a given rpm mdash (rpm1147)3
Max Motor Frame Size - 182T
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg
0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1500 298486 008 568 012 724 023
43 49 62
1800 357552 011 623 016 755 028 883 042
54 57 67 81
2100 417622 016 683 021 799 034 911 048 1022 065 1123 082
67 68 77 85 99 116
2400 477693 021 749 028 852 041 950 056 1048 073 1147 092 1238 112 1322 133
80 81 90 95 103 120 135 148
2700 536
765 029 817 036 911 050 1001 066 1088 084 1174 103 1262 124 1346 146 1424 169
91 94 103 105 113 125 138 150 164
3000 596838 037 887 045 972 061 1056 078 1136 097 1214 117 1292 138 1369 161 1448 185
102 106 111 115 122 133 142 153 166
3300 656912 048 957 057 1038 074 1115 092 1187 111 1261 132 1331 154 1403 177 1472 202
112 114 120 126 133 141 149 158 168
3600 715987 061 1029 070 1105 089 1176 108 1246 128 1312 149 1379 172 1443 196 1510 222
121 125 131 138 145 152 160 168 178
3900 7751063 075 1102 085 1174 106 1239 126 1305 147 1368 170 1430 193 1491 218 1549 244
133 137 143 149 157 165 173 181 189
4200 8341139 092 1175 103 1244 125 1307 147 1366 169 1428 193 1485 217 1542 243 1599 269
146 149 155 163 171 179 187 195 20
4500 8941215 112 1249 124 1315 147 1375 170 1430 193 1488 218 1544 244 1597 270
160 162 169 176 185 194 20 21
4800 9541292 134 1323 147 1386 172 1444 197 1498 221 1549 246 1604 273
171 174 181 190 199 21 22
5100 10131369 159 1399 172 1458 199 1513 226 1565 252 1615 278
184 187 195 20 21 23
5400 10731446 188 1474 201 1530 229 1584 258 1634 285
197 20 21 22 23
5700 11331523 219 1550 233 1603 263
21 22 22
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
14
TCB-1-10 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2555
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 2928
Maximum bhp at a given rpm mdash (rpm2760)3
Max Motor Frame Size - 143T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
480 260858 003 1011 005 1253 009
49 57 73
560 304947 004 1089 006 1321 011 1511 015
55 63 77 93
640 3471042 005 1171 008 1394 013 1578 018 1740 023 1892 029
63 70 82 96 112 133
720 3911141 007 1259 009 1470 015 1649 021 1806 027 1949 033 2079 039
72 76 89 100 115 132 150
800 4341239 009 1349 012 1548 018 1723 024 1876 031 2015 037 2144 044 2263 051
80 84 96 107 119 135 148 161
880 4781340 011 1444 014 1630 021 1798 027 1949 034 2084 042 2211 049 2329 057 2440 064
88 92 102 113 125 137 150 162 176
960 5211441 014 1541 017 1716 024 1876 031 2023 039 2157 047 2280 055 2396 063 2506 071
97 101 109 121 133 141 152 165 179
1040 5651544 017 1640 021 1805 028 1957 035 2099 044 2231 052 2352 060 2465 069
105 109 117 129 139 148 157 169
1120 6081648 021 1739 025 1895 032 2042 040 2178 049 2306 058 2426 067 2538 076
113 117 127 138 146 155 165 177
1200 6521752 025 1839 029 1989 037 2129 046 2259 055 2383 064 2501 073
122 126 137 145 153 163 175
1280 6951858 030 1940 034 2085 043 2218 052 2343 061 2464 071
132 137 145 152 162 173
1360 7391964 035 2041 040 2183 049 2308 058 2430 068 2545 078
145 149 154 162 172 183
1440 7822071 041 2144 046 2282 056 2401 066 2519 076
156 158 164 173 183
1520 8262177 048 2247 053 2380 064 2497 074
164 167 175 184
1600 8692285 056 2351 061 2479 072
173 177 185
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
15
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-10 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3120)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 3261300 007 1504 011 1875 021 2213 032
73 82 105 132
700 3801453 010 1630 014 1966 024 2273 036 2560 049
84 91 110 133 156
800 4341611 013 1768 018 2070 029 2355 042 2619 055 2872 070 3102 086
100 101 118 137 158 182 20
900 4891773 017 1917 023 2188 034 2448 048 2698 062 2932 078 3160 094 3371 111 3568 129
112 113 127 143 162 185 20 22 25
1000 543
1937 023 2071 029 2319 041 2559 055 2790 070 3011 086 3220 103 3430 122 3626 140
124 127 136 152 170 190 21 23 25
1100 5972104 029 2228 035 2457 048 2677 063 2892 079 3103 096 3303 114 3490 132 3685 152
138 143 146 161 179 195 21 23 25
1200 6522276 036 2389 043 2601 057 2807 073 3009 089 3199 107 3394 125 3578 145 3751 165
154 154 159 172 189 20 21 23 25
1300 7062449 045 2552 052 2753 067 2944 083 3128 101 3315 119 3488 138 3670 159 3841 180
164 166 172 183 195 21 22 24 25
1400 7602623 055 2717 062 2907 079 3083 095 3261 114 3433 133 3603 153 3763 173 3933 196
175 177 185 193 20 21 23 24 26
1500 8152797 066 2883 074 3063 092 3231 109 3398 128 3557 148 3721 169 3878 191 4026 212
186 189 197 20 21 22 23 25 26
1600 8692973 079 3052 087 3223 106 3384 125 3537 144 3693 165 3840 186 3995 209
198 20 21 21 22 23 24 25
1700 9233149 094 3224 103 3384 122 3538 142 3683 162 3831 184 3974 206
21 21 22 22 23 23 25
1800 9783325 110 3396 119 3546 140 3693 161 3834 182 3970 204
22 22 23 23 24 24
1900 10323502 129 3570 138 3710 159 3852 182 3988 204
23 24 24 25 25
2000 10863679 149 3744 159 3875 181 4012 204
25 25 25 26
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
16
TCB-1-12 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2490
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 3436
Maximum bhp at a given rpm mdash (rpm2202)3
Max Motor Frame Size - 145T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 0075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
700 380853 006 958 008 1158 014 1345 021 1518 028
62 66 79 94 110
800 434943 008 1042 011 1218 017 1386 024 1551 031 1703 040
66 70 83 96 111 125
900 4891037 010 1128 013 1287 020 1442 027 1587 035 1736 044 1873 053 2000 063
71 76 87 99 112 126 142 155
1000 5431132 013 1216 017 1363 024 1506 031 1643 040 1771 049 1906 059 2033 069 2151 079
78 83 91 103 115 128 143 156 170
1100 597
1229 016 1305 020 1447 028 1574 036 1702 045 1827 055 1943 065 2066 075 2183 086
86 89 96 108 120 133 144 157 171
1200 6521326 020 1398 025 1532 034 1649 042 1769 051 1884 061 1999 071 2105 082 2216 094
92 95 103 113 126 139 149 159 173
1300 7061426 025 1492 030 1619 039 1732 049 1839 058 1950 068 2055 079 2161 090 2260 102
98 102 112 121 134 145 154 164 176
1400 7601526 031 1588 036 1707 046 1817 056 1916 066 2019 076 2120 088 2217 099 2316 111
106 112 122 132 142 151 160 170 181
1500 8151627 037 1684 042 1796 053 1903 064 1999 075 2089 085 2188 097 2281 109 2372 121
119 125 135 144 149 157 167 176 187
1600 8691729 044 1781 050 1886 061 1990 073 2084 085 2170 096 2258 107 2350 120 2436 133
134 139 150 153 157 165 174 183 194
1700 9231830 053 1879 058 1980 070 2077 083 2170 095 2254 107 2334 119 2419 132
151 157 159 162 167 173 181 191
1800 9781932 062 1978 068 2074 080 2166 093 2256 107 2339 120 2417 132
166 166 168 171 176 182 190
1900 10322034 072 2078 078 2169 091 2256 105 2343 119 2425 133
173 173 176 180 185 192
2000 10862137 083 2179 090 2265 103 2348 118 2432 133
180 181 184 189 195
2100 11412240 096 2280 102 2361 117 2442 132
187 188 192 198
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
17
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-12 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 3274
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 321
Maximum bhp at a given rpm mdash (rpm2315)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
750 4071009 008 1226 014 1587 027
55 67 98
900 4891119 011 1315 018 1648 032 1936 049 2182 067
63 76 102 131 159
1050 5701238 015 1419 023 1728 039 1995 056 2240 076 2456 096
75 85 110 136 164 190
1200 6521363 020 1529 029 1813 046 2070 065 2299 085 2514 108 2710 131 2890 155
89 96 120 142 169 195 22 24
1350 733
1495 027 1643 036 1911 055 2151 076 2372 097 2574 120 2768 145 2948 171 3115 197
104 111 132 152 176 20 22 25 28
1500 8151630 034 1764 044 2018 066 2240 088 2452 111 2647 135 2828 160 3007 187 3174 216
120 129 145 166 186 21 23 26 29
1650 8961767 044 1887 054 2127 077 2338 101 2534 126 2727 151 2903 178 3067 205 3233 235
139 144 159 184 199 22 24 27 30
1800 9781908 055 2018 066 2239 090 2445 117 2630 143 2808 170 2983 198 3145 227
159 165 180 199 22 23 25 28
1950 10592053 068 2151 079 2356 105 2554 134 2731 162 2900 190 3064 220 3225 250
182 188 20 22 23 25 27 29
2100 11412198 083 2286 095 2477 122 2664 152 2839 183 2997 213 3154 244
21 22 22 23 25 27 29
2250 12222344 100 2423 113 2599 141 2777 173 2948 205 3104 238 3250 271
24 24 25 26 27 29 32
2400 13042490 119 2560 133 2726 163 2896 196 3058 230 3212 265
26 26 27 28 30 32
2550 13852637 141 2703 156 2858 187 3016 221 3169 257
28 29 29 31 32
2700 14672785 166 2847 181 2991 214 3138 248
31 31 32 34
2850 15482933 193 2992 209 3126 243 3262 279
34 34 35 37
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
18
TCB-1-13 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2355
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 3435
Maximum bhp at a given rpm mdash (rpm2119)3
Max Motor Frame Size - 145T
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 265660 003 792 005 1019 010
41 51 69
750 331760 005 874 007 1073 013 1254 019
48 58 71 84
900 398864 007 967 010 1146 016 1305 023 1459 030
58 64 75 86 102
1050 464973 009 1067 013 1230 020 1378 027 1512 036 1646 044 1770 053
66 70 80 91 103 120 140
1200 530
1085 013 1171 017 1321 024 1457 032 1585 041 1703 051 1820 061 1933 071 2039 081
72 77 86 96 108 120 136 153 172
1350 5971199 017 1277 022 1419 030 1545 039 1662 048 1777 058 1883 069 1984 080 2089 091
81 85 94 103 114 125 136 151 167
1500 6631316 023 1387 027 1520 037 1637 046 1749 059 1853 067 1957 078 2054 090 2146 102
90 94 102 112 122 132 143 155 169
1650 7301434 029 1499 034 1623 044 1736 055 1839 065 1940 077 2034 088 2128 100 2219 113
100 104 113 123 132 143 153 165 178
1800 7961552 037 1613 042 1729 054 1836 065 1935 076 2029 088 2121 100 2207 113 2293 126
112 115 125 134 144 154 165 177 190
1950 8621672 045 1728 052 1836 064 1939 076 2034 088 2123 100 2209 113 2294 127
124 129 138 147 156 167 178 190
2100 9291792 056 1844 062 1947 076 2044 089 2135 102 2221 115 2302 128
138 142 151 161 170 181 192
2250 9951913 067 1962 075 2058 089 2150 103 2238 117 2321 131
152 157 167 177 186 196
2400 10612034 081 2080 088 2171 104 2258 119 2342 133
169 174 184 194 20
2550 11282155 095 2199 104 2285 120
187 192 20
2700 11942277 112 2319 121
21 21
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
19
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
TCB-2-13 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2971
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 353
Maximum bhp at a given rpm mdash (rpm1933)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
800 353828 008 1026 014 1379 030
38 56 104
1000 442934 011 1108 018 1418 035 1692 055
44 60 101 135
1200 5301048 016 1206 024 1479 042 1731 064 1961 087
58 72 101 130 165
1400 6191171 022 1313 031 1562 051 1784 073 2002 099 2201 126 2391 155
75 87 106 128 160 189 22
1600 707
1300 030 1424 040 1657 062 1865 086 2053 112 2247 141 2425 171 2596 203 2759 237
97 100 115 133 156 184 21 24 27
1800 7961431 039 1545 051 1759 075 1950 101 2134 129 2300 157 2472 189 2636 223 2790 258
114 113 125 144 160 181 21 24 26
2000 8841565 051 1669 063 1868 090 2050 118 2217 148 2381 178 2531 210 2683 244 2836 282
127 127 137 157 170 186 21 23 26
2200 9731700 064 1797 078 1979 107 2152 138 2312 169 2464 202 2612 236 2750 270 2883 306
142 145 156 169 183 198 21 23 26
2400 10611836 081 1928 096 2097 127 2260 160 2413 194 2556 228 2695 264 2831 301 2959 338
164 169 174 182 197 21 23 24 26
2600 11501975 100 2060 116 2219 150 2371 185 2517 221 2656 257 2785 295 2914 334
190 192 193 196 21 23 24 26
2800 12382115 122 2194 140 2343 175 2484 212 2626 251 2758 290 2885 330
21 21 21 22 23 24 26
3000 13272256 148 2329 166 2470 204 2605 243 2737 284 2864 325
24 24 24 24 25 26
3200 14152397 177 2464 196 2600 236 2728 278 2849 320
26 26 26 27 27
3400 15042539 210 2601 230 2731 272 2852 316 2969 361
29 29 30 30 30
3600 15922681 247 2739 267 2863 312
33 33 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
20
TCB-1-16 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2000
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 4384
Maximum bhp at a given rpm mdash (rpm1378)3
Max Motor Frame Size - 182T
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1000 308507 005 612 009 802 017
37 43 59
1250 385584 008 671 012 833 021 985 032
45 49 62 81
1500 462668 011 743 016 884 026 1016 038 1145 052
54 58 69 84 103
1750 540755 016 821 021 944 032 1065 045 1176 059 1289 075 1392 091
64 68 79 93 105 120 136
2000 617
844 022 904 028 1014 040 1119 054 1225 069 1322 085 1422 102 1517 120 1605 139
76 81 92 104 113 124 140 157 175
2250 694934 030 989 036 1090 049 1185 064 1278 080 1373 097 1460 115 1547 134 1635 154
89 94 107 114 123 133 146 161 179
2500 7711026 039 1077 047 1169 061 1257 076 1342 092 1425 110 1511 130 1591 149 1666 170
104 110 119 126 134 144 156 169 184
2750 8481118 051 1166 059 1252 074 1334 091 1411 107 1489 126 1564 146 1643 167 1717 188
121 124 131 138 147 157 168 181 194
3000 9251210 064 1256 073 1337 090 1412 107 1486 125 1556 144 1627 165 1695 186 1769 209
134 138 145 152 161 171 183 194 21
3250 10031303 080 1347 090 1423 108 1494 127 1563 146 1630 166 1695 186 1760 209 1823 232
149 153 161 169 177 187 199 21 22
3500 10801397 098 1438 109 1511 128 1578 148 1642 169 1706 190 1768 211 1828 233 1889 258
166 170 179 187 195 21 22 23 24
3750 11571491 119 1530 130 1599 152 1663 173 1725 194 1784 216 1844 239 1900 262 1956 286
185 189 197 21 22 23 24 25 27
4000 12341585 143 1622 155 1689 178 1750 200 1809 223 1865 246 1921 270 1976 295
20 21 22 23 24 25 26 28
4250 13111680 170 1714 183 1779 207 1838 231 1893 255 1948 280 1999 304
23 23 24 25 26 28 29
4500 13881775 200 1807 214 1869 240 1926 265 1979 291
25 26 27 28 30
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
21
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
TCB-2-16 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2431
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 432
Maximum bhp at a given rpm mdash (rpm1406)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1200 370668 011 842 020 1137 041
46 61 104
1500 462749 015 899 025 1166 049 1395 077
55 68 102 138
1800 555843 021 969 033 1208 059 1424 089 1616 121
71 77 104 135 168
2100 648944 030 1053 042 1268 071 1461 103 1647 138 1813 175 1972 215
83 88 111 134 166 196 22
2400 740
1047 040 1144 054 1336 085 1518 120 1684 157 1847 197 1996 238 2140 283 2275 329
99 105 120 140 166 195 22 25 27
2700 8331152 053 1243 068 1412 101 1579 139 1739 179 1885 221 2033 266 2169 312 2297 359
116 122 132 150 171 195 22 25 28
3000 9251260 069 1345 086 1498 121 1651 161 1799 204 1941 248 2070 295 2206 344 2333 394
132 136 144 162 182 20 23 25 28
3300 10181373 089 1448 107 1588 144 1727 186 1866 231 2001 279 2129 328 2247 379 2370 432
147 151 161 177 195 22 24 26 29
3600 11111486 112 1553 131 1686 171 1813 215 1939 262 2065 312 2188 365 2306 418 2416 473
166 171 182 193 21 23 25 28 30
3900 12031600 140 1658 159 1786 202 1900 247 2020 297 2138 349 2252 404 2366 461
189 194 20 21 23 25 27 29
4200 12961715 172 1766 191 1888 238 1996 285 2106 336 2213 390 2324 448 2430 508
21 21 22 23 24 26 29 31
4500 13881831 208 1878 228 1990 277 2095 328 2193 380 2298 437 2398 496
23 23 24 25 27 28 31
4800 14811946 250 1992 271 2094 322 2196 376 2289 430 2385 488
25 26 27 28 29 31
5100 15742062 296 2105 319 2199 371 2297 429 2388 486
28 28 29 30 32
5400 16662179 349 2219 373 2305 426 2399 487
30 31 32 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
22
TCB-1-18 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1645
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 4843
Maximum bhp at a given rpm mdash (rpm1147)3
Max Motor Frame Size - 182T
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg
0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1500 298486 008 568 012 724 023
43 49 62
1800 357552 011 623 016 755 028 883 042
54 57 67 81
2100 417622 016 683 021 799 034 911 048 1022 065 1123 082
67 68 77 85 99 116
2400 477693 021 749 028 852 041 950 056 1048 073 1147 092 1238 112 1322 133
80 81 90 95 103 120 135 148
2700 536
765 029 817 036 911 050 1001 066 1088 084 1174 103 1262 124 1346 146 1424 169
91 94 103 105 113 125 138 150 164
3000 596838 037 887 045 972 061 1056 078 1136 097 1214 117 1292 138 1369 161 1448 185
102 106 111 115 122 133 142 153 166
3300 656912 048 957 057 1038 074 1115 092 1187 111 1261 132 1331 154 1403 177 1472 202
112 114 120 126 133 141 149 158 168
3600 715987 061 1029 070 1105 089 1176 108 1246 128 1312 149 1379 172 1443 196 1510 222
121 125 131 138 145 152 160 168 178
3900 7751063 075 1102 085 1174 106 1239 126 1305 147 1368 170 1430 193 1491 218 1549 244
133 137 143 149 157 165 173 181 189
4200 8341139 092 1175 103 1244 125 1307 147 1366 169 1428 193 1485 217 1542 243 1599 269
146 149 155 163 171 179 187 195 20
4500 8941215 112 1249 124 1315 147 1375 170 1430 193 1488 218 1544 244 1597 270
160 162 169 176 185 194 20 21
4800 9541292 134 1323 147 1386 172 1444 197 1498 221 1549 246 1604 273
171 174 181 190 199 21 22
5100 10131369 159 1399 172 1458 199 1513 226 1565 252 1615 278
184 187 195 20 21 23
5400 10731446 188 1474 201 1530 229 1584 258 1634 285
197 20 21 22 23
5700 11331523 219 1550 233 1603 263
21 22 22
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
15
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-10 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 4050
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 275
Maximum bhp at a given rpm mdash (rpm3120)3
Max Motor Frame Size - 145T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 3261300 007 1504 011 1875 021 2213 032
73 82 105 132
700 3801453 010 1630 014 1966 024 2273 036 2560 049
84 91 110 133 156
800 4341611 013 1768 018 2070 029 2355 042 2619 055 2872 070 3102 086
100 101 118 137 158 182 20
900 4891773 017 1917 023 2188 034 2448 048 2698 062 2932 078 3160 094 3371 111 3568 129
112 113 127 143 162 185 20 22 25
1000 543
1937 023 2071 029 2319 041 2559 055 2790 070 3011 086 3220 103 3430 122 3626 140
124 127 136 152 170 190 21 23 25
1100 5972104 029 2228 035 2457 048 2677 063 2892 079 3103 096 3303 114 3490 132 3685 152
138 143 146 161 179 195 21 23 25
1200 6522276 036 2389 043 2601 057 2807 073 3009 089 3199 107 3394 125 3578 145 3751 165
154 154 159 172 189 20 21 23 25
1300 7062449 045 2552 052 2753 067 2944 083 3128 101 3315 119 3488 138 3670 159 3841 180
164 166 172 183 195 21 22 24 25
1400 7602623 055 2717 062 2907 079 3083 095 3261 114 3433 133 3603 153 3763 173 3933 196
175 177 185 193 20 21 23 24 26
1500 8152797 066 2883 074 3063 092 3231 109 3398 128 3557 148 3721 169 3878 191 4026 212
186 189 197 20 21 22 23 25 26
1600 8692973 079 3052 087 3223 106 3384 125 3537 144 3693 165 3840 186 3995 209
198 20 21 21 22 23 24 25
1700 9233149 094 3224 103 3384 122 3538 142 3683 162 3831 184 3974 206
21 21 22 22 23 23 25
1800 9783325 110 3396 119 3546 140 3693 161 3834 182 3970 204
22 22 23 23 24 24
1900 10323502 129 3570 138 3710 159 3852 182 3988 204
23 24 24 25 25
2000 10863679 149 3744 159 3875 181 4012 204
25 25 25 26
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
16
TCB-1-12 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2490
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 3436
Maximum bhp at a given rpm mdash (rpm2202)3
Max Motor Frame Size - 145T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 0075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
700 380853 006 958 008 1158 014 1345 021 1518 028
62 66 79 94 110
800 434943 008 1042 011 1218 017 1386 024 1551 031 1703 040
66 70 83 96 111 125
900 4891037 010 1128 013 1287 020 1442 027 1587 035 1736 044 1873 053 2000 063
71 76 87 99 112 126 142 155
1000 5431132 013 1216 017 1363 024 1506 031 1643 040 1771 049 1906 059 2033 069 2151 079
78 83 91 103 115 128 143 156 170
1100 597
1229 016 1305 020 1447 028 1574 036 1702 045 1827 055 1943 065 2066 075 2183 086
86 89 96 108 120 133 144 157 171
1200 6521326 020 1398 025 1532 034 1649 042 1769 051 1884 061 1999 071 2105 082 2216 094
92 95 103 113 126 139 149 159 173
1300 7061426 025 1492 030 1619 039 1732 049 1839 058 1950 068 2055 079 2161 090 2260 102
98 102 112 121 134 145 154 164 176
1400 7601526 031 1588 036 1707 046 1817 056 1916 066 2019 076 2120 088 2217 099 2316 111
106 112 122 132 142 151 160 170 181
1500 8151627 037 1684 042 1796 053 1903 064 1999 075 2089 085 2188 097 2281 109 2372 121
119 125 135 144 149 157 167 176 187
1600 8691729 044 1781 050 1886 061 1990 073 2084 085 2170 096 2258 107 2350 120 2436 133
134 139 150 153 157 165 174 183 194
1700 9231830 053 1879 058 1980 070 2077 083 2170 095 2254 107 2334 119 2419 132
151 157 159 162 167 173 181 191
1800 9781932 062 1978 068 2074 080 2166 093 2256 107 2339 120 2417 132
166 166 168 171 176 182 190
1900 10322034 072 2078 078 2169 091 2256 105 2343 119 2425 133
173 173 176 180 185 192
2000 10862137 083 2179 090 2265 103 2348 118 2432 133
180 181 184 189 195
2100 11412240 096 2280 102 2361 117 2442 132
187 188 192 198
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
17
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-12 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 3274
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 321
Maximum bhp at a given rpm mdash (rpm2315)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
750 4071009 008 1226 014 1587 027
55 67 98
900 4891119 011 1315 018 1648 032 1936 049 2182 067
63 76 102 131 159
1050 5701238 015 1419 023 1728 039 1995 056 2240 076 2456 096
75 85 110 136 164 190
1200 6521363 020 1529 029 1813 046 2070 065 2299 085 2514 108 2710 131 2890 155
89 96 120 142 169 195 22 24
1350 733
1495 027 1643 036 1911 055 2151 076 2372 097 2574 120 2768 145 2948 171 3115 197
104 111 132 152 176 20 22 25 28
1500 8151630 034 1764 044 2018 066 2240 088 2452 111 2647 135 2828 160 3007 187 3174 216
120 129 145 166 186 21 23 26 29
1650 8961767 044 1887 054 2127 077 2338 101 2534 126 2727 151 2903 178 3067 205 3233 235
139 144 159 184 199 22 24 27 30
1800 9781908 055 2018 066 2239 090 2445 117 2630 143 2808 170 2983 198 3145 227
159 165 180 199 22 23 25 28
1950 10592053 068 2151 079 2356 105 2554 134 2731 162 2900 190 3064 220 3225 250
182 188 20 22 23 25 27 29
2100 11412198 083 2286 095 2477 122 2664 152 2839 183 2997 213 3154 244
21 22 22 23 25 27 29
2250 12222344 100 2423 113 2599 141 2777 173 2948 205 3104 238 3250 271
24 24 25 26 27 29 32
2400 13042490 119 2560 133 2726 163 2896 196 3058 230 3212 265
26 26 27 28 30 32
2550 13852637 141 2703 156 2858 187 3016 221 3169 257
28 29 29 31 32
2700 14672785 166 2847 181 2991 214 3138 248
31 31 32 34
2850 15482933 193 2992 209 3126 243 3262 279
34 34 35 37
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
18
TCB-1-13 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2355
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 3435
Maximum bhp at a given rpm mdash (rpm2119)3
Max Motor Frame Size - 145T
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 265660 003 792 005 1019 010
41 51 69
750 331760 005 874 007 1073 013 1254 019
48 58 71 84
900 398864 007 967 010 1146 016 1305 023 1459 030
58 64 75 86 102
1050 464973 009 1067 013 1230 020 1378 027 1512 036 1646 044 1770 053
66 70 80 91 103 120 140
1200 530
1085 013 1171 017 1321 024 1457 032 1585 041 1703 051 1820 061 1933 071 2039 081
72 77 86 96 108 120 136 153 172
1350 5971199 017 1277 022 1419 030 1545 039 1662 048 1777 058 1883 069 1984 080 2089 091
81 85 94 103 114 125 136 151 167
1500 6631316 023 1387 027 1520 037 1637 046 1749 059 1853 067 1957 078 2054 090 2146 102
90 94 102 112 122 132 143 155 169
1650 7301434 029 1499 034 1623 044 1736 055 1839 065 1940 077 2034 088 2128 100 2219 113
100 104 113 123 132 143 153 165 178
1800 7961552 037 1613 042 1729 054 1836 065 1935 076 2029 088 2121 100 2207 113 2293 126
112 115 125 134 144 154 165 177 190
1950 8621672 045 1728 052 1836 064 1939 076 2034 088 2123 100 2209 113 2294 127
124 129 138 147 156 167 178 190
2100 9291792 056 1844 062 1947 076 2044 089 2135 102 2221 115 2302 128
138 142 151 161 170 181 192
2250 9951913 067 1962 075 2058 089 2150 103 2238 117 2321 131
152 157 167 177 186 196
2400 10612034 081 2080 088 2171 104 2258 119 2342 133
169 174 184 194 20
2550 11282155 095 2199 104 2285 120
187 192 20
2700 11942277 112 2319 121
21 21
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
19
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
TCB-2-13 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2971
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 353
Maximum bhp at a given rpm mdash (rpm1933)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
800 353828 008 1026 014 1379 030
38 56 104
1000 442934 011 1108 018 1418 035 1692 055
44 60 101 135
1200 5301048 016 1206 024 1479 042 1731 064 1961 087
58 72 101 130 165
1400 6191171 022 1313 031 1562 051 1784 073 2002 099 2201 126 2391 155
75 87 106 128 160 189 22
1600 707
1300 030 1424 040 1657 062 1865 086 2053 112 2247 141 2425 171 2596 203 2759 237
97 100 115 133 156 184 21 24 27
1800 7961431 039 1545 051 1759 075 1950 101 2134 129 2300 157 2472 189 2636 223 2790 258
114 113 125 144 160 181 21 24 26
2000 8841565 051 1669 063 1868 090 2050 118 2217 148 2381 178 2531 210 2683 244 2836 282
127 127 137 157 170 186 21 23 26
2200 9731700 064 1797 078 1979 107 2152 138 2312 169 2464 202 2612 236 2750 270 2883 306
142 145 156 169 183 198 21 23 26
2400 10611836 081 1928 096 2097 127 2260 160 2413 194 2556 228 2695 264 2831 301 2959 338
164 169 174 182 197 21 23 24 26
2600 11501975 100 2060 116 2219 150 2371 185 2517 221 2656 257 2785 295 2914 334
190 192 193 196 21 23 24 26
2800 12382115 122 2194 140 2343 175 2484 212 2626 251 2758 290 2885 330
21 21 21 22 23 24 26
3000 13272256 148 2329 166 2470 204 2605 243 2737 284 2864 325
24 24 24 24 25 26
3200 14152397 177 2464 196 2600 236 2728 278 2849 320
26 26 26 27 27
3400 15042539 210 2601 230 2731 272 2852 316 2969 361
29 29 30 30 30
3600 15922681 247 2739 267 2863 312
33 33 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
20
TCB-1-16 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2000
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 4384
Maximum bhp at a given rpm mdash (rpm1378)3
Max Motor Frame Size - 182T
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1000 308507 005 612 009 802 017
37 43 59
1250 385584 008 671 012 833 021 985 032
45 49 62 81
1500 462668 011 743 016 884 026 1016 038 1145 052
54 58 69 84 103
1750 540755 016 821 021 944 032 1065 045 1176 059 1289 075 1392 091
64 68 79 93 105 120 136
2000 617
844 022 904 028 1014 040 1119 054 1225 069 1322 085 1422 102 1517 120 1605 139
76 81 92 104 113 124 140 157 175
2250 694934 030 989 036 1090 049 1185 064 1278 080 1373 097 1460 115 1547 134 1635 154
89 94 107 114 123 133 146 161 179
2500 7711026 039 1077 047 1169 061 1257 076 1342 092 1425 110 1511 130 1591 149 1666 170
104 110 119 126 134 144 156 169 184
2750 8481118 051 1166 059 1252 074 1334 091 1411 107 1489 126 1564 146 1643 167 1717 188
121 124 131 138 147 157 168 181 194
3000 9251210 064 1256 073 1337 090 1412 107 1486 125 1556 144 1627 165 1695 186 1769 209
134 138 145 152 161 171 183 194 21
3250 10031303 080 1347 090 1423 108 1494 127 1563 146 1630 166 1695 186 1760 209 1823 232
149 153 161 169 177 187 199 21 22
3500 10801397 098 1438 109 1511 128 1578 148 1642 169 1706 190 1768 211 1828 233 1889 258
166 170 179 187 195 21 22 23 24
3750 11571491 119 1530 130 1599 152 1663 173 1725 194 1784 216 1844 239 1900 262 1956 286
185 189 197 21 22 23 24 25 27
4000 12341585 143 1622 155 1689 178 1750 200 1809 223 1865 246 1921 270 1976 295
20 21 22 23 24 25 26 28
4250 13111680 170 1714 183 1779 207 1838 231 1893 255 1948 280 1999 304
23 23 24 25 26 28 29
4500 13881775 200 1807 214 1869 240 1926 265 1979 291
25 26 27 28 30
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
21
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
TCB-2-16 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2431
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 432
Maximum bhp at a given rpm mdash (rpm1406)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1200 370668 011 842 020 1137 041
46 61 104
1500 462749 015 899 025 1166 049 1395 077
55 68 102 138
1800 555843 021 969 033 1208 059 1424 089 1616 121
71 77 104 135 168
2100 648944 030 1053 042 1268 071 1461 103 1647 138 1813 175 1972 215
83 88 111 134 166 196 22
2400 740
1047 040 1144 054 1336 085 1518 120 1684 157 1847 197 1996 238 2140 283 2275 329
99 105 120 140 166 195 22 25 27
2700 8331152 053 1243 068 1412 101 1579 139 1739 179 1885 221 2033 266 2169 312 2297 359
116 122 132 150 171 195 22 25 28
3000 9251260 069 1345 086 1498 121 1651 161 1799 204 1941 248 2070 295 2206 344 2333 394
132 136 144 162 182 20 23 25 28
3300 10181373 089 1448 107 1588 144 1727 186 1866 231 2001 279 2129 328 2247 379 2370 432
147 151 161 177 195 22 24 26 29
3600 11111486 112 1553 131 1686 171 1813 215 1939 262 2065 312 2188 365 2306 418 2416 473
166 171 182 193 21 23 25 28 30
3900 12031600 140 1658 159 1786 202 1900 247 2020 297 2138 349 2252 404 2366 461
189 194 20 21 23 25 27 29
4200 12961715 172 1766 191 1888 238 1996 285 2106 336 2213 390 2324 448 2430 508
21 21 22 23 24 26 29 31
4500 13881831 208 1878 228 1990 277 2095 328 2193 380 2298 437 2398 496
23 23 24 25 27 28 31
4800 14811946 250 1992 271 2094 322 2196 376 2289 430 2385 488
25 26 27 28 29 31
5100 15742062 296 2105 319 2199 371 2297 429 2388 486
28 28 29 30 32
5400 16662179 349 2219 373 2305 426 2399 487
30 31 32 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
22
TCB-1-18 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1645
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 4843
Maximum bhp at a given rpm mdash (rpm1147)3
Max Motor Frame Size - 182T
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg
0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1500 298486 008 568 012 724 023
43 49 62
1800 357552 011 623 016 755 028 883 042
54 57 67 81
2100 417622 016 683 021 799 034 911 048 1022 065 1123 082
67 68 77 85 99 116
2400 477693 021 749 028 852 041 950 056 1048 073 1147 092 1238 112 1322 133
80 81 90 95 103 120 135 148
2700 536
765 029 817 036 911 050 1001 066 1088 084 1174 103 1262 124 1346 146 1424 169
91 94 103 105 113 125 138 150 164
3000 596838 037 887 045 972 061 1056 078 1136 097 1214 117 1292 138 1369 161 1448 185
102 106 111 115 122 133 142 153 166
3300 656912 048 957 057 1038 074 1115 092 1187 111 1261 132 1331 154 1403 177 1472 202
112 114 120 126 133 141 149 158 168
3600 715987 061 1029 070 1105 089 1176 108 1246 128 1312 149 1379 172 1443 196 1510 222
121 125 131 138 145 152 160 168 178
3900 7751063 075 1102 085 1174 106 1239 126 1305 147 1368 170 1430 193 1491 218 1549 244
133 137 143 149 157 165 173 181 189
4200 8341139 092 1175 103 1244 125 1307 147 1366 169 1428 193 1485 217 1542 243 1599 269
146 149 155 163 171 179 187 195 20
4500 8941215 112 1249 124 1315 147 1375 170 1430 193 1488 218 1544 244 1597 270
160 162 169 176 185 194 20 21
4800 9541292 134 1323 147 1386 172 1444 197 1498 221 1549 246 1604 273
171 174 181 190 199 21 22
5100 10131369 159 1399 172 1458 199 1513 226 1565 252 1615 278
184 187 195 20 21 23
5400 10731446 188 1474 201 1530 229 1584 258 1634 285
197 20 21 22 23
5700 11331523 219 1550 233 1603 263
21 22 22
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
16
TCB-1-12 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2490
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 3436
Maximum bhp at a given rpm mdash (rpm2202)3
Max Motor Frame Size - 145T
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 0075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
700 380853 006 958 008 1158 014 1345 021 1518 028
62 66 79 94 110
800 434943 008 1042 011 1218 017 1386 024 1551 031 1703 040
66 70 83 96 111 125
900 4891037 010 1128 013 1287 020 1442 027 1587 035 1736 044 1873 053 2000 063
71 76 87 99 112 126 142 155
1000 5431132 013 1216 017 1363 024 1506 031 1643 040 1771 049 1906 059 2033 069 2151 079
78 83 91 103 115 128 143 156 170
1100 597
1229 016 1305 020 1447 028 1574 036 1702 045 1827 055 1943 065 2066 075 2183 086
86 89 96 108 120 133 144 157 171
1200 6521326 020 1398 025 1532 034 1649 042 1769 051 1884 061 1999 071 2105 082 2216 094
92 95 103 113 126 139 149 159 173
1300 7061426 025 1492 030 1619 039 1732 049 1839 058 1950 068 2055 079 2161 090 2260 102
98 102 112 121 134 145 154 164 176
1400 7601526 031 1588 036 1707 046 1817 056 1916 066 2019 076 2120 088 2217 099 2316 111
106 112 122 132 142 151 160 170 181
1500 8151627 037 1684 042 1796 053 1903 064 1999 075 2089 085 2188 097 2281 109 2372 121
119 125 135 144 149 157 167 176 187
1600 8691729 044 1781 050 1886 061 1990 073 2084 085 2170 096 2258 107 2350 120 2436 133
134 139 150 153 157 165 174 183 194
1700 9231830 053 1879 058 1980 070 2077 083 2170 095 2254 107 2334 119 2419 132
151 157 159 162 167 173 181 191
1800 9781932 062 1978 068 2074 080 2166 093 2256 107 2339 120 2417 132
166 166 168 171 176 182 190
1900 10322034 072 2078 078 2169 091 2256 105 2343 119 2425 133
173 173 176 180 185 192
2000 10862137 083 2179 090 2265 103 2348 118 2432 133
180 181 184 189 195
2100 11412240 096 2280 102 2361 117 2442 132
187 188 192 198
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
17
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-12 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 3274
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 321
Maximum bhp at a given rpm mdash (rpm2315)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
750 4071009 008 1226 014 1587 027
55 67 98
900 4891119 011 1315 018 1648 032 1936 049 2182 067
63 76 102 131 159
1050 5701238 015 1419 023 1728 039 1995 056 2240 076 2456 096
75 85 110 136 164 190
1200 6521363 020 1529 029 1813 046 2070 065 2299 085 2514 108 2710 131 2890 155
89 96 120 142 169 195 22 24
1350 733
1495 027 1643 036 1911 055 2151 076 2372 097 2574 120 2768 145 2948 171 3115 197
104 111 132 152 176 20 22 25 28
1500 8151630 034 1764 044 2018 066 2240 088 2452 111 2647 135 2828 160 3007 187 3174 216
120 129 145 166 186 21 23 26 29
1650 8961767 044 1887 054 2127 077 2338 101 2534 126 2727 151 2903 178 3067 205 3233 235
139 144 159 184 199 22 24 27 30
1800 9781908 055 2018 066 2239 090 2445 117 2630 143 2808 170 2983 198 3145 227
159 165 180 199 22 23 25 28
1950 10592053 068 2151 079 2356 105 2554 134 2731 162 2900 190 3064 220 3225 250
182 188 20 22 23 25 27 29
2100 11412198 083 2286 095 2477 122 2664 152 2839 183 2997 213 3154 244
21 22 22 23 25 27 29
2250 12222344 100 2423 113 2599 141 2777 173 2948 205 3104 238 3250 271
24 24 25 26 27 29 32
2400 13042490 119 2560 133 2726 163 2896 196 3058 230 3212 265
26 26 27 28 30 32
2550 13852637 141 2703 156 2858 187 3016 221 3169 257
28 29 29 31 32
2700 14672785 166 2847 181 2991 214 3138 248
31 31 32 34
2850 15482933 193 2992 209 3126 243 3262 279
34 34 35 37
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
18
TCB-1-13 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2355
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 3435
Maximum bhp at a given rpm mdash (rpm2119)3
Max Motor Frame Size - 145T
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 265660 003 792 005 1019 010
41 51 69
750 331760 005 874 007 1073 013 1254 019
48 58 71 84
900 398864 007 967 010 1146 016 1305 023 1459 030
58 64 75 86 102
1050 464973 009 1067 013 1230 020 1378 027 1512 036 1646 044 1770 053
66 70 80 91 103 120 140
1200 530
1085 013 1171 017 1321 024 1457 032 1585 041 1703 051 1820 061 1933 071 2039 081
72 77 86 96 108 120 136 153 172
1350 5971199 017 1277 022 1419 030 1545 039 1662 048 1777 058 1883 069 1984 080 2089 091
81 85 94 103 114 125 136 151 167
1500 6631316 023 1387 027 1520 037 1637 046 1749 059 1853 067 1957 078 2054 090 2146 102
90 94 102 112 122 132 143 155 169
1650 7301434 029 1499 034 1623 044 1736 055 1839 065 1940 077 2034 088 2128 100 2219 113
100 104 113 123 132 143 153 165 178
1800 7961552 037 1613 042 1729 054 1836 065 1935 076 2029 088 2121 100 2207 113 2293 126
112 115 125 134 144 154 165 177 190
1950 8621672 045 1728 052 1836 064 1939 076 2034 088 2123 100 2209 113 2294 127
124 129 138 147 156 167 178 190
2100 9291792 056 1844 062 1947 076 2044 089 2135 102 2221 115 2302 128
138 142 151 161 170 181 192
2250 9951913 067 1962 075 2058 089 2150 103 2238 117 2321 131
152 157 167 177 186 196
2400 10612034 081 2080 088 2171 104 2258 119 2342 133
169 174 184 194 20
2550 11282155 095 2199 104 2285 120
187 192 20
2700 11942277 112 2319 121
21 21
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
19
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
TCB-2-13 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2971
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 353
Maximum bhp at a given rpm mdash (rpm1933)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
800 353828 008 1026 014 1379 030
38 56 104
1000 442934 011 1108 018 1418 035 1692 055
44 60 101 135
1200 5301048 016 1206 024 1479 042 1731 064 1961 087
58 72 101 130 165
1400 6191171 022 1313 031 1562 051 1784 073 2002 099 2201 126 2391 155
75 87 106 128 160 189 22
1600 707
1300 030 1424 040 1657 062 1865 086 2053 112 2247 141 2425 171 2596 203 2759 237
97 100 115 133 156 184 21 24 27
1800 7961431 039 1545 051 1759 075 1950 101 2134 129 2300 157 2472 189 2636 223 2790 258
114 113 125 144 160 181 21 24 26
2000 8841565 051 1669 063 1868 090 2050 118 2217 148 2381 178 2531 210 2683 244 2836 282
127 127 137 157 170 186 21 23 26
2200 9731700 064 1797 078 1979 107 2152 138 2312 169 2464 202 2612 236 2750 270 2883 306
142 145 156 169 183 198 21 23 26
2400 10611836 081 1928 096 2097 127 2260 160 2413 194 2556 228 2695 264 2831 301 2959 338
164 169 174 182 197 21 23 24 26
2600 11501975 100 2060 116 2219 150 2371 185 2517 221 2656 257 2785 295 2914 334
190 192 193 196 21 23 24 26
2800 12382115 122 2194 140 2343 175 2484 212 2626 251 2758 290 2885 330
21 21 21 22 23 24 26
3000 13272256 148 2329 166 2470 204 2605 243 2737 284 2864 325
24 24 24 24 25 26
3200 14152397 177 2464 196 2600 236 2728 278 2849 320
26 26 26 27 27
3400 15042539 210 2601 230 2731 272 2852 316 2969 361
29 29 30 30 30
3600 15922681 247 2739 267 2863 312
33 33 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
20
TCB-1-16 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2000
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 4384
Maximum bhp at a given rpm mdash (rpm1378)3
Max Motor Frame Size - 182T
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1000 308507 005 612 009 802 017
37 43 59
1250 385584 008 671 012 833 021 985 032
45 49 62 81
1500 462668 011 743 016 884 026 1016 038 1145 052
54 58 69 84 103
1750 540755 016 821 021 944 032 1065 045 1176 059 1289 075 1392 091
64 68 79 93 105 120 136
2000 617
844 022 904 028 1014 040 1119 054 1225 069 1322 085 1422 102 1517 120 1605 139
76 81 92 104 113 124 140 157 175
2250 694934 030 989 036 1090 049 1185 064 1278 080 1373 097 1460 115 1547 134 1635 154
89 94 107 114 123 133 146 161 179
2500 7711026 039 1077 047 1169 061 1257 076 1342 092 1425 110 1511 130 1591 149 1666 170
104 110 119 126 134 144 156 169 184
2750 8481118 051 1166 059 1252 074 1334 091 1411 107 1489 126 1564 146 1643 167 1717 188
121 124 131 138 147 157 168 181 194
3000 9251210 064 1256 073 1337 090 1412 107 1486 125 1556 144 1627 165 1695 186 1769 209
134 138 145 152 161 171 183 194 21
3250 10031303 080 1347 090 1423 108 1494 127 1563 146 1630 166 1695 186 1760 209 1823 232
149 153 161 169 177 187 199 21 22
3500 10801397 098 1438 109 1511 128 1578 148 1642 169 1706 190 1768 211 1828 233 1889 258
166 170 179 187 195 21 22 23 24
3750 11571491 119 1530 130 1599 152 1663 173 1725 194 1784 216 1844 239 1900 262 1956 286
185 189 197 21 22 23 24 25 27
4000 12341585 143 1622 155 1689 178 1750 200 1809 223 1865 246 1921 270 1976 295
20 21 22 23 24 25 26 28
4250 13111680 170 1714 183 1779 207 1838 231 1893 255 1948 280 1999 304
23 23 24 25 26 28 29
4500 13881775 200 1807 214 1869 240 1926 265 1979 291
25 26 27 28 30
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
21
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
TCB-2-16 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2431
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 432
Maximum bhp at a given rpm mdash (rpm1406)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1200 370668 011 842 020 1137 041
46 61 104
1500 462749 015 899 025 1166 049 1395 077
55 68 102 138
1800 555843 021 969 033 1208 059 1424 089 1616 121
71 77 104 135 168
2100 648944 030 1053 042 1268 071 1461 103 1647 138 1813 175 1972 215
83 88 111 134 166 196 22
2400 740
1047 040 1144 054 1336 085 1518 120 1684 157 1847 197 1996 238 2140 283 2275 329
99 105 120 140 166 195 22 25 27
2700 8331152 053 1243 068 1412 101 1579 139 1739 179 1885 221 2033 266 2169 312 2297 359
116 122 132 150 171 195 22 25 28
3000 9251260 069 1345 086 1498 121 1651 161 1799 204 1941 248 2070 295 2206 344 2333 394
132 136 144 162 182 20 23 25 28
3300 10181373 089 1448 107 1588 144 1727 186 1866 231 2001 279 2129 328 2247 379 2370 432
147 151 161 177 195 22 24 26 29
3600 11111486 112 1553 131 1686 171 1813 215 1939 262 2065 312 2188 365 2306 418 2416 473
166 171 182 193 21 23 25 28 30
3900 12031600 140 1658 159 1786 202 1900 247 2020 297 2138 349 2252 404 2366 461
189 194 20 21 23 25 27 29
4200 12961715 172 1766 191 1888 238 1996 285 2106 336 2213 390 2324 448 2430 508
21 21 22 23 24 26 29 31
4500 13881831 208 1878 228 1990 277 2095 328 2193 380 2298 437 2398 496
23 23 24 25 27 28 31
4800 14811946 250 1992 271 2094 322 2196 376 2289 430 2385 488
25 26 27 28 29 31
5100 15742062 296 2105 319 2199 371 2297 429 2388 486
28 28 29 30 32
5400 16662179 349 2219 373 2305 426 2399 487
30 31 32 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
22
TCB-1-18 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1645
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 4843
Maximum bhp at a given rpm mdash (rpm1147)3
Max Motor Frame Size - 182T
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg
0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1500 298486 008 568 012 724 023
43 49 62
1800 357552 011 623 016 755 028 883 042
54 57 67 81
2100 417622 016 683 021 799 034 911 048 1022 065 1123 082
67 68 77 85 99 116
2400 477693 021 749 028 852 041 950 056 1048 073 1147 092 1238 112 1322 133
80 81 90 95 103 120 135 148
2700 536
765 029 817 036 911 050 1001 066 1088 084 1174 103 1262 124 1346 146 1424 169
91 94 103 105 113 125 138 150 164
3000 596838 037 887 045 972 061 1056 078 1136 097 1214 117 1292 138 1369 161 1448 185
102 106 111 115 122 133 142 153 166
3300 656912 048 957 057 1038 074 1115 092 1187 111 1261 132 1331 154 1403 177 1472 202
112 114 120 126 133 141 149 158 168
3600 715987 061 1029 070 1105 089 1176 108 1246 128 1312 149 1379 172 1443 196 1510 222
121 125 131 138 145 152 160 168 178
3900 7751063 075 1102 085 1174 106 1239 126 1305 147 1368 170 1430 193 1491 218 1549 244
133 137 143 149 157 165 173 181 189
4200 8341139 092 1175 103 1244 125 1307 147 1366 169 1428 193 1485 217 1542 243 1599 269
146 149 155 163 171 179 187 195 20
4500 8941215 112 1249 124 1315 147 1375 170 1430 193 1488 218 1544 244 1597 270
160 162 169 176 185 194 20 21
4800 9541292 134 1323 147 1386 172 1444 197 1498 221 1549 246 1604 273
171 174 181 190 199 21 22
5100 10131369 159 1399 172 1458 199 1513 226 1565 252 1615 278
184 187 195 20 21 23
5400 10731446 188 1474 201 1530 229 1584 258 1634 285
197 20 21 22 23
5700 11331523 219 1550 233 1603 263
21 22 22
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
17
183 8
215 8
183 8
23
213 4
131 4
17 5 8
Maximum wMotor Cover
TCB-2-12 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 3274
Outlet Velocity = cfm X 0543
Tip Speed = rpm X 321
Maximum bhp at a given rpm mdash (rpm2315)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
750 4071009 008 1226 014 1587 027
55 67 98
900 4891119 011 1315 018 1648 032 1936 049 2182 067
63 76 102 131 159
1050 5701238 015 1419 023 1728 039 1995 056 2240 076 2456 096
75 85 110 136 164 190
1200 6521363 020 1529 029 1813 046 2070 065 2299 085 2514 108 2710 131 2890 155
89 96 120 142 169 195 22 24
1350 733
1495 027 1643 036 1911 055 2151 076 2372 097 2574 120 2768 145 2948 171 3115 197
104 111 132 152 176 20 22 25 28
1500 8151630 034 1764 044 2018 066 2240 088 2452 111 2647 135 2828 160 3007 187 3174 216
120 129 145 166 186 21 23 26 29
1650 8961767 044 1887 054 2127 077 2338 101 2534 126 2727 151 2903 178 3067 205 3233 235
139 144 159 184 199 22 24 27 30
1800 9781908 055 2018 066 2239 090 2445 117 2630 143 2808 170 2983 198 3145 227
159 165 180 199 22 23 25 28
1950 10592053 068 2151 079 2356 105 2554 134 2731 162 2900 190 3064 220 3225 250
182 188 20 22 23 25 27 29
2100 11412198 083 2286 095 2477 122 2664 152 2839 183 2997 213 3154 244
21 22 22 23 25 27 29
2250 12222344 100 2423 113 2599 141 2777 173 2948 205 3104 238 3250 271
24 24 25 26 27 29 32
2400 13042490 119 2560 133 2726 163 2896 196 3058 230 3212 265
26 26 27 28 30 32
2550 13852637 141 2703 156 2858 187 3016 221 3169 257
28 29 29 31 32
2700 14672785 166 2847 181 2991 214 3138 248
31 31 32 34
2850 15482933 193 2992 209 3126 243 3262 279
34 34 35 37
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
18
TCB-1-13 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2355
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 3435
Maximum bhp at a given rpm mdash (rpm2119)3
Max Motor Frame Size - 145T
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 265660 003 792 005 1019 010
41 51 69
750 331760 005 874 007 1073 013 1254 019
48 58 71 84
900 398864 007 967 010 1146 016 1305 023 1459 030
58 64 75 86 102
1050 464973 009 1067 013 1230 020 1378 027 1512 036 1646 044 1770 053
66 70 80 91 103 120 140
1200 530
1085 013 1171 017 1321 024 1457 032 1585 041 1703 051 1820 061 1933 071 2039 081
72 77 86 96 108 120 136 153 172
1350 5971199 017 1277 022 1419 030 1545 039 1662 048 1777 058 1883 069 1984 080 2089 091
81 85 94 103 114 125 136 151 167
1500 6631316 023 1387 027 1520 037 1637 046 1749 059 1853 067 1957 078 2054 090 2146 102
90 94 102 112 122 132 143 155 169
1650 7301434 029 1499 034 1623 044 1736 055 1839 065 1940 077 2034 088 2128 100 2219 113
100 104 113 123 132 143 153 165 178
1800 7961552 037 1613 042 1729 054 1836 065 1935 076 2029 088 2121 100 2207 113 2293 126
112 115 125 134 144 154 165 177 190
1950 8621672 045 1728 052 1836 064 1939 076 2034 088 2123 100 2209 113 2294 127
124 129 138 147 156 167 178 190
2100 9291792 056 1844 062 1947 076 2044 089 2135 102 2221 115 2302 128
138 142 151 161 170 181 192
2250 9951913 067 1962 075 2058 089 2150 103 2238 117 2321 131
152 157 167 177 186 196
2400 10612034 081 2080 088 2171 104 2258 119 2342 133
169 174 184 194 20
2550 11282155 095 2199 104 2285 120
187 192 20
2700 11942277 112 2319 121
21 21
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
19
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
TCB-2-13 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2971
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 353
Maximum bhp at a given rpm mdash (rpm1933)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
800 353828 008 1026 014 1379 030
38 56 104
1000 442934 011 1108 018 1418 035 1692 055
44 60 101 135
1200 5301048 016 1206 024 1479 042 1731 064 1961 087
58 72 101 130 165
1400 6191171 022 1313 031 1562 051 1784 073 2002 099 2201 126 2391 155
75 87 106 128 160 189 22
1600 707
1300 030 1424 040 1657 062 1865 086 2053 112 2247 141 2425 171 2596 203 2759 237
97 100 115 133 156 184 21 24 27
1800 7961431 039 1545 051 1759 075 1950 101 2134 129 2300 157 2472 189 2636 223 2790 258
114 113 125 144 160 181 21 24 26
2000 8841565 051 1669 063 1868 090 2050 118 2217 148 2381 178 2531 210 2683 244 2836 282
127 127 137 157 170 186 21 23 26
2200 9731700 064 1797 078 1979 107 2152 138 2312 169 2464 202 2612 236 2750 270 2883 306
142 145 156 169 183 198 21 23 26
2400 10611836 081 1928 096 2097 127 2260 160 2413 194 2556 228 2695 264 2831 301 2959 338
164 169 174 182 197 21 23 24 26
2600 11501975 100 2060 116 2219 150 2371 185 2517 221 2656 257 2785 295 2914 334
190 192 193 196 21 23 24 26
2800 12382115 122 2194 140 2343 175 2484 212 2626 251 2758 290 2885 330
21 21 21 22 23 24 26
3000 13272256 148 2329 166 2470 204 2605 243 2737 284 2864 325
24 24 24 24 25 26
3200 14152397 177 2464 196 2600 236 2728 278 2849 320
26 26 26 27 27
3400 15042539 210 2601 230 2731 272 2852 316 2969 361
29 29 30 30 30
3600 15922681 247 2739 267 2863 312
33 33 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
20
TCB-1-16 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2000
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 4384
Maximum bhp at a given rpm mdash (rpm1378)3
Max Motor Frame Size - 182T
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1000 308507 005 612 009 802 017
37 43 59
1250 385584 008 671 012 833 021 985 032
45 49 62 81
1500 462668 011 743 016 884 026 1016 038 1145 052
54 58 69 84 103
1750 540755 016 821 021 944 032 1065 045 1176 059 1289 075 1392 091
64 68 79 93 105 120 136
2000 617
844 022 904 028 1014 040 1119 054 1225 069 1322 085 1422 102 1517 120 1605 139
76 81 92 104 113 124 140 157 175
2250 694934 030 989 036 1090 049 1185 064 1278 080 1373 097 1460 115 1547 134 1635 154
89 94 107 114 123 133 146 161 179
2500 7711026 039 1077 047 1169 061 1257 076 1342 092 1425 110 1511 130 1591 149 1666 170
104 110 119 126 134 144 156 169 184
2750 8481118 051 1166 059 1252 074 1334 091 1411 107 1489 126 1564 146 1643 167 1717 188
121 124 131 138 147 157 168 181 194
3000 9251210 064 1256 073 1337 090 1412 107 1486 125 1556 144 1627 165 1695 186 1769 209
134 138 145 152 161 171 183 194 21
3250 10031303 080 1347 090 1423 108 1494 127 1563 146 1630 166 1695 186 1760 209 1823 232
149 153 161 169 177 187 199 21 22
3500 10801397 098 1438 109 1511 128 1578 148 1642 169 1706 190 1768 211 1828 233 1889 258
166 170 179 187 195 21 22 23 24
3750 11571491 119 1530 130 1599 152 1663 173 1725 194 1784 216 1844 239 1900 262 1956 286
185 189 197 21 22 23 24 25 27
4000 12341585 143 1622 155 1689 178 1750 200 1809 223 1865 246 1921 270 1976 295
20 21 22 23 24 25 26 28
4250 13111680 170 1714 183 1779 207 1838 231 1893 255 1948 280 1999 304
23 23 24 25 26 28 29
4500 13881775 200 1807 214 1869 240 1926 265 1979 291
25 26 27 28 30
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
21
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
TCB-2-16 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2431
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 432
Maximum bhp at a given rpm mdash (rpm1406)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1200 370668 011 842 020 1137 041
46 61 104
1500 462749 015 899 025 1166 049 1395 077
55 68 102 138
1800 555843 021 969 033 1208 059 1424 089 1616 121
71 77 104 135 168
2100 648944 030 1053 042 1268 071 1461 103 1647 138 1813 175 1972 215
83 88 111 134 166 196 22
2400 740
1047 040 1144 054 1336 085 1518 120 1684 157 1847 197 1996 238 2140 283 2275 329
99 105 120 140 166 195 22 25 27
2700 8331152 053 1243 068 1412 101 1579 139 1739 179 1885 221 2033 266 2169 312 2297 359
116 122 132 150 171 195 22 25 28
3000 9251260 069 1345 086 1498 121 1651 161 1799 204 1941 248 2070 295 2206 344 2333 394
132 136 144 162 182 20 23 25 28
3300 10181373 089 1448 107 1588 144 1727 186 1866 231 2001 279 2129 328 2247 379 2370 432
147 151 161 177 195 22 24 26 29
3600 11111486 112 1553 131 1686 171 1813 215 1939 262 2065 312 2188 365 2306 418 2416 473
166 171 182 193 21 23 25 28 30
3900 12031600 140 1658 159 1786 202 1900 247 2020 297 2138 349 2252 404 2366 461
189 194 20 21 23 25 27 29
4200 12961715 172 1766 191 1888 238 1996 285 2106 336 2213 390 2324 448 2430 508
21 21 22 23 24 26 29 31
4500 13881831 208 1878 228 1990 277 2095 328 2193 380 2298 437 2398 496
23 23 24 25 27 28 31
4800 14811946 250 1992 271 2094 322 2196 376 2289 430 2385 488
25 26 27 28 29 31
5100 15742062 296 2105 319 2199 371 2297 429 2388 486
28 28 29 30 32
5400 16662179 349 2219 373 2305 426 2399 487
30 31 32 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
22
TCB-1-18 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1645
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 4843
Maximum bhp at a given rpm mdash (rpm1147)3
Max Motor Frame Size - 182T
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg
0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1500 298486 008 568 012 724 023
43 49 62
1800 357552 011 623 016 755 028 883 042
54 57 67 81
2100 417622 016 683 021 799 034 911 048 1022 065 1123 082
67 68 77 85 99 116
2400 477693 021 749 028 852 041 950 056 1048 073 1147 092 1238 112 1322 133
80 81 90 95 103 120 135 148
2700 536
765 029 817 036 911 050 1001 066 1088 084 1174 103 1262 124 1346 146 1424 169
91 94 103 105 113 125 138 150 164
3000 596838 037 887 045 972 061 1056 078 1136 097 1214 117 1292 138 1369 161 1448 185
102 106 111 115 122 133 142 153 166
3300 656912 048 957 057 1038 074 1115 092 1187 111 1261 132 1331 154 1403 177 1472 202
112 114 120 126 133 141 149 158 168
3600 715987 061 1029 070 1105 089 1176 108 1246 128 1312 149 1379 172 1443 196 1510 222
121 125 131 138 145 152 160 168 178
3900 7751063 075 1102 085 1174 106 1239 126 1305 147 1368 170 1430 193 1491 218 1549 244
133 137 143 149 157 165 173 181 189
4200 8341139 092 1175 103 1244 125 1307 147 1366 169 1428 193 1485 217 1542 243 1599 269
146 149 155 163 171 179 187 195 20
4500 8941215 112 1249 124 1315 147 1375 170 1430 193 1488 218 1544 244 1597 270
160 162 169 176 185 194 20 21
4800 9541292 134 1323 147 1386 172 1444 197 1498 221 1549 246 1604 273
171 174 181 190 199 21 22
5100 10131369 159 1399 172 1458 199 1513 226 1565 252 1615 278
184 187 195 20 21 23
5400 10731446 188 1474 201 1530 229 1584 258 1634 285
197 20 21 22 23
5700 11331523 219 1550 233 1603 263
21 22 22
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
18
TCB-1-13 Level 1 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2355
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 3435
Maximum bhp at a given rpm mdash (rpm2119)3
Max Motor Frame Size - 145T
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
600 265660 003 792 005 1019 010
41 51 69
750 331760 005 874 007 1073 013 1254 019
48 58 71 84
900 398864 007 967 010 1146 016 1305 023 1459 030
58 64 75 86 102
1050 464973 009 1067 013 1230 020 1378 027 1512 036 1646 044 1770 053
66 70 80 91 103 120 140
1200 530
1085 013 1171 017 1321 024 1457 032 1585 041 1703 051 1820 061 1933 071 2039 081
72 77 86 96 108 120 136 153 172
1350 5971199 017 1277 022 1419 030 1545 039 1662 048 1777 058 1883 069 1984 080 2089 091
81 85 94 103 114 125 136 151 167
1500 6631316 023 1387 027 1520 037 1637 046 1749 059 1853 067 1957 078 2054 090 2146 102
90 94 102 112 122 132 143 155 169
1650 7301434 029 1499 034 1623 044 1736 055 1839 065 1940 077 2034 088 2128 100 2219 113
100 104 113 123 132 143 153 165 178
1800 7961552 037 1613 042 1729 054 1836 065 1935 076 2029 088 2121 100 2207 113 2293 126
112 115 125 134 144 154 165 177 190
1950 8621672 045 1728 052 1836 064 1939 076 2034 088 2123 100 2209 113 2294 127
124 129 138 147 156 167 178 190
2100 9291792 056 1844 062 1947 076 2044 089 2135 102 2221 115 2302 128
138 142 151 161 170 181 192
2250 9951913 067 1962 075 2058 089 2150 103 2238 117 2321 131
152 157 167 177 186 196
2400 10612034 081 2080 088 2171 104 2258 119 2342 133
169 174 184 194 20
2550 11282155 095 2199 104 2285 120
187 192 20
2700 11942277 112 2319 121
21 21
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
19
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
TCB-2-13 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2971
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 353
Maximum bhp at a given rpm mdash (rpm1933)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
800 353828 008 1026 014 1379 030
38 56 104
1000 442934 011 1108 018 1418 035 1692 055
44 60 101 135
1200 5301048 016 1206 024 1479 042 1731 064 1961 087
58 72 101 130 165
1400 6191171 022 1313 031 1562 051 1784 073 2002 099 2201 126 2391 155
75 87 106 128 160 189 22
1600 707
1300 030 1424 040 1657 062 1865 086 2053 112 2247 141 2425 171 2596 203 2759 237
97 100 115 133 156 184 21 24 27
1800 7961431 039 1545 051 1759 075 1950 101 2134 129 2300 157 2472 189 2636 223 2790 258
114 113 125 144 160 181 21 24 26
2000 8841565 051 1669 063 1868 090 2050 118 2217 148 2381 178 2531 210 2683 244 2836 282
127 127 137 157 170 186 21 23 26
2200 9731700 064 1797 078 1979 107 2152 138 2312 169 2464 202 2612 236 2750 270 2883 306
142 145 156 169 183 198 21 23 26
2400 10611836 081 1928 096 2097 127 2260 160 2413 194 2556 228 2695 264 2831 301 2959 338
164 169 174 182 197 21 23 24 26
2600 11501975 100 2060 116 2219 150 2371 185 2517 221 2656 257 2785 295 2914 334
190 192 193 196 21 23 24 26
2800 12382115 122 2194 140 2343 175 2484 212 2626 251 2758 290 2885 330
21 21 21 22 23 24 26
3000 13272256 148 2329 166 2470 204 2605 243 2737 284 2864 325
24 24 24 24 25 26
3200 14152397 177 2464 196 2600 236 2728 278 2849 320
26 26 26 27 27
3400 15042539 210 2601 230 2731 272 2852 316 2969 361
29 29 30 30 30
3600 15922681 247 2739 267 2863 312
33 33 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
20
TCB-1-16 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2000
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 4384
Maximum bhp at a given rpm mdash (rpm1378)3
Max Motor Frame Size - 182T
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1000 308507 005 612 009 802 017
37 43 59
1250 385584 008 671 012 833 021 985 032
45 49 62 81
1500 462668 011 743 016 884 026 1016 038 1145 052
54 58 69 84 103
1750 540755 016 821 021 944 032 1065 045 1176 059 1289 075 1392 091
64 68 79 93 105 120 136
2000 617
844 022 904 028 1014 040 1119 054 1225 069 1322 085 1422 102 1517 120 1605 139
76 81 92 104 113 124 140 157 175
2250 694934 030 989 036 1090 049 1185 064 1278 080 1373 097 1460 115 1547 134 1635 154
89 94 107 114 123 133 146 161 179
2500 7711026 039 1077 047 1169 061 1257 076 1342 092 1425 110 1511 130 1591 149 1666 170
104 110 119 126 134 144 156 169 184
2750 8481118 051 1166 059 1252 074 1334 091 1411 107 1489 126 1564 146 1643 167 1717 188
121 124 131 138 147 157 168 181 194
3000 9251210 064 1256 073 1337 090 1412 107 1486 125 1556 144 1627 165 1695 186 1769 209
134 138 145 152 161 171 183 194 21
3250 10031303 080 1347 090 1423 108 1494 127 1563 146 1630 166 1695 186 1760 209 1823 232
149 153 161 169 177 187 199 21 22
3500 10801397 098 1438 109 1511 128 1578 148 1642 169 1706 190 1768 211 1828 233 1889 258
166 170 179 187 195 21 22 23 24
3750 11571491 119 1530 130 1599 152 1663 173 1725 194 1784 216 1844 239 1900 262 1956 286
185 189 197 21 22 23 24 25 27
4000 12341585 143 1622 155 1689 178 1750 200 1809 223 1865 246 1921 270 1976 295
20 21 22 23 24 25 26 28
4250 13111680 170 1714 183 1779 207 1838 231 1893 255 1948 280 1999 304
23 23 24 25 26 28 29
4500 13881775 200 1807 214 1869 240 1926 265 1979 291
25 26 27 28 30
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
21
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
TCB-2-16 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2431
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 432
Maximum bhp at a given rpm mdash (rpm1406)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1200 370668 011 842 020 1137 041
46 61 104
1500 462749 015 899 025 1166 049 1395 077
55 68 102 138
1800 555843 021 969 033 1208 059 1424 089 1616 121
71 77 104 135 168
2100 648944 030 1053 042 1268 071 1461 103 1647 138 1813 175 1972 215
83 88 111 134 166 196 22
2400 740
1047 040 1144 054 1336 085 1518 120 1684 157 1847 197 1996 238 2140 283 2275 329
99 105 120 140 166 195 22 25 27
2700 8331152 053 1243 068 1412 101 1579 139 1739 179 1885 221 2033 266 2169 312 2297 359
116 122 132 150 171 195 22 25 28
3000 9251260 069 1345 086 1498 121 1651 161 1799 204 1941 248 2070 295 2206 344 2333 394
132 136 144 162 182 20 23 25 28
3300 10181373 089 1448 107 1588 144 1727 186 1866 231 2001 279 2129 328 2247 379 2370 432
147 151 161 177 195 22 24 26 29
3600 11111486 112 1553 131 1686 171 1813 215 1939 262 2065 312 2188 365 2306 418 2416 473
166 171 182 193 21 23 25 28 30
3900 12031600 140 1658 159 1786 202 1900 247 2020 297 2138 349 2252 404 2366 461
189 194 20 21 23 25 27 29
4200 12961715 172 1766 191 1888 238 1996 285 2106 336 2213 390 2324 448 2430 508
21 21 22 23 24 26 29 31
4500 13881831 208 1878 228 1990 277 2095 328 2193 380 2298 437 2398 496
23 23 24 25 27 28 31
4800 14811946 250 1992 271 2094 322 2196 376 2289 430 2385 488
25 26 27 28 29 31
5100 15742062 296 2105 319 2199 371 2297 429 2388 486
28 28 29 30 32
5400 16662179 349 2219 373 2305 426 2399 487
30 31 32 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
22
TCB-1-18 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1645
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 4843
Maximum bhp at a given rpm mdash (rpm1147)3
Max Motor Frame Size - 182T
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg
0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1500 298486 008 568 012 724 023
43 49 62
1800 357552 011 623 016 755 028 883 042
54 57 67 81
2100 417622 016 683 021 799 034 911 048 1022 065 1123 082
67 68 77 85 99 116
2400 477693 021 749 028 852 041 950 056 1048 073 1147 092 1238 112 1322 133
80 81 90 95 103 120 135 148
2700 536
765 029 817 036 911 050 1001 066 1088 084 1174 103 1262 124 1346 146 1424 169
91 94 103 105 113 125 138 150 164
3000 596838 037 887 045 972 061 1056 078 1136 097 1214 117 1292 138 1369 161 1448 185
102 106 111 115 122 133 142 153 166
3300 656912 048 957 057 1038 074 1115 092 1187 111 1261 132 1331 154 1403 177 1472 202
112 114 120 126 133 141 149 158 168
3600 715987 061 1029 070 1105 089 1176 108 1246 128 1312 149 1379 172 1443 196 1510 222
121 125 131 138 145 152 160 168 178
3900 7751063 075 1102 085 1174 106 1239 126 1305 147 1368 170 1430 193 1491 218 1549 244
133 137 143 149 157 165 173 181 189
4200 8341139 092 1175 103 1244 125 1307 147 1366 169 1428 193 1485 217 1542 243 1599 269
146 149 155 163 171 179 187 195 20
4500 8941215 112 1249 124 1315 147 1375 170 1430 193 1488 218 1544 244 1597 270
160 162 169 176 185 194 20 21
4800 9541292 134 1323 147 1386 172 1444 197 1498 221 1549 246 1604 273
171 174 181 190 199 21 22
5100 10131369 159 1399 172 1458 199 1513 226 1565 252 1615 278
184 187 195 20 21 23
5400 10731446 188 1474 201 1530 229 1584 258 1634 285
197 20 21 22 23
5700 11331523 219 1550 233 1603 263
21 22 22
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 1932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
19
203 8
23 5 8
197 8241 2
231 4
137 8
19
Maximum wMotor Cover
TCB-2-13 Level 2 Construction
CFM X 100
msup3hr X 100
Dimensions shown in inches
Maximum rpm mdash 2971
Outlet Velocity = cfm X 0442
Tip Speed = rpm X 353
Maximum bhp at a given rpm mdash (rpm1933)3
Max Motor Frame Size - 182T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
800 353828 008 1026 014 1379 030
38 56 104
1000 442934 011 1108 018 1418 035 1692 055
44 60 101 135
1200 5301048 016 1206 024 1479 042 1731 064 1961 087
58 72 101 130 165
1400 6191171 022 1313 031 1562 051 1784 073 2002 099 2201 126 2391 155
75 87 106 128 160 189 22
1600 707
1300 030 1424 040 1657 062 1865 086 2053 112 2247 141 2425 171 2596 203 2759 237
97 100 115 133 156 184 21 24 27
1800 7961431 039 1545 051 1759 075 1950 101 2134 129 2300 157 2472 189 2636 223 2790 258
114 113 125 144 160 181 21 24 26
2000 8841565 051 1669 063 1868 090 2050 118 2217 148 2381 178 2531 210 2683 244 2836 282
127 127 137 157 170 186 21 23 26
2200 9731700 064 1797 078 1979 107 2152 138 2312 169 2464 202 2612 236 2750 270 2883 306
142 145 156 169 183 198 21 23 26
2400 10611836 081 1928 096 2097 127 2260 160 2413 194 2556 228 2695 264 2831 301 2959 338
164 169 174 182 197 21 23 24 26
2600 11501975 100 2060 116 2219 150 2371 185 2517 221 2656 257 2785 295 2914 334
190 192 193 196 21 23 24 26
2800 12382115 122 2194 140 2343 175 2484 212 2626 251 2758 290 2885 330
21 21 21 22 23 24 26
3000 13272256 148 2329 166 2470 204 2605 243 2737 284 2864 325
24 24 24 24 25 26
3200 14152397 177 2464 196 2600 236 2728 278 2849 320
26 26 26 27 27
3400 15042539 210 2601 230 2731 272 2852 316 2969 361
29 29 30 30 30
3600 15922681 247 2739 267 2863 312
33 33 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
20
TCB-1-16 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2000
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 4384
Maximum bhp at a given rpm mdash (rpm1378)3
Max Motor Frame Size - 182T
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1000 308507 005 612 009 802 017
37 43 59
1250 385584 008 671 012 833 021 985 032
45 49 62 81
1500 462668 011 743 016 884 026 1016 038 1145 052
54 58 69 84 103
1750 540755 016 821 021 944 032 1065 045 1176 059 1289 075 1392 091
64 68 79 93 105 120 136
2000 617
844 022 904 028 1014 040 1119 054 1225 069 1322 085 1422 102 1517 120 1605 139
76 81 92 104 113 124 140 157 175
2250 694934 030 989 036 1090 049 1185 064 1278 080 1373 097 1460 115 1547 134 1635 154
89 94 107 114 123 133 146 161 179
2500 7711026 039 1077 047 1169 061 1257 076 1342 092 1425 110 1511 130 1591 149 1666 170
104 110 119 126 134 144 156 169 184
2750 8481118 051 1166 059 1252 074 1334 091 1411 107 1489 126 1564 146 1643 167 1717 188
121 124 131 138 147 157 168 181 194
3000 9251210 064 1256 073 1337 090 1412 107 1486 125 1556 144 1627 165 1695 186 1769 209
134 138 145 152 161 171 183 194 21
3250 10031303 080 1347 090 1423 108 1494 127 1563 146 1630 166 1695 186 1760 209 1823 232
149 153 161 169 177 187 199 21 22
3500 10801397 098 1438 109 1511 128 1578 148 1642 169 1706 190 1768 211 1828 233 1889 258
166 170 179 187 195 21 22 23 24
3750 11571491 119 1530 130 1599 152 1663 173 1725 194 1784 216 1844 239 1900 262 1956 286
185 189 197 21 22 23 24 25 27
4000 12341585 143 1622 155 1689 178 1750 200 1809 223 1865 246 1921 270 1976 295
20 21 22 23 24 25 26 28
4250 13111680 170 1714 183 1779 207 1838 231 1893 255 1948 280 1999 304
23 23 24 25 26 28 29
4500 13881775 200 1807 214 1869 240 1926 265 1979 291
25 26 27 28 30
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
21
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
TCB-2-16 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2431
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 432
Maximum bhp at a given rpm mdash (rpm1406)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1200 370668 011 842 020 1137 041
46 61 104
1500 462749 015 899 025 1166 049 1395 077
55 68 102 138
1800 555843 021 969 033 1208 059 1424 089 1616 121
71 77 104 135 168
2100 648944 030 1053 042 1268 071 1461 103 1647 138 1813 175 1972 215
83 88 111 134 166 196 22
2400 740
1047 040 1144 054 1336 085 1518 120 1684 157 1847 197 1996 238 2140 283 2275 329
99 105 120 140 166 195 22 25 27
2700 8331152 053 1243 068 1412 101 1579 139 1739 179 1885 221 2033 266 2169 312 2297 359
116 122 132 150 171 195 22 25 28
3000 9251260 069 1345 086 1498 121 1651 161 1799 204 1941 248 2070 295 2206 344 2333 394
132 136 144 162 182 20 23 25 28
3300 10181373 089 1448 107 1588 144 1727 186 1866 231 2001 279 2129 328 2247 379 2370 432
147 151 161 177 195 22 24 26 29
3600 11111486 112 1553 131 1686 171 1813 215 1939 262 2065 312 2188 365 2306 418 2416 473
166 171 182 193 21 23 25 28 30
3900 12031600 140 1658 159 1786 202 1900 247 2020 297 2138 349 2252 404 2366 461
189 194 20 21 23 25 27 29
4200 12961715 172 1766 191 1888 238 1996 285 2106 336 2213 390 2324 448 2430 508
21 21 22 23 24 26 29 31
4500 13881831 208 1878 228 1990 277 2095 328 2193 380 2298 437 2398 496
23 23 24 25 27 28 31
4800 14811946 250 1992 271 2094 322 2196 376 2289 430 2385 488
25 26 27 28 29 31
5100 15742062 296 2105 319 2199 371 2297 429 2388 486
28 28 29 30 32
5400 16662179 349 2219 373 2305 426 2399 487
30 31 32 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
22
TCB-1-18 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1645
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 4843
Maximum bhp at a given rpm mdash (rpm1147)3
Max Motor Frame Size - 182T
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg
0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1500 298486 008 568 012 724 023
43 49 62
1800 357552 011 623 016 755 028 883 042
54 57 67 81
2100 417622 016 683 021 799 034 911 048 1022 065 1123 082
67 68 77 85 99 116
2400 477693 021 749 028 852 041 950 056 1048 073 1147 092 1238 112 1322 133
80 81 90 95 103 120 135 148
2700 536
765 029 817 036 911 050 1001 066 1088 084 1174 103 1262 124 1346 146 1424 169
91 94 103 105 113 125 138 150 164
3000 596838 037 887 045 972 061 1056 078 1136 097 1214 117 1292 138 1369 161 1448 185
102 106 111 115 122 133 142 153 166
3300 656912 048 957 057 1038 074 1115 092 1187 111 1261 132 1331 154 1403 177 1472 202
112 114 120 126 133 141 149 158 168
3600 715987 061 1029 070 1105 089 1176 108 1246 128 1312 149 1379 172 1443 196 1510 222
121 125 131 138 145 152 160 168 178
3900 7751063 075 1102 085 1174 106 1239 126 1305 147 1368 170 1430 193 1491 218 1549 244
133 137 143 149 157 165 173 181 189
4200 8341139 092 1175 103 1244 125 1307 147 1366 169 1428 193 1485 217 1542 243 1599 269
146 149 155 163 171 179 187 195 20
4500 8941215 112 1249 124 1315 147 1375 170 1430 193 1488 218 1544 244 1597 270
160 162 169 176 185 194 20 21
4800 9541292 134 1323 147 1386 172 1444 197 1498 221 1549 246 1604 273
171 174 181 190 199 21 22
5100 10131369 159 1399 172 1458 199 1513 226 1565 252 1615 278
184 187 195 20 21 23
5400 10731446 188 1474 201 1530 229 1584 258 1634 285
197 20 21 22 23
5700 11331523 219 1550 233 1603 263
21 22 22
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
20
TCB-1-16 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2000
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 4384
Maximum bhp at a given rpm mdash (rpm1378)3
Max Motor Frame Size - 182T
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1000 308507 005 612 009 802 017
37 43 59
1250 385584 008 671 012 833 021 985 032
45 49 62 81
1500 462668 011 743 016 884 026 1016 038 1145 052
54 58 69 84 103
1750 540755 016 821 021 944 032 1065 045 1176 059 1289 075 1392 091
64 68 79 93 105 120 136
2000 617
844 022 904 028 1014 040 1119 054 1225 069 1322 085 1422 102 1517 120 1605 139
76 81 92 104 113 124 140 157 175
2250 694934 030 989 036 1090 049 1185 064 1278 080 1373 097 1460 115 1547 134 1635 154
89 94 107 114 123 133 146 161 179
2500 7711026 039 1077 047 1169 061 1257 076 1342 092 1425 110 1511 130 1591 149 1666 170
104 110 119 126 134 144 156 169 184
2750 8481118 051 1166 059 1252 074 1334 091 1411 107 1489 126 1564 146 1643 167 1717 188
121 124 131 138 147 157 168 181 194
3000 9251210 064 1256 073 1337 090 1412 107 1486 125 1556 144 1627 165 1695 186 1769 209
134 138 145 152 161 171 183 194 21
3250 10031303 080 1347 090 1423 108 1494 127 1563 146 1630 166 1695 186 1760 209 1823 232
149 153 161 169 177 187 199 21 22
3500 10801397 098 1438 109 1511 128 1578 148 1642 169 1706 190 1768 211 1828 233 1889 258
166 170 179 187 195 21 22 23 24
3750 11571491 119 1530 130 1599 152 1663 173 1725 194 1784 216 1844 239 1900 262 1956 286
185 189 197 21 22 23 24 25 27
4000 12341585 143 1622 155 1689 178 1750 200 1809 223 1865 246 1921 270 1976 295
20 21 22 23 24 25 26 28
4250 13111680 170 1714 183 1779 207 1838 231 1893 255 1948 280 1999 304
23 23 24 25 26 28 29
4500 13881775 200 1807 214 1869 240 1926 265 1979 291
25 26 27 28 30
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
21
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
TCB-2-16 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2431
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 432
Maximum bhp at a given rpm mdash (rpm1406)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1200 370668 011 842 020 1137 041
46 61 104
1500 462749 015 899 025 1166 049 1395 077
55 68 102 138
1800 555843 021 969 033 1208 059 1424 089 1616 121
71 77 104 135 168
2100 648944 030 1053 042 1268 071 1461 103 1647 138 1813 175 1972 215
83 88 111 134 166 196 22
2400 740
1047 040 1144 054 1336 085 1518 120 1684 157 1847 197 1996 238 2140 283 2275 329
99 105 120 140 166 195 22 25 27
2700 8331152 053 1243 068 1412 101 1579 139 1739 179 1885 221 2033 266 2169 312 2297 359
116 122 132 150 171 195 22 25 28
3000 9251260 069 1345 086 1498 121 1651 161 1799 204 1941 248 2070 295 2206 344 2333 394
132 136 144 162 182 20 23 25 28
3300 10181373 089 1448 107 1588 144 1727 186 1866 231 2001 279 2129 328 2247 379 2370 432
147 151 161 177 195 22 24 26 29
3600 11111486 112 1553 131 1686 171 1813 215 1939 262 2065 312 2188 365 2306 418 2416 473
166 171 182 193 21 23 25 28 30
3900 12031600 140 1658 159 1786 202 1900 247 2020 297 2138 349 2252 404 2366 461
189 194 20 21 23 25 27 29
4200 12961715 172 1766 191 1888 238 1996 285 2106 336 2213 390 2324 448 2430 508
21 21 22 23 24 26 29 31
4500 13881831 208 1878 228 1990 277 2095 328 2193 380 2298 437 2398 496
23 23 24 25 27 28 31
4800 14811946 250 1992 271 2094 322 2196 376 2289 430 2385 488
25 26 27 28 29 31
5100 15742062 296 2105 319 2199 371 2297 429 2388 486
28 28 29 30 32
5400 16662179 349 2219 373 2305 426 2399 487
30 31 32 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
22
TCB-1-18 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1645
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 4843
Maximum bhp at a given rpm mdash (rpm1147)3
Max Motor Frame Size - 182T
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg
0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1500 298486 008 568 012 724 023
43 49 62
1800 357552 011 623 016 755 028 883 042
54 57 67 81
2100 417622 016 683 021 799 034 911 048 1022 065 1123 082
67 68 77 85 99 116
2400 477693 021 749 028 852 041 950 056 1048 073 1147 092 1238 112 1322 133
80 81 90 95 103 120 135 148
2700 536
765 029 817 036 911 050 1001 066 1088 084 1174 103 1262 124 1346 146 1424 169
91 94 103 105 113 125 138 150 164
3000 596838 037 887 045 972 061 1056 078 1136 097 1214 117 1292 138 1369 161 1448 185
102 106 111 115 122 133 142 153 166
3300 656912 048 957 057 1038 074 1115 092 1187 111 1261 132 1331 154 1403 177 1472 202
112 114 120 126 133 141 149 158 168
3600 715987 061 1029 070 1105 089 1176 108 1246 128 1312 149 1379 172 1443 196 1510 222
121 125 131 138 145 152 160 168 178
3900 7751063 075 1102 085 1174 106 1239 126 1305 147 1368 170 1430 193 1491 218 1549 244
133 137 143 149 157 165 173 181 189
4200 8341139 092 1175 103 1244 125 1307 147 1366 169 1428 193 1485 217 1542 243 1599 269
146 149 155 163 171 179 187 195 20
4500 8941215 112 1249 124 1315 147 1375 170 1430 193 1488 218 1544 244 1597 270
160 162 169 176 185 194 20 21
4800 9541292 134 1323 147 1386 172 1444 197 1498 221 1549 246 1604 273
171 174 181 190 199 21 22
5100 10131369 159 1399 172 1458 199 1513 226 1565 252 1615 278
184 187 195 20 21 23
5400 10731446 188 1474 201 1530 229 1584 258 1634 285
197 20 21 22 23
5700 11331523 219 1550 233 1603 263
21 22 22
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
21
243 8
275 8
23 7 8281 2
26
161 8
217 8
Maximum wMotor Cover
TCB-2-16 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2431
Outlet Velocity = cfm X 0309
Tip Speed = rpm X 432
Maximum bhp at a given rpm mdash (rpm1406)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1200 370668 011 842 020 1137 041
46 61 104
1500 462749 015 899 025 1166 049 1395 077
55 68 102 138
1800 555843 021 969 033 1208 059 1424 089 1616 121
71 77 104 135 168
2100 648944 030 1053 042 1268 071 1461 103 1647 138 1813 175 1972 215
83 88 111 134 166 196 22
2400 740
1047 040 1144 054 1336 085 1518 120 1684 157 1847 197 1996 238 2140 283 2275 329
99 105 120 140 166 195 22 25 27
2700 8331152 053 1243 068 1412 101 1579 139 1739 179 1885 221 2033 266 2169 312 2297 359
116 122 132 150 171 195 22 25 28
3000 9251260 069 1345 086 1498 121 1651 161 1799 204 1941 248 2070 295 2206 344 2333 394
132 136 144 162 182 20 23 25 28
3300 10181373 089 1448 107 1588 144 1727 186 1866 231 2001 279 2129 328 2247 379 2370 432
147 151 161 177 195 22 24 26 29
3600 11111486 112 1553 131 1686 171 1813 215 1939 262 2065 312 2188 365 2306 418 2416 473
166 171 182 193 21 23 25 28 30
3900 12031600 140 1658 159 1786 202 1900 247 2020 297 2138 349 2252 404 2366 461
189 194 20 21 23 25 27 29
4200 12961715 172 1766 191 1888 238 1996 285 2106 336 2213 390 2324 448 2430 508
21 21 22 23 24 26 29 31
4500 13881831 208 1878 228 1990 277 2095 328 2193 380 2298 437 2398 496
23 23 24 25 27 28 31
4800 14811946 250 1992 271 2094 322 2196 376 2289 430 2385 488
25 26 27 28 29 31
5100 15742062 296 2105 319 2199 371 2297 429 2388 486
28 28 29 30 32
5400 16662179 349 2219 373 2305 426 2399 487
30 31 32 33
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
22
TCB-1-18 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1645
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 4843
Maximum bhp at a given rpm mdash (rpm1147)3
Max Motor Frame Size - 182T
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg
0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1500 298486 008 568 012 724 023
43 49 62
1800 357552 011 623 016 755 028 883 042
54 57 67 81
2100 417622 016 683 021 799 034 911 048 1022 065 1123 082
67 68 77 85 99 116
2400 477693 021 749 028 852 041 950 056 1048 073 1147 092 1238 112 1322 133
80 81 90 95 103 120 135 148
2700 536
765 029 817 036 911 050 1001 066 1088 084 1174 103 1262 124 1346 146 1424 169
91 94 103 105 113 125 138 150 164
3000 596838 037 887 045 972 061 1056 078 1136 097 1214 117 1292 138 1369 161 1448 185
102 106 111 115 122 133 142 153 166
3300 656912 048 957 057 1038 074 1115 092 1187 111 1261 132 1331 154 1403 177 1472 202
112 114 120 126 133 141 149 158 168
3600 715987 061 1029 070 1105 089 1176 108 1246 128 1312 149 1379 172 1443 196 1510 222
121 125 131 138 145 152 160 168 178
3900 7751063 075 1102 085 1174 106 1239 126 1305 147 1368 170 1430 193 1491 218 1549 244
133 137 143 149 157 165 173 181 189
4200 8341139 092 1175 103 1244 125 1307 147 1366 169 1428 193 1485 217 1542 243 1599 269
146 149 155 163 171 179 187 195 20
4500 8941215 112 1249 124 1315 147 1375 170 1430 193 1488 218 1544 244 1597 270
160 162 169 176 185 194 20 21
4800 9541292 134 1323 147 1386 172 1444 197 1498 221 1549 246 1604 273
171 174 181 190 199 21 22
5100 10131369 159 1399 172 1458 199 1513 226 1565 252 1615 278
184 187 195 20 21 23
5400 10731446 188 1474 201 1530 229 1584 258 1634 285
197 20 21 22 23
5700 11331523 219 1550 233 1603 263
21 22 22
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2232
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
22
TCB-1-18 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1645
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 4843
Maximum bhp at a given rpm mdash (rpm1147)3
Max Motor Frame Size - 182T
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg
0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1500 298486 008 568 012 724 023
43 49 62
1800 357552 011 623 016 755 028 883 042
54 57 67 81
2100 417622 016 683 021 799 034 911 048 1022 065 1123 082
67 68 77 85 99 116
2400 477693 021 749 028 852 041 950 056 1048 073 1147 092 1238 112 1322 133
80 81 90 95 103 120 135 148
2700 536
765 029 817 036 911 050 1001 066 1088 084 1174 103 1262 124 1346 146 1424 169
91 94 103 105 113 125 138 150 164
3000 596838 037 887 045 972 061 1056 078 1136 097 1214 117 1292 138 1369 161 1448 185
102 106 111 115 122 133 142 153 166
3300 656912 048 957 057 1038 074 1115 092 1187 111 1261 132 1331 154 1403 177 1472 202
112 114 120 126 133 141 149 158 168
3600 715987 061 1029 070 1105 089 1176 108 1246 128 1312 149 1379 172 1443 196 1510 222
121 125 131 138 145 152 160 168 178
3900 7751063 075 1102 085 1174 106 1239 126 1305 147 1368 170 1430 193 1491 218 1549 244
133 137 143 149 157 165 173 181 189
4200 8341139 092 1175 103 1244 125 1307 147 1366 169 1428 193 1485 217 1542 243 1599 269
146 149 155 163 171 179 187 195 20
4500 8941215 112 1249 124 1315 147 1375 170 1430 193 1488 218 1544 244 1597 270
160 162 169 176 185 194 20 21
4800 9541292 134 1323 147 1386 172 1444 197 1498 221 1549 246 1604 273
171 174 181 190 199 21 22
5100 10131369 159 1399 172 1458 199 1513 226 1565 252 1615 278
184 187 195 20 21 23
5400 10731446 188 1474 201 1530 229 1584 258 1634 285
197 20 21 22 23
5700 11331523 219 1550 233 1603 263
21 22 22
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2332
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
23
303 8
335 8
263 831
291 4
183 8
261 8
Maximum wMotor Cover
TCB-2-18 Level 2 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 2099
Outlet Velocity = cfm X 0199
Tip Speed = rpm X 478
Maximum bhp at a given rpm mdash (rpm1224)3
Max Motor Frame Size - 184T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1400 278588 011 725 020
52 62
1750 347666 016 785 026 995 050
68 75 94
2100 417752 023 857 034 1045 061 1214 090 1369 122
96 89 101 125 152
2450 487843 031 936 044 1105 073 1259 105 1404 140 1536 176
112 104 113 131 157 179
2800 556
937 042 1021 057 1177 089 1318 123 1450 161 1577 200 1697 241 1812 283
126 121 129 145 167 184 20 23
3150 6261033 055 1110 072 1253 107 1384 144 1508 184 1624 226 1738 270 1847 315 1949 362
139 139 146 163 178 191 21 23 25
3500 6951131 071 1202 090 1333 128 1457 169 1571 211 1682 255 1787 302 1889 350 1991 400
157 158 166 185 193 20 21 23 26
3850 7651230 091 1296 111 1416 152 1532 196 1642 241 1743 288 1845 337 1942 388 2032 440
177 180 191 20 21 22 23 24 26
4200 8341331 114 1391 135 1505 180 1612 227 1715 275 1815 325 1906 376 2000 430 2090 485
20 21 21 22 23 24 25 26 28
4550 9041433 141 1488 164 1595 212 1694 262 1793 314 1887 367 1977 421 2062 476
23 23 23 24 24 25 27 28
4900 9741535 173 1585 196 1687 248 1781 301 1873 356 1963 412 2050 469
25 25 25 26 26 27 29
5250 10431638 209 1683 233 1781 289 1871 345 1955 403 2042 462
27 27 27 28 28 30
5600 11131741 250 1784 276 1875 334 1961 394 2042 454
29 29 29 30 31
5950 11821844 296 1885 324 1971 384 2053 448
31 31 31 33
6300 12521948 348 1987 377 2067 440
33 33 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2432
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
24
TCB-1-22 Level 1 Construction
CFM X 1000
msup3hr X 1000
Dimensions shown in inches
Maximum rpm mdash 1375
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 5595
Maximum bhp at a given rpm mdash (rpm962)3
Max Motor Frame Size - 182T
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1600 221388 007 477 012
32 45
2000 277442 010 516 015 656 030
39 50 67
2400 332502 014 566 020 687 036 800 054 900 073
49 56 69 86 104
2800 387564 019 621 027 727 043 829 062 926 083 1013 105
60 64 76 86 103 121
3200 443
629 026 680 034 776 052 865 072 955 095 1039 119 1119 144 1192 169
71 75 83 93 105 123 142 163
3600 498695 035 741 044 829 063 911 085 991 108 1070 134 1145 160 1218 188 1286 216
85 87 92 102 114 127 145 165 190
4000 554762 046 804 056 884 076 960 099 1033 123 1105 149 1177 178 1244 208 1312 238
97 98 103 114 126 140 151 166 189
4400 609831 059 869 070 943 092 1014 116 1082 142 1147 168 1213 197 1278 229 1340 261
109 111 118 129 142 153 163 174 189
4800 664900 074 935 086 1004 110 1068 135 1133 163 1195 191 1254 220 1314 251
124 126 135 146 159 168 177 188
5200 720969 092 1002 105 1065 131 1127 158 1187 186 1244 216 1302 247 1356 278
140 143 152 166 174 183 193 20
5600 7751038 113 1069 126 1129 154 1187 183 1242 212 1298 244 1351 277
158 163 173 181 19 20 21
6000 8311108 136 1137 151 1193 181 1248 211 1301 242 1352 275
179 182 189 198 21 22
6400 8861178 163 1206 179 1259 210 1309 243 1361 276
193 197 21 22 23
6800 9411249 194 1274 210 1325 243 1373 278
21 21 22 24
7200 9971319 228 1344 245
23 23
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2532
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
25
363 8
395 8
333 4
28 3 8351 2
221 2
301 2
Maximum wMotor Cover
TCB-2-22 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1722
Outlet Velocity = cfm X 0139
Tip Speed = rpm X 583
Maximum bhp at a given rpm mdash (rpm910)3
Max Motor Frame Size - 213T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2000 277484 015 598 027
47 55
2500 346549 022 648 036 823 067
64 65 94
3000 415620 030 705 047 863 082 1004 121 1127 161
76 78 100 122 146
3500 484695 042 771 060 913 100 1040 143 1162 188 1270 235
90 93 110 129 153 171
4000 554
773 056 841 077 969 121 1089 168 1197 218 1305 269 1403 322 1493 376
108 110 124 142 160 177 197 22
4500 623853 074 915 097 1030 145 1141 196 1246 250 1341 307 1438 364 1528 423 1612 483
128 129 140 158 171 184 20 22 25
5000 692933 096 991 121 1098 173 1199 228 1297 287 1390 347 1476 410 1563 473 1646 538
146 148 160 175 184 195 21 23 25
5500 7611015 122 1069 149 1167 205 1261 265 1353 327 1440 392 1525 459 1604 527 1682 597
166 170 184 190 197 21 22 24 26
6000 8311098 152 1148 182 1241 243 1328 306 1411 373 1495 442 1575 513 1653 585
187 193 20 20 21 22 24 25
6500 9001181 188 1228 220 1315 285 1396 353 1476 424 1553 497 1630 572 1704 649
21 21 22 22 23 24 25 27
7000 9691265 229 1309 264 1391 334 1468 406 1543 480 1614 557 1687 636
23 23 24 24 25 26 27
7500 10381349 276 1390 314 1468 388 1542 464 1611 543 1681 624
25 25 26 26 27 28
8000 11081433 330 1472 370 1546 449 1617 530 1683 613
27 28 28 29 29
8500 11771518 390 1555 433 1626 517 1692 602
30 30 31 32
9000 12461603 457 1638 503 1706 592
33 34 34
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2632
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
26
TCB-1-24 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 1225
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 6414
Maximum bhp at a given rpm mdash (rpm729)3
Max Motor Frame Size - 184T
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2500 253355 012 416 019 536 036
33 40 61
3000 304401 016 456 025 557 044 655 066
43 51 65 91
3500 355448 023 500 032 587 052 672 076 757 102
57 62 79 95 108
4000 406497 031 545 041 626 063 701 088 775 116 850 146
70 77 98 103 111 131
4500 456
548 041 591 053 667 077 735 103 803 132 867 163 935 196 998 231
84 94 109 115 121 135 152 170
5000 507599 053 639 066 711 092 774 120 833 150 896 183 953 217 1015 254 1073 292
103 113 122 128 136 145 156 173 190
5500 558651 068 688 082 757 111 816 140 872 172 926 205 983 241 1035 279 1091 318
121 126 137 144 155 161 168 179 195
6000 609704 085 738 100 803 132 860 164 913 197 964 231 1013 268 1065 307 1114 348
136 141 152 166 171 177 183 192 20
6500 659757 105 789 122 850 155 905 190 955 225 1004 261 1050 299 1095 339 1144 382
151 157 172 184 188 193 20 21 22
7000 710811 129 840 146 897 182 951 220 1000 257 1045 295 1090 335 1132 375 1174 418
169 177 190 198 20 21 22 23 24
7500 761865 156 892 174 946 213 997 252 1045 292 1089 332 1130 373 1172 416 1212 460
191 197 20 21 22 23 24 25 26
8000 812919 187 944 206 995 247 1044 288 1091 331 1133 374 1173 417 1213 461
21 21 22 23 24 25 25 26
8500 862973 221 997 242 1046 285 1092 329 1137 374 1179 419 1218 464
22 23 23 24 25 27 28
9000 9131028 260 1051 282 1096 327 1140 373 1183 420 1224 469
24 24 25 26 27 29
9500 9641082 303 1104 326 1147 373 1189 422
25 26 27 28
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2732
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
27
421 2
453 4
347 842
371 4
245 8
343 4
Maximum wMotor Cover
TCB-2-24 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1425
Outlet Velocity = cfm X 0102
Tip Speed = rpm X 641
Maximum bhp at a given rpm mdash (rpm661)3
Max Motor Frame Size - 215T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
2800 284393 021 489 039
54 67
3500 355443 030 528 050 672 097
70 79 102
4200 426497 042 572 065 703 117 820 174
85 93 110 138
4900 497555 057 623 083 743 141 849 204 949 271
105 112 125 147 179
5600 568
616 076 676 105 786 169 887 237 978 310 1066 387 1146 466
127 129 141 162 185 21 23
6300 639679 099 733 132 834 201 928 276 1015 354 1095 436 1175 522 1248 610
147 149 161 182 195 21 23 26
7000 710742 128 792 164 886 239 973 319 1056 404 1133 492 1204 582 1277 677 1345 773
165 168 182 20 21 22 24 26 29
7700 781806 162 852 201 939 283 1021 369 1098 458 1173 552 1243 649 1308 749 1374 852
184 189 21 22 23 24 25 27 29
8400 852871 203 914 245 994 333 1072 425 1145 520 1214 619 1283 722 1347 828 1407 936
21 21 23 23 24 25 27 28 30
9100 923937 250 977 295 1052 389 1125 487 1194 589 1260 694 1324 802 1387 914
23 24 24 25 26 27 29 30
9800 9941002 304 1040 353 1111 453 1179 557 1246 665 1308 776 1369 890
25 26 27 28 29 30 31
10500 10651069 366 1105 419 1171 525 1235 635 1298 749 1359 866 1417 986
27 28 29 30 32 33 34
11200 11371135 436 1169 493 1233 605 1293 722 1352 842 1411 965
30 31 32 33 35 36
11900 12081202 515 1234 576 1295 695 1352 818 1408 944
33 34 35 36 38
12600 12791269 604 1299 668 1358 794 1412 923
36 37 38 40
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2832
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
28
TCB-1-30 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 955
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 7984
Maximum bhp at a given rpm mdash (rpm514)3
Max Motor Frame Size - 213T
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 75 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
3750 292293 019 343 030
44 49
4500 350332 027 376 039 456 069
51 55 66
5250 409372 037 413 051 483 083 550 121
60 63 76 92
6000 467413 050 451 067 516 101 576 141 634 184
71 76 90 101 113
6750 526
455 067 490 085 550 122 606 164 659 210 709 259
84 90 105 113 122 136
7500 584497 087 530 108 587 148 639 192 687 239 735 291 781 346 833 403
99 110 120 127 136 146 160 182
8250 643540 111 571 134 626 179 673 224 719 274 762 327 807 385 849 444 894 506
123 126 135 143 153 162 176 191 21
9000 701584 139 613 164 665 213 710 262 753 313 795 370 833 427 875 490 913 555
136 140 150 161 169 181 194 21 23
9750 759629 173 655 199 704 253 748 306 788 359 828 417 866 478 901 541 940 609
150 155 166 177 188 20 22 23 25
10500 818673 211 698 239 745 297 787 355 826 412 862 470 899 534 934 600
165 170 181 195 21 22 24 26
11250 876718 256 740 285 785 348 826 409 864 470 899 531 932 595
181 185 20 22 23 25 27
12000 935763 306 784 337 827 403 866 469 902 535 936 600
197 20 22 24 26 28
12750 993808 363 828 395 868 465 906 536 941 605
22 23 25 27 29
13500 1052853 427 872 461 910 534 947 610
25 25 28 30
14250 1110898 498 916 534 953 610
28 29 31
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 2932
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
29
481 2
523 4
407 8481 2
423 4
291 2
42
Maximum wMotor Cover
TCB-2-30 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1279
Outlet Velocity = cfm X 0078
Tip Speed = rpm X 785
Maximum bhp at a given rpm mdash (rpm548)3
Max Motor Frame Size - 254T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
4000 311375 032 456 056 597 114
59 63 95
4800 374417 044 489 071 618 133
68 73 98
5600 436461 058 527 090 644 157 749 235 844 319
80 84 105 136 172
6400 498509 076 569 111 675 185 772 266 863 358 945 454
95 98 116 138 176 21
7200 561
558 099 611 137 712 219 802 305 886 399 967 503 1040 610
112 115 130 146 177 21 23
8000 623609 126 658 168 750 257 834 348 913 448 989 555 1062 669 1130 788 1195 911
130 133 144 162 181 21 23 26 29
8800 685660 159 705 203 792 300 871 400 945 503 1016 614 1084 732 1152 858 1214 987
151 152 162 180 195 21 23 26 29
9600 748712 197 753 245 834 349 909 458 979 566 1047 682 1111 804 1174 932 1237 107
168 170 181 198 21 22 24 27 29
10400 810765 242 803 293 877 404 950 520 1017 638 1080 757 1142 885 1201 102 1259 115
186 190 20 21 23 24 26 27 30
11200 872818 295 854 348 923 465 992 589 1055 717 1117 843 1174 972 1233 111
21 21 22 23 25 26 28 29
12000 935872 355 905 411 970 533 1034 667 1096 800 1155 937 1211 107 1265 121
23 23 24 25 26 28 30 32
12800 997926 423 957 481 1018 609 1078 749 1138 891 1194 104 1248 118
25 26 26 27 29 30 32
13600 1060980 499 1009 560 1067 694 1124 840 1181 991 1235 114
27 28 29 30 31 33
14400 11221034 585 1062 649 1117 789 1171 940 1223 110 1277 126
30 31 32 33 34 36
15200 11841089 680 1115 747 1168 894 1218 105 1269 122
33 34 35 36 38
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3032
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does notinclude drive losses Performance ratings do not include the effects of appurtenances in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free fieldcalculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
30
TCB-1-36 Level 1 Construction
Dimensions shown in inches
Maximum rpm mdash 800
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 9424
Maximum bhp at a given rpm mdash (rpm397)3
Max Motor Frame Size - 215T
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
CFM OV
Static Pressure in Inches wg0125 025 05 075 1 125 15 175 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
5600 339273 032 311 048 379 086
54 65 81
6400 387301 042 336 060 398 101
65 77 87
7200 436330 055 362 075 420 118 473 167
80 85 95 106
8000 484360 070 389 092 443 139 491 190 539 246
92 95 104 116 129
8800 533
390 089 417 112 468 162 514 217 557 275 599 337
105 108 116 129 144 161
9600 581420 111 446 135 493 189 537 247 577 308 617 373 655 441
120 123 130 145 161 173 178
10400 630451 137 475 163 519 220 561 280 600 345 636 412 673 484 708 557
138 139 147 164 181 185 190 196
11200 678482 166 505 194 547 254 586 318 623 386 659 457 692 530 727 607 759 687
154 157 168 185 193 197 20 21 22
12000 727513 200 535 230 575 293 612 361 647 431 681 505 714 582 745 661 777 744
172 175 19 20 21 21 21 22 23
12800 775545 239 565 270 603 336 638 407 673 481 705 558 737 638 766 721 796 806
191 196 21 22 22 22 23 24 25
13600 824577 283 595 315 632 384 666 459 698 536 730 616 760 700 789 785
21 22 23 23 23 24 25 26
14400 872608 331 626 366 661 438 694 516 725 596 755 680 784 766
24 24 24 25 25 26 27
15200 921640 386 657 422 690 498 722 578 752 662 781 749
26 26 26 27 27 28
16000 969672 446 688 484 720 563 750 646 779 734
28 28 28 29 30
16800 1018704 512 720 552 750 634 779 720
30 30 31 32
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3132
Performance certified is for installation type B Free inlet Ducted outlet Power rating (bhp) does not includetransmission losses Performance ratings do not include the effects of appurtenances (accessories) in the airstream
The sound ratings shown are loudness values in fan sones at 5 ft (15 m) in a hemispherical free field calculated per AMCA Standard 301 Values shown are for installation type B free inlet fan sone levels
31
55
591 4
463 854
471 4
313 4
46 3 4
Maximum wMotor Cover
TCB-2-36 Level 2 Construction
Dimensions shown in inches
Maximum rpm mdash 1051
Outlet Velocity = cfm X 0061
Tip Speed = rpm X 956
Maximum bhp at a given rpm mdash (rpm391)3
Max Motor Frame Size - 256T
CFM OV
Static Pressure in Inches wg025 05 1 15 2 25 3 35 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
7200 436342 067 403 109 515 206
73 114 113
8400 509380 091 434 136 532 241 625 363
108 13 117 146
9600 581420 121 467 170 556 284 640 411 721 554
143 137 125 147 183
10800 654461 159 503 212 586 334 662 469 736 617 807 779
146 141 135 155 182 22
12000 727
504 206 542 263 617 392 688 537 756 690 822 857 886 104 945 122
152 147 148 167 187 21 24 28
13200 800547 261 581 323 650 459 717 613 779 775 841 946 901 113 960 133 1015 153
160 156 163 182 20 22 24 27 31
14400 872591 326 622 393 684 535 747 697 807 870 864 105 920 124 975 144 1030 165
172 174 180 198 21 23 25 27 31
15600 945635 402 664 474 722 625 780 794 837 976 890 117 943 136 994 156 1045 178
191 194 20 22 23 25 26 28 30
16800 1018679 488 707 567 761 728 814 902 868 109 920 129 968 150 1018 171
21 22 23 24 25 27 28 30
18000 1090724 587 750 673 800 843 849 102 901 122 950 143 998 165 1042 187
24 24 25 26 27 29 31 32
19200 1163769 698 793 793 840 972 887 116 935 136 982 158 1028 181
26 27 27 29 30 32 33
20400 1236 814 824 837 927 881 112 926 131 969 152 1015 175
29 29 30 32 33 34
21600 1309859 965 881 108 923 128 965 148 1006 169 1049 193
32 32 33 35 36 38
22800 1381905 112 925 124 966 145 1005 167 1045 189
35 36 37 38 40
24000 1454950 129 970 142 1008 165 1046 187
39 39 41 42
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment
7252019 TCB Catalog
httpslidepdfcomreaderfulltcb-catalog 3232
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt
or direct drive fans are designed for clean air applications
(intake exhaust return or make-up air systems) where
space is a prime consideration Capacities range from
62 cfm (105 m3
hr) to 26600 cfm (45000 m3
hr) and up to35 in wg (869 Pa) of static pressure Maximum operating
temperature is 180ordmF (82ordmC)
Model TCB centrifugal backward inclined belt drive fans for
higher pressures Capacities range from 360 cfm (612 m3 hr)
to 24000 cfm (40800 m3 hr) and up to 45 in wg (1118 Pa)
of static pressure Maximum operating temperature is 200ordmF
(93ordmC) Model TCB is available with UL 762 for restaurant
exhaust
Mixed flow models QEI (belt drive) or QEID (direct drive)
are designed for a wide range of applications including
clean air (intake exhaust return or make-up air systems)and specialized UL Listed applications such as emergency
smoke exhaust or restaurant grease exhaust Capacities
range from 1000 cfm (1700 m3 hr) to 96000 cfm
(163000 m3 hr) and up to 95 in wg (2370 Pa) of static
pressure Maximum continuous operating temperature for
standard construction is 200ordmF (93ordmC)
Building Value in Air
Greenheck delivers value
to mechanical engineers by
helping them solve virtually
any air quality challenges
their clients face with a
comprehensive selection of
top quality innovative air-
related equipment We offer
extra value to contractors
by providing easy-to-install
competitively priced reliable
products that arrive on time
And building owners and
occupants value the energy
efficiency low maintenance
and quiet dependable operation
they experience long after the
construction project ends
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement Greenheck reserves the right to change
specifications without notice
Specific Greenheck product warranties are located on greenheckcom within the product
area tabs and in the Library under Warranties
Our Commitment