TAC OP7 Installation Instructions Operator Panel

2
TAC OP7 Operator Panel OP7 adapter Xenta 700 Installation Instructions 02-00003-03-en March 2010 TAC OP7 1. Remote mounting kit 2. Door IP 65 3. Remote cables 2 RJ45 4. To OP7 or Remote/Wall mounting CPU cable: 4 x 0.14 mm 2 (AWG26) Plugs: Modular 4/4 36 mm (1.4 in.) Connection table: Modular Modular 4/4 4/4 1 1 2 2 3 3 4 4 RS 232 OP7 24 VAC Trans- former $$9 * Cut-out, and ** required area; mm (in.) † Emission damper is supplied with the OP7 adapter Xenta 700. Mount close to OP7! Dimensions Adapter Connection mm (in.) 92 (3.62) 108 (4.25) 25 (0.98) 31 (1.22) 42 (1.65) Remote (Cabinet door) Mounting and Connection 3 2 1 4 To OP7 adapter Xenta 700 Emission damper † 105 (4.1) 116 (4.6) * 28 (1.1) 35 (1.4) 16 (0.7) 16 (0.7) **

Transcript of TAC OP7 Installation Instructions Operator Panel

Page 1: TAC OP7 Installation Instructions Operator Panel

TAC OP7Operator Panel

OP7 adapter Xenta 700

Installation Instructions02-00003-03-en

March 2010

TAC OP71.

Remote mounting kit2.

Door IP 653.

Remote cables 2 RJ454.

To OP7 or Remote/Wall mounting

CPU cable: 4 x 0.14 mm2 (AWG26) Plugs: Modular 4/4

36 mm (1.4 in.)

Connection table: Modular Modular 4/4 4/4 1 1 2 2 3 3 4 4

RS 232

OP7

24 VAC

Trans-former

* Cut-out, and

** required area; mm (in.) † Emission damper is supplied with the OP7 adapter Xenta 700.

Mount close to OP7!

Dimensions Adapter Connection

mm(in.)

92(3.62)

108

(4.2

5)

25(0.98)

31(1.22)

42(1.65)

Remote (Cabinet door) Mounting and Connection

32

1

4

To OP7 adapter Xenta 700

Emissiondamper †

105 (4.1)

116

(4.6

)

*

28(1.1)

35(1.4)

16 (0.7

)

16 (0.7

)

**

Page 2: TAC OP7 Installation Instructions Operator Panel

Copyright © 2009-2010, Schneider ElectricAll brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. All rights reserved.

2 of 2

02-00003-03-en

For more information visit

www.schneider-electric.com/buildings

TAC OP71.

Wall mounting kit2.

-3.

Remote cables 2 RJ454.

RJ45 female/female 5. adapter

Additional Remote 6. cables 2 RJ45

TAC OP71.

Remote/Wall mounting kit2.

Door IP 653.

Remote cables 2 RJ454.

RJ45 female/female adapter5.

Additional Remote cables 2 RJ456.

Clean the wall and mounting kit •rear surfaces with the enclosed Surface Cleaner.

Attach the mounting kit to the •wall using the self-adhesive strips.

Alternatively, secure the back of •the kit with suitable screws.

OP7 adapter Xenta 700

† Emission damper is supplied with the OP7 adapter Xenta 700.

Mount close to OP7!

Wall Mounting and Connection

To OP7 adapterXenta 700

5

1

6

4

2

Emissiondamper †

Handheld terminal

5

1

4 or 6

To OP7 adapter Xenta 700, orRemote/Wall mounting holder

Emissiondamper †

RS 232

OP7

Trans-former

4 or 6

(To OP7 adapterXenta 700)

4

32

6 64

2

(To OP7 adapterXenta 700)

Ø 3.6(0.14)

Ø 2.9(0.11)

128.1 (5.0)

88.0

(3.5

)