TABLE OF CONTENTS CONCEPTUAL SPECIFICATION

576
U Hotels & Resorts EU Technical Standards Manual i TABLE OF CONTENTS CONCEPTUAL SPECIFICATION DESCRIPTION PAGE INTRODUCTION 2 GENERAL CONCEPT 9 ROOMS 19 BATHROOM 64 SUITES 71 CORRIDORS 74 SURROUNDINGS DESIGN 79 RECEPTION 84 PUBLIC CORRIDORS & SHOPS 97 CUSTOMER SERVICES 108 RESTAURANTS AND BARS 128 CONFERENCE AND FUNCTIONS 153 ADMINISTRATION 168 LAUNDRY 172 KITCHENS 185 COLD ROOMS 236 SUPPLY AND WASTE 243 EMPLOYEES 250 TECHNICAL ROOMS 256

Transcript of TABLE OF CONTENTS CONCEPTUAL SPECIFICATION

U Hotels & Resorts EU Technical Standards Manual

i

TABLE OF CONTENTS

CONCEPTUAL SPECIFICATION

DESCRIPTION PAGE

INTRODUCTION 2

GENERAL CONCEPT 9

ROOMS 19

BATHROOM 64

SUITES 71

CORRIDORS 74

SURROUNDINGS DESIGN 79

RECEPTION 84

PUBLIC CORRIDORS & SHOPS 97

CUSTOMER SERVICES 108

RESTAURANTS AND BARS 128

CONFERENCE AND FUNCTIONS 153

ADMINISTRATION 168

LAUNDRY 172

KITCHENS 185

COLD ROOMS 236

SUPPLY AND WASTE 243

EMPLOYEES 250

TECHNICAL ROOMS 256

U Hotels & Resorts EU Technical Standards Manual

ii

FIRE SAFETY 268

SOUND CONTROL & INSULATION 284

SIGNAGE 298

THE DISABLED 320

WATERPROOFING 326

EXTERIOR JOINERY (WOOD AND METAL WORK AND GLAZING) 334

INTERIOR JOINERY 339

LOCKS 347

CLOSURE 357

FINISHES 361

SANITARY PLUMBING 373

FIRE PROTECTION 414

FIRE DETECTION 424

VENTILATION – AIR CONDITIONING 438

ELECTRICITY 453

IT & LOW VOLTAGE 484

TELEPHONE 531

ELEVATORS (LIFTS) 542

FF & E (FURNITURE, FIXTURES AND EQUIPMENT) 554

SPARE PARTS 560

TAKEOVER BY HOTEL OPERATOR 572

U Hotels & Resorts EU Technical Standards Manual

Page 1 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Introduction

These documents are strictly confidential

All rights are strictly reserved

Reproduction or issue to third parties in any form whatsoever is not permitted without prior written authorisation from the proprietor

U Hotels & Resorts EU Technical Standards Manual

Page 2 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

INTRODUCTION

Purpose of these standards

Validity of these standards

U HOTELS & RESORTS EU technical documents list

Design team members and consultants

Pre-opening timeline area requirements

Acceptance of work

U Hotels & Resorts EU Technical Standards Manual

Page 3 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

PURPOSE OF THESE STANDARDS

This manual deals with architectural and technical design standards. This manual is associated with all documents useful for the design, construction

and maintenance of U Hotels & Resorts and listed under “Technical Documents List”.

These standards have been produced for designers so that throughout the hotel project development process they may check the functional, qualitative

and technical criteria have been taken into account, which should guarantee the owning companies and U Hotels & Resorts:

The best operating facilities

The greatest ease in the operation and maintenance of the installations

The continuous development of the good reputation of the chain and the implementation of its corporate image.

These documents indicate the general architectural and technical criteria from which the specific projects should be produced.

U Hotels & Resorts standards must be strictly applied with the only exceptions being:

Waiver scheduled in the specific Hotel Brief

Waiver accepted in writing by U Hotels and Resorts Management during the design of the hotel

Local codes supersedes the standards of these documents

These standards are presented in two parts:

a. Conceptual specifications - room analysis

b. Technical specifications - trade analysis

U Hotels & Resorts EU Technical Standards Manual

Page 4 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

VALIDITY OF THESE STANDARDS

This manual of standards is general and complementary to the detailed specific Hotel Brief. If on certain points of details there may be a contradiction,

the Hotel Brief has priority.

No waiver to the specifications may be considered without the prior agreement of U Hotels and Resorts Management who are the sole judge of the

interpretation and updating of these standards.

U HOTELS & RESORTS EU TECHNICAL DOCUMENT LIST

Facility Brief*

Hotel Brief *

Food & Beverage Brief*

Corporate Identity Manual

Design Guidelines

Technical Standards (this manual)

IT Standards (included in this manual)

(*) Written for each specific project, therefore only valid for that specific hotel

U Hotels & Resorts EU Technical Standards Manual

Page 5 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

DESIGN TEAM MEMBERS AND CONSULTANTS

To ensure that the design of a hotel evolves correctly, the presence of the following parties in the team are indispensable:

Required from the beginning of the project:

A Technical Representative or Delegate of the owning company

A Technical Representative of U Hotels and Resorts Management

A Project Manager & Construction Site Management

An Architect

A Structural Engineer

An MEP Engineer (Mechanical, Electrical, Plumbing, HAVAC)

An IT – Network Engineer (IPTV, IP PBX, CCTV (IP), Internet/Wi-Fi)

An Interior Designer

A Kitchen Consultant or Kitchen Supplier who can work on layout drawings and M&E drawings

The following consultants are required depending on the project:

An Acoustics Consultant

A Lighting Consultant

A Landscape Architect

A SPA specialist

A Purchasing Office and FF & E consultant

A Laundry Consultant (usually combined with a Kitchen Designer)

Any other consultants as needed, such as quality surveyors, official control firm etc.

U Hotels & Resorts EU Technical Standards Manual

Page 6 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

PRE-OPENING TIMELINE AREA REQUIREMENTS

To ensure the opening is structured and organized, it is necessary that certain premises are available to the operator at some point in advance during the

pre-opening period.

The table on the following page indicates, for the premises or equipment concerned, the availability datelines required before the opening date. These

datelines are expressed in weeks.

All the final keys or cards to the premises are handed over to the operator as and when they are set into service.

The below pre-opening schedule is given as example:

U Hotels & Resorts EU Technical Standards Manual

Page 7 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Section Location Remark

Pre Opening Office -22 -20 -18 -16 -14 -12 -10 -8 -6 -4 -2 Opening

General Managers Office Back of House

Human Resources Office Back of House

Offices, Accounting, F&B, HK Back of House

Canteen Back of House Before hand it should be leased out

Locker Rooms Back of House

Training Room Back of House

Toilets Back of House Locker room toilets

Front Office - Back Office Behind front office counter

Server Room Within the back office

Stores

Pre Opening FFE & OPE Function Rooms Floor covering should be temporary to avoid damage

General Store Back of House

F&B Stores Back of House

Laundry Back of House

House Keeping Back of House

Uniform Room Back of House For Pre-Opening Polo shirts would be used

Operations Back of House

Receiving

Production Kitchen To be ready for canteen food

Show kitchen Cooking training will be done in this kitchen

Pantry Function Room

Deli Bar & Kitchen With PMS connection

Bar Lounge With PMS connection

Engineering Workshop

Garbage Rooms Will be required and clearing would need to be organized

Operations Front of House

Front Office Lobby 3 weeks out, the PMS needs to be installed in this area

Main Restaurant 2 weeks out, the POS needs to be installed in this area

Bar Lounge 2 weeks out, the POS needs to be installed in this area

Deli - Restaurant 2 weeks out, the POS needs to be installed in this area

Spa 2 weeks out, the POS needs to be installed in this area

Gym / Fitness

Pool

Kids and Teenager Club

Library

Ballroom Will be used for staff meetings / briefings

Meeting Rooms

Elevator Give enough trial runs to get balance correct

Car Park

Rooms first lot To setup and train the housekeeping employees

Rooms second lot

General clean up work All suroundings Entire hotel team will walk property

Pre Opening Timeline Area Requirements

Please note in the green these areas will be required by the hotel operations for operational or storage or training purposes.

Required Dates

Requires, internet 4-Mpbs, phone connection, fax, copier,

furniture, as well working toilets during the pre-opening time

period.

Server racks, power, internet & lane cabling to be ready at

stated time for configuration of PMS & POS system

U Hotels & Resorts EU Technical Standards Manual

Page 8 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ACCEPTANCE OF WORK

Work per area is accepted by the Owners with the assistance of the persons mentioned in the “Design Team Members and Consultants” section, in respect

of the individual person’s specific input into the project. This acceptance must be made in the presence of the U Hotels and Resorts Management Team

which, except when otherwise arranged, will not take charge of the premises beforehand.

If partial or total opening of the uncompleted hotel is necessary due to commercial requirements, it does not indicate any acceptance of the work or

acceptance by U Hotels and Resorts of completion. Responsibility for non-accepted works cannot be apportioned to the operator in any way and should be

acknowledged by the Owner in writing during the handover.

The technical documents, operating instructions and as-built drawings should have been handed over to the hotel General Management at the moment of

acceptance or at the hotel takeover at the very latest.

Only the date of acceptance and not that of the possible takeover marks the start of the warranty period provided by the building contractors.

At the takeover of the premises, U Hotels and Resorts Management will write a technical report listing the deficiencies in the property from a hotel

operation point of view.

“See chapter Hotel Takeover”

U Hotels & Resorts EU Technical Standards Manual

Page 9 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GENERAL CONCEPT

General

Types of hotels

Characteristics specific to resort hotels

Size

Guest traffic

Luggage traffic

U Hotels & Resorts EU Technical Standards Manual

Page 10 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GENERAL

U Hotels and Resorts Management/Owner must follow a certain number of fundamental criteria which ensures that the hotel is easily perceived and

identified as a U Hotel or Resort. Furthermore, these criteria must contribute to strengthening the U Hotels & Resorts corporate identity. These criteria

guide the major aspects of the studies.

U Hotels & Resorts brand values:

Reach out

Brand appeals to high achievers even when on holiday or business who have clear and

consistent expectations and know what constitutes value and quality in their lives.

Restore

Cosseting and comfortable hotels and resorts, where welcoming and friendly employees will

refresh and rejuvenate guests with products, facilities and services delivered in an informal

environment. Guests will feel part of the family.

Reconnect

Through locations and warm uncomplicated service that encourages guests to step into the

local environment and experience its culture and heritage at their own pace, creating a

memorable, unique experience.

Location

A good location is the key to the success of any hotel project. With a poor location, even if the hotel itself is of high quality it will never enjoy total

commercial success.

U Hotels & Resorts EU Technical Standards Manual

Page 11 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Adaptation to the Site

Each project must be the subject of an architectural study. It is not necessary to follow a given approach based on a standard design. The landscape,

relief and surrounding environment must be integrated as essential elements in the overall architectural concept.

Protection of the Environment

Protection of the environment is a central component in U Hotels & Resorts’ positioning. This commitment must be taken into account right from the

initial studies and be reflected in the choice of installations and equipment. In particular, the following aspects must be considered:

Energy savings (VRV units, LED light, sensor switches)

Quality of the ambient air and external emissions

Water quality and limiting consumption, as well as pre-treatment, treatment or reuse of water

Absence of noise pollution

Conditions for storage or confinement of dangerous and/or toxic products

No use of toxic materials for construction or in equipment (asbestos, CFC, PBC, etc.)

Certain technologies, such as computerized maintenance aids, non-toxic replacement materials, etc., should be considered throughout the project

development phase. Whenever possible, these alternatives will be given priority.

Organisation of Space

The architectural concept must offer guests simple and easily recognizable spaces and volumes. The public areas will be limited to two or three levels.

Large architectural areas such as an atrium are desired, and must have a link to the public activities at the base (lobby, bars, restaurants, gym, pool

etc.).

U Hotels & Resorts EU Technical Standards Manual

Page 12 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

An Innovative Character

The hotel must be designed down to the last detail long before it begins operating. Consequently, it must be designed to be competitive at the time it

enters the market. This means planning with a very open mind when it comes to new or innovative concepts that will distinguish the hotel from the

competition.

A Timeless Character

For the architecture, interior design and equipment, “quality” above all means solid and robust. It is better to rely on traditional, natural methods and

materials.

Access

Given the various imperatives involved, the hotel’s surroundings should, as far as is possible, consist of a carefully designed and landscaped

environment, while ensuring the visibility of the hotel. There should not be a series of access ramps. Guests should not have to cross large, exposed

and cold expanses (made of mineral materials), such as parking areas to get to the entrance of the hotel.

Orientation

The hotel’s position should take maximum advantage of surrounding views, sun and daylight to enable guests to enjoy the view, particularly in the

lounges, restaurants, public areas and rooms.

Wind Exposure

It is imperative that drafts and other undesirable effects of wind (heat or cold, spreading of odours, smoke, etc.) be limited for the room balconies

and public terraces as well as the swimming pool areas.

Noise Protection

Appropriate measures must be taken to protect against noise from roads, airports, hotel machinery and equipment, nearby pubs and nightclubs, etc.

U Hotels & Resorts EU Technical Standards Manual

Page 13 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Landscaping

Even when there is no land available around the hotel, landscaping is an extremely important factor in creating a quality property. A specific study

by a specialist is always required, even if only the terraces and rooftops are visible to guests.

U Hotels & Resorts EU Technical Standards Manual

Page 14 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

TYPES OF HOTELS

There are two main types of hotels:

Resort Hotels

Resort hotels are often located on beaches or in particularly pleasant natural sites and feature larger outside areas. Here, the terrain offers space for

leisure activities including water sports, swimming pools, landscaped waterfalls, kid’s playground, botanical gardens, a golf course or other such

activities.

Business Hotels

The constructed space sometimes occupies the entire site minus the boundary size limitation. Some business hotels are also located in low - density

urban zones, where construction may leave room for access roads, parking lots and gardens. This enables greater flexibility in the layout of the

buildings.

U Hotels & Resorts EU Technical Standards Manual

Page 15 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CHARACTERISTICS SPECIFIC TO RESORT HOTELS

The approach for the creation of a “resort hotel” is different from that of a “business hotel”; to start with the degree of efficiency sought is not the

same. In urban areas with reduced plot areas, there is a certain density, with short, efficient paths between different areas required for guests in a hurry

who reside at the hotel on a short-term basis. On the other hand resort hotels welcome guests for a number of days which are entirely dedicated to rest,

relaxation and entertainment. The sites are larger and guests have time to walk around and enjoy the surroundings created for them. Open spaces,

gardens, points of interest and places for relaxing and enjoying life are all elements which must be a central part of the resort concept.

The following aspects lead the main directions of the studies carried out:

The hotel must be a pleasant place. This starts with the provision of places for relaxation, but also for meeting other people during evening get-

togethers, shows or other forms of entertainment. The organization of the spaces in which the guests live in the hotel must foster and encourage such

exchanges. Equally important in creating a pleasant ambiance as per the policy of the hotel’s operator to welcome, inform, meet and organize activities

for guests, taking advantage of the multiple facilities available.

The hotel must live up to the guest’s expectations. People choose to go to these hotels to escape from the stress of everyday life. They want to be

enchanted and charmed in an exotic place amid peace which they cannot find at home. They want a change of scene that is far removed from their

everyday concerns. The dreamlike character of the hotel and its strong “personality” must offer all these things to guests and create a desire to stay at

the hotel and to wish to return. The magic of the site must be found in the concept proposed by the architect in response to the U Hotels & Resort’s

Hotel Brief. This is the main responsibility of the architect, in conjunction with the landscape architect.

Landscaping: Whatever the size of the site, the resort hotel is first and foremost a “beautiful garden”. The gardens are the dominant and even priority

element in the composition of the hotel, integrating one or more centres of interest (pool, restaurant, bar, beach, island, etc.). These are the points

which attract guests during their stay. Whether the garden is very formally constructed or more freestyle in design, the vegetation must be carefully

chosen and adapted to the climate. The enticing colours and spaces full of charm, light and decor, must make the gardens places to be lived in and

seen, and this decor must be discovered progressively thanks to a seamless transition between different areas.

The character and climate of the area: The hotel must be integrated into the surroundings and the creation of a harmonious whole is essential. The

layout plan respects the topography and vegetation, if they are remarkable and a “talking point”. The buildings too may express a strong link with the

location and take advantage of certain elements, finding inspiration in the forms and principles behind local traditional cultural, architectural and

historical aspects area (if applicable).

U Hotels & Resorts EU Technical Standards Manual

Page 16 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SIZE

Business Hotels

The total gross area built per room-module generally varies between 50 to 60 m2 (not including parking areas).

This area is broken down as follows:

Guestrooms section: 30 m2 (total gross area) per room (hotels with guestrooms with 22 m2 of net living-room area) with toilet either separate or

isolated from the bathroom and with a conventional architectural concept (including horizontal and vertical circulations).

Remaining areas: 20 m2 (large hotels of 100-plus rooms) to 30 m2 (small hotels with 50 keys or less) per room-module. A 25 % factor is added to the

net area to calculate the total gross area per module; this difference covers space for conduits, vertical and horizontal circulation, structure, walls etc.

Resort Hotels

The total gross area built per room-module generally varies between 70 to 80 m2:

Guestrooms section:

A guestroom in a resort hotel is by definition more spacious than a business hotel room, since the guest spends a good portion of their stay in the room.

It is therefore preferable that the living area measure about 32 m2 extended by a balcony of 6 to 12 m2 (total gross area) per room.

Remaining areas: given the residential character of the projects, the distribution of the structures significantly increases the circulation areas, such as

walkways that are covered but not enclosed …etc. This means 20 to 30 m2 total gross area per room.

U Hotels & Resorts EU Technical Standards Manual

Page 17 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GUEST TRAFFIC

U Hotels & Resorts EU Technical Standards Manual

Page 18 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LUGGAGE TRAFFIC

1. Customer arrival flow to guest rooms. This depends on the Porte Cochere design but the luggage room should have a separate entrance from the Porte

Cochere with another entrance to the back of house which leads to the service elevator. This ensures no luggage is circulated through the public areas.

2. Flow from the guest rooms to the Porte Cochere (departure).

3. Long term luggage deposit should be separated for better security (large hotels only).

U Hotels & Resorts EU Technical Standards Manual

Page 19 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ROOMS

Concept

Architecture

Dimensions

Organisation

Decor

Equipment

Coverings

Furniture

Bedding Material Specification

U Hotels & Resorts EU Technical Standards Manual

Page 20 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CONCEPT

The room concept varies depending on whether the hotel is a “city centre business” property or a “resort” hotel. However, sometimes there is no clearly

defined line between the two types. The Hotel Brief must therefore define the type of hotel and the limits to be respected in terms of the concept.

In all cases, a complete mock-up room, including bathroom and corridor, must be built on site or in an agreed-upon location for each room type (one king &

one twin with connecting door minimum) and subjected to a detailed analysis. If necessary it must be corrected and revised before any final approval is

granted by U Hotels and Resorts Management. This approval must be received before any architectural or decorative (interior design) work can begin or

orders be placed.

“Business” Hotels

Business hotels have rooms with a residential character. The main functions of these rooms (rest, sleep and work) are treated on the basis of concepts

which avoid copying the outmoded “bed in a box” idea of standard hotel chain rooms, which are both too anonymous and unvarying from one country

to the next.

For U Hotels & Resorts, each new project is covered by a specific study for the standard room. This means that there is no such thing as a “standard”

U Hotels & Resorts room layout.

“Resort” Hotels

Resort-oriented hotels are different from business-oriented hotels in that the character emphasizes relaxation, rest and taking a break. The climate and

the site both have great influence on the concept. Consequently, the room must have a more innovative image that makes optimum use of space and

light. The room is opened to the outside with a terrace or balcony, which actively contribute to the “life” of the room.

The sleep/night function can be considered as distinct from the living room/terrace function. The bathroom must be spacious and largely opening on

to the room, possibly becoming an extension of the room itself (the boundary is changeable). The room must have natural lighting and if possible a

view of the sea or gardens. The comfort and layout/amenities must be designed to accommodate longer stays than at business hotels.

U Hotels & Resorts EU Technical Standards Manual

Page 21 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ARCHITECTURE

The total area of the guestroom floors or sections in a hotel represents approximately two-thirds of the total constructed area. This means that the way in

which the rooms are grouped has a fundamental influence on the architecture of the hotel or the buildings which comprise the hotel. It is also important to

note, that this type of study begins two to three years before the hotel actually opens. This makes it necessary to look ahead in order to satisfy the expectations

of the guests who will be staying at the hotel in the future. Other factors to be taken into account right from the start of this concept phase are the following

points which have direct impact on the size and shapes of bay windows.

Protection of facades from the sun

Sound insulation from both interior and exterior noise (C 21 Sound Control & Insulation)

Cleaning of the facades

The railings of balconies must allow a clear view whilst guests are seated inside the room

It must be possible to totally block out all daylight inside the room

Windows and treatment of windows

Windows must be designed to provide sound insulation, based on a calculation of the sound levels generated by the outside environment. They must also be

thermally treated: dark tinted windows should not be used. Windows should always have a section which can be opened. Where necessary, for safety and

security reasons, the opening section shall be equipped with a “stop” preventing it from being opened more than local regulations allow (especially when

children have access).

Where windows lead on to a terrace or balcony, safety shall also be taken into account, in accordance with applicable regulations. In all cases, the minimum

height of the handrail of the balcony shall be 1.10 meter from the floor, or 95 cm from the highest stepping point. The smallest size of gaps between railings

such as iron bars (which must be vertical and not horizontally positioned) must not be bigger than 12 cm.

U Hotels & Resorts EU Technical Standards Manual

Page 22 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

DIMENSIONS

The net area of a standard room-module is around 28 m2. The main area of the room excluding the bathroom should measure 22 m2.

The minimum central distance between the walls of the module is 3.8 m, and the overhead clearance of the ceiling is a minimum of 2.80 m in the

room and 2.40 m in the bathroom and entrance.

All specific information and exceptions, in particular for renovation of existing buildings, are included in the Hotel Brief. The final dimensions and

exact position of the walls and partitions which are part of the structural design may not by finalized until the organization of the room module has

been defined and approved. The number and location of these rooms is determined by conforming with local regulations; this information is included

in the Hotel Brief.

ORGANISATION

The following must be provided within the rooms with no exceptions;

An entrance which acts as a small hallway, avoiding a direct view of the bed.

A closet with shelves, drawers, a safe and a wardrobe.

A bathroom with 1 wash basin and vanity counter and separate shower stall and toilet which may be enclosed within a cubical.

A sleeping area with absorption type mini-bar and digital operated television, with a minimum of 40” to 43” screen size (depend on brand), which

streams 6 to 8 different music genres.

A work corner with desk, business unit and appropriate equipment (business hotels only).

An area with sofa (suites only), armchair and coffee table.

Significant variations are possible, as illustrated by some U Hotels & Resorts hotel guestrooms layouts (see below drawings).

U Hotels & Resorts EU Technical Standards Manual

Page 23 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SAMPLE DELUXE KING ROOM LAYOUT

U Hotels & Resorts EU Technical Standards Manual

Page 24 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SAMPLE DELUXE KING ROOM M&E SPECIFICATION

U Hotels & Resorts EU Technical Standards Manual

Page 25 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SAMPLE DELUXE TWIN ROOM LAYOUT

U Hotels & Resorts EU Technical Standards Manual

Page 26 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SAMPLE DELUXE TWIN ROOM M&E SPECIFICATION

U Hotels & Resorts EU Technical Standards Manual

Page 27 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SAMPLE SUPERIOR KING ROOM LAYOUT

U Hotels & Resorts EU Technical Standards Manual

Page 28 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SAMPLE SUPERIOR KING ROOM M&E SPECIFICATION

U Hotels & Resorts EU Technical Standards Manual

Page 29 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SAMPLE SUPERIOR TWIN ROOM LAYOUT

U Hotels & Resorts EU Technical Standards Manual

Page 30 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SAMPLE SUPERIOR TWIN M&E SPECIFICATION

U Hotels & Resorts EU Technical Standards Manual

Page 31 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SAMPLE SUITE ROOM LAYOUT

U Hotels & Resorts EU Technical Standards Manual

Page 32 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SAMPLE SUITE ROOM M&E SPECIFICATION

U Hotels & Resorts EU Technical Standards Manual

Page 33 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SAMPLE ROOM ELEVATION

U Hotels & Resorts EU Technical Standards Manual

Page 34 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

DECOR

The first visual impression of the room is the one perceived when the entrance door is opened. This impression must immediately convey a sense of

intimacy, calm and comfort through the colours, lighting and heat or freshness.

The harmony of the colours will vary according to the climate and the ambiance to be created, but must always remain consistent with the creation of a

uniformly high quality atmosphere. The decor must create a “local and homely” atmosphere in the room. Each room will be personalized with items such

as lithographs, art works, etc. Technology is present to cover all guest needs, but must remain discreet.

EQUIPMENT

Lighting must be carefully designed, with two types of lighting:

Ambient lighting, providing overall illumination of the room

Specific lighting for the desk, lounge area and for reading

Electrical equipment must include the following:

Entrance

1 master switch with micro-switch (this switch must not turn off the air-conditioning, refrigerator, IPTV and one power socket at work station)

1 two-way lighting switch for the ambient lighting (room and entrance)

1 switch for the bathroom lighting

1 outlet to allow housekeeping to use their equipment when cleaning the room (within the room/corridor)

Touch-contact or switch for the closet light

Bell for the entrance door including the DND / MUR indicators

Entrance and door lighting

Thermostat to control the room temperature

U Hotels & Resorts EU Technical Standards Manual

Page 35 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Bedroom

There should be a minimum of five light points (plus the reading lights), providing overall illumination of 150 lux. The minimum equipment is as

follows:

1 reading lamp on the desk (350 lux).

1 ambient light with two-way switch (one at the entrance).

Lighting for the mini-bar /TV cabinet.

1 free standing decorative light fixture at the seating area or day lounge.

Artwork lights.

Lighting for the balcony (if applicable).

“DND” (do not disturb) and “MUR” (make up room) switch.

The quality of the reading lights – at the bed, desk and armchair – is one of the factors which makes the room comfortable. These lights must be

carefully selected and must be sufficiently powerful to be connected via individual switches.

A number of electrical and low-voltage outlets must be provided in the room:

Wall outlets with extensions for bedside, desk and lounge lighting.

TV outlet RJ45 connected with CAT6e (TV with infrared remote control unit).

TV speaker jack (for the bathroom).

Mini-bar refrigerator outlet plus special connection if the hotel has computerized mini bar management. An RJ45 CAT 6E Ethernet circuit outlet

must be provided in all cases (see chapter T13 IT & Low Voltage, section 2 on structured cabling).

2 electrical outlets which include USB charger near or at the desk (lamp + computer) on a support that is easily accessible and coordinated with the

desk. This outlet will always be operated and not connected to the key card.

1 RJ45 telephone outlet at the main bedside (window side) connected to the in room router.

A switch near the window for the balcony light which must not be hidden by the curtains.

Each hotel room must have a bell which includes the DND / MUR indicators.

For equipment on the bedside table (lamp, telephone, etc.) and the room in general the cords should be of the same type and colour, and as short as

possible.

The switches and outlet face plates must match and follow the décor appropriately. It is preferable that these are not in white, except with white

finishes.

U Hotels & Resorts EU Technical Standards Manual

Page 36 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Telephone

One telephone line per room: (See chapter T13 IT & Low Voltage)

Phone on the bedside table close to the window side (wireless if possible). Telephone outlet should be under side table, hidden from guest sight.

Television – Radio

LED Hospitality TV sets with built in set top box, must be colour with stereo sound, multi standard and equipped to receive cable and satellite.

They must also feature a HDMI / USB socket, 50 channel minimum availability and an infrared remote control unit.

LED TV with a minimum size of 41" to 46”. For suites within the living room a minimum of 46" or larger is required. The TV should be visible from the bed and the reading/sitting area in the suites. It must have a swivel mount and/or be placed on top of a cabinet.

The middle of the screen should be about 1.35 m from the floor.

An alarm clock should be provided on the night table.

Fire Safety (see chapters T-9 Fire Protection and T-10 Fire Detection)

A smoke detector mounted in the centre of the room (above the bed) at the highest possible position.

An alarm must be recessed into the false ceiling over the entrance.

The above units need to be connected to a fire panel control board (Addressable) situated in the reception and engineering departments.

Air conditioning (see chapter T-11 Ventilation – Air Conditioning)

Fresh and centrally pre-treated air must be provided for the rooms and corridors.

Air outlets and intakes must be of a good quality to ensure that they integrate seamlessly with the interior design of the room.

Four-tube or two-tube fan coil units should be used, depending on the climate.

A wall-mounted thermostat with graduated temperature markings should be installed with on/off switch and three-speed fan control.

Sensor switch at Window or Balcony door to stop the Air Condition after 2 minutes of opening the window or door.

U Hotels & Resorts EU Technical Standards Manual

Page 37 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Locks

Guest Room Door Locks

Room locks should be standalone electronic RFID, programmable key types (Mifare or NFC with 1k or 4k capacity), battery operated and

interfaced with the PMS system (Comanche).

In humid, tropical and coastal climates, the provider of the systems must guarantee that their product can withstand local conditions.

It is recommended to use RFID door lock systems due to the security and reliability of contact-less technology. Due to today’s mobile gadgets the

lock system should be compatible with any preferable solution such as key cards, phones or other devices.

Recommended brands are Onity, VingCard or Kaba.

Connecting Door Locks

Connecting doors will be fitted with individual locks and deadbolts, with each separate door leaf being operable from its room-side only.

Connection between rooms if not enough space should be on the balconies if space available.

U Hotels & Resorts EU Technical Standards Manual

Page 38 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

COVERINGS

Floor (see T7 – Finishes)

Axminster type carpets with 80/20 % wool/nylon weave should be used for business hotels in living rooms, corridors, function rooms etc. In-room

foyers should be a hard durable material such as stone or wood.

Ceramic or stone tiling with anti-slip treatment and carpet rugs by the bed are to be used in warm and humid climates or in resort hotels (a floating

floor for soundproofing is necessary in this case) .

Partial wooden floors are also possible, using the same precautions as above.

The skirting must be chosen to match the coverings: tile or solid wood a minimum 12.5 cm high from the floor.

The balcony floors should be recessed by 2 cm and covered with a hard antislip tiling and with a gradient of 1:100 (by 1m width = 1cm).

Floor transitions are 2cm or less, except for the shower cubical which is 3 cm with a gradient of 1:60.

Waterproofing in the bathroom with a floor drain must be provided.

Terrazzo and polished concrete finish is not recommended due to cracking after a short time period.

Walls

Materials which cannot be washed or which have a deep relief texture should be avoided.

Stucco finishes with 3mm thickness is recommended due to long life and low maintenance. This is especially good to camouflage small wall

bumps, cracks or other imperfections as this finish does not reflect light.

Water- based matte finish for guest rooms or flat enamel finishes for corridors or halls.

U Hotels & Resorts EU Technical Standards Manual

Page 39 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Doors

Acoustic seal around the entire frame and a threshold bar or telescopic skirting to ensure soundproofing.

Wide-angle (160˚) eyepiece or peephole with cover set at a height of 155 to 160 cm from the floor.

Magnetic doorstop which can hold the door open.

Door panel minimum thickness 3.5 cm.

Concealed door closer.

U-buckle lock.

Frame behind the door for fire safety diagrams and instructions.

Room number matching the decor (see chapter C 22 Signage).

All doors must be flame resistant with a withstanding rate of 1 ½ hour (90 minutes) minimum.

Connecting doors between guest rooms must be double and have double seals and rebates around the entire doors to guarantee total sound insulation

if they are not located on a balcony. They must have the same degree of flame resistance as the entrance doors and be equipped with a single handle

and a latch bolt.

The entrance door must be solid core type and all doors must meet acoustic insulation requirements. (Refer to chapter C21)

Kids’ safety lock on balcony doors are required at a height of 140 cm from the floor, if the building is a high rise.

U Hotels & Resorts EU Technical Standards Manual

Page 40 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SAMPLE DOOR DETAIL

U Hotels & Resorts EU Technical Standards Manual

Page 41 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SAMPLE DOOR DETAIL

DOOR DETAIL

U Hotels & Resorts EU Technical Standards Manual

Page 42 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SAMPLE DOOR DETAIL

BOTTOM SEAL (ACOUSTIC SEAL)

U Hotels & Resorts EU Technical Standards Manual

Page 43 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Ceilings

The ceilings are a key factor in the overall decor, especially in the room (when viewed from a prone position on the bed).

Cornices or other decorative touches should be incorporated into flat ceilings.

It is recommended to have cove ceilings with indirect lighting with a minimal number of down light fixtures.

Large enough hatch at the entrance area (min. 80 x 60 cm) is required to be able to remove the fan coil unit. It is suggested to use the return air

grille for this purpose which is strong enough for repeat access.

U Hotels & Resorts EU Technical Standards Manual

Page 44 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FURNITURE

Closets or Wardrobes

Built-in furniture must use solid elements such as masonry, wood frames etc. The wardrobe is a high quality element with finishes that match the room

decor. Materials used could be hardwood, brass, stainless steel, mirrors, etc. at least 150 cm in length & 70 cm deep.

Closets or wardrobes must be divided into two sections:

o Hanging space with a shelf on top for extra pillows and a rod for hangers with a free space below the rod 170 cm & min. 100 cm in length.

o Drawer / shelf with 2 to 6 deep drawers 60 cm deep & 50 cm wide with cut out front panel, easy slide castors and a safety stop.

The two sections may be separated by providing a wardrobe plus a chest of drawers.

U Hotels & Resorts EU Technical Standards Manual

Page 45 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Furniture should include the following:

Electronic safe, placed on the drawer furniture and mounted to the wall at a height of min. 90 cm from the floor. Suggested size is to accommodate

at least a 15” laptop (HxWxD mm) 206x425x370 or 17” laptop 206x437x502. The safe must be battery operated with 4 or 6 digit key code and

digital LED display. Recommended brands (VingCard/Elsafe and Onity).

Frame mounted on the back of the room door to display the disclaimer for room rate, instructions and hotel responsibilities (only if required by local

legislation).

Foldable luggage rack (WxD cm) 75 x 60 if no built-in luggage rack is available.

Closet doors should be rollout type on nylon rollers (no rails on the floor) and equipped with noise dampers. Alternately, sets of double doors can be

used if they do not interfere with the corridor or the main door.

Closet-light position and shelf shape will allow proper illumination of the space, (recommend space saving LED rope light).

Auto light switch, (normal – on, push – off, turns off when cupboard door closes). Switch, 2mm depression required for operation and 5.5mm total

travel. Switching 1A max (250V), thermoplastic moulding.

Natural or artificial ventilation flow should be maintained at all times.

Additional details concerning the equipment defined above may be included in either the Hotel Brief or the guestroom FFE list.

U Hotels & Resorts EU Technical Standards Manual

Page 46 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Curtains

The bay windows and windows should be equipped as follows:

Sheer curtain, single rail - full width.

Lined curtains with a minimum 80% blackout rubber coat backing with the two rails overlapping at least 20 cm in the middle. Cleaning needs to be

guaranteed.

Curtain finishes a maximum 1 cm above the floor (depending on floor finish) |track has to be a minimum15 cm above the window | coving to hide

the tracks a min. 15 cm above the false ceiling and 20 cm wide for a double rail of sheer and lined curtain.

13 – 15 gliders per meter of track | 1 bracket per meter | 2 end return covers | drawing rod mounted to the gliders for easy movement.

Needs to be fire retardant, washable and stain resistant.

Both sides of the window require curtain cavities of about 30 cm to guarantee total blackout.

U Hotels & Resorts EU Technical Standards Manual

Page 47 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Luggage Racks

The luggage rack can be fixed preferably next to the closet.

It should have a back to protect the wall a minimum of 30 cm.

The minimum dimensions should be (LxHxD cm) 120 × 45 × 60.

The top may be covered with stone or solid wood with a hairline stainless steel bars or other hard surface if the rack is fixed.

U Hotels & Resorts EU Technical Standards Manual

Page 48 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Beds

Standard dimensions: The preferred standard bed would have a wood frame with separate headboard and no box spring.

Twin 90 x 200 cm 2 beds per twin room

King 180 x 200 cm

Height of the foundation will be 20.3 cm (8”) and the foundation top to floor at 32 cm (12.6”).

The recommended king mattress type is “Slumberland Linear Pocketed Springing System PS1500” or “Sealy Posturepedic Ultra Plush”.

All mattresses require turn labels with four quarters (1 to 4).

The bed height from mattress crown to floor is about 59.5 cm (23.4”).

King size beds must have a reinforced metal frame and additional feet to give stability or if box spring is used two individual units combined in one

frame.

SLUMBERLAND SPECIFICATION

U Hotels & Resorts MATTRESS

Spring System Linear Pocketed Springing System PS1500

Mattress Type DOUBLE SIDE

Quilt Panel Ticking

Anti-Dust Mite fire retardant damask ticking FA3259

Composition : 60% cotton 40% polyester

Weight 230gm/m2

Quilt Material Composition : 60% cotton 40% polyester

Weight 230gm/m2

15 gm Nonwoven Spun bond

Border Ticking Medium Hazard Proof Damask Ticking

Quilt Material 240 gm Bonded Polyester Fibre

15 gm Nonwoven Spun bond

Filling Materials Top Layer 30 mm D 28 PU Foam Sheet

(Upholstery) Lumbar Support and Conwed Plastic Netting

2nd Layer 2x16 mm Hot Melt Pad(one side each)

U Hotels & Resorts EU Technical Standards Manual

Page 49 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Bottom Materials Same as above

Bottom Panel Same as above

Ventilator NA

Border Tape 36 mm Binding Tape

Spring

Coil Type Linear Pocketed Springing System PPS1500

Wire Gauge 1.80mm

Height of Spring 152mm

Border Wire Wire Gauge 5.0mm

Edge Guard Wire Gauge 3.5mm Edge Stabilizer Wire

Packaging Inner Packing:0.095mm PVC Sheet

Outer Packing: PE Bag

Label Knight Guard Special Label

Season Turnable Label

MATTRESS HEIGHT (TOP TO BOTTM) 280mm(11") +/-10mm

FIRMNESS FIRM

SPRING / COIL COUNT

SIZE 120 x 200

180 x 200

IMAGE

U Hotels & Resorts EU Technical Standards Manual

Page 50 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Brand standard requires a solid wood frame bed.

However if this is not possible the following mattress base will

need to be used. Box Spring

TOP PANEL

1 Ticking

Anti-Dust Mite fire retardant damask ticking FA3259

Composition : 60% cotton 40% polyester

Weight 230gm/m2

Layer 1 Firmilater (11mm. Hotmelt)

SPRING CONTRUCTION

2

Coil type Slumberland posture spring PS1200

Wire tension 1720-1940 N/mm2

Wire surface coating Anti-rust lubricant coated

Coil wire 1.8 mm Diameter

Border 5 mm Diameter

Helical wire 1.4 Diameter

Edge stabilizer 3.5 mm

3

BOTTOM PANEL

Glides & Castors Glide 4 , Castors 2

Ticking Non-woven backing 70/m4

4

BORDER PANEL

Layer 1 Non-woven backing 25g/m3

Layer 2 9 mm high density foam D25

Tape edge

White binding type

Anti Dust Mite fire retardant damask ticking FA3259

Composition : 60% cotton 40% polyester

Weight 230gm/m2

Wooden component Tropical hardwood (with kiln drying & pressure

treatment)

Height castors & glides 6cm (+/- 0,5cm)

Height of spring divan 25cm (+/- 0,5cm)

5 Packaging PVC Sheet (0.09 mm) 1 pc., PE bag (0.15mm) 1pcs

Conner protective cart box 4pcs

U Hotels & Resorts EU Technical Standards Manual

Page 51 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

BEDDING MATERIAL SPECIFICATION

MATTRESS PROTECTOR (placed above the topper)

Fabric : 50% cotton 50% poly 180TC

Colour : white

Size : King 183 x 203 cm

Twin 93 x 203 cm

Filling : polyester padding 130gsm

Style : elastic 4 corners

MATTRESS TOPPER

Fabric : 100% cotton 233TC fibre proof

Colour : white

Size : King 180 x 200 + 7cm

Twin 90 x 200 + 7cm

Filling : Air ball fibre

Weight : King 5280 g

Twin 3170 g

U Hotels & Resorts EU Technical Standards Manual

Page 52 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

BED SHEET

Fabric : 100% cotton combed yarn 180x120/60x60

300TC

Colour : plain white

Size : King 310 x 300 cm

Twin 160 x 300 cm

Layers : 1st sheet covers the mattress

2nd sheet will be folded at the head end

PILLOW: DEFINITION

U Hotels & Resorts EU Technical Standards Manual

Page 53 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

BACK PILLOW

Fabric : 100% cotton 233TC

Colour : white

Size : 20 x 35 inches / 50 x 88 cm

Filling : Microfiber balls

Weight : 1150 grams

FRONT PILLOW

Fabric : 100% cotton 233TC down proof

Colour : white

Size : 19 x 29 inches / 48 x 73 cm

Filling : 25% white duck down

75% white duck feather

Weight : 1000 grams

U Hotels & Resorts EU Technical Standards Manual

Page 54 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

PILLOW PROTECTOR

Fabric : 50% cotton 50% polyester combed CVC 100x80/40x40

180TC with zipper

Colour : white

Size : Back 20 x 35 inches / 50 x 88 cm

Front 19 x 29 inches / 48 x 73 cm

BACK PILLOW CASE

Fabric : 100% cotton combed yarn 180x120/60x60

300TC Trellis Garden

Colour : white

Size : 21 x 36 + 3 inches / 53 x 91 + 7 cm

Style : flap 7 inches

U Hotels & Resorts EU Technical Standards Manual

Page 55 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FRONT PILLOW CASE

Fabric : 100% cotton combed yarn 180x120/60x60

300TC Trellis Garden

Colour : white

Size : 20 x 30 inches / 50 x 76 cm

Style : flap 6 inches

DUVET

Fabric : 100% cotton 233TC down proof with self-piping

Colour : white

Size : King 270 x 235 mm

Twin 180 x 235 mm

Filling : 40% white duck down

60% white duck feather

Weight : King 870 g

Twin 635 g

U Hotels & Resorts EU Technical Standards Manual

Page 56 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

DUVET COVER

Fabric : 100% cotton combed yarn 300TC Trellis Garden

Colour : white

Size : King 275 x 240 cm

Twin 185 x 240 cm

U Hotels & Resorts EU Technical Standards Manual

Page 57 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Bedside Tables and Bed Heads

Each side of the king bed has a loose bedside table. Twin beds will have a central table between the two beds larger in length.

King bedside table min. (LxWxH cm) 50x40x55, depending on what will be placed on these tables: lamp, telephone, alarm clock, etc.

Twin bedside table min. (LxWxH cm) 70x40x55, depending on what will be placed on these tables: lamp, telephone, alarm clock, etc.

The height of the top surface of the side tables should be 5 cm lower than the mattress to make it impossible to knock against it.

The tables should allow room for the items such as books, keys, phone, glasses etc.

Bedside tables should have night lights mounted below which are individually wired to the bedside switch

The telephone is generally placed closest to the window table.

A shelf or a drawer should be provided, with ski-slope, easy slide castor and safety stop.

It is recommended that control panels are not built into the night table. This is only acceptable if the controls are easy to access and if they are

visible and accessible from a prone position.

The bed head must be designed for different sized beds and decor schemes.

The height must be such that it is impossible to bump one’s head on an edge. Bed height is 59.5 cm therefore the suggested height is approx. 120

cm min from floor to headboard edge.

The material must be easy to wash. (No fabric).

It is preferable to use built-in lighting to eliminate side table lamps.

U Hotels & Resorts EU Technical Standards Manual

Page 58 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Armchairs and Tables

A minimum of one armchair or one armchair and a small sofa if size permits.

With removable covers for easy cleaning or if fabric is used needs to be “Scotch Guard” treated.

There must be carpet gliders or felt stickers under the feet depending on the floor surface.

The seat height of the armchairs is approx. 45 cm.

Except for the sofa, upholstered armrests should not be used.

The foam used for the seats and cushions should be either latex or foam made without CFC-based expansion agents.

A side table allowing guests to take breakfast and dinner in their room (HxLxW cm) 54x70x50 or a minimum 65 cm in diameter.

If glass is used for the table top it must be non-reflective.

Desks and Chairs

The desk should measure at minimum (LxWxH cm) 140x60x75 only in business hotels and suites.

It should have a drawer large enough to contain office stationary for business hotels, minimum of 10 cm.

It should preferably be located near the window and should have enough area for a desk lamp to leave maximum workspace on the desk.

At desktop height, there shall be two spare international electrical outlets or one international outlet including two (2) USB chargers.

The desk should have a chair or a chair with arm rests low enough to slide under the top.

Mini-Bar

Absorption system (noiseless) – no compressors – automatic defrosting.

Minimum capacity 40 litres, external dimensions are approx. (W x D x H) 435 x 440 x 560 mm.

The refrigerator should be enclosed, however with good air circulation. The sides and the bottom free space between refrigerator and furniture

needs to be min. 5 cm, at the back of refrigerator it requires a min. 10 cm. The furniture should have a vent to release hot air which should be hidden

and not obvious on top of the furniture.

Located either in the closet under the TV or next to the seating area. Glass-fronts are possible, where adapted to the decor.

Including cabinet, shelves or drawer for the list below :

o Standard Room

1 Capsule coffee machine

4 Coffee capsules

1 Water kettle

U Hotels & Resorts EU Technical Standards Manual

Page 59 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

2 Cappuccino cups with saucers

2 Coffee spoons

2 High ball glasses (Mini bar)

2 Whiskey Tumbler (bathroom)

Condiments include tea, sugar/crème and snacks

Tissue box with tissues

o Suite Room

1 Capsule coffee machine

4 Coffee capsules

1 Water kettle

2 Madison red wine glasses

2 High ball glasses (Mini bar)

2 Whiskey Tumbler (bathroom)

2 Coffee spoons

2 Teaspoons

2 Cappuccino cups with saucers

2 Espresso cups with saucers

Condiments include tea, sugar/crème and snack

Tissue box with tissues

U Hotels & Resorts EU Technical Standards Manual

Page 60 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SAMPLE MINI BAR DESIGN WITH AIR GAP

U Hotels & Resorts EU Technical Standards Manual

Page 61 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SAMPLE MINI BAR TRAY ARRANGE MENT

U Hotels & Resorts EU Technical Standards Manual

Page 62 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

TV Cabinet

The cabinet, which can also hold the mini-bar, is an important decorative element and must be treated as such.

Where there is limited space built-in wall units are preferable in order to conceal cabling at the back of TV but the cabling should be easy to access.

U Hotels & Resorts EU Technical Standards Manual

Page 63 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Mirrors

There should be a full-length mirror near the closet and/or the bathroom door with a minimum size of (HxW cm) 140x45.

The mirror should be well lit (250 to 300 Lux).

Other decorative mirrors may also be placed in the room.

The mirrors must have a frame or bevelled edges.

Decorative Items

There should be at least two pieces of artwork or a backdrop per room, correctly hung and well lit.

The light illumination for the artwork may be one of the ambient lighting therefore controlled by the two-way switch.

The artwork must be hung in such a way that the guest may not remove them.

Also loose items for decoration can be added to make the room feel warm (it is suggested to have some budget available to decorate the hotel)

Balcony (if applicable)

The balcony equipment depends on the size. At a minimum there should be two armchairs with removable cushions and a table.

Outside furniture should be used, preferably in natural hard wood or cast iron (no plastic, resin, or painted wood).

Lighting fixtures for the balcony need to blend into the overall façade lighting.

Operating Equipment

For all equipment such as pillows, duvets etc., refer to the hotel’s dedicated OPE list

U Hotels & Resorts EU Technical Standards Manual

Page 64 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 65 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

BATHROOM

Concept

Fixtures

Electricity and Low Voltage

Coverings

Accessories

Towels

U Hotels & Resorts EU Technical Standards Manual

Page 66 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CONCEPT

The bathroom should never be smaller than 8 m2 and dark colour schemes should be avoided, except if the bathroom has dedicated lighting.

It is important to achieve a uniform look between the floor, walls and ceiling, which need to be in harmony with the rest of the room’s décor.

The bathroom shall be one of the areas worked on by the Interior Designer.

U Hotels & Resorts EU Technical Standards Manual

Page 67 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FIXTURES

Toilet compartmentalized with a minimum (WxL cm) 100x110.

Compartment door has a preferred minimum width of 70 cm.

If there are space constraints, provide a toilet alcove that is not within view of the bathroom entry.

Provide one wall-hung or floor-mounted water closet with low-water consumption and quiet flush design.

Avoid placing the toilet directly in front of the entry door. It can also be in a separate room (as per the Hotel Brief).

1 Vanity/washbasin unit with a glass, marble or stone top and ledge positioned 85 cm from the ground.

Minimum length of 140 cm with a minimum drop facing of 25 cm.

The vitreous china sink is mounted under the top so that the joint is not visible and the overflow is located opposite the mirror side.

Sinks placed on the vanity counter should not exceed a height of 90 cm. Vanity counter level should be between 60 and 70 cm.

A mirror needs to be placed on a strip min. 10 cm above the vanity unit.

Detached from the wall to provide back ventilation (could be LED backlit for a better atmosphere).

Shower cubical with a minimum size of (WxL cm) 100×120 with an anti-slip floor.

Cubical door with a preferred minimum width of 70 cm.

Minimum of 2 cm recess / threshold into the cubical. Ratio of fall towards trap is between 1:60 and 1:80.

The shower trap must absorb twice the shower in-flow to prevent overflows.

Bench/footrest at a height of 45 cm.

Security or triplex glass (laminated) door not reaching the ceiling, maintaining a gap of 20 cm to the ceiling.

No plastic, wood or aluminium can be used for the cabin frame.

Rain shower head concealed into the ceiling or wall mounted with a minimum rain shower head size of 8 inches or 20 cm, positioned a minimum

210 cm from the bottom.

Hand held shower with 1.20 m long hose attached to the wall with an adjustable flow bar, positioned at least 190 cm from the bottom.

All the fixtures shall be stainless steel and equipped with 3-hole high quality mixer-faucets, sound-rated and with colour-coding (Gröhe or similar).

The bath, basin and bidet are equipped with pop-up waste facilities.

Ventilation: the extraction vents shall be installed above the toilet bowl and the shower if the WC is separate. Flows shall be carefully studied to

avoid any fogging of the mirror.

The bathroom door shall allow the necessary air flow from the bedroom. It shall be equipped with an inside lock and can be unlocked from the

outside in case of emergencies. The same applies to the WC (if separate).

U Hotels & Resorts EU Technical Standards Manual

Page 68 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ELECTRICITY AND LOW VOLTAGE

All electrical devices and lighting fixtures must be located at a horizontal distance of more than 60 cm from the shower.

Fixtures or outlets fitted around the shower area at not than less 225 cm, from the floor and 60 cm from the unit must be special low-voltage fixtures

or watertight fixtures with a double insulation.

Accent lighting shall be provided in front of the mirror at face height and a level of 400 lux.

Adequate levels must be provided around all the other fixtures of about 250 to 300 lux.

Backup light shall be separate from the mirror lighting. All light fixtures require plastic protection sheets if mounted into the ceiling.

Provide a 110/220 volt razor outlet for international plug use.

All the electrical equipment must be protected by a differential circuit breaker of 30 mA. The main metal fixtures shall be connected by

equipotential coupling and be grounded.

Magnifying mirror on a bracket wall-mounted close to the vanity unit.

A speaker minimum 6 W connected to the bedroom T.V. and sound system with volume control.

Phone with on-hook connection (same line as the main bedroom extension), accessible from the toilet at a height of 135 cm from the floor. This can

be optional due to nowadays extensive private mobile usage.

U Hotels & Resorts EU Technical Standards Manual

Page 69 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

COVERINGS

Floors

Decorative tiles, stone or marble semi-gloss or non-slip finish, providing sound insulation to not disturb the rooms on lower floors.

Waterproofing for wet areas:

o at least 10 cm over the hob or step down onto the bathroom floor should be waterproofed

o at least 15 cm up the walls inside the shower walls needs to be waterproofed

o the vertical angle between any two walls in the shower needs to be waterproofed up to at least 180 cm high

o the entire bathroom floor needs to be waterproofed if hard-wood flooring

Terrazzo, carpets, plywood or pressed wood are excluded

Install a floor drain only when required by regulations in leisure hotels or those with a Japanese clientele. (The shower drain can also be

used for that purpose). In that case, the bathroom floor must be fully waterproofed.

Sharp edges must be avoided or guarded or rounded if present.

Walls

Decorative tiles, stone, marble and glass/mirror on all walls, as well as under the sink along with decorative elements.

Sharp edges must be avoided or guarded or rounded if present.

Glass will need to be laminated.

Ceilings

Green board (green dry wall) for damp conditions, humidity and the occasional minor splashes of water.

It is recommended to have cove ceilings with indirect lighting with the least number of down light fixtures possible.

Access holes require aluminium frames.

If the fan coil unit is located in the bathroom, a large enough access hatch needs to be provided (min. 80 x 50 cm).

U Hotels & Resorts EU Technical Standards Manual

Page 70 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ACCESSORIES

Shaving mirror, as listed above.

Toilet paper roll dispenser.

Towel rack for 4 towels below the vanity counter.

Sanitary hose on guest’s right side, next to the toilet

Towel bar on the shower door outside of the cubical. (Door handle and towel bar should be one piece).

Small towel bar at vanity counter, mounted below the counter.

A hook for sanitary disposal bags near the toilet bowl (or given with the amenities on the tray).

A double or triple robe-hook.

Retractable clothes line or fixture to dry clothing.

Waste bin below vanity counter or adjacent to the toilet.

All accessories should have the same finish as the faucets.

For all unattached accessories (stool, soap dish, wastebasket, scale, tissue box etc.) see OPE listing.

For special accessories see Chapter C 23, the Disabled.

Towels

SIZE

(inch)

WEIGHT

(lbs =12 pcs)

SPEC DESIGN COLOUR

Face towel 12 12 1.5 100% Cotton 20/2 Double loop White

Hand towel 16 32 4 100% Cotton 20/2 Double loop White

Bath towel 40 60 24.5 100% Cotton 20/2 Double loop White

Pool towel 40 80 28 100% Cotton 20/2 Double loop Coloured, as per hotel theme

Shower mat 20 30 10 100% Cotton 20/2 Double loop White

U Hotels & Resorts EU Technical Standards Manual

Page 71 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SAMPLE BATHROOM ELEVATION

U Hotels & Resorts EU Technical Standards Manual

Page 72 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SUITES

Distribution and Location

U Hotels & Resorts Suites

U Hotels & Resorts EU Technical Standards Manual

Page 73 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

DISTRIBUTION AND LOCATION

The distribution shall be based on the Hotel Brief. Suites are usually located on floors which offer the best view.

U HOTELS & RESORTS SUITES (2 room modules for one key)

Should include:

A large bedroom with bathroom and dressing room within one bay.

A sitting room/dining room with office corner within one bay.

An entrance from the corridor leading to the sitting room bay.

A toilet room with vanity unit next to the entrance.

A twin bedroom that can be connected to the suite at the sitting area with a connecting door or via the balcony (rentable separately as a lock off).

U Hotels & Resorts EU Technical Standards Manual

Page 74 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CORRIDORS

Elevator Landings

Corridors

Housekeeping Pantries

U Hotels & Resorts EU Technical Standards Manual

Page 75 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ELEVATOR LANDINGS

Wide enough with a minimum of 250 cm and separate from the rest of the corridors.

Include an in-house telephone with a direct connection to operator on off-hook within the lift landing area.

LCD TV panel for hotel information (business hotels only).

The decor should include plants, waiting areas with armchairs, mirrors, antique furniture, paintings or lithographs.

The ceiling and walls should be given special attention to make the guest forget about the waiting time.

Elevator doors should be graffiti proof.

Natural lighting wherever possible.

U Hotels & Resorts EU Technical Standards Manual

Page 76 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CORRIDORS

The corridors do not only connect the guestrooms to the rest of the hotel but are also a statement of the hotel’s personality. This personality is usually

expressed in terms of decorations and special provisions must be arranged in advance. This may consist of varied ceiling heights, lighting effects,

doorways for each guestroom, top quality wall coverings, carpets with special designs and different colours and interesting floor themes.

SAMPLE CORRIDOR ELEVATION

Double corridors with a minimum width of 180 cm (single corridors 160 cm).

Ceiling height with a minimum of 240 cm.

Strategic locations like elevator landings and housekeeping pantry doors must utilize subtle corner and wall guards to protect against trolleys etc.

Design of signage (see chapter C-22 Signage and the Corporate Identity Manual).

Service shaft doors should be mounted on hidden hinges and could be disguised as picture frames or similar to fit into the corridor to have the

traditional shaft doors removed.

Shafts, due to fire-safety, must be plugged at each flooring level and provide a pipe sleeve for each pipe.

Up to 90 cm from floor should be of a solid material, protruding min. 2.5 cm from wall finish to protect the surface. Stone, wood, and stainless are

recommended.

U Hotels & Resorts EU Technical Standards Manual

Page 77 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Fire hose boxes and other equipment should be built-in or placed in a recessed location so as not to be an obstacle but still remain visible.

The necessary inspection accesses shall be installed in the false ceilings or in a shaft.

Indirect lighting for corridors with accent areas to break up the monotony.

Door numbers and signage require pin spot lighting or enough lux to read them with ease.

The lift landings should have stronger lighting than corridors.

There should be wall skirting of a minimum 10 cm.

Provide power outlets every 8 m, 20 cm above the floor finish.

U Hotels & Resorts EU Technical Standards Manual

Page 78 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

HOUSEKEEPING PANTRIES

Each block, cluster or floor should have a pantry, accessible from the guestroom corridor and service elevator landing if applicable.

Located in front of the elevator and provide at least a width of 250 cm with access to the emergency stairway. The service elevator landing should

always be lit.

Provide a door closer, door stopper, corner and door guards and floor number plates (on the landing and in the stairway).

Each pantry area should have power outlets and one wall mounted telephone, located close to the elevator.

The pantry should include:

o Linen room, with closets or a separate area for supplies with shelving, that can be locked plus a linen storage area and space to store

housekeeping baskets or trolleys (For 25-30 rooms = about 15 m²).

o A water station (for bucket) and single service sink (hot and cold water).

o WC for the employees (accessible from the service elevator landing on every other floor).

o Access to the linen chute, if any.

o Ice machine on every other floor.

U Hotels & Resorts EU Technical Standards Manual

Page 79 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SURROUNDINGS DESIGN

Concept

Pedestrian and Vehicle Traffic

Parking

Exterior Lighting

Landscaping

U Hotels & Resorts EU Technical Standards Manual

Page 80 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CONCEPT

When approaching the hotel, the surroundings must convey a feeling of warmth and welcome. The façade along with the hotel signage is an integral part of the entrance.

The façade should be accentuated by special lighting and landscaped decorations.

Directional signs should be located at strategic locations to emphasize the hotel’s facilities (see chapter C-22 Signage).

The exterior areas should be located so to not to disturb the interior area with noise, lighting or disturbances, whether the interior is for relaxed or

linked to a special zone such as a nightclub.

In city hotels a possible link between the hotel and the city can be via an exterior restaurant with a terrace. This terrace can be protected with

screens of vegetation or by a transparent enclosure such as a veranda.

For leisure hotels, the garden and swimming pool must be the focal point of the architectural concept towards which all the public areas converge.

PEDESTRIAN AND VEHICLE TRAFFIC

Pedestrian and vehicle traffic must be separate and all abrupt crossings avoided. Space must be provided for a waiting area.

Provide 2 lanes of automobile traffic in front of the entrance with each lane about 3 meters wide.

o 1 lane for waiting automobiles

o 1 passing lane

The road surface design in front of the main hotel entrance should be iconic with a pattern of interlocking stone paving or other neat looking floor

finishes.

U Hotels & Resorts EU Technical Standards Manual

Page 81 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

PARKING

The parking area should be in a shaded area if possible and within a short distance of the hotel area without obstacles to cross and in keeping with

the aesthetics of the surroundings.

A water tap and drain should be provided in an area where it will also be possible to wash cars but out of sight of the lobby.

In order to avoid large spans of asphalt, the use of an “evergreen” pavement should be studied, involving the installation of grassy areas.

Where underground parking areas are used, they shall be equipped with a water tap, water drainage for car-washing (as above), and road gutters at

the entry point and the foot of the ramps as well as including necessary ventilation.

Access to the hotel shall be controlled (guard rooms, automatic barriers, CCTV, and intercom link to the reception).

Directional signage for pedestrians and vehicles shall indicate the floor levels and painted lines shall be used to separate parking spaces.

Signs directing pedestrians toward the hotel entrance should be designed to present a visual image of quality.

In areas accessible to guests, paint, bright lighting, colours and other design features shall be used in order to avoid any gloomy or insecure feeling.

Where there is valet parking and the hotel has more than 80 rooms, a driver’s lounge will be provided. It will include an intercom connection with

the main entrance parking desk, a T.V., toilets and chairs.

In certain circumstances a sleeping room with wet facilities should be provided for drivers. This is for remote hotel locations or if a limousine

company is engaged for the services.

U Hotels & Resorts EU Technical Standards Manual

82 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

EXTERIOR LIGHTING

Night lighting shall be designed as part of the landscaping, where the vegetation provides an illuminated route through which the guest moves.

Directional spotlights should be used more often than luminous bollards and lampposts.

The exterior lighting shall have the functions listed below, in the form of the corresponding circuits:

Roadways and parking areas lit by lampposts; a lamp height not less than 3m above ground.

Decorative lighting for gardens, flower beds, bushes and spotlights for fountains.

Floodlighting of the facades (glare from the facade lighting must not disturb guest’s comfort in the rooms).

Sign lighting.

These circuits shall be controlled:

Automatically by timers. Each circuit must be programmable for different hours and scenes.

Manually from an electrical switchboard located in the reception area or control room.

Several electrical networks shall be provided for:

Watertight outlets.

Swimming pool.

Reduced garden lighting.

Activities.

Actual exterior lighting.

Heavy duty power supply circuits for outside functions in the resorts gardens e.g. buffets, shall be installed at strategic points.

In the activity areas, installation shall include watertight distribution boxes containing power outlets fixed to a concrete base. They shall be

operated from the control panel. The installation shall be completed by standby terminals on circuit breakers on electrical switchboards adjacent

to these areas.

Swimming pool lighting shall use 12 volts and be controlled from a separate control panel or control room.

These swimming pool spotlights should be removable.

The lighting fittings shall be selected based on the decoration project, keeping energy saving in mind.

U Hotels & Resorts EU Technical Standards Manual

83 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LANDSCAPING

It is advisable to call upon a landscape architect with a good knowledge of local vegetation to make an overall study of the exterior and interior

landscaping.

Existing trees should be kept for maximum integration with the surroundings and landscaping whenever a green field site is planned.

An automatic sprinkler system and draw-off taps should be installed where needed.

Topsoil, trees and plants should be added in sufficient size and quantity to create a greenery ambience as soon as the hotel is nearing opening.

Inside the hotel, it is preferable to group plants as accents rather than in dispersed pots. They should be placed in planters integrated with the

architecture and decoration. Those should be fitted in consideration with:

o Waterproofing

o Drainage

o Watering facilities

In a resort hotel, landscaping quality is as important as the architecture. Consequently, the landscape architect must work together with the

building architect in establishing the design, and he should participate in final realization of the layout drawings.

Swimming pool surroundings as well as beach layout and access to the sea, shall be integrated into this study if necessary.

A complete drainage system must allow quick evacuation of excess rainwater, especially in all accessible areas such as parking, walkways, and

sports areas etc. (see Chapter T8 Sanitary Plumbing).

U Hotels & Resorts EU Technical Standards Manual

84 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

RECEPTION

Entrance

Lobby

Guest Reception

Front Desk

Front Office Back of House

Schematic Layout

U Hotels & Resorts EU Technical Standards Manual

85 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ENTRANCE

Architecture – Decor

The hotel must have street frontage in accordance with its stature and importance.

The entrance faces the main access road.

Clearly and immediately visible and identifiable.

Consider elevated entrances.

Maintain accessibility.

Direct visual and pedestrian contact with the hotel’s setting.

Consider traffic and pedestrian flow.

Always use clear glass in this area.

Consideration of the quality of the materials, night lighting and signage all contribute to the U Hotels & Resorts specific appearance effort.

The layout will allow through-views to the outside and views of the landscape and the surroundings from the lobby entrance especially at resort

hotels.

Awning / Canopy

The awning, porch or canopy is an important architectural element which marks the entrance.

Needs to cover the road access (minimum 2 lanes).

Protection against rain with sufficient cutter capacity to ensure no overflow.

Well-lit at night.

If necessary, provide a bell (luggage), taxi and/or valet driver desk with telephones for hotels above 80 keys.

U Hotels & Resorts EU Technical Standards Manual

86 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LOBBY

Decor – Architecture

The lobby and reception area must be adjacent to the entrance and on the same level.

It must create a warm welcoming feeling for its guests. U Hotels & Resorts does not want to create a “monumental” feeling.

The decor emphasizes open spaces and views of the outside with as few obstacles as possible such as voluminous curtains, very low ceilings or

hand rails.

The overall character is provided by using a few items of quality, such as local craftwork or original artworks and furniture.

If water features are available, they shall be studied and calculated in terms of aesthetics, noise, spray pattern (diameter), lighting, pumps,

balance tank etc.

Avoid using dark colours.

Look for quality materials which are to be highlighted with natural lighting whenever possible.

Artificial lighting should only be used to indicate circulations and signage as well as create decorative and functional accents.

The lighting should be split into several circuits, all controlled by dimmers with 3 to 4 settings. The dimmer controls and other circuits, as well

as the following commands, are all located in the back of house of the reception area:

Provide 10/16 A+E power outlets 20 cm above the floor after every 750 cm around the public areas and adjacent hallways.

U Hotels & Resorts EU Technical Standards Manual

87 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GUEST RECEPTION

Purpose

The Lobby has two functions. These functions can be separated if needed with the help of the elevators or a seating area located in between

these two locations.

o Reception Area

The front desk is the central point for all the hotel’s guest services.

Reception personnel must be able to see the arriving guest immediately.

Guest must be able to recognize the front desk without guidance.

The front desk should be a desk and not a counter which acts as a barrier.

Does not need to be in direct contact with the entrance and requires a free space between without obstacles.

The desk should have clear signage and well-arranged natural lighting if possible.

o Meeting, Information and Activity Point

The lobby is a starting point for all the services that enliven the hotel such as conference rooms, restaurants, bars, gardens and

leisure activities.

Acts as a meeting place & information area.

Includes a comfortable waiting area which could be connected with a lounge bar.

Avoid adding mezzanines that break the flow of circulation.

Keep high ceilings to give an overall spacious impression.

From initial design phase the internal signage needs to be given attention for guests arriving at the lobby and those exiting the

elevator.

U Hotels & Resorts EU Technical Standards Manual

88 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FRONT DESK (Guest Reception)

Needs to be visible and accessible from the main entrance without blocking the view of the lobby or hindering the transparent view from the entrance.

Front office desk requirements (in all cases):

Desk ;

o For sitting reception desk- L,W,H 300 x 90 x 74 cm per station with 4 chairs for guests & 2 chairs for employees.(1 station

accommodate 2 employees)

o For standing reception desk - L,W,H 230 x 90 x 74 cm per station (1 station accommodates 2 employees)

One computer notebook or very slick designed screens with wireless mouse and keyboard computers per station connected with LAN.

Provide filing slots, printer, guest key card encoder, key rack, credit card terminal, and passport scanner for each station below the desk. Digital telephone.

UPS (power back up for computers if a desktop version is chosen.)

7 double sockets for all gadgets.

2 telephone lines (telephone & credit card terminal)

4 LAN connections (CAT 6)

U Hotels & Resorts EU Technical Standards Manual

89 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FRONT DESK – SITTING STYLE

U Hotels & Resorts EU Technical Standards Manual

90 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FRONT DESK – SITTING STYLE

U Hotels & Resorts EU Technical Standards Manual

91 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FRONT DESK – STANDING STYLE (* Only with AHS approval)

U Hotels & Resorts EU Technical Standards Manual

92 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FRONT DESK – STANDING STYLE (* Only with AHS approval)

U Hotels & Resorts EU Technical Standards Manual

93 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Bellboy Station (if required):

With a view of or at the entrance.

These areas do not need specific signage.

They must be distinguishable by their personality and décor.

Requires a telephone.

Two-way speaker system to the drivers’ room (if available).

Close access to the luggage room.

U Hotels & Resorts EU Technical Standards Manual

94 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FRONT OFFICE (BACK OF HOUSE)

Located behind the reception desks and hidden away and inaccessible to the guests, these areas include:

Open office for the front office team with shared working stations.

Each station requires a computer terminal (100 key hotels require 2 work stations).

Reservation stations (100 key hotels require 2 work stations).

Each station comprises of a desktop computer with UPS power back up, connected to a LAN line, and a telephone.

Private office cubical for the Front Office Manager (minimum 7 m2).

A luggage room, with:

o Secured access.

o Possible access from the Port Cochere and leading to the service elevator.

o Luggage and cart storage area.

o A whiteboard.

U Hotels & Resorts EU Technical Standards Manual

95 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SCHEMATIC LAYOUT

Front Office Back of House (small hotel)

U Hotels & Resorts EU Technical Standards Manual

96 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SCHEMATIC LAYOUT

Front Office Back of House (large hotel)

U Hotels & Resorts EU Technical Standards Manual

97 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

PUBLIC CORRIDORS & SHOPS

Concept

Lifts

Stairways for Public Areas

Toilets

Shopping Area

Concession Shops

U Hotel & Resorts Boutiques

U Hotels & Resorts EU Technical Standards Manual

98 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CONCEPT

Operating principles:

Corridors and passageways branching off the main lobby must be designed to allow the guest to quickly understand the hotel layout.

Must have unity in style and décor.

Should follow the overall concept of interior design linking the public areas with the guest rooms.

Provide rooms for storage of maintenance materials, thoughtfully distributed and equipped with water supply and drainage.

Wall finishes need to be durable with solid materials such as stone, concrete etc. especially from floor level up to 0.90 m. to prevent the wall

from scratches. Wallpaper is not recommended.

Equipment:

The use of skylights should be avoided and indirect lighting be used instead.

Lighting of decorative elements and/or of ceilings is preferred.

Provide power outlets within the corridors every 750 cm, and 20 cm above the floor, including store rooms.

Shaft access sizes should be minimized to small doors and operate like a window.

Shafts between floors should be closed off with steel plates or filled with concrete.

Doors:

They must be sturdy and able to withstand intensive use.

Must be fire-rated for 90 minutes.

Acoustic proof.

Electronic locks are required and systems with RFID are preferred. Those locks should be used for all types of doors and not only guest room

doors, to manage and control work flow.

U Hotels & Resorts EU Technical Standards Manual

99 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ELEVATORS (LIFTS)

The elevator bank must be visible from the reception area.

When guests come down from their rooms, they must see the lobby and find easy the directions to hotel facilities.

As elevator cars are confined spaces and can be claustrophobic to certain guests though this can be remedied through:

o Wall coverings with special decorations.

o Active areas like TV screens with advertising or information.

o Glass walls may be used to give a view of the outside.

The coverings and doors must be made from materials resistant to shock, tearing and graffiti.

The button panel should be easy to read and list the main functions of the different floors (see chapter T15- Lifts).

The interior designer shall determine how they are to be handled (see chapter C-22 Signage).

The landings must include furniture and decorations.

U Hotels & Resorts EU Technical Standards Manual

100 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

STAIRWAYS FOR PUBLIC AREAS

Stairways should be equipped with the following:

Where fitted with carpets add “stair step nosing”.

Where fitted with stone add “non-skid strip nosing” or use anti slip stone with a rough surface.

A handrail.

Continuous equal lighting flowing over the stairs.

Floor numbering.

U Hotels & Resorts EU Technical Standards Manual

101 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

TOILETS

Organisation:

Toilets should be located near the lobby, restaurants, and conference and administration rooms and by other facilities as required. Toilets must not

open directly into the restaurants and bars or public areas under any circumstances.

Men’s and women’s toilets must be separate, even if they have a common entrance.

They should each have a vestibule or zigzag access.

The direction in which the doors swing open should be studied in relation to the viewing angles.

Compartments should be enclosed, have locks and be ventilated as per the below dimensions.

Privacy panels between the urinals (partition).

A toilet for the disabled should be provided for the main lobby and conference rooms (see chapter C 23- The disabled for toilet layout).

A small cleaning closet should be provided for each floor in the public areas.

U Hotels & Resorts EU Technical Standards Manual

102 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SAMPLE DRAWING OF PUBLIC TOILET

U Hotels & Resorts EU Technical Standards Manual

103 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Decor

The decor must avoid looking “clinical”.

The qualitative aspect must be kept in mind. Make sure that materials and fittings used can be easily cleaned.

U Hotels & Resorts EU Technical Standards Manual

104 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Equipment and Accessories.

The following should be installed in each compartment:

Double toilet paper roll dispenser.

Sanitary hose, located on the right side of guests.

Drainage, located under the sanitary hose.

Garbage bin.

Clothes hook behind the door.

Sliding bolt with indicator which can be unlocked from the outside.

The following should be provided in the toilets:

One full-length mirror.

Hot air hand dryer or hand towel tray.

Soap dispenser for antibacterial hand soap.

Door closer for the toilet entrance door.

Disabled toilet for men and women at the lobby and conference area.

Mechanical ventilation.

Efficient deodorising system.

Automatically flushing urinals with either a timer or photoelectric cell.

Vanity area (women’s toilets).

U Hotels & Resorts EU Technical Standards Manual

105 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SHOPPING AREA (IF APPLICABLE)

Organisation:

The shops should never constitute a significant part of the hotels outside frontage.

They should be organised as a shopping arcade located near and visible from the lobby.

This area shall be one of the focal points of activity in the hotel.

In keeping with this feeling, the sterile, bland standardisation common to shopping malls is to be avoided.

Locations on the mezzanine, basement levels or in dead-ends are not recommended.

There are two types of shop: those operated under concession and those managed directly by U Hotels & Resorts.

U Hotels & Resorts EU Technical Standards Manual

106 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CONCESSION SHOPS

Depending on the situation, these shops can either be delivered to the concessionaires fully equipped and decorated (by the hotel interior designer), or

delivered as a shell with the technical elements for connection (electricity, telephone lines & LAN, plumbing, heating, ventilation), but without any

decoration. This part is then carried out by the tenant’s interior designer.

In both cases, the design must be approved by U Hotels and Resorts Management.

The type and number of shops is defined in the Hotel Brief.

Decor

Interior design and equipment, conducted by the tenants, (or their interior designer) must have prior approval from U Hotels and Resorts Management

and the hotel interior designer, who will remain in charge of decorating the shop front windows, protective grilles and signs.

Equipment

The following equipment is always part of the hotel general construction, not only of its shop fittings:

Plumbing, standby water supply, drainage, metering, central air conditioning.

U Hotels & Resorts EU Technical Standards Manual

107 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U HOTELS & RESORTS BOUTIQUES

Electrical distribution panel, metering, general circuit breaker

2 telephone lines, metering

Unfinished floor

Walls or partitions (undecorated)

Signage

Storage area, (delivered unfinished)

U Hotels & Resorts EU Technical Standards Manual

Page 108 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CUSTOMER SERVICES

Business Centre / Library

Swimming Pools

Ancillary Facilities

Fitness Centre

Spa & Wellness

Tennis Facilities

U Hotels & Resorts EU Technical Standards Manual

Page 109 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

BUSINESS CENTRE / LIBRARY

Depending on the market and guest expectations, business hotels and city hotels will have separate business centres; however resorts will feature areas

called libraries where guests can check their personal emails or just sit and read a book. For smaller properties, the library can be combined with the lounge

bar.

General Organisation

The Business Centre/Libraries should be well located and visible from the hotel lobby or the hotel main corridors if possible.

This area should include:

A sign outside the room displaying opening hours.

A hostess desk, cabinet, locker with space for a computer with modem, work processor, spread sheet and printer (connected to the LAN).

A secretariat area with shelves for documentation.

A fax, photocopier, telephone and conveniently placed clock (business hotels only).

Office supplies and equipment conforming to the OPE list.

Comfortable armchairs or couches, a low table, floor lamps and two desks with two laptops or large sized tablets which are connected to the WIFI

system and connected to a central printer.

Smaller hotels can incorporate the library into the lobby lounge, which accommodates book shelves and has terminals to access the internet for free.

U Hotels & Resorts EU Technical Standards Manual

Page 110 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SWIMMING POOLS

General Concept

In all cases, the swimming pool must conform to local technical and safety regulations (notably depth marking, life safety equipment, presence of a

lifeguard, push-button alarms and pump switch-off, separate instruction panels for warnings and rules (large letters), etc.).

The shape of the pool is not restricted and the rules are only limited by imagination and originality. Thus, round or rectangular swimming pools

rarely correspond to these criteria and are not desirable.

It is preferable for the swimming pools to be designed with skimming or overflowing water i.e. infinity edge.

Access to the pool should be as direct as possible to avoid crossing the hotel lobby.

Wherever possible, swimming pools should be located on the ground floor in contact with the rest of the site rather than on terraces.

The swimming pool area should be protected from strong winds.

Pool dimensions depend on the Hotel Brief and should be adapted to the possibilities of the site. In all cases, it should provide a clear length of

around 25 m.

Pool surroundings should be at least twice the area of the pool. This space should have enough room for sunbathers and the installation of

umbrellas and tables with enough clearance for traffic.

Provide plants and landscaping around the pool surroundings, and create several “natural” areas for more privacy.

U Hotels & Resorts EU Technical Standards Manual

Page 111 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

The buildings should not shade the swimming pool (study cast shadows according to latitude and to Northern or Southern hemispheres). However,

some shaded areas are required close by. When creating shaded areas with vegetation, avoid using deciduous trees near the swimming pool.

In all cases, the swimming pool should have a shallow and deep end and a separate pool for children (maximum depth 30 cm). The layout of this

pool should be designed for safety (barriers) and easy surveillance, while limiting the amount of noise.

Access to the pools shall be through full-sized steps with handrails rather than ladders.

The shallowest part of the main pool shall be at least 1.20 m deep.

The deepest point of the main pool should be at least 1.40 m deep.

Slopes in the area around the pool and a drainage system should prevent rainwater from running into the pool.

Resort Hotel Swimming Pools

In a resort hotel, the recreational character of the pool should be accentuated with “extras” such as waterfalls, whirlpools, Jacuzzi, slides etc.

The landscaping should be abundant and closely linked to the water theme: small islands with grass and plants or rocky borders with small

waterfalls into the main pool for example.

At the seaside, an overflowing type swimming pool gives a very strong visual connection between the pool and ocean.

Consider providing a small pool for children in a shaded, protected and fenced (>1m) area if the hotel is targeting families.

The pool surroundings should be large enough and well equipped to accommodate all of the hotel guests, keeping in mind that a person on a sun

lounger takes up 2m².

It is preferable for guests on sun loungers to looking at the pool and ocean view (if applicable) and to face the sun. Nevertheless, it is necessary to

provide some shaded areas around the pool zone.

The swimming pool should be close to the restaurants and bars; it creates an environment where everyone can see or be seen and increases business

at the sales outlets. However, its location must also be carefully studied in order to avoid noise nuisances to rooms.

U Hotels & Resorts EU Technical Standards Manual

Page 112 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Whirlpools and Jacuzzis

Special care must be taken to provide:

Adapted hand rails to prevent falls

Slip-free floors

Extra water-purifying devices

Outlets large enough to avoid any suction risk

Proper temperature control to avoid burns from water or accessories

Control for children’s’ access (1 m peripheral fence with gate)

Materials and equipment (see the FFE list for mobile equipment and furniture)

The design of all built-up areas, especially the shape, materials and colours of the low wall and posts, should take into account that guests in swimming

suits may come in direct skin contact with the hard surfaces.

The pool deck should be covered with a skid proof, washable and non-porous material; plas-wood (artificial wood) is preferred.

Provide foot baths, railings and showers on the main passageways. Footbaths are especially important when the swimming pool borders a sandy

beach.

The swimming pool should be built traditionally (reinforced concrete and tiling); metal pools should not be used.

The depth must be indicated in 15 cm-high letters at each end and each change of depth, along with “no diving” signs.

U Hotels & Resorts EU Technical Standards Manual

Page 113 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Diving boards should be avoided for safety purposes.

The pool should be equipped with 12 V underwater lighting. It should be removable and have enough cable to rest the spotlights on the edge of the

pool for maintenance.

The pool surroundings and direct environment should be attractively and practically lit at night. Provide power outlets conforming to regulations for

entertainment activities.

The pool surroundings should be built with a slope to drain off rainwater.

The pool’s bottom tiling may include a decorative design (no logos) which may be reproduced on the pool decks.

See chapter T-8 Plumbing for the pool’s water treatment.

Water in the pools should only circulate through overflow gutters; the level of the water is then flush with the pool edges.

The drainage and filtering outlets shall be planned to avoid any situation where a suction effect could occur, with special care taken for children’s

pools and Jacuzzis.

All grilles must be securely fastened.

For outdoor pools, the terraces and their approaches should be equipped with enough outlets to connect a sound system, portable kitchen devices,

special lighting, etc.

The swimming pools should have all the necessary operating equipment: water treatment and cleaning equipment, handrails, etc.

U Hotels & Resorts EU Technical Standards Manual

Page 114 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SWIMMING POOL RULES: EXAMPLE

POOL RULES

The following rules are designed for your safety and convenience.

WARNING:

NO DIVING

No Lifeguard on duty.

● No running.

● No topless.

● No diving.

● Spitting or blowing the nose is prohibited while using the pool.

● Do not use while under the influence of alcohol or drugs.

● Anyone under 12 must be accompanied at all times by a person over 12 years of age.

● Absolutely no glassware is allowed in the pool area.

● Appropriate swimwear must be worn in the pool.

● No cut-off jeans or long pants allowed.

● No flotation devices or toys except back bubbles and water wings are allowed in the pool.

● Pushing, wrestling, ball games, dunking, splashing or causing undue disturbance in and about the pool will not be tolerated.

● All persons using the pool do so at their own risk and sole responsibility.

● The hotel accepts no liability for any injury, death or loss of personal items associated with the use of the pool.

● No pets allowed.

Pool Hours: 06.00 am to 08.00 pm

In case of emergency, use the phone marked EMERGENCY

U Hotels & Resorts EU Technical Standards Manual

Page 115 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ANCILLARY FACILITIES

Locker and Shower Rooms (Business Hotels and City Hotels):

Provide men’s and women’s locker rooms with changing rooms, showers, toilets and sinks.

Access to the pool should be through the shower room with a required passage through the footbath.

Towel Distribution Kiosk and Access Control

Provide a kiosk equipped with shelves for clean towels and a counter for distribution to guests.

Adjacent to the fresh towels it requires a basket for used towels which can be built into the same cabinet. Another basket would be required at the

vanity counter within the locker rooms.

Kiosk includes a desk and telephone for the pool supervisor and storage for the first aid equipment.

Storeroom

In the same area as the locker rooms and kiosk.

For storing swimming pool equipment: parasols, pool furniture, cleaning equipment and gear for diving lessons.

U Hotels & Resorts EU Technical Standards Manual

Page 116 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FITNESS CENTRE

The swimming pools locker rooms are often combined with body care and fitness equipment to create a Fitness Centre for city type hotels.

For resort type properties a shower room is adjacent to the swimming pool area with no lockers.

Depending on the Hotel Brief, the men’s and women’s facilities should be well separated.

This area should also include the following areas:

o Sauna and/or steam bath.

o Reception area with towel and bathrobe distribution counter

o Storeroom for sports equipment and various bathing or massage products.

Gym/Fitness Centre

o Equipment’s depend on space availability, for an 120 key hotel following equipment are suggested;

3x Treadmills

2x Elliptical machines

1x Upright bike

1x Recumbent bike

1x Cable motion

1x Dumbbell

3-4 Selectorized weight equipment

3x Flat and adjustable bench

o Equipment should be of good quality and 7-10 year frame warranty like Life Fitness, Technogym, Precor or Cybex

o Floor covering should be purpose gym flooring; (Gym above guest rooms should be on double floors, due to noise pollution)

Gym rubber tiling

Parquet, with solid wood to be able to maintain the floor if it gets scratched

Do not use carpets, except where strong air ventilation and an ozone machines are included.

The Fitness Centre may include additional facilities such as tennis, squash courts, volleyball and a golf simulator as well as a health food bar or

restaurant.

U Hotels & Resorts EU Technical Standards Manual

Page 117 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FITNESS RULES: EXAMPLE

GYM REGULATIONS

The gym is accessible 24 hours on a daily basis for hotel guests only; however please note there may be no fitness attendant on duty at various times

of the day.

Should you wish to have personal instructor, please contact reception and this can be arranged with prior notice.

Please read the instructions provided for the operation of the equipment before undertaking any exercise.

If you have not participated in an exercise program recently you are advised to consult a doctor before undertaking any activity.

Children and teenagers under the age of 12 years must be accompanied by and be under the supervision of a parent or guardian when using any gym

equipment.

Please do not bring glassware of any kind into the gym area.

Eating and smoking is not permitted in the gym.

As a courtesy to other guests, please wipe equipment with a clean towel after use.

Appropriate sport shoes and gym clothing are required to be worn at all times.

No wet bathing costumes are permitted in this area.

In case of any emergency please use the house phone, dial “0” and indicate the nature of your emergency.

All persons using the gym area do so at their own risk and sole responsibility. The hotel accepts no liability of injury or loss associated

with the use of the fitness centre gym and / or its equipment.

U Hotels & Resorts EU Technical Standards Manual

Page 118 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GYM SERVICE STATION: EXAMPLE

U Hotels & Resorts EU Technical Standards Manual

Page 119 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SPA & WELLNESS

The following information is a general overview only. The brief for this area should be drawn up with a specialized consultant.

SPA

These standards provide general guidelines and features of spas when operated jointly with U Hotels & Resorts. It does not attempt to define all the

possibilities and features of such spas in general.

For any given location and depending on the site, size, climate, supply and demand and technical considerations, a specific brief for an adapted spa will be

drafted together with a specialized consultant.

Thus the first step in the spa definition must be to designate this consultant. Along these guidelines, a site visit shall then be organized as a priority in order

to develop the Brief on an adapted technical basis.

The spa should include:

Access from the hotel, as well as for outside guests.

A reception – administration area with

o reception desk

o office displaying the treatment schedule

o retail space

o waiting area

Corridors connecting the different treatment areas.

Manager’s office.

Preparation area for herbs and spices to be used and combined with the employees’ area & toilet.

Treatment rooms – number of rooms will depend on the size of hotel.

Wet facilities area such as steam room, sauna, jet pool, or Vichy shower.

Relaxation area and yoga or meditation room.

All treatment rooms are open to daylight with outside private views wherever possible.

A quiet relaxation area with music, both open to daylight and natural surroundings.

Lounges with:

U Hotels & Resorts EU Technical Standards Manual

Page 120 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

o Relaxation areas facing the view (if applicable).

o Reading corner / library.

Health food bar / drink station

Plant rooms and service rooms including :

o service entrance

o personnel lounge

o technical room for all spa facilities

Personnel locker rooms with vanity counter, showers and toilets.

Linen storeroom and supervised area for guests’ personal belongings.

As for the Spa, a shop and connection to a beauty salon is desirable.

U Hotels & Resorts EU Technical Standards Manual

Page 121 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GENERAL TECHNICAL INFORMATION

In each treatment room, the following should be provided :

o Full-height millwork with a sink, a linen drop basket, and cabinet for product/linen storage.

o Large floor drains in the showers (mud baths).

o Seating for foot ritual.

o A shower (if possible)

The main technical space should be easily accessible for any problems with the plumbing, drainage, floor drains, etc.

Floors should be completely waterproof with ceramic up stands and baseboards.

Treatment bed should be accessible from all sides with 0.90 meter of circulation space.

Power cables for mobile units with rollers should be high off the ground (no wires on the floor), or, provide floor outlet.

All lighting should be dimmable.

Independent licensed music provided by a central music system with volume control for each section.

SPA DISCLAIMER: EXAMPLE

SPA DISCLAIMER

Our hotel’s spa treatments are strictly provided for general relaxation purposes only and are not intended in any way to be a

substitute for professional medical diagnosis or treatment by a certified health professional for any condition, medical or otherwise.

Hotel and its management and staff hold no responsibility whatsoever on all liabilities, claims, expenses, damages and losses, including

legal fees, arising out of or in connection with the spa treatments, services and/or facilities.

U Hotels & Resorts EU Technical Standards Manual

Page 122 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SPA LAYOUT: EXAMPLE

SINGLE TREATMENT ROOM

U Hotels & Resorts EU Technical Standards Manual

Page 123 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SPA LAYOUT: EXAMPLE

DOUBLE TREATMENT ROOM

U Hotels & Resorts EU Technical Standards Manual

Page 124 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LOCKER EXAMPLE

U Hotels & Resorts EU Technical Standards Manual

Page 125 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

TENNIS FACILITIES

Tennis courts must be covered with an officially approved surface:

o i.e. Astroturf, clay, cement

o have a 1% gradient from the axis centreline to prevent too much rainwater accumulating

o peripheral drainage surrounding the court must be provided

The court’s main axis should be north-south for open-air courts.

Avoid shadow casting on the courts (trees, buildings).

Avoid planting trees with extensive root systems near the tennis courts.

Showers, lavatories and locker should be designed in common with the other sports and fitness centre facilities.

The equipment must be designed in line with regulations approved by the International Tennis Federation.

Provide a separation fence between 2 adjacent courts.

Open air courts:

o Provide night lighting using fixed floodlights on lateral supports at least 9 m high.

o Lighting should be at least 300 lux through the volume in which the ball moves, i.e., up to around 4m from the ground, with a uniformity

factor of >7.

o Court lighting should be controlled by a programmable timer.

U Hotels & Resorts EU Technical Standards Manual

Page 126 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LAYOUT OF OPEN AIR COURTS

Covered courts:

The lighting required in the playing area is 500 lux. It can be provided by LED lamps etc. parallel to the court’s lengthwise axis.

U Hotels & Resorts EU Technical Standards Manual

Page 127 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LAYOUT OF COVERED COURTS

U Hotels & Resorts EU Technical Standards Manual

Page 128 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

RESTAURANTS AND BARS

U Hotels & Resorts Restaurant Concepts

Regulatory Standards

Food and Beverage Principles

All Day Dining

Speciality / Theme Restaurants

Swimming Pool - Beach Restaurant/Bar

Bar Principles

Lobby Bar

Wine / Club / Exotic Bar

Cigar Lounge

U Hotels & Resorts EU Technical Standards Manual

Page 129 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U HOTELS & RESORTS CONCEPT

The U Hotels & Resorts food and beverage concept is based on:

Its ability to adapt this know-how and precisely adjust its offer to exceed the expectations of potential clientele, particularly local clientele.

The concept, for each restaurant, is based on a “stand alone” philosophy. In other words, each restaurant should develop its own identity separate

from that of the hotel, giving as much as possible the feeling that it is an independent operation.

However from a technical standpoint this concept, along with its objectives, must integrate a certain number of rules in terms of location, access,

layout, organisation, equipment and decor.

The food & beverage brief and customer capacity vary considerably, since each project depends on the market potential and type of hotel

(“business” or “resort”). However, there are always a certain number of basic concepts to consider, for example:

o Specialty restaurant

o All day dining

o Themed restaurants

o Swimming pool-beach restaurant/bar

o Bar

o Wine bar

The design, layout and equipment of these public F & B premises must respect a certain number of technical standards:

o Conform to local regulations (or agreed referenced international regulations by default). When both are available, the most stringent

provisions shall be applied.

o Meet the qualitative objectives of U Hotels & Resorts defined in the image standards.

o The precise food & beverage brief is defined for each project in a dedicated document.

U Hotels & Resorts EU Technical Standards Manual

Page 130 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

REGULATORY STANDARDS

Health and Safety

The premises used as restaurants, bars, etc., must be suitably equipped to avoid any risk of contamination to the food products that are served or eaten:

Certain premises and equipment should not be installed nearby (waste collection, polluted effluents, etc.).

Public areas should be pressurized higher than the adjacent premises to avoid any transmission of odours, notably from the kitchens.

Walls, ceilings and floors as well as fittings should be designed to enable constant cleaning.

Adjacent public lavatories should never be directly accessible from the restaurant or bar areas. Hand-towel distributors must be installed close to the

sinks.

Health and safety regulations for F & B facilities must be respected and followed as per the 40 point check list provided by U Hotels & Resorts

Access for the Disabled

Generally, all F & B sales outlets must conform to disabled access standards. In the absence of local regulations, at least 1 restaurant and 1 bar should meet

these requirements.

Smoking Areas

It is quite common to have enclosed public areas, restaurants and bars as non-smoking areas.

Wherever possible, all restaurants and bars must have an area for smokers which should be located on the outdoor terrace. The same counts for the public

areas, which should allocate smoking areas with ashtrays and be well-marked.

U Hotels & Resorts EU Technical Standards Manual

Page 131 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FOOD AND BEVERAGE PRINCIPLES

Each food or beverage outlet within the hotel will receive a dedicated Food & Beverage brief including:

Theme or purpose of the outlet.

Specific interior guidelines with proposed materials, finishes, art effects etc.

Operational details with the amount of service stations, POS terminals, opening time, meal periods, manpower etc.

Proposed entertainment systems such as music, TV’s, live bands etc.

Indicative food and beverage menu.

Proposed uniforms.

Layout

Restaurants and bars should be grouped on the same level as the hotel’s main centres of activity.

They should have physical and visual contact with the outside and should never be located underground and, if possible, not on an upper floor.

The swimming pool restaurant/bar or some bars may sometimes be installed in a specific area.

As often as possible, food outlets should be grouped around or very close to the main kitchen for direct service. In other cases, the satellite kitchen

assigned to them should be at the same level and immediately adjacent to the areas served.

Whenever possible, their assigned areas should be free of:

o Columns.

o Architectural elements which create constraints should be removed or isolated such as:

o corridor effect

o dead corners that are difficult to integrate

o differences in levels

o noisy areas or sources of pollution

U Hotels & Resorts EU Technical Standards Manual

Page 132 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Signage-Access

In addition to inside access, the restaurants and bars are located to provide direct access from the outside (separate from the hotel entrance).

Inside visibility and access for the hotel’s guests should be clear and simple with the appropriate directional signage, in conformity with U Hotels &

Resorts standards.

The outside access is attractive and well-lit and sets of double doors.

Windows should always be clear and protection from the sun provided when necessary.

Each sales outlet is indicated by a specific sign, both outside and inside, in harmony with the general signage.

Lighting-Electricity

Several circuits should be used in the electrical installation including a backup circuit.

The lighting must be adjustable using several pre-programmed dimmers, located at the reception desk of each outlet.

Provide special lighting with low voltage spotlights for buffets and displays, special lighting for a band in the entertainment area and lighting for the

menu boards and signs.

Provide enough electrical connections for at least:

o Reception / hostess desk : power outlets, 1 lecturer light

o Computerised cashier stations installed in the room: computer LAN and electrical outlets (with backup) and credit card terminal outlets.

o Maintenance: 1 baseboard power outlet along the walls every 7 m and at the base of each column.

o Service stations: outlets for hot plates and P.O.S. equipment (LAN and electrical).

o Live music: suitable power outlets built in the baseboards or floor.

o In the buffet area, built-in outlets for mobile equipment.

Buffet

When a buffet style breakfast or meal is served, it should preferably be composed of fixed or mobile, refrigerated, heated or neutral elements, plate-

warming and induction chafing dish units and live station if possible.

Electrical outlets should be positioned to allow changes in the arrangement of buffets.

In general, the buffets must be visible from the restaurant entrance, easily accessible by customers even at peak times (double the service lines).

U Hotels & Resorts EU Technical Standards Manual

Page 133 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Computerised P.O.S. System and Cash Registers

According to U Hotels & Resorts specifications, the order taking and bill-printing terminals must be set up next/within to the service stations

(P.O.S. system) and linked to the local area network.

Each cashier stand (one to two per outlet, in addition to the ordinary P.O.S. terminals) should have a credit card swipe machine (EDC), linked to the

telephone network.

Sound System

Provide a quality sound system (with adjustable volume for every area) which can receive either one of the hotel’s central channels, or

programming specific to the different sales outlets. It should be installed in the back office server rack. This is likely to be in the form of a PC with

soundcard and loaded with licensed music connected to an amplifier and speakers.

Telephone

Each sales outlet should be equipped with an extension/telephone line that can be switched over (for restaurants) to the F & B Management office,

and /or the switchboard to take reservations when the restaurant is closed.

The phone must be on the reception or hostess stand and the ringer volume adjustable.

A cordless phone should also be provided for guest use.

U Hotels & Resorts EU Technical Standards Manual

Page 134 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SERVICE STATION LAYOUT

U Hotels & Resorts EU Technical Standards Manual

Page 135 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

HOSTESS COUNTER

U Hotels & Resorts EU Technical Standards Manual

Page 136 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Ventilation-Air Conditioning

Each room should have its own air conditioning thermostat, controlled according to its level of occupancy.

Whenever possible, particularly for the bars, natural ventilation should be provided.

Avoid creating a cold barrier along the windows.

When regulating the air conditioning, compartmentalized dining rooms should be kept in mind.

Kitchen

Provide an entry space with two sets of double swinging doors (no centre post) between each sales outlet and its service area (kitchen, pantries).

This conceals the area and provides soundproofing.

The doors will be provided with bull’s eye windows and kick protection plates on both sides.

The space between the two sets of doors in each entry should be large enough (1.5 meters) to hold a removable double step doormat.

The services bars, open kitchens and special pantries are described in chapter C15-Kitchens.

Service Stations and Cashier

The service stations (see drawings) should be spread around the room, one for every 20 to 25 place settings.

In addition to their service and clearing functions they must include the computerised point of sales (P.O.S.) and bill-printer terminals.

They should have spare power outlets as well for the P.O.S. and printer terminal power and LAN (RJ45) outlets.

In the restaurants one station, located near the entrance or in the bar counter, is dedicated to the cashiers’ stand. In gourmet and specialty

restaurants, this is generally located in the kitchen pantry area. In the bars it is incorporated into the bar counters.

Furniture and Equipment

Apart from the functional elements described below, the decor of all outlets should always include objects and artwork directly related to its

personality and properly chosen and highlighted by the interior designer.

The furniture should be selected by the interior designer with U Hotels and Resorts Management approval according to the concept of each outlet,

with the following standards in mind:

U Hotels & Resorts EU Technical Standards Manual

Page 137 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SPACING OF CHAIRS AND TABLE DIMENSIONS

All Day Dining

Speciality Restaurant

Bistro Restaurant

PERSONS

TERRACE %

ROOM%

SIZE

ROUND CAFÉ TABLE 2 30% 0% Dia 0.80

SQUARE TABLE 2 30% 40% 0.80×0.80

SQUARE TABLE 4 40% 50% 1.20 ×1.20

ROUND TABLE 6 10% Dia.1.40

PERSONS TERRACE % ROOM% SIZE

SQUARE TABLE 2 50% 30% 0.80× 0.80

RECTAGULAR TABLE 4 50% 40% 1.40× 0.80

ROUND TABLE 4 0% 20% Dia. 1.20

ROUND TABLE 6 10% Dia.1.40

PERSONS % SIZE

SQUARE TABLE 2/4 40% 0.80× 0.70

RECTANGULAR TABLE 4 50% 1.20 ×0.70

ROUND TABLE 4 OPTIONAL Dia.1.40

ROUND TABLE 6 10% Dia.1.60

U Hotels & Resorts EU Technical Standards Manual

Page 138 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Bars

Furniture height to be determined (meal service)

Table with adjustable bases should not be used as they are not stable.

The restaurant table height should be 75 cm and the chair seats 45 cm high.

The bar table depth should be 45 cm (60 cm if snacks and meals are served).

Chairs and armchairs must be equipped with silent plastic disks on hard floors and gliders on carpets.

If the seats and backs are covered with fabric, they should be treated against stains and be removable and washable.

When the furniture includes benches their height and seating depth must be carefully gauged to the height of the table for maximum comfort (max.

height difference 30 cm). A prototype should be tested and submitted for approval.

PERSONS SIZE

SEATS AT COUNTER AS PER HOTEL BRIEF

ROUND CAFÉ TABLE 2/3 Dia.0.80

ROUND CAFÉ TABLE 4/5 Dia. 1.10

RECTANGULAR TABLE 4/6 0.70 × 1.10

TABLE FINISH TOP BASE

ALL DAY DINING &

SPECIALITY

wood or marble with rim or hard

aesthetic and washable material

Cast iron or varnished

metal

BISTRO RESTAURANT hard/washable material

chosen by interior designer

wood or varnished cast

aluminium

BARS covering chosen by interior

designer

interior designer’s easy

maintenance choice

U Hotels & Resorts EU Technical Standards Manual

Page 139 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Deli / Gourmet Restaurant

Service stations and tables arranged against the walls must be equipped with rear stops.

Table decor

This category includes the following items:

tablecloth, napkins

flatware (silver plate or polished stainless steel)

dinnerware

glassware

all other items used to set tables (vases, candleholders, etc.)

Their selection is based on qualitative criteria:

suitable for professional use (resistant, durable)

matches or expresses the restaurant decor and concept

financial budget of each project

Their technical specifications are to be found in the OPE list.

U Hotels & Resorts EU Technical Standards Manual

Page 140 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ALL DAY DINING

Concept

The All Day Dining outlet is the hotel’s main restaurant. It is located close to the lobby and served by the main kitchen.

A lively and friendly restaurant with its formula and decor adapted to meet client expectations: either typical and traditional or adapted to the local style.

Depending on the situation, it can be positioned as an informal restaurant.

It is most often a reasonably priced restaurant open for breakfast, lunch and dinner (possibly even afternoon tea and late dinner).

Serves a continental buffet and a la carte menu, possibly even a brunch once a week.

The decor is typical and cordial but its quality and personality must be outstanding. The atmosphere is informal and friendly.

The cooking will be both western and local fare.

Operation

In most hotels, it is the F & B sales outlet that serves the largest number of individual customers for breakfast, lunch and dinner. Its capacity should be

adapted to the market and the total number of restaurants in the hotel.

The classic design is composed of 3 main areas: bar, dining room, and outdoor terrace.

The bar has 2 functions:

Attract and draw the clientele in from the outside. It should be located close to the outside entrance.

Waiting bar serving snacks and beverages and a service bar serving the restaurant’s beverages.

Whenever possible it should be located next to the kitchen serving the all-day dining restaurant.

Dining Room

Mostly used for serving meals but may also serve afternoon tea, snacks or late suppers depending on the time of day.

U Hotels & Resorts EU Technical Standards Manual

Page 141 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Terrace

Open or covered depending on weather conditions; air conditioned or heated if necessary.

It should have a wide view to the outside through sliding glass doors.

Mostly used for serving snacks and beverages during the day.

Meals can also be served during peak hours (extension of the dining room).

The all-day dining can accessed from the outside through a specific entrance, but it also has direct access from the lobby for hotel guests.

Minimum area requirement: 2 m²/chair

Decor and Equipment

The seating and table arrangement should be separated into different areas, shapes and heights to avoid monotony.

The ceiling design must incorporate into the room’s general decor and add to the harmony. Technical elements (lighting, air conditioning, sound

system) must also blend with the decor.

The quality of day lighting is particularly important. The windows must be clear.

Lighting should be indirect and carefully designed. All lighting should be installed over 1.80 m from the floor, so as not to be obtrusive. No

individual lighting is necessary. The floor should never be lit, unless a high quality and easily maintained material is used.

The benches and chairs must be set up to serve tables for 2, 4, 6, and 8 diners.

The décor and art effects’ major aspects should be drawn from what makes this market place popular

The furniture should be simple and durable but comfortable and in character with the type of restaurant.

The bar counter with any kind of durable top should be equipped with a foot rail. The bar counter’s basic equipment is identical to that described in

chapter C 14 Kitchens; additional equipment such as a draft beer installation may be added depending on the Food & Beverage Brief.

Flowers and plants (notably on the terrace) should be carefully arranged as they are part of the decor concept.

U Hotels & Resorts EU Technical Standards Manual

Page 142 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SPECIALITY RESTAURANT

Concept

The hotel’s specialty restaurant usually (but not exclusively) serves refined cuisine with a special theme to stand out in the local restaurant scene.

It plays a fundamental role in how the hotel, its general activity and its food & beverage service is perceived locally (particularly banqueting business), and

is a reflection of the brand image of all U Hotels & Resorts hotels.

Its main characteristics (other than the food served) are a refined decor with personalised, superlative service.

It should serve lunch and dinner.

The classic or modern decor should be elegant, refined and very comfortable.

Operation

Provide a separate entrance from the roadside if possible to give a free standing feel to the outlet.

Provide a small reception and beverage bar as a waiting area with seating possibilities.

The seating amount for the restaurant should be determined according to the initial market study and as defined in the Food & Beverage Brief.

Provide 2 small private rooms adjacent to the dining area (with a private entrance if possible) to accommodate between 8 and 12 people.

Space the table’s well-enough apart to reinforce the feeling of comfort and luxury and to provide a calm and private setting at each table and

facilitate service around the chairs.

Recommended density: 3 m²/ chair.

Décor and Equipment

The restaurant’s decor must reflect sophistication and peace. The atmosphere and style should reinforce the idea of space, comfort, luxury and

refinement.

Natural lighting is necessary for the lunch service.

The artificial lighting must be adjustable and be flattering to both diners and food.

In order to divide the room into several areas, provide folding screens or openwork partitions which look part of the restaurant.

The floor must be covered with a stretched, high quality woven carpet except in high traffic areas and tropical countries where it is preferable to use

a high quality, easily maintained hard floor covering with occasional rugs.

The chairs must have wooden arms low enough to slide under the table.

Provide small service tables (one for every 10 place settings).

U Hotels & Resorts EU Technical Standards Manual

Page 143 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

A spot lit “show piece” (tapestry, pottery, sculpture etc) should mark the entrance to the restaurant.

Walls and ceilings should be made with sound absorbent materials for the acoustic comfort of guests.

Small stools should be available for ladies handbags etc.

THEMED RESTAURANTS

These restaurants are a basic element of the hotel’s food and beverage activity and their decor must create a completely different surrounding. Minimum

area requirement: 2m²/ chair.

LOCAL CUISINE RESTAURANT

This restaurant’s essential quality is its authenticity and credibility which must initially show through the decor and interior design.

Creating this type of restaurant requires an in-depth study of the habits and customs of the country in which the hotel is established.

These factors must be taken into account at the start of the project.

The restaurant’s kitchen, most often independent, should meet the special requirements of the type of cooking served and the work habits.

An outside location is frequently used.

THEMED CUISINE RESTAURANT

The aim of this restaurant is to use a typical concept based either on the culinary tradition of a country or on a range of foods (grilled, seafood, etc.) or even

a restaurant style (steakhouse, tavern, tapas bar, etc.) and develop the appropriate surroundings and entertainment. The theme and decor must be developed

to a maximum degree, without turning into a caricature, in order to offer a completely unique eating and entertainment experience. Many elements can

create this experience, such as cooking or preparing food “a la minute” in front of the guest.

U Hotels & Resorts EU Technical Standards Manual

Page 144 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FOOD MARKET

The “Food Market” comprises of several small restaurants: traditional, local or themed (with the characteristics defined above) and gathered in one area

(mall, promenade, and square).

The wide choice of restaurants, decors, foods and prices is the main attraction.

The Food Market is above all a centre of activity and aimed at the local clientele as well as hotel guests.

It should be designed to create unity.

Although every restaurant should have its own typical decor, the central area (mall, promenade, square, etc.) must have a coherent and attractive style

different from the hotel’s usual decor. This style should highlight the windows, facades and characteristic signs of each sales outlet. On a practical level,

these restaurants can be totally independent from the central facilities, which are usually far removed. Their kitchen, pantry and storage areas are separate,

although some of them may be shared. Because several outlets may be grouped this way, the capacity of each should be limited (about 40 seats).

SWIMMING POOL – BEACH RESTAURANT/BAR

This outlet has a simple menu and several functions. It serves:

lunch and dinner,

snack, sandwiches and beverages all day

as a centre of activity for buffets and theme nights (particularly in resort hotels)

This restaurant must be designed as an informal area for relaxation but functionally equipped for complete operational autonomy. In certain cases, this

outlet only acts as a bar (see following paragraph).

Its layout and functions vary greatly between “business” and “resort” hotels.

Business Hotel

The restaurant or “pool-snack” serves lunch, snacks and beverages during the day and sometimes dinner.

In certain hotels (limited potential market), it may act only as a bar, in which case it should be designed for this purpose only.

U Hotels & Resorts EU Technical Standards Manual

Page 145 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Resort Hotel

Here the beach restaurant/bar plays an essential part in the hotel’s entertainment in general and acts as a liaison between the beach and swimming

pool.

It must therefore be designed as an independent and autonomous restaurant and serve:

o Meals using prepared or pre-cooked food

o Beverages and refreshments

o The swimming pool and beach

o It is also an ideal sales outlet for buffets and theme nights.

In its most complete version, the restaurant/bar should include the following areas:

o bar

o service counter for finishing and /or serving meals

o open cooking-preparation area : barbecue

o pantry area with the following functions :

­ service pantry

­ Cooking - preparation area (with extraction fan, grease filters, etc.)

­ dish, pots and pans washing area

­ refrigerated storerooms

­ temporary garbage collection area

Ventilation, air conditioning and soundproofing of pantry areas must be designed to avoid any nuisance and optimise working conditions.

The layout should be based on the dominant winds.

Provide a service access for carts.

U Hotels & Resorts EU Technical Standards Manual

Page 146 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Decor and Equipment

The lighting and sound system must be designed to accommodate entertainment or dancing and should be integrated with the landscaping of the

pool. A special place should be reserved for this purpose (podium).

Special care must be given to the sound system, which must be of high quality but avoid any excess noise for the hotel guests. (Distance, screens,

orientation etc.).

The decor should have a local theme. Local architectural touches and the use of local crafts should underline the originality of the swimming pool

restaurant/bar.

The furniture should be simple, comfortable, functional and different in the meal area, which may be a terrace (covered or open depending on

weather conditions) or the “beach/pool” relaxation area. It should be weather and rot-resistant, easily cleaned, in light and bright colours and of

“natural” materials: quality synthetic resin, rattan, teak, treated ecru canvas, etc.

There should be enough tables, chairs, café tables and parasols to meet the needs of the Food & Beverage Brief.

Since the tables are usually not covered, the table tops must be made of an attractive and easily cleaned material.

Equipment marked with advertising (regardless of the sponsor’s quality) is never to be used.

Provide a shaded area: verandas, canopies (made of traditional materials), parasols, etc.

Provide an additional storeroom (aside from the swimming pool equipment storeroom) to store the various items required for special events.

U Hotels & Resorts EU Technical Standards Manual

Page 147 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

BAR PRINCIPLES

The term “bar” means any sales outlet whose main activity is the sale of beverages, with or without alcohol, possibly accompanied by limited food service

(cocktail snacks, etc.). Bars may be quite varied and are differentiated mainly by their setting and decor.

Bars should be designed to provide easy access for hotel guests as well as local clientele and close to a busy passageway or area with considerable

activity.

(There should be clearly indicated signs and directional signage).

Regardless of the type of bar (club, lounge, waiting area, theme (exotic) or discotheque), the technical facilities must include:

o a bar counter with :

On the guest side

­ A hard (stone, wood or metal) totally washable material for the top (height = 110 cm ; width = 40 cm minimum), with a slight

overhang

­ A foot rest (height = 20 cm)

On the service side: (H = 85-90 cm)

­ Front refrigerated unit, double sink, cocktail unit, POS and credit-card terminal plus spare outlets and telephone.

­ Back refrigerated unit equipped with doors and shelves, bottles displayed in the top part (unit must be locked when bar is closed:

sliding panels or rolling shutters).

o a pantry with :

­ Beer pump and storage as per the Hotel Brief

­ Storage for the day

­ A glass washing area with glass washing machine

­ Icemaker

­ Hot and cold water sink with dish rack

­ Possibly a coffee machine

U Hotels & Resorts EU Technical Standards Manual

Page 148 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

The pantry should be located behind the counter area (direct access) and be large enough to provide the bar with enough autonomy during opening

hours and avoid any traffic linked to clearing or supplying through the hotel’s public areas.

The bars should be equipped with:

o A service telephone and cordless phone.

o Independent sound system.

o Light dimmers.

o Video-projector integrated in the ceiling with built-in electric screen, according to the Hotel Brief.

o Band area if applicable with all the necessary outlets, according to the Hotel Brief.

o TV outlets.

Provide service stations with P.O.S. and Printer terminals.

For the signage, refer to the Corporate Identity Manual and chapter C-22 Signage.

U Hotels & Resorts EU Technical Standards Manual

Page 149 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SAMPLE BAR DRAWING

U Hotels & Resorts EU Technical Standards Manual

Page 150 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LOBBY BAR

Concept

The bar should be open and integrated near the hotel lobby to create a pleasant extension of the hotel. It is a natural waiting and meeting area, very

visible and easy to reach and usually located in a public traffic area.

Operation

The bar serves all types of beverages, as well as coffee and tea, day and night.

It may act as the waiting area for the brassiere.

It includes 2 areas:

o A discrete and more intimate area.

o A table area visible from the lobby.

Decor and Equipment

It is preferable to use hard floor coverings.

The furniture should differ from area to area.

The terraces should include small tables, chairs and a few stools around the bar, while the more intimate area should have light armchairs and

settees (avoid ottomans).

U Hotels & Resorts EU Technical Standards Manual

Page 151 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

WINE / CLUB / EXOTIC BAR

Concept

This type of bar is enclosed, and has a “private club” atmosphere, refined setting and comfortable facilities that make it an ideal meeting point for

local clientele and hotel guests. It plays an important role in integrating the hotel into the city’s lifestyle and can be themed around a wine bar.

Operation

This is an enclosed bar highlighting the sales of wines located near the restaurants.

Decor and Equipment

Its atmosphere is intimate and its decor refined and comfortable with armchairs and low armless chairs.

The furniture should be arranged to accommodate groups of 2 to 5 people.

Provide an area for entertainment (piano or even a band) with power outlets and sound system.

The floor should be covered with high-quality, woollen carpets stretched on underlay.

EXOTIC BAR

This is a theme bar differentiated by its decor and playfully entertaining atmosphere.

It is an essential entertainment sales outlet for certain hotels.

It operates like the club bar and can be substituted for the latter.

U Hotels & Resorts EU Technical Standards Manual

Page 152 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CIGAR LOUNGE

Concept

The cigar lounge, or cigar bar, allows after meal smoking and coffee and liquor drinking in a very classical and comfortable atmosphere.

Operation

Located close to and working in co-ordination with one of the main restaurants.

There is a small counter, used mainly for service.

Decor and Equipment

Different themes are possible, the British-club, with leather-covered “Chippendale” furniture being the most obvious.

It is a quiet place with a thick carpet, antiques and a fireplace where applicable.

The cigar and liquor storage is enhanced, to emphasize the preservation and quality selection of the products.

Special care is taken to provide proper ventilation and avoid any spreading of smoke to adjacent areas.

U Hotels & Resorts EU Technical Standards Manual

Page 153 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CONFERENCE AND FUNCTIONS

General Principles

Access Lobby / Foyer

Ballroom (multi-purpose room)

Meeting Rooms

Decor

Lighting and Equipment

Furniture

Back – Of – The – House Areas

Audio – Visual Management Alternatives

U Hotels & Resorts EU Technical Standards Manual

Page 154 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GENERAL PRINCIPLES

Operating Principle

The design and decor of the facilities and function rooms should reflect a multi-functional use.

They usually give onto open spaces such as foyers and corridors and include cloakrooms and public toilets.

Whenever possible they should be located on the ground floors with separate entrances.

Service corridors independent from those of the public serve the different rooms and lobbies.

These rooms should benefit from natural lighting during the day but must be possible to black-out the openings during projections.

Wherever possible they should have outside terraces and gardens for smoking areas and or events.

Rooms may be grouped or separated by soundproof folding partitions, integrated in the architecture.

o These soundproof, non-combustible folding partitions can be handled by one person, they do not require a ground track (noise reduction 48

dB (A) or STC, including ceiling insulation, to achieve an in-situ better than Dn or NR45), and are used to vary utilization of the rooms,

particularly the dimensions of the ballrooms.

Sufficiently large storage spaces, well-distributed and accessible by all rooms, should be provided to store the mobile furniture:

o Movable raised platforms, dance floors, decorations, chairs, tables, etc.

o It must be possible to store all banquet equipment outside of the function rooms.

The floors of each conference room, including the service corridors, must resist an imposed duty load of 500 kg/m² minimum.

A service entrance should be provided for truck delivery of banquet and exhibition equipment and include loading dock, goods lift, sash openings

and doors. Minimum width: 250 cm, height: 240 cm.

U Hotels & Resorts EU Technical Standards Manual

Page 155 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ACCESS LOBBY / FOYER

It communicates with the hotel lobby and if possible has another direct access to the outside.

All the lobbies should absorb the increase in traffic caused by the activities of the rooms, without there being any repercussions on the hotel’s

regular operation.

If there is a difference in levels between the entrance and the conference rooms, specific elevators and/or escalators or stairs must be provided.

In addition, a staircase should constitute as integral architectural element and limit the use of mechanical means of access.

The area has to be multi-functional to be able to accommodate coffee breaks / buffets or exhibitions or displays.

U Hotels & Resorts EU Technical Standards Manual

Page 156 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

BALLROOM (MULTI-PURPOSE ROOM)

Purpose

It must be suitable for a wide variety of uses:

Conferences and meetings

Weddings

Banquets and cocktail parties

Exhibitions, fashion shows

The ceiling height must be proportional to the room size. Normally a minimum height of 5.5 m is required.

Conferences

Provide professional audio visual systems currently in use:

o Wireless microphones

o HDMI access to projectors with audio

o Hidden screens

o Pre-set lighting system with different themes

The equipment must be dividable so that each part of the room can be used individually.

Banquets

A satellite kitchen makes it possible to serve a large number of meals prepared in the main kitchen (hot and cold transfer system.) Service doors to

kitchen and set-up areas are double, thus forming an air lock.

U Hotels & Resorts EU Technical Standards Manual

Page 157 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

MEETING ROOMS

They are designed for meetings and small conferences.

Most of them should be supplied by the satellite kitchen of the ballroom via the service

corridors.

The rooms should be located to receive as much daylight as possible.

Provide professional audio visual system currently in use:

o Wireless microphones.

o HDMI access to oversized television screens or projectors with audio.

o Hidden screens.

o Pre-set lighting system with different themes.

U Hotels & Resorts EU Technical Standards Manual

Page 158 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

DECOR

The décor has to be adaptable to accommodate all aspects from a working environment to festive settings.

The finishing materials should be extremely resistant.

o Door edges need to be protected

o Doors should have a bracing system to keep them open

o Walls, up to 0.9 -1.0 m should have a hard surface such as stone above alternate panels of mirroring and padded material to soften the room.

o Floors: Axminster carpet (80/20 - wool/nylon) or hard surface such as stone with carpet rugs

It should be possible to modify all the decor elements (including lighting) to expand utilization possibilities. The decor should be designed so that

each room has a personality that corresponds to its name, within a uniform setting.

The meeting rooms should be identified by individual 22” TV screens, recessed into the wall adjacent to each meeting room access.

U Hotels & Resorts EU Technical Standards Manual

Page 159 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LIGHTING AND EQUIPMENT

Requires a dimmer system with minimum of 6 to 8 theme settings from a working environment to a festive setting for:

o Conferences

o Presentations

o Entertainment

o Weddings

o Fashion Shows

Separate stage lighting is required in larger function rooms.

Any chandeliers should not obstruct video or any other projections.

Individual built-in and hide-away projectors and screens for each room.

Specific temporary lighting should be provided for buffets (along one end of the room).

Emergency lighting blocks (emergency exit and ambient lighting) must be carefully integrated in the decor.

There is a clear distinction between room lighting, which is fixed and entertainment lighting, which is additional (and often subcontracted to outside

firms).

The banquet areas should also be able to accommodate the installation of equipment specific to the different types of events: video projector,

movable decor, light suspension bridge, portable A/V control board, stage curtains, screen, buffets, exhibits, etc.

With this in mind, the different rooms and foyers should be equipped with the following equipment also perfectly integrated in the room decor:

Room control boards (switches, pre-programmed control buttons);

Located in each room close to the entrance at 120 cm from the floor. A faceplate which controls the following functions:

o Light switch with pre-programmed light settings.

o Volume control.

o “Up and down” controls for ceiling recessed screens.

o “Open and close” controls for black-out curtains.

U Hotels & Resorts EU Technical Standards Manual

Page 160 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Conference Modules

Each room should contain a minimum of one face plate 30 cm above the floor containing:

o Telephone & LAN access (RJ 45 with CAT 6E cabling).

o TV outlet (Digital or Analogue, depending on the guest room system).

o Minimum 2 HDMI outlets connected to the control booth.

o Minimum 4 outlets of earthed power sockets of 220V with international face plates.

There should be enough of these modules to limit the amount of electric cables on the floor; a minimum of 1 per room and within the foyer or

approximately every 8 meters apart. One station should be close to the podium location of each room.

Power supply 16 A+E electrical outlets with 2 phase and 32 A+E protected high voltage outlets with 3 phase and 415V located within each room

close to the stage area.

Fixed hanging bars for spotlights and moving heads. The associated electrical outlet boxes should be concealed behind trap doors in the drop

ceiling.

Lighting bar conceal hanger for large ballroom

U Hotels & Resorts EU Technical Standards Manual

Page 161 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Plates with double hooks set in the drop ceiling space, with trap doors for access and used to hang a light suspension bridge for shows. Along each

plate electric connection boxes with outlets linked to the control booth.

LCD projector mounts, concealed behind trap doors in the drop ceiling. Next to each support in the drop ceiling space, LCD projector connection

boxes linked to the conference module (power outlet + remote control and video link: Barco system).

Built – in projection screens, controlled from the conference modules and the control booth.

U Hotels & Resorts EU Technical Standards Manual

Page 162 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Speakers in the ceiling (and on the wall in the main function room) linked to the control booth including subwoofer for the main function room.

Blackout curtains in front of windows, electrically controlled from the conference modules.

Mouldings for wall hangings, on the periphery of rooms and the foyer.

Lighting tracks with low voltage spotlights integrated in the ceiling on the periphery of rooms to light the boards

Decorative tracks recessed in the drop ceiling on the periphery of certain rooms to hang various items (stage curtains, mobile decor, etc.), identical

to the mobile wall tracks.

Maintenance electrical outlets all around the room at every 8 meters if possible combined with the conference module plate.

Portable telephone outlets at the entrance of each room and in each foyer for the hostesses.

Direct TV outlets in each room within the conference module system

Surveillance cameras and remote video cameras linked to monitors in the control booth and with the ability to project onto the screens within the

rooms.

The air conditioning in each room should take into account the heat generated by:

o Lighting

o Entertainment lighting

o Hot buffets and live stations

o Maximum occupation during cocktail parties, i.e. 0.75 m²/person

Each room must be independently controlled with thermostats in the room and not accessible to the public. The trap doors in the drop ceiling should

be made of metal, without hinges.

U Hotels & Resorts EU Technical Standards Manual

Page 163 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

BALLROOM AUDIO AND VISUAL DIAGRAM

U Hotels & Resorts EU Technical Standards Manual

Page 164 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

MEETING ROOM AUDIO AND VISUAL DIAGRAM

U Hotels & Resorts EU Technical Standards Manual

Page 165 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FURNITURE

The furniture must be flexible in order to adapt to various types of meetings. It should be solid and light. Chairs and armchairs should be stackable. See

Hotels OPE list.

Within the foyer reception only desks with chairs should be permanent units which are movable if required. Also if space is sufficient within the foyer area

seating corners should be created with coffee tables.

U Hotels & Resorts EU Technical Standards Manual

Page 166 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

BACK OF THE HOUSE AREAS

Employee toilets for both men and women.

Sufficient amount of storage space near the rooms or along the service corridors, to store all the mobile banquet furniture. Provide 20% of the ball

room’s surface area.

Audio visual control booths with specific storage room (centralization of all conference audio-visual equipment, and in certain cases, that of entire

hotel).

Optional offices and optional storage for an AV manager, as per the Hotel Brief (equipment identical to that in administrative offices).

U Hotels & Resorts EU Technical Standards Manual

Page 167 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

AUDIO – VISUAL MANAGEMENT ALTERNATIVES

Using Outside Services

In this case, rooms should be built with all the basic equipment in terms of wiring, connections and furniture with management assigned to an integrated

subcontractor.

This reduces the investment in terms of equipment and implies complete subcontracting of labour, equipment and maintenance.

Not Using Outside Services

This requires a substantial investment in terms of equipment and U Hotels & Resorts personnel to manage and maintain the installations.

The design must enable simple utilization. The equipment should be chosen from local distributors capable of providing the appropriate replacement

equipment and service.

U Hotels & Resorts EU Technical Standards Manual

Page 168 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ADMINISTRATION

General

Meeting Rooms

Offices Accessible to Guests

Other Offices

U Hotels & Resorts EU Technical Standards Manual

Page 169 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GENERAL

All offices should, if possible, have natural lighting.

The exact number of offices is defined in the Facility / Hotel Brief.

A separate workstation will be provided for the General Manager’s Secretary.

The accounting department, the computer room and the General Cashier are located in the same area.

Each working station will have 1 telephone and 2 LAN (R.J. 45) outlets and 2 double electrical sockets.

See FF& E listing for furniture and office equipment.

MEETING ROOMS

Located in the middle of office area and equipped with a white board and LCD projection equipment.

U Hotels & Resorts EU Technical Standards Manual

Page 170 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

OFFICES ACCESSIBLE TO GUESTS

These offices should be able to receive guests or suppliers through the welcome area and its waiting area without passing through the service corridors.

This concerns the following positions:

General Manager

Food & Beverage Manager (also in contact with the employees)

Banqueting Manager

Financial Controller (with accounting)

Director of Sales & Marketing and team (if on site)

Director of Events and team

Others accessible to guests

Accounting

There will be, for example, in a 100-room hotel about 6 posts. The exact number is defined in the Hotel Brief.

2 separate offices at least should be provided:

1 for the Financial Controller

1 for the General Cashier (with the service safes and a counter opening on a service corridor).

U Hotels & Resorts EU Technical Standards Manual

Page 171 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

OTHER OFFICES

Photocopying and Telecommunications

It includes a photocopy machine, fax machine, computer with internet access, reservations terminal and cupboard.

Computer Room

A specialised room which is explained under T-13 IT & Low Voltage.

Storage and Coffee Room

It includes key-locked cupboards for supplies and all necessary mechanical and electrical connections (electrical, cold and hot water, sink

drainage).

Archives and Files

It is a key-locked small room for administrative archives.

Sales Supplies Room

It stores folders, brochures, leaflets etc. next to or in the sales office.

Toilets

Unisex toilets.

U Hotels & Resorts EU Technical Standards Manual

Page 172 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LAUNDRY

Linen Circuit

Type and Quantity of Linen

General Concept

Technical Notes

Typical Layout

Protection of the Environment

U Hotels & Resorts EU Technical Standards Manual

Page 173 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LINEN CIRCUIT

Optional

The laundry is either handled by the hotel or subcontracted to an outside firm as per the Hotel Brief. If the work is subcontracted the hotel laundry shall

simply include a small client laundry and dry cleaning facilities, as well as dirty linen storage, clean linen storage, uniform storage, the housekeepers’

office, and the Executive Housekeeper’s office. Direct access is then required between the loading dock and the clean and dirty linen stores. Conversely,

when the hotel provides outside laundry services a special counter or shop accessible from the outside must be planned.

The following chapter deals with laundry facilities integrated in the hotel.

U Hotels & Resorts EU Technical Standards Manual

Page 174 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

TYPE AND QUANTITY OF LINEN

The laundry’s capacity depends on the weight of the linen to be handled, hence the Hotel’s maximum capacity, the number of weekly changes and the

number of hours the equipment is in service.

Type of linen weight (kg)

Flat linen

King-size bed linen

o 2 cotton sheets (130 g/m²) 2.26

o 2 cotton pillowcases (+2 pillow covers) (130 g/m²) 0.21

o 1 cotton draw-sheet (420 g/m²) 1.68

o Total 4.15

Twin bed linen (2 beds)

o 4 cotton sheets (130g/m²) 2.9

o 4 cotton pillowcases (+ 4 pillow covers) (130 g/m²) 0.42

o 2 cotton draw-sheets (420 g/m²) 1.68

o Total 5

Bathrooms

o 2 bath sheets (460 g/m²) 1.13

o 2 bath towels (460 g/m²) 0.35

o 2 washcloths (380 g/m²) 0.07

o 1 bath mat (690 g/m²) 0.30

o Total 1.85

Note, in case of bathrobes, add 0.8 kg/room

U Hotels & Resorts EU Technical Standards Manual

Page 175 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Restaurant

o Cotton table linen per place setting 0.250 kg

Kitchen

o Towels (per kitchen employee) 0.500 kg

Form linen

o Chef:

o jackets

o trousers

o caps 1.230 kg

o aprons

o Women’s overalls 0.350 kg

o Steward‘s outfit 0.900 kg

o Waitress uniform 1.000 kg

o Waiter uniform 0.900 kg

o Working overalls 1.000 kg

Miscellaneous items per room

(Cotton bedspread, curtains, sheer curtains, suites bathrobes etc.) 0.250 kg (per day)

Beach – swimming pool linen 0.850 kg (per day and per room)

Number of changes:

Bathroom: 14 times a week

Room: 7 times a week (except pillow covers twice a week)

Restaurant: 3 times a day

Personnel and kitchen: 7 times a week

Various (in rotation): 0.250 kg per day

U Hotels & Resorts EU Technical Standards Manual

Page 176 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Laundering Capacity

This capacity is defined using the following general formula for a theoretical 70% city-hotel occupancy rate:

(H × K1×S1) + (R ×K2× S3) + (C ×K3× S3) + (D× K4 ×S4) = kg of linen per hour,

8 – Hour daily operation of installations’, 5 days a week- 5 × 8/70%

H = Number of hotel rooms

K1 = Kg of linen per room (average) = 6.5 kg

S1 = Number of changes per week = 7

R = Number place settings in the restaurants

K2 = Kg of linen per place setting, per meal = 0.25 kg

S2 = Number of changes per week = 3 × 7 = 21

C = Number of personnel

K3 = Kg of linen per person, per day = 0.5 kg

S3 = Number of changes per week = 7

D = Number of hotel rooms

K4 = Kg of misc. and guest linen to be washed per room per day = 0.25 kg

S4 = Number of changes per week = 7

The capacity of the machines must incorporate the duration of the cycles (45 min for washing and the unloading time (15 min).

U Hotels & Resorts EU Technical Standards Manual

Page 177 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Breakdown of Activities

Large-size flat work 45-50%

o bed sheets

o table linen

o curtains

o covers

o draw-sheets

Small-size work 10-15%

o pillowcases

o place mats

o napkins (restaurant)

o kitchen and workshop cloths

o kitchen rags

o aprons (kitchen personnel)

Form work 10%

o personnel clothing

o guest clothing

o covers

Drying work 25-30%

o bath mats and towels

o bath towels

o wash cloths

o swimming pool towels

o mats, curtains

Steam finish 5%

o personnel clothing (uniforms)

o guest clothing

o covers

The figures shown for drying and steam finishing work tend to increase in view of the growing use of poly cotton in clothing.

U Hotels & Resorts EU Technical Standards Manual

Page 178 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GENERAL CONCEPT

The laundry should include the following areas:

Dirty Linen Area

This room is used to sort, weigh and store dirty linen. It should be located close to the service elevators so as to communicate with the floor

pantries. This room should always be directly connected to the laundry washing area.

Provide sufficient ceiling height in the receiving room (see drawing).

Between this room and the washing areas, the dirty laundry is stored and stored in fixed, open bins. At least 4 of these bins are necessary to separate

the types of handling required.

The linen is transported in push carts and these must be storable in this room (4 cart per 100 rooms).

This room’s equipment should include a built-in weighing scale, a floor drain and a cart-disinfecting station.

Laundry Area

The operation’s central point; this is where the dirty linen arrives and the clean linen is taken to the storage and use areas.

Depending on the hotel’s capacity, the laundry area should contain the following equipment:

o Washing

At least 2 powerful washer-extractor machines, programmable and well-balanced to prevent vibrations, with steam water heating,

and another, small-capacity, electrical machine to wash the guests’ personal linen

Double sink unit for soaking/hand washing

o Drying and ironing of flat-linen/towels

1 small rotary dryer for the guest’s personal linen

1 or 2 rotary dryers (towels)

1 ironing line including (depending on capacity to be handled):

one 3-station feeder or 1 cart to feed in the sheets,

1 ironing dryer with at least 2 rollers- service width: 3.40 m with folder attached.

U Hotels & Resorts EU Technical Standards Manual

Page 179 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

o Drying and ironing of various linen and form linen

1 group of shirt and cotton work clothing presses, or 1 mixed group, presses and shirt mannequin

1 general purpose press

1 or several professional ironing tables

o Miscellaneous

1 sewing machine

1 marking machine

o Handing/folding

Dirty laundry carts

storage bins or wheels (sorted linen)

clean wet laundry carts

rack carts to carry sorted flat linen and towels

mobile wardrobes form linen on hangers

folding tables for :

All small items

Towels

o Linen storage

Shelves, about 2.20 m high, 0.50 m wide, oven-baked finish or stainless-steel. See FFE list.

Laundry Manager’s office

o The Laundry Manager’s office must be located in this area. It should include a display phone and a computer terminal linked to the hotel’s

property management system (PMS).

Detergent storage room

o Used to store detergents and dry cleaning products with floor drain and appropriate ventilation.

Note = dangerous chemicals in significant quantities must be stored outside in a specific, protected area.

U Hotels & Resorts EU Technical Standards Manual

Page 180 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Plant Room

It must be soundproof and include:

1 vacuum pump

1 air compressor with reserve with mono-block air dryer, integral cooler and inlet and outlet filters

1 extraction lint collector

1 water softener if the TH (hardness) of the water is over 20˚F (use softened water at 7 TH) (Refer to chapter T8, section 8, for definitions)

high pressure vapour production unit with smoke tube, horizontal model with: water softener, dosing pump and water feed tank

steam supply through 2 or 3 separate circuits:

o one direct, 12 bar¹ circuit for the ironing dryer

o one 9 bar circuit for the rotary dryers

o one 6 bar circuit for the other equipment, including dry cleaning

Housekeeper’s Laundry Area

When the linen is clean, it should be transferred to the new or clean linen storage located in this area and close to the laundry area and service

corridors or elevators.

This area should include a Laundry Manager’s office, a space for housekeepers, a new linen reserve room, clean linen storage space for linen in

need of repairs, a work area, a distribution counter for chamber maids, a uniform storage area with a service counter on the service corridor, a

sewing machine and table.

The ceiling height in these clean rooms should be at least 2.40 m, with a floor covering of tiles or vinyl slabs and walls either painted or rough

coated.

This area should also include:

o A room to store guest supplies

o A cleaning products storage room

¹1 bar = 10Pa

U Hotels & Resorts EU Technical Standards Manual

Page 181 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

The Executive Housekeeper’s office should open on the service corridor close to the linen distribution counter and if possible be located in a key part of the

laundry for effective supervision. It shall be glassed-in as much as possible for proper viewing of the surroundings. This office, as well as the

housekeeper’s space, shall be equipped with 2 display phones and a computer terminal linked to the hotel’s property management system (PMS).

Annexes

These rooms are also managed by the Executive Housekeeper:

o Floral preparation room

It should include a work bench, double sink and cold store/refrigerator.

o Mini-bar service room

It should include lockable cupboards with shelves.

U Hotels & Resorts EU Technical Standards Manual

Page 182 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

TECHNICAL NOTES

The calculated live load on the floor must be at least 500 kg/m² with additional stresses due to the heavy equipment and vibrations.

Gutters with large grates, drains and filters must be provided for drainage of the washing machines.

All rooms must be equipped with smoke detectors (insurance classification: very dangerous).

Wall and floor coverings must be made of hard and washable materials with non-skid for the floors. It is preferable to tile the walls up to 2.10 m,

with protection angles on projection corners.

Avoid the use of drop ceilings.

The clearance height should incorporate the size of the machines and their eventual replacement (suggested minimum height: 4 m).

Provide waterproofing for the floors, floor drains, slope forms and gutter protection angle bars, particularly in front of the washing machines.

Provide sufficient space around the machines for maintenance access.

Storage areas must be at least 2.40 m high with fluorescent lighting and good air circulation.

The shelving units consist of 100 cm ling and 50 cm deep metal elements with rounded corners and no perforations, 5 shelves per unit.

The electrical installation must include an emergency stop button that stops all the rotating machines.

Each machine must be equipped with a visible shut-off selector switch.

The equipment must be of superior quality, officially approved by U Hotels & Resorts, and meet the following criteria:

­ 304 L stainless steel

­ with adjustable base, mounted on anti-vibration stands of resilient material

­ with individual stopcocks

Heating-ventilation-air conditioning. See chapter T-11 Ventilation – Air conditioning

Particular attention must be given to the design of air supply and exhaust circuits to ensure the best possible working conditions and safety of dry

cleaning operations.

Notes:

Because of the forced extraction of the roll-ironer (hoods), rotary dryers and vacuum pump, it is imperative that their networks be separate from the

start, and then regrouped if necessary at the end of the line in a common duct under low pressure.

The presses, finishing tables and washing machine vents are under atmospheric pressure. A separate air extraction system must be installed next to

these machines.

The equipment size and type imply that the installation be as far away as possible from any public area. Especially avoid any installation of equipment

above public areas (see chapter C-21 Sound Control & Insulation).

U Hotels & Resorts EU Technical Standards Manual

Page 183 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

TYPICAL LAYOUT

1 Washer-Extractor 60 kg. 2 Washer-Extractor 40 kg.

3 Washer-Extractor 25 kg.

4 Dryer 77 kg.

5 Dryer 55 kg.

6 Dryer 34 kg.

7 Flatwork Ironer 1 roll/

⌀ 500x3,200 mm

8 Form Finisher

9 Electric Steam Boiler with

Two Steam Irons

10 Vacuum Ironing Table

11 Single Bowl Sink

12 Working Table ( for Flatwork

linen)

U Hotels & Resorts EU Technical Standards Manual

Page 184 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

PROTECTION OF THE ENVIRONMENT

In order to satisfy environmental protection requirements, the equipment must be selected according to the following criteria:

Minimum energy consumption (electricity, water and vapour)

Automatic programmable dosing of detergent products

Control of effluents and air pollution

Recuperation of toxic vapours (dry cleaning products in particular)

Limited noise pollution and vibrations

Whenever possible:

Re-utilisation of the last rinse water as first soaking water

Pre-treatment or treatment of wastewater

U Hotels & Resorts EU Technical Standards Manual

Page 185 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

KITCHENS

General

Flow of Work

Design

Joinery – Glazing – Locksmithing

Waterproofing

Coverings

Plumbing Sanitation

Fire Protection

H V A C

Electricity

Low Voltage

Equipment

Main Kitchen

Display Kitchen

Employees Cafeteria

Bar Pantry

Pool Snack Bar Pantry

Satellite Kitchens

U Hotels & Resorts EU Technical Standards Manual

Page 186 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GENERAL

This concerns the preparation of dishes and the supply of drinks to all the distribution points in the hotel. This section includes the main kitchen as well as

the satellite kitchens and pantries described further on and communications with the sources of supply together with the service liaisons with the consumer

points.

The principle of forward movement shall be used in the organization of all food-service flows, in order to avoid any cross-contamination of foods with

different levels of hygiene.

Supplies

The goods arrive at the hotel at the receiving dock under the direction of the receiving office and are stored under the control of the storekeeper in the

following corresponding areas:

food supplies : food stores and cold storage rooms

beverages : beverage store and refrigerated beverage store

cleaning and other products : food stores + chemical products storage (bulk storage)

glass, porcelain, silverware : bulk storage and FFE store

The main kitchen receives all the goods according to the chef’s requirements from the storage area.

Transformation – Fabrication

As much as possible, most functions will be gathered in the main kitchen, in particular: main restaurant kitchen, room service and service bar.

All kitchen areas must be key-locked (in case all rooms are not on the same level, vertical means of circulation will be provided: goods elevators and

stairs).

Distribution

This is done directly from the main kitchen (s) or from satellite kitchens (functions, specialties).

The kitchen must be totally separable (doors with locks) from adjacent non-kitchen areas.

U Hotels & Resorts EU Technical Standards Manual

Page 187 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FLOW OF WORK

U Hotels & Resorts EU Technical Standards Manual

Page 188 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 189 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

DESIGN

Module

Floors must be designed in consideration of the large number of holes needed for gutters, traps and piping and cold room recesses.

Dropped girders for the above and below floors should be avoided to facilitate the passage of ducts and piping (liquid waste, in particular).

Ducts and Pipes

In order to avoid maintenance problems, electrical boxes and piping and cables will not be left exposed but be integrated in technical shafts.

Recommended Ceiling Heights

Headroom between finished floor and ceilings (under beams, if applicable) should be a minimum of:

o Store room : 2800 mm minimum

o Kitchen : 3300 mm minimum

o Banquet satellite kitchen : 2800 mm minimum

Load Tolerance

At least the following floor loads should be taken into account in calculations for the concrete structure:

o Storeroom level : 600 kg/m²

o Kitchen level : 500 kg/m²

o Function satellite kitchen : 500 kg/m²

U Hotels & Resorts EU Technical Standards Manual

Page 190 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Circulations

Carts and trolleys shall be a maximum of 150 cm long × 90 cm wide.

All corridors, doors, service and freight elevators should be sized in accordance with these dimensions.

The minimum width of service corridors should be 1.60 m to 1.80 m.

Floors

There must be no steps between kitchens or in kitchens, including access to cold storage rooms (walk-in refrigerators and freezers), in order to

allow free circulation of trolleys.

Any differences in floor height can be compensated by ramps with a slope (not to exceed 4%).

Provisions for depressed slabs under cold rooms should be made from the beginning of the construction.

Partitions

Wall surfaces must be smooth, rot-proof, shock-resistant, watertight and easy to clean and disinfect. (See Section 6- coverings – below, and chapter

T7).

Partitions, doors, windows and ceilings must be resistant to humidity and high temperatures and allow easy cleaning.

Outside of air-conditioned areas, the partitions within the kitchen areas are generally 1.80m high at a minimum. They should be tiled to their full

height.

On a functional level, separate entrances must be provided for personnel, merchandise and trash, in compliance with the principle of separating

clean/soiled-handling areas as requested by food and beverage health regulations.

On the loading dock, goods receiving should be separate from the garbage area.

U Hotels & Resorts EU Technical Standards Manual

Page 191 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

JOINERY – GLAZING – LOCKSMITHING

Large Windows

The following areas should be equipped with half- height glazed partitions:

Receiving office

Purchasing office

Storekeeper office

Executive Chef’s office

Between preparation areas

Between hot pastry and cold pastry (where applicable)

Service Hatches, Roller Blinds

To be provided:

Goods receiving: roller blinds

Main service bar : roller blind

Storekeeper : service hatch

Bar : roller blind

Doors

All service doors leading to kitchens and ancillary areas will be swinging doors (double doors where possible), with a passage width of 90 cm.

These doors will be fitted with a stainless steel plate 110 cm high with protection of stainless steel edge angles.

Doors leading to public areas must be metallic, or laminate-coated on both sides and fitted with kick plates. They should also have locks to control

area access when needed.

All doors will be equipped with automatic door closers.

Other doors will be finished with washable materials.

All doors in the vicinity of the kitchen, particularly those in communication with public areas, will be equipped with locks and bolts according to

the hotel-keying schedule.

All doors, (except those leading to public areas), will be outfitted with a square 30 × 30 cm oculus, and centred at 160 cm from the floor.

U Hotels & Resorts EU Technical Standards Manual

Page 192 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Air-lock

Two-way service vestibules will be installed between kitchens and public areas with a minimum width of 1.50 m.

These vestibules will be large enough to install the switchboxes for the electricity and sound system for the public areas.

Windows

Where possible natural light is needed.

All windows shall be fitted with washable insect screens

Anti-Trolley Wall Protection

All posts and protruding angles of kitchen partitions and service corridors should be equipped with stainless steel protection or rubber castors about

2 meters high.

For all kitchens aisles and freestanding walls, metallic channels measuring 15 cm high and 4 cm thick will be installed along the walls, 70 cm above

the finished floors.

U Hotels & Resorts EU Technical Standards Manual

Page 193 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

WATERPROOFING

All floors in kitchens, pantries, storerooms, cellars and cold rooms should be sufficiently watertight to permit hosing down of the floor. A slope will

be included in the design for water evacuation. Expansion joints will be avoided in these zones, as well as close proximity with dangerous rooms

(transformer stations etc.).

The waterproofing and flashing shall be recessed into the wall (allowing kitchen equipment to be placed flush against wall).

Rounded-groove type baseboards are used to meet regulatory requirements.

Areas around the traps, gutters and sleeves should be perfectly watertight for the installation of water and electricity ducts.

These sleeves should be 5 cm above the finished floor and be filled with a watertight, resilient material.

Plan to install traps allowing evacuation of liquid waste around the watertight areas. Square and screwed special kitchen traps will be used.

U Hotels & Resorts EU Technical Standards Manual

Page 194 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

COVERINGS

Floor Coverings

Floor level:

All floors will be flat, except for a very slight slope around the floor gutters and traps.

Stands:

Avoid heavy masonry pedestals for mounting kitchen equipment; instead use equipment (either free-standing on stainless-steel legs) against the

wall on a central beam or attached to the wall.

Materials:

The floors of kitchens and ancillary areas will be covered in 20 x 20 cm square-edge, 12 mm thick minimum non-slip stoneware tiles with rounded-

channel baseboards.

Foot Mats:

Large walk off mats (12 mm thick) will be recessed in the floor space of the service vestibules leading towards the public areas (from the kitchens).

Wall Coverings

All walls in kitchens and ancillary areas will be covered in top quality clay tiles in minimum size as of the floor tile, to the ceiling.

Use stainless steel plates on top of ceramic tiles behind heat sources.

Ceilings

If there are no suspended ceilings, ceilings will be painted with an easily-washable vinyl lacquer conforming to health standards.

In general, try to avoid passing ducts and pipes along kitchen ceilings to facilitate the cleaning process.

If ducts and pipes must be installed in this way they should be insulated or lagged and painted in the same manner as ceilings.

U Hotels & Resorts EU Technical Standards Manual

Page 195 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

PLUMBING SANITATION

Energy Sources

Use gas for all cooking appliances, except for deep fat fryers, salamanders, steam ovens and cookers (with local steam production only). If tanks of

gas are used, plan to install tanks providing a minimum supply of 10 days.

Distribution

Water will be distributed at a pressure of 3 bar. Hot and cold water must be softened to a maximum ph of 7. Hot water will be distributed at a

minimum temperature of 50˚C using a circuit independent from that used for rooms and bathrooms.

Hot and cold water pipes: Minimum diameter is 15 mm, or 26 mm for large apparatus, with attachment by cylindrical brackets.

The whole distribution system should be concealed. Each supply line will end with an easily accessible stop valve (independent of the valve which

may already exist on the apparatus).

Drainage

They will be equipped with T-shaped clearing holes at each change in direction and along long straights.

Traps of gutters should be provided on major equipment and in each room, including beverages store, food store, cold rooms, garbage areas, etc.

The ground traps and gutters must be provided with removable dirt pans.

All gutters should have rounded corners to avoid deposits.

Drains will feed into a system comprising a mud collector, a grease trap and a starch decanting unit.

These fixtures will be located relatively far from the kitchens (to enable cooling down of grease), and will be easily accessible for cleaning. They

will be located outside the building or even in the parking areas.

A cold water spray with control system will be required to cool liquid wastes from the kitchen upstream of the grease traps.

U Hotels & Resorts EU Technical Standards Manual

Page 196 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Drainage Drawing

U Hotels & Resorts EU Technical Standards Manual

Page 197 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 198 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 199 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Gas

The gas installation must be in compliance with international standards or with local regulations if these are more restrictive.

A gas meter will be provided for each kitchen.

An easily-accessible gas pressure reducing and stop valve must be placed on the right-hand side of every gas appliance.

A master solenoid valve providing automatic cut-off as soon as excessive flow rate occurs. (i.e. a break in the pipe) will be placed at the entrance to

each kitchen and will allow cut-off of the main gas supply (punch stop).

At crucial areas like the gas plant and the hot kitchen gas detectors will need to be installed.

Hygiene

All kitchen areas shall be equipped with micro-spray units for cleaning and disinfection.

In the different kitchen zones hand wash washbasins shall be provided, along with soap and single-use towels dispensers.

Insect killers will be installed where appropriate.

U Hotels & Resorts EU Technical Standards Manual

Page 200 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FIRE PROTECTION

Fire protection comprises of two traditional systems:

o Portable fire extinguishers containing 9 kg of CO2

o Automatic CO2 or Inergen extinguishers installed in each exhaust hood are required.

Chapter T 9 Fire Protection and T 10 Fire Detection must be strictly followed. Provide an automatic gas cut-off solenoid valve activated with the hood

exhaust and with manual reset.

U Hotels & Resorts EU Technical Standards Manual

Page 201 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

H V A C

General Conditions

All kitchens and ancillary areas should be ventilated and air-conditioned if necessary to maintain an indoor temperature of 26 ˚C, independent of

outdoor climatic conditions.

Relative humidity of these areas should be under 50%.

Furthermore, the following areas must be air-conditioned to make sure the inside temperature does not exceed 22˚ C: cold preparation-storage,

pastry-bakery (ovens in operation).

Double-flow hoods will be used.

The wine cellar should be kept at a maximum temperature of 18 ˚C (except for the refrigerated wine storeroom).

Ventilation

Minimum air renewal rate should be 25 volumes/hour for large kitchens and 30 volumes/hour for small kitchens unless calculations show that a

lower value will suffice.

Location of air diffusers should allow coverage of the whole area without creating “dead spots” where greasy vapour can build up.

Plan to blow fresh air through the exhaust hoods to create an air curtain around the hood.

The washing and work stations should be provided with enhanced ventilation.

Kitchens are kept at a lower pressure than the surrounding environment, in order to avoid odour propagation (air intake 90% of exhaust).

When new air comes partially from adjoining public areas, sound-insulation screens should be installed to avoid transmitting kitchen noises.

Two-speed exhaust systems should be installed to limit operating costs; controls will be kept near the Executive Chef’s office.

Care must be taken to ensure that the kitchen remains at a lower pressure than adjoining public areas when low exhaust speed is used.

Hoods

Hoods will be installed over all appliances releasing large quantities of heat, smoke and steam, i.e. range, kettles, dishwashing machines, pastry

ovens.

Hoods will be constructed of stainless steel (possibly other materials for “open display kitchens” e.g. glass or copper), and will be equipped with

vertical walls reaching to the ceiling to contain sudden releases of steam.

The lower edge will be 205 cm from the finished floor and this edge will be larger than appliance surfaces by 30 cm all the way around.

Watertight channels around the interior of the hoods will enable condensation recovery.

U Hotels & Resorts EU Technical Standards Manual

Page 202 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Air speed between stove and hood should be at least 0.15 m/sec.

Washable, easily removable grease filters should be installed above fryers, grills and broilers. Gutters should be installed under the grease filters.

At least two sets of filters will be provided.

Watertight, heat-resistant lights should be installed inside the hoods.

A pressure compensation system should be installed on exhaust systems fitted with grease filters to offset load losses due to the filters.

Ducts

Kitchen exhaust ducts should be made of galvanized steel (fire-resistant for at least 15 minutes), and watertight for cleaning (stapled ducts are

absolutely forbidden, use welded joints), sloped in the direction of air circulation and with a drain trap at the lowest point.

Monthly duct cleaning means that cleaning hatches measuring about 40 x 30 cm must be installed at all angles, every five meters on long straight

sections and at the base of every vertical section (with drain trap). Hatches should be fastened with stainless winged-nuts and casketed.

The bottom part of the horizontal ducts should have openings with internal flanges to avoid condensation drip.

Hood exhaust ducts should be insulated with high temperature insulation.

Avoid using pressure dampers which are difficult to clean.

Seek a natural balance in terms of calculation duct cross-sections.

Exhaust Fans

Exhaust fans must not be shared with other areas except for kitchens and pantries. They must have a two-speed motor located outside the air flow.

The exhaust registers must be far from windows and fresh air inlets and within a non-enclosed part of the building where it is protected from strong

winds.

Exhaust registers should be studied in order to avoid dirtying the façade

Exhaust motors create a lot of noise; due to this the location should be as far as possible from guest circulation areas.

U Hotels & Resorts EU Technical Standards Manual

Page 203 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ELECTRICITY

Lighting

Lighting for kitchen and ancillary areas will be controlled on a room-by-room basis, and will have 40% backup in all zones, including storage areas.

Kitchen lighting will be at 500 lux, storage zones at 100 lux and distribution and cashier areas at 750 lux.

Lighting will be provided by fluorescent tubes or LED as close as possible to a natural lighting environment.

Lights will be located in watertight fixtures, suspended a maximum of 2.60 meters above the finished floor or recessed into the ceiling.

The general power panel will be separated from the lighting panel.

Electrical Power Supply:

Each kitchen’s electrical power will be provided near the Executive Chef’s office (outside the office), or at a central point with one backed-up line

(grounded, three-phase + neutral) and a non-backed-up line (grounded, three-phase + neutral).

Depending on the climate, all equipment will be adapted accordingly particularly the contactor coils.

Sufficient power capacity (about 30%) will be provided to enable the addition of future complementary equipment. For this purpose, each

switchbox compartment will also be equipped with two contact breakers (4 × 10 A) and two contact breakers (4 × 20 A), with fuse-equipped

disconnectors. The kitchen should be provided with sufficient conductors and counter outlets to allow for an evolution and increase in the number

of equipment and power required.

Distribution:

Electrical distribution is through cable racks, routed under kitchen floors and behind wall tiles to a minimum height of 1.20 meters to the right of

each kitchen appliance.

Avoid placing outlets any lower because of the danger of water splashing.

Electrical distribution points should terminate in watertight circuit breakers placed to the right of each apparatus.

This is independent of the switches or disconnectors integral to the apparatus.

All switchboxes, electrical equipment and kitchen equipment must be grounded.

The circuits and outlets shall be adapted in terms of location, number, power and type to the equipment chosen for the kitchen layouts and studies.

U Hotels & Resorts EU Technical Standards Manual

Page 204 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Emergency Supply Circuits:

The following equipment must have backup supply:

Cold storage rooms

Refrigerators

Refrigerated cabinets and counters

Freezers

Ice machines

Kitchen exhaust fans

At least one stove, to enable basic cooking

For all-electric kitchens, the following equipment should also be backed up to allow minimum food and beverage service:

1 oven

1 broiler

1 bain-marie

1 fryer

1 overhead grill (salamander)

Outlets:

Besides the specific outlets for kitchen equipment, all electrical outlets will be watertight units 1.20 meters above the finished floor in the various

kitchens, pantries and storage rooms. These outlets must be grounded.

Catering satellite kitchens should be equipped with at least six outlets, each rated at 3 000 W, taking special plugs.

These outlets should be recessed in the wall to allow connection of cold n hot and hold ‘n serve banquet trolleys.

Special outlets connected to emergency power supplies should be installed for the POS (restaurants, bar and room-service).

These outlets will be connected directly to the switchboxes on each floor (to avoid voltage drops), and should correspond to the specific needs of

selected equipment (special case: data processing equipment requiring an inverter).

U Hotels & Resorts EU Technical Standards Manual

Page 205 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LOW VOLTAGE

Property Management System

The equipment shall be defined according to the U Hotels & Resorts Hotel Brief.

In the kitchen zones, “order-taker” terminal P.O.S. system printers shall be provided for the service bar, cold prep and central cooking distribution.

In certain areas (room-service, food-store, cashiers chef’s office) emergency-supplied double power outlets shall be provided as well as RJ 45

outlets with CAT 6 cables to connect to the PMS and POS.

Telephones

The following telephone sets should be installed:

One wall-mounted set in each kitchen section and in the pastry-bakery.

One desktop set plus separate RJ 45 (CAT 6) outlet in:

o Executive Chef’s office

o Receiving office

o Purchasing office

Two or three sets in an extension hunting group, answering one-digit calls for the Room Service (Your Dining) office if applicable.

These sets will be equipped with headsets and can be forwarded to another set for night service.

Each set will have a screen for display of the internal calling unit and display of calling party data.

U Hotels & Resorts EU Technical Standards Manual

Page 206 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

EQUIPMENT

This will consist of:

o 314 L stainless steel or 316 L in open-air sea-side areas

o with adjustable sanitary feet

o of very high quality, designed for intensive use

o approved by U Hotels & Resorts

o with key-locking drawers

o equipped with back and /or side splashes appropriate for use

The mobile carts will have maximum dimensions of 1.50 × 0.90 m.

The grease and starch traps will be cleanable and accessible from an outside room.

Standard Thickness for Kitchen Equipment

General standard 'custom made' stainless steel equipment shall be made of stainless steel type AISI 304 for all exposed surfaces. Different thickness of each

piece of equipment shall depend on the purpose of use and individual specification attached for each project submission.

General standard of thickness used in production:

Components Material Used

Sink drain boards No. 16 gauge. Stainless steel

Sink bowls No. 16 gauge. Stainless steel

Sink waste 50mm. brass housing with twist handle complete with overflow

Bain-Marie tank No. 16 gauge. Stainless steel

Table top No. 16 gauge. Stainless steel

Cabinet body back & sides No. 20 gauge. Stainless steel. Fronts 18 SWG

Under shelf & Intermediate shelf No. 16 gauge. Stainless steel

Over shelf & Wall shelf No. 18 gauge. Stainless steel. Wall Bracket 16 SWG

U Hotels & Resorts EU Technical Standards Manual

Page 207 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Drawers No. 18 gauge. Stainless steel.

Drawer face No. 18 gauge. Stainless steel.

Drawer housing / Frame No. 16 gauge. Stainless steel.

Drawer slide Heavy duty rust proof steel ball bearing wheels with

cold rolled steel and zinc plate

Hinged door No. 18 gauge. Stainless steel.

Sliding door No. 18 gauge. Stainless steel.

Sliding door hanger and guide Stainless steel over mounted door hanger with

stainless steel tread and ball bearing

Exhaust hood No. 18 gauge. Stainless steel.

Grease filter for exhaust hood Baffle type stainless steel

Legs 38 mm. O.D. stainless steel

Feet Stainless steel clad adjustable bullet feet

Cross rail 25 mm. O.D. stainless steel

Caster Heavy-duty caster 4" or 5" wheel diameter. Either specified

swivel tread or swivel plate, to be hardened steel ball bearing.

Stainless Steel finished.

Heating element Stainless steel type for immersion

Incoloy-type for dry heat

Switch, breaker & Magnetic Mitsubishi/ Telemecanique

Thermostat Dixell / Carre l/ Danfoss / Every Control

U Hotels & Resorts EU Technical Standards Manual

Page 208 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

MAIN KITCHEN

General Criteria

This is located in direct contact with all the food-distribution outlets and, if possible, all the beverage distribution points.

It should be linked with the storages, cold rooms and stores via means providing for easy circulation (whether corridors or goods elevators).

The number of ancillary kitchens will be limited as far as possible.

The different parts of the main kitchen are:

Daily stores (cold rooms) see section C 16

Fruit and vegetable preparation

Fish preparation

Meat preparation

Central cooking zone

Cold preparation

Buffets preparation

Bakery-pastry

Room-service

Dish washing

Utensils pot washing

Service bar

Banquet kitchen

Chef’s office

Note: the main service bar may, in some instances, be coupled with the room service.

Cold room

Food store

Order taker

Cafeteria kitchen

U Hotels & Resorts EU Technical Standards Manual

Page 209 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Areas

As indicated in the hotel brief, they are a first approach which must be adapted to each building’s constraints and each project in particular.

Schematic drawings are attached for each zone, as a checklist and guideline. However, for each project, the layouts and equipment lists can only be the

result of a specific study by a specialized kitchen consultant.

Description of Zones:

Note = In some cases, a pre-treatment area (before storage) will be provided at the same level as the loading dock.

Fruit and Vegetable Preparation:

This receives the raw products from the storage area. Here all the fruit and vegetables are cleaned and prepared.

Once prepared, the products are stored in the cold room reserved for fruit and vegetables ready for use.

Meat and Fish Preparation:

The meat and fish are cleaned and cut up, after which they are stored in the cold room and fish drawers until they are used by the chef.

This zone is air-conditioned and kept at 22 ˚C.

Central Cooking Zone:

This is the most important zone in the main kitchen and contains all the equipment necessary to cook food. It prepares and finishes the hot dishes. It

receives the pieces ready to cook from the cold rooms and preparation zone. It receives the clean kitchen utensils from the utensils washing.

It receives clean plates from the dish washing area.

It distributes the cooked dishes via the distribution counter, which has a plate heater counter.

The Chef’s office should be located alongside and in visual contact with this zone.

A hood with ventilation covers the whole cooking zone.

Heated shelves for plates.

Infrared lamps for the hot dishes on the counter pass shelves.

U Hotels & Resorts EU Technical Standards Manual

Page 210 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Cold Preparation:

Receives the food prepared in the preparation zones and products such as dairy items directly from the cold storage rooms. These products are then

stored in refrigerators.

The chinaware arrives in this zone from the dishwashing area.

Prepares the cold dishes such as salads, sandwiches and seafood.

Distributes these cold dishes across a counter.

Bakery-Pastry:

Receives the products directly from the general store and stores them in its own cold rooms. Also receives the pots, dishes and moulds from the

utensils washing area.

It produces bread, pastry, croissants, etc. and stores them in carts, portable baskets and in its own cold rooms.

Hot and cold sections shall be kept separate. The cold section is fully air-conditioned at 22C.

Room Service (Your Dining):

In direct contact with the service corridors or elevators servicing the bedroom levels.

Unless impossible, it should be located close to the all-day dining restaurant and be part of the main kitchen. It receives the food from almost all the

kitchen zones.

Prepares the breakfasts.

Lays the dishes on the service tables.

Stores certain products in its own cabinets and refrigerators.

Centralized the orders to be served in the rooms.

Distributes its production via service elevators to the rooms on service tables, carts and trays and stores all of the latter equipment.

Sends all the soiled ware to the dish washing area.

Requires a telephone and a P.O.S. terminal, a cash register station and work posts for taking orders.

A refrigerated food reserve will be provided for night service.

Note that, in a traditional business hotel, more than 15% of guests use this service for breakfast.

U Hotels & Resorts EU Technical Standards Manual

Page 211 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Dishwashing Area:

This zone receives all the dirty ware (chinaware, glass silver) on a special sorting table from all the outlets connected with the kitchen and Room

Service (Your Dining).

Once clean, the ware is stored on shelves and distributed on carts between the different services:

o Room Service (Your Dining)

o Cold preparation service

o Central cooking zone

o Service bar

o Catering pantry (and other pantries, if any)

o Steward store

Utensils Pot Washing

Receives all the pots and all utensils from the central cooking zone, preparation zone, bakery and pastry.

The utensils are washed and repaired there before returning them to the zone where they are used.

One of the sinks shall be equipped with an adjustable heating system.

Service Bar:

Its function is to distribute the wines, liquors and other beverages to the restaurants and reception rooms.

It receives clean glasses from the dishwashing area, distributes the beverages in bottles or glasses over a counter, recovers all the empty bottles for

control and sends them to the empty bottles storage area for recycling.

Banquet Satellite Kitchen

It is always necessary to serve all the reception rooms, whatever their situation in relation to the main kitchen.

All the dishes, prepared in large quantities in the main kitchen, should be served at the same time and kept hot or cold in the banquet satellite

kitchen on portable carts (in special stores, or plug-in).

Sufficient space should be provided in this area to store the service carts and also a coffee preparation zone and service bar. If the reception rooms

are far from the main kitchen or are located on another level, a dish washing zone will be provided.

The banquet kitchen must be linked to the reception rooms by a corridor separate from the public corridors.

U Hotels & Resorts EU Technical Standards Manual

Page 212 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Chef’s Office and Store:

Located in the centre of the main kitchen.

The Chef should be able to see the maximum number of activities from this office, notably the central cooking zone and dish and food circulation in

and outside the kitchen and particularly the distribution counters.

The Chef’s office will contain shelves, a computer terminal, a telephone set centralizing all the kitchen zones and a separate, lockable store.

Steward‘s Office and Store:

These are located close to the main kitchen and reserved for the sole use of the steward, who controls the silver, cutlery and special banqueting

items (the reserve is key-locked).

A separate reserve for cleaning supplies must be provided.

Cashier and Order Terminals:

Provide a cashier terminal (POS) in the restaurant pantries and in the Room Service order taker cabin. Each station requires the following:

o POS terminal (Touch screen with CPU or separate CPU connected to a UPS).

o Cashier printer

o Cash drawer (usually only one per outlet)

o Credit card swipe machine connected with CAT 6 & Phone cable

o Telephone

For each cashier terminal provide an illuminated work station (usually the side station),.

Two double socket pockets and two RJ45 with CAT 6 sockets.

U Hotels & Resorts EU Technical Standards Manual

Page 213 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

DISPLAY KITCHEN

If direct service from the main kitchen is impossible or if the environment of the kitchen zone is a factor which can be attractive to the customers,

the kitchen can be designed as visible to the customers; for example for the local specialty restaurant.

In all cases a pantry will be required for the operations invisible to the customers (storage of carts, dirty ware etc) and a suitable means of

transporting food will be provided from the main kitchen, storages and preparation zones.

The dishes will be served to the dining room via a hot/cold distribution counter.

EMPLOYEE CAFETERIA

This is self-service with hot and cold dishes, drinks, tea and coffee.

It receives the food from the main kitchen and it sends the soiled ware there.

In some cases preparations and dish and pot washing will be done on the spot. Equipment will then be provided to make it autonomous.

BAR PANTRIES

These are distributed according to the hotel brief and are all fully equipped. Apart from the public area which has a counter, stools and the equipment

required to serve all sorts of drinks, this service area has a daily reserve, a glass-washing machine, storage, ice-cube machine and coffee machine.

U Hotels & Resorts EU Technical Standards Manual

Page 214 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

POOL SNACK BAR PANTRY

The swimming pool snack bar is located adjacent or close to the pool. It contains a satellite kitchen capable of preparing and serving a limited

number of simple hot or cold dishes and all drinks.

All the food comes from the main kitchen.

The dishes are served on the counter and at the tables around the pool. A daily food and drinks store is added with a dishwasher, the service section

being concealed from the public.

SATELLITE KITCHENS

These are kitchens designed to receive prepared dishes from the main kitchen and preserve them in ideal conditions as well as prepare their own

specialized dishes, to be served at special consumption points such as meeting rooms, cocktail parties, and specialty restaurants.

Hot and cold trolley storage must therefore be provided and the equipment necessary to serve coffee and drinks, as well as reduced storage,

preparing and cooking equipment.

In certain cases (regional cooking or a considerable distance from the main kitchen for example), it is necessary to provide full storage, preparation,

cooking and dishwashing zones.

U Hotels & Resorts EU Technical Standards Manual

Page 215 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LAYOUTS

SMALL TO MEDIUM HOTEL KITCHEN

U Hotels & Resorts EU Technical Standards Manual

Page 216 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

MEAT AND FISH PREPARATION

K Butcher (Meat & Poultry)

U Hotels & Resorts EU Technical Standards Manual

Page 217 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

MEAT AND FISH PREPARATION

K- BUTCHER (SEAFOOD) BG-MEAT WALK-IN CHILLER

K-01 Single Bowl Sink Unit BG-01 Meat Panel Type Cold Room

K-02 Fish Preparation Table With Double Sink BG-02 Shelving Unit

K-03 Spray Unit BH-POULTRY WALK-IN CHILLER

K-04 Waste Bin BH-01 Poultry Panel Type Cold Room

K-05 Working Bench BH-02 Shelving Unit

K-06 Scale BF-SEAFOOD WALK-IN CHILLER

K-07 Double Wall Shelf BF-01 Seafood Panel Type Cold Room

K-08 Counter Type Refrigerator BF-02 Shelving Unit

K-09 Double Wall Shelf BF-03 Shelving Unit

K-10 Double Bowl Sink Unit BE- WALK-IN FREEZER

K-11 Spare Number BE-01 Panel Type Deep Freezer

K-12 Counter Type Refrigerator BE-02 Shelving Unit

K-13 Bone Saw Machine M-POT-WASH AREA

K-14 Meat Mincing Machine M-01 Shelving Unit

K-15 Universal Machine Um 12 M-02 Working Bench

K-16 Working Bench M-03 Three Bowl Sink Unit

K-17 Wall Shelf M-04 Waste Bin

K-18 Double Bowl Sink Unit M-05 Spray Unit

K-19 Hand Wash Sink Unit M-06 Hand Wash Sink Unit

K-20 Pre-Wash Hose M-07 Pre-Wash Hose 10 Mt

K-21 Double Bowl Sink Unit M-08 Pot Carrying Trolley

K-22 Vacuum Machine Y-FLOOR THROUGH

K-23 Universal Machine Um 44 Y-01 Floor Through

Y-02 Floor Through

Y-03 Floor Through

Y-04 Insect Killer

U Hotels & Resorts EU Technical Standards Manual

Page 218 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

VEGETABLE PREPARATION

U Hotels & Resorts EU Technical Standards Manual

Page 219 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

VEGETABLE PREPARATION

A-RECEIVING + PRE-WASH AREA J-15 Waste Bin

A-01 Scale J-16 Spray Unit

A-02 Double Bowl Sink Unit J-17 Upright Type Refrigerator

A-03 Spray Unit J-18 Hand Wash Sink Unit

A-04 Waste Bin J-19 Pre-Wash Hose

A-05 Meat and Vegetable Trolley J-20 Mobile Working Bench

A-06 Working Bench J-21 Waste Bin

A-07 Shelving Unit J-22 Potato & Onion Storage

A-08 Cargo Carrying Trolley BJ-VEGETABLE WALK-IN CHILLER

A-09 Shelving Unit BJ-01 Vegetable Panel Type Cold Room

A-10 Working Bench BJ-02 Shelving Unit

A-11 Shelving Unit

J- VEGETABLE PREPARATION AREA

J-01 Potato Peeling Machine

J-02 Vegetable Washing Machine

J-03 Bench With Strainer

J-04 Spray Unit

J-05 Double Bowl Sink Unit

J-06 Working Bench

J-07 Vegetable Cutting Machine

J-08 Double Wall Shelf

J-09 Slicer

J-10 Wall Shelf

J-11 Counter Type Refrigerator

J-12 Scale

J-13 Vegetable Cutting Machine

J-14 Double Bowl Sink Unit

U Hotels & Resorts EU Technical Standards Manual

Page 220 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CENTRAL COOKING

U Hotels & Resorts EU Technical Standards Manual

Page 221 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CENTRAL COOKING

L-01 Pre-Wash Hose L-25 Wok Cooker

L-02 Hand Wash Sink Unit L-26 Rice Warmer

L-03 Working Bench L-27 Bain Marie

L-04 Double Wall Shelf L-28 Cooker

L-05 Double Bowl Sink Unit L-29 Working Bench

L-06 Double Wall Shelf L-30 Grill Plate

L-07 Waste Bin L-31 Grill Plate

L-08 Convection Oven L-32 Working Bench

L-09 Wall Type Hood L-33 Fryer

L-10 Blast Chiller L-34 Chip Scuttles

L-11 Tray Trolley L-35 Working Bench

L-12 Mobile Top Bench L-36 Service Shelf

L-13 Counter Type Refrigerator L-37 Counter Type Refrigerator

L-14 Working Bench L-38 Double Wall Shelf

L-15 Single Bowl Sink Unit L-39 Island Type Hood

L-16 Tray Trolley L-40 Shelving Unit

L-17 Tilting Boiling Pan (150lt) L-41 Spare Number

L-17.1 Tilting Boiling Pan (250lt) L-42 Working Bench

L-18 Tilting Bratt Pan L-43 Fryer

L-19 Working Bench L-44 Spare Number

L-20 Double Wall Shelf L-45 Pasta Cooker

L-21 Working Bench L-46 Convection Oven

L-22 Double Wall Shelf L-47 Dim Sum Steamer

L-23 Double Wall Shelf L-48 Salamander

L-24 Duck Roster L-49 Mixer

U Hotels & Resorts EU Technical Standards Manual

Page 222 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

COLD PREPARATION

U Hotels & Resorts EU Technical Standards Manual

Page 223 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

COLD PREPARATION

BC -WALK-IN CHILLER U-09 Vegetable Cutter Machine

BC-01 Panel Type Cold Room U-10 Slicer

BC-02 Shelving Unit U-11 Wall Shelf

BC-03 Tray Trolley U-12 Scale

BD -WALK-IN FREEZER U-13 Working Bench

BD-01 Panel Type Deep Freezer U-14 Citrus Juicer Machine

BD-02 Shelving Unit U-15 Toaster Machine

BD-03 Tray Trolley U-16 Spare Number

U – COLD KITCHEN (BREAKFAST) U-17 Working Bench

U-01 Hand Wash Sink Unit U-18 Double Wall Shelf

U-02 Pre-Wash Hose U-19 Wall Shelf & Prep Unit

U-03 Single Bowl Sink Unit U-20 Counter Type Refrigerator

U-04 Waste Bin U-21 Working Bench

U-05 Working Bench U-22 Service Shelf

U-06 Wall Shelf U-23 Shelving Unit

U-07 Scale U-24 Induction Cooker

U-08 Counter Type Refrigerator

U Hotels & Resorts EU Technical Standards Manual

Page 224 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

BAKERY / PASTRY / ICE CREAM

U Hotels & Resorts EU Technical Standards Manual

Page 225 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

BAKERY / PASTRY / ICE CREAM

D-BAKERY E-08 Working Bench

D-01 Single Bowl Sink Unit E-09 Spray Unit

D-02 Waste Bin E-10 Waste-Bin

D-03 Dough Divider Machine E-11 Three Wall Sink Unit

D-04 Mixer E-12 Mobile Working Bench

D-05 Mixer E-13 Wall Shelf & Hooks

D-06 Working Bench E-14 Wall Shelf & Hooks

D-07 Wall Cupboard E-15 Shelving Unit

D-08 Induction Cooker E-16 Shelving Unit

D-09 Mixer E-17 Mobile Working Bench

D-10 Counter Type Refrigerator F - CHOCOLATE

D-11 Marble Top Machine F-01 Hand Wash Sink Unit

D-12 Hand Wash Sink Unit F-02 Pre-Wash Hose

D-13 Pre-Wash Hose F-03 Upright Type Refrigerator

D-14 Tray Trolley F-04 Single Bowl Sink Unit

D-15 Service Shelf F-05 Waste Bin

D-16 Ingredient Bin F-06 Counter Type Refrigerator

D-17 Dough Roll Out Machine F-07 Double Wall Shelf

D-18 Shelving Unit F-08 Scale

D-19 Mobile Working Bench F-09 Chocolate Warmer

D-20 Bread Slicing Machine F-10 Double Wall Shelf

D-21 Doughnut Machine F-11 Working Bench W/Drawers

E - PASTRY G - ICE CREAM PREPARATION

E-01 Wall Type Hood G-01 Single Bowl Sink Unit

E-02 Deck Oven G-02 Waste Bin

E-03 Prover Cabinet G-03 Working Bench

E-04 Convection Oven G-04 Freezer + Ice Cream Unit

E-05 Tray Trolley G-05 Double Wall Shelf

E-06 Shelving Unit G-06 Upright Type Deep Freezer

U Hotels & Resorts EU Technical Standards Manual

Page 226 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

MAIN KITCHEN

H – DOUGH AREA BM – WALK-IN CHILLER

H-01 Single Bowl Sink Unit BM-01 Panel Type Cold Room

H-02 Waste Bin BM-02 Shelving Unit

H-03 Mixer BM-03 Mobile Working Bench

H-04 Mixer BN – WALK –IN CHILLER

H-05 Working Bench BN-01 Panel Type Cold Room

H-06 Double Wall Shelf BN-02 Shelving Unit

H-07 Double Wall Shelf BN-03 Mobile Working Bench

H-08 Counter Type Refrigerator BO – WALK-IN FREEZER PASTRY

H-09 Scale BO-01 Pastry Panel Type Deep Freezer

H-10 Working Bench BO-02 Shelving Unit

H-11 Mixer BO-03 GN 2/1 Tray Trolley

H-12 Double Wall Shelf

H-13 Marble Top Bench

H-14 Service Shelf

H-15 Ingredient Bin

H-16 Hand Wash Sink Unit

H-17 Pre-Wash Hose

H-18 Double Wall Shelf

U Hotels & Resorts EU Technical Standards Manual

Page 227 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 228 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 229 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

POTS AND PANS

M-01 Shelving Unit

M-02 Working Bench

M-03 Three Bowl Sink Unit

M-04 Waste Bin

M-05 Spray Unit

M-06 Hand Wash Sink Unit

M-07 Pre-Wash Hose 10 Mt.

M-08 Pot Carry

U Hotels & Resorts EU Technical Standards Manual

Page 230 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

DISHWASHING AREA

DW-01 L-Shape Dirty Dish Table w/ Drop off Station

DW-02 Mobile Plastic Garbage Bin

DW-03 Over Rack Shelf

DW-04 Pre-Rinse Unit

DW-05 Ventilator w/fresh Air Return (body only)

DW-06 Floor Channel & Gully w/ Grating

DW-07 Hood Type Dish Washer

DW-08 Clean Dish Table w/2 Rack Slide

DW-09 Wall Rack Shelf

DW-10 4-Tiers Slatted Shelf

DW-11 4-Tiers Slatted Shelf

DW-12 4-Tiers Slatted Shelf

DW-13 Hose Reel – w. Chemical Mixer

U Hotels & Resorts EU Technical Standards Manual

Page 231 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

BANQUET SATTELITE PICK UP AREA

U Hotels & Resorts EU Technical Standards Manual

Page 232 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CATERING – BAR

BD-01 Cabinet for Post Mix w Spray Gun BD-06 Water Filter

BD-02 Work Cabinet w/1 Rack Slide BD-07 Sink Cabinet, 1 Bowl Front L/H Side Open To Suit

BD-03 Cocktail Unit w/ Speed Rail BD-10 Under Counter Refrigerator (L), 2 Doors

BD-04 Coffee Machine BD-11 Under Counter Refrigerator (R), 2 Doors

BD-05 Mobile Plastic Garbage Bin BD-12 Floor Channel & Gully w/Grating

U Hotels & Resorts EU Technical Standards Manual

Page 233 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SWIMMING POOL BAR / RESTAURANT

UPB-01 Work Cabinet w. Hinge Door UPB-13 Bar Blender

UPB-02 Work Cabinet UPB-14 Work Cabinet

UPB-03 Glass Washer UPB-15 Rack Slide Cabinet

UPB-04 Drop In Sink Cabinet w. Trash Drawer UPB-16 Cocktail Unit w. Ice Bin

UPB-05&6 U/C Refrigerator, 2 Glass Doors UPB-17 Drop In Sink Cabinet w. Trash Drawer

UPB-07 Water Boiler UPB-18 C/C Ice Machine

UPB-08 Coffee Machine UPB-19 Work Cabinet

UPB-09 Work Cabinet w. Hinge Door UPB-20 POS Station

UPB-11 Water Filter w. UV System UPB-21 Work Cabinet

UPB-12 Work Cabinet w Hinge Door UPB-22+23 Juice Extractor / Ice Crusher

U Hotels & Resorts EU Technical Standards Manual

Page 234 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SATELLITE KITCHENS EXAMPLE: SPECIALITY RESTAURANT

USK-01 Equipment Stand

USK-02 Convection Oven

USK-03 Exhaust Hood w. Fresh Air

USK-04 U/C Refrigerator, 2 Doors

USK-05 Work Cabinet

USK-06 Double Wall Shelf

USK-07 U/C Refrigerator, 2 Drawer

USK-08 6 Open Burner Gas Range w. Stand

USK-09 Gar Fryer

USK-10 Gas Griddle w/ Stand

USK-11 Electric Salamander w. Hanging Shelf

USK-12 Work Table

USK-13 Sink Cabinet, 1 Bowl & Trash Drawer

USK-14 Work Table

USK-15 Drop-In Induction Units

USK-16 Heat Lamps

USK-17 Drop-In Frost Top w. Remote Condensing

USK-18 Conveyor Toaster

U Hotels & Resorts EU Technical Standards Manual

Page 235 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CANTEEN DISPENSE

ST-01 Rice Warmer ST -08 Post Mix

ST -02 1-Tier Wall Shelf ST -09 Ice Bin Cabinet

ST -03 Food Warmer w/3 GN 1/1 ST -12 Hand Wash Sink Cabinet, Knee Operated

ST -04 Glass Rack Cabinet ST -13 Soiled Dish Table

ST -05 Tray Slide ST -14 Tray Slide

ST -06 Sandwich ( R) Unit ST -15 Mobile Plastic Garbage Bin

ST -07 Water Boiler ST -16 Utility Cart

U Hotels & Resorts EU Technical Standards Manual

Page 236 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

COLD ROOMS

General

Temperatures

Construction

Electrical Equipment

Refrigeration Equipment

Doors

Interior Equipment

U Hotels & Resorts EU Technical Standards Manual

Page 237 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GENERAL

They are of 2 types:

Main store

Daily store

Daily stores are located near cold and hot preparation areas in the main kitchen and also in the satellite kitchens and pantries.

These two types of cold rooms are complemented by refrigerated stores and drawers of different sizes, according to kitchen needs.

There must be a cold room for fruits and vegetables, one for meat/ fish / poultry and one for butter, eggs and cheeses.

There must be also at least one -20˚C deep-freeze room.

The size and number of cold rooms for a particular project will be defined by U Hotels & Resorts.

The bakery-pastry is equipped with a separate cold room and freezer.

U Hotels & Resorts EU Technical Standards Manual

Page 238 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

TEMPERATURES

Maximum temperatures inside the cold storage rooms will be maintained at:

Meats 0 to + 4˚C

Fish 0 to + 2˚C

Dairy products 0 to + 6˚C

Vegetables 0 to + 8˚C

Frozen foods - 20˚C

Wine cellar + 14˚C

Daily cold rooms 0 to + 3˚C

Pastry 0 to + 3˚C

Frozen pastry - 20˚C

To achieve these temperatures, the following elements will have to be taken into account:

Ambient temperature

Quantity by weight of merchandise

Rate of deliveries

Defining these elements depends on the local climatic and supply conditions for each hotel.

U Hotels & Resorts EU Technical Standards Manual

Page 239 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CONSTRUCTION

Dimensions

Minimum internal height : 2,40 m and 2,10 under evaporator

Net door passageway dimensions: 1.90 × 0.90 m.

Area : as per brief, and allowing for trolley manoeuvring

Design

Cold rooms should preferably be built in place using traditional materials with possibly prefabricated panels and must follow precisely the

manufacturer specifications.

For masonry rooms, floors will be constituted of successive layers of: a watertight coating of asphalt with upsweep, insulation, a concrete slab and

20×20 cm non-slip stoneware tiles.

In both cases, the chamber will be carefully sealed from the ground to avoid all water infiltration.

Freezers will be equipped with an insulated ventilation system.

Floor slopes in the rooms will be a minimum of 1% towards the door.

Channelled stoneware baseboards are placed between floors and walls.

Walls will be covered with square-edged, light-coloured enamelled clay tiles or stainless steel.

Ceilings will have a cement rendering and painted with two coats of white paint approved by the health authorities.

All principal walls within the room will be protected by metallic angles to a height of 2 meters.

There should be no sill between the floor of the cold rooms and the surrounding areas.

From the start of construction, make allowances for depressed concrete slabs (about 18 cm for coolers, 23 cm for freezers).

Water Drainage

All water from washing and de-icing will be drained via floor traps located in the neutral chamber providing access to the cold room.

Drainage pipes within the freezers will be equipped with low-voltage heating elements.

U Hotels & Resorts EU Technical Standards Manual

Page 240 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ELECTRICAL EQUIPMENT

All electrical installations for the cold storage rooms (refrigerating equipment, lighting, alarms, compressor room lighting, and temperature recorder) will

have an emergency power supply.

The compressor room will be outfitted with a metallic cabinet containing:

A main disconnect switch

Compressor motor protection devices and resistance heating for de-icing (contact breakers with thermal and differential protection)

Clocks or time limit switches to control de-icing

Transformers to power lighting and heating cords

Fuse protection for lighting and heating cords

The front panel of this cabinet will contain:

Signal lights for each motor, indicating on, off or fault

Signal lights for rooms de-icing

This cabinet should work in emergency mode with a push button for “operation test “and “lamp test”.

Fault alarms are sent to the hotel’s BCS in Engineering and to the Executive Chef’s and Security office.

Room lighting is 24 V. dc through moulded watertight round fixtures with 60 W lamps and wire-net protection.

An outside switch with a 24 V signal light controls this lighting. It is also operable from the inside.

Each room will also have an occupation sound alarm installed near the door which can be controlled from inside the room in addition to the

mechanical security device.

Each room will be equipped with a safety thermostat allowing a light and / or sound alarm to be set off in case of an abnormal interior temperature.

This alarm will be sent to the hotel’s BCS.

De-icing is an automatic operation carried out through programmable timers.

In low-temperature rooms, de-icing will be done electrically with the safety thermostats automatically cutting off power to the resistance coils as

soon as the evaporator fins show an excessive temperature.

All equipment must be grounded.

U Hotels & Resorts EU Technical Standards Manual

Page 241 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

REFRIGERATION EQUIPMENT

Compressors for all the cold rooms will be grouped in a separated compressor area and specially ventilated with a screened façade.

Compressors will be semi-hermetic recycled water condenser units powered by electric motors. They will use a heat-recovery system and a specific

cooling tower. They will be equipped with HP pressure-sensitive safety switches.

There will be a single compressor for each room, installed on an anti-vibration stand.

Evaporators are ceiling units with flow control by thermostatic pressure reducing valves.

A door contact switch will cut off power to the evaporator fan (s) in case the door is opened.

Each room’s temperature will depend on an adjustable thermostat located close to the entrance door, controlling a solenoid valve on the refrigerant

piping.

Recording thermometers will be installed outside each room to indicate inside temperatures.

U Hotels & Resorts EU Technical Standards Manual

Page 242 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

DOORS

The doors to the rooms will be armoured with 1-meter high stainless steel sheets. These will be hermetically-sealed doors with standard dimensions

of 190 × 90 cm.

They will be provided with a manual interior opening system for safety.

The installation of “air-seal” curtains at the entrance to rooms is recommended.

Calculations will take into account frequent door openings. In some cases, the possibility of a fast freezer compartment will be studied.

Locks will be key operated and integrated on the hotel key-chart (see chapter T-5 Locks).

INTERIOR EQUIPMENT

Cold rooms will be provided with stainless steel shelves and hooks rods.

This equipment must be removable and of easy maintenance.

U Hotels & Resorts EU Technical Standards Manual

Page 243 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SUPPLY AND WASTE

Supply and Waste Circuit

Supply Reception

Goods Storage

Waste Areas

Typical Layout

U Hotels & Resorts EU Technical Standards Manual

Page 244 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SUPPLY AND WASTE CIRCUIT

This schematic layout is to be adapted as per the Hotel Brief.

U Hotels & Resorts EU Technical Standards Manual

Page 245 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SUPPLY RECEPTION

Service Yard

Reserved for delivery trucks uploading on the loading dock and entry and exit manoeuvres.

This is an enclosed space with a door equipped with impact fenders; it will be tarred or cemented with a steep gully slope, waste traps and water

points.

It will be illuminated.

Any view from the rooms on this yard will be avoided (by roofing etc.); in all cases the minimum clear height will be 4.10 m.

Loading Dock

Separate from the garbage and employee platform.

It is at the height of the rear of the trucks, protected by a buffer, and with an angle-iron nosing.

It will have a gutter with grating at the foot of the platform; the whole of the platform can be key-locked (grill or gate) via passkey.

All the walls will be covered with tiles and equipped with metal angle plates at all exposed corners.

Floor will be tiled or epoxy painted.

It will include:

o a weighing machine (500 kg)

o a floor drain

o double sink

The staircase linking the platform to the yard will be equipped with step-nosing and skid-proof strips.

Goods Receiving Office

This is an entry and exit control office with distribution to the storage areas.

It will have a large window bay with counter giving onto the platform.

U Hotels & Resorts EU Technical Standards Manual

Page 246 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Purchasing Office

This is located close to the goods entrance and is accessible to visitors.

The goods receiving and purchasing offices have electrical and computer terminal connections as per all other offices.

In small hotels of less than 80 rooms they can be combined.

Sorting and Washing

These areas are only needed in special cases where regulations or the nature of deliveries require preparation before storage.

These areas will be defined in the Hotel Brief.

U Hotels & Resorts EU Technical Standards Manual

Page 247 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GOODS STORAGE

All the following premises are located in the same area supervised by the storekeeper. The walls are protected by a rail installed at a certain height to

protect against impacts due to the trolleys and the corners will be equipped with angle plates.

All stores will be equipped with shelves and illuminated in the circulation centre line.

Food and Beverage Stores

Beverage store: this contains a beverage area of about three quarters of the total area maintained at 16˚C. A quarter of the general space will be

devoted to an 18˚C cold room for white wines, beer and champagne.

Mini-bar store: located inside the beverage store.

Food store: this contains the preserves and groceries; its entry and exit area should have a landing enabling carts to park. It also contains a

storekeeper’s office, who visually supervises the movements of the goods (the door contains a letter box and the desk has a connected computer

terminal).

Cold stores: see Chapter C-16 Cold rooms.

General Stores

Bulk store: this contains operations equipment, guest supplies and a stationary store.

OPE store: adjacent to the general store equipped half with shelves and half with free space. It contains chinaware, glassware and cutlery. These

may also be separate stores.

Records: its size enables it to store 10 years of records. It is illuminated, ventilated and protected against rodents. Be aware of fire prevention.

Dangerous products store: ideally located outside it contains all chemical and maintenance products and can be integrated in the bulk store. Be

aware of fire prevention.

Outdoor Store: shelters gas cylinders with a fire hydrant present.

U Hotels & Resorts EU Technical Standards Manual

Page 248 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

WASTE AREAS

Located close to the receiving dock but on a separate dock if possible to avoid any contamination.

Floors and full height walls are tiled.

A disinfection post, (micro-spray type) in a central position will clean all areas.

Each room will be provided with a floor drain.

In all cases these are necessary:

Trash store

Refrigerated garbage: refrigerated room receiving waste from kitchens

Empty bottles: can be equipped with a glass compactor

This area layout depends on:

Possible use of compactor or crusher

Waste removal system.

NB: the total daily waste to remove can be 4 kg/guest room (annual average)

U Hotels & Resorts EU Technical Standards Manual

Page 249 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

TYPICAL LAYOUT

Typical layout of receiving area

A1 Scale

A2 Double Bowl Sink

A3 Spray Unit

A4 Waste Bin

A5 Meat & Vegetable

Trolley

A6 Working Bench

A7 Shelving Unit

A8 Cargo Carrying Trolley

A9 Shelving Units

A10 Working Bench

A11 Shelving Units

U Hotels & Resorts EU Technical Standards Manual

Page 250 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

EMPLOYEES

Personnel Circuit

Time Keeper – Security

Human Resources Offices

Medical Services

Locker Rooms – Washrooms

Cafeteria

Miscellaneous

Service Corridors

U Hotels & Resorts EU Technical Standards Manual

Page 251 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

PERSONNEL CIRCUIT

The personnel have a specific entry completely separate from the goods and garbage.

U Hotels & Resorts EU Technical Standards Manual

Page 252 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

TIME KEEPER OFFICE – SECURITY

Located near the specific employee entrance in order to allow visual control of entrances and departures.

It can be combined with a security room when there is no specific security office (provide a counter in the service corridor and a notice board). The

room will be secured by a key.

It is equipped with a personnel time management system with a magnetic card reader outside the time keeper’s office and a terminal and printer in

the personnel office.

In smaller hotels these functions, although still identified by separate desks, can be combined with the receiving/purchasing areas in one volume as

long as visual control can be kept on both employees and goods entrances and movements.

HUMAN RESOURCES OFFICES

Includes a DHR office and a room with a secretary and reception area plus a training room on the personnel entrance circuit before or after the time

keeper.

The secretary’s area must control the access to the director’s office.

MEDICAL SERVICE (FOR HOTELS WITH 80+ ROOMS)

This is used by the employees but can be accessible to customers if required.

It includes (if fully equipped):

a medical treatment room

a consulting room

U Hotels & Resorts EU Technical Standards Manual

Page 253 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LOCKER ROOMS – WASHROOMS

The space scheduled in the brief takes into account:

The number of employees

The male/female proportion.

The number of temporary employees (“casuals”) for which additional locker rooms and washrooms must be provided (usually, about 5% of the total

with separate toilets).

In all cases the equipment will include:

For all areas:

waterproofing with floor drain and a minimum slope of 2%

tiling on the floors and walls

a clock

significant exhaust ventilation (approximately 5 vol/h)

watertight round-type luminous points, with metal protection, placed well above the passageway

locker approximate dimensions: 180 cm high, 60 cm deep, 35cm wide (single or double height).

benches

full-length mirrors

a shoe-shining point

fixed garbage cans

For the toilets:

washbasins with mirrors, shaver plugs, soap dispensers and hand dryers

showers with concealed pipes and changing booths with double coat hangers.

toilets with coat hanger.

floor drains will be provided to avoid any stagnant water.

U Hotels & Resorts EU Technical Standards Manual

Page 254 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

As a rule one piece of equipment will be provided (WC + shower + washbasin) for every 30 people.

For service rooms far away from locker rooms, specific washrooms will be provided.

It is necessary to provide a few lockers for dirty work, with a locker for work clothes and a locker for civilian clothes (kitchen employees,

maintenance employees and gardeners).

CAFETERIA

Self-service type for all employees.

Care will be given to the decoration and lighting. It will be soundproofed.

Its equipment, apart from the tables and chairs, will include beverage distributors, sound system, TV’s and notice boards.

The personnel washrooms will be nearby.

Provide a storage room.

Finishes and equipment will be chosen in coordination with the main consultant.

In most cases, food preparation should be prepared in an adjacent main kitchen to reduce the need for a separate kitchen, as well as a dish

washing area. If this is not possible then a separate food preparation and dishwasher area should be provided for.

MISCELLANEOUS

Recreation Room

Will include a TV set, armchairs and low tables. A space will be provided for billiards, table tennis or other games.

Bicycle and Motorcycle Garage

At the service courtyard level: it is fenced off, covered and enclosed with a wire fence.

It is used for employee’s bicycles and motorcycles (if applicable).

U Hotels & Resorts EU Technical Standards Manual

Page 255 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SERVICE CORRIDORS

The service circulations will be designed in order to connect together the different rooms in the most functional and simplest possible way.

On all corridors used by trolleys (which means everywhere, except specific personnel circuits) protection rails, angle corners and 1.80 m

minimum width or more according to traffic will be provided.

Steps will be avoided; ramps will be 5 % slope (maximum 10% for extreme cases and short runs) and with anti-skid texture.

Door sizes will be standardized. For example, simple doors would be 100 cm and double doors could be 140 cm. If possible, doors should be

avoided across service passageways. They should always be protected by from carts by high kick plates, and fitted with oculus where necessary.

Service elevators and hoists will be always in close proximity to a service stair allowing direct connections in case of breakdown or maintenance

(specifically for service entrances, connections between kitchen and storage and housekeeping pantries).

U Hotels & Resorts EU Technical Standards Manual

Page 256 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

TECHNICAL ROOMS

General

Boiler Room

Domestic Hot Water Production

Refrigeration Room

Air Handling Units

Water Boosters and Water Tank

Elevator Machinery

Transformer and Electrical Switch Gear Rooms

PABX and Battery Rooms

Generators Room

Workshops

Miscellaneous Rooms

U Hotels & Resorts EU Technical Standards Manual

Page 257 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GENERAL

Location in the Hotel

These rooms should be grouped in a clearly defined technical area so as to facilitate maintenance operations and ensure optimum operating

conditions.

Their location will be adopted so as to limit as far as possible any harmful effects to the guestrooms and areas to which the public is admitted. Give

thought to noise from the elevator machinery and generators.

The secondary technical rooms (central ventilation units, elevator machinery) when required will be placed alongside the service rooms, corridors

and rooms with a high noise level.

Give thought to the layout of the smoke discharge ducts from the boiler room and the electric generator when locating the rooms.

In all cases these rooms will be given acoustic treatment according to the acoustic specifications of the technical standards (transmission of

vibration and air noises) concerning public rooms, service areas and guest rooms. See Chapter C-21 Sound Control and Insulation.

Accesses and Communications

The technical rooms should be accessible to trucks in view of subsequent replacement of the equipment. In particular, provide a passage sufficiently

wide and high.

Rooms should be served by service stairs and elevators in order to allow access of employees, materials and goods.

The communications between the different rooms should enable members of the maintenance teams to circulate without interference with the hotel

guests. Technical access to terraces will be provided in order to avoid passage through guest room corridors.

Finishes of the Rooms and Passageways

The finishes will be as follows:

Concrete floor coated with dustproof epoxy paint.

Walls and ceilings: concrete or masonry coated with dustproof paint (car park type).

All the metal parts will have two coats of rust-repellent paint and two coats of finishing paint.

U Hotels & Resorts EU Technical Standards Manual

Page 258 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Lighting

The levels of illumination are those defined in Chapter T-12 Electricity. The appliances are installed to illuminate the equipment, especially the

switchboards and measuring instruments.

Electrical Equipment and Low Voltage

Apart from the supply of the technical equipment, provide in all rooms:

o a panel containing one 2 × 10/16 AMPS grounded outlet and one 2 × 32 AMPS grounded outlet protected by differential residual circuit

breaker, sensitivity 30 mA

o emergency lighting via self-contained units secured over the exits

o lighting taken from the emergency power supply for certain priority premises (maintenance offices and workshops, control room, boiler

rooms, transformer, LVS, electric generator, elevator machinery)

o Wall-mounted telephone sets in the rooms and passageways.

The power cabinet will be separate from the lighting cabinet.

The workshops equipped with machine tools will have emergency punch switches, cutting off all the power distributed throughout the room.

Air Conditioning and Ventilation

Efficient ventilation of rooms will be provided.

Provide efficient ventilation of the premises and air conditioning if the heat releases or sensitivity of the equipment requires. In all cases, maintain a

temperature less than or equal to 28˚C, if necessary (for instance by recycling the air exhausted from the public premises).

The ventilation outlets should be at least 2.5 m away from any opening.

Miscellaneous Equipment

Doors with anti-panic opening will give access to staircase or emergency exits.

Floors drains in all rooms (except electrical rooms), and waterproofing on the floor if they are above another room.

All arrangements necessary to handle the equipment (provide a rail above all heavy equipment).

All the technical equipment will be installed on a stand with anti-vibration mounts.

Water taps will be provided in order to maintain and clean technical rooms.

U Hotels & Resorts EU Technical Standards Manual

Page 259 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Safety instructions, maintenance procedures and flow diagram panels will be posted next to the corresponding equipment.

BOILER ROOM

Access

This must be through a lobby with a mandatory second access door (for emergencies).

Layout of the Equipment

The boilers will be installed so that the clear space between the wall of the boiler room and the side of the nearest boiler is more than 1 m.

The minimum clear space between boilers should be 0.80.The minimum clear space in front (or the back) of the boilers should be 2.5 m so as to be

able to remove water tubes when necessary.

The clear spaces thus defined should have a minimum height of 2.00 m from the floor.

Fire Safety

Smoke detectors.

Safety breaker: this cuts off the gas, fuel oil and electricity supply from outside the room.

Boilers are installed on a 10 cm minimum height concrete pad.

Ventilation

Besides smoke breeching and stacks (or chimneys), the boiler room must have two permanent air supply openings and exhausts:

Exhausts: located in the ceiling to evacuate air with one or several ducts associated with the smoke ducts. Their total section is at least equal to the

half-section of the smoke ducts.

Air supply: at floor level in order to maintain atmospheric pressure inside the boiler room.

U Hotels & Resorts EU Technical Standards Manual

Page 260 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Construction Rules for Chimneys

The chimneys should, where possible, be constructed outside the building without disturbing the architecture.

The indoor ducts will be constructed inside a ventilated shaft built of non-combustible and inflammable materials with a firebreak degree complying

with the regulations in force. In the event of there being no regulations, a 2-hour fire-break degree will be provided.

This shaft should be permanently ventilated by openings emerging directly on the outside and with a minimum section of 0.04 m².

The size of the shaft should provide for inspection of each smoke duct over their whole length on at least one side. For this purpose, rungs with rest

landings and safety hoops, or any other system of inspection, must be provided.

The minimum opening of the clean out at the bottom of each duct will be 0.05 m².

The shaft itself cannot be considered as high ventilation of the boiler room, but this latter duct can be built inside.

The smoke ducts will have a minimum thickness of 22 cm with a material approved by a laboratory officially recognized by the insurance

companies.

The layout of the chimney stack stubs and rain cap on the roof should be designed so that the prevailing winds do not bear down the smoke onto the

openings or equipment.

U Hotels & Resorts EU Technical Standards Manual

Page 261 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

DOMESTIC HOT WATER PRODUCTION

Location

Substations whose maximum power is under 5800 kW can be located in the buildings.

Special Construction Arrangements

The floor of the room should form a reservoir of at least 5 m³ for substations with a power under 2300 kW and 10 m³ minimum for substations with

higher power.

REFRIGERATION ROOM

Access and Location

Room communicating as directly as possible with the cooling towers.

Layout of Equipment

The machines will be located so that the clear space between the walls of the room and the side of the nearest machine is more than 1.50 m.

The minimum clear space between the machines will be 1.50 m.

A minimum distance must be provided in front of (or behind) each machine equal to the length of the exchangers to provide for easy pipe

replacement. This distance will not be less than 2.50 m.

U Hotels & Resorts EU Technical Standards Manual

Page 262 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Ventilation and Air Conditioning

The room should be ventilated mechanically by an exhaust fan the flow rate P of which, (in m³/h) can be calculated by the following formula:

P = 50 23 G

G being the weight in kilograms of the quantity of cooling fluid in the plant installed in the machine room.

Air supply will be via the low point if heavier than air refrigerants are used or the high point if lighter than air refrigerants are used.

Start-up of the exhaust fan shall be activated by an emergency switch located outside the start-up of the exhaust fan and shall be activated by an

emergency switch located outside the room.

In tropical climates, air conditioning will be provided according to the supplier’s requirements in order to protect the electronic board.

U Hotels & Resorts EU Technical Standards Manual

Page 263 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

AIR HANDLING UNITS

Rooms housing A.H.Us must be independent from the boiler room, refrigeration room and electrical rooms.

The layout of the equipment should provide for easy circulation and removal of filters and coils.

Floor drains required (and waterproofing if the room is not at ground level).

WATER BOOSTERS AND WATER TANKS

The technical room containing the main pipes, valves and boosting should be at least 1.00 m below the lower level of the water tanks so as to

provide for gravity flow of the water either towards the booster or towards the drain.

Slopes should be provided on the floor to drain off towards the drainage lifting station.

Spaces of at least 1 meter should be left between the large pipes and between the different pieces of equipment.

Water tanks will be equipped with access hatches and interior ladders for cleaning.

ELEVATOR MACHINERY

The ventilation should be efficient. The temperature in elevator machine room should be kept at 35 C or below.

U Hotels & Resorts EU Technical Standards Manual

Page 264 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

TRANSFORMER AND ELECTRICAL SWITCH GEAR ROOMS

Layout of Equipment

Provide sufficient space allowing maximum accessibility and at least the following clearances:

o HV substation: behind 0.10 m (1 m if accessibility behind is required); in front 1.20 m.

o LV switchboard: behind 0.80 m with passage from front to back; in front 1.20 m.

o Transformers: if they are installed against a partition wall, provide 20 cm between the partition and the transformers; 1.50 m to let through

the transformers; 0.60 m between transformers and 0.20 m behind.

Floor reservoir will be provided for liquid insulator transformers.

Avoid all water influxes and provide a threshold at the entrance; if the room is in the basement provide a tanking.

The transformer room will generally open directly onto the outside and will be located so as to be as near as possible to the centre of gravity of the

powers to be serviced.

Follow the specifications of the local power supplier.

Passage of Cables

The cables should be laid in troughs covered with metal plates.

The layout and dimensions of the troughs should enable the cables bending radius to be respected, and the cables to be placed in a single layer with

30% reserve space.

Ventilation

The ventilation will preferably be natural for the rooms.

In the event of this natural ventilation being impossible owing to the layout of the rooms, or if the temperature of the site is higher than 30˚C, then

mechanical ventilation must be provided.

This ventilation will be controlled by thermostat which will trigger the speed of the fan.

A spare fan will be provided for all the rooms ventilated mechanically with a selector switch and automatic starting on an operating failure of a fan

in service.

U Hotels & Resorts EU Technical Standards Manual

Page 265 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Miscellaneous Arrangements

Provide all the necessary safety and working equipment (pole, gloves, mats, stools).

Provide the labelling of the cables.

Avoid water pipes in rooms above electrical stations.

Provide waterproofing on the floor if there is a risk of leakage.

Provide a 15 cm threshold with the outside.

PABX AND BATTERY ROOMS

The premises must remain absolutely clean: general dustproof paint and acid-proof tiling is required on the floor.

Sufficiently well sized to provide 1.00 m circulation between cabinets and between batteries.

Ventilation according to constructor’s instructions and provide air conditioning of the room.

GENERATOR ROOM

Will be located close to the main electrical switchgear with easy access for the equipment.

The minimum circulation around the generator should be 1.50 m.

Provide soundproofing for the room or the generator engine and vibration isolators.

Provide engine-cooling system.

Provide adequate ventilation for engine and generator radiated heat.

Locate the batteries on a raised stand.

The room will be equipped with a day fuel tank and transparent tube level gauge.

Smoke exhaust with a silencer will be located in order to create minimum pollution and sound nuisance, away from air intakes and windows.

U Hotels & Resorts EU Technical Standards Manual

Page 266 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Sample drawing of Generator Room

U Hotels & Resorts EU Technical Standards Manual

Page 267 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

WORKSHOPS

Electricity: provide wall mounted electrical panels with low voltage outlets, TV outlet, RJ45 outlet,

Paint shop: mechanical exhaust with filter.

MISCELLANEOUS ROOMS

Technical Control Room:

This room will contain, among other items, the main mimic panels and central computer of the hotel systems control (BCS), technical alarms

signals, remote controls, the central sound and T.V. racks, sprinkler alarms, technical system regulation control and a paging station. It can include a

desk for a technical department assistant. It is located close to the Engineer’s office and/or close to the main plant room.

This room, as well as the main I.T. room (if any), shall have a smoke and heat detection system.

Engineer’s office and assistant.

Drawings and files room with a drawing table.

Technical stores.

These are under the responsibility of the engineer: Storage of spare parts required for current maintenance (bulbs, thermostats, spare tools,

measuring instruments, etc.).

Maintenance lockers and washroom.

To be provided only in the event of the technical areas being remote from the personnel’s premises.

Technical shafts and galleries.

The voids in the dropped ceilings and large technical shafts must be equipped with lighting and socket outlets.

Sewage treatment plant.

Swimming pool treatment room (see chapter T-8 Sanitary Plumbing)

Lifting station

Kitchen grease separator (see chapter C 15 Kitchens)

Cold rooms compressors see chapter (C 16 Cold Rooms)

U Hotels & Resorts EU Technical Standards Manual

Page 268 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FIRE SAFETY

General

Building Organisation

Covering Materials

Emergency Lighting

Miscellaneous

U Hotels & Resorts EU Technical Standards Manual

Page 269 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

These specifications are given as information only and are not limiting.

GENERAL

The U Hotels & Resorts standards do not require full sprinklers in all cases. See Chapter T-9 Fire Protection. Furthermore, the fire code of the country in

which the building is located must be observed as a priority. The rules that provided below are an example of building organisation and equipment

considered as a minimum requirement.

U Hotels & Resorts EU Technical Standards Manual

Page 270 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

BUILDING ORGANISATION

Access to Buildings

The building should open, directly or indirectly, on one or several public roads with a minimum width of 8 meters to provide access for fire engines

and enable them to manoeuvre.

One façade at least should be accessible to fire trucks though a ladder access allowing installation of fire ladders. (See attached sketches).

Open spaces can replace ladder access as long as they allow installation of fire ladders in different spots in order to reach a window in each fire

sector of the building.

Isolation towards Adjacent Buildings

A hotel must be isolated from any adjacent building in order to avoid a fire spreading.

Means of Egress

Number and dimensions according to the number of people in the building.

On each floor, these numbers should take the upper floors into account.

U Hotels & Resorts EU Technical Standards Manual

Page 271 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

BUILDING ORGANISATION

Capacity Number of

staircases Total minimum width of stairs

1 to 19 people

20 to 50 people

51 to 100 people

101 to 200 people

1

2

2

2

0.90 m (“1 unit” width)

0.90 m + accessory passage with minimum width 0.60

m

0.90 m + 0.90 m or 1.40 + 0.60

0.90 m + 1.40 m

Stairs

The corridors and enclosed or open-air staircases giving onto the exits should be distributed so as to avoid dead-end corridors of more than 10 m

and so that the distance from a room door to the closest stair is no more than 35 m (20 m in high-rise buildings). They should open directly outside

at the ground floor or less than 20 m from a protected exit way.

Open interior stairs are limited to one, connecting the two lower floors, in specific cases such as between the lobby and the first floor. They require

a specific study to follow the applicable codes, especially in terms or smoke removal.

Passages and Exits

Each passage should have a width in proportion to the number of people liable to use it, i.e. generally 0.60 m per fraction of 100 people or “unit” ,

given that no passage will be less than 1.40 m wide (i.e. two “units”). (Except for the supplementary and accessory passages). All the widths are

designed after deducting possible projections (pilasters, display cases, flap-seats, lockers etc.) excluding projections less than or equal to 10 cm

(handrails).

Long floor corridors should be subdivided at least every 30 m by sets of 90 minute flameproof walls and doors.

U Hotels & Resorts EU Technical Standards Manual

Page 272 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Exit Doors

These should have the following standardized dimension, ± 5%

single-leaf door 0.90 m minimum (one “unit”)

two equal leaf doors 1.40 m minimum (two “unit”)

two unequal leaf doors 1.80 m minimum, (3 “unit”) the largest should not be more than 1.10 m wide

Except for guestroom doors or doors leading to rooms occupied by less than 50 people they should open in the direction of the exit. Revolving doors can

only be accepted as an addition to the necessary passages. The opening of doors must not interfere with exit corridors.

Doors opening onto fire stairs must be self-closing and rated 2-hour fire resistant or 90 minute flame resistant.

U Hotels & Resorts EU Technical Standards Manual

Page 273 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 274 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Fire Resistance Rating

Exterior wall fire rating:

o Fire resistant wall: with all adjacent buildings, this should consist of a 2-hour fire-resistant wall, being increased to 3 hours if the adjacent

building contains special fire hazards.

o Isolation versus the building opposite: when the building opposite is less than 8 m from the façade, one of the facades should be 1 hour fire-

resistant.

o Floors: The isolation should be 2-hour fire-resistant. This degree will be increased to 3 hours if the adjacent building presents a fire hazard.

Fire rating between floors:

o Facades must not be built out of easily combustible materials and must be studied in order to limit the spread of fire from one level to the

other.

o Unless the building is fully sprinkler equipped, and the facades are made of fire-rated materials, the rule C + D> 1.30 m concerning fire

spreading obstacles from one floor to another must be applied (C = vertical distance from window top to window bottom, D = horizontal

distance from glass plane to floor edge).

o For hotels containing less than 1,500 people the floors should be 1 hour fire resistant.

Fire rating degree between kitchen, technical rooms and public areas:

o The kitchens, linen stores and laundries should not control the exits at the disposal of the public. These areas should be isolated from the

public areas by 1-hour fire-resistant walls, floors and partitions.

o The communicating bays or doors should be 90 minute fire-resistant.

Fire rating degree between high-risk areas and public areas:

o The maintenance and repair workshop, dangerous chemicals store and parking areas must be isolated from public areas by 2 hour fire-

resistant walls, floors and partitions.

o The communication bays or doors should be one hour fire-resistant.

U Hotels & Resorts EU Technical Standards Manual

Page 275 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Staircase shafts:

o These should be partitioned off by 90 minute fire-resistant walls, covered with incombustible materials. The doors should be 30 minute

flame-resistant.

Fire dampers:

o All the ducts crossing fire-resistant walls or floors must be provided with fire dampers at the crossing point.

Cases of high-rise buildings:

o The staircases should be partitioned off with 2-hour fire-resistant walls, including the vertical conduits.

o The doors and hatches should be 1-hour fire-resistant.

o The corridor enclosures should be 1-hour fire-resistant.

Fire stability of structures:

o The structures should be stable in fire for 90 minutes. This requires sufficient covering of the concrete reinforcement rods and rules out any

unprotected metal structure.

o In the case of a high-rise building, the structural elements of the building should be rated 2-hour fire-resistant.

U Hotels & Resorts EU Technical Standards Manual

Page 276 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

COVERING MATERIALS

Except in guestrooms in low-rise buildings, the following should be in non-combustible materials (rated MO) or at least permanently non-

inflammable (M1):

o the hooking systems (rods, rings etc)

o the hangings and floating covering materials

o dropped ceilings and ceiling coverings (with MO suspension system)

o floating cross-curtains.

The following should be in materials permanently difficult to ignite (M2):

o non-floating covering materials

o translucent dropped ceilings.

o the relief decorative elements

The following should not be in easily inflammable materials (or better than M4):

o the space between materials and walls

o the floor coverings

Cases of high-rise buildings:

o the dropped ceilings should be rated 15 minute fire-stable in the public corridors

o all the covering materials should be at least difficult to ignite (M2)

o passages and the kitchens should be non-combustible(MO)

o the covering supports should always be non-combustible (MO).

U Hotels & Resorts EU Technical Standards Manual

Page 277 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

EMERGENCY LIGHTING

The emergency lighting consists of:

o illuminated exit signage clearly indicating the direction of egress enabling everybody to get access to the outside plus identifying obstacles

and changes in direction

o the mandatory ambient lighting when the numbers of the public may be 100 per level and 50 in the basement. The light sources should not

be more than 15 m apart.

The emergency lighting can be of two types:

o central source with batteries or generators

o via self-contained units with a battery and charger for each unit.

See Chapter T 12 Electricity (subchapter emergency lighting).

Cases of high-rise buildings:

o all the materials making up this installation should be incombustible

o the emergency generator must supply the emergency installations before any other load.

o emergency installations have completely separate and duplicate protected electrical circuits.

U Hotels & Resorts EU Technical Standards Manual

Page 278 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SMOKE EXHAUST

Objectives

Smoke exhausts have three objectives:

In an initial stage; to enable the occupants of the compartment where the fire has broken out evacuate rapidly and get to a protected space as soon as

possible, without being hindered by smoke and without this smoke spreading out of the compartment.

In a second phase; to enable the rescue teams to rapidly locate the fire’s source and extinguish it without being impeded by the capacity of the

smoke.

To prevent smoke entering the staircases and adjacent compartments.

Natural Smoke Venting

Staircase:

In the upper part, the stairwell shaft should contain vents (skylights, exterior wall windows) with releasing devices enabling them to be opened from

the ground floor and the top landing floor while simultaneously opening the fresh-air supply.

Horizontal corridors:

o Very long corridors should be intersected every 25 to 30 m maximum by 90 minute flame-proof doors.

o Each compartment thus formed should be equipped with a smoke-exhaust device.

o The vents should have a ratio of 1/50 of the surface of the corridor or compartment.

o The distance between an air supply and a smoke exhaust should not exceed 10 m in a straight corridor and 7 m if there are changes in

direction.

Rooms to which the public is admitted:

o All the rooms to which the public has access should contain, in their upper part, one or several horizontal or vertical vents communicating

with the outside (ratio: 1/100 of the surface).

o If these vents are normally closed, it should be possible to open them by releasing stations easily accessible from the floor of the room and

located close to the main entrances. This station will be duplicated by an automatic releasing device connected to a smoke detector placed

close to an air return outlet.

U Hotels & Resorts EU Technical Standards Manual

Page 279 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Mechanical Smoke Removal

When natural smoke exhaust is not possible, then mechanical systems will be used. In case of fire, enclosed fire stairs will be supplied with fresh air and

kept at a pressure higher than that of adjacent areas.

Rooms under 300 sqm.

All the mechanical systems providing a minimum exhaust flow of 1 cu.m/s per 100 sqm can be used on condition that:

The lower part of the exhaust grille is located in the upper third of the room and at a minimum distance of 1.80 m from the floor.

The ducts are in non-combustible, non-flammable material, 1-hour fire-rated.

The exhaust fans can fulfil their function for a minimum time of 2 hours with smoke at 400˚C.

The ducts emerge at more than 8 m from an obstacle higher than them.

Smoke exhaust will be controlled by an automatic releasing device via detectors sensitive to smoke and combustion gases.

The automatic release will be duplicated by a manual station.

Room more than 300 sqm.

Creation of sections (which need not be materialised), of 300 sqm maximum.

Per section, provide at least one exhaust outlet normally closed by a 2-hour rated damper the opening of which is linked to the smoke detector.

The total exhaust flow per section should be at least 3 cu.m/s.

Exhaust will be obtained by fans. These can be grouped and used to exhaust several sections

NB.

In the event of several rooms being served by a mechanical smoke-exhaust system, the flow rate of the fan should be able to provide the total flow

rate corresponding to smoke exhaust of the two largest rooms.

Fresh-air supplies: in all cases, natural fresh air supplies will be provided allowing the sweeping of the rooms. The fresh air supply flow rates will

be 40% less than that of the air exhausted.

The fresh air supply grilles will be blanked off by fire dampers in the case of several grilles being placed on the same circuit. These dampers will be

controlled by the detectors.

U Hotels & Resorts EU Technical Standards Manual

Page 280 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

In the event of the rooms being wide open on the outside, the openings can be considered as suppliers of fresh air.

Corridors

Mechanical smoke exhausts should be designed on the basis of 0.5 cu.m./s per fraction of 100 people.

The distance between an air supply and an exhaust outlet should not exceed 20 m in the case of a straight corridor and 14 m in the case of a non-

straight corridor.

The fire detection automatically activates the smoke-removal systems (fans and dampers).

Cases of high-rise buildings:

The communications between one compartment and another and with the stairwells should be equipped with smoke-proof vestibules at least 3 m³

each. The vestibule enclosures will be built to constitute a 2-hour fire-rated separation.

The stairwells should be kept constantly free of smoke.

The vestibules should be kept free of smoke in normal times and equipped so as to eliminate fumes rapidly when being used in case of fire in the

adjacent compartments.

Smoke should be permanently exhausted from the corridors in case of fire in the compartment.

According to the applicable code, different organizations could be adopted.

The stairs blowers shall ensure a minimum air speed of 0.5 m/s when the door is opened with an adjacent lobby.

This flow, added to the lobby air blower flow, shall ensure a minimum air speed of 1 m/s when the door is opened with an adjacent corridor.

The corridor extraction flow shall be at least 1.3 times the amount of the air supplied to it.

U Hotels & Resorts EU Technical Standards Manual

Page 281 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SMOKE REMOVAL

EXAMPLE A:

Blowers in stair, vestibules and corridors

Extraction in vestibules and corridors

U Hotels & Resorts EU Technical Standards Manual

Page 282 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SMOKE REMOVAL

EXAMPLE B:

Blower in stair and vestibules

transfer from lobbies

extraction from corridors

Stair to vestibule door (CF 1 hour)

Vestibule blower flap (PF 1 hour closed in waiting position, opened by fire

detection)

Vestibule to corridor door (CF ½ hour PF 1 hour)

Transfer flap (PF 1 hour, opened in waiting, position, closed if T > 70˚c)

Corridor extraction fire dampers (CF 2 hours, opened by fire detection,

spacing less than10 m

Extraction fan rated for 450˚c for 2 hours

Vestibule blower fan

Vestibule blower duct (CF 2 hour)

Corridor extraction duct (CF 2 hour)

CF = Fire resistant

PF = Plan resistant

U Hotels & Resorts EU Technical Standards Manual

Page 283 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

MISCELLENOUS

Boiler Room

See Chapter C19 Technical Rooms

Gas Installation

See Chapter T8 Sanitary Plumbing – subchapter 6: gas

Air Treatment and Ventilation

See Chapter T 11 Ventilation – Air conditioning

Electrical Installation

See Chapter T 12 Electricity

Elevators and Escalators

See Chapter T 15 Elevators (lifts)

Kitchen

See Chapter C 15 Kitchens

Fire Fighting Means

See Chapter T 9 Fire Protection and T 10 Fire Detection

U Hotels & Resorts EU Technical Standards Manual

Page 284 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SOUND CONTROL & INSULATION

General

Grade Vibrations

Outdoor Airborne Sound

Indoor Airborne Sound

Impact Noises

Noise from Collective Equipment

Noises from Individual Equipment

Outside Equipment noises

U Hotels & Resorts EU Technical Standards Manual

Page 285 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GENERAL

Adequate sound control is one of the fastest-growing requirements in today’s hotel buildings.

Maximum Sound Levels

The current chapter deals with measures to be taken. These measures must achieve the following objectives (values are calculated according to EN/ISO

717-1):

Maximum general Sound level resulting

sound level from collective equipment

dB (LnAT)¹ noises dB (LnAT)

Guest rooms 32 30

Lobby 40 35

Restaurant 40 38

Meeting rooms, lounges 32 30

Offices 35 33

Kitchen, laundry 48 45

Sound insulation at different parts of the building will be designed to allow the following minimum value of insulation:

Noise given by Noise perceived by

Sound reduction in dB

(DnTA or RA or NR)²

Corridors Guest rooms (bed area)

40 (door itself: 37)

Guest rooms (or bathrooms) Guest rooms (or bathrooms)

53

Restrooms Guest rooms or public rooms

59

Meeting rooms Guest rooms or public rooms

59

U Hotels & Resorts EU Technical Standards Manual

Page 286 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Importance of a good acoustical design, sound insulation and reverberation control

Whatever the detailed measures, acoustical comfort will not be achieved if basic measures are not taken during the building design. It is much cheaper to

avoid noise problems in the initial design period than to correct them later.

GRADE VIBRATIONS

In case of projects built near an expressway, measures will be taken to avoid vibration transmission able to bring acoustical nuisance.

An anti-vibration break must be provided between the foundations and the building-bearing structure.

Therefore the bearing surface must rest on the foundations through vibration isolators.

In case of a building where only a part of the building needs to be insulated from grade vibrations, it is then necessary to provide a vertical

expansion joint at full height, between the insulated part and the non-insulated part.

OUTDOOR AIRBORNE SOUND

According to the level of the outdoor sound, the sound reduction of the façade should be adapted so as to obtain a sound level in the bedroom not exceeding

32 dB (LnAT). In all cases, the sound reduction of the façade should be 30 dB (DnTA or RA) at least.

Care must be taken over the following points:

Have a sufficient weight per square meter for the solid sections of the façade

Have sufficiently thick glass and frame without sound leaks. Glass façade is recommended to be of equal or higher than laminated ¼” +0.06 mm.

PVB+1/4” (STC-39, OITC-34)

In the case of double glazing, provide different thicknesses of the two panes with a large air gap in-between and absorbing material on the sides.

Avoid sound leaks in the façade (ventilation inlets, rolling shutters, boxes, roof structure etc.)

If necessary, install double windows.

U Hotels & Resorts EU Technical Standards Manual

Page 287 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Light weight block (G4) wall with cavity Light weight block (G4) wall without cavity

Overall thickness: minimum 200 mm. Overall thickness: minimum 250 mm.

U Hotels & Resorts EU Technical Standards Manual

Page 288 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

To analyse the noise from to the street it will be necessary to:

Either make measurements according to the following criteria: the equivalent noise level will be measured taking the adequate time constants into

account (refer to NF S 31010 standard or approved equivalent) – the method used is to average the energy received from 8:00 AM to 8:00 PM. (For

comparison, the level between 8:00 PM and 8:00 AM shall also be computed).

The measurements will be made 2 meters in front of the future façade of the building

U Hotels & Resorts EU Technical Standards Manual

Page 289 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

INDOOR AIRBORNE SOUND

In the layout, make sure to keep apart from noise-producing areas (technical rooms, nightclub, gym, and noisy animate areas) the rooms which

require a low sound level (bedrooms, conference rooms).

Insulation between bedrooms¹ : this should be at least 53 dB (DnTA) in situ and can be obtained by:

o 15 cm of concrete, or

o Special partitions and lining system which have been tested and achieved a high sound rating.

Insulation between bedroom and corridor: this should be at least 40 dB (DnTA) and can be obtained by :

o 15 cm of concrete, or

o 15 cm of solid bricks or concrete blocks coated on both sides, or

o Special partitions and lining system which have been tested and achieved a high sound rating.

o Dry walls with uneven side thickness, acoustical fillings, and special acoustical precautions (at the floor, ceiling and posts).

To achieve these figures it is imperative to take special care of the quality of the entrance door and connecting doors which determine most of the

acoustic attenuation of the partitions, and should have a rating of 37 dB (DnTA) minimum.

Entrance Doors

hardwood frame

thickness 40 mm with solid core

double rebate on the door edges and its frame

peripheral acoustic gasket

telescopic acoustic skirting

closer concealed in frame head

Connecting Doors (for each)

hardwood frame

thickness 40 mm with solid core

solid wood threshold with rebates involving the 2 doors

double rebate on the door edges and the frames

peripheral acoustic gasket

U Hotels & Resorts EU Technical Standards Manual

Page 290 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SAMPLE DOOR DETAIL

Bottom seal

U Hotels & Resorts EU Technical Standards Manual

Page 291 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

The following points should also be carefully checked:

The fresh air inlet: provide a sound trap ensuring the necessary attenuation. Pipes from above bathrooms in false ceilings should be avoided or

sound treated.

Any PVC waste water pipe above the ceiling must be wrapped with sound insulation. Pipe lag or sound barrier foams is recommended for best

performance. However minimum performance of 2” stone wool is accepted. Those products are available by Wilhams, Armacell or Rockwool.

The switches, socket outlets and bathroom air exhausts must not be installed opposite each other on the same wall.

IMPACT NOISES

In all bathrooms and in the case of hard floor coverings (marble or tiling), provide a soundproofed floating topping.

Provide a floor covering producing good insulation against impact noises (fitted carpet with foam underfelt).

For the floating toppings, ensure that the work is done correctly and in particular that the screws fastening the sanitary appliances do not cross them.

U Hotels & Resorts EU Technical Standards Manual

Page 292 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

NOISES FROM COLLECTIVE EQUIPMENT

The noise level generated in guestrooms by such equipment (elevators, exhaust fans, etc.) should not exceed 30 dB (LnAT).

Layout Precautions

The first precaution is a correct layout of the public premises and rooms versus the collective equipment.

Avoid a room being adjacent to an elevator shaft.

Do not superpose a room and:

o kitchen

o elevator machinery

o any technical rooms (exhaust fan or air coolers, for example).

Elevators

In the event of one side of the shaft being in contact with the rooms the wall must be lined with an air void between the two sides on all the contact faces.

The machinery will be placed above the shafts and not in contact with premises to which the public is admitted. The machines will be installed with anti-

vibration pads.

Technical Rooms

The mechanical equipment rooms shall be located far away from sensitive room

Use non sensitive buffer zones between and size equipment rooms to have sufficient space for operation, inspection and maintenance of all

equipment.

Fans, chillers and the like should not be located close to walls where sound can build up in the narrow space

U Hotels & Resorts EU Technical Standards Manual

Page 293 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Provide:

Anti-vibration sleeves on all the couplings, piping, rotating machines

Flexible sleeves on all the fan/duct couplings

Masonry stand laid on anti-vibration springs for all rotating machines including the boilers

Fairing on the burners and the emergency generators

Avoid rotation speeds above 1450 rpm for the pumps and burners

Wall balanced washing/drying machines, with automatic compensation and anti-vibration bases.

Sound attenuators on the outlet of the smoke ducts so as to obtain 42 dB(LnAT) on the façade nearest the outlet

Sound attenuators on all the exhaust ventilators to obtain 42 dB (LnAT) on the façade closest to the outlet

Sound attenuators on the outlets and return of the air-handling units

All the pipes and ducts held by anti-vibration supports, for complete insulation with respect to the structure.

U Hotels & Resorts EU Technical Standards Manual

Page 294 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Special case of the generator

As this is particularly noisy, special precautions must be taken:

Construction:

Floor:

As a general rule, see that the generator room is on a backfill.

Ceiling:

Provide a solid slab weight higher than 500 kg/sqm, doubled with a dropped ceiling in rigid and fixed sheets placed at least 10 cm below the

underside of the slab.

Wall in Elevation:

Provide two solid masonry walls (identical material separated by an air void of 3 cm minimum of different thicknesses whose total weight should be

greater than 450 kg/sqm). The walls in elevation will not be integrated with the slab. Example: two concrete walls respectively 15 cm and 10 cm

thick

Doors:

Double soundproof doors with a lobby in-between.

Generator Equipment:

Generator placed on min. 25 cm thick slab with anti-vibration springs in-between

Sound attenuators on the ventilation outlets in the room

Sound attenuators on the gas exhaust.

U Hotels & Resorts EU Technical Standards Manual

Page 295 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Piping

Water speed: the water speed in the risers will be limited to 1.2 m/s and 1.5 m/s in the main basement or crawl space distributions.

Supply pressure: maximum pressure 3 bars.

Pipe attachment: all the clamps or yokes attaching the pipes should be provided with rings or resilient devices.

Slab or wall crossings: the pipes should be enclosed with an insulating sheath projecting 10 cm on either side.

Vertical Shafts

Pipes attachment: all the attaching clamps will be provided with rings in a resilient material.

Slab or wall crossings: the pipes should be enclosed with an insulating sheath protruding 10 cm on either side.

Ducts

Duct air speed will be limited (see Chapter T 11Ventilation – Air Conditioning). Outlets and inlets will be selected in order to avoid any noise.

All pipe works penetrating the building wall or floors shall be installed in steel pipe sleeves with rock wool placing between the pipe and the sleeve.

This is to minimize transmission of hydraulic vibration from the pipe to the walls.

See detail below;

U Hotels & Resorts EU Technical Standards Manual

Page 296 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

NOISE FROM INDIVIDUAL EQUIPMENT

The noise level generated by such equipment in a guest room (living area) should not exceed 30 dB (LnAT).

WC:

o the flushing mechanism should be silent.

o the outlet should be such that the connection to the shaft does not take place in the rooms located underneath.

Showers: the shower tub is separated from the adjacent walls.

Piping:

o the water speed should be less than 1.2 m/s.

o the sizing should be sufficient and at least the following:

Appliance Minimum supply Minimum drainage

Flow (I/s) Section (mm) Flow (I/s) Section (mm)

Basin 0.10 15 0.75 30

Shower 0.25 20 0.50 40

WC 0.10 15 1.50 80

Should be provided with fastening devices equipped with resilient rings.

Where crossing slabs or walls, the piping is enclosed with an insulating sheath.

Tap fittings: these should be of excellent quality and have an acoustic rating offering a guarantee of low sound level (35 dB (LnAT) in room).

Switches: switches operate silently.

Fan coil unit:

o the FCUs are three-speed + stop type.

o speed 1 should not create a sound level in the room above 30 dB (LnAT) speed 2, a sound level above 32 dB (LnAT) and the maximum

speed a sound level above 35 dB(LnAT).

U Hotels & Resorts EU Technical Standards Manual

Page 297 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

OUTSIDE EQUIPMENT NOISES

Particular attention will be given to exterior outlets, especially for ducts coming from noisy spaces such as technical rooms.

Their position and size will be studied in order to avoid any sound nuisance for the hotel surroundings.

The position of AC water cooling towers and air compressors will be studied in order to cause minimum nuisance.

U Hotels & Resorts EU Technical Standards Manual

Page 298 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SAMPLE DETAILS FOR NOISE AND VIBRATION REDUCTION

All ducts penetrating the building wall or floors shall be installed in duct sleeves with Rock wool placing between the duct and the sleeve. This is to

minimize transmission of vibration from the duct to the walls. See detail below

U Hotels & Resorts EU Technical Standards Manual

Page 299 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SIGNAGE

OUTDOOR SIGNAGE

General

Hotel Name

Pre – Opening / Construction Boards

Traffic Signage

Car Park Signage

Access Signage

Identification Plate

Technical Specifications

INDOOR SIGNAGE

General

Directional Signage

Information Signage

Commercial Signage

Banqueting Signage

Floors Numbering

Guest Rooms Numbering

U Hotels & Resorts EU Technical Standards Manual

Page 300 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

OUTDOOR SIGNAGE

GENERAL

Refers to outdoors signs, (luminous or illuminated), including access signs, canopy signs or roof signs etc.

Also refers to outdoor directional signage, including street signs for vehicles or pedestrians.

HOTEL NAME

The total specific name, as defined in the Hotel Brief, with a dedicated name followed by the geographical location, will be drawn according to

standard graphics (example “U Chiang Mai”, “U Zenmaya Phuket” or “U Sukhumvit Bangkok”).

PRE – OPENING/CONSTRUCTION BOARDS

During site construction pre-opening boards, illuminated at night, will be installed at strategic positions to be visible to road and pedestrian traffic.

TRAFFIC SIGNAGE

Road signs installed on the main traffic streets will clearly lead to the hotel where possible

CAR PARK SIGNAGE

Any directional signage will be as per local road signage.

ACCESS SIGNAGE

A sign indicating the hotel name will be installed at the property entrance. It will be illuminated in all cases.

Different signage regulations may apply depending on the location of the property. Please contact your local authority for information and guidance.

In some countries, such as Thailand and due to the signboard tax rate, there should be local script on top (left or right corner) of signage above any

graphic elements. The designer should refer to the local authority for regulations.

Size and location will be defined in order to obtain a good perception before entering the property.

IDENTIFICATION PLATE

The identification plate is in bronze or stone and installed near the main entrance door. It must indicate the hotel and city name.

U Hotels & Resorts EU Technical Standards Manual

Page 301 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

BUILDING SIGNAGE

A U logo installed on top of the building façade where it is easily noticed. The size shall be large enough to be viewed from a distance.

It will consist solely of the logo. No location name or other indicator is required.

TECHNICAL SPECIFICATIONS

Lighting

Signs are based on illuminated individual letters which can be illuminated:

either by individual lights integrated in each caisson letter

either by a back projection giving an illuminated background to each letter

or by direct lighting from projectors. In the latter case, the projectors must be positioned to avoid any nuisance to rooms or the hotel access and

environment.

They must be accessible and dismountable with a transformer for each letter.

U Hotels & Resorts EU Technical Standards Manual

Page 302 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Letters

The letters’ minimum height should be referred from size chart and letters and will be wide enough to be legible from a desirable distance

Typeface is “ Copperplate ” ( light or regular)

Letter colours will be chosen according to the background and preferably high contrast in order to maintain good visibility.

Materials

Letters will be made of steel with matte finish, anodised aluminium or aluminium with baked enamel lacquer.

Miscellaneous

In all cases, access will be provided for maintenance with hooks on top of the mural support.

Electrical outlets will be provided for an eventual gondola. The anchoring of signs and the signs themselves will be designed to resist exterior

elements.

U Hotels & Resorts EU Technical Standards Manual

Page 303 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ACCESS SIGNAGE DIMENSION GUIDELINE

Use only the approved logos from the Corporate Marketing Office

Clear space around logo according to “x” height as shown on top right

Clear space is the minimum space maintained around the logo. It also defines the minimum distance that the logo is placed from the edges.

U Hotels & Resorts EU Technical Standards Manual

Page 304 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

OUTDOOR SIGNAGE

U Hotels & Resorts EU Technical Standards Manual

Page 305 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

INDOOR SIGNAGE

GENERAL

Signage should be designed so as to be clearly perceived both by guests entering the hotel and ones already in residence coming down from the above

floors. Signage must allow the guest to be immediately aware of the direction of the various facilities of the hotel. Signage must inform guests about

current activities and promote points of sale. Also required for service areas and fire safety. Positioned so as to not create potentially dangerous obstacles.

Interior signage should be designed and implemented on a property to property basis which should be influenced by the interior design of the property in

terms of size, colour and placement with the exception of fire and safety signage which must be in accordance with specific local or international

regulations. The typeface and font used for related signage must be in accordance with the brand identity manual.

DIRECTIONAL SIGNAGE

Rooms Accessible by Guests

These are directional signals as well as room identification, such as numbers for bedrooms and floors, washrooms, offices, service etc. These signs

should be easily legible and especially designed from the standpoint of permanent lighting. They should be in full harmony with the decor and

interior architecture.

Typeface is Copperplate (light, regular) or Goudy Old Style (regular, bold)

Guest Elevators

Signage includes:

Floor numbers facing elevator doors or on the door frames

Wall-mounted directory listing the public areas of each level near the call button box in the cabins

Non-smoking floors indicated next to floor buttons in the elevator cars

U Hotels & Resorts EU Technical Standards Manual

Page 306 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Indoor Car Park

Signage includes:

Proximity signs indicating the direction or location of car parks

Entry and exit signs

Access sign towards the elevators lobby for access to the hotel lobby in the case of an underground car park.

Floor markings: yellow lines, arrows, parking bays, parking bay numbers and car park level.

Back of the House

Signage includes:

Administrative offices: designation of each office and directional signage

Technical rooms: designation of each room

Service areas: designation of each room

Service lifts: floor number in front of lift doors

This signage will be made from materials of a lesser quality as ones in public areas, but always maintaining a coherence of design and format graphics.

Fire Safety

Signage includes:

Floor plans on guest elevators landings

Notice board and plan on back of guest room doors

Logos on fire stairs doors

Floor numbers on each landing at the fire exit, facing the door

Arrows indicating the direction (up or down to find the exit in the fire stairwell)

Location of fire hoses and fire extinguishers

U Hotels & Resorts EU Technical Standards Manual

Page 307 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Miscellaneous

These also must be provided:

Notice board for guestroom rates and hotel liability, (to be fixed with discretion in the guest room entry cupboard) (see also local regulations).

Signage for smoking and non-smoking zones

Disabled signage (toilets, car parks)

Any extra signage required by local regulations

INFORMATION SIGNAGE

Information Boards (changeable signs)

Refers to:

Temporary information which lists the hotel’s daily events, meetings etc

Permanent information such as posters for bars and restaurants,

These different information boards are constituted by wall-mounted boards or panels with electronic displays.

Their usual locations are the lobby, ballroom access and elevator landings.

They will be integrated in the Interior Design Project and illuminated by direct lighting.

U Hotels & Resorts EU Technical Standards Manual

Page 308 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

COMMERCIAL SIGNAGE

Restaurants and Bars

Signs indicate the name at the entrance of points of sale to attract guests.

Graphics will be studied following names defined in the Hotel Brief. They will be drawn by the Interior Designer or the Graphics Consultant.

Menus will have the same typeface as these signs.

BANQUETING SIGNAGE

Each meeting room name will be indicated on a programmable electronic display, (part of 2.3 above), to temporarily indicate the function name

in the room and the current activities.

FLOOR NUMBERING

A number corresponding to each floor, as indicated in the elevators and key tags:

o 2ND basement: B2

o 1st basement : B1

o ground floor : G

o 1st floor : 1

o 2nd floor : 2

Number 13 is deleted for floor levels.

The first number (or the first two in the case of more than 10 floors) of each number therefore indicates the floor.

U Hotels & Resorts EU Technical Standards Manual

Page 309 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GUEST ROOM NUMBERING

The two (or three) last figures indicate the number of the room on the floor.

Operating

A vertical alignment of room numbers should be respected if possible.

On each floor, the room with the smallest number is the furthest away from the lift landing, turning left.

For this to have any meaning where there is an even side and an odd side, the rooms opposite each other have consecutive numbers. (i.e. =

some numbers can be omitted, in order to follow this rule).

Room number 13 will be excluded. Other auspicious numbers depending on location and owner’s preferences will need to be considered.

The top of room number sign should be at 1600mm from floor level.

Position room number sign on the wall adjacent to the door frame, not on the door panel.

Design

Lettering and background should be of high contrast. Black on white or white on black provide maximum contrast.

When using colours, tones are important. Light colour letters on a dark background is advisable.

A sign must be visible in daylight and at night. Efficient lighting is required for guests to see the sign clearly.

When a sign is illuminated, the light source must be shielded from the viewer to prevent glare.

The surface of the sign should have a matt finish to reduce reflection and glare.

U Hotels & Resorts EU Technical Standards Manual

Page 310 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

EXAMPLE OF GUESTROOM NUMBER PLATE

INDOOR SIGNAGE

U Hotels & Resorts EU Technical Standards Manual

Page 311 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LEGIBILITY CHART

U Hotels & Resorts EU Technical Standards Manual

Page 312 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

EXAMPLE OF INDOOR SIGNAGE LEVEL

U Hotels & Resorts EU Technical Standards Manual

Page 313 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 314 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

INDOOR SIGNAGE

EXAMPLE OF ROOM NUMBERING

U Hotels & Resorts EU Technical Standards Manual

Page 315 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

EXAMPLE OF SIGNAGE LAYOUT

U Hotels & Resorts EU Technical Standards Manual

Page 316 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

EXAMPLE OF SIGNAGE DRAWING

U Hotels & Resorts EU Technical Standards Manual

Page 317 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

EXAMPLE OF SIGNAGE DRAWING

U Hotels & Resorts EU Technical Standards Manual

Page 318 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

EXAMPLE OF SIGNAGE DRAWING

SIGNAGE AT GUESTROOM DOOR

U Hotels & Resorts EU Technical Standards Manual

Page 319 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

EXAMPLE OF SIGNAGE DRAWING

SIGNAGE AT GUEST ELEVATOR

U Hotels & Resorts EU Technical Standards Manual

Page 320 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

THE DISABLED

Access

Public Areas

Signage

Elevators

U Hotels & Resorts EU Technical Standards Manual

Page 321 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

An approved international set of rules and regulations will apply if there are no local regulations. Local regulations will supersede the below.

ACCESS

Main Entrance

If the entrance is higher than the sidewalk, a ramp will be provided in order to avoid any steps. Slope must be according to the local regulations.

U Hotels & Resorts EU Technical Standards Manual

Page 322 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

PUBLIC AREAS

These must all be accessible and usable by individuals with disabilities, as much as possible without assistance.

Steps will be avoided and if there are any, provide a ramp with a maximum slope of 4%. Slightly higher slopes are possible for shorter runs in

case of absolute necessity (see attached sketches). The height of any riser on the routes of the disabled will not exceed 4 cm (bevelled) or 2 cm

(straight). The maximum cross-slope is 2 %.

The ramps have an attached handrail when more than 40 cm high and landings. Landings will have a minimum size of 1.20 × 1.40 m.

The main access routes have a minimum width of 1.40 meters and secondary ways of 0.80 m. Doors shall leave a clear passage of at least 90

cm, or 80 cm for doors leading to small rooms (such as toilets, bathrooms and elevators).

All the items to be handled, whether switches, telephones, lift call buttons, automatic vending machines, ice cube dispensers, counters, mirrors,

handrails and grab bars will be placed at heights that can be used by the disabled. (Maximum: 130 cm, minimum: 40 cm for the accessible

parts).

Public toilets will have, at each accessible level, a stall accessible to men and one for women, with adequate clear turning space, equipment and

amenities.

At least one elevator should be fitted for handicap customers which should be marked on the ground floor

U Hotels & Resorts EU Technical Standards Manual

Page 323 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 324 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SIGNAGE

Signage should be able to be read by the disabled and the children.

Besides areas where information is necessary (car parks, public toilets, lifts) no specific signage will be provided.

Pathways and premises accessible to the disabled must be indicated with the international symbol

U Hotels & Resorts EU Technical Standards Manual

Page 325 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ELEVATORS

Elevator call buttons can include Braille numbers and a sound level indicator.

Elevator cabin

Minimum size: 100×130 cm

Minimum weight: 630 kg - 8 people

Necessary for sliding doors: minimum passage width: 80 cm.

U Hotels & Resorts EU Technical Standards Manual

Page 326 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

WATERPROOFING

General Notes

Roof Terrace

Car Park Terrace

Traditional Forms of Roof

Glass Roofs

Swimming Pool – water tank

Floors

U Hotels & Resorts EU Technical Standards Manual

Page 327 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GENERAL NOTES

Particular attention must be paid to waterproofing which must carry a 5-10 year guarantee depend on item and location.

Various processes can be employed provided that these always comply with regulations and the licensing conditions for products used.

Terraces which are visible from public rooms will be laid out in such a way as to produce decorative effects, examples of this being geometric

designs, use of several colours or landscaping.

U Hotels & Resorts EU Technical Standards Manual

Page 328 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ROOF TERRACE

By way of example, the following forms of waterproofing can be used for straight sections:

o poured asphalt

o multi-layer systems: reinforced bitumen and bitumen-coated felt

o Elastomeric membrane.

The waterproofing system will be established with a slope (minimum 2%) and will incorporate thermal insulation as well as the required up

stand and flashing.

Protection is provided by a layer of gravel (minimum 4 cm) or the waterproofing system will have its own protection.

For areas accessible to the public or service areas around technical facilities, protection will be provided by concrete flagstones on supports or

on a sand + Kraft paper separating layer.

Any parapet up stand is to be protected by a ledge; any expansion joint will be protected by metal capping.

Special Points

These points are for those which display the most risk and have to be given particular attention (chimney outlets, waste vents, and rainwater

inlets). Up stands must be protected.

Removal of Rain Water

Different systems can be considered: sealed gratings, overflows etc. Any rainwater inlet must not involve a catchment area of more than 700 m²

and there must be at least two inlets per catchment area.

U Hotels & Resorts EU Technical Standards Manual

Page 329 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CAR PARK TERRACE

If there is a terrace accessible to motor traffic, the multi-layer-waterproofing complex must be protected:

by a hot-applied bituminous coating (minimum 4 cm) for heavy-duty parking spaces (up to 13 tons per axle)

by self-locking flagstones placed on a bed of sand for light-duty parking spaces (less than 2 tons per axle).

U Hotels & Resorts EU Technical Standards Manual

Page 330 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

TRADITIONAL ROOFING (tiles, slates, shingles, zinc, copper etc.)

Care must be taken to see that these are properly placed with a slope which must lie between certain limits which are compatible with the material and

its method of attachment.

Examples:

Slates : minimum incline 30% - maximum incline vertical

Roman tiles : minimum incline 25% - maximum incline 40%

Shingles : minimum incline 20%

Wooden shingles : minimum incline 33%

Galvanized steel pans : prohibit any contact with copper or lead,

Tin and untreated steel

Painted aluminium pans : only use sheets which have been given a factory-applied heat bonded enamel coat

It is recommended that an incline greater than 5 mm/m is used for troughs and gutters.

U Hotels & Resorts EU Technical Standards Manual

Page 331 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GLASS – ROOFS

Glass

This is the material to be preferably used. It is recommended that laminated glass be used.

Plastic Materials

Failing the use of glass, the project may use polycarbonate in preference to any other material in order to achieve good UV resistance and to

prevent yellowing and cracking with time.

U Hotels & Resorts EU Technical Standards Manual

Page 332 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SWIMMING POOL – WATER TANK

Waterproofing is achieved using various processes:

o incorporated into the reinforced concrete mass

o by applying a smoothing coat then a sealing coating of strong cement mortar with incorporation of a water-proofing agent applied in

successive layers to give a total thickness of 30 mm,

o by thick cladding of reinforced resin.

For swimming pools, a finish of large-size tiles is essential.

In seismic areas, a technical solution will be selected which will allow seismic movements and cracks which might result from them in the

concrete shells to be absorbed.

Where possible, one should avoid having swimming pools or sheets of water which are placed above inhabited rooms.

If this cannot be avoided, particular attention must be paid to waterproofing.

U Hotels & Resorts EU Technical Standards Manual

Page 333 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FLOORS

Waterproofing is also required for certain interior floors:

o kitchens and annexes

o laundries

o employee locker rooms and toilets

and in certain special cases:

o bathrooms (floor drains)

o balconies above inhabited rooms.

U Hotels & Resorts EU Technical Standards Manual

Page 334 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

EXTERIOR JOINERY (WOOD AND METAL WORK AND GLAZING)

Water Proofing – distortion

Wood Joinery

Metalwork

Mixed Units

Glasswork – glazing

Railings

Maintenance

U Hotels & Resorts EU Technical Standards Manual

Page 335 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

WATERPROOFING - DISTORTION

The characteristics of sound external joinery are:

o water tightness

o air tightness

o ability to withstand high wind pressures without excessive distortion

o fire resistance, in relation to conditions of use and current regulations concerning sound insulation

All joinery, metalwork and glazing installed must have a test certificate guaranteeing good results in the areas mentioned above.

Greater or lesser requirements as to such results may be needed, depending upon exposure of facades and the level of winds.

In addition, facades will be designed in such a way as to absorb any foreseeable expansion without making noise.

WOOD JOINERY

The material used for wood joinery will be selected in relation to the climate (tropical or temperate).

Wood joinery must be of additional thickness in maritime zones.

It must be treated with insecticide and fungicide products either by injection under pressure or by immersion. If a product is impregnated, it

must not wash off.

U Hotels & Resorts EU Technical Standards Manual

Page 336 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

METALWORK

Metalwork must only be installed when the shell has been completed, in order to avoid any risk of deterioration or temporary removal and the premises

and apertures must have been cleaned. To a large extent, the quality of waterproofing and good function depends upon the quality of finish of the shell

into which they are installed.

There must be no gaps in weld seams. Traces of welding must be removed by grinding and polishing so that they do not detract either from the

appearance or the waterproofing quality of the work.

It must be possible to take out door leaves and mechanisms without having to remove the entire frame.

All along the frames there must be devices for collection and removal of rainwater drips and water created by condensation. Rooms in which

high condensation may occur must have a system for taking water to the outside.

Slide tracks for sliding door panels must be located at the bottom. It must not be possible for sliding doors to jump from the frames.

Contact between different metals must be avoided, particularly in moist locations.

Where access can be gained to ground floor rooms from outside, external doors and windows will be provided with locks which will use the

same key as that for the entrance door to the room.

Aluminium Frames

They must be anodized (20 minimum) or given a heat-bonded lacquer coat at the factory.

Rollers, made preferably of Teflon, must guarantee that sliding units operate properly.

There must be a high quality closure system with security device.

Steel Frames

They must be given anti-corrosion treatment which is of superior quality and finish.

In no circumstances must they be used at seaside locations (corrosive atmosphere).

When using stainless steel, use 304L or 316 L in a seaside location.

Hardware

Hardware and screws must be completely stainless and suitable for the frames used.

U Hotels & Resorts EU Technical Standards Manual

Page 337 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

MIXED UNITS

These units have the advantage of combining the durability of a metal external section and the aesthetic of a wooden internal face.

They can be used where it is desired to avoid any thermal bridge in the façade.

GLASSWORK AND GLAZING

Coloured Glass

Coloured or reflective glass must be installed to reduce heat (particularly for air-conditioned rooms).

All tinted glass must be tempered.

Compound Glass

For sky domes it is essential that laminated glass be used (which is both tinted and reflective) in order to prevent unreasonable consumption of energy

for air conditioning.

Tempered Glass

Glazing for doors and external glazed partitions on the ground floor must be tempered glass. Such glass is to be marked by adding a decorative

emblem at eye level.

Mirrors

Silvering on mirrors will have a minimum thickness of 5 microns. The glass will be slightly separated from its supports in order to allow air

circulation. Mirrors will be secured by mechanical means (wall fixings).

U Hotels & Resorts EU Technical Standards Manual

Page 338 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

RAILINGS

These must be designed with especially durable materials so as to allow for intensive use without risk and long lasting quality over time.

The handrail and framework of the railings must be of a type requiring minimum maintenance (heat-bounded lacquered aluminium, stainless

steel, impregnated wood etc.).

MAINTENANCE

Suitable fittings will be provided to allow for cleaning and maintenance of glazing and frames: a cradle will be installed if it is not possible to

carry out the work easily.

In particular, bedroom window frames must be of an opening type or must have an opening section to allow for easy cleaning.

U Hotels & Resorts EU Technical Standards Manual

Page 339 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

INTERIOR JOINERY

Bedroom Doors

Doors of Common Areas

Technical Facilities Access Doors

Panelling, Skirting and Cornices

Sound Insulation Partitions

Bar Counter

Rear of Bar Furnishings

Reception Desks

U Hotels & Resorts EU Technical Standards Manual

Page 340 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

BEDROOM DOORS

Entrance Doors

These are solid-core with minimum dimensions of 830 x 2,040 mm

They are equipped with a spy hole, concealed door closer and door stop with hold-open position.

Protective plates are placed around handles and locks. Metal doorframes should be avoided for acoustic reasons.

Particular attention must be paid to sound insulation. Doors will be provided with a peripheral sound reduction strip of neoprene. Doors and

frames will be double rebated.

They must be flame-resistant for 90 minutes.

The door must also fit as flush as possible to the finished floor level. Under no circumstance must the gap be used for air renewal for the

bedroom.

Internal Doors

These are the WC and bathroom doors.

They will be equipped with doorstops and sound buffers.

Protection plates will be placed around locks and handles.

They will have devices allowing them to be locked from the inside with the possibility of release from the outside.

Depending on the MEP design it may require louvers for air circulation.

Closet Doors

Doors will preferably be of the sliding type. The door casing on the front of the cupboard with sliding doors must be independent of the

adjacent partitions, by insertion of expandable joints.

The width of the sliding panels must be no less than 2/5 of the height.

They will be suspended on nylon rollers and equipped with sound buffers.

They can be fitted with an external full-length mirror.

For details of drawers, clothing rods and cupboard shelves, see section C3 - Rooms.

U Hotels & Resorts EU Technical Standards Manual

Page 341 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

DOORS OF COMMON AREAS

These are connecting doors between public areas, doors between a service area and a public area, interior doors within service areas and doors

of technical facilities.

They will have a fire rating in accordance with regulations.

Door closers, doorstops and soundproofing joints will be used for all floors.

Service doors will be provided with a glass panel, particularly between the kitchen area and the restaurant rooms.

Where doors separating service rooms (kitchens, floor service rooms, technical facilities rooms) from public rooms (restaurants, passageways,

bars), are concerned, these will be given sound insulation by means of an all-round soundproofing strip. They will open from public areas by

pulling, in order to limit damage to the front panel by trolleys and carts (except for emergency exits). Special care will be given to their front

finish.

They must have a minimum thickness of 40 mm and if of single leaf type must have minimum dimensions of 900 x 2,040 mm.

Doors giving onto service rooms are protected by separate protection plates and plinths and kick plates where carts are used or hands are not

free (e.g. = kitchens).

Emergency exits must be capable of being opened when pushed (panic bars).

U Hotels & Resorts EU Technical Standards Manual

Page 342 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

TECHNICAL FACILITIES ACCESS DOORS

Conference Modules Cabinet Doors

These will have clear dimensions of 200 x 50 cm. They comprise of:

a sub-frame of hardwood fixed to the wall

a hardwood frame

a solid door leaf 40 mm thick of exotic wood swinging on invisible hinge plates

The door leaf has a built-up facing in harmony with the decoration of the walls.

The plinth of the door leaf is hinged horizontally onto the door leaf so that it can be lifted and must form an aperture which allows for electric wires

and cables connected in the cabinet to pass through.

Opening Panels of Control Panels

They comprise of:

a frame of hardwood fixed to the wall

a solid-core panel 20 mm thick of exotic wood swinging on invisible hinge plates

The panel has a built-up facing in harmony with the decoration of the walls; closed by bolt and has a knob on the front of the facing.

Doors of Technical Shafts

They comprise of:

a sub-frame of hardwood fixed to the wall, having in its lower portion a horizontal strip for attachment of the room skirting

a hardwood frame

a solid-core door leaf 40 mm thick of exotic wood swinging on invisible hinges

U Hotels & Resorts EU Technical Standards Manual

Page 343 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

The door leaf has a built-up facing in harmony with the decoration of the walls.

Doors are locked and tied to the hotel key-chart.

PANELLING SKIRTING, MOLDINGS AND CORNICES

Panelling is fashioned from flat lathe panels or similar with a low flammability rating (M1), with wood cladding protected at the bottom by

skirting.

Half height panels have at the top moulding, the height of which will be specified so as to give protection to the dado and wall from scraping by

chair backs.

Full height panels have a cornice at the top which links up with the false ceiling.

Wall mouldings, skirting, borders and cornices are of solid wood.

Panelling is positioned so as to allow free circulation of a strip of air between the wall and the back of the elements which form the panelling.

U Hotels & Resorts EU Technical Standards Manual

Page 344 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SOUND INSULATION PARTITIONS

Partition walls must have a minimum in-situ installed acoustic attenuation factor of 45 dB (DnTA or NR), i.e. of at least STC 48 to 50.

Every measure must be taken to give sound insulation in the top portion from the concrete beam as far down as the suspender rail including the

metal supporting beam, so as to eliminate any sound bridge.

The panels will have metal protection against trolleys and must be 100 mm minimum thickness.

There must not be any floor rail.

U Hotels & Resorts EU Technical Standards Manual

Page 345 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

BAR COUNTER

This is made up from solid-core waterproof panels of low flammability rating (M1), for all frontal, return and internal structure elements.

The panels must incorporate any apertures, cut-outs and recesses needed for installation of bar equipment:

o hot and cold water supply

o sink and draining board

o ice cube container

o connections for supply of electricity, computer system and telephone

o incorporation of refrigeration equipment

o Incorporation of and power supply for a glass washing unit.

The upper horizontal panel and the structure are designed to carry a tablet of high grade material and any other decorative facings specified by

the interior designer.

On the inside a satin-finish stainless steel work surface placed on a waterproof panel must incorporate all necessary apertures and cut-outs.

The link between the work surface and the lower face of the decorative counter is likewise made of stainless steel.

There must be a flashing around the stainless steel panel in order to prevent water from running off.

The equipment beneath the work surface includes:

o Sliding lockable drawer units running on telescopic runners

o Storage with fronts made of solid-core panels (M1) closed by invisible spring hinges, with mortise locks and internal panels of

laminated board on aluminium racks.

U Hotels & Resorts EU Technical Standards Manual

Page 346 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

REAR OF BAR FURNISHINGS

In general, these furnishings comprises of:

o a high unit with shelving for bottles, frames for glasses and a niche to hold a coffee machine placed on the low unit top.

o a low unit with sets of sliding drawers, refrigerated storage, sage storage and possibly storage for bar sound equipment.

Made of solid waterproof panels, rated as low flammability (M1).

The panels will incorporate any apertures and cut-outs necessary for installation of the coffee machine.

The niche which is intended to hold the coffee machine has a backing of insulating material and a stainless covering sheet in order to facilitate

cleaning.

The top portion of the niche also includes a removable grille for steam extraction by flexible tubular sleeve which is connected to the general

extraction system.

Doors of refrigerated units have all necessary insulation layers.

Around the doors of refrigerated units there are recessed rubber joints with counter-rebates.

All doors are kept closed by handles with integral locks.

RECEPTION DESKS

Facilities beneath the work surface include:

sets of sliding drawers on telescopic runners with locks

recesses for baskets, with integral opening front panels, swung from invisible hinges and closed by magnetic catches

low tops on telescopic runners for printers

a removable false panel to allow for insertion of cables and inspection for maintenance.

U Hotels & Resorts EU Technical Standards Manual

Page 347 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LOCKS

General

Electronic Locks

Conventional Locks

Key Chart

U Hotels & Resorts EU Technical Standards Manual

Page 348 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GENERAL

All guestrooms must be fitted with electronic locks operated by RFID key cards.

The supplier’s choices for both conventional and electronic locks should be submitted to U Hotels and Resorts Management for approval before

any order is placed.

The finishes shall be adapted for use and chosen in agreement with the interior designer.

Only locks of superior quality will be selected. They will be tropicalized or guaranteed for seaside use where applicable.

No padlocks are acceptable in any situation.

U Hotels & Resorts EU Technical Standards Manual

Page 349 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ELECTRONIC LOCKS

Electronic locks should generally be fitted as guestroom locks only.

In specific cases, and as per the Hotel Brief, they can also be used for public (e.g. Conference rooms) and service (e.g. Stores) areas.

Operation

The system could comprise of the following:

a central processing unit with a monitor, printer, identifier-encoder and inverter located in the computer room

identifier-encoders at reception

identifiers in the Front Office Manager’s office, at restaurants and bar cashier counters.

a portable dialogue computer for reading the information stored in locks

battery-powered electronic locks

RFID key or magnetic-strip key cards with unlimited reprogramming capacity

Key Cards

Encoding:

Cards will be encoded at reception using an encoder when customers are allocated a room.

Advance encoding with limited date/time validity:

The operator may create a guest room key card in advance (once a reservation has been made). The key card will then be usable only for the

duration of the guest’s stay.

Encoding of different cards for one guest room in the event of multi-occupancy in that room.

Instant encoding in the event of loss:

A new card can be created immediately with a different code should a guest lose their key card.

U Hotels & Resorts EU Technical Standards Manual

Page 350 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Guest Key Cards

Simple graphics, on the same side as the chip, should be used to indicate how to insert the card into the lock.

The card must be water and heat-resistant and fit easily into a pocket or wallet.

The reverse of the card may be used for advertising or for displaying the hotel logo.

Front Back

U Hotels & Resorts EU Technical Standards Manual

Page 351 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Key Cards for Employees’ Use Only

Encoder card:

Allows access to and use of the encoder on input of a password.

Emergency key card:

The emergency key card should open all door types in case of emergency (even if they are locked from the inside).

Master key card:

Able to unlock all doors (except for guestroom doors locked from the inside).

Card giving access to a floor, building or department:

As a function of the hotel’s operational organization and hierarchy, this card should authorise access by employees to specific floors,

buildings and departments within pre-programmed time limits. Access is not authorized if the door is locked from the inside.

“Initialisation” card:

Initialises the encoder and the locks on system start-up.

“Prohibit” card:

Prohibits customer access to a guestroom where necessary.

“Customer re-authorisation” card:

Restores the original conditions. This card is only used after the “prohibit” card.

“Employee prohibit” card:

Prohibits employee’s access to a bedroom at a customer’s request, or for any other reason.

“Employees re-authorisation” card:

Restores the original conditions. This card is only used after the “employee prohibit” card.

“Test” card:

Used during maintenance to carry out a series of checks on the lock.

“Cleaning” card :

Used for periodic cleaning of the card reading head.

Blanks

The system should initially be supplied with sufficient blanks to cover six months’ operation, with at least 6 passes of each kind.

The manufacturer must guarantee future supply of blanks and their price, and print to them with the text agreed by U Hotels and Resorts

Management.

U Hotels & Resorts EU Technical Standards Manual

Page 352 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Locks

A closed door is always automatically locked.

The lock should comprise of:

a door-knob, with latch function

a security counter-latch

an interior dead-bolt (one inch) locking system with indicator, which can be unlocked from the outside in case of emergency

the external control plate with the computer reader and knob

the internal plate, with knob and dead-bolt control

the mortise-type mechanical casing

Electronic Accuracy

When a card is inserted, the microcomputer reads it, compares it instantly with all the data stored, and authorizes or prohibits access.

Alternatively, it may check the time validity of the card by comparing the encoded data with the data on the clock inside the electronic unit. An

auxiliary memory is used to store the last 150 card codes used in the lock. The codes can be read or printed out easily. Each opening of the lock,

and each attempt to open the lock, is stored in the memory with an indication of user identity and date/time.

Compliance with Safety Standards

The lock should be reversible, with an anti-intruder device and a panic-opening facility on the inside.

The dead bolt should lock the latch when the door is closed, preventing any attempt to force the lock.

The customer must be able to ensure privacy be turning a control on the inside to lock the dead bolt.

To exit the room, turning the knob on the inside should activate both the latch and the dead bolt.

Battery Power Supply

The electronic lock should be supplied with power by alkaline batteries with a guaranteed lifespan of more than one year, assuming that the

door is opened ten times per day on average.

The batteries should be located on the outside to allow them to be replaced without opening the door.

U Hotels & Resorts EU Technical Standards Manual

Page 353 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Indicator Lights

Two lights on the external plate should indicate the following:

green: access authorized

red: card read error or card not valid

red and green: batteries low

Portable Dialogue Computer

The portable dialogue computer should be capable of communication with both the electronic locks and the encoder.

Programming:

Transfers the initialisation data to the locks; fulfils the same function as the initialization card.

Retrieval:

Retrieves the data (date, time and card identification) relating to the last 150 door uses from the auxiliary memory and transfers it to the encoder

for printing.

Test function:

Analyses faults. Power is supplied by rechargeable batteries (average lifespan 5 years).

Identifier-Encoder

Identifier-encoders should be capable of creating and checking cards, displaying codes and printing the information on the card.

They should be accessible only by using the attendant card, followed by a secret password.

Only the senior operator should be able to read, print or cancel all passwords.

The encoders should be supplied with electrical power, with a battery for memory back-up in the event of an electrical failure.

Central Processing Unit

The central processing unit should interface with the Property Management System.

It should also interface with the Point of Sale system for payment using key cards and charging back to a single customer invoice.

U Hotels & Resorts EU Technical Standards Manual

Page 354 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Key Cards used During Installation

During the pre-opening period of the hotel, all key cards used during installation should be returned to the hotel General Manager or

automatically invalidated, and the supplier should undertake not to keep any nor pass any on to any person without the approval of U Hotels &

Resorts.

U Hotels & Resorts EU Technical Standards Manual

Page 355 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CONVENTIONAL LOCKS

All doors other than guestroom entrance doors should be fitted with key-operated locks with a three level master key system. Exceptions are for

internal doors and communicating doors in guestrooms and emergency exits (which are equipped with special closure fastenings). U Hotels &

Resorts recommends using electronic locks for all important access doors such as stores, cashier / safe rooms, locker rooms, front office access

and other similar access doors.

All areas under concession must have a locking system independent of the hotel’s general key structure, except the master key.

The doors are not automatically locked when they are closed.

Each lock should comprise of:

o a cylinder operating a catch bolt

o a security counter latch

o a door handle (service) or knob (public areas) ( with latch function)

Optionally, the doors can be double-locked from the inside or the outside.

Keys

Each lock should be supplied with a set of 3 keys and a blank.

Each key or master key should be supplied marked with the letters and figures corresponding to the area concerned.

All master keys should only be given to the hotel General Manager or Hotel/Resident Manager. The supplier must not leave a general master

key with any other person.

Drawings

Before the order for the locks is placed the chosen supplier must provide, for approval by the operator, a complete series of drawings indicating

all doors (with suitable numbering), along with a list and detailed description of all locks.

U Hotels & Resorts EU Technical Standards Manual

Page 356 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

KEY CHART

Emergency key: able to lock, double-lock and unlock all internal and external doors even if double-locked.

Master key: able to lock and unlock all internal and external doors (except for double-locked doors).

Section master keys: able to open and close or double-lock all rooms/areas shown on the chart.

Partial master keys: able to open and close the rooms/area shown on the chart; unable to open or close double-locked doors.

Individual keys: able to open and close only the rooms/areas to which they are allocated.

Six copies of all master keys should be supplied.

U Hotels & Resorts EU Technical Standards Manual

Page 357 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CLOSURE

General Notes

Emergency Exits

Services Entrances

Loading Dock

Public Entrances

Underground Garage Entrance

U Hotels & Resorts EU Technical Standards Manual

Page 358 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GENERAL NOTES

The closure systems must prohibit or control access to the building, control admission of air and light and provide a screen against the wind,

rain and exceptionally bad weather as well as providing fire resistance in accordance with the requirements specified in section C-20 Fire

Safety.

Above all, they must protect the hotel against break-ins and must allow the hotel to be totally closed off, using the general passkey for the locks.

They are provided for exits, including:

o emergency exits

o service entrances,/entrances from the yard and from the loading dock

o public entrances

o underground garage entrance

U Hotels & Resorts EU Technical Standards Manual

Page 359 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

EMERGENCY EXITS (See section T-13 IT & Low Voltage)

This covers all doors on emergency staircases and specific emergency exits used by employees and guests in the event of fire or danger.

All doors which are used as emergency exits must have a panic bar or some other approved device on the inside.

They are also locked by magnetic valves, so as to prevent any access from outside. Locking with electro-magnets and automatic unlocking are

linked to automatic systems for fire detection with, in certain cases, internal phones and monitoring cameras.

SERVICE ENTRANCES

These are metal swing doors which can be locked using the hotel passkey and which can be opened manually from inside as the leaves can be

unlocked simply by pushing.

LOADING DOCK

It must be possible to close off the dock by means of an electrically-operated metal curtain, a hinged grille or roller grille or as an alternative, a

wheel gate.

The type of system is selected in relation to the dimensions of the aperture to be closed off.

PUBLIC ENTRANCES

Numerous systems are envisaged for the main entrances of the hotel. These may involve:

o manual swing doors

o automatic sliding doors

o automatic or manual rotating doors

U Hotels & Resorts EU Technical Standards Manual

Page 360 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Swing doors and sliding doors must be of 2-stage type, forming an air lock. In all cases it must be possible to lock them using the hotel pass

key.

The number and dimensions of such doors are specified in relation to the amount of traffic and fire regulations for building evacuation in the

event of fire.

In all cases they will be equipped with tempered glass, possibly with metal frames to give protection from luggage trolleys, etc.

If doors are entirely of glass they are to have a discreet emblem (logo) + 1.50 m from ground level so that they can be easily visually identified

to avoid accidental collisions.

UNDERGROUND GARAGE ENTRANCE (managed by hotel)

Access to the garage must incorporate a total shut-off system by means of automatic doors.

Entrances to and exits from the underground garage are controlled by a system of automatic barriers with magnetic strip ticket, coin operated or

by guest key-cards. There must be supervision 24 hours a day by security in a cabin or possibly by centralised system of remote monitoring in

the case of a low capacity garage.

The automatic barriers can also be associated with an automatic till which is linked to the hotel cashier’s office, with internal phone and

invoicing system.

U Hotels & Resorts EU Technical Standards Manual

Page 361 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FINISHES

Summary Table

General Notes

Carpets

Tiles

Wooden Floors

Plastic Floors

Paint

Stretched Fabrics

False Ceilings

Lighting Fixtures

Doors

U Hotels & Resorts EU Technical Standards Manual

Page 362 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SUMMARY TABLE

Key

Floors Ceilings Doors - WC Woven carpet (category 1,2 or 3) - VP Wash-fast vinyl paint - ME Metal

- TC Tufted carpet - GP Wash-fast glycerophtalic paint - LA Laminated

- AR Rugs - ST Employees - PA Painted

- NT Non-slip tiles - AT Acoustic tile false ceiling - WF Wood faced

- VS Vitrified stoneware - AP Aluminium or lacquered steel pans - HG Tempered glass

- SM Stone, marble - WS Wooden slats - DE According to room decoration

- WF Wood floor - SC Special ceilings - SD Special door(fire rated, heat

insulated.)

- VT Vinyl tiles - AD Automatic door (tempered glass)

- FP Floor paint Lighting

- SC Special covering - I Incandescent lighting

- FF False floors - F Fluorescent lighting

- BP Bituminous paving - C Fluo-compact lighting

- L Chandelier

- B Box/Pan

Walls - S Spot

- VP Wash-fast vinyl paint - P Lamp on stand

- GP Glycerophtalic paint - W Sealed lighting unit

- WT Wall textile & flammability category - R Strip

- VC Vinyl covering - D Decorative lighting

- GT Glazed tiles - O Optical fibre

- CE Ceramic

- GL Glass paste

- SC Special cladding

- AC Acoustic cladding

- +V Vinyl base or wooden base for painting

- +H Hardwood base

- +R Protective railing

U Hotels & Resorts EU Technical Standards Manual

Page 363 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

- +C Angle protection

ROOMS FLOORS WALLS CEILINGS LIGHTING DOORS

Lobby, foyer, entrance SM + AR or WC1 SC SC

L + S

+0

(high ceilings)

AD

Reception SM or WC1 SC SC S DE

General services VT or TC VP +V AT or AP FR LA

Business centre WC2 WT2 + H AT or ST CD + CP HG

Health club NT

(U4 P2 E3 C2) CE GP FW or CW LA or PA

Swimming pool+ restaurant

bar

NT or VS(U4 P2 E3

C2) CE or VS SC FW + S HG

Restaurant + bars WC1 or SC SC SC D HG

Public toilets/washrooms VS

(U3 P2 E3 C1) CE or GL AT or AP CS DE

Main ballroom WC1 +WF SC (AC + protection

up to 1 m) SC L + D DE

Function rooms WC1 WT2 + H ST S DE

Audio/video control room VT VP + V VP BF LA or PA

Clinic TC + VS

(U3 P3 E2 C2) VC + V AT BF + CP LA or PA

Administration offices WC3 VC + V AT BF + CP WF

Secretariat offices WC3 VC +V AT BF LA or PA

U Hotels & Resorts EU Technical Standards Manual

Page 364 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ROOMS FLOORS WALLS CEILINGS LIGHTING DOORS

Laundry VS

(U4 P3 E3 C2)

GT and VP

+C VP or AP FW

ME or

LA+ME

Linen room VT or VS (U3 P3 E2

C1) VP + V AP FB

ME or LA +

ME

Kitchen +

accessories

NT(U4 P3 E3

C2+rounded base GT and GP+C

Washable AP

with acoustic

insulation

FR recessed

LA + ME +

Special

protection

Loading platform FP GT VP FW ME

Storage VS VP VP FR ME

Cold stores VS

(U4 P3 E2 C2) GT VP

W+

protection grille SD

Trash/garbage NT

(U4 P3 E2 C2) GT VP FW ME

Employee locker and

washrooms

VS

(U3 P3 E2 C2) GT and VP VP or AP FB LA or PA

Employee cafeteria VS

(U4 P3 E2 C2) GP or VC+V AT FB LA or PA

Engineering areas FP VP VP FR SD

Workshops VT VP VP FR ME

Guestrooms WC3 or WF or SM +

AR VP or VC+H VP or ST IP +ID

Guestrooms entrance Ditto VP or VC+H ST or AT or WS S SD + WF or

DE

Guestroom bathrooms SM or VS CE or GL or SC ST or AP or WS CD LA or WF or

DE

Room corridors WC2 WT2 or VC+

H+R+C

ST or decorative

AT IS and FD WR or DE

U Hotels & Resorts EU Technical Standards Manual

Page 365 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ROOMS FLOORS WALLS CEILINGS LIGHTING DOORS

Pubic elevators SC SC SC CS or FD SD

Service elevators VT SC GP FR ME

Floor housekeeping pantry

NT or VT + brush

mat in front of door VP + V + C AP FR

LA or PA +

protection and

automatic door

closer

Service staircase FP + non-slip nosing VP VP FR LA or PA

Service corridors VT or VS (U4 P3 E2

C2) VP + R +C VP FR

ME+ signs +

protection

GENERAL NOTES

Care must be taken to see that the material is suitable for the purpose with regards to its resistance to wear, impact and chemical corrosion.

Particular attention will be paid to fire prevention regulations for the premises concerned.

A threshold must be inserted wherever the floor cladding changes.

The use of corner protection strips for any projecting angles of walls will be universally adopted in all service passageways, including certain

facilities.

U Hotels & Resorts EU Technical Standards Manual

Page 366 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CARPETS

Objectives

The technical (durability, maintenance), acoustic and aesthetic qualities of carpets constitute an important element of the brand image and comfort of

the hotel.

The intervals between replacements linked with operating economy is also a feature for consideration among the characteristics.

Technical Specifications WC1, 2 and 3

Weaving:

o Carpets will preferably be of the Wilton type or possibly Axminster (if the characteristics are as close as possible to those of Wilton

carpets).

o Synthetic carpets outside public rooms will be given anti-static treatment and will have the same characteristics as wool carpets. In

certain special exceptional cases, and only with U Hotels and Resorts Management approval, they may be used in guest rooms.

Treatment:

o if not synthetic, the backing will be treated against insects and fungi

o the treatment product must not be toxic

Colouring and design:

o the colour must go right through the carpet in a uniform manner

o a design and shade (1 to 5 by cards) will be specified by the interior designer and approved by U Hotels and Resorts Management before

an order is made.

Cleaning:

o the manufacturer is required to submit specifications (to avoid deterioration or discolouration) with their tender.

Fire resistance:

o they must be classified as “moderately flammable - difficult to ignite”.

Classification:

o The BS 7131 classification corresponding to the specifications required by U Hotels & Resorts is class 4 (heavy industrial use); T5 for

bedroom corridors, staircases and public zones and class 3 (or T4) (moderate industrial use) for bedrooms.

Laying:

o laying will be by stretching and fixing with nailed strips on a good quality felt underlay in all rooms accessible to customers i.e. public

rooms, passageways and guestrooms

U Hotels & Resorts EU Technical Standards Manual

Page 367 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

at sites which display problems of hygiene (tropical environments, seaside etc. ) laying may be by means of adhesives using a double system of

adhesion (underlay + carpet)

laying will be by adhesive in offices.

U Hotels & Resorts EU Technical Standards Manual

Page 368 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

TILES

Nature of Material:

Choice of tiles will be determined by the use required of them (see UPEC rating, as per NF/CSTB standard).

Whatever the precise nature of the material, they will always be of optimum quality.

Colours will be uniform.

Thickness tolerances will be a maximum of + 0.2 mm; dimension tolerances will be a maximum of + 0.5%.

Water absorption shall not exceed 3 to 7% of dry weight.

Care must be taken regarding resistance to atmospheric agents and to frost if outside.

Use

They will be laid in a totally flat manner, with the screed being used to correct any irregularities in the base. The plane surface will not display a

rise of more than 3 mm over a distance of 2 m taken in any direction.

Pipes and conduits may be allowed to run beneath the tiling provided that there is a covering of at least 5 mm in thickness. If pipes are required

to cross the tiling, the tiled surface must take into account any cut-offs and joints. Slopes of 1% will be provided in rooms that have floor

drains.

Ensure that inspection traps are installed.

There must be protective angles around any such traps (movable portion, fixed portion).

Joints

Tiles must always be laid with joints.

Areas of more than 60 m² with the same sealed covering must be interrupted by a joint, as well as at every 8 linear meters for any passageway.

In hot countries and those with a wide temperature range, the interruptions shall be at least every 30 m².

If the covered area is more than 12 m² a gap must be left between the last line of tiles and the vertical walls or pillars. This will be a peripheral

joint filled with laying mortar.

U Hotels & Resorts EU Technical Standards Manual

Page 369 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

WOODEN FLOORS

Nature

Parquet strips must never be made from sapwood nor treated with hardener. Moisture content of the various constituent elements must not

exceed 20%.

Construction

The floor must be designed and constructed in such a way as not to give rise to any moisture coming up to the flooring.

Temperature of the base and the rooms must be above 5˚C, with ambient air that has a maximum humidity level of 70%.

The plane surface must not have any deflection of more than 5mm over two meters’ length in any direction.

The floors must be flush with the coverings of adjacent rooms with a maximum tolerance of +2 mm and with a threshold strip being used.

Insulation from impact noise will be provided for surrounding rooms.

U Hotels & Resorts EU Technical Standards Manual

Page 370 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

PLASTIC FLOORS

Nature

The materials must be resistant to chemical agent and greases and they must have good resistance to cigarette burns.

They must be rot proof.

They must be of a homogeneous composition and coloured throughout.

They must withstand abrasion, scratches and soiling (test certificates to be provided).

As regards resistance, they must be category 33 (high commercial) or 41 (moderate industrial) according to EN 685.

The dimensions must remain stable over time.

Laying

The surface of the slab used as a base will be smoothed off with an appropriate product.

They come as tiles (for sticking down) or as breadths (stuck down or stretched) for lying with butted joints and welded with a hot air blowpipe

with or without welding bead (heat welding).

Baseboards of the same material are glued.

PAINT

Qualities

Brands will be chosen in relation to supply requirements and consequently widely distributed brands will be used.

For all exterior painting, a 10-year guarantee will be obtained. Internal paintwork must always be wash-fast.

Plaster and the various layers of paint must be compatible with each other.

Use

Unless specially authorised, all paintwork must have at least a topcoat.

The surface condition and preparation of bases will be subject to the grades specified.

U Hotels & Resorts EU Technical Standards Manual

Page 371 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

STRETCH FABRICS

Quality

Care will be taken regarding dimensional stability of fabrics in variations of ambient temperature.

Very thick fabrics will be chosen if the colours selected are light in order to avoid the backing becoming apparent through transparency.

Use

All cracks in walls and ends of any pipes will be carefully filled.

FALSE CEILINGS

False ceilings in public rooms, corridors and bedroom entrances must be designed to allow easy access to any technical equipment located

above them.

Thus they will either be designed in the form of removable panels or provided with access flaps positioned in an appropriate manner and of

aesthetic appearance.

The design will be such that they can withstand frequent handling and they must be made of material which can be washable to remove any

finger marks.

Spaces above recessed spotlights will be the subject of adequate ventilation in order to prevent any black marks around the spotlight corolla.

The material must also be capable of withstanding (without deterioration) any occasional leakage from plumbing or possible condensation

arising out of inadequate insulation of chilled water piping.

U Hotels & Resorts EU Technical Standards Manual

Page 372 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LIGHTING FIXTURES

Refer to T12 Electricity, Section : Distribution

DOORS

Refer to T4 Interior Joinery

U Hotels & Resorts EU Technical Standards Manual

Page 373 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SANITARY PLUMBING

Cold Water

Hot Water

Watering System

Waste Water – sewage

Rainwater

Gas

Sanitary Ware

Water Treatment

U Hotels & Resorts EU Technical Standards Manual

Page 374 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

COLD WATER

Water Quality

Analysis:

Bacteriological and chemical analysis of the water supply must be made.

Standards:

Local sanitary standards must be observed if they are more demanding than the recommendations of WHO (World Health Organization – cf.

file “International standards for drinking water”).

WHO Recommendations:

In all cases these WHO recommendations must be considered the minimum quality. If they are not achieved, extra water treatment must be

provided by chlorination, filtration or some other process.

U Hotels & Resorts EU Technical Standards Manual

Page 375 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

General Connection and Dimensions of Network Pipes

The general connection serving the hotel with drinking water must be capable of providing an hourly through-put on average of = daily

consumption/10 and a peak through-put which is double that figure.

Pressure:

o reserve supply at 1 bar ¹ after meters and filters

o manometer to be installed to monitor pressure

o dispatch to control panel.

The simultaneity coefficient used in calculations for designing dimensions of network pipes must never be below 0.25.

Water Reserves

Cold water requirements

To be calculated according to the hotel. As an initial approximation, daily requirements per occupied bedroom are:

(cf. 8 below for qualities)

Drinking water:

Bedrooms 0.35 m³

Sanitary requirements (public and service) 0.10 m³

Kitchens 0.15 m³

Swimming pool and others 0.15 m³

_____________

0.75 m³ /day

softened water:

For air conditioning 0.45 m³ (hot climates, water-cooling towers)

Laundry 0.20 m³ (if there is one)

_____________

0.65 m³/day

untreated water :

Sprinklers (for 10 acres (4 hectares) of ground) 0.10 m³/day

U Hotels & Resorts EU Technical Standards Manual

Page 376 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Total 1.50 m³/day /bedroom occupied

This total may be reduced to 1 m³/day/bedroom available for calculation of water reserve.

Capacity of water reserve (adapt according to U Hotels & Resorts Hotel Brief):

o very reliable network: double supply connection and fire reserve only

o reliable town network: 1.5 day i.e. 1 m³/bedroom

o unreliable town network: 3 days i.e. 3 m³/bedroom.

The reliability of the network will be determined statistically over several years. In all cases, the firefighting water reserve must be added to the

capacity determined in this way.

In order to allow for maintenance of reserves, they will be split into three sections.

Description of reserves

Each reserve must be independent and must comprise of:

o supply by ball-cock control

o emergency supply delivered from outside through a valve (emergency water truck, fire engine, …)

o a drain at the lowest portion and bypass to allow for cleaning

o an outlet for general purposes

o an outlet for firefighting needs at a lower level

o an overflow

o ball-operated level monitors

o an external tube level indicator

o possibility for injection of products for sterilization

o vent with anti-mosquito grille

o access for employees (trap, ladders)

o very low voltage illumination or rechargeable electric torch

o report to control panel for overflow and low level.

Communication must be provided between the 3 tanks in the low portion to the opposite high portion in order to create a permanently traversing

circulation of water thus preventing stagnation.

U Hotels & Resorts EU Technical Standards Manual

Page 377 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Pressure Boost

Need for pressure boosting:

This need for storage and circulation within such storage requires distribution by pressure boosters with an intake of water into the storage tanks

and delivery for possible treatment and use.

Pressure boosting principle

The pressure must be created by pressure-maintaining booster sets, using the principle below:

o three pumps constantly provide the required throughput at the specified pressure

o a fourth pump will provide for exceptional throughput peaks and emergencies

o cascade starting of the pumps will be automatic as well as stopping them

o regulation of the whole unit’s operation must take into account:

­ pressure-maintaining level

­ pump start-up pressure

­ pump stopping pressure

­ the cyclical permutation of pumps with choice of the pressure-maintaining pump

­ the timer for stopping the pumps after a forced period of operation in order to restrict the number of occasions when the motors

have to start up each hour

­ provision of measurement, monitoring and regulation apparatus

­ alarms to be sent to the hotel building control system

­ anti-vibration collars where the pumps are connected and pumps to be mounted

­ on bases with resilient material

There will be a separate set for all guestrooms using variable speed pumps.

The minimum pressure at the points of use will be 1 bar and the maximum pressure 3 bars. Notes to be made of special pressures required by

certain specialist equipment.

Pressure variations at any individual outlet shall be limited to 0.5 bar.

U Hotels & Resorts EU Technical Standards Manual

Page 378 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Cold Water Distribution

Nature of piping:

o main distribution preferably in PPR piping

o connection to apparatus by cold-drawn copper tube. These tubes will be chromed on visible sections

o no item of piping, production or treatment equipment made of copper, brass or bronze must be located upstream of any galvanized steel

distribution piping.

Piping dimensions:

maximum velocity 1.2 m/s in columns

1.5 m/s below ground

Insulation:

o To prevent condensation, cold water pipes are insulated in non-air conditioned premises whenever the ambient humidity requires it.

o They are protected against freezing (by heated strip if necessary) in unprotected premises such as garages.

o The insulation must withstand impact and must form a vapour barrier.

Fixing:

All cold water piping must be secured by anti-vibration fixings.

Removable reference tube sections:

These must be provided downstream of main connections or water treatment equipment.

Passages through walls and floors:

Sleeves with lagging. The sleeves must be raised a few centimetres above the surface of the floor.

U Hotels & Resorts EU Technical Standards Manual

Page 379 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Cold water system riser diagram

U Hotels & Resorts EU Technical Standards Manual

Page 380 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Cold Water Metering

The metering system will comprise of (as a minimum):

general metering on entry into the building

metering on entry to all premises under concession and outside U Hotels & Resorts management

metering of kitchen network

metering of laundry

metering of swimming pool

metering of air cooling towers (if water-cooled)

metering of sprinklers

metering of water for steam production

metering of supply to hot water production

metering of bedroom wings.

U Hotels & Resorts EU Technical Standards Manual

Page 381 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

HOT WATER

Production

Suggested Principles:

o production by water heaters and exchangers (instantaneous production permitted)

o the primary liquid will be hot water produced by the boiler plant

o there will be heat recovery from condensers of the air conditioning sets and the cold storage rooms

o production of hot water will be provided by three separate sets mounted in parallel. Each set will have one or more modules and must be

capable of providing 50% of total requirements.

Requirements:

o bedrooms: 0.25 m³/day/bedroom with delivery temperature of 50 to 55˚C (implying a production temperature of about 60˚C)’

o kitchen and laundry 0.15 m/day/bedroom with production temperature of 70-75˚C (with mixing valve in kitchens to bring down water to

60˚C).

o if heated water is needed for the swimming pool, it will have its own integral re-heater

o the drop in temperature between the production point and the most remote point of use must not be more than 5˚C,

o a safety cut-out will prevent the temperature from being more than 5% above the desired temperature

o minimum storage: 60 litres per bedroom and 10 litres per restaurants seat, at 55˚C minimum.

Equipment

o the materials constituting the exchanger must be made of stainless steel,

o the secondary outlet collector will be of galvanized steel,

o no element in contact with water must be made of copper or brass, except where the networks are entirely made of copper.

Associated Devices:

o thermometers will be placed at secondary outlets and at the primary inlet and loop return with a repeater in the B.C.S.,

o a degassing device will be placed at the secondary water outlet. It will have a velocity reduction chamber, an automatic drain cock with

its isolation valve and a manual drain facility,

o an inspection coupler with valves and bypass will be provided in a horizontal section at the commencement and at the return from

circulation.

o Solar production:

In locations where the average time when the sun is visible is more than 2,800 hours per year, research can be undertaken into the

possibility of pre-heating of sanitary hot water using solar energy.

U Hotels & Resorts EU Technical Standards Manual

Page 382 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Hot Water Distribution

Nature (1), design dimensions, fastening, reference tubes, passages through walls and floors: see cold water network

o compensation bends and other systems of expansion (isolating rings) to be provided wherever necessary and to allow sliding at hook-up

points.

Insulation:

This must be provided everywhere for

o piping

o valves

o hot water heaters

of a material which withstands impact in all accessible parts.

Circulation pipes:

o the hot water distribution piping must be looped and circulated in order to ensure immediate drawing of hot water,

o there will be 2 circulating pumps in parallel; one in service, the other in reserve. Pumps will be connected by anti-vibration collars and

will be mounted on a base with resilient material.

The network shall be studied in order to avoid any dead sections and facilitate balancing.

U Hotels & Resorts EU Technical Standards Manual

Page 383 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Metering of Hot Water

Separate sections with independent metering will be provided for:

o bedrooms

o kitchens

o laundry

Premises under concession not managed by U Hotels & Resorts

(1) Note: in any part of a network of galvanized steel, the temperature must never exceed 60°C

WATERING SYSTEM

Network

Semi-flexible piping of high-density polyethylene outside buildings.

Watering Nozzles

The watering hydrants must be distributed in green spaces in such a way that any point that may be watered is at most 40 meters from the

nearest hydrant.

The hydrants must have a nominal diameter of 40 mm.

They will be of the non-freezing type in countries where the minimum temperature goes below 0˚C.

They must be cast, with internal equipment of brass and galvanised accessories.

Automatic Sprinklers

These to be provided in relation to landscaping (with programming clock).

Recycling of Water Leaving the Sewage Treatment Plant

U Hotels & Resorts EU Technical Standards Manual

Page 384 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

If regulations permit, water coming from the water treatment plant will be used for watering if it meets monitored qualities.

Internal and External Garden Features

Provision of drainage and watering hydrants and for fixed garden features and drip feed watering system.

Pavement, Parking Area and Service Yard

Draw-off taps and traps for cleaning to be provided.

U Hotels & Resorts EU Technical Standards Manual

Page 385 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

WASTE WATER - SEWAGE

Drainage from Sanitary Apparatus

Principle:

Separate networks for wastewater and sewage.

Networks:

o connection of fixtures to soil pipes by cold-drawn copper tube,

o separate connection for bathtubs

o clearing plugs at the ends of piping

o standard sanitary cast-iron waste stack with tested joints, excluding any PVC network,

o piping and down-pipes to be fixed with anti-vibration fittings,

o cleaning eye at the foot of each down-pipe,

o avoid offsets in the ceiling of public rooms; if there is any offset, provide a device for collection of any leaks,

o horizontal cast-iron collectors with a minimum slope of 2 cm/m.

o clearing plugs at each change in direction

o all soil pipes are to be extended above the roof line in order to guarantee ventilation.

Networks buried in buildings:

o Manholes will be provided at changes in direction (both horizontal and vertical).

o These manholes will be sealed and will have a curette to facilitate the flow of waste.

o Covers for these manholes will be sealed with a rubber joint and will have a covering which is identical to that of the room in which

they are located.

o Peripheral angles to be installed.

o The distance between manholes must not be more than 10 metres.

Kitchen Drainage

The kitchen network will be separate.

Before being taken to the sewage treatment plant water coming from the kitchens must pass through the following devices:

o water coming from peeling machines: starch trap

o water coming from vegetable preparation: sludge separator

U Hotels & Resorts EU Technical Standards Manual

Page 386 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

o water coming from kitchens and sinks: sludge separator then grease trap.

Access to these devices for inspection, cleaning and emptying must be extremely easy.

Garage Drainage

Before being taken to the sewage treatment plant, water coming from the garages must pass through the following devices:

floor gullies

sludge separator

Hydrocarbons traps downstream of the sludge separator.

Access to these devices for inspection, cleaning and emptying must be extremely easy.

Water Lifting

If a lifting station is necessary it is essential that this has two pumps, each of which is capable of providing 100% throughput. The station will have

guiding bars which allow one to raise and lower the pumps using chains or handling cables.

The protection and control cabinet must allow for:

systematic permutation of the running order of the pumps

automatic replacement of one pump by the other in the event of default

manual starting for testing and checking

start, stop and default warning lights for each pump

alarm report to the main BCS control panel.

Sewage Treatment Plant Principle:

o Where wastewater is not treated by the public networks waste water and sewage derived from the hotel must be treated before being

disposed of in the sewer or to the natural outlet.

This sewage treatment plant will be downstream of the specialist treatment processes for kitchens and garages.

o The units will be made up exclusively from concrete and will be designed to fit into the site as discreetly as possible.

The unit will be made of the activated sludge biological purification type with aeration and sewage settling and will process all

wastewater. Rainwater need not be sent to it.

U Hotels & Resorts EU Technical Standards Manual

Page 387 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Positioning

As far as possible from the hotel in order to prevent noise, odour and unsightliness. To be specified in relation to the prevailing winds.

Drainage

Residual water will be drained off in accordance with local legislation and must therefore display the appropriate characteristics. Additional

treatment (filtering, sterilization or UV) will be installed in necessary, in particular where water is reused for watering of spaces accessible to

the public.

U Hotels & Resorts EU Technical Standards Manual

Page 388 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Waste water system diagram

U Hotels & Resorts EU Technical Standards Manual

Page 389 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Water treatment –septic tank

The tanks will have a minimum 6 hour of holding time before discharge to the environment.

U Hotels & Resorts EU Technical Standards Manual

Page 390 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Water treatment –septic tank

U Hotels & Resorts EU Technical Standards Manual

Page 391 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Water treatment –grease interceptor

U Hotels & Resorts EU Technical Standards Manual

Page 392 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Water treatment –distribution box

U Hotels & Resorts EU Technical Standards Manual

Page 393 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

RAINWATER

Principle

Separated from waste water and sewage for the entire network (down-pipes and collectors).

Network

cast-iron down-pipes,

plugs at the foot of the down-pipe

collectors of identical construction to those for waste water

buried network in concrete or PVC

inspection manholes in accordance with the same rules as for the waste water network

Pumping Up

Pumping up of rainwater must be entirely exceptional. The same principle to be used as for sewage if pumping up is compulsory.

U Hotels & Resorts EU Technical Standards Manual

Page 394 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GAS

City Gas Connection

Connection by the distributor or in accordance with the instructions.

Dimensions:

o according to needs for production of heat,

o at least 500 kcal per consumer and per meal for use in the kitchen.

Gas Storage (if needed)

Where there is no city network, gas storage will be created in the form of gas cylinders which give minimum supply of 10 days.

Location and ventilation to be in accordance with local regulations and operating criteria, but includes aesthetic criteria.

Enclosed or with peripheral fencing.

Tapping units protected by a lockable hood.

Road access for tanker truck.

Stoppage by emergency push-switch.

Suitable firefighting resources (powder extinguishers, firefighting network)

Pressure Reduction Station

A delivery unit and pressure reduction station will be provided. It will contain the distributor’s metering system and will allow gas to be

supplied at a useful transport pressure. For use, additional pressure reduction units which are placed in line with equipment (boiler plant,

kitchen apparatus, laundry) will provide service pressure.

Within buildings, the transport pressure in the distribution network will never be greater than 2.1 bars.

Gas detectors will be provided in all closed areas.

Noise precaution for airborne noise and vibrations.

Safety signalling system.

U Hotels & Resorts EU Technical Standards Manual

Page 395 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Network

Safety and shut-off facilities prescribed by the distributor and regulations for leak detectors.

As a minimum:

o general shut-off valve outside the buildings

o shut-off valve at each pressure reduction point

o shut-off valve on entry into the building

o shut-off valve on entry into each premises where gas is used

o solenoid valve linked to ventilation in the kitchen

The valves are of an officially approved type.

Horizontal runs are located in spaces that are ventilated and capable of inspection.

Metering

Separate meters to be provided for:

boiler plant

kitchen

U Hotels & Resorts EU Technical Standards Manual

Page 396 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LPG Station

U Hotels & Resorts EU Technical Standards Manual

Page 397 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LPG Station

U Hotels & Resorts EU Technical Standards Manual

Page 398 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LPG Single Line Diagram

U Hotels & Resorts EU Technical Standards Manual

Page 399 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 400 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Safety Distance

U Hotels & Resorts EU Technical Standards Manual

Page 401 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Safety Distance

Warning Signs

U Hotels & Resorts EU Technical Standards Manual

Page 402 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Electrical Wiring for Gas Station

U Hotels & Resorts EU Technical Standards Manual

Page 403 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 404 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Riser Diagram

U Hotels & Resorts EU Technical Standards Manual

Page 405 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SANITARY WARE

Bedroom Equipment (also refer to chapter C3)

General provisions

o all sanitary apparatus will be white or a pale colour

o risers should never be embedded and piping should not be embedded where possible

o visible piping to be reduced as much as possible

o taps and fittings must have a minimum 10-year guarantee and must operate silently. Mechanism is to be of the out-of-water type with 3 /

4 turn ceramic heads including hot/cold colour-coding. Taps, drains, traps, pull chains and anti-splash plugs made of chromed brass of

superior quality (Grohe or similar).

o All drains (especially showers) shall have a capacity at least equivalent to double the supply flow.

all piping will have an equipotential link and will be earthed

Suites may have more luxurious sanitary equipment than the standard bedrooms

Water flows to fixtures

The following shall be considered as minimum flows of cold, hot or mixed water:

Showers = 12 I/min

Toilets = 8 I/min

Washbasins = 12 I/min

Showers:

o acid-resistant enamelled cast iron or built-up with tiles or stone and water proofing

o bottom to incorporate anti-slip treatment as manufactured

o clear depth 10 cm ; recess 3 cm with respect to the adjacent floor

o built-up units have a 3 cm minimum threshold; they can be flush with the bathroom floor if the shower drain is used as a floor drain, in

which case the floor has a 1% slope to drain and is fully waterproof

o removable bell-trap top for cleaning

o the trap must absorb twice the shower flow

o tiles overlap to pan edges with fungicide-treated silicone between the tiling and the shower pan

o single-handle or 3-hole thermostatic or press static mixer valve

o spot-directed towards the vertical wall of shower cabin in order to restrict noise and leave free access to controls

o tempered-glass enclosure and door on non-tiled walls with stainless-steel hardware and supports

U Hotels & Resorts EU Technical Standards Manual

Page 406 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

WC bowls

o preferably a wall hung bowl, with direct flush and siphon action and made of vitrified porcelain

o cistern fixed to wall and preferably recessed into the wall with direct flushing handle

o fully-closing seat with lid of white or pale colour

o flushing valve prohibited in bedroom floors as being too noisy

o in Islamic countries, provide a hand-held shower next to the toilet if there is no bidet

Wash basins

o bathroom vanity unit with integral bowl of vitrified porcelain, fixed beneath a stone or marble panel. Waterproofing provided by

elastomeric joints with peripheral anti-drip recess

o bowl equipped with overflow, positioned if possible on the opposite side to the mirror

o 3 / 4 turn ceramic double head 3-hole mixer taps

The bathroom vanity unit will comprise of:

a backing strip 10 cm high or panel with full-width mirror,

a drop facing of a minimum height of 25 cm

10 cm high plinths attached to the wall on each side of the bathroom unit with mirrors on top

The top of the vanity unit will be located 85 cm from the finished floor level.

Floor drain

o If a floor drain is to be installed in the bathroom (which is not recommended), the following requirements must be met:

waterproofing over the entire bathroom floor with slope towards the drain

Accessories

o Items to be provided: ­ shower towel rails

­ double hand towel rails

­ double toilet paper holders

­ shaving mirror

­ tempered glass screens and doors

U Hotels & Resorts EU Technical Standards Manual

Page 407 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

­ shower curtain and rod

­ sanitary bag hook

­ retractable clothes line

­ double robe hooks

­ soap trays

­ grab bars for shower (as per FFE and interior designer’s lists).

o The finish of all accessories must match that of the sanitary fittings (stainless steel or chrome-plated).

Public Toilets

Obligatory waterproofing, draw-off cock and floor drain

WC bowls (wall hung)

U Hotels & Resorts EU Technical Standards Manual

Page 408 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

WATER TREATMENT

Treatment of Water for Domestic Use

Cold water for domestic use

o objective

­ total TH (total hardness) is not important if below approx. 300 ppm. (1)

­ PH above 7 and below 8.5

­ bacteriological quality in accordance with criteria specified in 1 above

o treatment equipment

­ softener to adjust total TH where necessary to a correct level; below 300 ppm and ideally around 100 ppm

­ dosing pump for injection of alkaline drinkable products (caustic soda or carbonate of soda) to bring pH above 7. If after

injection of the above product a residue to CO2 carbonic gas remains, it will be necessary to install a neutralizer which will

allow the CO2 to be fixed with natural mineral products (Neutralite),

­ dosing pump with supply of chlorinated solutions (Javel water, HTH, …) making it possible to bacteriological treat the water if

necessary or an approved system of sterilization by ultra violet rays (UVC).

Steam boiler plant

o objectives:

­ total TH = 0 ppm

­ pH above or equal to 8.5

o treatment equipment:

­ softener using ion exchanger resin to bring total TH to 0 ppm

­ dosing pump coupled with boiler feed water pump for injection of alkaline products, so as to obtain pH above 8.5.

Steam condensation returns are always acid, except in the case of priming (sodium gas mixed with H20). In this case, de-concentration purging is to be

provided to maintain a TAC (total alkali metric content) (2) of around 100˚F maximum.

Closed circuit for technical equipment (heating circuit, chilled water circuit).

o objectives:

­ total TH = 0 ppm

­ PH above or equal to 8.5

o treatment equipment

­ softener to bring down total TH to 0 ppm

U Hotels & Resorts EU Technical Standards Manual

Page 409 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

­ mixing pot for alkaline product balls for correction of pH below 8.5.

­ Cooling-tower circuit

o objectives:

­ TH = 0 ppm

­ pH above 8.5 anti-algae

o treatment equipment:

­ softener to bring TH to 0 ppm

­ dosing pump for injection of alkaline products in order to bring pH above 8.5

­ Proportional dosing pump for injection of anti-algae product (Javel water or chlorinated product).

Laundry washing machines

o objectives:

­ cold water: TH unimportant if TH is below 300 ppm

­ pH unimportant (within general specified limits)

­ hot water: TH of 0 to 50 ppm

o treatment equipment:

­ cold water for rinsing: no special treatment but washing machines are to be connected to cold water

­ network, upstream of water treatment (hard water)

­ hot water: water softener if necessary.

Kitchen

o objective:

­ TH= 0 ppm only for the following items of equipment: coffee machine (espresso and percolator), ice machine, glass washing

machine,

o treatment equipment:

­ either a special circuit with water softened to TH of 0˚

­ or individual softener in line with each item of apparatus.

­ hot water for domestic use

o objective:

­ TH of 60 to 100 ppm

­ pH unimportant

o treatment equipment:

­ softener to bring TH to correct value

U Hotels & Resorts EU Technical Standards Manual

Page 410 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

­ dosing pump for film forming treatment with product tank and pulse meter

­ allowing for dosage in relation to actual water consumption and not in relation to

theoretical throughput as for alkaline treatment.

Protection Against Corrosion

This film-forming treatment is used to protect piping from the corrosive action of certain types of water (in particular soft water), by the deposit

of a protective film. Need for it is established by the analysis mentioned in 1, in conjunction with the treatments mentioned above at the time of

the technical studies for each project.

In the case of steel tube installations, a cold water distribution installation must be protected against corrosion if the water passing through it,

considered at 20˚C, is in one or more of the conditions shown in the following table.

U Hotels & Resorts EU Technical Standards Manual

Page 411 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

TABLE 1 (cold water)

A hot water distribution installation must be protected against corrosion if the water passing through it, considered at 20˚C, is in one or more of

the conditions shown in table 2.

TABLE 2 (hot water)

U Hotels & Resorts EU Technical Standards Manual

Page 412 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Treatment relates to all circuits but the products used are not the same.

o Product to be employed

­ cold or hot water for domestic use: of foodstuff quality, being made up using silicates, silicone poly-phosphates and zinc

phosphates

­ water for plant use:

heating plant: nitrites/soda

Chilled water: benzotriazol, nitrites (for effective protection of copper and steel).

o Treatment equipment:

­ Injection will be carried out using:

a dosage set made up from:

­ a dosing pump }dimensions to be appropriate for

­ a product tank }maximum water throughout

­ a pulse meter }expressed towers,

This being for water for domestic use and cooling towers.

A mixing pot (stainless steel mixing bottle) for heating and chilled water circuits where the volume is below 5 m³

Water takes-off will be installed upstream and downstream of each treatment device, in order to allow for inspection.

In all cases, after analysis and comparison of the different requirements, the idea will be to group together the various treatments in order to

create an efficient central installation.

Swimming Pool Treatment

Treatment equipment:

Dosing pump to allow for introduction of flocculent products (coagulation of small particles by aluminium sulphate), automatic sensors and

dosing pump for chlorinating (sterilization) of water by introduction of Javel water, super-chlorine, calcium hypochlorite, automatic sensors and

dosing pumps:

o for injection of anti-algae product

o for injection of acid product if pH of water is above 8.2

o for injection of alkaline product if pH of water is below 6.9

U Hotels & Resorts EU Technical Standards Manual

Page 413 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Pre-filters and closed sand filters, with automatic back-washing, recycling throughput: the volume of water in the swimming pool will be

filtered in a maximum of 4 hours for those sections of the pool more than 1.5m deep, and a maximum of 1.5 hours for the other sections, with

the rate at which water passes through the sand filters not exceeding 50 m/h. For the shallow pools (children’s’), the filtration cycle may not

exceed 0.5 hours.

For Jacuzzis, the recycling rate is at least 10 turnovers per hour; the daily input of new water will be at least equal to 30 litres per bather,

circulation pumps. Automatic (Pool-swipe type) and manual suction sweepers.

The treatment products used must allow the following concentrations to be maintained:

o Free chlorine: 0.4 mg/I < c< 1.4 mg/I for 6.9 < pH < 7.7

o Combined chlorine concentration ≤ 0.6 mg/I

o Bromine: 1 mg/I < c < 2 mg/I for 7.5 < pH < 8.2

Operation of the dosing pumps will thus be controlled by measurement of these concentrations by chlorastat or bromstat, carried out on water

as it leaves the pools.

U Hotels & Resorts EU Technical Standards Manual

Page 414 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FIRE PROTECTION

Fire Fighting Resources

Sprinklers

Fire Plugs with Hose and Spout

Fire Pump

Extinguishers

Wet Risers

Dry Risers

Standpipes

U Hotels & Resorts EU Technical Standards Manual

Page 415 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FIRE FIGHTING RESOURCES

The resources for firefighting can be:

sprinklers

Hose reels with adjustable nozzle

fixed and mobile extinguishers

wet risers

dry risers

stand pipes

They must comply with current and local regulations with the specifications set out below being minimum specifications.

U Hotels & Resorts EU Technical Standards Manual

Page 416 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SPRINKLERS

General Arrangements

U Hotels & Resorts prefers general adoption of the automatic extinguishment system by sprinklers. However if this is not feasible for budgetary

reasons then this Fire Protection system may be omitted in place of alternative systems.

The task of sprinklers is threefold:

monitoring

extinguishment

alarm

The system is made up of four sections:

the sprinkler heads

the networks of pipes made of steel tubes

the monitoring units which locate the sprinkler

the hydraulic equipment.

Sprinkler Heads

The heads can be of various types:

o spraying the water upwards and downwards

o spraying the water downwards (“spray pendent”)

o spraying the water upwards (“spray upright”)

o high temperature in hot zones.

The distance between sprinklers and walls or partitions must not be greater than half the spacing allocated between sprinklers by the regulations

specific to each type of installation, and in no circumstances may it be more than 2.30 m.

They are distributed at a rate of at least 1 every 12 m² with, for bedrooms, 2 sprinkler heads in the bedroom area, 1 in the entrance area and

possibly 1 in the bathroom.

U Hotels & Resorts EU Technical Standards Manual

Page 417 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Each enclosed-head sprinkler is held closed by either a heat-sensitive glass bulb or a two-part metal link held together with fusible alloy such as

Wood’metal and other alloys with similar compositions. When ambient temperature reaches designed activation temperature, the bulb breaks.

The table below based on NFPA 13 table 3-2.5.1 shows different activation temperatures of sprinkler with the bulb colour

Temperature

Classification

Maximum Ceiling

Temperature

Sprinkler

Activation

Temperature

Liquid Alcohol in

Glass Bulb Colour

Colour Code

(with Fusible Link)

Ordinary 38 °C/100 °F 135 °F-170 °F Orange (135°F)

Red (155°F) black; no color

Intermediate 66 °C/150 °F 175 °F-225 °F Yellow (175°F)

Green (200°F) White

High 107 °C/225 °F 250 °F-300 °F Blue Blue

Extra High 149 °C/300 °F 325 °F-375 °F Purple Red

Very Extra High 191 °C/375 °F 400 °F-475 °F Black Green

Ultra High 246 °C/475 °F 500 °F-575 °F Black Orange

Ultra High 329 °C/625 °F 650 °F Black Orange

Piping

This can be water filled, i.e. permanently under pressure. There is the possibility of mixed installations which are only filled with air in a frost

period.

Monitoring Centre

This identifies the sprinkler head which is operating and triggers the alarms. It comprises:

stop valves with alarm

water alarm check valves

hydraulic turbines which set off the alarms and various monitoring elements

U Hotels & Resorts EU Technical Standards Manual

Page 418 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

1. Stop Valve 2. Valve Monitor 3. Alarm Valve 4. Sprinkler Head 5. Alarm Test Valve 6. Alarm Bell (Gong) 7. Pressure Switch 8. Jockey Pump 9. Flow Switch

This centre transmits the alarms to the control room and the telephone exchange.

Hydraulic Equipment

This involves:

a pressure booster plus motor driven pump

an air compressor

a pressure tank

water reserves, the capacities of which will be specified by the criteria of insurance companies. Whatever the circumstance, they will not be less

than 35 m³.

Typical Sprinkler System Diagram

U Hotels & Resorts EU Technical Standards Manual

Page 419 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FIRE PLUGS WITH HOSE AND SPOUT

These must be placed inside so that the entire area of the premises can be effectively reached. In premises with particular risks, all points must

come within the range of at least two nozzles. Preferably they will be placed as close as possible to the outside of the premises to be protected,

in common passageways.

They must be encased in unlocked cabinets which do not project into the passageways.

They must have a semi-rigid pipe at least 20 m long without any intermediate joint with a check valve and there must be brackets for

supplementary equipment such as fire buckets and fire axes.

The minimum operating pressure must not be below 2.5 bar (36 p.s.i.); the supply of water must be via pressurized water piping fed from the

public mains. Preferably, the distribution network should be constructed in “meshed” form, with lower and upper ring.

U Hotels & Resorts EU Technical Standards Manual

Page 420 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FIRE PUMPS

Part of fire sprinkler system’s water supply

The pump is connected to the public water supply piping or use a static water source such as tank, reservoir or lake

Provide water flow at a higher pressure to the sprinkler system and hose standpipes

A jockey pump is a small pump connected to a fire system to maintain pressure in a fire protection piping system

U Hotels & Resorts EU Technical Standards Manual

Page 421 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

EXTINGUISHERS

Fixed Extinguishers

Fixed extinguishment systems with automatic triggering are specified for the following facilities:

kitchen hoods (Co2)

boiler burners (powder extinguishers)

main electrical equipment rooms (Inergen).

These systems have a separate alarm which is linked to the fire detection centre.

Mobile Extinguishers

Portable or mobile extinguishers are:

o atomized water in bedrooms, offices, linen stores

o Co2 in services rooms and premises with electrical apparatus

o 50 kg polyvalent powder on wheeled frames in parking areas and plant rooms.

They are distributed in clear areas, easily visible and accessible and protected from major temperature changes.

Where placed in areas with public access, they are housed in wall cupboards or recesses designed to blend with the decor of the building.

U Hotels & Resorts EU Technical Standards Manual

Page 422 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

WET RISERS

These columns are associated with the fireplugs with hose and spout.

The fire outlets for these columns must be located in stairwells and staircases.

The supply unit for each column (feed tank, supercharger and pump) must ensure an hourly throughput of 60 m³ under static pressure between

4.5 and 8.5 bars (65 and 125 p.s.i.).

It must be possible to refill the columns from two 65 mm apertures equipped with valves and located at the fire department access level less

than 60 m away from a standpipe or hydrant.

DRY RISERS

The supply connections for dry risers must be easily accessible to the fire department on the wall which is closest to the standpipes or fire

hydrants. The distance between these connections and the hydrants must not be more than 60 meters.

The outlets must be located in the stairwells or staircases. They must be of a type which is suitable for the fire department equipment and must

have a hydrant key.

U Hotels & Resorts EU Technical Standards Manual

Page 423 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

STANDPIPES

If the public water plugs are too far away, or if they provide inadequate throughput, there can be a requirement to install private standard

standpipes for the hotel.

They must be painted to comply with local standards.

They can be substituted by water supplies which are easy to use: flowing water, tanks, and swimming pools.

Arrangements will be made so that any water overflowing into any storey at the time of a fire can be drained off and will not invade the

staircases, lifts and hoist.

U Hotels & Resorts EU Technical Standards Manual

Page 424 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FIRE DETECTION

General Notes

Detection Principle

Detectors

Alarm Push Buttons

Smoke Outlet Control Push Buttons

Communications Centre

Electrical Supply

Fault Warning

Alarm Warning

Automatic Extinguishment Control

Fire Suppression System

Automatic Control System

U Hotels & Resorts EU Technical Standards Manual

Page 425 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GENERAL NOTES

The purpose of the fire detection installation is to detect fires as soon as they start, to give the alarm and to trigger the automatic controls.

The zones to be protected will cover all public areas, service areas and extraction conduits from such premises.

The detection system will automatically control mechanical and natural smoke removal from the zone in question and all the automatic controls

described hereafter.

DETECTION PRINCIPLE

Fire detection equipment is generally installed throughout the premises, with the exception of bathrooms and toilets.

They system is of the analogue type and allows each detector to be addressed. However, all public areas could be of conventional system.

The control centre, detectors and pushbuttons form a homogeneous package, with continuous dialogue being maintained between the various

elements.

The sensors continuously transmit readings to the control centre which compares them with the programmed figures.

The control centre can then decide to give the detector alarm status or to record it as faulty.

U Hotels & Resorts EU Technical Standards Manual

Page 426 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

DETECTORS

The detectors will be tailored to the premises to be monitored, in particular:

o Preference will be given to use of smoke detectors in all premises such as passageways, conference halls, restaurants and ventilation

ducts (blown air and recovery).

o Thermo-velocimetric detectors in service rooms, car parks, storage rooms and kitchens.

o Thermostatic detectors in workshops.

The area monitored by a detector will not be more than 50 m² in rooms. In passageways, maximum spacing will be 20 meters.

The entire system will be divided into zones, in which case an individual zone will not have more than 25 detectors, or one floor or part of one

floor of bedrooms.

There will be a smoke detector at the entrance to each bedroom, even if it is protected by sprinklers.

They will operate on 24V direct current.

Each detector controls an individual operating light indicator, incorporated into its base.

Detectors must remain in alarm mode until it is cancelled by manual operation at the detection control centre; at such time they must

automatically revert to the monitoring mode.

Smoke detector over the bed in guestroom will have a sounder base with minimum 95 decibels at the pillow.

U Hotels & Resorts EU Technical Standards Manual

Page 427 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ALARM PUSH BUTTONS

On each floor and close to each staircase there will be a push button or some other alarm device, in accordance with local regulations.

Push buttons will be in red boxes of the fixed glass type. Breaking the glass sends the alarm warning to the control centre.

They are of the flush fit type.

They are equipped with a red-coloured face frame and a fire symbol indicating their purpose.

SMOKE OUTLET CONTROL PUSH BUTTONS

These push buttons may only be used by firemen or the hotel security team and are used for manually opening the smoke vents.

They have the same characteristics as the alarm push buttons; their use is clearly indicated so that they cannot be confused with the others.

COMMUNICATIONS CENTRE

This is located in the fire safety and plant control room or engineering offices, with repeaters in the security office and in the reception/guest

service centre.

The electronic equipment of the control centre must make it possible to:

o Process rapidly a considerable number of possible information items (alarm, fault, monitoring etc) whilst observing degrees of urgency

between the relevant signals.

o Transmit such information easily by remote means.

o Maintain continuous monitoring of:

­ the electrical supply network

­ the condition of batteries

­ all automatic controls

­ detection networks

­ monitoring lines

It is equipped with a specific screen, or a glazed panel which allows the signals to be displayed.

U Hotels & Resorts EU Technical Standards Manual

Page 428 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Optical and sound signalling of faults and alarms must not be confused with each other.

The control centre must automatically display on a separate screen all occurrences in the installation in chronological order.

Identification of detectors and push buttons is carried out automatically on the screen. A sound signal gives automatic warning of the

occurrence of any event.

The control centre is equipped with a printer which enables a detailed listing to be produced of events of the past week, with corresponding

dates and times.

It is also equipped with a remote transmission facility capable of calling automatically and in sequence programmed telephone numbers in the

event of an alarm.

U Hotels & Resorts EU Technical Standards Manual

Page 429 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ELECTRICAL SUPPLY

The control centre is supplied from the electricity main supply and includes a battery charger and set of batteries.

The batteries are cut in and shut off automatically when the normal power supply breaks down or is re-established.

The battery capacity is sufficient to allow emergency operation for 12 hours minimum.

FAULT WARNING

All defects in the installation must be automatically notified to the communications centre by optical and sound signal.

The sound signal can be halted without interrupting operation of the luminous optic signal.

The optical fault warning must be maintained until the defect disappears or is rectified.

ALARM WARNING

The alarm warning is carried out:

o By sound and visual means in the communications centre and on the repeater panels.

o By alarm sirens and visual signs in passageways and rooms.

The alarm in bedrooms (signal for evacuation) will take two forms:

o By broadcasting a message from reception using public address equipment.

o By buzzers and blinkers placed in each bedroom and passageway, controlled automatically via the fire detection system and with a time

limit and facility for cancellation from the fire safety and plant control centre.

These alarm system are connected to the emergency power supply described in T7 – Electrical Supply.

U Hotels & Resorts EU Technical Standards Manual

Page 430 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FIRE ALARM SYSTEM DIAGRAMME

U Hotels & Resorts EU Technical Standards Manual

Page 431 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 432 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 433 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 434 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

AUTOMATIC EXTINGUISHMENT CONTROL

The high voltage/low voltage room and the generating set room (Inergen), the lift machinery rooms (powder), the kitchen hoods (CO2) and the

boiler burners (powder) are equipped with appropriate automatic fire extinguishment systems.

These systems are controlled:

o Automatically via the fire detection installation: automatic control with time limit.

o Manually, from an electric push button placed under glass and linked directly to the communications centre: manual control with time

limit.

FIRE SUPPRESSION SYSTEM

Most fires in hotels or restaurants ignite in the kitchens by deep-fat fryer, wok and grill therefore this system is compulsory for any main

kitchen hood.

Cooking equipment currently manufactured uses more efficient burners, resulting in much higher heating rates. More cooking is done with

vegetable oil instead of animal fats. Vegetable oils have a much higher auto ignition temperature. Fryers are now made with improved

insulation that slows the cooling rate, but which also increases the risk of a re-flash in the event of fire.

Fire suppression systems are custom fit and require a dedicated consultant to specifically tailor them.

o Kitchen suppression systems are actuated by a fusible links located above the cooking appliances.

o The links melt during a fire, causing a cartridge to fire propelling gas into the liquid agent tank.

o The distribution piping system carries the agent to nozzles located above the cooking appliances, in the plenum above the filters, and in

the duct above the plenum.

U Hotels & Resorts recommends internationally approved products like;

o Ansul R-102 ( www.ansul.com )

o Range Guard UL 300 ( www.rangeguard.com )

o Pyrochem ( www.pyrochem.com )

U Hotels & Resorts EU Technical Standards Manual

Page 435 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 436 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 437 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

AUTOMATIC CONTROL SYSTEM

The communications centre carries out programming and control of the following automatic control systems, tailored in accordance with current and

local regulations:

Initiation of evacuation signal in rooms of the section concerned, including passageways and rooms holding more than 20 people.

Automatic closing of fire cut-off doors which are normally kept open continuously by magnetic catches.

Opening smoke extraction outlets.

Closing the gas shut-off valve which supplies the heating plant and the kitchen.

Lift non-stops system.

Reset to zero lifts which are automatically brought down to the hotel entrance level.

Halting ventilation fans with automatic restarting after the end of the fire alarm.

Unlocking of external doors in emergency staircases leading outside.

Automatic control of mechanical smoke removal system (blowing + extraction).

Automatically controlled fire dampers.

Power supply and control: power supply to automatic control systems goes via the detection centre. All automatic control systems of the positive safety

type, i.e. in the event of supply or control cable being cut, the systems served react as though there were a fire alarm.

U Hotels & Resorts EU Technical Standards Manual

Page 438 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

VENTILATION – AIR CONDITIONING

General Notes

Treatment of Rooms

Heat Production

Cold Production

Distribution Network and Terminal Equipment

U Hotels & Resorts EU Technical Standards Manual

Page 439 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GENERAL NOTES

External temperature and humidity conditions

Local meteorological readings as a working basis

Internal temperature and humidity conditions

“Winter” (cold season):

o bathrooms 24˚C (+ 2˚C)

o bedrooms 22˚C (+ 2˚C)

o meeting rooms

o restaurant

o lounge 20˚C (+ 2˚C)

o cafeteria

o bar

o lobby

o shops 20˚C (+ 2˚C)

o passages

o offices 20˚C (+ 2˚C)

o fitness& recreation areas 24˚C (+ 2˚C)

o indoor pools Refer to C10,2

o workshops

o laundries service room

o kitchens involving Employee 18˚C (minimum)

o offices

U Hotels & Resorts EU Technical Standards Manual

Page 440 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

o linen store

o various stores rooms without employees 14˚C

Relative humidity ≥ 40%

“Summer” (hot season)

Air conditioned or not

Temperatures where premises are air-conditioned:

air conditioned premise(when Ext. T > 25˚C)

o internal temperature in ˚C = 20˚ + 0.32 × (external temperature -20˚), with an absolute maximum of 25˚C in all situations with reference

relative humidity of 50%. Internal humidity: between 30 and 60%

o calculation of all installations (more specifically conference rooms and banqueting rooms) will take into consideration the unoccupied

calorific loading of such installations, in particular lighting and those due to occupants, at a rate of 4 persons per 3 m² in a cocktail

configuration for the conference rooms.

Kitchen

o internal temperature in ˚C = 20˚ + 0.40 × ( external temperature -25˚)

o internal humidity < 60%

Laundry

o internal temperature in ˚C = 20˚ + 0.40 × ( external temperature -25˚) taking into

account heat released from machines humidity of < 75 %

Wine Cellar: 16˚C (outside cold room)

Ventilation rate

Bedrooms and public rooms:

o bedroom

­ fresh air: 2 volumes per hour, minimum 120 m³/h

U Hotels & Resorts EU Technical Standards Manual

Page 441 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

­ extraction for bathroom > 120 m³/h

o rate of extraction from kitchenettes of suites and serviced apartments

­ extraction: 120 m³/h

­ fresh air: supplement in relation to number of rooms in order to balance extraction

o rooms on each floor (ice machine)

­ extraction: 120 m³/h

­ fresh air in passages to balance

o public rooms with high occupancy rate

minimum fresh air according to possible number of occupants:

­ less than 100 : 50 m³/h per occupant (10 vol./Hr minimum in changing rooms)

­ 100 t0 500 : 35 m³/h per occupant

­ Fitness centre : 50 m³/h per occupant

U Hotels & Resorts EU Technical Standards Manual

Page 442 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Service Rooms:

Fresh air

(in volume/hour)

Extraction

(in volume/hour)

kitchen

30 minus air transferred

from restaurant

34

Transfer between the restaurant and the kitchen will arise by natural overpressure via a duct which has acoustic lining.

It is essential that all the kitchen and annex facilities are placed at lower pressure compared with the surrounding rooms.

Special attention will be paid to the design of the hood of the cooking area.

laundry and dry cleaning

30 35

washing up

20 25

glass washing (per unit) 4,000 m³/h

Employee and other stores 6 6

workshops 10 10

boiler plant (with

modulation according to

output and regulation)

40 20

refrigerating sets 15 20

air units 10 15

transformer set 15 18

generating set 20 according to set

lift machinery 15 15

telephone

exchange/PABX

15 10

offices 3 3

U Hotels & Resorts EU Technical Standards Manual

Page 443 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

NB: for technical and service rooms, indicated ventilation rates can be reduced if the rooms are air-conditioned.

TREATMENT OF ROOMS

Bedrooms (according to location)

Distribution of pre-treated fresh air with bedrooms.

Fan-coil unit linked through loops to two different networks, one permanently conveying cold water and the other conveying hot water.

Individual regulation by environment thermostat.

Control for fan (3 speeds + Off position).

An automatic electric switch makes it possible to stop the fan-coil fan and close off the cooled water valves if the windows or the balcony doors

are opened.

Restaurants, Conference and Meeting Rooms

Individual 4 tube treatment unit per room.

Low pressure blowing system with distribution of treated air and regulation per rooms.

Partial recycling of air.

Each portion of the multipurpose hall and each meeting room must have its own unit and be regulated in an independent manner.

Air extracted from public rooms may be recovered to supply the technical rooms and in certain cases service rooms.

Bars

One hundred per cent fresh air low pressure individual unit.

Kitchen, Laundry

Individual treatment unit per room; low pressure blowing unit with distribution of treated air and regulation per room. Air transferred from

restaurant for kitchen.

U Hotels & Resorts EU Technical Standards Manual

Page 444 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

HEAT PRODUCTION

Administration and Service Offices

Pre-treated fresh air + fan-coil

Other Service Rooms

Low pressure centralized treatment. A static heating circuit will cater for:

occasional heat requirements

heating of passages

heating of glazed zones in order to prevent condensation

Garages

Ventilation will be designed in such a way so as not to exceed the maximum carbon oxides concentration threshold.

U Hotels & Resorts EU Technical Standards Manual

Page 445 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

COLD PRODUCTION

Chilled Water Production Sets

Type of chilled water production sets:

o Unit discharge capacity < 600 KW: piston set

o Unit discharge capacity > 600 KW: centrifuge or worm set

Coolant fluid: The system will utilize fluids, the ozone depletion factor of which is the lowest available on the market such as HFCs (e.g. R125,

R134 a…mixtures). CFCs and HCFCs are forbidden.

As an indication, the absolute minimum nominal capacity is minus 1000 calories/sec/room, to be multiplied by 2 for the installed capacity.

NB: 1 KCAL = 3.97 BTU = 4186 J = 4.18 KW × S

Number of chilled water generators:

o total discharge capacity < 3,000 KW N = 2

o total discharge capacity > 3,000 KW N = 3

o in addition to the previous sets, there will be a supplementary piston set of capacity equal to 30% of the unit capacity of the main sets

Control equipment:

o thermostatic release valve

o step-by control with minimal and maximum contact thermometer, dial thermometer for cold water

o antifreeze protection thermostat

o high and low pressure safety device

o oil pressure monitor

A cabinet containing the equipment with operating and breakdown indicator, manometer, relays, fuses, cables, etc.

A starter with autotransformer system enabling the start-up intensity to be restricted to 3 times the operation intensity.

Throughput monitors for chilled water circuits and condenser cooling water circuits, which automatically stop the compressor if there is no

circulation.

Sound breakers: these units will be placed on anti-vibration bases with flexible collars inserted for connections to hydraulic networks.

In general, sets will provide pre-heating of hot domestic water supply by recover of heat with double condensers.

U Hotels & Resorts EU Technical Standards Manual

Page 446 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Air Cooling Units (cooling towers)

Number of items of apparatus: 2 as minimum each having 70% capacity.

Preferably water towers (except in countries where water is scare or expensive, where air condensers will be provided).

o Equipment to be provided:

o a stainless steel basin will be equipped with a salinometer controlling an electromagnetic valve for reducing concentration of mineral

salts and a supply cock with float

o antifreeze safety device

o drains

Location takes into account visual nuisances due to steam and mist and sound nuisances. If there is risk of noise nuisance, install sound traps.

In all sites exposed to dust (for example from sand winds) and in all cases for cooling of heat pumps circuits, provide “closed” air cooling

systems in which the cooled water is not in direct contact with the atmosphere.

o Water supply:

­ metering

­ treatment to obtain 0 total hardness and pH> 8.5

­ treatment against bacteria

­ algaecide treatment

­ pre-heating of domestic hot water

All components will be specially protected against corrosion and will be fireproofed.

U Hotels & Resorts EU Technical Standards Manual

Page 447 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

DISTRIBUTION NETWORKS AND TERMINAL EQUIPMENT

Ventilation Network

Ducts:

Ducts will generally be of galvanized sheet metal.

Inspection flaps:

o every 3 m for extraction systems requiring periodical maintenance (kitchens)

o in line with each fire damper, control register, sound attenuator, and change of direction.

Fire dampers:

To be provided where passing through walls or fire resistant floors. Warning systems to be provided for the largest with automatic resetting. Manual resetting for bedrooms.

Diffusers:

These must be equipped with adjustment flaps. Ensure that there is good diffusion (for examples avoid having jets of cold air directly aimed at head of people). Positioning and quality of diffusers to be adaptable to decorative conditions in bedrooms and public rooms.

Fans:

These will be mounted on bases with anti-vibration materials and will be connected to the ducts by flexible collars

all blower fans, handling station fans and extraction fans will be centrifugal fans

kitchen extraction fans will have a drain at a low point in the shell.

Air-handling units:

These will have a double envelope of galvanized sheet metal, with 50 mm insulation of glass wool. Assembly by stainless screws.

Air humidification (if necessary):

o by direct projection of saturated steam in the event of low pressure steam being available (can be considered also vial special electric

boiler unit)

o also possible by evaporator

U Hotels & Resorts EU Technical Standards Manual

Page 448 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

o overflow and drain pipe to be provided in tanks. The water supply quality will comply with 0 total hardness and pH > 8.5. It will be

treated against the development of bacteria.

Filtration:

o 2 sets of filters

o the first filter to have interchangeable front elements (efficiency of 90% in ASHRAE gravimetric test)

o the second will be a bag filter

U Hotels & Resorts EU Technical Standards Manual

Page 449 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Water Networks

Piping:

See requirements for sanitary plumbing networks. PVC piping may also be used. Preference may be given to the umbrella system.

Valves:

To be installed:

o at all connections to main piping

o at all pumps and generally all items of equipment

o for all tanks

Pumps:

One pump always to be provided as a stand-by.

Air bleed points and sludge drains:

o air bleed points to be created at high points on covers, with drain valve

o at low points of columns: sludge collection pots with drain cocks

o main boiler plant collectors to be equipped with drains

Paint:

Paintwork to be in standard colours for piping with signs for fluid movement direction.

Insulated piping will be identified by rings of appropriate colour, made of adhesive strip or painted on and placed every meter on the running

portion and at the location of any obstacles such as valve, cocks, passages through walls or floors and changes in direction.

Indication of direction of circulation of fluids to be given by arrows, particularly where there are obstacles (essential for valves and stopcocks).

Literal indications as to the exact nature of the fluid are to be given by tags or direct inscriptions.

U Hotels & Resorts EU Technical Standards Manual

Page 450 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Insulation

Insulation to be provided for hot water and chilled water and steam, including for valves, tanks, and pump bodies.

The insulation is to be resistant to impact.

All treated air ducts will be insulated or double lined. Recycled air ducts passing through non-air conditioned rooms and intakes of external air

in cold climates must be insulated.

Insulation must comply with local fire regulations, and must be of a type which withstands moisture. A continuous vapour barrier is

compulsory for all-cold air ducts and chilled water pipes.

Preference may be given to the system of pre-insulated piping.

Fan-Coil Units

Fan-coils will comprise a galvanized section frame to which will be fixed:

the heat exchange batteries (one for heating, the other for cooling)

a silent operation outward flow turbine with three blowing speeds (below 35 dB (LnAT) in bedroom for speeds3, 32 dB for speed 2, 30 dB for

speed 1)

an insulated tank for condensation recovery, with drainage to a recovery network (plastic with adequate slope)

a dry-operating regeneration type filter

the batteries will be of copper tubing with aluminium fins

The equipment will consist of two versions:

horizontal presentation without body for installation in false ceiling (bedrooms)

vertical presentation with body for wall mounting

4 position control box (stop + 3 speeds).

acoustics: See section C-21 Sound Insulation.

Economic cycle A: in countries of groups 1 and 2, air conditioning systems using recycled air will be investigated in order to operate on an

economic cycle.

This cycle uses the possibilities of free cooling in the intermediate season, taking in up to 100% of direct external air.

U Hotels & Resorts EU Technical Standards Manual

Page 451 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Control System

Advanced control systems for VRV indoor units

U Hotels & Resorts EU Technical Standards Manual

Page 452 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Centralised control systems for VRV indoor units

Up to 64 groups of indoor units (128 units) can be centrally controlled

Optional controllers for centralised control can be combined freely and a system can be designed in accordance with building scale and

purpose.

System integration with various air-conditioning peripheral equipment, such as a Heat Ventilator, is easily made.

Wiring can be run up to a total length of 2 km and adapt easily to large-scale system expansion.

U Hotels & Resorts EU Technical Standards Manual

Page 453 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ELECTRICITY

General Notes

Transformation – High Voltage Equipment

General Low Voltage Panel

Cabinets

Distribution

Safety Lighting

Emergency Generating Sets

Lightning Protection

U Hotels & Resorts EU Technical Standards Manual

Page 454 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GENERAL NOTES

The building will be supplied via a transformer station which will contain the transformers, each of which supplies a set of general low voltage

bars.

Emergency power supplied by the generating set will be input at the low voltage bars set.

Links between the generating set and the general low voltage panel must be as short as possible.

Installations must be designed to operate on a sector basis, in order to guarantee vertical and horizontal selectivity for medium and low voltage

with default to ground or short circuit.

This means that protection devices are calibrated and have the necessary cut-off powers to ensure that only the item of equipment located

directly upstream of the fault is triggered.

As a standard the neutral will be grounded.

All protections in the general panel and in the secondary panels will be by means of circuit breakers, including protection for secondary outlets

provided by modular circuit breakers.

Voltage drops in the networks must not exceed the following limit between the low voltage terminals of the transformer and the remotest point

in the installation:

o 2% for lighting and sockets

o 3% for power.

All electrical equipment will be designed to take into account the climatic conditions of the site.

For any tall building (the height of which is more than 28 m), 2 low voltage panels must be provided, supplying the safety installations. If one

of these panels loses current, an automatic converter switches the supply to the other panel. A 2-hour fire retardant bulkhead must separate the

two panels from each other.

U Hotels & Resorts EU Technical Standards Manual

Page 455 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Below is a sample of a Single Line Electricity Diagram

U Hotels & Resorts EU Technical Standards Manual

Page 456 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Electricity System Diagram

U Hotels & Resorts EU Technical Standards Manual

Page 457 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Electricity System Diagram

U Hotels & Resorts EU Technical Standards Manual

Page 458 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Electricity System Diagram

U Hotels & Resorts EU Technical Standards Manual

Page 459 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Electricity System Diagram

U Hotels & Resorts EU Technical Standards Manual

Page 460 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Electricity System: MDB and Generator Room

U Hotels & Resorts EU Technical Standards Manual

Page 461 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

TRANSFORMATION – HIGH VOLTAGE EQUIPMENT

General Provisions

The supply and transformer stations will contain, unless indicated otherwise by the distributors:

switched input cells according to type of distribution

1 metering device and general high voltage circuit breaker

transformer protection cells

transformers

The supply station and transformer station will preferably be located in the same room, or in two adjacent rooms.

Failing this, the transformer station will be supplied via 2 looped medium voltage cables.

Constitution and Equipment

The installed transformer capacity will be as calculated from basic capacities, using packing factors and multiplied by 0.8, plus 50% increase.

If there is no recommended requirement, the transformer station will be composed of pre-fabricated cells.

The insulating voltage and the breaking power will be matched to the distributor’s network.

The cells will be equipped with regulation mechanical locking systems and protection screens, as specified by the distributor.

The front panel of the cells will contain the synoptic diagram of the installation created in aluminium strips, with invisible fixing and engraved

inscriptions clearly indicating the nature of the cell and function of the control equipment.

The unifiliar diagram of the station will be placed in a frame underneath transparent plastic film.

U Hotels & Resorts EU Technical Standards Manual

Page 462 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Transformer Room

U Hotels & Resorts EU Technical Standards Manual

Page 463 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GENERAL LOW VOLTAGE PANEL

Shell

The entire low voltage panel will take the form of pre-fabricated cells

The units will be of steel protected against corrosion and coated with two layers of glycerophtalic paint.

Separate metering systems will be provided for:

o laundry

o chilled-water/cold production and air-handling units

o kitchen (if using electricity)

o extractors

Electrical Equipment

General circuits leaving the low voltage panel will be separated:

o on the one hand into power circuits (1 circuit per installation the capacity of which is≥ 30 kVA)

o on the other hand, socket and lighting circuits.

The minimum insulation voltage will be at least 500 V.

Circuit protection equipment will consist solely of circuit breakers. All circuits are individually protected and switched.

All equipment must carry short circuit currents during the time needed for operation of protection.

In particular, where protection is provided via a fuse with associated circuit breaker with high breading power, fuses must be calibrated to act

before the short circuit intensity has reached a figure that will be dangerous for the circuit breaker.

Total selectivity must be guaranteed between protection of supply and protection of outlets.

Distribution will be made in such a manner as to identify inputs and outputs.

U Hotels & Resorts EU Technical Standards Manual

Page 464 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Measuring Apparatus

Measuring units will be recessed into the front panel of the cells.

The following equipment will be provided:

o 1 indicator voltmeter per set of bars with commutator including an “off” position

o 1 indicator ampere meter per phase

o 1 3-phase power factor indicator.

Installation Balancing

The power factor of the installation will be automatically raised to the figure required by the local distributor.

This installation will comprise a battery of protected condensers, with non-flammable dielectric insulator placed in a low voltage panel cell and

provided for each power transformer.

The batteries must be capable of carrying voltage exceeding their nominal voltage by at least 10% without damage.

The insulation level will be 3 kV.

Each battery will be equipped with an integral discharge device.

Power Allocation

Outlets from the sets of bars will be distributed so as to balance the load on transformers. A mechanical locking system will prevent

transformers from being placed in parallel.

U Hotels & Resorts EU Technical Standards Manual

Page 465 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CABINETS

General Remarks

Secondary panels established for each zone will have general protection for lighting.

All circuits will be linked to ground without exception. At all points the ground resistance will be below 100 Ohms

In general, secondary circuits will be sub-divided in such a way that each monophase circuit supplies no more than 8 light points or 8 10/16 A

sockets.

Circuits will be loaded to maximum of 70% of their capacity.

Circuit breakers will be preferred to fuses.

All socket circuits and bathroom circuits will further be protected by 30 mA differential circuit breakers.

All other circuits will further be protected by differential circuit breakers, rated as adapted to the installations, individually or by group of the

same nature.

All panels will be designed to have 30% spare outlets.

The unifiliar diagram for the panel will be placed under plastic in the cabinet.

The hotel building itself (rooms) will be supplied by one or more floor panels set up in wall-mounted cases with distribution by conduit to the

bedroom protection panels located in cases placed between 2 bedrooms.

Metering = see section 3 above.

Floor Panels

Floor panels will be constructed with a frame, painted with one layer of anti – rust paint and 2 coats of glycerophtalic paint, carrying all the

equipment.

This frame will be mounted either in a polyethylene case forming a cabinet with a door, which is lockable, where the panel is of the visible type

(in particular in technical rooms and general services), or directly within a masonry shaft, with lockable door for other building distribution

panels. Accessibility of equipment in the shafts must be ensured.

The frame should be equipped with horizontal rails that can be adjusted for height and depth. The rails will carry all the equipment.

Inputs and outputs will be done through clamped terminal strips.

Metal labels fixed to the front, below each control or protection unit will identify all circuits.

Cabling will run through a plastic trough placed in the same plane as the equipment, so as to be easily accessible.

One output per bedroom is necessary.

General services for each floor will be supplied from the floor panels.

U Hotels & Resorts EU Technical Standards Manual

Page 466 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Bedroom Panels

Function:

Each panel will have at the in lead and for each room a general switch, a thermal circuit breaker, and a 30 m amp differential type modular

circuits’ breaker. There will then be 5 outputs per room:

o 1 lighting output

o 1 output for fan-coil and refrigerator, TV and desk in the suites

o sockets, independent of the general switch

o 1 output for sockets

o 1 output for the bathroom

o 1 output for bathroom emergency light point

For each room, at least these 5 circuits are to be provided. They are protected individually by micro circuit breakers.

(Also refer to Chapter C2)

Constitution

They are located in a position not normally accessible to guests.

They will take the form of a PVC box that will be impermeable to jets of water and will be connected through the bottom.

The internal frame will be equipped with rails carrying the equipment.

Below a sample diagram of an in room RCU (Room Control Unit)

U Hotels & Resorts EU Technical Standards Manual

Page 467 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 468 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Technical Rooms’ Panels

Technical room panels will have on the front all the warning lighting and the control switches and push buttons.

Safety Panels

Safety equipment will be supplied via special panels, which are fire resistant and which comply with the relevant fire standards.

U Hotels & Resorts EU Technical Standards Manual

Page 469 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

DISTRIBUTION

Lighting Levels

The lighting levels to be observed in the various rooms are defined below:

U Hotels & Resorts EU Technical Standards Manual

Page 470 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Packing Factor

The packing factors to be used in determination of networks are as follows:

o terminals, power, lighting, sockets circuits 1

o general lighting and sockets circuits 0.9

o general power circuits 1

Power determination

o Lighting : power consumed

o 2-way sockets:

­ 2 × 10/16 A : 100 W

­ 2 × 20 A : 500 W

­ 2 × 32 A : 1500 W

Specialist equipment and sockets will be counted respectively for their power consumed and their nominal rating.

Conduits

General networks

Cables will be placed in cable runs in passageways and in vertical shafts, identified.

Sheaths will be used passing through walls and floors.

In shafts, they will be separated from the water circuits and the low voltage circuits.

In public rooms and guestrooms, networks will be embedded in sleeves with cables identified. Fire-resistant cables and panels must feed all

emergency installations.

Secondary networks

From the secondary panels, these will be PVC insulated unarmoured cable (fire-resistant for emergency installations).

They will be set into the false ceiling, in a cable track for public rooms, or in tubing.

Safety networks

In tall buildings (more than 28 m high), safety installations must be supplied via fire resistant cables, each installation being supplied by two

cables.

U Hotels & Resorts EU Technical Standards Manual

Page 471 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Sockets

Surface-mounted:

These will be of two types:

o in wet service rooms: PVC waterproof units, fed via visible conduit and supplied with the corresponding plugs.

o in technical rooms: metal industrial type sockets, supplied with the corresponding plugs.

Recessed, flush-mounted type (all public rooms and other service rooms):

o Secured by screws.

o The twin sockets will be mounted on a single insulation backing plate.

o Shaver sockets will be of the International, multiple-pin type, with safety transformer (dual voltage).

Switches

The mechanism will be of the silent type.

o Surface mounted:

o Placed in technical rooms and wet service rooms. Waterproof, PVC, fed via surface mounted conduit.

o Flush (all public rooms and other service rooms): Attached by screws.

Light fittings

Light fittings will be selected to:

o guarantee illumination with the best possible yield in the specific conditions of the room and the use to which it is put,

o be sturdy, easy to maintain and of pleasing appearance,

o comply with safety conditions.

For general illumination, the uniformity factor must not be below 0.8.

The position and type of light fittings will be such that there is negligible glare.

All the above data will be valid apart for rooms having accent and decorative lighting. For such rooms, it is essential that a lighting specialist

should be consulted (public rooms and guestrooms).

The colour – rendering index of sources will lie between 70 and 85.

For bathrooms, one may use either incandescent lamps or fluorescent lamps with “luxury” white tubes having a colour rendition index of 95.

U Hotels & Resorts EU Technical Standards Manual

Page 472 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Light fittings will selected in relation to the rooms in which they are placed (dust, humidity, impact resistance, electrical safety, double

insulation within 60 cm of showers, category for thermal behaviour) and must not give rise to noise. The number of different fixture types will

be restricted to those most suitable, as standardization must be aimed at.

Access to bulbs and accessories must be easy for exchange and maintenance.

In public areas, light fittings must be of incombustible materials in any tall building (above 28 m), or difficult to ignite in other cases.

Ease of cleaning must be ensured.

Dimmer switches for public rooms:

Dimmer switches installed in emergency circuits will have a device which, if current is interrupted in that circuit, will short circuit the dimmer

switch and the main switch and will give 100 % illumination for the circuit.

Their capacity will be adjusted to the room concerned. Special research must be carried out if involving fluorescent tubes.

Positioning of dimmers will be chosen in a discreet manner.

U Hotels & Resorts EU Technical Standards Manual

Page 473 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SAFETY LIGHTING

Location

Passageways, exits and emergency exits will be identified by battery-fed safety lighting fixtures of the 60 lumens type.

The battery-fed safety lighting fixtures will have notices “exit”, “emergency exit”, “→” according to disposition. Apart from the regulation

position, certain fixtures can be placed lower down, in order to facilitate evacuation in the case of explosion or fire.

Nature

In general, safety lighting, unlike emergency lighting (see below) will be of the non-permanent type, except for the ballroom where such

lighting, according to the equipment and classification of the building, must be of the permanent type, with emergency power supply and buffer

batteries.

Start-up in the event of any breakdown in the power mains supply will be undertaken via a remote-control device acting on all the fixtures in

the same installation.

U Hotels & Resorts EU Technical Standards Manual

Page 474 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

EMERGENCY GENERATING SETS

Installations to be Protected

Installations to be protected by generating sets will be as follows:

o auxiliary units of the generating sets

o lighting in passageways, public rooms and technical rooms (1/3 of each installation including safety lighting fixtures and safety lighting

in general.

o ambient lighting in bathrooms (1 point)

o firemen’s public and service elevators necessary for safety

o a minimum of 1 public + 1 service elevators, with other units being brought down to ground floor level (with time delay starting).

o all extraction fans

o distribution of hot and cold water for domestic use.

o circulation pumps

o booster pumps (and fire boosters)

o mechanical smoke removal devices

o lift pumps

o fire network pumps

o cold rooms and cold stores

o certain kitchen equipment (see section C 14 Kitchens) and 50% of kitchen lighting

o all low voltage installations, including the Fidelio Opera Express connections and all I.T. equipment.

o computerized cash-registers and the electronics management system (P.O.S, P.M.S).

o detection, alarms and monitoring system, control room (B.C.S),

o indication of positions of fire dampers and of elevator fire doors.

o automatic doors

Installations which are not protected will be automatically cut off as soon as there is a power mains breakdown and the generating sets start up.

Fire safety installations will be given priority supply.

U Hotels & Resorts EU Technical Standards Manual

Page 475 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Number of Sets

Where a building is less than 28 meters high, for protected installations operations a single set will be provided if the protected P <400 kVA,

and 2 sets if protected P >400 kVA.

If the building is more than 28 meters high, or should it be essential for the electrical power plant to operate continuously (low reliability of

distributors’ supply network) at least 2 generating sets will be provided, each capable of:

the first to provide supply to building safety installations

the second to provide supply to protected building installations.

In that configuration, the protected installations are automatically cut off in the event of breakdown of one of the sets.

Set Specification

Engine:

The diesel engine will be of the low or medium speed type, designed for hard work and using diesel fuel. The average consumption must be

below 170 g/hp/h.

The intake system will be of the supercharged type, with maximum 60% supercharging rate.

The engine will be designed for easy access and will have at least individual cylinder heads and lateral doors that allow piston rods and pistons

to be assembled without doing more than removing these doors.

Engine pre-heating will be carried out by electrical resistances which are immersed in the cooling water circuit on the one hand and by a

water/oil exchanger for the lubrication circuit on the other hand.

The engine will have a cartridge air filter which must keep back 85% of particles with a diameter of more than 5 microns.

Each engine will be equipped with an electronic speed regulator.

The instantaneous variation in speed after a sudden variation from full load to zero, or conversely, must not exceed 10% of the nominal value

and the speed must be brought down within steady state speed limit ( + 2%) in less than 3 seconds.

The variation in speed figure will be between + 2% as between no load running and full load running.

In all cases, the speed will be stabilized without pumping after 5 seconds.

Hoods will protect the flywheel, as well as all moving parts.

U Hotels & Resorts EU Technical Standards Manual

Page 476 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Cooling:

An air-cooling tower for each set will be located outside and will be designed for permanent operation compatible with the temperatures at the

site.

It will be made of non-corroding material or protected by metal treatment against corrosion.

Start-up of the cooling tower fan will be linked with operation of the set. The cooling tower will be stopped during start-up of the engine until it

reaches operating temperature.

An expansion tank will ensure that the cooling circuits are constantly filled.

All piping between the thermal engine and the cooling tower will be made of seamless steel tubing.

Minimum hourly surcharge of 10%, every 12 hours in the climatic conditions of the site.

Alternator:

The alternator will have the following characteristics:

continuous operation

vacuum impregnation

screen protected rainproof protection

heating up below 100˚C

accuracy of no-load or on-load regulation for nominal power factor of 0.8 f or sudden variation in normal loading, current will be re-established

in less than 0.6 seconds

surcharge: 10% for 1 hour every 12 hours without permanent heating

harmonic distortion between phase and neutral <1%

total harmonic distortion, including harmonic 3 <3%

Load ballast:

In order to carry out operational tests of the set at 40% minimum load, load ballasts (power = 40% minimum of set power) made up of stainless

steel resistances (18/8) are provided to operated cooled by forced ventilation.

Maximum heating up will be 250˚C and the fusion point will be above 1,300˚C.

U Hotels & Resorts EU Technical Standards Manual

Page 477 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Start-up:

The generating set will have automatic starting, in the event of power mains breakdown. Power flow will be established in less than 10 seconds.

Stoppage when the power main is recovered will be carried out with time delay of:

o minutes at normal speed

o minutes at decreasing speed

Compressed air system:

This system will be used for engines having power above 500 hp.

Capacities of air bottles will be sufficient to give six start-up tests without refilling.

The air will be supplied via an automatic starting electric compressor, which will allow the reserve to be filled in a maximum of one hour and in

an emergency by a compressor driven by a diesel engine.

The air bottles will be equipped with valves, safety valves, and manometers, with isolation cock.

The inside of the bottles will be treated so as to prevent any oxidation.

Electrical system:

The system is used for engines with power of under 500 hp.

The electric starter will be supplied from a lead battery. Capacity will be sufficient to give six start-up tests without recharging.

The charger will operate automatically and will have 2 conditions: charging and maintenance.

It will be designed to carry without deterioration:

o the output obtained with low battery

o a clear short circuit at the use terminals.

U Hotels & Resorts EU Technical Standards Manual

Page 478 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Emergency system:

Whatever the starting system, an emergency starting system must be provided.

Cut-off:

If there is a breakdown in power supplied by the distributor and the generating set starts up, unprotected general electrical panel outputs are

automatically cut off by the contact opening.

If the power mains supply is restored, these outputs will be automatically cut in by closure of the contactor.

Exhaust:

The exhaust system will comprise of:

o one silencer per set, providing attenuation compatible with the two noise levels

o permissible in the different premises of the hotel or in the neighbourhood according to the “acoustic” requirements (see Chapter C20),

o steel horizontal pipe, with sealed expansion collar,

o vertical pipe taken through bronze rollers and expansion device placed in masonry shaft.

The entire exhaust system will be sealed for waterproofing and must not transmit vibrations to neighbouring portions.

It will be insulated so as to restrict the external temperature of the pipes to 80˚C.

The overall pressure drop from the exhaust piping (including the silencer) must not exceed 250 mm water height.

U Hotels & Resorts EU Technical Standards Manual

Page 479 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Sample drawing of Generator Set

U Hotels & Resorts EU Technical Standards Manual

Page 480 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Supply

Storage tank:

The quantity stored must allow for independent operation of the generating plant for 1 day.

Tanks will be of the single wall type, stored in a waterproof concrete pit, or of the double walled type, installed directly in a ditch.

Supply reservoir:

A 1 – day reservoir of 0.5 m³ will be installed in the generating set room and will supply the engine or engines.

It will be connected to the engine by seamless copper tube piping. Flexible hoses will be interposed between the engine and the reservoir, in

order to prevent breakages through vibration.

The reservoir will be automatically filled from the storage tanks by means of electric pumps (2, one being emergency). It will also be equipped

with a manual pump.

U Hotels & Resorts EU Technical Standards Manual

Page 481 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Sample drawing of Storage Tank

U Hotels & Resorts EU Technical Standards Manual

Page 482 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Sample drawing of Storage Tank

U Hotels & Resorts EU Technical Standards Manual

Page 483 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LIGHTNING PROTECTION

A lightning conductor system will be designed case by case, in particular for tall, or isolated structures, and in zones where the keraunic level is

over 25 (or NG max = 2 NG = 2,25 impacts/year/km²) and installed in such a way as to cover all buildings constructed.

As the case may be, and taking into account aesthetic problems, preference will be given to systems in a Faraday cage, or possibly lightning

conductor with arcing device.

It will comprise of:

Copper or stainless steel capturing points, with diameter of more than 18 mm located at the top, on the periphery and on all projecting portions

of roofs. These points will have a maximum spacing of 10 meters (or 15 m) for a height of 30 cm (or 50 cm).

Flat roof conductors (30 × 2 mm), forming a mesh of 15 m maximum and joining the points together (Faraday cage).

Identical vertical conductors, placed at the angles and projecting portions of the building constituting a mesh cage and taking the shortest route

to ground. (Buildings using an exposed and continuous metal framework can use this in lieu of the conductors linking between the points and

the ground).

The conductors will be protected against impact, particularly up to minimum height of 2 m from the ground. Each vertical conductor will be equipped

with a ground measurement bar.

A specific ground connection, with resistance below 10 Ohms, linked to the ground of the electrical installations of the building. This will be

comprised of conductors which are identical to the vertical conductors, arranged in goose foot pattern at a depth of more than 60 cm and having

a length of 2 to 3 m for each vertical conductor, with a linking belt of the same nature (the grounding system for electrical installations,

comprising a loop at the base of a trench, can form this link).

On the other hand, the electrical installation will be protected by an anti- lightning system installed immediately after the main connection

circuit breaker if it is differential.

U Hotels & Resorts EU Technical Standards Manual

Page 484 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

IT & LOW VOLTAGE

Computer Room

Structured Cabling

Unstructured Cabling

Background Music System

Audio Visual Equipment For Conference Facility

Access Control System

Electronic Clocking-on System

Hospitality Information Technology Systems

IPTV System

Automatic Wake-up Call Function

U Hotels & Resorts EU Technical Standards Manual

Page 485 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

COMPUTER ROOM

This room is required to be secured from unauthorized access, under lock & key and has special needs; power supply comes from the emergency generator

grid with independent air condition units in addition or in lieu of the normal AC. The location of the server room can be anywhere as long as the following

considerations are adhered to:

Not below any pipes carrying liquids or which are required to have periodic maintenance

Air ducts serving other areas must not pass through the Server Room

Not adjacent to engineering facilities such as generator rooms, electrical switch gear rooms, air-condition units, any kind of compressors and

electric motor facilities

A location without the risk of damage or exposure to fire, water, heat, dust, corrosive fumes, heat and smoke

Not adjacent to a ‘busy corridor’ area and certainly not in any areas from which the general public may have access to.

The server room must have a raised floor and wide doors (above standard) to allow for equipment to pass comfortably.

The floor immediately above the Server Room must be watertight and any openings in the Computer Room ceiling, walls or floor must be sealed

to the full thickness of the ceiling, wall, or floor.

Walls, floors, ceilings and doorways should have a one hour minimum fire resistance rating carried to the underside of the construction. All

materials used in the construction of the Computer Room including walls, floors, ceilings, raised floors, partitions etc. should have flame spread

ratio of 25 or less. Doors should have a minimum 60 minute fire proof rating.

No signs, directions, or public-facing windows indicating or revealing the presence of the IT&T facility.

Besides industry sized computer racks, steel or metal shelves and metal furniture are recommended (wood and plywood are not suitable)

Room Size

Server rooms for smaller hotels should be between 8-10m² to accommodate all computer servers housed in 42U sized racks (2-3) with following

equipment’s;

o Uninterruptible power supply (UPS)

o Telephone systems (PBX)

o Fire suppression system FM200 or Novem1230

o Air condition, two units to have guaranteed 24hour coverage

o Main distribution frames for data and power (MDFs)

o Working desk with chair and all manuals

U Hotels & Resorts EU Technical Standards Manual

Page 486 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Fire Protection

A special and separate fire protection for the equipment inside the computer room is necessary to protect the systems from fire and water damage caused

by the normal water based sprinkler systems. The gas from this system is non- toxic and not harmful to people. The installation of this system needs to

be performed by a company which specialized in firefighting equipment installation and is recognized by local building and safety authorities. The image

below illustrates the system but may differ from your environment.

It is recommended to use FM200 or Novem1230 clean agent type of system.

U Hotels & Resorts EU Technical Standards Manual

Page 487 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Lighting

Computer room requires 350 Lux

All lights within the room need to be connected to the UPS grid

LED or fluorescent lights in sufficient quantity should be used

U Hotels & Resorts EU Technical Standards Manual

Page 488 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Power Supply

Clean and sufficient electrical power at all times is an absolute requirement. Power is supplied from the common grid, the emergency generator grid and

the UPS (uninterruptable power supply) with battery back-up. A single Phase 3 to 5kVA UPS with battery back-up is required and built into each

computer rack.

The UPS MCB board distributes power to:

o each of the computer racks

o wall socket outlets opposite the computer racks at 1000mm height from the floor which serves for occasional maintenance equipment to

be connected

o all fluorescent lights in the server room

o the fire suppression system

Electrical Ground or Earth Wire:

o It is most important that ALL EQUIPMENT (UPS, PABX, computer racks etc.) are connected to a very good ground connection.

Part of the commissioning of any parts of the IT&T installation is scientific proof of acceptable ground connection.

U Hotels & Resorts EU Technical Standards Manual

Page 489 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Air Conditioning

Systems function best in a cool, dry and well ventilated environment. To assure a stable environment, air conditioning units need to be installed and

function continuously:

The Server Room will have a primary air-conditioning system, usually a ceiling mounted fan coil, supplied from the building central system,

capable of providing a room temperature of 18°C to 20°C (max 23°C).

In some regions the requirement for dehumidification must also be examined to maintain a 40% - 50% relative humidity in the room.

Air ducts serving other areas must not pass through the Computer Room

An independent, back-up air-conditioning unit, usually a split DX system, must be installed and connected to the emergency power grid so that in

case of mains power failure, cooling will continue to be available. A malfunction alarm for the air conditioning unit or a high temperature alarm

for the Server Room must be located where the resort’s fire alarm panel is located to assure this is monitored continuously

Special care must be taken when condensation water returns are installed to avoid these running close to any IT&T equipment

Cable Routing in the Computer Room

The cable routing for both, power and data is from ceiling trays dropped into the racks.

Important: data cables (fibre-optic and copper) require smooth bending radius and appropriate cable trays designed for IT must be used.

Cable damage is the most common and a costly expense in IT budgets.

U Hotels & Resorts EU Technical Standards Manual

Page 490 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

STRUCTURED CABLING

The objective of a structured cabling system is to unify over a single cable infrastructure the transmission of data, voice and video. This cabling system

used the Internet Protocol (IP) signal to transmit the information. The network bandwidth has to be 1 Gigabyte Ethernet and is required to accommodate

future growth and applications such as TV and Video signal which demand high bandwidth. CAT6, CAT6e and CAT7 1000BASE-TX and Single Mode

Fibre Optical cable 1000BASE-LX should only be used.

Systems such as fire detection are considered as independent for technical reasons at this time, and must be covered separately.

CAT 6 and 6e copper cabling (IP)

This cable consists of eight cores copper cable which are twisted around the middle to guarantee data quality. It is also referred to “UTP cable”

or “unshielded twisted pair”.

Each cable can only be run for a total length of 90 meters.

Patch cords or cable between wall outlets and using device should not be longer than 2 meters.

The same applies to patch cords connecting servers to routers and switches.

Special care must be taken when laying the cables in conduits and on cable trays. Conduits and cable trays need to be at least 50 cm away from

electrical power lines and fluorescent lights to avoid electromagnetic induction.

CAT6, CAT6e and CAT7 (1000BASE-TX) cable will comply with standard installation practices regarding bend radius for copper cables. We

recommend you follow these practices closely for all installations, i.e. 4 times the diameter of the cable. The diameter of a plenum UTP cable is

approximately 0.6 cm.

All cables jackets must be Low Smoke Zero Halogen or Low Smoke Free of Halogen (LSZH or LSOH).

Fibre optical cabling (IP)

Single mode fibre optical cable (SMF) 1000BASE-LX must be used when distances above 90 meters are to be covered.

Depending on the cable run location, either an in-door variety or a shielded out-door type needs to be used.

This type of cable usually covers 5 km of distance. It is important to follow the cable manufacture’s cabling and bend radius instructions. If no

minimum bend radius is specified, one is usually safe in assuming a minimum long-term low-stress radius not less than 15 times the cable

diameter.

U Hotels & Resorts EU Technical Standards Manual

Page 491 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Wireless Access Points (Wi-Fi signal distribution)

Ruckus, Zebra, Cisco or Meraki by Cisco branded products should be used to ensure a self-healing and stable Wi-Fi environment.

These products are designed for a large number of concurrent users and seamless mobility within the network.

The set-up consists of a number wireless access points and a single controller.

The selection of the number and models of wireless access points is dependent on each local environment and needs to be determined accordingly

by an authorized dealer.

Wireless Connection Quality Standard

To ensure the wireless connections have excellent quality, the signal strength measured in dBm must be -65 dBm or better in the following

areas

o Guest room: bed, desk, and balcony

o Public areas: lobby area, business centre, restaurant, meeting room, and poolside daybed

Wireless Installation Approach

For typical rooms it is strongly recommended each has a Wi-Fi access point installed.

1 AP (access point) for 2 rooms may be applicable if signal quality meets brand standard.

For lobby, restaurants and meeting rooms or any other high density guest area, high capacity models are recommended.

U Hotels & Resorts EU Technical Standards Manual

Page 492 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SYSTEM DIAGRAMME SAMPLE

U Hotels & Resorts EU Technical Standards Manual

Page 493 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 494 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 495 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

UNSTRUCTURED CABLING

Coaxial Cable for TVs (only if IPTV is not available)

Cable

Drop cable shall be quad-shielded RG6 that meets all fire codes including plenum space, and is equal to or exceeds Belden 1189A specifications.

Drop lengths shall not exceed 250 feet over RG6. If the drop exceeds 250 feet but is under 500 feet RG11 must be used

All distribution exceeding 250 feet, but under 500 feet shall be quad shielded RG11 that meets all fire codes including plenum space, and is equal

to or exceeds Belden 1617A specifications.

If the distribution exceeds 500 feet Times Microwave hard line or an equivalent must be used

Connectors

Connectors shall be LRC snap-n-seal for all coaxial cable. Connectors for hard line shall meet or exceed Gilbert brand.

Splitters

All splitters and directional couplers shall be 1 GHz band pass, rf shielded, externally grounded, low insertion, return, and tap loss.

They shall also be highly isolated.

Public Address System Cabling

Public Address System cabling is determined by the brand and specifications of the system and contractor chosen which forms part of the Fire

Prevention System installation.

U Hotels & Resorts EU Technical Standards Manual

Page 496 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Sample Diagramme of IP Distribution

U Hotels & Resorts EU Technical Standards Manual

Page 497 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 498 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Audio Visual Cabling in Rooms

To minimize cabling, its costs and constraints as well to guarantee a flawless guest experience, a HD (high definition) media hub should be used

to allow guests to connect PC, camera and iXxx to the TV.

These are available from companies such as TeleAdapt and GuestLink.

The units are available in various configurations and can be placed at the desk, the television set and/or the bed side.

Depending on the HD Media Hub configuration the following cabling is required to the HD Media Hub:

o Power (follow power rating from the vendor)

o Internet CAT6

o HDMI cable to the compatible television set

Background Music Cabling and Public Address System (PA system)

The cabling specifications are supplied by the vendors and may vary depending on the distance to be covered.

A public address system centres around an amplifier and from there to speakers.

Connected to the amplifier are microphones and audio players such as CD/DVD player, USB players and background music systems.

Background music systems are personal computer based and receive the music updates over the Internet and are subscription-based. Speaker

zones are defined and playlists are composed to achieve the desired mood music in each area covered.

NOTE; Public address system speaker cannot be used as music speakers. If background music will be plaid through the same system, it requires

to have music speakers.

Public Address System

The public address system is part of the fire, life and safety devices provided by the same company which installs the fire, life and safety

equipment.

The public address system alerts occupants of an impending emergency, sounding an alarm and announcing safety information.

The system must comply with all local codes required for the official operating licenses.

U Hotels & Resorts EU Technical Standards Manual

Page 499 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

PUBLIC ADDRESS SYSTEM DIAGRAMME

U Hotels & Resorts EU Technical Standards Manual

Page 500 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

BACKGROUND MUSIC SYSTEM

The background music systems are used to play appropriate mood music in chosen areas of the operation such as outlets, public areas, gym and guest

rooms. The system must comply with national and international public copyright laws in regards to the public performance acts. The systems must be

configurable to play composed lists of music at certain times of the day and different lists in different locations to create different moods at different

times.

Central System

These systems can be installed and maintained centrally on a PC installed with a soundcard in the same location as the public address system.

The music can be played over the central PA system, however if this is the case the speakers will need to follow music specifications.

All public areas like Lobby, Restaurants, Gym etc., should have their own dedicated music designed for their hours of operation, which is piped

to each PA system in the respective location.

Location Specific System

Some systems are deployed near to the locations where the music is to be played and the background music system is connected to local amplifiers

which connect a local set of speakers, independent of the public address system.

In-Room Music

Basic Set Up

Music Styling Company will provide 5 to 6 genres of licensed music located on a computer in the computer room, close to the MATV

system. This will be fed through the MATV system as individual channels to the IPTV

Advanced Set Up

IPTV will have several in-room entertainment programs included Gaming, TV, Music, Local Info, Newspapers etc. This system would

be interfaced with the PMS system, which could do also handle room service orders etc.

U Hotels & Resorts EU Technical Standards Manual

Page 501 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

AUDIO VISUAL EQUIPMENT FOR CONFERENCE FACILITY

Operating Principles

The ballroom should be divided into 2 or 3 zones, each with its own equipment.

It must be possible to combine all this equipment when the whole room is used.

o The ballroom should be equipped with the following:

o Acoustic equipment for sound broadcasting, divided into several zones

o LCD projectors

o Retractable matt-white screens

The meeting rooms should be equipped with the following:

o Acoustic equipment for sound broadcasting

o LCD projectors

o Retractable mat-white screens

The central audio-video unit located in the sound or technical control room includes:

o Electrical acoustic equipment for recording and broadcasting sound

o An audio/video monitoring system

o An audio dispatcher

o A video dispatcher

Central Audio – Video Unit

The central audio-video unit should comprise of the following:

A mixing console integrated into a worktop.

An audio rack with:

o A branching table bringing together all the returning cables from the different rooms

o Amplifier frames corresponding to the zones of the ballroom or the various meeting rooms

o A graphic equalizer system for the different areas

o Audio monitoring equipment including an amplifier and monitor speakers

o Recording and broadcasting equipment (DVD players)

U Hotels & Resorts EU Technical Standards Manual

Page 502 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

A rack with:

o A branching table bringing together all the returning cables from the different rooms

o A DVD distribution system including high=performance distributors compatible with all the composite signals

o A monitoring system comprising a selector and a monitor

Installation in the Rooms

Lighting control panel (comprising switches, dimmers and pre-programmed controls) located next to the entrance.

Audio visual equipment, installation and training on the operation should be performed by a professional audio visual consultant.

The equipment should be completely independent with a zone-based installation and should comprise the following:

All rooms:

o Speakers flush-mounted into the false ceiling, minimum power of 4 watts, with a rigid metal grille

o Conference cabinets (see chapter C-12, ballroom and meeting rooms). These cabinets, located on all 4 sides of the rooms, provide the

following:

­ telephone connection points

­ video connection points

­ audio and video fold back connection points linked to the control room

­ electrical points

­ protected power outlets

­ microphone connection points

­ “raise” and “lower” controls for the screen (which is flush-mounted in the false ceiling)

­ closure control for the blackout curtains

­ LCD projector control

­ slide projector control

Ballroom

High performance ceiling mounted projector(s), HDMI connectivity, 3,000-5,000 lumens, up to 300 inches (7.6m) diagonal projection,

native resolution XGA 1024x768 pixels with Wi-Fi connectivity

Suitable sized, retractable projection screen(s)

Fixed and/or portable LED TV sets minimum 55” (1.4)

Microphones (Podium, Table, Floor) wired and wireless (VHF or UHF)

U Hotels & Resorts EU Technical Standards Manual

Page 503 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Lapel microphone - wireless (VHF or UHF)

6 channel microphone and line mixer

DVD player and recorder

Independent sound system and speakers

Internet (wired and Wi-Fi), telephone and TV connectivity

electrical connection boxes hidden behind hatches in the false ceiling, above fixed suspension bars or plates with double hooks (for

suspending spotlights or lighting bridges)

electrical rails with low-voltage spots, set into the false ceiling around the edges of the rooms

Function Rooms

High performance ceiling and/or desk projectors, 2,000 lumens, 40-246 inches (1-6m) diagonal projection, native resolution XGA

1024x768 pixels, build in speakers

Suitable sized, retractable projection screen(s)

DVD player

Internet (wired and Wi-Fi), telephone and TV connectivity

White/glass boards build in wall, markers

Portable whiteboards W=69” H=52” Diagonal=77” (W=1.75 H=1.35m Diagonal=1.95m) and Flipcharts, Markers

Electronic Whiteboard, W=69” H=52” Diagonal=77” (W=1.75 H=1.35m Diagonal=1.95m)

Fixed or movable LED TV set up to 55” (1.4m)

Internet (wired and Wi-Fi), telephone and TV connectivity

Signage

Display sets up to 21” (53cm) diagonal dimension in function/ball room area

Web-based management with password access control

Multilingual management interface

Presentation management and scheduling

System event log

Presentation playing log

Presentation play/pause/stop control function

U Hotels & Resorts EU Technical Standards Manual

Page 504 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ACCESS CONTROL SYSTEM

As much as possible, key systems should be used to secure administrative and back of house areas, offices, stores etc.

CCTV installation (cameras, recorders, monitors) To save cabling costs and maximize the IP network, it is proposed to use an IP based CCTV system with IP cameras using PoE (power

over Ethernet). At least the following locations need to be covered with surveillance cameras, however it is advisable to contact the

insurance provider to receive further advice:

Front desk

Lobbies and waiting areas

Driveways, access to property

Car park areas

Public area walkways

Pool and recreation areas

Guest room floors

Receiving area

Back of house office area

Back of house corridors and walkways (housekeeping, engineering)

Central Security Surveillance Console

TV screens located in the security room and should comprise the following:

A 50 cm monitor

A multiplexer for 6 cameras with capability for viewing pictures from 4 cameras in separate windows on the monitor or viewing a single

camera in full screen display

A programmable digital recorder

Cameras and Recorders

The cameras installed should be wide – angle video cameras. Cameras in decorated rooms/areas should be integrated with the decor, while

external cameras should be contained in secure, watertight cases.

Cameras should monitor all entrances to the hotel (Employee entrance, car park entrance, and service entrance), emergency stairway exits and

the lobby front desk.

U Hotels & Resorts EU Technical Standards Manual

Page 505 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

The recorders should be of the digital type.

They shall operate continuously so that at all times a record is kept of the image of all cameras in a sequence of at least 24 hours. They

continuously show the date and time on the recorded picture.

Front Desk Alarm System

The Front Desk and General Cashier should be equipped in all cases with an alarm bell system relayed to the security room.

Television Equipment

The television equipment should comprise the following:

HF modulators:

o The HF modulators should be connected to the audio-video outputs of the DVDs by means of suitable connectors.

o They should transmit the information received to the channels of the collective network.

o They should be of the professional type, with rack-type fixing.

1 dispatch board:

o The dispatch board should be installed, with rack-type fixing, to allow easy access.

o It should have at least 3 audio – video inputs:

­ one input should be permanently connected by means of a suitable cable to the ballroom (for meetings, conferences etc.)

­ two standby inputs should be available for external audio-video sources.

Monitors:

A semi-professional – type colour video monitor should be provided downstream of each DVD to allow permanent monitoring of the quality

of the programs transmitted by the audio-video sources.

DVD players : apart from the recording functions they will have the same characteristics and be multi-zoned, for best flexibility of use.

U Hotels & Resorts EU Technical Standards Manual

Page 506 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ACCESS CARD SYSTEM SAMPLE

U Hotels & Resorts EU Technical Standards Manual

Page 507 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Injecting Programs into the Collective Installation

The following should be provided for the transmission of internal programs (30 simultaneous channels) to the collective installation:

o in the case of a collective installation with selective (single-channel) amplification, 3 single-channel amplifier modules corresponding to

the HP frequency of each modulator .

o in the case of a collective installation with wide-band or wide band by band amplification, a multiplexer with a minimum of 3 channels

and the protective features required to prevent interference between the different channels.

The multiplexer output should be connected by means of a Cat 6 cable for injection into the wide-band or wide band by band amplifier.

Preamplifiers and amplifiers:

The necessary preamplifiers and amplifiers must be provided if reception conditions dictate. One of the three following type of amplifiers may

be used:

o selective (single – channel) amplifier

o wide-band amplifier

o wide band by band amplifier

The use of filters may be necessary to eliminate parasitic frequencies arising from other types of transmissions.

U Hotels & Resorts EU Technical Standards Manual

Page 508 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Receivers

Television sets:

39” LCD TVs, with edge back light LED for standard guestrooms

46”LCD TVs, with edge back light LED for suites and bedrooms

Employee cafeteria, recreation room

infra-red remote control

2 HDMI connectors + 2 USB connector

at least 30 pre-selected channels

maximum volume limit in guest rooms

no facility for guests to modify basic settings

The default settings of the television channels should be controlled from the central unit

U Hotels & Resorts EU Technical Standards Manual

Page 509 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ELECTRONIC CLOCKING – ON SYSTEM

The electronic clocking-on system is a micro-computer-based attendance management system interfaced with the property management system,

capable of handling fixed, flexi-time and multiple schedules, and 2×8/3×8 shifts.

The system should comprise of:

o A micro-computer

o A communications card

o Software

o A printer

o Two terminals for reading finger prints or eye scanning in the clocking-on area

U Hotels & Resorts EU Technical Standards Manual

Page 510 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

HOSPITALITY INFORMATION TECHNOLOGY SYSTEMS

Software:

Hotel Guestroom Booking Systems Online hotel reservations are becoming a very popular method for booking hotel rooms. Prior to the internet, travellers wrote, called the

hotel directly or used travel agents to make a reservation which is time consuming and had constant room inventory errors due to the

manual process.

Travellers can book rooms by using several online travel agents to compare prices and facilities at different hotels. Nowadays, online

travel agents (OTA) maintain detailed information about hotels, prices and deals. Many also allow reviews of the traveller to be recorded

with the online travel agent. Online hotel reservations are also helpful for making last minute travel arrangements. Hotels may drop the

price of a room if some rooms are still available, which can be picked up within seconds on the net.

Therefore Absolute Hotel Services has developed with our partners to have the most efficient system to capture more bookings through

the internet, reduce manual work and get fewer errors by atomized bookings.

Due to constant development Absolute Hotel Services put in place a system which is lasting and will be continuously updated by its

partners which does not affect the flow of bookings but actually will enable an increase in booking streams in future as the internet booking

system is constantly evolving.

Partners

Partner / Tool Function

Website by Travelclick Website development, Search Engine Optimization (SEO) and technology support. The website is

managed by the hotel property and supervised by the corporate office.

i-Stay by Travelclick Booking Engine setup and technology support which is interfaced with the (PMS) Property

Management System through the channel manager.

Channel Manager by Siteminder Updates hotel prices and inventories on all Internet platforms like Hotel Website, OTA, GDS and

some online B2B agents etc. at the same time with one entry to be able to adapt immediately to

market changes. Two way interface with the PMS system

Facebook Booking Engine Booking engine through i-Stay on a free basis. If there is a high social activity at site, the engine

could be extended for an additional cost.

Property Management System AHS has partnered with Comanche which provide a complete property management system (PMS)

which does not require interface between front and back of house systems.

U Hotels & Resorts EU Technical Standards Manual

Page 511 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 512 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Comanche International Property Management Solution (PMS)

This solution includes:

o Front Office / Reservations

o Point of Sales (POS)

o Call Accounting

o Accounts Receivable

o Accounts Payable

o Inventory System

o General Ledger

Anti-Virus Software o Symantec Anti-Virus software. This software has been proven not to interfere with the PMS operation.

o The software is installed in two locations, all notebooks, workstations and servers (client) and a manager module on a dedicated

workstation grade PC in the computer room.

o The manager will update workstations and manage virus outbreaks on the network.

o There are two versions to be chosen from: Microsoft-only networks and Microsoft & Linux networks

High Speed Internet Access Control

Recommended vendors & product:

o Forigate products

o Xpossible Internet Access Management software

Human Resource & Payroll System

Recommended vendors & products:

o Orisoft, Cadena

Alternative systems should be compliant with local regulations & reporting needs:

owners/partners should propose systems for our evaluation

U Hotels & Resorts EU Technical Standards Manual

Page 513 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Time & Attendance System It is recommended to use a solution which interfaces to the Human Resources & payroll system to take advantage of data integration of both

systems.

Internet Bandwidth Standards We are physically separating guest internet access and administrative access in our property networks for accessibility and security reasons.

Administrative internet access:

It carries our email and information from the property management. Security is of the utmost importance. We require a minimum

bandwidth of 5-10Mb for administrative internet access.

Guest internet access:

Needs to be quick and free from unnecessary restrictions to guests. To achieve a reasonable level of customer satisfaction both elements

must be at an acceptable minimum standard of bandwidth and Wi-Fi signal strength

Minimum Bandwidth Standards for Guest & Public areas. Back of House systems require min 10 Mbps additional:

20 Mbps bandwidth for up to 100 rooms without function room space

25 Mbps bandwidth for up to 100 rooms with function room space

30 Mbps bandwidth for up to 200 rooms with function room space

40 Mbps bandwidth for over 200 rooms and function room space

All guest access will be landing to the login page as per sample below.

Function room space, public areas and outlets:

U Hotels & Resorts EU Technical Standards Manual

Page 514 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

These require more Wi-Fi coverage to serve a large number of devices in a relatively small area. There is a need to install more Wi-Fi

access points (antennae) than normally required. The minimum standard for function room space and public areas is one (1) Wi-Fi access

point (all recommended brand high density model) for every twenty-five (50) users.

Bandwidth management (Xpossible v.5 or equivalent):

This solution is required to manage the guest internet, even if it is free to guests. It prevents bandwidth hogging by individual users and

manages downloads by bit torrents etc. This product is recommended and mandatory for Thailand hotels and resorts to comply with the

Thai computer crime act. Details at http://www.xpossible.com/solutions.php.

When total usage reaches 75% of available bandwidth, the following restrictions will automatically be applied:

P2P, bit torrent etc. will be restricted to 10% of total bandwidth

Email and Internet browser will be restricted to 60% of total bandwidth

VoIP will be restricted to 30% of total bandwidth

As soon as total bandwidth consumption falls below 55%, all above restrictions are lifted.

Concurrent access per guest room:

In properties where internet access is free of charge, there is no limit of concurrent users under a single user ID.

Commonly there is one User ID per guest room, however upon request there can be multiple user IDs per guest room thus increasing the

number of concurrent devices.

Login process with Xpossible (or equivalent) for guests free of charge:

We propose to have a 1-screen login process for systems managed with Xpossible version 5 which is composed of the screen including

user ID, password and ICT law agreement statement (Thailand only).

U Hotels & Resorts EU Technical Standards Manual

Page 515 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Electronic Mail and Domain Name

Domain Name Registration The AHS marketing department is designated to register the domain name and will set up all necessary pre-opening email accounts and

forward the relevant information to the users.

The TS team will organise Office 365 yearly licenses as official communication platform for the group. After the setting is done the GM

will be responsible for the email accounts. The email administrator login credentials must be sent to AHS Marcom.

Local ISP Electronic Mail Hosting This is not allowed due to safety issues and corporate governance.

U Hotels & Resorts EU Technical Standards Manual

Page 516 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SUMMARY OF HARDWARE AND SOFTWARE REQUIREMENTS FOR A HOTEL INSTALLATION

Due to constant Hard- & Software specification changes the dedicated list within the Pre-Opening Budget will need to be used as updated

guideline.

Item Description Remark

Hardware

Desktop PC Dual Core i5, 4GB Ram (HP, Dell, Lenovo)

Desktop PC Dual Core i7, 8GB Ram (HP, Dell, Lenovo) Night Audit &

Reservations Team only

UPS APC BACK‐UPS CS 500VA/300 Watt 230V

Notebook

Dual Core i5, 4GB Ram (HP, Dell, Lenovo)

Tablet 32 GB – Wi-Fi (Samsung or iPad) For Sales Team usage

Printer HP LaserJet P2055dn (CE459A)

PABX Printer Epson LQ 300 Dot-Matrix

Pay Slip Printer Epson LQ-590 Dot Matrix

Finger Print Scanner (Time

keeping)

Needs to be interface able with the HR payroll and timekeeping system. Depending

on property size it is recommended to have two terminals.

• 1 for check-in

• 1 for check-out

Printer Shared 4in1 for shared office space (copy, printer, scanner, fax)

HP

Xerox

Minolta

Leased on Monthly basis

U Hotels & Resorts EU Technical Standards Manual

Page 517 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Fax General fax unit

Purchasing office, if still

required

Passport Scanner Fujitsu fi60-f (PA03595-B001)

Front office counter

Kids Club Vii Game

X-Box

POS Hardware (Point of Sales)

POS Terminal

Touchscreen including CPU

Posiflex PS 3315E

Win Pro 10 64Bit Eng Intl 1pk DSP OEI DVD

Cash Drawer

Posiflex CR 3100

Guest Check Printer

Epson TM-U220A (Interface : Serial, Parallel, USB)

Bar Printer

Epson TM-U220A (Interface : Serial, Parallel, USB)

Kitchen Printer

Epson TM-U220A (Interface : Serial, Parallel, USB)

Server Hardware

Network Switches Cisco or HP

The objective is to achieve a Gigabyte network with VLAN capability in

combination with copper CAT6 or CAT7 and fibre optical cables. The switches

need to support both cabling types and power over Ethernet for devices such as

wireless access points and security cameras.

Virtualization Platform VMware vSphere 6 Essentials Kit for 3 hosts (Max 2 processors per host)

Subscription only for VMware vSphere 6 Essentials Kit for 1 year

Compulsory

Active Directory - Windows

Server 2016

WinSvrSTDCore 2016 SNGL OLP 2Lic NL CoreLic (for OA server), including

file sharing

Virtualization Backup Veeam Backup Essentials Enterprise 2 socket bundle for Vmware Compulsory

U Hotels & Resorts EU Technical Standards Manual

Page 518 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Windows Server 2016 - (3

licenses) for AD,

HR, File Server

WinSvrSTDCore 2016 SNGL OLP 2Lic NL CoreLic Compulsory

Server for PMS Dell or HP (DL380 or R730 -Dual Processor with 64GB RAM, HDD 300GB x 5,

10 GbE NIC)

Compulsory

Backup Server Dell or HP (DL380 or R730 -Dual Processor with 64GB RAM, HDD 300GB x 6,

10 GbE NIC)

Compulsory

Active Directory Server/

Backup Server /Antivirus

Server

Required 1 server, one for front of house and one for back of house applications.

Recommended brand HP or Dell rack server.

HP ProLiant DL380 Gen9

Intel E5-2620v3

16GB (1x16GB Registered DIMMs, 2133 MHz)

HP Embedded 1Gb Ethernet 4-port 331i Adapter

HP Flexible Smart Array P440ar/2GB

2x HP 500W Flex Slot Platinum Power Supply

Rack (2U), HP Easy Install Rails with CMA

HP 3y 4h 24x7 ProLiant DL38x HW Support

HP 9.5mm SATA DVD-ROM

4 x HP 300GB 12G SAS 15K rpm SFF (2.5-inch)

LTO -5 Tape Drive , 14 x LTO-5 Data Cartridges

Windows Server 2012 R2

Symantec Backup Exec 2014 Server License

1 unit

PC for In-house Music Same specification as the Desktop PC CPU including a Sound Card with minimum

8 channels

PC for Interface such as:

(Comanche & PABX)

(Comanche & Doorlock)

(Comanche & Siteminder)

HP ProDesk 400 G2 SFF Business PC

Win10 Pro 64

Intel Core i5-4570 3.2G 6M HD 4600 CPU

4GB DDR3-1600 DIMM (1x4GB) RAM

500GB 7200 RPM 3.5 Hard Drive

U Hotels & Resorts EU Technical Standards Manual

Page 519 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

(Comanche & IPTV)

and other Interfaces as

required.

Slim SuperMulti Optical Disc Drive

Parallel Port Adapter

HP Serial Port Adapter

Access Points - Hot Spots

Each Guest room will have its private Wi-Fi bubble which connects TV and Phone

at the same time.

Guest Room;

Zebra AP 7502

Ruckus H 500

HP – Aruba 303H

Public Areas;

Anti-Virus/Spam for email Fortimail 100C

Fire Wall, IPSec, SSL VPN,

Antivirus, Antispam

Fortigate 80C

Computer Log (Thailand) Fortianalyzer 100C

Server and accessory rack 42 U

Power supply for tower rack UPS APC 3 to 5 KVA depend on rack content

Work station for the Server

Room to access each server

KVM Switch, Monitor, Mouse, Keyboard

IP PABX NEC SV 9300

Alcatel Omni PCX

Computer Room and IT staff

office items

3-5 Racks 42 U

Raised Floor

Rack mounted UPS

U Hotels & Resorts EU Technical Standards Manual

Page 520 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Air Conditioning Systems

FM200 or Novec1230 - Fire Suppression

Office set up for 1 staff and vendors for repairs and maintenance

Filing & storage cabinets for logs, manuals and spare parts

IT Schematics Rack layout with components.

This is an indication only and components vary from installation to installation.

The PABX (+1 rack or wall mounted) and IP TV head end (+2 racks) is not

included.

Rack dimension to consider for the sizing of the computer room. Two racks for

computer equipment and one rack for a PBX system. Another two racks need to be

added for an IP TV solution.

Kids Club

Wii-Game

X-Box

Software

PC-OS WinPro 10 SNGL OLP NL Legalization GetGenuine Compulsory

Productivity Software Office 365 Compulsory

Email - Hosting Office 365 Compulsory

Antivirus Kaspersky Endpoint Security for Business – Select Compulsory

PDF - Free version. www.xodo.com

Acrobat – PDF

Only selected position

would get licensed Adobe

Acrobat versions.

Marcom Team (only for large

hotels)

Creative Cloud Version of;

Adobe Photoshop

Adobe Illustrator

U Hotels & Resorts EU Technical Standards Manual

Page 521 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Sales Force Sales Force licenses for salesforce.com application Compulsory

HR Software

• OA & Soft system (Thailand)

• Cadena HR Software (Vietnam)

High Speed Internet Access

Control

This solution is required to manage the guest internet, even if it is free to guests. It

prevents bandwidth hogging by individual users and manages downloads by bit

torrents etc. This product is recommended and mandatory for Thailand hotels and

resorts to comply with the Thai computer crime act. Details at

http://www.xpossible.com/solutions.php.

Compulsory

Music Software • Music Styling - Licenses are per Zone As per Zones

U Hotels & Resorts EU Technical Standards Manual

Page 522 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

PMS & POS Software (Property Management System & Point of Sales System)

Comanche Front Office System (charged per key available)

Comanche Point of Sales System

Comanche POS Order station

Comanche kitchen / Bar printer stations

Comanche Call Accounting & Interface

Comanche PABX/PMS Interface

Comanche Two way Interface with Siteminder

Comanche Door lock Interface Onity or similar

Comanche Internet Log Interface Guest password creation (Xpossible)

Comanche Review Pro Interface

Comanche IPTV Interface

Comanche Back Office System AP/AR/GL and financial statement

Comanche Inventory System PU/Inventory/Recipe & Cost Control

Comanche Event Management System

Report extraction Module

Linux Server Operating system

U Hotels & Resorts EU Technical Standards Manual

Page 523 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Server Rack

U Hotels & Resorts EU Technical Standards Manual

Page 524 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 525 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Cabling schematic from Computer Room to Floor Switch and to Guest Room for standard configuration (Guest Network MUST be physically separate

from Back of House network for security reasons)

U Hotels & Resorts EU Technical Standards Manual

Page 526 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Cabling schematic from Computer Room to Floor Switch and to Guest Room in a minimum configuration Guest Network MUST be physically

separate from Back of House network for security reason)

IP TV SYSTEM

The IP TV system consists of TV channel feeds (by cable or satellite dish) into signal converters, distributed via the local area network to a set

top box in the room which connects to the TV set:

IP TV and Music System Diagram

U Hotels & Resorts EU Technical Standards Manual

Page 527 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

UHR information channel is required to be a landing page when TV is turned on in all guestrooms.

U Hotels & Resorts EU Technical Standards Manual

Page 528 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Addendum

Comanche International Configuration Shell

Hotel Description EXAMPLE data:

Hotel Name : Eastin Grand Hotel Sathorn Bangkok Company Name : BTS Assets Co., Ltd. Address: 14/F, TST Tower, 21 Vibhavadi-Rangsit Road, Chomphon, Chatuchak, Bangkok 10900 Thailand Tel: +66 (0) 2 2108100 Fax: +66 (0) 2 2108399 Floor Qty: 32 floors Room Qty: 390 rooms Billing Address: BTS Assets Co., Ltd. 33/1 South Sathorn Road, Yannawa, Sathorn, Bangkok 10120 Tax ID: 3 1014 8040 5 Hotel Logo: Please see separate attached file

Floor Plan Please see separate attached file

U Hotels & Resorts EU Technical Standards Manual

Page 529 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

AUTOMATIC WAKE – UP CALL FUNCTION

General

A program on the hotel PABX should allow programming of automatic wake-up calls at the times required (see chapter T 13 Telephone,

paragraph on Hotel PABX functions).

Programming of wake-up calls should be possible from the reception, by the concierge and the phone operators; the same PBX program should

enable simultaneous wake-up calls to be made to several guests, for example for group departures.

Operation

It must be possible to print out the information on a printer, with indication of the time programmed, guestroom number and wake-up time.

Modifications or cancellations must be possible, with modifications also being printed via a printer.

It must be possible to check the programmed wake-up time at any time.

Wake-up messages should be received via telephone sets, with a rapid ringing sequence, with a second call after a few minutes if the guest does

not pick up the phone following the first call.

The wake-up time, and acknowledgment of receipt of the call when the guest’s handset is picked up, should also be stored and printed via a

printer.

Guest Room Alarm Clock

Guest room alarm clocks are independent individual alarm clocks placed on or flush-mounted in the main bedside table (see chapter C-2 Rooms

paragraph on fittings)

The appearance and exact dimensions should be the decision of the interior designer.

The alarm clock system should be on a 24 hour basis, and the mechanism should have a silent movement.

Wake-up should be programmed by turning a button. Commands should be validated by pressing a switch and a dim indicator light should

come on.

Cancellation or modification of the programmed times must be possible.

Digital clock (Depending on Hotel Program)

In some countries, a digital clock may be incorporated into the television set with adjustable brightness and alarm clock function.

U Hotels & Resorts EU Technical Standards Manual

Page 530 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

In-House Communications (replaces paging)

General:

The most common tool used is a mobile phone with GSM (Global System for Mobile Communications) standards. Local providers will have

deck phone or offer packages which cover the entire hotel.

System:

Indoor coverage is also supported by GSM and may be achieved by using an indoor picocell base station, or an indoor repeater with distributed

indoor antennas fed through power splitters to deliver the radio signals from an antenna outdoors to the separate indoor distributed antenna

system. These are typically deployed when a lot of call capacity is needed indoors. However, this is not a prerequisite, since indoor coverage is

also provided by in-building penetration of the radio signals from any nearby cell.

Users:

Subscriber Identity Module (SIM)

One of the key features of GSM is the Subscriber Identity Module, commonly known as a SIM card. The SIM is a detachable smart card

containing the user's subscription information and phone book.

Depending on package some operators will block this just for internal hotel use by allowing the phone to use only a single SIM, or only a SIM

issued by them; this practice is known as SIM locking.

U Hotels & Resorts EU Technical Standards Manual

Page 531 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

TELEPHONE

Characteristics of PABX

Electrical Power Supply

Alarms

PABX Capacity

Internal Processor

Classes of Service

Attendant Consoles

PABX Hotel Functions

Interface

Dedicated Lines

Connection Cables

Telephone Outlets

Numbering Plan

Billing

Administration and Services Telephone Sets

Guest Services Telephone Sets with Display

Guest Room Telephone Sets

U Hotels & Resorts EU Technical Standards Manual

Page 532 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CHARACTERISTICS OF PABX

The PABX is of the digital technology electronic switching type, with direct connection to the public network.

Equipment is accessed from the front panel. The back panel primarily contains fixed wiring and remains accessible.

The PABX must have an ambient temperature operating range between + 15˚ and 30˚C and a relative humidity rating of up to 80%. It must be

able to withstand temperature changes of + 10˚C per hour and changes in relative humidity of + 10% per hour.

ELECTRICITY POWER SUPPLY

The electrical power supply is connected to the backup power supply.

It consists of two rectifiers (minimum), one output cabinet and batteries which give the installation an operating time of 8 hours minimum.

The batteries are installed in buffer configuration with the chargers to avoid micro cut-offs.

All elements comprising the telephone installation and peripherals (printers, streamers, display screen, etc.) must function without cut-off in the

event of a mains power failure. All these elements are also connected to the backup power supply with an inverter.

U Hotels & Resorts EU Technical Standards Manual

Page 533 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ALARMS

A system of technical alarms is connected to the BCS (see T14), with repeat signals at the telephone switchboard.

These alarms signal the following failures:

o no mains power supply at rectifier

o no 48V current output from rectifier

o abnormally high or low battery voltage

o inverter anomaly

o operating fault affecting PBX/Property management System interface

A printer also prints out a fault report.

PABX CAPACITY

The connection to the public telephone network will be either using individual analogue lines.

When individual lines are used their total number will be:

Total outside (trunk) lines: 0.3 × no. of room-modules + 15

Total internal extensions: 3.5 × number of room-modules + 15% spare capacity

Attendant consoles: number of trunk lines (rounded off to highest number)

40

U Hotels & Resorts EU Technical Standards Manual

Page 534 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

INTERNAL PROCESSOR

The PABX is a stored-program type.

The program must be able to adapt to the specific needs of the hotel during operation.

In the event of a failure, the processor must automatically reload to restore 100% normal traffic.

CLASSES OF SERVICE

All fax, modem and/or internet lines included in the above extension total shall be of the analogue type.

The Guestrooms Ethernet computer lines are not included in the above number, as they function separately from the telephone network system.

(See T13).

Each extension can be assigned one of the following classes of service:

o internal extension (internal traffic only)

o controlled access (access to incoming calls only or via switchboard)

o local or regional access only

o unrestricted access (international)

Extensions can be switched at night to other service categories or the class of service may be changed at pre-programmed times.

U Hotels & Resorts EU Technical Standards Manual

Page 535 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ATTENDANT CONSOLES

Each attendant console can be used independently. The circuits are sized to enable an attendant to process at least five calls simultaneously.

The standard features and functions are available:

o placing of outside or internal call on hold with programmable music-on-hold

o transfer of a call between attendant consoles

o automatic transfer of outside call to busy extension (camp-on) with music-on-hold and programmable message with possible

reconnection to outside call (recovery)

o signalling of waiting calls and room service signalling

o signalling of internal extension called

o signalling of calling extension (at the switchboard, and also at the room service, housekeeper, front desk, concierge, valet)

o trunk line reservation

U Hotels & Resorts EU Technical Standards Manual

Page 536 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

PABX HOTEL FUNCTIONS

The PABX should offer all or most of the following hotel functions:

Night forwarding

Night service

Voice prompts

Internal directory

Abbreviated dialling (single digit)

Voice mail

Message waiting signal

Check in /check out

Room status

Automatic wake-up call (including groups).

VIP code

Conference calls

Feature package transfer

Direct inward dialling

Do Not Disturb

Prepayment

Call parking

Group management

Remote maintenance system

U Hotels & Resorts EU Technical Standards Manual

Page 537 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

INTERFACE

The interface between the Property Management System and the PABX carries the following information:

o billing information

o two-way information on check in / checkout and room status information

o direct inward dialling information for rooms and meeting room extensions

o guest room directory information

o automatic wakeup information.

Guest directory information is entered via the Property Management System.

The Property Management System receives or exchanges data with the PABX on a step-by step basis. The data is stored in both the PABX and

the PMS.

DEDICATED LINES

Access to advanced technologies and efficient maintenance services, dedicated line provisions comprise the following:

o connection to the PABX main distribution frame

o a dedicated line in the BCS control room, connected to the fire department

o a dedicated line in the PABX room, for remote maintenance of the switchboard

o a dedicated line in the reservations office, for remote maintenance of the electronic key system

o 43dedicated lines in the computer room for remote maintenance of IT system (PMS, points of sale, office systems).

The number of dedicated lines required shall be specified by U Hotels and Resorts Management with a technical consultant specialist.

U Hotels & Resorts EU Technical Standards Manual

Page 538 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CONNECTION CABLES

All individual distribution and connections shall be done through a structured cabling system, as described in chapter T14, section1. This will

be rated CAT 6, so that all lines can be reprogrammed for other uses, such as data transmission throughout the whole building.

TELEPHONE OUTLETS

Telephone outlets in all areas must be fitted with international type plugs (ISO = RJ 45), with the same rating as the structured cabling used

(Cat 6).

The outlets used and their connections, will offer the possibility to divide an RJ 45 plug into several units (such as INFRA + duplicators).

In service areas and guestrooms it must be impossible to remove the telephone sets from the outlets without special tooling.

U Hotels & Resorts EU Technical Standards Manual

Page 539 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

NUMBERING PLAN

The numbering plan is adapted to the hotel to make the extension number correspond to the guestroom and floor number (functional

numbering).

Internal numbering uses three to five digits (1 prefix + 2 to 4 digits).

Dialling without a prefix is possible using time-outs.

BILLING

Billing encompasses the following:

o the programmable billing system, which interfaces with the Property Management System.

o billing management from a terminal + printer in the switchboard room.

o a pulse generator (if the local network does not generate pulse).

The centralized billing system must enable display and printout of billing information (billing units ) for:

o outgoing lines (trunk lines)

o direct inward dialling lines (DID)

o individual services (departments)

o internal extensions with breakdown by service/department

o unassigned billing units

o attendant billing units

The system must enable step-by step printout (on the switchboard printer) of the following information:

o internal calling extension

o outside number dialled

o date and time of call

o call duration

o number of billing pulses for the call

o call mode used

o call charges

U Hotels & Resorts EU Technical Standards Manual

Page 540 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ADMINISTRATION AND SERVICES TELEPHONE SETS

The telephone sets used must offer the following features:

programmable fixed and delayed call forwarding

variable call forwarding

camp-on busy extension with call waiting signal on called extension

grouped lines (“hunting groups”) with pre-set or variable call routing

three-way conferencing including 1 trunk line party

off-hook dialling (“hot line”) or automatic call to pre-programmed number

password controlled extension barring

storing of last external number dialled.

U Hotels & Resorts EU Technical Standards Manual

Page 541 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GUEST SERVICES TELEPHONE SETS WITH DISPLAY

These sets have an LCD display which shows the calling room number, guest name, language and status.

This information is entered via the Property Management System; dialogue between the PABX and the PMS computer makes any further data

entry unnecessary.

Simultaneous calls are handled on multi line sets or by extension groups

These telephone sets have a memory for recording of calls which are not immediately answered. The caller receives a recorded message stating

that the call has been recorded and will be returned as soon as possible. Message waiting notification is transmitted to the person who was

unable to answer the call.

This type of telephone is used by the housekeeper, room service, laundry, concierge, front desk, bellboy, restaurants, and health club and

business centre.

GUEST ROOM TELEPHONE SETS

The guest rooms are equipped with two telephone lines. A wall mounted set with off-hook connection in the bathroom is connected to the same

line modem as the telephones in the room, one on the night table.

For suites with three sets, adjustable ring tones are provided for the room extensions and the living room extensions.

The sets do not have a message waiting features as they tend to be of an antique design.

U Hotels & Resorts EU Technical Standards Manual

Page 542 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ELEVATORS (LIFTS)

General

Typical Equipment

Guest Elevators

Service Elevators

Escalators

Cleaning Cradles

U Hotels & Resorts EU Technical Standards Manual

Page 543 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GENERAL

To define the system for guest and service elevators, the following rules should be applied:

Discrimination between guest and service traffic.

Quality of traffic:

o Guest: in balanced, bi-directional service

­ A max. probable waiting time on the landing of 35 seconds

­ A volume of traffic in 5 minutes of at least 10% of the estimated population, i.e.: 1.5 individuals x 0.7 x number of bedrooms,

plus users of possible other premises = number of users of upper floor areas.

These criteria generally entail providing one or two elevators (lifts) per 100 rooms with approximately 4 floors.

o Service: generally, the hotel should be equipped with a number of service elevators equal in minimum to 2/3 the number of guest

elevators.

The speed and other basic characteristics are identical for both.

U Hotels & Resorts EU Technical Standards Manual

Page 544 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

TYPICAL EQUIPMENT

The following gives the equipment corresponding to the traffic criteria.

It allows anticipating equipment based on an initial approximation.

This choice has to be validated by a precise study adapted to each project, taking into account particularly special traffic.

In some cases, it is anticipated to make a choice:

o Regarding the number of cabins, to take into account the type of hotel:

­ resort

­ business

o Regarding the speed, following the number of hotel floors

U Hotels & Resorts EU Technical Standards Manual

Page 545 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GUEST ELEVATORS

Car

The metallic car is composed of:

A bearing frame with support structure, guides and parachute

A noise protected platform. The noise protection is made by rubber pads between the frame and the platform structure. This structure is covered

by a minimum 60 mm thick wood (oak) deck. The top floor covering is required in hard material, such as mat, adapted carpet or marble.

A right angle shaped metallic cabin made of stiffened (or ribbed) panels no connected to the bearing frame. This box is clad with removable

decorative panels resistant to graffiti.

An emergency hatch.

A ceiling made of ribbed panels supporting a decorative false ceiling, including the lighting fixtures (150 lux) and a battery-powered

emergency lighting.

Accessories:

o stainless steel or brass hand bar

o loud speaker connected to the central sound system (for announcement only)

o telephone connected by simple off hooking to BCS control room

o electronic promotional panel for points of sale

o maximum authorized load indication and regulation panel, where applicable

This cabin is decorated by the interior designer in harmony with the decoration of premises and public passageways.

Sliding Doors

The landing and cabin doors will be sliding central opening type, in double-face box structure and soundproofed.

The opening and the closing of the cabin/landing doors will be synchronized and automatically controlled.

The cabin doors will have an electronic detector, detecting from a distance the presence of an obstacle which will cause the door to reopen.

The detection limits the movement of the doors to a minimum and in particular cuts out any unnecessary reopening.

When the closing of the doors is prevented for an abnormal time, the detection becomes inoperative and the doors are closed at a reduced speed

with an audible signal warning passengers.

U Hotels & Resorts EU Technical Standards Manual

Page 546 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

The door opening is never less than 90 cm.

When the cabin is moving, the cabin door and the landing door of the stop level begin their movement of opening during the approach of the

cabin to the self-levelling zone.

Inside and outside finishes: decorative materials resistant to graffiti to be specified by the interior designer. (No paint or brushed or polished

metal).

Manoeuvring

The cars are equipped with a selective collective up/down manoeuvre.

In the case of a full load, a “non-stop” device cancels the landing calls.

All elevators are equipped with a mechanical braking device, functioning automatically in case of excessive speed.

A permanent validity control has to delete automatically all calls when the number of call orders recorded in the cabin is significantly higher

than the passengers it contains.

At rest, at least one elevator stays at the lobby floor level with the doors open.

The equipment includes:

o A car button box with:

­ luminous buttons per floor served

­ one off-switch, in parallel with the alarm bell

­ an alarm button connected to the safety control panel in the control room (with battery)

­ key control (lift boy service)

A luminous and audible car position indicator in each cabin, at the lobby level and at the other public levels, with illuminated figures indicating

the level on which the car is stopped or the level on which the car is passing.

Landing boxes

o to intermediate landings: luminous buttons to go up or down 1 chime signalling the arrival of a cabin

o to the end landings: one luminous button 1 chime signalling the arrival of a cabin

In case of fire or power failure, see chapter T-10 Fire Detection Section 11 (Automatic-controls System), and chapter T-112 Electricity, Section

7 (Emergency Generators).

All lifts must come to the ground floor during a general fire alarm and can only be command override by a fireman switch.

U Hotels & Resorts EU Technical Standards Manual

Page 547 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SERVICE ELEVATORS

Operation

They have to allow:

o Rapid luggage delivery in guestrooms

o An easy passageway for all types of service carts (i.e. cleaning carts, room service carts etc)). Elevators car dimensions and sliding door

clearance will be in accordance with the type of service carts.

o Approximate dimensions (to check with selected suppliers):

Luggage trucks: H 200, L 130, I 70

Room-service tables: L 100, I 75 (folded table) or Ǿ 100 (non-folded table), H100

At least one cabin must be large enough to accommodate a stretcher or coffin (200 to 210 cm long).

o Other transport means, such as:

­ laundry trucks

­ maintenance trolley

­ furniture moving

Cabins

The metallic car includes:

A bearing frame with suspension, guides and parachute

A platform made of iron welded-channels and noise protection made by rubber pads.

A right-angle shaped metallic box made of ribbed panelling

Vertical cladding and ceiling by steel plates with recessed lighting fixtures (150 lux), and battery powered emergency light.

An emergency hatch

A shock-resistant belt all around inside panels

Accessories

o telephone set connected by simple off hooking to the B.C.S. control room

The manoeuvres and controls are identical to those of the guest elevators.

U Hotels & Resorts EU Technical Standards Manual

Page 548 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Machine Rooms (public and service elevators)

They shall be equipped with automatic fire-extinguishing devices (powder), as mentioned in chapter T10 (section 10).

U Hotels & Resorts EU Technical Standards Manual

Page 549 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Typical Car Arrangement

U Hotels & Resorts EU Technical Standards Manual

Page 550 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

U Hotels & Resorts EU Technical Standards Manual

Page 551 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ESCALATORS

Mechanism

The support chassis is made of welded wire mesh with reinforced sections covered with steel sheeting.

The assembly is set on anti-vibration pads.

The drive mechanism installed at the head is mounted on a sliding chassis to allow easy adjustment of the pull chain motor.

The steps are made of lightweight alloy and are anti-skid and interchangeable.

Two flat steps at the top and bottom make it easy to get on and off the escalator.

Emergency Stop

The escalator is equipped with a band brake, the braking torque of which is significantly lower in the up direction than in the down direction, in

order to reduce the risk of people falling when the brake is activated.

A second safety brake makes it possible to directly act on the main shaft.

Safety Devices

The escalator is equipped with easily visible emergency stop buttons. A digital display clearly indicated the source of the shutdown and the

procedure to be followed to return the escalator to service. There is a main switch to put the escalator back into service using a key.

In addition to the emergency stop buttons, safety contacts (break in operating chains contact, separator plate contact, beginning of banister rail

contact) are provided to automatically shut down the escalator in the event of danger.

U Hotels & Resorts EU Technical Standards Manual

Page 552 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

CLEANING CRADLES

Buildings with windows that cannot be cleaned from the inside should be provided with a cleaning cradle (also applicable to interior patios).

Emergency System

Emergency evacuation is obtained either by gravity, with permanent control over the down movement by a speed limiter brake or if possible

owing to the height of the building with a manual hoisting system.

Braking System

This system should provide for:

o electro-brake on the motor

o safety, jaw-type electro-brake operating automatically in case of an increase in the descending speed

o centrifugal type seen-limiter brake, operating if the first two are unlocked by permanent manual action in view of evacuation of the

cradle in case of power failure

Roof Cart

The roof cart is driven electrically and moves on rail.

The guide rollers hold the roof cart along its route along the façade.

Carrier Arms

No electrical conduits are visible along the arms.

At the base of each carrier arm, an electrical contact inhibits any raising or descending movement if the corresponding arm is not in the correct

service position.

Cradle

Built of light metal.

The floor is non-slip.

The sides are at least 1 m high and are extended up to 1.30 m by a handrail.

Protected with rubber foam on three sides.

The cradle should stop automatically at the extreme top and bottom levels

U Hotels & Resorts EU Technical Standards Manual

Page 553 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Anti – Fall System

An anti-fall system is provided via two emergency cables supporting no loads during normal operation.

Building height permitting, an individual protection device of the stop-fall type is provided.

Guidance

In the case of high-rise buildings (with a total height over 28 m), a cradle guidance system is provided on the facades of the building preventing

any horizontal movement or swaying.

Electrical Equipment

Watertight and dust-proof type, with all wiring-connections protected by a stuffing box.

All motors are protected individually against overloads and short-circuit.

U Hotels & Resorts EU Technical Standards Manual

Page 554 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

FF & E (FURNITURE, FIXTURES AND EQUIPMENT)

List of Small Operating Equipment (“OPE”)

List of Operating Furniture and Fixtures

List of Furniture and Fixtures of Decorative Relevance and Fixed Decoration Items

U Hotels & Resorts EU Technical Standards Manual

Page 555 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LIST OF SMALL OPERATING EQUIPMENT ITEMS (“OPE.”)

Small operating equipment items cover the following articles for the different sectors of the hotel:

ROOM DIVISION Room linen/towels

Room chinaware

Room glassware

RESTAURANTS Silverware

Wood-wickerwork

Stainless steel

Restaurant linen

Trays

Chinaware

Ovenware crockery

Chafing dish

Glassware

KITCHEN Food handling/containers

Pots and pans

Cutlery

Kitchen utensils

PASTRY KITCHEN Pots and pans

Shaped cutters

Decor nozzles and pouches

Tins

Pastry moulds

Biscuit trays

Utensils

U Hotels & Resorts EU Technical Standards Manual

Page 556 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

THEME RESTAURANT

Same as the above restaurants, plus specialised:

Wood- wickerwork

Service cutlery

Cutlery

Miscellaneous

Flatware-hollowware

Chinaware

Stone-earthenware

Copperware

Cast iron utensils

Glassware

THEME KITCHENS Same as the above kitchens, plus specialised: Wood – bambooware Pots and pans Cutlery Small equipment Flat-hollowware Earthenware Utensils Copperware THEME PASTRY KITCHEN Same as the above pastry items, plus specialised moulds and biscuits trays EMPLOYEES Stainless steel Linen Trays Chinaware Glassware MEDICAL EQUIPMENT First aid Medical examination room

U Hotels & Resorts EU Technical Standards Manual

Page 557 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

MAINTENANCE

All light tools and minor items of equipment needed for repair, maintenance and security tasks. This list is drawn up with reference to the

equipment and technical installation for each project.

UNIFORMS

Uniforms for all personnel whether in contact with guests or not.

Front of house uniforms be designed and implemented on a property to property basis which should be influenced by the interior design of the

property in terms of style and colour. When planning uniforms the following must always be followed and considered:

o Materials selected should be durable, comfortable and easily laundered which means the avoidance of materials requiring dry cleaning.

Common material mix would be 60-80% cotton and the remaining would be polyester.

o Materials selected should be assured to have continued stock and availability for replacement orders.

o In some cases and locations footwear will be included as part of the uniform.

ITEMS FOR SPECIFIC DIVISIONS

Defined with reference to the specific features of each project.

Depending on contractual conditions, the listing is generally produced by U Hotels and Resorts Management, in accordance with a standard

computerized program.

The basic data is:

o Casual, comfortable and locally infused.

o Maximum of 2 pieces of uniform (shirt and trousers).

o Same uniform for all front of house positions. Exceptions would be the following departments; kitchen, stewarding, engineering, pool &

fitness employees.

Corresponding to the essential features for operation and the brand image standards.

The listing is handed over by U Hotels and Resorts Management to the Owning Company.

LIST OF OPERATING FURNITURE AND FIXTURES (O.F.F E.)

U Hotels & Resorts EU Technical Standards Manual

Page 558 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

The list of basic furniture and fixtures covers all movable furniture, equipment and fittings as well as the elements needed for furnishing and

good operation of the public rooms and the hotel services, in respect of which U Hotels & Resorts wishes to see adopted specific items of

equipment which meet its operating criteria and/or its image.

This list should be done in accordance with the following classification.

1. Rooms division

2. Housekeeping

3. Rooms

4. Restaurants and bars

5. Banquets

6. Administration offices

7. Back of the house and employee areas

8. Vehicles/transportation

9. Leisure facilities

They are complemented by the lists of kitchen and laundry equipment, which are drawn up by their own specific consultants ( as explained in

the introduction).

U Hotels & Resorts EU Technical Standards Manual

Page 559 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LIST OF FURNITURE AND FIXTURES OF DECORATIVE NATURE AND FIXED DECORATION ITEMS

This covers all fixed or movable furnishings and decorative elements for the public rooms, administrative rooms and the accommodation in the

hotel.

Some of the movable items will be shown on the above hotel operating furniture and fixture list as “defined by interior designer”.

On the other hand, any fixed decoration is entirely specific to each project and is totally the concern of the interior designer.

Therefore it is up to the interior designer to produce a comprehensive list of such furnishings etc and fixed or movable decorative elements,

supplementing the decoration plans file. These lists must be coordinated between the I.D. and the owner.

It is particularly important that the architect and interior designer should also provide the specifications and should incorporate into the overall

construction budget all those articles which are not included in the operating furniture and fixture budget or the decoration fixtures and fittings

budget.

U Hotels & Resorts EU Technical Standards Manual

Page 560 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SPARE PARTS

General Notes

Sanitary Plumbing

Electricity

Low Voltage Equipment

Air Conditioning

Kitchen and Laundry

Public Areas

Accommodation

U Hotels & Resorts EU Technical Standards Manual

Page 561 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

GENERAL NOTES

The provision of spare parts at the time of hand-over of the hotel will be an integral part of contracts awarded to contractors.

The precise list will be specified by agreement with the different manufacturers and suppliers of equipment and fittings.

The lists below are theoretical lists given by way of example. Arrangements must be made for the necessary storage spaces for all spare parts.

U Hotels & Resorts EU Technical Standards Manual

Page 562 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

SANITARY PLUMBING

Water Tanks

1 ball cock with float

1 strainer

Booster Pump

1 pressures tat

1 set of cams for permutation

1 anti-vibration collar

Distribution

Cold and hot water

o anti-hammer unit of each diameter

o automatic drain cock of each diameter

Hot water

Production by modules

o regulation thermostat

o 1 safety thermostat

o 1 automatic drain cock

o 1 manual drain cock

o 1 thermometer for the boiler chimney outlet

o 1 level monitor for water top-up

Hot water return

o 2–column base valves

U Hotels & Resorts EU Technical Standards Manual

Page 563 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Drainage

1 separator hydrocarbons sensor

Pumping Up

1 retaining flap of each type

1 level monitor with cable

Sanitary Apparatus and Sanitary Fittings

Apparatus : 1% of each type

Complete tap fittings : 1% of each type

Handle pieces : 2% of each type

Toilet tanks and systems : 2% of each type (bedrooms)

: 3% of each type (public and Employee toilets)

Water Treatment (softener and filters)

1 softener control panel

2 sets of anodes

1 complete set of special valves

1 dosing pump of each type

Irrigation System

1 valve of each type

10 sprinkler heads

3% lengths of piping for each diameter

1 timer of each type

U Hotels & Resorts EU Technical Standards Manual

Page 564 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Swimming Pool – Jacuzzi

1 pump of each type

1 submerged lighting unit

1 rotary valve

2 heating elements for swimming pool heating

1 through-put monitor

1 jet pump (Jacuzzi)

1 thermostat of each type

spare parts for swimming pool cleaning machine

Drainage Network Pump

1 level gauge of each type

1 check valve of each type

U Hotels & Resorts EU Technical Standards Manual

Page 565 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

ELECTRICITY

Supply and Transformer Station

1 set of fuses for high voltage cell

1 circuit breaker of each type

1 pull-out drawer of each type

set of low voltage fuses

Diesel Generating Set

2 fuel filters cartridges

2 oil filters cartridges

2 air filters cartridges

2 sets of joints for maintenance operations

General Equipment

1 set of 10 fuses of each of the calibres and types installed

1 set of the various contactors or circuit breakers used

1 complete set equal to number of indication lamps installed

5% of sockets of each type installed

5% of safety lighting blocks

5% simple, two-way and push button switches and dimmers of each type installed

5 lighting fixtures of each type installed

Switchboards, Power

2% of circuit breakers of each type

3% of contactors of each type

U Hotels & Resorts EU Technical Standards Manual

Page 566 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Dimmers

1 remote control of each type

1 variator module of each type

Bedrooms

2% of circuit breakers of each type

3% of contactors of each type

Electric Switchboards, lighting

2% of circuit breakers of each type

3% of contactors of each type

U Hotels & Resorts EU Technical Standards Manual

Page 567 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

LOW VOLTAGE

Fire Detection (maintenance contract to be established)

10 detectors : 5 heat detectors , 5 smoke detectors

1 feed slide drawer

1 control slide door

Time Distribution

1 clock of each type

3% of guestroom alarm-clocks

Telephones (maintenance contract to established)

1 set of fuses

1 set of push buttons and warning lamps

6 hand sets of each type

1 electronics board for central computer

1 electronics board of each type for the PBX functions

Sound Equipment (emergency amplifier and tuner incorporated into rack)

3 ceiling loudspeakers of each type

T.V. Distribution System

1 modulator of each type

3% of television sets of each type

Audio-Visual system

2 lamps for each type of projector

U Hotels & Resorts EU Technical Standards Manual

Page 568 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

1 printed circuit for motorized projectors

1 remote control

1 case for slide projector

1 sound volume switch unit

1 emergency amplifier

Safety Panels and Alarm Control

1 set of alarm lamps equal to the number of lines

5% of push buttons of each type

U Hotels & Resorts EU Technical Standards Manual

Page 569 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

AIR CONDITIONING

Chilled Water Production

Pumps

o emergency pump to be installed for each type

Cooling units

o oil filter cartridges of each type

o de-humidifier cartridges of each type

Steam Boiler (1 water feed pump to be installed as back-up)

1 manometer of each type

1 thermometer of each type

1 drain sealing joints and cylinder rings for each boiler

1 steam trap of each type

Oil or Gas Burner

1 box boiler relays for each type

2 sets electrodes

2 sets nozzles

2 combustion monitoring photo-electric cells

1 gas injection crosshead for atmospheric burners

Circulation Electro Pumps

1 pump of each type

1 rotary gaskets, if required, per type of pump

Fan Motor Set

1 electronic motor per power range (minimum 5 – maximum 10)

1 set of spare belts for each fan

U Hotels & Resorts EU Technical Standards Manual

Page 570 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

Valves, Fittings, Pipes

2 cocks of each diameter and each type

2 automatic drain cocks

Regulators

3-bedroom temperature thermostats

3-fan-coil regulating valves

2 thermostats, air stats of each type

2 motors and regulating valves of each type

Air Handling Unit

set of air filters for each unit

1 sensor of each type

1 differential pressure switch of each type

Extractors

1 set of grease filters for each extractor

1 set of filters for each fresh air fan

Sundries

10 fan-coil motors

1 set if filters complete for each type

10% (minimum 20) of fan-coil filters for bedrooms or individual heat pumps

10% of nozzles for air washer

5 activation coils for fire dampers and cut-off doors

5 clock face thermometers for fluid insertion

5 clock face manometers

U Hotels & Resorts EU Technical Standards Manual

Page 571 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

1 set of rollers for each type of pump and fan

KITCHEN AND LAUNDRY

The list of spare parts will be produced by U Hotels and Resorts Management along with the supplier, with reference to equipment installed.

PUBLIC AREAS

10% of carpets of each type

5% of fabrics of each type

ACCOMMODATION

5% of fabrics of each type for curtains

5% of fabrics of each type for upholstery

1% furniture elements

10% carpets of each type

5% of curtain rails

1% of lighting fixtures of each type

2% of door locks

1% of floor-standing lamps

5% of wall coverings

5% of light shades of each type

1% of electrical accessories

1% of tiles

2% of corridor lighting fixtures

1% of sanitary fittings

U Hotels & Resorts EU Technical Standards Manual

Page 572 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

TAKEOVER BY HOTEL OPERATOR

Maintenance Contracts

Guarantees

Insurance

As-Built Plans

U Hotels & Resorts EU Technical Standards Manual

Page 573 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

MAINTENANCE CONTRACTS

All indications relating to maintenance of equipment must be mentioned in the tender documents, following which they will then be the subject

of contractual requirement to be met by the successful contractors.

For all installation work, the tendering contractors must submit with their quotation a draft maintenance contract in which they undertake to

guarantee work on the equipment requiring qualified personnel available locally (chilled water production set, heat pumps, generating sets, lift,

automatic exchange, etc.) by the manufacturer or by personnel approved by the owner and operator, for a minimum 5 year period.

The analysis of these proposals will be an element which determines the final choice of the contractors to carry out the operation.

On the other hand, the choice of equipment must take into account availability from stock of spare parts which exists locally. If there were to be

no stock, it would be necessary to add to the list of spare parts a supplementary list relating to the equipment excluded.

GUARANTEES

Any moving equipment (in particular rotating machinery) must be selected taking into account that they must provide uninterrupted service of

8,000 hours without curative maintenance. The manufacturer will have to provide a total guarantee for two years parts and labour and a

guarantee for 5 years for replacement of defective equipment. In addition, contractors must submit with their tenders:

o Diagrams and exploded view of equipment

o A precise and detailed list of the intended equipment.

U Hotels & Resorts EU Technical Standards Manual

Page 574 To reach table of contents, press CTRL+Home for PC/ fn+left arrow for Mac

INSURANCE

Prior to take-over by the hotel operators, the owning company must have taken out the insurance policies specified in the management contract.

AS – BUILT PLANS

One month before acceptance of the work, the contractor must supply a file of as – built documents for the installation actually undertaken.

Acceptance cannot be given within less than one month after hand-over of the documents.