DATE : TRANSMITTAL No. :
04-ago-09 33 70 02.00 10 - 6
TO : U.S ARMY CORPS OF ENGINEERS FROM : CONTRACT No. CHECK ONE :
THIS IS A NEW TRANSMITTAL
THIS IS A RESUBMITTAL OF
TRANSMITTAL
SPECIFICATION SEC. No. 33 70 02.00 10 PROJECT TITLE AND LOCATION CHECK ONE : THIS TRANSMITTAL IS
(Cover only one section with each transmittal) FOR FIO GOV'T APPROVAL
ITEM MFG OR CONTR No. FOR VARIATION FOR
No. CAT CURVE OF CONTRACTOR (See CE
DRAWING OR COPIES SPEC. DRAWING USE CODE instruction USE
BROCHURE No. PARA No. SHEET No. No.6) CODE
(See instruction No. 8)
a. c d e f g h i
5 SD-03 3 3.12.3 N/A A
6 SD-03 3 3.12.6 N/A A
REMARKS.
Standards on page 1.Operating Instructions: Digital Earth Tester on pages 5 to 8.
Operating Instructions: Digital Insulation Tester on pages 6 & 7.
Testing Equipment: Digital Earth Tester on pages 9 & 11.
Testing Equipment: Digital Insulation Tester on pages 12 & 14.
ENCLOSURES RETURNED (List by Item No.) NAME, TITLE AND SIGNATURE OF APPROVING AUTHORITY DATE
ENG FORM 4025-R, MAR 95 EDITION OF SEPT 93 IS OBSOLETE SHEET 1 OF 1
contract drawings and specifications except as other wise stated
ANDRES GALVISCQC MANAGER
CAICEDO INGENIERIA LTDA
SECTION II - APPROVAL ACTION
ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND
Ground - Resistance Tests
Low-Voltage Cable Test
I certify that the above submitted items have been reviewed
in detail and are correct and in strict conformance with the
AIRFIELD IMPROVEMENTS & D/B UPGRADE HANGAR, JUANCHACO, COLOMBIA
DESCRIPTION OF ITEM SUBMITTED CONTRACT REFERENCE
(Type, size, model, number, etc.) DOCUMENT
b.
TRANSMITTAL OF SHOP DRAWINGS, EQUIPMENT DATA, MATERIAL SAMPLES OR
MANUFACTURER'S CERTIFICATES OF COMPLIANCE
(Read instructions on the reverse side prior to initiating this form) ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND
SECTION I - REQUEST FOR APPROVAL OF THE FOLLOWING ITEM
Colombia Project Office
UNIT 5147 APO -
AA 340
CAICEDO INGENIERIA LTDA.
Calle 68No. 4A - 77 Bogotá, Colombia W 91278-04-D-028
Tel 011 57 1 322 11 04
[email protected] TASK ORDER No. 010
CAICEDO ING. LTDA CONTRACT W91278-04-D-0028 TASK ORDER No. 0010
Transmittal No. 6
Specification SECTION 33 70 02.00 10 - Paragraphs: 3.12.3 & 3.12.6 PHASE I – ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND
CONTRACTOR:
Caicedo Ingenieria LTDA
CONTRACT W91278-04-D-0028 TASK ORDER No. 0010 AIRFIELD IMPROVEMENTS & D/B HANGAR UPGRADE
Calle 68 # 4A - 77, Bogotá Ph. (057) 1 3221104, Fax (057) 1 3221105
e-mail: [email protected], [email protected] PAGE 1
Attached to this submittal is the testing data for:
Table 1. Earth and Insulation Testing.
ISS
UE
SP
EC
S &
D
ES
IGN
R
EQ
UIE
RM
EN
TS
PA
RR
AG
RA
PH
SU
PP
LIE
RS
SU
PP
LIE
R
ST
AN
DA
RD
Gro
un
d -
Resis
tan
ce
Tests
The combined resistance of separate systems may be used to
meet the required resistance:
Ground ring - 5 ohms.
3.12.3
Logistics S&S Ltd.
Measurement made with the Digital Earth Tester Model 4105A.
Dust and drip proof.(Designed to
IEC60529 IP54).
Designed to meet IEC61010-1,
IEC61557 safety standard.
Lo
w-V
olt
ag
e C
ab
le T
est
Low-voltage cable, complete with splices, shall be tested for
insulation resistance after the cables are installed, in their final configuration, ready for connection
to the equipment, and prior to energization.
The test voltage shall be 500 volts dc.
The minimum value of insulation shall be:
R in megohms = (rated voltage in kV + 1) x 304.8/(length of cable in meters).
R in megohms = 0.3418 For both lighting circuits 1 & 2.
3.12.6
Logistics S&S Ltd.
Measurement made with the Digital High Voltage Insulation Tester
Model 3125.
IEC 61010-1 CAT.III 600V, pollution
Degree 2. Safety Standard. IEC 61557.
Wide range from 500V to 5000V and
up to 1000GΩ.
Polarization Index measurement (PI).
Timer Measurement functions. R in megohms = 204MΩ Circuit 1.
PI = 2.41 R in megohms = 260MΩ Circuit 2. PI = 1.51
ANDRES GALVIS QCME
CAICEDO ING. LTDA CONTRACT W91278-04-D-0028 TASK ORDER No. 0010
Transmittal No. 6
Specification SECTION 33 70 02.00 10 - Paragraphs: 3.12.3 & 3.12.6 PHASE I – ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND
CONTRACTOR:
Caicedo Ingenieria LTDA
CONTRACT W91278-04-D-0028 TASK ORDER No. 0010 AIRFIELD IMPROVEMENTS & D/B HANGAR UPGRADE
Calle 68 # 4A - 77, Bogotá Ph. (057) 1 3221104, Fax (057) 1 3221105
e-mail: [email protected], [email protected] PAGE 2
KYORITSU - DIGITAL EARTH TESTER MODEL 4105A OPERATING INSTRUCTIONS
1. Battery voltage check if a battery low symbol shows, do not proceed with testing. 2. Test Leads connection (Precise Measurement).
Stick the attached Auxiliary earth Spikes in line and connect the test leads as shown below. 3. Earth Voltage Measurement Set the range switch to Earth Voltage position and make sure
that the indicated value is 10V or less. If the earth voltage is higher, it may result in excessive errors in earth resistance measurement.
4. Checking of Auxiliary Earth Spikes Connection (Check Function of Auxiliary Earth Resistance). Set the range switch to 2000 Ω position and press the “PRESS TO TEST” Button if the auxiliary earth resistance is too higher the symbol “ . . . “Blinks. Reduce the resistance by rechecking the connection, changing the site to stick earth spikes, of pouring water over the spikes.
5. Measurements (Precise Measurement) Set the range switch to the desire position and press the “PRESS TO TEST” button.
6. Measurement (Simplified Measurement) When auxiliary earth spikes cannot be stick, an approximate earth resistance can be obtained by two wire system designed to make measurement using an existing earth electrode. Make sure to use the specified simplified measurement probe.
CAICEDO ING. LTDA CONTRACT W91278-04-D-0028 TASK ORDER No. 0010
Transmittal No. 6
Specification SECTION 33 70 02.00 10 - Paragraphs: 3.12.3 & 3.12.6 PHASE I – ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND
CONTRACTOR:
Caicedo Ingenieria LTDA
CONTRACT W91278-04-D-0028 TASK ORDER No. 0010 AIRFIELD IMPROVEMENTS & D/B HANGAR UPGRADE
Calle 68 # 4A - 77, Bogotá Ph. (057) 1 3221104, Fax (057) 1 3221105
e-mail: [email protected], [email protected] PAGE 3
EARTH TESTING ON-SITE – JULY 1TH AND 31TH, 2009. First Test located on electrical vault behind of Bravo´s Hangar and the last test, locate on Bravo’s taxiway.
Figure 1. Grounding Electrode and Bonding system test, grounding wire connection.
Figure 2. Auxiliary earth Spikes connections.
CAICEDO ING. LTDA CONTRACT W91278-04-D-0028 TASK ORDER No. 0010
Transmittal No. 6
Specification SECTION 33 70 02.00 10 - Paragraphs: 3.12.3 & 3.12.6 PHASE I – ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND
CONTRACTOR:
Caicedo Ingenieria LTDA
CONTRACT W91278-04-D-0028 TASK ORDER No. 0010 AIRFIELD IMPROVEMENTS & D/B HANGAR UPGRADE
Calle 68 # 4A - 77, Bogotá Ph. (057) 1 3221104, Fax (057) 1 3221105
e-mail: [email protected], [email protected] PAGE 4
Figure 4. Grounding rod & wire on Handole. (The same for Manholes distribution).
Figure 5. Earth Voltage very good, 0.03V less than 10V limit.
CAICEDO ING. LTDA CONTRACT W91278-04-D-0028 TASK ORDER No. 0010
Transmittal No. 6
Specification SECTION 33 70 02.00 10 - Paragraphs: 3.12.3 & 3.12.6 PHASE I – ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND
CONTRACTOR:
Caicedo Ingenieria LTDA
CONTRACT W91278-04-D-0028 TASK ORDER No. 0010 AIRFIELD IMPROVEMENTS & D/B HANGAR UPGRADE
Calle 68 # 4A - 77, Bogotá Ph. (057) 1 3221104, Fax (057) 1 3221105
e-mail: [email protected], [email protected] PAGE 5
Figure 6. Earth testing at 2000Ω, very good rate 1Ω below than 5Ω limit.
(Same rate Measurement for all connections in electrical vault).
Figure 7. Earth testing at 2000Ω, good rate 4Ω below than 5Ω limit.
(Same rate Measurement for grounding rod and wire installed on airfield).
CAICEDO ING. LTDA CONTRACT W91278-04-D-0028 TASK ORDER No. 0010
Transmittal No. 6
Specification SECTION 33 70 02.00 10 - Paragraphs: 3.12.3 & 3.12.6 PHASE I – ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND
CONTRACTOR:
Caicedo Ingenieria LTDA
CONTRACT W91278-04-D-0028 TASK ORDER No. 0010 AIRFIELD IMPROVEMENTS & D/B HANGAR UPGRADE
Calle 68 # 4A - 77, Bogotá Ph. (057) 1 3221104, Fax (057) 1 3221105
e-mail: [email protected], [email protected] PAGE 6
KYORITSU - DIGITAL HIGH VOLTAGE INSULATION TESTER MODEL 3125
1. Battery voltage check if a battery low symbol shows, do not proceed with testing. 2. Test Leads connection (Precise Measurement).
Stick the attached cable conductor and ground earth wire in line and connect the test leads as shown below.
3. Insulation Measurement Set the range switch to 5000V position and make sure that the indicated value is 5000V or grater. If the voltage is lower, it may result in excessive errors in isolation measurement.
4. Checking the conductor and ground connection is correctly the measurement in earth shall be zero 0V. Set the range switch to 5000 V position and press the “PRESS TO TEST”
5. Measurements (Precise Measurement) Set the range switch to the desire position and press the “PRESS TO TEST” button.
Figure 8. Insulation testing, circuit 1.
CAICEDO ING. LTDA CONTRACT W91278-04-D-0028 TASK ORDER No. 0010
Transmittal No. 6
Specification SECTION 33 70 02.00 10 - Paragraphs: 3.12.3 & 3.12.6 PHASE I – ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND
CONTRACTOR:
Caicedo Ingenieria LTDA
CONTRACT W91278-04-D-0028 TASK ORDER No. 0010 AIRFIELD IMPROVEMENTS & D/B HANGAR UPGRADE
Calle 68 # 4A - 77, Bogotá Ph. (057) 1 3221104, Fax (057) 1 3221105
e-mail: [email protected], [email protected] PAGE 7
Figure 9. Insulation testing, circuit 2.
CAICEDO ING. LTDA CONTRACT W91278-04-D-0028 TASK ORDER No. 0010
Transmittal No. 6
Specification SECTION 33 70 02.00 10 - Paragraphs: 3.12.3 & 3.12.6 PHASE I – ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND
CONTRACTOR:
Caicedo Ingenieria LTDA
CONTRACT W91278-04-D-0028 TASK ORDER No. 0010 AIRFIELD IMPROVEMENTS & D/B HANGAR UPGRADE
Calle 68 # 4A - 77, Bogotá Ph. (057) 1 3221104, Fax (057) 1 3221105
e-mail: [email protected], [email protected] PAGE 8
TESTING EQUIPMENT
SPECIFICATION SECTION 33 70 02.00 10
Paragraphs: 3.12.3 & 3.12.6
Ground-Resistance Tests & Low-Voltage Cable Test
Products Catalogue
CAICEDO ING. LTDA CONTRACT W91278-04-D-0028 TASK ORDER No. 0010
Transmittal No. 6
Specification SECTION 33 70 02.00 10 - Paragraphs: 3.12.3 & 3.12.6 PHASE I – ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND
CONTRACTOR:
Caicedo Ingenieria LTDA
CONTRACT W91278-04-D-0028 TASK ORDER No. 0010 AIRFIELD IMPROVEMENTS & D/B HANGAR UPGRADE
Calle 68 # 4A - 77, Bogotá Ph. (057) 1 3221104, Fax (057) 1 3221105
e-mail: [email protected], [email protected] PAGE 9
DIGITAL EARTH TESTER MODEL 4105A Soft Case Model • Dust and drip proof.(designed to IEC 529 IP54) • In addition to the facility for precision measurement, test leads for simplified two wire
measuring system also supplied as standard accessories. (unit can be hung from the neck for simplified measurement)
• Designed to meet IEC 61010-1 safety standard. • Capable of measuring earth voltage. • Automatic warning when resistance of auxiliary earth spikes is in excess of tolerance. • Small and lightweight. Shock resistant new case material. • 2mA measuring current permits earth resistance tests without tripping earth leakage current
breakers in the circuit under test.
Figure 10. Earth Tester Equipment.
Quality and reliability is our tradition.
NEW
NEW
KEW EARTH
Dust and drip proof.(Designed to IEC60529 IP54)In addition to the facility for precision measurement, test leads for simplified two wire measuring system also supplied as standard accessories.(unit can be hung from the neck for simplified measurement)Designed to meet IEC61010-1, IEC61557 safety standard.Capable of measuring earth voltage.Automatic warning when resistance of auxiliary earth spikes is in excess of tolerance.Small and Iightweight. Shock resistant new case material and taut-band movement.2mA measuring current permits earth resistance tests without tripping earth leakage current breakers in the circuit under test.
KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD.
ISO 9001/EN 29001/BS 5750APPROVED BY BVQI
Earth Resistance Tester Series are small, lightweight and dust & drip-proof.
MODEL 4102A
Earth Tester
MODEL 4105A
Digital Earth Tester
MODEL 4102A Soft Case ModelMODEL 4102A-H Hard Case ModelMODEL 4105A Soft Case ModelMODEL 4105A-H Hard Case Model
MODEL 4102A-H (Hard Case Model)
MODEL7095 MODEL8032 MODEL7127
Safety Warnings
Please read the“Safety Warnings”in the instruction manual supplied with the instrument thoroughly and completely for correct use.Failure to follow the safety rules can cause fire, trouble, electrical shock, etc.Therefore, make sure to operate the instrument on a correct power supply and voltage rating marked on each instrument.
02.02F PRINTED IN JAPAN
DISTRIBUTOR
No. 5-20 Nakane 2-chome, Meguro-ku, Tokyo, 152-0031 Japan
Phone:81-3-3723-0131 Fax:81-3-3723-0152
URL:http://www.kew-ltd.co.jp
E-mail:info @ kew-ltd.co.jp
Factories:Uwajima & Ehime
KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD.
※The contents of this catalogue may be subject to change without notice.
INSTRUMENT LAYOUT
ACCESSORIES
SPECIFICATIONS
Measurement Ranges
Accuracy
Applicable Standards
Overload Protection
Safety Standard
Withstand Voltage
Power Source
Dimensions
Weight
Accessories
7095(Test Leads)×1set(red-20m,yellow-10m,green-5m)
8032(Auxiliary earth spikes)×1set
7127(Simplified measurement probe)×1set
R6P(AA)×6, Neck strap, Instruction Manual
3700V AC for 1 minute
IEC60529 IP54
Earth Resistance:0-12 Ω/0-120 Ω/0-1200 Ω
Earth Voltage(50,60Hz):0-30V AC
Earth Resistance:0-20 Ω/0-200 Ω/0-2000 Ω
Earth Voltage(50,60Hz):0-200V AC
Earth Resistance:±2%rdg±0.1Ω(20Ωrange)±2%rdg±3dgt(200Ω/2000Ωrange)Earth Voltage:±1%rdg±4dgt
Earth Resistance:±3% of full scale
Earth Voltage:±3% of full scale
Earth Resistance:276V AC for 10 seconds
across 2 of the 3 terminals
Earth Voltage:276V AC for 1 minute
Earth Resistance:280V AC for 10 seconds
across 2 of the 3 terminals
Earth Voltage:300V AC for 1 minute
105(L)×158(W)×70(D)mm
550g approx.600g approx.
R6P(AA)(1.5V)×6
Model 4102A/4102A-H Model 4105A/4105A-H
IEC61010-1 CAT. 300V Pollution Degree 2,IEC61557
MODEL 4102AEarth Tester
MODEL 4105A
Digital Earth Tester
Scale Board OK Lamp Press To Test Button Range Selector Switch LCD Display Indication LED With
Test Leads Auxiliary Earth Spikes Simplified Measurement Probe Safery Alligator Clip Test Bar
Carrying Case
Soft Case(4012A,4105A)
Hard Case(4012A-H,4105A-H)
CAICEDO ING. LTDA CONTRACT W91278-04-D-0028 TASK ORDER No. 0010
Transmittal No. 6
Specification SECTION 33 70 02.00 10 - Paragraphs: 3.12.3 & 3.12.6 PHASE I – ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND
CONTRACTOR:
Caicedo Ingenieria LTDA
CONTRACT W91278-04-D-0028 TASK ORDER No. 0010 AIRFIELD IMPROVEMENTS & D/B HANGAR UPGRADE
Calle 68 # 4A - 77, Bogotá Ph. (057) 1 3221104, Fax (057) 1 3221105
e-mail: [email protected], [email protected]
PAGE 12
Digital High Voltage Insulation Tester Model 3125 • Wide range measurements from 500V to 5000V and up to 1000GΩ. • Large digital display with Bar Graph indication and back light. • Polarization Index measurement (PI). • Timer measurement function. • Indication of Output voltage and Discharge voltage. • Auto-discharge function and Voltage output warning function. • Auto power off and Battery Check. • Safety standard IEC 61010-1 CAT.III 600V
Figure 11. Insulation Tester Equipment.
Optional Accessories
Polarization Index
Specifications
500V0.0~99.9MΩ100~999MΩ
±5%rdg±3dgt
1mA [email protected]Ωload500VDC+30% -0%
1000V0.0~99.9MΩ100~999MΩ1.00~1.99GΩ
±5%rdg±3dgt
1mA to1.2mA@1MΩload
1000VDC+20%-0%
2500V0.0~99.9MΩ100~999MΩ1.00~9.99GΩ10.0~99.9GΩ
±5%rdg±3dgt
1mA [email protected]Ωload2500VDC+20%
-0%999 Counts(1000 counts only at 1000GΩ)
About 1000mA(During measurement)5320V AC for 5 seconds
IEC 61010-1 CAT.3 600V, pollution Degree 2DC12V : R14× 8 pcs
205(L) × 152(W) × 94(D)mmapprox. 1.8kg
Polarization Index is one of the factors to check the condition of insulation.The polarization Index is defined as the ratio between the resistance value in 10 minutes and the resistance value in 1 minute after switch is on.
1.3mA approx.
5000V0.0~99.9MΩ100~999MΩ1.00~9.99GΩ10.0~99.9GΩ
100~1000GΩ(1TΩ)±5%rdg±3dgt
±20%(100GΩor more)
1mA to1.2mA@5MΩload
5000VDC+20% -0%
AC/DC V30~600V
AC/DC(50/60Hz)
±2%rdg±3dgt
630 Counts25mA approx.
Polarization index 4 or moreVery good Good
1.5~1.04.0~1.5Dubious
1.0 or lessUnsatisfactoryCriteria
LINE PROBE WITH ALLIGATOR CLIP : 3000mm
ADAPTOR FOR RECORDER(OUTPUT 1mV/1μA)CONNECTOR SIDE : 200mmALLIGATOR CLIP SIDE : 1100mm
MODEL 7168 MODEL 8302
Insulation resistance Voltage measurementRange
Measuringrange
Accuracy
Short Circuit CurrentRated test Current
Open circuit voltage
Maximum displayCurrent consumptionWithstand VoltageSafety standardPower supplyDimensionsWeightAccessories
MODEL 3125 Output characteristics6000
5000
Out p
ut V
olta
ge(V
)
Insulation Resistance(GΩ)
4000
3000
2000
1000
00.0001 0.001 0.01 0.1 1 10 100 1000
LINE PROBE 7165 ALKALINE BATTERY SIZE C(LR14×8PCS) EARTH CORD 7166 INSTRUCTION MANUALGUARD CORD 7164 HARD CASE : MODEL 9124 PICKEL TYPE PROD 8019
Calculation formula :Polarization Index = resistance value in 10 minutes (TIME2) / resistance value in 1 minute (TIME1)
Setting interval is as follows.TIME1 00:10~59:30 TIME2 00:20~60:00 (Remarks : 00:10 means 10 seconds)
Since polarization Index varies with moisture absorption regardless of the shape or size of insulator,it gives significant criteria to verify the insulation. Following table shows the criteria.
For inquires or orders :
Safety Warnings :Please read the "Safety Warnings" in the instruction manual supplied with the instrument thoroughly and completely for correct use. Failure to follow the safety rules can cause fire, trouble, electrical shock, etc. Therefore, make sure to operate the instrument on a correct power supply and voltage rating marked on each instrument.
The contents of this leaflet are subject to change without notice. 04.04ADIn consideration of the environment, soy ink and recycled paper were used in this publication.
CAICEDO ING. LTDA CONTRACT W91278-04-D-0028 TASK ORDER No. 0010
Transmittal No. 6
Specification SECTION 33 70 02.00 10 - Paragraphs: 3.12.3 & 3.12.6 PHASE I – ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND
CONTRACTOR:
Caicedo Ingenieria LTDA
CONTRACT W91278-04-D-0028 TASK ORDER No. 0010 AIRFIELD IMPROVEMENTS & D/B HANGAR UPGRADE
Calle 68 # 4A - 77, Bogotá Ph. (057) 1 3221104, Fax (057) 1 3221105
e-mail: [email protected], [email protected]
PAGE 15
TESTING RESULTS & CERTIFICATION
SPECIFICATION SECTION
33 70 02.00 10
Paragraphs: 3.12.3 & 3.12.6
Ground-Resistance Tests & Low-Voltage Cable Test