8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations
1/28
FOR APPROVAL
Rev Date Prepared Checked Approved Details of Revision
Owner
B 2010/07/15 BT JL MP For Approval
BT CP MP For Approval2010/09/27C
-
8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations
2/28
DOOSAN PROJECTS INDIA PVT., LTD
W.O. No: T10107 Calc T10107-VE04-P1UHA-160004 Sheet Cont'd
Client : GMR Energy Limited Project Raipur Chhattisgarh 2 X 685 MW CTPP
Title: Raipur-Chhattisgarh CTPP - Analysis & Design of PA Fan Foundation
CALCULATION COVER SHEET
TABLE OF CONTENTS
LEAD SHEET SHEET NO.
PURPOSE
REFERENCES
DESIGN REQUIREMENTS
UNCONFIRMED ASSUMPTIONS
DESIGN PROCEDURES
CONCLUSIONS
BODY OF CALCULATION
3
3
3
4
5
6
4
APPENDIX A (Includes Applicable References) A1
1 2
-
8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations
3/28
DOOSAN PROJECTS INDIA PVT., LTD
W.O. No: T10107 Calc : T10107-VE04-P1UHV-160001 Sheet No: Cont'd on:
Prepared By: J.L. Date Checked By: Date:
Title: Raipur-Chhattisgarh CTPP - Analysis & Design of PA Fan Foundation
REVISION RECORD
2010/05/13
M. PatelC. PB. Tandon
2010/09/15
For approvalC
Revision
print/sign/date
Status Preparer Checker Approver
print/sign/date
Description of Revision
print/sign/date
Revision to calculations because of
dimensional changes in PA Layout &
providing an isolation pad between PA
Foundation and Boiler Mat
2010/09/21 2010/09/24
CP 2010/09/21
2 3
-
8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations
4/28
DOOSAN PROJECTS INDIA PVT., LTD
W.O. No: T10107 Calc : T10107-VE04-P1UHA-160004 Sheet No: Cont'd on:
Prepared By: B. Tandon Date C hecked By: Date:
Title: Raipur-Chhattisgarh CTPP - Analysis & Design of PA Fan Foundation
PURPOSE
REFERENCES
Codes & Standards
1. Indian Standard: IS: - 2000 -Code of Practice for Plain and Reinforced Concrete (Fourth Revision)
2. Indian Standard: IS: - 2008
3. Indian Standard IS: -Criteria for Earthquake Resistant Design of Structures Part 1
4. Indian Standard: IS:
5. Indian Standard: IS: -1986
6. Indian Standard: IS:
7. Indian Standard: IS:
Reference Drawings/Documents
No. Drawing/Document No. Drawing/Document Description
1. T10107-VB00-P0-UZ1-171001 2010/05/06Design Criteria for Civil, Structural &
Architectural Work
1.0
The purpose of this calculation is to design the foundation of the PA FAN for the Raipur-Chhattisgarh CTPP project.
456
2.0
2.1
Date
2010/04/6
- Criteria for Earthquake Resistant Design of Structures Part 4 Industrial
Structures Including Stack-like Structures
- Code of Practice for Design and Construction of Foundations in Soils:
General Requirements
-2002
-2005
1786 -Specification for High Strength Deformed Bars & Wires for Concrete
Reinforcement
2.2
-1979 Code of Practice for Design and Construction of Machine Foundations,
Part 4 Foundation for Rotary Type Machines of Low Frequency
1893
1893
2974
1904
2974 -1982 Code of Practice for Design and Construction of Machine Foundations,
Part 1 Foundation for Reciprocating Type Machines
. oosan ro ec s n a v ., ., raw ngs;
a. T10107-UE00-P0UHA-320001 Rev.B Boiler General Arrangement, (Key Plan)"
b T10107 YD00 P0HLB 310002 Rev B PA Fan Layout Drawing
2010/07/29
2010/09/13C
CP 2010/09/21
3 4
-
8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations
5/28
DOOSAN PROJECTS INDIA PVT., LTD
W.O. No: T10107 Calc : T10107-VE04-P1UHA-160004 Sheet No: Cont'd on:
Prepared By: B. Tandon Date C hecked By: Date:
Title: Raipur-Chhattisgarh CTPP - Analysis & Design of PA Fan Foundation
2010/04/6
Material
Concrete
Reinforcement
Site Location
Design Ground Elevation
The finish grade level provided by GMR shall be at elevation 313.0 m in BTG area/ Section 1.3.4, Ref. # 1
Design Ground Water Elevation
All concrete reinforcement shall be high strength deformed reinforcing bars with a minimum yield
strength, fy = 415 N/mm2, conforming to IS-1786.
Concrete for the boiler building foundation mat, which is integral with PA FAN foundation, shall
consist of grade M25 concrete with a cube strength of f'ck = 25 N/mm2 conforming with IS-456.
Design Ground Water Table shall be taken as 7.5m below final grade elevation - as recommended in final
Geotechnical Investigation Report.
3.2
3.3
3.4
3.3
The site of the Raipur- Chhattisgarh Coal Fired Power Plant is located near Raikheda Village, Raipur
District, in the State of Chhattisgarh, India. The site is about 12 Km from the Tilda town and 55 Km
from Raipur.
Primary Air Fan piers shall consist of grade M35 concrete with a cube strength of f'ck = 35
N/mm2 conforming with IS-456.
Soil Coefficient of Sub grade Reaction
The foundation shall be supported on a mass of lean concrete resting on weathered rock (layer III) with a
ffi i t f b d d l f 3 6 k / 3 S A di C
3.5
CP 2010/09/21
4 5
-
8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations
6/28
DOOSAN PROJECTS INDIA PVT., LTD
W.O. No: T10107 Calc : T10107-VE04-P1UHA-160004 Sheet No: Cont'd on:
Prepared By: B. Tandon Date C hecked By: Date:
Title: Raipur-Chhattisgarh CTPP - Analysis & Design of PA Fan Foundation
2010/04/6
CONCLUSION
Natural Frequencies are outside 30% of M/C operating Freq. i.e. not between 17.4 Hz to 32.3 Hz
Vertical Natural Frequency = Hz , OK No Resonance as damping ratio > 0.707
Horizontal Natural Frequency = Hz , OK No Resonance as damping ratio > 0.707
Rocking Natural Frequency = Hz , OK
For Reinf. Details see contract Drawings.
BODY OF CALCULATION
Calculations begin on following page.
7.8
6.7
> 7.1
7.0
6.0
C
CP 2010/09/21
5 6
-
8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations
7/28
W.O. No: T10107 Calc No:T10107-VE04-P1UHA-160004 Sheet No: Cont'd on:
Prepared By: BT Date: Checked By: Date:
Title: 2 x 685 MW RAIPUR - CHHATTISGARH Coal Fired Power Plant - Primary Air Fan equipment Foundation
Rev C, 2010-9-15
PA FAN Foundation
DOOSAN PROJECTS INDIA PVT., LTD
2010/4/6
acua ons ase on en or rawng - - - evson - ece ve
Machine Loading includes Dynamic load at starting of motor as well as fan load in running conditionDead Load Vertical MD = 8 * 29 +6 * 21 +8 * 31 =
Longitudnal (Axial) Force FSY = 8 * 1.8 +6 * 3.5 +8 * 5.3 =
Lateral Force (Horiz) FSX = 8 *0 + 6 * 0.9 +8 * 0.8 =
Dynamic Force =Fd-v = 8 * 49 +6 * 0.5 +8 * 12 =
11.8 KN
491.0 KN
606.0 KN
77.8 KNC
Lateral Force (Horiz) FX = 8 * 49 +6 * 0.5 +8 * 10 =
Machine Operating Speed =
Soil Parameters
From Geotechnical Report
Density of Soil, s =' = =
475.0 KN
24.8 Hz
15.74 kN/m3
C
,
Shear Modulus, G =2000(/(2*(1+0.35)) = =
Allowable Soil Bearing Pressure @ Rock level EL 305.5 =Weight of 2.0m lean concrete - 2.0m soil wt = (145-110) x 3.2808 3/2200 x 2 =
Allowable Soil Bearing Pressure under boiler mat which supports Fan block, qa = =
Acceptance Cr iteria (based on Vendor's requirements)
50.00 MT/m21.12 MT/m2
.
740.7 kg/cm2 72592.6 kN/m2
.
479.3 kN/m248.88 MT/m2
C
and 20% away from double of speed frquency.
Therefore, Natural Frequency shall not occur between 17.36 Hz To 32.24 Hz and 39.68 Hz To 59.52 Hz
2) Per Vendor the stiffness of foundation has to be > 10 6 N/mm
3) P d f d ti h ldb i i f 25 ti t 931 6 KN
CCCC
6 7
CP 2010/09/21
-
8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations
8/28
W.O. No: T10107 Calc No:T10107-VE04-P1UHA-160004 Sheet No: Cont'd on:
Prepared By: BT Date: Checked By: Date:
Title: 2 x 685 MW RAIPUR - CHHATTISGARH Coal Fired Power Plant - Primary Air Fan equipment Foundation
Rev C, 2010-9-15
DOOSAN PROJECTS INDIA PVT., LTD
2010/4/6
L =12.45m
B 520
7 8
CP 2010/09/21
-
8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations
9/28
W.O. No: T10107 Calc No:T10107-VE04-P1UHA-160004 Sheet No: Cont'd on:
Prepared By: BT Date: Checked By: Date:
Title: 2 x 685 MW RAIPUR - CHHATTISGARH Coal Fired Power Plant - Primary Air Fan equipment Foundation
Rev C, 2010-9-15
DOOSAN PROJECTS INDIA PVT., LTD
2010/4/6
General revision to calculations due to increase in PA fdn block thickness.
Z Foundation Embedment depth 3.50 m
X FOR FOUNDATION, =M{(B2 +t2)/12 +(CGz2)}
B FOR EQUIPMENT, =M(CGz2)
t Wfnd / Wequip =22.36 (RECOMMENDED MINIMUM =2.25 )
W Rotor mass = =nd . =
L B t CGX CGY CGZ WCGX WCGY WCGZ ISUPPORT PAD #1 12.45m 5.20m 4.50m 2.60m 6.23m 2.25m 17846 42727 15443 6296.1
SUPPORT PAD #2 6.30m 5.20m 0.69m 2.60m 3.15m 4.84m 1385 1678 2580.25 1398.1
SUPPORT PAD #3 2.75m 5.20m 0.24m 2.60m 11.08m 4.62m 210 896 373.56 194.44
Motor - - - 2.60m 4.00m 6.00m 487 749 1124 687.02
Foundation Weight
L
Equipment80.86 kN
6863.73 kN
532.56 kN
187.31 kN . . . .
Shaft+coupling 2.60m 7.70m 5.19m 31 91 61 32.296
r assemble & Fan Casing 2.60m 10.98m 6.00m 352 1486 812 496.38
Silencer & Duct Not included as it is supported by aux. boiler steel and there is a flexible joint between duct and equipment.
TOTALS: 20310 47626 20394 9104
Mx due to Axial Ld FSY = 77.8 x6 = 466.8 kN-mMy due to Lateral Ld FSx = 11.8 x6 = 70.8 kN-m
.
7811.56 kN
135.33 kN
11.77 kN
Static check - Soil Pressure
CGX(EQUIP & FOUND) = 20310.05 / 7811.56 = 2.60m ex = 2.6 - 2.6 = 0.00m 0% of foundation width
CGY (EQUIP & FOUND) 476256 / 781156 6 10 6 23 61 0 13 0 1% f f d ti l th
8 9
CP 2010/09/21
-
8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations
10/28
W.O. No: T10107 Calc No:T10107-VE04-P1UHA-160004 Sheet No: Cont'd on:
Prepared By: BT Date: Checked By: Date:
Title: 2 x 685 MW RAIPUR - CHHATTISGARH Coal Fired Power Plant - Primary Air Fan equipment Foundation
Rev C, 2010-9-15
DOOSAN PROJECTS INDIA PVT., LTD
2010/4/6
DYNAMIC CHECK:
Vertical Translation (Per ARYA)
Area of rectangular foundation base, A = 12.45 x 5.2 =
A 64.74
3.142
64.74 m2
4.54 mEquivalent radius of foundation base, ro = = =
Spring Constantz
=2.14 (fig. 4-1, ref 4 ) for B/L = 0.42
(Table 4-1, ref 4 )
( 72593 )( 2.14 ) ( 5.2 )( 12.45 )
Equivalent spring constant Kz =Gz BL
(1 - )
1 k 1
2 m 6.28
W 7812
g 9.815
( 1 - 0.35 )
7.8 Hz795.904
Mass, m = = = 795.88
1922999
=
==
kN/sec2
-m
Vertical Natural Frequency = fnz =
7812Mass Ratio = z =
W (1-)=
4sro3
(1 - 0.35 )= (Table 4-3, ref 4 )
4 (15.74 )( 4.54 )0.862
3
9 10
CP 2010/09/21
-
8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations
11/28
W.O. No: T10107 Calc No:T10107-VE04-P1UHA-160004 Sheet No: Cont'd on:
Prepared By: BT Date: Checked By: Date:
Title: 2 x 685 MW RAIPUR - CHHATTISGARH Coal Fired Power Plant - Primary Air Fan equipment Foundation
Rev C, 2010-9-15
DOOSAN PROJECTS INDIA PVT., LTD
2010/4/6
0.425
( 1.71 )
= 0.784Modified dam in ratio, D' =
0.425 (z)
NOTE: If Dz > .707, NO RESONANCE WILL OCCUR
.0.86
, z z
Horizontal Translation (Per ARYA)
A 64.74
3.142
Spring Constant x
= 1 (fig. 4-1, ref 4 ) for B/L = 0.42
Equivalent radius of foundation base, ro = = = 4.54 m
1 k 12 m 6.28
Equivalent spring constant Kx = 2(1 +) Gx BL = 2( 1 +0.35)( 72593 )( 1 ) ( 5.2 )( 12.45 ) = 1577039 kN/m
7811.56( 7 - 8(0.35))= 1.071
Horizontal Natural Frequency, fnx = =1577039
= 7.1 Hz795.88
Mass ratio = =W (7 - 8)
=3
Geometric Damping ratio Dz = 0.288/Bz = 0.278 (Table 4-3, ref 4 )Internal Damping Di of Soil =negligible
.32(1 - )sro
3 x 32 ( 1 - 0.35 )(15.74 )( 4.54 ) 3
10 11
CP 2010/09/21
-
8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations
12/28
W.O. No: T10107 Calc No:T10107-VE04-P1UHA-160004 Sheet No: Cont'd on:
Prepared By: BT Date: Checked By: Date:
Title: 2 x 685 MW RAIPUR - CHHATTISGARH Coal Fired Power Plant - Primary Air Fan equipment Foundation
Rev C, 2010-9-15
DOOSAN PROJECTS INDIA PVT., LTD
2010/4/6
Torsional Excitation (Rocking) Dynamic Analysis (Per ARYA)
=
LB3 ( 12.45 )( 5.2 )
Rocking Spring Coefficient = = 0.424 ( FROM FIGURE 1 WITH B/L =0.42 )
( 3 )( 3.14 )3.69 m=
9104.4 Kn-m-sec2
Equivalent radius of
foundation base, ro ==
344
1 k 1
2 6.28
72592.59( 0.42 )( 12.45 )( 5.2 ) =1 - 0.35
15923679 kN-m/rad
= 6.7 Hz
3( 9104.37 )( 1 - 0.35)
Rocking SpringConstant =
k =
Rocking Natural Frequency = fn = =15923679
9104.37
GLB2
1 -
3 1 -
2
( 1 +(2.02 ) (2.02)
. .= 2.02
8ro5 8 ( 15.74 / 9.815)(3.69 )
Mass ratio = u =
=
0.15 = 0.035) B
DampingRatio
D = 0.15
6.7 HzDamped Rocking Natural
fd =fn
=6.66
=
5
2
Consider embedment effect
b d f ld l b li bl if b kfill i ll d i h f d i d
.1 - 2 D 1 - 2 ( 0.035 )Frequency =
2
11 12
CP 2010/09/21
-
8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations
13/28
W.O. No: T10107 Calc No:T10107-VE04-P1UHA-160004 Sheet No: Cont'd on:
Prepared By: BT Date: Checked By: Date:
Title: 2 x 685 MW RAIPUR - CHHATTISGARH Coal Fired Power Plant - Primary Air Fan equipment Foundation
Rev C, 2010-9-15
DOOSAN PROJECTS INDIA PVT., LTD
2010/4/6
8.42
= 8.4 Hz
Damped Rocking Natural
fd =
fn
= 2
FREQUENCY RATIO, r =Fo / fn =
Check Displacement @ Machine shaft Elevation:
Horizontal mode:
1
^ ^ ^
.1 - 2 D2 1 - 2 ( 0.017 )Frequency =
magnification factor Mr =
24.8 / 8.4 = 2.95
2
1-r 2 2 + 2Dxr 2
where r = / n = f /fn = 24.8/9.2 = 2.685 = 2 x freq. in Hz
Hence, Mr = 0.157
Displacement response X =Mr * Fx /kx = 0.157 x 475 / 2680471x 1000
x = 0.0277 mm
Rotational Mode: 1
((1-r 2) 2 +(2Dr) 2)
where r = / n = f /fn = 24.8/8.4 = 2.945
magnification factor Mr =
T oug t e un a ance orce at catastrop c amage s ony 78 N, ut u Dynamc Horzonta oa =475 N s
used for calculating Displ. -- Conservative
, r .
T = 9.0*4*2.010 = 72.36 kNm
i l
(Max rotating Load due to unbalance of the fan motor =
9kN @ 2 rows of 4 supports, spaced at 2.01m))
12 13
CP 2010/09/21
-
8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations
14/28
W.O. No: T10107 Calc No:T10107-VE04-P1UHA-160004 Sheet No: Cont'd on:
Prepared By: BT Date: Checked By: Date:
Title: 2 x 685 MW RAIPUR - CHHATTISGARH Coal Fired Power Plant - Primary Air Fan equipment Foundation
Rev C, 2010-9-15
DOOSAN PROJECTS INDIA PVT., LTD
2010/4/6
SUMMARY OF RESULTS
NATURAL FREQUENCIES SHALL NOT OCCUR BETWEEN 17.36 Hz to 32.24 Hz and 39.68 Hz to 59.52 Hz
Undamped Frequency (withou embed. ): Damped Frequency (resonant Freq) with embedment effect
Vertical Natural Frequency = 7.8 Hz , OK Vertical Damped Natural Frequency = >8.9 Hz , OK
Horizontal Natural Frequency = 7.1 Hz , OK Horizontal Damped Natural Frequency = >9.2 Hz , OK
Rocking Natural Frequency = 6.7 Hz , OK Rocking Damped Natural Frequency = 8.4 Hz , OK
Check Soil Pressure under Dynamic loading:
Additional Vertical Force =
Additional My due to Lateral Ld FDx = 475 x0 = 0 kN-m
P Mx 491.0 0
A Sx 64.74 56.1
=
Additional Soil Pressure due to Dynamic Loading = q =
491.0 KN
=
7.6 kN/m2
+ +
Total Bearing Pressure = + =