    DOOSAN PROJECTS INDIA PVT., LTD

    W.O. No: T10107 Calc T10107-VE04-P1UHA-160004 Sheet Cont'd

    Client : GMR Energy Limited Project Raipur Chhattisgarh 2 X 685 MW CTPP

    Title: Raipur-Chhattisgarh CTPP - Analysis & Design of PA Fan Foundation

    CALCULATION COVER SHEET

    TABLE OF CONTENTS

    LEAD SHEET SHEET NO.

    PURPOSE

    REFERENCES

    DESIGN REQUIREMENTS

    UNCONFIRMED ASSUMPTIONS

    DESIGN PROCEDURES

    CONCLUSIONS

    BODY OF CALCULATION

    3

    3

    3

    4

    5

    6

    4

    APPENDIX A (Includes Applicable References) A1

    1 2

  • 8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations

    3/28

    DOOSAN PROJECTS INDIA PVT., LTD

    W.O. No: T10107 Calc : T10107-VE04-P1UHV-160001 Sheet No: Cont'd on:

    Prepared By: J.L. Date Checked By: Date:

    Title: Raipur-Chhattisgarh CTPP - Analysis & Design of PA Fan Foundation

    REVISION RECORD

    2010/05/13

    M. PatelC. PB. Tandon

    2010/09/15

    For approvalC

    Revision

    print/sign/date

    Status Preparer Checker Approver

    print/sign/date

    Description of Revision

    print/sign/date

    Revision to calculations because of

    dimensional changes in PA Layout &

    providing an isolation pad between PA

    Foundation and Boiler Mat

    2010/09/21 2010/09/24

    CP 2010/09/21

    2 3

  • 8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations

    4/28

    DOOSAN PROJECTS INDIA PVT., LTD

    W.O. No: T10107 Calc : T10107-VE04-P1UHA-160004 Sheet No: Cont'd on:

    Prepared By: B. Tandon Date C hecked By: Date:

    Title: Raipur-Chhattisgarh CTPP - Analysis & Design of PA Fan Foundation

    PURPOSE

    REFERENCES

    Codes & Standards

    1. Indian Standard: IS: - 2000 -Code of Practice for Plain and Reinforced Concrete (Fourth Revision)

    2. Indian Standard: IS: - 2008

    3. Indian Standard IS: -Criteria for Earthquake Resistant Design of Structures Part 1

    4. Indian Standard: IS:

    5. Indian Standard: IS: -1986

    6. Indian Standard: IS:

    7. Indian Standard: IS:

    Reference Drawings/Documents

    No. Drawing/Document No. Drawing/Document Description

    1. T10107-VB00-P0-UZ1-171001 2010/05/06Design Criteria for Civil, Structural &

    Architectural Work

    1.0

    The purpose of this calculation is to design the foundation of the PA FAN for the Raipur-Chhattisgarh CTPP project.

    456

    2.0

    2.1

    Date

    2010/04/6

    - Criteria for Earthquake Resistant Design of Structures Part 4 Industrial

    Structures Including Stack-like Structures

    - Code of Practice for Design and Construction of Foundations in Soils:

    General Requirements

    -2002

    -2005

    1786 -Specification for High Strength Deformed Bars & Wires for Concrete

    Reinforcement

    2.2

    -1979 Code of Practice for Design and Construction of Machine Foundations,

    Part 4 Foundation for Rotary Type Machines of Low Frequency

    1893

    1893

    2974

    1904

    2974 -1982 Code of Practice for Design and Construction of Machine Foundations,

    Part 1 Foundation for Reciprocating Type Machines

    . oosan ro ec s n a v ., ., raw ngs;

    a. T10107-UE00-P0UHA-320001 Rev.B Boiler General Arrangement, (Key Plan)"

    b T10107 YD00 P0HLB 310002 Rev B PA Fan Layout Drawing

    2010/07/29

    2010/09/13C

    CP 2010/09/21

    3 4

  • 8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations

    5/28

    DOOSAN PROJECTS INDIA PVT., LTD

    W.O. No: T10107 Calc : T10107-VE04-P1UHA-160004 Sheet No: Cont'd on:

    Prepared By: B. Tandon Date C hecked By: Date:

    Title: Raipur-Chhattisgarh CTPP - Analysis & Design of PA Fan Foundation

    2010/04/6

    Material

    Concrete

    Reinforcement

    Site Location

    Design Ground Elevation

    The finish grade level provided by GMR shall be at elevation 313.0 m in BTG area/ Section 1.3.4, Ref. # 1

    Design Ground Water Elevation

    All concrete reinforcement shall be high strength deformed reinforcing bars with a minimum yield

    strength, fy = 415 N/mm2, conforming to IS-1786.

    Concrete for the boiler building foundation mat, which is integral with PA FAN foundation, shall

    consist of grade M25 concrete with a cube strength of f'ck = 25 N/mm2 conforming with IS-456.

    Design Ground Water Table shall be taken as 7.5m below final grade elevation - as recommended in final

    Geotechnical Investigation Report.

    3.2

    3.3

    3.4

    3.3

    The site of the Raipur- Chhattisgarh Coal Fired Power Plant is located near Raikheda Village, Raipur

    District, in the State of Chhattisgarh, India. The site is about 12 Km from the Tilda town and 55 Km

    from Raipur.

    Primary Air Fan piers shall consist of grade M35 concrete with a cube strength of f'ck = 35

    N/mm2 conforming with IS-456.

    Soil Coefficient of Sub grade Reaction

    The foundation shall be supported on a mass of lean concrete resting on weathered rock (layer III) with a

    ffi i t f b d d l f 3 6 k / 3 S A di C

    3.5

    CP 2010/09/21

    4 5

  • 8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations

    6/28

    DOOSAN PROJECTS INDIA PVT., LTD

    W.O. No: T10107 Calc : T10107-VE04-P1UHA-160004 Sheet No: Cont'd on:

    Prepared By: B. Tandon Date C hecked By: Date:

    Title: Raipur-Chhattisgarh CTPP - Analysis & Design of PA Fan Foundation

    2010/04/6

    CONCLUSION

    Natural Frequencies are outside 30% of M/C operating Freq. i.e. not between 17.4 Hz to 32.3 Hz

    Vertical Natural Frequency = Hz , OK No Resonance as damping ratio > 0.707

    Horizontal Natural Frequency = Hz , OK No Resonance as damping ratio > 0.707

    Rocking Natural Frequency = Hz , OK

    For Reinf. Details see contract Drawings.

    BODY OF CALCULATION

    Calculations begin on following page.

    7.8

    6.7

    > 7.1

    7.0

    6.0

    C

    CP 2010/09/21

    5 6

  • 8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations

    7/28

    W.O. No: T10107 Calc No:T10107-VE04-P1UHA-160004 Sheet No: Cont'd on:

    Prepared By: BT Date: Checked By: Date:

    Title: 2 x 685 MW RAIPUR - CHHATTISGARH Coal Fired Power Plant - Primary Air Fan equipment Foundation

    Rev C, 2010-9-15

    PA FAN Foundation

    DOOSAN PROJECTS INDIA PVT., LTD

    2010/4/6

    acua ons ase on en or rawng - - - evson - ece ve

    Machine Loading includes Dynamic load at starting of motor as well as fan load in running conditionDead Load Vertical MD = 8 * 29 +6 * 21 +8 * 31 =

    Longitudnal (Axial) Force FSY = 8 * 1.8 +6 * 3.5 +8 * 5.3 =

    Lateral Force (Horiz) FSX = 8 *0 + 6 * 0.9 +8 * 0.8 =

    Dynamic Force =Fd-v = 8 * 49 +6 * 0.5 +8 * 12 =

    11.8 KN

    491.0 KN

    606.0 KN

    77.8 KNC

    Lateral Force (Horiz) FX = 8 * 49 +6 * 0.5 +8 * 10 =

    Machine Operating Speed =

    Soil Parameters

    From Geotechnical Report

    Density of Soil, s =' = =

    475.0 KN

    24.8 Hz

    15.74 kN/m3

    C

    ,

    Shear Modulus, G =2000(/(2*(1+0.35)) = =

    Allowable Soil Bearing Pressure @ Rock level EL 305.5 =Weight of 2.0m lean concrete - 2.0m soil wt = (145-110) x 3.2808 3/2200 x 2 =

    Allowable Soil Bearing Pressure under boiler mat which supports Fan block, qa = =

    Acceptance Cr iteria (based on Vendor's requirements)

    50.00 MT/m21.12 MT/m2

    .

    740.7 kg/cm2 72592.6 kN/m2

    .

    479.3 kN/m248.88 MT/m2

    C

    and 20% away from double of speed frquency.

    Therefore, Natural Frequency shall not occur between 17.36 Hz To 32.24 Hz and 39.68 Hz To 59.52 Hz

    2) Per Vendor the stiffness of foundation has to be > 10 6 N/mm

    3) P d f d ti h ldb i i f 25 ti t 931 6 KN

    CCCC

    6 7

    CP 2010/09/21

  • 8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations

    8/28

    W.O. No: T10107 Calc No:T10107-VE04-P1UHA-160004 Sheet No: Cont'd on:

    Prepared By: BT Date: Checked By: Date:

    Title: 2 x 685 MW RAIPUR - CHHATTISGARH Coal Fired Power Plant - Primary Air Fan equipment Foundation

    Rev C, 2010-9-15

    DOOSAN PROJECTS INDIA PVT., LTD

    2010/4/6

    L =12.45m

    B 520

    7 8

    CP 2010/09/21

  • 8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations

    9/28

    W.O. No: T10107 Calc No:T10107-VE04-P1UHA-160004 Sheet No: Cont'd on:

    Prepared By: BT Date: Checked By: Date:

    Title: 2 x 685 MW RAIPUR - CHHATTISGARH Coal Fired Power Plant - Primary Air Fan equipment Foundation

    Rev C, 2010-9-15

    DOOSAN PROJECTS INDIA PVT., LTD

    2010/4/6

    General revision to calculations due to increase in PA fdn block thickness.

    Z Foundation Embedment depth 3.50 m

    X FOR FOUNDATION, =M{(B2 +t2)/12 +(CGz2)}

    B FOR EQUIPMENT, =M(CGz2)

    t Wfnd / Wequip =22.36 (RECOMMENDED MINIMUM =2.25 )

    W Rotor mass = =nd . =

    L B t CGX CGY CGZ WCGX WCGY WCGZ ISUPPORT PAD #1 12.45m 5.20m 4.50m 2.60m 6.23m 2.25m 17846 42727 15443 6296.1

    SUPPORT PAD #2 6.30m 5.20m 0.69m 2.60m 3.15m 4.84m 1385 1678 2580.25 1398.1

    SUPPORT PAD #3 2.75m 5.20m 0.24m 2.60m 11.08m 4.62m 210 896 373.56 194.44

    Motor - - - 2.60m 4.00m 6.00m 487 749 1124 687.02

    Foundation Weight

    L

    Equipment80.86 kN

    6863.73 kN

    532.56 kN

    187.31 kN . . . .

    Shaft+coupling 2.60m 7.70m 5.19m 31 91 61 32.296

    r assemble & Fan Casing 2.60m 10.98m 6.00m 352 1486 812 496.38

    Silencer & Duct Not included as it is supported by aux. boiler steel and there is a flexible joint between duct and equipment.

    TOTALS: 20310 47626 20394 9104

    Mx due to Axial Ld FSY = 77.8 x6 = 466.8 kN-mMy due to Lateral Ld FSx = 11.8 x6 = 70.8 kN-m

    .

    7811.56 kN

    135.33 kN

    11.77 kN

    Static check - Soil Pressure

    CGX(EQUIP & FOUND) = 20310.05 / 7811.56 = 2.60m ex = 2.6 - 2.6 = 0.00m 0% of foundation width

    CGY (EQUIP & FOUND) 476256 / 781156 6 10 6 23 61 0 13 0 1% f f d ti l th

    8 9

    CP 2010/09/21

  • 8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations

    10/28

    W.O. No: T10107 Calc No:T10107-VE04-P1UHA-160004 Sheet No: Cont'd on:

    Prepared By: BT Date: Checked By: Date:

    Title: 2 x 685 MW RAIPUR - CHHATTISGARH Coal Fired Power Plant - Primary Air Fan equipment Foundation

    Rev C, 2010-9-15

    DOOSAN PROJECTS INDIA PVT., LTD

    2010/4/6

    DYNAMIC CHECK:

    Vertical Translation (Per ARYA)

    Area of rectangular foundation base, A = 12.45 x 5.2 =

    A 64.74

    3.142

    64.74 m2

    4.54 mEquivalent radius of foundation base, ro = = =

    Spring Constantz

    =2.14 (fig. 4-1, ref 4 ) for B/L = 0.42

    (Table 4-1, ref 4 )

    ( 72593 )( 2.14 ) ( 5.2 )( 12.45 )

    Equivalent spring constant Kz =Gz BL

    (1 - )

    1 k 1

    2 m 6.28

    W 7812

    g 9.815

    ( 1 - 0.35 )

    7.8 Hz795.904

    Mass, m = = = 795.88

    1922999

    =

    ==

    kN/sec2

    -m

    Vertical Natural Frequency = fnz =

    7812Mass Ratio = z =

    W (1-)=

    4sro3

    (1 - 0.35 )= (Table 4-3, ref 4 )

    4 (15.74 )( 4.54 )0.862

    3

    9 10

    CP 2010/09/21

  • 8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations

    11/28

    W.O. No: T10107 Calc No:T10107-VE04-P1UHA-160004 Sheet No: Cont'd on:

    Prepared By: BT Date: Checked By: Date:

    Title: 2 x 685 MW RAIPUR - CHHATTISGARH Coal Fired Power Plant - Primary Air Fan equipment Foundation

    Rev C, 2010-9-15

    DOOSAN PROJECTS INDIA PVT., LTD

    2010/4/6

    0.425

    ( 1.71 )

    = 0.784Modified dam in ratio, D' =

    0.425 (z)

    NOTE: If Dz > .707, NO RESONANCE WILL OCCUR

    .0.86

    , z z

    Horizontal Translation (Per ARYA)

    A 64.74

    3.142

    Spring Constant x

    = 1 (fig. 4-1, ref 4 ) for B/L = 0.42

    Equivalent radius of foundation base, ro = = = 4.54 m

    1 k 12 m 6.28

    Equivalent spring constant Kx = 2(1 +) Gx BL = 2( 1 +0.35)( 72593 )( 1 ) ( 5.2 )( 12.45 ) = 1577039 kN/m

    7811.56( 7 - 8(0.35))= 1.071

    Horizontal Natural Frequency, fnx = =1577039

    = 7.1 Hz795.88

    Mass ratio = =W (7 - 8)

    =3

    Geometric Damping ratio Dz = 0.288/Bz = 0.278 (Table 4-3, ref 4 )Internal Damping Di of Soil =negligible

    .32(1 - )sro

    3 x 32 ( 1 - 0.35 )(15.74 )( 4.54 ) 3

    10 11

    CP 2010/09/21

  • 8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations

    12/28

    W.O. No: T10107 Calc No:T10107-VE04-P1UHA-160004 Sheet No: Cont'd on:

    Prepared By: BT Date: Checked By: Date:

    Title: 2 x 685 MW RAIPUR - CHHATTISGARH Coal Fired Power Plant - Primary Air Fan equipment Foundation

    Rev C, 2010-9-15

    DOOSAN PROJECTS INDIA PVT., LTD

    2010/4/6

    Torsional Excitation (Rocking) Dynamic Analysis (Per ARYA)

    =

    LB3 ( 12.45 )( 5.2 )

    Rocking Spring Coefficient = = 0.424 ( FROM FIGURE 1 WITH B/L =0.42 )

    ( 3 )( 3.14 )3.69 m=

    9104.4 Kn-m-sec2

    Equivalent radius of

    foundation base, ro ==

    344

    1 k 1

    2 6.28

    72592.59( 0.42 )( 12.45 )( 5.2 ) =1 - 0.35

    15923679 kN-m/rad

    = 6.7 Hz

    3( 9104.37 )( 1 - 0.35)

    Rocking SpringConstant =

    k =

    Rocking Natural Frequency = fn = =15923679

    9104.37

    GLB2

    1 -

    3 1 -

    2

    ( 1 +(2.02 ) (2.02)

    . .= 2.02

    8ro5 8 ( 15.74 / 9.815)(3.69 )

    Mass ratio = u =

    =

    0.15 = 0.035) B

    DampingRatio

    D = 0.15

    6.7 HzDamped Rocking Natural

    fd =fn

    =6.66

    =

    5

    2

    Consider embedment effect

    b d f ld l b li bl if b kfill i ll d i h f d i d

    .1 - 2 D 1 - 2 ( 0.035 )Frequency =

    2

    11 12

    CP 2010/09/21

  • 8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations

    13/28

    W.O. No: T10107 Calc No:T10107-VE04-P1UHA-160004 Sheet No: Cont'd on:

    Prepared By: BT Date: Checked By: Date:

    Title: 2 x 685 MW RAIPUR - CHHATTISGARH Coal Fired Power Plant - Primary Air Fan equipment Foundation

    Rev C, 2010-9-15

    DOOSAN PROJECTS INDIA PVT., LTD

    2010/4/6

    8.42

    = 8.4 Hz

    Damped Rocking Natural

    fd =

    fn

    = 2

    FREQUENCY RATIO, r =Fo / fn =

    Check Displacement @ Machine shaft Elevation:

    Horizontal mode:

    1

    ^ ^ ^

    .1 - 2 D2 1 - 2 ( 0.017 )Frequency =

    magnification factor Mr =

    24.8 / 8.4 = 2.95

    2

    1-r 2 2 + 2Dxr 2

    where r = / n = f /fn = 24.8/9.2 = 2.685 = 2 x freq. in Hz

    Hence, Mr = 0.157

    Displacement response X =Mr * Fx /kx = 0.157 x 475 / 2680471x 1000

    x = 0.0277 mm

    Rotational Mode: 1

    ((1-r 2) 2 +(2Dr) 2)

    where r = / n = f /fn = 24.8/8.4 = 2.945

    magnification factor Mr =

    T oug t e un a ance orce at catastrop c amage s ony 78 N, ut u Dynamc Horzonta oa =475 N s

    used for calculating Displ. -- Conservative

    , r .

    T = 9.0*4*2.010 = 72.36 kNm

    i l

    (Max rotating Load due to unbalance of the fan motor =

    9kN @ 2 rows of 4 supports, spaced at 2.01m))

    12 13

    CP 2010/09/21

  • 8/22/2019 T101017-VE04-P1UHA-160004_Analysis and Design of PA Fan Foundation - Calculations

    14/28

    W.O. No: T10107 Calc No:T10107-VE04-P1UHA-160004 Sheet No: Cont'd on:

    Prepared By: BT Date: Checked By: Date:

    Title: 2 x 685 MW RAIPUR - CHHATTISGARH Coal Fired Power Plant - Primary Air Fan equipment Foundation

    Rev C, 2010-9-15

    DOOSAN PROJECTS INDIA PVT., LTD

    2010/4/6

    SUMMARY OF RESULTS

    NATURAL FREQUENCIES SHALL NOT OCCUR BETWEEN 17.36 Hz to 32.24 Hz and 39.68 Hz to 59.52 Hz

    Undamped Frequency (withou embed. ): Damped Frequency (resonant Freq) with embedment effect

    Vertical Natural Frequency = 7.8 Hz , OK Vertical Damped Natural Frequency = >8.9 Hz , OK

    Horizontal Natural Frequency = 7.1 Hz , OK Horizontal Damped Natural Frequency = >9.2 Hz , OK

    Rocking Natural Frequency = 6.7 Hz , OK Rocking Damped Natural Frequency = 8.4 Hz , OK

    Check Soil Pressure under Dynamic loading:

    Additional Vertical Force =

    Additional My due to Lateral Ld FDx = 475 x0 = 0 kN-m

    P Mx 491.0 0

    A Sx 64.74 56.1

    =

    Additional Soil Pressure due to Dynamic Loading = q =

    491.0 KN

    =

    7.6 kN/m2

    + +

    Total Bearing Pressure = + =