systems Remote Monitoring Networking Automatic transfer ...€¦ · c150 d5 150 120 136 109...

16

Transcript of systems Remote Monitoring Networking Automatic transfer ...€¦ · c150 d5 150 120 136 109...

  • R emote Monitoringand control

    software

    Networkingproducts

    P arallelingsystems

    Automatictransfer switches

    G enerator setcontrols

  • Engine Dimension (mm)Wet

    Weight (kg)

    Fuel Tank

    kVA kW kVA kW kVA kW Model L x W x H without fuel (L)

    C17 D5 16.5 13 15 12 X2.5-G2 PI044G PS0600 1667 x 930 x 1247 582 150

    C22 D5 22 17 20 16 X2.5-G2 PI144D PS0600 1667 x 930 x 1247 582 150

    C28 D5 27.5 22 25 20 X2.5-G2 PI144F PS0600 1667 x 930 x 1247 605 150

    C33 D5 33 26.4 30 24 X3.3-G1 PI144G PS0600 1753 x 930 x 1250 875 175

    C38 D5 38 30.4 35 28 X3.3-G1 PI144H PS0600 1753 x 930 x 1250 910 175

    C44 D5L 44 35 40 32 4BTAA3.3G13 UCI224C PS0600 2050 x 967 x 1510 909 156

    C55 D5L 55 44 50 40 4BTAA3.3G13 UCI224D PS0600 2050 x 967 x 1510 922 156

    C66 D5L 66 52 60 48 4BTAA3.3G13 UCI224F PS0600 2050 x 967 x 1510 969 156

    C90 D5 90 72 82 65 6BTA5.9-G5 UCI224G PC1.2 2268 x 1094 x 1576 1244 350

    C110 D5 110 88 100 80 6BTA5.9-G5 UCI274C PC1.2 2268 x 1094 x 1576 1244 340

    C150 D5 150 120 136 109 6BTAA5.9-G6 - UCI274E PC1.2 2550 x 1100 x 1850 1635 448

    C170 D5 170 136 155 124 6BTAA5.9-G7 - UCI274E PC1.2 2550 x 1100 x 1850 1635 448

    C175 D5e 175 140 158 126 QSB7-G5 IIIA / T3 UCI274F PC1.2 2656 x 1100 x 1658 1572 464

    C200 D5e 200 160 182 146 QSB7-G5 IIIA / T3 UCI274H PC1.2 2656 x 1100 x 1658 1670 464

    C220 D5e 220 176 200 160 QSB7-G5 IIIA / T3 UCI274H PC1.2 2656 x 1100 x 1658 1670 464

    C220 D5 220 176 200 160 6CTAA8.3-G2 PC1.2 2746 x 1100 x 1646 2500 350

    C250 D5 250 200 227 182 6CTAA8.3-G9 UCDI274J PC1.2 2746 x 1100 x 1646 2500 350

    C275 D5 275 220 250 200 QSL9-G5 4g UCDI274K PC1.2 3135 x 1100 x 1928 2347 608

    C275 D5B 275 220 250 200 6LTAA9.5G3 UCDI274K PC1.2 2800 x 1100 x 1871 2282 533

    C300 D5 300 240 275 220 QSL9-G5 4g HCI4D PC1.2 3549 x 1100 x 1928 2570 608

    C300 D5B 300 240 275 220 6LTAA9.5G3 HCI4D PC1.2 2800 x 1100 x 1871 2495 533

    C330 D5 330 264 300 240 QSL9-G5 4g HCI4D PC1.2 3135 x 1100 x 1928 2570 608

    C330 D5B 330 264 300 240 6LTAA9.5G1 HCI4D PC1.2 2800 x 1100 x 1871 2495 533

    C350 D5B 350 280 320 256 6LTAA9.5G1 HCI4E PC1.2 2800 x 1100 x 1871 2579 533

    C400 D5 400 320 360 288 QSG12G1 HCI4F PC2.2 3686 x 1160 x 2266 4053 772

    C450 D5 450 352 409 327 QSG12G2 HCI5C PC2.2 3686 x 1160 x 2266 4053 772

    C450 D5e 450 360 409 327 QSX15-G8 S II HCI5C PC2.2 3427 x 1500 x 2066 4121 711

    C450 D5eB 450 360 409 327 QSZ13 G7 S IIIa / T3 HC5IC PC2.2 3686 x 1160 x 2266 4053 772

    C500 D5 500 400 455 364 QSZ13 G5 S II / T2 HC5IC PC2.2 3686 x 1160 x 2266 4053 772

    C500 D5e * 500 400 455 364 455 364 QSX15-G8 S II HCI5C PC2.2 3427 x 1500 x 2066 4121 711

    C550 D5e * 550 440 500 400 500 400 QSX15-G8 S II HCI5D PC2.2 3427 x 1500 x 2066 4975 711

    ControllerModel

    Standby Rated Prime Rated DCC Rated

    Emissions Alternator

  • Engine Dimension (mm)Wet

    Weight (kg)

    Fuel Tank

    kVA kW kVA kW kVA kW Model L x W x H without fuel (L)

    C640D5 631 505 575 460 KTAA19-G6 HCI5E PC1.2 3684 x 1454 x 2000 4703 option

    C660 D5 ST2 660 528 600 480 QSK19-G4 T2 HCI5F PC3.3 4270 x 1674 x 2178 5073 option

    C690D5 688 550 625 500 KTAA19-G6A HCI5F PC1.2 3684 x 1454 x 2000 4700 option

    C700 D5 * 706 565 640 512 640 512 VTA28-G5 HCI5F PC3.3 4047 x 1608 x 1942 5760 option

    C825 D5A * 825 660 750 600 750 600 VTA28-G6 HCI6G PC3.3 4047 x 1608 x 2187 6040 option

    C900 D5 * 900 720 820 656 820 656 QSK23-G3 4g HCI6H PC3.3 4266 x 1879 x 2052 6680 option

    C1000 D5 * 1041 833 939 751 939 751 QST30-G3 HCI6J PC3.3 4297 x 1685 x 2079 6296 option

    C1100 D5 * 1110 888 1000 800 1000 800 QST30-G4 HCI6K PC3.3 4417 x 2000 x 2387 7374 option

    C1100 D5B * 1132 906 1029 823 1029 823 KTA38-G5/G14 HCI6K PC3.3 4470 x 1785 x 2229 8350 option

    C1250 D5A 1250 1000 1125 900 1125 900 KTA38G9 P1734A PC3.3 4722 x 1785 x 2241 8569 option

    C1400 D5 * 1400 1120 1250 1000 1250 1000 KTA50-G3 PI734B PC3.3 5283 x 2066 x 2233 10075 option

    C1675D5 * 1675 1340 1400 1120 1400 1120 KTA50-G8 PI734D PC3.3 5690 x 2033 x 2330 10324 option

    C1675 D5A * 1675 1340 1500 1200 1500 1200 KTA50-GS8 PI734D PC3.3 5690 x 2033 x 2330 10324 option

    C1760 D5e * 1760 1408 1600 1280 1600 1280 QSK60-GS3 2g PI734D PC3.3 6175 x 2494 x 3422 15736 option

    1825DQGAM * 1825 1460 1650 1320 1650 1320 QSK50G7 T2 PI734F PC3.3 6381 x 2285 x 2474 11293 option

    C2000 D5 * 2063 1650 1875 1500 1875 1500 QSK60-G3/G11 T2 PI734F PC3.3 6175 x 2286 x 2537 15152 option

    C2250 D5 * 2250 1800 2000 1600 2000 1600 QSK60-G4/G11 T2 PI734G PC3.3 6175 x 2286 x 2537 15510 option

    C2500 D5A * 2500 2000 2250 1800 2250 1800 QSK60-G8/G18 4g/T2 LVSI804R PC3.3 6175 x 2494 x 3166 17217 option

    C2750 D5B * 2750 2200 2500 2000 2500 2000 QSK60G22 2g LVSI804X PC3.3 7101 x 2635 x 3186 21106 option

    C2750 D5 * 2750 2200 2500 2000 2500 2000 QSK78-G9 4g LVSI804S PC3.3 5671 x 2948 x 3197 18871 option

    C3000 D5 * 3000 2400 2750 2200 2750 2200 QSK78-G9 4g LVSI804T PC3.3 5671 x 2948 x 3197 19282 option

    C3500 D5 * 3500 2800 3125 2500 3125 2500 QSK95G4/G10 T2/4g LVSI804W PC3.3 7889 x 3028 x 3810 29500 option

    C3750 D5 * 3750 3000 3350 2680 3350 2680 QSK95G4/G10 T2 LVSI804X PC3.3 7889 x 3028 x 3810 29500 option

    Model

    Standby Rated

    Prime Rated DCC Rated

    Emissions ControllerAlternator

  • Standby Prime Dimension (mm) L x W x H Fuel Tank

    kVA kVA L x W x H dBA@1m dBA@7m (L)

    C17 D5 16.5 15 2082 x 987 x 1525 907 74 63 150

    C22 D5 22 20 2082 x 987 x 1525 950 74 63 150

    C28 D5 27.5 25 2082 x 987 x 1525 930 74 63 150

    C33 D5 33 30 2242 x 967 x 1513 1235 75 65 175

    C38 D5 38 35 2242 x 967 x 1513 1270 75 65 175

    C44 D5L 44 40 2270 x 975 x 1920 1236 77 68 156

    C55 D5L 55 50 2270 x 975 x 1920 1236 77 68 156

    C66 D5L 66 60 2270 x 975 x 1920 1423 77 68 156

    C90 D5 90 82 3166 x 1100 x 1981 1818 78 69 350

    C110 D5 110 100 3166 x 1100 x 1981 1876.25 78 69 340

    C150 D5 150 136 3520 x 1120 x 2080 2390 77 68 448

    C170 D5 170 155 3520 x 1120 x 2080 2390 79 67 448

    C175 D5e 175 158 3900 x 1100 x 2072 3108 77 69 464

    C200 D5e 200 182 3900 x 1100 x 2072 3206 76 68 464

    C220 D5e 220 200 3900 x 1100 x 2072 3206 77 69 464

    C220 D5 220 200 3670 x 1100 x 2045 3296 76 68 350

    C250 D5 250 227 3670 x 1100 x 2045 3296 76 68 350

    C275 D5 275 250 4254 x 1424 x 2215 3924 77 69 608

    C275 D5B 275 250 4256 x 1424 x 2216 4190 77 69 533

    C300 D5 300 275 4254 x 1424 x 2215 4147 77 69 608

    C300 D5B 300 275 4256 x 1424 x 2216 4403 77 69 533

    C330 D5 330 300 4254 x 1424 x 2215 4147 77 69 608

    C330 D5B 330 300 4256 x 1424 x 2216 4403 77 69 533

    C350 D5B 350 320 4256 x 1424 x 2216 4487 77 69 533

    C400 D5 400 360 5110 x 1563 x 2447 5281 76 69 772

    C450 D5 450 409 5106 x 1553 x 2447 5281 76 69 772

    C450 D5e 450 409 5106 x 1553 x 2447 5426 77 69 711

    C450 D5eB 450 409 5094 x 1564 x 2446 5281 77 70 772

    C500 D5 500 455 5094 x 1564 x 2446 5281 77 70 772

    C500 D5e 500 455 5106 x 1553 x 2447 5426 77 69 711

    C550 D5e 550 500 5106 x 1553 x 2447 5576 77 70 711

    ModelWet Weight

    without fuel (kg)

    Sound Levels

  • GensetModel Engine Alternator Controller

    ContainerModel

    kVA kW kVA kW

    C640D5 631 505 575 460 KTAA19-G6 HCI544E PC1.2 20ft

    C700D5 706 565 640 512 VTA28G5 HCI534F PC3.3-MLD 20ft - HC

    C825D5 825 660 750 600 VTA28G6 HCI634G PC3.3-MLD 20ft - HC

    C900D5 900 720 820 656 QSK23-G3 HCI634H PC3.3 20ft - HC

    C1000D5 1062 850 1012 810 KTA38G5 HCI634J PC3.3-MLD 20ft - HC

    C1100D5B 1132 906 1029 823 KTA38G5 HCI634K PC3.3-MLD 20ft - HC

    C1250D5A 1250 1000 1125 900 KTA38G9 PI734A PC3.3-MLD 20ft - HC

    C1400D5 1400 1120 1250 1000 KTA50G3 PI734B PC3.3-MLD 40ft - HC

    C1675D5 1675 1340 1400 1120 KTA50GS8 PI734D PC3.3-MLD 40ft - HC

    C1675D5A 1675 1340 1500 1200 KTA50GS8 PI734D PC3.3-MLD 40ft - HC

    C2000D5 2063 1650 1875 1500 QSK60G3 PI734F PC3.3-MLD 40ft - HC

    C2250D5 2250 1800 2000 1600 QSK60G4 PI734G PC3.3-MLD 40ft - HC

    C2500D5A 2500 2000 2250 1800 QSK60G8 LVSI804R PC3.3-MLD 40ft - HC

    Standby Ratings Prime Ratings

  • PS0600 PC 1.2 PC 2.2 PC 3.3 PS0600 PC 1.2 PC 2.2 PC 3.3GeneralAVR • • • • Under & Over Voltage • • • •Electronic Governning • • • • Under & Over Frequency • • • •Glow plug control • • ▫ ▫ Overcurrent • • • •Cycle cranking • • • • Earth Leakage - ▫ ▫ ▫Full authority engine control - ▫ ▫ ▫ Reverse Power - - • •Networking (LonWorks) - - - - Reverse Var - - • •Networking (ModBus) • • • •Fuault history • • • • Low Oil Pressure • • • •operator interface Low Engine Coolant Temperature • • • •Manual start/stop • • • • High Engine Coolant Temperature • • • •Auto/remote start • • • • Low Coolant Level • - ▫ ▫Exercise function • - • • Low Battery Voltage • • • •Auto LED • • • • High Battery Voltage • • • •Not in Auto LED - • • • Battery Alternator Charge Fault • • • •Manual LED • • • • Over Current • • • •Common Shutdown LED • • • • Overload • • • •Common Warning LED • • • •Exercise LED - • • • Auto Synchronizing (Utility Bus) - - - •Emergency stop (local and remote) • • • • Base Load - - - •Alphanumeric screen • • • • Synchroscope - - - •Remote start input active led • • • • Peak Lopping - - - •Fault reset • • • •Measurement&Instrumentation - Engine Open Tranaition Transfer - - - •Oil Pressure • • • • Hard Closed Transition - - - •Oil Temperature - - • • Soft Closed Transition (ramping) - - - •Water Temperature • • • • Transfer & Base Load (Utility) - - - •Engine Speed • • • • Gen/Mains Breaker Control - - - •Hours Run • • • • Gen/Mains Breaker Status Protection - - - •Number of Starts • • • •Battery Voltage • • • • Operating Temp.Range -40 °C to + 70 °C • • • •Exhaust Temperature - - - - Operating Temp. User Interface -20 °C to + 70 °C • • • •Measurement&Instrumentation - Alternator Humidity up to 95% (non condensing) • • • •3 Phase L-L&L-N Voltage & Frequency • • • •3 Phase Current • • • • CE Compliant • • • •kWh - - • • NFPA110 - - • •Total kVA • • • • UL508 Listed - - • •Total kW et kVAr • - • • UL Certified - - • •PF • - • •Per Phase kVAr, kW • - • • Digital Inputs (shutdown, warning or status) 4 4 4 4Per Phase kVA • - • • Relay Outputs 2 2 4 4Shutdowe Protection & Indication - Engine Configurable Innput/Output ▫ ▫ ▫ ▫Low Fuel Level • ▫ ▫ ▫High Fuel Level - - ▫ ▫ • Standard ▫ Option - not AvailableLow Oil Pressure • • • •Hign Engine Coolant temperature • • • •Failure to Crank Shutdown • • • •Over Crank (Failure to Start) - • • •Overspeed • • • •

    PowerCommand Generator ContorlPowerCommand Generator ContorlMain Features Main FeaturesShutdown Protection & Indication - Alternator

    Threshold Warning Indications

    Paralleling Capability

    Power Transfer Function

    Environment

    Codes & Standards

    Controller Inputs/Outputs

  • power.cummins.com

    The graphical interface is easy to understand and navigate thus minimizing downtime and maximizing power

    system performance. Here are a few examples of user screens:

    HOME PAGE

    POWER SYSTEM EVENT NOTIFICATION

    WEB-BASED USER INTERFACE

    SETUP PAGE GENERATOR SET DATA PAGEDisplays system status, device status and graphing capabilities, yielding a comprehensive overview of your power system.

    Cummins Power Generation generator sets and transfer switches

    Third-party generator sets and transfer switches

    Sensors and output controls

    SMS/Text

    SMTP/Email

    SNMP/Traps

    Access the user interface from any PC, Mac or Windows 8 tablet

    Guides the user through network settings, device configurations, data log preferences, user profile settings and notifications via wizards, reducing configuration and installation time.

    Displays Annunciator, Alternator and Engine data for the selected generator set. Provides the ability to remotely start and stop generators, as well as acknowledge and reset faults.

    User-friendly icons provide point-and-click access to all functions.

    Compatible with Cummins Power Generation equipment, third-party equipment, sensors and output controls

    while offering multiple ways to view data and receive notifications.

    Ideal solution for remotely monitoring your integrated power system.

  • 14 power.cummins.com

    Level-1 (OTPC/OHPC control)

    Level-2 (OTPC/OHPC/CHPC/BTPC control)

    GTEC/OTEC control

    Microprocessor controls

    Sensing3-Phase voltage-sensing utility

    3-Phase voltage-sensing generator — single phase — single phase

    Electrical isolation from AC mains high impedance transformer transformer

    Voltage-sensing accuracy +/-2% +/-1% +/-1%

    O/U voltage-sensing utility U/V only

    O/U voltage-sensing generator U/V only

    O/U frequency-sensing utility —

    O/U frequency-sensing generator U/F only

    Voltage imbalance — —

    Phase rotation — —

    Loss of phase

    General features/serviceabilityDoor-mounted

    Controls isolated from switch during service

    Single control package for sensing/timing

    Voltage surge immunity

    Optically isolated customer I/O —

    Method(s) for sensor/timer adjustments LED configuration front panel, service software front panel, service software

    Number of time/date-stamped events — 50 50

    Real-time clock (RTC) —

    On-board diagnostics/fault detection

    Field-upgradeable software, PC diagnostics —

    Fully adjustable timers, sensors and control parameters adjustable in steps

    Mode control keyswitch interface with control —

    Supported voltages120V; 200-240V; 380-480V or ( 220-277V L-N); 600V

    Transition modesProgrammed transition

    Open transition with sync-check sensor —

    In-phase monitor — —

    Closed transition (momentary) — —

    Closed transition (soft loading/paralleling) — — —

    Display/metering/user interfaceDisplay offered/type — VFD VFD

    Front-panel LED status lamps 6-fixed (8 for config.) 6 fixed 6 fixed

    Front-panel test

    Front-panel TD override

    Front-panel lamp test/fault reset —

    Front-panel set exerciser w/display w/displayColor-coded bar graph meters for voltage, current, frequency, kW & power factor — —

    Engine-exerciser clockCalendar-based exerciser with real-time clock —

    Once/week exerciser — —

    Exerciser via external clock module — —

    Number of exercise programs 1 1 8

    Power output for external timer — — —

    Exercise exceptions — 1 8

    Standard Features Optional Features — Not Available

    • Standard Features ◦ Optinal Features - Not Available

    GTEC/OTEC control

    Level-1 (OTPC/OHPC control)

    Level-2 (OTPC/OHPC/CHPC/BTPC

    control)Sensing3-Phase voltage-sensing utility • •3-Phase voltage-sensing generator - single phase •Eletrical isolation from AC mains • transformer • transformerVoltage-sensing accuracy +/-1% +/-1%O/U voltage-sensing utility • •O/U voltage-sensing generator • •O/U voltage-frequency utility • •O/U voltage-frequency generator • •Voltage inbalance - •Phase rotation - •Loss Phase • •General features/serviceabilityDoor-mounted • •Controls islated from switch during sevice • •Single control package for sensing/timing • •Voltage surge immunity • •Optically isolated customer I/O • •Method(s) for senser/timer adjustments front panel, sevice sofeware front panel, sevice sofewareNumber of time/date-stamped events 50 50Real-time clock (RTC) • •On-board diagnostics/fault detection • •Field-upgradeable software, PC diagnostics • •Fully adjustable timers, sensors and control parameters • •Mode control keyswtich interface with control ◦ ◦Supported voltages120V;200-240V;380-480V or (220-277V L-N); 600V • •Transition modesProgrammed transtion • •Open transition with sync-check sensor • •In-phase monitor - -Closed transiton (momentary) - •Closed transiton (soft loading/paralleling) - -Display/metering/user interfaceDisplay offered/type ◦ VFD ◦ VFDFront-panel LED status lamps 6-fixed 6-fixedFront-panel test • •Front-panel TD override • •Front-panel lamp test/fault reset • •Front-panel set exerciser w/display w/displayColor-coded bar graph meters for voltage, current, frequency, kW & power factor - •

    Engine-exerciser clockCalendar-based exerciser with real-time clock • •Once/week exerciser - -Exerciser via external clock module - -Number of exercise programs 1 8Power output for external timer - -Execise exceptions •1 •8

    -••1--

    6-fixed (8 for config.)••-•

    -

    •-•--

    -

    -•-

    adjustable in steps-

    •••-

    LED configuration-

    -U/F only

    --•

    •- single phase

    • hegh impedance +/-2%U/V onlyU/V only

  • Time delaysDisplays timer delay countdown • •Field-adjustable time delays • •Time-delay engine start • •Time-delay transfer (normal to emerg) • •Time-delay retransfer (emerg to norm) • •Time-delay engine cooldown • •Time-delay elevator pre-transfer • •Time-delay programmed transition (delayed neutral) • •Time-delay override/bypass feature • •Automatic generator-generator changeover timer — •Customer inputs/outputsRemote test with load/transfer to generator • •Remote engine start • •Transfer inhibit • •Re-transfer inhibit • •Generator (source-2) common alarm • •Utility (source-1) common alarm • •Panel security lock • •Load shed input • •Generator battery charger status input • •Remote time delay override/bypass — —Remote lamp test/fault reset — —Synchronizer enable • •Bypass switch position contacts — •Generator interfaceGenerator (1) start contact (relay) • •Generator (2) start contact — •3-wire generator start compatible (use LT for this feature) — —Relay outputsSource-1 connected • •Source-2 connected • •Source-1 available • •Source-2 available • •ATS not in auto • •Test/exercise active • •Pre-transfer/load disconnect • •Load shed active • •Failure to disconnect — •Failure to close/open • •Failure to sync • •Remote communicationsRemote communications module • •Remote communications description LonWorks, NCM LonWorks, NCMRemote fault dial-out/paging • •Remote dial-in access • •Event login 50 50ATS load sequencing control • •Peer-peer system status data • •Internet-accessible sites — —Current / load monitoring — •Agency approvals, code/standards GTEC OTEC OTPC/OHPC OTPC/OHPC/CHPC/BTPCUL1008 — • • •IEC • — — —CSA, NFPA, IEEE — • • •IBC — • • •NEMA ICS 10 — • • •

    — — — —

    — — — — —

    — —

    • relay drives — — —

    — —

    ••

    — —

    — •

    — — —

    ••

    — — — —

    •••

    ••

    — •••••

    15power.cummins.com

    PowerCommand controls optimize the reliability and performance of the power generation system while keeping costs competitive and providing unique capabilities for the entire system.

    Time delaysDisplays timer delay countdown —

    Field-adjustable time delays

    Time-delay engine start

    Time-delay transfer (normal to emerg)

    Time-delay retransfer (emerg to norm)

    Time-delay engine cooldown

    Time-delay elevator pre-transfer

    Time-delay programmed transition (delayed neutral)

    Time-delay override/bypass feature

    Automatic generator-generator changeover timer — —

    Customer inputs/outputsRemote test with load/transfer to generator

    Remote engine start

    Transfer inhibit

    Re-transfer inhibit

    Generator (source-2) common alarm —

    Utility (source-1) common alarm —

    Panel security lock —

    Load shed input —

    Generator battery charger status input —

    Remote time delay override/bypass — —

    Remote lamp test/fault reset — — —

    Synchronizer enable —

    Bypass switch position contacts — —

    Generator interfaceGenerator (1) start contact (relay)

    Generator (2) start contact — —

    3-wire generator start compatible (use LT for this feature) — — —

    Relay outputsSource-1 connected

    Source-2 connected

    Source-1 available —

    Source-2 available —

    ATS not in auto —

    Test/exercise active —

    Pre-transfer/load disconnect relay drives

    Load shed active —

    Failure to disconnect — —

    Failure to close/open —

    Failure to sync —

    Remote communicationsRemote communications module —

    Remote communications description — LonWorks, NCM LonWorks, NCM

    Remote fault dial-out/paging —

    Remote dial-in access —

    Event login — 50 50

    ATS load sequencing control —

    Peer-peer system status data —

    Internet-accessible sites — — —

    Current / load monitoring — —

    Agency approvals, code/standards GTEC OTEC OTPC/OHPC OTPC/OHPC/CHPC/BTPCUL1008 —

    IEC — — —

    CSA, NFPA, IEEE —

    IBC —

    NEMA ICS 10 —

    Level-1 (OTPC/OHPC control)

    Level-2 (OTPC/OHPC/CHPC/BTPC control)

    GTEC/OTECcontrol

  • 3Public