Synchronous Generator
-
Upload
pathum-sudasinghe -
Category
Documents
-
view
5 -
download
1
description
Transcript of Synchronous Generator
Synchronous Generator
Name : S.P.M SudasingheIndex No. : 100523GGroup : G - 12Field : EEDate of Performance : 2013/08/28Date of Submission : 2013/09/20
EE 3092Laboratory Practice V
Instructed by: Mr K.K.M.S Kariyawasam
OBSERVATIONS
Name: S.P.M Sudasinghe
Index no: 100523G
Group: G – 12
Date: 2013/08/28
Instructed by: Mr K.K.M.S Kariyawasam
1. Open Circuit Test
VO/C (V) If (A)20 0.0140 0.0460 0.0580 0.07100 0.10120 0.12140 0.14160 0.17180 0.20200 0.24220 0.30240 0.38260 0.51270 0.592. Short Circuit Test
Is/c (A) If (A)0 01 0.022 0.043 0.054 0.085 0.106 0.12
3. Load Test – Inductive Load
IL (A) VL (V)3.5 2204.0 2164.5 2125.0 2065.5 2026.0 1964. Load Test – Resistive Load
IL (A) VL (V)0.38 2180.76 2161.16 2161.48 2145. Nameplate data of Synchronous machine
Rated Voltage = 240 V
Rated Current = 6.66 A
CALCULATIONS1. Calculations of Synchronous Reactance SynchronousReactance=X S=
V O /C
I S /CFrom open circuit & short circuit characteristics (graph 1),VO/C = 60V and IS/C = 2.5 A when If = 0.05 A∴ XS=
602.5
=25Ω
Similarly XS can be calculated for other values of field currents using the graph 1If (A) Observations from graph 1 Calculated XS (Ω)VO/C (V) IO/C (A)0.05 60 2.5 25.000.10 106 5.0 21.200.15 145 7.5 19.330.20 176 10.0 17.600.25 202 12.5 16.160.30 220 15.0 14.670.35 235 17.5 13.430.40 246 20.0 12.300.45 254 22.5 11.290.50 260 25.0 10.400.55 265 27.5 9.640.60 270 30.0 9.00
2. Calculation of Short Circuit Ratio ShortCircuit Ratio=Field current for rated o /c voltage
Field current for rated s /c currentAs I f ∝ I aSCR= Armature current at rated o/c voltage
rated s /c currentFrom nameplate data of synchronous machine,Rated voltage = 240 VRated current = 6.66 A
From graph 1,Armature current at rated o/c voltage = 18 A∴SCR=¿ 18
6.6 = 2.7
3. Calculation of saturated synchronous reactance In per units,X S (SAT ) , pu=
1SCR
∴ XS ( SAT ) , pu=¿ 12.7
= 0.37 puIn ohms,
X S (SAT )=X S (SAT ), pu×V rated
I rated
∴ XS (SAT )=¿ 0.37 × 2406.66
= 13.33 Ω4. Calculation of Load Voltages
E=V +~I (ra+ jX s)Where,E – No load voltageV – Terminal voltageXs – Synchronous reactance per phasera – resistance per phase
Neglecting resistance,E=V + I ¿
E=(V−I X s sinφ )+ jI X scos φ
∴E2=V 2−2VI X ssin φ+ I2 X s2
No load voltage is set to 220V. By graph 1, field current = If = 0.3 A and Is/c = 15 AHence synchronous reactance can be calculated using graph 1 as,X S (@I f=0.3 A )=
V o / c
I s/ c=220
15=14.67Ω
Assuming synchronous reactance depends only on field current, hence it is constant throughout the load test,X S=14.67ΩSample calculation for 1A Load current
-------------- (1)
a) For purely resistive load (cos φ = 1) cos φ=1
⇒
φ=0From equation 1,V 2−2V ×1×14.67×0+12×14.672=2202
V = ±219.51 V = 219.51Va) For cos φ = 0
cos φ=0⇒
φ=±900For φ=900,V 2−2V ×1×14.67×sin 900+12×14.672=2202
V 2−29.34 V−48184.79=0
V=234.67∨V=−205.33
∴ V= 234.67 VFor φ=-900,V 2−2V ×1×14.67×sin (−900 )+12×14.672=2202
V 2+29.34V−48184.79=0
V=205.33∨V=−234.67
∴ V= 205.33b) For cos φ = 0.9 cos φ=0.9
⇒
φ=±25.840For φ=25.840,V 2−2V ×1×14.67×sin 25.840+12×14.672=2202
V 2−12.79V−¿0
V=225.99∨V=−213.21
∴ V= 225.99 VFor φ=-25.840,V 2−2V ×1×14.67×sin (−25.840 )+12×14.672=2202
V 2+12.79V−48184.79=0
V=213.21∨V=−225.99
∴ V= 213.21VSimilarly terminal voltages can be calculated for other load currents.IL (A) Terminal Voltage (V)cosφ=1 cosφ = 0 cosφ = 0.9Lagging Leading Lagging Leading
(φ = -900) (φ = 900) (φ = -25.840) (φ = 25.840)1 219.51 205.33 234.67 213.21 226.002 218.03 190.66 249.34 205.62 231.204 212.03 161.32 278.68 187.99 239.146 201.62 131.98 308.02 166.88 243.618 186.08 102.64 337.36 141.83 244.1410 163.95 73.30 366.70 112.04 239.9112 131.95 43.96 396.04 75.91 229.36
DISCUSSION
1. Importance of SCR with respect to the generator performance
The ratio of field current required to produce rated voltage on open circuit to field current required to
circulate rated current on short-circuit, while the machine is mechanically driven at synchronous speed
is known as short-circuit ratio (SCR).
A small value of SCR indicates a smaller value of current under short circuit conditions owing to large
value of synchronous reactance. A machine with high value of SCR will have lower value of Xd
leading to
(i) Higher synchronizing power and so higher stability limit
(ii) Good inherent voltage regulation
(iii) Higher short-circuit current.
(iv) Satisfactory parallel operation of machines due to higher synchronizing power.
SCR for low speed generators is 1.0 to 1.5 and for modern turbo-generators is 0.5 to 0.6
2. Variation of synchronous reactance with field current
Synchronous reactance=V o /c
I s / c
It may be seen from graph 2 that the synchronous reactance decrease with the increase in field current.
This is due to magnetic saturation effect. As long as the resultant flux density due to the effect of
armature and field currents, is below the knee point of the saturation curve the flux produced per
ampere of armature current is approximately constant. Therefore the synchronous reactance is
constant. For higher flux densities the flux produced per ampere decreases and consequently the
synchronous reactance decreases.
3. Synchronous generator has characteristic of current transformer
When the secondary winding of a current transformer is short circuited, that short circuit current is
proportional to the primary current. Similarly, when the armature is short circuited in a synchronous
generator, we can observe from graph 1(the short circuit characteristic curve) that the short circuit
armature current is proportional to the field current. Hence, the synchronous generator shows
characteristics of a current transformer.
Synchronous generator’s field current depends on the connected load. Similarly in a current
transformer, the primary current depends on the load connected to the secondary winding.
Hence the armature winding of the synchronous generator act as secondary winding of the current
transformer and the field winding of the synchronous generator is similar to the primary winding of a
current transformer.
4. Variation of terminal Voltage with Load current for various power factor loads
For unity power factor, and for lagging power factors Terminal voltage always decrease when the load
current increase. But for leading power factors terminal voltage increases first and begin to fall after
some point when the load current increases. From the graph 5 we can see that load having 90 leading
power factor angle (zero leading power factor) is approximately a straight load characteristic and
always increase with load. Zero lagging power factor load has also a straight load characteristic and it
decrease always.
Normally the terminal voltage falls with the increase in load current. Reason is the increase in voltage
drop through synchronous impedance due to increasing load current.
When the power factor is leading (highly capacitive load) the effect of armature flux is to help the
main flux, hence to generate more emf. This causes the terminal voltage to increase first. But after
some value of load current effect of voltage drop through synchronous impedance becomes higher than
the increase in generated emf. Then terminal voltage starts to decrease after some value of load
current.
When power factor is lagging (highly inductive load) the effect of armature flux is to oppose the main
flux, hence to reduce generate emf. Hence terminal voltage falls rapidly with load current for lagging
power factors. Reduction of voltage with load current for lagging power factors is more than unity and
leading power factors.