SYMBOLS AND GENERAL NOTES - Lowell, MA
Transcript of SYMBOLS AND GENERAL NOTES - Lowell, MA
EL 39.68±
EL 65.68±
EL 39.68±
NOTES:
1. CONTAINMENT LINER SHALL BE INSTALLED ON
THE INTERIOR, TOP, AND BOTTOM SURFACES OF
THE CONTAINMENT CURBS; THE FULL
CONTAINMENT FLOOR SURFACE AREA, AND ALL
SURFACES OF THE EXISTING TRENCH DRAIN AND
WALLS WITHIN THE CONTAINMENT AREA TO EL
41.68 INCLUDING BENEATH CONTAINMENT CURB.
SEE SPECIFICATION SECTION 09 90 00 FOR
ADDITIONAL CONTAINMENT LINER
REQUIREMENTS.
2. ALL REPAIR AND DEMOLITION WORK SHALL BE
INCLUDED IN THE CONTRACTOR’S BASE BID
UNLESS SPECIFICALLY NOTED TO BE PART OF A
UNIT PRICE BID ITEM.
3. CONTRACTOR SHALL REPAIR LEAKING CONCRETE
CONSTRUCTION JOINTS PER REPAIR ITEM NOTES 1
AND 6/S-002. THESE REPAIRS SHALL BE
CONSIDERED PART OF REPAIR ITEM 5. SEE
REPAIR ITEM NOTES ON S-002.
4. CONSTRUCTION JOINT LOCATION IN NEED OF
REPAIR IS NOT SHOWN ON BOTTOM PLAN.
ACTUAL LOCATION OF INDICATED CONSTRUCTION
JOINT IS FURTHER WEST OF BISULFITE AREA IN
TUNNEL. CONSTRUCTION JOINT LOCATION SHALL
BE IDENTIFIED DURING JOINT INSPECTION PER
REPAIR ITEM NOTE 1 ON S-002. SEE PHOTO
6/S-563.
5. EXISTING TRENCH DRAIN SHALL REMAIN
COMPLETELY OPEN TO ALLOW DRAINAGE
THROUGH CONTAINMENT AREA. THIS SHALL
INCLUDE AREAS OF TRENCH DRAIN UNDER NEW
CONTAINMENT CURB.
6. SEE STRUCTURAL STANDARD DETAIL SHEETS FOR
REFERENCED DETAILS.
7. CONTRACTOR SHALL REPAIR LEAKING CONCRETE
EXPANSION JOINTS PER REPAIR ITEM NOTES 1
AND 9/S-002. THESE REPAIRS SHALL BE
CONSIDERED PART OF REPAIR ITEM 8. SEE
REPAIR ITEM NOTES ON S-002.
8. EXPANSION JOINT LOCATION IN NEED OF REPAIR
IS NOT SHOWN ON BOTTOM PLAN. ACTUAL
LOCATION OF INDICATED EXPANSION JOINT IS IN
TUNNEL BETWEEN SECONDARY CLARIFIERS AND
OPERATIONS LABORATORY/ADMINISTRATION
BUILDING. EXPANSION JOINT LOCATION SHALL BE
IDENTIFIED DURING JOINT INSPECTION PER
REPAIR ITEM NOTES 1 ON S-002. SEE PHOTO
7/S-563.
9. CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS AND ELEVATIONS.
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
HAZEN AND SAWYER
24 FEDERAL STREET, 5TH FLOOR
BOSTON, MA 02210
LOWELL REGIONAL WASTEWATER UTILITY
DUCK ISLAND WWTF IMPROVEMENTS
PHASE 2A
REV ISSUED FOR DATE BY
CITY OF LOWELL
LOWELL MASSACHUSETTS
0 1"1/2"
90230-411
HAZEN NO.:
DATE:
MAY 2017
DRAWING
NUMBER:
D. ST. MARIE
1 CONSTRUCTION SET
05/17
DSM
K. FICKER
S. ROESER
S-561
BISULFITE STORAGE
STRUCTURAL
PLAN, SECTION, AND
DETAILS
W. LEADBITTER
S-561
A
S-561
A
9'-0"48'-8"
11'-3"
10"47'-0"10"
10"
x EL 39.68±
CONTAINMENT LINER,
SEE NOTE 1/S-561, TYP
CONCRETE LEAKING CONSTRUCTION
JOINT REPAIR, SEE NOTES 3 AND
4/S-561 (UNIT PRICE BID ITEM)
EXISTING TRENCH DRAIN,
SEE NOTE 5/S-561
CONCRETE CRACK REPAIR, SEE NOTE
2/S-562, TYP (UNIT PRICE BID ITEM)
15"
TYP
#3 ADHESIVE DOWEL, EF, MIN
EMBED = 6" (6 TOTAL PER
CURB TO WALL CONNECTION)
EXISTING TRENCH DRAIN,
SEE NOTE 5/S-561
EXISTING WALL
EXISTING SLAB
DETAIL1
S-5613/4" = 1'-0"
CONCRETE SPALL REPAIR, SEE NOTE
4/S-562, TYP (UNIT PRICE BID ITEM)
EXISTING TRENCH DRAIN,
SEE NOTE 5/S-561
BOTTOM PLAN
3/16" = 1'-0"
SECTION
S-561
A
1/4" = 1'-0"
DETAIL2
S-5611/2" = 1'-0"
#3@12" ADHESIVE DOWELS,
MIN EMBED = 6", MIN LAP
SPLICE = 15", TYP OF THREE
SIDES
10"Wx24"H CONCRETE
CONTAINMENT CURB,
REINFORCEMENT PER
SECTION A/S-561
10"Wx24"H CONCRETE
CONTAINMENT CURB
#3@12" HORZ
BARS, EF
0325302
RETROFIT WATERSTOP
10"Wx24"H CONCRETE
CONTAINMENT CURB
EXISTING EXPANSION JOINT TO REMAIN
FILL IN EXISTING FLOOR
DRAIN SUMP WITH CONCRETE
#3@12" BARS, EW, TYP
#3@12" BARS, EW, TYP
#3@12" ADHESIVE DOWELS, MIN
EMBED = 6", MIN LAP SPLICE =
15", TYP OF THREE SIDES
FILL IN EXISTING FLOOR
DRAIN SUMP WITH CONCRETE
EXISTING CONCRETE SLAB
1
S-561
TYP
NOTE: NEW CONCRETE CONTAINMENT CURB NOT SHOWN FOR CLARITY.
2
S-561
FILL IN EXISTING FLOOR
DRAIN SUMP WITH CONCRETE
A A
CONCRETE LEAKING EXPANSION
JOINT REPAIR, SEE NOTES 7 AND
8/S-561 (UNIT PRICE BID ITEM)
EXISTING EXPANSION JOINT
PLAN
SECTION A-A
#3@12" ADHESIVE
DOWELS, EF, MIN
EMBED = 6", HOOKED
CONTAINMENT LINER,
SEE NOTE 1/S-561
EXISTING HANDRAIL,
TYP
EL 65.68±
NOTES:
1. ALL REPAIR AND DEMOLITION WORK SHALL BE
INCLUDED IN THE CONTRACTOR’S BASE BID
UNLESS SPECIFICALLY NOTED TO BE PART OF A
UNIT PRICE BID ITEM.
2. CONTRACTOR SHALL REPAIR CONCRETE CRACKS
PER REPAIR ITEM NOTES 1, 4, AND 5/S-002.
THESE REPAIRS SHALL BE CONSIDERED PART OF
REPAIR ITEMS 3 AND 4. SEE REPAIR ITEM NOTES
ON S-002.
3. CONTRACTOR SHALL REMOVE EXISTING
EQUIPMENT ACCESS DOOR INCLUDING EMBEDDED
FRAME AND REPLACE WITH NEW ACCESS DOOR
PER SPECIFICATION SECTION 05 54 63. NEW
ACCESS DOOR SHALL BE SAME SIZE AS EXISTING
ACCESS DOOR. CONTRACTOR SHALL FIELD
VERIFY ACCESS DOOR OPENING DIMENSIONS.
CONTRACTOR SHALL COORDINATE LOCATION OF
NEW ACCESS DOOR WITH OPENING FROM
REMOVED ACCESS DOOR. CONTRACTOR SHALL
CONNECT NEW FRAME DRAIN PIPE FOR ACCESS
DOOR INTO EXISTING FRAME DRAIN PIPE.
4. CONTRACTOR SHALL REPAIR CONCRETE SPALLS
PER REPAIR ITEM NOTES 1, 7, AND 8/S-002.
THESE REPAIRS SHALL BE CONSIDERED PART OF
REPAIR ITEMS 6 AND 7. SEE REPAIR ITEM NOTES
ON S-002.
5. SEE STRUCTURAL STANDARD DETAIL SHEETS FOR
REFERENCED DETAILS.
6. PHOTOS 3 AND 5 SHOW EXISTING EQUIPMENT
ACCESS DOOR.
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
HAZEN AND SAWYER
24 FEDERAL STREET, 5TH FLOOR
BOSTON, MA 02210
LOWELL REGIONAL WASTEWATER UTILITY
DUCK ISLAND WWTF IMPROVEMENTS
PHASE 2A
REV ISSUED FOR DATE BY
CITY OF LOWELL
LOWELL MASSACHUSETTS
0 1"1/2"
90230-411
HAZEN NO.:
DATE:
MAY 2017
DRAWING
NUMBER:
D. ST. MARIE
1 CONSTRUCTION SET
05/17
DSM
K. FICKER
S. ROESER
S-562
BISULFITE STORAGE
STRUCTURAL
TOP PLAN AND SECTION
W. LEADBITTER
TOP PLAN
1/4" = 1'-0"
CONCRETE CRACK
REPAIR, SEE NOTE
2/S-562, TYP
(UNIT PRICE BID
ITEM)
TYP0331004
10"W x 8"H
CONC CURB
6'-0"x6'-0" AL ACCESS
DOOR, SEE NOTE 3/S-562
SECTION
S-562
B
1/2" = 1'-0"
S-562
B
S-562
B
TYP0331004
10"W x 8"H
CONC CURB
6'-0"x6'-0" AL ACCESS
DOOR, SEE NOTE 3/S-562
EXISTING HANDRAIL,
TYP
TYP0325302
RETROFIT
WATERSTOP
CONCRETE CRACK REPAIR,
SEE NOTE 2/S-562, TYP OF
TOP AND UNDERSIDE OF
ELEVATED SLABS AND WALLS
(UNIT PRICE BID ITEM)
CONCRETE SPALL REPAIR, SEE NOTE
4/S-562, TYP OF TOP AND
UNDERSIDE OF ELEVATED SLAB AND
WALLS (UNIT PRICE BID ITEM)
x EL 65.68±
S-563
4
S-563
2
S-563
1
S-563
5
S-563
3
EXISTING GRATING ABOVE
EXISTING LOUVER
S-561
A
S-561
A
NOTES:
1. ALL REPAIR AND DEMOLITION WORK SHALL BE
INCLUDED IN THE CONTRACTOR’S BASE BID
UNLESS SPECIFICALLY NOTED TO BE PART OF A
UNIT PRICE BID ITEM.
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
HAZEN AND SAWYER
24 FEDERAL STREET, 5TH FLOOR
BOSTON, MA 02210
LOWELL REGIONAL WASTEWATER UTILITY
DUCK ISLAND WWTF IMPROVEMENTS
PHASE 2A
REV ISSUED FOR DATE BY
CITY OF LOWELL
LOWELL MASSACHUSETTS
0 1"1/2"
90230-411
HAZEN NO.:
DATE:
MAY 2017
DRAWING
NUMBER:
D. ST. MARIE
1 CONSTRUCTION SET
05/17
DSM
K. FICKER
S. ROESER
S-563
BISULFITE STORAGE
STRUCTURAL
PHOTOS
W. LEADBITTER
CONCRETE CRACK REPAIR, SEE
NOTE 2/S-562, TYP OF TOP AND
UNDERSIDE OF ELEVATED SLABS
AND WALLS (UNIT PRICE BID ITEM)
CONCRETE CRACK REPAIR, SEE NOTE 2/S-562, TYP
OF TOP AND UNDERSIDE OF ELEVATED SLABS AND
WALLS (UNIT PRICE BID ITEM)
CONCRETE CRACK REPAIR,
SEE NOTE 2/S-562, TYP OF
TOP AND UNDERSIDE OF
ELEVATED SLABS AND WALLS
(UNIT PRICE BID ITEM)
CONCRETE SPALL REPAIR, SEE NOTE 4/S-562,
TYP OF TOP AND UNDERSIDE OF ELEVATED
SLAB AND WALLS (UNIT PRICE BID ITEM)
CONCRETE CRACK REPAIR, SEE NOTE 2/S-562,
TYP OF TOP AND UNDERSIDE OF ELEVATED
SLABS AND WALLS (UNIT PRICE BID ITEM)
PHOTO
S-562
1
TOS EL 65.68 OVERVIEW
NO SCALE
PHOTO
S-562
2
CRACKING NEAR EXISTING LOUVER GRATING
NO SCALE
PHOTO
S-562
5
CRACKING NEAR EXISTING EQUIPMENT ACCESS DOOR
NO SCALE
PHOTO
S-562
4
LADDER ACCESS DOOR
NO SCALE
PHOTO
S-562
3
EQUIPMENT ACCESS DOOR
NO SCALE
PHOTO
S-561
6
CONSTRUCTION JOINT IN TUNNEL WEST OF BISULFITE AREA
NO SCALE
PHOTO
S-561
7
EXP JOINT IN TUNNEL BETWEEN SECONDARY CLARIFIERS AND ADMIN BUILDING
NO SCALE
CONCRETE LEAKING CONSTRUCTION
JOINT REPAIR, SEE NOTES 3 AND
4/S-561 (UNIT PRICE BID ITEM)
CONCRETE LEAKING EXPANSION
JOINT REPAIR, SEE NOTES 7 AND
8/S-561 (UNIT PRICE BID ITEM)
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
HAZEN AND SAWYER
24 FEDERAL STREET, 5TH FLOOR
BOSTON, MA 02210
LOWELL REGIONAL WASTEWATER UTILITY
DUCK ISLAND WWTF IMPROVEMENTS
PHASE 2A
REV ISSUED FOR DATE BY
CITY OF LOWELL
LOWELL MASSACHUSETTS
0 1"1/2"
90230-411
HAZEN NO.:
DATE:
MAY 2017
DRAWING
NUMBER:
D. ST. MARIE
1 CONSTRUCTION SET
05/17
DSM
K. FICKER
S. ROESER
S-1001
STANDARD DETAILS
STRUCTURAL
STANDARD DETAILS -
SHEET 1
W. LEADBITTER
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
HAZEN AND SAWYER
24 FEDERAL STREET, 5TH FLOOR
BOSTON, MA 02210
LOWELL REGIONAL WASTEWATER UTILITY
DUCK ISLAND WWTF IMPROVEMENTS
PHASE 2A
REV ISSUED FOR DATE BY
CITY OF LOWELL
LOWELL MASSACHUSETTS
0 1"1/2"
90230-411
HAZEN NO.:
DATE:
MAY 2017
DRAWING
NUMBER:
D. ST. MARIE
1 CONSTRUCTION SET
05/17
DSM
K. FICKER
S. ROESER
S-1002
STANDARD DETAILS
STRUCTURAL
STANDARD DETAILS -
SHEET 2
W. LEADBITTER
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
HAZEN AND SAWYER
24 FEDERAL STREET, 5TH FLOOR
BOSTON, MA 02210
LOWELL REGIONAL WASTEWATER UTILITY
DUCK ISLAND WWTF IMPROVEMENTS
PHASE 2A
REV ISSUED FOR DATE BY
CITY OF LOWELL
LOWELL MASSACHUSETTS
0 1"1/2"
90230-411
HAZEN NO.:
DATE:
MAY 2017
DRAWING
NUMBER:
D. ST. MARIE
1 CONSTRUCTION SET
05/17
DSM
K. FICKER
S. ROESER
S-1003
STANDARD DETAILS
STRUCTURAL
STANDARD DETAILS -
SHEET 3
W. LEADBITTER
ABBREVIATION
AB ANCHOR BOLT
AC ASBESTOS CEMENT
AD AREA DRAIN
ADJ ADJUSTABLE
AGGR AGGREGATE
AGL ABOVE GRADE LEVEL
AL ALUMINUM
ALLOW ALLOWANCE/ALLOWABLE
ALT ALTERNATE
APPROX APPROXIMATE
ASB ASBESTOS
ASPH ASPHALT
AT ASPHALT TILE
B BASELINE
BD BOARD
BFE BOTTOM OF FITTING ELEV
BFV BUTTERFLY VALVE
BITUM BITUMINOUS
BL BUILDING LINE
BLDG BUILDING
BLK BLOCK
BM BENCH MARK
BOC BACK OF CURB
BOT BOTTOM
BRG BEARING
BRK BRICK
BRL BUILDING RESTRICTION LINE
BRZ BRONZE
BT BOLT
BV BALL VALVE
CB CATCH BASIN
C/C CC CENTER TO CENTER
CE CONSTRUCTION EASEMENT
CEM CEMENT
CER CERAMIC
CF CUBIC FEET
CFM CUBIC FEET PER MINUTE
CLKG CAULKING
CLR CLEAR
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY UNIT
CO CLEANOUT
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
CORP CORPORATION
CPP CORRUGATED PLASTIC PIPE
CP CONCRETE PLANK
CRS COURSE
CT CERAMIC TILE
CTJ CONTROL JOINT
CV CHECK VALVE
CW COLD WATER
CY CUBIC YARD
DET DETAIL
DI DUCTILE IRON
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DISCH DISCHARGE
DIST DISTRIBUTION
DL DEAD LOAD
DN DOWN
DOZ DOZEN
DWG DRAWING
DWL DOWEL
E ELECTRICAL
EA EACH
EC ECCENTRIC
EF EACH FACE
EFF EFFLUENT
EIP EXIST IRON PIPE
EL ELEVATION
ELL ELBOW
ENGR ENGINEER
ENT ENTRANCE
EOG EDGE OF GRAVEL
EOP EDGE OF PAVEMENT
EQ EQUAL
EQPT EQUIPMENT
EW EACH WAY
EX EXISTING
EXH EXHAUST
EXP EXPANSION
EXT EXTERIOR
FAB FABRICATE
F&C FRAME AND COVER
F&G FRAME AND GRATE
FC FLUSHING CONNECTION
FD FLOOR DRAIN
FDN FOUNDATION
FH FIRE HYDRANT
FIN FINISH
FLG FLANGE
FLXC FLEXIBLE CONNECTION
FM FORCE MAIN
FNTP FEMALE NATIONAL PIPE THREAD
FPRF FIREPROOF
FRP FIBERGLASS REINFORCED PLASTIC
FT FEET
FTG FOOTING/FITTING
FURR FURRING/FURRED
G GAS/GAS LINE
GA GAUGE
GAL GALLON
GC GENERAL CONTRACTOR
GL GLASS
GPM GALLONS PER MINUTE
GV GATE VALVE
GW GUY WIRE
GYP GYPSUM
H HEIGHT
HDW HARDWARE
HEX HEXAGONAL
HORZ HORIZONTAL
HP HORSEPOWER
HPT HIGH POINT
HRG HIGH RESISTANCE GROUNDING
HVAC HEATING,VENTILATION AND AIR
CONDITIONING
HW HOT WATER
HWL HIGH WATER LEVEL
HWY HIGHWAY
HYD HYDRAULIC
I IRON
ID INSIDE DIAMETER
IF INSIDE FACE
IN INCH
INCL INCLUDED
INF INFLUENT
INT INTERIOR
INV INVERT
JB JUNCTION BOX
JCT JUNCTION
JT JOINT
L LENGTH/ANGLE
LAB LABORATORY
LAT LATERAL
LAV LAVATORY
LF LINEAR FEET
LG LONG
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LPT LOW POINT
LRG LOW RESISTANCE GROUNDING
LVR LOUVER
LWL LOW WATER LEVEL
MAINT MAINTENANCE
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MG MILLION GALLONS
MGD MILLION GALLONS PER DAY
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MJ MECHANICAL JOINT
MO MASONRY OPENING
MOD MODIFY/MODIFIED
MON MONUMENT
MTD MOUNTED
MTG MOUNTING
MULT MULTIPLE
N NORTH
NA NOT APPLICABLE
NACL SODIUM CHLORIDE
NAOH SODIUM HYDROXIDE
NAD '83 NORTH AMERICAN DATUM '83
NAVD '88 NORTH AMERICAN VERTICAL DATUM '88
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OHE OVERHEAD ELECTRIC
OPER OPERATOR
OPNG OPENING
OPP OPPOSITE
ORIG ORIGINAL
OVHD OVERHEAD
PAR PARALLEL
PCC POINT OF COMPOUND CURVE
PCF POUNDS PER CUBIC FOOT
PE PLAIN END
PERF PERFORATED
PERP PERPENDICULAR
PFM PUBLIC FACILITIES MANUAL
PI POINT OF INTERSECTION
P PROPERTY LINE/PLATE
PNL PANEL
PP POWER POLE
PREFAB PREFABRICATED
PRV PRESSURE RELIEF VALVE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POINT OF TANGENT/POINT
PV PLUG VALVE
PVC POLYVINYL CHLORIDE
PVMT PAVEMENT
QTY QUANTITY
R RADIUS/RISER
RCP REINFORCED CONCRETE PIPE
RD ROAD/ROOF DRAIN
RECIR RECIRCULATION
RECT RECTANGULAR
RED REDUCER
REF REFERENCE
REG REGISTER
REINF REINFORCING
REM REMOVE
REQD REQUIRED
REST RESTRAINED
REV REVISE
RJ RESTRAINED JOINT
RM ROOM
RND ROUND
RO ROUGH OPENING
RPM REVOLUTIONS PER MINUTE
RR RAILROAD
RT RIGHT
R/W RIGHT OF WAY
S SOUTH/SLOPE
SAN SANITARY
SBL SURVEY BASELINE
SBS SODIUM BISULFITE
SC SECONDARY CONTAINMENT
SCH SCHEDULE
S/D STORM/SITE DRAIN
SECT SECTION
SERV SERVICE
SEW SEWER
SF SQUARE FEET
SHT SHEET
SI SQUARE INCH
SIM SIMILAR
SPD SUMP PUMP DISCHARGE
SPEC SPECIFICATION
SQ SQUARE
STA STATION
STD STANDARD
STG STORAGE
SST STAINLESS STEEL
STL STEEL
STR STRUCTURAL
SUB SUBSTITUTE
SUP SUPPLY
SUR SURFACE
SUSP SUSPENDED
SWD SIDE WATER DEPTH
SYM SYMMETRICAL
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TAN TANGENT
TBM TEMPORARY BENCH MARK
TBR TO BE REMOVED
TC TOP OF CURB
TDH TOTAL DYNAMIC HEAD
TEMP TEMPERATURE
THK THICK
THRU THROUGH
TOC TOP OF CONCRETE
TOD TOP OF DECK
TOF TOP OF FOOTING
TOG TOP OF GRATING
TOM TOP OF MASONRY/MANHOLE
TOS TOP OF STEEL
TOW TOP OF WALL
TOL TOLERANCE
TS TEST STATION
TYP/(TYP) TYPICAL
UG UNDERGROUND
UGE UNDERGROUND ELECTRIC
UGG UNDERGROUND GAS
UH UNIT HEATER
UNFIN UNFINISHED
UTIL UTILITY
VAC VACUUM PIPE
VCP VITRIFIED CLAY PIPE
VEL VELOCITY
VERT VERTICAL
VOL VOLUME
VP VENT PIPE
W/M WATER METER
W WEST/WIDTH
W/ WITH
WF WIDE FLANGE
WH WALL HYDRANT
WL WATER LEVEL
W/L WATER LINE
W/M WATER METER
W/O WITHOUT
WP WATERPROOF
WPFG WATER PROOFING
WPT WALL PENETRATING TYPE
WSE WATER SURFACE ELEVATION
WSP WEATHER STRIP
WT WEIGHT
WV WATER VALVE
WWF WELDED WIRE FABRIC
YD YARD
YR YEAR
P. KNOWLES
J. BAUER
M-001
MECHANICAL
ABBREVIATION AND
SYMBOLS
P. KNOWLES
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
HAZEN AND SAWYER
24 FEDERAL STREET, 5TH FLOOR
BOSTON, MA 02210
LOWELL REGIONAL WASTEWATER UTILITY
DUCK ISLAND WWTF IMPROVEMENTS
PHASE 2A
REV ISSUED FOR DATE BY
CITY OF LOWELL
LOWELL MASSACHUSETTS
0 1"1/2"
90230-411
HAZEN NO.:
DATE:
MAY 2017
DRAWING
NUMBER:
D. ST. MARIE
1 CONSTRUCTION SET
05/17
DSM
PNEUMATIC CYLINDER ACTUATOR
VALVES
CHECK VALVE
BLIND FLANGE
HARNESSED EXPANSION JOINT
EXPANSION JOINT
HARNESSED FLANGE COUPLING ADAPTER
FLANGE COUPLING ADAPTER
HARNESSED FLEXIBLE COUPLING
FLEXIBLE COUPLING
WELDED OR REINFORCED CONCRETE
MECHANICAL JOINT
BELL & SPIGOT
FLANGE OR MECHANICAL COUPLING
UNION
HYDRAULIC CYLINDER ACTUATOR
FLEXIBLE CONNECTION
EXISTING PIPING, EQUIPMENT & STRUCTURE
WORK INCLUDED UNDER THIS CONTRACT
NEEDLE VALVE
HANDWHEEL OPERATOR
REDUCER
CAP OR PLUG
BLIND FLANGE
AIR RELEASE VALVE
BALL VALVE
CHECK VALVE
ECCENTRIC PLUG VALVE
GATE VALVE
GLOBE VALVE
LINE TYPES
ECCENTRIC PLUG VALVE
GATE VALVE
GLOBE VALVE
BALL VALVE
NEEDLE VALVE
ELECTRIC MOTOR ACTUATOR
SOLENOID ACTUATOR
DRAIN
VENT
FLAP VALVE
BUTTERFLY VALVE
PRESSURE REGULATING VALVE
PRESSURE REDUCING VALVE
AIR STATION W/QUICK DISCONNECT
STOPPLE VALVE, TEE FITTING
SYMBOLS
MISCELLANEOUS
LOW POINT DRAIN,
FLUSHING CONNECTION
DEMOLITION
SECTION AND DETAIL KEYING
DRAWING FROM WHERE SECTION WAS TAKEN
DRAWING WHERE SECTION IS SHOWN
(B) THE SECTION SHOWN ON DRAWING A6 IS IDENTIFIED AS FOLLOWS:
(A) A SECTION CUT ON DRAWING A3 IS IDENTIFIED AS FOLLOWS:
DRAWINGS ARE CROSS REFERENCED IN THE FOLLOWING METHOD:
SECTION LETTER
SECTION LETTER
DETAILS ARE CROSS REFERENCED IN A SIMILAR MANNER, EXCEPT DETAILS
ARE IDENTIFIED BY A SQUARE WITH A NUMBER IN THE UPPER HALF.
STANDARD DETAILS ARE REFERENCED BY A UNIQUE SEVEN DIGIT NUMBER
AND ARE SHOWN ON THE CONTRACT DRAWINGS BY ONE OF TWO METHODS:
1509203 REFERENCED ITEM
SEE 1509203 REFERENCED ITEM
A-6
A
A-6
A
1
A3
DRAWING WHERE PHOTO IS SHOWN
PHOTO NUMBER
(C) PHOTOS ARE REFERENCED IN THE FOLLOWING METHOD:
FUTURE PROPOSED WORK (CONTRACT 2B)
PIPING
J. IRVING
J. BAUER
M-121
HEADWORKS - INFLUENT
BUILDING
MECHANICAL
SCREW PUMPS -
DEMOLITION PLAN
D. ST. MARIE
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
HAZEN AND SAWYER
24 FEDERAL STREET, 5TH FLOOR
BOSTON, MA 02210
LOWELL REGIONAL WASTEWATER UTILITY
DUCK ISLAND WWTF IMPROVEMENTS
PHASE 2A
REV ISSUED FOR DATE BY
CITY OF LOWELL
LOWELL MASSACHUSETTS
0 1"1/2"
90230-411
HAZEN NO.:
DATE:
MAY 2017
DRAWING
NUMBER:
D. ST. MARIE
1 CONSTRUCTION SET
05/17
DSM
DEMO GREASE LINE
(TYP OF 4)
DEMOLITION PLAN
1/4" = 1'-0"
REMOVE EXISTING 4" PW
LINE. RELOCATE AS SHOWN
ON M-122
(TYP FOR 2)
1 2 3
A
B
J. IRVING
J. BAUER
M-122
HEADWORKS - INFLUENT
BUILDING
MECHANICAL
SCREW PUMPS - BOTTOM
PLAN
D. ST. MARIE
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
HAZEN AND SAWYER
24 FEDERAL STREET, 5TH FLOOR
BOSTON, MA 02210
LOWELL REGIONAL WASTEWATER UTILITY
DUCK ISLAND WWTF IMPROVEMENTS
PHASE 2A
REV ISSUED FOR DATE BY
CITY OF LOWELL
LOWELL MASSACHUSETTS
0 1"1/2"
90230-411
HAZEN NO.:
DATE:
MAY 2017
DRAWING
NUMBER:
D. ST. MARIE
1 CONSTRUCTION SET
05/17
DSM
BOTTOM PLAN
1/8" = 1'-0"
EXISTING 4" PW
(SPRAY PIPING)
(TYP OF 2)
EXISTING 8" PW
CL EL 88.94
EXISTING 6" PW CL
EL 88.94
1 1/2" CL EL 53.09
AIR DIFFUSERS
(TYP)
EXISTING 52" X 60"
SELF-CONTAINED
SLUICE GATE
48" SIPHON CL
EXISTING 42" X 60"
SELF-CONTAINED
SLUICE GATE
EXISTING 36" X 60"
SELF-CONTAINED
SLUICE GATE
30" SIPHON CL
36" SIPHON CL
EXISTING 6" POLYMER &
CHLORINE DIFFUSER
2" PVC
(TYP OF 4)
NEW GREASE LINES
(TYP OF 4)
RELOCATED 4" PW (SPRAY PIPING).
RELOCATE EXISTING ELECTRICAL
CONDUIT AS NEEDED TO INSTALL
RELOCATED SPRAY WATER LINE
(TYP OF 2)
321
B
A
INCREASE SIZE OF EXISTING WALL
CORE AS NEEDED TO INSTALL
RELOCATED SPRAY WATER PIPING
(TYP OF 2)
NOTES:
1. EACH SCREW PUMP PILLOW BLOCK AND FLANGE
UNIT SHALL BE OVERHAULED. PILLOW BLOCK
SHALL BE DISASSEMBLED AND ALL MECHANICAL
TOLERANCES SHALL BE MEASURED TO WITHIN
BEARING MANUFACTURE SPECIFICATION. INSTALL
NEW SPHERICAL ROLLER BEARINGS AND JM
CLIPPER SEALS. BEARINGS SHALL BE SKF MODEL
NO. 29452 AND NO. 23048. FLANGE SHALL BE
SANDBLASTED AND COATED IN ACCORDANCE
WITH SPECIFICATION SECTION 09 90 00.
OVERHAUL SERVICES SHALL BE PROVIDED BY
FIRST ELECTRIC MOTOR SERVICE, INC., 73
OLYMPIA AVENUE, WOBURN, MA 01801 OR
APPROVED EQUAL.
1 6
NOTES:
1. INSTALL CONNECTIONS TO EXISTING SODIUM BISULFITE
DOSING PIPING BASED ON THE SODIUM BISULFITE PIPING
CONNECTION DETAIL ON THIS SHEET WHICH
CORRESPONDS TO THE AREA CALLED OUT IN PHOTO 1 OF
THIS SHEET. REPLACE EXISTING SBS FEED PIPE OUTSIDE
OF CONTAINMENT THROUGH EXTERIOR WALL AND PROVIDE
TRANSITION FITTING TO EXISTING SINGLE WALL
DISCHARGE HEADER WITHIN CHLORINE CONTACT TANK.
2. COORDINATE WITH WORK ON SHEET M563.
3. SEE SECTION 01 92 13 FOR MAINTENANCE OF PLANT
OPERATIONS DUING CONSTRUCTION. NOTIFY PLANT STAFF
BEFORE TESTING ANY CHEMICAL SYSTEM.
4. CONTRACTOR SHALL FIELD VERIFY ALL MEASUREMENTS.
5. SUPPORT ALL PIPEWORK IN ACCORDANCE WITH SECTION
40 05 13.02.
P. KNOWLES
J. BAUER
M-521
EFFLUENT BUILDING
MECHANICAL
EFFLUENT BUILDING PLAN
S. CLUFF
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
HAZEN AND SAWYER
24 FEDERAL STREET, 5TH FLOOR
BOSTON, MA 02210
LOWELL REGIONAL WASTEWATER UTILITY
DUCK ISLAND WWTF IMPROVEMENTS
PHASE 2A
REV ISSUED FOR DATE BY
CITY OF LOWELL
LOWELL MASSACHUSETTS
0 1"1/2"
90230-411
HAZEN NO.:
DATE:
MAY 2017
DRAWING
NUMBER:
D. ST. MARIE
1 CONSTRUCTION SET
05/17
DSM
1
M-521
PHOTO
NO SCALE
1
M-521
EXISTING SODIUM BISULFITE
METERING SKID
DOWN TO EFFLUENT PUMP ROOM, SEE
DRAWING M-563 FOR CONTINUATION
SEE NOTE 1
BISULFITE PIPING PLAN ABOVE ELEVATION 67.68
1/4" = 1'-0"
3/4" HOSE SBS FEED
IN NEW 2" SCH 80 PVC
EXISTING GLOBE VALVE
TYP OF 2
NEW 1" PVC SCH 80
SLIP COUPLING
NEW 3/4"x1"x1" PVC
SCH 80 TEE
NEW 1" PVC SCH 80 SBS
FEED PIPE
EXISTING BALL VALVE
TYP OF 2
OUTSIDE EXISTING
CONTAINMENT AREA
INSIDE EXISTING
CONTAINMENT AREA
NEW 3/4" HOSE SBS FEED IN 2" SCH
80 PVC. NEW DOUBLE WALL PIPING
IS FROM NEW SBS METERING PUMP
INSTALLED AS PART OF CONTRACT
2B.
NEW 3/4" PVC SCH 80
SBS FEED PIPE
NEW 1" PVC SCH 80
UNION TYP OF 2
SODIUM BILSULFITE PIPING CONNECTION DETAIL
NTS
FROM EXISTING SBS
METERING PUMPS
REPLACE EXISTING WITH 3/4" HOSE
SBS FEED IN 2" SCH 80 PVC
EXISTING SODIUM BISULFITE METERING SKID
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
HAZEN AND SAWYER
24 FEDERAL STREET, 5TH FLOOR
BOSTON, MA 02210
LOWELL REGIONAL WASTEWATER UTILITY
DUCK ISLAND WWTF IMPROVEMENTS
PHASE 2A
REV ISSUED FOR DATE BY
CITY OF LOWELL
LOWELL MASSACHUSETTS
0 1"1/2"
90230-411
HAZEN NO.:
DATE:
MAY 2017
DRAWING
NUMBER:
D. ST. MARIE
1 CONSTRUCTION SET
05/17
DSM
SEE NOTE 4
NOTES:
1. SEE SECTION 01 92 13 FOR MAINTENANCE OF PLANT OPERATIONS DURING
CONSTRUCTION. MAINTAIN ABILITY FOR PLANT OPERATORS TO METER SODIUM
HYPOCHLORITE AT REQUIRED FEED RATES DURING THE PERIOD OF
CONSTRUCTION.
2. COORDINATE CLEANING AND DISPOSAL OF HAZARDOUS MATERIALS (ALL
CHEMICALS) IN ACCORDANCE WITH SECTION 01 35 43.13. ESTIMATED
MAXIMUM VOLUME OF CHEMICAL DISPOSED IS 3,000 GALLONS.
3. COORDINATE WITH OWNER FOR ELECTRICAL SAFING, LOCK-OUT-TAG-OUT AND
REMOVAL AND REUSE OF ELECTRICAL CONDUIT AND INSTRUMENTATION.
4. REMOVE AND DISPOSE (2) EXISTING 10,500 GALLON FRP TANKS, ALL
CHEMICAL IDENTIFICATION SIGNS, ASSOCIATED PIPING, BRACKETS AND TANK
BRACING SYSTEMS. REMOVE ELECTRICAL CONDUIT AND INSTRUMENTATION
WIRING TO EXTENT DETERMINED BY OWNER FOR REMOVAL OF TANK.
5. REUSE SAFETY LADDER AND ASSOCIATED CONNECTIONS FOR NEW 10,500 GAL
HDPE TANKS AND MODIFIED STRUCTURES. ALL ITEMS DAMAGED BY
CONTRACTOR THAT ARE INTENDED FOR REUSE SHALL BE REPLACED AT NO
ADDITIONAL COST TO THE OWNER.
6. CONTRACTOR TO COORDINATE WITH OWNER REGARDING TEMPORARY
REMOVAL OF PLANT FACILITIES FOR CONSTRUCTION PURPOSES. ANY EXISTING
FACILITIES TEMPORARILY REMOVED SHALL BE RESTORED BY CONTRACTOR TO
EXISTING CONDITIONS.
1
3
M-541
4
M-541
M-541
5
M-541
REMOVE AND REUSE SAFETY LADDER
SEE NOTE 5
SEE NOTE 4 REGARDING
ELECTRICAL CONDUIT AND
WIRING
REUSE CONTAINMENT SLEEVES
BETWEEN BUILDING AND
SECONDARY CONTAINMENT
REMOVE AND DISPOSE PVC PIPE
AND FITTINGS TO HYPO BUILDING.
SEE PHOTO 5 FOR EXTENTS OF
WORK. SEE NOTE 2.
REMOVE AND DISPOSE
PVC PIPE AND
FITTINGS
TYP OF (2) TANKS
SEE NOTE 4
REGARDING
ELECTRICAL CONDUIT
AND WIRING
2
M-541
P. KNOWLES
J. BAUER
M-541
SODIUM HYPOCHLORITE
TANKS
MECHANICAL
DEMOLITION PLAN
S. CLUFF
REMOVE AND DISPOSE SUCTION PIPE TO UNION. SEE NOTE 1.
REMOVE AND DISPOSE PRESSURE RELIEF PIPE TO UNION
SODIUM HYPOCHLORITE AND PUMP BUILDING
1/4" = 1'-0"
PHOTO
NO SCALE
EXISTING STORAGE TANKS SCOPE OF REMOVAL
M-541
1
PHOTO
NO SCALE
EXISTING STORAGE TANKS SCOPE OF REMOVAL
M-541
2
PHOTO
NO SCALE
EXISTING SUCTION AND PRESSURE RELIEF PIPING
M-541
3
PHOTO
NO SCALE
SUCTION & PRESSURE RELIEF PIPING OUTSIDE BUILDING
M-541
4
PHOTO
NO SCALE
EXISTING STORAGE TANKS SCOPE OF REMOVAL
M-541
5
P. KNOWLES
J. BAUER
M-542
SODIUM HYPOCHLORITE
TANKS
MECHANICAL
PLAN
S.CLUFF
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
HAZEN AND SAWYER
24 FEDERAL STREET, 5TH FLOOR
BOSTON, MA 02210
LOWELL REGIONAL WASTEWATER UTILITY
DUCK ISLAND WWTF IMPROVEMENTS
PHASE 2A
REV ISSUED FOR DATE BY
CITY OF LOWELL
LOWELL MASSACHUSETTS
0 1"1/2"
90230-411
HAZEN NO.:
DATE:
MAY 2017
DRAWING
NUMBER:
D. ST. MARIE
1 CONSTRUCTION SET
05/17
DSM
NOTES:
1. INSTALL NEW CHEMICAL RECEIVING AND STORAGE SYSTEM, TO INCLUDE: (2) 10,500
GALLON HDPE CHEMICAL STORAGE TANKS AND RELATED PIPING.
2. SEE SECTION 01 92 13 FOR MAINTENANCE OF PLANT OPERATIONS DURING
CONSTRUCTION. COORDINATE WITH PLANT STAFF ON SCHEDULING OF CHEMICAL
DELIVERIES AROUND CONSTRUCTION ACTIVITIES. MAINTAIN ABILITY FOR PLANT
OPERATORS TO METER SODIUM HYPOCHLORITE AT REQUIRED FEED RATES DURING THE
PERIOD OF CONSTRUCTION.
3. REUSE AND REINSTALL WORK SAFETY LADDERS ON NEW EXISTING HDPE TANKS.
4. TEMPORARY CHEMICAL SUPPLY HOSE AND NEW SODIUM HYPOCHLORITE SUPPLY PIPING
TO REUSE EXISTING 4” PIPE SLEEVE BETWEEN SECONDARY CONTAINMENT AREA AND
PUMP BUILDING.
5. NEW PRESSURE RELIEF OVERFLOW LINE TO USE EXISTING 4” PIPE SLEEVE BETWEEN
PUMP BUILDING AND SECONDARY CONTAINMENT AREA. NEW PIPE MUST BE WITHIN
CONFINES OF CONTAINMENT AREAS AT ALL TIMES.
FUTURE PROPOSED HORIZONTAL SPILL
CONTAINER FOR CHEMICAL DELIVERY.
SEE FUTURE SPILL CONTAINER
CONNECTION DETAIL THIS SHEET
(CONTRACT 2B)
(2) NEW 10,500 GAL HDPE TANKS
NEW 2" SCH 80 PVC PIPE SODIUM
HYPOCHLORITE TRANSFER
NEW 2" PVC SCH 80 SODIUM
HYPOCHLORITE SUPPLY
NEW EMERGENCY SHOWER/EYEWASH
STATION TO BE INSTALLED BY OWNER
SODIUM HYPOCHLORITE TANK PLAN
1/4" = 1'-0"
EXISTING DRAIN PIPE FROM PUMP
CONTAINMENT TO TANK
CONTAINMENT
EXISTING DRAIN TO EFFLUENT
DISINFECTION TANKS
NEW 1/2" PVC SCH 80 PRESSURE
RELIEF OVERFLOW LINE, SEE NOTE 5
FUTURE PROPOSED SODIUM
HYPOCHLORITE PERISTALTIC
PUMPS, TYP OF 2
ON EXISTING PUMP PEDESTALS
(CONTRACT 2B)
FUTURE PROPOSED SODIUM
HYPOCHLORITE PERISTALTIC PUMPS
ON NEW PUMP PEDESTALS
(CONTRACT 2B)
FUTURE PROPOSED EMERGENCY
SHOWER/EYEWASH STATION
(CONTRACT 2B)
FUTURE PROPOSED NEW SODIUM
HYPOCHLORITE PUMP CONTROL
PANEL (CONTRACT 2B)
1
5
°
1
2
0
°
4" PVC FLANGED FITTING
FLOAT SWITCH
2" PVC FLANGED FITTING
FILL CONNECTION
3" PVC FLANGED FITTING
OVERFLOW CONNECTION
24" MANWAY
6" FLANGED FITTING
VENT CONNECTION
1" PVC MOLDED OUTLET
RELIEF OVERFLOW
4" FLANGED FITTING
DISCHARGE CONNECTION
AT BASE OF TANK
1/2"= 1'-0"
TANK CONNECTION DETAIL
TANK CONNECTION LOCATIONS
SEE TANK CONNECTION DETAIL
THIS SHEET
3
0
°
12'-0"
9'-0"
12'-0"
2
0
°
8
5
°
1
'
-
1
0
1
/
2
"
3/4"x3/4"x3/4" HOSE BARB
Y-CONNECTOR
3/4"x3/4"x3/4" HOSE BARB
Y-CONNECTOR
TEMPORARY 3/4" REINFORCED
PVC HOSE, SEE NOTE 2
TEMPORARY 3/4" REINFORCED
PVC HOSE INSIDE EXISTING 4"
SLEEVE, SEE NOTE 5
1
M-542
2
M-542
MAKE MODIFICATIONS AS NECESSARY
TO TANK FLUSH PIPE TO CONNECT
TEMPORARY 3/4" REINFORCED PVC
HOSE USING COMPRESSION FITTING,
SEE NOTE 2, TYP OF (2) TANKS
MAKE MODIFICATIONS AS NECESSARY
TO PUMP SUCTION LINE TO CONNECT
TEMPORARY 3/4" REINFORCED PVC
HOSE USING COMPRESSION FITTING,
SEE NOTE 2, TYP OF (2) TANKS
FUTURE SPILL
CONTAINER
(CONTRACT 2B)
EXISTING BERM BELOW
TOP OF WALL
EL 68.38'
1/2"= 1'-0"
FUTURE SPILL CONTAINER CONNECTION DETAIL
NEW 2" SCH 80 PVC SODIUM
HYPOCHLORITE TRANSFER FILL
PIPE WITH 2" FEMALE CAM AND
GROOVE DRY DISCONNECT
FITTING AND CAP, TYP OF (2),
CL EL 68.88'
NEW 2" SCH 80 PVC UNION,
TYP OF (2)
NEW 3" SCH 80 PVC OVERFLOW PIPE.
TERMINATE 6" ABOVE SLAB ELEVATION
SEE NOTE 3
PHOTO
NO SCALE
TEMPORARY SODIUM HYPOCHLORITE
FEED CONNECTION TO TANK
1
M-542
PHOTO
NO SCALE
TEMPORARY SODIUM HYPOCHLORITE
FEED CONNECTION TO PUMPS
2
M-542
EXISTING ANCHORS, SEE
STRUCTURAL DRAWINGS
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
HAZEN AND SAWYER
24 FEDERAL STREET, 5TH FLOOR
BOSTON, MA 02210
LOWELL REGIONAL WASTEWATER UTILITY
DUCK ISLAND WWTF IMPROVEMENTS
PHASE 2A
REV ISSUED FOR DATE BY
CITY OF LOWELL
LOWELL MASSACHUSETTS
0 1"1/2"
90230-411
HAZEN NO.:
DATE:
MAY 2017
DRAWING
NUMBER:
D. ST. MARIE
1 CONSTRUCTION SET
05/17
DSM
P. KNOWLES
J. BAUER
M-562
BISULFITE STORAGE
MECHANICAL
SODIUM BISULFITE SITE
PLAN
S. CLUFF
NOTES:
1. CONTRACTOR SHALL FIELD VERIFY ALL MEASUREMENTS.
2. REMOVE EXISTING 6’-0" x 6'-0" ACCESS DOOR TO ALLOW NEW SODIUM BISULFITE
STORAGE TANKS TO BE LOWERED INTO UTILITY TUNNEL. NEW ACCESS DOOR TO BE
INSTALLED AFTER SODIUM BISULFITE TANKS ARE LOWERED INTO TUNNEL. SEE
STRUCTURAL SHEET FOR DETAILS OF ACCESS DOOR CONSTRUCTION.
3. PIPE SUPPORT SHALL BE IN ACCORDANCE WITH SECTION 40 05 13.02.
4. PIPE SLOPES TO ASSIST GRAVITY DRAINAGE. AFTER ELBOW PIPE IS HORIZONTAL
AT EL 63.3. TRANSITION TO DOUBLE WALL PIPE 6" BEFORE PENETRATION THROUGH
TUNNEL WALL. CONTINUATION OF DOUBLE WALL PIPE INSIDE TUNNEL SHOWN FOR
REFERENCE ONLY. SEE SHEET M-563 FOR CONTINUATION OF DOUBLE WALL SBS
FILL PIPE INSIDE TUNNEL.
5. SEE MECHANICAL DETAIL SHEET M-1001 FOR REFERENCE DETAILS
NEW SODIUM BISULFITE PLAN
1" = 10'-0"
FUTURE PROPOSED CONTROL
PANEL FOR SBS SUPPLY SYSTEM
(CONTRACT 2B)
NEW 6'-0" X 6'-0"' ACCESS DOOR,
SEE NOTE 2
PROPOSED FUTURE HORIZONTAL
SPILL CONTAINER FOR CHEMICAL
DELIVERY (CONTRACT 2B)
SLOPE
NEW DOUBLE WALL 2" PVC SCH
80 SBS FILL PIPE IN 3" PVC SCH
80 SC PIPE
SEE NOTE 4
EXISTING 6'-0" X 6'-0" ACCESS DOOR
AT EL 65.68
1'-3"
1509217
NEW PENETRATION, EL 63.3
20'-9"
1509217
NEW 3" PENETRATION, EL 66.13
6"
6"
2" FEMALE CAM LOCK
FITTING WITH CAP
CL EL 68.68
SECONDARY
CLARIFIER #4
SECONDARY
CLARIFIER #3
PHOTO
NO SCALEM-562
1
EXISTING ACCESS DOOR REMOVAL
SEE NOTE 2
1
M-562
1509402
NEW 2" SCH 80 PVC PIPE SBS FILL
PIPING ATTACHED TO CLARIFIER WALL
SEE NOTE 3
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
HAZEN AND SAWYER
24 FEDERAL STREET, 5TH FLOOR
BOSTON, MA 02210
LOWELL REGIONAL WASTEWATER UTILITY
DUCK ISLAND WWTF IMPROVEMENTS
PHASE 2A
REV ISSUED FOR DATE BY
CITY OF LOWELL
LOWELL MASSACHUSETTS
0 1"1/2"
90230-411
HAZEN NO.:
DATE:
MAY 2017
DRAWING
NUMBER:
D. ST. MARIE
1 CONSTRUCTION SET
05/17
DSM
NOTES:
1. CONTRACTOR SHALL FIELD VERIFY ALL MEASUREMENTS.
2. EXISTING PIPES NOT SHOWN ON PLAN VIEWS FOR CLARITY. REFER TO SECTION 1 FOR
LOCATIONS OF EXISTING PIPES.
3. SEE SECTION 01 92 13 FOR MAINTENANCE OF PLANT OPERATIONS DURING CONSTRUCTION.
4. OUTLINE OF SECONDARY CONTAINMENT CURB SHOWN FOR REFERENCE ONLY. SEE
STRUCTURAL SHEET FOR SECONDARY CONTAINMENT CURB CONSTRUCTION.
5. SEE SHEET M-562 FOR NEW ACCESS DOOR TO FACILITATE INSTALLATION OF TANKS IN
TUNNEL.
6. ALL SODIUM BISULFITE PIPING OUTSIDE OF SECONDARY CONTAINMENT CURB TO BE DOUBLE
WALL ACCORDING TO SECTION 40 05 13.73. SEE SECTION 40 05 13.02 FOR PIPE SUPPORT/PIPE
HANGER SPECIFICATIONS. SEE SHEET M-521 FOR CONTINUATION OF SODIUM BISULFITE FEED
PIPE OUTSIDE TUNNEL. 3/4" HOSE SBS FEED SHALL BE A CONTINUOUS LENGTH BETWEEN
CONNECTION TO CARRIER WATER PIPE AND CONNECTION TO EXISTING SODIUM BISULFITE
PIPING SYSTEM SHOWN ON SHEET M-521.
7. SEE SECTION 43 41 45 FOR SPECIFICATIONS OF FIBERGLASS TANKS INCLUDING VENT LINE
AND PASSIVE SCRUBBER. VENT TANKS TO COMMON 4" HEADER TERMINATING THROUGH
EXISTING FAN HOUSE TO PASSIVE SCRUBBER AS SHOWN ON SECTION 1 THIS SHEET. VENT
LINE NOT SHOWN ON TUNNEL TANK PLAN FOR CLARITY.
8. SEE M-1001 FOR MECHANICAL REFERENCE DETAILS.
9. REMOVE AND DISPOSE ENTIRE FLANGED SECTIONS OF EXISTING 12” D.I. PLANT WATER PIPE
WITHIN LIMITS SHOWN AND REPLACE WITH NEW PLANT WATER PIPING. COORDINATE WITH
PLANT STAFF BEFORE ISOLATING PLANT WATER PIPE. REPLACE EXISTING GATE VALVE ON
PLANT WATER PIPE.
10. SEE STRUCTURAL SHEETS FOR MODIFICATIONS TO EXISTING FLOOR DRAIN AND EXISTING
TRENCH DRAIN.
11. INSTALL SBS SUCTION AND DISCHARGE PIPE AS SHOWN ON SECTION 2 THIS SHEET TO ALLOW
FUTURE CONNECTION TO PROPOSED DUPLEX CHEMICAL PUMPING SKID DURING CONTRACT 2B.
MATCH CL EL OF SBS SUCTION PIPE TO INSTALLED ELEVATION OF DISCHARGE NOZZLE ON SBS
STORAGE TANK. SBS DISCHARGE PIPE NOT SHOWN ON SECTION 1 THIS SHEET FOR CLARITY.
TERMINATE SBS SUCTION AND DISCHARGE PIPE AT INSIDE WALL OF SECONDARY
CONTAINMENT CURB.
TUNNEL TANK PLAN
1/4" = 1'-0"
NEW 3/4" HOSE
SBS FEED IN NEW
2" SCH 80 PVC,
CL EL 52.88
M-563
1
M-563
1
NEW 2953 GAL
FIBERGLASS TANK
SECTION
M-563
1
1/4" = 1'-0"
SECONDARY CONTAINMENT,
SEE NOTE 4
2" PVC SCH 80 SBS FILL PIPE
CL EL 51.70
FUTURE PROPOSED DUPLEX
CHEMICAL PUMPING SKID
(CONTRACT 2B)
8" SM, CL EL 51.02
12" DR, CL EL 47.72
6" CHLORINE, CL EL 50.38
8" SM
12" DR
6" CHLORINE
8" WAS, CL EL 50.38 AND CL EL 52.38
30" RAS
NEW DOUBLE WALL 2" PVC SCH 80
SBS FILL PIPE IN 3" PVC SCH 80 SC
PIPE CL EL 54.55
8" WAS
30" RAS, CL EL 51.58
EXISTING LADDER TO
SECONDARY CLARIFIER WALKWAY
EXISTING TUNNEL EXIT STAIRWAY
12" PW
NEW 2953 GAL
FIBERGLASS TANK
4" OVERFLOW
TERMINATE 1" AFF THROUGH
DUCK BILL FITTING
NEW 1" SBS PVC SCH 80
SUCTION PIPE
UP TO EFFLUENT
BUILDING PLAN
SEE DRAWING
M-521 FOR
CONTINUATION
4" OVERFLOW (TYP)
24" MANWAY
LEVEL SENSOR (TYP) (CONTRACT 2B)
4" VENT (TYP)
12" PW, CL EL 48.78, SEE NOTE 9
4" VENT LINE THROUGH PASSIVE
SCRUBBER, SEE NOTE 7
6'-10"
NEW 2" PVC SCH 80 SBS FILL
CL EL 51.70
11'-4"
11'-4"
9'-1"
10"
(TYP)
47'-0"
12"
12"
10"
NEW 1/2" PVC SCH 80
SBS DISCHARGE, CL EL 46.50
NEW 2" PVC SCH 80
SBS SUCTION.
NEW 1" PVC SCH 80 SBS CARRIER WATER
PIPE, CAP END FOR FUTURE CONNECTION
CL EL 47.38 (CONTRACT 2B)
NEW 3/4" HOSE SBS FEED IN
NEW 2" SCH 80 PVC PIPE
CL EL 52.88
1
M-563
NEW 3/4" HOSE SBS FEED IN
2" SCH 80 PVC CL EL 52.88'
EXISTING TRENCH DRAIN
SEE NOTE 10
FUTURE PROPOSED DUPLEX
CHEMICAL PUMPING SKID
(CONTRACT 2B)
NEW 3/4" HOSE SBS FEED IN NEW 2"
SCH 80 PVC PIPE FROM EL 47.38 TO
EL 52.88
LIMITS OF REMOVAL EXISTING PLANT
WATER PIPE FROM FLANGE TO FLANGE
REPLACE EXISTING PLANT WATER
UPSTREAM ISOLATION GATE VALVE
3'-8"
6"
1" PVC SCH 80 UNION
1/2"x1"x1" SCH 80 PVC TEE
NEW 1" PVC SCH 80 SLIP TO
3/4" HOSE BARB WITH
COMPRESSION FITTING
1'-7 1/4"
EL 39.68
OUTLINE OF ACCESS HATCH ON
SECONDARY CLARIFIER WALKWAY
SHOWN FOR INFO, SEE SHEET M-562
P. KNOWLES
J. BAUER
M-563
BISULFITE STORAGE
MECHANICAL
TUNNEL SUPPLY PLAN AND
SECTION
S.CLUFF
EXISTING FLOOR DRAIN,
SEE NOTE 10
200 CFM 4" x 12" ACTIVATED
CARBON AIR SCRUBBER
EXISTING FAN HOUSE
EL 65.68
EL 57.18
PHOTO
NO SCALE
PLANT WATER PIPE MODIFICATION,
SEE NOTE 9
1
M-563
1509200
NEW 6" PENETRATION
1509211
NEW DOUBLE WALL 2" PVC SCH 80 SBS FILL
PIPE IN 3" PVC SCH 80 SC PIPE. THROUGH
NEW CORE PENETRATION AT CL EL 63.30.
SEE NOTE 6
1509211
NEW PENETRATION CL EL 63.30
M-563
2
M-563
2
NEW 2" PVC SCH 80 SBS
SUCTION, SEE NOTE 11
1/2" NPT SUCTION
1/2" NPT DISCHARGE
2 1/4"
NEW 1/2" PVC SCH 80 SBS DISCHARGE,
EL 46.50, SEE NOTE 11
OUTLINE OF EXISTING FAN HOUSE SHOWN
FOR INFO. SEE SECTION 1 ON THIS SHEET
FUTURE PROPOSED DUPLEX
CHEMICAL PUMPING SKID
WITH SUPPORT (CONTRACT 2B)
SECTION
1" = 1'-0"
FUTURE PROPOSED DUPLEX CHEMICAL
PUMPING SKID CONNECTION DETAIL
2
M-563
NOTES:
1. SEE SECTION 23 10 00 FOR DETAILS OF NEW FUEL OIL SUPPLY AND STORAGE
SYSTEM INCLUDING INTEGRATION WITH EXISTING GENERATOR SYSTEM AND
EXISTING VEEDER ROOT MODEL TLS300C CONTROL AND ALARM PANEL, AND ALL
NEW ASSOCIATED FITTINGS, VALVES, PIPING AND INSTRUMENTATION.
2. SEE SECTION 01 92 13 FOR MAINTENANCE OF PLANT OPERATIONS DURING
CONSTRUCTION. COMPLETE INSTALLATION AND TESTING OF NEW FUEL OIL
SUPPLY AND STORAGE SYSTEM BEFORE BEGINNING DECOMISSIONING OF
EXISTING FUEL OIL SUPPLY AND STORAGE SYSTEM.
3. SEE SHEET C-004 FOR DETAILS OF UNDERGROUND FUEL OIL RETURN AND
SUPPLY PIPE INSTALLATION. SEE SHEET C-006 FOR MINIMUM COVER REQUIRED
FOR PIPE BURIAL.
4. SEE SHEET C-004 FOR DETAILS OF EXISTING FUEL OIL SUPPLY SYSTEM
DECOMMISSIONING. NEW FUEL OIL SUPPLY SYSTEM SHALL BE INSTALLED,
TESTED AND OPERATING SUCCESSFULLY PRIOR TO DEMOLISHING EXISTING
FUEL TANKS. CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR THE PROTECTION
OF AND TEMPORARY MATERIALS REQUIRED FOR THE USE OF THE EXISTING
TANK DURING CONSTRUCTION.
5. COORDINATE WORK WITH ELECTRICAL SHEET FOR DETAILS OF POWER AND
COMMUNICATION TO NEW TANK LEVEL MEASURING DEVICE AND NEW
CONTAINMENT SUMP LEAK DETECTOR AND INTEGRATION WITH THE EXISTING
VEEDER ROOT MODEL TLS300C CONTROL AND ALARM PANEL.
6. PROVIDE PIPE SUPPORTS IN ACCORDANCE WITH SECTION 40 05 13.02
7. SCHEMATICS THIS SHEET SHOWN FOR INFORMATION ONLY. SEE SHEET C-004
AND SECTION 23 10 00 FOR FURTHER CONSTRUCTION DETAILS. BOTTOM
INVERT ELEVATION OF TRANSITION ASSEMBLY ADJACENT TO STORAGE TANK
SHALL BE AT 65.05 AND SHALL NOT INCLUDE 6" SC PIPE FITTINGS OR A LEAK
DETECTOR SENSOR.
8. SEE SHEET S-1002 FOR STRUCTURAL REFERENCE DETAILS.
9. COORDINATE CLEANING AND DISPOSAL OF HAZARDOUS MATERIALS IN
ACCORDANCE WITH SECTION 01 35 43.13.
10. SEAL AROUND ALL PIPE WALL PENETRATIONS USING SILICONE BASED SEALANT.
11. DO NOT BOND END CAP AND TERMINATION FITTING TO PIPE TO ALLOW FUTURE
REMOVAL FOR INSPECTION.
12. INSTALL VERTICAL LENGTH OF 18" HDPE CORRUGATED CULVERT PIPE DOWN TO
HORIZONTAL RUN OF UNDERGROUND FUEL OIL PIPE TO PROVIDE PROTECTION
TO VERTICAL RUN OF FUEL OIL PIPE. BACK FILL INSIDE CULVERT PIPE WITH
SELECT FILL TO WITHIN 4" OF GRADE AND APPLY PEA GRAVEL ABOVE SELECT
FILL TO MATCH NEW GRADE.
P. KNOWLES
J. BAUER
M-981
FUEL OIL STORAGE AND SUPPLY
MECHANICAL
PLAN AND SECTION AND GENERATOR
NEW FUEL SUPPLY SYSTEM
SCHEMATIC
S. CLUFF
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
HAZEN AND SAWYER
24 FEDERAL STREET, 5TH FLOOR
BOSTON, MA 02210
LOWELL REGIONAL WASTEWATER UTILITY
DUCK ISLAND WWTF IMPROVEMENTS
PHASE 2A
REV ISSUED FOR DATE BY
CITY OF LOWELL
LOWELL MASSACHUSETTS
0 1"1/2"
90230-411
HAZEN NO.:
DATE:
MAY 2017
DRAWING
NUMBER:
D. ST. MARIE
1 CONSTRUCTION SET
05/17
DSM
4" SCH 40 CARBON STEEL
EMERGENCY VENT PIPE
8" INTERSTITIAL
EMERGENCY VENT
4" SCH 40 CARBON STEEL PRIMARY VENT
PIPE CONNECTION
18" LOOSE BOLT MANWAY
4" TANK LEVEL GAUGE
CONNECTION
2" FLANGED TANK DISCHARGE
NOZZLE AT BASE OF TANK
FUEL TANK SECTION
1/2" = 1'-0"
R
4
'-
0
"
3
0
°
14'-0"
14'-9" O
VERALL H
EIG
HT
3'-6"
1 3'012"
1/2"=1'-0"
3
0
°
7'-0"
2" INTERSTITIAL MONITOR
CONNECTION FOR SIGHT GLASS
2" SCH 40 CARBON STEEL
FUEL OIL FILL PIPE
2" FEMALE CAM AND
GROOVE DRY BREAK
FITTING WITH CAP
EL 3.50 AGL
2" IN 4" OVERFILL
PROTECTION VALVE WITH
REMOTE FILL CONNECTION
4" SCH 40 CARBON STEEL
PRIMARY VENT WITH RAIN CAP
4" SCH 40 CARBON STEEL
EMERGENCY VENT WITH RAIN CAP
NEW FRP 2"x4" DOUBLE
WALL FUEL RETURN PIPE
8,000 GALLON 10'Ø x 14'H DOUBLE WALL
STEEL STORAGE TANK WITH 2" POUR FOAM
INSULATION AND CARBON STEEL OUTER WRAP
2" SIGHT GLASS FOR LEAK
MONITORING IN INTERSTITIAL
SPACE
EXTERIOR EQUIPMENT PAD
COORDINATE SIZE AND
LOCATION WITH
APPROVED EQUIPMENT
TOP OF SLAB EL 69.50
EXISTING GENERATOR
ENCLOSURE
EXISTING GENERATOR
DAY TANK
EXISTING PRIMARY VENT
EXISTING EMERGENCY VENT
NEW PENETRATIONS
INTO GENERATOR
ENCLOSURE
2" IN 4" OVERFILL
PROTECTION VALVE WITH
REMOTE FILL CONNECTION
EXISTING HIGH-LOW FLOAT
SWITCH CONTROL FOR
PUMP/SOLENOID ACTUATION
EXISTING FUEL PUMP
WITH STRAINER,
TYP OF (2)
NEW SOLENOID VALVE
NEW 2" SCH 40 CARBON
STEEL FUEL PIPE
NEW FRP 2"x4" DOUBLE
WALL FUEL FEED PIPE
4" CONNECTION FOR LEVEL MEASURING
DEVICE. CONNECT TO EXISTING
VEEDER ROOT MODEL TLS 300 ALARM
PANEL IN ELECTRICAL BUILDING
4" FLANGED TANK
DISCHARGE NOZZLE
NEW BELOW GROUND
HORIZONTAL PIPE MIN SLOPE 2%
TOWARDS CONTAINMENT SUMP
SEE NOTE 3
0331607
FUEL TANK PLAN
1/2" = 1'-0"
4" SCH 40 CARBON STEEL PRIMARY VENT
PIPE AND 4" SCH 40 CARBON STEEL
EMERGENCY VENT PIPE. SHALL BE 4'-0"
MINIMUM ABOVE TOP OF TANK
2" INTERSTITIAL MONITOR
CONNECTION FOR SIGHT GLASS
HORIZONTAL SPILL
CONTAINER
2" SCH 40 CARBON STEEL
FUEL OIL FILL PIPE
2" SCH 40 CARBON STEEL
FUEL OIL RETURN PIPE
NEW LOCKABLE
BALL VALVE
NEW ISOLATION
BALL VALVES
SEE NOTE 6
8" SCH 40 CARBON STEEL INTERSTITIAL
EMERGENCY VENT PIPE SHALL BE 4'-0"
MINIMUM ABOVE TOP OF TANK
EXTERIOR EQUIPMENT PAD COORDINATE
SIZE AND LOCATION WITH APPROVED
EQUIPMENT TOP SLAB EL 69.50
0331607
BOTTOM INVERT
ELEVATION 65.05
GENERATOR NEW FUEL SUPPLY SYSTEM SCHEMATIC SEE NOTE 7
NTS
FUEL OIL PIPE TRANSITION AND LEAK
DETECTION ASSEMBLY SCHEMATIC SEE NOTE 7
NTS
4" FRP END CAP,
TYP OF 2, SEE NOTE 11
4" FRP PIPE
6"x4" FRP TERMINATION FITTING
WITH 3/4" NPT TAP, SEE NOTE 11
3/4" NPT PVC CABLE GLAND FOR
LEVEL SENSOR INSTRUMENT CABLE
EXISTING GENERATOR
ENCLOSURE ON EQUIPMENT PAD
2" SCH 40 STEEL FUEL PIPE THROUGH
FRP SC PIPE, SEE NOTE 10
6" FRP SC PIPE
2" SCH 40 CARBON STEEL FUEL PIPE
2" FRP FUEL SUPPLY PIPE
6" FRP SC PIPE
LEAK DETECTOR SENSOR
6" x 4" FRP CONCENTRIC
REDUCER
4" FRP SC PIPE
4" FRP SC TEE,
TYP OF 2
2" FRP ELBOW BELLED,
TYP OF 4
1'-0"
MAX.
2'-0"
2'-7"
MIN
.
3'-0"
MIN
.
INVERT EL 64.29
2" FRP BELL x 2" FNPT ADAPTER,
TYP OF 2
2" FRP FUEL RETURN PIPE
6" FRP SC PIPE
4" FRP SC PIPE
4" FRP SC ELBOW,
TYP OF 2
4" FRP SC PIPE
NEW ISOLATION
BALL VALVE
EL 70.35
INVERT EL 64.29
18" CORRUGATED HDPE
CULVERT PIPE. PERFORATED
ABOVE GRADE TO FACILITATE
DRAINAGE. SEE NOTE 12
SEE "FUEL OIL PIPE TRANSITION
AND LEAK DETECTION ASSEMBLY
SCHEMATIC" ON THIS SHEET
SEE "FUEL OIL PIPE TRANSITION
AND LEAK DETECTION ASSEMBLY
SCHEMATIC" ON THIS SHEET
ELEVATED FLOOR PENETRATION
1509200
FLOOR SLEEVE SHALL
BE SIZED TO ALLOW
PASSAGE OF PIPE
FLANGE
CONCRETE
FLOOR
STEEL FLOOR
SLEEVE
PIPE
PROVIDE STEEL
RING COVER
MIN
3"
COMPRESSIBLE LINK TYPE
SEAL, TWO REQUIRED FOR
WALL THICKNESS GREATER
THAN 10"
FOR PIPE DIA 4" AND LESS, THE
WALL PENETRATION FOR
EXISTING WALLS MAY BE CORE
DRILLED AND SEALED WITH
COMPRESSIBLE LINK TYPE SEAL.
NONSHRINK GROUT
WALL PIPE WITH INTEGRAL
WATERSTOP (PExPE)
PIPE, 6" DIA MAX
STAINLESS STEEL BOLTS
NEW CONCRETE WALL
EXISTING CONCRETE WALL
6"
1509211
LINK SEAL WALL PENETRATION
PROVIDE 1/4" MIN PIPE
SLEEVE AT CONCRETE
MASONRY UNITS
CONCRETE MASONRY
UNIT WALL
PREMOLDED JOINT FILLER,
WRAP AROUND PIPE
1/2"x5/8" DEEP
SEALANT - BOTH SIDES
(MAKE AIRTIGHT)
EXISTING CONCRETE WALLNONSHRINK GROUT
PIPE
CUT CONCRETE MASONRY
UNITS AS REQUIRED
CAULKED WALL PENETRATION
1509217
PIPE WALL SUPPORT
CHANNEL FRAME
CARRIER PIPE
PIPE CLAMP
"Z" CLAMP
1509402
EXPANSION ANCHOR
BOLTS AS REQUIRED
PIPE WALL SUPPORT AND SUPPORT RACK
SHALL BE ASSEMBLED W/ CHANNEL FRAMES
AND ACCESSORIES AS MANUFACTURED BY
UNISTRUT CORP OR EQUAL
P. KNOWLES
J. BAUER
M-1001
STANDARD DETAILS
MECHANICAL
STANDARD DETAILS -
SHEET 1
P. KNOWLES
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
HAZEN AND SAWYER
24 FEDERAL STREET, 5TH FLOOR
BOSTON, MA 02210
LOWELL REGIONAL WASTEWATER UTILITY
DUCK ISLAND WWTF IMPROVEMENTS
PHASE 2A
REV ISSUED FOR DATE BY
CITY OF LOWELL
LOWELL MASSACHUSETTS
0 1"1/2"
90230-411
HAZEN NO.:
DATE:
MAY 2017
DRAWING
NUMBER:
D. ST. MARIE
1 CONSTRUCTION SET
05/17
DSM
HORIZONTAL SPILL CONTAINER
7/64" DIA MOUNTING HOLES
(TYP 4)
12"
24" SQUARE
12"
1/ 2" NPT DRAIN
GENERAL NOTES:
1. ALL POWER AND CONTROL CONDUITS ARE SHOWN DIAGRAMATICALLY EXACT RUNS
SHALL BE DETERMINED BY THE ELECTRICAL CONTRACTOR IN THE FIELD, EXCEPT WHERE
SPECIFICALLY DIMENSIONED ON PLANS.
2. ALL EXPOSED CONDUIT SHALL BE RUN PARALLEL TO BUILDING WALLS AND BEAMS
EXCEPT WHERE OTHERWISE SHOWN ON PLANS.
3. EXPOSED CONDUIT SHALL BE SUPPORTED FROM WALLS BY APPROVED HANGERS OF
ANGLE OR CHANNEL CONSTRUCTION.
4. EXACT CONDUIT STUB-UP LOCATIONS ARE TO BE DETERMINED BY THE ELECTRICAL
CONTRACTOR BASED ON THE CERTIFIED MANUFACTURER'S DRAWINGS OF THE
RESPECTIVE EQUIPMENT. CONDUITS FOR THE EQUIPMENT SHALL BE INSTALLED BASED
ON THE REQUIREMENTS OF THE ACTUAL EQUIPMENT FURNISHED.
5. ALL PANELBOARD CIRCUIT BREAKERS SHALL BE RATED AT 20 AMPS UNLESS NOTED
OTHERWISE.
6. ALL SINGLE PHASE POWER CONDUITS SHALL BE 3/4" WITH 3 # 12 (1-HOT, 1-NEUTRAL,
1-GROUND) AWG. UNLESS NOTED OTHERWISE.
7. FOR ALL EXTERIOR WORK AREAS, ALL CONDUITS & FITTINGS SHALL HAVE 40 MIL PVC
COATED, 2 MIL URETHANE COATED INTERIOR. ALL CONDUIT SUPPORTS AND HARDWARE
SHALL BE STAINLESS STEEL TYPE 316. ALL JUNCTION AND PULL BOXES SHALL BE 10
GAUGE, STAINLESS STEEL TYPE 316.
FOR ALL INTERIOR WORK INSIDE EXISTING ELECTRICAL BUILDING AREAS, ALL
CONDUITS & FITTINGS SHALL RIGID METAL CONDUIT. ALL CONDUIT SUPPORTS SHALL BE
AND HARDWARE SHALL BE STEEL. ALL JUNCTION AND PULL BOXES SHALL BE 10 GAUGE,
STEEL.
8. ALL ELECTRICAL WORK SHALL CONFORM TO THE LATEST EDITION OF THE NATIONAL
ELECTRIC CODE, AS WELL AS THE OTHER APPLICABLE FEDERAL STATE AND LOCAL LAWS
AND/OR ORDINANCES.
9. ALL OUTDOOR ENCLOSURES SHALL BE TYPE NEMA 4X STAINLESS STEEL UNLESS
OTHERWISE NOTED. ALL ENCLOSURES IN ELECTRICAL ROOM SHALL BE NEMA TYPE 12.
10. ALL COMPONENTS OF THE ELECTRICAL SYSTEM SHALL BE PROPERLY GROUNDED.
11. CONTRACTOR SHALL FURNISH AND INSTALL ALL ELECTRICAL EQUIPMENT REQUIRED TO
PROVIDE A COMPLETED SYSTEM IN WORKING ORDER.
12. ALL ELECTRICAL EQUIPMENT SHALL BE IDENTIFIED VIA NAMEPLATE. ALL CONTROL AND
POWER CONDUITS SHALL BE IDENTIFIED VIA CONDUIT TAGS.
13. THE CONTRACTOR SHALL VISIT THE SITE OF WORK PRIOR TO PREPARING HIS BID IN
ORDER TO FAMILIARIZE HIMSELF WITH DIFFICULTIES TO THIS PROJECT FROM THE
STANDPOINT OF UNDERSTANDING ALL FIELD CONDITIONS. WHENEVER A CONFLICT
OCCURS BETWEEN THE CONTRACT DRAWINGS, SPECIFICATIONS, AND THE
REQUIREMENTS OF THE ACTUAL FIELD CONDITIONS, THE CONTRACTOR SHALL BID ON
THE MOST EXPENSIVE METHOD OF CONSTRUCTION AND WILL NOT BE ENTITLED TO AN
EXTRA COST UNLESS MATERIALS OR EQUIPMENT NOT SHOWN ON THE DRAWINGS OR
SPECIFICATIONS OR REQUIRED BY FIELD CONDITIONS MUST BE INSTALLED.
14. THE SYMBOLS AND ABBREVIATIONS LISTED REPRESENT A COMPREHENSIVE STANDARD
GUIDE INTENDED FOR GENERAL USE ON LOWELL REGIONAL WASTEWATER UTILITY DUCK
ISLAND WWTF IMPROVEMENTS. THEREFORE, NOT ALL OF THE SYMBOLS AND
ABBREVIATIONS CONTAINED IN THIS LIST ARE NECESSARILY USED ON THIS PARTICULAR
CONTRACT.
15. CROSS OFF LINE INDICATES DEMOLITION AND REMOVAL.
16. FOR COORDINATION REFER TO MECHANICAL, AND CIVIL DRAWINGS.
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
HAZEN AND SAWYER
24 FEDERAL STREET, 5TH FLOOR
BOSTON, MA 02210
LOWELL REGIONAL WASTEWATER UTILITY
DUCK ISLAND WWTF IMPROVEMENTS
PHASE 2A
REVISSUED FOR
DATE BY
CITY OF LOWELL
LOWELL MASSACHUSETTS
0 1"1/2"
90230-411
HAZEN NO.:
DATE:
MAY 2017
DRAWING
NUMBER:
D. ST. MARIE
1 CONSTRUCTION SET
05/17DSM
W. TORRES
K. AVALOS
EG-001
FUEL OIL STORAGE AND SUPPLY
ELECTRICAL
SYMBOLS AND GENERAL NOTES
H. HARRY
CONDUIT CONCEALED IN CEILING, WALLS, BELOW
OR IN FLOOR SLAB, OR ABOVE HUNG CEILING IN
CONDUIT EXPOSED
CONDUIT TURNING DOWN
CONDUIT TURNING UP
PLAN LAYOUT
EXISTING EQUIPMENT
FINISHED AREAS
CONDUIT CONCEALED UNDERGROUND
JB EXP
JUNCTION BOX
EXP - EXPLOSION PROOF NEMA 7
ELECTRICAL CONTROL PANEL
L IS
LEVEL SENSOR
IS - INTRINSICALLY SAFE
NON FUSED DISCONNECT SWITCH
JUNCTION BOX
GROUND
EXISTING
EXPLOSION PROOF
JB
GND
EXIST
EXP
CIRCUIT BREAKER
DOWN
CONTROL PANEL
CONTROL
CIRCUIT
BREAKER
AMERICAN WIRE GAUGE
ABOVE FINISHED GRADE
ABOVE FINISHED FLOOR
DN
CP
CNTL
CKT
AFG
AWG
BKR
CB
AFF
ABBREVIATIONS
UNDERGROUND CABLE OR CONDUITUGE
PANELPNL
TYPICAL
(TYP)
UNLESS OTHERWISE NOTEDUON
NATIONAL ELECTRICAL CODEN.E.C.
LEVELL
MANUFACTURERMFG
SCHEDULE
SCH
TIWISTED SINGLE PAIR CABLETSP
TOP OF CONDUIT
TOC
NOTES:
1. CONTRACTOR SHALL REMOVE AND DISPOSE OF EXISTINGCONTROL/POWER CABLE AND CONDUITS INCLUDINGCONDUIT SUPPORTS AND INSTRUMENTATION. THIS WORKSHALL BE DONE AFTER THE NEW FUEL TANK SYSTEM ISCONSTRUCTED COMPLETELY AND FULLY OPERATIONAL.
2. CONTRACTOR SHALL FURNISH AND INSTALLCONTROL/POWER CONDUCTS AND CONDUITS AS SHOWN ONTHIS DWG.
3. CONTRACTOR SHALL FURNISH AND INSTALL (1) 1-POLE 20ABREAKER AT THE EXISTING LIGHTING PANEL.
4. CONTRACTOR SHALL FURNISH AND INSTALL A NEMA7 TYPEJUNCTION BOX WITH TERMINATION BLOCKS FORCONNECTING FIELD SENSOR CABLE WITH INCOMING #14CONDUCTORS FROM THE VEEDER ROOT CONTROL PANEL.PVC-RMC SEALING TYPE EYS CONDUIT FITTING AND 3/4" PVCTO 3/4" RGS TRANSITION FITTING SHALL BE PROVIDED.
5. CONTRACTOR SHALL CORE DRILL (1) HOLE THROUGH THEEXISTING CONCRETE WALL FOR THE HORIZONTAL SPILLCONTAINER 120V POWER CONDUIT. PROVIDE 3/4" PVC TO3/4" RGS TRANSITION FITTING.
6. REFER TO CIVIL AND MECHANICAL DRAWINGS FORCOORDINATION.
7. CONTRACTOR SHALL USE THE SAME EXISTING CORE DRILLEDHOLE PENETRATION FOR THE NEW CONDUIT INSTALLATION.
8. CONNECT NEW LEVEL SENSOR TO THE EXISTINGVEEDER-ROOT PANEL ACCORDING TO EXISTINGVEEDER-ROOT MANUFACTURER'S GUIDELINES. REFER TOSPEC. SECTION 23 10 00 ABOVE GROUND STORAGE TANKFUEL OIL FOR DETAILS AND COORDINATION.
9. CONTRACTOR SHALL FURNISH AND INSTALL 2" WIDE,DETECTABLE IDENTOLINE WARNING TAPE-ELECTRIC 12"ABOVE FROM THE TOP OF THE CONDUITS. THE IDENTOLINEWARNING TAPE SHALL HAVE THE LEGEND "CAUTION: BURIEDELECTRIC LINE BELOW."
P
L
A
N
T
N
O
R
T
H
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
HAZEN AND SAWYER
24 FEDERAL STREET, 5TH FLOOR
BOSTON, MA 02210
LOWELL REGIONAL WASTEWATER UTILITY
DUCK ISLAND WWTF IMPROVEMENTS
PHASE 2A
REV ISSUED FOR DATE BY
CITY OF LOWELL
LOWELL MASSACHUSETTS
0 1"1/2"
90230-411
HAZEN NO.:
DATE:
MAY 2017
DRAWING
NUMBER:
D. ST. MARIE
1 CONSTRUCTION SET
05/17
DSM
0
1/4"=1'-0"
1 21 7'3
15' PROPERTY LINE SETBACK
PROPERTY LINE
FLEXIBLE CONDUIT
MFG PROBE CABLE
SEE NOTE 4
3/4" RGS
2#12 + 1#12 GWD
EXISTING ELECTRICAL SERVICE BUILDING
W. TORRES
K. AVALOS
EP-981
FUEL OIL STORAGE AND SUPPLY
ELECTRICAL
PLAN
H. HARRY
EXISTING ELECTRICAL
UNDERGROUND DUCTBANK
EXISTING CU-2
EXISTING DSW-CU-2
SEE NOTE 1
EXISTING HORNS/STROBE
EXISTING HORNS/STROBE
ACKNOWLEDGE/RESET
EXISTING VEEDER-ROOT PANEL
SEE NOTE 8
TO EXISTING LIGHTING PANEL SEE NOTE 3
3/4"
PVC-SCH80
(1) TSP #16
SEE NOTE 5
SEE NOTE 7
3/4" PVC-(1)TSP #16
3/4" PVC-SCH 80
2#12 + 1#12 GND
TOC 18" BELOW GRADE (TYP)
SEE NOTE 9 (TYP)
HORIZONTAL SPILL
CONTAINER
LEVEL SENSOR BY OTHERS
IS
J
EXP
L
J
EX-001
1
EX-001
1
FUEL TANK PLAN
1/4" = 1'-0"
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
HAZEN AND SAWYER
24 FEDERAL STREET, 5TH FLOOR
BOSTON, MA 02210
LOWELL REGIONAL WASTEWATER UTILITY
DUCK ISLAND WWTF IMPROVEMENTS
PHASE 2A
REV ISSUED FOR DATE BY
CITY OF LOWELL
LOWELL MASSACHUSETTS
0 1"1/2"
90230-411
HAZEN NO.:
DATE:
MAY 2017
DRAWING
NUMBER:
D. ST. MARIE
1 CONSTRUCTION SET
05/17
DSM
W. TORRES
K. AVALOS
EX-001
ELECTRICAL
DETAILS
H. HARRY
EQUIPMENT MOUNTING PEDESTAL
NTS
NOTES:
1. ALL MOUNTING HARDWARE TO BE STAINLESS
STEEL. USE WASHERS AND SPLIT LOCK-WASHERS
UNDER ALL NUTS.
TYPICAL THRU WALL CONDUIT BANK
NTS
B281SQ POST BASE FOR B22A
NTS
NOTES:
1. STANDARD FINISH: SS4
2. WT./C 400 LBS
6
"
4
1
/
4
"
6
"
4
1
/
4
"
3 1/2"
3/4" DIA 4 HOLES
3 5/16"
BLOCK OR CONCRETE WALL NEW
OR EXISTING CONSTRUCTION
INTERIOR OR EXTERIOR
FILL IN VOIDS ALL ROUND WITH
FIRE BARRIER CAULK OR PUDDY
AS REQ'D
CONDUITS
FOR FIRE OR NON FIRE RATED WALLS
USE TW SERIES "THRU-WALL
BARRIER" SUITABLE FOR TYPE OF
APPLICATION MANUFACTURED BY
CROUSE-HINDS OR EQUAL APPROVED
BY THE ENGINEER.
SUPPORTS AS REQ'D
UNION WITH PVC COATING
GRADE
PVC SCH 80
CONDUIT COUPLING
JUNCTION BOX,
PULL BOX OR
OTHER EQUIPMENT
CONDUIT HUB WITH
PVC COATING
PVC COATED
R.G.S. CONDUIT
TYPICAL CONDUIT TERMINATION AT
OUTDOOR EQUIPMENT
NTS
USE BUSHING AND BODY OF GRIP FITTING AND
ADAPTOR NUT SUPPLIED WITH LEVEL PROBE
LIQUIDTIGHT FITTING KIT SUPPLIED WITH THE
LEVEL PROBE
FLEXIBLE CONDUIT & MFG PROBE CABLE SUPPLIED
WITH LEVEL PROBE
PVC-RGS EY TYPE FITTING WITH
EPOXY SEAL PER NFPA SPECS
3/4" PVC-RGS
CONDUIT BRACKETS
STAINLESS STEEL
TYPE 316 (TYP)
SUPPLIED BY TANK
MFG (TYP)
PVC-RGS
JUNCTION BOX
TYPE GUAC
3/4" PVC-RGS
SECTION
EP-981
1
NTS
EXPLOSION PROOF JUNCTION BOX
RISER PIPE WITH PROBE SUPPLIED
WITH LEVEL PROBE.
ELEVATION
PLAN
ELECTRICAL EQUIPMENT
ENCLOSURE
POST BASE (TYP)
3/4" DIA HOLE (TYP)
B22A CHANNEL (TYP)
MO
UN
T AT 3'-0"
4" STAINLESS STEEL
TYPE 316 B22A
CHANNEL
ELECTRICAL EQUIPMENT
ENCLOSURE
FLOOR OR
PLATFORM
1" NON-SHRINK
GROUT
REFER TO B281SQ
POST BASE
STAINLESS STEEL TYPE
316 BOLTS AND WASHERS
1/2" DIAMETER ADHESIVE
ANCHORS W/MIN EMBEDMENT
4 1/4" (TYP OF 4)