SV/S KNX-Power Supplies

36
PRODUCT MANUAL ABB i-bus® KNX SV/S KNX-Power Supplies

Transcript of SV/S KNX-Power Supplies

Page 1: SV/S KNX-Power Supplies

— PRODUCT MANUAL

ABB i-bus® KNX SV/S KNX-Power Supplies

Page 2: SV/S KNX-Power Supplies
Page 3: SV/S KNX-Power Supplies

ABB i-bus® KNX Contents

SV/S xx.xxx.x.1 | 2CDC501049D0201 Rev. A i

Contents side

1 General ................................................................................................. 3 1.1 Using the product manual .............................................................................................................3 1.1.1 Structure of the product manual ...................................................................................................4 1.1.2 Notes ............................................................................................................................................4 1.2 Product and functional overview ...................................................................................................5 1.2.1 Brief overview ...............................................................................................................................5

2 Device technology ............................................................................... 7 2.1 Standard Power Supply, 640/320/160 mA, MDRC .......................................................................7 2.1.1 Technical data ..............................................................................................................................7 2.1.2 Connection schematic ..................................................................................................................9 2.1.3 Dimension drawing ..................................................................................................................... 10 2.1.4 Operating and display elements ................................................................................................. 11 2.1.5 Mounting and installation ............................................................................................................ 11 2.2 KNX Power Supply with diagnostics, 640/320 mA, MDRC ......................................................... 12 2.2.1 Technical data ............................................................................................................................ 12 2.2.2 Connection schematic ................................................................................................................ 15 2.2.3 Dimension drawing ..................................................................................................................... 16 2.2.4 Operating and display elements ................................................................................................. 17 2.2.5 Mounting and installation ............................................................................................................ 18

3 Start-up ............................................................................................... 19 3.1 Overview..................................................................................................................................... 19 3.2 Conversion of previous application program versions ................................................................ 20 3.2.1 Procedure ................................................................................................................................... 20 3.3 Parameters ................................................................................................................................. 21 3.3.1 Parameter window General ........................................................................................................ 22 3.4 Communication objects .............................................................................................................. 24 3.4.1 Summary of communication objects ........................................................................................... 24 3.4.2 Communication objects, General ................................................................................................ 25

4 Planning and application .................................................................. 27 4.1 Additional voltage output ............................................................................................................ 27 4.2 Reset .......................................................................................................................................... 28 4.3 Faults .......................................................................................................................................... 29

A Appendix ............................................................................................ 31 A.1 Ordering details .......................................................................................................................... 31

Page 4: SV/S KNX-Power Supplies
Page 5: SV/S KNX-Power Supplies

ABB i-bus® KNX General

SV/S xx.xxx.x.1 | 2CDC501049D0201 Rev. A 3

1 General

KNX power supplies provide the system voltage (SELV) for KNX components. The choked output voltage powers individual components and enables them to communicate.

1.1 Using the product manual

This manual provides detailed technical information about the power supplies and how to mount and program them. Device application is explained using examples.

This manual is subdivided into the following sections:

Section 1 General

Section 2 Device technology

Section 3 Commissioning

Section 4 Planning and application

Section A Appendix

Page 6: SV/S KNX-Power Supplies

ABB i-bus® KNX General

4 2CDC501049D0201 Rev. A | SV/S xx.xxx.x.1

1.1.1 Structure of the product manual

All parameters are initially described in chapter 3. Following the parameter descriptions are descriptions for the communication objects.

Please note

The descriptions of parameters and communication objects in section 3 apply only to those power supplies with diagnostics functions (SV/S 30.320.2.1 and SV/S 30.640.5.1).

1.1.2 Notes

Notes and safety instructions are represented as follows in this manual:

Please note

Tips for usage and operation

Examples

Application examples, installation examples, programming examples

Important

These safety instructions are used as soon as there is danger of a malfunction without risk of damage or injury.

Caution These safety instructions are used as soon as there is danger of a malfunction without risk of damage or injury.

Danger These safety instructions are used if there is a danger to life and limb with inappropriate use.

Danger These safety instructions are used if there is an extreme danger to life with inappropriate use.

Page 7: SV/S KNX-Power Supplies

ABB i-bus® KNX General

SV/S xx.xxx.x.1 | 2CDC501049D0201 Rev. A 5

1.2 Product and functional overview

ABB power supplies are designed to be fully compatible with each other. Devices with diagnostics or bus functions for complex applications are available alongside standard devices. An uninterruptable battery backed-up version is also available.

All KNX power supplies have an integrated choke. They connect to the ABB i-bus® KNX via a bus connection terminal.

1.2.1 Brief overview

SV/S 30.160.1.1

SV/S 30.320.1.1

SV/S 30.640.3.1

SV/S 30.320.2.1

SV/S 30.640.5.1

SU/S 30.640.1**

Property Standard Diagnostics Back-up supply

Supply voltage (in V AC) 100 – 240 100 – 240 100 – 240 100 – 240 100 – 240 210 – 240 KNX rated voltage (in V DC) 30 30 30 30 30 30 KNX rated current (in mA) 160 320 640 320 640 640 Type of installation MDRC MDRC MDRC MDRC MDRC MDRC Mounting width in space units 4 4 4 4 4 8 Integrated choke Short-circuit and overload monitoring

Mains failure back-up time (in ms)

200 ms 200 ms 200 ms 200 ms 200 ms 200 ms without battery

Mains failure back-up time If used with a sealed lead-acid battery, e.g. - AM/S 12.1 - SAK 7 - 2 x SAK 7 in parallel - SAK 12 - 2 x SAK 12 in parallel - SAK 17: - 2 x SAK 17 in parallel

- - - - -

10 min.* up to 2.5 h* up to 5 h* up to 5.5 h* up to 11 h* up to 8 h* up to 16 h*

Output voltage without choke (30 V DC)

- - - -

Diagnostics or bus function - - - -

Output voltage indicator Overload Indicator Bus current indicator - - - - Telegram traffic indicator - - - - Communication error indicator - - - - Bus reset button and indicator - - - - Mains voltage OK indicator - - - - - Battery voltage OK indicator - - - - -

Floating contact for fault reporting

- - - - -

* Times based on a new battery at rated load

** see product manual 2CDC501002D0203

Page 8: SV/S KNX-Power Supplies
Page 9: SV/S KNX-Power Supplies

ABB i-bus® KNX Device technology

SV/S xx.xxx.x.1 | 2CDC501049D0201 Rev. A 7

2 Device technology

2.1 Standard Power Supply, 640/320/160 mA, MDRC

KNX power supplies generate and monitor the KNX system voltage (SELV). The bus line is decoupled from the power supply by an integrated choke. The voltage output is short-circuit and overload protected. The two-color LED indicates device output status.

Device type SV/S 30.640.3.1 has an additional 30 V DC short-circuit and overload protected voltage output that can be used to power an additional bus line (in combination with a separate choke).

2.1.1 Technical data

Supply Supply voltage Us 100 – 240 V AC, 50/60 Hz (85…265 V AC)

Power consumption - SV/S 30.160.1.1 - SV/S 30.320.1.1 - SV/S 30.640.3.1

Normal operation Maximum 6.6 W 21 W 12.5 W 30 W 24 W 55 W

Power loss - SV/S 30.160.1.1 - SV/S 30.320.1.1 - SV/S 30.640.3.1

Normal operation Maximum 1.8 W 4.4 W 2.5 W 6 W 4 W 9 W

Outputs KNX voltage output I1 Rated voltage UN Minimum distance between 2 SV/S in one line

1 line with integrated choke 30 V DC +1/-2 V, SELV 200 m (KNX bus line)

Voltage output I2 (SV/S 30.640.3.1 only) Rated voltage UN

without choke 30 V DC +1/-1 V, SELV The voltage output without choke may only be used to power an additional bus line in combination with a separate choke.

Current - SV/S 30.160.1.1 - SV/S 30.320.1.1 - SV/S 30.640.3.1 (total current I1 and I2)

Rated curr. Overload curr. Short-circuit curr. IN IOvl ISc 160 mA 0.3 A 0.5 A 320 mA 0.5 A 0.8 A 640 mA 0.9 A 1.4 A

Power failure buffering time 200 ms

Connections KNX Bus connection terminal

Mains voltage input Screw terminal 0.2…2.5 mm2 fine-strand 0.2…4 mm2 solid

Tightening torque Maximum 0.6 Nm

Operating and display elements LED status (two-colored green/red) Green: I < IOvl Red: overload. Red, flashing: short-circuit

Degree of protection IP 20 EN 60 529

2CD

C 0

71 0

04 S

0014

Page 10: SV/S KNX-Power Supplies

ABB i-bus® KNX Device technology

8 2CDC501049D0201 Rev. A | SV/S xx.xxx.x.1

Protection class II EN 61 140

Isolation category Overvoltage category Pollution degree

III under EN 60 664-1 2 under EN 60 664-1

Temperature range Operation Storage Transport

-5 °C…+45 °C -25…+55 °C -25…+70 °C

Ambient conditions Maximum air humidity 93 %, no condensation allowed

Design Modular installation device (MDRC) Modular installation device, Pro M

Main dimensions (H x W x D) 90 x 72 x 64.5 mm

Mounting width 4 x 18 mm modules

Mounting depth 64.5 mm

Mounting On 35 mm mounting rail EN 60 715

Mounting position As required

Weight Approx. 0.25 kg

Housing, color Plastic housing, gray

Approvals KNX under EN 50 090-1, -2

CE mark In accordance with the EMC guideline and low voltage guideline

Important

If the device overheats due to extended overload (> 100 °C in housing) it switches off automatically. The LED is off. The device can be switched on again only after it has been disconnected from the mains for 60 seconds and has cooled to operational temperature internally. Eliminate the cause of the overload before switching back on. When commissioning the device, ensure that the rated current is not continuously exceeded. The voltage output without choke ( I2) is not electrically isolated from the KNX voltage output (I1). It may only be used to power an additional bus line in combination with a separate choke. It may not, for example, be used to power IP devices (see SELV guidelines). Devices are designed for continuous operation. They are not approved for frequent switching on and off.

Page 11: SV/S KNX-Power Supplies

ABB i-bus® KNX Device technology

SV/S xx.xxx.x.1 | 2CDC501049D0201 Rev. A 9

2.1.2 Connection schematic

1 Bus connection terminal

2 Label carrier

3 Power supply connection Us

4 Status LED

5 Voltage output without choke, I2 (SV/S 30.640.3.1 only)

2CD

C07

2007

F001

3

Page 12: SV/S KNX-Power Supplies

ABB i-bus® KNX Device technology

10 2CDC501049D0201 Rev. A | SV/S xx.xxx.x.1

2.1.3 Dimension drawing

2CD

C07

2013

F001

3

Page 13: SV/S KNX-Power Supplies

ABB i-bus® KNX Device technology

SV/S xx.xxx.x.1 | 2CDC501049D0201 Rev. A 11

2.1.4 Operating and display elements

Indicator Description Function LED status (green/red)

Two-colored indicator for displaying mains voltage, overload and short-circuit. For SV/S 30.640.3.1, overload and short-circuit current values apply to the total current, I = I1 + I2

Green: Device operating normally (I < IOvl) Red: Overload (IOvl < I < ISc) Red, flashing: Current limiting is active Output voltage regulated downwards (I = ISc) OFF: Mains voltage absent

2.1.5 Mounting and installation

Accessibility to the device for the purpose of operation, testing, visual inspection, maintenance and repair must be provided compliant to VDE 0100-520.

Mounting Mounting and commissioning may only be carried out by electrical specialists. The appropriate standards, directives, regulations and specifications should be observed when planning and setting up electrical installations.

Protect the device from moisture, dirt and damage during transport, storage and operation.

Only operate the device within the specified technical data!

The device should only be operated in an enclosed housing (distribution board)!

Cleaning If devices become dirty, they can be cleaned using a dry cloth. Should a dry cloth not remove the dirt, they can be cleaned using a slightly moistened cloth and soap solution. Corrosive agents or solutions should never be used.

Maintenance The device is maintenance-free. No repairs should be carried out by unauthorized personnel if damage occurs, e.g. during transport and/or storage. The warranty expires if the device is opened.

Page 14: SV/S KNX-Power Supplies

ABB i-bus KNX Device technology

12 2CDC501049D0201 Rev. A | SV/S xx.xxx.x.1

2.2 KNX Power Supply with diagnostics, 640/320 mA, MDRC

KNX power supplies generate and monitor the KNX system voltage (SELV). The bus line is decoupled from the power supply by an integrated choke. Bus current, bus voltage, overload and other messages can be sent via KNX for monitoring and diagnostic purposes. The voltage output is short-circuit and overload protected.

The LEDs indicate the bus current consumption and the status of the line or device. Device type SV/S 30.640.5.1 has an additional 30 V DC short-circuit and overload protected voltage output that can be used to power an additional bus line (in combination with a separate choke).

2.2.1 Technical data

Supply Supply voltage Us 100 – 240 V AC, 50/60 Hz (85…265 V AC)

Power consumption - SV/S 30.320.2.1 - SV/S 30.640.5.1

Normal operation Maximum 12.5 W 30 W 24 W 55 W

Power loss - SV/S 30.320.2.1 - SV/S 30.640.5.1

Normal operation Maximum 2.5 W 6 W 4 W 9 W

Outputs KNX voltage output I1 Rated voltage UN Minimum distance between 2 SV/S in one line

1 line with integrated choke 30 V DC +1/-2 V, SELV 200 m (KNX bus line)

Voltage output I2 (SV/S 30.640.5.1 only) Rated voltage UN

without choke 30 V DC +1/-1 V, SELV The voltage output without choke may only be used to power an additional bus line in combination with a separate choke.

Current - SV/S 30.320.2.1 - SV/S 30.640.5.1 (total current I1 and I2)

Rated curr. Overload curr. Short-circuit curr. IN IOvl ISc 320 mA 0.5 A 0.8 A 640 mA 0.9 A 1.4 A

Power failure buffering time 200 ms

Connections KNX Bus connection terminal

Mains voltage input Screw terminal 0.2…2.5 mm2 fine-strand 0.2…4 mm2 solid

Tightening torque Maximum 0.6 Nm

2CD

C07

1017

S001

3

Page 15: SV/S KNX-Power Supplies

ABB i-bus KNX Device technology

SV/S xx.xxx.x.1 | 2CDC501049D0201 Rev. A 13

Operating and display elements Programming button and LED (red) For assignment of the physical address

UN OK LED (green) ON: Bus voltage and mains voltage OK

LED I > Imax (red) ON: Short-circuit or overload

Bus current LEDs (7 x yellow) ON: Indicates present bus current

Telegr. LED (yellow) ON: Telegram traffic

Comm. error LED (yellow) ON: Communication error on bus

Reset button and LED (red) ON: Line reset. To reset the device, press the button until the LED comes on. The line is disconnected from the voltage supply for 20 seconds. The LED then goes off again. OFF: Reset is complete.

Degree of protection IP 20 EN 60 529

Protection class II EN 61 140

Isolation category Overvoltage category Pollution degree

III under EN 60 664-1 2 under EN 60 664-1

Temperature range Operation Storage Transport

-5 °C…+45 °C -25…+55 °C -25…+70 °C

Ambient conditions Maximum air humidity 93 %, no condensation allowed

Design Modular installation device (MDRC) Modular installation device, Pro M

Main dimensions (H x W x D) 90 x 72 x 64.5 mm

Mounting width 4 x 18 mm modules

Mounting depth 64.5 mm

Mounting On 35 mm mounting rail EN 60 715

Mounting position As required

Weight Approx. 0.26 kg

Housing, color Plastic housing, gray

Approvals KNX under EN 50 090-1, -2

CE mark In accordance with the EMC guideline and low voltage guideline

Device type Application Maximum number of

communication objects Maximum number of group addresses

Maximum number of associations

SV/S 30.320.2.1 SV/S 30.640.5.1

Power Supply, Diagnosis, 320mA/...* Power Supply, Diagnosis, 640mA/...*

7 9

254 254

254 254

* … = current version number of the application

Page 16: SV/S KNX-Power Supplies

ABB i-bus KNX Device technology

14 2CDC501049D0201 Rev. A | SV/S xx.xxx.x.1

Please note

ETS and the current version of the device application are required for programming. The current version of the application is available for download at www.abb.com/knx. After import it is available in ETS under ABB/System devices/Power Supplies. The device does not support the password function of the KNX device in ETS. If you inhibit access to all the project devices using a BCU code, it has no effect on this device. Data can still be read and programmed.

Important

If the device overheats due to extended overload (> 100 °C in housing) it switches off automatically. All LEDs are OFF. The device can be switched on again only after it has been disconnected from the mains for 60 seconds and has cooled to operational temperature internally. Eliminate the cause of the overload before switching back on. When commissioning the device, ensure that the rated current is not continuously exceeded. The voltage output without choke ( I2) is not electrically isolated from the KNX voltage output (I1). It may only be used to power an additional bus line in combination with a separate choke. It may not, for example, be used to power IP devices. Devices are designed for continuous operation. They are not approved for frequent switching on and off.

Page 17: SV/S KNX-Power Supplies

ABB i-bus KNX Device technology

SV/S xx.xxx.x.1 | 2CDC501049D0201 Rev. A 15

2.2.2 Connection schematic

1 Bus connection terminal

2 Programming button and LED (red)

3 Label carrier

4 Reset button and LED (red)

5 Comm. error LED (yellow)

6 Telegr. LED (yellow)

7 Power supply connection Us

8 UN OK LED (green)

9 I > Imax LED (red)

10 Bus current LED (7 x yellow)

11 Voltage output without choke, I2 (SV/S 30.640.5.1 only)

2CD

C07

2001

F001

3

Page 18: SV/S KNX-Power Supplies

ABB i-bus KNX Device technology

16 2CDC501049D0201 Rev. A | SV/S xx.xxx.x.1

2.2.3 Dimension drawing

2CD

C07

2004

F001

3

Page 19: SV/S KNX-Power Supplies

ABB i-bus KNX Device technology

SV/S xx.xxx.x.1 | 2CDC501049D0201 Rev. A 17

2.2.4 Operating and display elements

Operation/ Indicator light

Description Function

LED green

Indicates status of mains and output voltage The LED is off during programming.

ON: Mains voltage present, device operating normally (I < IOvl)

OFF: Mains voltage absent

LED red

Indicates overload/short-circuit current. The LED lights up when the output current exceeds the overload limit (I > IOvl). For SV/S 30.640.5.1, overload and short-circuit current values apply to the total current, I = I1 + I2

SV/S 30.320.2.1 SV/S 30.640.5.1 ON (I > IOvl) I > 500 mA I > 900 mA

7 LEDs (yellow) LED No.: 7. 6. 5. 4. 3. 2. 1.

Indicates present bus current If a current value exceeds/falls below the indicator value by +/- 5 % for at least 110 ms, the LED comes ON/goes OFF. Example, SV/S 30.640.5.1: LED No. 2 (200 mA) lights up if the output current exceeds/stays at 210 mA for 110 ms. The LED goes off if the current falls below 190 mA for at least 110 ms.

LED No.:

SV/S 30.320.2.1 SV/S 30.640.5.1 Indicator value [mA]

Indicator value [mA]

7. 350 700

6. 300 600

5. 250 550

4. 200 400

3. 150 300

2. 100 200

1. 50 100

Triggers and indicates a bus reset. This function can be triggered only when mains voltage is applied. Operating one line with two power supplies: when the mains supply fails, the Reset button on the affected device does not function.

Reset button: Pressing the button for > 2 seconds triggers a reset. The line shorts. Pressing the button again during a reset has no effect (no reaction, no retrigger, no interrupt, etc.)

ON: After pressing for > 2 secs. or for the duration of the reset (20 s) after receiving the object value.

ON: After 20 s reset Flashes: At 4.8 Hz while being pressed

Indicates a KNX telegram AN: Receiving telegram

OFF: Stand-by mode

Indicates a communication error on the bus

ON: The LED comes ON for 1 second and is retriggerable if there is a transmission error or if a telegram fails or is incomplete (e.g. “BUSY”, “NAK” (receipt not correct)).

OFF: Device working normally

Please note

Individual LEDs may flash during downloads or while the application is being unloaded.

Page 20: SV/S KNX-Power Supplies

ABB i-bus KNX Device technology

18 2CDC501049D0201 Rev. A | SV/S xx.xxx.x.1

2.2.5 Mounting and installation

Accessibility to the device for the purpose of operation, testing, visual inspection, maintenance and repair must be provided compliant to VDE 0100-520.

Commissioning requirements To commission the device you will need a PC with ETS, a connection to the ABB i-bus®, e.g. via a KNX interface, and a supply voltage of 110/230 V.

Mounting Mounting and commissioning may only be carried out by electrical specialists. The appropriate standards, directives, regulations and specifications should be observed when planning and setting up electrical installations.

Protect the device from moisture, dirt and damage during transport, storage and operation.

Only operate the device within the specified technical data!

The device should only be operated in an enclosed housing (distribution board)!

Supplied state The device is supplied with the physical address 15.15.255.

The application program is pre-installed. It is therefore only necessary to load group addresses and parameters during commissioning.

However, the complete application program can be reloaded if required. Downloads may take longer after a change of application program, an interrupted download or after unloading a device.

Assignment of the physical address The assignment and programming of the physical address is carried out in ETS.

The device features a programming button for assignment of the physical device address. The red Programming LED lights up after the button has been pushed. It goes off as soon as ETS has assigned the physical address or the Programming button is pressed again.

Cleaning If devices become dirty, they can be cleaned using a dry cloth. Should a dry cloth not remove the dirt, they can be cleaned using a slightly moistened cloth and soap solution. Corrosive agents or solutions should never be used.

Maintenance The device is maintenance-free. No repairs should be carried out by unauthorized personnel if damage occurs, e.g. during transport and/or storage. The warranty expires if the device is opened.

Page 21: SV/S KNX-Power Supplies

ABB i-bus KNX Start-up

SV/S xx.xxx.x.1 | 2CDC501049D0201 Rev. A 19

3 Start-up

This section describes the functions of the SV/S 30.640.5.1 and SV/S 30.320.2.1 KNX power supplies. The devices are parameterized using the application program and Engineering Tool Software (ETS).

The application program can be found at ABB/System devices/Power Supplies.

For parameterization purposes, a PC or Laptop with ETS and a connection to the KNX, e.g. USB or IP interface, is required.

Please note

While programming the SV/S, all indicators are off and the Reset button does not function. This is also the case when the device is unloaded (ETS). However, the output voltage is generated irrespective of the indicators.

3.1 Overview

The ABB i-bus® KNX SV/S 30.640.5.1 and SV/S 30.320.2.1 power supplies have extended features for monitoring and diagnostics. The table below gives an overview of functions, the values that can be queried, and the status messages for the application program. General SV/S 30.320.2.1 SV/S 30.640.5.1 In-operation function for device monitoring ■ ■

Request status/measured values ■ ■

Bus voltage UN ■ ■

Bus current I1 ■ ■

Current voltage output I2 - ■

Total current I (= I1 + I2) - ■

Bus current I1 or total current I > rated current In ■ ■

Overload I > Imax ■ ■

Trigger bus reset ■ ■

Page 22: SV/S KNX-Power Supplies

ABB i-bus KNX Start-up

20 2CDC501049D0201 Rev. A | SV/S xx.xxx.x.1

3.2 Conversion of previous application program versions

For ABB i-bus® KNX devices, it is possible to adopt the parameter settings and group addresses from earlier versions of the application program from ETS3.

At the time of the market launch of the SV/S 30.640.5.1 and SV/S 30.320.2.1 power supplies there is no previous version of the application program. However, the conversion function can still be useful to transfer the parameterization settings and group addresses of one device to another of the same type.

3.2.1 Procedure

• Import the current VD file into ETS and add a product to the project, using the current application program.

• After you have parameterized a device, you can transfer the settings to a second device. For this purpose, the devices must already be available in the ETS project.

• Right click on the product and select Conversion in the context menu for this purpose.

• Then follow the instructions in the dialog window.

• Finally, you must replace the physical address and delete the old device.

Page 23: SV/S KNX-Power Supplies

ABB i-bus KNX Start-up

SV/S xx.xxx.x.1 | 2CDC501049D0201 Rev. A 21

3.3 Parameters

The SV/S 30.640.5.1 and SV/S 30.320.2.1 power supplies have an application program which allows you to set the measured and status values that can be queried. ETS is required for this programming.

The application program is available in ETS under ABB/System devices/Power Supplies.

The following section describes the parameters of the application program. Parameter windows are structured dynamically so that further parameters may be enabled depending on the settings and the function.

The default values of the parameters are underlined, e.g.

Options: yes no

Page 24: SV/S KNX-Power Supplies

ABB i-bus KNX Start-up

22 2CDC501049D0201 Rev. A | SV/S xx.xxx.x.1

3.3.1 Parameter window General

Send communication object "In operation" Options: no

send value 0 cyclically send value 1 cyclically

The communication object In operation indicates the presence of the device on the bus. This cyclic telegram can be monitored by an external device. If a telegram is not received, the device may be defective or the bus cable to the transmitting device may be interrupted.

no: The communication object In operation is not enabled.

• send value 0/1 cyclically: The communication object In operation (No. 0) is sent cyclically via KNX. An additional parameter appears:

Sending cycle time in s [1...65,535] Options: 1…60…65,535

Here the time interval, at which the communication object In operation (No. 0) cyclically sends a telegram, is set.

Enable communication object "Request status/measured values" 1 bit Options: no

yes

This communication object is used for requesting status and measured values. If it receives a telegram with the value 0 or 1 (depending on parameterization), measured values (communication objects 2-5) are sent via the bus. Status values (communication objects 6-7) are sent depending on parameterization

• yes: The 1 bit communication object Request status/measured values is displayed. An additional parameter is displayed:

Request with object value Options: 0

1 0 or 1

0: A telegram with object value 0 triggers sending of measured and status values.

1: A telegram with object value 1 triggers sending of measured and status values.

0 or 1: A telegram with object value 0 or 1 triggers sending of measured and status values.

Page 25: SV/S KNX-Power Supplies

ABB i-bus KNX Start-up

SV/S xx.xxx.x.1 | 2CDC501049D0201 Rev. A 23

Send status values Options: no, update only

after a change after request after a change or request

These parameters determine the send behavior of the status values. Status values are:

Total current I > Rated current In (SV/S 30.640.5.1 only)

Bus current > Rated current In (SV/S 30.320.2.1)

Overload I > Imax

• no, update only: The status values are updated but not sent (the values can be read from the communication objects).

• after a change: The status values are sent after a change.

• on request: The status values are sent after a request.

• after a change or request: The status values are sent after a change or a request.

Enable communication object “Trigger bus reset” 1 bit Options: no

yes

This parameter enables the communication object to trigger a bus reset, which shorts the bus line for 20 seconds.

• yes: The 1 bit communication object Trigger bus reset is displayed. An additional parameter is displayed:

Bus reset on object value Options: 0

1 0 or 1

0: The bus reset is triggered by object value 0

1: The bus reset is triggered by object value 1

0 or 1: The bus reset is triggered by object value 0 or 1

Page 26: SV/S KNX-Power Supplies

ABB i-bus KNX Start-up

24 2CDC501049D0201 Rev. A | SV/S xx.xxx.x.1

3.4 Communication objects

3.4.1 Summary of communication objects

CO No. Function Name Data Point

Type (DPT) Length Flags

C R W T A

0 In Operation General DPT 1.002 1 bit x x x

1 Request status/measured values General DPT 1.017 1 bit x x

2 Bus voltage UN Measured value DPT 14.027 4 byte x x x

3 Bus current I1 (only with SV/S 30.640.5.1) Bus current I (only with SV/S 30.320.2.1)

Measured value DPT 14.019 4 byte x x x

4 Current voltage output I2 (only with SV/S 30.640.5.1)

Measured value DPT 14.019 4 byte x x x

5 Total current I (only with SV/S 30.640.5.1)

Measured value DPT 14.019 4 byte x x x

6

Total current I > Rated current In (640 mA) (only with SV/S 30.640.5.1) Bus current > Rated current In (320 mA) (only with SV/S 30.320.2.1)

Status value

DPT 1.005 1 bit x x x

7 Overload I > Imax Status value DPT 1.005 1 bit x x x

8 Trigger bus reset General DPT 1.017 1 bit x x

* CO = communication object

Page 27: SV/S KNX-Power Supplies

ABB i-bus KNX Start-up

SV/S xx.xxx.x.1 | 2CDC501049D0201 Rev. A 25

3.4.2 Communication objects, General

No. Function Communication object name Data type Flags

0 In Operation General 1 bit DPT 1.002

C, R, T

The communication object is enabled if send value 0/1 cyclically is selected for the parameter Send communication object "In operation" in the General parameter window. In order to regularly monitor the presence of the device on the KNX, an in-operation monitoring telegram can be sent cyclically on the bus. As long as the communication object is activated and has a group address has been assigned, it sends a parameterizable in-operation telegram cyclically.

1 Request status/measured values General 1 bit DPT 1.017

C, W

If this communication object receives a telegram with the value 0 or 1 (depending on parameterization), the measured values of communication objects 2-7 are sent. Telegram value 1/0 = Request status values

2 Bus voltage Un Measured value 4 byte DPT 14.027

C, R, T

On request, the device uses this communication object to send the bus voltage Un to the device in V. Object value is updated every second.

3 Bus current I1 (only with SV/S 30.640.5.1) Bus current I (only with SV/S 30.320.2.1)

Measured value 4 byte DPT 14.019

C, R, T

On request, the device uses this communication object to send the bus voltage Un to the device in A. Object value is updated every second.

4 Current voltage output I2 (only with SV/S 30.640.5.1)

Measured value 4 byte DPT 14.019

C, R, T

On request, the device uses this communication object to send the current I2 on the voltage output in A. Object value is updated every second.

5 Total current I (only with SV/S 30.640.5.1)

Measured value 4 byte DPT 14.019

C, R, T

On request, the device uses this communication object to send the total current I (I1 + I2) in A. Object value is updated every second.

6 4*

Total current I > Rated current In (640 mA) (only with SV/S 30.640.5.1) Bus current > Rated current In (320 mA) (SV/S 30.320.2.1)

Status value 1 bit DPT 1.005

C, R, T

The device uses this communication object to report whether the rated current has been exceeded. If the rated current is exceeded for 10 seconds then a telegram with the value 1 is sent. The value is immediately reset to 0 when the rated current falls below the limit value. The object value is sent when there is a change, and on request. Telegram value: 0 = Bus current < Rated current IN

SV/S 30.320.2.1: IN < 315 mA SV/S 30.640.5.1: IN < 630 mA 1 = Bus current > Rated current IN SV/S 30.320.2.1: I > 320 mA for longer than 10 s SV/S 30.640.5.1: I > 640 mA for longer than 10 s

* Object no. for SV/S 30.320.2.1

Page 28: SV/S KNX-Power Supplies

ABB i-bus KNX Start-up

26 2CDC501049D0201 Rev. A | SV/S xx.xxx.x.1

7 5*

Overload I > Imax Status value 1 Bit DPT 1.005

C, R, T

The device uses this communication object to report that an overload has been detected on the output. If an overload is detected for > 10 seconds then a telegram with the value 1 is sent. The object value 0 is sent as soon as the current falls back within the limit value IOvl. Overload limit values IOvl: SV/S 30.320.2.1: IOvl = 500 mA +/- 5 % hysteresis SV/S 30.640.5.1: IOvl = 900 mA +/- 5 % hysteresis Telegram value: 0 = no overload (LED I > Imax is OFF)

SV/S 30.320.2.1: I = < 475 mA SV/S 30.640.5.1: I = < 855 mA 1 = overload (LED I > Imax is ON) SV/S 30.320.2.1: I = > 525 mA SV/S 30.640.5.1: I = > 950 mA

8 6*

Trigger bus reset General 1 bit DPT 1.017

C, W

This communication object triggers a reset for 20 seconds. The bus line is disconnected from the output voltage and shorted. This restarts devices connected to this bus line. The Reset LED lights up for the duration of the reset. Lines with two power supplies: a bus reset can be triggered only when mains voltage is applied. Telegram value: 1/0 = reset

* Object no. for SV/S 30.320.2.1

Page 29: SV/S KNX-Power Supplies

ABB i-bus KNX Planning and application

SV/S xx.xxx.x.1 | 2CDC501049D0201 Rev. A 27

4 Planning and application

4.1 Additional voltage output

Type SV/S 30.640.5.1 and SV/S 30.640.3.1 devices have a 30 V DC voltage output without choke. This can be used in combination with an additional choke to power a main or area line. To do this, the devices must be installed in accordance with the connection schematic below.

Please note

The voltage output without choke may not be used for other purposes (e.g. for connecting sensors to a binary input) because in the event of an error on the voltage output (e.g. a short-circuit) the power supply and therefore the whole KNX line connected to it will fail! The voltage output without choke ( I2) is not electrically isolated from the KNX voltage output (I1). It may only be used to power an additional bus line in combination with a separate choke. It may not, for example, be used to power IP devices (see SELV guidelines).

Page 30: SV/S KNX-Power Supplies

ABB i-bus KNX Planning and application

28 2CDC501049D0201 Rev. A | SV/S xx.xxx.x.1

4.2 Reset

During a reset the bus line is disconnected from the output voltage and shorted. This restarts devices connected to this bus line. The red Reset LED lights up for the duration of the reset. The LED goes off when the reset is complete. A reset takes around 20 seconds.

If the line is to be disconnected from the voltage for an extended period, pull off the bus connection terminals from the KNX power supply.

Reset via bus connection terminal Pull off the device's bus connection terminal for approx. 20 seconds.

Reset via button On type SV/S 30.640.5.1 and SV/S 30.320.2.1 power supplies a reset can be carried out using the Reset button. To reset the device, press the Reset button on the front for > 2 seconds. Pressing the button again during a reset has no effect (no reaction, no retrigger, no interrupt, etc.)

Reset via bus On type SV/S 30.640.5.1 and SV/S 30.320.2.1 power supplies a reset can also be carried out via the bus. The reset is triggered when a telegram is received via communication object no.8, Trigger bus reset. A bus reset can be triggered only when mains voltage is applied.

Page 31: SV/S KNX-Power Supplies

ABB i-bus KNX Planning and application

SV/S xx.xxx.x.1 | 2CDC501049D0201 Rev. A 29

4.3 Faults

SV/S 30.640.3.1, SV/S 30.320.1.1 and SV/S 30.160.1.1 Indicators for normal operation, short-circuit and overload

green/ red

Description

Recommendation

ON green

Device operating normally.

ON red

Output overloaded. Rectify overload or reduce number of bus devices until there is no longer an overload and only the green UN OK LED is lit.

Flashing red

Current limiting active. Reduce number of bus devices until only the green UN OK LED is lit.

SV/S 30.640.5.1 and SV/S 30.320.2.1 Indicators for normal operation, short-circuit and overload

Description

Recommendation

ON OFF Device operating normally. OFF ON Current limiting active. Rectify cause of short-circuit or reduce number

of bus devices until there is no longer an overload and only the green UN OK LED is lit.

ON ON Output overloaded. Reduce number of bus devices until there is no longer an overload and only the green UN OK LED is lit.

OFF OFF No mains supply. Apply mains voltage and carry out a reset if applicable.

Communication error indicators

Description

Recommendation

ON

The LED comes ON for 1 second if there is a transmission error or if a telegram fails or is incomplete (e.g. “BUSY”, “NAK” (receipt not correct)).

If the LED lights up frequently or flashes, check the topology or connections. For a more accurate diagnosis, use ETS Bus Monitor logging.

Page 32: SV/S KNX-Power Supplies
Page 33: SV/S KNX-Power Supplies

ABB i-bus KNX Appendix

SV/S xx.xxx.x.1 | 2CDC501049D0201 Rev. A 31

A Appendix

A.1 Ordering details

Short description Description Order No. bbn 40 16779 EAN

Price group

Weight 1 pcs [kg]

Pkg qty [pcs.]

SV/S 30.160.1.1 KNX Power Supply, 160 mA, MDRC 2CDG110144R0011 86666 8 P2 0.25 1

SV/S 30.320.1.1 KNX Power Supply, 320 mA, MDRC 2CDG110166R0011 90619 7 P2 0.25 1

SV/S 30.640.3.1 KNX Power Supply, 640 mA, MDRC 2CDG110167R0011 90621 0 P2 0.25 1

SV/S 30.320.2.1 KNX Power Supply with diagnostics, 320 mA, MDRC

2CDG110145R0011 83766 8 P2 0.26 1

SV/S 30.640.5.1 KNX Power Supply with diagnostics, 640 mA, MDRC

2CDG110146R0011 86669 9 P2 0.26 1

SU/S 30.640.1 Uninterruptible KNX Power Supply, 640 mA, MDRC

GHQ6310049R0111 51477 4 P2 0.55 1

Page 34: SV/S KNX-Power Supplies

ABB i-bus® KNX Appendix

32 2CDC501049D0201 Rev. A | SV/S xx.xxx.x.1

Notes

Page 35: SV/S KNX-Power Supplies
Page 36: SV/S KNX-Power Supplies

— ABB STOTZ-KONTAKT GmbH Eppelheimer Straße 82 69123 Heidelberg, Germany Telefon: +49 (0)6221 701 607 Telefax: +49 (0)6221 701 724 E-Mail: [email protected] Further Information and Local Contacts: www.abb.com/knx

— © Copyright 2017 ABB. We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase or-ders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or pos-sible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations con-tained therein. Any reproduction, disclosure to third par-ties or utilization of this contents - in whole or in parts - is forbidden without prior written consent of ABB AG.

Ord

er N

umb

er 2

CD

C50

1049

D0

201

Rev

. A (0

8.20

18)