SUBSTATION & SWITCHYARD STRUCTURE’S

57
HOW ELECTRICITY IS DELIVERED TO YOUR HOME HOW ELECTRICITY IS DELIVERED TO YOUR HOME GENERATION TRANSMISSION 230kV DELIVERY POINT SUBSTATION SUB-TRANSMISSION DISTRIBUTION

Transcript of SUBSTATION & SWITCHYARD STRUCTURE’S

Page 1: SUBSTATION & SWITCHYARD STRUCTURE’S

HOW ELECTRICITY IS DELIVERED TO YOUR HOME

HOW ELECTRICITY IS DELIVERED TO YOUR HOME

GENERATION TRANSMISSION 230kV

DELIVERY POINT SUBSTATION

SUB-TRANSMISSION

DISTRIBUTION

Page 2: SUBSTATION & SWITCHYARD STRUCTURE’S

DEFINATION’S

SUBSTATION:-AN ASSEMBLAGE OF EQUIPMENT THROUGH WHICH ELECTRICAL ENERGY IN BULK IS PASSED FOR THE PURPOSE OF SWITCHING OR MODIFYING ITS CHARACTERISTICS

SWITCHYARD:-AN ASSEMBLAGE OF SWITCHES, POWER CIRCUIT BREAKERS, BUSES AND AUXILIARY EQUIPMENT THAT IS USED TO COLLECT POWER FROM THE GENERATORS OF A POWER PLANT AND DISTRIBUTE IT TO THE TRANSMISSION LINES AT A LOAD POINT.

AS FAR AS STRUCTURES ARE CONCERNED, THE TERMS SUBSTAION AND SWITCHYARD WILL BE USED INTERCHANGEABLY.

Page 3: SUBSTATION & SWITCHYARD STRUCTURE’S

Switchyard Type• Conventional Air Insulated Type.• Gas Insulated type.• Outdoor Gas Insulated type.

Page 4: SUBSTATION & SWITCHYARD STRUCTURE’S

Switchyard Type

AIR INSULATED SUBSTATION :-• AN AIR INSULATED SUBSTATION OR

SWITCHYARD HAS THE INSULATING MEDIUM OF AIR

GAS INSULATED SUBSTATION:-• SULFUR HEXAFLUORIDE (SF6) GAS

INSULATED SUBSTATION

Page 5: SUBSTATION & SWITCHYARD STRUCTURE’S

SUBSTATION & SWITCHYARD STRUCTURE’S

• TO SUPPORT ELECTRICAL EQUIPMENTS SUCH AS• CABLE BUS,• RIGID BUS,• STRAIN BUS CONDUCTORS;• SWITCHES;• SURGE ARRESTERS;• INSULATORS

Page 6: SUBSTATION & SWITCHYARD STRUCTURE’S

SUBSTATION & SWITCHYARD STRUCTURE’S

• COMMON MATERIALS USED ARE;» CONCRETE» STEEL» ALUMINUM» WOOD

Page 7: SUBSTATION & SWITCHYARD STRUCTURE’S

SUBSTATION & SWITCHYARD STRUCTURE’S

• LATTICED ANGLES ( CHORDS & TRUSSES)• WIDE FLANGES• TUBES (ROUND, SQUARE & RECTANGULAR)• PIPES• POLYGONAL TUBES (STRAIGHT OR TAPERED)

Page 8: SUBSTATION & SWITCHYARD STRUCTURE’S

GANTRY BEAM & TOWER

Page 9: SUBSTATION & SWITCHYARD STRUCTURE’S
Page 10: SUBSTATION & SWITCHYARD STRUCTURE’S
Page 11: SUBSTATION & SWITCHYARD STRUCTURE’S

EQUIPMENT SUPPORTING BOX / TUBETYPE STRUCTURE

Page 12: SUBSTATION & SWITCHYARD STRUCTURE’S

BUSWORK SYSTEM

• RIGID BUS SYSTEM :-An Extruded Metallic Conductor. The conductor material is usually an aluminum alloy / also be Copper.

• STRAIN BUS SYSTEM:-A stranded wire conductor installed under tension.

• CABLE BUS SYSTEM:-Low-tension, stranded conductors supported on station post insulators.

Page 13: SUBSTATION & SWITCHYARD STRUCTURE’S

ELECTRICAL CLEARANCE

ELECTRICAL CLEARANCES PROVIDE THE PHYSICAL SEPRATION NEEDED FOR PHASE-TO-PHASE, PHASE-TO-STRUCTURE AND PHASE-TO-GROUND AIR GAPS TO PROVIDE SAFE WORKING AREAS AND TO PREVENT FLASHOVERS.

Page 14: SUBSTATION & SWITCHYARD STRUCTURE’S

SHORT-CIRCUIT FORCE

SHORT-CIRCUIT FORCES ARE STRUCTURE LOADS THAT ARE CAUSED BY SHORT-CIRCUIT CURRENTS. SHORT-CIRCUIT CURRENTS ARE THE RESULT OF ELECTRICAL FAULTS CAUSED BY EQUIPMENT OR MATERIAL FAILURE, LIGHTNING OR OTHER WEATHER-RELATED CAUSES, AND ACCIDENTS

Page 15: SUBSTATION & SWITCHYARD STRUCTURE’S

ELECTRICAL EQUIPMENT AND SUPPORTS

POWER TRANSFORMER & AUTOTRANSFORMER– SUPPORT :- THE POWER TRANSFORMER AND

AUTOTRANSFORMER ARE SUPPORTED DIRECTLY ON A FOUNDATION.

SHUNT REACTOR– SUPPORT :- THE SHUNT REACTOR IS SUPPORTED

DIRECTLY ON A FOUNDATION

Page 16: SUBSTATION & SWITCHYARD STRUCTURE’S

GENERAL DEFINITION:GENERAL DEFINITION:

TRANSFORMER IS AN ELECTRICAL DEVICE THAT TRANSFERS ENERGY FROM ONE CIRCUIT TO ANOTHER BY MAGNETIC COUPLING WITH NO MOVING PARTS

TRANSFORMERS ARE USED TO CONVERT BETWEEN HIGH AND LOW VOLTAGES, TO CHANGE IMPEDANCE, AND TO PROVIDE ELECTRICAL ISOLATION BETWEEN CIRCUITS

Page 17: SUBSTATION & SWITCHYARD STRUCTURE’S

TRANSFORMER FOUNDATION

Page 18: SUBSTATION & SWITCHYARD STRUCTURE’S

FIRE PROTECTION WALL

Page 19: SUBSTATION & SWITCHYARD STRUCTURE’S

ELECTRICAL EQUIPMENT AND SUPPORTS

CURRENT-LIMITING INDUCTOR OR AIR CORE REACTOR– SUPPORT :- THE SUPPORTING PEDESTALS ARE BOLTED

DIRECTLY TO THE FOUNDATION.LINE TRAP / WAVE TRAP

– SUPPORT :- THE LINE TRAP CAN BE MOUNTED VERTICALLY OR HORIZONTALLY ON EITHER A SINGLE OR MULTIPLE PEDESTAL SUPPORT STRUCTURE. THE LINE TRAP CAN ALSO BE SUSPENSION MOUNTED FROM A STRUCTURE.

Page 20: SUBSTATION & SWITCHYARD STRUCTURE’S

ELECTRICAL EQUIPMENT AND SUPPORTS

COUPLING CAPACITOR VOLTAGE TRANSFORMER– SUPPORT :- THE CCVT IS USUALLY SUPPORTED ON A

SINGLE PEDESTAL.DISCONNECT SWITCH (VERTICAL BREAK, CENTER BREAK,

SINGLE SIDE BREAK OR DOUBLE SIDE BREAK)– SUPPORT :- THE DISCONNECT SWITCH IS

SUPPORTED ON A COMMON STRUCTURE FOR VOLTAGE LESS THAN 500kV.

Page 21: SUBSTATION & SWITCHYARD STRUCTURE’S

DISCONNECTOR SUPPORTING STRUCTURE

Page 22: SUBSTATION & SWITCHYARD STRUCTURE’S

ELECTRICAL EQUIPMENT AND SUPPORTS

LOAD INTERRUPTER SWITCH / CIRCUIT SWITCHER / LINE CIRCUIT BREAKER– SUPPORT :- THE CIRCUIT SWITCHER SUPPORTED ON

A COMMON STRUCTURE FOR VOLTAGE LESS THAN 500kV.(DYNAMIC LOAD ON OPENING OR CLOSING .

CIRCUIT BREAKER– SUPPORT :- CIRCUIT BREAKERS, INCLUDING THEIR

SUPPOTING FRAMES, ARE ANCHORED DIRECTLY ON THE FOUNDATION.

Page 23: SUBSTATION & SWITCHYARD STRUCTURE’S

ELECTRICAL EQUIPMENT AND SUPPORTS

POTENTIAL AND CURRENT TRANSFORMERS– SUPPORT :- PTs & CTs ARE USUALLY SUPPORTED ON A

SINGLE PEDESTAL OR LATTICE STAND STRUCTURE.CAPACITOR BANK

– SUPPORT :- USUALLY SUPPORTED ON A SINGLE PEDESTAL OR LATTICE STAND STRUCTURE.OUTER PERIPHERY OF THE BANK SHOULD BE ENCLOSED INSIDE A FENCE FOR PROTECTION OF PERSONNEL; IF ELECTRICAL CLEARANCE IS NOT PROVIDED.

Page 24: SUBSTATION & SWITCHYARD STRUCTURE’S

EQUIPMENT SUPPORTING LATTICE TYPE STRUCTURE

Page 25: SUBSTATION & SWITCHYARD STRUCTURE’S

ELECTRICAL EQUIPMENT AND SUPPORTS

SHUNT CAPACITOR– SUPPORT :- THE SUPPORT

IS PROVIDED BY A METAL PLATFORM.THE PLATFORM MUST BE MOUNTED ON INSULATORS THAT ARE BOLTED TO THE FOUNDATION.

SURGE ARRESTER– SUPPORT :- SURGE

ARRESTER CAN BE SUPPORTED ON A SINGLE PEDESTAL OR LATTICE STAND STRUCTURE OR DIRECTLY MOUNTED ON TRANSFORMER.

Page 26: SUBSTATION & SWITCHYARD STRUCTURE’S

EQUIPMENT SUPPORTING LATTICE TYPE STRUCTURE

Page 27: SUBSTATION & SWITCHYARD STRUCTURE’S

ELECTRICAL EQUIPMENT AND SUPPORTS

NEUTRAL GROUNDING RESISTOR– SUPPORT :- RESISTORS ARE

SOMETIMES MOUNTED ON SEPARATE STRUCTURES BUT ARE USUALLY MOUNTED ON THE TRANSFORMER TANK.

CABLE TERMINATOR / POTHEAD– SUPPORT :- SUPPORT

STRUCTURES OF CABLES TERMINATORS OF INDIVIDUAL PHASES CAN BE COLUMNS RESTING ON A FOUNDATION. A STRUCTURE SUPPORTING THREE PHASES CAN ALSO BE USED.

Page 28: SUBSTATION & SWITCHYARD STRUCTURE’S

ELECTRICAL EQUIPMENT AND SUPPORTS

INSULATOR (PORCELAIN,GLASS & COMPOSITE MATERIALS ARE USED FOR SUSPENSION & POST INSULATORS)– SUPPORT :-

INSULATORS CAN BE SUPPORTED ON A SINGLE-PHASE OR THREE PHASE STRUCTURE.

Page 29: SUBSTATION & SWITCHYARD STRUCTURE’S

LOADING CRITERIA FOR SUBSTATION STRUCTURES

• DEAD LOADS• EQUIPMENT OPERATING LOADS• TERMINAL CONNECTION LOADS FOR

ELECTRICAL EQUIPMENT• WIRE TENSION LOADS• WIND LOADS• COMBINED ICE AND WIND LOADS• EARTHQUAKE LOADS• SHORT CIRCUIT LOADS• CONSTRUCTION & MAINTENANCE LOADS

Page 30: SUBSTATION & SWITCHYARD STRUCTURE’S

9,81.mi

fs

SAG DUE TO CONDUCTOR

fs = w.Lc28.T

fs = maximum conductor sag (m)

wi = weight of conductor (kg/m)

Lc = conductor span length (m)

T = tension per conductor (kg)

T

Lc

Page 31: SUBSTATION & SWITCHYARD STRUCTURE’S

Construction and commissioning ofsub station

Construction and commissioning of sub station isa subject describing the actual execution details.

• These sub station land is initially selected and the final level to be kept for construction of substation is decided on the basis of contour survey of the sub station land. So that the land development is carried out economically.

• The land development is then carried out accordingly• The sub station equipments and gantry foundations are

then cast. • The control room is also constructed as per drawing.

Page 32: SUBSTATION & SWITCHYARD STRUCTURE’S

SITE WORK FOR EQUIPMENT FOUNDATION

Page 33: SUBSTATION & SWITCHYARD STRUCTURE’S

PEDESTAL WITH ANCHOR BOLT

Page 34: SUBSTATION & SWITCHYARD STRUCTURE’S

CONNECTION BETWEEN STRUCTURE & PEDESTAL

Page 35: SUBSTATION & SWITCHYARD STRUCTURE’S

Construction and commissioning ofsub station

• The construction of sub station includes some of following activities.

• The arrangement of 3 phase supply up to 200 KVA• Erection of sub station columns and beams.• Stringing of various buses in the sub station.• Erection of equipment structures and equipments• Erection of equipment in control room• The earthing mesh and earthing electrodes work• The equipments are connected to each other, to bus,

etc. by carrying out jumpering work as specified in the lay out .

• The clamps and connectors are used while jumpering

Page 36: SUBSTATION & SWITCHYARD STRUCTURE’S

INDOOR CABLE TRENCH

Page 37: SUBSTATION & SWITCHYARD STRUCTURE’S

INSIDE CABLE TRENCH WITH PERFORATED TRAYS

Page 38: SUBSTATION & SWITCHYARD STRUCTURE’S

CABLE ENTRY TO INDOOR TRENCH

Page 39: SUBSTATION & SWITCHYARD STRUCTURE’S

Construction and commissioning ofsub station

• Commissioning of breakers, isolator alignments are carried out.

• Battery charging, charger commissioning making DC supply available for testing purposes.

• Commissioning of C & R panels relays etc.• The transformer erection filtration and testing

Lightening in control room and switch yard.• Metal spreading• Commissioning after proper testing is carried out.

Page 40: SUBSTATION & SWITCHYARD STRUCTURE’S

OUTSIDE CABLE TRENCH

Page 41: SUBSTATION & SWITCHYARD STRUCTURE’S

CABLE TRENCH WITH COVER

Page 42: SUBSTATION & SWITCHYARD STRUCTURE’S

CHAIN LINK FENCE

Page 43: SUBSTATION & SWITCHYARD STRUCTURE’S

COMPLETED SUBSTATION VIEW

Page 44: SUBSTATION & SWITCHYARD STRUCTURE’S

-: Design Example :-

Design a Single Phase Bus Support for a Substation in Nagpur, given the following information,

– Height of Bus Centerline above foundation = 5.5 m– Schedule 40 aluminum bus = 100 mm (mass = 5.51 kg/m)– Maximum Short Circuit force = 550 N/m– Short Circuit reduction factor = 0.66– Bus Support Spacing = 6.0 m– Insulator Height (hi) = 2.0 m – Insulator Diameter (Di) = 0.28 m– Insulator Weight (Wi) = 140 kg– Basic Wind Speed (Vb) = 33 m/sec (Zone = 1)– Reliability level = 2 (Return period of design loads 150 yrs)– Terrain Category = 2

Page 45: SUBSTATION & SWITCHYARD STRUCTURE’S

LATTICE STRUCTURE DETAILS:-Main Leg = ISA65x65x6 @ 5.8kg/mBracing,Inclined = ISA45x45x5 @ 3.4kg/mPlan = ISA45x45x5 @ 3.4kg/mPart of Structure = 04Each Part Length = 850 mmInclined Length = 931 mmBack to Back of Str. = 380 mm

Page 46: SUBSTATION & SWITCHYARD STRUCTURE’S

• Short-Circuit Loading:-• Fsc = 6.0 m x 0.66 x 550 N/m• Fsc = 2178 N• Mom @ Base = 5.5 m x 2178 N• Mom @ Base = 11979 N.m

Page 47: SUBSTATION & SWITCHYARD STRUCTURE’S

Wind Loading :-• IS 802 (Part 1 / Sec 1) :1995,• Basic wind speed Vb = 33 m/sec• Metrological Reference wind speed VR is,• VR = Vb / K0 , where K0 = 1.375 (cl. 8.2 pg 3)• VR = 33 / 1.375 = 24 m/sec• Design wind speed Vd = VR x K1 x K2,• Where K1 = Risk Coeff. (cl. 8.3.1)• K1 = 1.08 (Table 2)• Where K2 = Terrain roughness coeff. (cl.8.3.2)• K2 = 1.00 (Table 3)• Design wind speed Vd = 24 x 1.08 x 1.0 = 25.92 m/sec

Page 48: SUBSTATION & SWITCHYARD STRUCTURE’S

Wind Loading :-Design wind pressure Pd = 0.6 Vd2 (cl. 8.4)Pd = 0.6 x 25.92 x 25.92 = 403.11 N/sq.m==============================================Wind load on Conductor Fwc (cl 9.2)Fwc = Pd x Cdc x L x d x Gc,Where,

Cdc = Drag coeff, taken as 1.0 for conductor L = wind span, being sum of half the span on either side of supporting point in metersd = diameter of cable / tubeGc = gust response factor (Table 7) = 1.83Fwc = 403.11 x 1.0 x 6 x 0.1 x 1.83Fwc = 442.615 N (737.7 N/sq.m)

Page 49: SUBSTATION & SWITCHYARD STRUCTURE’S

Wind Loading :-• Wind load on Insulator Strings (Fwi) :- (cl 9.3)• Fwi = Cdi x Pd x Ai x Gi• Where,• Cdi = drag coeff to be taken as 1.2• Ai = 50 % of the area of insulator string projected on

a plane which is parallel to the longitudinal axis of the string

• Gi = Gust response factor (Table 6) = 1.92• Fwi = 1.2 x 403.11 x 0.5 x 2 x 0.28 x 1.92• Fwi = 260.1 N (928.8 N/sq.m)

Page 50: SUBSTATION & SWITCHYARD STRUCTURE’S

• Wind on structure Fwt = Pd x Cdt x Ae x Gt• Where,• Cdt = Drag coeff for panel under consideration

against which the wind is blowing . Values of Cdtfor different solidity ratios are given in Table 5.

• Solidity ratio (Φ) is equal to the effective area of a frame normal to the wind direction divided by the area enclosed by the boundary of the frame normal to the wind direction.

• Solidity ratio (Φ) = Aeff / Agross• Ae = Total net surface area of the legs, bracing,

cross arms and secondary members of the panel projected normal to the face in m2

• Gt = Gust response factor, Table 6

Wind Loading :-

Page 51: SUBSTATION & SWITCHYARD STRUCTURE’S

Solidity Ratio (Φ) = Ae / Ag Φ = 0.678 / 1.292 = 0.525Drag Coeff Cdt = 2.0 (Table 5)Gt = 1.92 (Table 6)Fwt = 403.11 x 2 x 0.678 x 1.92Fwt = 1049.50 N (1547.92 N/sq.m)

0.678Total Net Surface Area Ae =0.0680.0450.3843,5,7 & 9

1.292Gross Surface Area Ag = 3.4 m x 0.38 m

0.1680.0450.93142,4,6 & 8

0.4420.0653.421

Area (sq.m)

Width (m)

Length (m)

NosMember

Page 52: SUBSTATION & SWITCHYARD STRUCTURE’S

Wind load summary :-

5363.001752.22Totals

1784.151.71049.5Wind on Structure (Fwt)

1144.444.4260.1Wind on Insulator (Fwi)

2434.415.5442.62Wind on Bus (Fwc)

Moment @ Base (N.m)

Lever Arm (m)

Force (N)

Description

Page 53: SUBSTATION & SWITCHYARD STRUCTURE’S

Earthquake Loading:-

IS 1893 (Part 1) : 2002Design Horizontal Acceleration Coeff (Ah),Ah = Z I / 2R * Sa/gZ = Zone factor = Zone II = 0.10 (Table 2)I = Importance factor = 1.5 (Table 6)R = Response reduction factor = 4 (Table 7)Sa/g = Avg. response acceleration coeff for rock or soil

sites as given by fig 2 & Table 3 based on appropriate natural periods and damping of the structure.

Fundamental Natural Period Ta = 0.085 h0.75

Ta = 0.085 x 3.40.75 = 0.213 secSa/g = 2.5Hence, Ah = 0.10 x 1.5 x 2.5 / 2 x 4 = 0.047

Page 54: SUBSTATION & SWITCHYARD STRUCTURE’S

Earthquake Loading:-

IS 1893 (Part 1) : 2002Design Seismic Base Shear VB = Ah WW = Seismic weight of the structure

508.92162.78Totals

141.081.7180kg x 9.81 x 0.047 = 82.99

EQ on Structure

284.024.4140kg x 9.81 x 0.047 = 64.55

EQ on Insulator

83.825.56m x 5.51 kg/m x 9.81 x 0.047 = 15.24

EQ on Bus

Moment @ Base (N.m)

L.A (m)

Force (N)Description

Page 55: SUBSTATION & SWITCHYARD STRUCTURE’S

Results:-

• SCF + WL :-Force = 2178 + 1752.22 = 3930.22 NMoment @ Base = 11979 + 5363 = 17342 N

• SCF + EQ :-Force = 2178 + 162.78 = 2340.78 NMoment @ Base = 11979 + 508.92 = 12487.92 N

The combined loading of wind and short-circuit forces produce the greatest forces and moment at the base design for this condition. Therefore seismic forces are not critical for this structure.

Page 56: SUBSTATION & SWITCHYARD STRUCTURE’S

Forces in the Member:-

Moment at the base causes tension and compression in the chord angles.C = Tensile or Compressive forceC = 17342 N.m / [ 2(0.380 – 2 x 0.0181)]C = 25221.1 N per legP = Applied load P + C = [140 x 9.81 + 6 x 54] / 4 + 25221.1P + C = 25645.45 N per legForces in bracing member shall be 25 % of the leg member.

Page 57: SUBSTATION & SWITCHYARD STRUCTURE’S

Thank you..