Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 1 of 27
PROJECT INFORMATION
PROJECT NAME: Dwarsberg Switching Substation
SCHEME NAME: PPC Strengthening
SUBSTATION NAME: Dwarsberg 132/22 kV Switching Substation
OPERATING UNIT: Northern Grid
PROJECT NUMBER: N.ETDALBS.D.NG.INT.TE
PROJECT UNIQUE IDENTIFIER: NDwa06 P01
Revision: 2
RELATED/SUPPORTING DOCUMENTS
STATION ELECTRIC DIAGRAM : 0.08/19986 Rev. 0
KEY PLAN : 0.08/19987 Rev. 1
PLANNING/TECHNICAL REPORT
Title: Dwaalboom PPC/BPC Network Analysis,
Report No.: TSP Report 06/32
Revision - 2 June 2011.
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 2 of 27
1 PROJECT DESCRIPTION
Provide a platform so as to construct Dwarsberg 132/22 kV Switching Substation. The 132 kV Yard and 22 kV
Yard will have the following layout. A six bay 132 kV (Φ 200 x 6 WT Al TUBE) double Tubular bus-bar
arrangement with a 132 kV Bus Coupler to couple the two bus-bars. The 132 kV double bus-bar arrangement
assures security of supply to BPC. A 22 kV 4 bay single Bull conductor Strung bus-bar arrangement.
The 132 kV Feeders namely Dwaalboom to Gaborone South and Spitskop to Segoditshane need to be
switched. They serve an international customer and have need of Double bus-bar selection with a By-pass
facility on the 4 x 132 kV bays. Dwaalboom PPC will always have security of supply from a line perspective
irrespective of any single contingency.
To provide an auxiliary supply; a 132/22 kV 10 MVA Star/Delta Transformer with a NEC/NER/Aux 22/0.4 kV
Transformer will be set up. The Aux 22/0.4 kV Transformer will also provide a 400 V, 315 kVA, Aux supply.
A 22 kV Distribution Line will supply the Switching Substation to ensure a backup supply via the 22/0.4 kV,
315 kVA Aux Transformer.
The 132/22 kV 10 MVA Transformer is sufficiently rated to provide a constant auxiliary supply, as well as to
strengthen the local 22 kV network if required.
The construction of this substation is to ensure that Eskom meets the PPC contractual agreements.
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 3 of 27
2 SUBSTATION LAYOUT DESIGN AND APPLICATIONS
2.1 Philosophy of Design
2.1.1 132 kV System
The “Hybrid” type substation layout is planned to accommodate a 132 kV Bus-bar 1 & 2,
Φ200 x 6 WT Al Tubular design with Double bus-bar selection and By-pass facility for the feeder bays.
1 x 132/22 kV 10 MVA Star/Delta Transformer,
1 x 132 kV Transformer bay,
4 x132 kV Feeder bays,
1 x 132 kV Bus Coupler bay,
3 x 132 kV VT’s on Busbar 1 & 2,
3. HIGH LEVEL SCOPE
3.1. 132 kV Yard
The scope of work for the 132 kV System is as follows:
Qty Bay Scope of Work
1 Feeder-1 3 x conventional Isol, 1 x Inline Isol, 1 x CB, 3 x CT’s, & 3 x SA’s, 12 x C4
Post I’s and 1 x 1JB0333 & 1JB0602
String 1 x Bull conductor at dropper level.
3 Feeder-2, 3 & 4 3 x conventional Isol, 1 x Inline Isol, 1 x CB, 3 x CT’s, 2 x VT’s, 2 x Line
Trap’s, 3 x SA’s, 8 x C4 Post I’s and 1 x 1JB0333 & 1JB0602
String 1 x Bull conductor at dropper level.
1 Transformer-1
132/22 kV 10 MVA
Star/Delta Transformer
2 x conventional Isol, 1 x CB, 3 x CT’s, & 3 x SA’s and 1 x 1JB0333 & TDB
String 1 x Bull conductor at dropper level.
(SA’s mounted on Trfr.)
1 Bus Coupler -“A” 2 x conventional Isol, 3 x CT’s, 1 x CB and 5 x C4 Post I’s. and 1 x 1JB0333
String 2 x Bull conductor at dropper level.
2 sets Busbar-1 & 2
Voltage
Transformers
3 x VT’s.
String 1 x Centipede conductor at dropper level.
3.2.1 22 kV Yard
22 kV Strung single Bull conductor bus-bar
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 4 of 27
1 x 22 kV Transformer / NEC/NER/Aux Trfr.-1 Bay, 1 x 22/0.4 kV 315 kVA Dyn11 Aux. Trfr-2 Bay, 1 x 22 kV Feeder Bay, 1 x Spare Bay 3 x 22 kV Busbar VT’s
The scope of work for the 22 kV System is as follows:
Qty Bay Scope of Work
1 Feeder-1 2 x Isol, 1 x CB, 3 x CT’s, 3 x SA’s, 3 x 33 kV PI’s and 1 x 1JB1700 structure
mounted.
String 1 x Centipede conductor at dropper level.
1 22 kV Transformer-1
1 x Isol, 1 x CB, 3 x CT’s, 6 x SA’s. and 1JB1700 structure mounted & TDB
String 1 x Bull conductor. (SA’s mounted on Trfr.)
1 NEC/NER/Aux Trfr-1 String 1 x PVC Centipede conductor at dropper level
1 Aux Transformer-2 2 x Isol, 3 x CT’s, 1 x CB, 3 x SA’s., 3 x 33 kV PI’s, and 1JB1700 structure
mounted
String 1 x Centipede conductor at dropper level.
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 5 of 27
4 SUBSTATION DESIGN SPECIFICATIONS AND CONFIGURATION
4.2 HV Equipment
System Voltage (kV)
Rated normal current (A, min)
Short-circuit withstand current
(kA, min)
CT Bus Zone Ratio
BIL (kV, min)
Specific creepage distance
(mm/kV, min)
132 kV 2500 A 40 kA 1/1000 550 31
22 kV 2500 A 20 kA No BZ 150 25 & 31
4.3 Calculated Fault Current Levels
System Voltage (kV)
1Ǿ Fault Level (kA)-2013 3Ǿ Fault Level (kA) Medupi end state
Current New Current New
132 kV N/A 9.3 N/A 6.9
22 kV - - - -
4.4 Earthing System Design
System Voltage (kV) Earth-Tails Rating (kA)
132 kV 40 kA
22 kV 20 kA
4.5 Busbar Design
System Voltage
(kV)
Bulbar Configuration Electrical Clearances (min) Conductor Type
Bus-bar Rating @ 85 oC (A)
Phase-to-phase (mm)
Phase-to-earth (mm)
Current New
132 kV Double Bus Bar (1 & 2)
Tubular 1650 1200 Φ200 x 6 WT
Al N/A 4750
22 kV Single Bus Bar
Strung conductor 580 430 1 x Bull
N/A 1353
4.6 Station DC Voltage 110 V
4.7 Insulator Type
Glass & Composite
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 6 of 27
5 CIVIL/STRUCTURAL REQUIREMENTS
5.1 Geotechnical Required
5.2 Topographical survey Required
5.3 Earthworks Required
5.4 Buildings Required
5.5 Foundations, plinths and trenches Required
5.6 Earth-mat (3 x tails) per 132 kV equipment structure (2 x tails) per 22 kV equipment structure
5.7 Yard Stone Required
5.8 Fencing Required
5.9 Roads Required
5.10 Drainage Required
5.11 Structural steel Required
5.12 Oil Dam Required
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 7 of 27
6 132 kV YARD REQUIREMENTS
6.1 132 kV Feeder-1 Bay (Dwaalboom-1 Dx)
6.1.1 132 kV Primary Plant Requirements
Qty Equipment Specification
Ne
w
Ex
isti
ng
Re
loc
ate
Re
pla
ce
De
co
mm
iss
ion
Cre
ep
ag
e
(mm
/kv
)
Su
pp
ort
Str
uc
ture
F
ou
nd
ati
on
Comment
3 Isolator Conventional
3-Ph, 2500A, 40kA (motorised) X
31 X X Steel Support by supplier
1 Inline Isolator 3-Ph, 2500A, 40kA (motorised) X
31 X X Steel Support by supplier
1 Circuit Breaker 3-Ph, 3150A, 40kA, (3 x Mec.) Single pole tripping & ARC capability
X
31 X X Steel Support by supplier
3 Current Transformer 2500A,40kA,6 Core:2 P,2 B,2 M X 31 X X Bus zone 1/1000
3 Surge Arrester 132kV 80 % X 31 X X
12 Post Insulators C4-550 X 31 X X
1 Junction Box 1JB0333 X X Foundation only
1 Junction Box 1JB0602 X
Structure
mounted
Conductor 1 x Bull X
Quantity depends on final design
Labels Standard X
Quantity depends on final design
6.1.2 Secondary Plant Requirements
Discipline Requirements
6.1.2.1 Protection
One new HV Feeder protection scheme with Transfer and current differential protection One 1JB0333 One 1JB0602 Cables
6.1.2.2 Control Alarms wired to IDF
6.1.2.3 Measurements Measurements transducer for HV Feeder scheme
6.1.2.4 Teleprotection Distribution to install a fibre optic cable on the line to Dwaalboom Substation
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 8 of 27
6.2 132 kV Feeder-2 Bay (Spitskop-1)
6.2.1 132 kV Primary Plant Requirements
Qty Equipment Specification
Ne
w
Ex
isti
ng
Re
loc
ate
Re
pla
ce
De
co
mm
iss
ion
Cre
ep
ag
e
(mm
/kv
)
Su
pp
ort
Str
uc
ture
F
ou
nd
ati
on
Comment
3 Isolator Conventional
3-Ph, 2500A, 40kA (motorised) X
31 X X Steel Support by supplier
1 Inline Isolator 3-Ph, 2500A, 40kA (motorised) X
31 X X Steel Support by supplier
1 Circuit Breaker 3-Ph, 3150A, 40kA, (3 x Mec.) Single pole tripping & ARC capability
X
31 X X Steel Support by supplier
3 Current Transformer 2500A,40kA,6 Core:2 P,2 B,2 M X 31 X X Bus zone 1/1000
3 Surge Arrester 132 kV , 80 % X 31 X X
2 Line Trap X 31 X X
2 Voltage Transformer ([132√3kV][110/√3V]-[110/√3V]) X 31 X X
8 Post Insulators C4-550 X 31 X X
1 Junction Box 1JB0333 X X Foundation only
1 Junction Box 1JB0602 X Structure mounted
Conductor 1 x Bull X
Quantity depends on final design
Labels Standard X
Quantity depends on final design
6.2.2 Secondary Plant Requirements
Discipline Requirements
6.2.2.1 Protection
One new HV Feeder protection scheme with Transfer One 1JB0333 One 1JB0602 Cables
6.2.2.2 Control Alarms wired to IDF
6.2.2.3 Measurements Measurements transducer for HV Feeder scheme
6.2.2.4 Teleprotection New Teleprotection equipment Two LME’s
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 9 of 27
6.3 132 kV Feeder-3 Bay (Segoditshane-1)
6.3.1 132 kV Primary Plant Requirements
Qty Equipment Specification
Ne
w
Ex
isti
ng
Re
loc
ate
Re
pla
ce
De
co
mm
iss
ion
Cre
ep
ag
e
(mm
/kv
)
Su
pp
ort
Str
uc
ture
F
ou
nd
ati
on
Comment
3 Isolator ( Conventional )
3-Ph, 2500A, 40kA (motorised) X 31 X X Steel Support by supplier
1 Inline Isolator 3-Ph, 2500A, 40kA (motorised) X 31 X X Steel Support by supplier
1 Circuit Breaker 3-Ph, 3150A, 40kA, (3 x Mec.) Single pole tripping & ARC capability
X 31 X X Steel Support by supplier
3 Current Transformer 2500A,40kA,6 Core:2 P,2 B,2 M X 31 X X Bus zone 1/1000
3 Surge Arrester 132 kV, 80 % X 31 X X
2 Line Trap X 31 X X
2 Voltage Transformer ([132√3kV][110/√3V]-[110/√3V]) X 31 X X
8 Post Insulators C4-550 X 31 X X
1 Junction Box 1JB0333 X X Foundation only
1 Junction Box 1JB0602 X Structure mounted
Conductor 1 x Bull X
Quantity depends on final design
Labels Standard X
Quantity depends on final design
6.3.2 Secondary Plant Requirements
Discipline Requirements
6.3.2.1 Protection
One new dual impedance EHV Feeder protection scheme with Transfer One 1JB0333 One 1JB0602 Cables
6.3.2.2 Control Alarms wired to IDF
6.3.2.3 Measurements Measurements transducer for HV Feeder scheme
6.3.2.4 Teleprotection New Teleprotection equipment Two LME’s
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 10 of 27
6.4 132 kV Feeder-4 Bay (Derdepoort-1) (Gaborone South)
6.4.1 132 kV Primary Plant Requirements
Qty Equipment Specification
Ne
w
Ex
isti
ng
Re
loc
ate
Re
pla
ce
De
co
mm
iss
ion
Cre
ep
ag
e
(mm
/kv
)
Su
pp
ort
Str
uc
ture
F
ou
nd
ati
on
Comment
3 Isolator Conventional
3-Ph, 2500A, 40kA (motorised) X 31 X X Steel Support by supplier
1 Inline Isolator 3-Ph, 2500A, 40kA (motorised) X 31 X X Steel Support by supplier
1 Circuit Breaker 3-Ph, 3150A, 40kA, (3 x Mec.) Single pole tripping & ARC capability
X 31 X X Steel Support by supplier
3 Current Transformer 2500A,40kA 6 Core:2 P,2 B,2 M X 31 X X Bus zone 1/1000
3 Surge Arrester 132 kV, 80 % X 31 X X
2 Line Trap X 31 X X
2 Voltage Transformer ([132√3kV][110/√3V]-[110/√3V]) X 31 X X
8 Post Insulators C4-550 X 31 X X
1 Junction Box 1JB0333 X X Foundation only
1 Junction Box 1JB0602 X Structure mounted
Conductor 1 x Bull X
Quantity depends on final design
Labels Standard X
Quantity depends on final design
6.4.2 Secondary Plant Requirements
Discipline Requirements
6.4.2.1 Protection
One new dual impedance EHV Feeder protection scheme with Transfer One 1JB0333 One 1JB0602 Cables
6.4.2.2 Control Alarms wired to IDF
6.4.2.3 Measurements Measurements transducer for HV Feeder scheme
6.4.2.4 Teleprotection New Teleprotection equipment Two LME’s
6.5 132 kV (10 MVA) Transformer 1 Bay
6.5.1 Primary Plant Requirements
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 11 of 27
Qty Equipment Specification
Ne
w
Ex
isti
ng
Re
loc
ate
Re
pla
ce
De
co
mm
iss
ion
Cre
ep
ag
e
(mm
/kv
)
Su
pp
ort
Str
uc
ture
F
ou
nd
ati
on
Comment
1 Transformer 132/22 kV 10 MVA Star/Delta Transformer YnD1
X 31 N/A X
2 Isolator conventional
3-Ph, 2500A, 40kA, (motorised) X 31 X X Steel Support by supplier
1 Circuit Breaker 3-Ph, 3150A, 40kA ( 1 x Mec.) three pole tripping capability
X 31 X X Steel Support by supplier
3 Current Transformer 2500A,40kA,6Core: 2 P,2 B,2 M X 31 X X Bus zone 1/1000
3 Surge Arrester 132kV, 80 % X 31 X To be mounted onto transformer
3 Post Insulators 275 kV ( C6-1175) X 31 X X
1 TDB Type-1 X X Foundation only
1 Junction Box 1JB0333 X X Foundation only
Conductor 1 x Bull X
Quantity depends on final design
Labels Standard X
Quantity depends on final
design
6.5.2 Secondary Plant Requirements
Discipline Requirements
6.5.2.1 Protection
One HV Transformer (Low MVA) protection scheme One 1JB0333 TDB Type 1 Cables
6.5.2.2 Control Alarms wired to IDF
6.5.2.3 Measurements Measurements scheme configured for HV Transfomer
6.5.2.4 Teleprotection N/A
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 12 of 27
6.6 132 kV Bus Coupler “A” Bay
6.6.1 Primary Plant Requirements
Qty Equipment Specification
Ne
w
Ex
isti
ng
Re
loc
ate
Re
pla
ce
De
co
mm
iss
ion
Cre
ep
ag
e
(mm
/kv
)
Su
pp
ort
Str
uc
ture
F
ou
nd
ati
on
Comment
1 Circuit Breaker
3-Ph, 3150A, 40kA (3 x Mec.) Single pole tripping & ARC capability
X 31 X X Steel Support by supplier
3 Current Transformer 2500A,40kA,6Core:2 P,2 B,2 M X 31 X X Bus zone 1/1000
2 Conventional Isolator
3-Ph, 2500A, 40kA (motorised) X 31 X X Steel Support by supplier
5 Post Insulators C4-550 X 31 X X
1 Junction Box 1JB0333 X X Foundation only
Conductor 2 x Bull X
Quantity depends on final design
Labels Standard X
Quantity depends on final design
6.6.2 Secondary Plant Requirements
Discipline Requirements
6.6.2.1 Protection One Bus Coupler protection scheme with Transfer capabilities One 1JB0333 Cables
6.6.2.2 Control D25 for a Bus Coupler
6.6.2.3 Measurements Measurements scheme configured for a Bus Coupler
6.6.2.4 Teleprotection N/A
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 13 of 27
6.7 132 kV Bus Bar 1 & 2 VT Bay
6.7.1 Primary Plant Requirements
Qty Equipment
For a Bus bar Specification
Ne
w
Ex
isti
ng
Re
loc
ate
Re
pla
ce
De
co
mm
iss
ion
31
Cre
ep
ag
e
(mm
/kv
)
Su
pp
ort
Str
uc
ture
F
ou
nd
ati
on
Comment
6 EMVTs ([132√3kV][110/√3V]-[110/√3V]) X 31 X X Class: 0.2 – 3P
2 Junction Box 1JB0901 X X Foundation only
Conductor 1 x Centipede
X Quantity depends on final design
Labels
X Quantity depends on final design
6.7.2 Secondary Plant Requirements
Discipline Requirements
6.7.2.1 Protection Two 1JB0901 Cables
6.7.2.2 Control N/A
6.7.2.3 Measurements N/A
6.7.2.4 Teleprotection N/A
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 14 of 27
7 22 kV YARD REQUIREMENTS
7.1 22 kV Feeder-1 Bay (Dwaalboom)
7.1.1 22 kV Primary Plant Requirements
Qty Equipment Specification
Ne
w
Ex
isti
ng
Re
loc
ate
Re
pla
ce
De
co
mm
iss
ion
Cre
ep
ag
e
(mm
/kv
)
Su
pp
ort
Str
uc
ture
F
ou
nd
ati
on
Comment
2 Isolator ( Conventional )
3-Ph, 2500A, 25kA (Hand) X 25 X X Steel Support by supplier
1 Circuit Breaker 33 kV 3-Ph, 2500A, 25 kA, X 25 X X Steel Support by
supplier
3 Current Transformer 2500A,25kA, 4 Core:2 P, & ,2 M X 25 X X
3 Surge Arrester 22 kV 100 % Metal Oxide Arrester
X 25 SA’s & PI’s
shared Cap
3 33 kV Post Insulators
C4-200 X 25 X X SA’s & PI’s
shared Cap
Conductor 1 x Centipede X
Quantity depends on final design
Labels Standard X
Quantity depends on final design
7.1.2 Secondary Plant Requirements
Discipline Requirements
7.1.2.1 Protection One Rural feeder protection scheme One 1JB1700 structure mounted JB Cables
7.1.2.2 Control Alarms wired to IDF
7.1.2.3 Measurements Measurements transducer for Rural feeder
7.1.2.4 Teleprotection N/A
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 15 of 27
7.2 22 kV Transformer Bay-1
7.2.1 22 kV Primary Plant Requirements
Qty Equipment Specification
Ne
w
Ex
isti
ng
Re
loc
ate
Re
pla
ce
De
co
mm
iss
ion
Cre
ep
ag
e
(mm
/kv
)
Su
pp
ort
Str
uc
ture
Fo
un
da
tio
n
Comment
1 Isolator ( Conventional )
3-Ph, 2500A, 25kA (Hand) X 25 X X Steel Support by supplier
1 Circuit Breaker 33 kV 3-Ph, 2500A, 25 kA, X 25 X X Steel Support by supplier
3 Current Transformer 2500A, 25 kA,4 Core:2 P,&,2 M X 25 X X
1 NEC/NER/Aux Trfr 22/0.4 kV, 360 A, 315 kVA X 31 X X
6 Surge Arrester 22 kV 100 % Metal Oxide Arrester
X 25 X
3 x To be mounted onto transformer & 3x on support
Conductor 1 x PVC Centipede & Bull X
Quantity depends on final design
Labels Standard X Quantity depends on final design
7.2.2 Secondary Plant Requirements
Discipline Requirements
7.2.2.1 Protection Protection scheme included under 6.5.2 One 1JB1700 structure mounted JB Cables
7.2.2.2 Control Included under 6.5.2
7.2.2.3 Measurements Included under 6.5.2
7.2.2.4 Teleprotection Included under 6.5.2
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 16 of 27
7.3 22/0.4 kV Auxiliary Transformer Bay-2
7.3.1 22 kV Primary Plant Requirements
Qty Equipment Specification
Ne
w
Ex
isti
ng
Re
loc
ate
Re
pla
ce
De
co
mm
iss
ion
Cre
ep
ag
e
(mm
/kv
)
Su
pp
ort
Str
uc
ture
F
ou
nd
ati
on
Comment
2 Isolator ( Conventional )
3-Ph, 2500A, 25kA (Hand) X 25 X X Steel Support by supplier
1 Circuit Breaker 33 kV 3-Ph, 2500A, 25 kA, X 25 X X Steel Support by supplier
3 Current Transformer 2500A, 4 Core:2 P,&,2 M X 25 X X
1 Aux. Transformer 22 kV / 0.4 kV 315 kVA Dyn11 Aux Transformer
X 31 X X
3 Surge Arrester 22 kV 100 % Metal Oxide Arrester
X 25 SA’s & PI’s shared Cap
3 33 kV Post Insulators
C4-200 X 25 X X SA’s & PI’s shared Cap
1 TDB TDB Type 1 X X Foundation only
Conductor 1 x Centipede X Quantity depends on final design
Labels Standard X
Quantity depends on final design
7.3.2 Secondary Plant Requirements
Discipline Requirements
7.3.2.1 Protection
One Bus Coupler Protection scheme modified for Transformer protection One 1JB1700 structure mounted JB One TDB Type 1 Cables
7.3.2.2 Control Alarms wired to IDF
7.3.2.3 Measurements Measurements Transducer normally used for an HV Feeder
7.3.2.4 Teleprotection N/A
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 17 of 27
8 COMMON YARD REQUIREMENTS
8.1 Auxiliary/Construction Supply To be supplied i.e. 22/0.4 kV (315 kVA at 400 V)
8.2 AC Reticulation One AC Board Type 1; Three Plug Boxes; Cables;
8.3 Busbars Conductor Strung
22 kV
1 x Bull conductor, 22 kV Main Steelwork & related hardware
Post
insulators
132 kV 42 ( C8-550 ) on Steel supports & Φ200 x 6 WT Al Tubular Conductor
22 kV No B/B PI’s are utilised
8.4 Insulators Glass & Composite
8.5 Portable Earthing Required for both yards
8.6 Overhead Earth Wire Required
8.7 Labels Busbar labels Required
Safety labels Required
Phasing discs Required
8.8 Eskom Telecoms Microwave Tower 75m,
5 Port Wave guide entry
Overhead racking for the waveguide
Cisco router.
Telephone switch
Microwave Radio Equipment
Bandwidth Management equipment.
Fibre Optic Terminal Equipment
3 (600 x 600) Cabinets
ADM
EAS Unit
PABX & telephones
Direct control circuits
D400 circuits
Disturbance Recorder circuit
TWS Recorder Circuit
8.9 Operating Floodlighting/ Security
Lighting Required
8.10 Safety & Security Standard non- lethal fence with Access gate and all associated equipment required
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 18 of 27
8.11 Control &
Battery Room
Protection One Low Impedance Buszone scheme
Disturbance Recorder
TWS recorder
Control D400
D20
2 x FSP
Patch Panels
Gateway switch 2100
Fibre Optic Cables
IDF Equipment
IHMI
Telecom cables
Teleprotection Included in Bay equipment (May be replaced due to OPGW installation)
Metering Three meter point scheme - on the BPC lines and 132/22kV Transformer.
Stats metering (x2) on the other two 132kV lines
DC
Systems
110V DC 110V DC Batteries and stands
Dual Chargers
Dual Boards
50V DC 50V DC Batteries and stands
Dual Chargers
Dual Boards
Under-frequency load
shedding UFLS scheme is not required
Office Furniture Required
8 RELATED PROJECTS
Waterberg GX Int F/L Management Plan – Spitskop
Spitskop n-1 500MVA 400/132/22kV Transformers 41 & 42 replacement
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 19 of 27
9 SPECIAL PROJECTS
9.1 Gaborone South – 132kV Dwarsberg Switching Station Feeder bay (Dwaalboom Substation)
9.1.1 Primary Plant Requirements
Qty Equipment Specification
Ne
w
Ex
isti
ng
Re
loc
ate
Re
pla
ce
De
co
mm
iss
ion
Cre
ep
ag
e
(mm
/kv
)
Su
pp
ort
Str
uc
ture
F
ou
nd
ati
on
Comment
2 Line Trap X X 31 Use existing
structures
2 Voltage Transformer ([132√3kV][110/√3V]-[110/√3V]) X X 31 Use existing
structures
Labels Change Labels X X
Quantity depends on final design, Label may be changed
9.1.2
Discipline Requirements
9.1.2.1 Protection Interface to new Teleprotection Equipment
9.1.2.2 Control Existing (Possible change of database)
9.1.2.3 Measurements Existing
9.1.2.4 Teleprotection New Teleprotection equipment Two LME’s
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 20 of 27
9.2 Segoditshane – 132kV Dwarsberg Switching Station Feeder bay (Spitskop)
9.2.1 Primary Plant Requirements
Qty Equipment Specification
Ne
w
Ex
isti
ng
Re
loc
ate
Re
pla
ce
De
co
mm
iss
ion
Cre
ep
ag
e
(mm
/kv
)
Su
pp
ort
Str
uc
ture
F
ou
nd
ati
on
Comment
2 Line Trap X X 31 Use existing
structures
2 Voltage Transformer ([132√3kV][110/√3V]-[110/√3V]) X X 31 Use existing
structures
Labels Standard X X
Quantity depends on final design
9.2.2 Secondary Plant Requirements
Discipline Requirements
9.2.2.1 Protection Interface to new Teleprotection Equipment
9.2.2.2 Control Existing (Possible change of database)
9.2.2.3 Measurements Existing
9.2.2.4 Teleprotection New Teleprotection equipment Two LME’s
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 21 of 27
9.3 Dwaalboom DX Substation 132 kV Dwarsberg Switching Station Feeder Bay (Derdepoort)
9.3.1 132 kV Primary Plant Requirements
Qty Equipment Specification
Ne
w
Ex
isti
ng
Re
loc
ate
Re
pla
ce
De
co
mm
iss
ion
Cre
ep
ag
e
(mm
/kv
)
Su
pp
ort
Str
uc
ture
F
ou
nd
ati
on
Comment
2 Line Trap X X
Conductor 1 x Bull X X
Quantity depends on final design
Labels Standard X X
Quantity depends on final design
9.3.2 Secondary Plant Requirements
Discipline Requirements
9.3.2.1 Protection One new DX HV Feeder protection scheme without Transfer and current differential protection One CTJB (Structure Mounted) Cables
9.3.2.2 Control Alarms wired to IDF
9.3.2.3 Measurements Measurements transducer for HV Feeder scheme
9.3.2.4 Teleprotection Distribution to install a fibre optic cable on the line to Dwaalboom Switching Substation
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 22 of 27
Revision Control
DWARSBERG SWITCHING SUBSTATION: ASSET SPECIFICATION
REV NO DESCRIPTION RESPONSIBLE DATE
0 Initial scope of work Scharrett Buchner 21/09/2013
PTM&C initial scope of work Jan Calitz 28/10/2013
1 Removed E /Switches from 132 kV Isolators and added 275 kV PI’s in 132 kV Trfr-1 Bay
Scharrett Buchner 08/05/2014
1 PTM&C revised scope of work Jan Calitz 22/05/2014
2 PTM&C removed EHV Feeder schemes & added QOS meter.
Jan Calitz 01/12/2014
2 Removed all buildings except (Control and Access control buildings) & revised PI quantities
Scharrett Buchner 11/12/2014
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 23 of 27
COMPILED BY:
DISCIPLINE NAME DATE SIGNATURE
Substation Engineering – Electrical Scharrett Buchner 30-01-2015 Page-24
Substation Engineering – Civil Dawie Senekal 30-01-2015 Page-24
Substation Engineering – Lighting, HVAC & AC Reticulation
Anton Naude 30-01-2015 Page-24
PTM&C Engineering Jan Calitz 18-12-2014 Page-24
REVIEWED AND ACCEPTED BY:
DISCIPLINE NAME DATE SIGNATURE
Project Originator Kabir Singh 27-05-2015 Page-24
Project Manager Manqoba Nkosi 27-05-2015 Page-24
Substation Engineering Derrick Delly 03-02-2015 Page-24
HV Plant Engineering Sibongile Maphosa 04-06-2015 Page-25
PTM&C Engineering Leon Kotze 29-05-2015 Page-24
System Operations Comfort Masike 28-05-2015 Page-24
Operating Unit HV Plant Calvin Bongwe 24-06-2015 Page-26
Safety and Risk Management Willem Bosh 26-06-2015 Page-27
AUTHORISED BY:
NAME DATE SIGNATURE
Substation Engineering DRT Chairperson
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 24 of 27
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 25 of 27
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 26 of 27
Substation Asset Specification
Dwarsberg 132/22 kV Switching Substation
Unique Identifier 240-57617932
Document Type Template
Revision 1.0
Effective Date 10 Sep 2013
Reference Number NDwa06P01-C07- 01
Group Technology (Engineering)
NDwa06 P01– Dwarsberg 132/22 kV Switching Substation Page 27 of 27