    System

    26/05/2Printed Date:PEPSICO - 22Job:

    PROCESS OMark:

    CAPS 4.14.1443 C:\Proyectos 2014\PEPSICO - 220514.gfcj Page

  • 5/22/2018 Submittals Equipos GREENHECK

    2/17

    Sound Power by Octave BandSound

    Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

    Inlet 99 94 89 87 83 79 75 70 89 77 30

    26.88

    66.5

    1.75

    62.63

    45

    61.25

    Model: RBU-3L54-75

    Propeller Upblast Belt Drive

    DimensionalQuantity 6

    Weight w/o Acc's (lb) 751

    Weight w/ Acc's (lb) 809

    Max T Motor Frame Size 254

    Roof Opening (in.) 63 x 63

    PerformanceRequested Volume (CFM) 43,000

    Actual Volume (CFM) 43,000

    External SP (in. wg) 0.1

    Total SP (in. wg) 0.1

    Fan RPM 494

    Operating Power (hp) 6.58

    Elevation (ft) 43

    Airstream Temp.(F) 70

    Air Density (ft3) 0.075

    Drive Loss (%) 3.8

    Tip Speed (ft/min) 6,986

    Static Eff. (%) 11

    Motor

    Motor Mounted Yes

    Size (hp) 7 1/2

    V/C/P 460/60/3

    Enclosure TEFC

    Motor RPM 1725

    Windings 1

    NEC FLA* (Amps) 11

    Notes:All dimensions shown are in units of in..

    *FLA - based on tables 150 or 148 of National Electrical

    Code 2002. Actual motor FLA may vary, for sizing thermal

    overload, consult factory.

    LwA - A weighted sound power level, based on ANSI S1.4

    dBA - A weighted sound pressure level, based on 11.5 dB

    attenuation per Octave band at 5 ft - dBA levels are not

    licensed by AMCA International

    Sones - calculated using AMCA 301 at 5 ft

    26/05/2Printed Date:PEPSICO - 22Job:

    FG WAREHOMark:

    CAPS 4.14.1443 C:\Proyectos 2014\PEPSICO - 220514.gfcj Page

  • 5/22/2018 Submittals Equipos GREENHECK

    3/17

    Model: RBU-3L54-75

    Propeller Upblast Belt Drive

    Standard Construction Features:

    - Curb caps and drive frame assemblies of galv steel sizes 18 to 48, painted steelsizes 54 and 60 - Galvanized steel windband with built in damper stops - Butterfly

    dampers - Fabricated steel propeller - Ball bearing motors - Adjustable motor

    plate - Variable pitch motor pulley - Fan shaft mounted in pillow block bearings

    with grease zerks - Static free belts - Corrosion resistant fasteners

    Options & Accessories:NEMA Premium Efficient Motor - meets NEMA Table 12-12

    UL/cUL 705 Listed - "Power Ventilators"

    Roof Curb-Galv., GPI-66.5-G12, Under Sized 1.5 in. Total

    Coating Hi-Pro Polyester, Concrete Gray-RAL 7023, Fan And Attached Acc

    Galvanized Construction

    Steel Propeller

    Steel Butterfly Damper

    Bearings with Grease Fittings

    Unit Warranty: 1 Yr (Standard)

    26/05/2Printed Date:PEPSICO - 22Job:

    FG WAREHOMark:

    CAPS 4.14.1443 C:\Proyectos 2014\PEPSICO - 220514.gfcj Page

  • 5/22/2018 Submittals Equipos GREENHECK

    4/17

    52

    72

    35.25

    49.63

    37.5

    2.5

    StaticPressure(in.wg)

    0.0

    0.1

    0.2

    0.3

    0.4

    0.5

    0.6

    0.7

    0.8

    BrakePowe

    r(hp)

    0.0

    0.3

    0.6

    0.9

    1.2

    1.5

    1.8

    2.1

    2.4

    Volume (CFM) x 1,000

    0 2 4 6 8 10 12 14 16 18 20

    506FR

    PM

    Do not

    operate

    in sh

    aded

    area

    System

    26/05/2Printed Date:PEPSICO - 22Job:

    CORN CLMark:

    CAPS 4.14.1443 C:\Proyectos 2014\PEPSICO - 220514.gfcj Page

  • 5/22/2018 Submittals Equipos GREENHECK

    5/17

    Sound Power by Octave BandSound

    Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

    Inlet 92 90 86 83 79 75 71 65 85 74 24

    AIR FLOW

    See the Assembly Drawing For

    Selected Accessories

    56

    2

    25

    19

    49.25

    Model: SBE-2L48-50

    Sidewall Belt Drive Exhaust Fan

    DimensionalQuantity 2

    Weight w/o Acc's (lb) 279

    Weight w/ Acc's (lb) 573

    Max T Motor Frame Size 184

    Optional Damper (in.) 50 x 50

    Wall Opening (in.) 57.75 x 57.75

    PerformanceRequested Volume (CFM) 23,000

    Actual Volume (CFM) 23,000

    External SP (in. wg) 0.4

    Total SP (in. wg) 0.4

    Fan RPM 518

    Operating Power (hp) 3.86

    Elevation (ft) 43

    Airstream Temp.(F) 70

    Air Density (ft3) 0.075

    Drive Loss (%) 4.1

    Tip Speed (ft/min) 6,506

    Static Eff. (%) 39

    Motor

    Motor Mounted Yes

    Size (hp) 5

    V/C/P 460/60/3

    Enclosure TEFC

    Motor RPM 1725

    Windings 1

    NEC FLA* (Amps) 7.6

    Notes:All dimensions shown are in units of in..

    *FLA - based on tables 150 or 148 of National Electrical

    Code 2002. Actual motor FLA may vary, for sizing thermal

    overload, consult factory.

    LwA - A weighted sound power level, based on ANSI S1.4

    dBA - A weighted sound pressure level, based on 11.5 dB

    attenuation per Octave band at 5 ft - dBA levels are not

    licensed by AMCA International

    Sones - calculated using AMCA 301 at 5 ft

    26/05/2Printed Date:PEPSICO - 22Job:

    UTILITMark:

    CAPS 4.14.1443 C:\Proyectos 2014\PEPSICO - 220514.gfcj Page

  • 5/22/2018 Submittals Equipos GREENHECK

    6/17

    Model: SBE-2L48-50

    Sidewall Belt Drive Exhaust Fan

    Standard Construction Features:

    - Galvanized steel fan panel - Die formed, galvanized steel drive frame assembly- Fabricated steel propeller for Levels 1 and 2, welded and painted steel for Level

    3 - Adjustable motor pulley - Ball bearing motors - Fan shaft mounted in ball

    bearing pillow blocks - Static resistant belts - Corrosion resistant fasteners

    Options & Accessories:NEMA Premium Efficient Motor - meets NEMA Table 12-12

    UL/cUL 705 Listed - "Power Ventilators"

    Damper, WD-320-PB-50X50, Gravity Operated (Mounted), Coated

    Short Wall Hsg, Flush Int., (2A-Exh), w/ OSHA Grd., Ctd with Hi-Pro Polyester,

    Concrete Gray-RAL 7023

    Galvanized Damper Guard

    Coating Hi-Pro Polyester, Concrete Gray-RAL 7023, Fan & Attached Accessories

    Bearings with Grease Fittings

    Unit Warranty: 1 Yr (Standard)

    26/05/2Printed Date:PEPSICO - 22Job:

    UTILITMark:

    CAPS 4.14.1443 C:\Proyectos 2014\PEPSICO - 220514.gfcj Page

  • 5/22/2018 Submittals Equipos GREENHECK

    7/17

    DAMPER TYP. SECTION VIEW

    50

    50

    3.5

    1.5

    2.75

    Standard Construction Features:

    - Model WD-320 is a vertical mount exhaust damper and is constructed of 18 ga galvanized steel with pre-punched mount

    holes and a flanged frame - Damper blades are 0.025 in. roll formed aluminum with vinyl seals on the closing edge - Steel

    are 0.188 in. diameter zinc plated mounted steel in acetal bushings - Synthetic axle bearings

    Notes: All dimensions shown are in units of in.

    Width And height furnished approximately 0.125 in. undersize

    Vertical Mount Exhaust Damper

    Model: WD-320

    26/05/2Printed Date:PEPSICO - 22Job:

    UTILITMark:

    CAPS 4.14.1443 C:\Proyectos 2014\PEPSICO - 220514.gfcj Page 1

  • 5/22/2018 Submittals Equipos GREENHECK

    8/17

    56.38

    3

    56.38

    44

    Standard Construction Features:

    - Galvanized steel construction - Heavy gauge mounting flanges - Pre-punched mounting holes - Insflanges allow damper to be mounted - Overlapping weatherhood flange keeps rain out - OSHA Prote

    guard of welded steel wire completely protects the drive side of the wall housing.

    Notes: All dimensions shown are in units of in.

    Short Wall Housing

    26/05/2Printed Date:PEPSICO - 22Job:

    UTILITMark:

    CAPS 4.14.1443 C:\Proyectos 2014\PEPSICO - 220514.gfcj Page 1

  • 5/22/2018 Submittals Equipos GREENHECK

    9/17

    Sound Power by Octave BandSound

    Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

    Inlet 91 89 85 82 78 74 70 64 84 73 22

    AIR FLOW

    See the Assembly Drawing For

    Selected Accessories

    56

    2

    25

    19

    49.25

    Model: SBE-2L48-50

    Sidewall Belt Drive Exhaust Fan

    DimensionalQuantity 2

    Weight w/o Acc's (lb) 279

    Weight w/ Acc's (lb) 573

    Max T Motor Frame Size 184

    Optional Damper (in.) 50 x 50

    Wall Opening (in.) 57.75 x 57.75

    PerformanceRequested Volume (CFM) 23,000

    Actual Volume (CFM) 23,000

    External SP (in. wg) 0.4

    Total SP (in. wg) 0.4

    Fan RPM 495

    Operating Power (hp) 3.88

    Elevation (ft) 43

    Airstream Temp.(F) 0

    Air Density (ft3) 0.086

    Drive Loss (%) 4.1

    Tip Speed (ft/min) 6,224

    Static Eff. (%) 39

    Motor

    Motor Mounted Yes

    Size (hp) 5

    V/C/P 460/60/3

    Enclosure TEFC

    Motor RPM 1725

    Windings 1

    NEC FLA* (Amps) 7.6

    Notes:All dimensions shown are in units of in..

    *FLA - based on tables 150 or 148 of National Electrical

    Code 2002. Actual motor FLA may vary, for sizing thermal

    overload, consult factory.

    LwA - A weighted sound power level, based on ANSI S1.4

    dBA - A weighted sound pressure level, based on 11.5 dB

    attenuation per Octave band at 5 ft - dBA levels are not

    licensed by AMCA International

    Sones - calculated using AMCA 301 at 5 ft

    26/05/2Printed Date:PEPSICO - 22Job:MECH ROOM 1Mark:

    CAPS 4.14.1443 C:\Proyectos 2014\PEPSICO - 220514.gfcj Page 1

  • 5/22/2018 Submittals Equipos GREENHECK

    10/17

    Model: SBE-2L48-50

    Sidewall Belt Drive Exhaust Fan

    Standard Construction Features:

    - Galvanized steel fan panel - Die formed, galvanized steel drive frame assembly- Fabricated steel propeller for Levels 1 and 2, welded and painted steel for Level

    3 - Adjustable motor pulley - Ball bearing motors - Fan shaft mounted in ball

    bearing pillow blocks - Static resistant belts - Corrosion resistant fasteners

    Options & Accessories:NEMA Premium Efficient Motor - meets NEMA Table 12-12

    UL/cUL 705 Listed - "Power Ventilators"

    Damper, WD-320-PB-50X50, Gravity Operated (Mounted), Coated

    Short Wall Hsg, Flush Int., (2A-Exh), w/ OSHA Grd., Ctd with Hi-Pro Polyester,

    Concrete Gray-RAL 7023

    Galvanized Damper Guard

    Coating Hi-Pro Polyester, Concrete Gray-RAL 7023, Fan & Attached Accessories

    Bearings with Grease Fittings

    Unit Warranty: 1 Yr (Standard)

    26/05/2Printed Date:PEPSICO - 22Job:MECH ROOM 1Mark:

    CAPS 4.14.1443 C:\Proyectos 2014\PEPSICO - 220514.gfcj Page 1

  • 5/22/2018 Submittals Equipos GREENHECK

    11/17

    DAMPER TYP. SECTION VIEW

    50

    50

    3.5

    1.5

    2.75

    Standard Construction Features:

    - Model WD-320 is a vertical mount exhaust damper and is constructed of 18 ga galvanized steel with pre-punched mount

    holes and a flanged frame - Damper blades are 0.025 in. roll formed aluminum with vinyl seals on the closing edge - Steel

    are 0.188 in. diameter zinc plated mounted steel in acetal bushings - Synthetic axle bearings

    Notes: All dimensions shown are in units of in.

    Width And height furnished approximately 0.125 in. undersize

    Vertical Mount Exhaust Damper

    Model: WD-320

    26/05/2Printed Date:PEPSICO - 22Job:MECH ROOM 1Mark:

    CAPS 4.14.1443 C:\Proyectos 2014\PEPSICO - 220514.gfcj Page 1

  • 5/22/2018 Submittals Equipos GREENHECK

    12/17

    56.38

    3

    56.38

    44

    Standard Construction Features:

    - Galvanized steel construction - Heavy gauge mounting flanges - Pre-punched mounting holes - Insflanges allow damper to be mounted - Overlapping weatherhood flange keeps rain out - OSHA Prote

    guard of welded steel wire completely protects the drive side of the wall housing.

    Notes: All dimensions shown are in units of in.

    Short Wall Housing

    26/05/2Printed Date:PEPSICO - 22Job:MECH ROOM 1Mark:

    CAPS 4.14.1443 C:\Proyectos 2014\PEPSICO - 220514.gfcj Page 1

  • 5/22/2018 Submittals Equipos GREENHECK

    13/17

    Int er na l v iew

    Width and Height furnished approximately 0.250 in. under size.

    EACC-4014 in. Frame, Concealed Actuator

    Appl ication & DesignEACC-401 is a combination louver/damper designed to protect air intake

    exhaust openings in building exterior walls that, at times, require tight air soff. Design incorporates a drainable head member, drainable stationary blad

    operable blades and a concealed actuator within the louver sill. When

    operable blades are open, airflow is permitted through the louver, when

    blades are closed, a tight seal is created to prevent the passage of air.

    Construction Features

    Frame Depth (in.): 4 Frame Thickness (in.): 0.125 Louver Material: Alumin

    Frame Type: Channel Sizing: Nominal Fixed Blade Thick. (in.): 0.0

    Adj. Blade Thick. (in.): 0.081 Blade/Jamb Seals: Yes Axle Bearings: Synth

    Axle Material: Steel

    Options and Accessories

    Finish

    Louver Finish Type: Mill

    ActuatorActuator Type: 120 VAC Actuator Mount: Internal Actuator Location: Left

    Actuator Fail. Pos.: Closed Act. Operating Mode: Two Position Transformer: None

    NEMA Enclosure: 1 Act. Access: Internal

    Insect ScreenInsect Screen Location: Internal Insect Screen Type: Aluminum

    FiltersFilter Material: Aluminum Filter Type: Permanent Filter Supplier: Greenheck

    Filter Removal: Rear Filter Depth (in.): 2.000

    WarrantyProduct Warranty: 1 Yr (Standard)

    Summary

    ID # Tag Qty. W (in.) H (in.)Free Area

    (ft2)Drive. Actuator Model Sect. Wide

    Sect.

    High

    Sect.

    Ship

    Actuato

    Ship Sec

    1-1 12 75.000 75.000 15.39 11-1FIL-0 MS4120F1006 2 1 24 1

    PerformanceID # Application Volume (CFM) Press. Drop (in. wg) Free Area Velocity (ft/min) BPWP (ft/min)

    1-1 Intake 7,667 0.028 481 1,192

    **Calculated pressure drop does not include the effects of screens, filters or other accessories

    26/05/2Printed Date:PEPSICO - 22Job:

    LOUVER UTILITIES & MECH ROMark:

    CAPS 4.14.1443 C:\Proyectos 2014\PEPSICO - 220514.gfcj Page 1

  • 5/22/2018 Submittals Equipos GREENHECK

    14/17

    Larger openings may require field assembly of multiple louver panels to make up the overall opening size. Individual louver panels are designed to withstand windloads up to a maximum of 25

    PSF (size and configuration dependent). Design, materials and installation of structural reinforcement required to adequately support large sections or multiple section assemblies within a large

    opening are not provided by Greenheck. Unless specifically indicated, the following are NOT included in the quote provided: structural steel, installation hardware (anchors, angle clips,

    continuous angles, shims, fasteners, inserts, backer rod and sealant), field measuring and/or installation, miscellaneous flashing, trim or enclosures, blank off panels, mullion covers or mullion

    hardware, hinged frames or removable subframes, custom bird/insect screen, 3-coat, metallic and/or exotic paint finishes, bituminous paints for unlike metals, any applicable taxes, stamped and

    sealed structural calculations seismic calculations or job specific engineered submittal drawings.

    26/05/2Printed Date:PEPSICO - 22Job:

    LOUVER UTILITIES & MECH ROMark:

    CAPS 4.14.1443 C:\Proyectos 2014\PEPSICO - 220514.gfcj Page 1

  • 5/22/2018 Submittals Equipos GREENHECK

    15/17

    Louvers Product Limited Warranty

    Thank you for purchasing Greenheck louvers. Greenheck warrants this equipment to be free from defect in material and workmanship for a period of

    yearfrom the date of product shipment. Any units or parts, which prove defective during the warranty period, will be repaired or replaced at our optio

    when returned to our factory, transportation prepaid. Unless agreed upon otherwise Greenheck will not be held responsible for costs associated with

    removal or installation of product(s).

    The legal remedies described in this Limited Warranty are the sole exclusive remedy of Customer. This limited warranty will be void if payment from

    Customer is not received within a commercially reasonable time frame. GREENHECK MAKES NO OTHER WARRANTY, EITHER EXPRESS OR

    IMPLIED, REGARDING ITS PRODUCTS, OR ITS SELECTION AND APPLICATION, INCLUDING, BUT NOT LIMITED TO, COMPLIANCE WITH

    BUILDING CODES, SAFETY CODES, LAWS, MERCHANTABILITY OR FITNESS OR A PARTICULAR PURPOSE. This limited warranty is extende

    solely to the Customer. It is nontransferable and non-assignable, and the Customer shall not permit or authorize its employees, agents, representativ

    or customers to claim, represent or imply that this limited warranty extends or is available to anyone other than the Customer.

    In the event of material breach by the Customer of any of the conditions of this warranty, Greenheck shall have no liability for and product failure clai

    Failure to pay Greenheck in full for original services will automatically make this warranty null and void.

    Greenheck will not be held liable for incidental or consequential damages of any kind. The limited warranty of product(s) replaced or repaired under

    limited warranty shall be limited to the remainder of the original warranty period. Greenheck reserves the right to reasonable field access to diagnos

    and repair any product alleged to be defective. This limited warranty may not be modified by anyone and may not be changed by such things as

    purchase order forms or acceptance forms, unless otherwise agreed upon by Greenheck.

    This limited warranty is provided in lieu of any other warranty requirements or obligations, including, but not limited to, those within project specificati

    All notices and claims given under or pursuant to this agreement shall be in writing and sent by certified or registered mail, postage prepaid, return

    receipt requested to: Greenheck, Attn: Louver Sales, 525 Western Road, Schofield, WI 54476.

    By proceeding to use our products and services on your project, you accept the terms of these limited warranties.

    26/05/2Printed Date:PEPSICO - 22Job:

    LOUVER UTILITIES & MECH ROMark:

    CAPS 4.14.1443 C:\Proyectos 2014\PEPSICO - 220514.gfcj Page 1

  • 5/22/2018 Submittals Equipos GREENHECK

    16/17

    Int er na l v iew

    Width and Height furnished approximately 0.250 in. under size.

    FSJ-4024 in. Frame, J Blade

    Appl ication & DesignFSJ-402 is fabricated stationary louver designed to protect air intake

    exhaust openings in building exterior walls. Design incorporates stationastyle blades. The FSJ-402 is an extremely efficient louver with AM

    LICENSED PERFORMANCE DATA enabling designers to select and apply w

    confidence.

    Construction Features

    Frame Depth (in.): 4 Frame Thickness (ga): 18 Louver Material: 304

    Frame Type: Channel Sizing: Nominal Fixed Blade Thick. (ga):

    Shape: Rectangular Welded Construction: Yes

    Options and Accessories

    FinishLouver Finish Type: Mill

    Insect ScreenInsect Screen Location: Internal Insect Screen Type: Stainless

    FiltersFilter Material: Aluminum Filter Type: Permanent Filter Supplier: GreenheckFilter Removal: Rear Filter Depth (in.): 2.000

    WarrantyProduct Warranty: 1 Yr (Standard)

    Summary

    ID # Tag Qty. W (in.) H (in.) Free Area (ft2) Sect. Wide Sect. High Sect. Ship

    3-1 24 132.000 66.000 30.13 3 1 72

    PerformanceID # Application Volume (CFM) Press. Drop (in. wg) Free Area Velocity (ft/min) BPWP (ft/min)

    3-1 Intake 25,000 0.096 798 834

    **Calculated pressure drop does not include the effects of screens, filters or other accessories

    Larger openings may require field assembly of multiple louver panels to make up the overall opening size. Individual louver panels are designed to withstand windloads up to a maximum of 25

    PSF (size and configuration dependent). Design, materials and installation of structural reinforcement required to adequately support large sections or multiple section assemblies within a large

    opening are not provided by Greenheck. Unless specifically indicated, the following are NOT included in the quote provided: structural steel, installation hardware (anchors, angle clips,

    continuous angles, shims, fasteners, inserts, backer rod and sealant), field measuring and/or installation, miscellaneous flashing, trim or enclosures, blank off panels, mullion covers or mullion

    hardware, hinged frames or removable subframes, custom bird/insect screen, 3-coat, metallic and/or exotic paint finishes, bituminous paints for unlike metals, any applicable taxes, stamped and

    sealed structural calculations seismic calculations or job specific engineered submittal drawings.

    26/05/2Printed Date:PEPSICO - 22Job:

    LOUVERS PROCMark:

    CAPS 4.14.1443 C:\Proyectos 2014\PEPSICO - 220514.gfcj Page 1

  • 5/22/2018 Submittals Equipos GREENHECK

    17/17

    Louvers Product Limited Warranty

    Thank you for purchasing Greenheck louvers. Greenheck warrants this equipment to be free from defect in material and workmanship for a period of

    yearfrom the date of product shipment. Any units or parts, which prove defective during the warranty period, will be repaired or replaced at our optio

    when returned to our factory, transportation prepaid. Unless agreed upon otherwise Greenheck will not be held responsible for costs associated with

    removal or installation of product(s).

    The legal remedies described in this Limited Warranty are the sole exclusive remedy of Customer. This limited warranty will be void if payment from

    Customer is not received within a commercially reasonable time frame. GREENHECK MAKES NO OTHER WARRANTY, EITHER EXPRESS OR

    IMPLIED, REGARDING ITS PRODUCTS, OR ITS SELECTION AND APPLICATION, INCLUDING, BUT NOT LIMITED TO, COMPLIANCE WITH

    BUILDING CODES, SAFETY CODES, LAWS, MERCHANTABILITY OR FITNESS OR A PARTICULAR PURPOSE. This limited warranty is extende

    solely to the Customer. It is nontransferable and non-assignable, and the Customer shall not permit or authorize its employees, agents, representativ

    or customers to claim, represent or imply that this limited warranty extends or is available to anyone other than the Customer.

    In the event of material breach by the Customer of any of the conditions of this warranty, Greenheck shall have no liability for and product failure clai

    Failure to pay Greenheck in full for original services will automatically make this warranty null and void.

    Greenheck will not be held liable for incidental or consequential damages of any kind. The limited warranty of product(s) replaced or repaired under

    limited warranty shall be limited to the remainder of the original warranty period. Greenheck reserves the right to reasonable field access to diagnos

    and repair any product alleged to be defective. This limited warranty may not be modified by anyone and may not be changed by such things as

    purchase order forms or acceptance forms, unless otherwise agreed upon by Greenheck.

    This limited warranty is provided in lieu of any other warranty requirements or obligations, including, but not limited to, those within project specificati

    All notices and claims given under or pursuant to this agreement shall be in writing and sent by certified or registered mail, postage prepaid, return

    receipt requested to: Greenheck, Attn: Louver Sales, 525 Western Road, Schofield, WI 54476.

    By proceeding to use our products and services on your project, you accept the terms of these limited warranties.

    26/05/2Printed Date:PEPSICO - 22Job:

    LOUVERS PROCMark:

    CAPS 4.14.1443 C:\Proyectos 2014\PEPSICO - 220514.gfcj Page 2