Job Name Location Purchaser Engineer Submitted to Reference Approval Construction Unit Designation Schedule # SUBMITTAL Page 1 of 4 www.SamsungHVAC.com Specifications AC024MNHDCH/AA Samsung Duct S, Single Zone Duct, Split System AC024MNHDCH/AA AC024JXADCH/AA 24,000 / 27,000 7,000 - 27,000 5,200 - 31,000 20.0 / 11.8 3.44 10.6 10146782 1 / 208-230 / 60 176 - 254 (max. 3% deviation from each) 2.8 / 9.4 / 12.0 2.5 / 10.6 / 14.5 20 13.5 47 1/4 X 9 13/16 X 27 9/16 37 X 39 11/16 X 12 3/4 89.3 142 45 15/16 X 8 11/16 45 15/16 X 8 11/16 Aluminum Fin / Copper Tube Aluminum, flat fin, micro channel 28 / 32 / 36 50 / 50 23 ~ 115°F(-5 ~ 46°C) 0 ~ 115°F(-18 ~ 46°C) w/ baffle -4 ~ 76°F(-20 ~ 24°C) 61 ~ 90°F(16 ~ 32°C) T ≤ 80°F(27°C) 1/4" 5/8" 164 98 1 1/16" ID for 3/4" PVC R410A Electronic Expansion Valve 74.08 25 ft 0.11 oz/ft over 25 ft Inverter Driven, Twin BLDC, Rotary 9.0 BLDC With Axial Type Fan (1) 0.48 A / 125 W / 2,190 CFM MWR-SH00N MWR-WE13UN MRK-A10N AR-EH03U MRW-TA FB-DS2 MIM-B14 MIM-N01 CKN-250 WBF-2M 25' - ILS-2509 50' - ILS-5009 MIM-H03UN WBB-3M Nominal Capacity Cooling / Heating (Btu/h) Cooling (Btu/h) Heating (Btu/h) Voltage ø / V / Hz Cooling (A) Heating (A) Max. Breaker Amps Indoor Unit Outdoor Unit Indoor Unit Outdoor Unit Supply (in.) Return (ID, in.) Type Outdoor Unit Indoor Unit dB(A) L / M / H Outdoor Unit dB(A) Cooling / Heating (high) Heating Cooling Heating High side (flare) Low side (flare) Factory Charge oz. RLA Amps Simplified Premium w/scheduling Simplified Touch Controller Wireless Signal Receiver Wireless Controller Front Back Certifications Safety ETL (UL 1995) Wireless Signal Control Optional Accessories External Contact Control Central Control Interface Module for Connection to DVM Plus Controls (non-NASA) Wall Bracket (for outdoor unit) Wind Baffles Line Sets - insulated and flared, interconnect cables included Filter Box Devices: PCB fuses, indoor unit terminal block thermal fuse, current transformer, over-voltage protection, crankcase heating, temperature limit protection logic, compressor overload sensing External Temperature Sensor Wi-Fi Adapter Wired Controller FLA / Watts / CFM (max.) Refrigerant Type Control Method Charged for Additional Refrigerant Compressor Type Condenser Fan Motor Operating Temperatures °F(°C) Outdoor Cooling Indoor Pipe Connections Indoor & Outdoor Maximum (ft.) Maximum Vertical Separation (ft.) Condensate Connection (with included adapter) W X H X D (in.) Weight (lbs.) Heat Exchanger Indoor Unit Sound Pressure Level Dimensions Duct Connections (W X H) Model Indoor Unit Model Number Outdoor Unit Model Number AHRI Certification Number Power Working Voltage Range (VAC) Operating Current (min. / std. / max.) Min. Circuit Ampacity (A) Performance 1 Capacity Range SEER / EER COP (nominal heating) HSPF MWR-SH11UN Horizontal discharge airflow Low ambient control built in The outdoor unit shall supply power to indoor unit via 14 AWG X 3 power wire Auto-restart after power loss The outdoor unit shall have a snow accumulation prevention option setting to prevent snow drifting against an idle outdoor unit. The indoor and outdoor units shall have a removable EEPROM that stores system programming information, unit name, and other data All indoor unit addressing and option settings shall be done digitally; the indoor unit does not contain rotary dials or setting switches. The indoor unit shall have a built-in condensate pump as standard with a 29" lift (from bottom of unit) and float switch that disables indoor unit during overflow detection. Pipe connections at the outdoor unit shall be made inside the unit chassis. Refrigerant pipes can exit through the front, side, rear, or bottom sides of the outdoor unit. The outdoor unit shall have a night time quiet mode option to reduce operating sound during the night (automatic or manual activation with dry contact signal). Construction The outdoor unit shall be galvanized steel with a baked on powder coated finish for durability The indoor unit shall be insulated, galvanized steel. Heat Exchanger The indoor unit heat exchanger shall be mechanically bonded fin to copper tube The outdoor unit heat exchanger shall be aluminum, flat fin, micro channel Controls Control signal shall be a DDC type signal Interconnect control wire between outdoor indoor unit shall be 16AWG X 2 shielded Wired or wireless controls must be purchased separately Connection to optional wired controllers shall be 2 X 16AWG shielded wire Controls shall integrate with a BMS system The system shall integrate with the Samsung NASA Controls Solution The indoor unit shall have automatic air volume scanning for simple setup and optimized comfort settings for the occupant. The indoor unit shall have smart-tuning function that can provide optimized comfort by allowing the occupant to offset the fan CFM curve with a wired remote controller (MWR- SH10N, MWR-WE13N, MWR-SH11UN, MWR-WE13UN) to increase or decrease airflow. The indoor unit shall allow service access from four sides (top, bottom, left, right). BLDC (1) With Sirocco Fan (3) 530 / 618 / 706 (at standard ESP) 153 W / 1.5 A 0.10 0.1 - 0.8 Air Volume CFM (L/M/H) Standard ("WC) Min. / Max. ("WC) Evaporator Fan Static Pressure Type Output (W) / FLA (A) Total CFM Range 2 530 - 1,035 2 Refer to installation manual for full fan curve details Samsung HVAC maintains a policy of ongoing development, specifications are subject to change without notice. Refer to www.AHRIdirectory.org for current reference numbers. No additional interface modules/adapters are required when connecting to Samsung NASA DVM S central control options. Refrigerant System The refrigerant shall be R410A The compressor shall be hermetically sealed, inverter controlled, twin BLDC Rotary Refrigerant flow shall be controlled by an electronic expansion valve at outdoor unit Soft-start to reduce current demand during compressor start Warranty 10 years compressor, 10 years parts, 1 year limited labor (conditions apply) www.SamsungHVAC.com © 2019 Samsung HVAC SHA-CAC-03012019 1 Certified in accordance with the AHRI Unitary Small Air-Source Heat Pumps (USHP) Certification Program which is based on the latest edition of AHRI Standard 210/240.

Transcript of SUBMITTAL Job Name Location Purchaser Engineer Submitted ... · Job Name Location Purchaser...

Page 1: SUBMITTAL Job Name Location Purchaser Engineer Submitted ... · Job Name Location Purchaser Engineer Submitted to Reference Approval Construction Unit Designation Schedule # SUBMITTAL

Job Name LocationPurchaser EngineerSubmitted to Reference Approval ConstructionUnit Designation Schedule #

SUBMITTAL Page 1 of 4 www.SamsungHVAC.com

Specifications

AC024MNHDCH/AASamsung Duct S, Single Zone Duct, Split System

AC024MNHDCH/AAAC024JXADCH/AA

24,000 / 27,0007,000 - 27,0005,200 - 31,000

20.0 / 11.83.4410.6

10146782

1 / 208-230 / 60176 - 254 (max. 3% deviation from each)

2.8 / 9.4 / 12.02.5 / 10.6 / 14.5

2013.5

47 1/4 X 9 13/16 X 27 9/1637 X 39 11/16 X 12 3/4

89.3142

45 15/16 X 8 11/1645 15/16 X 8 11/16

Aluminum Fin / Copper TubeAluminum, flat fin, micro channel

28 / 32 / 3650 / 50

23 ~ 115°F(-5 ~ 46°C)0 ~ 115°F(-18 ~ 46°C) w/ baffle

-4 ~ 76°F(-20 ~ 24°C)61 ~ 90°F(16 ~ 32°C)

T ≤ 80°F(27°C)

1/4"5/8"16498

1 1/16" ID for 3/4" PVC

R410AElectronic Expansion Valve

74.0825 ft

0.11 oz/ft over 25 ft

Inverter Driven, Twin BLDC, Rotary9.0

BLDC With Axial Type Fan (1)0.48 A / 125 W / 2,190 CFM

MWR-SH00N

MWR-WE13UN

MRK-A10NAR-EH03UMRW-TAFB-DS2MIM-B14

MIM-N01

CKN-250WBF-2M

25' - ILS-250950' - ILS-5009

MIM-H03UN

WBB-3M

Nominal Capacity Cooling / Heating (Btu/h)Cooling (Btu/h)Heating (Btu/h)

Voltage ø / V / Hz

Cooling (A)Heating (A)

Max. Breaker Amps

Indoor UnitOutdoor UnitIndoor UnitOutdoor UnitSupply (in.)Return (ID, in.)

TypeOutdoor Unit

Indoor Unit dB(A) L / M / HOutdoor Unit dB(A) Cooling / Heating (high)

HeatingCoolingHeating

High side (flare)Low side (flare)

Factory Charge oz.

RLA Amps

Simplified

Premium w/schedulingSimplified Touch Controller

Wireless Signal ReceiverWireless Controller

FrontBack

CertificationsSafety

ETL (UL 1995)

Wireless Signal Control

Optional Accessories External Contact Control

Central Control Interface Module for Connection to DVM Plus Controls (non-NASA)Wall Bracket (for outdoor unit)

Wind Baffles

Line Sets - insulated and flared, interconnect cables included

Filter Box

Devices: PCB fuses, indoor unit terminal block thermal fuse, current transformer, over-voltage protection, crankcase heating, temperature limit protection logic, compressor overload sensing

External Temperature Sensor

Wi-Fi Adapter

Wired Controller

FLA / Watts / CFM (max.)

Refrigerant

TypeControl Method

Charged for Additional Refrigerant

CompressorType

Condenser FanMotor

Operating Temperatures °F(°C)

OutdoorCooling

Indoor

Pipe Connections

Indoor & Outdoor

Maximum (ft.)Maximum Vertical Separation (ft.)Condensate Connection (with included adapter)

W X H X D (in.)Weight (lbs.)

Heat ExchangerIndoor Unit

Sound Pressure Level

Dimensions

Duct Connections(W X H)

ModelIndoor Unit Model NumberOutdoor Unit Model Number

AHRI Certification Number

Power

Working Voltage Range (VAC)Operating Current(min. / std. / max.)

Min. Circuit Ampacity (A)

Performance 1Capacity Range

SEER / EER COP (nominal heating)HSPF

MWR-SH11UN

• Horizontal discharge airflow

• Low ambient control built in

• The outdoor unit shall supply power to indoor unit via 14 AWG X 3 power wire

• Auto-restart after power loss

• The outdoor unit shall have a snow accumulation prevention option setting to prevent snow drifting against an idle outdoor unit.

• The indoor and outdoor units shall have a removable EEPROM that stores system programming information, unit name, and other data

• All indoor unit addressing and option settings shall be done digitally; the indoor unit does not contain rotary dials or setting switches.

• The indoor unit shall have a built-in condensate pump as standard with a 29" lift (from bottom of unit) and float switch that disables indoor unit during overflow detection.

• Pipe connections at the outdoor unit shall be made inside the unit chassis. Refrigerant pipes can exit through the front, side, rear, or bottom sides of the outdoor unit.

• The outdoor unit shall have a night time quiet mode option to reduce operating sound during the night (automatic or manual activation with dry contact signal).

ConstructionThe outdoor unit shall be galvanized steel with a baked on powder coated finish for durability

The indoor unit shall be insulated, galvanized steel.

Heat ExchangerThe indoor unit heat exchanger shall be mechanically bonded fin to copper tube

The outdoor unit heat exchanger shall be aluminum, flat fin, micro channel

ControlsControl signal shall be a DDC type signal

Interconnect control wire between outdoor indoor unit shall be 16AWG X 2 shielded

Wired or wireless controls must be purchased separately

Connection to optional wired controllers shall be 2 X 16AWG shielded wire

Controls shall integrate with a BMS system

The system shall integrate with the Samsung NASA Controls Solution

• The indoor unit shall have automatic air volume scanning for simple setup and optimized comfort settings for the occupant.

• The indoor unit shall have smart-tuning function that can provide optimized comfort by allowing the occupant to offset the fan CFM curve with a wired remote controller (MWR-SH10N, MWR-WE13N, MWR-SH11UN, MWR-WE13UN) to increase or decrease airflow.

• The indoor unit shall allow service access from four sides (top, bottom, left, right).

BLDC (1) With Sirocco Fan (3)530 / 618 / 706 (at standard ESP)

153 W / 1.5 A0.10

0.1 - 0.8

Air Volume CFM (L/M/H)

Standard ("WC)Min. / Max. ("WC)

Evaporator Fan

Static Pressure

Type

Output (W) / FLA (A)Total CFM Range 2 530 - 1,035

2 Refer to installation manual for full fan curve detailsSamsung HVAC maintains a policy of ongoing development, specifications are subject to change without notice. Refer to www.AHRIdirectory.org for current reference numbers.

No additional interface modules/adapters are required when connecting to Samsung NASA DVM S central control options.

Refrigerant SystemThe refrigerant shall be R410A

The compressor shall be hermetically sealed, inverter controlled, twin BLDC Rotary

Refrigerant flow shall be controlled by an electronic expansion valve at outdoor unit

Soft-start to reduce current demand during compressor start

Warranty10 years compressor, 10 years parts, 1 year limited labor (conditions apply)

www.SamsungHVAC.com© 2019 Samsung HVAC

SHA-CAC-03012019

1 Certified in accordance with the AHRI Unitary Small Air-Source Heat Pumps (USHP) Certification Program which is based on the latest edition of AHRI Standard 210/240.

Page 2: SUBMITTAL Job Name Location Purchaser Engineer Submitted ... · Job Name Location Purchaser Engineer Submitted to Reference Approval Construction Unit Designation Schedule # SUBMITTAL

888-699-6067 www.SamsungHVAC.com

Page 2 of 4 SUBMITTAL AC024MNHDCH/AASamsung Duct S, Single Zone Duct, Split System AC024MNHDCH/AA Fan Characteristics (P-Q Curve)

Fan performance characteristics based on installation option setting (7 fan options)

Exte

rnal

Sta

tic P

ress

ure

(inW

C)

Exte

rnal

Sta

tic P

ress

ure

(inW

C)

Exte

rnal

Sta

tic P

ress

ure

(inW

C)

Exte

rnal

Sta

tic P

ress

ure

(inW

C)

Exte

rnal

Sta

tic P

ress

ure

(inW

C)

Exte

rnal

Sta

tic P

ress

ure

(inW

C)

Airflow Rate (CFM) Airflow Rate (CFM)

Airflow Rate (CFM)

Airflow Rate (CFM) Airflow Rate (CFM)

Airflow Rate (CFM)

400 500 600 700 800 900 10000

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

400 500 600 700 800 900 1000 11000

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

500 600 700 800 900 1000 11000

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

500 600 700 800 900 1000 11000

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

500 600 700 800 900 1000 11000

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

500 600 700 800 900 1000 11000

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

External Static Pressure (inWC) 0.24<P≤ 0.35

Option Code01B0EC-1E55D1-274750-374020

3External Static Pressure (inWC)

0.35<P≤ 0.47Option Code

01B0EC-1E5937-274750-3740204

External Static Pressure (inWC) P=0.10 (Default)

Option Code01B0EC-1E5407-274750-374020

1External Static Pressure (inWC)

0.10<P≤ 0.24Option Code

01B0EC-1E547B-274750-3740202

External Static Pressure (inWC) 0.47<P≤ 0.60

Option Code01B0EC-1E599D-274750-374020

5

1

2

Lower limit ofexternalstatic pressure

Upper limit ofexternalstatic pressure

3

Lower limit ofexternalstatic pressure

HIGH

LOW

Upper limit ofexternalstatic pressure

MID

4

Lower limit ofexternalstatic pressure

HIGH

LOW

Upper limit ofexternalstatic pressure

MID

5

Lower limit ofexternalstatic pressure

HIGH

LOW

Upper limit ofexternalstatic pressure

MID

External Static Pressure (inWC) 0.60<P≤ 0.70

Option Code01B0EC-1E5AF3-274750-374020

6

6

Lower limit ofexternalstatic pressure

HIGH

LOW

Upper limit ofexternalstatic pressure

MID

HIGH

LOW

MID

HIGH

LOW

MID

Exte

rnal

Sta

tic P

ress

ure

(inW

C)

Airflow Rate (CFM)

500 600 700 800 900 1000 11000

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

External Static Pressure(inAq) 0.70<P≤

0.80

Option Code01B0EC-1E5E59-274750-374020

7

7

Lower limit ofexternalstatic pressure

Upper limit ofexternalstatic pressureHIGH

LOW

MID

Page 3: SUBMITTAL Job Name Location Purchaser Engineer Submitted ... · Job Name Location Purchaser Engineer Submitted to Reference Approval Construction Unit Designation Schedule # SUBMITTAL

888-699-6067 www.SamsungHVAC.com

Page 3 of 4 SUBMITTAL AC024MNHDCH/AASamsung Duct S, Single Zone Duct, Split System AC024MNHDCH/AA Dimensional Drawing

NO Name Description1 Liquid pipe connection Ø1/4"2 Gas pipe connection Ø5/8"3 Drain pipe connection 1 1/16" ID for 3/4" PVC4 Power supply connection -5 Air discharge flange -6 Air filter -7 Suspension point 5/16" ~ 3/8"

13/16" or more

13/16" or moreCeiling

Unit Clearance From StructureStructure

Service Access

UnitUnit D

epth

+ 2"

Unit Width (W)

A=W+4"

Inspection Opening Requirements

In applications where there is not a tile ceiling, an inspection hole is required.If height between ceiling and structure is 1.64' or more, inspection opening "B" is recommended. If height between ceiling and structure is less than 1.64', inspection opening "A" and "B" is recommended.(verify state and local codes).

B=19 11/16" min.

27 9

/16"

19 11/16"47 1/4"

51 3/16"

Inspection opening

9 1/4"

14 3/16" 3"

8 11

/16"

9 3/

4"3

3/4"

[Right View]

14

3

25 3/4"

[Front View]

Suspension bolt(4xM8 ~M10)

30-Ø 0.13" hole Return air flange 45 15/16"

29 1

/4"27

1/2

"

Return air flange

[Top View]

23 3

/4"

Susp

ensi

on P

ositi

on

Supply air direction

47 1/4"49 1/4" (Suspension Position)

11 x P100=1100

5

6

5 3/

4"6 1

/2"

7 1/4

"

7

45 15/16"

Page 4: SUBMITTAL Job Name Location Purchaser Engineer Submitted ... · Job Name Location Purchaser Engineer Submitted to Reference Approval Construction Unit Designation Schedule # SUBMITTAL

888-699-6067 www.SamsungHVAC.com

Page 4 of 4 SUBMITTAL AC024MNHDCH/AASamsung Duct S, Single Zone Duct, Split System AC024JXADCH/AA Dimensional Drawing

4 - ø15/32"

37 1/8"

37" 11 9/32"

24 7/16"

38 1

1/16

"

25 3

/4"

39 1

1/16

"14

3/1

6"

15 1

/8"

19 5

/16"

27 1

/16"

TOP

FRONT FRONT WITHOUT SERVICE COVER

12 3

/4"

No. Description

Liquid service valve2Suction service valve

3 Drainage hole

1

4 Power and communication conduit openings