Sub-Cooling · 2017-05-17 · To obtain the amount of sub-cooling subtract 111°F from 120°F. The...
Transcript of Sub-Cooling · 2017-05-17 · To obtain the amount of sub-cooling subtract 111°F from 120°F. The...
Sub-Cooling
Subcooling Method
SUBCOOLING METHOD IS USED IN SYSTEMS THAT HAVE A TXV METERING DEVICE
CONDENSER Temperatures
Pressures States
• High Pressure High Temperature Superheated Vapor
• Saturation Point • (vapor changing to a
liquid as heat is removed)
CONDENSER INLET
CONDENSER OUTLET
• High Pressure Sub-cooled Liquid
Saturated Liquid Pressure and Temperature
Pressure
Saturated
Condensing
Temperature
Condenser Side
Sat. Cond. Temp.
Pressure
Saturated Liquid Pressure
Sub-cooling
Charging Method
METERING DEVICES - TXV
Charging Thermostatic Expansion Valve (TEV) Systems
• The TEV will maintain design superheat under a variety of conditions
• For this reason, these systems must be CHARGED using sub-cooling
• Proper sub-cooling will maintain a positive liquid seal at the TEV entrance
• Determine the required sub-cooling from the IO or the unit datasheet (usually from about 8°F to about 12°F
Temperature Probe Test Point Locations
• LIQUID LINE SERVICE VALVE (Smaller of the two copper lines)
• INSULATE THE PROBE FOR A MORE ACCURATE READING
• Allow the unit to operate for 15 to 20 minutes before checking the sub-cooling.
• This is to insure stable operation. If the temperatures and pressures will not stabilize, look for other problems before attempting to check sub-cooling.
• Attach an accurate thermometer to the liquid line near the inlet to the metering device if possible. A condenser outlet reading may be taken but will be in error by the amount of liquid line temperature/pressure losses.
Checking Sub-cooling
• Record the temperature reading.
• Connect a manifold gauge set to the liquid service valve and record the pressure. Again, discharge pressure may be used but allowances must be made for condenser coil pressure drop.
• Using a Pressure/Temperature Chart, find the saturation temperature for the liquid pressure obtained.
• Subtract the line temperature from the saturation temperature. The difference is the amount of sub-cooling.
Suction Line (Vapor)
Liquid Line
111°F
Determine Operating Sub-cooling
Measure Liquid Line Temperature
118 PSIG 417 PSIG
• Measure Liquid Line Pressure
• Convert Pressure to Saturation Temperature
• Subtract SATURATION Temperature from
ACTUAL Temperature
• The Difference is OPERATING Sub-cooling
Checking Subcooling
EXAMPLE: a. Liquid Line Pressure = 417 b. Corresponding Temp. °F. = 120° c. Thermometer on Liquid line = 111°F. To obtain the amount of sub-cooling subtract
111°F from 120°F. The difference is 9° sub-cooling.
Sub-cooling should be 9 ºF (+ or - 2°F)
Add charge to raise subcooling. Recover charge to lower subcooling.
Sub-cooling = Sat. Liquid Temp. - Liquid Line Temp.
• Low sub-cooling indicates a condenser that is starved for liquid refrigerant
• Long liquid lines
• High vertical separation
• Liquid lines exposed to high ambient temperatures
• Low condenser air flow
• Inadequate condenser size
Low Sub-cooling
• High sub-cooling indicates a condenser flooded with liquid refrigerant
• Refrigerant overcharge
• Low outdoor ambient temperatures
• Liquid line restriction
• Incorrect or faulty metering device
High Sub-Cooling
Proper measurement and interpretation of Superheat & Sub-cooling is the only way to
determine proper operation and performance of HVAC systems
The Service Technician must develop these skills and use them correctly
Summary