STYRAX INSTRUMENTS INDIA PVT LTD2.imimg.com/data2/CX/UY/MY-2112424/4-to-12-door...Using “ ”and...

17
Instruction Manual Ver 1.1 STYRAX INSTRUMENTS INDIA PVT LTD INSTRUCTION MANUAL INTERLOCKING SYSTEM (UPTO 12 DOOR) MODEL NO: ILS1058 VERSION: 1.1 Styrax Instruments India Pvt. Ltd. PLOT No.48-51,Dollapally, Phase V Extn. I.D.A., Jeedimetla, Hyderabad 014 Andhra Pradesh, INDIA Ph: +91 40 2309 3314 Fax: +91 40 2309 3315 www.styraxinstruments.com Email: sales@styraxinstruments.com Instrument SI. No :

Transcript of STYRAX INSTRUMENTS INDIA PVT LTD2.imimg.com/data2/CX/UY/MY-2112424/4-to-12-door...Using “ ”and...

Page 1: STYRAX INSTRUMENTS INDIA PVT LTD2.imimg.com/data2/CX/UY/MY-2112424/4-to-12-door...Using “ ”and “ “ keys the programmer can set the door delay time as required. Using “ ”and

Instruction Manual Ver 1.1

STYRAX INSTRUMENTS INDIA PVT LTD

INSTRUCTION MANUAL

INTERLOCKING SYSTEM (UPTO 12 DOOR) MODEL NO: ILS1058

VERSION: 1.1

Styrax Instruments India Pvt. Ltd. PLOT No.48-51,Dollapally,

Phase V Extn. I.D.A.,

Jeedimetla, Hyderabad – 014

Andhra Pradesh, INDIA

Ph: +91 40 2309 3314

Fax: +91 40 2309 3315

www.styraxinstruments.com

Email: [email protected]

Instrument SI. No :

Page 2: STYRAX INSTRUMENTS INDIA PVT LTD2.imimg.com/data2/CX/UY/MY-2112424/4-to-12-door...Using “ ”and “ “ keys the programmer can set the door delay time as required. Using “ ”and

Instruction Manual (Ver1.1)

STANDARD PACK

1) Instruction Manual --- 1 No

2) ILS-1058 Instrument --- 1 No

Checked By :

Date :

1. DESCRIPTION:

In clean room areas, any personnel passing through an unclassified area to a classified area is required to

pass through series of rooms. In each room certain steps need to be followed. This procedure ensures that the

person is not carrying any external contamination in to the process area and also the pressure in each room is

maintained before opening of door.

Door Inter Locking System achieves in prevention of process area contamination by

Preventing simultaneous access of doors/Rooms.

Ensures that when one door for a room is OPEN then all other doors in that particular room are closed.

Programmable delay between each door openings to maintain required pressure.

In Emergency an override key is available on a push button module for opening the door.

2. CONTROLLER FEATURES:

Advanced Micro controller based.

Supports Maximum of 12 doors & 24 Push buttons.

Supports Maximum of 12 Emergency Stations.

Sequence of door inter Locking is field configurable.

Delay between door openings is field configurable from 0 to 999 Sec.

Auto close time is field configurable from 0 to 999 Sec.

Facility available to read feed back from Magnetic Lock.

8x2 DOT MATRIX LCD for Programming.

Easy use Soft touch Tactile Membrane keypad & user-friendly programming options.

Non-Volatile Flash memory to store programming parameters.

Supports Access control module interface.

SPECIFICATIONS:

GENERAL

Push Button Inputs : 12 No.

Door Feedback Inputs : 12 No, 24V.

Door Control Outputs : 12 No, 24V / 25mA

Keypad : Soft touch Tactile Membrane Keys, 4.

Display : 8x2 Alphanumeric LCD.

Page 3: STYRAX INSTRUMENTS INDIA PVT LTD2.imimg.com/data2/CX/UY/MY-2112424/4-to-12-door...Using “ ”and “ “ keys the programmer can set the door delay time as required. Using “ ”and

Instruction Manual (Ver1.1)

Memory : Non-Volatile Flash.

Delay between each door : Programmable 0 to 999 Sec.

Door control sequencing : Programmable.

ENCLOSURE:

Enclosure type : MS (Siemens gray, Powder coated)..

Mounting : Flush / Panel / Wall mounting.

POWER:

Power source : 100 to 260 V, AC 50 Hz.

ENVIORMENTAL:

Temperature : 0 to 500C.

RH : 10 – 95%, Non-condensing.

MECHANICAL:

Weight : approx. 1Kg.

Dimensions : 495X295X50 mm

3. Push Button Station

Features: Elegant look Legrand Silver painted plastic Bezel/Face plate.

Indication facility for Door entry permitted / prohibited.

Support an entry switch for opening the door.

Long Life BAR LED for door open/close indication.

Elegant look Silver painted plastic Bezel with appropriate curvature to prevent resting of dust & powder.

Easy mounting arrangement for fixing on Doorframes or on Wall.

Specifications:

GENERAL:

Keypad : Soft touch Tactile Membrane Key

Status LED’s : WAIT Message for Door Open / Entry Prohibited.

GO Message for Door Close / Entry Permitted.

Digital Input (LED) : 24V DC

Life : 100, 000 Cycles Min.

ENCLOSURE:

Enclosure type : Legrand Silver painted plastic Bezel/Face plate.

Mounting : Flush mounting.

Dimension : 3”X3” Single Module.

POWER:

Page 4: STYRAX INSTRUMENTS INDIA PVT LTD2.imimg.com/data2/CX/UY/MY-2112424/4-to-12-door...Using “ ”and “ “ keys the programmer can set the door delay time as required. Using “ ”and

Instruction Manual (Ver1.1)

Supply Voltage : 24V/50mA DC

4. Emergency Station

Features: Elegant look Legrand Silver painted plastic Bezel/Face plate.

Support an push button switch for opening the all doors.

Elegant look Silver painted plastic Bezel with appropriate curvature to prevent resting of dust & powder.

Easy mounting arrangement for fixing on Doorframes or on Wall.

Specifications:

GENERAL:

Keypad : Soft touch Tactile Membrane Key

Digital Input (LED) : 24V DC

Life : 100, 000 Cycles Min.

ENCLOSURE:

Enclosure type : Legrand Silver painted plastic Bezel/Face plate.

Mounting : Flush mounting.

Dimension : 3”X3” Single Module.

POWER:

Supply Voltage : 24V/50mA DC

5. Electromagnetic locks:

A magnetic lock is a simple locking device that consists of an electromagnet

and armature plate. By attaching the electromagnet to the door frame and the

armature plate to the door, a current passing through the electromagnet

attracts the armature plate holding the door shut

The magnetic lock relies upon some of the basic concepts of

electromagnetism. Essentially it consists of an electromagnet attracting a

conductor with a force sufficiently large enough to prevent the door from

being opened.

Page 5: STYRAX INSTRUMENTS INDIA PVT LTD2.imimg.com/data2/CX/UY/MY-2112424/4-to-12-door...Using “ ”and “ “ keys the programmer can set the door delay time as required. Using “ ”and

Instruction Manual (Ver1.1)

6. OPERATION:

Key operation

▲: Increment key: To increment the parameter value.

►: Right shift key: To shift the cursor position to the right side.

OK: To enter a particular program parameter.

PRG: To enter into program mode and to exit the program mode.

PROGRAM MODES

S.NO MODE DESCRIPTION

1 Auto Lock To select time between the door release and re- energizing

the lock as required.

2 nC All doors to be in Normally Open/Normally Close

position

3 Emrgency Configure the doors for Emergency.

4 DI Configure the Door 1.

5 DII Configure the Door 2.

6 DIII Configure the Door 3.

7 DIV Configure the Door 4.

8 DV Configure the Door 5.

9 DVI Configure the Door 6.

10 DVII Configure the Door 7.

11 DVIII Configure the Door 8.

12 New Psd. To Enter new password.

Brief description of the program mode.

1) Auto Lock: This mode is to set the time between de-energizing of the electric strike or electro

magnetic lock and re-energizing the electric strike or electro magnetic lock.

2) nC: This mode is to enable the user to keep the doors either in the normally open (normally un locked)

or normally close (normally locked) position.

3) Emrgnency: This mode is to select the doors to be configured to emergency input i.e. which doors

should be interlocked to the emergency key press.

4) DI - DVIII: This mode is to select the doors to be configured to a particular door input i.e. which doors

should be interlocked to the that door’s key press.

5) New Psd.: This mode is to allow the user to enter a new password.

PROGRAMMING

NOTE: 1) The default value of the auto close timer is 4sec.

2) By default, all the doors will be in normally closed (normally locked) position.

3) By default, no door will be configured to any other door for interlocking.

4) By default, the delay timers of all doors are 000sec.

PROGRAM MODE:

i). Press “PRG” key to enter into the PROGRAM MODE.

ii). The following menu is displayed.

Page 6: STYRAX INSTRUMENTS INDIA PVT LTD2.imimg.com/data2/CX/UY/MY-2112424/4-to-12-door...Using “ ”and “ “ keys the programmer can set the door delay time as required. Using “ ”and

Instruction Manual (Ver1.1)

Use “►” key to move to the required location.

Use “▲” key to increment the location value (0 - 9).

Use “OK” key after entering the PASS WORD. (Default PASS WORD is 100)

The menu in the PROGRAM MODE is shown below.

Auto Lock Delay:

Using “▲”and “►” keys the programmer can set the auto close time delay i.e the time between the door release

and energising the lock as required.

Use “OK” key to go to next menu.

Normally Open/Normally Close, Lock:

Using “▲” key the programmer can configure the doors as normally open or normally close.

Y :-Normally Close.

N:- Normally Open.

Use “►” key to move to the next location (EM LOCK).

Y :- Electro magnetic lock.

Use “OK” key to go to next menu.

NOTE:

* Possible Mode of operations:

Page 7: STYRAX INSTRUMENTS INDIA PVT LTD2.imimg.com/data2/CX/UY/MY-2112424/4-to-12-door...Using “ ”and “ “ keys the programmer can set the door delay time as required. Using “ ”and

Instruction Manual (Ver1.1)

Emergency Configuration:

Emrgency

X X X X X X X X

Using “▲”and “►” keys the programmer can configure the doors (1-8) for emergency.

0 – Emergency inactive.

1 – Emergency active.

Use “OK” key to go to next menu.

GO, WAIT message toggle indicates that emergency or fire situation, in this situation both doors in un locked

condition up to 8 sec.

Door 1 Configuration:

SI. NO.

Mode of Operation

Program mode

1.

Normally Closed

Electro magnetic lock.

nC: Y

EM LOCK: Y

Normally Closed

Electric striker.

nC: Y

EM LOCK: N

Mode Description:

*Locking device is Electro magnetic lock or Electric striker. Normally locked:

In this mode, initially all doors in locked condition. Door access by using push button. Message

indication provided on the push button station indicates whether person can access the door or not.

Go = GO indicates that person can access the door.

Wait = WAIT indicates that person cannot access the door.

If emergency button pressed, all doors (emergency configured doors) will be unlocked up to 8 sec &

indication on push button will be toggle indicates emergency.

2.

Normally Open

Electro magnetic lock.

nC: N

EM LOCK: Y

Normally Open

Electric striker.

nC: N

EM LOCK: N

Mode Description:

*If locking device is Electromagnetic lock, separate reed Switch (magnetic sensor) is need be used.

Normally Un locked:

In this mode, initially all doors in un locked condition, here push buttons are used only for indication

purpose (no need to press the button). Message indication provided on the push button station indicates

whether person can access the door or not.

In this mode controller continuously monitors status of the door (open/close) through feed back from

magnetic lock. If any door is open then the system will lock the remaining doors as per configuration and

for duration required.

Go = GO indicates that person can access the door.

Wait = WAIT indicates that person cannot access the door.

If emergency button pressed, all doors (emergency configured doors) will be unlocked up to 8 sec &

indication on push button will be toggle indicates emergency.

Page 8: STYRAX INSTRUMENTS INDIA PVT LTD2.imimg.com/data2/CX/UY/MY-2112424/4-to-12-door...Using “ ”and “ “ keys the programmer can set the door delay time as required. Using “ ”and

Instruction Manual (Ver1.1)

DI XXX

d X X X X X X X

xxx -: door delay (secs). Time after which door will open after the closure of some door in its set.

Using “▲”and “►” keys the programmer can set the door delay time as required.

Using “▲”and “►” keys the programmer can configure the doors (1-8) for Door 1 set.

d – not applicable.

0 – Door not selected for inter locking with Door 1.

1 – Door selected for inter locking Door 1.

Use “OK” key to go to next menu.

Door 2 Configuration:

DII XXX

X d X X X X X X

xxx -: door delay (secs). Time after which door will open after the closure of some door in its set.

Using “▲”and “►” keys the programmer can set the door delay time as required.

Using “▲”and “►” keys the programmer can configure the doors (1-8) for Door 2 set.

d – not applicable.

0 – Door not selected for inter locking with Door 2.

1 – Door selected for inter locking with Door 2.

Use “OK” key to go to next menu.

Door 3 Configurations:

DIII XXX

X X d X X X X X

xxx -: door delay (secs). Time after which door will open after the closure of some door in its set.

Using “▲”and “►“ keys the programmer can set the door delay time as required.

Using “▲”and “►” keys the programmer can configure the doors (1-8) for Door 3 set.

d – not applicable.

0 – Door not selected for inter locking with Door 3.

1 – Door selected for inter locking with Door 3.

Use “OK” key to go to next menu.

Door 4 Configuration:

Page 9: STYRAX INSTRUMENTS INDIA PVT LTD2.imimg.com/data2/CX/UY/MY-2112424/4-to-12-door...Using “ ”and “ “ keys the programmer can set the door delay time as required. Using “ ”and

Instruction Manual (Ver1.1)

DIV XXX

X X X d X X X X

xxx -: door delay (secs). Time after which door will open after the closure of some door in its set.

Using “▲”and “►” keys the programmer can set the door delay time as required.

Using “▲”and “►” keys the programmer can configure the doors (1-8) for Door 4 set.

d – not applicable.

0 – Door not selected for inter locking with Door 4.

1 – Door selected for inter locking with Door 4.

Use “OK” key to go to next menu.

Door 5 Configuration:

DV XXX

X X X X d X X X

xxx -: door delay (secs). Time after which door will open after the closure of some door in its set.

Using “▲”and “►” keys the programmer can set the door delay time as required.

Using “▲”and “►” keys the programmer can configure the doors (1-8) for Door 5 set.

d – not applicable.

0 – Door not selected for inter locking with Door 5.

1 – Door selected for inter locking with Door 5.

Use “OK” key to go to next menu.

Door 6 Configurations:

DVI XXX

X X X X X d X X

xxx -: door delay (secs). Time after which door will open after the closure of some door in its set.

Using “▲”and “►” keys the programmer can set the door delay time as required.

Using “▲”and “►” keys the programmer can configure the doors (1-8) for Door 6 set.

d – not applicable.

0 – Door not selected for inter locking with Door 6.

1 – Door selected for inter locking with Door 6.

Use “OK” key to go to next menu.

Door 7 Configuration:

DVII XXX

X X X X X X d X

xxx -: door delay (secs). Time after which door will open after the closure of some door in its set.

Using “▲”and “►” keys the programmer can set the door delay time as required.

Using “▲”and “►” keys the programmer can configure the doors (1-8) for Door 7 set.

Page 10: STYRAX INSTRUMENTS INDIA PVT LTD2.imimg.com/data2/CX/UY/MY-2112424/4-to-12-door...Using “ ”and “ “ keys the programmer can set the door delay time as required. Using “ ”and

Instruction Manual (Ver1.1)

d – not applicable.

0 – Door not selected for inter locking with Door 7.

1 – Door selected for inter locking with Door 7.

Use “OK” key to go to next menu.

Door 8 Configuration:

DVIII XXX

X X X X X X X d

xxx-: door delay (secs). Time after which door will open after the closure of some door in its set.

Using “▲”and “►” keys the programmer can set the door delay time as required.

Using “▲”and “►” keys the programmer can configure the doors (1-8) for Door 8 set.

d – not applicable.

0 – Door not selected for inter locking with Door 8.

1 – Door selected for inter locking with Door 8.

Use “OK” key to go to next menu.

New Password:

New Psd

X X X

Use “►” key to move to the required location.

Use “▲” key to increment the location value(0 - 9).

Press “OK” key and then again press PRG To enter the new password and store all parameters.

7. Wiring Diagrams:

Page 11: STYRAX INSTRUMENTS INDIA PVT LTD2.imimg.com/data2/CX/UY/MY-2112424/4-to-12-door...Using “ ”and “ “ keys the programmer can set the door delay time as required. Using “ ”and

Instruction Manual (Ver1.1)

Page 12: STYRAX INSTRUMENTS INDIA PVT LTD2.imimg.com/data2/CX/UY/MY-2112424/4-to-12-door...Using “ ”and “ “ keys the programmer can set the door delay time as required. Using “ ”and

Instruction Manual (Ver1.1)

Page 13: STYRAX INSTRUMENTS INDIA PVT LTD2.imimg.com/data2/CX/UY/MY-2112424/4-to-12-door...Using “ ”and “ “ keys the programmer can set the door delay time as required. Using “ ”and

Instruction Manual (Ver1.1)

Page 14: STYRAX INSTRUMENTS INDIA PVT LTD2.imimg.com/data2/CX/UY/MY-2112424/4-to-12-door...Using “ ”and “ “ keys the programmer can set the door delay time as required. Using “ ”and

Instruction Manual (Ver1.1)

8. MECHANICAL DRAWINGS:

Figure for Installation of ILS-1058 Controller:

Front View Diagram of ILS-1058 Controller:

Page 15: STYRAX INSTRUMENTS INDIA PVT LTD2.imimg.com/data2/CX/UY/MY-2112424/4-to-12-door...Using “ ”and “ “ keys the programmer can set the door delay time as required. Using “ ”and

Instruction Manual (Ver1.1)

9. ORDERING INFORMATION: l). Door Interlocking System ( up to 8 Door):

Includes,

a) Door interlock controller (8Door):

b) Push Button Station:

Model No X Description

ILS-1054 X 4-Door interlocking System

ILS-1055 X 5-Door interlocking System

ILS-1056 X 6-Door interlocking System

ILS-1057 X 7-Door interlocking System

ILS-1058 X 8-Door interlocking System

Model No X Description

ILS-1054C X 4-Door interlocking Controller

ILS-1055C X 5-Door interlocking Controller

ILS-1056C X 6-Door interlocking Controller

ILS-1057C X 7-Door interlocking Controller

ILS-1058C X 8-Door interlocking Controller

Page 16: STYRAX INSTRUMENTS INDIA PVT LTD2.imimg.com/data2/CX/UY/MY-2112424/4-to-12-door...Using “ ”and “ “ keys the programmer can set the door delay time as required. Using “ ”and

Instruction Manual (Ver1.1)

c) Emergency Station:

d) IO MODULE:

e) Electromagnetic Lock:

e) Power Supply:

10. TROUBLE SHOOTING:

SL.NO Problem Cause Action

1. No Message indication. Power Failed Check the Power supply connections.

2. Indication on Push button

blinking.

Noise Switch OFF and switch ON again. If

problem is reported again then contact to the

factory.

3. Continuous WAIT

indication on push button

Other door is not

closed properly or

magnet armature not

fixed properly

Adjust armature until get GO

NOTES:

Model No X

ILS-105P 1. PLASTIC LEGRAND PUSH BUTTON

ILS-105P 2. SS FRAME PUSH BUTTON

Model No X

ILS-105E 1. PLASTIC LEGRAND PUSH BUTTON

ILS-105E 2. SS FRAME PUSH BUTTON

Model No X

ILS-IO X

Model No X

EML 1. Bar Electro magnetic lock

Model No X

ILS-PS X

Page 17: STYRAX INSTRUMENTS INDIA PVT LTD2.imimg.com/data2/CX/UY/MY-2112424/4-to-12-door...Using “ ”and “ “ keys the programmer can set the door delay time as required. Using “ ”and

Instruction Manual (Ver1.1)

For Further Information Contact:

Styrax Instruments India Pvt. Ltd. PLOT No.48-51, Dollapally road, Phase V Extn. I.D.A., Jeedimetla, Hyderabad – 014

Andhra Pradesh, INDIA

Ph: +91 40 2309 3314, +91 9640447474, Fax: +91 40 2309 3315

www.styraxinstruments.com

Email: [email protected]