Steady-State and Dynamic Performance Characterization of a Microturbine

24
Steady-State and Dynamic Performance Characterization of a Microturbine Power System 2002 Impact of Distributed Generation Conference March 13-15, 2002 Clemson, SC Rick Langley EPRI PEAC Corporation Knoxville, TN

description

Steady-State and Dynamic Performance Characterization of a Microturbine. Power System 2002 Impact of Distributed Generation Conference March 13-15, 2002 Clemson, SC Rick Langley EPRI PEAC Corporation Knoxville, TN. Microturbine System Under Test. - PowerPoint PPT Presentation

Transcript of Steady-State and Dynamic Performance Characterization of a Microturbine

Page 1: Steady-State and Dynamic Performance Characterization of a Microturbine

Steady-State and Dynamic Performance Characterization of a Microturbine

Power System 2002

Impact of Distributed Generation Conference

March 13-15, 2002

Clemson, SC

Rick Langley

EPRI PEAC Corporation

Knoxville, TN

Page 2: Steady-State and Dynamic Performance Characterization of a Microturbine

Microturbine SystemUnder Test

• Microturbine installed in EPRI PEAC’s Distributed Resource and Power Quality Park (DRPQ Park) in January of 2001

• The system was installed for technology demonstrations and lab testing of DER technologies.

Page 3: Steady-State and Dynamic Performance Characterization of a Microturbine

Microturbine SystemUnder Test

• Three-phase Inverter-based DER– Grid-Dependent

• 400-480Vac, 45-65Hz

– Grid-Independent• 150-480Vac, 10-60Hz

• Automatic “mode-transfer” capability allows the unit to automatically switch from grid-dependent mode to grid-independent mode and back, based on the health of the utility power supply.

Distributed Resource Type

Microturbine Generator

Grid-Dependent Capable

Yes

Grid-Independent Capable

Yes

Automatic Mode-Transfer

Yes

Output kW, kVA – Grid-Dependent

28, 28

Output kW, kVA – Grid-Independent

28, 40(@ 0.7pf min)

Fuel Type / Fuel Pressure

Low-pressureNatural Gas / 15 psi

Page 4: Steady-State and Dynamic Performance Characterization of a Microturbine

Microturbine SystemUnder Test

• The microturbine does not have a discrete generator or combination generator/feeder protection relay.

• The microturbine relies on its own microprocessor-based protection system that is built into the system controls.

• The system has a separate voltage monitor relay used to determine if the power grid is suitable for connection (nominal voltage level and unbalance).

• The microturbine’s grid-dependent and grid-independent protective functions are user-programmed (undervoltage, overvoltage, over-frequency, and under-frequency).

Page 5: Steady-State and Dynamic Performance Characterization of a Microturbine

Microturbine SystemUnder Test

• The microturbine’s grid-dependent protection functions were set according to IEEE P1547-Draft 8.

Microturbine Setup

Automatic Mode-Transfer Enabled

Automatic Restart Enabled

Grid-Dependent Protection Function Settings

Type Setpoint Time-Delay

UndervoltageLevel 1

424.0V (88%)

2.0 sec

UndervoltageLevel 2

240.0V (50.0%)

0.010 sec (not changeable)

OvervoltageLevel 1

528.0V (110%)

1.0 sec

OvervoltageLevel 2

576.0V (120%)

0.010 sec (not changeable)

Under-frequency 59.3Hz 0.010 sec (not changeable)

Over-frequency 60.5Hz 0.010 sec (not changeable)

Page 6: Steady-State and Dynamic Performance Characterization of a Microturbine

Test Categories

• Grid-Dependent Tests– Characterization of Nominal Voltage Tolerance Thresholds

• Voltage Unbalance, Overvoltage, & Undervoltage Tests.

– Characterization of Response to Voltage Variations• Voltage Sags, Swells, Capacitor-Switching Transients.

– Tendency to Island• Voltage interruptions and Single-Phasing.

• Grid-Dependent Tests– Characterization of Dynamic Loading Performance

• Resistive Step Loading

• Motor Starting

Page 7: Steady-State and Dynamic Performance Characterization of a Microturbine

Characterization of Nominal Voltage Tolerance Thresholds

• Changes in the Local EPS Nominal Voltage– Undervoltage

– Overvoltage

– Voltage Unbalance

Page 8: Steady-State and Dynamic Performance Characterization of a Microturbine

Characterization of Nominal Voltage Tolerance Thresholds

• Voltage Unbalance Tests– Local EPS voltage unbalance was slowly varied until the microturbine tripped, i.e., ceased to energy the Local EPS.– The microturbine tripped at 3% voltage unbalance.

• Undervoltage Tests– Local EPS voltage level was slowly decreased until the microturbine tripped.– The microturbine tripped at ~90% of nominal voltage.

• Overvoltage Tests– Local EPS voltage was slowly increased until the microturbine tripped.– The microturbine tripped at ~110% of nominal voltage.

Page 9: Steady-State and Dynamic Performance Characterization of a Microturbine

Characterization of Nominal Voltage Tolerance Thresholds

• Significance– The IEEE P1547 standard does not

specifically identify these tests.– However, these issues are important because

they represent of the potential variability in electric power systems.

– DER systems should be designed so that they are compatible with the normal variability of the Local EPS.

Page 10: Steady-State and Dynamic Performance Characterization of a Microturbine

Characterization of Response to Voltage Variations

• Single-phase, two-phase, and three-phase voltage sags of various magnitudes and durations were applied to the Local EPS.

Page 11: Steady-State and Dynamic Performance Characterization of a Microturbine

Characterization of Response to Voltage Variations

0

10

20

30

40

50

60

70

80

90

100

0 20 40 60 80 100 120 140 160 180Sag Duration

(in cycles)

Sag

Mag

nit

ud

e(i

n %

of

nom

inal

)

-500

-400

-300

-200

-100

0

100

200

300

400

500

0 0.05 0.1 0.15 0.2 0.25

Time (in seconds)

Vol

tage

(in

Vol

ts)

-20

-15

-10

-5

0

5

10

15

20

Cu

rrent (in

Am

ps)

Load Van Utility Van Turbine Ia

Page 12: Steady-State and Dynamic Performance Characterization of a Microturbine

Characterization of Response to Voltage Variations

• Significance– According to IEEE P1547, a DG system should trip

offline if the magnitude of the Local EPS voltage falls below 88% for 2 seconds or 50% for 10 cycles.

– It also states that the DG shall not reconnect until the Local EPS voltage is within Range B of ANSI C84.1.

– The test results show that the microturbine system under test responded in a manner that was consistent with the programming of the microturbine’s grid-dependent protective functions and the criteria defined by the IEEE draft standard.

Page 13: Steady-State and Dynamic Performance Characterization of a Microturbine

Tendency to Island

• Single- and three-phase voltage interruptions were applied to the Local EPS at several different durations.

Page 14: Steady-State and Dynamic Performance Characterization of a Microturbine

Tendency to Island

Microturbine Setpoint

Load Setpoint

Interruption Type

Response Time

30kW 15kW Single-Phase

42 cycles (0.7 sec)

15kW 15kW Single-Phase

1440 cycles (24.0 sec)

7.5kW 15kW Single-Phase

120 cycles (2.0 sec)

15kW 15kW Three-Phase 1 cycle (0.017 sec)

Page 15: Steady-State and Dynamic Performance Characterization of a Microturbine

Tendency to Island

• Significance– Significant variability in detection time to single-

phasing conditions based on the microturbine and load setpoints.

– Single-phasing detection times were greater than the Voltage Disturbance criteria defined by IEEE P1547 (reference Section 4.2.1) .

• IEEE P1547 criteria for voltage <50% of nominal is 0.16 sec.

– Three-phase interruption detection time was very fast with little variability in response regardless of the microturbine and load setpoints.

Page 16: Steady-State and Dynamic Performance Characterization of a Microturbine

Tendency to Island

• Significance– None of the relevant standards (IEEE P1547, IEEE

929, and UL 1741) directly address how three-phase DER systems should react to single-phasing conditions .

– There will be many locations where distribution protection equipment, such as fuses, sectionalizers, or reclosers, may open only one phase in a three-phase system.

– These test results clearly demonstrate the need for the clarification of the classification of single-phasing in the DER interconnection standards.

Page 17: Steady-State and Dynamic Performance Characterization of a Microturbine

Characterization of Dynamic Loading Performance

• The objective was to characterize the microturbine system’s grid-independent performance during dynamic loading conditions:– Motor Starting

– Resistive Step-Loading

Page 18: Steady-State and Dynamic Performance Characterization of a Microturbine

Characterization of Dynamic Loading Performance

• 15kW to 30kW Resistive Step Load– The temporary

voltage drop was less than 5% of nominal.

• 30kW to 15kW Resistive Step Load– The temporary

voltage rise was less than 6% of nominal.

0

25

50

75

100

125

150

175

200

225

250

275

300

0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45

Time(in seconds)

Vol

tage

(in

rm

s V

olts

)

0

5

10

15

20

25

30

35

40

45

50

55

60

Cu

rrent

(in rm

s Am

ps)

Van Ia

Page 19: Steady-State and Dynamic Performance Characterization of a Microturbine

Characterization of Dynamic Loading Performance

• “Line-starting” of a 5-hp (3.73-kW) three-phase induction motor. – The voltage on Phase A

was reduced to 28% of its nominal value.

– Phases B and C were affected to a lesser degree at 58% and 81% of nominal, respectively.

– The system voltage returned to nominal as soon as the motor accelerated to the full speed.

0

25

50

75

100

125

150

175

200

225

250

275

300

0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55

Time(in seconds)

Vol

tage

(in

rms

Vol

ts)

0

10

20

30

40

50

60

70

80

90

100

110

120

Current

(in rms A

mps)

Van Ia

Page 20: Steady-State and Dynamic Performance Characterization of a Microturbine

Characterization of Dynamic Loading Performance

• Significance– The ability to operate Distributed Energy Resources

in grid-independent modes can significantly increase system reliability.

– When grid power is not available, DER systems can be valuable assets to maintain critical facility loads.

– However, compatibility between the critical loads and the standby DER can be an issue.

– In some cases, alternative-starting methods, such as soft-starters for “line-connected” motors, may be required.

Page 21: Steady-State and Dynamic Performance Characterization of a Microturbine

Conclusion

• Distributed energy resources hold great promise for improving the efficiency and reliability of the nation’s electric power systems.

• However, before the full benefits of DER can be realized, a number of potential barriers to interconnection of DR equipment must be overcome.

• In its recent report, “Making Connections,” DOE’s National Renewable Energy Laboratory (NREL) identified a number of technical issues, business practices, and regulatory rules that can increase the cost of and unnecessarily delay or even stop viable projects with potential benefits for both end users and power-delivery companies.

Page 22: Steady-State and Dynamic Performance Characterization of a Microturbine

Conclusion

• EPRI, the utility industry, and the DOE are responding with initiatives to test and certify DER hardware with research projects aimed at “breaking down the barriers” to interconnection by answering technical questions about DER capabilities for end-users and the electric utility grid through:– Developing engineering guides, software tools, and test protocols,

– Conducting field demonstrations and laboratory testing, and

– Supporting education, training, and standards development activities for DER.

– Testing of this microturbine DER system supports these initiatives.

Page 23: Steady-State and Dynamic Performance Characterization of a Microturbine

Conclusion

• The microturbine has operated reliably during many grid voltage disturbance tests and demonstrations.

• Its built-in protection functions have met most, but not all the response expectations of IEEE P1547 and utility wires companies.– The single-phasing issue is still open.

• Analysis of the test results reveals that this system is best suited for grid-connect that do not have interruption-free power requirements and standby power applications .

• In grid-independent or standby power applications, load and microturbine compatibility should be reviewed before installation.– Alternative load starting and powering methods may be required.

• Testing continues on the microturbine system at the EPRI PEAC laboratory.

Page 24: Steady-State and Dynamic Performance Characterization of a Microturbine

Acknowledgements

• This research was supported in part by the U.S. Department of Energy, Office of Power Technologies under Contract DE-AC05-00OR22725 with UT-Battelle.

• Member’s of EPRI’s Completing the Circuit for their support of this research.