Static Frequency Converters With Reduced Parasitic Effects

download Static Frequency Converters With Reduced Parasitic Effects

of 6

Transcript of Static Frequency Converters With Reduced Parasitic Effects

  • 8/11/2019 Static Frequency Converters With Reduced Parasitic Effects

    1/6

    2004

    35th Annual IEEE Power Elecrronirs Specialists Conference

    Aar hm , G ermany , 2 4

    Static frequency converters with reduced parasitic effects

    Oliver Drubel Max Hobelsb erger

    Drubel@,ieee.org

    ALSTOM (Switzerland) Ltd.,

    Turboge nerator Development, Zentralstr.

    40

    CH-5242 Birr, 0liver.drubel~alstom.nower.com

    ALSTO M (Switzerland) Ltd.

    Custom er Service

    A b s l r a c l : Parasitic effects caused by static frequency

    converters, like EMI, may endanger the reliable operation of

    drives or turbine shaft arran gemen ts and diminish its lifetime.

    Converter drive applications for large plants up to 500MVA

    can cause shaft voltages up

    to

    SOOV,, if a non optim ised

    converter design is chosen. This phenomenon is investigated.

    Design options for the converter and the plant arrangement

    are discussed. The influence of the most suitable solution and

    their influence upon electromagnetic interference (EMI) and

    the shaft voltages is shown and conformed by measurements

    in real power plants.

    K e y w o r d s :

    Static frequency converter, EMI, shaft voltage,

    power application

    I

    INTRODUCTION

    Recent developmen ts in power generation equ ipment show an

    increasing growth

    in

    the installed unit power of gas turbines.

    Gas turbines with up to 260 MW are proven d esign with high

    reliability. Whereas steam turbines are capable to run up

    independently, gas turbines have to be started and driven until

    they turn fast enough to allow ingnition and self-sustaining

    operation. Ignition may not be possible until up to

    80%

    of

    nominal speed.

    For running up the turbine it is state of the art to use the

    turbo-generator as motor. Electrical power is supplied

    to

    the

    generator-motor by

    a

    variable-speed starting device like a

    static frequency con verter (SFC). A typical start arrangemen t

    is givenin fig. 1.

    This SFC has to deliver considerable amounts of power, e.g.

    5-15

    MW for a typical large gas turbine. The SFC is

    disconnected from the generator after running up the gas-

    turbine to ignition and self-sustained operation. The

    generator-motor is consequently used as generator. Usually

    this start-up operation with active SFC takes only a cou ple of

    minutes, e.g. 7 minutes w hich is only a short period of time.

    Because of this short period some effects and phenomena

    during start-up were not discovered until recently.

    However due to modern use of gas-turbine plants to generate

    peak-load turbines must be switched on and off several times

    per day; and in between these times of full operation there are

    also prolonged periods of active SFC-operation for

    maintenance purposes. Therefore shaft voltages during start

    static frequency con version have to be cared for as well.

    A key component to reduce shaft voltages is the design of the

    SFC [3]. Therefore the SFC is within the focus of this

    investigation.

    11 OBSERVED EFFECTS AT A TYPICAL POWER PLANT

    Strong electromagnetic interferences occurred at sensors,

    video screens and distributed control equipment (DCS) at a

    typical

    300

    MVA gas-turbine plant during SFC-operation.

    The powerful SFC and the close proximity of control

    equipment

    to

    the SFC has been the main reason for these

    disturbances. The grounding and shielding of systems was

    then improved to reduce the interference to acceptable levels

    which appea red to be qu ite costly.

    Furthermore it was observed during maintenance works that

    the fuse at the NDE shaft-grounding module ( RC-module

    in

    Fig. 1: Electrical power plant equipment for starting the gas

    Fig. 2) had blown.

    turbine

    0-7803-8399-0/04/ 20.0082 4

    EEE. 4365

    mailto:Drubel@,ieee.orgmailto:Drubel@,ieee.org
  • 8/11/2019 Static Frequency Converters With Reduced Parasitic Effects

    2/6

    2004 35th Annu al IE EE Power Electronics Specialists Conference

    The grounding arrangement is shown in Fig. 2 below. The

    shaft has its main grounding at the drive-end (DE) of the

    generator. At the non-driven end (NDE) the shaft is

    additionally grounded by a mainly capacitive element.

    Therefore no low-frequency current can flow. H ow we r high-

    frequency voltage peaks (typically caused by the SCKs

    thyristors oft he excitat ion system) are strongly dam ped [ I ] .

    Tvbb.

    Aacken. Germany,

    2004

    turbine. Every 6.66 ms a huge peak appeares, followed by a

    much lower peak after 3.33 ms. It is evident that the rectifier

    at the input-side of the SFC has to be considered as the

    primary cause.

    111 INVESTIGA TION O F THE SFC GENERATED SHA FT

    VOLTAGE

    Within electrical machines shaft voltages occur

    on

    account of

    different effects [1-6,10]. With the application of power

    electronic devices, new types of shaft voltage sources occur

    [3-61. In general shaft voltages due to power electronics are

    either capacitive or inductive.

    After the introduction of power electronics for static

    excitation the voltage peaks of the rectifier bridge caused

    severe voltage peaks

    on

    the shaft [I]. These kind of peaks

    occurred during normal operation. The voltages were coupled

    by the capacitance between the rotor-field winding and the

    shaft. Therefore the shaft current is different at the drive end

    in comparison with the non-drive end. Reichert, Amman,

    Posedel and Joho designed a method to suppress the shaft

    voltages in 1988. In order to avoid a direct coupling of the

    shaft at the non-drive end (NDE) they coupled the shaft

    capacitively to ground, see

    [ I ]

    Some other publications related to experie nce with conve rter

    fed asynchronous machines [4,6] an inductively coupled the

    shaft voltage. Here the currents at drive end and non-drive

    end must be the same.

    Synchronized m easure men ts at the DE-side an d the NDE-side

    showed that a positive p ulse at the NDE-side coincides with a

    negative pulse at the DE-side and vice versa. So the picture of

    a closed current loop arises with the current being induced by

    changing mag netic fields in the stator core. This hypothesis is

    supported by the observation that the pulses at NDE have

    low- impedant sources. Current strengths of up to 70 A were

    measured which could not be explained by capacitive

    coupling.

    These kinds of shaft voltages are clearly inductively caused

    with the SFC as main root cause. Th e speed independent time

    period of 3.33ms with stro ng pulses every 6.66 ms reveals the

    strong relation to the SF C's rectifier. A typical electrical

    design of a co nverte r fed plant drive is given in Fig.4. Fig. 4

    reveals a strong asymm etry concerning the arrangement o f the

    main choke between the rectifier and converter. According to

    this model current measurement coils (Rogovsky coils) and

    voltage senso rs have been installed at a multitude of

    significant locations in the real equipment and corresponding

    measurements were done.

    .

    SMI xmdm WGnumm WGxmdm

    n o m

    DEM

    R C M

    C

    B m

    CVBRUd

    Fig

    2:

    Grounding scheme o f shaft train with KC-module

    Measurements determined voltage peaks with abnormally

    high amplitudes, fig.3, during active SFC-operation to be the

    cause of th e blown fuse .

    200

    speed n i l 8 9 rpm

    150

    100

    50

    I

    -

    0

    >

    5 50

    -100

    -150

    -200

    c

    v)

    0.01 0.02 0.03

    25OF; I

    I

    I

    '

    Time

    s )

    Fig. 3: Shaft voltage peaks at ND E during turbine run up

    The shown voltage pattern is in its timely distribution of

    peaks independent of the turning speed of the running-up

    m

  • 8/11/2019 Static Frequency Converters With Reduced Parasitic Effects

    3/6

    2004

    35th

    A n n u l IEEE Power

    Electronics Specialists

    Conference

    Anchen.

    Germany. 2W4

    The static frequency converter consists of two thyristor

    bridges. It is a current-type converter: Between both bridges a

    D.C. circuit exists with one choke only in the positive branch.

    The negative branch connects both bridges directly. The

    bridge at the grid side is used to adjust the voltage level of the

    D.C. circuit (and hence the DC current) and works asla

    rectifier. During o ne period of 20m s each o f the 6 thyristors is

    switched

    on

    and off. Three of them are connected to the

    positive branch (link) with the choke, the other three are

    directly connected to the output -rectifier bridge.

    The bridge at the machine side works as a converter. A t lower

    speeds it operates in block mode, afterwards it works as LCI

    converter.

    1.

    It was determined that the start-up transformer could not be

    the source of the pulses.

    A

    clear relationship between the shaft voltages and the

    transformer currents should exist in case of the transformer as

    voltage source. Figure 5 show s the summation of all three

    transformer phase currents.

    Shafivolaee

    at non

    d

    end

    I50

    IO0

    SO

    0

    -50

    -100

    -150

    Fig. 5: Relationship between the summation current of all

    transformer phases a nd the shaft voltage.

    N o relationship between the shaft voltage and the summation

    current can be found in Fig. 5

    2.

    Whereas the transformer as source of the new sha ft voltage

    phenomenon could be excluded, the SFC seem s to be the real

    source.

    It is obvio us from Fig.

    6

    that a strong common-mode cu rrent

    (summation of all phase currents)

    flows

    into the SFC and out

    of it again without alteration. The conclusion is that the

    current loop must be closed via the generator, ground, the

    shielding of the SFC supply-cables and their shielding

    capacitances. There are no other connections left. The

    similarity between curve shap es of common mode current and

    shaft voltage is also striking.

    100

    0

    -100

    Sh&vo lege

    IMP 4456)

    2001

    50

    t v

    I I I I J I

    0.0194

    0.01 0.0198

    Time

    t ( s )

    Fig. 6 : Current into the SFC and out of the SFC

    3. In [ 6 ] it was shown how the shaft voltage is induced by a

    circulating flux flow through the generator core. The

    circulating flux flow can only occur

    in

    case of a difference

    between the current in the positive and negative axial

    direction. Therefore the current of the stator terminals and the

    neutrals is measured, Fig. 7.

    -200

    a r r e n t at Etdmr neutral

    w

    4440)

    -240

    b -280

    -300 (MP4436)

    -3201

    - 3 4 0 b , I , , , , I , , ,

    ~,

    , , I , ,

    , I ,

    0.01976 0.01978 0.0198 0.01982 0.01984

    Time

    t s)

    Fig. 7: Current into one generator terminal and out of the

    generator neutral conn ection

    Indeed figure 7 eveals a phase difference of about I0-15p

    between the curren t at the phase-terminal and at the neutral

    connection. The time constants of the shaft voltage-pulses and

    the difference curren t between the stato r terminal-current and

    neutral-current are fairly similar. It will cause a circular

    magnetic flux in the stator core and hence induce the shaft-

    voltage pulses.

    In the following more em phasis is given

    to

    voltages measured

    in or at the SFC during these switching processes. All these

    voltage-surges and oscillations contribute to overall EM1 and

    also to increased stress of components.

    It can be seen in Fig. 8 that during valve-change-over of the

    corresponding conducting thyristors of the rectifier-bridge

    very strong current-oscillations appear in the two connected

    cables a nd their shields.

    4367

  • 8/11/2019 Static Frequency Converters With Reduced Parasitic Effects

    4/6

    2 4

    35th Annual IEEE

    Power

    Elecrrunics Specialisrs Conference

    Aachen Germany, 2004

    0.021 0.0212

    o 021 Time

    1

    s)

    Fig. 8: Current in the grounding-connections of the

    transformer SFC cable a) Phase U, b) Phase V, c) Phase W

    These currents flow in differential mode and do not influence

    the shaft voltage. They produce however strong EM1 due to

    the relatively high frequencies involved.

    Fig. 9 and Fig. 10show the considerable common-mode

    voltage pulses and steep voltage slopes to which the whole

    SFC-system and also the generator winding is subjected. The

    commo n mode voltage is given by the summ ation

    o f

    the three

    terminal voltages,

    F

    0 5 10 I S

    20 25

    Tirnr rnr)

    Fig. 10

    Voltages to ground at the SFC input terminals

    r j

    2

    . . . .

    1 1

    .

    5

    10 I5 20 25 ~~

    Timc(rnr)

    .~

    Fig. 1 I Voltages at the links inside the SFC

    The negative-link potential voltage (curve 3 is pushed down

    very steeply

    to

    low values. At the same time the potentials at

    the SFC-inputs are pushed up. However, when the positive-

    link thyristors are switching almost no effect on the shaft-

    voltage can be o bserved. This

    is

    due

    to

    the protecting effect

    of the inductor in the positive link.

    In

    Fig. 1 1 it is clearly visible that

    the

    shaft-voltage pulses

    coincide with every switching of the rectifier-thyristors

    connected to the negative link. Fig. 12 gives

    a

    magnified view

    of the processes.

    2.5 s h # ' * a . m Y w h - t m

    .nm*ndsma-

    w

    , W . b 8 r n W d r n

    A.---

    -.-. . ._

    __.

    wYp.*n..-.

    -d.r.V*

    ,

    > -0.5

    0.W5

    0.01 0.015

    0.02

    0.025 0.1

    0.035

    0.04 0045

    0.05

    Time

    I) - 1 . 5

    I_

    Fig. 9: Commo n mode voltage at SFC-input terminals

    -2.5

    6.4 6.5 6.6

    6.1

    6.8

    6.9 7.1 7

    ~

    Time , lo

    Fig. 12 Voltages of links inside the SFC

    The potential of the negative link starts to slope steeply

    downwards. The potential of the voltage between the choke

    and generator follows and also the shaft voltage follows. This

    is again a clear indication that switching of the rectifier

    4368

  • 8/11/2019 Static Frequency Converters With Reduced Parasitic Effects

    5/6

    2004

    35th Annual IEEE Power Electronics Specialists Conference

    thyristors connected to the negative link cause the pulses on

    the shaft voltage.

    IV IMPROVED SFC DESIGN

    The influence of the SFC design is one of the dominant

    factors for the parasitic effects, which can he seen at the shaft.

    The direct connection of rectifier thyristors to the negative

    link and with it to the generator connections has been

    identified above as main cause for high frequency pulses.

    This configuration can be used a s long as the shaft voltages

    stay within appropriate limits [1,7-91. If these limits are

    exceeded the SF C needs to be modified.

    One very effective modification is

    to

    use a split choke within

    the d.c. circuit of the SFC. A split or preferably symmetric

    inductor will prevent steep gradients and HF-pulses from

    travelling into the generator. The choke will significantly

    reduce the voltage gradients to which the generator winding is

    subjected and keep

    it

    at acceptable values. This design

    ensures a very smooth operation. It is also an economically

    acceptable solution because no large additional components

    are needed in general: The main inductor is split into two

    halfs, wh ich is often quite feasible. No big ch anges are caused

    electrically to the SFC by this change: The internal DC-

    current path and its control is still dominated by the same

    inductances.

    The beneficial influence of the choke on the high-frequency

    generation ofth e SFC can he seenin Fig. 13.

    The shaft voltage during a commutation at the positive link of

    the SFC is only

    a

    third or even less than during a

    commutation at the negative link. The main reason for this is

    the strong HF-damping by the choke, see fig.

    13

    below. In

    Fig. 13 it is clearly visible that the HF-content

    of

    the voltage

    after the choke is almost negligible.

    Aachen Germany 2004

    ShaRvoltage(MP4456)

    000

    MOO

    4000

    d .c .

    link

    voltage

    befors &e

    choke,

    tranrformrside MP 455)

    d.c.

    linkvoltage

    a fe r & e choke,

    MP4454)

    - E -2oooE Y

    .0176 0.0178

    0.018

    -4WE -30;j174

    Time t

    s)

    Fig. 13Voltages before and after the choke, positive link

    Beside the influence of the SFC (steepness of voltagelcurrent

    changes), other parameters like the cable length between the

    start up transformer and the SF C as well as between the SFC

    end the generator have to be taken into account.

    Generally, modifications to converters within plants of some

    IOOMVA output have to be b ased on

    a

    deep understanding of

    the phenomenon involved. The refore design modifications to

    the static frequency converter (SFC) must take into account

    all main com ponents which are involved. Mod ifications need

    firstly

    to

    he simulated by using simplified mathematical

    models

    of the whole plant with all the main par& involved.

    The effectiveness has

    to

    he shown in simulations. The

    proposed design improvem ent is a result of these simulations.

    VI SUCCESSFULLY IMPLEMENTED MODIFICATION

    The influence of the modifications could be proven in the

    meantime at several power plants which showed high shaft-

    voltage pulses. All the plants had long cab les between start-

    up transformer and SFC resulting in high coupling

    capacitance to ground at the inputs of the SFC.

    The main modification has been the implementation of a

    symmetrical choke in both d.c. links of the SFC. The

    influence of this change within the frequency converter

    design is shown in fig. 15 .

    4369

  • 8/11/2019 Static Frequency Converters With Reduced Parasitic Effects

    6/6

    2004

    35111

    Annu al I EE E Power Elecrronics Specialists Conference

    Aachen, German),, 2004

    Time

    t

    @s)

    Fig. 15: Measured shaft voltages with and without

    symmetrical choke

    The modification has been a complete success. The high-

    freque ncy compon ents (-5OkHz) of the shaft-v oltage pulse

    have almost completely disappeared. They are efkctiv ely

    blocked by the inductors in both links. There is no low-

    impedance grou nd-loop anymore for HF-bursts cau sed by the

    SFC. Only a signal of considerable lower frequency -10

    kHz) and much lower amplitude is left. The voltage peaks

    have been reduced to a third of the original value. High

    frequency signals causing EM1 have almost been eliminated

    by this relatively simp le modification.

    Furthe rmore it became clear that the source-impedance of the

    pulses could be considerably increased by the additional

    choke. That means that the capacitive grounding module at

    the ND E-side of the generator can reduce the vo ltage pulses

    even further without being subjected to increased

    electricaVthermal stress due to high HF-c urrents .

    It was possible to reduce the level of shaft voltages even

    below the expe cted level.

    V CONCLUSIONS

    Measurements in a 300MVA power plant allowed to identify

    the mechanism w hich causes the observed HF shaft-voltage

    pulses at converter-fed large electrical machines. The root

    causes for these pulses were a SFC which p roduces com mon-

    mode HF-voltage pulses together with a mainly capacitively

    conducting electrical loop which couples thc pulses

    inductively onto the shaft .

    Based on the improved understanding of the phenomenon,

    mod ifications have been implemented in a power plant w hich

    were able to reduce the shaft voltages by a factor of

    3.6.

    The key factor for the successful voltage reduction has been

    a design-change within the converter. Instead of using a

    single choke in the internal DC-loop in an asymmetric

    configuration, two chokes are arranged in a symmetrical

    way. The two chokes effectively block HF-pu lses and reduce

    EM1 considerably.

    VI REFERENCE

    [ I ] Amann C ., Reichert K., Joho R., Possedel Z.: SHAFT

    VOLTAGES IN GENERATORS WITH STATIC

    EXCITATION SYSTEMS

    -

    PROBLEMS AND

    SOLUTION, IEEE Trans. Energy Conversion, vol .

    3,

    no.

    2,

    j u n e

    1988.

    [2]

    Torlay

    I.

    E., Corenwinder C., Audoli A., Herigault J.,

    Foggia A.: Analysis of Shaft Voltages in Large

    Synchronous Generators, International Electric

    Machines and Drives Conference, 9-12 may 1999,

    Seattle, Washington, US.

    [3]

    Link P. J.: Minimizing Electric Bearing Currents in

    ASD Systems, IEEE Industry Application Magazine,

    JulyiAugust 1999, pp. 55 - 66.

    [4] Miitze A.: Bearing Cu rrents in Inverter-Fed AC-Motors,

    Dissertation University of Darmstadt,

    23.1.2004.

    [5]

    Cheng

    S. ,

    Lip0 T., Fitzgerald D.: Modeling of Motor

    Bearing Currents in PWM Inverter Drives, IEEE

    Trans. on Industry Applications, vol.

    32,

    no.

    2,

    march-

    April 1993

    [6]Hausberg V., Seinsch H. 0 : Kapazitive

    Lagerspannungen und Strome bei umrichtergespeisten

    Induktionsmaschinen, Electrical Engineering

    (82).

    pp,

    153-162, 2000.

    [7]

    Amman C. U.:Wellenspannungen in grossen, statisch

    erregten Turbogeneratoren, Dissertation ETH-Zurich,

    1988.

    [8] VDE

    0141/5.76:

    ,,Bestimmungen f~ Erdungen in

    Wechselstromanlagen

    f

    Nennspannung, VDE Verlag

    [9] AIEE Co mm ittee Report: ,,Voltage gradients through

    the ground under fault condition, Trans. AIEE Part 111,

    (1958)

    pp.

    669-692.

    [IO]

    Hausberg V., Seinsch H. 0 : Kapazitive

    Lagerspannungen und Strljme bei u mrichtergespeisten

    Induktionsmaschinen, Electrical Engineering

    (82).

    pp.

    153-162, 2000.

    4370