Joint Standard Document between Energex and Ergon Energy ENERGEX Limited ABN 40 078 849 055 Ergon Energy Corporation Limited ABN 50 087 646 062 Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon Energy and Energex internet site www.ergon.com.au and www.energex.com.au to obtain the latest version. Approver Ana Smith De Perez General Manager Asset Standards Energy Queensland If RPEQ sign off required insert details below. Certified Person name and Position Registration Number Carmelo Noel Manager Line Standards 8802 Abstract: This standard provides information concerning the format, placement and physical details of site identification labels, operational identifier labels, equipment labels, cable destination labels, and signage within the Low Voltage (LV) distribution network. It is intended to assist designers and construction staff in specifying, ordering and fitting labels. Keywords: Label, Labelling, signage, identifier, LV network

Transcript of Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this...

Page 1: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Joint Standard Document between Energex and Ergon Energy

ENERGEX Limited ABN 40 078 849 055 Ergon Energy Corporation Limited ABN 50 087 646 062

Standard for Network Labelling and

Signage

If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Energy and Energex internet site www.ergon.com.au and www.energex.com.au to obtain the latest

version.

Approver

Ana Smith De Perez

General Manager Asset Standards

Energy Queensland

If RPEQ sign off required insert details below.

Certified Person name and Position Registration Number

Carmelo Noel

Manager Line Standards

8802

Abstract: This standard provides information concerning the format, placement and physical details

of site identification labels, operational identifier labels, equipment labels, cable destination labels,

and signage within the Low Voltage (LV) distribution network. It is intended to assist designers and

construction staff in specifying, ordering and fitting labels.

Keywords: Label, Labelling, signage, identifier, LV network

Page 2: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Standard for LV Network Labelling and

Signage

Check this is the latest version before use i EX 01969 Ver 1

EE STNW1176 Ver 1

Joint Standard Document between Energex and Ergon Energy

Energex Limited ABN 40 078 849 055 Ergon Energy Corporation Limited ABN 50 087 646 062

For definitive document version and control detail, please refer to the information stored on the

Process Zone.

Revision history

Revision date Version

number

Author Description of change/revision

April 2019 1 Adam Bletchly Original Issue.

Document approvals

Name Position title Signature Date

Peter Price Head of Corporate Strategy & Executive

General Manager Asset Safety &

Performance

<dd/mm/yy>

Ana Smith De Perez General Manager Asset Standards <dd/mm/yy>

Stakeholders / distribution list

Name Title Role

Russ Christ Regional Manager Southern

Networks

Endorse

Keegan Oliver Regional Manager Northern

Networks

Endorse

Steven Lynch Regional Manager South East

Networks

Endorse

Adam Bletchly UG & PL Standards Engineer Endorse

Sean Mc Guinness Manager Lines Design &

Engineering

Endorse

Jeff Shears Manager Lifecycle Engineering

Lines

Endorse

Page 3: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Standard for LV Network Labelling and

Signage

Check this is the latest version before use ii EX 01969 Ver 1

EE STNW1176 Ver 1

Joint Standard Document between Energex and Ergon Energy

Energex Limited ABN 40 078 849 055 Ergon Energy Corporation Limited ABN 50 087 646 062

Table of Contents

1 Overview .............................................................................................................................. 1

1.1 Purpose ...................................................................................................................... 1

1.2 Scope ......................................................................................................................... 1

2 References ........................................................................................................................... 1

2.1 Energex controlled documents .................................................................................... 1

2.2 Ergon Energy controlled documents ........................................................................... 1

2.3 Other documents ........................................................................................................ 2

2.3.1 Australian and Australian/New Zealand Standards ........................................ 2

3 Legislation, regulations, rules, and codes ............................................................................. 2

4 Definitions, acronyms, and abbreviations.............................................................................. 2

4.1 Definitions ................................................................................................................... 2

4.2 Acronyms and abbreviations ....................................................................................... 2

5 Types and Purpose of Labelling ........................................................................................... 4

5.1 HV Distribution Equipment Labels ............................................................................... 5

5.1.1 Ergon Energy ................................................................................................ 5

5.1.2 Energex ......................................................................................................... 5

5.2 Low Voltage Equipment .............................................................................................. 6

5.2.1 Cable Destination .......................................................................................... 6

5.2.2 Site ID ........................................................................................................... 6

6 Label Content ....................................................................................................................... 6

6.1 Cable Destination ........................................................................................................ 6

6.2 Site Identification ......................................................................................................... 7

6.2.1 Ergon ............................................................................................................ 7

6.2.2 Energex ......................................................................................................... 7

6.3 Component and Operational Labels for HV Apparatus ................................................ 9

6.3.1 Ergon Energy ................................................................................................ 9

6.3.2 Energex ......................................................................................................... 9

7 Physical Details .................................................................................................................. 10

7.1 Materials ................................................................................................................... 10

7.2 Colours ..................................................................................................................... 10

7.3 Standard Dimensions ................................................................................................ 11

7.4 Method of Fixing ....................................................................................................... 11

7.4.1 Indoor Application ........................................................................................ 12

7.4.2 Outdoor Application ..................................................................................... 12

Page 4: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Standard for LV Network Labelling and

Signage

Check this is the latest version before use Page 1 EX 01969 Ver 1

EE STNW1176 Ver 1

Joint Standard Document between Energex and Ergon Energy

Energex Limited ABN 40 078 849 055 Ergon Energy Corporation Limited ABN 50 087 646 062

1 Overview

1.1 Purpose

The purpose of this Standard is to provide information concerning the format, placement and

physical details of cable destination labels and signage within the Low Voltage network.

This Standard is intended to ensure safe and secure operation of a Distributor’s Low Voltage

Distribution System.

1.2 Scope

This standard applies to the Energy Queensland Limited distribution network outside of major

substations.

This standard provides information concerning the format, placement and physical details of site

identification labels, operational identifier labels, equipment labels, cable destination labels and

signage within the distribution network. It is intended to assist designers and construction staff in

specifying, ordering and fitting labels.

Accuracy and consistency of labels is essential as this affects the safety of switching operators,

construction and maintenance staff. Therefore, compliance with this standard is mandatory. It is

not intended that this Standard be retrospective however where labelling and signage is updated it

shall be to this standard where possible.

2 References

2.1 Energex controlled documents

A copy of the latest version of this Energex Standard may be obtained from the following website:

https://www.energex.com.au

Document number or location

(if applicable)

Document name Document type

00305 Energex Underground

Distribution Construction Manual

Manual

4920 Energex Overhead Distribution

Construction Manual

Manual

00796 Queensland Public Lighting

Construction Manual

Manual

2.2 Ergon Energy controlled documents

A copy of the latest version of this Ergon Energy Standard may be obtained from the following

website:

https://www.ergon.com.au

Page 5: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Standard for LV Network Labelling and

Signage

Check this is the latest version before use Page 2 EX 01969 Ver 1

EE STNW1176 Ver 1

Joint Standard Document between Energex and Ergon Energy

Energex Limited ABN 40 078 849 055 Ergon Energy Corporation Limited ABN 50 087 646 062

Document number or location

(if applicable)

Document name Document type

Ergon Energy Underground

Construction Manual

Standard

Ergon Energy Overhead

Construction Manual

Standard

Queensland Public Lighting Standard

STNW1172 Standard for Network

Operational Identification and

Naming of Field Switching

Devices

Standard

STNW1173 Standard for Network

Operational Identification and

Naming Guideline Feeders

Standard

2.3 Other documents

Australian and Australian/New Zealand Standards 2.3.1

Document number Document name Document type

AS/NZS 1734 Aluminium and Aluminium Alloys – Flat Sheet,

Coiled Sheet and Plate

AU/NZ Joint Standard

3 Legislation, regulations, rules, and codes

Legislation, regulations, rules, and codes

Nil

4 Definitions, acronyms, and abbreviations

4.1 Definitions

For the purposes of this standard, the following definitions apply:

Term Definition

Shall Indicates a mandatory requirement

Should or may Indicates a recommendation

4.2 Acronyms and abbreviations

The following abbreviations and acronyms appear in this standard.

Abbreviation,

Acronyms

Definition

LV Low Voltage

Page 6: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Standard for LV Network Labelling and

Signage

Check this is the latest version before use Page 3 EX 01969 Ver 1

EE STNW1176 Ver 1

Joint Standard Document between Energex and Ergon Energy

Energex Limited ABN 40 078 849 055 Ergon Energy Corporation Limited ABN 50 087 646 062

Abbreviation,

Acronyms

Definition

ABS Air Break Switch

BW or BWB Black background, White lettering

CB Circuit Breaker

CFI Cable Fault Indicator

C/I Commercial / Industrial

DB Disconnect Box

DFD Direct Fuse Direct

EDO Expulsion Dropout Fuse

ES Earth Switch

FU Fuse Unit

GT Ground Transformer

H ‘H’ Frame Structure

HV High Voltage

ID Identification

LHS Left Hand Side

LP Link Pillar

LTS Load Transfer Switch

OH Overhead

P Pole Site Prefix

PMR Pole Mounted Recloser

PMT Padmount Transformer (Cubicle or Kiosk Substation)

PT Pole Transformer

RHS Right Hand Side

RM or RMU Ring Main Unit

RW (or RWR) Red Background, White lettering

SF or SFU Switch Fuse (Unit)

SC Cubicle Substation (PMT)

SG Ground Substation

SL Streetlight

SP Pole Substation

SR Voltage Regulator

SS Switchgear Substation

Page 7: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Standard for LV Network Labelling and

Signage

Check this is the latest version before use Page 4 EX 01969 Ver 1

EE STNW1176 Ver 1

Joint Standard Document between Energex and Ergon Energy

Energex Limited ABN 40 078 849 055 Ergon Energy Corporation Limited ABN 50 087 646 062

Abbreviation,

Acronyms

Definition

SWBD Switchboard

T Tower prefix

TR Transformer

U Underground site prefix (pillar, cable joint, disconnect box)

UG Underground

URD Underground Residential Development

WB (or WBW) White Background, Black lettering

X HV Switch Prefix (ABS, PMR, Sectionaliser, LTS, etc.)

5 Types and Purpose of Labelling

Labelling assists with the safe operation of the distribution network by clearly identifying electrical

plant items and what they are connected to, these include:

Type Purpose

Site Identification Labels

(e.g. SC65789 on a PMT,

P788510 on a pole)

These identify the geographical site within the network. There are various site

types depending upon the equipment installed.

Site Component Labels

(e.g.TR2 for the second

transformer within a GT

station)

In switchgear substations, and in GT stations where there is more component of

a particular type, component identifiers are used to uniquely specify the various

items of plant.

Operational Labels

(e.g. IS38 and SF29 on

the front panel of an

RMU)

Operational labelling is primarily to assist switching operators to identify HV

equipment and validate switching requirements. All operable points on the HV

network are assigned an identifier with which they must be labelled. The

combination of Site ID and Operational Identifier (e.g. SG3887/IS11) is unique

within the Energex network. Switches on the LV network are not assigned

operational identifiers.

Cable Destination Labels

(e.g. TO P587891

JONES RD on a RMU

cable box)

Cable destination labelling is placed at cable terminations, or at the switches

associated with cable terminations. These labels show where remote ends of

cables terminate, or what circuits will be affected when a switching point is

operated. Unlike the overhead network, underground mains cannot readily be

traced without access to records. Destination labels help repair crews to trace

cables and locate any faults.

Feeder Labels

(e.g. EMP2 on a RMU

cable box above cable

destination label)

These supplement cable destination labels. They identify 11 kV feeders

emanating from a major (switchgear) substation. They are placed at the first

cable termination along the feeder outside the substation, immediately above

the cable destination label.

Operating Sketch Small single line diagrams are affixed to RMUs showing their internal

configuration - the isolators, switch/fuse tee-offs, earth switches and internal bus

linkage. (These diagrams are provided by the manufacturer for certain items of

equipment.

Page 8: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Standard for LV Network Labelling and

Signage

Check this is the latest version before use Page 5 EX 01969 Ver 1

EE STNW1176 Ver 1

Joint Standard Document between Energex and Ergon Energy

Energex Limited ABN 40 078 849 055 Ergon Energy Corporation Limited ABN 50 087 646 062

Type Purpose

Other Signage and

Labels

These include Switch Description labels (e.g. Earth Switch, Isolator or Earth

Switch for IS1129), Fuse Compartment labels, Phase Identification labels (e.g.

UVW to CBA), Separate HV & LV Earthing signs and Danger signs. Some of

these labels are fitted by the manufacturer, others by the installation crew.

Some of these signs are standard stores items.

5.1 HV Distribution Equipment Labels

Ergon Energy 5.1.1

For Ergon Energy distribution area, refer Standard for Network Operational Identification and

Naming of Field Switching Devices, STNW1172 and the relevant construction manual e.g.

Overhead or Underground.

Energex 5.1.2

5.1.2.1 Padmount Substations

These are assigned a Site ID – SCxxxxx. The RMU or SFU (CFC or DFD units) within the

padmount is not assigned any component ID. However, the switching points within the unit will be

assigned HV Operational IDs – ISxx, SFxx.

Unused circuits on an RMU or SFU need not be labelled “SPARE”

5.1.2.2 Ground Transformers Stations

These are assigned a Site ID – SGxxxxx. RMUs and transformers within the substation enclosure

carry component labels, e.g. RM1, TR2.

Ground Transformer cable boxes are fitted with cable destination labels if there is more than one

transformer at the site or the transformer is remote from the RMU controlling it.

5.1.2.3 Free Standing RMUs, Switch/Fuse Units or Three-way Isolators

These are assigned a Site ID - Xyyyyy. In older sites, a RMU station may be allocated the same

designation as that of the ground transformer station it controls.

RMUs are usually fitted with operational identifiers, cable destination and site sketch labels. The

other types of labels described are also fitted where applicable.

Switch/Fuse Units (SFU) are labelled similarly to RMUs. However, whereas the switch/fuse is

labelled “TO TRANSFORMER” on a RMU, the HV cable destination is used on a SFU, e.g. TO

SMITH RD P894332.

5.1.2.4 Poles

Poles shall be fitted with site ID labels and cable destination labels where cables terminate on the

pole (optional for minor/service cables).

Page 9: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Standard for LV Network Labelling and

Signage

Check this is the latest version before use Page 6 EX 01969 Ver 1

EE STNW1176 Ver 1

Joint Standard Document between Energex and Ergon Energy

Energex Limited ABN 40 078 849 055 Ergon Energy Corporation Limited ABN 50 087 646 062

5.1.2.5 Overhead Equipment

Overhead Equipment such as pole-mounted reclosers, sectionalisers and load transfer switches do not require destination labelling. However, these are fitted with Site ID labels and, where applicable, feeder labels.

5.1.2.6 Underground Cable Joints

There is no requirement to physically label underground cable joints with Site ID, although the technique shown for LV disconnect boxes (refer drawing 6454-A4) may be used.

5.2 Low Voltage Equipment

Operational Labels and Feeder Labels are not used on the LV network. However Site ID and

Cable Destination labelling is very important. All LV switches on the underground network of

operational significance should be fitted with these types of labels.

Cable Destination 5.2.1

Mandatory for all LV distribution cables in the underground distribution network. It is not required

for service cables. Nevertheless, labels may be used on service cables where the destination is

obscure, e.g. down an easement.

Cable destination labels shall be fitted at the following locations:

LV switchboards – free-standing or within integrated padmount substations

Link pillars

Cable terminations on poles

Disconnect boxes

LV Feeder Pillars and Parallel Links (in older urban networks).

Unused circuits on LV switchboards need not be labelled “SPARE”.

Site ID 5.2.2

Normal service pillars, Cross-road pillars, Link pillars and sectionalising pillars shall be fitted with

Site ID labels. Link Pillars will be identified with a label ‘LP’ (refer Drawing 6828-A4).

There is no requirement to physically label underground cable joints with Site ID, although the

technique shown for LV disconnect boxes (refer Drawing 6454-A4) may be used.

6 Label Content

6.1 Cable Destination

Cable Destination shall have the following information as a minimum:

Commence with “To”

Street Address of the Destination Site. The street No. is recommended where there is more

than one site of this type within the street (expect for pole sites). For major buildings or places,

the premise name may be used instead of the street address.

Destination Site ID’s

Page 10: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Standard for LV Network Labelling and

Signage

Check this is the latest version before use Page 7 EX 01969 Ver 1

EE STNW1176 Ver 1

Joint Standard Document between Energex and Ergon Energy

Energex Limited ABN 40 078 849 055 Ergon Energy Corporation Limited ABN 50 087 646 062

Indication of any TEE connections within the circuit. Where a LV circuit has no ties to other

switchboards, Poles, Link Pillars etc. it is not necessary to list all far end service pillars/live

enbd joints.

Concluded with ‘DIRECT’ or ‘AND SERVICES’, depending on whether there are services off

the circuit, either from service pillars or service tee joints.

Other helpful information may be added at any point in the label. This is particularly important

where there is possibility of confusion between circuits. Information concerning circuit

direction/route may be supplied, e.g. JONES RD EAST, or BANKS RD RHS. (LHS and RHS of the

street is determined by looking outwards from the site and then following the ‘nose’ of the cable to

its destination.) Where two cables have a common source, a common destination and follow

similar routes, these should be designated ‘A’ and ‘B’.

Refer to Drawing 6370-A4 for cable destination label format.

Where a LV cable has no connections to link pillars, poles, disconnect boxes, LV switchboards etc.

(apart from its point of supply), the destination shown on the label shall be either:

the street or premise(s) supplied;

the direction of the outgoing cable (where other options are not suitable);

the street and site ID of the service pillar or live end joint furthest from the supply point

(excluding cross street pillars/pits fed by 16mm cable);

a combination of the above.

It is not necessary to name each street supplied or all pillars at the ends of radials. The aim is

merely to indicate the general area of supply and differentiate the cable from any others in the

vicinity.

Cable destination labelling is not required for service cables. Nevertheless, labels may be used

with these cables where the destination is obscure, e.g. down an easement.

6.2 Site Identification

A ‘site’ is a geographical location where the Distributor’s equipment is installed. A Site ID is

established at the time of installation to identify the asset within the network.

Ergon 6.2.1

For Ergon Energy distribution area, refer the relevant construction manual, e.g. Overhead or

Underground.

Energex 6.2.2

The Site ID consists of a one or two character (alphabetical) prefix, according to the type of site,

followed by a number or name. The type of site depends upon the type of equipment installed.

The types of sites are as shown below:

Page 11: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Standard for LV Network Labelling and

Signage

Check this is the latest version before use Page 8 EX 01969 Ver 1

EE STNW1176 Ver 1

Joint Standard Document between Energex and Ergon Energy

Energex Limited ABN 40 078 849 055 Ergon Energy Corporation Limited ABN 50 087 646 062

SS Switchgear Substation (with CBs)

SP Pole-mounted Substation (pole transformer)

SG Ground Substation (ground transformer, not including PMTs or freestanding RMU/FU stations

SC Padmount Transformer

SR Voltage Regulator

X HV Switch (includes ABS, PMRs, sectionalisers, LTSs and freestanding RMUs, FUs or 3-way

isolators)

P Pole

TW Tower

ST Structure, e.g. ‘H’ Frame

U Underground Network Component (pillar, cable joint or disconnect box)

L Street Light

CU Tariff 21 Light

W Rate 3 street light pole or consumer property pole (i.e. Non-Energex)

M Meter

A Aerial

RR Radio Repeater

MISC Miscellaneous

For example, a pole site may be P123456, a link pillar U98765 or a padmount substation

SC55443.

Overhead and underground sites do not need to have the site type prefix, e.g. P, TW, ST or U,

fitted to the item. Only the number is attached, e.g. 123456. The prefix is included in the site ID

label only on SS, SP, SC, SG, SR or X sites.

For switchgear substations, the identifier following the SS prefix is a three-character entity which

relates to the substation name or location, e.g. SSCPL (Coopers Plains Zone Substation) or

SSAHD (Alexandra Headland Zone Substation).

Where there are multiple pieces of equipment at a site, the site type shall become that of the

predominant type of equipment. For example, a pole carrying a transformer shall be designated

SP123456, not P123456. Likewise an ABS pole shall be assigned an X site ID and not a P site.

SS

SP SG SC SR

X

P TW ST U

L CU W M A MISC RR

High Importance

Low Importance

Page 12: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Standard for LV Network Labelling and

Signage

Check this is the latest version before use Page 9 EX 01969 Ver 1

EE STNW1176 Ver 1

Joint Standard Document between Energex and Ergon Energy

Energex Limited ABN 40 078 849 055 Ergon Energy Corporation Limited ABN 50 087 646 062

For distribution substations, the site includes all plant within the substation enclosure (excluding

poles and cable joints, which are assigned independent site IDs). HV components within sites

shall themselves carry a component label where this is considered necessary or useful (refer

drawing 6815-A4).

However for switchgear substations (SS sites), a single site ID covers ALL enclosures within the

building or parcel of land.

Rate 3 streetlight (customer, owned, installed and operated) poles shall be labelled with a large 3

as well as the site ID.

Not all equipment assigned a site ID requires physical labelling on site, eg underground cable

joints would not normally be labelled to identify them.

Past practices, now discontinued, but still evident within the network include:

o pole site IDs not unique within Energex area. Many older pole IDs need to be combined

with a location code to uniquely specify an asset.

o assigning of ‘W’ sites to customer property poles. These are no longer numbered.

o poles carrying multiple site IDs – one for the pole, one for the street light, one for pole-

mounted equipment etc. These are now combined into a single site ID based upon the

predominant plant item.

o assignment of ‘A’ or ‘AB’ sites for ABSs. These are now assigned an ‘X’ prefix.

6.3 Component and Operational Labels for HV Apparatus

Ergon Energy 6.3.1

For Ergon Energy distribution area, refer Standard for Network Operational Identification and

Naming of Field Switching Devices, STNW1172 and the relevant construction manual e.g.

Overhead or Underground.

Energex 6.3.2

6.3.2.1 Component ID

HV components within sites shall themselves carry a component label where this is considered

necessary or useful.

Generally component labels shall be fitted to all plant within a switchgear substation, and

elsewhere to those components of which there is more than one item installed at a particular site.

For example, a GT station with two transformers and two RMUs would have components labelled

TR1, TR2, RM1 and RM2.

Component abbreviations include:

CB Circuit Breaker

RM Ring Main Unit or Three-way Isolator

TR Transformer

Page 13: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Standard for LV Network Labelling and

Signage

Check this is the latest version before use Page 10 EX 01969 Ver 1

EE STNW1176 Ver 1

Joint Standard Document between Energex and Ergon Energy

Energex Limited ABN 40 078 849 055 Ergon Energy Corporation Limited ABN 50 087 646 062

MU Metering Unit

FU Fuse Unit

A numeric identifier is appended to the abbreviation. For CBs this is normally a form of digit

number e.g. 2012, for other items this is normally a single digit, e.g. RM2.

6.3.2.2 Operational ID

Certain components, such as RMUs and CBs may comprise more than one operable point. For

example, an RMU typically includes two isolators, one switch/fuse and three earth switches. A

circuit breaker may have an internal earth switch. Each operable point is assigned an operational

ID and labelled accordingly.

Operational abbreviations include:

ES Earth Switch

IS Isolator

SF Switch Fuse

A two-digit number (ranging from 11 to 99) is appended to the prefix, e.g. IS38. The number is

somewhat arbitrary. It is selected so as to be different from any other isolators or switch fuses on

nearby plant or on plant to which cables emanating from the device connect.

7 Physical Details

7.1 Materials

For indoor equipment or labels that are not exposed to the environment, materials shall be UV 2

ply laminated acrylic (Gravoply Ultra or equivalent).

For outdoor equipment, 5251 H38 1.6mm thick anodised aluminium plate to AS 1734.

No other types of labelling material can be used e.g. Dymo tape is not acceptable as a labelling

material.

Site ID labels vary according to the type of equipment to which they are attached. For timber

poles these are stamped aluminium; for most other applications they are adhesive vinyl. Full

details are provided in the equipment-specific drawings that follow.

7.2 Colours

Interior labels for distribution switchgear use the following colours:

HV Cable Destination: BLACK background, WHITE lettering (BW)

LV Cable Destination: WHITE background, Black lettering (WB)

Operational ID: WHITE background, Black lettering (WB)

Feeder ID: BLACK background, WHITE lettering (BW)

Page 14: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Standard for LV Network Labelling and

Signage

Check this is the latest version before use Page 11 EX 01969 Ver 1

EE STNW1176 Ver 1

Joint Standard Document between Energex and Ergon Energy

Energex Limited ABN 40 078 849 055 Ergon Energy Corporation Limited ABN 50 087 646 062

Operating Sketch: RED background, WHITE lettering (RW)

RMU, MU, 3way Isolator: WHITE background, BLACK lettering (WB)

Exterior labels have SILVER lettering etched into the aluminium kolana bronze, red, green, or

blue background, and BLACK lettering etched into aluminium yellow or white background.

Note

The colours may different from those used for HV Equipment within switchgear substations (SS sites).

7.3 Standard Dimensions

Equipment-specific drawings should be consulted where possible for dimensions. These may

be found in the High Voltage and Low Voltage Equipment. The following dimensions are

provided as a guide only.

Equipment Description Label Type Label Size Text Height

RMU1 Site ID 150 x 50 20

Operational ID 150 x 50 20

Feeder ID 250 x 40 20

Cable Destination 250 x 40 10 (or to suit)

Operating Sketch 100 x 100 5 (or to suit)

Transformer Cable Box Cable Destination 250 x 40 10 (or to suit)

LV Switchboard – Circuit

Isolators

Cable Destination 80 x 35 5 (or to suit)

LV Switchboard –

Transformer Isolator

Cable Destination 80 x 35 6

Link Pillars – current style Cable Destination 150 x 50 5 (or to suit)

Link Pillars – old style Cable Destination 200 x 50 5 (or to suit)

Service Pillars Pillar ID 190 x 50 50mm Letters

Disconnect Boxes Cable Destination 160 x 40 5 (or to suit)

LV Parallel Links Cable Destination 80 x 35 5 (or to suit)

LV Feeder Pillars Cable Destination 80 x 35 5 (or to suit)

Pole Cable Destination 300 x 100 12 (or to suit)

7.4 Method of Fixing

Separate attachment methods/instructions for some types of labels may be located on individual

drawings; these should be referred to as well as the following instructions.

Labels shall be affixed to timber poles with galvanized clouts. On concrete poles ‘band-it’ straps

shall be used.

Elsewhere the equipment surface shall be thoroughly cleaned prior to affixing the label to ensure it

remains in place for the life of the label.

1 Dimension for, Krone and Hazemeyer RMUs (which types are used in integrated padmount substation)

differ from that tabulated above.

Page 15: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Standard for LV Network Labelling and

Signage

Check this is the latest version before use Page 12 EX 01969 Ver 1

EE STNW1176 Ver 1

Joint Standard Document between Energex and Ergon Energy

Energex Limited ABN 40 078 849 055 Ergon Energy Corporation Limited ABN 50 087 646 062

Indoor Application 7.4.1

For the South East (Energex) region use 3M brand 4945 double-sided adhesive tape (Stock

Code 14738). In the Northern and Southern (Ergon) regions use 3M branded RP45F double-

sided adhesive tape (Stock Code 2461127). The amount to be used will depend upon the label

dimensions. Generally, two or three strips are sufficient.

Outdoor Application 7.4.2

Use Silastic sealing compound or Maxbond type contact glue. If it is necessary to use

mechanical fasteners, ensure that these are made from a non-corrosive material such as brass

or stainless steel and seal any holes that are drilled with silicone.

Page 16: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Standard for Network Labelling and Signage

11KV NETWORK LABELLING Go to SECTION INDEX Back to MAIN INDEX

Page 17: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

THE ISOLATOR N

UMBER O

R T

ERMINAL,

WHERE A

PPLICABLE E

G R

MU ISOLATOR,

SWITCH F

USE U

NIT, CIRCUIT B

REAKER

NO, CABLE P

OSITION (FRONT O

R B

ACK,

CABLE B

OX A

/B/C E

TC).

KL

ELEMENTS 'B', 'F' AND 'K'

STREET A

DDRESS O

F T

HE D

ESTINATION S

ITE.

THE S

TREET N

o. IS R

EQUIRED W

HERE T

HERE IS M

ORE T

HAN

ONE S

ITE O

F T

HIS T

YPE W

ITHIN T

HE S

TREET, EXCEPT F

OR

POLE S

ITES.

FOR M

AJO

R B

UILDINGS O

R P

LACES, THE P

REMISE N

AME M

AY

BE U

SED INSTEAD O

F T

HE S

TREET A

DDRESS.

THESE E

LEMENTS A

RE N

OT R

EQUIRED W

HEN D

ESTINATION IS

WITHIN S

AME S

ITE. DESTINATION L

ABEL

ELEMENT 'A'

FOR R

ADIAL C

ABLES U

SE "

TO"

FOR T

EED C

ABLES U

SE "

TEE"

SCxxxxx

ELEMENT 'G'

COMPONENT ID T

O B

E U

SED O

NLY

WHERE T

HERE A

RE M

ULTIPLE R

MUS

AT T

HE S

AME S

ITE.

SMITH R

D x

xx

ANZ B

ANK

A TEE

F

BC

G RMx

H

SGxxxxx

THE D

ESTINATION S

ITE ID. THE O

RDER IN W

HICH D

ESTINATION S

ITES

ARE P

OSITIONED IN T

HE L

ABEL W

ILL B

E IN T

HE F

OLLOWING H

EIRARCHY:

1.SWITCHGEAR S

UBSTATION S

ITES e

.g. SSxxx.

2.DI STRIBUTION S

UBSTATION S

ITES e

.g. SGxxxxx, SCxxxxx.

3.POLE S

ITES e

.g. Pxxxxxx.

4.LIVE E

ND J

OINT (POTHEAD) e.g. Uxxxxx.

ELEMENTS 'C', 'H' A

ND 'L' ELEMENTS 'D' AND 'I'

DE /J

ISxx

I

ISxx

/

WHERE T

HERE M

AY B

E C

ONFUSION IDENTIFYING T

HE C

ABLE D

IRECTION, ADDITIONAL INFORMATION

MAY B

E A

DDED T

O T

HE A

BOVE P

ARAMETERS, eg. SMITH R

D 3

5 S

C456321

VIA E

ASEMENT.

Pxxxxxx

JONES R

D

ELEMENTS 'E' AND 'J'

INDICATES A

'TEE' CONNECTION IN T

HE

CABLE.

NETWORK LABELLING & SIGNAGE11kV NETWORK EXAMPLESCABLE DESTINATION LABELS

6369-A4 C

UNCONTROLLED COPY

Page 18: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

MASTER SELECTION DIAGRAM FOR 11 kV EXAMPLES

THE EXAMPLES GIVEN REPRESENT COMMON

SITUATIONS FOUND IN THE DISTRIBUTION NETWORK.

FOR COMPLICATED NETWORKS SUCH AS THREE

FEEDER RADIALS REFER TO THE SUBSTATION

DESIGN STANDARD.

C

JOINTCABLE

SFUPMTC

OH LINEUG CABLEPOLE

SYMBOL LEGEND

Pxxxxxx

GT RMU

EDO

SGyyyyy TR1

SGxxxxx

TR2

SCzzzzz

SGyyyyy

Pxxxxxx

SEE DOC.6377A4

SGxxxxx

EXAMPLE

RM1

SCwwwww

C

RM2

SWITCHGEARSUBSTATION SSxxx

SEE DOC.6813A4

EXAMPLE

Pxxxxxx

EXAMPLE

SEE DOC.6372A4

SGxxxxx

SCzzzzz

C

SGxxxxx

SCzzzzz

C

LIVE END JOINT

6373A4

EXAMPLE

SEE DOC.

Pxxxxxx

6374A4

EXAMPLE

SEE DOC.

SGyyyyy

TR3

SEE DOC.6376A4

EXAMPLE

RM3

SCxxxxxx

Pxxxxxx

C

EXAMPLE

6375A4SEE DOC.

REFER TO FOLLOWING

SHEETS FOR LABELLING

DETAILS.

NETWORK LABELLING & SIGNAGE11kV NETWORK EXAMPLESMASTER SELECTION DIAGRAM

6371-A4 C

J.TUNNEYK.GOSDEN

G.SAMUELS

CD.LloydA.TiekenD.Langley

UNCONTROLLED COPY

Page 19: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Pxxxxxx

JONES RD

SMITH R

D

BANKS RD

1

TO BANKS RDPxxxxxx

(CNR SMITH RD)

TO SSxxxCBxxxx

2

SUBSTATION TO POLE

SSxxx

EXAMPLE A

11 kV

XXXX FEEDER lD LABEL

G. WILLIS

Template Updated

B 7/5/03

A.Tieken

D.Langley

D.Lloyd

K. GOSDEN

J.TUNNEY

24/10/00

R.DOUGLAS

NTS

6372-A4 B

NETWORK LABELLING & SIGNAGE11kV NETWORK EXAMPLESEXAMPLE A

UNCONTROLLED COPY

Page 20: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

SUBSTATION TO RMU

BANKS RD

SMITH R

D

1JONES RD

(POTHEAD)LIVE END JOINT

2

3

5

6

7

1

TO BANKS RD 20(CNR SMITH RD)SGxxxxx ISxx

6

TO BANKS RD 20(CNR SMITH RD)SGxxxxx ISyy

TO BANKS RD 35SCzzzzz ISzz

3

TOTRANSFORMER

4

TO BANKS RDLHS Uxxxxx

5

TOTRANSFORMER

7TO SSxxxCBxxxx

2

EXAMPLE B

11 kV

SGxxxxx

No.20

Uxxxxx

SCzzzzzNo.35

XXXX FEEDER ID LABEL

RMU TO RMU

RMU TO LIVE END JOINT

NOTE: Where Live End Joint has no Site ID allocated

substitute <Street Address> "LIVE END JOINT"

for "Uxxxxx".

G. WILLIS

Freestanding RMU site added

C 6/12/06

R.Krosch

B.Somers

K.Nuttall

B.Brunsman

R.Krosch

24/10/00

R.DOUGLAS

NTS

6373-A4 C

NETWORK LABELLING & SIGNAGE11kV NETWORK EXAMPLES

EXAMPLE B

XyyyyySGxxxxxSCxxxxx

UNCONTROLLED COPY

Page 21: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

SUBSTATION TO RMU

BANKS RD

SMITH R

D1

JONES RD

2

3

4

6

1

TO BANKS RD 20(CNR SMITH RD)SGxxxxx ISxx

TO

TRANSFORMER

4

TO SSxxx

CBxxxx

2

EXAMPLE C

SSxxx

11 kV

SGxxxxx

No.20

SCzzzzzNo.35

XXXX FEEDER ID LABEL

RMU TO DFD UNIT

Pxxxxxx

5

3

TEE BANKS RD 35SCzzzzz SFyy /

BANKS RD Pxxxxx

6

TEE BANKS RD 20 SGxxxxx ISuu /

BANKS RD Pxxxxx

altered. G. WILLIS

DFD Labelling method

C 22/03/2004

A. TIEKEN

D. LANGLEY

C. LEE

K. GOSDEN

J.TUNNEY

24/10/00

R.DOUGLAS

NTS

6374-A4 C

NETWORK LABELLING & SIGNAGE11kV NETWORK EXAMPLES

EXAMPLE C

7

TEE BANKS RD 20SGxxxxx ISuu /

BANKS RD Pxxxxx

7

See DWG

8356-a4

5

BANKS RD 20 SGxxxxx ISuu

See DWG

7453-a4

NOTE

1. DFD units have no isolators for incoming cables. The incoming

cables terminate directly on the bus. Only the Transformer

supplied from the switch fuse can be isolated by this unit. DFD

units are treated in a similar manner to TEEs.

DFD UNIT TO POLE

BANKS RD 35 SCzzzzz SFyy /11kV CABLE TEE

UNCONTROLLED COPY

Page 22: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

SUBSTATION TO FU WITH TEE TO POLE

JONES RD

BANKS RD

EXAMPLE D

SCxxxxx

XXXX FEEDER ID LABEL3

TEE SSxxx CBxxxx /SMITH RD 35SCxxxxx SFxx

XXXX FEEDER ID LABEL2

TEE SSxxx CBxxxx /BANKS RD Pxxxxxx

Pxxxxxx

C

SMITH R

D

1

TEE SMITH RD 35SCxxxxx SFxx /

BANKS RD Pxxxxxx

11 kV

No.35

NETWORK LABELLING & SIGNAGE11kV NETWORK EXAMPLESEXAMPLE D

6375-A4 C

UNCONTROLLED COPY

Page 23: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

SUBSTATION TO MULTI-RMU GT SITE

11 kV EXAMPLE E

BANKS RD

SMITH R

D

1

JONES RD

(11KV FEEDER COMPRISES TWO CABLES)

TR1

RM1 RM2

TR2

RM3

THE RMUs ARE INSTALLED IN THE SAME

SUBSTATION ENCLOSURE AS TR1 AND TR2 AND

HAVE THE SAME SITE ID. TR3 IS INSTALLED IN A

REMOTE SUBSTATION ENCLOSURE BUT ON THE

SAME PROPERTY AND HAS A DIFFERENT SITE ID.

THE TWO CABLES EMANATE FROM A COMMON CB

WITHIN THE ZONE SUBSTATION.

2

SGxxxxx

SSxxx

7

4

5

6 10

9

8

13

12

3 11

No35

1

CABLE 'A' TO BANKS RD35 RM1 SGxxxxx ISuu

3

CABLE 'A' TO SSxxxCBxxxx

2

CABLE 'B' TO BANKS RD 35 RM3 SGxxxxx ISzz

4

TO RM2ISww

5

TOTR1

6

TO RM1SFpp

9

TOTR2

8

TO RM3ISyy

7

TO RM1ISvv

10

TO RM2SFqq

13

TO BANKS RD 35SGyyyyy

12

CABLE 'B' TO SSxxxCBxxxx

11

TO RM2ISxx

14

TO BANKS RD 35 RM3SGxxxxx SFrr

XXXX FEEDER ID LABEL

XXXX FEEDER ID LABEL

14

SGyyyyy

G. WILLIS

Template Updated

B 7/5/03

A.Tieken

D.Langley

D.Lloyd

K. GOSDEN

J.TUNNEY

24/10/00

R.DOUGLAS

NTS

6376-A4 B

NETWORK LABELLING & SIGNAGE11kV NETWORK EXAMPLES

EXAMPLE E

UNCONTROLLED COPY

Page 24: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

SUBSTATION TO RMU WITH TEE TO FU

9

No.35

TOTRANSFORMER

6

10

TO BANKS RD 35SCzzzzz ISvv

11

3

TEE BANKS RD 35SCzzzzz ISzz / BANKSRD 40 SGyyyyy SFyy

9

TEE BANKS RD 40SGyyyyy SFyy / SMITHRD 24 SGxxxxx ISuu

TOTRANSFORMER

10

2

No.24

SMITH R

D

Pxxxxxx

11

3

TO BANKS RDPxxxxxx

8

8

SCzzzzz

BANKS RD

SGxxxxx

JONES RD

XXXX FEEDER ID LABEL

& RMU TO POLE

TO SSxxxCBxxxx

2

1

SSxxx

TO SMITH RD 24SGxxxxx ISxx

1

11 kV

EXAMPLE F

7

TEE BANKS RD 35SCzzzzz ISzz / SMITHRD 24 SGxxxxx ISuu

No.40

7

SGyyyyy

6

NETWORK LABELLING & SIGNAGE11kV NETWORK EXAMPLES

EXAMPLE F

6377-A4 C

NTS

R. DOUGLAS

24-10-00

J.TUNNEY

K.GOSDEN

G. SAMUELS

C 7/5/03

D.Lloyd

A.Tieken

D.Langley

Template Updated

UNCONTROLLED COPY

Page 25: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

5

TO BANKS RD Pxxxxxx

6

TO JONES RDSCwwwww ISyy

8

TO BANKS RDPyyyyy

7

TO BANKS RDSGyyyyy

BANKS R

D

11 kV EXAMPLE G

1

TO SMITH RD SCvvvvvBACK CABLE

2

TO SCxxx CBxxxx

JONES RD

SMITH R

D

SSxxx

1

2 No. 35

SCvvvvv

C

3

5

4 C

SCwwwww

4

TO SMITH RDSCwwwww FRONT CABLE

3

TO JONES RDSCwwwww ISxx

RMU TO POLE & POLE TO GT

7

Pyyyyyy

SGyyyyy

8

Pxxxxxx

6

SUBSTATION TO RMU

NETWORK LABELLING & SIGNAGE11kV NETWORK EXAMPLES

EXAMPLE G

6813-A4 C

NTS

R.DOUGLAS

24-10-00

J.TUNNEY

K.GOSDEN

G.WILLIS

C 7/5/03

D.Lloyd

A.Tieken

D.Langley

Template Updated

RDU removed

EDO references removed

UNCONTROLLED COPY

Page 26: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

HIGH VOLTAGE EQUIPMENT Go to SECTION INDEX Back to MAIN INDEX

Standard for Network Labelling and Signage

Page 27: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

DESTINATION

CABLE

BOX

CABLE

6BW

200x40

LETTER

SIZE

20

20

BW

200x40

BOX

CABLE

WB

170x50

IDENTIFICATION

ISIS

SF

IDENTIFICATION

FEEDER

ISOLATOR

ISOLATOR

NEAR

SIZE

LABEL

COLOUR

LABEL

LABEL INFORMATION

LOCATION

LABEL

DESCRIPTION

LABEL

WU

V

OPERATIONAL ISOLATOR

IDENTIFICATION

eg. IS57 o

r SF58

FEEDER IDENTIFICATION

eg. EMP2

DESTINATION L

ABEL

eg. LONDON 7

6

UW

VU

WV

VW

U

NOTES

1. Labels to be made from GRAVOPLY II (1.5mm) or similar.

IS99

150

10

25

11∅

170

50

PROJECT No.

STATION No.

LOCATION

FOR F

USE U

NITS U

SE

THIS C

OLUMN O

NLY

RMU

FUSE U

NIT

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

ABB ANDELECT RMU / FU

G. SAMUELS

Template Updated

B 8/5/03

A.Tieken

D.Langley

D.Lloyd

K. GOSDEN

J.TUNNEY

24/10/00

R.DOUGLAS

NTS

6395-A4 B

NETWORK LABELLING & SIGNAGEHV EQUIPMENT

ORDER FORM

ABB ANDELECT RMU/FU

UNCONTROLLED COPY

Page 28: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

NEAR

ISOLATOR

1. Labels to be made from GRAVOPLY II (1.5mm) or

similar. If the RMU is installed outdoors then the

labels are tobe made from KOLANA BRONZE (1.2mm)

2. The Feeder Identification Label is only required

if the RMU is the first termination outside a

PROJECT No.

STATION No.

Thick Anodised Aluminium Plate.

NOTES

LOCATION

COLOUR

LABEL

LABEL

SIZE

150x50

WB

LETTER

SIZE

20

COMPONENT IDENTIFICATION

OPERATIONAL ISOLATOR

eg. IS57 o

r FU58

FEEDER IDENTIFICATION

DESTINATION L

ABEL

LABEL INFORMATION

RMU

IDENTIFICATION

eg. RM1

eg. LONDON 7

6

eg. EMP2

FUSE U

NIT

LABEL

LOCATION

FRONT

LABEL

DESCRIPTION

IDENTIFICATION

RMU

170x50

250x40

WB

BW

250x40

BW

20

20 6

FOR F

USE U

NITS U

SE

THIS C

OLUMN O

NLY

ISSF

ISIS/SF

ISOLATOR

CABLE

BOX

CABLE

BOX

IDENTIFICATION

IDENTIFICATION

FEEDER

DESTINATION

CABLE

ABB ANDELECT RMU / FU - FREESTANDING

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

ABB ANDELECT RMU/FU FREESTANDING

ORDER FORM

6396-A4 C

NTS

R.DOUGLAS

24-10-00

J.TUNNEY

K.GOSDEN

G.SAMUELS

C 8/5/03

D.Lloyd

A.Tieken

D.Langley

Template Updated

Zone Substation.

UNCONTROLLED COPY

Page 29: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

1. Labels to be made from GRAVOPLY II (1.5mm) or similar.

NOTES

FEEDER

eg. RM1

eg. +1A

B

IDENTIFICATION

COMPONENT

DESIGN IDENTIFICATION

150x50

LABEL

SIZE

50x20

100x40

100x30

LABEL INFORMATION

FRONT V

IEW

ISIS

SF

WB

20

LETTER

SIZE

COLOUR

LABEL

BLUE W

10

GW

WB

8 15IS

SF

eg. EMP2

eg. EARTH S

WITCH F

OR IS57

FEEDER IDENTIFICATION

EARTH S

WITCH

DESCRIPTION

eg. LONDON 7

6

eg. IS57 o

r FU58

IDENTIFICATION

OPERATIONAL ISOLATOR

DESTINATION L

ABEL

SIDE V

IEW

IS

RMU

LOCATION

LABEL

DESCRIPTION

LABEL

NEAR

FRONT

FRONT

NEAR

EARTH S

W

ISOLATOR

EARTH S

WITCH

IDENTIFICATION

IDENTIFICATION

DESIGN

DESCRITION

IDENTIFICATION

ISOLATOR

150x50

150x50

150x50

20

BW

BW

10

BW

10

CABLE

FRONT

BOX

IDENTIFICATION

CABLE

DESTINATION

SIDE W

ALL

INSIDE

DESTINATION

CABLE

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

PROJECT No.

STATION No.

LOCATION

ALSTOM FLUROKIT M24 RMU

G. SAMUELS

Template Updated

B 8/5/03

A.Tieken

D.Langley

D.Lloyd

K. GOSDEN

J.TUNNEY

24/10/00

R.DOUGLAS

NTS

6397-A4 B

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

ORDER FORM

ALSTOM FLUROKIT M24 RMU

UNCONTROLLED COPY

Page 30: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

1. Labels to be made from GRAVOPLY II (1.5mm) or similar.

NOTES

LABEL

240x75

SIZE

LABEL INFORMATION

eg. 2012

eg. EMP2

eg. RM1

IDENTIFICATION

OPERATIONAL C

B

eg. LONDON 7

6

DESTINATION L

ABEL

COMPONENT

IDENTIFICATION

FEEDER IDENTIFICATION

LABEL

COLOUR

WB

LETTER

SIZE

50

FRONT V

IEW

SIDE V

IEW

LABEL

DESCRIPTION

IDENTIFICATION

LOCATION

LABEL

FRONT

CB

150x50

250x40

250x40

WB

BW

50

20

BW

10DESTINATION

CABLE

FEEDER

IDENTIFICATION

IDENTIFICATION

FRONT

FRONT

FRONT

RMU

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

PROJECT No.

STATION No.

LOCATION

BROWN BOVERI RGB12 SWITCHGEAR

G. SAMUELS

Template Updated

B 8/5/03

A.Tieken

D.Langley

D.Lloyd

K. GOSDEN

J.TUNNEY

24/10/00

R.DOUGLAS

NTS

6398-A4 B

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

ORDER FORM

BROWN BOVERI RGB12 SWITCHGEAR

UNCONTROLLED COPY

Page 31: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

NOTES

1. Labels to be made from GRAVOPLY II (1.5mm) or similar.

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

ISOLATOR

IDENTIFICATION

OPERATING S

KETCH

SUPPLIED W

ITH R

MU

COMPONENT

eg. RM1

COLOUR

LABEL

LABEL

150x50

SIZE

LETTER

WB

20

SIZE

FRONT V

IEW

LABEL INFORMATION

DESTINATION L

ABEL

OPERATIONAL ISOLATOR

FEEDER IDENTIFICATION

eg. EMP2

eg. IS57 o

r FU58

IDENTIFICATION

eg. LONDON 7

6

SIDE V

IEW

LOCATION

FRONT

LABEL

LABEL

DESCRIPTION

RMU

150x50

250x40

250x40

WB

BW

20

20

BW

10

SF

ISIS

IS/SF

CABLE

FRONT

CABLE

BOX

BOX

FEEDER

DESTINATION

CABLE

If the RMU is installed outdoors then the labels are to

be made from KOLANA BRONZE (1.2mm) Thick Anodised

Aluminium Plate.

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

PROJECT No.

STATION No.

LOCATION

GEC DDFC & DDFD RMU

G. SAMUELS

Template Updated

B 8/5/03

A.Tieken

D.Langley

D.Lloyd

K. GOSDEN

J.TUNNEY

24/10/00

R.DOUGLAS

NTS

6435-A4 B

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

ORDER FORM

GEC DDFC & DDFD RMU

UNCONTROLLED COPY

Page 32: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

DESTINATION

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

DESCRIPTION

150x50

WB

20

ISOLATOR

SUPPLIED W

ITH R

MU

OPERATING S

KETCH

COMPONENT

IDENTIFICATION

eg. RM1

LABEL

150x50

SIZE

LETTER

LABEL

WB

COLOUR

20

SIZE

OPERATIONAL ISOLATOR

DESTINATION L

ABEL

FEEDER IDENTIFICATION

FRONT V

IEW

LABEL INFORMATION

eg. IS57 o

r FU58

IDENTIFICATION

eg. LONDON 7

6

eg. EMP2

SIDE V

IEW

LOCATION

FRONT

LABEL

LABEL

RMU

250x40

250x40

BW

20

BW

10

SF

ISIS

IS/SF

CABLE

BOX

FRONT

CABLE

BOX

FEEDER

CABLE

1. Labels to be made from GRAVOPLY II (1.5mm) or similar.

If the RMU is installed outdoors then the labels are to

be made from KOLANA BRONZE (1.2mm) Thick Anodised

Aluminium Plate.

NOTES

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

PROJECT No.

STATION No.

LOCATION

GEC T3/OF RMU

G. SAMUELS

Template Updated

B 8/5/03

A.Tieken

D.Langley

D.Lloyd

K. GOSDEN

J.TUNNEY

24/10/00

R.DOUGLAS

NTS

6436-A4 B

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

ORDER FORM

GEC T3/OF RMU

UNCONTROLLED COPY

Page 33: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

FOR F

USE U

NITS U

SE

THIS C

OLUMN O

NLY

HAZEMEYER M

AGNEFIX

MD T

YPE 2

,3,4&6.

1.Labels t

o b

e m

ade f

rom G

RAVOPLY II (1.5mm) or similar.

NOTES

DESTINATION L

ABEL

eg. To L

YTTON 9

19

OPERATING S

KETCH

FEEDER IDENTIFICATION

OPERATIONAL ISOLATOR

eg. IS19

or SF20

IDENTIFICATION

eg. QNP12A

RMU O

PERATING S

KETCH 6

DM

TYPE 6

RMU O

PERATING S

KETCH 6

DL

HAZEMEYER M

AGNEFIX

MD T

YPE 1

RMU O

PERATING S

KETCH 6

DN

HAZEMEYER M

AGNEFIX

MD T

YPE 5

TYPE 2

TYPE 4TYPE 3

IS

80x40

75x20

6BW

WB

SIZE

LABEL

COLOUR

LABEL

10

LETTER

SIZE

LABEL INFORMATION

SF

ISIS

IDENTIFICATION

DESCRIPTION

NEAR

LOCATION

LABEL

FRONT

ISOLATOR

LABEL

ISOLATOR

CABLE

DESTINATION

PLATE

FUSE U

NIT

RMU

RMU is t

he f

irst

term

ination o

uts

ide a

Zone S

ubsta

tion.

2.The F

eeder

Identifica

tion L

abel is o

nly required if th

e

PROJECT No.

STATION No.

LOCATION

HAZEMEYER RMU / FU

G. SAMUELS

Template Updated

B 8/5/03

A.Tieken

D.Langley

D.Lloyd

K. GOSDEN

J.TUNNEY

24/10/00

R.DOUGLAS

NTS

6437-A4 B

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

ORDER FORM

HAZEMEYER RMU/FU

UNCONTROLLED COPY

Page 34: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

NOTES

1. Labels to be made from GRAVOPLY II (1.5mm) or similar.

If the RMU is installed outdoors then the labels are to

be made from KOLANA BRONZE (1.2mm) Thick Anodised

Aluminium Plate.

COMPONENT

OPERATING S

KETCH

CABLE

FEEDER

IDENTIFICATION

IDENTIFICATION

DESTINATION

LABEL

DESCRIPTION

IDENTIFICATION

ISOLATOR

LABEL

150x50

SIZE

LETTER

LABEL

COLOUR

WB

SIZE

20

eg. LONDON 7

6

eg. EMP2

eg. IS57 o

r FU58

OPERATIONAL ISOLATOR

IDENTIFICATION

FEEDER IDENTIFICATION

DESTINATION L

ABEL

FRONT V

IEW T

YPE E

TV2

LABEL INFORMATION

IDENTIFICATION

eg. RM1

FRONT V

IEW T

YPE G

F3

LOCATION

FRONT

LABEL

RMU

250x40

150x50

250x40

WB

BW

20

20

BW

10

ISSF

ISIS/SF

CABLE

BOX

FRONT

CABLE

BOX

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

PROJECT No.

STATION No.

LOCATION

LONG & CRAWFORD

ETV2 & GF3 RMU

G. SAMUELS

Template Updated

B 8/5/03

A.Tieken

D.Langley

D.Lloyd

K. GOSDEN

J.TUNNEY

24/10/00

R.DOUGLAS

NTS

6439-A4 B

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

ORDER FORM

LONG & CRAWFORD ETV2 & GF3 RMU

UNCONTROLLED COPY

Page 35: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

NOTES

1. Labels to be made from GRAVOPLY II (1.5mm) or similar.

If the RMU is installed outdoors then the labels are to

be made from KOLANA BRONZE (1.2mm) Thick Anodised

Aluminium Plate.

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

OPERATING S

KETCH

eg. RM1

IDENTIFICATION

COMPONENT

LABEL

COLOUR

150x50

LABEL

SIZE

LETTER

WB

SIZE

20

FRONT V

IEW

LABEL INFORMATION

IDENTIFICATION

OPERATIONAL ISOLATOR

eg. LONDON 7

6

DESTINATION L

ABEL

FEEDER IDENTIFICATION

eg. IS57 o

r FU58

eg. EMP2

SIDE V

IEW

LABEL

LOCATION

FRONT

DESCRIPTION

LABEL

RMU

250x40

150x50

250x40

WB

BW

20

20

BW

10

SF

ISIS

IS/SF

CABLE

FRONT

CABLE

BOX

BOX

ISOLATOR

FEEDER

DESTINATION

CABLE

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

PROJECT No.

STATION No.

LOCATION

LONG & CRAWFORD R3, R4/J4 AND J4 RMU

DWN

REC'D

CKD

DATE

SCALE

APP'D

G. SAMUELS

Template Updated

B 8/5/03

A.Tieken

D.Langley

D.Lloyd

K. GOSDEN

J.TUNNEY

24/10/00

R.DOUGLAS

NTS

6440-A4 B

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

ORDER FORM

LONG & CRAWFORD R3, R4/J4 & J4 RMU

UNCONTROLLED COPY

Page 36: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

NOTES

1. Labels to be made from GRAVOPLY II (1.5mm) or similar.

If the RMU is installed outdoors then the labels are to

be made from KOLANA BRONZE (1.2mm) Thick Anodised

Aluminium Plate.

DESTINATION

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

DESCRIPTION

OPERATING S

KETCH

FRONT V

IEW W

ITH G

F3 S

W F

USE

COLOUR

SIZE

150x50

LABEL

LABEL

WB

LETTER

SIZE

20

FEEDER IDENTIFICATION

IDENTIFICATION

OPERATIONAL ISOLATOR

eg. IS57 o

r FU58

eg. EMP2

LABEL INFORMATION

DESTINATION L

ABEL

eg. LONDON 7

6

IDENTIFICATION

COMPONENT

eg. RM1

FRONT V

IEW

FRONT

LABEL

LOCATION

LABEL

RMU

150x50

250x40

250x40

WB

BW

20

20

BW

10

SF

ISIS

IS/SF

BOX

CABLE

BOX

CABLE

FRONT

ISOLATOR

FEEDER

CABLE

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

PROJECT No.

STATION No.

LOCATION

LONG & CRAWFORD

T3GF3 & T4GF3 RMU

G. SAMUELS

Template Updated

B 8/5/03

A.Tieken

D.Langley

D.Lloyd

K. GOSDEN

J.TUNNEY

24/10/00

R.DOUGLAS

NTS

6441-A4 B

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

ORDER FORM

LONG & CRAWFORD T3GF3 & T4GF3 RMU

UNCONTROLLED COPY

Page 37: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

SKETCH 6

DJ

OPERATING S

KETCH

eg. RM1

COMPONENT

IDENTIFICATION

LABEL

SIZE

150x50

LABEL INFORMATION

eg. IS57 o

r FU58

OPERATIONAL ISOLATOR

OPERATIONAL ISOLATOR

eg. IS57 o

r FU58

FEEDER IDENTIFICATION

DESTINATION L

ABEL

LABEL

COLOUR

LETTER

SIZE

KB

20

FRONT V

IEW

IDENTIFICATION

IDENTIFICATION

eg. EMP2

eg. LONDON 7

6

SIDE V

IEW

IDENTIFICATION

DESCRIPTION

LOCATION

LABEL

FRONT

LABEL

RMU

150x50

50x20

250x40

250x40

KB

WB

20 8

KB

20

IS IS

KB

6

SF

SF

IS IS

CABLE

CABLE

IDENTIFICATION

ISOLATOR

ISOLATOR

IDENTIFICATION

IDENTIFICATION

ISOLATOR

UNDER

COVER

NEAR

CABLE

BOX

FEEDER

DESTINATION

BOX

1. Labels to be made from GRAVOPLY II (1.5mm) or similar.

If the RMU is installed outdoors then the labels are to

be made from KOLANA BRONZE (1.2mm) Thick Anodised

Aluminium Plate.

NOTES

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

PROJECT No.

STATION No.

LOCATION

LUCY RMU

This document must not be

whole without writtenpermission from ENERGEX

reproduced in part or DWN

APP'D

DWN

CKD

DATE

REC'D

CKD

DATE

SCALE

APP'D

G. SAMUELS

Template Updated

C 8/5/03

A.Tieken

D.Langley

D.Lloyd

K. GOSDEN

J TUNNEY

24-10-00

R DOUGLAS

NTS

6442-A4 C

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

ORDER FORM

LUCY RMU

UNCONTROLLED COPY

Page 38: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

LABEL INFORMATION

1.Labels t

o b

e m

ade f

rom G

RAVOPLY II (1.5mm) or similar.

NOTES

LABEL

LETTER

LABEL

DESTINATION L

ABEL

eg. RM1

COMPONENT IDENTIFICATION

OPERATIONAL ISOLATOR

IDENTIFICATION

eg. IS57 o

r CB58

FEEDER IDENTIFICATION

eg. EMP2

DESTINATION L

ABEL

eg. LONDON 7

6Conc

Plinth

Fro

nt

of

RMU

eg. LONDON 7

6

LABEL

LABEL

IS/CB

(2 o

ff)

150x50

250x40

250x40

170x50

SIZE

20

SIZE

20

20

WB

WB

COLOUR

BW

6BW

(X)(S

C) SG

ISCB

IS

IDENTIFICATION

RMU

IDENTIFICATION

IDENTIFICATION

FEEDER

ISOLATOR

DESCRIPTION

LOCATION

FRONT

NEAR

CABLE

ISOLATOR

BOX

DESTINATION

CABLE

CABLE

BOX

RMU is t

he f

irst

term

ination o

uts

ide a

Zone S

ubsta

tion.

2.The F

eeder

Identifica

tion L

abel is o

nly r

equired if th

e

PROJECT No.

STATION No.

LOCATION

MERLIN GERIN RMU

Altern

ate

position for

component

identifica

tion label.

(New s

tyle R

MU.)

This document must not be

whole without writtenpermission from ENERGEX

reproduced in part or DWN

APP'D

DWN

CKD

DATE

REC'D

CKD

DATE

SCALE

APP'D

G. SAMUELS

Template Updated

B 8/5/03

A.Tieken

D.Langley

D.Lloyd

K. GOSDEN

J.TUNNEY

24/10/00

R.DOUGLAS

NTS

6443-A4 B

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

ORDER FORM

MERLIN GERIN RMU

UNCONTROLLED COPY

Page 39: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

1. Labels to be made from GRAVOPLY II (1.5mm) or similar.

If the RMU is installed outdoors then the labels are to

be made from KOLANA BRONZE (1.2mm) Thick Anodised

Aluminium Plate.

NOTES

DESCRIPTION

ISOLATOR

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

DESTINATION

FRONT

20

WB

150x50

LABEL

SIZE

LABEL

COLOUR

LETTER

SIZE

IDENTIFICATION

eg. RM1

OPERATIONAL ISOLATOR

IDENTIFICATION

COMPONENT

DESTINATION L

ABEL

FEEDER IDENTIFICATION

eg. IS57 o

r FU58

OPERATING S

KETCH

eg. LONDON 7

6

eg. EMP2

LABEL INFORMATION

FRONT V

IEW

TYPE O

DTYPE V

L

FRONT V

IEW

LABEL

LOCATION

LABEL

RMU

250x40

150x50

250x40

20

BW

WB

20

BW

10

ISSF

ISIS/SF

BOX

CABLE

FRONT

CABLE

BOX

FEEDER

CABLE

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

PROJECT No.

STATION No.

LOCATION

MI AUSTRALIA (SLATTER) OD & VL RMU

This document must not be

whole without writtenpermission from ENERGEX

reproduced in part or DWN

APP'D

DWN

CKD

DATE

REC'D

CKD

DATE

SCALE

APP'D

G. SAMUELS

Template Updated

B 8/5/03

A.Tieken

D.Langley

D.Lloyd

K. GOSDEN

J.TUNNEY

24/10/00

R.DOUGLAS

NTS

6444-A4 B

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

ORDER FORM

MI AUSTRALIA (SLATTER) OD & VL RMU

UNCONTROLLED COPY

Page 40: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

NOTES

1. Labels to be made from GRAVOPLY II (1.5mm) or similar.

If the RMU is installed outdoors then the labels are to

be made from KOLANA BRONZE (1.2mm) Thick Anodised

Aluminium Plate.

OPERATING S

KETCH

COMPONENT

CABLE

LABEL

DESCRIPTION

IDENTIFICATION

IDENTIFICATION

ISOLATOR

IDENTIFICATION

FEEDER

DESTINATION

LETTER

SIZE

LABEL

150x50

COLOUR

LABEL

WB

SIZE

20

IDENTIFICATION

OPERATIONAL ISOLATOR

eg. IS57 o

r FU58

DESTINATION L

ABEL

eg. EMP2

eg. LONDON 7

6

FEEDER IDENTIFICATION

LABEL INFORMATION

FRONT V

IEW

eg. RM1

IDENTIFICATION

SIDE V

IEW

FRONT

LABEL

LOCATION

RMU

250x40

150x50

250x40

WB

BW

20

20

BW

10

ISSF

ISIS/SF

BOX

CABLE

FRONT

BOX

CABLE

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

PROJECT No.

STATION No.

LOCATION

& T01/T112 RMUs

REYROLLE JKSS, JSSS

This document must not be

whole without writtenpermission from ENERGEX

reproduced in part or DWN

APP'D

DWN

CKD

DATE

REC'D

CKD

DATE

SCALE

APP'D

G. SAMUELS

Template Updated

B 8/5/03

A.Tieken

D.Langley

D.Lloyd

K. GOSDEN

J.TUNNEY

24/10/00

R.DOUGLAS

NTS

6445-A4 B

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

ORDER FORM

REYROLLE JKSS, JSSS & T01/T112 RMU

UNCONTROLLED COPY

Page 41: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

NOTES

1. Labels to be made from GRAVOPLY II (1.5mm) or similar.

If the RMU is installed outdoors then the labels are to

be made from KOLANA BRONZE (1.2mm) Thick Anodised

Aluminium Plate.

DESTINATION

ISOLATOR

IDENTIFICATION

IDENTIFICATION

DESCRIPTION

IDENTIFICATION

TYPE C

ROF

FRONT V

IEW

150x50

LABEL

SIZE

COLOUR

LABEL

WB

SIZE

LETTER

20

OPERATING S

KETCH

IDENTIFICATION

OPERATIONAL ISOLATOR

eg. IS57 o

r FU58

eg. EMP2

eg. RM1

COMPONENT

IDENTIFICATION

FEEDER IDENTIFICATION

eg. LONDON 7

6

DESTINATION L

ABEL

LABEL INFORMATION

eg. EMP2

FEEDER IDENTIFICATION

eg. LONDON 7

6

DESTINATION L

ABEL

FRONT V

IEW

TYPE N

X3F

FRONT V

IEW

LABEL

LOCATION

FRONT

LABEL

RMU

250x40

150x50

250x40

WB

BW

20

20

BW

10

ISSF

ISIS/SF

CABLE

BOX

FRONT

CABLE

BOX

FEEDER

CABLE

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

PROJECT No.

STATION No.

LOCATION

SOUTH WALES CROF & NX3F RMU

G. SAMUELS

Template Updated

B 8/5/03

A.Tieken

D.Langley

D.Lloyd

K. GOSDEN

J.TUNNEY

24/10/00

R.DOUGLAS

NTS

6446-A4 B

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

ORDER FORM

SOUTH WALES CROF & NX3F RMU

UNCONTROLLED COPY

Page 42: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

MET U

NIT

WB

30

150x50

LABEL

SIZE

LABEL INFORMATION

eg. EMP2

eg. MU1

DESTINATION L

ABEL

FEEDER IDENTIFICATION

IDENTIFICATION

COMPONENT

eg. LONDON 7

6

FRONT V

IEW

LETTER

SIZE

COLOUR

LABEL

SIDE V

IEW

LABEL

LOCATION

DESCRIPTION

LABEL

250x40

250x40

1020

BW

BW

CABLE

BOX

FRONT

CABLE

BOX

IDENTIFICATION

FEEDER

IDENTIFICATION

DESTINATION

CABLE

1. Labels to be made from GRAVOPLY II (1.5mm) or similar.

If the RMU is installed outdoors then the labels are to be made from

KOLANA BRONZE (1.2mm) Thick Anodised Aluminium Plate.

NOTES

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

PROJECT No.

STATION No.

LOCATION

11kV METERING UNIT

G. SAMUELS

Template Updated

B 8/5/03

A.Tieken

D.Langley

D.Lloyd

K. GOSDEN

J.TUNNEY

24/10/00

R.DOUGLAS

NTS

6451-A4 B

NETWORK LABELLING & SIGNAGE

HV EQUIPMENT LABELLING

ORDER FORM

11kV METERING UNIT

UNCONTROLLED COPY

Page 43: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

EXTERNAL SIGNAGE - SQUARE TYPE PMT

PLACE ON LABEL ABOVE

NEXT TO 'STATION'.

12207

NUMBERS "1-0"

LETTER "C"

LETTER "S"

STATION

11649

11630

11621

11633

1015mm ABOVE PLINTH.

TO LV DOOR. TOP OF SIGN

MANUFACTURER.

USE "3M" 220 BLACK

SCOTCHCAL CAST VINYL

LETTERS. (6off)

INSTALLER.

(1off)

12198

CodeStock

SIGN

HIGH VOLTAGE

DANGER

FITTED BY

MANUFACTURER.

TO HV & LV DOOR. TOP OF SIGN

1150mm ABOVE PLINTH.

(2off)

REMARKS

SIGN TO BE FITTED TO

= = 1015

1150

STATION

HIGH VOLTAGE

SG1455

DANGER

EACH SIDE OF PMT.

TRANSFORMER. (2off)

REAR OF CUBICLE ABOVE

ADDITIONAL SIGNS FITTED TO

REAR SIGNS NOT REQUIRED FOR

G. SAMUELS

C08088 ITEMS NOTE ADDED

D 25/02/10

B.BRUNSMANN

P.RELF

R. English

K. GOSDEN

J.TUNNEY

24/10/00

R.DOUGLAS

NTS

6816-A4 D

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

SQUARE TYPE PMT

IF EQUIPMENT IS

DAMAGED OR UNSECURED

13 12 53

CONTACT ENERGEX ON

HIGH VOLTAGE

DANGER

IF EQUIPMENT IS

DAMAGED OR UNSECURED

13 12 53

SC22094CONTACT ENERGEX ON

22094

MANUFACTURER.

TO HV DOOR.

25mm BELOW DANGER H.V. SIGN.

(1off)

25

WTC C08088 SQ PMT DIST TXS

= =

1015

1150

25

NEW SQUARE PMT

OLD SQUARE PMT

REAR SIGNS NOT REQUIRED

FOR WTC C08088 SQ PMTDIST TXS

UNCONTROLLED COPY

Page 44: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

REMARKSFITTED BYStock

SIGN

NUMBERS "1-0"

LETTER "C"

LETTER "S"

HIGH VOLTAGE

DANGER

INSTALLER.

USE "3M" 220 BLACK

SCOTCHCAL CAST VINYL

11630

11621

LETTERS. (6 off)

11633

11649

12207ACCESS SIDE WHERE REQUIRED

TOP OF SIGN 1015mm ABOVE

PLINTH BY ENERGEX. (1 off)

MANUFACTURER.

TO ALL SIDES. TOP OF SIGN

1150mm ABOVE PLINTH.

DISC 1215mm ABOVE PLINTH.

TO LV DOOR. CENTRE OF

MANUFACTURER.

12198

(4 off)

(1 off)

ADDITIONAL SIGN FITTED TO

1215

1150

1015

=

THIS IS THE ACCESS SIDE

SIGN TO BE FITTED IF

LV=

HIGH VOLTAGE

DANGER

Padmounted

=

Substation.

=

HV

HIGH VOLTAGE

DANGER

SG1455

SG1455STATION

STATION

Code

NEXT TO 'STATION'.

PLACE ON LABEL ABOVE

1015mm ABOVE PLINTH.

TO LV DOOR. TOP OF SIGN

MANUFACTURER.

(1 off)

EXTERNAL SIGNAGE - RECTANGULAR TYPE PMTs

G. SAMUELS

NEW SIGN ADDED, SC22094.

C 25/02/10

R. KROSCH

G. TREAGLE

R. ENGLISH

K. GOSDEN

J.TUNNEY

24/10/00

R.DOUGLAS

NTS

6817-A4 C

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

RECTANGULAR TYPE PMT

IF EQUIPMENT IS

DAMAGED OR UNSECURED

13 12 53

SC22094CONTACT ENERGEX ON

MANUFACTURER.

TO ALL SIDES.

25mm BELOW DANGER HV SIGN22094

& STATION SIGN (LV DOOR).

IF EQUIPMENT IS

DAMAGED OR UNSECURED

13 12 53

SC22094CONTACT ENERGEX ON

25

(4 off)

IF EQUIPMENT IS

DAMAGED OR UNSECURED

13 12 53

CONTACT ENERGEX ON 25

STATION

UNCONTROLLED COPY

Page 45: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

STOCK CODE 15981

AS FOLLOWS

LETTER SIZE 3.5mm

UG CABLE HAS BEEN CONNECTED

EQUIPMENT MARKINGS U V W

CABLE PHASE MARKINGS A C B

STOCK CODE 15981

LETTER SIZE 5.0mm

TRANSFORMER MARKINGS

CABLE PHASE MARKINGS

UG CABLE HAS BEEN CONNECTEDAS FOLLOWS

A B C

A B C

STOCK CODE 20790

STOCK CODE 20790

STOCK CODE 20729

UG CABLE HAS BEEN CONNECTED

CABLE PHASE MARKINGS

TRANSFORMER MARKINGS A B C

C B A

AS FOLLOWSSTOCK CODE 20792

PHASE CONNECTION LABELS

G. SAMUELS

Trans phasing labels added

C 19/10/06

B.Brunsman

B.Somers

K.Nuttall

K. GOSDEN

J.TUNNEY

24/10/00

R.DOUGLAS

NTS

6818-A4 C

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

PHASE CONNECTION LABELS

AS FOLLOWS

STOCK CODE 15980

EQUIPMENT MARKINGS

CABLE PHASE MARKINGS

UG CABLE HAS BEEN CONNECTED

U V W

A B C

STOCK CODE 15980

A C B

A B C

UG CABLE HAS BEEN CONNECTED

STOCK CODE 20791

CABLE PHASE MARKINGS

TRANSFORMER MARKINGS

AS FOLLOWSSTOCK CODE 20791

LETTERSIZE 2.0mmSTOCK CODE 15982

AS FOLLOWS

CABLE PHASE MARKINGS

EQUIPMENT MARKINGS

UG CABLE HAS BEEN CONNECTED

STOCK CODE 15982

U V W

C B A

UNCONTROLLED COPY

Page 46: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 47: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

(1) "DANGER HIGH VOLTAGE" SIGN (Stock Code 12198) fixed 1150 above plinth

(2) "STATION" SIGN (Stock Code 12207) to be fitted by ENERGEX 50mm below

(3) Station Numbers using "3M" 220 black SCOTCHCAL CAST VINYL to be

NUMBERS "1-0"

LETTER "X"

HIGH VOLTAGE

DANGER

SIGN

1162111630

11654

12201

1

4

Stock Code QTY

STATION

SIGN

X11567

or floor level by manufacturer. Fixed by blind rivets (sealed type).

ordered separately. Not included in material list as Stock Codes.

"DANGER HV SIGN" on front of unit.

HIGH VOLTAGE

DANGER

NOTES

STATION

HIGH VOLTAGE

DANGER

1150

= =

QTY

12207 1

50

=

==

=

Stock Code

RM6 RMUs

G. SAMUELS

SafeLink enclosure included.

C 22/03/2004

A.Tieken

D.Langley

C.Lee

K. GOSDEN

J.TUNNEY

24/10/00

R.DOUGLAS

NTS

6820-A4 C

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

ENCLOSED RMU SWITCHING STATIONS

X11567STATION

1150

==X11567STATION

==

SAFELINK RMUs

50

UNCONTROLLED COPY

Page 48: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 49: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

AS FOLLOWS REGIONAL AREAS.ABOVE UG CABLE BOX.

UG CABLE HAS BEEN CONNECTED

UG CABLE HAS BEEN CONNECTED

EQUIPMENT MARKINGS

CABLE PHASE MARKINGS

U

C

AS FOLLOWS

CABLE PHASE MARKINGS A

EQUIPMENT MARKINGS

AS FOLLOWS

U

EQUIPMENT MARKINGS

CABLE PHASE MARKINGS

U

A(1 for each termination).

15982V W

B A

BC

15981WV

15980V W

B C

TRANSFORMERS FROM

EXISTING BRISBANE METRO

THIS SIGN TO BE USED IN

PADMOUNTED TRANSFORMERS.

CONTRACT (C51/91)

BRISBANE METRO PADMOUNTED

THIS SIGN TO BE USED IN

UG CABLE HAS BEEN CONNECTED

UG CABLE HAS BEEN CONNECTED

C

U

U

A

UG CABLE HAS BEEN CONNECTED

UG CABLE HAS BEEN CONNECTED

A

U

PHASE CONNECTION SEQUENCE BETWEEN HV EQUIPMENT AND CABLES

ENERGEX REGIONAL

W B

HV RMU/FU AND

TERMINAL MARKING

TRANSFORMER # ( )

U

V

ENERGEX BRISBANE

METRO AREA HV

A

C

FEEDER CABLE

SIGN

CABLE PHASE MARKINGS

EQUIPMENT MARKINGS

AS FOLLOWS

EQUIPMENT MARKINGS

CABLE PHASE MARKINGS

AS FOLLOWS

AS FOLLOWS

CABLE PHASE MARKINGS

EQUIPMENT MARKINGS

MANUFACTURER.

INSTALLER.

INSIDE HV END DOOR. TOP

OF SIGN 1150mm ABOVE

PLINTH. (1 off)C

A

B

FITTED BYStock

AB

WV

THIS SIGN TO BE USED IN

REMARKS

V W

C B

CB

WV

NOT BE USED ADJACENT

TO THIS TRANSFORMER

THIS WARNING NOTICE

MUST NOT BE REPLACED

BY A GPO

SEE SUBSTATION DESIGN

CONSTRUCTION MANUAL

VOLUME 10 SECTION 1

CAUTION

SEPARATE HV & LV

EARTHING

240V APPLIANCES MUST

LV

PHASE CONNECTION SEQUENCE BETWEEN HV EQUIPMENT AND CABLES

U

V

W

A

B

C

A

C

B

ENERGEX BRISBANE

METRO AREA HV

HV RMU/FU AND

TRANSFORMER # ( )

TERMINAL MARKING

ENERGEX REGIONAL

FEEDER CABLEFEEDER CABLE

PMT

Rectangular Type

CAUTION SEPARATE 11kV & LV EARTHING

Code

INSTALLER.

(1 for each termination).

ABOVE UG CABLE BOX.

ABOVE UG CABLE BOX.

(1 for each termination).

INSTALLER.

OR

OR

INTERNAL SIGNAGE - PMTs

LV

HV

Square Type

PMT

amended. Shown changes as #. G. SAMUELS

Phase Connection Labels

2/02/07

B.Brunsman

B.Somers

K.Nuttall

K. GOSDEN

J.TUNNEY

24/10/00

R.DOUGLAS

NTS

6823-A4 C

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

PMTs - INTERNAL

(Obselescent)

Stock Code 17954

Stock Code 15983

(A)

(B)

(C)

(A)

(B)

(C)

For separate HV and LV earthing situations remove clearly tagged ("for seperate earthing remove this cable")

HV and LV earthing bridge cable between LV switchboard earth bar and station earthing point.

NOTE:

MAY APPEAR ON

EXISTING SEPERATELY

INSTALLATIONSEARTHED

AREAS HV

FEEDER CABLE

AREAS HV

UNCONTROLLED COPY

Page 50: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

C.Muller

CFI info added

C 16/04/08

R.KROSCH

A.McCOOK

R.ENGLISH

A.Tieken

D.Langley

13/6/02

D.Lloyd

NTS

7453-A4 C

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

ORDER FORM

ABB SAFELINK CFC RMU

is installed in a Zone Substation

3. Design I.D and Component I.D lables are only required if the RMU

LOCATION

2. The Feeder Identification Label is only required if the

RMU is the first termination outside a Zone Substation.

DESIGN

1. Labels to be made from GRAVOPLY II (1.5mm) or similiar.

ABB SAFELINK CFC RMU

STATION No.

PROJECT No.

See N

ote

3

DESIGN IDENTIFICATION

eg. +1A

B

See N

ote

3

COMPONENT

IDENTIFICATION

eg. RM1

eg. UVW to A

BC/ACB/CBA

PHASE C

ONNECTION

LABELS

NOTES

LABEL

150x40

SIZE

DESTINATION L

ABEL

OPERATIONAL ISOLATOR

IDENTIFICATION

eg. IS57 o

r SF58

eg. TO ISXXXX S

CXXXX

FEEDER IDENTIFICATION

LABEL INFORMATION

ISSF

IS

FRONT V

IEW

SIZE

LETTER

20

LABEL

COLOUR

WB

See n

ote

2eg. EMP2

SIDE V

IEW

IDENTIFICATION

LABEL

FRONT

LOCATION

LABEL

DESCRIPTION

RMU

50x20

100x40

150x40

150x50

150x50

201510

BLUE W

WB

BW

IS

1010BW

BW

SF

IS

CABLE

CABLE

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

ISOLATOR

NEAR

FRONT

FRONT

FEEDER

ISOLATOR

DESTINATION

DESTINATION

BOX

INSIDE

SIDE W

ALL

CABLE

eg. TO P

XXXXX V

IA

DESTINATION L

ABEL

11kV B

US A

T S

CXXXX

(see n

ote

4)

(see n

ote

4)

4. See drawings 8358-a4a & 8356-a4a for other destination labels

CFI fitt

ed b

y m

anufa

cture

r.

Not

labelled

UNCONTROLLED COPY

Page 51: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

DRAWING D.Langley

C08088 ITEM CHANGES TO

E 21/12/2011

B. BRUNSMANN

P. RELF

R. English

A.Tieken

J.Tunney

3/7/02

D.Lloyd

NTS

7790-A4 E

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

ORDER FORM

TRANSFORMER & CABLE DESTINATION LABELS

more than one transformer at the site or the transformer

2. Cable destination labels are only required if there is

LOCATION

GROUND AND DRY TYPE TRANSFORMERS

is remote from the switchgear controlling it.

SIZECOLOUR ATTACHING OF LABELSIZE

be made from Laminated ABS Plastic (1.5mm)

1. Labels to be made from ABS Plastic (1.5mm) or similar.

If the transformer is installed outdoors then the labels are to

NOTES

150X50 WB

250X40 BW

10

10

LABEL LABEL SITE LOCATION FORTEXTLABEL INFORMATION

eg. TR1

P654987

eg. TO SMITH RD

STATION No.

PROJECT No.

GROUND TRANSFORMER

CABLE BOX / DRY TYPE

TRANSFORMER HV DOOR OR

CABLE BOX

GROUND TRANSFORMER /

DRY TYPE TRANSFORMER

HV DOOR OR CABLE BOX.

TRANSFORMER & CABLE DESTINATION LABELS

WARNING

TRANSFORMERWILL TRIP IF

DOOR IS OPENED

100x80 YB 10 2

26x26 RW 10 1

ABOVE DOORHANDLE OF DRY

TYPE TRANSFORMER

X1DOORBELOW

FUSE LINK SWITCHLINK

LABELSIZE COLOUR

LABELSIZETEXT No. of

LABELSSITE LOCATION FORATTACHING OF LABEL LABEL INFORMATION

70x30 RW7 TEST BLOCK

COVER IN415V SUPPLY

BEHIND COVER5 MDI BOX

DANGER

SC

20702

20703

20701

100x40 WB 20 1 MDIBOX MDI BOX

1

ABB DRY TYPE TRANSFORMERS ONLY

UNCONTROLLED COPY

Page 52: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

removed from incoming

cablesD. LANGLEY

Operational ID labels

B 22/3/2004

A. TIEKEN

D.LANGLEY

C. LEE

A. TIEKEN

D. LANGLEY

15/5/03

D. LLOYD

NTS

8358-A4 B

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

ORDER FORM

ABB SAFELINK DFD SFU

is installed in a Zone Substation

3. Design I.D and Component I.D lables are only required if the RMU

LOCATION

2. The Feeder Identification Label is only required if the

RMU is the first termination outside a Zone Substation.

DESIGN

1. Labels to be made from GRAVOPLY II (1.5mm) or similiar.

ABB SAFELINK DFD SFU

STATION No.

PROJECT No.

See N

ote

3

DESIGN IDENTIFICATION

eg. +1A

B

See N

ote

3

COMPONENT

IDENTIFICATION

eg. RM1

eg. UVW to A

BC/ACB/CBA

PHASE C

ONNECTION

LABELS

NOTES

LABEL

150x40

SIZE

DESTINATION L

ABEL

OPERATIONAL ISOLATOR

IDENTIFICATION

eg. SF58

eg. TEE B

ANKS R

D 2

0

FEEDER IDENTIFICATION

LABEL INFORMATION

SF

FRONT V

IEW

SIZE

LETTER

20

LABEL

COLOUR

WB

See n

ote

2eg. EMP2

SIDE V

IEW

IDENTIFICATION

LABEL

FRONT

LOCATION

LABEL

DESCRIPTION

RMU

50x20

100x40

150x40

150x50

150x50

201510

BLUE W

WB

BW

1010BW

BW

SF

CABLE

CABLE

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

ISOLATOR

NEAR

FRONT

FRONT

FEEDER

ISOLATOR

DESTINATION

DESTINATION

BOX

INSIDE

SIDE W

ALL

CABLE

DESTINATION L

ABEL

SGxxxxx ISuu /

4. See drawings 7453-a4b & 8356-a4a for other destination labels

BANKS R

D P

xxxxx

(See N

ote

4)

UNCONTROLLED COPY

Page 53: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Copyright

NETWORK LABELLING & SIGNAGE

8448-A4

HV EQUIPMENT LABELLING

ABB SAFELINK CCC THREE WAY SWITCH

ORDER FORM

4. See drawings 8358-a4a & 8356-a4a for other destination labels

ABB SAFELINK CCC THREE WAY SWITCH

1. Labels to be made from GRAVOPLY II (1.5mm) or similiar.

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

3. Design I.D and Component I.D lables are only required if the RMU

is installed in a Zone Substation

PROJECT No.

STATION No.

eg. +1A

BDESIGN IDENTIFICATION

See N

ote

3

(see n

ote

4)

11kV B

US A

T S

CXXXX

DESTINATION L

ABEL

eg. TO P

XXXXX V

IA

PHASE C

ONNECTION L

ABELS

eg. UVW to A

BC/ACB/CBA

eg. RM1

COMPONENT IDENTIFICATION

See N

ote

3

NOTES

See n

ote

2

OPERATIONAL ISOLATOR

FEEDER IDENTIFICATION

eg. EMP2

ISIS

IS

FRONT V

IEW

(see n

ote

4)

eg. TO ISXXXX S

CXXXX

eg. IS57 o

r SF58

IDENTIFICATION

DESTINATION L

ABEL

SIDE V

IEW

LOCATION

BLUE W

50x20

150x40

LABEL

LABEL

SIZE

WB

COLOUR

150x40

100x40

WB

BW

150x50

150x50

BW

BW

LABEL INFORMATION

10

LETTER

20

SIZE

15IS

20

ISIS

10 10

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

DESCRIPTION

IDENTIFICATION

DESIGN

LOCATION

FRONT

LABEL

LABEL

RMU

FRONT

FRONT

NEAR

ISOLATOR

CABLE

FEEDER

ISOLATOR

CABLE

DESTINATION

DESTINATION

SIDE W

ALL

INSIDE

BOX

CABLE

APP'D:

CKD:

DRN:

B

Copyright

C. Lee

A. Tieken

J. Sokac

DATE: 16/04/2008

APP'D:

CKD:

DRN:

R.ENGLISH

R.KROSCH

A.McC

OOK

CFI fitt

ed b

y m

anufa

cture

r.

Not

labelled

CFI note

added

UNCONTROLLED COPY

Page 54: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Copyright

8449-A4

HV EQUIPMENT LABELLING

ABB SAFELINK CFCF RMU

ORDER FORM

4. See drawings 8358-a4a & 8356-a4a for other destination labels

ABB SAFELINK CFCF RMU

1. Labels to be made from GRAVOPLY II (1.5mm) or similiar.

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

3. Design I.D and Component I.D lables are only required if the RMU

is installed in a Zone Substation

PROJECT No.

STATION No.

eg. +1A

B

DESIGN IDENTIFICATION

See N

ote

3

(see n

ote

4)

11kV B

US A

T S

CXXXX

DESTINATION L

ABEL

eg. TO P

XXXXX V

IA

PHASE C

ONNECTION L

ABELS

eg. UVW to A

BC/ACB/CBA

eg. RM1

COMPONENT IDENTIFICATION

See N

ote

3

NOTES

See n

ote

2

OPERATIONAL ISOLATOR

FEEDER IDENTIFICATION

eg. EMP2

ISSF

IS

FRONT V

IEW

(see n

ote

4)

eg. TO ISXXXX S

CXXXX

eg. IS57 o

r SF58

IDENTIFICATION

DESTINATION L

ABEL

SIDE V

IEW

LOCATION

BLUE W

50x20

150x40

LABEL

LABEL

SIZE

WB

COLOUR

150x40

100x40

WB

BW

150x50

150x50

BW

BW

LABEL INFORMATION

10

LETTER

20

SIZE

15IS

20

SF

IS

10 10

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

DESCRIPTION

IDENTIFICATION

DESIGN

LOCATION

FRONT

LABEL

LABEL

RMU

FRONT

FRONT

NEAR

ISOLATOR

CABLE

FEEDER

ISOLATOR

CABLE

DESTINATION

DESTINATION

SIDE W

ALL

INSIDE

BOX

CABLE

APP'D:

CKD:

DRN:

Copyright

C. Lee

A. Tieken

J. Sokac

SF

SF

CBA

ACB

SC15982

SC15981

ABC

SC15980

LABEL

CFI fitt

ed b

y m

anufa

cture

r.

Not

labelled

UNCONTROLLED COPY

Page 55: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

ORIGINAL ISSUE

Copyright

NETWORK LABELLING & SIGNAGE

8450-A4

HV EQUIPMENT LABELLING

ABB SAFEPLUS - 2 TRANSFORMER UNITORDER FORM

ABB SAFEPLUS - 2 TRANSFORMER UNIT

PROJECT No.

STATION No.

LOCATION

APP'D:

CKD:

DRN:AORIGINAL ISSUE

Copyright

C. Lee

A. Tieken

J. Sokac

CB

SF

SF

CB

BLUE W

50x20

LABEL

LABEL

SIZE

COLOUR

170x40

100x40

WB

BW

150x50

150x50

BW

BW

LABEL INFORMATION

10

LETTER

SIZE

15 20 10 10

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

DESCRIPTION

DESIGN

LOCATION

LABEL

FRONT

FRONT

NEAR

CB

CABLE

FEEDER

OPERATIONAL

CABLE

DESTINATION

DESTINATION

SIDE W

ALL

INSIDE

BOX

CABLE

150x50

BW

10

FRONT

CABLE

CABLE

DESTINATION

BOX

REAR

100x40

WB

15IDENTIFICATION

NEAR

ISOLATOR

OPERATIONAL

1. Labels to be made from GRAVOPLY II (1.5mm) or similiar.

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

3. This label is not required for feeders terminating in the same substation.

For example, a feeder used to connect two switchboards together in the same room.

NOTES

CB

CB

ISSF

ISSF

DESIGN IDENTIFICATION

eg. +1A

02

PHASE C

ONNECTION L

ABEL

eg. UVW to A

BC/ACB/CBA

OPERATIONAL IDENTIFIER(S)

Examples:

For CB U

nits, CB2232 &

IS2239

For SF U

nits, SF1T

49

FEEDER IDENTIFICATION

eg. CSTQEA23 (see n

ote

3).

DESTINATION L

ABEL

Examples:

For

CB U

nits, TO C

BXXXX S

SXXXX

For SF U

nits, TO T

R1

BK.NUTTALL

R.KROSCH

G.JAYAWEERA

Phase C

onnection

labels S

C a

dded.

B

CBA

ACB

SC15

982

SC15

981

ABC

SC15

980

LABEL

(4 L

ABELS)

UNCONTROLLED COPY

Page 56: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

ORIGINAL ISSUE

Copyright

NETWORK LABELLING & SIGNAGE

8451-A4

HV EQUIPMENT LABELLING

ABB SAFEPLUS - 3 TRANSFORMER UNITORDER FORM

ABB SAFEPLUS - 3 TRANSFORMER UNIT

PROJECT No.

STATION No.

LOCATION

A

Copyright

C. Lee

A. Tieken

J. Sokac

CB

SF

SF

SF

CB

1. Labels to be made from GRAVOPLY II (1.5mm) or similiar.

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

3. This label is not required for feeders terminating in the same substation.

For example, a feeder used to connect two switchboards together in the same room.

NOTES

FEEDER IDENTIFICATION

eg. CSTQEA23 (see n

ote

3).

DESTINATION L

ABEL

Examples:

For CB U

nits, TO C

BXXXX S

SXXXX

For

SF U

nits, TO T

R1

DESIGN IDENTIFICATION

eg. +1A

02

PHASE C

ONNECTION L

ABEL

eg. UVW t

o A

BC/ACB/CBA

OPERATIONAL IDENTIFIER(S)

Examples:

For

CB U

nits, CB2232 &

IS2239

For

SF U

nits, SF1T

49

BLUE W

50x20

LABEL

LABEL

SIZE

COLOUR

170x40

100x40

WB

BW

150x50

150x50

BW

BW

LABEL INFORMATION

10

LETTER

SIZE

15 20 10 10

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

DESCRIPTION

DESIGN

LOCATION

FRONT

FRONT

NEAR

CB

CABLE

FEEDER

OPERATIONAL

CABLE

DESTINATION

DESTINATION

SIDE W

ALL

INSIDE

BOX

CABLE

150x50

BW

10

FRONT

CABLE

CABLE

DESTINATION

BOX

REAR

100x40

WB

15IDENTIFICATION

NEAR

ISOLATOR

OPERATIONAL

CB

CB

ISSF

ISSF

SF

(5 L

ABELS)

BK.NUTTALL

R.KROSCH

G.JAYAWEERA

Design Identifica

tion

labels Q

ty. ch

anged.

B28/07/06

CBA

ACB

SC15

982

SC15

981

ABC

SC15

980

LABEL

+1

+1

+1

+1

+1

UNCONTROLLED COPY

Page 57: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

AORIGINAL ISSUE

Copyright

NETWORK LABELLING & SIGNAGE

8452-A4

HV EQUIPMENT LABELLING

ABB SAFEPLUS - MESH POINT UNITORDER FORM

ABB SAFEPLUS - MESH POINT UNIT

1. Labels to be made from GRAVOPLY II (1.5mm) or similiar.

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

3. This label is not required for feeders terminating in the same substation.

For example, a feeder used to connect two switchboards together in the same room.

PROJECT No.

STATION No.

NOTES

LOCATION

BLUE W

50x20

LABEL

LABEL

SIZE

COLOUR

170x40

100x40

WB

BW

150x50

150x50

BW

BW

LABEL INFORMATION

10

LETTER

SIZE

15CB

20

CB

10 10

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

DESCRIPTION

DESIGN

LOCATION

LABEL

FRONT

FRONT

NEAR

CB

CABLE

FEEDER

OPERATIONAL

CABLE

DESTINATION

DESTINATION

SIDE W

ALL

INSIDE

BOX

CABLE

Copyright

C. Lee

A. Tieken

J. Sokac

CB

SF

SF

SF

CB

150x50

BW

10

FRONT

CABLE

CABLE

DESTINATION

BOX

REAR

CB

CB

FEEDER IDENTIFICATION

eg. CSTQEA23 (see n

ote

3).

DESIGN IDENTIFICATION

eg. +1A

02

PHASE C

ONNECTION L

ABEL

eg. UVW t

o A

BC/ACB/CBA

DESTINATION L

ABEL

Examples:

For CB U

nits, TO C

BXXXX S

SXXXX

For

SF U

nits, TO T

R1

OPERATIONAL IDENTIFIER(S)

Examples:

For

CB U

nits, CB2232 &

IS2239

For

SF U

nits, SF1T

49

100x40

WB

15IDENTIFICATION

NEAR

ISOLATOR

OPERATIONAL

ISIS

ISSF

SF

SF

(6 L

ABELS)

CBA

ACB

SC15

982

SC15

981

ABC

SC15

980

LABEL

BK.NUTTALL

R.KROSCH

G.JAYAWEERA

Design Identifica

tion

labels Q

ty. ch

anged.

B28/07/06

UNCONTROLLED COPY

Page 58: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

LABEL INFORMATION

ATTACHING O

F L

ABEL

SITE L

OCATION F

OR

80x60

LABEL

SIZE

Loca

tion

Plant No.

PROJECT No.

STATION No.

LOCATION

11kV RMU LABEL

A.McCook

R.Krosch

A.McCook

18/10/2007

C.LEE

NTS

9373-A4 C

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

ORDER FORM

WARNING LABEL FOR 11kV OIL RMU's

COLOUR

LABEL

YELLOW

PLASTIC

STOCK

CODE

212

75

4∅ H

OLE (1 off)

80

3mm L

ETTERING W

ITH

2mm L

INE S

PACING

5mm L

ETTERING

FUSE C

ARRIER M

UST N

OT B

E

REMOVED F

ROM T

HE O

IL T

ANK T

O

REPLACE H

V F

USES.

OIL T

ANK M

AY C

ONTAIN L

IVE

CONDUCTORS W

ITH S

WITCHES O

FF.

CONTACT S

WITCHING C

OORDINATOR

BEFORE R

EPLACING F

USE.

REPLACEMENT F

USES S

HALL C

OMPLY

WITH T

ECHNICAL INSTRUCTION T

SD013.

LEAVE S

TIRRUPS IN T

HE O

PEN P

OSITION.

ENGAGED IN T

HE F

USE C

LIP. N

EVER

FUSE S

TIRRUPS A

RE U

PRIGHT A

ND

WHEN F

ITTING F

USES E

NSURE A

LL 6

80x30

YELLOW

PLASTIC

Loca

tion

Plant No.

21313

30

C

Approved

Date

Checked

Drawn A.McCook

R. Krosh

Note added.

02/04/2008

NOTE: Refer to TSD0092B

R. English

UNCONTROLLED COPY

Page 59: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

CHANGE D.Langley

DRAWING TITLE BLOCK

B 21/12/2011

B. BRUNSMANN

P. RELF

R. English

R.KROSCH

A. McCOOK

02/04/2008

R.ENGLISH

1:1

9489-A4 B

NETWORK LABELLING & SIGNAGEHV EQUIPMENT LABELLING

TRANSFORMERS ORDER FORM

WARNING LABEL FOR ABB DRY TYPE

ATTACHING O

F L

ABEL

SITE L

OCATION F

OR

100 x

80

LABEL

SIZE

COLOUR

LABEL

YELLOW

PLASTIC

IF D

OOR IS O

PENED

TRANSFORMER W

ILL T

RIP

ABS PLASTIC 1.5mm OR SIMILARMATERIAL

LETTERING BLACK LETTERING ON YELLOW BACKGROUND

STOCK

CODE

20702

80

100

2 O

FF P

ER T

RANSFORMER

Loca

te a

djace

nt

to th

e

door

handles f

or

both

HV

and L

V s

ides o

f Dry

Type

Tra

nsfo

rmers

UNCONTROLLED COPY

Page 60: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

AORIGINAL ISSUE

Copyright

NETWORK LABELLING & SIGNAGE

9510-A4

HV EQUIPMENT LABELLING

ABB SAFELINK CFCC RMUORDER FORM

4. See drawings 8358-a4a & 8356-a4a for other destination labels

ABB SAFELINK CFCC RMU

1. Labels to be made from GRAVOPLY II (1.5mm) or similiar.

RMU is the first termination outside a Zone Substation.2. The Feeder Identification Label is only required if the

3. Design I.D and Component I.D lables are only required if the RMU

is installed in a Zone Substation

PROJECT No.

STATION No.

eg. +1A

B

DESIGN IDENTIFICATION

See N

ote

3

(see n

ote

4)

11kV B

US A

T S

CXXXX

DESTINATION L

ABEL

eg. TO P

XXXXX V

IA

PHASE C

ONNECTION L

ABELS

eg. UVW t

o A

BC/ACB/CBA

eg. RM1

COMPONENT IDENTIFICATION

See N

ote

3

NOTES

See n

ote

2

OPERATIONAL ISOLATOR

FEEDER IDENTIFICATION

eg. EMP2

ISSF

IS(see n

ote

4)

eg. TO ISXXXX S

CXXXX

eg. IS57 o

r SF58

IDENTIFICATION

DESTINATION L

ABEL

SIDE V

IEW

LOCATION

BLUE W

50x20

150x40

LABEL

LABEL

SIZE

WB

COLOUR

150x40

100x40

WB

BW

150x50

150x50

BW

BW

LABEL INFORMATION

10

LETTER

20

SIZE

15IS

20

SF

IS

10 10

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

DESCRIPTION

IDENTIFICATION

DESIGN

LOCATION

FRONT

LABEL

LABEL

RMU

FRONT

FRONT

NEAR

ISOLATOR

CABLE

FEEDER

ISOLATOR

CABLE

DESTINATION

DESTINATION

SIDE W

ALL

INSIDE

BOX

CABLE

APP'D:

CKD:

DRN:

Copyright

R.ENGLISH

R.KROSCH

A.McCOOK

IS

IS

CBA

ACB

SC15982

SC15981

ABC

SC15980

LABEL

CFI fitt

ed b

y m

anufa

cture

r.Not

labelled

UNCONTROLLED COPY

Page 61: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 62: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

NOTES

"' <>

I .

HSS/TAMCO FALCON RMU LABEL

Smm LETTERING --+--2mm LINE SPACING & WARNING

RESTRICTED OPERATING CONDITIONS APPLY

CIRCUIT BREAKER EARTH SWITCH MAY ONLY BE SWITCHED FROM

EARTH ON TO EARTH OFF WHEN THE SWITCHGEAR BUSBAR IS

DE-ENERGISED

80

~+---3mm LETTERING WITH 2mm LINE SPACING

. I

1. Labels to be made from Laminated ABS plastic (1.5mm) or similar. 2. Block lettering on yellow background to warning sign to AS1319 3. Character types to Hel vetica Medium series 'C' to AS/NZS 17 44

egex SCALE NTS NETWORK LABELLING & SIGNAGE APP'D R.English

HV EQUIPMENT LABELLING DATE 28/1012011

([)COPYRIGHT 2011 ENERGEX REC'D G.Towler WARNING LABEL FOR HSS/hmco Falcon RMU CKD P.Relf ORDER FORM

This document must not be reproduced in pnrt or OWN P.Relf

I10891-A41 A whole without written I CAD permission from ENERGEX

UNCONTROLLED COPY

Page 63: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 64: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 65: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Copyright

NETWORK LABELLING & SIGNAGE

11288-A4

HV EQUIPMENT LABELLING

ERL SWITCHCRAFT iGIS KKT RMU (INDOOR)

APP'D:

CKD:

DRN:

B

Copyright

A. SMITH

B. BRUNSMANN

M. BAKKER

DATE: 16/12/2013

ORDER FORM

is installed in a Zone Substation

3. Design I.D and Component I.D lables are only required if the RMU

LOCATION

2. The Feeder Identification Label is only required if the

RMU is the first termination outside a Zone Substation.

DESIGN

1. Labels to be made from GRAVOPLY II (1.5mm) or similiar.

ERL SWITCHCRAFT iGIS KKT RMU

STATION No.

PROJECT No.

See N

ote

3

DESIGN IDENTIFICATION

eg. +1A

B

See N

ote

3

COMPONENT

IDENTIFICATION

eg. RM1

eg. UVW to A

BC/ACB/CBA

PHASE C

ONNECTION

LABELS NOTES

LABEL

150x40

SIZE

DESTINATION L

ABEL

OPERATIONAL ISOLATOR

IDENTIFICATION

eg. IS57 o

r SF58

eg. TO ISXXXX S

CXXXX

FEEDER IDENTIFICATION

LABEL INFORMATION

FRONT V

IEW

SIZE

LETTER

20

LABEL

COLOUR

WB

eg. EMP2 S

ee n

ote

2

SIDE V

IEW

IDENTIFICATION

LABEL

FRONT

LOCATION

LABEL

DESCRIPTION

RMU

50x20

100x40

150x40

150x50

150x50

201510

BLUE W

WB

BW

IS

1010BW

BW

ISSF

CABLE

CABLE

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

ISOLATOR

NEAR

FRONT

FRONT

FEEDER

OPERATIONAL

DESTINATION

DESTINATION

BOX

INSIDE

SIDE W

ALL

CABLE

eg. TO P

XXXXX V

IA

DESTINATION L

ABEL

11kV B

US A

T S

CXXXX

CFI fitt

ed b

y m

anufa

cture

r.

FRONT P

ANEL

ISIS

SF

DANGER L

ABEL B

Y M

ANUFACTURER

APP'D:

CKD:

DRN:

A.SMITH

B.BRUNSMANN

B.BRUNSMANN

EARTH S

WITCH L

ABEL

ADDED

EARTH S

WITCH

DESCRIPTION

eg. EARTH S

WITCH F

OR IS57

100x30

8GW

DESCRIPTION

EARTH S

W

NEAR

EARTH S

WITCH

AORIGINAL ISSUE

CBA

ACB

SC15

982

SC15

981

ABC

SC15

980

LABEL

UNCONTROLLED COPY

Page 66: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Copyright

NETWORK LABELLING & SIGNAGE

11289-A4

HV EQUIPMENT LABELLING

ERL SWITCHCRAFT iGIS KKK THREE WAY SWITCH (OUTDOOR)

ORDER FORM

ERL SWITCHCRAFT iGIS KKK THREE WAY SWITCH (OUTDOOR)

1. Labels to be made from GRAVOPLY II (1.5mm) or similiar.

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

3. Design I.D and Component I.D lables are only required if the RMU

is installed in a Zone Substation

PROJECT No.

STATION No.

eg. +1A

BDESIGN IDENTIFICATION

See N

ote

3

11kV B

US A

T S

CXXXX

DESTINATION L

ABEL

eg. TO P

XXXXX V

IA

PHASE C

ONNECTION L

ABELS

eg. UVW to A

BC/ACB/CBA

eg. RM1

COMPONENT IDENTIFICATION

See N

ote

3

NOTES

See n

ote

2

OPERATIONAL ISOLATOR

FEEDER IDENTIFICATION

eg. EMP2

FRONT V

IEW

eg. TO ISXXXX S

CXXXX

eg. IS57 o

r SF58

IDENTIFICATION

DESTINATION L

ABEL

SIDE V

IEW

LOCATION

BLUE W

50x20

150x40

LABEL

LABEL

SIZE

WB

COLOUR

150x40

100x40

WB

BW

150x50

150x50

BW

BW

LABEL INFORMATION

10

LETTER

20

SIZE

15IS

20

ISIS

10 10

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

DESCRIPTION

IDENTIFICATION

DESIGN

LOCATION

FRONT

LABEL

LABEL

RMU

FRONT

FRONT

NEAR

ISOLATOR

CABLE

FEEDER

ISOLATOR

CABLE

DESTINATION

DESTINATION

SIDE W

ALL

INSIDE

BOX

CABLE

APP'D:

CKD:

DRN:

A

Copyright

A. SMITH

B. BRUNSMANN

M. BAKKER

ORIGINAL ISSUE

CFI fitt

ed b

y m

anufa

cture

r.

PANEL F

RONT

ISIS

IS

DANGER L

ABEL B

YMANUFACTURER

APP'D:

CKD:

DRN:

A.SMITH

B.BRUNSMANN

B.BRUNSMANN

BDATE: 16/12/2013

EARTH S

WITCH L

ABEL

ADDED

EARTH S

WITCH

eg. EARTH S

WITCH F

OR IS57

DESCRIPTION

IDENTIFICATION

NEAR

EARTH S

W

EARTH S

WITCH

100x30

GW

8

CBA

ACB

SC15

982

SC15

981

ABC

SC15

980

LABEL

UNCONTROLLED COPY

Page 67: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Copyright

NETWORK LABELLING & SIGNAGE

11290-A4

HV EQUIPMENT LABELLING

ERL SWITCHCRAFT iGIS KKTT RMU (indoor)

ORDER FORMAPP'D:

CKD:

DRN:

A

Copyright

A. SMITH

B. BRUNSMANN

M. BAKKER

ORIGINAL ISSUE

ERL SWITCHCRAFT iGIS KKTT RMU (indoor)

1. Labels to be made from GRAVOPLY II (1.5mm) or similiar.

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

3. Design I.D and Component I.D lables are only required if the RMU

is installed in a Zone Substation

PROJECT No.

STATION No.

NOTES

LOCATION

BLUE W

50x20

150x40

LABEL

LABEL

SIZE

WB

COLOUR

150x40

100x40

WB

BW

150x50

150x50

BW

BW

LABEL INFORMATION

10

LETTER

20

SIZE

15IS

20

ISSF

10 10

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

DESCRIPTION

IDENTIFICATION

DESIGN

LOCATION

FRONT

LABEL

LABEL

RMU

FRONT

FRONT

NEAR

ISOLATOR

CABLE

FEEDER

OPERATIONAL

CABLE

DESTINATION

DESTINATION

SIDE W

ALL

INSIDE

BOX

CABLE

SF

11kV B

US A

T S

CXXXX

eg. TO P

XXXXX V

IA

eg. TO ISXX S

CXX

eg. +1A

B S

ee N

ote

3

DESIGN IDENTIFICATION

DESTINATION L

ABEL

PHASE C

ONNECTION L

ABELS

eg. UVW t

o A

BC/ACB/CBA

eg. RM1 See N

ote

3

COMPONENT IDENTIFICATION

EARTH S

WITCH

FEEDER IDENTIFICATION

eg. EMP2 S

ee n

ote

2

eg. EARTH S

WITCH F

OR IS57

DESCRIPTION

DESTINATION L

ABEL

CFI fitt

ed b

y m

anufa

cture

r.FRONT V

IEW

DANGER L

ABEL

BY M

ANUFACTURER

SIDE V

IEW

PANEL F

RONT

APP'D:

CKD:

DRN:

A. SMITH

B. BRUNSMANN

B. BRUNSMANN

BDATE: 16

/12/2013

EARTH S

WITCH L

ABEL

ADDED

OPERATIONAL ISOLATOR

eg. IS57 o

r SF58

IDENTIFICATION

DESCRIPTION

NEAR

EARTH S

W

EARTH S

WITCH

100x30

GW

8

CBA

ACB

SC15

982

SC15

981

ABC

SC15

980

LABEL

UNCONTROLLED COPY

kd048
Typewritten Text
kd048
Typewritten Text
kd048
Typewritten Text
Page 68: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

Copyright

NETWORK LABELLING & SIGNAGE

11291-A4

HV EQUIPMENT LABELLING

ERL SWITCHCRAFT iGIS MESH SWITCHGEAR

2 TRANSFORMER UNIT (VTTV) ORDER FORM

ERL SWITCHCRAFT iGIS MESH SWITCHGEAR - 2 TRANSFORMER UNIT (VTTV)

PROJECT No.

STATION No.

LOCATION

APP'D:

CKD:

DRN:AORIGINAL ISSUE

Copyright

A. SMITH

B. BRUNSMANN

M. BAKKER

BLUE W

50x20

LABEL

LABEL

SIZE

COLOUR

170x40

100x40

WB

BW

150x50

150x50

BW

BW

LABEL INFORMATION

10

LETTER

SIZE

15 20 10 10

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

DESCRIPTION

DESIGN

LOCATION

LABEL

FRONT

FRONT

NEAR

CB

CABLE

FEEDER

OPERATIONAL

CABLE

DESTINATION

DESTINATION

SIDE W

ALL

INSIDE

BOX

CABLE

150x50

BW

10

FRONT

CABLE

CABLE

DESTINATION

BOX

REAR

100x40

WB

15IDENTIFICATION

NEAR

ISOLATOR

OPERATIONAL

1. Labels to be made from GRAVOPLY II (1.5mm) or similiar.

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

3. This label is not required for feeders terminating in the same substation.

For example, a feeder used to connect two switchboards together in the same room.

NOTES

CB

CB

ISSF

ISSF

DESIGN IDENTIFICATION

eg. +1A

02

PHASE C

ONNECTION L

ABEL

eg. UVW t

o A

BC/ACB/CBA

OPERATIONAL IDENTIFIER(S)

Examples:

For

CB U

nits, CB2232 &

IS2239

For

SF U

nits, SF1T

49

FEEDER IDENTIFICATION

eg. CSTQEA23 (see n

ote

3).

DESTINATION L

ABEL

Examples:

For

CB U

nits, TO C

BXXXX S

SXXXX

For

SF U

nits, TO T

R1

CBA

ACB

SC15

982

SC15

981

ABC

SC15

980

LABEL

(4 L

ABELS)

CB

SF

SF

CB

DANGER L

ABEL B

YMANUFACTURER

EARTH S

WITCH

DESCRIPTION

eg. EARTH S

WITCH F

OR IS57

100x30

GW

8DESCRIPTION

NEAR

EARTH S

W

EARTH S

WITCH

APP'D:

CKD:

DRN:

A.SMITH

B.BRUNSMANN

B.BRUNSMANN

BDATE: 18

/12/2013

EARTH S

WITCH L

ABEL

ADDED

-

Sto

ckCode

UNCONTROLLED COPY

Page 69: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

ORIGINAL ISSUE

Copyright

NETWORK LABELLING & SIGNAGE

11292-A4

HV EQUIPMENT LABELLING

ERL SWITCHCRAFT MESH SWITCHGEAR

3 TRANSFORMER UNIT (VTTTV) ORDER FORM

ERL SWITCHCRAFT iGIS MESH SWITCHGEAR - 3 TRANSFORMER UNIT (VTTTV)

PROJECT No.

STATION No.

LOCATION

A

Copyright

A. SMITH

B. BRUNSMANN

M. BAKKER

1. Labels to be made from GRAVOPLY II (1.5mm) or similiar.

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

3. This label is not required for feeders terminating in the same substation.

For example, a feeder used to connect two switchboards together in the same room.

NOTES

FEEDER IDENTIFICATION

eg. CSTQEA23 (see n

ote

3).

DESTINATION L

ABEL

Examples:

For

CB U

nits, TO C

BXXXX S

SXXXX

For SF U

nits, TO T

R1

DESIGN IDENTIFICATION

eg. +1A

02

PHASE C

ONNECTION L

ABEL

eg. UVW t

o A

BC/ACB/CBA

OPERATIONAL IDENTIFIER(S)

Examples:

For

CB U

nits, CB2232 &

IS2239

For

SF U

nits, SF1T

49

BLUE W

50x20

LABEL

LABEL

SIZE

COLOUR

170x40

100x40

WB

BW

150x50

150x50

BW

BW

LABEL INFORMATION

10

LETTER

SIZE

15 20 10 10

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

DESCRIPTION

DESIGN

LOCATION

FRONT

FRONT

NEAR

CB

CABLE

FEEDER

OPERATIONAL

CABLE

DESTINATION

DESTINATION

SIDE W

ALL

INSIDE

BOX

CABLE

150x50

BW

10

FRONT

CABLE

CABLE

DESTINATION

BOX

REAR

100x40

WB

15IDENTIFICATION

NEAR

ISOLATOR

OPERATIONAL

CB

CB

ISSF

ISSF

SF

(5 L

ABELS)

CBA

ACB

SC15

982

SC15

981

ABC

SC15

980

LABEL

CB

SF

SF

SF

CB

DANGER L

ABEL B

YMANUFACTURER

EARTH S

WITCH

DESCRIPTION

eg. EARTH S

WITCH F

OR IS57

A.SMITH

B.BRUNSMANN

B.BRUNSMANN

DATE: 10

/01/2014

B

EARTH S

WITCH L

ABEL

ADDED

-

100x30

GW

8DESCRIPTION

NEAR

EARTH S

W

EARTH S

WITCH

Sto

ckCode

UNCONTROLLED COPY

Page 70: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

AORIGINAL ISSUE

Copyright

NETWORK LABELLING & SIGNAGE

11293-A4

HV EQUIPMENT LABELLING

ERL SWITCHCRAFT iGIS MESH SWITCHGEAR

3 TRANSFORMER UNIT (VTTVT-V) ORDER FORM

ERL SWITCHGEAR iGIS MESH SWITCHGEAR - 3 TRANSFORMER UNIT (VTTVT-V)

1. Labels to be made from GRAVOPLY II (1.5mm) or similiar.

RMU is the first termination outside a Zone Substation.

2. The Feeder Identification Label is only required if the

3. This label is not required for feeders terminating in the same substation.

For example, a feeder used to connect two switchboards together in the same room.

PROJECT No.

STATION No.

NOTES

LOCATION

BLUE W

50x20

LABEL

LABEL

SIZE

COLOUR

170x40

100x40

WB

BW

150x50

150x50

BW

BW

LABEL INFORMATION

10

LETTER

SIZE

15CB

20

CB

10 10

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

DESCRIPTION

DESIGN

LOCATION

LABEL

FRONT

FRONT

NEAR

CB

CABLE

FEEDER

OPERATIONAL

CABLE

DESTINATION

DESTINATION

SIDE W

ALL

INSIDE

BOX

CABLE

Copyright

A. SMITH

B. BRUNSMANN

M.BAKKER

150x50

BW

10

FRONT

CABLE

CABLE

DESTINATION

BOX

REAR

CB

FEEDER IDENTIFICATION

eg. CSTQEA23 (see n

ote

3).

DESIGN IDENTIFICATION

eg. +1A

02

PHASE C

ONNECTION L

ABEL

eg. UVW t

o A

BC/ACB/CBA

DESTINATION L

ABEL

Examples:

For

CB U

nits, TO C

BXXXX S

SXXXX

For SF U

nits, TO T

R1

OPERATIONAL IDENTIFIER(S)

Examples:

For

CB U

nits, CB2232 &

IS2239

For

SF U

nits, SF1T

49

100x40

WB

15IDENTIFICATION

NEAR

ISOLATOR

OPERATIONAL

ISIS

ISSF

SF

SF

(6 L

ABELS)

CBA

ACB

SC15

982

SC15

981

ABC

SC15

980

LABEL

CB

SF

SF

CB

SF

CB

DANGER L

ABEL B

YMANUFACTURER

A. SMITH

B. BRUNSMANN

M.BAKKER

BDATE: 20/12/2013

EARTH S

WITCH L

ABEL

ADDED

-

GW

100x30

8DESCRIPTION

NEAR

EARTH S

W

EARTH S

WITCH

EARTH S

WITCH

DESCRIPTION

eg. EARTH S

WITCH F

OR IS57

Sto

ckCode

UNCONTROLLED COPY

Page 71: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

AORIGINAL ISSUE

Copyright

NETWORK LABELLING & SIGNAGE

11294-A4

HV EQUIPMENT LABELLING

ERL SWITCHCRAFT iGIS KKKT RMU

ORDER FORM

ERL SWITCHCRAFT iGIS KKKT RMU

1. Labels to be made from GRAVOPLY II (1.5mm) or similiar.

RMU is the first termination outside a Zone Substation.2. The Feeder Identification Label is only required if the

3. Design I.D and Component I.D lables are only required if the RMU

is installed in a Zone Substation

PROJECT No.

STATION No.

eg. +1A

B

DESIGN IDENTIFICATION

See N

ote

3

11kV B

US A

T S

CXXXX

DESTINATION L

ABEL

eg. TO P

XXXXX V

IA

PHASE C

ONNECTION L

ABELS

eg. UVW t

o A

BC/ACB/CBA

eg. RM1

COMPONENT IDENTIFICATION

See N

ote

3

NOTES

See n

ote

2

OPERATIONAL ISOLATOR

FEEDER IDENTIFICATION

eg. EMP2

eg. TO ISXXXX S

CXXXX

eg. IS57 o

r SF58

IDENTIFICATION

DESTINATION L

ABEL

SIDE V

IEW

LOCATION

BLUE W

50x20

150x40

LABEL

LABEL

SIZE

WB

COLOUR

150x40

100x40

WB

BW

150x50

150x50

BW

BW

LABEL INFORMATION

10

LETTER

20

SIZE

15IS

20

ISIS

10 10

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

DESCRIPTION

IDENTIFICATION

DESIGN

LOCATION

FRONT

LABEL

LABEL

RMU

FRONT

FRONT

NEAR

ISOLATOR

CABLE

FEEDER

ISOLATOR

CABLE

DESTINATION

DESTINATION

SIDE W

ALL

INSIDE

BOX

CABLE

APP'D:

CKD:

DRN:

Copyright

A. SMITH

B. BRUNSMANN

M. BAKKER

SF

CFI fitt

ed b

y m

anufa

cture

r.

PANEL F

RONT

FRONT V

IEW

ISIS

ISSF

DANGER L

ABEL B

Y

MANUFACTURER

APP'D:

CKD:

DRN:

A.SMITH

B.BRUNSMANN

B.BRUNSMANN

BDATE: 10/01/2014

EARTH S

WITCH

eg. EARTH S

WITCH F

OR IS57

DESCRIPTION

GW

100X30

8DESCRIPTION

EARTH S

WITCH

NEAR

EARTH S

W

EARTH S

WITCH L

ABEL

ADDED

-

CBA

ACB

SC15

982

SC15

981

ABC

SC15

980

LABEL

Sto

ckco

de

UNCONTROLLED COPY

kd048
Typewritten Text
kd048
Typewritten Text
Page 72: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

LOW VOLTAGE URD Go to SECTION INDEX Back to MAIN INDEX

Standard for Network Labelling and Signage

Page 73: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 74: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 75: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 76: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 77: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 78: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 79: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 80: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 81: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 82: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

LOW VOLTAGE C&I Go to SECTION INDEX Back to MAIN INDEX

Standard for Network Labelling and Signage

Page 83: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 84: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 85: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 86: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 87: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 88: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 89: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 90: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 91: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

LOW VOLTAGE EQUIPMENT Go to SECTION INDEX Back to MAIN INDEX

Standard for Network Labelling and Signage

Page 92: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 93: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 94: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 95: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 96: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 97: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 98: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 99: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 100: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 101: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 102: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 103: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 104: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

This document must not be

whole without writtenpermission from ENERGEX

reproduced in part or DWN

APP'D

DWN

CKD

DATE

REC'D

CKD

DATE

SCALE

APP'D

K. POULSEN

A ORIGINAL

B.BRUNSMANN

B.BRUNSMANN

09/01/14

A.SMITH

NTS

11133-A4 A

NETWORK LABELLING & SIGNAGELV EQUIPMENT LABELLING TYPICAL

NOJA CABINETS

LV DISTRIBUTION SUPPLY CABINETS

UPPER REMOVABLE PANEL

LOWER REMOVABLE PANELGROUND LEVEL

For all enquires telephone 13 12 53

STOCKCODE

22873

22878

11621 ... 11630

FITTED BY REMARKS

MANUFACTURER

MANUFACTURER

TO TOP OF LEFT DOOR (1 OFF)

MANUFACTURER

TO TOP OF RIGHT DOOR

INSTALLER

USE "3M" 220 BLACK SCOTCH

CAST VINYL NUMBERS 25mm HIGH

SIGN

PLACE ON

ENERGEX LABEL

UNDER LOGO

NUMERALS"1-10"

TEXT: ARIAL 15mm

TEXT: ARIAL 4mm180

100

For all enquires telephone 13 12 53

180

100

60

15

SUPPLIED BY

MANUFACTURER

UNCONTROLLED COPY

Page 105: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

This document must not be

whole without writtenpermission from ENERGEX

reproduced in part or DWN

APP'D

DWN

CKD

DATE

REC'D

CKD

DATE

SCALE

APP'D

K. POULSEN

A ORIGINAL

B.BRUNSMANN

B.BRUNSMANN

09/01/14

A.SMITH

NTS

11134-A4 A

NETWORK LABELLING & SIGNAGELV EQUIPMENT LABELLING TYPICAL

SUPPLY CABINETS ORDER FORM

LV SW/BD FOR LV DISTRIBUTION

LABEL INFORMATION

3

4

2

WB80x35

80x35 WB

80x35 WB

5

5

5

No.

CIRCUIT

1 80x35 WB

LABEL

SIZE COLOUR

LABEL

5

LETTER

SIZE

PROJECT No.

STATION No.

LOCATION

LV DISTRIBUTION SUPPLY CABINETS LV SWBD - SWITCH FUSE CIRCUITS

DUPLICATE LABELS NOTE:

FOR IEC/DIN TYPE SWITCHGEAR A LABEL MOUNTING STRIP IS SUPPLIED FOR MOUNTING ON THE BASE OF

SWITCHBOARD FRAME. THE LABEL MOUNTING STRIP TO BE MARKED WITH DUPLICATE (ADDITIONAL TO PRIMARY

LABELS AS ABOVE) ABS PLASTIC LABELS TO CORRELATE WITH THE CIRCUIT/FUSE SWITCH DISCONNECTOR

MANUFACTURERS LABEL POSITION.

7

8

6

WB80x35

80x35 WB

80x35 WB

5

5

5

5 80x35 WB 5

eg. TO BROWN ST. LP1219 & SERVICES

eg. TO LYTTON RD. P4789

LV FEEDER DESTINATION

PLEASE SEE DUPLICATE LABELS NOTE BELOW

FRONT (DOOR OPEN)

PRIMARY LABEL NOTE

FOR IEC/DIN TYPE LV SWITCHGEAR, POSITION LABELS

ON THE STRIP FUSES/ISOLATER IN APPROPRIATE

POSITION AS PROVIDED BY MANUFACTURER.

UNCONTROLLED COPY

Page 106: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

POLE & POLE MOUNTED EQUIPMENT Go to SECTION INDEX Back to MAIN INDEX

Standard for Network Labelling and Signage

Page 107: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 108: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 109: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 110: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 111: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 112: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 113: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 114: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 115: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 116: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 117: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 118: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 119: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 120: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 121: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 122: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

UNCONTROLLED COPY

Page 123: Standard for Network Labelling and Signage...Standard for Network Labelling and Signage If this standard is a printed version, to ensure compliance, reference must be made to the Ergon

MISCELLANEOUS Go to SECTION INDEX Back to MAIN INDEX

Standard for Network Labelling and Signage