STANDARD DRAWINGS Application of Standard Drawings ...

145
STANDARD DRAWINGS Application of Standard Drawings The standard drawings below shall be used in the design and construction of public improvements in the City of Beaverton. Disclaimer and Design Engineer’s Responsibilities The standard drawings are not to scale, are schematic in nature, and may not be suitable “as is” for a specific use or location. Therefore, it is the Design Engineer’s responsibility to ensure that all of the design components in a standard drawing are suitable for: the use intended, each specific location, and safe use by the general public. In addition, the sizes of, locations of, and spaces between the components must all be sufficient to meet all project requirements and the City’s operational and maintenance requirements. Requirements for Modification of a Standard Drawing All modified standard drawings and supplemental drawings shall have the City’s title block, logo, block information, drawing title and number removed, and shall bear the seal of the Design Engineer responsible for modifying or preparing them, respectively. If the City’s title for a standard drawing is re- used on a modified standard drawing, the word “(MODIFIED)” in all upper case letters and enclosed in parentheses as shown, shall be added at the end of the title. In addition, it is the Design Engineer’s responsibility to modify and/or supplement the standard drawings with technical specifications and additional drawings as necessary to provide a complete, properly functioning project that conforms in all respects to the City’s requirements.

Transcript of STANDARD DRAWINGS Application of Standard Drawings ...

Page 1: STANDARD DRAWINGS Application of Standard Drawings ...

STANDARD DRAWINGS Application of Standard Drawings The standard drawings below shall be used in the design and construction of public improvements in the City of Beaverton.

Disclaimer and Design Engineer’s Responsibilities The standard drawings are not to scale, are schematic in nature, and may not be suitable “as is” for a specific use or location. Therefore, it is the Design Engineer’s responsibility to ensure that all of the design components in a standard drawing are suitable for: the use intended, each specific location, and safe use by the general public. In addition, the sizes of, locations of, and spaces between the components must all be sufficient to meet all project requirements and the City’s operational and maintenance requirements.

Requirements for Modification of a Standard Drawing All modified standard drawings and supplemental drawings shall have the City’s title block, logo, block information, drawing title and number removed, and shall bear the seal of the Design Engineer responsible for modifying or preparing them, respectively. If the City’s title for a standard drawing is re-used on a modified standard drawing, the word “(MODIFIED)” in all upper case letters and enclosed in parentheses as shown, shall be added at the end of the title. In addition, it is the Design Engineer’s responsibility to modify and/or supplement the standard drawings with technical specifications and additional drawings as necessary to provide a complete, properly functioning project that conforms in all respects to the City’s requirements.

Page 2: STANDARD DRAWINGS Application of Standard Drawings ...

130 Standard AC Monument Box

131 PCC Monument Box

135 Asphalt Centerline Monuments

136 Concrete Centerline Monuments

137 Gravel Centerline Monuments

138Post-Construction CenterlineMonuments

140 Mailbox Locations

200-1 Minimum Arterial Street Widths

200-2 Minimum Collector Street Widths

200-3Minimum Neighborhood Route Street

Widths

200-4 Minimum Local Street Widths

201 Minimum Cul-De-Sac Standards

202 Offset Crown

203 Interim Turnaround

204 Standard Utility Details

205 Standard Monolithic Curb and Gutter

206 Mountable Curb and Gutter

207 Mountable Curb and Gutter at Vault

208 Type A" Replacement Curb"

209Retrofit Curb Cuts in Existing Curb andGutter

210 Standard Commercial Driveway

211 Standard Residential Driveway

215 Standard Sidewalk

216 Curb Tight Sidewalk

217Standard to Curb Tight SidewalkTransition

220 Curb Extension

221 Future Street Extension Sign

231 Retrofit Single Sidewalk Ramp with

Planter Strip

233 Retrofit Curb Tight Single Sidewalk Ramp

240 Standard Sidewalk Treewell

241 Curb Tight Sidewalk Treewell with Grate

242 Treewell Irrigation

245 Asphaltic Concrete Speed Hump

246 Asphaltic Concrete Speed Table

250 Asphaltic Concrete Speed Hump with

Median Island

251 Asphaltic Concrete Speed Table with

Median Island

255 Speed Table with Crosswalk

256 Speed Table with Crosswalk and Median

Island

260 Traffic Circle

270 Standard Block Wall

220-1 Concrete Roadways

220-2 Manhole and Inlet Concrete Boxouts

250-3 Concrete Roadway Repair

300 Pipe Trench Backfill

301 Conduit Trench Backfill

302 Pavement Cut Restoration

305 Street Cut in PCC Pavement

Perpendicular or Skewed to Centerline

306 Street Cut in PCC Pavement Parallel to

Centerline

310 Corrective AC Pavement Inlay Example

"A-1" for Utility Cut

311 Corrective AC Pavement Inlay Example

"A-2" for Utility Cut

312 Corrective AC Pavement Inlay Example

"A-3" for Utility Cut

313 Corrective AC Pavement Inlay Example

"B-1" for Utility Cut

Standard Drawings Index

Sheet

Number

Sheet

Title

Sheet

Number

Sheet

Title

Page 3: STANDARD DRAWINGS Application of Standard Drawings ...

314 Corrective AC Pavement Inlay Example

"B-2" for Utility Cut

315 Corrective AC Pavement Inlay Example

"B-3" for Utility Cut

320 Manhole Adjustment Sequence Option 1

321 Manhole Adjustment Sequence Option 2

330 CWS Standard Manhole with C.O.B.

Modifications

331 Manhole Connections

335 CWS Flat Top Manhole with C.O.B.

Modifications

336 Shallow Manhole Cone

340 Standard Cleanout in Existing Street

345 Curb Inlet Catch Basin with C.O.B.

Modifications

350 Gravity Pipe Anchor

360 CWS Flow Control Structure with C.O.B.

Modifications

370 CWS Streetside LIDA Planter (No Street

Parking)

371 CWS Streetside LIDA Planter with Street

Parking

510 Rock Flow Spreader for WQ Swale

520 PVC Gasketed Saddle

400 Typical Sign Assembly

405 Typical Sign Locations

407 No Parking Signs

410 Street Name Sign 4 Inch Tall Letters

411 Street Name Sigh 6 Inch Tall Letters

412 Block Number Plate Mounting

416 Private Street Sign

417 Private Driveway Sign

420 Crosswalk Closure Barricade

425 Loop Wire Entrance Sand Pocket

430 Pedestrian Push Button Post

435 Street Barricade - Type III

436 Street Barricade - Type III at WideTransitions

700 Typical Shared-Use Path

705 Mid-Block Pedestrian Crossing

710 Vehicle Barrier Locations & FenceOpenings

715 Removable Vehicle Barrier Post

620-1 Typical Water Line Trench Backfill

630-1 Typical Water Line & Fire HydrantLocation

630-2 Tapping Sleeve

630-3 2" Standard Blow-Off Assembly -Permanent

630-4 2" Blow-Off Assembly for FutureExtension

630-5 4" Blow-Off Assembly for FutureExpansion

630-6 2" Automatic Flushing Device (for Future

Extension)

630-7 2" Automatic Flushing Device

630-8 Straddle Blocks

630-9 Thrust Blocks

640-1 Typical Water Valve Location

640-2 Typical Standard Valve Box Setting

640-3 High Volume Traffic Lid for 910 Series

Valve Box

640-4 Valve Operator Extension

640-5 ¾" or 1" Combination Air and Vacuum

Valve (CARV) Below Grade

640-6 ¾" or 1" Combination Air and Vacuum

Valve (CARV) at Grade

640-7 ¾" or 1" Air Release Valve (ARV)

Standard Drawings Index

Sheet

Number

Sheet

Title

Sheet

Number

Sheet

Title

Page 4: STANDARD DRAWINGS Application of Standard Drawings ...

640-8 2" Combination Air & Vacuum Valve

(CARV)

650-1 Fire Hydrant Clear Zone

650-2 Fire Hydrant Assembly Installation

650-3 Fire Hydrant Assembly Flange Joint

Installation

650-4 Typical Hydrant Marker Locations

660-1 Service Abandonment

660-2 Sampling Station Installation

660-3 1" Service Connection

660-4 1½" and 2" Irrigation Service Connection

660-5 1½" and 2" Service Connection

670-1 Vault Ladder Installation

670-2 Sump Pump Installation

670-3 Compound Water Meter Vault

680-1 Electrolysis Test Station Wire Installation

680-2 Terminal Board Test Station - Types A-D

680-3 Polyethylene Encasement for DIP

680-4 Protective Geomembrane Sleeve Wrap

for Crossing Cathodically ProtectedPipes

680-5 Protective Sleeve Slip-On for Crossing

Cathodically Protected Pipes

680-6 Combined CP Test Station Above Grade

Installation Details

680-7 Combined CP Test Station Below Grade

Installation Details

680-8 General Corrosion Control Details

680-9 Bonding Of DIP Joints and Fittings

680-10 Dielectric Isolation Joints

690-1 Cross Connection Protection for Tanker

Trucks

690-2A Backflow Preventer for ResidentialIrrigation Systems

690-2B Backflow Preventers for ResidentialIrrigation Systems

690-3A ¾" or 1" Double Check Valve Assembly

(DC)

690-3B 1¼" to 2" Double Check Valve Assembly

(DC)

690-4A 3" and Larger Double Check Valve

Assembly (DC)

690-4B 3" and Larger Double Check Valve

Assembly (Detail Notes)

690-5A 3" and Larger Double Check Detector

Assembly

690-5B 3" and Larger Double Check Detector

Assembly

690-5C 3" and Larger Double Check Detector

Assembly (Detail Notes)

690-6 ¾" to 2" Reduced Pressure Backflow

Assembly (RP) Above Ground

690-7 ¾" to 2" Reduced Pressure Backflow

Assembly (RP) in Berm

690-8 3" to 10" Reduced Pressure Backflow

Assembly (RP) Above Ground

690-9 3" to 10" Reduced Pressure Backflow

Assembly (RP) in Berm

690-10 Reduced Pressure Backflow Assembly

(RP) Discharge Rates

690-11 2" PRV at N-C Pressure Zone Break

Standard Drawings Index

Sheet

Number

Sheet

Title

Sheet

Number

Sheet

Title

Page 5: STANDARD DRAWINGS Application of Standard Drawings ...

1. Standard monument box for AC pavement shall be cast iron with 8-inch minimum inside diameter,

Olympic Foundry # M1014 or equal.

2. Matching monument box cover shall be cast iron with MON or MONUMENT cast into the top face,

Olympic Foundry # 14 - 6169 or equal.

3. New manholes are to be located a minimum of 4 feet from center of its base to monument box.

4"

5/8"

NOTES:

13 5/8" Ø

8 1/4" Ø

BOX SECTION

7 5/8" Ø

11" Ø

COVER

9 5/8" Ø

8"

SCALE: NONE

DATE: JUNE 2018

STANDARD AC MONUMENT

BOX130

Page 6: STANDARD DRAWINGS Application of Standard Drawings ...

5/8"

2 3/8"

1. Monument box for PCC pavement shall be cast iron with 8 inch minimum inside diameter, Olympic

Foundry # M1015 or equal.

2. Matching monument box cover shall be cast iron with MON or MONUMENT cast into the top face,

Olympic Foundry # 14 - 6174 or equal.

3. New manholes are to be located a minimum of 4 feet from center of its base to monument box.

NOTES:

8" Ø

11 3/8" Ø

BOX SECTION

3/4"

3/4"

1 1/2"

10 1/2" Ø

7 1/2" Ø

3/4"

COVER

9 1/4" Ø

1"Ø

3/8" Ø

9"

SCALE: NONE

DATE: JUNE 2018PCC MONUMENT BOX 131

Page 7: STANDARD DRAWINGS Application of Standard Drawings ...

AC PAVEMENT

METAL CAP

POINT ON TANGENT

1. All monuments shall use either 5 8 inch Ø x 30 inches long iron rod or 3 4 inch Ø x 30 inches long iron pipe.

2. All monuments shall be in accordance with the Oregon Revised Statutes Chapters 92 and 209.

3. For post-construction monumentation on existing asphalt surfaces, see Beaverton Standard

Dwg 138.

CENTERLINES

NOTES:

SEE NOTE 1

NATIVE

GROUND

METAL CAP

RAISE

1"

BASE COURSE

AC PAVEMENT

STANDARD AC MONUMENT BOX

SEE Beaverton Standard

Dwg 130

SEE NOTE 1

NATIVE

GROUND

BASE

COURSE

DEPRESS 1/2"

SCALE: NONE

DATE: JUNE 2018

ASPHALT CENTERLINE

MONUMENTS135

Page 8: STANDARD DRAWINGS Application of Standard Drawings ...

1. All monuments shall use either 5 8 inch Ø x 30 inches long iron rod or 3 4 inch Ø x 30 inches long iron pipe.

2. All monuments shall be in accordance with the Oregon Revised Statutes Chapters 92 and 209.

3. Place 3 - 2"x2" spacers, cut from 2" concrete patio block, evenly spaced to match finish grade.

4. For post-construction monumentation on existing asphalt surfaces, see Beaverton Standard Dwg 138.

POINT ON TANGENT

6" LENGTH OF 6" Ø THINWALL

PVC PIPE EXTENDING 1"

BELOW SPACER BLOCKS

2" SPACER BLOCK

SEE NOTE 3

SEE NOTE 1

NOTES:

CENTERLINES

SUBGRADE

COMPACTED

TO MIN 95%

METAL CAP SET AT

MIDPOINT OF BOX

BASE COURSE

(IF REQUIRED)

COMPACTED

TO MIN 95%

PCC PAVEMENT

2"

PCC

PAVEMENT

PCC MONUMENT BOX

SEE Beaverton Standard

Dwg 131

SEE NOTE 1

BASE

COURSE

NATIVE

GROUND

DEPRESS 1/2"

METAL CAP

SCALE: NONE

DATE: JUNE 2018

CONCRETE CENTERLINE

MONUMENTS136

Page 9: STANDARD DRAWINGS Application of Standard Drawings ...

NATIVE GROUND

1. All monuments shall use either 5 8 inch Ø x 30 inches long iron rod or 3 4 inch Ø x 30 inches long iron pipe.

2. All monuments shall be in accordance with the Oregon Revised Statutes Chapters 92 and 209.

NOTES:

CENTERLINES

METAL

CAP

SEE NOTE 1

SURFACE COURSE

BASE COURSE

SCALE: NONE

DATE: JUNE 2018

GRAVEL CENTERLINE

MONUMENTS137

Page 10: STANDARD DRAWINGS Application of Standard Drawings ...

METAL CAP SET AT

MIDPOINT OF BOX

PCC COLLAR

2" SPACER BLOCK

SEE NOTE 4

6" LENGTH OF 6" Ø THINWALL

PVC PIPE EXTENDING 1"

BELOW SPACER BLOCKS

1. All monuments shall use either 5 8 inch Ø x 30 inches long iron rod or 3 4 inch Ø x 30 inches long iron pipe.

2. All monuments shall be in accordance with the Oregon Revised Statutes Chapters 92 and 209.

3. Monument box shall be set within a 6 inch wide, round collar of 5,000 psi, high-early Portland

Cement Concrete.

4. Place 3 - 2"x2" spacers, cut from 2" concrete patio block, evenly spaced to match finish grade.

5. For post-monumentation on existing concrete surfaces, core-drill or diamond saw-cut is required.

NATIVE

GROUND

NOTES:

CENTERLINES

SEE NOTE 1

PCC MONUMENT BOX

SEE Beaverton Standard

Dwg 131

BASE COURSE

(IF REQUIRED)

COMPACTED

TO MIN 95%

2"

6"Ø

SUBGRADE

COMPACTED

TO MIN 95%

AC PAVEMENT

BASE COURSE

SCALE: NONE

DATE: JUNE 2018

POST-CONSTRUCTION

CENTERLINE MONUMENTS138

Page 11: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018MAILBOX LOCATIONS 140

NOTES:

1. BOX NUMBERS AND NAMES SHALL NOT BE LESS THAN 1" HIGH

2. POSTS MUST BE OF ADEQUATE STRENGTH AND SIZE

3. ALL MAILBOX LOCATIONS AND CLUSTERS MUST CONFORM TO THE REQUIREMENTS OF THE

UNITED STATES POSTAL SERVICE (USPS)

4. INSTALLATION SHALL COMPLY WITH AASHTO - ROADSIDE DESIGN GUIDE (CHAP 11)

5. FOR STREETS WITH GRAVEL SHOULDERS (NO CURBS), FACE OF MAILBOX SHALL BE SET AT

THE BACK OF THE GRAVEL SHOULDER

6. MAINTAIN 5' MINIMUM CLEAR ZONE AT THE BACK OF THE MAILBOX FOR ADA ACCESS. FOR

EXISTING SIDEWALKS WITHOUT THE 5' MIN CLEAR ZONE, CONSTRUCT ADDITIONAL SIDEWALK

PANELS AT BACK OF SIDEWALK, MINIMUM 3' EACH SIDE OF MAILBOX OR MATCH EXISTING

SIDEWALK PANELS, WHICHEVER IS GREATER. NEW BACK OF SIDEWALK SHALL MEET 5' MIN

CLEAR ZONE REQUIREMENTS. TRANSITION NEW PANELS TO EXISTING WALK WITH 45°

TRIANGULAR SHAPED PANELS

Page 12: STANDARD DRAWINGS Application of Standard Drawings ...

12'11'12'5' 11' 12'11'11' 5'0.5' 0.5'

2.0% TYP

TRAVEL LANE

0.5' 5'

PLANTER

7.5'6'

SIDEWALK

LANEBIKE

SIDEWALK

6'

0.5'

7.5'

BIKELANE

5'

TRAVEL LANE

12'

PLANTER

LANEBIKE

SIDEWALK

0.5'

PLANTER

6' 7.5'

2.0% TYPTRAVEL LANE

5' 12'

TRAVEL LANE

11'

12'12' 5'

62'

PAVED WIDTH

ROW

34'

TRAVEL LANE2.0% TYP

2 LANES

2.0% TYP LANEBIKE

0.5'

SIDEWALK

7.5' 6'

PLANTER

SIDEWALK

68'

3 LANES

PAVED WIDTH

ROW

74'

46'

12'

TRAVEL LANE2.0% TYP

12'

ROW96'

6'7.5'

LANEBIKE

5' 0.5'

PLANTER SIDEWALK

5 LANES

PAVED WIDTH

12'

TRAVEL LANE

11'

ROW

118'

PAVED WIDTH

90'

LANEBIKE

2.0% TYPTRAVEL LANE

12' 5'

PLANTER

7.5'

0.5'

6'

1. A planter strip is required on all Arterials.

2. Paved width and planter strip are measured to face of curb.

3. Provide 0.5 feet from right-of-way line to the back of sidewalk for maintenance and survey monument protection.

4. Street trees and street lights are required and shall be located within the planter strip.

5. Engineer/Designer is required to check for special district design parameters. Contact Community Development -

Planning Division for additional information.

6. Power, street lights, traffic signal, and all other franchise utility boxes/vaults shall be located outside of ADA ramps

& landings.

SIDEWALK

2.0% TYP

TRAVEL LANE

NOTES:

6' 7.5'

PLANTER

BIKELANE

TRAVEL LANE TRAVEL LANE BIKELANE

7 LANES

TURN LANE/MEDIAN TRAVEL LANE

2.0% TYP

TRAVEL LANETRAVEL LANE

SIDEWALK

6'7.5'

PLANTER

SC

ALE

: NO

NE

DA

TE

:JU

NE

2018

MIN

IMU

M A

RTE

RIA

L S

TR

EE

T

WID

TH

S2

00

-1

TURN LANE/MEDIAN

TURN LANE/MEDIAN

Page 13: STANDARD DRAWINGS Application of Standard Drawings ...

7.5'

BIKE

PLANTER

LANETRAVEL LANETRAVEL LANEBIKE

NOTES:

SIDEWALK PLANTER

6' 7.5'

3 LANES

2.0% TYPLANE 2.0% TYP

PLANTER

0.5'

0.5'

6'

SIDEWALK

34'

PAVED WIDTH

2 LANES

PAVED WIDTH

ROW

12'5'

7.5'

BIKELANE

5' 12'

TRAVEL LANE

2.0% TYP

74'

46'

12' 12' 5'

TRAVEL LANE

2.0% TYP

12'

BIKELANE

5'

ROW

62'

SIDEWALKPLANTER

7.5' 6'

0.5'

6'

SIDEWALK

0.5'

SCALE: NONE

DATE: JUNE 2018

MINIMUM COLLECTOR

STREET WIDTHS200-2

1. A planter strip is required on all Collectors.

2. Paved width and planter strip are measured to face of curb.

3. Provide 0.5 feet from right-of-way line to the back of sidewalk for maintenance and

survey monument protection.

4. Street trees and street lights are required and shall be located within the planter strip.

5. Engineer/Designer is required to check for special district design parameters. Contact

Community Development - Planning Division for additional information.

6. Power, street lights, traffic signal, and all other franchise utility boxes/vaults shall be

located outside of ADA ramps & landings.

TURN LANE/MEDIAN

Page 14: STANDARD DRAWINGS Application of Standard Drawings ...

5' SIDEWALK

7.5'

PLANTER

5' SIDEWALK

NOTES:

0.5'

ROW

PAVED WIDTH

NR 3

NO PARKING

PLANTER

7.5'

12'

2.0% TYP

TRAVEL LANE TRAVEL LANE

12'

2.0% TYP

24'

50'

7.5'

PLANTER

5' SIDEWALK

0.5'

5' SIDEWALK

0.5'

PARKING2.0% TYP

TRAVEL LANEPARKING TRAVEL LANE

ROW

PAVED WIDTH

TRAVEL LANE

10'

PARKING BOTH SIDES

NR 1

PARKING ONE SIDE

NR 2

2.0% TYPPARKING

7.5'

PLANTER

8'

PLANTER

7.5'

2.0% TYP

28'

2.0% TYP

10'

TRAVEL LANE

7.5'

PLANTER

54'

PAVED WIDTH

ROW

7' 10'

60'

34'

10' 7'

0.5'

5' SIDEWALK

0.5'

5' SIDEWALK

0.5'

SCALE: NONE

DATE: JUNE 2018

MINIMUM NEIGHBORHOOD

ROUTE STREET WIDTHS200-3

1. A planter strip is required on all Neighborhood Routes.

2. Paved width and planter strip are measured to face of curb.

3. Provide 0.5 feet from right-of-way line to the back of sidewalk for maintenance and

survey monument protection.

4. Street trees and street lights are required and shall be located within the planter strip.

5. Engineer/Designer is required to check for special district design parameters. Contact

Community Development - Planning Division for additional information.

6. Power, street lights, traffic signal, and all other franchise utility boxes/vaults shall be

located outside of ADA ramps & landings.

Page 15: STANDARD DRAWINGS Application of Standard Drawings ...

PLANTER

PLANTER

5'

SIDEWALKSIDEWALK

NOTES:

0.5'

FOR ADT OF 500 VEHICLES PER DAY

NO PARKING

PAVED WIDTH

ROW

2.0% TYP

_<

PLANTER

5' 6.5'

TRAVEL LANE

10'

L 3

TRAVEL LANE

20'

44'

10'

6.5'

PLANTER

PLANTER

SIDEWALK

5'

0.5'

5'

SIDEWALK

0.5'

2.0% TYP2.0% TYP

TRAVEL LANE

L2

PAVED WIDTH

FOR ADT OF 500 VEHICLES PER DAY

ROW

2.0% TYP

PARKING

6.5'

PLANTER

<_

7'

6.5'

PARKING

14'

6.5'

7'

28'

52'

L1

TRAVEL LANE

ROW

PAVED WIDTH

PARKING

7' 10'

TRAVEL LANE

34'

10'

58'

7'

PARKING

0.5'

0.5'

5'

SIDEWALK

SIDEWALK

6.5' 5'

0.5'

SCALE: NONE

DATE: JUNE 2018

MINIMUM LOCAL STREET

WIDTHS200-4

1. A planter strip is required on all Arterials.

2. Paved width and planter strip are measured to face of curb.

3. Provide 0.5 feet from right-of-way line to the back of sidewalk for maintenance and

survey monument protection.

4. Street trees and street lights are required and shall be located within the planter strip.

5. For cul-de-sac requirements, see drawing 201

6. Engineer/Designer is required to check for special district design parameters. Contact

Community Development - Planning Division for additional information.

7. Power, street lights, traffic signal, and all other franchise utility boxes/vaults shall be

located outside of ADA ramps & landings.

Page 16: STANDARD DRAWINGS Application of Standard Drawings ...

1. See drawing 200-4 for Local Street right-of-way and paved width standards.

2. Length of cul-de-sac shall not exceed 200 feet.

3. On a cul-de-sac serving only residential uses and having no more than five abutting

residential units, the dimensions of the cul-de-sac bulb may be reduced to provide:

a. a minimum 24 foot radius to face of curb,

b. a minimum 30 foot radius to right of way,

c. a minimum 5 foot wide curb tight sidewalk (measured from back of curb) with

easements for street trees and street lighting outside of the right of way.

4. Refer to USPS standards for Cluster Box Unit (CBU). Preferred location of CBUs shall

be in cul-de-sac throat.

25' RADIUS

RIGHT-OF-WAY

SEE NOTE 1

PAVED WIDTH

SEE NOTE 1

NOTES:

0.5'

WAY

RIGHTOF

57' R

AD

IUS

RIG

HT-O

F-W

AY

6.5' PLANTER STRIP

25' RADIUS

5' SIDEWALK

45' RADIUSTO FACE OF CURB

TO

TH

E N

EA

R S

IDE

RIG

HT

-OF

-WA

Y O

F I

NT

ER

SE

CT

ING

ST

RE

ET

LE

NG

TH

OF

CU

L-D

E-S

AC

0.5'

SCALE: NONE

DATE: JUNE 2018

MINIMUM CUL-DE-SAC

STANDARDS201

MAILBOX CLUSTER UNIT

(CBU) LOCATED IN

CUL-DE-SAC THROAT.

SEE NOTE 4

Page 17: STANDARD DRAWINGS Application of Standard Drawings ...

The City Engineer must give specific approval for use of an offset crown.

Offset crown cross-sections may be used in areas of substantial cross-slope.

Offset crown cross-sections shall not be used to increase design speed in horizontal

curves. Super elevation sections shall be used for that purpose.

Maximum elevation difference of curbs or edge of pavement is determined by

cross-slopes and width of street.

NOTES:

1.

2.

3.

4.

2.0% TYP

GU

TT

ER

FA

CE

CU

RB

LIN

E

OFFSET CROWN CROSS-SECTION

8' MIN.

1/4

CL

PAVED WIDTH

CU

RB

LIN

E

SCALE: NONE

DATE: JUNE 2018OFFSET CROWN 202

2.0% TO5.0% MAX.

Page 18: STANDARD DRAWINGS Application of Standard Drawings ...

EXTRUDED ORMOUNTABLE CURB

Access width can be narrowed to 20 feet with the approval of the Fire Marshal and City

Engineer.

Curb height is not to exceed 6-inches.

"NO PARKING" area is to be defined by yellow curb.

"NO PARKING / FIRE LANE / TOW ZONE" sign locations to be determined by the Fire

Marshal and City Engineer.

Drainage is required to prevent ponding.

Area of turnaround is to be permanently maintained, cleared and unobstructed at all times.

Adjacent landscape is to be approved by City of Beaverton Board of Design Review.

Use of this turnaround at any specific site must be approved by the Fire Marshal and City

Engineer.

SECTION A-A

8'

1.

2.

3.

4.

5.

6.

7.

8.

NOTES:

A A

24'

55'

24'

24'

10'

20'

90'

3'

R 25'

45'

69' EASEMENTLIMITS

FACE

CURBOF

8'

25' R

20'

3'24'

EASEMENT

OFCURB

FACE

LIMITS

SCALE: NONE

DATE: JUNE 2018INTERIM TURNAROUND 203

Page 19: STANDARD DRAWINGS Application of Standard Drawings ...

NOTES:

1. Utilities shall be located as shown unless otherwise approved by the City Engineer.

2. The SANITARY SEWER ZONE shown above is the preferred corridor in which

sewers are to be located, unless otherwise approved by the City Engineer.

3. Storm sewer and gas are to be located on the south or west side of the street.

4. Water, communications, and power are to be located on the north or east side of

the street.

5. Install sanitary and storm sewer to Clean Water Services Design & Construction

Standards.

6. The separation between water lines and sewer lines, subject to approval by the

City Engineer, may be less than 10 feet, as per Oregon Dept. of Human Services

Rules, Public Water Systems, ORS 333-061-0050 (9)

7. Sanitary/Storm sewer manholes and water valve covers shall be located outside of

vehicle wheel paths

SCALE: NONE

DATE: JUNE 2018STANDARD UTILITY DETAILS 204

SANITARY SEWER

ZONE (10')

3.5'

10' MIN

PREFERRED

SEE NOTE 6

18" MIN

SEE NOTE 6

8' P.U.E. STREET RIGHT OF WAY

WIDTH VARIES

8' P.U.E.

30" MIN

COVER

30" MIN

COVER

WIDTH VARIES

6"

6"

SANITARY SEWER

MAIN

WATER MAINGAS

STORM SEWER

MAIN

ELEC CO.

STANDARD SIDEWALK &

PLANTER STRIP. SEE

DRAWING 215

CURB & GUTTER.

SEE DRAWING 205

VARIES

Page 20: STANDARD DRAWINGS Application of Standard Drawings ...

1/2" MAX

DRAINAGE WEEPHOLE

3" ID PLASTIC PIPE

WITH COUPLING

1. For use along medians, gutters may be reduced when preapproved by City Engineer.

2. Concrete to have compressive strength of 4,000 psi at 28 days.

3. Expansion joints to be provided at each:

a. Point of tangency.

b. Cold joint.

c. Side of inlet structures.

d. Side of driveways.

4. Expansion joint material to be pre-molded, asphalt impregnated, non-extruding, with a

thickness of 1/2 inch.

5. Contraction Joints shall have:

a. Spacing of not more than 15 feet.

b. Depth of joint of at least 112 inches.

6. Base rock 112"-0 or 3/4"-0, 95% (AASHTO T-180) compaction. Base rock shall be to

subgrade of street structure or 7.5 inches, whichever is greater, and shall extend 12

inches behind the curb.

7. Drainage weephole shall be:

a. 3-inch diameter I.D. plastic pipe with coupling and beveled outlet end to match face

of curb.

b. Centered with contraction joints.

c. Core-drilled through existing curbs for drainage access.

8. Proof roll subgrade and base rock section prior to placement of curb.

1/2" RADIUS

NOTES:

1" BATTER

ROAD

6"

6"

BASE COURSE

24"

1" RADIUS

1"

1"1" RADIUS

STREET WIDTHFACE OF CURB

6"

12"

BACKFILLBEHINDCURB ANDGUTTER

12"

SCALE: NONE

DATE: JUNE 2018

STANDARD MONOLITHIC

CURB AND GUTTER205

Page 21: STANDARD DRAWINGS Application of Standard Drawings ...

1. Mountable curb and gutter REQUIRES PREAPPROVAL by the City Engineer.

This curb design is limited to use in cul-de-sacs and other special circumstances

specifically approved.

2. Weepholes for downspout drain pipes are not allowed with this curb type, but

weepholes for vault drain pipes are allowed. See Beaverton Standard Dwg 202.

Vault drain pipe shall be 3" I.D. plastic pipe with coupling.

3. Concrete to have compressive strength of 4,000 psi at 28 days.

4. Expansion joints to be provided at each:

a. Point of tangency.

b. Cold joint.

c. Side of inlet structures.

d. Side of driveways.

5. Expansion joint material to be pre-molded, asphalt impregnated, non-extruding, with a

thickness of 1/2 inch.

6. Contraction Joints shall have:

a. Spacing of not more than 15 feet.

b. Depth of joint of at least 112 inches.

7. Base Rock 112"-0 or 3/4"-0, 95% (AASHTO T-180) compaction. Base rock shall be to

subgrade of street structure or 7.5 inches, whichever is greater, and shall extend 12

inches behind the curb.

1"

8"

23"

SEE NOTE 2

VAULT DRAIN

VAULT LOCATIONSWEEPHOLE (AT

NOTES:

12"

ONLY)

GUTTER

512"12"

MIN

BACKFILLBEHINDCURB AND

1/2" R

24"

1" R

15"

112"

CURB AT

VAULT DRAIN

WEEPHOLE

1" R1" R

412"

6"

1"

1/2"

5"

SCALE: NONE

DATE: JUNE 2018

MOUNTABLE CURB AND

GUTTER206

BASE COURSE

SEE NOTE 7

Page 22: STANDARD DRAWINGS Application of Standard Drawings ...

1.0' LENGTH OF STANDARD

CURB AND GUTTER

PROJECTED

BACK LINE OF

MOUNTABLE

CURB

PROJECTED

BACK LINE OF

MOUNTABLE

CURB

5.0' LENGTH OF

MODIFIED CURB

AND GUTTER

INLET CATCH BASIN AT CENTER OF 5.0'

LENGTH OF MODIFIED CURB AND GUTTER

CONTRACTION JOINT AT

CENTERLINE OF WEEPHOLE

GUTTER AND CURB INLET CATCH

BASIN (CG-2) PER CWS STANDARDS6"

VAULT DRAIN WEEPHOLE FRONT VIEW

INLET CATCH BASIN FRONT VIEW

1.5'

MOUNTABLE

GUTTERCURB AND

RADIUS SAME AS MOUNTABLECURB AND GUTTER

1.5'

NO EXPANSION JOINTS ALLOWEDIN THIS SECTION

IN THIS SECTIONNO EXPANSION JOINTS ALLOWED

CURB AND GUTTERRADIUS SAME AS MOUNTABLE

GUTTER

MOUNTABLECURB AND

3" ID WEEPHOLE

1.5' 1.5'

1. Mountable curb and gutter REQUIRES PREAPPROVAL by the City Engineer.

2. This drainage weephole to be used only with gravity vault drains.

3. Concrete to have compressive strength of 4,000 psi at 28 days.

4. Drainage weephole shall be 3 inch diameter ID plastic pipe with coupling and beveled

outlet end to match face of curb.

5. Modified standard curb and gutter to be same as standard curb and gutter except for

gutter width shown.

NOTES:

SCALE: NONE

DATE: JUNE 2018

MOUNTABLE CURB & GUTTER AT

VAULT207

Page 23: STANDARD DRAWINGS Application of Standard Drawings ...

SURFACE

NOTES:

1. Type 'A' curb REQUIRES PREAPPROVAL by the City Engineer.

For use ONLY when replacing similar curb. This curb is not intended for new construction.

2. Concrete to have compressive strength of 4,000 psi at 28 days.

3. Expansion joints to be provided at each:

a. Point of tangency.

b. Cold joint.

c. Side of inlet structures.

d. Side of driveways.

4. Expansion joint material to be pre-molded, asphalt impregnated, non-extruding, with a

thickness of 1/2 inch.

5. Contraction joints shall have:

a. Spacing of not more than 15 feet.

b. Depth of Joint of at least 112 inches.

6. Base rock 112"-0 or 3/4"-0, 95% (AASHTO T-180) compaction. Base rock shall be to subgrade

of street structure or 7.5 inches, which ever is greater, and shall extend 12 inches behind the

curb.

7. Drainage weephole shall be:

a. 3 inch I.D. plastic pipe with coupling and beveled outlet end to match face of curb.

b. Centered with contraction joints.

BACKFILL BEHIND CURB1/2" MAX

16"

1/2" R

DRAINAGE WEEPHOLE3" ID PLASTIC PIPEWITH COUPLING

PAVEMENT

FACE OF CURBWIDTH OF STREET

1" R6"

6"

BASE COURSE

12"9"

SCALE: NONE

DATE: JUNE 2018

TYPE ʺAʺ REPLACEMENT

CURB208

Page 24: STANDARD DRAWINGS Application of Standard Drawings ...

3"

1. Retrofit curb and gutter REQUIRES PREAPPROVAL by the City Engineer. Removing

only the top portion of the curb to make the curb cut is not allowed, unless expressly

approved. Remove curb shown cross-hatched above, except as required otherwise by

note #2.

2. If curb is to be removed before final asphalt lift is in place or if pavement is PCC, gutter

must be removed with curb. Replace existing curb and gutter with new curb and gutter

with curb cut per Beaverton Standard Dwg 205.

3. If all asphalt lifts are in place, curb only shall be removed at full depth, and reinstalled

with #4 rebar. Rebar dowels shall be placed 3 inches below top of gutter and shall be

18 inches maximum on center and 6 inches from each end of cut.

4. Saw-cut line shall be as close to face of curb as possible.

5. Concrete to have compressive strength of 4,000 psi at 28 days.

6. Bevel the curb cut back from gutter to back of curb at 8.33% (1:12).

7. Curb joint shall be a trowelled joint with a minimum 1/2 inch radius along back of curb.

8. Tie ends of new curb to existing curbs with #4 rebar dowels centered in curb and 3"

below top of curb.

NOTES:

ROAD SURFACE

#4 REBAR @ 18" OC

6"

4"

2" DEEP SAWCUT AND

VERTICAL BREAK

SEE NOTE 3 & 4

12" RADIUS

12" LIP

4"

11"

MIN

8"

FACE OF CURBSTREET WIDTH

SEE NOTE 6

JOINT - SEE NOTE 7

NEW DRIVEWAY

PER CITY

STANDARDS

6"

SCALE: NONE

DATE: JUNE 2018

RETROFIT CURB CUTS IN

EXISTING CURB AND GUTTER209

EXISTING COMPACTED

BASE COURSE

SEE NOTE 8

Page 25: STANDARD DRAWINGS Application of Standard Drawings ...

2% SIDEWALK

CROSS-SLOPE

1/2" EXPOSURE

VARIES

10'-0"

6"x 6"x10 GA. MESH

SECTION B-B

CURB AND

SIDEWALK

BEYOND

1. Section A-A may be used for curb-tight sidewalk driveway aprons if sidewalk's width is 10' or more.

2. Concrete shall have a minimum breaking strength of 4,000 psi after 28 days.

3. Curb joint shall be a troweled joint with a minimum 1/2 inch radius along back of curb.

4. Expansion joints shall be 1/2 inch pre-molded asphalt impregnated material, cedar or approved equal

extending from top of base to finished grade.

5. For driveways 24 feet wide or greater, concrete to be increased to a 7 inch depth.

6. Finish with broom and edge all joints.

7. Weepholes not to be placed in wing.

8. If curbing is being removed to install a driveway and the gutter should become separated from the

driving surface in excess of 1/16 inch, then the gutter shall also be removed and replaced.

9. Wings of the commercial driveway which are a portion of the sidewalk shall not exceed 8.333% (1:12).

10. ODOT Standard Drawings for driveways may be used when preapproved by City Engineer.

11. Slope of the driveway may be away from the curb when preapproved by City Engineer.

SECTION A-A AGGREGATE BASE

NOTES:

6"x6"x10 GA. MESH

112" ABOVE BASE

SLOPE VARIES

1:12 (8.33%) MAX

EXPANSION

JOINTS

USE EXTG EXPANSION

JOINT OR SAWCUT AND

PLACE COLD JOINT (TYP.)

CURB AND

SIDEWALK

BEYOND

1/2"

PLANTER

AREA

EXPANSION

JOINTS

FACE OF

CURB

R/W LINE

6"

MAX 15%

ELEVATION

MAX12%

PRIVATEDRIVEWAY

3/4"- 0 CRUSHED ROCK

2" OF COMPACTED

6"2% SIDEWALK

CROSS-SLOPE

6"

4'-0" MIN

R/WLINE

1/2"

6"

CURB JOINTS

40' MAX / 15' MIN

DRIVEWAY

CONTRACTION

JOINTS

PLAN

10'-0"A

7'-6"MIN

20'-0"MAX

A

7'-6"MIN

20'-0"MAX

B

B

PRIVATE

MAX 12%

MAX 15%

DRIVEWAY

LINER/W

CONTRACTION

JOINTS

SCALE: NONE

DATE: JUNE 2018

STANDARD COMMERCIAL

DRIVEWAY210

Page 26: STANDARD DRAWINGS Application of Standard Drawings ...

1. Section A-A may be used for curb-tight sidewalk driveway aprons if sidewalks width is 10' or more.

2. Concrete shall have a minimum breaking strength of 4,000 psi after 28 days.

3. Finish with broom and edge all joints.

4. If curbing is being removed to install a driveway and the gutter should become separated from the

driving surface in excess of 1/16 inch, then the gutter shall also be removed and replaced.

5. Curb joint shall be a troweled joint with a minimum 1/2 inch radius along back of curb.

6. Expansion joints shall be 1/2 inch pre-molded asphalt impregnated material, cedar or approved

equal extending from top of base to finished grade.

7. Weepholes shall not be placed in wing.

8. Slope of the driveway may be away from the curb when preapproved by City Engineer.

9. Refer to Beaverton Development Code for additional driveway requirements.

SECTION B-B

SCORINGINTERVAL

2" OF COMPACTED

3/4" - 0 CRUSHED ROCK

AGGREGATE BASE

1/2" MAX

LIP

SECTION A-A

NOTES:

2" OF COMPACTED

3/4" - 0 CRUSHED ROCK

AGGREGATE BASE

FACE OF

CURB

COLD JOINT

SLOPE

VARIES -

1:12 (8.33%)

MAX

CURB AND

SIDEWALK

BEYOND

PLANTER

AREA

VARIES

VARIES

R/W LINE

6"

DRIVEWAYPRIVATE

MAX 15%

MAX 12%

ELEVATION

4'-0" MIN

2% SIDEWALK

CROSS-SLOPE

6"

6"

1/2" MAX

LIP

CURB AND

SIDEWALK

BEYOND

R/W

PLAN

EXPANSION

JOINT

30' MAX / 12' MIN

DRIVEWAY

3'

MIN A

CURB

JOINT

A

B6'

MIN.

B

6"

USE EXTG EXPANSION

JOINT OR SAWCUT AND

PLACE COLD JOINT (TYP)

2% SIDEWALK

CROSS-SLOPE

MAX 12%

MAX 15%

PRIVATEDRIVEWAY

3/8" DEEP

SCORING

REQUIRED5'-0"

SCALE: NONE

DATE: JUNE 2018

STANDARD RESIDENTIAL

DRIVEWAY211

Page 27: STANDARD DRAWINGS Application of Standard Drawings ...

PLANTER STRIP

1. Concrete shall have a minimum compressive strength of 4,000 psi at 28 days. For slump see

specifications.

2. Sidewalk panels shall be square with their length equal to the sidewalk's width, except that sidewalks

in the Regional Center, Town Center, Station Area and Station Community districts may be wider than

6 feet, in which cases their panels may be 4 to 6 feet square, but all of equal size.

3. Expansion joints to be placed at sides of driveway approaches, utility vaults, sidewalk ramps and/or at

points of tangency in curb as shown on the standard drawings for sidewalk ramps and at spacing not to

exceed 45 feet.

4. Sidewalk shall have a minimum thickness of 4 inches, except that sidewalk that is intended as a portion

of a driveway shall have a minimum thickness of 6 inches. See Beaverton Standard Dwgs 210 & 211.

5. Finish with broom and edge all joints.

6. Width of curb is included in planter strip width.

7. Street trees are required except where specifically modified or waived in writing by the City Engineer.

8. For sidewalk repairs, replacements and installations in existing developments, match existing width of

sidewalks, and sidewalk panels' widths and lengths.

FOR LOCAL STREETS6.5' MIN

NEIGHBORHOOD ROUTEFOR ARTERIAL, COLLECTOR AND

7.5' MIN

COMPACTED SUBGRADE

ROAD

NOTES:

SIDEWALK

2" OF COMPACTED 3/4" -0

CRUSHED ROCK AGGREGATE BASE

VARIES

IN DISTRICTS PER THE

DEVELOPMENT CODE

SEE NOTE 2

FOR ARTERIAL AND COLLECTOR

5' MIN

6"R/W

2 %

AND LOCAL STREETS

6' MIN

FOR NEIGHBORHOOD ROUTE

SEE NOTE 4

SCALE: NONE

DATE: JUNE 2018STANDARD SIDEWALK 215

Page 28: STANDARD DRAWINGS Application of Standard Drawings ...

1. Curb tight sidewalks REQUIRE PREAPPROVAL by the City Engineer.

They are used for sidewalk repairs, replacements and installations in existing developments. Match

width of existing sidewalks, and widths and lengths of existing sidewalk panels.

2. Concrete shall have a minimum compressive strength of 4,000 psi at 28 days, For slump see

specifications.

3. Sidewalk panels shall be square with their length equal to the sidewalk's width, except that sidewalks

in the Regional Center, Town Center, Station Area and Station Community districts may be wider than

6 feet, in which cases their panels may be 4 to 6 feet square, but all of equal size.

4. Expansion joints to be placed at sides of driveway approaches, utility vaults, sidewalk ramps and/or at

points of tangency in curb as shown on the standard drawings for sidewalk ramps and at spacing not to

exceed 45 feet.

5. For sidewalks adjacent to the curb and poured at the same time as the curb, the joint between them

shall be troweled with a minimum 1/2 inch radius.

6. Sidewalk shall have a minimum thickness of 4 inches, except that sidewalk that is intended as a portion

of a driveway shall have a minimum thickness of 6 inches. See Drawings 210 & 211.

7. Where vehicular access across sidewalk is required by City, a 40 foot long section of sidewalk shall be

provided in the access area, shall be 6-inches thick and shall be reinforced with 6"x6"x10 ga steel

mesh. Location of 40 foot long section to be as directed by City Engineer.

8. Finish with broom and edge all joints.

9. Street trees, treewells and grates are required except where specifically modified or waived in writing

by the City Engineer.

10. For sidewalk widths around grated treewells, and tree grate requirements, see Beaverton Standard

Dwg 241.

COMPACTED SUBGRADE

NOTES:

CURB JOINT

ROAD

SEE NOTE 5

VARIES

IN DISTRICTS PER THE

DEVELOPMENT CODE

SEE NOTE 3

2" OF COMPACTED 3/4" - 0

CRUSHED ROCK

AGGREGATE BASE

SEE NOTE 6

R/W

2%

7' MIN

FOR ARTERIAL AND COLLECTOR

6' MIN

AND LOCAL STREETS

FOR NEIGHBORHOOD ROUTE

SCALE: NONE

DATE: JUNE 2018CURB TIGHT SIDEWALK 216

6"

MIN

R/W OR

AS DETERMINED

Page 29: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

STANDARD TO CURB TIGHT

SIDEWALK TRANSITION217

1. Curb Tight Sidewalk REQUIRES PREAPPROVAL by City Engineer. Submit the

design for a specific project with transitions from a Standard Sidewalk with planter

strip to curb tight sidewalk.

2. For Standard Sidewalk information see Beaverton Standard Dwg 215.

3. For Curb Tight Sidewalk information see Beaverton Standard Dwg 216.

4. Curb radius shown is for cul-de-sac. Other curves as approved by City Engineer.

STRAIGHT ROADWAY

SIDEWALK

CURB &

GUTTER

10' R

SEE NOTE 3

6'

OR

7'

NOTES:

PLANTER

STRIP

SEE NOTE 2

6.5'

OR

7.5'

5'

OR

6'

10' R

5' R

20' TRANSITION

R/W SHIFT

6" R/W

CURB &

GUTTER

PRC

SEE NOTE 4

SIDEWALK

45' R

6" R/WSEE NOTE 3

6'

OR

7'

CUL-DE-SACS & CURVES

PC

PLANTER

STRIP

34' R

SEE NOTE 2

25' R

6.5'

OR

7.5'5'

OR

6'

5' R

Page 30: STANDARD DRAWINGS Application of Standard Drawings ...

NOTES:

1. Extensions are intended to simulate a parked vehicle, therefore shall only be allowed in

conjunction with on-street parking.

2. Intersection radii shall be checked to assure safe passage of the design vehicle. In all

cases, emergency vehicles shall be accommodated.

3. Drainage shall be addressed with the appropriate agency.

4. Refer to Engineering Design Manual for ADA ramp, sidewalk, planter strip, parking lane,

and travel lane requirements.

CL

Parking Travel LanePlanterSidewalk

Pla

nte

rS

ide

walk

R = 20' min

SCALE: NONE

DATE: JUNE 2018

CURB EXTENSION 220

R= 5' (typ)

Page 31: STANDARD DRAWINGS Application of Standard Drawings ...

1. Flat blanks shall be 0.080 inch gauge with 6063 T6 alodine coated aluminum substrate.

2. All letters shall be black and series are as noted.

3. Background shall be white 3M Scotchlite brand High Intensity Reflective sheeting.

4. For sign mounting, see drawing 400.

5. Border shall be offset 12" from edge of sign and shall be 3 4" wide6. Corner radii shall be 1.875"

NOTES:

NOTICETHIS ROAD WILL BE

FUTURE DEVELOPMENT

CITY OF BEAVERTON

5"

B2"

2"

C2"

2"

C2"

2"

C3"

5"

3 r

ow

s 1

14"

C letters

11

4"

line s

pacin

g

1"1114"

112"

112"

EXTENDED WITH

503 - 526 - 2420

FOR INFO CONTACT

2"

2"

2"

1"7.5"

1"

SCALE: NONE

DATE: SEPT 2018

FUTURE STREET EXTENSION

SIGN221

Page 32: STANDARD DRAWINGS Application of Standard Drawings ...

SECTION A-A

EX

IST

ING

SID

EW

ALK

1. Retrofit ramp REQUIRES PREAPPROVAL by the City Engineer.

2. Sidewalk ramp shall meet ADA Standards.

3. This drawing is for retrofitted ramps only, where site constraints prohibit installing two ramps. The

Engineer shall prepare a site-specific drawing for each ramp, accepting full responsibility for correcting

all unacceptable ramp construction resulting from applying this drawing "as is".

4. Sawcut and remove the existing sidewalk, curb and gutter to the nearest cold joint.

5. Ramp shall be located relative to crosswalk or stop line.

6. Detectable warning shall be 24 inches long in the direction of travel and full width of the ramp, made

of concrete imbedded yellow tiles, that have truncated domes aligned on a square grid with its gridlines

parallel and perpendicular to the centerline of the ramp, from the approved list in the Engineering

Design Manual, Sec 210.10.

7. Concrete shall have a compressive strength of 4,000 psi at 28 days.

8. Bevel the curb cut from gutter to back of curb at 8.33% (1:12).

9. Construct curb with varying exposure tapered longitudinally so that the top of the curb matches the

normal projected back of sidewalk as shown in section B-B.

10. Score at grade changes, surface texture changes and at other points shown. Edges shall be shined.

11. Curb inlet or catch basin shall not be allowed in front of sidewalk ramp.

VARIES

B

PL

AN

TE

R

CONSTRUCT

EXPANSION

JOINT

REPLACE CURB OR

CURB AND GUTTER TO

MATCH EXISTING

121

LCRAMP LOCATION

SEE NOTES 3

AND 5

5'M

IN

NOTES:

121

501

VARIESVARIES

SECTION B-B

B

CURB

EXISTING

SIDEWALK

P TERAL N

VARIES 4' MIN

CONSTRUCT

EXPANSION JOINT

CONSTRUCT

EXPANSION JOINT

CONSTRUCT EXPANSION JOINT

CURB

11 2:1

2:1

CURB AND

SIDEWALK

BEYOND

TYPICAL SCORED

JOINT - SEE NOTE 10

112 CURB CUT - SEE NOTE 9

CURB DETAIL

BROOM FINISH TYP

CURB - SEE DETAIL

AND NOTE 9

DETECTABLE

WARNING

SEE NOTE 61" R

VARIESVARIES

NOTE 9

SEE

1" R

NOTE 9

12" R

SEE

7"

6"

VARIES

2' MIN

SEENOTE 9

A

A

SCALE: NONE

DATE: JUNE 2018

RETROFIT SINGLE SIDEWALK

RAMP WITH PLANTER STRIP231

6' WINGS

TYP EACH SIDE

Page 33: STANDARD DRAWINGS Application of Standard Drawings ...

1. Retrofit ramp REQUIRES PREAPPROVAL by the City Engineer.

2. Sidewalk ramp shall meet ADA Standards.

3. This drawing is for retrofitted ramps only, where site constraints prohibit installing two ramps. The

Engineer shall prepare a site-specific drawing for each ramp, accepting full responsibility for correcting

all unacceptable ramp construction resulting from applying this drawing "as is".

4. Sawcut and remove the existing sidewalk, curb and gutter to the nearest cold joint.

5. Each ramp shall be located relative to crosswalk or stop line.

6. Detectable warning shall be 24 inches long in the direction of travel and full width of the ramp, made

of concrete imbedded yellow tiles, that have truncated domes aligned on a square grid with its gridlines

parallel and perpendicular to the centerline of the ramp, from the approved list in the Engineering

Design Manual, Sec 210.10.

7. Concrete shall have a compressive strength of 4,000 psi at 28 days.

8. Bevel the curb cut from gutter to back of curb at 8.33% (1:12).

9. Construct curb with varying exposure tapered longitudinally so that the top of the curb matches the

normal projected back of sidewalk as shown in section B-B.

10. Score at grade changes, surface texture changes and at other points shown. Edges shall be shined.

11. For sidewalk widths, see drawing 216.

12. Curb inlet or catch basin shall not be allowed in front of sidewalk ramp.

SECTION A-A

REPLACE CURB OR CURB AND

GUTTER TO MATCH EXISTING,

AS REQUIRED

5'

MIN

B

EX

IST

ING

SID

EW

ALK

112

CONSTRUCT

EXPANSION

JOINT

6'

RAMP LOCATION

SEE NOTES 3

AND 5

CL

6' MIN

TYP

NOTES:

B

A

A

EXISTING

SIDEWALK

CURB

VARIES

SEE NOTE 11CURB AND

SIDEWALK

BEYOND11 2:1

150

2:1

24"

CURB CUT

SEE NOTE 8121

SEE

6'

CONSTRUCT

EXPANSION JOINT

CONSTRUCT

EXPANSION JOINT

BROOM FINISH

TYPICAL

TYPICAL SCORED

JOINT - SEE NOTE 10

DETECTABLE WARNING

SEE NOTE 6

CURB - SEE DETAIL

AND NOTE 9

CONSTRUCT EXPANSION JOINT

6"

7"

SEE

12" R

NOTE 9

1" R

SEE

NOTE 9

VARIESVARIES

1" R

NOTE 9

CURB

RAMP4' MIN

SECTION B-B

CURB DETAIL

SCALE: NONE

DATE: JUNE 2018

RETROFIT CURB TIGHT

SINGLE SIDEWALK RAMP233

Page 34: STANDARD DRAWINGS Application of Standard Drawings ...

1. Tree species and caliper size are to be approved by the City Arborist.

2. Adjust planting locations so that tree crown or root ball does not conflict with above

or below - ground utilities.

3. Do not undermine curb or sidewalk when excavating.

4. An 18 inches deep, root barrier shall be added where required by the City Arborist.

5. Opposite tree stakes, provide two, 3 inch diameter ADS perforated pipe watering

troughs, filled with pea gravel.

6. Provide a loop in chain lock or guy hose large enough to allow for trunk growth.

7. Tree stakes are to be removed following the required establishment period.

HAND TAMPED

NATIVE SOIL

NOTES:

THOROUGHLY

MOISTENED

NATIVE SOIL

PLACE 2" x 2" STAKES

OUTSIDE ROOT BALL

SET TOP OF ROOT

BALL AT GRADE

2"- 4" OF BARK MULCH

WHERE SPECIFIED

TREE TYPE & CALIPER SIZE

SEE NOTE 1

1" PLASTIC CHAIN OR

RIGID GUY WITH HOSE LOOP

SEE NOTE 68"

ROOT BARRIER

SEE NOTE 4

FOLD BACK, TRIM &

REMOVE TOP HALF OF

BURLAPPED ROOT BALL

CROSS-SECTION

EXISTING

NATIVE SOIL

WATERING

TROUGH

SEE NOTE 5

SCALE: NONE

DATE: JUNE 2018

STANDARD SIDEWALK

TREEWELL240

Page 35: STANDARD DRAWINGS Application of Standard Drawings ...

7' - 11 7/8" GRATE

GRATE PLAN VIEW

1. Grates are to be made of cast iron with a natural finish.

2. Castings will be 3/4 inch thick in 4 pieces.

3. The center opening shall be 16 inch diameter with a breakout at 2312 inches.

4. Slotted penetrations shall be no greater than 3/8 inch wide.

5. An 18 inch deep root barrier shall be placed at both sides and along sidewalk face.

6. Provide two, 3 inch diameter ADS perforated pipe watering troughs filled with pea gravel.

7. Do not undermine curb or sidewalk when excavating.

8. ADA clearance shall be 4 feet as shown, unless otherwise permitted by the City Engineer

pursuant to a design exception under Section 160 of the Engineering Design Manual.

TREEWELL CROSS-SECTION

ROOTBALL

CURB

WATERING

TROUGH

NOTES:

SIDEWALK

WATERING TROUGH

SEE NOTE 6

FOLD BACK, TRIM &

REMOVE TOP HALF OF

BURLAPPED ROOT BALL

HAND TAMPED

NATIVE SOIL

THOROUGHLY

MOISTENED

NATIVE SOIL

SIDEWALK

TREE TYPE &

CALIPER SIZE

AS SPECIFIED BY

CITY ARBORIST

1/4"

TREE GRATECURB

1/4" x 2" x 2"TAB WITH SLOTWELDED TO GRATE FRAME

FORM 1" X 1"

CONC LIP ON 3

SIDES TO SEAT

GRATE FRAME

SEE

DETAILS

6" GRATE TO

ROOTBALL

CLEARANCE

ROOT

BARRIER

SEE NOTE 5EXISTING

NATIVE SOIL

#3 REBAR 5" LONG @ 16" OC

BENT DOWN AT 45° TYPICAL

4' x 8' x 1" GRATE

& FRAME ASSEMBLY:

OLYMPIC FOUNDRY

STA 48"X96" OR URBAN

ACCESSORIES KIVA RCT

GRATE & "S" FRAME

3/8" x 2" REMOVABLE X-BAR MIN

FRAME PLAN VIEW

ADA

CLEARANCE

4' MIN1 1/2" x 2" WELDED T-BAR MIN

GRATE FRAME

SIDEWALK

TREE GRATEGRATE FRAME

3/4"

#3 REBAR

CONCRETE

ANCHOR: RED

HEAD DYNABOLT,

1/2" Ø BOLT, 3"

MIN EMBEDMENT

SIDEWALK ANCHORDETAIL

CURB ANCHORDETAIL

CURB

ANCHOR

SEE DETAIL

8' - 1/8" ID8' - 5/8" OD

4' -

1/8

" ID

4' -

5/8

" O

D

3' - 11 7/8"

GRATE

SCALE: NONE

DATE: JUNE 2018

CURB TIGHT SIDEWALK

TREEWELL WITH GRATE241

Page 36: STANDARD DRAWINGS Application of Standard Drawings ...

FOLD BACK, TRIM &

REMOVE TOP HALF OF

BURLAPPED ROOT BALL

TREEWELL CROSS-SECTION

3" DIA. SLEEVE -

EXTEND 2" BEYOND

WALL OF TREEWELL

4" ADS PERF PIPE

FILLED WITH PEA GRAVEL

SCH 40 PVC 1/2" F-AD.

STREET EL, SCH 80 PVC

1/2" THREADED RISER,

NO. 514-20 TOROBUBBLER

SCH 40 PVC (VARIES) REDUCER,

SCH 40 PVC (VARIES) X 1/2" TEE,

SCH 40 PVC 1/2" STREET EL

CLASS 200 PVC 1/2" PIPE

THOROUGHLY

MOISTENED

NATIVE SOIL

SIDEWALK

4" ADS PERF PIPE

FILLED WITH PEA GRAVEL

2" MAX

SCH 40 PVC - SIZE

VARIES FROM 2" TO 3/4"

3" Ø SLEEVE - EXTEND

2" BEYOND WALL OF TREEWELL

TORO 514-20 FLOOD - 30 PSI

BUBBLER, SCH 80 PVC

1/2" THREADED RISER

6" GRATE TO

ROOTBALL

CLEARANCE

TREE TYPE & CALIPER

SIZE AS SPECIFIED BY

CITY ARBORIST

GRATE & FRAME ASSEMBLY

SEE Beaverton Standard Dwg 241

HAND TAMPED

NATIVE SOIL

SIDEWALK

ROOT

BARRIER

8'

4'

TREEWELL PLAN VIEW

2" 4" ADS PERF PIPE

FILLED WITH PEA GRAVEL

SIDEWALK

SCH 40 PVC (VARIES) X 1/2" TEE,

SCH 80 PVC 1/2" RISER,

NO. 514-20 TORO BUBBLERSCH 40 PVC PIPE

SIZE VARIES FROM 2" TO 3/4"

CURB

18" ROOT BARRIER

AT 3 SIDEWALK FACES

ROOTBALL

SCALE: NONE

DATE: JUNE 2018

TREEWELL IRRIGATION 242

Page 37: STANDARD DRAWINGS Application of Standard Drawings ...

Grind for extra depth at edges as shown.

Apply bitumal tack coat over air-blown cleaned and

swept asphalt concrete.

Asphalt shall be rolled for compaction per specifications.

Finish edges by applying tack coat and sand sweeping.

Tack coat shall conform to ODOT Specifications, Type

CSS-1, CSS-1H.

EDGE TAPER DETAIL

PLAN VIEW

SECTION A-A

EXISTING AC OR

PCC PAVEMENT

PAVING MATERIAL:

Level 2, 12" ACP

CURB OR

CURB AND

GUTTER

B

A

PARABOLIC

SEE SECTION B-B

12"18"

1.

2.

3.

4.

B

[Approved for use when the conditions

below exist.]

Locations per approved plan.

Neighborhood Routes and Local Streets

only.

Posted speed 25 mph.

Tangent sections or curves with 300 ft.

radius or larger.

Grade less than 8%.

No more than 2 travel lanes.

Not an existing or planned Transit Route.

Not a Primary Emergency Vehicle Route.

PAVEMENT

MARKING DETAIL

SECTION B-B

SEE EDGE

TAPER DETAIL

A

GRIND 1" DEEP x 15" WIDE

FOR EXTRA DEPTH AT EDGE

1.

2.

3.

4.

5.

6.

7.

8.

PARABOLIC

CROWN

SCALE: NONE

DATE: JUNE 2018

ASPHALTIC CONCRETE

SPEED HUMP245

Page 38: STANDARD DRAWINGS Application of Standard Drawings ...

[Approved for use when the conditions

below exist.]

1. Locations per approved plan.

2. Posted speed 25 mph.

3. Tangent sections or curves with

300 ft. radius or larger.

4. Grade less than 8%.

5. No more than 2 travel lanes.

EDGE TAPER DETAIL

SECTION A-A

PLAN VIEW

PAVING MATERIAL:

Level 2, 12" ACP

EXISTING AC OR

PCC PAVEMENT

B

A

B

PARABOLIC

SEE SECTION B-B

12"18"

CURB OR

CURB AND

GUTTER

1. Grind for extra depth at edges as shown.

2. Apply bitumal tack coat over air-blown cleaned and swept

asphalt concrete.

3. Asphalt shall be rolled for compaction per specifications.

4. Finish edges by applying tack coat and sand sweeping.

Tack coat shall conform to ODOT Specifications, Type

CSS-1, CSS-1H.

PAVEMENT

MARKING DETAIL

SECTION B-B

SEE EDGE

TAPER DETAIL

GRIND 1" DEEP x 15" WIDE

FOR EXTRA DEPTH AT EDGE

PARABOLIC

CROWN

A

SCALE: NONE

DATE: JUNE 2018

ASPHALTIC CONCRETE

SPEED TABLE246

Page 39: STANDARD DRAWINGS Application of Standard Drawings ...

20'

AGGREGATE BASE

Locations per approved plan.

Neighborhood Routes and Local

Streets only.

Posted speed 25 mph.

Tangent sections or curves with 300 ft.

radius or larger.

Grade less than 8%.

Not an existing or planned Transit Route.

Not a Primary Emergency Vehicle Route.

[Approved for use when the conditions

below exist.]

EXISTING AC OR

PCC PAVEMENT

PLAN VIEW

SECTION A-A

40' MIN

12'

PAVING MATERIAL:

Level 2, 12" ACPSPEED TABLE

EXTG AC

PAVEMENT

1.

2.

3.

4.

5.

6.

7.

SECTION D-D

20'

2'9.5'

21'

9.5'

REFLECTIVE

PAVEMENT

MARKERS

PARABOLIC

SEE

SECTION

VIEW "B-B"

NEW 4" AC MIN THICKNESS

SAWCUT

CURB OR CURB

AND GUTTER

REFLECTIVE

PAVEMENT

MARKERS

CURB INLET CATCH

BASIN TYP

21'

14'

MIN

4' MIN

SAWCUT

14'-0"

TOPSOIL

GRIND 1" DEEP

x 15" WIDE FOR

EXTRA DEPTH AT EDGE

14'

MIN

WHITE

STRIPING

APPLY PER

SPECIFICATIONS

MULCH

AGGREGATE BASEAGGREGATE BASE

EXCAVATE EXISTING PAVEMENT AND BASE ROCK TO NATIVE

SOIL BUT NOT LESS THAN 1' BELOW EXISTING GRADE.

PAVEMENT MARKING DETAIL

SECTION B-B PARABOLIC

CROWN4'-0"

1. Median Island may be constructed without speed

hump.

2. Sawcut and remove existing A.C. for construction of

traffic circle by one of two methods:

a. Sawcut to within 2 inches of curb form line, fill void

between curb and pavement with concrete, or

b. Remove a minimum of 14 inches beyond curb

form line, patch pavement with Level 2, 12" ACP.Finish edges by applying tack coat and sand

sweeping.

3. Construct Type 'A' P.C.C. curb for island perimeter.

4. Construct A.C. speed hump between curbs.

a. Grind for extra depth at edge as shown.

b. Apply tack coat over air-blown cleaned and swept

asphalt concrete.

c. Finish edges by applying tack coat and sand

sweeping. Tack coat shall conform to ODOT

Specifications, Type CSS -1, CSS -1H.

SECTION C-C

SCALE: NONE

DATE: JUNE 2018

ASPHALTIC CONCRETE SPEED

HUMP WITH MEDIAN ISLAND250

Page 40: STANDARD DRAWINGS Application of Standard Drawings ...

PLAN VIEW

AGGREGATE BASE

[Approved for use when the conditions

below exist.]

Locations per approved plan.

Posted speed 25 mph.

Tangent sections or curves with

300 ft. radius or larger.

Grade less than 8%.

EXISTING AC OR

PCC PAVEMENT

20'

1.

2.

3.

4.

APPLICATION NOTES:

PAVING MATERIAL:

Level 2, 12" ACPSPEED TABLE

42'

10'10'10'10'

REFLECTIVE

PAVEMENT

MARKERS

SAWCUT

PARABOLIC

SEE SEC B-B

NEW 4" AC MIN THICKNESS

EXITG AC PAVEMENT

2'

KEEP

RIGHT

SIGN

SECTION A-A

CURB OR

CURB AND

GUTTER

SECTION D-D

SECTION B-B PARABOLIC

CROWN

42'

14'

MIN

4' MIN

CURB INLET CATCH BASIN

TYP20'

22'

40' MIN

14'

MIN

REFLECTIVE

PAVEMENT

MARKERS

SAWCUT

14'-0"

TOPSOIL

GRIND 1" DEEP

x 15" WIDE FOR

EXTRA DEPTH AT EDGE

MULCH

EXCAVATE EXISTING PAVEMENT AND BASE ROCK TO NATIVESOIL BUT NOT LESS THAN 1' BELOW EXISTING GRADE.

AGGREGATE BASE

PAVEMENT MARKING DETAIL

AGGREGATE BASE

4'-0"

WHITE STRIPING

APPLY PER

SPECIFICATIONS

KEEP

RIGHT

SIGN

CONSTRUCTION NOTES:

SECTION C-C

1. Median island may be constructed without speed hump.

2. Sawcut and remove existing A.C. for construction of traffic

circle by one of two methods:

a. Sawcut to within 2 inches of curb form line, fill void

between curb and pavement with concrete, or

b. Remove a minimum of 14 inches beyond curb form line,

patch pavement with compacted Level 2, 12" ACP. Finishedges by applying tack coat and sand sweeping.

3. Construct Type 'A' P.C.C. curb for island perimeter.

4. Construct A.C. speed table between curbs.

a. Grind for extra depth at edge as shown.

b. Apply tack coat over air-blown cleaned and swept asphalt

concrete.

c. Finish edges by applying tack coat and sand sweeping.

Tack coat shall conform to ODOT Specifications, Type

CSS -1, CSS -1H.

SCALE: NONE

DATE: JUNE 2018

ASPHALTIC CONCRETE SPEED

TABLE WITH MEDIAN ISLAND251

Page 41: STANDARD DRAWINGS Application of Standard Drawings ...

Construct A.C. speed table between curbs.

a. Grind for extra depth at edge as shown.

b. Apply tack coat over air-blown cleaned and swept asphalt

concrete.

c. Finish edges by applying tack coat and sand sweeping. Tack coat

shall conform to ODOT Specifications, Type CSS -1, CSS -1H.

See Beaverton Standard Dwg 420 for barrier details.

MIN

5' R TYP

SECTION B-B

GRIND 1" DEEP

x 15" WIDE FOR

EXTRA DEPTH

AT EDGE

4'5' R TYP

PLAN VIEW

BARRIER AS REQUIRED

1.

2.

AGGREGATE BASE

18"TYP

CURB OR CURB

AND GUTTER

[Approved for use when the

conditions below exist.]1.

2.

3.

4.

5.

SLOPE VARIES

PAVEMENT MARKING

DETAIL

SECTION C-C

SECTION A-A

4'

12'-0"

2'

3'

LC ROAD

LC HUMP

EXISTING AC OR

PCC PAVEMENT

PAVING MATERIAL:

Level 2, 12" ACPSPEED TABLE

Locations per approved

plan.

Posted speed 25 mph.

Tangent sections or curves

with 300 ft. radius or larger.

Grade less than 8%.

No more than two travel

lanes.

TYP

CURB INLET CATCH

BASIN TYP

8'

18"

18"TYP

TYP

BARRIER AS REQUIRED

PARABOLIC

CROWN

SIDEWALK SLOPE: 50:1

SCALE: NONE

DATE: JUNE 2018

SPEED TABLE WITH

CROSSWALK255

Page 42: STANDARD DRAWINGS Application of Standard Drawings ...

Median island may be constructed without speed hump.

Sawcut and remove existing A.C. for construction of median island by

one of two methods:

a. Sawcut to within 2 inches of curb form line, fill void between curb

and pavement with concrete, or

b. Remove a minimum of 14 inches beyond curb form line, patch

pavement with compacted Level 2, 12" ACP. Finish edges by applying tack coat and sand sweeping.

Construct Type 'A' P.C.C. curb for island perimeter.

For speed hump details, see drawing 255.

For barrier details, see drawing 420.

REFLECTIVE

PAVEMENT

MARKERS

CURB - SEE NOTE 3

BARRIER AS REQUIRED

AGGREGATE BASE

1.

2.

3.

4.

5.

SAWCUT

6" TYP

NEW AC 4"MIN THICKNESS

EXTG AC

PAVEMENT

REFLECTIVE

PAVEMENT

MARKERS

EXTG AC PAVEMENT

TOP OF SPEED TABLE

EXISTING GRADE

Locations per approved

plan.

Posted speed 25 mph.

Tangent sections or curves

with 300 ft. radius or larger.

Grade less than 8%.

No more than two travel

lanes.

MIN

TOPSOILMULCH SAWCUT

[Approved for use when the

conditions below exist.]

1.

2.

3.

4.

5.

EXCAVATE EXISTING PAVEMENT AND BASE ROCK TO NATIVE

SOIL BUT NOT LESS THAN 1' BELOW EXISTING GRADE

WHITE STRIPING

APPLY PER

SPECIFICATIONS

CURB INLET CATCH

BASIN TYP

BARRIER AS REQUIRED

8'

4'5' R TYP

KEEP

RIGHT

SIGN

4' MIN

14'

CL

6'-0"

CROSSWALK &

SPEED TABLE

14'MIN

MIN

KEEP

RIGHT

SIGN

14'

5' R TYP

14'-0"

PLAN VIEW

AGGREGATE BASE

1' MIN

SECTION A-A

SCALE: NONE

DATE: JUNE 2018

SPEED TABLE WITH

CROSSWALK AND MEDIAN

ISLAND256

Page 43: STANDARD DRAWINGS Application of Standard Drawings ...

Locations per approved plan.

Posted speed 25 mph.

No more than 2 travel lanes.

EXISTING GRADE

[Approved for use when the

conditions below exist.]

6"

16' MIN

17'

18'

19'

20'

OPENING

WIDTH

OFF-SET

DISTANCE

5.5' MAX

5.0'

4.5'

4.0'

3.5' OR LESS

30"

7"

12"

3"

SAWCUT

AGGREGATE BASE

1.

2.

3.

Sawcut and remove existing AC for construction of traffic circle by

one of two methods:

a. Sawcut to within 2 inches of curb form line, fill void between

curb and pavement with concrete, or

b. Remove a minimum of 14 inches beyond curb form line, patch

pavement with compacted Level 2, 12" ACP. Finish edges byapplying tack coat and sand sweeping.

Contraction joint spacing shall be not more than 10 feet equally

spaced around circle. Depth of the joint shall be at least 112 inches.

EXCAVATE EXISTING PAVEMENT AND

ROCK BASE TO NATIVE SOIL - BUT NOT

LESS THAN 12" BELOW EXISTING GRADE

1" R

1/2" R

1" R

SAWCUT

BATTER 1" IN 7"

VARIE

S

A

MULCH

OFF-SET

DISTANCE

VARIES

A

5.5' MAX

VARIES

PLAN VIEW

16' -

20'

OPENIN

G W

IDTH

24"8"

12"

TOPSOIL

SECTION A-A

1.

2.

SCALE: NONE

DATE: JUNE 2018

TRAFFIC CIRCLE 260

Page 44: STANDARD DRAWINGS Application of Standard Drawings ...

1. Install per manufacturer's recommendations. Block style, size and batter may

vary, see specifications.

2. Connect 3" PVC drain pipe with 45° bend to perforated pipe. Daylight with

Weephole through curb at 8' minimum from end of retaining wall.

HEIGHT VARIES AS REQUIRED

12"

4"

SOD

R/W

6"

TOP SOIL

FILTER FABRIC

18" DEEP

ROOT BARRIER

DRAIN ROCK

NOTES:

BATTER

CORNER

BLOCKS

CAP AS REQUIRED

WALKSLOPED

CORNER FRONT VIEW

ABUTTING SIDEWALK

3" Ø PERFORATED PIPE

CROSS SECTION

3/4"-0 BASE

ABUTTING SIDEWALK

SCALE: NONE

DATE: JUNE 2018

STANDARD BLOCK WALL 270

Page 45: STANDARD DRAWINGS Application of Standard Drawings ...

Roadway

7" - 8"

812" - 10"

1012" & up

1"

114"

112"

12"

12"

12"

SCALE:

PLAN

NTS

Tool edgeEdge of concrete pvmt.

18" dowel bars(see dowel bar table)

Transverse constr.joints See Detail "A"

Longitudinal joint

36" tie bars6"

18"

15' Max.*

Lan

e w

idth

Lan

e w

idth

Lan

e w

idth

SCALE:

DETAIL "A"

NTS

SCALE:

LONGITUDINAL JOINT

SECTION C-C

NTS

SCALE:

TRANSVERSE JOINT

NTS

Tool edges

18" dowel bars(see dowel bar table)

Saw and seal joint

18" dowel bars(see dowel bar table)

#5 tie bar 36" long@ 36" centers

Saw and seal joint

#5 tie bar 36" long@ 36" centers

T T

T T

T/2

T/2

T/2

T/2

T/4

T/4

DOWEL BAR TABLE

Pvmt.Thkn.

(T)

DowelDia.

C/CDowel

Spacing

*Spacing between transverse jointsshall not exceed 15 feet or 24 x theslab thickness on unbound base or21 x slab thickness on stabilizedbase.

Transversecontractionjoints

NOTES:

1. Install tie bars along longitudinal joints between concrete panels. Tie barsare not installed between concrete pavement and ACP pavement.

2. Center tie bars and dowel bars on joint.

3. If the time frame designated for opening traffic is less than 72 hours after

concrete placement, provide Class HES4000 - 112 concrete designed to attain a

minimum average compressive strength of 3,000 psi prior to allowing traffic on

the concrete. Otherwise furnish Class 4000 - 112 paving concrete.

4. The surface of the concrete shall have a textured finish using a steel-tine

tool with 1 8 inch tines that will mark the finished concrete to a depth of 116 inchto 18 inch. Randomly space the markings from ½ inch to 1¼ inches as approved.Avoid overlaps of the texturing. Markings shall be transverse to the roadwaycenterline and full roadway width.

5. New interior longitudinal and transverse joints shall be sawcut as soon asthe concrete has set enough to allow sawing without tearing or raveling.

6. The new saw cut transverse and longitudinal joints shall be filled withpoured rubber-asphalt joint filler. The saw cut joint shall be flushed with water,vacuumed to remove cement slurry and dried before installing the joint filler.

7. Irregularly shaped panels, rectangular panels with an aspect ratio exceeding1:1.25, and panels containing more than one utility structure (such asmanholes, valves, etc.) shall be reinforced. See reinforcement grid details thissheet.

8. All tie bars and dowel bars shall be Grade 60 steel and shall be smooth,epoxy coated, circular, and greased.

SCALE:

TYPICAL PAVEMENT SECTION

NTS

Textured finish(See note 4)

PCC pavement(See note 3)

Aggregate base

T

Skewedjoint

Dowelparallel to

roadway CL

SCALE:

DOWEL AT SKEWED JOINT

NTS

AA BB

C

C

Section A-A

Construction Joint

Section B-B

Contraction Joint

Contact Joint Weakened Plane Joint

See Std. Drg. No. 220-2 for boxouts andreinforcement at manholes and inlets

90° preferred60° minimum

2"typ.

3"typ.

Smooth dowel ortie bar per plan

#5 bar @ 12" on center eachway supported on bar chairs.Locate per plan

SCALE:

REINFORCEMENT GRID

NTS

#5 bars @ 12" oncenter, each way.

Place T/3 (2" min.)clear from topsurface of concrete

18" dowel bars(See dowel

bar table)

T/3

2"

min

.

FILENAME: 220-1.dwg

SCALE: NONE

DATE: JUNE 2018

CONCRETE ROADWAYS 220-1

Page 46: STANDARD DRAWINGS Application of Standard Drawings ...

Boxout on Joint or

Wholly Within Panel

1. Place 2 layers of #30 felt bond breaker meeting therequirements of ASTM D226, Type II at isolation joints.

2. Locate joint on center of manhole rim when possible.

INLET

Curb

R=4'-0"

Joint

Join

tJo

int

Joint

Join

t (i

f

pre

sen

t)

Transverse joint

Isolation joint

(2) #4 bars (hoops) @ 3" on center.3" minimum clearance fromisolation joint. 2" minimum verticalclearance from surface of conrete.

Concrete pavement

Gutter

Isolation joint

(8) #5 bars @ 12" oncenter each way. 3"min.clearance fromisolation joint. 2" min.vertical clearance fromsurface of concrete.

(8) #5 bars @ 12" oncenter each way. 2"min. verticalclearance fromsurface of concrete.

(2) #4 bars (hoops) @ 3" oncenter. 3" minimum clearancefrom isolation joint. 2"minimum vertical clearancefrom surface of conrete.

12"

min

.

SCALE:

MANHOLE BOXOUTNTS

Boxout on Joint Intersection

SCALE:

BASIN (CG-2) BOXOUTGUTTER & CURB INLET CATCH

NTS

NOTES:

Join

t (i

f

pre

sen

t)

Isolation joint12"

min

.

FILENAME: 220-2.dwg

SCALE: NONE

DATE: JUNE 2018

MANHOLE AND INLET

CONCRETE BOXOUTS220-2

Page 47: STANDARD DRAWINGS Application of Standard Drawings ...

7" - 8"

812" - 10"

1012" & up

1"

114"

112"

Pvmt. Thkn. (T) Dowel Dia.

Existingpanel

NOTES:

1. Install tie bars along longitudinal joints between full panel replacement and existing concrete pavement. Tiebars are not installed between concrete pavement and ACP pavement.

2. Place 2 layers of #30 felt bond breaker meeting the requirements of ASTM D226, Type II at joints betweenpanel replacement and existing panel.

3. Place new dowel bars between any existing (cut) dowel bars.

4. Center tie bars and dowel bars on joint.

5. Any repair of PCC pavement must be a full panel replacement.

6. Dowel holes should be 116 inch oversize in diameter and 9 inches to 9.5 inches deep for 18 inch long smoothdowels and 18 inches to 18.5 inches deep for 36 inch long tie bars. A hand held drill is not allowed.

7. Fill clean dowel hole with quick-set epoxy grout complying with ASTM C 881 Types IV or V, Grade 3, Classes B &C, suitable for anchoring smooth dowel bars in hardened concrete and on the ODOT QPL. Insert smooth fullygreased dowels with grout retention ring into hole.

8. If the time frame designated for opening traffic is less than 72 hours after concrete placement, provide Class

HES4000 - 112 concrete designed to attain a minimum average compressive strength of 3,000 psi prior to

allowing traffic on the concrete. Otherwise furnish Class 4000 - 112 paving concrete.

9. The surface of the concrete shall have a textured finish using a steel-tine tool with 18 inch tines that will markthe finished concrete to a depth of 116 inch to 18 inch. Randomly space the markings from ½ inch to 1¼ inches asapproved. Avoid overlaps of the texturing. Markings shall be transverse to the roadway centerline and fullroadway width.

10. New interior longitudinal and transverse joints shall be sawcut as soon as the concrete has set enough to allowsawing without tearing or raveling.

11. The new saw cut transverse and longitudinal joints shall be filled with poured rubber-asphalt joint filler. Thesaw cut joint shall be flushed with water, vacuumed to remove cement slurry and dried before installing thejoint filler.

12. Irregularly shaped panels, rectangular panels with an aspect ratio exceeding 1:1.25, and panels containing morethan one utility structure (such as manholes, valves, etc.) shall be reinforced. See reinforcement grid details thissheet.

13. All tie bars and dowel bars shall be Grade 60 steel and shall be smooth, epoxy coated, circular, and greased.

See note 2

Existing transversejoint18" dowel bars

36" tie bars

Edge of conc. pvmt.

18" dowel bars

Existing edge. of shldr. (typ.)

Existinglongitudinaljoint

Saw and seal joint(See notes 11 and 12)

Saw and seal joint(See notes 11 and 12)Tool edge

Resin bonded anchor

18" dowel bars @ 12" centers(See dowel bar table)

18" dowel bars @ 12" centers(See dowel bar table)

Drill and secure dowelbars into extg. conc. pvmt.(See notes 7 and 8)

#5 tie bars 36" long@ 36" centers

#5 tie bars 36" long@ 36" centers

T T

T/2T/2

T

T/2

T

T/2

Dowel Bar Table

Existingpanel

Existingpanel

Newpanel

Existingpanel

Newpanel

Newpanel

Newpanel

ExistingpanelExisting

panel

Existingpanel

Newpanel

12

"

18"Lan

e w

idth

Co

ncr

ete

pa

ve

me

nt

T/3

T/4

Section C-C

Contact Joint

Section D-D

Weakened Plane Joint

Section B-B

Contraction Joint

Section A-A

Construction Joint

SCALE:

TRANSVERSE JOINT

NTS

SCALE:

LONGITUDINAL JOINT

NTS

SCALE:

PLAN VIEW

NTS

Extg. conc. pvmt. New conc. pvmt.

Extg. conc. pvmt.New conc. pvmt.

Bond breaker(See note 2)

Bond breaker(See note 2)

AABB

D

D

C

C

Existingpanel

SCALE:

TYPICAL PAVEMENT SECTION

NTS

Textured finish

(See note 10)

Extg.aggregatebase

T

New panel

See Std. Drg. No. 220-2 for boxouts andreinforcement at manholes and inlets

Skewedjoint

Dowelparallel to

roadway CL

SCALE:

DOWEL AT SKEWED JOINT

NTS

PCC pavement(See note 9)

SCALE:

PLACEMENT NEAR JOINTS

REINFORCEMENT GRID

NTS

2"typ.

3"typ.

Smooth dowel ortie bar per plan

#5 bar @ 12" on center eachway supported on bar chairs.Locate per plan

90° preferred60° minimum

Tool edge (typ.)

SCALE:

REINFORCEMENT GRID

NTS

#5 bars @ 12" oncenter, each way.

Place T/3 (2" min.)clear from topsurface of concrete

T/3

2"

min

.

FILENAME: 250-3.dwg

SCALE: NONE

DATE: JUNE 2018

CONCRETE ROADWAY REPAIR 250-3

Page 48: STANDARD DRAWINGS Application of Standard Drawings ...

1. These trench backfill requirements apply to all public utility pipes. For additional requirements, see

CWS Design and Construction Standards and City's Engineering Design Manual section 211.

2. For trenches 12" wide or less in streets with classifications higher than Residential, use controlled

density fill (CDF) as per sec 210.19. For all other trenches, use 3/4" - 0" aggregate compacted to

95% of max density per AASHTO t-99 and ODOT/APWA spec 00405.

3. Use class 'A' backfill compacted to 90% of max density per AASHTO t-99 and ODOT/APWA spec

00405.

4. Tracer wire shall be placed above non-metalic pipe and 2 feet below finished grade when required

by Oregon State Plumbing code. Reference City's EDM section 211.1.4.o. Storm and sanitary

sewer services shall be marked with magnetic tape per CWS D&C section 5.09.4.c

5. Restore to original conditions or better. See specifications and drawing 302.

6. For conduit trench requirements see drawing 301.

7. The City reserves the right to require compaction testing of the bedding material when it exceeds

the 4-inch base section beneath the pipe.

BEDDING

PIPE ZONE

T-CUT & PAVEMENT

RESURFACING

SEE NOTE 5

WITHIN STREET

RIGHT-OF-WAY

BACKFILL

SEE NOTE 2

TRACER WIRE

SEE NOTE 4

EXISTING

PAVEMENT

SECTION

SEE NOTE 5

NOTES:

BACKFILL

SEE NOTE 3

A

"A" min."D" nom.

4-10

12-16

18-21

24-30

36-72

16

24

18

12

9

SHORING/TRENCH

CLEARANCE

WIDTH TABLE

(in.) (in.)

SHORING/TRENCH

CLEARANCE WIDTH

SEE TABLE ABOVE

RESTORE TO PRE-EXISTING

CONDITIONS OR BETTER

PER SPECS

6"

D/2

4"

VA

RIA

BL

E D

EP

TH

OF

CU

T

AS APPROVED BY CITY ENGINEER

OUTSIDE STREET RIGHT-OF-WAY

D 34" - 0" PIPE BEDDING

AND

PIPE ZONE MATERIAL

SCALE: NONE

DATE: JUNE 2018PIPE TRENCH BACKFILL 300

Page 49: STANDARD DRAWINGS Application of Standard Drawings ...

1. THESE TRENCH BACKFILL REQUIREMENTS APPLY TO ALL PUBLIC UTILITY PIPES. FOR

ADDITIONAL REQUIREMENTS, SEE CWS DESIGN AND CONSTRUCTION STANDARDS AND

CITY'S ENGINEERING DESIGN MANUAL SECTIONS 211

2. FOR TRENCHES 12" WIDE OR LESS IN STREETS WITH CLASSIFICATIONS HIGHER THAN

RESIDENTIAL, USE CONTROLLED DENSITY FILL (CDF) AS PER SEC 210.19. FOR ALL

OTHER TRENCHES, USE 3/4" - 0" AGGREGATE COMPACTED TO 95% OF MAX DENSITY

PER AASHTO T-99 AND ODOT/APWA SPEC 00405.

3. USE CLASS 'A' BACKFILL COMPACTED TO 90% OF MAX DENSITY PER AASHTO T-99 AND

ODOT/APWA SPEC 00405.

4. TRACER WIRE SHALL BE PLACED ABOVE NON-METALIC PIPE AND 2 FEET BELOW

FINISHED GRADE WHEN REQUIRED BY OREGON STATE PLUMBING CODE. REFERENCE

CITY'S EDM SECTION 211.1.4.o.

5. RESTORE TO ORIGINAL CONDITIONS OR BETTER. SEE SPECS AND BEAVERTON

STANDARD DWG 302.

WITHIN EXTG PAVED AREAS

& UNDER EXTG SIDEWALKS

T-CUT & PAVEMENT

RESURFACING

SEE NOTE 5

NOTES:

BACKFILL

SEE NOTE 2

EXISTING

PAVEMENT

SECTION

SEE NOTE 5

CDF, SAND OR PEA

GRAVEL PER SPECS

4"

VA

RIA

BL

E D

EP

TH

OF

CU

T

RESTORE TO PRE-EXISTING

CONDITIONS OR BETTER

PER SPECS

TRACER WIRE

SEE NOTE 4

BACKFILL

SEE NOTE 3

OUTSIDE PAVED AREAS

6"

SCALE: NONE

DATE: JUNE 2018CONDUIT TRENCH BACKFILL 301

Page 50: STANDARD DRAWINGS Application of Standard Drawings ...

WIDENED T-CUT PAVEMENT

RESTORATION AREA

WIDTH VARIES

BASE COURSE

SEE NOTE 4C

1. This drawing applies to trench cuts and other kinds of pavement cuts.

2. For width dimensions, see Engineering Design Manual and the notes that follow.

3. Sawcut existing AC pavement full depth. Sawcut existing PCC pavement according to Drawing

310

4. Restore existing pavement material(s) to pre-existing or better conditions. Thickness shall be as

follows:

a. For existing Portland Cement Concrete (PCC): existing pavement thickness plus 2 inches, but

not less than 8 inches. On Arterial and Collector streets, concrete patching material shall be high

early strength class 5,000 psi PCC approved by City Engineer.

b. For existing Asphalt Concrete (AC): resurface to a minimum of 312" of Level 2, 12" ACP or existing

AC thickness plus 2 inches, whichever is greater, but do not exceed 6 inches. Compact AC in

2-inch maximum lifts to 91% of maximum density (Rice).

c. Base course shall be 3/4"-0 aggregate compacted to 95% of max density as per AASHTO T-99

and ODOT/APWA Spec 00405. Minimum thickness shall be 8 inches under AC pavement and 2

inches under PCC pavement.

5. All cut edges of AC shall be sand sealed with CRS-1 or CRS-2 emulsified asphalt or equal.

6. If new edge of pavement is less than three feet from another patch, curb or edge of street, replace

the pavement in between.

7. If any part of more than one pre-existing patch edge is within 3 feet of the T-cut, remove and

restore the pavement to the far edge of the furthest pre-existing patch.

8. On longitudinal pavement cuts, the edge of the T-cut shall not lie in a wheel path. Width of T-cut

shall be widened where necessary to move the edge out of the wheel path and either to parallel

and 6 inches from the nearest lane line, or to the location required by note 6 or 7 above as

applicable, whichever is the furthest from the pavement cut.

9. If an edge of a T-cut will be within 5 feet or less of an area of distressed existing pavement, the

length and width of the pavement restoration shall be determined by City Engineer upon

notification by the Contractor.

10. Width from edge of trench shall be 6 inches minimum for trenches that are 12 inches wide or less

and 12 inches minimum for trenches wider than 12 inches. The width may be increased up to 10

feet on both sides of the pavement cut as approved by City Engineer.

T-CUT WIDENING AREA

EXTG BASE ROCK

SAWCUT SOUND

EXISTING PAVEMENT

SEE NOTE 3

NOTES:

CROSS SECTION

MIN12"

WIDTH

SEE NOTE 10

VARIES

NEW T-CUT

PAVEMENT

EDGE LINE

STANDARD T-CUT PAVEMENT

RESTORATION AREA

SEE NOTE 2

SCALE: NONE

DATE: JUNE 2018

PAVEMENT CUT

RESTORATION302

Page 51: STANDARD DRAWINGS Application of Standard Drawings ...

LONGITUDINAL JOINT PER OPTION B

UTILITY

TRENCH

HIGH EARLY STRENGTH

1. OPTION A (not allowed on Arterial streets, bus routes or truck routes.): Sawcut pavement 4 inches

deep or 1/2 the panel thickness (T), whichever is greater, before removal. Break out with mechanical

hammer and carefully remove remaining concrete next to joint so as not to disturb the pavement

surface to remain. One side of utility cut is to be along existing joint. OPTION B: Sawcut pavement full

depth and install 112 inch Ø dowels as shown. After drilling holes, place non-shrink grout in back of

holes before inserting dowels. (Note: At interfaces of two adjacent new panels, an approved keyway

may be substituted for dowels. For sawcuts through existing panel joints, sawcut existing panel joint(s)

full depth before removing existing pavement.)

2. Partial panel replacement may be approved by the City Engineer per the Engineering Design Manual.

3. If utility trench width is greater than 1/2 of the panel width, then remove pavement to the next joint.

4. If utility trench wall must be closer than 3 feet from the joint, then remove pavement to the joint.

5. When panels are offset or irregular in any manner, the City Engineer shall determine the area of

pavement replacement.

6. After placement of pavement, re-sawcut the joints that intersect the trench. The depth of sawcut is to

be T/3. Seal the new joints per the Engineering Design Manual.

7. If pavement is undermined during repair, sawcut and remove pavement back to undisturbed subgrade.

8. If pavement is damaged during repair, sawcut and remove back to undamaged pavement.

UNDISTURBED SUBGRADE

SAWCUT AND BREAK OUT

REMAINING CONCRETE

SEE NOTE 1. WHERE PAVEMENT

BREAKOUT UNDERMINES SAWCUT

EDGE MORE THAN 2 FEET

LONG ALONG EDGE, FOLLOW

OPTION B REQUIREMENTS

ARTERIALS,

BUS ROUTES

AND TRUCK

ROUTES

OTHER

STREETS,

MEDIAN

LANES AND

TURN LANES

NOTES:

5,000 PSI PCC

3' MIN

3' MIN

T (THICKNESS)

T / 2

INLETSTANDARD CURB & GUTTER

UTILITY TRENCH

FORM NEW

JOINT AND SEAL

WITH APPROVED

SEALANT

MANHOLE

PROVIDE BOND BREAKER TYP

OPTION A - 8' MIN

OPTION B - 6' MIN

24"

CROSS SECTION

PLAN VIEW

FULL

PANEL

TYP

EXISTING

JOINTS

24"

T + 2", BUT NOT

LESS THAN 8"3/4"-0 AGG BACKFILL COMPACTED

TO 95% MAX DENSITY AS PER

AASHTO T-99

INSTALL 11

2" Ø DOWELS,18" LONG @ 12" CENTERS

SAWCUT FULL DEPTH

SEE NOTE 1

SCALE: NONE

DATE: JUNE 2018

STREET CUT IN PCC

PAVEMENT PERPENDICULAR

OR SKEWED TO CENTERLINE305

Page 52: STANDARD DRAWINGS Application of Standard Drawings ...

INSTALL #5 TIE BARS,

20" LONG @ 30" CENTERS

UNDISTURBED SUBGRADE

SAWCUT AND

BREAK OUT REMAINING

CONCRETE - SEE NOTE 1

1. OPTION A : Sawcut pavement 4 inches deep or 1/2 the panel thickness (T), whichever is greater,

before removal. Break out with mechanical hammer and carefully remove pavement next to joint so as

not to disturb the pavement surface to remain. OPTION B: Sawcut pavement full depth and install #5

tie bars and 112 inch Ø dowels as shown (minimum of 2). (Note: At interfaces of two adjacent new

panels, an approved keyway may be substituted for dowels.)

2. Tie bars: after drilling holes, place non-shrink grout in back of holes before inserting tie bars.

3. Partial panel replacement may be approved by the City Engineer per the Engineering Design Manual.

4. If utility trench width is greater than 1/2 of the panel width, then remove pavement to the next joint. For

sawcuts through existing panel joints, sawcut existing panel joint(s) full depth before removing existing

pavement.

5. If utility trench wall must be closer than 3 feet from the joint, then remove pavement to the joint.

6. When panels are offset or irregular in any manner, the City Engineer shall determine the area of

pavement replacement.

7. After placement of pavement, re-sawcut the joints that intersect the trench. The depth of sawcut is to

be T/3. Seal the new joints per the Engineering Design Manual.

8. If pavement is undermined during repair, sawcut and remove pavement back to undisturbed subgrade.

9. If pavement is damaged during repair, sawcut and remove back to undamaged pavement.

HIGH EARLY STRENGTH

T (THICKNESS)

NOTES:

5,000 PSI PCC

3' MIN

3' MIN

ARTERIALS,

BUS ROUTES

AND TRUCK

ROUTES

OTHER

STREETS,

MEDIAN

LANES AND

TURN LANES

UTILITY TRENCH

24" 24"

SAWCUT FULL

DEPTH - SEE NOTE 1

T / 2

INSTALL #5 TIE BARS,

20" LONG @ 30" CENTERS

3/4"-0 AGG BACKFILL COMPACTED

TO 95% MAX DENSITY AS PER

AASHTO T-99

T + 2", BUT NOT

LESS THAN 8"

PLAN VIEW

TRANSVERSE JOINTS

11

2" Ø DOWELS,18" LONG @ 12"

CENTERS TYP

STANDARD CURB

AND GUTTER

CROSS SECTION

UTILITY

TRENCH

PROVIDE BOND

BREAKER TYP

LONGITUDINAL JOINT

PER OPTION B

6' MIN

6' MIN

JOINTS

EXISTING

SCALE: NONE

DATE: JUNE 2018

STREET CUT IN PCC PAVEMENT

PARALLEL TO CENTERLINE306

Page 53: STANDARD DRAWINGS Application of Standard Drawings ...

1. If any part of an AC pavement restoration fails, a corrective inlay will be required. The width and

length of the inlay will be determined by the City Engineer pursuant to these Standard Drawings.

2. In this example, the utility cut or trench is located within an AC roadway without a bike lane or

parking lane, and there is less than 3 feet between the final pavement cut and the edge of AC

pavement. Therefore, the permitee shall grind and inlay to the edge of the pavement as shown.

3. Where there is 3 feet or more between final pavement cut and edge of AC pavement, permitee

may "jog" the grind and inlay as shown. The number of jogs shall be kept to a minimum.

6. The width of example "A-1" grind / mill and inlay shall be 9 feet minimum, 13 feet maximum.

TRAVEL LANE

OR TURN LANE

TRAFFIC FLOW

EDGE OF EXAMPLE

"A-1" FINAL PAVEMENT

CUT ("T"-CUT)

NOTES:

TRAVEL LANE,

TURN LANE OR MEDIAN

WIDTH VARIES

LANE

LINE

6" TYP

3' MIN TYP

1' MIN TYP

JOG INLAY - SEE NOTE 3

WIDTH OF INLAY

SEE NOTE 4

TRAVEL LANE

WIDTH VARIES

SHOULDER,

PLANTER

STRIP OR

SIDEWALK

TY

P

15'

FACE OF CURB, EDGE

OF PAVEMENT OR

EDGE OF CONCRETE

GUTTER

UTILITY CUT/TRENCH

WALL EXAMPLE "A-1"

LESS THAN 3'

BETWEEN THE FINAL

PAVEMENT CUT AND

THE EDGE OF AC

PAVEMENT

TRAFFIC FLOW

EDGE OF INLAY

EXAMPLE "A-1"

SCALE: NONE

DATE: JUNE 2018

CORRECTIVE AC PAVEMENT

INLAY EXAMPLE ʺA-1ʺ FOR

UTILITY CUT OR TRENCH310

Page 54: STANDARD DRAWINGS Application of Standard Drawings ...

TRAVEL LANE,

TURN LANE OR MEDIAN

WIDTH VARIES

1' MIN TYP

6" TYP

3' MIN TYP

If any part of an AC pavement restoration fails, a corrective inlay will be required. The width and

length of the inlay will be determined by the City Engineer pursuant to these Standard Drawings.

In this example, the utility cut or trench is located within an AC roadway without a bike lane or

parking lane, and there is 3 feet or more between the final pavement cut and the edge of AC

pavement.

The width of example "A-2" grind / mill and inlay shall be 9 feet minimum, 13 feet maximum.

1.

2.

3.

TRAVEL LANE

OR TURN LANE

TRAFFIC FLOW

NOTES:

LANE

LINE

EDGE OF INLAY

WIDTH OF INLAY

SEE NOTE 3

TRAVEL LANE

WIDTH VARIES

15'

TY

P

SHOULDER,

PLANTER

STRIP OR

SIDEWALK

3' OR MORE

BETWEEN THE FINAL

PAVEMENT CUT AND

THE EDGE OF AC

PAVEMENT

FACE OF CURB, EDGE

OF PAVEMENT OR

EDGE OF CONCRETE

GUTTER

EDGE OF EXAMPLE

"A-2" FINAL PAVEMENT

CUT ("T"-CUT)

UTILITY CUT/TRENCH

WALL EXAMPLE "A-2"

TRAFFIC FLOW

1' MIN TYP

TY

P1

5'

EXAMPLE "A-2"

SCALE: NONE

DATE: JUNE 2018

CORRECTIVE AC PAVEMENT

INLAY EXAMPLE ʺA-2ʺ FOR

UTILITY CUT OR TRENCH311

Page 55: STANDARD DRAWINGS Application of Standard Drawings ...

TRAVEL LANE,

TURN LANE OR MEDIAN

WIDTH VARIES

TRAVEL LANE

OR TURN LANE

TRAFFIC FLOW

WIDTH OF INLAY - SEE NOTE 3

1. If any part of an AC pavement restoration fails, a corrective inlay will be required. The width and

length of the inlay will be determined by the City Engineer pursuant to these Standard Drawings.

2. In this example, the utility cut or trench is located within an AC roadway without a bike lane or

parking lane, and there is less than 5 feet between parallel trench cuts.

3. The width of example "A-3" grind/mill and inlay shall be 9 feet minimum, 24 feet maximum, and

shall not encroach on adjacent travel lane or turn lane unless one of the two parallel pavement

cuts is in each lane, and then not more than 2 feet.

1' MIN

6" TYP

LESS THAN 5'

BETWEEN

PARALLEL

TRENCH

CUTS

EDGE OF

INLAY

TY

P

15'

UTILITY

CUT/

TRENCH

WALL

EXAMPLE

"A-3"

NOTES:

TRAVEL LANE

WIDTH VARIES

SHOULDER,

PLANTER

STRIP OR

SIDEWALK

VARIES

3' MIN

TYP

FACE OF

CURB, EDGE

OF PAVEMENT

OR EDGE OF

CONCRETE

GUTTER

EDGE OF

VISIBLE OLD

CUT OR

SECOND NEW

CUT

EDGE OF

EXAMPLE "A-3"

FINAL

PAVEMENT

CUT ("T"-CUT)

LANE

LINE

TRAFFIC FLOW

1' MIN TYP

EXAMPLE "A-3"

SCALE: NONE

DATE: JUNE 2018

CORRECTIVE AC PAVEMENT

INLAY EXAMPLE ʺA-3ʺ FOR

UTILITY CUT OR TRENCH312

Page 56: STANDARD DRAWINGS Application of Standard Drawings ...

1. If any part of an AC pavement restoration fails, a corrective inlay will be required. The width and

length of the inlay will be determined by the City Engineer pursuant to these Standard Drawings.

2. In this example, the utility cut or trench is located within an AC roadway with a bike lane or parking

lane, and there is less than 3 feet between the final pavement cut and the edge of AC pavement.

3. The number of jogs in the inlay shall be kept to a minimum.

4. The width of example "B-1" grind / mill and inlay shall be 9 feet minimum, 13 feet maximum.

TRAVEL LANE

OR TURN LANE

TRAFFIC FLOW

NOTES:

TRAVEL LANE,

TURN LANE OR MEDIAN

WIDTH VARIES

LANE

LINE

1' MIN TYP

3' MIN TYP

JOG IN INLAY

SEE NOTE 3

WIDTH OF INLAY - SEE NOTE 4

BIKE LANE OR

PARKING LANE

(WIDTH VARIES)TRAVEL LANE

WIDTH VARIES

TY

P

15'

SHOULDER,

PLANTER

STRIP OR

SIDEWALK

LESS THAN 3'

BETWEEN THE FINAL

PAVEMENT CUT AND

THE EDGE OF THE AC

PAVEMENT

FACE OF CURB, EDGE

OF PAVEMENT OR

EDGE OF CONCRETE

GUTTER

LANE

LINE

BIKE LANE

TRAFFIC FLOWTRAFFIC FLOW

EDGE OF INLAY

UTILITY CUT/TRENCH

WALL EXAMPLE "B-1"

EDGE OF EXAMPLE

"B-1" FINAL PAVEMENT

CUT ("T"-CUT)

EXAMPLE "B-1"

SCALE: NONE

DATE: JUNE 2018

CORRECTIVE AC PAVEMENT

INLAY EXAMPLE ʺB-1ʺ FOR

UTILITY CUT OR TRENCH313

Page 57: STANDARD DRAWINGS Application of Standard Drawings ...

1. If any part of an AC pavement restoration fails, a corrective inlay will be required. The width and

length of the inlay will be determined by the City Engineer pursuant to these Standard Drawings.

2. In this example, the utility cut or trench is located within an AC roadway with a bike lane or parking

lane, and there is 3 feet or more between the edge of AC pavement and final pavement cut.

3. The number of jogs in the inlay shall be kept to a minimum.

4. The width of example "B-2" grind / mill and inlay shall be 9 feet minimum, 13 feet maximum.

6" TYP

TRAVEL LANE

OR TURN LANE

TRAFFIC FLOW

NOTES:

TRAVEL LANE,

TURN LANE OR MEDIAN

WIDTH VARIES

3' MIN TYP

1' MIN TYP

LANE

LINE

JOG IN INLAY

SEE NOTE 3

TY

P

15'

WIDTH OF INLAY - SEE NOTE 4

BIKE LANE OR

PARKING LANE

WIDTH VARIES

TRAVEL LANE

WIDTH VARIES

15'

TY

P

SHOULDER,

PLANTER

STRIP OR

SIDEWALK

3' OR MORE BETWEEN

EDGE OF AC

PAVEMENT AND FINAL

PAVEMENT CUT

FACE OF CURB, EDGE

OF PAVEMENT OR

EDGE OF CONCRETE

GUTTER

EDGE OF EXAMPLE

"B-2" FINAL PAVEMENT

CUT ("T"-CUT)

LANE

LINE

TRAFFIC FLOW BIKE LANE

TRAFFIC FLOW

EDGE OF INLAY

UTILITY CUT/TRENCH

WALL EXAMPLE "B-2"

EXAMPLE "B-2"

SCALE: NONE

DATE: JUNE 2018

CORRECTIVE AC PAVEMENT

INLAY EXAMPLE ʺB-2ʺ FOR

UTILITY CUT OR TRENCH314

Page 58: STANDARD DRAWINGS Application of Standard Drawings ...

LANE

LINE

TRAVEL LANE,

TURN LANE OR MEDIAN

WIDTH VARIES

WIDTH OF INLAY

SEE NOTE 4

TRAVEL LANE

OR TURN LANE

TRAFFIC FLOW

1. If any part of an AC pavement restoration fails, a corrective inlay will be required. The width and

length of the inlay will be determined by the City Engineer pursuant to these Standard Drawings.

2. In this example, the utility cut or trench is located within an AC roadway with a bike lane or parking

lane, and there is less than 5 feet between parallel trench cuts.

3. The number of jogs in the inlay shall be kept to a minimum.

4. The width of example "B-3" grind / mill and inlay shall be 9 feet minimum, 24 feet maximum, and

shall not encroach on adjacent travel lane or turn lane unless one of the two parallel pavement

cuts is in each lane, and then the grind / mill and inlay shall not encroach more than 2 feet.

NOTES:

6" TYP

LESS THAN

5' BETWEEN

PARALLEL

TRENCH

CUTS

EDGE OF

VISIBLE

OLD CUT

OR

SECOND

NEW CUT

JOG IN INLAY

SEE NOTE 3

EDGE OF

INLAY

3' MIN

TYP

TRAFFIC FLOW BIKE LANE

TRAFFIC FLOW

EXAMPLE "B-3"

UTILITY CUT/

TRENCH WALL

EXAMPLE "B-3"

9' MINTYP

FACE OF

CURB, EDGE

OF PAVEMENT

OR EDGE OF

CONCRETE

GUTTER

EDGE OF

EXAMPLE

"B-3" FINAL

PAVEMENT

CUT ("T"-CUT)

1' MIN TYP

3' MIN TYP

LANE

LINE SHOULDER,

PLANTER

STRIP OR

SIDEWALK

TRAVEL LANE

WIDTH VARIES

BIKE LANE OR

PARKING LANE

WIDTH VARIES

2' MAX TYP

SCALE: NONE

DATE: JUNE 2018

CORRECTIVE AC PAVEMENT

INLAY EXAMPLE ʺB-3ʺ FOR

UTILITY CUT OR TRENCH315

Page 59: STANDARD DRAWINGS Application of Standard Drawings ...

1. This manhole adjustment method is to be used for adjusting a new or existing manhole after

paving over it with the HMAC base and wearing courses.

2. Cover manhole with building paper and construct HMAC base and wearing courses.

3. Sawcut square or circular excavation around manhole 12 inches minimum from manhole

frame. Orient diagonal of square so that it is parallel to roadway centerline.

4. Raise manhole frame and cover to finish grade by installing concrete grade rings and leveling

mortar. No more than 10 inches of concrete grade rings shall be used to adjust any manhole

to grade. Metal paving rings/risers are not allowed, except as necessary during a pavement

overlay project, in which case only one (1) paving ring is allowed. Engineer must design and

include calculations in the construction plan set, showing which manhole adjustment option

will be used at each location.

5. Backfill with early strength PCC and HMAC wearing course.

BACKFILL WITH EARLY STRENGTH CONCRETE AS REQUIRED

AC PAVEMENT

WEARING COURSE

#4 BAR OR

HOOP - 2 EACH

NOTES:

#4 BAR OR

HOOP

AC PAVEMENT

BASE COURSE

SECTION A-A

DIR

EC

TIO

N

OF

TR

AV

EL

MANHOLEA

PLAN

CONCRETE GRADE RINGS - SEE NOTE 4

MORTAR

2" MAX

RAISE AS

DIRECTED CUT LINE

11

2" MIN

A

CUT LINE

12" MIN SAND

SEAL

SCALE: NONE

DATE: JUNE 2018

MANHOLE ADJUSTMENT

SEQUENCE OPTION 1320

Page 60: STANDARD DRAWINGS Application of Standard Drawings ...

AC PAVEMENT

WEARING COURSE

BACKFILL WITH EARLY STRENGTH CONCRETE AS REQUIRED

#4 BAR OR

HOOP - 2 EACH

NOTES:1. This manhole adjustment method is to be used for adjusting a new or existing manhole before paving

over it with the HMAC wearing course or a pavement overlay.

2. If manhole is in street to be overlaid, go directly to note 3. If manhole is in a new pavement section,

cover manhole with building paper and construct HMAC base course over manhole.

3. Sawcut square or circular excavation around manhole 12 inches minimum from manhole frame. Orient

diagonal of square so that it is parallel to roadway centerline.

4. Raise manhole frame and cover to finish grade by installing concrete grade rings and leveling mortar.

No more than 10 inches of concrete grade rings shall be used to adjust any manhole to grade. Metal

paving rings/risers are not allowed, except as necessary during a pavement overlay project, in which

case only one (1) paving ring is allowed. Engineer must design and include calculations in the

construction plan set, showing which manhole adjustment option will be used at each location.

5. Backfill with early strength PCC.

6. Construct HMAC wearing course.

AC PAVEMENT

BASE COURSE

#4 BAR OR

HOOP

12" MIN

11

2" MIN

CUT LINE

RAISE AS

DIRECTED

MORTAR

2" MAX

CONCRETE GRADE RINGS - SEE NOTE 4

CUT LINE

A

PLAN

A MANHOLE

SECTION A-A

DIR

EC

TIO

N

OF

TR

AV

EL

SCALE: NONE

DATE: JUNE 2018

MANHOLE ADJUSTMENT

SEQUENCE OPTION 2321

Page 61: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

CWS STANDARD MANHOLE

WITH C.O.B. MODIFICATIONS330

Page 62: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018MANHOLE CONNECTIONS 331

Page 63: STANDARD DRAWINGS Application of Standard Drawings ...

* 36", TYP

OR 6"

BEYOND

TRENCHLINE,

WHICHEVER IS

GREATER

1. This drawing replaces CWS Standard Dwg 050

and has been modified for use by City of Beaverton

Ordinance #4303.

2. All joints and rubber gaskets shall conform to the

requirements of ASTM C-433.

3. All manhole sections shall conform to the

requirements of ASTM C-478 and applicable

provisions of drawing 330.

4. Steps required on flat top manholes deeper than

48 inches.

5. *When depth of manhole is less than 4 feet, make

hole for frame and cover in center of cover slab.

Provide cover slab reinforcing design for all

applications. Submit design to the City for review.

6. *Impact slab required when cover slab protrudes into

road base material. Provide impact slab reinforcing

design. Submit design to the City for review.

7. *Provide cover slab reinforcing design for all applications. Submit design to the City for review.

8. *The City reserves the right to deviate from this drawing and related requirements in the

Engineering Design Manual as dictated by project design parameters, and as approved by

the City Engineer.

* 2"

MIN

TYP

NOTES:

* 6" MIN

10"

* IMPACT SLAB

RUBBER

GASKET

* INDICATES MODIFICATIONS

OF CWS STANDARD DWG 050

RUBBER GASKET

FLAT TOP(OPTIONAL)

25"

48"

CONCRETE8" MIN

* 5

9"

MA

X

SE

E N

OT

E 5

58" Ø

64" Ø

23"

48"

* AC =

11

2"

* 8"

MIN

* AC = 11

2"* COVER SLAB

SCALE: NONE

DATE: JUNE 2018

CWS FLAT TOP MANHOLE

WITH C.O.B. MODIFICATIONS335

Page 64: STANDARD DRAWINGS Application of Standard Drawings ...

1. Manhole cone shall be manufactured by Cascade Concrete Products Inc or approved equal and

conform to the requirements of ASTM C-478 and applicable provisions of drawing 330

2. Reinforcing steel is grade 60. Steel area is 0.12 square inch per foot, (D3 on 3 inch spacing), 2" clear

of the external surface.

3. All joints and rubber gaskets shall conform to the requirements of ASTM C-433.

4. Concrete shall have a 28 day ultimate strength of 4000 psi.

5. Lower section height varies and is to be deternmined by engineer.

NOTES:

18"MAX36"

STANDARD OR SUBURBAN STYLE

FRAME & COVER AS SPECIFIED

CONCRETE DONUTS

IF REQUIRED

REINFORCING STEEL

SEE NOTE 2

5" MIN

25"

48" JOINT

SEE NOTE 3

SEE NOTE 5

5" MIN

SCALE: NONE

DATE: JUNE 2018SHALLOW MANHOLE CONE 336

Page 65: STANDARD DRAWINGS Application of Standard Drawings ...

STANDARD CAST

IRON FRAME AND

COVER PER CWS

STANDARD DWG 160

SEE NOTE 2

2" MIN

CLEARANCE

CONCRETE ENCASED

BOTTOM OF WYE

FOR PLASTIC PIPE

1. Concrete encase entire wye section and 45° bend if

concrete pipe.

2. Cleanout in sidewalk to be centered in sidewalk width.

3/4"-0

DETAIL

MAINTO SEWER

FINISH GRADE

NOTES:

STANDARD MANHOLE

GRADE RING

TOPSOIL UNLESS

OTHERWISE

SPECIFIED

WATERTIGHT PIPE

PLUG WITH STOPS

PROVIDE 3/4"-0 FOR A

MINIMUM OF 6" AROUND

CLEANOUT

SEE DETAIL

4" MIN

NON-SHRINK GROUT

MIN6"

PLUG AT END OF

SEWER MAIN

3/4"-0

TO BUILDING

SCALE: NONE

DATE: JUNE 2018

STANDARD CLEANOUT IN

EXISTING STREET340

Page 66: STANDARD DRAWINGS Application of Standard Drawings ...

NOTES:

1. Curb inlet top section and base are similar to, and

structural reinforcing is equal to, ODOT/APWA curb inlet

Type CG-3 Alternate Top Section, with altered

dimensions, as shown.

2. All fabricated metal parts shall be new structural, ASTM

A-36 steel, and be hot-dipped galvanized after

fabrication, and all steel reinforcing shall be as per

ODOT/APWA Standard Dwg ERD372.

3. All poured in place concrete shall have a 28 day

strength of 3,000 psi, and slump of 2" to 4"

4. Install steps when distance from top of lid to flowline of

pipe is greater than 48 inches, see Clean Water Services

Standard Dwg 100. Set first step 12 inches from top of

grate.

5. Install structure on minimum of 8 inches of 3/4"-0

compacted base material.

PLAN VIEW

A

SECTION A-A

OF DEPRESSED GUTTER AT CURB INLET

PERSPECTIVE VIEW

SCALE: NONE

DATE: JUNE 2018

CURB INLET CATCH BASIN

WITH C.O.B. MODIFICATIONS345

36" 42" 36"

30" wide

curb inlet opening

6"

(typ)

39"

27"

Back of curb

Face of curb

Gutter edge

Flow line

Manhole cover & frame.

See CWS Standard Details

110, 120, or 130

A

Outlet pipe

(location

varies)

Angle nosing

312"x31

2"x14"

Face of curb

Concrete gutter

Pavement

3" weep hole located

at base of roadway

subgrade

7.5

"

min

40"

2% Slope max

Manhole steps

See note 4

18

" m

in

su

mp

Outlet pipe

(location varies)

28"

12" premolded

expansion joint

filler (typ)

Water tight seal.

See drawing 331

Sidewalk or planter strip - See

approved construction plans

Scored joint

in sidewalk

SECTION B-B

B

B

12"x10" anchor boltw/ (2) nuts

12"x8" anchor bolts

18

" m

in

su

mp

3"

min

.

Flow line

Face of curb30" wide

curb inlet opening4"

op

enin

g

min

Weep hole

Outlet pipe

(location per plans)

72"

ma

x

11

2"

de

pre

ssio

n

Page 67: STANDARD DRAWINGS Application of Standard Drawings ...

ELEVATION

CONCRETE

This detail is required only when pipe slope is 20% or greater.

1'-0"

6" MIN

12"

MIN

PIPE BEDDING

POUR CONCRETE

AGAINST

UNDISTURBED SOIL

1'-0"

NOTE:

PLAN

MIN12"

TRENCH

WIDTH AS

REQUIRED

12"MIN

6" MIN

12" MIN

SOCKET

CLAMP

BENT #5

REBAR

12" MIN

UNDERGROUND

SOCKET CLAMPPVC OR ABS

GRAVITY PIPE

TRENCH

BOTTOM

#5 REBAR FORMED INTO Z-BEND

MAINTAIN 3" MIN CLEARANCE

SECTION

WIDTHTRENCH

3,000 PSI COMPRESSIVE STRENGTH

PCC THRUST BLOCK AGAINST

UNDISTURBED EARTH BEARING AREA

ON BOTH SIDES OF PIPE

15 feet

or concrete encasement

MINIMUM ANCHOR SPACING,

CENTER TO CENTER

35 feet

SLOPE

0.20 - 0.34

0.35 - 0.50

0.51 +

25 feet

SCALE: NONE

DATE: JUNE 2018GRAVITY PIPE ANCHOR 350

Page 68: STANDARD DRAWINGS Application of Standard Drawings ...

FILENAME: 360.dwg

SCALE: NONE

DATE: JUNE 2018

CWS FLOW CONTROL STRUCTURE

WITH C.O.B. MODIFICATIONS360

t

Ƒ

Page 69: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

CWS STREETSIDE LIDA PLANTER

(NO STREET PARKING) WITH

C.O.B. MODIFICATIONS370

ST

OR

M

DR

AI

N

D

UM

P NO WA STE

!

D

RA

I NS TO STREA

M

ST

OR

M

DR

AI

N

DU

MP NO WA ST

E

!

D

RA

I NS TO STREA

M

Page 70: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

CWS STREETSIDE LIDA PLANTER

WITH STREET PARKING WITH

C.O.B. MODIFICATIONS371

ST

OR

M

DR

AI

N

D

UM

P NO WA STE

!

D

RA

I NS TO STREAM

ST

OR

M

DR

AI

N

D

RA

I NS TO STREAM

D

UM

P NO WA STE

!

Page 71: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

ROCK FLOW SPREADER FOR

WQ SWALE510

6"

4"

16"

FLOW 2:1

NOTES:

1. INSTALL FLOW SPREADERS AT 50 FT. INTERVAL MEASURED ALONG SWALE CENTERLINE AND

DOWNSTREAM OF THE PT OF EACH CURVE.

2. ROCK SHALL BE ANGULAR AND BLOCKY WITH 75% FRACTURED FACE MINIMUM.

3. FLOW SPREADER ROCK SIZE SHALL BE BASED ON VELOCITY OF FLOWS. 8"-10" ROCK CAN BE

USED FOR THE WATER QUALITY FLOW. ROCK SIZE MUST BE ENGINEERED FOR FLOWS GREATER

THAN THE WATER QUALITY FLOW.

4. FLOW SPREADER ROCK SHALL BE PLACED ON NATIVE SOIL PRIOR TO PLACEMENT OF TOP SOIL.

NATIVE

SOIL

SWALE

BOTTOMFLOW

SPREADER

ROCK

12"

RIV

ER

RO

CK

3"

DE

EP

A

A

SECTION A-A

SAMPLE WQ SWALE

PLAN VIEW

3'-0"

50' MAX @ CL

TOP OF SWALE

SWALE BOTTOM

SWALE CL

Page 72: STANDARD DRAWINGS Application of Standard Drawings ...

NOTES:1. Indexed PVC gasketed saddle shall conform to ASTM 3034 SDR35.

2. PVC compounds shall conform to ASTM d1784 with cell class of 12454-B/C or 12364-C.

3. All elastomeric seals (rubber gaskets) shall conform to ASTM F477.

4. Indexed PVC gasketed saddle shall be installed with rubber gaskets approved for the

sewer main wall configuration (profile or smooth wall).

5. Stainless steel bands shall be 300 series, 916" band width, cadmium plated, carbon steel,and attached with hex head, slotted screws.

6. Insertion hole shall be core drilled.

7. Indexed saddle shall be inserted a minimum of 14" from outside wall of host pipe andshall not protrude beyond the inside wall of the host pipe.

SCALE: NONE

DATE: JUNE 2018PVC GASKETED SADDLE 381

Insta

ll per

note

#7

Stainless steel bandStorm or sanitary pipe

Rubber gasket

PVC Saddle (tee)

Strap retainer ridges

Page 73: STANDARD DRAWINGS Application of Standard Drawings ...

1. Sign post shall be inserted a minimum of 12 inches into the 36 inch base.

2. See Chapter 4 of the Engineering Design Manual for the material specifications.

NOTES:

DRIVE RIVET DETAIL

WASHER

DRIVE RIVET

FOR MOUNTING SIGN

3/8" CUT

18" SLEEVE

36" BASE

SIGN POST

SECTION A - A

2 DRIVE RIVETS

SET 90° APART

SCALE: NONE

DATE: JUNE 2018TYPICAL SIGN ASSEMBLY 400

Page 74: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

TYPICAL SIGN LOCATIONS 405

CROSS INTERSECTION

1. Sign locations shall be according to the MUTCD and as modified herein.

2. Signs where the sidewalk is curb tight shall be located 6 inches outside the sidewalk

to a maximum distance of 7 feet from the face of curb.

NOTES:

SIGN TREE

MIN

OR

ST

RE

ET

SIGN TREE

MAJOR STREET

TEE INTERSECTION

SIGN TREE

SIGN TREE

Page 75: STANDARD DRAWINGS Application of Standard Drawings ...

NOTES:

1. Flat blanks shall be 0.080" gauge with 6063 T6 alodine coated aluminum substrate.

2. Background shall be white 3M Scotchlite brand High Intensity Reflective sheeting.

3. Symbol shall be black, 5" EM series

4. Legend text shall be 1.5" C series.

5. Border, legend, circle & diagonal shall be red.

6. For sign mounting, see drawing 400.

SCALE: NONE

DATE: JUNE 2018NO PARKING SIGNS 407

8"P 5

" E

M

TOW - AWAYZONE

1.5

" C

1.5

" C

2.5

"1

.5"

1.5

"

0.7

5"

1.8

75"

ZONETOW - AWAY

P

PZONE

YTOW - AWA

7.75"

12" x 18"

12" x 18"38

"

38

"

12"

18"

R= 1.5"

Page 76: STANDARD DRAWINGS Application of Standard Drawings ...

1. On all streets with posted speeds of 25 mph or less, new street name letters shall be 4 inches tall.

2. Letter styles from the Standard Alphabets for Highway Signs Manual shall be as follows:

a. For the name of street use 4 inch series 'C'.

b. For numbered streets use 4 inch series 'D' for the number and 3 inch series 'C' for the suffix.

c. For prefixes, suffixes and block numbers use 3 inch series 'C'.

3. All signs shall include block numbers, as assigned by the City. Number streets shall include block

numbers only when they differ from the actual street number.

4. Flat blanks for 4 inch street name signs shall be 0.100 inch gauge with 6063 T6 alodine coated

aluminum substrate.

5. The minimum length shall be 24 inches and the maximum length shall be 36 inches, in 6 inch

increments, with 1.5 inch radius corners.

6. Street name signs shall be green 3M Scotchlite brand High Intensity Prizmatic Reflective sheeting.

7. All letters, numbers and borders shall be white 3M Scotchlite brand High Intensity Prizmatic

Reflective sheeting.

8. For post mounting assembly see Beaverton Standard Dwg 400.

NOTES:

117 AvethSW

CRITICAL DIMENSIONS

A B C D E

8" 4" 3" 1 12" 1 1116"

E

A C

VARIES - SEE NOTE 5

3/16" BORDER

B

BLOCK NUMBER PLATE

See Beaverton

Standard Dwg 412

D - MIN D - MINE

CanyonSW Dr

3700

SCALE: NONE

DATE: JUNE 2018

STREET NAME SIGN 4 INCH

TALL LETTERS410

Page 77: STANDARD DRAWINGS Application of Standard Drawings ...

1. On all streets with posted speeds of 30 mph and greater, new street name letters shall be

6 inches tall.

2. Letter styles from the Standard Alphabets for Highway Signs Manual shall be as follows:

a. For the name of street use 6 inch series 'C'.

b. For numbered streets use 6 inch series 'D' for the number and 4 inch series 'C' for the suffix.

c. For prefixes and suffixes use 4 inch series 'C'.

3. All signs shall include block numbers, as assigned by the City. Number streets shall include

block numbers only when they differ from the actual street number.

4. Flat blanks for the 6 inch street name signs shall be 0.100 inch gauge with a 6063 T6 alodine

coated aluminum substrate.

5. The minimum length shall be 24 inches and the maximum length shall be 48 inches, in 6 inch

increments, with 1.5 inch radius corners.

6. Street name signs shall be green 3M Scotchlite brand High Intensity Prizmatic Reflective

sheeting.

7. All letters, numbers and borders shall be white 3M Scotchlite brand High Intensity Prizmatic

Reflective sheeting.

8. For post mounting assembly see Beaverton Standard Dwg 400.

NOTES:

D - MIN

BLOCK NUMBER PLATE

SEE Beaverton Standard

Dwg 412

CA

E

E

3/8" BORDER

D - MIN

VARIES - SEE NOTE 5

E

C B

CRITICAL DIMENSIONS

A B C D E

10" 6" 4" 2 14" 1 12"

2SW Stnd

3700

FarmingtonSW Rd

SCALE: NONE

DATE: JUNE 2018

STREET NAME SIGH 6 INCH

TALL LETTERS411

Page 78: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

BLOCK NUMBER PLATE

MOUNTING412

UPPER PLATE LOCATION

(2) 3/16" HOLES AT 1/4"

FROM TOP OR BOTTOM

EDGE OF BLANK

NOTES:1. Flat blanks shall be 0.060 inch gauge with 6063 T6 alodine coated aluminum substrate.

2. Both sides of block number plate shall be green 3M Scotchlite brand High Intensity

Prizmatic Reflective sheeting.

3. All numbers shall be 3 inch series "B", white 3M Scotchlite brand High Intensity

Prizmatic Reflective sheeting.4. Always mount lower plate on the side nearest to intersection

5. For street name sign, see Beaverton Standard Dwg 411.

LOWER PLATE LOCATION

LC

1.5"

.25"

TYPICAL NUMBER PLATE

4.5"

9"

.75" BORDER

.75" BORDER

3" B LETTERS

3/16" x 1/2" REACH

POP RIVETS

Page 79: STANDARD DRAWINGS Application of Standard Drawings ...

1. Flat blanks shall be 0.080 inch gauge with 6063 T6 alodine coated aluminum substrate.

2. All letters shall be black series "C".

3. Background shall be white 3M Scotchlite brand High Intensity Reflective sheeting.

4. For sign mounting, see Beaverton Standard Dwg 400.

0.375" SPACE0.375" BORDER

18"

NOTES:

3.75" 3.75"

1.5"

BLACK LETTERING ON WHITE BACKGROUND

LC

2.5"

2"

2 C

2.75"

1.5"

1.5 C

2 C

1.5 C

12"

SCALE: NONE

DATE: JUNE 2018

PRIVATE STREET SIGN 416

Page 80: STANDARD DRAWINGS Application of Standard Drawings ...

1. Flat blanks shall be 0.080 inch gauge with 6063 T6 alodine coated aluminum substrate.2. All letters shall be black and series are as noted.

3. Background shall be white 3M Scotchlite brand High Intensity Reflective sheeting.

4. For sign mounting, see Beaverton Standard Dwg 400.

NOTES:

18"

0.375" SPACE0.375" BORDER

1.5"

BLACK LETTERING ON WHITE BACKGROUND

CL

3.75"

12"

1.5 C

2 B

1.5 C

1.5"

2.75"

2 C

2"

2.5"

3.75"

SCALE: NONE

DATE: JUNE 2018PRIVATE DRIVEWAY SIGN 417

Page 81: STANDARD DRAWINGS Application of Standard Drawings ...

SIGN FACE

NYLON WASHER

FLAT STEEL WASHER

FLAT STEEL WASHER

8 Ø GALV BOLT

8 Ø GALV BOLT

2" x /4" GALV STRAP

FLAT STEEL

8 Ø GALV BOLT

SIGN MOUNTING

LOCKNUT

LOCKNUT

SECTION A-A

WASHER

1

/ "3

FLAT STEELWASHER

LOCKNUT

FLUSH V-WING

MOUNTING BRACKET

2" x /4"

GALVANIZED STRAP

1

3/ "

NYLON WASHER

1

SIGN FACE

2" x /4"

GALV STRAP

/ "3

WASHER

WASHERNYLON

WASHERFLAT STEEL

FLAT STEEL

SIDE VIEW

1. Specific signing as directed by MUTCD or as

allowed by the City Traffic Engineer.

2. Use predrilled (ODOT style) "V-Loc Mailbox

Support System".

3. Cut bolt end within 1/4 inch of nut, deform end

to prevent removal.

4. All bolts, nuts and washers shall be galvanized

steel unless otherwise noted.

5. Barricade is to be located 12 inches from back

of curb.

SEE SIGN

DETAILMOUNTING

12"

2' MIN

SEE NOTE 1

A

9"

14' 7 /2"

3.5'

LOWER 3/8"Ø HOLES

TO BE SHOP-DRILLED BY

CONTRACTOR

SIDEWALK

A

"V-LOC" POST MOUNTING SOCKET

CROSSWALK

CLOSED

OR 22 - 7

NOTES:

FRONT VIEW

SCALE: NONE

DATE: JUNE 2018

CROSSWALK CLOSURE

BARRICADE420

Page 82: STANDARD DRAWINGS Application of Standard Drawings ...

1. A minimum 6 inch core drill hole, at 6 to 12 inches from the edge of pavement or 6 inches

from the lip of gutter pan or face of curb when gutter is not present.

2. Seal the top of conduit with duct seal.

NOTES:

MIN

SEE NOTE 2

SAND

CLEAN4" MIN

2"

6"

SEE NOTE 1

RUBERIZED ASPHALT SEALANT

6" SCH 40 PVC CONDUIT

MORTAR

2" MIN CONDUIT OR

AS SHOWN ON PLANS

SCALE: NONE

DATE: JUNE 2018

LOOP WIRE ENTRANCE SAND

POCKET425

Page 83: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

PEDESTRIAN PUSH BUTTON

POST430

Conduit shall protrude a maximum of 2 inches above the finished surface foundation.

ELEVATION

NOTE:

BACK OF

SIDEWALK

1'-6"

4'-2"

(4) 3/4" ØHOLES

CUT HOLE TO FIT PIPE

BASE PLATE

5"

5"

5/8" x 12" ANCHOR

BOLTS, TOTAL = 4

45°

STD THREADED

212" PIPE CAP

212" STD GALV

STEEL PIPE

112" CONDUIT

PIPE

BASE

1/4

SECTION

3/8"

1'-6"BOLT CIRCLE

AT 412" Ø

Page 84: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018STREET BARRICADE - TYPE III 435

SECTION A-A

ELEVATION

NOTES:

1. Rails shall be white and red encapsulated

lens sheeting.

2. Rails shall be 2"x8" pressure treated lumber.

3. See Manual on Uniform Traffic Control

Devices for Streets and Highways and the

Oregon Supplement.

4. For wider applications, multiple sections as

shown shall be used.

SECTION B - B

12"

12"

12"

5'-0"

3'-0"

min

16'-0" 16'-0"

4"

6"45°

1'-0"

typ

14'-0"

O.C. max

Page 85: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

STREET BARRICADE - TYPE III

AT WIDE TRANSITIONS436

SECTION A-A

ELEVATION

NOTES:

1. Rails shall be white and red encapsulated

lens sheeting.

2. Rails shall be 2"x8" pressure treated lumber.

3. See Manual on Uniform Traffic Control

Devices for Streets and Highways and the

Oregon Supplement.

4. For wider applications, multiple sections as

shown shall be used.

5. The above barricade indicates that the

traffic passes of the left of the device. If

traffic is to pass to the right, the stripes

angle must be reversed.

SECTION B - B

12"

12"

12"

2"x8" rails w/3

8" galv bolts,nuts, & washers

212"x21

2" sleeve (18" L)

214"x21

4" anchor (36" L)

2"x2" sign post

(6' L, 12" embed)

(2) drive rivets

set 90° apart

5'-0"

3'-0"

min

4'-0" min to 16'-0" max

w/ (2) posts

6"45°

1'-0"

typ

14'-0"

O.C. max

A

A

B B

Ground line

Galvanized "Unistrut

Telespar" or 12 gauge

perforated posts. See

Section B-B for sizes &

lengths

Page 86: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018TYPICAL SHARED-USE PATH 700

NOTES:

1. If maximum allowable slope of 3:1 must be exceeded or a retaining wall is to be constructed

at edge of path (with City Engineer's approval only), provide handrail approved by the City

Engineer along the entire length of the non-conforming slope or retaining wall.

2. Edge clearance of 2' or more is desirable from handrails, trees, walls, fences, poles, guardrails

or other lateral obstructions.

3. 3:1 side slope is desirable for mowing purposes.

4. Provide City approved drainage pipe at low points.

5. Reseed disturbed surfaces.

6. Path may be offset from centerline of property corridor only with approval from the City

Engineer.

7. Path cross-slope to be designed at 1.5% max, 2.0% max constructed.

TYPICAL SECTION

10'

1'

Min

2'

1'

Min

Provide ditch as req'd

for proper drainage.

2:1 Max slope

3" Level 2, 12" ACSee note 7

Handrail where

req'd.

See note 1

3:1 Max

15'

Property Corridor

Tamp & bevel

exposed edge

of AC

Reseed with grass.

See note 5

10" aggregate

base

Page 87: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

MID-BLOCK PEDESTRIAN

CROSSING705

NOTES:

Approved for use under the following conditions:

1. Locations per approved plan.

2. Neighborhood routes & local streets only.

3. Street has posted speed 25 mph or less.

4. Tangent sections or curves with 300' radius or larger

5. Street has no more than 2 travel lanes.

Other conditions require a design exception. See Sect 160 of the

Engineering Design Manual.

Barricade as required

per drawing 420

8.0"

Ramp

MUTCD W11-2 ADVANCED

PEDESTRIAN CROSSING sign

Distance per plan

8.0"

Min

CL

Shared-use path.

See drawing 700

Sidewalk

Planter

Sidewalk

Planter

R= 5'

(typ)

ADA Accessible Ramp. See Sect 210.22.2

of the Engineering Design Manual

MUTCD W11-2 ADVANCED

PEDESTRIAN CROSSING sign

Barricade as required

per drawing 420

Page 88: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

VEHICLE BARRIER LOCATIONS

& FENCE OPENINGS710

PLAN VIEW

SECTION A-A

7' max7' max

Removable vehicle

barrier post. See

drawing 715

Shared-Use path.

See drawing 700

A

A

10'-20'

3' 3' 3' 3'

2'

4" yellow stripe

Fencing & post

Existing or new gate/end post

Fence

Page 89: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

REMOVABLE VEHICLE

BARRIER POST715

NOTES:

1. Barrier is to be used only when specifically approved by City Engineer.

2. barrier is not to be used on fire accesses.

3. padlock to be provided by the City.

516" coil-proof chain

links with top link

welded in vertical

position

66"

18"

516" chain link welded

in vertical position at

center point

5" Ø x 18" ASTM

A-120 galv steel

pipe

REMOVABLE POST

POST BASE INSTALLATION

2"

13

4"

2"

18" Ø

#4 x 8" rebar welded

to pipe bottom

14"

12"

3,000 psi compressive

strength concrete

Aggregate drain

rock base

AC surface

Undisturbed native soil

4" Ø ASTM A-120

galv steel pipe

4" NPT pipe cap

19.5

"

Page 90: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

TYPICAL WATER LINE

TRENCH BACKFILL620-1

Page 91: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

TYPICAL WATER LINE & FIRE

HYDRANT LOCATION630-1

Page 92: STANDARD DRAWINGS Application of Standard Drawings ...

1

2

3

4

5

TABLE 1

BRANCH

PIPE DIA

(IN)

THRUST BLOCK

BEARING AREA

(MIN SF)

THRUST BLOCK

CONCRETE

(MIN CY)

4 1.3 0.05

6 2.8 0.10

8 5.0 0.18

10 11.3 0.42

12 20.1 0.75

18 26.0 0.97

1

2

3

4

5

SCALE: NONE

DATE: JUNE 2018

TAPPING SLEEVE 630-2

Page 93: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

2″ STANDARD BLOW-OFF

ASSEMBLY - PERMANENT630-3

1

2

3

4

5

6

7

8

9

10

9

7

6

1

3

2

10 10

8

5

4

Page 94: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

2″ BLOW-OFF ASSEMBLY FOR

FUTURE EXTENSION630-4

1

2

3

4

5

6

1

6

3

4

5

2

Page 95: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

4″ BLOW-OFF ASSEMBLY FOR

FUTURE EXPANSION630-5

1

2

3

4

5

6

7

1

2

3

6

7 7

45

Page 96: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

2″ AUTOMATIC FLUSHING

DEVICE (FOR FUTURE EXTENSION) 630-6

1

2

3

4

5

6

7

8

8

9

8

9 9

1

1

5

2 3

7

4

6

6

5 2

3

4

10

10

11

11

Page 97: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

2″ AUTOMATIC FLUSHING DEVICE 630-7

1

2

3

4

5

6

7

8

9

9

1

1

5

2

37

4

5 2

3

4

10

10

6

8

6

8

11

11

Page 98: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018STRADDLE BLOCKS 630-8

Page 99: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018THRUST BLOCKS 630-9

Page 100: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

TYPICAL WATER VALVE

LOCATION640-1

1

2

3

4

5

6

6

3

2

5

1

3

Page 101: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

TYPICAL STANDARD VALVE

BOX SETTING640-2

1

12

2

3

4

3

4

Page 102: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

HIGH VOLUME TRAFFIC LID

FOR 910 SERIES VALVE BOX640-3

1

2

3

4

1

2

3

4

Page 103: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018VALVE OPERATOR EXTENSION 640-4

1

2

3

4

5

1

2

2

3

4

5

Page 104: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

¾″ OR 1″ COMBINATION AIR AND

VACUUM VALVE (CARV) BELOW

GRADE640-5

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

1

3

4

5 6 7

8

9

13

14

14

15

16

2

11

1210

Page 105: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

¾ʺ OR 1ʺ COMBINATION AIR

AND VACUUM VALVE (CARV)

AT GRADE640-6

1

2

3

4

5

6

7

8

9

10

11

12

13

14

1

3

4

12

56

7

8

9

10

11

13

2

14

Page 106: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

¾ʺ OR 1ʺ AIR RELEASE

VALVE (ARV)640-7

1

2

3

4

5

6

7

8

9

10

1

2

8

10

3 4 5

7

6

9

Page 107: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

2ʺ COMBINATION AIR &

VACUUM VALVE (CARV)640-8

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

1

3

2

4

6

9

8

4

5

7 1211

10

16 14

15

15

17

13

18

Page 108: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018FIRE HYDRANT CLEAR ZONE 650-1

••••••••

•••••

Page 109: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

FIRE HYDRANT ASSEMBLY

INSTALLATION650-2

1

2

3

4

5

6

7

8

1

2

3

4

5

3

7

6

8

8

Page 110: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

FIRE HYDRANT ASSEMBLY

FLANGE JOINT INSTALLATION650-3

1

2

3

4

5

6

7

1

7

8

54

2

3

8

Page 111: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

TYPICAL HYDRANT MARKER

LOCATIONS650-4

Page 112: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

SERVICE ABANDONMENT 660-1

Page 113: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

SAMPLING STATION

INSTALLATION660-2

Page 114: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

1ʺ SERVICE CONNECTION 660-3

1

2

3

4

5

6

64

3

1

2

5

6

Page 115: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

1½ʺ AND 2ʺ IRRIGATION

SERVICE CONNECTION660-4

Page 116: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

1½ʺ AND 2ʺ SERVICE

CONNECTION660-5

Page 117: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

VAULT LADDER INSTALLATION 670-1

1

2

3

4

2

4

2

3

1

Page 118: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018SUMP PUMP INSTALLATION 670-2

Page 119: STANDARD DRAWINGS Application of Standard Drawings ...

SLOPE =1

4" / ft

CUSTOMER. INSTALLATION OF METER BY CITY. METER COST PAID BY CUSTOMER.

WATER SERVICE LINE AND METER VAULT (AS SHOWN BELOW) PROVIDED BY

1. This is a public facility, governed by UPC, SOPC and Oregon Dept. of Human Services,as applicable.

2. Finished grade shall slope away from the vault cover to prevent ponding around the cover.

3. Vault door mechanisms shall not project below the ceiling of the vault interior.

4. Aluminum ladder with extension to be O.S.H.A. approved, (Utility Vault Co. 1672 or equal). Ladder to

have clear access from vault door.

5. Seal pipe penetrations with nonshrink grout to achieve a water tight seal. Piping shall not be directly

imbedded in concrete or masonry. Provide pipe straps for thrust resistance per State of Oregon

Plumbing Code (SOPC).

6. Check valve to be union style (compression) or install

union with check valve.

7. Slope interior toward end of floor for sump or gravity

drain outlet. Trim floor drain grating as required for

pump installation. For alternate floor center drain,

see Drawing 690-4A.

6"

MIN

FLOW

NOTES:

GASKET

SEALS

DRAIN TO DAYLIGHT

CINCH ANCHORS

FLOW

FLANGE

COUPLING

ADAPTOR

LADDER WITH

EXTENSION

PUMP

GATE VALVE

CHECK VALVE

2" DRAIN TO DAYLIGHTWITH ACCESSIBLEBACKWATER VALVE

RODENTSCREEN

12" MIN36" MAX

3"

4" & 6"

8"

METERSIZE

676-WA

687-WA

810-LA

GRATE

COPPER PIPE7" MIN

VAULT DOOR

SEE NOTE 3

THRUST BLOCK

AS REQUIRED

RETAINER GLAND

SPOOL FLG x PE

PUMP DISCHARGE TO

APPROVED LOCATION

FLOW

6"

MIN

NONSHRINK GROUT

SLOPE - SEE NOTE 23" MIN

12"

2 PIPE SUPPORTSBOLTED TO FLOOR

PUMP

SECTION

UTILITY VAULT CO. VAULT MODEL NO.

J-5AL

J-5AL

JD-3AL

BILCO - VAULTDOOR MODEL NO.

FLOW

SCALE: NONE

DATE: JUNE 2018

COMPOUND WATER METER

VAULT670-3

Page 120: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

ELECTROLYSIS TEST STATION

WIRE INSTALLATION680-1

Dielectric isolation joint

ISOLATION JOINT TEST STATION

Note: Isolation flange joint shown,

others similar

Exothermic weld wire

connection (typ)

See drawing 680-8

Test station. See drawings

680-6 or 680-7

Insulating casing seal

Casing pipe

Carrier pipe

Test wires (typ)

CASING TEST STATION

COMBINATION TEST STATION

Test wires

(typ)Exothermic weld wire

connection (typ)

See drawing 680-8

MONITORING TEST STATION

1'-0" MAX

No. 8 AWG stranded copper wire

(one shown, two required)

Test station. See drawings

680-6 or 680-7

Dielectric isolation joint

Insulating casing seal

2" PVC pipe with loose top

end cap, no bottom cap

Valve box & cover,

see drawing 640-2

Page 121: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

TERMINAL BOARD TEST

STATION - TYPES A-D680-2

Page 122: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

POLYETHYLENE ENCASEMENT

FOR DIP680-3

1

2

3

4

5

6

1

2 3 4 5 6

Page 123: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

PROTECTIVE GEOMEMBRANE

SLEEVE WRAP FOR CROSSING

CATHODICALLY PROTECTED PIPES680-4

Page 124: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

PROTECTIVE SLEEVE SLIP-ON FOR

CROSSING CATHODICALLY

PROTECTED PIPES OR STRUCTURES

680-5

Page 125: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

COMBINED CP TEST STATION

ABOVE GRADE INSTALLATION

DETAILS680-6

TYPE A TYPE B

TEST STATION INSTALLATION

24"x24"x6" CONCRETE

PAD, SIDEWALK SLAB,

OR PAVEMENT

VALVE BOX & COVER.

SEE DRAWING 640-2

8" PVC PIPE. PROVIDE

24" MINIMUM LENGTH

FROM FINISHED GRADE

TO BOTTOM OF PVCPIPE

TEST STATION WIRES

PER TEST STATIONTYPE & WIRE

IDENTIFICATION

Page 126: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

COMBINED CP TEST STATION

BELOW GRADE INSTALLATION

DETAILS680-7

TYPE C

TYPE D

TEST STATION INSTALLATION

24"x24"x6" CONCRETE

PAD, SIDEWALK SLAB,

OR PAVEMENT

VALVE BOX & COVER.

SEE DRAWING 640-2

8" PVC PIPE. PROVIDE

24" MINIMUM LENGTH

FROM FINISHED GRADE

TO BOTTOM OF PVCPIPE

TEST STATION WIRES

PER TEST STATIONTYPE & WIRE

IDENTIFICATION

Page 127: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

GENERAL CORROSION CONTROL

DETAILS680-8

EXOTHERMIC WELD CAP,

ELASTOMERIC FILLED

COPPER SLEEVE

(AS REQUIRED)

CABLE

INSULATION

PIPE OR FITTING

EXOTHERMICWELD

NOTES:1. APPLY WELD CAP DIRECTLY TO PIPE, NOT TO PIPE WRAP.

USE PRIMER AS REQUIRED BY THE MANUFACTURER.

2. COMPLETELY ENCLOSE WIRE WITHIN WELD CAP

3. REPAIR ANY DAMAGED COATING NOT COVERED BY

WELD CAP

EXOTHERMIC WELD - DI & STEEL PIPE

EXOTHERMIC WELD, WRAP

ALL EXPOSED METAL WITH

PVC TAPE

FACTORY INSTALLED 12"Ø STEEL ROD.EXTEND ROD 1" ABOVE CEMENT COATING

PORTLAND CEMENT GROUT OR

MORTAR. 3 4" OVER ALL METAL

EXOTHERMIC WELD - MCSP & CCP PIPE

GALVANIC ANODE INSTALLATION

NOTES:1. LOCATE ANODES WITHIN 3' HORIZONTALLY OF

CENTERLINE OF PIPE.

2. PLACE GALVANIC ANODE IN CLEAN NATIVE BACKFILL

AND COMPACT TO 12" ABOVE ANODE.

3. ANODES MAY BE PLACED HORIZONTALLY OR

VERTICALLY (HORIZONTALLY SHOWN)

4. ANODE WIRE SHALL BE EXOTHERMIC WELDED TIRECTLY

TO PIPE OR INCORPORATED INTO THE JOINT BOND WITH

A SPLIT-BOLT CONNECTION.

3' M

INIM

UM

PIPE Ø # OF ANODES

16" OR SMALLER 1 PER 100' (2 MIN)

18" - 32" 2 PER 100'

32" OR LARGER 4 PER 100'

PIPE Ø # OF ANODES

16" OR SMALLER 2 (1 PER END)

18" OR LARGER 4 (2 PER END)

FOR PIPE RUNS 100' OR GREATER

FOR PIPE RUNS LESS THAN 100'

ANODE SCHEDULE

Page 128: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

BONDING OF DIP JOINTS AND

FITTINGS680-9

Page 129: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

DIELECTRIC ISOLATION

JOINTS680-10

Steel Washer with

oversized ID (typ)

Insulating Washer

(typ)

Tape wrap circumference of

flange with 20 mil PVC tape

Insulating sleeve,

length to extend

into oversized ID

steel washer

Full face 18" thickinsulating gasket

See note

2

NOTES

INSULATING FLANGE DETAIL

1. Below grade insulating flange

installations as shown

2. Bolt length shall be long enough

to have a minimum of three

threads exposed beyond nut

when fully tightened

3. For high strength bolts, additional

standard high strength washers

required

FLEX COUPLING

4. Center flexible coupling over

insulating boots

5. Exothermic weld to coupling prior

to assembly. Do not burn boots

6. Bond the coupling to a protected

side of the joint where specified

Dielectric isolation

flange joint

FLG x MJ coupling

adapter or FLG x PE

spool

DIELECTRIC ISOLATION

JOINT ASSEMBLY

DIELECTRIC ISOLATION

FLEXIBLE COUPLING

INSULATING FLANGE DETAIL

Exothermic weld wire

connection (typ)

Mastic or epoxy coat

this weld

No 12 AWG solid copper

wire. Provide bond only

where specified

Insulating boot (typ)

Page 130: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: AUG 2018

CROSS CONNECTION PROTECTION

FOR TANKER TRUCKS690-1

Page 131: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

BACKFLOW PREVENTER FOR

RESIDENTIAL IRRIGATION SYSTEMS690-2A

Page 132: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

BACKFLOW PREVENTERS FOR

RESIDENTIAL IRRIGATION

SYSTEMS690-2B

Page 133: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

¾ʺ OR 1ʺ DOUBLE CHECK

VALVE ASSEMBLY (DC)690-3A

Page 134: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

1¼″ TO 2″ DOUBLE CHECK

VALVE ASSEMBLY (DC)690-3B

Page 135: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

3″ AND LARGER DOUBLE

CHECK VALVE ASSEMBLY (DC) 690-4A

7 12

9

10

8

2 3

1

6

5 4

11

Page 136: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

3″ AND LARGER DOUBLE CHECK

VALVE ASSEMBLY (DETAIL NOTES) 690-4B

Page 137: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

3″ AND LARGER DOUBLE CHECK

DETECTOR ASSEMBLY690-5A

9

8

13

14 1610

127

6

5 4

11

2 3

15

Page 138: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

3″ AND LARGER DOUBLE CHECK

DETECTOR ASSEMBLY690-5B

Page 139: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

3″ AND LARGER DOUBLE

CHECK DETECTOR ASSEMBLY

(DETAIL NOTES)690-5C

Page 140: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

¾″ TO 2″ REDUCED PRESSURE

BACKFLOW ASSEMBLY (RP)

ABOVE GROUND690-6

Page 141: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

¾″ TO 2″ REDUCED PRESSURE

BACKFLOW ASSEMBLY (RP) IN

BERM690-7

Page 142: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

3″ TO 10″ REDUCED PRESSURE

BACKFLOW ASSEMBLY (RP)

ABOVE GROUND690-8

Page 143: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

3″ TO 10″ REDUCED PRESSURE

BACKFLOW ASSEMBLY (RP) IN

BERM690-9

Page 144: STANDARD DRAWINGS Application of Standard Drawings ...

SCALE: NONE

DATE: JUNE 2018

REDUCED PRESURE

BACKFLOW ASSEMBLY (RP)

DISCHARGE RATES690-10