Sprinkler Protection of Non-Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas

Transcript of Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter...

Page 1: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Sprinkler Protection of Non-Storage Occupancies with High Ceiling Clearance

20 May, 2014Peter Thomas

Page 2: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Background

• Architectural designs create real fire protection challenges to fire engineers. “The Taller” seems to be “The Better”

• Sprinkler performance and effectiveness in buildings with high roofs and non-storage occupancies such as atria, convention centers, casinos, auditoriums, theaters, exposition halls and others, is not well understood.

Page 3: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Introduction – Current Situation

Convention CenterCeiling Height of 18 m

What is sprinkler protection based on current installation standards?

Page 4: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Introduction – Current Situation

• EN 12845 (OH 4)5.0 mm/min 360 sq m

• NFPA 13 (OH 2)8.1 mm/min 139 sq m

6.1 mm/min 372 sq m

• FMDS 3-26 (HC 3)20.0 mm/min 280 sq m

• China GB 50084 (OH 1)6.0 mm/min 160 sq m

• Australia AS 2118.1(High Hazard- Process)12 mm/min 360 sq m

• Singapore CP52Not Allowed

Page 5: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Test Plan

Page 6: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Test Fuel and Fuel Array Arrangement

Page 7: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Sprinkler System

Page 8: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Full Scale Fire Test 1

• Fuel Arrangement: Group A Plastics

• Ceiling height: 12 m

• Fuel Height: 1.63 m

• Clearance to ceiling: 10.4 m

• Arrangement of fuel package: 8 by 2, solid pile

• Ignition Location: Under 1 sprinkler

• Density: 15 mm/min

• Sprinklers: K115, RTI 105 (m-s)1/2 Standard Response, Pendent

• Spacing: 3.0 m x 3.0 m

Page 9: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Full Scale Fire Test 1

Page 10: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Full Scale Fire Test 1

Page 11: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Full Scale Fire Test 1

Page 12: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Full Scale Fire Test 2

• Fuel Arrangement: Group A Plastics

• Ceiling Height: 16 m

• Fuel Height: 1.63 / 1.13 m

• Clearance to ceiling: 14.4 m

• Arrangement of fuel package: 8 by 2, solid pile

• Ignition Location: Under 1 sprinkler

• Density: 20 mm/min

• Sprinklers: K115, RTI 35 (m-s)1/2 Quick Response, Pendent

• Spacing: 3.0 m x 3.0 m

Page 13: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Full Scale Fire Test 2

Page 14: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Full Scale Fire Test 2

Page 15: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Full Scale Fire Test 2

Page 16: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Full Scale Fire Test 3

• Fuel Arrangement: Group A Plastics

• Ceiling Height: 16 m

• Fuel Height: 1.63 / 1.13 m

• Clearance to ceiling: 14.4 m

• Arrangement of fuel package: 8 by 2, solid pile

• Ignition Location: Under 1 sprinkler

• Density: 23 mm/min

• Sprinklers: K161, RTI 138 (m-s)1/2 Standard Response, Pendent

• Spacing: 3.0 m x 3.0 m

Page 17: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Full Scale Fire Test 3

Page 18: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Full Scale Fire Test 3

Page 19: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Full Scale Fire Test 4

• Fuel Arrangement: Group A Plastics

• Ceiling Height: 18 m

• Fuel Height: 1.63 m

• Clearance to ceiling: 16.4 m

• Arrangement of Fuel Package: 6 by 2, solid pile

• Ignition Location: Under 1 sprinkler

• Density: 40 mm/min

• Sprinklers: K363, RTI 130 (m-s)1/2 Standard Response, Pendent

• Spacing: 3.0 m x 3.0 m

Page 20: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Full Scale Fire Test 4

Page 21: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Full Scale Fire Test 4

Page 22: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Full Scale Fire Test 5

• Fuel Arrangement: Group A Plastics

• Ceiling Height: 18 m

• Fuel Height: 1.63

• Clearance to Ceiling: 16.4 m

• Arrangement of Fuel package: 6 by 2, solid pile

• Ignition Location: Between 4 sprinklers

• Density: 40 mm/min

• Sprinklers: K363, RTI 130 (m-s)1/2 Standard Response, Pendent

• Spacing: 3.0 m x 3.0 m

Page 23: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Full Scale Fire Test 5

Page 24: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Full Scale Fire Test 5

Page 25: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Test Summary• Effectiveness of sprinkler to control depends on

delivered density• Under 12 m ceiling, K 115 sprinkler at 15 mm/min.

did not control the fire.• Under 16 m ceiling, K115 sprinkler at 20mm/min.

did not control the fire. A K160 sprinkler marginally controlled the fire at 23 mm/min.

• Under 18 m ceiling, K363 sprinkler at 40 mm/min. generates significantly larger drops and effectively controlled the fire.

Page 26: Sprinkler Protection of Non- Storage Occupancies with High Ceiling Clearance 20 May, 2014 Peter Thomas.

Conclusion

• EN 12845 (OH 4)5.0 mm/min 360 sq m

• NFPA 13 (OH 2)8.1 mm/min 139 sq m

6.1 mm/min 372 sq m

• FMDS 3-26 (HC 3)20.0 mm/min 280 sq m

• China GB 50084 (OH 1)6.0 mm/min 160 sq m

Change – 40 mm/min 160 sq m with K360 sprinklers

• Australia (AS 2118.1)(High Hazard- Process)12 mm/min 360 sq m

• Singapore CP52Not Allowed over 13 m

Proposed change - 12 mm/min 360 sq m with K160 sprinklers