SPI-Programmable - Fundamentals · PDF file3.1 Current Transformers 10 3.2 Power Supply, ......
Transcript of SPI-Programmable - Fundamentals · PDF file3.1 Current Transformers 10 3.2 Power Supply, ......
SPI-Programmable
Overcurrent and Earth Fault Indicators
USER MANUAL
issue 2.1
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 1
Publication Notice
All enquiries and questions should be addressed to Fundamentals Limited at the address given below.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means, including photocopying, electronic, mechanical, recording or otherwise, without the prior written permission of the copyright holder.
Fundamentals Ltd provide this document as is, without warranty of any kind either expressed or implied including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose. Fundamentals Ltd may make changes or improvements in the software, equipment, or specifications described in this document at any time and without notice. These changes will be incorporated in new releases of this document.
Fundamentals Ltd owns the IPR of the technology contained in this manual. The product was distributed by Nortech Management Ltd for a period of time and equipment illustrations may depict the Nortech logo.
This publication could contain technical inaccuracies or typographical errors. Fundamentals Ltd shall not be liable for any damages (including, but not limited to, consequential, indirect or incidental, special damages or loss of profits or data) even if Fundamentals Ltd have been informed of their potential occurrence, arising out of or in connection with this document or its use.
English Edition All trademark names used in this manual are hereby acknowledged.
Fundamentals Limited Unit 4, Hillmead Enterprise Park Marshall Rd Swindon Wiltshire SN5 5FZ United Kingdom Tel: +44 (0) 1793 847163 Fax: +44 (0) 1793 847245 Web: www.fundamentalsltd.co.uk
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 2
Contents
1 General Description 3
2 Operation 5
3 Connections 10
3.1 Current Transformers 10 3.2 Power Supply, Voltage Sensing, Remote Reset &
Alarms 15 3.2.1 Power Supply 15 3.2.2 Mains Sensing 15 3.2.3 Reset 15 3.2.4 Alarms 15
4 Specification 16
5 Environmental Withstand 17
6 Installation 18
7 Operational Checks 20
7.1 Selector Switch Settings 20 7.2 Testing 21 7.2.1 Commissioning Testing 21 7.2.2 Routine Testing 21
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 3
1 General Description
The SPi programmable range of fault indicators are designed for application to distribution networks where automated switchgear is installed. When a true fault is detected the indicator operates alarm contacts for remote indication and illuminates an integral Light Emitting Diode (LED). Indicators, strategically placed in the distribution network aid identification of a faulty section of network as shown in fig.1 where a fault occurs at position A.
Fig.1 SPi application to a distribution network
Three designs are available: -
1. An open frame DIN rail mounting unit, figure 2
2. A weather proof unit intended for mounting external to switch-gear, figure 3
3. A weather proof unit intended for mounting external to switch-gear and for use with flexible band CTs only, figure 4
A range of level settings and operating modes are provided as standard, including overcurrent, earth-fault, sensitive earth-fault and persistent current alarms for non-tripping situations. Transient faults can be detected with extended indicating times to allow for a planned inspection of suspect line sections.
The SPi-OCEF programmable is used with three current transformers (CT) mounted within automated switchgear. A separate resistor board is used with the indicator for direct connection to the CTs. Removable connectors on the board allow for connection to the SPi indicator. The separate resistor board is not required for use with flexible band CTs. The power supply to the indicator is taken from local switchgear DC power supply and inputs are provided for local supply voltage sensing.
For a permanent fault the indicating period is selectable for up to 6 hours. For a transient fault the indicating period is 24 hours. In each case contacts are operated for remote alarms.
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 4
Inter-board
connectorsAlarms
Fault
NORTECH
MANAGEMENT LTD. UK
www.nortechonline.co.uk
OC
1-2
TIME
5-6
MODE
7-8
0.5A
0.75A
1.0A
1.25A
0.08A
0.12A
0.16A
0.20A
3hr
4hr
5hr
6hr
TRANS
SEF
TRANS
+ SEF
NORMPULSE/
PHASE
EF
3-4
SWITCH SETTINGS
SPi-OCEF
Fault Indicator
VoltageSer. No.
AL/CT
9-10
PULSE/
CORE
HOLD/
PHASE
HOLD/
CORE
SEFPrstnt Crnt
Test/Reset
Ser. No. Ser. No.
Fig.2 SPi-OCEF DIN rail Programmable Indicator
Voltage
SEF
TEST / RESETPress until indicator
stays on
Voltage
VersionSer. No
SPi-OCEFPROGRAMMABLE OVERCURRENT &
EARTH FAULT
INDICATOR
NORTECH MANAGEMENT
LTD, UK
www.nortechonline.co.uk
FAULT
Fig.3 SPi-OCEF Potted Programmable Indicator in IP65 enclosure
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 5
Voltage
SEF
TEST / RESETPress until indicator
stays on
Voltage
Version
SPi-OCEFPROGRAMMABLE OVERCURRENT &
EARTH FAULT
INDICATOR
NORTECH
MANAGEMENT LTD, UK
www.nortechonline.co.uk
FAULT
Voltage
FAULTTEST / RESETPress until indicator
stays on
Voltage
VersionSer. No
SPi-OCEFPROGRAMMABLE OVERCURRENT &
EARTH FAULT INDICATOR
For use with band CTs only
NORTECH
MANAGEMENT LTD, UK
www.nortechonline.co.uk
SEF
Fig.4 SPi-OCEF Potted Programmable Indicator in IP65 enclosure for use with band CTs
2 Operation
Measurement of current is made every 1mSec. When current above the threshold setting of the indicator is measured a fault calculation is initiated. The algorithm used for fault measurement allows the indicator to grade with the minimum settings likely to be used by the source protection relays and at the same time avoid possible mis-measurement due to capacitive charge currents.
The indicator characteristic is shown in App.A against typical source protection minimum settings.
The indicator determines a fault as follows: -
IF the current exceeds the characteristic criteria (app. A)
AND the supply is off within 500mS after the current dropping below the threshold set point
THEN a fault is set
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 6
When set for sensitive earth fault (SEF) a fault is defined after 5 seconds of persisting current.
A fault is indicated on the SPi-OCEF by two LEDs. LED1 Indicates for Over Current or Earth Fault and LED2 indicates for SEF. Remote indication is by way of normally open volt free contacts which are closed at the start of the indicating period. Relay contacts can be set as fleeting (2 seconds), or permanently closed until the end of the indicating period or until supply is restored .
When a fault is detected the indicator will not monitor further fault occurrences for 3 minutes following the event to allow for auto-reclose sequence completion. The device will indicate for both transient and permanent faults. When set for permanent fault indications only, the indicator will reset on restoration of supply.
When set for transient fault indications and indicating for fault, the SPi will monitor for new faults and update alarms and indications accordingly, as described below.
For the purpose of explanation the charts below show the operation of the indicator under various fault indicating situations assuming a 3 hour permanent fault time-out period:
On fault detection the indicator will flash to indicate fault passage. If the line voltage is immediately restored the unit will indicate for a total of 24 hours and at the same time monitor the circuit for further faults. If supply is restored immediately, the indicator will sense for new faults after 3 minutes. If supply is restored after the initial 3 minute period following a fault, the indicator will sense for new faults immediately.
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 7
If, following a fault, supply is not restored, the unit will indicate for 3 hours. If supply is restored during this period the unit will indicate for 24 hours and monitor and update for further faults.
If, following a fault, supply is not restored within 3 hours, the unit will reset. On restoration of supply the indicator will monitor for new faults.
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 8
If, when indicating for a transient fault, fault current is measured, the unit will fully update for the new fault.
If, when indicating for a transient fault, fault current is measured and the line voltage is immediately restored, the unit will indicate for a further 24 hours and fully update for further faults.
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 9
If, when indicating for a transient fault supply is lost with no detected fault current, the unit will reset.
If a current above the threshold level is measured and the current continues to flow for 30 seconds, the indicator will flash LED’s alternately and operate relay 2. The indicator will continue to flash until the current ceases.
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 10
3 Connections
3.1 Current Transformers
The SPi-OCEF is designed for use with 1A secondary phase mounted current transformers that can be any ratio. If the sensitive earth-fault selection is used, however, the CTs must be matched so that minimal out of balance currents are produced under full load conditions.
Figures 5A and 5B show the arrangement for the phase mounted CTs and the connections from the CT resistor block to the indicator unit. The CTs are terminated at screw terminal connectors for safety. The inter-board wiring is terminated at each end by removable plug connections that facilitate removal of the indicator if required without the need to short out the CT wiring.
Figure 5C shows an alternative arrangement where a core balance CT is used for detection of earth-fault current. In this case a common connection between the CT secondary connections is made to the CT C terminal of the CT resistor block.
Figure 5D shows an arrangement where ‘band CTs are used. In this case the CT resistor block is not required. This type of indicator can only be used in the configuration shown.
Important note:
Phase mounted current transformers must be securely mounted around the cable cores at a point where the core earthed screen passes through and beyond the CT. The jointing procedure for the cable termination should specify the method to be adopted in order to ensure electrical stress control.
The secondary wiring must be earthed, as shown by figure 4A, 4B and 4C.
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 11
21 3 4
CT
B
CT
A
CT
C
CO
M
Phase
mounted
CT's
Inter-board
connections
Fault
NORTECH
MANAGEMENT LTD. UK
www.nortechonline.co.uk
OC
1-2
TIME
5-6
MODE
7-8
0.5A
0.75A
1.0A
1.25A
0.08A
0.12A
0.16A
0.20A
3hr
4hr
5hr
6hr
TRANS
SEF
TRANS
+ SEF
NORMPULSE/
PHASE
EF
3-4
SWITCH SETTINGS
SPi-OCEF
Fault Indicator
VoltageSer. No.
AL/CT
9-10
PULSE/
CORE
HOLD/
PHASE
HOLD/
CORE
SEFPrstnt Crnt
Test/Reset
Ser. No. Ser. No.
Fig. 5A Current Transformer and Inter-board connections to a DIN rail unit
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 12
21 3 4
CT
B
CT
A
CT
C
CO
M
Phase
mounted
CT's
Inter-board
connections
1 2 43
OC
1-2
TIME
5-6
MODE
7-8
200A
300A
400A
500A
30A
50A
70A
90A
3hr
4hr
5hr
6hr
TRANS
SEF
TRANS
+ SEF
NORM PULSE
EF
3-4
SWITCH SETTINGS
ALARM
9-10
PULSE
HOLD
HOLD
Fault
SEF
Prstnt Crnt
Test/Reset
INDICATIONS
Fig. 5B Current Transformer and Inter-board connections to a potted unit
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 13
Fig. 5C
Current Transformer connections when using 1 x Core balanced CT + 2 x phase CTs
21 3 4
CT
B
CT
A
CT
C
CO
M
Core
mounted
CT
Phase
mounted
CT's
Fig 3C
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 14
Core
mounted
band CT
Phase
mounted
band CT's
1 2 43
OC
1-2
TIME
5-6
MODE
7-8
200A
300A
400A
500A
30A
50A
70A
90A
3hr
4hr
5hr
6hr
TRANS
SEF
TRANS
+ SEF
NORM PULSE
EF
3-4
SWITCH SETTINGS
ALARM
9-10
PULSE
HOLD
HOLD
Fault
SEF
Prstnt Crnt
Test/Reset
INDICATIONS
Fig. 5D Current Transformer connections to a ‘band CT’ unit
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 15
3.2 Power Supply, Voltage Sensing, Remote Reset & Alarms
Figure 6 shows the connections to the indicator. Complete isolation is provided between the power supply, the CT input, the mains supply sensing, reset input and the alarm outputs.
BAT
NEG
BAT
POS
MAIN
SENSE
MAIN
SENSE
RESET
POS
RESET
NEG1 2 3 4
ALRM
1
ALRM
1
ALRM
2
ALRM
2
Fig. 6 Connections
3.2.1 Power Supply
The power supply is a nominal 24VDC, the battery earthing may be either positive or negative.
3.2.2 Mains Sensing
An input for local supply sensing is required for fault determination. The voltage applied must be above 40V AC up to 250VAC when the supply is on. After supply is restored, to ensure that supply is fully on, a period of 10 seconds must elapse before the indicator will respond to further fault situations.
3.2.3 Reset
A voltage (9-48VDC) applied to the reset input (polarity sensitive) will reset the indicator.
3.2.4 Alarms
Normally open, isolated contacts are provided for remote signalling of a Fault (Relay 1) and persistent current above the threshold levels but without a loss of supply (Relay 2). The operation of the alarm contacts can be selected to operate as a fleeting alarm (2 seconds duration) or be permanently closed during the indicating period.
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 16
4 Specification
Power Supply 1. 14-30V DC (24V nominal)
Quiescent current 30mA
Maximum 100mA, full fault indications
Mains Sensing 40VAC – 250VAC
Reset 1. Local push button, press until both LED’s stay on
2. Remote pulsed reset signal from local telemetry system (9-48VDC) of more than 0.5sec. duration
3. On completion of timing period
Over Current Sensitivity Range
(15%)
0.5A, 0.75A, 1.0A and 1.25A secondary current
(250A, 375A, 500A and 625A primary current using 500/1 CTs)
200A, 300A, 400A and 500A primary current using band CTs
Earth Fault Sensitivity
Range (15%)
Using 3 x Phase CTs
0.08A, 0.12A, 0.16A and 0.2A secondary current
(40A, 60A, 80A and 100A primary current using 500/1 CTs)
Using Core Balanced CT
A single setting of 0.833 A (20%) secondary current
(50A primary current using a 60/1 CT)
Using BAND CT arrangement
30A, 50A, 70A and 90A
Sensitive Earth Fault
Sensitivity (20%)
Using 3 x Phase CTs
5 seconds duration of 0.025A secondary current
Note: while this function is provided, the noise level at this very low current level may give rise to spurious operation
(12.5A primary current using 500/1 CTs)
Using Core Balanced CT (recommended)
A single setting of 0.12A secondary
(7A primary using a 60/1 CT)
Indicator Fault - Red flashing LED1 at 1 second interval
SEF - Red flashing LED2 at 1 second interval
Test - both LED’s flash at 1 second interval, then steady
Persistent Current above threshold without loss of voltage signal - after 30 seconds, LED’s flash alternately until current ceases
Remote Alarm options Two output relays, one for Fault (Alarm 1) and one for persistent current (Alarm 2) with selectable operation as follows: -
1. Fleeting normally open volt free contacts (2.0 Sec)
2. Normally open volt free contacts closed during indicating period
The contact rating is 2A at 30VDC or 0.5A 120VAC
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 17
5 Environmental Withstand Insulation
Between any terminal and earth 1.5kV RMS for 1 minute
Between independent circuits 1.5kV RMS for 1 minute
Across normally open contacts 1kV RMS for 1 minute
High Frequency Disturbance
2.5kV Common mode (longitudinal) No mal-operation
1kV Series mode (transverse) No mal-operation
Electrostatic Discharge
8kV contact No mal-operation
Fast Transient
2kV 5/50nSec. 2.5kHz repetitive No mal-operation, steady state, operated or during fault measurement
EMC
Susceptibility 100kHz to 1gHz, 3V/ metre on all planes, no mal-operation
Emissions No significant emissions
Current Injection
Operation Threshold 15% up to at least 20,000A primary current for 3 Sec. through xxx/1 current transformer
Mechanical
General The auxiliary Resistor board and the Indicator are mounted on DIN rail mounting assemblies.
Dimensions Auxiliary Resistor Unit 45Wx78Hx 50D
SPi Indicator (DIN) 112Wx112Hx42D
SPi Indicator (potted) 120Wx120Hx105D
Temperature range -25C to +70C ambient
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 18
6 Installation
The SPi-OCEF programmable indicator is used in conjunction with a CT resistor block. The general outline of DIN rail mounted version and the CT resistor block are shown below in fig.7. The weatherproof version is mounted in a case identical to the SPi-OCEF indicator. The relay fascia design is shown in fig.3 (earlier in the document) and the lid rear in fig.8 below.
Current Transformers are connected to the CT resistor block using conductors of sufficient rating for the expected maximum fault current. Care must be taken to ensure that the CTs are mounted with the correct polarity.
109.00
122.0
0
45.0017.00
Fig. 7 Indicator and CT resistor block, general outline
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 19
1 2 3 4
120.00
120.0
0
Fig. 8 Potted indicator, general outline
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 20
7 Operational Checks
7.1 Selector Switch Settings
The SPi can be programmed for each installation and operational condition by use of a 10 way DIL selector switch. The switch functions are as follows: -
Switch Function
1-2 Overcurrent setting range (CT secondary) nominal 15%
0.5A, 0.75A, 1.0A, 1.25A
200A, 300A, 400A, 500A (band version)
3-4 Earth-fault setting range (CT secondary) nominal 15%
0.08A, 0.12A, 0.16A, 0.2A
30A, 50A, 70A, 90A (band version)
SEF level if set is the same for all EF settings
5-6 Indicating time for permanent fault indications
3hr, 4hr, 5hr, 6hr
7-8 Normal Permanent fault indication only
No Sensitive earth-fault monitor
Transient Transient fault indications
SEF Sensitive earth-fault monitor
Trans/SEF Transient indications AND Sensitive EF
9 Pulsed alarm (2 seconds) or Permanent alarm (closed until supply restored or to end of indicating period)
10 Selection for CT arrangement
1 - 3 phase mounted CTs
2 - 2 phase mounted and 1 core balance CT
Note: This function is not applicable to the band CT version
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 21
7.2 Testing
7.2.1 Commissioning Testing
When installed and with the indicator powered up, primary current injection should be carried out to confirm that the CTs are of the correct ratio and polarity. When the current setting of the indicator is reached the appropriate LED will illuminate. As the current is increased above the fault level threshold the LED will switch off as the fault curve time is reached (see app. A).
It is important that CT polarities are correct, the table below shows the minimum tests that should be carried out to confirm correct secondary CT wiring connections. With sensitive earth fault (switch 7) selected, apply a current of 10A through the primary connections of the CTs and confirm the indicator response.
CT A
Source Load
CT B
Source Load
CT C
Source Load
SPi
Indication
Test 1 Inject EF
Test 2 Inject EF
Test 3 Inject EF
Test 4 Injection
Link
None
Test 5 Injection
Link
None
A full operational check of the indicator is achieved as follows: -
1. Apply voltage to the unit and wait for 10 seconds
2. Inject fault current for testing purposes, the LED will indicate when the threshold operating current is reached. When the curve time is reached the LED will switch off.
3. Switch supply AND fault current OFF at the same time
4. Confirm correct indications and alarms
7.2.2 Routine Testing
When powered up the test/reset button located on the lid of the SPi-EF can be used in two ways to confirm the operational readiness, and functionality of the indicator. When testing is being carried out the indicator continues to monitor for fault situations.
1. When operated the LED’s will flash for a short time and then steady until the test/reset button is released, the remote alarm relay contacts will not be operated (Testing Mode 1).
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 22
2. If the power supply to the SPi is removed within 15 seconds of test 1, both remote alarm contacts will close and both LED’s will indicate, allowing confirmation of the remote fault indication circuitry. The unit will indicate for 15 seconds and then reset, if supply is restored within 15 seconds the indicator will reset (Testing Mode 2).
If required a full check for operation can be carried out by current injection across the CT secondary terminals of the indicator with simultaneous removal of the mains sensing supply.
PRODUCT USER MANUAL doc ref SPi-Programmable issue 2.03
Fundamentals Ltd Page 23
App. A
SPi-EF Response against Normal Inverse & Very
Inverse curves using 0.1TM
0.01
0.10
1.00
10.00
1 10 100
PSM
Se
co
nd
s @
0.1
TM
Standard Very SPi-EF