NOTICE
INTRODUCTION
QUALITY ASSURANCE
RECOMMENDED ORDERING PARAMETERS
HALOGEN FREE - LOW SMOKE & FUME - FIRE RETARDANT CABLES5.1 - 0.6/1 KV Unarmoured5.2 - 0.6/1 KV Steel or Aluminium tape armoured5.3 - 0.6/1 KV Steel Wire armoured
HALOGEN FREE - LOW SMOKE & FUME - FIRE RESISTANT CABLES6.1 - 0.6/1 KV Unarmoured6.2 - 0.6/1 KV Steel or Aluminium tape armoured6.3 - 0.6/1 KV Steel Wire armoured6.4 - 300/500 V Screened Fire Alarm Cables
PETROCHEMICAL INDUSTRY CABLES7.1 - 0.6/1 KV Lead sheathed, Steel tape Armoured7.2 - Instrumentation cables, Lead sheathed, Steel tape Armoured
CONTROL, TRAFIC AND DATA CABLES8.1 - Multicores, Overall screen8.2 - Multipairs, Overall screen8.3 - Multipairs, Individual screen
SUBSTATION AND PILOT CABLES9.1- Power and signalling cables, Fire retardant, Halogen free, Low
smoke and fume9.2 - Control & Telecommunication, Screened, Fire retardant cables
AIRFIELD LIGHTING CABLES
HANDLING & LIFT CABLES11.1 - 450/750 V PVC flat, Flexible cables11.2 - 0.6/1 KVThermoplastic rubber flat, Flexible cables11.3 - Flat lift cables11.4 - Flat lift cables with strain bearing members
SUBMERSIBLE PUMP CABLES12.1 - 450/750 V Thermoplastic rubber round flexible cable12.2 - 0.6/1 KV PE/PE Round flexible cables12.3 - 0.6/1 KVPE/PE Flat flexible cables
P a g e
1
2
3
3
46
1 01 2
1 41 61 82 02 2
2 42 42 6
2 82 93 13 3
3 53 5
3 7
3 9
4 04 04 24 44 6
4 84 85 05 2
1
2
3
4
5
6
7
8
9
10
11
12
CONTENTS
1
As this catalogue is not intended to cover all of LIBAN CABLES SAL possibilities inspecial cables manufacturing, the hereafter listing of the types of cables is not restrictivebut only indicative of the main and most current types we manufacture.
On the other hand, our specification sheets are inspired mainly from the most usuallyrequired.
Whereas, in facts some special cables may require special conception, fully within thecapabilities of LIBAN CABLES SAL, ISO 9001 certified, precisely because in positionto conceive / tailor your special needs.
That is why, while consulting this brochure, it is important to take into account that anycombination or change of the constructional details mentioned in this catalogue remainfeasible, on base of special conception / development, matching any special or differentspecifications.
Finally, and within our policy of constant improvement, we reserve the right to alter anypart of the information contained in this publication without incurring any obligation. Inall cases this brochure being only indicative, and unless expressly agreed upon, it cannotbe considered by any mean as contractual document.
1 NOTICE
Devoted to the manufacturing of electric and telecomcables, Liban Cables is the first and largest supplier inLebanon and a leader in the Middle-East region.
Liban Cables was founded in 1968 by a group ofLebanese industrialists backed up by the technicalassistance of two international leading firms :
- Les Cables de Lyon - France (became ALCATELafterwards)
- Phelps Dodge - U.S.A.
Staffed with qualified engineers and highly skilledtechnicians, our plant is located in Nahr-Ibrahim at 30Km from Beirut, where cables are designed andmanufactured according to all internationalspecifications : IEC, VDE, UTE, BS and others oncustomer request.
Early after its foundation, Liban Cables has become themajor supplier of the Lebanese market in both the publicand private sectors. The product range of Liban Cablescovers all electric cables, copper communicationscables, (and optical fiber cables since 1995), in additionto a wide variety of special cables manufactured oncustomer request.
High quality cables, continuous developments of theproduction range, direct and fast shipments havecontributed in rendering Liban Cables an importantexporter for many countries on the three limitrophecontinents (Asia, Europe, Africa). Liban Cablesproducts are particularly appreciated by administrationsand international contractors operating in the region andseeking reliable and direct supplies of power andcommunication cables.
2 INTRODUCTION
2
3
Step by step, from raw material to final product, quality constitutes a major concern toLiban Cables.
Raw material are continuously and repetitively tested from trial orders till the last batchreceived afterwards.
In addition to the final tests carried out on finished products, work in process is alreadytested within two simultaneous procedures :
- A built in quality control system carried out by the production itself at any step of workin process.
- A parallel and contradictory procedure is also carried out on the same stages andproducts by independent inspectors reporting to the quality control service.
End users and/or third part inspection authorities are also constantly commissioning thefinished products and assessing the strict conformity to ordered specifications.
In fact, our ISO 9001 certification stated in Feb 1997 by the International CertificationNetwork (EQNET) is certified by the French Association for Quality Assurance (AFAQ),the well known rigourous and independant accredited European assessor. Thiscertification, under reference AFAQ Nº QUAL/ 1997 / 7034, confirms the soundness andthe performance of the Quality System we apply for the Design, the Development, theManufacturing and the Marketing & Sales of all our products.
For prompt quotation / supplies, please make sure your inquiries and your orders aresecuring the following data :
1 - International or Special Standard. (Alternatively, the precise usage of the cable.)
2 - Constructional details
3 - Other requirements
4 - Packing
5 - Required delivery time
6 - Required validity
3 QUALITY
4 RECOMMENDED ORDERING PARAMETERS
HALOGEN FREE, LOW SMOKE,FIRE RETARDANT CABLES
5
COMMON GENERAL CHARACTERISTICS
FIRE PERFORMANCES
FIRE RETARDANT FLAME RETARDANT
IEC 332 Part 3NF C 32-070 Cat. C1* (test no 2) + NF C 32-072BS 4066 Part 3NBN C 30-004 Cat. F2UNE 20-427 + UNE 20-432(3)DIN VDE 0472 Teil 804(C)CEI 20-22-3IEEE 383
IEC 332 Part 1CENELEC HD 405.1NF C 32-070 Cat. C2 (test no1)BS 4066 Part 1NBN C 30-004 Cat. F1UNE 20-432 (1)DIN VDE 0472 Teil 804 (B)CEI 20-35UL44
4
NBSchamber Test
NF C 20-902/1BS 6401-83CEI 20-37
IEC 754 Part 1 + Part 2CENELEC HD 602 S1NF C 32-074NF C 20-453 + NF C 20-454BS 6425 Part 1 + LULUNE 21-147 Part 1 + Part 2DIN VDE 0472 Teil 813CEI 20-37
* NF C 32-070 tests are designed for cables diameters: ≤ 70 mm for no2 test - C1
CORE IDENTIFICATION : According to customer requirements
27 M3 Chamber test
IEC 1034UITPAPTATest E4CENELEC HD 606 1/2 S1NF C 32-073BS 7622-93UNE 21172 DraftDIN VDE 0472 Teil 816
LOW SMOKE NON CORROSIVITY- NON TOXICITY
HALOGEN FREE, LOW SMOKE,FIRE RETARDANT CABLES
5
Copper
1.52.54610162535507095120150185240300400500630
Aluminium
162535507095120150185240300400500630
Conductorsizes
(mm2)
------
16120024231037743750457567978394010831254
-
121150184237289337389447530613740856996
24334558801071351692072683283824435096046998399581077
84103129159209253296343395471547663770899
2636496386115149185225289352410473542641741
---
91108135164211257300346397470543
---
2332425475100127157192246298346399456538620
---
7797120147187227263302346409471
---
37486380104136173208247304360410463518598677
---
104133160188233275314359398458520
---
3141536687113144174206254301343387434501565
---
87111134160197234266300337388440
---
24.814.89.26.23.72.41.61.2-----------
4.02.51.9-----------
21.512.88.05.43.22.11.351.00.750.550.420.350.300.250.210.200.170.150.14
3.452.21.61.220.850.650.520.430.360.290.260.230.210.18
Voltage dropcos ϕ = 0.8(V/Ax km) Buried cable
Current carrying capacities (A)(single circuit ratings)
3(1)2(1)3(1)2(1)3(1)2(1) 3(1) 2(1)
Cables in free air≤ 5 cores cablessingle core cables(2) ≤ 5 cores cables
free air
buried
1.52.54
1.52.54
162128
212634
111722
162128
915
1419
814
1217
814
1116
712
1014
21.512.88.0
21.512.88.0
Current carrying capacities (A)
3(1)2(1)27 3724197 12
Numberof coresInstalation C. sizes
(mm2)
Multicore cables Voltage dropcos ϕ = 0.8(V/Ax km)
CURRENT RATING GENERAL CONDITIONSThese current data are indicated for continuous dutyoperation and apply to :
• Maximum conductor temperature• Industrial frequency
- Cable in free air (Laying on perforated trays)• Ambient temperature
- Directly buried cable :• Ambient ground temperature• Soil thermal resistivity• Laying depth
Current rating ...data according to :- IEC 364-5-523 (1983)- or NF C 15-100 (1991)- or LIBAN CABLES data
For other laying conditions, see here aboverecommandations or standard.
90oC50Hz
30oC
20oC1 K.m/W0.7m
(1) Number of loaded conductors - (2) Trefoil for 3 single core cables
6
1 - Conductorsstranded copper or aluminium, class 2NF C 32-013 / IEC 228
2 - InsulationSpecial XLPE
3 - Filler(optional)
4 - Outer sheathHalogen free CompoundColour : black
N.B.:Colours and other constructional detailscan be according to customer specialrequirements.
Sheath marking- Name of manufacturer- Metric marking- Number of cores / cross sectional area(mm2)- Other : as per customer requirements
Fire performances :See page 4
Electrical data :See page 5
CONSTRUCTION
ACCORDING TO :NF C 32-323IEC 502 (for dimensions)Maximum conductortemperature : 90o C
5.1 - 0.6 / 1 kv Unarmoured Cables
- Halogen free - Low smoke
- Fire retardant
HALOGEN FREE, LOW SMOKE,FIRE RETARDANT CABLES
5
1
2
3
4
3 G 1.53 G 2.53 G 43 G 63 G 103 G 163 G 253 G 35
1 x 1.51 x 2.51 x 41 x 61 x 101 x 161 x 251 x 351 x 501 x 701 x 951 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 630
2 x 1.52 x 2.52 x 42 x 62 x 102 x 162 x 252 x 35
3 x 1.53 x 2.53 x 43 x 63 x 103 x 163 x 253 x 353 x 503 x 703 x 953 x 1203 x 1503 x 1853 x 2403 x 300
5.05.56.06.57.38.5
10.211.312.414.316.017.519.521.524.527.030.034.038.5
8.89.6
10.511.513.014.517.519.5
9.210.011.012.013.515.519.021.024.528.532.536.040.044.550.556.0
6.67.07.68.29.210.512.513.515.017.019.021.023.025.528.531.034.538.543.0
10.511.513.014.016.018.522.024.5
11.012.513.515.017.019.523.526.029.034.038.542.547.553.059.566.0
606570758595115125135155175190210230260280310350390
65708085100115135150
70758590105120145160175205235255285320360400
607090115160230340440570800108013401640200027003200410051006600
1401802403104206009001150
16020027035051074011101570207029103880487059807370970012000
7
Specifications can change according to customer requirements
Cables (mm2)
COPPER (cl2)
Outerdiam. Min. bendingradius(mm)➀
Weightapprox.(kg/km)Min.
(mm)Max.(mm)
INSTALLATIONThese cables will be installed according to the wiring regulations and installationstandards in operation
Laying temperature : In case of laying between 0 and -10oC, it is advised to warm upagain the cables in a hot room 48 hours minimum before installation.
Use of these cables should be limited to short lenghts when buried in soil non saturatedwith water.
G = with green / yellow core➀ Values to be doubled during laying operations• Other sizes are also available
UNARMOURED, HALOGEN FREE , LOW SMOKE,FIRE RETARDANT CABLES
8
4 G 1.54 G 2.54 G 44 G 64 G 104 G 164 G 254 G 35
5 G 1.55 G 2.55 G 45 G 65 G 105 G 165 G 25
7 G 1.57 G 2.57 G 4
12 G 1.512 G 2.512 G 4
19 G 1.519 G 2.5
27 G 1.527 G 2.5
37 G 1.537 G 2.5
4 x 1.54 x 2.54 x 44 x 64 x 104 x 164 x 254 x 354 x 504 x 704 x 954 x 1204 x 1504 x 1854 x 2404 x 300
5 x 1.55 x 2.55 x 45 x 65 x 105 x 165 x 25
7 x 1.57 x 2.57 x 4
10 x 1.510 x 2.5
12 x 1.512 x 2.512 x 4
14 x 1.514 x 2.5
19 x 1.519 x 2.5
27 x 1.527 x 2.5
37 x 1.537 x 2.5
9.810.512.013.015.017.020.523.027.031.536.040.044.550.056.562.5
10.511.513.014.016.518.523.0
11.512.513.5
14.515.5
14.516.017.5
15.017.0
17.019.0
20.022.5
22.525.0
12.013.014.516.018.521.025.528.532.537.542.547.552.559.066.573.5
13.014.516.017.520.023.028.0
13.515.016.5
16.519.0
17.019.521.5
18.020.5
19.522.5
23.027.0
25.529.5
758090100115130155175195225255285315355400445
8090100105120140170
8590100
100115
105120130
110125
120135
140165
155180
190240320430630930142019902480370046906210765094201240015300
22029039053078011401750
250390530
420560
420650890
500670
620840
870
11101680
Specifications can change according to customer requirements
Cables (mm2)
COPPER (cl2)
3 x 50 + 253 x 70 + 503 x 95 + 50
3 x 120 + 703 x 150 + 703 x 185 + 703 x 240 + 95
26.631.134.738.942.647.153.2
31.136.240.645.449.554.461.5
190220245275300330370
246034204360560066707980
10500
Outerdiam. Min. bendingradius(mm)➀
Weightapprox.(kg/km)Min.
(mm)Max.(mm)
G = with green / yellow core➀ Values to be doubled during laying operations• Other sizes are also available
UNARMOURED, HALOGEN FREE, LOW SMOKE,FIRE RETARDANT CABLES
9
3 G 163 G 253 G 353 G 50
4 G 164 G 254 G 354 G 50
1 x 161 x 251 x 351 x 501 x 701 x 951 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 630
2 x 162 x 252 x 35
3 x 163 x 253 x 353 x 503 x 703 x 953 x 1203 x 1503 x 1853 x 2403 x 300
4 x 164 x 254 x 354 x 504 x 704 x 954 x 1204 x 1504 x 1854 x 2404 x 300
8.510.211.312.414.316.017.519.521.524.527.030.034.038.5
14.517.519.4
15.519.021.024.528.532.536.040.044.550.556.0
26.631.134.738.942.647.153.2
17.020.523.027.031.536.040.044.550.056.562.5
10.512.513.515.017.019.021.023.025.528.531.034.538.543.0
18.522.024.5
19.523.526.029.034.038.542.547.553.059.566.0
31.136.240.645.449.554.461.5
21.025.528.532.537.542.547.552.559.066.573.5
95115125135155175190210230260280310350390
115135150
120145160175205235255285320360400
190220245275300330370
130155175195225255285315355400445
1301802202703404605506407909901230155020002540
360530660
4206207709701330171021202590324040805090
1130160018902400284034304320
51075094011801630211026103210401050306280
Specifications can change according to customer requirements
Cables (mm2)
Aluminium (cl2)
Outerdiam. Min. bendingradius(mm)➀
Weightapprox.(kg/km)Min.
(mm)Max.(mm)
G = with green / yellow core➀ Values to be doubled during laying operations• Other sizes are also available
3 x 50 + 353 x 70 + 503 x 95 + 50
3 x 120 + 703 x 150 + 703 x 185 + 703 x 240 + 95
UNARMOURED, HALOGEN FREE, LOW SMOKE,FIRE RETARDANT CABLES
10
1 - ConductorsBare copper :• (≤ 4 mm2) Copper :Solid-class 1 or stranded class 2• (≥ 6 mm2) Stranded copper oraluminium, class 2NF C 32-013 / IEC 228
2 - InsulationSpecial XLPE
3 - Filler (optional) + InnersheathHalogen free CompoundColour : black
4 - Armour• Black or galvanized steel tapes(aluminium tapes for single corecables)
5 - Outersheath:Halogen free CompoundColour : black
N.B.:Colours and other constructional detailscan be according to customer specialrequirements.
Sheath marking- Name of manufacturer- Metric marking- Number of cores / cross sectional area(mm2)- Other : as per customer requirements
Fire performances :See page 4
Electrical data :See page 5
CONSTRUCTION
ACCORDING TO :NF C 32-323IEC 502 (for dimensions)Maximum conductortemperature : 90o C
5.2 - 0.6 / 1 kv Armoured (by tapes)
- Halogen free - Low smoke
- Fire retardant
HALOGEN FREE, LOW SMOKE,FIRE RETARDANT CABLES
5
1
3
4
5
2
11
2 x 1.52 x 2.52 x 42 x 62 x 102 x 162 x 252 x 35
3 x 1.53 x 2.53 x 43 x 63 x 103 x 163 x 253 x 353 x 503 x 703 x 953 x 1203 x 1503 x 1853 x 2403 x 300
3 G 1.53 G 2.53 G 43 G 63 G 103 G 163 G 253 G 353 G 50
3 x 50 + 353x70+503x95+503x120+703x150+703x185+703x240+95
10.511.012.013.515.017.020.022.5
11.011.512.514.016.017.521.023.527.032.036.540.545.049.556.061.0
11.011.512.514.016.017.521.023.527.0
29.034.038.042.546.550.557.5
14.515.517.018.020.022.526.529.0
15.016.517.519.021.023.528.030.534.039.045.550.055.060.567.574.5
15.016.517.519.021.023.528.030.534.0
36.041.547.552.557.062.570.0
120125140145160180220235
120135140155170190225245275315365400440485540600
120135140155170190225245275
290335380420460500560
250290350450600800
1 1501 500
270330420520700980
1 4001 8002 3503 2004 5505 7006 9008 400
10 60013 000
270330420520700980
1 4001 8002 350
2 8003 8005 2006 5007 6009 000
12 000
520740890
580830
1 0101 2501 6702 5103 0203 6504 3805 3506 600
580830
1 0101 250
1 4401 9302 7103 2903 8904 5605 650
4 x 1.54 x 2.54 x 44 x 64 x 104 x 164 x 254 x 354 x 504 x 704 x 954 x 1204 x 1504 x 1854 x 2404 x 300
4 G 1.54 G 2.54 G 44 G 64 G 104 G 164 G 254 G 354 G 50
5 G 1.55 G 2.55 G 45 G 65 G 105 G 165 G 25
7 G 1.512 G 1.519 G 1.527 G 1.537 G 1.5
7 G 2.512 G 2.519 G 2.527 G 2.537 G 2.5
11.512.513.515.017.019.523.026.029.536.540.545.549.554.561.567.5
11.512.513.515.017.019.523.026.029.5
12.513.514.516.519.522.525.5
14.017.019.523.025.5
15.019.021.525.528.5
16.017.018.520.022.525.530.033.537.544.550.055.060.567.075.082.5
16.017.018.520.022.525.530.033.537.5
17.018.520.021.524.527.533.0
17.521.023.527.530.0
19.023.527.031.534.5
130140150160180205240270300360400440485540600660
130140150160180205240270300
140150160175200220265
140170190220240
155190220255280
320390490620860
1 2001 7502 3002 9504 5005 8007 2008 800
10 60013 80017 000
320390490620860
1 2001 7502 3002 950
360440560720
1 0001 4002 100
420660850
1 2001 450
540830
1 1501 7002 000
690980
1 2001 4902 4002 9803 6404 3805 2506 4507 900
690980
1 2001 490
Specifications can change according to customer requirements
Cables(mm2)
Cables(mm2)
Outerdiam. Outerdiam.Min.bendingradius(mm)➀
Min.bendingradius(mm)➀Min.
(mm)Min.(mm)
Max.(mm)
Max.(mm)
G = with green / yellow core➀ Values to be doubled during laying operations• Other sizes are also available
Copper CopperAlu Alu
Weightapprox.(kg/km)
Weightapprox.(kg/km)
INSTALLATIONThese cables will be installed according to the wiring regulations and installationstandards in operation
Laying temperature : In case of laying between 0 and -10oC, it is advised to warm upagain the cables in a hot room 48 hours minimum before installation.
ARMOURED ( BY TAPES), HALOGEN FREE, LOW SMOKE,FIRE RETARDANT CABLES
12
1 - ConductorsBare copper :• (≤ 4 mm2) Copper :Solid-class 1 or stranded class 2• (≥ 6 mm2) Stranded Copper oraluminium, class 2NF C 32-013 / IEC 228
2 - InsulationSpecial XLPE
3 - Filler(optional) + InnersheathHalogen free polyolefin
4 - Armour• Single layer of galvanized steelwires (aluminium wire for single corecables)
5 - Outer sheath:Halogen free polyolefinColour : black
N.B.:Colours and other constructional detailscan be according to customer specialrequirements.
Sheath marking- Name of manufacturer- Metric marking- Number of cores / cross sectional area(mm2)- Other : as per customer requirements
Fire performances :See page 4
Electrical data :See page 5
CONSTRUCTION
ACCORDING TO :
IEC 502 (for dimensions)
Maximum conductor temperature : 90o C
5.3 - 0.6 / 1 kv Steel WireArmoured
- Halogen free - Low smoke
- Fire retardant
HALOGEN FREE, LOW SMOKE,FIRE RETARDANT CABLES
5
1
2
3
4
5
13
2 x 1.52 x 2.52 x 42 x 62 x 102 x 162 x 252 x 35
3 x 1.53 x 2.53 x 43 x 63 x 103 x 163 x 253 x 353 x 503 x 703 x 953 x 1203 x 1503 x 1853 x 2403 x 300
3 G 1.53 G 2.53 G 43 G3 G 103 G 163 G 253 G 353 G 50
3 x 50 + 353x70+503x95+503x120+703x150+703x185+703x240+95
12.012.513.515.017.019.523.525.5
12.513.014.016.018.020.525.027.030.035.039.042.548.053.059.064.0
12.513.014.016.018.020.525.027.030.0
33.037.541.046.050.054.061.0
16.017.518.520.022.026.030.032.0
16.518.519.021.023.026.532.034.037.042.048.052.058.063.070.576.0
16.518.519.021.023.026.532.034.037.0
40.045.050.556.060.566.073.5
160175185200220260300320
165185190210230265320340370420480520580630710760
165185190210230265320340370
400450505560605660735
340390470570880
1 1201 7002 000
370430510780980
1 2901 9402 3903 0004 2505 4006 5008 500
10 00012 40015 000
370430510780980
1 2901 9402 3903 000
3 7004 8505 9007 7009 000
10 50013 300
73010901190
7701 1501 3401 6002 2202 9803 4504 5005 2206 2607 620
7701 1501 3401 600
1 9002 4703 0803 9004 6105 3206 260
4 x 1.54 x 2.54 x 44 x 64 x 104 x 164 x 254 x 354 x 504 x 704 x 954 x 1204 x 1504 x 1854 x 2404 x 300
4 G 1.54 G 2.54 G 44 G 64 G 104 G 164 G 254 G 354 G 50
5 G 1.55 G 2.55 G 45 G 65 G 105 G 165 G 25
7 G 1.512 G 1.519 G 1.537 G 1.5
7 G 2.512 G 2.519 G 2.537 G 2.5
13.014.016.017.519.523.027.030.033.538.543.048.553.058.065.570.5
13.014.016.017.519.523.027.030.033.5
14.015.017.019.021.524.529.5
14.519.022.027.5
16.520.524.031.0
17.518.521.022.525.029.034.037.541.546.552.558.064.070.579.085.5
17.518.521.022.525.029.034.037.541.5
18.520.022.524.026.529.537.0
18.523.026.032.0
20.525.029.537.0
175185210225250290340375415465525580640705790855
175185210225250290340375415
185200225240265295370
185230360320
205250295370
410490720870
1 1401 6502 3002 8503 8505 1006 5508 500
10 10012 00015 20018 500
410490720870
1 1401 6502 3002 8503 850
460560800
1 0001 4501 9302 720
550920
1 3002 050
7701 1501 6502 600
9501 2901 5001 9502 7203 3704 3005 0305 9507 1008 600
9501 2901 5001 950
Specifications can change according to customer requirements
Cables(mm2)
Cables(mm2)
Outerdiam. Outerdiam.Min.bendingradius(mm)➀
Min.bendingradius(mm)➀Min.
(mm)Min.(mm)
Max.(mm)
Max.(mm)
G = with green / yellow core➀ Values to be doubled during laying operations• Other sizes are also available
Copper CopperAlu Alu
Weightapprox.(kg/km)
Weightapprox.(kg/km)
INSTALLATIONThese cables will be installed according to the wiring regulations and installationstandards in operation
Laying temperature : In case of laying between 0 and -10oC, it is advised to warm upagain the cables in a hot room 48 hours minimum before installation.
ARMOURED (STEELWIRES), HALOGEN FREE, LOW SMOKE,FIRE RETARDANT CABLES
14
HALOGEN FREE, LOW SMOKE,FIRE RESISTANT CABLES
6
COMMON GENERALCHARACTERISTICS
FIRE PERFORMANCES
FIRE RESISTANT FIRE RETARDANT
IEC 331BS 6387 Cat. CWZUNE 20-431DIN VDE 0472Teil 814(180 mm)
FLAME RETARDANT
IEC 332 Part 1CENELEC HD 405.1NF C 32-070 Cat. C2 (test no1)BS 4066 Part 1NBN C 30-004 Cat. F1UNE 20-432 (1)DIN VDE 0472 Teil 804 (B)CEI 20-35UL44
IEC 332 Part 3NF C 32-070 Cat. C1* (test no2)+ NF C 2-072BS 4066 Part 3NBN C 30-004 Cat. F2UNE 20-427 + UNE 20-432 (3)DIN VDE 0472 Teil 804 (C)CEI 20-22-3IEEE 383
NBSchamber Test
NF C 20-902/1BS 6401-83CEI 20-37
IEC 754 Part 1 + Part 2CENELEC HD 602 S1NF C 32-074NF C 20-453 + NF C 20-454BS 6425 Part 1 + LULUNE 21-147 Part 1 + Part 2DIN VDE 0472 Teil 813CEI 20-37
* NF C 32-070 tests are designed for cables diameters: ≤ 70 mm for no2 test - C1
CORE IDENTIFICATION : According to customer requirements
27 M3 Chambertest
IEC 1034UITP APTATest E4CENELEC HD 606 1/2 S1NF C 32-073BS 7622-93UNE 21172 (Draft)DIN VDE 0472 Teil 816
LOW SMOKE NON CORROSIVITY- NON TOXICITY
21.512.88.0
21.512.88.0
HALOGEN FREE, LOW SMOKE,FIRE RESISTANT CABLES
Copper
1.52.54610162535507095120150185240300400500630
Conductorsizes
(mm2)
------
16120024231037743750457567978394010831254
24334558801071351692072683283824435096046998399581077
2636496386115149185225289352410473542641741
---
2332425475100127157192246298346399456538620
---
37486380104136173208247304360410463518598677
---
3141536687113144174206254301343387434501565
---
24.814.89.26.23.72.41.61.2-----------
21.512.88.05.43.22.11.351.00.750.550.420.350.300.250.210.200.170.150.14
Voltage dropcos ϕ = 0.8(V/Ax km) Buried cable
Current carrying capacities (A)(single circuit ratings)
3(1)2(1)3(1)2(1)3(1)2(1) 3(1) 2(1)
Cables in free air≤ 5 cores cablessingle core cables(2) ≤ 5 cores cables
free air
buried
1.52.54
1.52.54
162128
212634
111722
162128
915
1419
814
1217
814
1116
712
1014
Current carrying capacities (A)
27 3724197 12
Numberof coresInstalation C. sizes
(mm2)
Multicore cables
CURRENT RATING GENERAL CONDITIONSThese current data are indicated for continuous dutyoperation and apply to :
• Maximum conductor temperature• Industrial frequency
- Cable in free air (Laying on perforated trays)• Ambient temperature
- Directly buried cable :• Ambient ground temperature• Soil thermal resistivity• Laying depth
Current rating ...data according to :- IEC 364-5-523 (1983)- or NF C 15-100 (1991)- or LIBAN CABLES data
For other laying conditions, see here aboverecommandations or standard.
90oC50Hz
30oC
20oC1 K.m/W0.7m
(1) Number of loaded conductors - (2) Trefoil for 3 single core cables
15
Voltage dropcos ϕ = 0.8(V/Ax km)
16
1 - ConductorsBare copper :• solid-class 1 (≤ 4 mm2)• stranded-class 2 (≥ 6 mm2)NF C 32-013 / IEC 228
2 - Mica tape
3 - InsulationSpecial XLPE
4 - Filler(optional)
5 - Outer sheathHalogen free compound,Colour : black
N.B.:Colours and other constructional detailscan be according to customer specialrequirements.
Sheath marking- Name of manufacturer- Metric marking- Number of cores / cross sectional area(mm2)- Other : as per customer requirements
Fire performances :See page 18
Electrical data :See page 19
CONSTRUCTION
ACCORDING TO :NF C 32-323IEC 502 (for dimensions)Maximum conductortemperature : 90o C
6.1 - 0.6 / 1 kv Unarmoured
- Halogen free - Low smoke
- Fire resistant, Fire retardant
HALOGEN FREE, LOW SMOKE,FIRE RESISTANT CABLES
6
INSTALLATIONThese cables will be installed according to the wiring regulations and installationstandards in operation.
The use of these cables will be limited to short lenghts when buried in soil non-saturatedwith water.
Laying temperature : in case of laying between 0 and -10oC, it is advised to warm upagain the cables in a hot room 48 hours minimum before installation.
1
2
3
4
5
17
1 x 1.51 x 2.51 x 41 x 61 x 101 x 161 x 251 x 351 x 501 x 701 x 951 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 630
2 x 1.52 x 2.52 x 42 x 62 x 102 x 162 x 252 x 35
3 G 1.53 G 2.53 G 43 G 63 G 103 G 163 G 25
3 x 1.53 x 2.53 x 43 x 63 x 103 x 163 x 253 x 353 x 503 x 703 x 953 x 1203 x 1503 x 1853 x 2403 x 300
5.86.06.67.08.08.7
10.811.812.914.716.518.020.022.024.527.030.534.038.5
8.810.611.512.914.416.519.521.5
9.210.012.213.215.017.521.0
9.210.012.213.215.017.521.023.025.529.533.537.041.045.551.556.5
6.67.07.68.29.2
10.512.513.515.017.019.021.023.025.528.531.034.538.543.0
10.511.712.714.116.018.522.024.0
11.012.513.414.617.019.523.5
11.012.513.414.617.019.523.526.029.034.038.542.547.553.059.566.0
606570758090
110120130150170180200220250280310350390
65708085
100110130150
70758090
100120140
70758090
100120140160175205230255285320360400
7080
110120170230340440600820
1 1001 3701 6702 0402 6803 5004 4406 7107 190
170210270350480670
1 0001 280
190240320410590840
1 250
190240320410590840
1 2501 6402 1302 9803 9604 9606 0807 4809 830
12 100
3 x 50 + 353 x 70 + 503 x 95 + 503x120+703x150+703x185+703x240+95
4G 1.54 G 24 G 44 G 64 G 104 G 164 G 25
4 x 1.54 x 24 x 44 x 64 x 104 x 164 x 254 x 354 x 504 x 704 x 954 x 1204 x 1504 x 1854 x 2404 x 300
5 G 1.55 G 2.55 G 45 G 65 G 105 G 165 G 25
7 G 1.57 G 2.57 G 4
12 G 1.512 G 2.512 G 4
19 G 1.519 G 2.519 G 4
37 G 1.537 G 2.5
27.532.035.039.543.047.153.2
9.812.113.114.716.517.023.0
9.812.113.114.716.517.023.025.528.033.037.041.045.551.057.563.0
10.511.514.014.018.018.525.5
13.014.115.5
16.518.020.0
19.021.023.5
25.528.0
31.136.240.645.449.554.461.5
12.013.314.516.018.021.025.5
12.013.314.516.018.021.025.528.532.537.542.547.552.559.066.573.5
13.014.516.017.520.023.028.0
14.215.517.0
18.520.022.0
21.523.526.0
28.531.0
190220245275300330370
758090100110130160
758090100110130160170195225255285315355400440
8090100110120140170
8595100
110120130
130140160
170190
2 5303 5004 4405 6906 7708 080
10 700
220290380500720
1 0001 580
220290380500720
1 0001 5802 0502 6903 7805 0606 3107 7709 550
12 60015 500
270340450590860
1 2301 900
330430570
540720970
7501 0101 410
1 3701 870
Specifications can change according to customer requirements.
Cables(mm2)
Cables(mm2)
Outerdiam. Outerdiam.Min.bendingradius(mm)➀
Min.bendingradius(mm)➀Min.
(mm)Min.(mm)
Max.(mm)
Max.(mm)
G = with green / yellow core➀ Values to be doubled during laying operations• Other sizes are also available
Weightapprox.(kg/km)
Weightapprox.(kg/km)
UNARMOURED, HALOGEN FREE, LOW SMOKE,FIRE RESISTANT CABLES
18
1 - ConductorsBare copper :• solid-class 1 (≤ 4 mm2)• stranded-class 2 (≥ 6 mm2)NF C 32-013 / IEC 228
2 - Mica tape3 - Insulation
Special XLPE4 - Filler(optional) + Innersheath
Halogen free polyolefin5 - Armour
Black or galvanized steel tapes(Aluminium tapes for single corecables)
6 - Outer sheathHalogen free compoundColour : black
N.B.:Colours and other constructional detailscan be according to customer specialrequirements.Sheath marking- Name of manufacturer- Metric marking- Number of cores / cross sectional area(mm2)- Other : as per customer requirementsFire performances :See page 18Electrical data :See page 19
CONSTRUCTION
ACCORDING TO :NF C 32-323IEC 502 (for dimensions)Maximum conductortemperature : 90o C
6.2 - 0.6 / 1 kv Armoured (tapes)
- Halogen free - Low smoke
- Fire resistant, Fire retardant
HALOGEN FREE, LOW SMOKE,FIRE RESISTANT CABLES
6
INSTALLATIONThese cables will be installed according to the wiring regulations and installationstandards in operation
Laying temperature : in case of laying between 0 and -10oC, it is advised to warm upagain the cables in a hot room 48 hours minimum before installation.
1
2
3
4
5
6
19
2 x 1.52 x 2.52 x 42 x 62 x 102 x 162 x 252 x 35
3 G 1.53 G 2.53 G 43 G 63 G 103 G 163 G 25
3 x 1.53 x 2.53 x 43 x 63 x 103 x 163 x 253 x 353 x 503 x 703 x 953 x 1203 x 1503 x 1853 x 2403 x 300
4 G 1.54 G 2.54 G 44 G 64 G 104 G 164 G 25
10.511.012.013.515.017.020.022.5
11.011.512.514.016.017.521.0
11.011.512.514.016.017.521.023.527.032.036.540.545.049.556.061.0
11.512.513.515.017.019.523.0
14.515.517.018.020.022.526.529.0
15.016.517.519.021.023.528.0
15.016.517.519.021.023.528.030.534.039.045.550.555.060.567.574.5
16.017.018.520.022.525.530.0
120125140145160180220235
120135140155170190225
120135140155170190225245275315365400440485540600
130140150160180205240
270320380500650870
1 1901 560
290360460560750
10301450
290360460560750
103014501850240032804650580071508600
1080013300
340430530680930
1 3001 880
4 x 1.54 x 2.54 x 44 x 64 x 104 x 164 x 254 x 354 x 504 x 704 x 954 x 1204 x 1504 x 1854 x 2404 x 300
5 G 1.55 G 2.55 G 45 G 65 G 105 G 165 G 25
3x50+353x70+503x95+503x120+703x150+703x185+703x240+95
7 G 1.57 G 2.57 G 4
12 G 1.512 G 2.512 G 4
19 G 1.519 G 2.519 G 4
37 G 1.537 G 2.5
11.0512.513.515.017.019.523.026.029.536.540.545.549.554.561.567.5
12.513.514.516.519.522.525.5
29.034.038.042.546.550.557.5
14.015.016.5
17.019.021.0
19.521.526.0
25.528.5
16.017.018.520.022.525.530.033.537.544.550.055.060.567.075.082.5
17.018.520.021.524.527.533.0
36.041.547.552.557.062.570.0
17.519.021.5
21.023.526.5
23.527.029.0
30.034.5
130140150160180205240270300360400440485540600660
140150160175200220265
290335380420460500560
140155170
170190210
190220230
240280
340430530680930
1 3001 8802 4003 0904 7006 0007 5009 1009 900
14 30017 600
390480610790
1 0901 5102 230
2 9204 0005 4206 7708 0009 430
12 500
450580760
710900
1 130
9901 3001 720
1 7002 270
Specifications can change according to customer requirements.
Cables(mm2)
Cables(mm2)
Outerdiam. Outerdiam.Min.bendingradius(mm)➀
Min.bendingradius(mm)➀Min.
(mm)Min.(mm)
Max.(mm)
Max.(mm)
G = with green / yellow core➀ Values to be doubled during laying operations• Other sizes are also available
Weightapprox.(kg/km)
Weightapprox.(kg/km)
ARMOURED ( BYTAPES ), HALOGEN FREE, LOW SMOKE,FIRE RESISTANT CABLES
20
1 - ConductorsBare copper :• solid-class 1 (≤ 4 mm2)• stranded-class 2 (≥ 6 mm2)NF C 32-013 / IEC 228
2 - Mica tape3 - Insulation
Special XLPE4 - Filler(optional) + Innersheath
Halogen free polyolefin5 - Armour
• Single layer of galvanized steelwires (Aluminium wires for singlecore cables)
6 - Outer sheathHalogen free compoundColour : black
N.B.:Colours and other constructional detailscan be according to customer specialrequirements.Sheath marking- Name of manufacturer- Metric marking- Number of cores / cross sectional area(mm2)- Other : as per customer requirementsFire performances :See page 18Electrical data :See page 19
CONSTRUCTION
ACCORDING TO :IEC 502 (for dimensions)Maximum conductortemperature : 90o C
6.3 - 0.6 / 1 kv Steel wireArmoured
- Halogen free - Low smoke
- Fire resistant, Fire retardant
HALOGEN FREE, LOW SMOKE,FIRE RESISTANT CABLES
6
INSTALLATIONThese cables will be installed according to the wiring regulations and installationstandards in operation
Laying temperature : in case of laying between 0 and -10oC, it is advised to warm upagain the cables in a hot room 48 hours minimum before installation.
1
2
3
4
5
6
21
2 x 1.52 x 2.52 x 42 x 62 x 102 x 162 x 252 x 35
3 G 1.53 G 2.53 G 43 G 63 G 103 G 163 G 25
3 x 1.53 x 2.53 x 43 x 63 x 103 x 163 x 253 x 353 x 503 x 703 x 953 x 1203 x 1503 x 1853 x 2403 x 300
4 G 1.54 G 2.54 G 44 G 64 G 104 G 164 G 25
12.012.513.515.017.019.523.525.5
12.513.014.016.018.020.525.0
12.513.014.016.018.020.525.027.030.035.039.042.548.053.059.064.0
13.014.016.017.519.523.527.0
16.017.518.520.022.026.030.032.0
16.518.519.021.023.026.532.0
16.518.519.021.023.026.532.034.037.042.048.052.058.063.070.576.0
17.518.521.022.525.029.034.0
160175185200220260300320
165185190210230265320
165185190210230265320340370420480520580630710760
175185210225250290340
360420510620950
1 2001 8002 150
390460520840
1 0501 3602 100
390460520840
1 0501 3602 1002 5203 2004 5105 6806 8308 800
10 30012 80015 400
440540780940
1 2201 8502 500
4 x 1.54 x 2.54 x 44 x 64 x 104 x 164 x 254 x 354 x 504 x 704 x 954 x 1204 x 1504 x 1854 x 2404 x 300
5 G 1.55 G 2.55 G 45 G 65 G 105 G 165 G 25
3x50+353x70+503x95+503x120+703x150+703x185+703x240+95
7 G 1.57 G 2.57 G 4
12 G 1.512 G 2.512 G 4
19 G 1.519 G 2.519 G 4
37 G 1.537 G 2.5
13.014.016.017.519.523.027.030.033.538.543.048.553.058.065.570.5
14.015.017.019.021.524.529.5
33.037.541.046.050.054.061.0
14.516.517.5
19.020.522.5
22.024.026.0
27.531.0
17.518.521.022.525.029.034.037.541.546.552.558.064.070.579.085.5
18.520.022.524.026.529.537.0
40.045.050.556.060.566.073.5
18.520.522.5
23.025.027.5
26.029.532.0
32.037.0
175185210225250290340375415465525580640705790855
185200225240265295370
400450505560605660735
185205225
230250275
260295320
320370
440540780940
1 2201 8502 5003 0204 0505 3006 8008 850
10 60012 50015 80019 200
490600890
1 1001 5502 0502 870
3 9005 0706 2008 0009 350
10 90013 700
590820950
9901 2501 450
1 4501 8002 150
2 2002 800
Specifications can change according to customer requirements.
Cables(mm2)
Cables(mm2)
Outerdiam. Outerdiam.Min.bendingradius(mm)➀
Min.bendingradius(mm)➀Min.
(mm)Min.(mm)
Max.(mm)
Max.(mm)
G = with green / yellow core➀ Values to be doubled during laying operations• Other sizes are also available
Weightapprox.(kg/km)
Weightapprox.(kg/km)
ARMOURED ( STEELWIRES ), HALOGEN FREE, LOW SMOKE,FIRE RESISTANT CABLES
22
1 - ConductorsBare copper :• stranded-class 2NF C 32-013 / IEC 228
2 - Mica tape3 - Insulation
Special XLPE4 - Circuit protective / drain wire
Stranded copper conductor5 - Aluminium / Polyester tape6 - Outersheath
Halogen free compoundColour : red or white
N.B.:Colours and other constructional detailscan be according to customer specialrequirements.Sheath marking- Name of manufacturer- Metric marking- Number of cores / cross sectional area(mm2)- Other : as per customer requirementsFire performances :See page 18
CONSTRUCTION
ACCORDING TO :BS 6387Maximum conductortemperature : 90o C
6.4 - 300 / 500 V Screened, Fire Alarm Cables
- Halogen free - Low smoke
- Fire resistant, Fire retardant
HALOGEN FREE, LOW SMOKE,FIRE RESISTANT CABLES
6
4
6
1
2
3
5
23
2 x 1 + 12 x 1.5 + 1.52 x 2.5 + 2.52 x 4 + 4
3 x 1 + 13 x 1.5 + 1.53 x 2.5 + 2.5
4 x 1 + 14 x 1.5 + 1.54 x 2.5 + 2.5
7 x 1 + 17 x 1.5 + 1.5
12 x 1.5 + 1.512 x 2.5 + 2.5
19 x 1.5 + 1.519 x 2.5 + 2.5
15202736
141824
141824
811
912
811
44291811
382515
382515
4429
2918
2918
8.29.2
10.111.4
8.69.9
11.0
9.610.912.0
11.413.1
17.319.3
20.622.8
7595
135185
90125170
115165210
170240
400545
585810
Specifications can change according to customer requirements.
Cables (mm2)Permissible
current rating(A)
Voltage dropcos ϕ = 0.8(V/Ax km)
Weightapprox.(kg/km)
Other sizes are also available
NominalOuterdiam.
(mm)
300 / 500 V SCREENED, FIRE, ALARM CABLES,HALOGEN FREE, LOW SMOKE,
FIRE RESISTANT CABLES
24
PETROCHEMICAL INDUSTRY CABLES7
1 - ConductorsBare copper :• solid-class 1 (≤ 4 mm2)• stranded-class 2 (≥ 6 mm2)NF C 32-013 / IEC 228
2 - InsulationXLPE
3 - FillersheathPVC
4 - SheathLead
5 - BeddingPaper tapes
6 - ArmourSteel tape or wires, or flat wire plushellicaly applied tape.
7 - OutersheathPVC - HRColour : black
N.B.:Colours and other constructional detailscan be according to customer specialrequirements.IdentificationAccording to customer requirementsSheath marking- Name of manufacturer- Metric marking- Number of cores / cross sectional area(mm2)- Other : as per customer requirements
CONSTRUCTION
7.1 - POWER CABLES
- 0.6 / 1 kv, Lead Sheathed, Steel tape orwire armoured- NFC 32 - 111- Maximum conductortemperature : 90o C
1
2
3
4
5
6
7
25
2 x 1.52 x 2.52 x 42 x 62 x 102 x 162 x 252 x 352 x 502 x 702 x 952 x 1202 x 1502 x 1852 x 240
3 x 1.53 x 2.53 x 43 x 63 x 103 x 163 x 253 x 353 x 503 x 703 x 953 x 1203 x 1503 x 1853 x 240
4 x 1.54 x 2.54 x 44 x 64 x 104 x 164 x 254 x 354 x 504 x 704 x 954 x 1204 x 150
5 x 1.55 x 2.55 x 45 x 65 x 105 x 165 x 25
34465974
101128162195235290347397444500584
34465974
101128162170204252302345390444522
2940516488
111141170204252302345390
2940516488
111141
2433455880
107142175212270327379435496579
2433455880
107142157190242293339386435504
223040527196
127157190242293339386
223040527196
127
24.814.89.26.23.72.41.61.20.90.70.40.3
0.280.2
0.19
21.512.8
83.83.22.1
1.351
0.750.550.420.350.3
0.250.21
21.512.8
85.43.22.1
1.351
0.750.550.420.350.21
21.512.8
85.43.22.1
1.35
12.913.716.518.721.323.127.329.932.535.541.6454953.859.6
13.414.217.519.522.224.228.83234.339.64447.952.257.563.5
1417.218.421.223.626.631.134.639.24347.952.257.1
16.918.219.522.725.628.734
103109132149170184218239260284333360390430477
107113140156177193230256274316352383417460508
112137147169188212248276313344383417547
135145156182205230272
475540795
1 0301 3551 6002 2052 7053 2853 9005 3906 3557 5059 010
11 245
515590925
1 1401 4951 8702 6053 2703 9705 0056 5007 7459 150
11 03513 755
565880
1 0251 3251 7002 2003 0403 8305 1856 1607 9259 435
11 275
820985
1 1501 5602 0102 6303 660
Usual Technical DataConductor : CopperSpecifications can change according to customer requirements
Cables (mm2)
Permissible current rating(A) Nominal
Outerdiam( mm )
Weightapprox.
(Kg/Km)
Voltage dropcos ϕ = 0.8(V/Ax km)
Min. bendingradius( mm )Buried Open air
PETROCHEMICAL INDUSTRY CABLES0.6 / 1 KV, LEAD SHEATHED, STEEL TAPE ARMOURED
26
PETROCHEMICAL INDUSTRY CABLES7
1 - ConductorsBare copper :
• Model 05 : 0.8 mm wire( cross-section area 0.5 mm2 )
• Model 09 : 7 x 0.4 mm wires( cross-section area 0.88 mm2 )
2 - InsulationSpecial PVC
3 - Individual screen ( if applicable )Aluminium / polyester tape withtinned copper ( 7 x 0.20 mm ) drainwire
4 - Sheath ( if applicable )PVC
5 - General screenAluminium / polyester tape withtinned copper drain wire ( 7 x 0.20 mm )
6 - Inner sheathPVC - HR
7 - SheathLead if aromatic hydrocarbons arepresent
8 - Armoursteel tapes or wires
9 - Outer sheathPVC - HRColour : Light blue
N.B.:Colours and other constructional detailscan be according to customer specialrequirements.IdentificationAccording to customer requirements
Sheath marking- Name of manufacturer- Size
- Metric marking- Other : as per customer requirements
CONSTRUCTION
7.2 - INSTRUMENTATION CABLES
- 300 / 500 V, Lead sheathed,
Steel tape armoured
APPLICATION- NFM 87 - 202 instrumentation cables are used in the oil industryto transmit d.c. ora.c. analog signals.
ACCORDING TO :NF M 87 - 202Maximum conductortemperature : 70
oC
12
3
4
5
6
7
8
9
27
01 IP09 EGSFEGPFEGFA
03 IP05 EGSFEGPFEGFAEISFEIPFEIFA
07 IP05 EGSFEGPFEGFAEISFEIPFEIFA
12 IP05 EGSFEGPFEGFAEISFEIPFEIFA
19 IP05 EGSFEGPFEGFAEISFEIPFEIFA
713.110.9
8.614.812.613.620.417.9
11.117.615.41825.322.5
1420.318.524.432.129.3
16.823.721.328.536.833.6
70530205
110710270280
1 140550
165950380420
1 735740
2601 270
520700
2 5401 140
3751 150
6801 0503 4701 590
27 IP05 EGSFEGPFEGFAEISFEIPFEIFA
01 IT09 EGSFEGPFEGFA
07 IT05 EGSFEGPFEGFAEISFEIPFEIFA
12 IT05 EGSFEGPFEGFAEISFEIPFEIFA
01 IQ 09 EGSFEGPFEGFA
19.326.62434.543.239.8
7.413.511.3
12.819.517.119.526.824.2
1622.920.525.533.630.4
7.91411.8
5151960880
1 4104 6802 110
80570225
2301 130
480490
1 880830
3801 690
695780
2 8501 250
100610240
Technical DataNF M 87 - 202
TYPE
NominalOuterdiam
( mm )
Weightapprox.
(Kg/Km)TYPE
NominalOuterdiam
( mm )
Weightapprox.
(Kg/Km)
LETTER - DIGIT CODING EXPLANATION1st series = number of pairs, triples or quads : 01 to 272nd series = as pair (IP), as triple (IT) as quad (IQ)3rd series = core 05 or 094th series = general screen (EG), individual screen + general screen (EI)5th series = mechanical protection : without armour (SF), with armour (FA), with lead +
armour (PF)
other sizes and constructions are also available
PETROCHEMICAL INDUSTRY CABLESINSTRUMENTATION CABLES
300 / 500 V, LEAD SHEATHED, STEEL TAPE ARMOURED
28
CONTROL, TRAFFIC AND DATA CABLES8
Maximum conductortemperature : 105oC
Technical data forconductors
Identification of coresAccording to customers requirements.
0.22
0.34
0.50
0.75
1.00
1.50
24
22
7 x 0.20
7 x 0.25
16 x 0.20
24 x 0.20
32 x 0.20
32 x 0.25
87.2
55.8
39.0
26.0
19.5
13.3
110
125
140
160
180
180
Cross-section area(mm2)
Capacitancebetween cores
(nF/km)
Numberand∅ of wires (mm)
Electricalresistance
(Ω/km)
Equivalence sizeAWG
COMMON GENERAL CHARACTERISTICS
APPLICATIONControl, Traffic and Data cables are designed for all control links : connection ofremote control, data processing, electronic, remote monitoring, telemetry, robot andautomation equipment.These cables are also suitable for home computing requirements.
N.B.:Different specification can be offered on special request
CONTROL, TRAFFIC AND DATA CABLES8
1 - ConductorsStranded, bare copper
2 - InsulationPVC TI 2according to NF C 32 201
3 - TapePolyester
4 - ScreenAluminium / Polyester tape or coppertape
5 - SheathPVC TM 2according to NF C 32 201
N.B.:Colours and other constructional detailscan be according to customer specialrequirements.Core IdentificationBy colour coding or numberingMinimum Bending radius6 x outer diameter
CONSTRUCTION
8.1 - 300 / 500 V MULTICORES OVERALL SCREENED CABLES
- Maximum conductortemperature : 70o C
1
2
34
5
29
354045556090
120155185210
4045556075
115155215
4555657090
135185270295365
60658095
115180265400470515
708095
110140225340495575645
80100120140175
4.74.95.25.55.97.38.39.7
10.310.9
5.05.25.65.96.37.99.0
10.8
5.35.55.96.36.88.59.8
12.012.713.6
5.96.26.67.17.79.8
11.514.415.616.2
6.36.67.17.78.3
10.813.115.717.418.0
6.77.07.68.28.9
2 x 0.223 x 0.224 x 0.225 x 0.227 x 0.22
12 x 0.2219 x 0.2225 x 0.2230 x 0.2237 x 0.22
2 x 0.343 x 0.344 x 0.345 x 0.347 x 0.34
12 x 0.3419 x 0.3427 x 0.34
2 x 0.503 x 0.504 x 0.505 x 0.507 x 0.50
12 x 0.5019 x 0.5027 x 0.5032 x 0.5037 x 0.50
2 x 0.753 x 0.754 x 0.755 x 0.757 x 0.75
12 x 0.7519 x 0.7527 x 0.7532 x 0.7537 x 0.75
2 x 1.03 x 1.04 x 1.05 x 1.07 x 1.0
12 x 1.019 x 1.024 x 1.032 x 1.037 x 1.0
2 x 1.53 x 1.54 x 1.55 x 1.57 x 1.5
Technical Data
Specifications can change according to customer requirements.
Cables(mm2)
Weight approx.(kg/km)
Outerdiametermax. (mm)
other sizes are also available
CONTROL, TRAFFIC AND DATA CABLES
30
CONTROL, TRAFFIC AND DATA CABLES8
1 - ConductorsStranded, bare copper
2 - InsulationPVC TI 2according to NF C 32 201
3 - TapePolyester (optional)
4 - General ScreenDrain copper wire 0.22mm2
Aluminium / Polyester tape or coppertape
5 - SheathPCV TM 2according to NF C 32 201
N.B.:Colours and other constructional detailscan be according to customer specialrequirements.Core IdentificationBy colour codingMinimum Bending radius6 x outer diameter
CONSTRUCTION
8.2 - 300 / 500 V MULTIPAIRS, OVERALL SCREENED CABLES
- Maximum conductortemperature : 70o C
1
3
2
4
5
31
2 P0.22
3 P0.22
4 P0.22
5 P0.22
7 P0.22
12 P0.22
15 P0.22
20 P0.22
6.7
7.1
7.6
8.3
9.0
11.3
12.8
14.7
70
80
90
100
120
180
230
295
2 P0.343 P0.344 P0.34
2 P0.503 P0.504 P0.50
2 P0.753 P0.754 P0.75
7.37.78.3
7.88.29.0
9.09.4
10.6
8595
105
95110125
120140180
Technical Data
Specifications can change according to customer requirements.
Cables(mm2)
Cables(mm2)
Outerdiameter
max. (mm)
Weightapprox.(kg/km)
Weightapprox.(kg/km)
Outerdiameter
max. (mm)
other sizes are also available
32
CONTROL, TRAFFIC AND DATA CABLES8
1 - ConductorsStranded, bare copper
2 - InsulationPVC TI 2according to NF C 32 201
3 - PairingWrapped with polyester tape(optional)
4 - Individual screenAluminium / Polyester tape
5 - TapePolyester (optional)
6 - SheathPCV TM 2according to NF C 32 201
N.B.:Colours and other constructional detailscan be according to customer specialrequirements.PairidentificationBy colour codingMinimum Bendius radius6 x outer diameter
CONSTRUCTION
8.3 - 300 / 500 V MULTIPAIRS, INDIVIDUALLY SCREENED CABLES
- Maximum conductortemperature : 70o C
1
3 2
4
5
6
33
75
90
127
85
105
100
125
130
165
7.3
7.8
9.4
7.9
8.4
8.5
9.0
9.6
10.2
2 P0.22
3 P0.22
5 P0.22
2 P0.34
3 P0.34
2 P0.50
3 P0.50
2 P0.75
3 P0.75
Technical Data
Specifications can change according to customer requirements.
Cables(mm2)
Weight approx.(kg/km)
Outerdiametermax. (mm)
other sizes are also available
34
1 - ConductorBare copper :• stranded-class 2NF C 32-013 / IEC 228
2 - InsulationXLPE
3 - Inner sheathHalogen free compound
4 - ScreenCopper tape (s)
5 - OutersheathHalogen free compoundcolour : black
N.B.:Colours and other constructional detailscan be according to customer specialrequirements.
Sheath marking- Name of manufacturer- metric marking- number of cores / cross sectional area (mm2)- Other : as per customer requirements
CONSTRUCTION
ACCORDING TO :DIMENSIONS : IEC 502NF C 32-070 - Tests no1 and 2IEC 332-3Maximum conductortemperature : 90o C
9.1 - Powerand Signalling Cable- Screened- Fire retardant- Halogen free, Low smoke
SUBSTATION & PILOT CABLES9
1
2
3
4
5
35
Technical Data
Specifications can change according to customer requirements
2 x 1.53 x 1.54 x 1.55 x 1.57 x 1.512 x 1.519 x 1.527 x 1.537 x 1.5
2 x 2.53 x 2.54 x 2.55 x 2.57 x 2.512 x 2.519 x 2.527 x 2.537 x 2.5
2 x 43 x 44 x 45 x 47 x 4
2 x 63 x 64 x 65 x 67 x 6
2 x 103 x 104 x 105 x 10
2 x 163 x 164 x 165 x 16
2 x 253 x 254 x 255 x 25
3 x 25 + 163 x 35 + 253 x 50 + 353 x 70 + 503 x 95 + 50
11.011.512.013.014.017.520.023.526.0
12.012.513.014.015.019.022.026.029.5
13.013.514.515.517.0
13.514.015.516.518.0
15.016.017.519.0
17.518.520.022.0
20.522.024.026.5
23.026.029.033.537.0
13.013.514.515.516.020.523.027.030.0
14.014.515.516.517.522.025.530.033.5
15.015.517.018.019.5
16.016.518.019.521.0
17.518.520.022.0
20.021.523.025.0
24.025.528.030.5
27.030.033.538.542.5
105110120125130170190220240
115120125135140180205240270
120125140150160
130135150160170
140150160180
160175185200
190205230250
220240270310340
22025028032037058077010601320
265300340390470750102014201810
330370440500620
390450540630790
520630760890
72088010701270
1040130015901910
14701950256035304460
Cables (mm2)Outerdiam. Min. bending
radius(mm)➀
Weightapprox.(kg/km)Min.
(mm)Max.(mm)
36
1 - ConductorSolid bare copper :diam. 6 /10 mm or 9/10 mm
2 - InsulationStranding :Pairs or star quads
3 - Screen• Polyester - aluminium tape• Copper continuity wire, diam.5 / 10 mm
4 - InnersheathSpecial PVC
5 - Screencopper tape
6 - OutersheathSpecial PVCColour : black
N.B.:Colours and other constructional detailscan be according to customer specialrequirements.
ApplicationThese cables are designed for control ortelecommunication cable networkswhich must be protected againstelectromagnetic disturbances, inparticular in high voltage transformerequipment.
CONSTRUCTION
ACCORDING TO :HN 33-S-4 (for screen and sheath)NF C 32-070 - Tests no1 and 2Maximum conductor temperature :70o C
9.2 - Control and Telecommunicationscreened cables
- Fire retardant
SUBSTATION & PILOT CABLES9
1
2
3
4
5
6
37
350
500
770
1 240
2 140
16.0
18.8
24.0
29.4
40.0
7 q 6 / 10 mm
14 q 6 / 10 mm
28 q 6 / 10 mm
56 q 6 / 10 mm
112 q 6 / 10 mm
Cables(mm2)
Weightapprox.(kg/km)
Max. diam.(mm)
q = quads• Other sizes are also available
Identification of coresAccording to customers requirements.
CONTROL AND TELECOMUNICATIONSCREENED CABLES
38
1 - ConductorStranded bare or tinned copper Class2 or class 5Cross sectional area : 2.5, 4 or 6 mm2
NF C 32-013IEC 228
2 - InsulationXLPE
3 - Sheath (optional)XLPE, PE or PVC
1 - ConductorsStranded bare or tinned copperCross sectional area : 6 or 8 mm2 or 8AWG
2 - Semi-conductive layerExtruded or tape
3 - InsulationXLPE
4 - ScreenSemi-conductive layer (extruded ortape) and copper tape (s)
5 - SheathXLPE, PE or PVC
CONSTRUCTION (Unless differently required)
CONSTRUCTION (Unless differently required)
Medium voltage cables up to 6 KV
Low voltage cables1 or 2 coresLow voltage : 1 KVor less, as per customer requirements.
AIRFIELD LIGHTING CABLES10
Application
These cables are used in airfield lighting systems :• primary cables in medium voltage transformer circuits (series circuits)• secondary cables in low voltage for lighting fixtures
Design on request according to :France : STNA, ADPstandardsUSA: FAA-L824. Type A, B ou C standards.Or others specifications or standards, as per customer requirements.
1
2
3
4
5
1
2
3
39
1 - ConductorBare copper :Flexible-class 5IEC 228
2 - InsulationPVC
3 - OutersheathSpecial PVCcolour : black
N.B.:Colours and other constructional detailscan be according to customer specialrequirements.
Core IdentificationAccording to customer requirementsusually as follows :cables < 6 cores : color codecables > 5 cores : printed numbersgreen / yellow core also available
Sheath marking- Name of manufacturer- Metric marking- Size- Other : as per customer requirements
These cables are in accordance withCENELEC harmonization document HD359 / VDE 0281 / BS 6977 / CEI 20 - 25 /NF C 32 - 202 /SR C 36 / NEN 3623 / UNE 21 153
ApplicationThese cables are used for festoons,trolleys, overhead cranes inside oroutside.
CONSTRUCTION
CENELEC HD 359 S9IEC 227 Part 6Maximum conductortemperature : 70o C
11.1 450 / 750 V Flat cables
HANDLING & LIFT CABLES11
1
3
2
40
4 G 1.5
4 G 2.5
4 G 4
4 G 6
4 G 10
4 G 16
4 G 25
4 G 35
4 G 50
4 G 70
4 G 95
5 G 1.5
5 G 2.5
7 G 1.5
7 G 2.5
7 G 4
8 G 1.5
8 G 2.5
9 G 1.5
10 G 1.5
12 G 1.5
12 G 2.5
12 G 4
16 G 1.5
18 G 1.5
15 x 5
18.5 x 5.7
21 x 6.5
23 x 7
28.8 x 9
36.8 x 10.8
45.5 x 13.5
50.5 x 14.8
56 x 16.5
63 x 18
72.5 x 20.5
18 x 5
22 x 5.7
26 x 5
32.3 x 5.7
40 x 6.8
29 x 5
34.5 x 5.7
32 x 5
35 x 5
40.5 x 5
50.5 x 5.7
57 x 6.8
53.5 x 5
58 x 5
20
27
36
48
63
85
112
138
168
213
258
18
25
15
20
25
14
20
12
12
11
16
20
10
8
20.2
12.3
7.8
5.3
3.2
2.0
1.3
0.97
0.74
0.55
0.42
20.2
12.3
20.2
12.3
7.8
20.2
12.3
20.2
20.2
20.2
12.3
7.8
20.2
20.2
40
45
55
65
75
80
100
120
130
140
200
40
45
40
45
55
40
45
40
40
40
45
55
40
40
150
210
300
385
620
990
1 550
2 030
2 650
3 650
4 550
180
260
260
380
550
300
405
330
360
420
620
880
560
620
Cables(mm2)
Bendingradius( mm )
Permissiblecurrent rating
(A) (1)
(cos ϕ = 0.8)Voltage drop(V/Ax km)
Overalldimensions
( mm )
Weightapprox.
(Kg/Km)
Technical Data
Specifications can change according to customer requirements
➀ Ambient temperature : 30oC• Other sizes are also available
450 / 750 V FLAT CABLES
41
1 - ConductorBare copper :Flexible-class 5IEC 228
2 - InsulationTPR(thermoplastic rubber)
3 - OutersheathTPRcolour : black
N.B.:Colours and other constructional detailscan be according to customer specialrequirements.
Core IdentificationAccording to customer requirementsfrom 6 cores : printed numbers with 1green / yellow core
Sheath marking- Name of manufacturer- Metric marking- Size- Other : as per customer requirements
Voltage testBetween conductors3500 V - 50 Hz
ApplicationThese cables are used for hoistingsystems, festoons, trolleys, overheadcranes, out doors with low temperature.
CONSTRUCTION
Maximum conductortemperature : 85o C
11.2 - 0.6 / 1 KV Thermoplastic rubber flat cables- Halogen free- Low smoke
HANDLING & LIFT CABLES11
1
3
2
42
4 G 1.5
4 G 2.5
4 G 4
4 G 6
4 G 10
4 G 16
4 G 25
4 G 35
4 G 50
4 G 70
8 G 1.5
8 G 2.5
12 G 1.5
12 G 2.5
16 x 5
19 x 5.7
21 x 6.5
23.5 x 7
29 x 9
35 x 10.4
45.5 x 13.5
50.5 x 14.8
56 x 16.5
63 x 18
29 x 5
35 x 5.7
41 x 5
51 x 5.7
22
30
40
52
70
95
127
157
190
242
16
25
12
20
22.1
13.3
8.3
5.5
3.3
2.1
1.3
0.97
0.74
0.55
22.1
13.3
22.1
13.3
50
55
65
70
90
105
135
150
165
180
50
55
50
55
110
170
250
330
550
800
1 350
1 800
2 400
3 250
220
330
320
490
Cables(mm2)
Bendingradius( mm )
Permissiblecurrent rating
(A)
(cos ϕ = 0.8)Voltage drop(V/Ax km)
Overalldimensions
( mm )
Weightapprox.
(Kg/Km)
Technical Data
Specifications can change according to customer requirements
➀ Ambient temperature : 30oC• Other sizes are also available
0.6 / 1 KV THERMOPLASTIC RUBBER FLAT CABLES
43
1 - ConductorBare copper :Flexible-class 5IEC 228
2 - InsulationSpecial PVC
3 - Outer sheathSpecial PVCcolour : black
N.B.:Colours and other constructional detailscan be according to customer specialrequirements.
Core IdentificationPrinted numbers with 1 yellow / greencore
Laying upIn parallel by group from 2 to 5 coreswith a striping thread in each group.
Sheath marking- Name of manufacturer- Metric marking- Size- Other : as per customer requirements
ApplicationThese cables are used as pendant liftcables where freely suspended lengthmust not exceed 45 meters and thetravelling speed must not exceed 4m/Sfor ambient temperature between -15
oC
to 40oC.
This standard allows to include 3telecomminication units in centralposition (copper pairs or quads screenedor unsceened, coaxial, optical fibers).
CONSTRUCTION
CENELEC HD 359 S3 Draft
Maximum conductortemperature : 70o C
11.3 - 300 / 500 V Flat lifts cables
HANDLING & LIFT CABLES11
1
3
2
44
12 G 0.75
16 G 0.75
18 G 0.75
20 G 0.75
24 G 0.75
12 G 1
16 G 1
18 G 1
20 G 1
24 G 1
29.4 x 3.7
38.8 x 3.7
43.3 x 3.7
48.3 x 3.7
57.7 x 3.7
31 x 3.9
41 x 3.9
48.8 x 3.9
51.1 x 3.9
61.1 x 3.9
34.5 x 4.5
45.5 x 4.5
51 x 4.5
57 x 4.5
68 x 4.5
36 x 4.6
47 x 4.6
51.7 x 4.5
59 x 4.6
70 x 4.6
6
5
5
4
4
8
7
6
6
6
280
360
400
440
520
320
420
470
500
610
Cables(mm2)
Permissiblecurrent rating
(A)➀
Weightapprox.
(Kg/Km)Min.( mm )
Max.( mm )
Technical Data
Specifications can change according to customer requirements
➀ Ambient temperature : 30oC• Other sizes are also available
Overall dimensions
300 / 500 V FLAT LIFT CABLES
45
1 - ConductorBare copper :Flexible-class 5IEC 228
2 - InsulationPVC
3 - OutershearthPVCcolour : black
4 - Strain bearing membersGalvanized steel
N.B.:Colours and other constructional detailscan be according to customer specialrequirements.
Core IdentificationPrinted numbers with 1 yellow / greencore
Laying upIn parallel by group from 2 to 5 coreswith a striping thread in each group.
Sheath marking- Name of manufacturer- Metric marking- Size- Other : as per customer requirements
They are in accordance with CENELECharmonization document HD 359 andvarious national standards (CEI 2025, BS6977, NF C 32-202, VDEO 281, UNE21153)
ApplicationWith strain bearing members, thesecables can be used for freely suspendedlength up to 120 meters and the travellingspeed must not exceed 1.6m/s.
CONSTRUCTION
CENELEC HD 359 S2
Maximum conductortemperature : 70o C
11.4 - 300 / 500 V Flat lifts cables
HANDLING & LIFT CABLES11
1
3
2
4
46
24 G 0.75
24 G 1
68.5 x 3.7
72.5 x 3.9
75 x 4.3
78.2 x 4.5
4
6
600
690
Cables(mm2)
Permissiblecurrent rating
(A)➀
Weightapprox.
(Kg/Km)Min.( mm )
Max.( mm )
Technical Data
Specifications can change according to customer requirements
➀ Ambient temperature : 30oC• Other sizes are also available
Overall dimensions
300 / 500 V FLAT LIFT CABLES
47
1 - ConductorBare or tinned copperFlexible-class 5NF C 32-013IEC 228
2 - InsulationThermoplasticrubber
3 - OutersheathThermoplasticrubbercolour : black
N.B.:Colours and other constructional detailscan be according to customer specialrequirements.
Marking- Name of manufacturer- Metric marking- Size- Other : as per customer requirements
ApplicationThese cables are designed forsubmersible power supply used intowater.
CONSTRUCTION
12.1 - 450 / 750 V Termoplastic rubber,
round orflat flexibe cable
SUBMERSIBLE PUMP CABLES12
ACCORDING TONF C 32-102HD 22.4 S2Water absorption tests:IEC 811.1.3VDE 0472 Teil 802NF C 32-026HD 505-1-3 s1Maximum conductor temperature : 90o C
1
3
2
CONSTRUCTION
48
12.514.516.020.025.529.534.038.044.0
13.515.518.022.028.032.037.542.048.5
CURRENT RATING GENERAL CONDITIONSThe following current data are indicated for continuousduty operation and apply to :
• Maximum conductor temperature• Industrial frequency• Free air ambient temperature
90oC50Hz30oC
3 G 1.53 G 2.53 G 43 G 63 G 103 G 163 G 253 G 353 G 50
4 G 1.54 G 2.54 G 44 G 64 G 104 G 164 G 254 G 354 G 50
2433455880
107142175212
223040527196
127157190
28.016.910.57.04.02.51.681.220.87
23.314.08.745.863.442.211.461.070.78
9.611.513.014.520.022.526.529.534.5
10.512.514.516.521.524.529.533.038.0
50606580
105120140155180
55657590
115130150170200
160220300410720
1010145019002580
195270380520900
1260185024003290
Cables (mm2)Permissible
current rating(A)
Voltage dropcos ϕ = 0.8(V/Ax km)
Outerdiam. Min. bendingradius(mm)➀
Weightapprox.(kg/km)Min.
(mm)Max.(mm)
G = with green / yellow core➀ Values to be doubled during laying operations• Other sizes are also available
450 / 750 V THERMOPLASTIC RUBBER ROUND FLEXIBLE CABLE
49
1 - ConductorFlexible bare copper class 5NF C 32-013IEC 228
2 - InsulationPolyethylen
3 - OutersheathPolyethylencolour : black
N.B.:Colours and other constructional detailscan be according to customer specialrequirements.(+ green / yellow conductor whenrequired)Sheath marking- Name of manufacturer- Metric marking- Size- Other : as per customer requirements
ApplicationSubmersible pump power supply cablesmust have excellent water tightness andvery good insulation. Polyethylen is thematerial that best meets theserequirements. The special PVC sheathimproves the cable flexibility comparedto a PE sheath. The designed materialsare suitable for use in drinking water.
Cables with food-grade flexible PVCsheath, can also be manufactured
Use ambient temperature :• in the water : up to 40oC• in the air : -20oC to + 60oC
Maximum use depth : up to 200 m.
CONSTRUCTION
Maximum conductortemperature : 70o C
12.2 - 0.6 / 1 K/V PE / PE Round Cables
SUBMERSIBLE PUMP CABLES12
1
3
2
50
11.012.513.214.516.618.823.526.530.035.040.044.0
11.613.014.015.518.022.026.529.533.0
3 x 1.53 x 2.53 x 43 x 63 x 103 x 163 x 253 x 353 x 503 x 703 x 953 x 120
4 G 1.54 G 2.54 G 44 G 64 G 104 G 164 G 254 G 354 G 50
17.5243241577696
119144184223259
17.5243241577696
119144
21.512.88.05.43.22.11.351.00.750.550.420.35
21.512.88.05.43.22.11.351.00.75
10.011.012.013.215.117.221.523.527.431.836.540.0
10.511.512.514.016.019.524.026.530.0
70758090
100115145160180210240260
70808595
110135160180200
130170220285430650
1 0201 3201 8102 6203 3204 200
150200270350540820
1 2901 6802 300
Cables (mm2)
Ambient temperature oC 5 10 15 20 25 30 35 40 45 50 55 60
Correction factors 1.27 1.22 1.17 1.12 1.06 1.00 0.94 0.87 0.79 0.71 0.61 0.50
Permissiblecurrent rating
(A)
Voltage dropcos ϕ = 0.8(V/Ax km)
Outerdiam. Min. bendingradius(mm)➀
Weightapprox.(kg/km)Min.
(mm)Max.(mm)
Also single core cables : on special requestG = with green / yellow core➀ Values to be doubled during laying operations• Other sizes are also available
CURRENT RATING GENERAL CONDITIONSThe following current data are indicated for continuousduty operation and apply to :
• Maximum conductor temperature• Industrial frequency• Free air ambient temperature
70oC50Hz30oC
Technical Data
PE / PE Round cables
Specifications can change according to customer requirements
0.6 / 1KV PE / PE ROUND CABLES
51
1 - ConductorFlexible bare copper class 5NF C 32-013IEC 228
2 - InsulationPolyethylen
3 - Outer shearthPolyethylencolour : black
N.B.:Colours and other constructional detailscan be according to customer specialrequirements.Core IdentificationAccording to customer requirements(+ green / yellow for 4 core cables).Laying upConductors are side by side and parallel.Sheath marking- Name of manufacturer- Metric marking- Size- Other : as per customer requirements
ApplicationSubmersible pump power supply cablesmust have excellent water tightness andvery good insulation. Polyethylen is thematerial that best meets theserequirements. The flat shape makes itpossible to obtain smaller overalldimensions and a tighter bending radius.The designed materials are suitable foruse in drinking water.
Cables with food grade flexible PVCsheath, can also be manufactured.Use ambient temperature :• in the water : up to 40oC• in the air : -20oC to + 60oCMaximum use depth : up to 200 m.
CONSTRUCTION
Maximum conductortemperature : 70o C
12.3 - 0.6 / 1 K/V PE / PE Flat Flexible Cables
SUBMERSIBLE PUMP CABLES12
1
3
2
52
3 x 1.53 x 2.53 x 43 x 63 x 103 x 163 x 253 x 353 x 503 x 70
4 G 1.54 G 2.54 G 44 G 64 G 104 G 164 G 254 G 354 G 50
17.5243241577696
119144184
17.5243241577696
119144
21.512.88.05.43.22.11.351.00.750.55
21.512.8
8.05.43.22.11.351.00.75
13.1 x 5.714.4 x 5.615.9 x 6.518.4 x 7.221.6 x 8.826.4 x 10.532.4 x 13.236.0 x 14.439.7 x 15.947.5 x 18.9
15.8 x 5.019.5 x 5.621.5 x 6.523.6 x 7.229.1 x 8.835.3 x 10.443.6 x 13.248.4 x 14.453.5 x 15.9
25253030404555606580
202530304045556065
90125180235390600920
1 2801 7202 460
115170240330530810
1 2201 7002 500
Cables (mm2)
Ambient temperature oC 5 10 15 20 25 30 35 40 45 50 55 60
Correction factors 1.27 1.22 1.17 1.12 1.06 1.00 0.94 0.87 0.79 0.71 0.61 0.50
Permissiblecurrent rating
(A)
Voltage dropcos ϕ = 0.8(V/Ax km)
Externalnominal
dimensions(mm)
Min. bendingradius(mm)➀
Weightapprox.(kg/km)
G = with green / yellow core➀ Values to be doubled during laying operations• Other sizes are also available
CURRENT RATING GENERAL CONDITIONSThe following current data are indicated for continuousduty operation and apply to :
• Maximum conductor temperature• Industrial frequency• Free air ambient temperature
70oC50Hz30oC
Technical Data
PE / PE Flat cables
Specifications can change according to customer requirements
0.6 / 1 KV PE / PE FLAT FLEXIBLE CABLE
53