Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers,...

29
Soft- Starters Drives A new product for OEM’s, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

Transcript of Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers,...

Page 1: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

Soft-Starters

Drives

A new product forOEM’s,

End Users, Panel Shops,

Facilities Engineers,Maintenance Personnel,

MRO Accounts …

High Speed J (HSJ)

Page 2: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

2

Electronic Motor Control

Industrial Power Consumption

Motors75%

Lighting15%

Std Outlet usage10%

With many motors in use, industry trend leads to energy savings and increased reliability.

Page 3: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

3

By-pass at Start

0

200

400

600

800

1000

0 20 40 60 80 100

% of Motor RPM

% o

f FL

A

Electro Mechanical Starter

Soft-Starter

Drive

Changing Trends in Electronic Motor Control

Page 4: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

4

Changing Trends in Electronic Motor Control

Sales Unit Trends

-10

10

30

50

1 2 3 4

Years (Current - Past)

Perc

ent Electronic

Controllers

MechanicalStarters

Market for Electronic Controllersis steadily growing

Page 5: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

5

Leaders of Electronic Motor Controllers

Allen Bradley

ABB

Cutler Hammer

Square D

GE Danfoss

Toshiba

Hitachi

AC Tech

Yaskawa

Page 6: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

6

Cost reduction of Electronic Motor Control

Manufacturers remove high speed fuse (Semiconductor fuse) from medium to low power Drives/Soft-starters (200HP and below)

Manufacturers suggest controller protection to comply with NEC using Circuit Breaker or UL listed fuses.

Manufacturers justify removal of high speed fuse by arguing their system is self protected (IGBT).

Page 7: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

7

Preventing AC Drive failure and collateral damage

Over-current protection comparison

Drives’ failures cause analyses

Introduction of a new fuse for drives

Page 8: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

8

• Rectifier converting AC to DC

• DC Filter/Bus storing energy to be used as output power.

• Inverter (IGBT) converting DC to AC to feed motor.

Preventing AC Drive failure and collateral damage

AC drives are broken down to 3 operational blocks

Page 9: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

9

Preventing AC Drive failure and collateral damage

Description of most dominant failure of AC Drives

Over-voltage condition caused by high switching frequencies will cause the drive to fail. These transient over-voltages can be caused by high switching frequencies of drives themselves, by inductive switching within a facility, from poor power quality, or by mother nature (lightning).

A Transient voltage higher than the IGBT max voltage rating will irreversibly damage the IGBT and eliminate its self-protection characteristics. In this condition the drive cannot shut down on its own.

Page 10: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

10

Preventing AC Drive failure and collateral damage

IGBT Module section

The IGBT is not a “fail-safe” component, i.e. if it fails (avalanche mode) it will leave the circuit in short circuit condition and allow the DC link capacitor bank to quickly discharge through the shorted IGBT.

High fault current will lead to the melting of the bonding wire and cause the IGBT case to rupture.

This case rupture will certainly ruin the drive and surrounding components.

Only a high speed fuse can prevent this case rupture.

Page 11: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

11

Preventing AC Drive failure and collateral damage

DC Capacitor / Filter Section

Capacitors can be damaged from a shorted IGBT or when the internal dielectric can no longer withstand the applied voltage and breaks down. The result is a low impedance current path generating excessive heat and pressure that can cause violent case rupture.

The amount of physical damage is relative to the amount of energy stored and how fast the capacitor is charged or discharged.

Only a high speed fuse on the AC line side can limit the potential damage.

Page 12: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

12

F1

DC

F3

+

-

5

2 4 6

31

F2

ACSupply

a

b

c

Id

0.577Id

0.816Id

Preventing AC Drive failure and collateral damage

Rectifier section

The rectifier section of an AC drive is built with either diodes or SCR’s. Rectifiers have a good withstand to transient over-voltage but are very susceptible to over-current (short circuits).

In the event of an internal fault condition due to a faulty components within the AC drive, the rectifier will be subject to damaging current levels.

Only a high speed fuse will protect the rectifier section.

Page 13: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

13

Preventing AC Drive failure and collateral damage

Description of most dominant failure of AC Drives

During a short circuit fault, only a high speed fuse will limit the amount of energy rushing into the drive and isolate the damage at the component level.

Using a high speed fuse protects components and equipment from a violent rupture if a short circuit occurs. The end user will only need to swap drives facilitating maintenance and reducing down time. The failed drives could be repaired.

A high speed fuse lowers the possibility of personal injury from conditions such as arc flash.

Page 14: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

14

I2t comparison 200A fuse

Class T Class J RK5 Semi-F 150kA2s 300kA2s 1600kA2s 78kA2s

Fast acting / no time delayClass T

Class J Fast acting or time delay

Class R Fast acting or time delay

Semiconductor Ultra rapid / high speed

Typical fuse protection suggested by manufacturers

Preventing AC Drive failure and collateral damage

Page 15: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

15

0

2

4

6

8

Circuit Breaker

Traditional Branch Fuse

High Speed Fuse

Let

-Th

rou

gh

Cu

rre

nt

Time

Preventing AC Drive failure and collateral damage

Over-current protection comparison

For the same fault condition, the traditional branch circuit protection devices, such as circuit breakers and fuses (Class T, J, RK…) are restricted in their capability to limit the amount of thermal energy.

They will not protect the input rectifier, eliminate capacitor rupture or isolate a faulty IGBT.

Page 16: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

16

Electro Mechanical start showing the fuse inrush withstanding requirement. UL Listed Class J (TD)

Electro Mechanical Starter 20A

FLA

Inrush

Preventing AC Drive failure and collateral damage

Over-current protection comparison

Page 17: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

17

High speed semiconductor fuses do not provide overload protection and do not withstand inrush current.

Over-Load

Inrush

Preventing AC Drive failure and collateral damage

Over-current protection comparison

Page 18: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

18

FLA

Inrush

Class J TD provides high inrush capability that is unnecessary for Drives& Soft-Starters

With an electronic motor control, the inrush current has significantly decreased.

Preventing AC Drive failure and collateral damage

Over-current protection comparison

Page 19: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

19

Introduction of a new fuse for drives & soft starters.

Class J

High Speed

+ =

High Speed Class J (HSJ)

The Solution

Page 20: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

20

Starting characteristic of Drive

The HSJ Solution

A new fuse for drives

The HSJ fuse line has melting curves that mirror the starting parameters of drives and also provides energy limitation to protect sensitive power electronics.Inrush requirements………..– AC Drives: 200% FLA for 60 sec – (every 5 min for 1 hour)– Soft-Starters: 450% FLA for 15

sec – (every 10 min for 10 times per

day)

Page 21: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

21

Let

-Th

rou

gh

Cu

rren

t

Time

The HSJ can provide short-circuit protection comparable to semiconductor fuses.

The HSJ Solution

HSJ has lower let-through current

Page 22: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

22

The HSJ Solution

High-speed performance protects sensitive power semiconductors

Complies with NEC requirements for branch circuit protection

Page 23: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

23

Features and Benefits

UL listed to 248-8

UL Class J dimension

CSA certified to C22.2

600VAC/500VDC

15A to 600A

200kA interrupting rating

Very low I2t

Easily coordinated with drives and soft starters

The HSJ Solution

Page 24: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

24

Protection Method

Circuit Breaker(UL Listed)

Class J, T, RK1RK5 Fuse (UL Listed)

Semiconductor Fuse(UL Rec)

NEW HSJ(UL Listed)

Code BranchCircuit

Protection

Drive orSoft-Starter

Protection

Limitations of Traditional Circuit Protection

Circuit breakers will provide NEC code compliance, but no high-speed protection for internal power electronicsUsing older UL listed fuses will meet NEC code compliance, but will provide limited protection to internal power electronicsSemiconductor fuses alone provide high-speed protection for internal electronics, however - although UL component recognized, they are not UL listed class fuses and will not provide NEC code compliance.

Preventing AC Drive failure and collateral damage

Page 25: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

25

The New HSJ “Hybrid” Approach

Mersen HSJ & fused switch combination

The best fault protection and code compliance available.

Superior cost-effective solution to inadequate circuit breakers.

Competition has fast-acting Class J but with 60-70% Higher I2t than Mersen HSJ.

Page 26: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

26

Rule of thumb to size the HSJ

Based on FLA

– For drives with IGBT

• 1.3 to 1.5 times FLA

– For soft starters (diodes or SCR’s

• 1.5 to 2 times FLA

OR

Based on Max I for 60 Sec.• 1.1 times I for normal duty• 1.5 times I for heavy duty

Page 27: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

27

Application notes/alerts

Two considerations to know about the by-pass option

It is important to understand typical options provided with electronic motor controllers. The option that most directly effects the fuse selection is the “Bypass Option.”

– by-pass electronic controller at start-up– by-pass electronic controller during operation

Page 28: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

28

vBypass at start-up

Bypass during operation

The HSJ is not suited for bypass electronic controller

at start-up operation.

The HSJ is very well suited for bypass electronic controller

during operation after the equipment is started and

operating at full load current.

Application notes/alerts

Page 29: Soft-Starters Drives A new product for OEMs, End Users, Panel Shops, Facilities Engineers, Maintenance Personnel, MRO Accounts … High Speed J (HSJ)

29

To learn more…

The HSJ provides the performance needed for today’s electronic motor controllers. A clear understanding of the motor controller is key to selling the benefits of the HSJ.

For more information about our new line of High Speed J products visit www.us-ferrazshawmut.mersen.com, contact your Mersen representative, or call us today at 978-462-6662.