SMOKEX® EMERGENCY SMOKE EXTRACT · 2015. 8. 26. · ment for the extraction of fire smoke. They...
Transcript of SMOKEX® EMERGENCY SMOKE EXTRACT · 2015. 8. 26. · ment for the extraction of fire smoke. They...
-
AIR VENTT E C H N O L O G Y
SMOKEX®
EMERGENCY
SMOKE
EXTRACT
C E certified to Class F300/120 or F400
-
Tel: 01264 356415 Fax: 01264 337854
Email: [email protected] Web: www.airventtechnology.co.uk
Page 2
JTCHT SMOKEX®
Centrifugal induction fans for car park ventilation
F300/120
Pages 6-7
CAHT SMOKEX® High efficiency duct axial fans
F300/120 - F400
Pages 8-14
LCAHT SMOKEX®
High performance duct axial fans
F300/120 - F400
Page 15
CRHHT SMOKEX® Centrifugal roof fans
F400
Pages 16-18
CRHT SMOKEX® Vertical discharge centrifugal roof fans
F400
Pages 19-22
PRQ/HT SMOKEX®
Backward curved centrifugal fans
F400
Pages 23-26
CBBHT SMOKEX® Belt driven double inlet box fans
F400
Pages 27-30
Car Park Ventilation - Principles and Solutions Pages 31-33
Accessories Pages 34-39
SMOKEX®Emergency Smoke ExtractIndex
LCA-JT/HT SMOKEX® Axial impulse fans for car park ventilation
F300/120 - F400
Pages 4-5
-
Tel: 01264 356415 Fax: 01264 337854
Email: [email protected] Web: www.airventtechnology.co.uk
Page 3
IntroductionThe mechanical ventilation systems
shown in this catalogue resolve the prob-
lems connected to smoke extraction at
high temperature and are the ideal solu-
tion for emergency extraction in case of
fire.
Potential Risks in Fire Situation• release of gas and toxic substances
causing eyes to water and conse-
quent difficulty in escaping
• ashes can be suspended in the atmos-
phere leading to reduced or no visi-
bility
• development of very high tempera-
tures
• the increase of carbon monoxide and
reduction of oxygen in the air (possi-
bly leading to asphyxiation)
Function and Advantages of
Mechanical Ventilation in
Case of Fire
1. Mechanical ventilation removes
smoke and fumes produced by a fire
and by creating negative pressure (in
the ambient) it prevents smoke
spreading into other parts of the
building. This makes it easier for
people to escape and simplifies the
job of the fire and rescue services.
2. In enclosed areas, temperatures can
easily exceed 1000° C, causing com-
bustion from heat radiation and mak
ing any external extinguishing opera
tion useless. Keeping the tempera
ture relatively low (300°- 400° C) by
extracting hot air, can avoid the col-
lapse of support structures. In addi-
tion, the higher oxygen levels will
cause better combustion and thus,
for most materials, a lower produc-
tion of toxic smoke.
3. Mechanical ventilation allows the sit-
ing of the exhaust outlets away from
the fire. High temperature axial fans
are easily connected to a duct sys-
tem.
4. Mechanical ventilation allows the ex-
traction of cold fumes, which since
they remain at a lower level are dan-
gerous and are difficult to remove
using static systems.
5. Mechanical ventilation allows for ven-
tilation in normal circumstances
(clean air), using products with two
speed motors: at low speed for nor-
mal ventilation (so with lower noise
level) and at high speed for emer-
gency conditions. For this type of op-
eration, it is necessary to install the
fan with a dedicated power line that
automatically operates in case of fire.
CertificationEmergency Smoke Extract fan design and
installation is regulated by the European
standard EN12101-3, which establishes
the temperature ranges/operation time
certified products must comply with.
The SMOKEX® range is CE certified
to classes F300 and F400 and guaranteed
to operate at 300°C for two hours in
compliance with EN12101-3 standard by
the Applus laboratories in Barcelona.
SMOKEX®Emergency Smoke ExtractPrinciples and Solutions
-
Tel: 01264 356415 Fax: 01264 337854
Email: [email protected] Web: www.airventtechnology.co.uk
Page 27
Description
The belt driven double inlet CBBHT fansare designed for installation into indus-trial buildings where there is a require-ment for the extraction of fire smoke.
They are suitable for continu-ous operation in clean air andnon dusty smoke to a maxi-
mum temperature of +200°C. Inemergency smoke extract situa-tions the range will operate at+400°C for 120 minutes and is CEcertified to F400 in compliancewith EN12101-3 by the Applus lab-oratories in Barcelona.
Construction• Dismountable cabinet in galvanized
steel sheet. Double inlet impeller
with forward curved blades in galva-
nized steel sheet.
• Belt coupling with self aligning sup-
ports, outside the airflow. Height ad-
justable motor support plate for the
tensioning of the belt. Belt coupling
protected by a guard in galvanized
sheet.
Motor• Asynchronous three-phase motor, IP55 mechanical protection, insula tion class F, single or double polarity, suitable for S1 service, mounting type B3, construction according to IEC/EEC (UNEL MEC).• Arrangement 9: belt coupling with motor placed on the upper panel.• Arrangement 12: belt coupling with motor placed aside on a common base plate (only for motors above 7.5kW).
Also available• Model with 2 Pole motor
Model A B H C D E ØF G I L M QKg
min max
CBBHT 250 650 600 600 300 300 158 405 100 370 230 300 350 75-90
CBBHT 300 730 700 680 350 350 173 500 100 425 255 340 410 100-135
CBBHT 350 860 800 750 400 400 173 610 100 470 280 375 410 145-270
CBBHT 400 1030 900 840 450 450 173 650 100 535 305 420 420 210-330
CBBHT 450 1200 1000 960 500 500 173 750 100 630 330 480 420 250-500
CBBHT 500 1250 1200 1020 600 600 173 800 100 640 380 510 420 310-590
Dimensions (mm)
F400
SMOKEX®Belt driven double inlet box fansCBBHT
-
Tel: 01264 356415 Fax: 01264 337854
Email: [email protected] Web: www.airventtechnology.co.uk
Page 28
Technical DataFrequency 50Hz: Air temperature 15°C: Barometric pressure 760 mm Hg: Air specific weight 1.22 Kg/m3
Lp: sound pressure level measured at 1.5 m
Model No PhaseSpeed
rpm
Power
kW
In
Ampsm3/hr IP/CL
Mot
(Gr)
Lp
dB(A)
CBBHT 254/A T 1800 2.20 4.90 5700 55/F 100 66
CBBHT 254/B T 1600 1.50 3.45 5050 55/F 90 64
CBBHT 254/C T 1400 1.10 2.64 4300 55/F 90 61
CBBHT 254/D T 1200 0.75 1.93 3700 55/F 80 57
CBBHT 254/E T 1000 0.37 1.11 3150 55/F 71 53
Model No PhaseSpeed
rpm
Power
kW
In
Ampsm3/hr IP/CL
Mot
(Gr)
Lp
dB(A)
CBBHT 304/A T 1800 5.50 11.0 9700 55/F 132 72
CBBHT 304/B T 1600 4.00 8.26 8700 55/F 112 69
CBBHT 304/C T 1400 3.00 6.47 7400 55/F 100 67
CBBHT 304/D T 1200 2.20 4.90 6300 55/F 100 63
CBBHT 304/E T 1000 1.10 2.64 5300 55/F 90 59
SMOKEX®Belt driven double inlet box fansCBBHT
-
Tel: 01264 356415 Fax: 01264 337854
Email: [email protected] Web: www.airventtechnology.co.uk
Page 29
Technical DataFrequency 50Hz: Air temperature 15°C: Barometric pressure 760 mm Hg: Air specific weight 1.22 Kg/m3
Lp: sound pressure level measured at 1.5 m
Model No PhaseSpeed
rpm
Power
kW
In
Ampsm3/hr IP/CL
Mot
(Gr)
Lp
dB(A)
CBBHT 354/A T 1600 11.00 21.30 13600 55/F 160 74
CBBHT 354/B T 1400 5.50 11.00 12000 55/F 132 71
CBBHT 354/C T 1200 4.00 8.26 10100 55/F 112 68
CBBHT 354/D T 1000 2.20 4.90 8250 55/F 100 64
CBBHT 354/E T 800 1.10 2.64 6800 55/F 90 59
Model No PhaseSpeed
rpm
Power
kW
In
Ampsm3/hr IP/CL
Mot
(Gr)
Lp
dB(A)
CBBHT 404/A T 1400 11.00 21.30 18200 55/F 160 74
CBBHT 404/B T 1200 7.50 14.60 16000 55/F 132 72
CBBHT 404/C T 1000 4.00 8.26 13000 55/F 112 68
CBBHT 404/D T 800 2.20 4.90 10100 55/F 100 63
SMOKEX®Belt driven double inlet box fansCBBHT
-
Tel: 01264 356415 Fax: 01264 337854
Email: [email protected] Web: www.airventtechnology.co.uk
Page 30
Technical DataFrequency 50Hz: Air temperature 15°C: Barometric pressure 760 mm Hg: Air specific weight 1.22 Kg/m3
Lp: sound pressure level measured at 1.5 m
Model No PhaseSpeed
rpm
Power
kW
In
Ampsm3/hr IP/CL
Mot
(Gr)
Lp
dB(A)
CBBHT 454/A T 1400 22.00 38.80 25500 55/F 180 74
CBBHT 454/B T 1200 15.00 27.70 22000 55/F 160 72
CBBHT 454/C T 1000 7.50 14.60 18000 55/F 132 68
CBBHT 454/D T 800 4.00 8.26 14500 55/F 112 63
CBBHT 454/E T 600 1.50 3.45 11000 55/F 90 60
Model No PhaseSpeed
rpm
Power
kW
In
Ampsm3/hr IP/CL
Mot
(Gr)
Lp
dB(A)
CBBHT 504/A T 1400 30.00 53.00 35000 55/F 225 82
CBBHT 504/B T 1200 22.00 38.80 30000 55/F 180 78
CBBHT 504/C T 1000 15.00 27.70 25000 55/F 160 74
CBBHT 504/D T 800 7.50 14.60 20000 55/F 132 70
CBBHT 504/E T 600 3.00 6.47 15000 55/F 100 64
SMOKEX®Belt driven double inlet box fansCBBHT
-
Air Vent Technology reserves the right to alter specifications as part of its policy of continuous development Aug2015/ESE/02© E & O.E
AIR VENT TECHNOLOGY LTD 56 Reith WayPortway Industrial EstateAndoverHampshire SP10 3TY
Tel: +44(0)1264 356415 Fax: +44(0)1264 337854 Email: [email protected] Web: www.airventtechnology.co.uk Part of the Vectaire Group of Companies
Certificate No: GB9455