SMDB-F34EPROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE:OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB - F34ELOCATION: ELECT. ROOM34TH FLOORSR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP10035FIRE PROOF4C 701C 3524.123.4523.270.75(N/A)OUTGOING1BOOSTER WAT. PTP2035XLPE /SWA/PVC4C 41C 41.001.001.003.004P ELCB 100 mA2DB - RETP4035XLPE /SWA/PVC4C 101C 102.602.952.708.253LIFT - 1TP16035FIRE PROOF4C 701C 3512.0012.0012.0036.004P ELCB 300 mA4LIFT - 1 CONTROLSP2035FIRE PROOF2C 41C 41.00--1.00DP ELCB 100 mA5SEF - 1TP2035FIRE PROOF4C 41C 41.001.001.003.004P ELCB 100 mA6SPF - 1TP3235FIRE PROOF4C 61C 63.003.003.009.004P ELCB 100 mA7SPF - 2TP2035FIRE PROOF4C 41C 42.502.502.507.504P ELCB 100 mA8SPARETP20351.001.001.003.00SMDB- F34E CONNECTED TO: MDB - ETOTAL CONNECTED LOAD PER PHASE24.123.523.270.75TOTALDEMAND FACTOR0.90MAX. DEMAND..63.68KWTOTAL CONNECTED LOAD (3PH)70.75KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-F20EPROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE:OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB - F20ELOCATION: ELECT. ROOM20TH FLOORSR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP10035FIREPROOF4C 351C 16(N/A)OUTGOING1DB - F20ETP4035XLPE /SWA/PVC4C 101C 102.502.402.407.302DB - F23ETP4035XLPE /SWA/PVC4C 101C 102.502.402.407.303DB - F26ETP4035XLPE /SWA/PVC4C 101C 102.502.402.407.304DB - F29ETP4035XLPE /SWA/PVC4C 101C 102.502.402.407.305DB - F32ETP4035XLPE /SWA/PVC4C 101C 102.502.402.407.306SPARETP20351.001.001.003.00SMDB- F20E CONNECTED TO: MDB - ETOTAL CONNECTED LOAD PER PHASE13.5013.0013.0039.50TOTALDEMAND FACTOR0.90MAX. DEMAND..35.55KWTOTAL CONNECTED LOAD (3PH)39.50KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-F1EPROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE:OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB - F1ELOCATION: ELECT. ROOMFIRST FLOORSR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP20035FIREPROOF4C 951C 50(N/A)OUTGOING1SEF - 2TP2035FIRE PROOF4C 41C 41.001.001.003.04P ELCB 100 mA2DB- F1ETP6335XLPE /SWA/PVC4C 161C 166.005.806.5018.33DB - F2ETP4035XLPE /SWA/PVC4C 101C 105.255.655.3016.204DB - F5ETP4035XLPE /SWA/PVC4C 101C 106.255.306.4017.9505DF - F10ETP4035XLPE /SWA/PVC4C 101C 106.255.306.4017.9506DF - F15ETP4035XLPE /SWA/PVC4C 101C 106.255.306.4017.950SMDB- F1E CONNECTED TO: MDB - ETOTAL CONNECTED LOAD PER PHASE31.0028.3532.0091.35TOTALDEMAND FACTOR0.90MAX. DEMAND..82.22KWTOTAL CONNECTED LOAD (3PH)91.35KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-MDF-DUPROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE:OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB - MDF-DULOCATION: MDF. ROOMSR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP10035XLPE/SWA/PVC4C 351C 16(N/A)OUTGOING1DB -UPS-1TP4035XLPE /SWA/PVC4C 101C 102.602.802.608.002UPS-1 BY DUTP4035XLPE /SWA/PVC4C 101C 100.500.500.501.50AS PER DU REQUIREMENT3DB -UPS-2TP4035XLPE /SWA/PVC4C 101C 102.602.802.608.004UPS-2 BY DUTP4035XLPE /SWA/PVC4C 101C 100.500.500.501.50AS PER DU REQUIREMENT5RECTIFIER BY DUTP4035XLPE /SWA/PVC4C 101C 100.500.500.501.50AS PER DU REQUIREMENT6CCUTP4035XLPE /SWA/PVC4C 101C 105.005.005.0015.007SPARETP40350.500.500.501.50SMDB- RN CONNECTED TO: MDB - ETOTAL CONNECTED LOAD PER PHASE12.2012.6012.2037.00TOTALDEMAND FACTOR0.90MAX. DEMAND..33.30KWTOTAL CONNECTED LOAD (3PH)37.00KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-B1EPROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE:OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB - B1ELOCATION: LV. ROOMSR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP40035FIRE PROOF4C 3001C 150(N/A)OUTGOING1SEWAGE LIFT PUMPTP2035XLPE /SWA/PVC4C 41C 41.001.001.003.004P ELCB 100 mA2SUMP PUMP-1TP2035XLPE /SWA/PVC4C 41C 40.500.500.501.50ELS 100-300 mA+Shunt Trip3SUMP PUMP-2TP2035XLPE /SWA/PVC4C 41C 40.500.500.501.50ELS 100-300 mA+Shunt Trip4DB - B3ETP4035XLPE /SWA/PVC4C 101C 104.254.253.9012.405WATER TRANSF. PUMPTP10035XLPE /SWA/PVC4C 351C 1610.0010.0010.0030.00ELS 100-300 mA+Shunt Trip6BMAF - 1TP2035FIRE PROOF4C 41C 41.501.501.504.504P ELCB 100 mA7BMAF - 2TP2035FIRE PROOF4C 41C 41.501.501.504.504P ELCB 100 mA8BEF - 2TP3235FIRE PROOF4C 61C 63.003.003.009.004P ELCB 100 mA9BEF - 1TP3235FIRE PROOF4C 61C 63.003.003.009.004P ELCB 100 mA10DB - B1ETP4035XLPE /SWA/PVC4C 101C 104.655.103.8513.6011DB - UPSTP6335XLPE /SWA/PVC4C 251C 1610.409.2010.4030.0012DB - CKETP6335XLPE /SWA/PVC4C 161C 167.107.406.9021.4013DB - CETP4035XLPE /SWA/PVC4C 101C 104.153.404.7012.2514SMDB-MDF-DUTP10035XLPE /SWA/PVC4C 351C 1612.2012.6012.2037.0015DUMP WAITER ELEVATORTP3235XLPE /SWA/PVC4C 61C 61.001.001.003.004P ELCB 300 mASMDB- RN CONNECTED TO: MDB - ETOTAL CONNECTED LOAD PER PHASE64.7563.9563.95192.65TOTALDEMAND FACTOR0.90MAX. DEMAND..173.39KWTOTAL CONNECTED LOAD (3PH)192.65KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-RNPROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE:OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB - RNLOCATION: ELECT. ROOMROOF FLOORSR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP80035XLPE/SWA/PVC2x4C.3002x1C.150(N/A)OUTGOING1LIFT - 2TP10035XLPE/SWA/PVC4C 701C 3512.0012.0012.0036.004P ELCB 300 mA2LIFT - 2 CONTROLSP2035XLPE/SWA/PVC2C 41C 41.00--1.0DP ELCB 100 mA3LIFT - 3TP10035XLPE/SWA/PVC4C 701C 3512.0012.0012.0036.004P ELCB 300 mA4LIFT - 3 CONTROLSP2035XLPE/SWA/PVC2C 41C 4-1.0-1.0DP ELCB 100 mA5LIFT - 4TP10035XLPE/SWA/PVC4C 701C 3512.0012.0012.0036.004P ELCB 300 mA6LIFT - 4 CONTROLSP2035XLPE/SWA/PVC2C 41C 4--1.001.0DP ELCB 100 mA7LIFT - 5TP10035XLPE/SWA/PVC4C 701C 3512.0012.0012.0036.004P ELCB 300 mA8LIFT - 5 CONTROLSP2035XLPE/SWA/PVC2C 41C 41.00--1.0DP ELCB 100 mA9LIFT - 6TP10035XLPE/SWA/PVC4C 701C 3512.0012.0012.0036.004P ELCB 300 mA10LIFT - 6 CONTROLSP2035XLPE/SWA/PVC2C 41C 4-1.0-1.0DP ELCB 100 mA11SERVICE LIFT - 1TP10035XLPE/SWA/PVC4C 351C 169.09.09.027.04P ELCB 300 mA12SERVICE LIFT - 1 CONTROLSP2035XLPE/SWA/PVC2C 41C 4--1.01.0DP ELCB 100 mA13SERVICE LIFT - 2TP10035XLPE/SWA/PVC4C 351C 169.09.09.027.04P ELCB 300 mA14SERVICE LIFT - 2 CONTROLSP2035XLPE/SWA/PVC2C 41C 41.0--1.0DP ELCB 100 mA15EXHAUST FAN-1SP2035XLPE/SWA/PVC2C 41C 4-1.00-1.0DP ELCB 100 mA16EXHAUST FAN -2SP2035XLPE/SWA/PVC2C 41C 4-1.001.0DP ELCB 100 mA17FAHU - 2TP20035XLPE/SWA/PVC4C 951C 5024.024.024.072.0ELS 100-1000 mA+Shunt Trip18FAADE LIGHTTP6335--8.08.08.024.0SMDB- RN CONNECTED TO: BUSBAR # 4TOTAL CONNECTED LOAD PER PHASE113.00113.00113.00339.00TOTALDEMAND FACTOR0.90MAX. DEMAND..305.10KWTOTAL CONNECTED LOAD (3PH)339.00KWRCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-PBK (NEW)PROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE:OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB - PBKLOCATION: MECHANICAL ROOM35TH FLOORSR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP16035XLPE/SWA/PVC4C 701C 35(N/A)OUTGOING1HOTPLATE OVEN -11TP4035XLPE/SWA/PVC4C 101C 104.004.004.0012.004P ELCB 100 mA2SALAMANDER -10TP3235XLPE/SWA/PVC4C 61C 62.002.002.006.004P ELCB 100 mA3FRY TOP -9TP3235XLPE/SWA/PVC4C 61C 62.002.002.006.004P ELCB 100 mA4FRYER -8TP3235XLPE/SWA/PVC4C 61C 62.002.002.006.004P ELCB 100 mA5AHU-K6TP6335XLPE/SWA/PVC4C 161C 165.005.005.0015.004P ELCB 100 mA6DB - PBKTP6335XLPE/SWA/PVC4C 161C 167.508.408.0023.90SMDB- PBK CONNECTED TO: SMDB -35NTOTAL CONNECTED LOAD PER PHASE22.5023.4023.0068.90TOTALDEMAND FACTOR0.90MAX. DEMAND..62.01KWTOTAL CONNECTED LOAD (3PH)68.90KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-F35NPROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE:OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB - F35NLOCATION: MECHANICAL ROOM35TH FLOORSR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP25035XLPE/SWA/PVC4C 1501C 70(N/A)OUTGOING1DB - RNTP6335XLPE/SWA/PVC4C 161C 167.157.058.1522.352HOTWATER - RETP2035XLPE/SWA/PVC4C 41C 41.501.501.504.504P ELCB 100 mA3FILTERED WATERTP3235XLPE/SWA/PVC4C 61C 63.003.003.009.004P ELCB 100 mA4COLD WATERTP2035XLPE/SWA/PVC4C 41C 42.002.002.006.004P ELCB 100 mA5BOILER RE.TP2035XLPE/SWA/PVC4C 41C 40.500.500.501.504P ELCB 100 mA6SOFT WATERTP3235XLPE/SWA/PVC4C 61C 63.003.003.009.004P ELCB 100 mA7SMDB - PBKTP16035XLPE/SWA/PVC4C 701C 3522.5023.4023.0068.90SMDB- F35N CONNECTED TO: BUSBAR # 4TOTAL CONNECTED LOAD PER PHASE39.6540.4541.15121.25TOTALDEMAND FACTOR0.90MAX. DEMAND..109.13KWTOTAL CONNECTED LOAD (3PH)121.25KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-F34NPROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE: MAY 2010OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB - F34NLOCATION: ELECT. ROOM34TH FLOORSR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP30035XLPE/SWA/PVC4C 1851C 95(N/A)OUTGOING1DB - F34N1TP6335XLPE/SWA/PVC4C 161C 1612.0012.3013.0037.302DB - F34N2TP4035XLPE/SWA/PVC4C 101C 104.253.253.9511.453SWIMMING POOLTP25035XLPE/SWA/PVC4C 1501C 7023.0023.0023.0069.004P ELCB 100 mA4SAUNA (F)TP4035XLPE/SWA/PVC4C 101C 103.003.003.009.004P ELCB 100 mA5STEAM (F)TP4035XLPE/SWA/PVC4C 101C 103.003.003.009.004P ELCB 100 mA6STEAM (M)TP4035XLPE/SWA/PVC4C 101C 103.003.003.009.004P ELCB 100 mA7SAUNA (M)TP4035XLPE/SWA/PVC4C 101C 103.003.003.009.004P ELCB 100 mA8SPARETP20352.002.002.006.009SPARETP20352.002.002.006.00SMDB- F34N CONNECTED TO: BUSBAR # 4TOTAL CONNECTED LOAD PER PHASE55.2554.5555.95165.75TOTALDEMAND FACTOR0.90MAX. DEMAND..149.18KWTOTAL CONNECTED LOAD (3PH)165.75KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-T2PROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE:OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB - T2LOCATION: ELECT. ROOM31ST - 33RD FLOORSSR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP25035XLPE/SWA/PVC4C 1501C 7037.63433.8105.40(N/A)OUTGOING1DB - T2 - 1TP6335PVC / SC4X1C 251C 169.408.508.4526.352DB - T2 - 2TP6335PVC / SC4X1C 251C 169.408.508.4526.353DB - T2 - 3TP6335PVC / SC4X1C 251C 169.408.508.4526.354DB - T2 - 4TP6335PVC / SC4X1C 251C 169.408.508.4526.35SMDB- T2 CONNECTED TO: BUSBAR # 4TOTAL CONNECTED LOAD PER PHASE37.6034.0033.80105.400TOTALDEMAND FACTOR0.90MAX. DEMAND..94.86KWTOTAL CONNECTED LOAD (3PH)105.40KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-F21-F22PROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE:OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB - F21 / F22LOCATION: ELECT. ROOM21ST & 22ND FLOORSSR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP22535XLPE/SWA/PVC4C 1201C 70(N/A)OUTGOING1DB - (21 / 22) - 1TP6335PVC / SC4X1C 251C 168.858.007.9024.752DB - (21 / 22) - 3TP6335PVC / SC4X1C 251C 168.858.007.9024.753DB - (21 / 22) - 4TP6335PVC / SC4X1C 251C 168.858.007.9024.754DB - (21 / 22) - 5TP4035PVC / SC4X1C 161C 164.905.604.7015.205DB - (21 / 22) - 6TP6335PVC / SC4X1C 251C 168.858.007.9024.75SMDB- F1 / F22 CONNECTED TO: BUSBAR # 3TOTAL CONNECTED LOAD PER PHASE40.3037.6036.30114.200TOTALDEMAND FACTOR0.90MAX. DEMAND..102.78KWTOTAL CONNECTED LOAD (3PH)114.20KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-T1PROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE: MAY 2010OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB - T1LOCATION: ELECT. ROOM20TH, 23RD-30TH FLOORSSR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP30035XLPE/SWA/PVC4C 1851C 95(N/A)OUTGOING1DB - T1 -1TP6335PVC / SC4X1C 251C 168.858.007.9024.752DB - T1 -2TP4035PVC / SC4X1C 161C 164.905.604.7015.203DB - T1 -3TP6335PVC / SC4X1C 251C 168.858.007.9024.754DB - T1 -4TP6335PVC / SC4X1C 251C 168.858.007.9024.755DB - T1 -5TP4035PVC / SC4X1C 161C 164.905.604.7015.206DB - T1 -6TP6335PVC / SC4X1C 251C 168.858.007.9024.75SMDB- T1 CONNECTED TO: BUSBAR # 3 / 4TOTAL CONNECTED LOAD PER PHASE45.2043.2041.00129.400TOTALDEMAND FACTOR0.90MAX. DEMAND..116.46KWTOTAL CONNECTED LOAD (3PH)129.40KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-F20NPROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE:OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB - F20NLOCATION: ELECT. ROOM20TH FLOORSR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP40035XLPE/SWA/PVC4C 3001C 150(N/A)OUTGOING1GSM EQUIPMENTTP2035XLPE/SWA/PVC4C 41C 41.001.001.003.004P ELCB 100 mA2FAHU - 1TP12535XLPE/SWA/PVC4C 501C 2522.0022.0022.0066.00ELS 100-1000 mA+Shunt Trip3DB - F20NTP6335XLPE/SWA/PVC4C 161C 166.407.106.5020.004DB - F23NTP6335XLPE/SWA/PVC4C 161C 166.407.106.5020.005DB - F26NTP6335XLPE/SWA/PVC4C 161C 166.407.106.5020.006DB - F29NTP6335XLPE/SWA/PVC4C 161C 166.407.106.5020.007DB - F32NTP6335XLPE/SWA/PVC4C 161C 166.407.106.5020.008SPARETP20351.001.001.003.009SPARETP20351.001.001.003.00SMDB- F20N CONNECTED TO: BUSBAR # 3TOTAL CONNECTED LOAD PER PHASE57.0060.5057.50175.00TOTALDEMAND FACTOR0.90MAX. DEMAND..157.50KWTOTAL CONNECTED LOAD (3PH)175.00KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-F5-F19PROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE: MAY 2010OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB -F5- F19CONSULTANT: M/S. IAN BANHAN & ASSOCIATESLOCATION: ELECT. ROOM5TH - 19TH FLOORSR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP20035XLPE/SWA/PVC4C 951C 50(N/A)OUTGOING1DB - GR1SP4025PVC/ SC2X1C 161C 164.80--4.802DB - GR2SP4025PVC/ SC2X1C 161C 16-4.80-4.803DB - GR3SP4025PVC/ SC2X1C 161C 16--4.804.804DB - GR4SP4025PVC/ SC2X1C 161C 164.80--4.805DB - GR5SP4025PVC/ SC2X1C 161C 16-4.80-4.806DB - GR6SP4025PVC/ SC2X1C 161C 16--4.804.807DB - GR7SP4025PVC/ SC2X1C 161C 164.80--4.808DB - GR8SP4025PVC/ SC2X1C 161C 16-4.80-4.809DB - GR9SP4025PVC/ SC2X1C 161C 16--4.804.8010DB - GR10SP4025PVC/ SC2X1C 161C 164.80--4.8011DB - GR11SP4025PVC/ SC2X1C 161C 16-4.80-4.8012DB - GR12SP4025PVC/ SC2X1C 161C 16--4.804.8013DB - GR13SP4025PVC/ SC2X1C 161C 164.80--4.8014DB - GR14SP4025PVC/ SC2X1C 161C 16-4.80-4.8015DB - GR15SP4025PVC/ SC2X1C 161C 16--4.804.8016DB - GR16SP4025PVC/ SC2X1C 161C 164.80--4.8017DB - GR17SP4025PVC/ SC2X1C 161C 16-4.80-4.8018DB - GR18SP4025PVC/ SC2X1C 161C 16--4.804.80SMDB- F5 - F19 CONNECTED TO: BUSBAR # 1 / 2TOTAL CONNECTED LOAD PER PHASE28.8028.8028.8086.40TOTALDEMAND FACTOR0.90MAX. DEMAND..77.76KWTOTAL CONNECTED LOAD (3PH)86.40KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-F16 (R1)PROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE:OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB -F16LOCATION: ELECT. ROOM16TH FLOORSR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP25035XLPE/SWA/PVC4C 1501C 70(N/A)OUTGOING1DB - GR1SP4025PVC/ SC2X1C 161C 164.80--4.802DB - GR2SP4025PVC/ SC2X1C 161C 16-4.80-4.803DB - GR3SP4025PVC/ SC2X1C 161C 16--4.804.804DB - GR4SP4025PVC/ SC2X1C 161C 164.80--4.805DB - GR5SP4025PVC/ SC2X1C 161C 16-4.80-4.806DB - GR6SP4025PVC/ SC2X1C 161C 16--4.804.807DB - GR7SP4025PVC/ SC2X1C 161C 164.80--4.808DB - GR8SP4025PVC/ SC2X1C 161C 16-4.80-4.809DB - GR9SP4025PVC/ SC2X1C 161C 16--4.804.8010DB - GR10SP4025PVC/ SC2X1C 161C 164.80--4.8011DB - GR11SP4025PVC/ SC2X1C 161C 16-4.80-4.8012DB - GR12SP4025PVC/ SC2X1C 161C 16--4.804.8013DB - GR13SP4025PVC/ SC2X1C 161C 164.80--4.8014DB - F16KTP6335XLPE/SWA/PVC4C 161C 168.208.209.1025.5015DB - F16NTP4035XLPE/SWA/PVC4C 101C 106.206.106.2018.5016AUTOMATIC COFFEE M/C -9TP4035XLPE/SWA/PVC4C 101C 104.604.704.7014.004P ELCB 100 mASMDB- F16 - CONNECTED TO: BUSBAR # 2TOTAL CONNECTED LOAD PER PHASE43.0038.2039.20120.40TOTALDEMAND FACTOR0.90MAX. DEMAND..108.36KWTOTAL CONNECTED LOAD (3PH)120.40KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-F4 (R1)PROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE:OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB -F4LOCATION: ELECT. ROOM4TH FLOORSR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP22535XLPE/SWA/PVC4C 1201C 70(N/A)OUTGOING1DB - GR1SP4025PVC/ SC2X1C 161C 164.80-4.802DB - GR2SP4025PVC/ SC2X1C 161C 16-4.80-4.803DB - GR3SP4025PVC/ SC2X1C 161C 16--4.804.804DB - GR4SP4025PVC/ SC2X1C 161C 164.80--4.805DB - GR5SP4025PVC/ SC2X1C 161C 16-4.80-4.806DB - GR6SP4025PVC/ SC2X1C 161C 16--4.804.807DB - GR7SP4025PVC/ SC2X1C 161C 164.80--4.808DB - GR8SP4025PVC/ SC2X1C 161C 16-4.80-4.809DB - GR9SP4025PVC/ SC2X1C 161C 16--4.804.8010DB - GR10SP4025PVC/ SC2X1C 161C 164.80--4.8011DB - GR11SP4025PVC/ SC2X1C 161C 16-4.80-4.8012DB - GR12SP4025PVC/ SC2X1C 161C 16--4.804.8013DB - GR13SP4025PVC/ SC2X1C 161C 164.80--4.8014DB - F4KTP6335XLPE/SWA/PVC4C 161C 169.19.19.027.215DISHWASHER -26TP4035XLPE/SWA/PVC4C 101C 103.13.103.209.44P ELCB 100 mASMDB- F4 - CONNECTED TO: BUSBAR # 1TOTAL CONNECTED LOAD PER PHASE36.2031.4031.4099.00TOTALDEMAND FACTOR0.90MAX. DEMAND..89.10KWTOTAL CONNECTED LOAD (3PH)99.00KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-F3NPROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE:OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB - F3NLOCATION: ELECT. ROOM3RD FLOORSR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP63035XLPE/SWA/PVC2X4C 1852 X 1C95(N/A)OUTGOING1DB - F3N1TP6335XLPE/SWA/PVC4C 161C 167.407.807.1522.352DB - F3N2TP6335XLPE/SWA/PVC4C 161C 169.1510.209.3028.653LAUNDRYTP2035XLPE/SWA/PVC4C 41C 41.501.501.504.504P ELCB 100 mA4AHU - 5TP6335XLPE/SWA/PVC4C 161C 1610.0010.0010.0030.004P ELCB 100 mA6AHU - 6TP4035XLPE/SWA/PVC4C 101C 105.005.005.0015.004P ELCB 100 mA8AHU - 7TP6335XLPE/SWA/PVC4C 161C 1610.0010.0010.0030.004P ELCB 100 mA10AHU - 8TP6335XLPE/SWA/PVC4C 161C 169.009.009.0027.004P ELCB 100 mA12DB - F4NTP4035XLPE/SWA/PVC4C 101C 104.054.954.4013.4013SERVICE LIFT-3TP6335XLPE/SWA/PVC4C 161C 165.005.005.0015.004P ELCB 300 mA14SERVICE LIFT CONTROL-3SP2035XLPE/SWA/PVC2C 41C 40.50--0.50DP ELCB 100 mA15DB - F5NTP6335XLPE/SWA/PVC4C 161C 167.807.308.0023.1016DB - F10N2) PROVIDE EARTH LEAKAGE AND UNDER VOLTAGE PROTECTION FOR EQUIPMENT IN RESPECTIVE CONTROL PANELS AND COMPLY WITH DEWA REQUIREMENTSTP6335XLPE/SWA/PVC4C 161C 167.807.308.0023.1017DB - F15N2) PROVIDE EARTH LEAKAGE AND UNDER VOLTAGE PROTECTION FOR EQUIPMENT IN RESPECTIVE CONTROL PANELS AND COMPLY WITH DEWA REQUIREMENTSTP6335XLPE/SWA/PVC4C 161C 167.807.308.0023.1018SPARETP32353.003.003.009.004P ELCB 100 mA19SPARETP20351.001.001.003.00SMDB- F3N CONNECTED TO: MDB - 2TOTAL CONNECTED LOAD PER PHASE89.0089.3589.35267.70TOTALDEMAND FACTOR0.90MAX. DEMAND..240.93KWTOTAL CONNECTED LOAD (3PH)267.70KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-F2NPROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE:OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB - F2NLOCATION: ELECT. ROOM2ND FLOORSR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP20035XLPE/SWA/PVC4C 1201C 50(N/A)OUTGOING1DB - F2N1TP6335XLPE/SWA/PVC4C 161C 169.508.908.7027.102DB - F2N2TP4035XLPE/SWA/PVC4C 101C 104.454.353.9012.703DB - F2N3TP6335XLPE/SWA/PVC4C 161C 167.307.308.3022.904SPARETP32352.872.862.878.604P ELCB 100 mA5SPARETP32353.003.003.009.004P ELCB 100 mA6SPARETP32353.003.003.009.004P ELCB 100 mA2) PROVIDE EARTH LEAKAGE AND UNDER VOLTAGE PROTECTION FOR EQUIPMENT IN RESPECTIVE CONTROL PANELS AND COMPLY WITH DEWA REQUIREMENTSSMDB- F2N CONNECTED TO: MDB - 2TOTAL CONNECTED LOAD PER PHASE30.1229.4129.7789.30TOTALDEMAND FACTOR0.90MAX. DEMAND..80.37KWTOTAL CONNECTED LOAD (3PH)89.30KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-F1K (NEW)PROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE: MAY 2010OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB - F1KCONSULTANT: M/S. IAN BANHAN & ASSOCIATESLOCATION: ELECT. CABINET1ST FLOORSR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP40035XLPE/SWA/PVC4C 3001C 150(N/A)OUTGOING1DB - F1KTP6335XLPE/SWA/PVC4C 161C 168.278.979.1726.402DB - F1K1TP6335XLPE/SWA/PVC4C 161C 169.909.908.9028.703CONVEYOR DISHWASHER -68TP8035XLPE/SWA/PVC4C 251C 1611.7011.7011.6035.004P ELCB 100 mA4ELECT INDUCTION UNIT - 76TP3235XLPE/SWA/PVC4C 61C 63.103.203.209.504P ELCB 100 mA5SPARETP20351.401.301.304.004P ELCB 100 mA6ELECT CONVECTION OVEN -119TP8035XLPE/SWA/PVC4C 251C 1611.7011.7011.6035.004P ELCB 100 mA7ELECT INDUCTION COOK TOP -122TP3235XLPE/SWA/PVC4C 61C 62.302.302.407.004P ELCB 100 mA8ELECT INDUCTION COOK TOP -122TP3235XLPE/SWA/PVC4C 61C 62.302.402.307.004P ELCB 100 mA9ELECT TOP -123TP3235XLPE/SWA/PVC4C 61C 63.003.003.009.004P ELCB 100 mA10FABRICATED HOTPLATE RACE2) PROVIDE EARTH LEAKAGE AND UNDER VOLTAGE PROTECTION FOR EQUIPMENT IN RESPECTIVE CONTROL PANELS AND COMPLY WITH DEWA REQUIREMENTSTP3235XLPE/SWA/PVC4C 61C 62.002.002.006.004P ELCB 100 mA11COMBI - OVENTP6335XLPE/SWA/PVC4C 161C 166.006.007.0019.004P ELCB 100 mA12SALAMNDERTP3235XLPE/SWA/PVC4C 61C 62.002.002.006.004P ELCB 100 mA13BLAST CHILLERTP3235XLPE/SWA/PVC4C 61C 63.003.003.009.004P ELCB 100 mASMDB- F1K CONNECTED TO: SMDB - F1NTOTAL CONNECTED LOAD PER PHASE66.6767.4767.47201.60TOTALDEMAND FACTOR0.90MAX. DEMAND..181.44KWTOTAL CONNECTED LOAD (3PH)201.60KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-F1N (R1)PROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE:OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB - F1NLOCATION: ELECT. ROOM1ST FLOORSR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP63035XLPE/SWA/PVC2X 4C 1852X 1C 95(N/A)OUTGOING1DB - F1N1TP6335XLPE/SWA/PVC4C 161C 164.905.304.9515.152DB - F1N2TP4035XLPE/SWA/PVC4C 101C 104.503.904.5512.953SMDB - F1KTP40035XLPE/SWA/PVC4C 3001C 15066.6767.4767.47205.004AHU - 4TP4035XLPE/SWA/PVC4C 101C 103.003.003.009.004P ELCB 100 mA8AHU - K5TP2035XLPE/SWA/PVC4C 41C 41.001.001.003.006SPARETP20351.001.001.003.002) PROVIDE EARTH LEAKAGE AND UNDER VOLTAGE PROTECTION FOR EQUIPMENT IN RESPECTIVE CONTROL PANELS AND COMPLY WITH DEWA REQUIREMENTSSMDB- F1N CONNECTED TO: MDB - 1TOTAL CONNECTED LOAD PER PHASE81.0781.6781.97244.71TOTALDEMAND FACTOR0.90MAX. DEMAND..220.24KWTOTAL CONNECTED LOAD (3PH)244.71KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-CK (NEW)PROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE:OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB - CKLOCATION: ELECT. CABINETCONCOURSE LEVELSR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP35035XLPE/SWA/PVC4C 2401C120(N/A)OUTGOING1DB - CKTP8035XLPE/SWA/PVC4C 251C 167.9011.607.6027.102DB - CK1TP4035XLPE/SWA/PVC4C 101C 105.705.605.8017.103DISHWASHER -145TP4035XLPE/SWA/PVC4C 101C 104.104.204.2012.504P ELCB 100 mA4FRYERTOP -67TP3235XLPE/SWA/PVC4C 61C 62.002.002.006.004P ELCB 100 mA5HOTPLATE -70TP2535XLPE/SWA/PVC4C 61C 61.401.301.304.004P ELCB 100 mA6BAKERY OVEN -71TP3235XLPE/SWA/PVC4C 61C 63.003.003.009.004P ELCB 100 mA7COMBI OVEN -131TP3235XLPE/SWA/PVC4C 61C 63.103.104.0010.204P ELCB 100 mA8HEATER PLATE -125TP2535XLPE/SWA/PVC4C 61C 61.301.401.304.004P ELCB 100 mA9PASTA COOKER -126TP6335XLPE/SWA/PVC4C 161C 166.706.606.7020.004P ELCB 100 mA10SPARETP20352.002.002.006.0011SPARETP20352.002.002.006.0012DECK OVENTP6335XLPE/SWA/PVC4C 161C 1610.009.009.0028.004P ELCB 100 mA2) PROVIDE EARTH LEAKAGE AND UNDER VOLTAGE PROTECTION FOR EQUIPMENT IN RESPECTIVE CONTROL PANELS AND COMPLY WITH DEWA REQUIREMENTSSMDB- CN CONNECTED TO: MDB - 1TOTAL CONNECTED LOAD PER PHASE49.2051.8048.90149.90TOTALDEMAND FACTOR0.90MAX. DEMAND..134.91KWTOTAL CONNECTED LOAD (3PH)149.90KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-CN (R1)PROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE: MAY 2010OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB - CNCONSULTANT: M/S. IAN BANHAN & ASSOCIATESLOCATION: ELECT. ROOMCONCOURSE LEVELSR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP63035XLPE/SWA/PVC2X4C 1852X 1C95(N/A)OUTGOING1DB - C1NTP4035XLPE/SWA/PVC4C 101C 103.402.652.808.852DB - C2NTP4035XLPE/SWA/PVC4C 101C 102.602.753.058.403DB - C3NTP4035XLPE/SWA/PVC4C 161C 167.706.556.1520.403DB - C4NTP6335XLPE/SWA/PVC4C 161C 167.506.857.5021.854SMDB - CKTP35035XLPE/SWA/PVC4C 2401C 12049.2051.8048.90149.905AHU - 2TP6335XLPE/SWA/PVC4C 161C 168.008.008.0024.004P ELCB 100 mA6AHU - 3TP6335XLPE/SWA/PVC4C 161C 168.008.008.0024.004P ELCB 100 mA7AHU - K2TP6335XLPE/SWA/PVC4C 161C 167.007.007.0021.004P ELCB 100 mA8AHU - K4TP2035XLPE/SWA/PVC4C 41C 41.001.001.003.00SMDB- CN CONNECTED TO: MDB - 1TOTAL CONNECTED LOAD PER PHASE94.4094.6092.40281.40TOTALDEMAND FACTOR0.90MAX. DEMAND..253.26KWTOTAL CONNECTED LOAD (3PH)281.40KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-B1WB (NEW)PROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE: MAY 2010OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB - B1WBCONSULTANT: M/S. IAN BANHAN & ASSOCIATESLOCATION: ELECTRICAL CABINETBASEMENT 1SR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP16035XLPE/SWA/PVC4C 701C 35(N/A)OUTGOING1INDUCTION COOK TOP -8TP3235XLPE/SWA/PVC4C 61C 62.302.302.407.004P ELCB 100 mA2INDUCTION COOK TOP -8TP3235XLPE/SWA/PVC4C 61C 62.302.402.307.004P ELCB 100 mA3DISH WASHER -38TP3235XLPE/SWA/PVC4C 61C 63.303.303.209.804P ELCB 100 mA4DB - B1WBTP6335XLPE/SWA/PVC4C 161C 1611.4011.4011.1033.905SPARETP20351.001.01.03.004P ELCB 100 mA6INDUCTION COOK TOP -8TP3235XLPE/SWA/PVC4C 61C 62.002.002.006.004P ELCB 100 mASMDB- B1N CONNECTED TO: MDB - 1TOTAL CONNECTED LOAD PER PHASE22.3022.4022.0066.70TOTALDEMAND FACTOR0.90MAX. DEMAND..60.03KWTOTAL CONNECTED LOAD (3PH)66.70KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)

SMDB-B1N (R1)PROJECT: PULLMAN HOTEL TOWERDETAILS OF CONNECTED LOAD / MAX. DEMANDAREA: JLT, DUBAI3B+C+1+34+MECH.FLOORSPLANNED COMPLETION DATE: MAY 2010OWNER: H.H.SH. AHMED BIN SAIF AL NAHYANPLOT No: 393-929SMDB REF: SMDB - B1NCONSULTANT: M/S. IAN BANHAN & ASSOCIATESLOCATION: LV ROOMBASEMENT 1SR. No.CIRCUIT FEEDER DB NO.SP/ TPRATING-AMPSFAULT DUTY KAPVC/XLPECABLE SIZELENGTH OF CABLE (mtrs)ECC SIZE-1C mm2CONNECTED LOAD-KWKWH METERREMARKSTPACBMCCBMCBSWA/PVC2/4 x 1C mm22/3/4C mm2R-PHASE KWY-PHASE KWB-PHASE KWTOTAL KW1 Ph (1)3 Ph (2)3 Ph (3)LV/HV CT (4)INCOMERTP40035XLPE/SWA/PVC4C 3001C 150(N/A)OUTGOING1DB - B3NTP4035XLPE/SWA/PVC4C 101C 105.655.505.0516.202DB - B2NTP4035XLPE/SWA/PVC4C 101C 106.215.955.8117.973AHU - 1TP6335XLPE/SWA/PVC4C 161C 165.005.005.0015.004P ELCB 100 mA4AHU - K1TP6335XLPE/SWA/PVC4C 161C 165.005.005.0015.004P ELCB 100 mA5SMDB - B1WBTP16035XLPE/SWA/PVC4C 701C 3522.3022.422.066.706DB - B1N1TP4035XLPE/SWA/PVC4C 101C 106.355.77.019.007DB - B1N2TP4035XLPE/SWA/PVC4C 101C 102.302.502.507.308DB - B1N3TP4035XLPE/SWA/PVC4C 101C 105.505.505.5016.509DB-SHOPTP3235XLPE/SWA/PVC4C 101C 101.001.01.03.004P ELCB 100 mA10AHU-K3TP4035XLPE/SWA/PVC4C 101C 104.004.04.012.004P ELCB 100 mASMDB- B1N CONNECTED TO: MDB - 2TOTAL CONNECTED LOAD PER PHASE63.3162.5562.81188.67TOTALDEMAND FACTOR0.90MAX. DEMAND..169.80KWTOTAL CONNECTED LOAD (3PH)188.67KWCONTRACTOR: LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521TEL No. 04 885 1700Fax No. 04 885 1618Type of Meter (Rating of Incomer) :(1) UP TO 60A(2) UP TO 100A(3) 125-160A(4) LV CTHV CT A(1 PHASE)(3 PHASE)