Smart Motor Controllers - SMCTM-3, SMCTM Flex Soft · PDF file150-F251NBD 251 222 182 141 560...

3
[email protected] | [email protected] 1300 446 226 | www.rexelautomation.com.au Smart Motor Controllers - SMC TM -3, SMC TM Flex Soft Starters Reap the benefits of high productivity on your plant floor with the SMC TM soft starters. Our soft starters are designed for flexibility and scalability with integrated features and functionality to help reduce your energy costs and maximize your investments.

Transcript of Smart Motor Controllers - SMCTM-3, SMCTM Flex Soft · PDF file150-F251NBD 251 222 182 141 560...

Page 1: Smart Motor Controllers - SMCTM-3, SMCTM Flex Soft · PDF file150-F251NBD 251 222 182 141 560 x 225 x 253.8 (30.4kg) ... LCD display, IP66, Remote Door Mount 150-TC1 SMCTM-Flex terminal

[email protected] | [email protected]

1300 446 226 | www.rexelautomation.com.au

Smart Motor Controllers - SMCTM-3, SMCTM Flex Soft Starters

Reap the benefits of high productivity on your plant floor with the SMCTM soft starters. Our soft starters are designed for flexibility and scalability with integrated features and functionality to help reduce your energy costs and maximize your investments.

Page 2: Smart Motor Controllers - SMCTM-3, SMCTM Flex Soft · PDF file150-F251NBD 251 222 182 141 560 x 225 x 253.8 (30.4kg) ... LCD display, IP66, Remote Door Mount 150-TC1 SMCTM-Flex terminal

SMCTM- 3 Optional Accessories

150-CA11 Auxiliary Contact Block 1 n/O 1 N/C, side mount

150-CA20 Auxiliary Contact Block 2 N/O, side mount

150-C84 480V Protective Module - 150-C3...37A

150-C84P 480V Protective Module - 150-C43...85A

150-F84L Protective Module, 480V, 150-C108...1250A

199LF1 Terminal Lug 108…251A (Pkg. Qty. 3), 16…120mm2

199LG1 Terminal Lug 317…480A (Pkg. Qty. 3), 25…240mm2

193-ER1A SMCTM-3 remote reset magnet, 230V AC

150-CF64 SMCTM-3 fan to suit 150-C3...37, internal mount

SMCTM- 3 Compact

Compact design provides true three-phase control, increased intelligence and unmatched performance. Motor and system diagnostics and an electronic overload with adjustable trip class reduce downtime and protect valuable assets.

• Compact footprint• Easy and secure setup• Integrated bypass• Five Start/Stop modes• No communications

SMCTM Flex Modular

Modular design features advanced intelligence, performance and diagnostics; communications flexibility; removable control module, power modules and fan assembly in a cost-effective package for your demanding production applications.

• Modular for installation and maintenance• Built-in LCD and keypad• Integrated bypass• Nine Start/Stop modes and up to three slow-speed modes• Full metering and diagnostics• Communication capable

[email protected] | [email protected]

Panel Mount - IP2X 200 to 480V AC Three-Phase

For models 150-C3...85 refer to SMCTM selection guide for starts/hour information.Ratings for models 150-C108...480 are based on 6 starts/hour equally spaced, 50°C.For 24V AC/DC control, change suffix ‘D’ to ‘R’.

Part Number LightDuty(A, 3 wire)

Medium (Normal) Duty (A, 3 wire)

H x W x D (mm) Control Voltage

150-C3NBD 3 3 140 x 45 x 100 100 - 240V AC

150-C9NBD 9 9 140 x 45 x 100 100 - 240V AC

150-C16NBD 16 16 140 x 45 x 100 100 - 240V AC

150-C19NBD 19 19 140 x 45 x 100 100 - 240V AC

150-C25NBD 25 25 140 x 45 x 100 100 - 240V AC

150-C30NBD 30 30 140 x 45 x 100 100 - 240V AC

150-C37NBD 37 37 140 x 45 x 100 100 - 240V AC

150-C43NBD 43 43 206 x 72 x 130 100 - 240V AC

150-C60NBD 60 60 206 x 72 x 130 100 - 240V AC

150-C85NBD 85 85 206 x 72 x 130 100 - 240V AC

150-C108NBD 108 108 444 x 197 x 206 100 - 240V AC

150-C135NBD 135 135 444 x 197 x 206 100 - 240V AC

150-C201NBD 201 201 560 x 225 x 266 100 - 240V AC

150-C251NBD 251 222 560 x 225 x 266 100 - 240V AC

150-C317NBD 317 311 600 x 290 x 298 100 - 240V AC

150-C361NBD 361 311 600 x 290 x 298 100 - 240V AC

150-C480NBD 480 433 600 x 290 x 298 100 - 240V AC

Panel Mount - IP00/IP20 200 to 480V AC Three-Phase

For 24V AC/DC control, change suffix ‘D’ to ‘R’; separate 120 or 240V single-phase power supply is required for fan operation.

Part Number100-240V AC Control Voltage

LightDuty(A, 3 wire)

Medium (Normal) Duty

(A, 3 wire)

Heavy Duty

(A, 3 wire)

Severe Duty

(A, 3 wire)

H x W x D (mm)

150-F5NBD 5 5 5 5 321 x 150 x 230 (5.7kg)

150-F25NBD 25 25 25 25 321 x 150 x 230 (5.7kg)

150-F43NBD 43 43 42 31 321 x 150 x 230 (5.7kg)

150-F60NBD 60 60 51 36 321 x 150 x 230 (5.7kg)

150-F85NBD 85 85 71 51 321 x 150 x 230 (5.7kg)

150-F108NBD 108 108 94 71 443.7 x 196.4 x 212.2 (15kg)

150-F135NBD 135 116 94 71 443.7 x 196.4 x 212.2 (15kg)

150-F201NBD 201 201 182 141 560 x 225 x 253.8 (30.4kg)

150-F251NBD 251 222 182 141 560 x 225 x 253.8 (30.4kg)

150-F317NBD 317 311 256 202 600 x 290 x 276.5 (45.8kg)

150-F361NBD 361 311 256 202 600 x 290 x 276.5 (45.8kg)

150-F480NBD 480 433 356 278 600 x 290 x 276.5 (45.8kg)

Panel Mount - IP00/IP20 200 to 480V AC Three-Phase

For 110 / 120 V DC control, change suffix ‘A’ to ‘E’

Part Number 230 V AC Control Voltage

LightDuty(A, 3 wire)

Medium (Normal) Duty

(A, 3 wire)

Heavy Duty

(A, 3 wire)

Severe Duty

(A, 3 wire)

H x W x D (mm)

150-F625NBA 625 625 607 501 1041.1 x 596.9 x 346.2 (179 Kg)

150-F780NBA 780 719 607 501 1041.1 x 596.9 x 346.2 (179 Kg)

150-F970NBA 970 851 709 571 1041.1 x 596.9 x 346.2 (224 Kg)

150-F1250NBA 1250 1039 859 680 1041.1 x 596.9 x 346.2 (224 Kg)

199LF1 Terminal Lug 108…251A (Pkg. Qty. 3), 16…120mm2

199LG1 Terminal Lug 317…480A (Pkg. Qty. 3), 25…240mm2

150TC1 IEC Terminal Cover, Line or Load, 108...135A Devices (1 piece)

150TC2 IEC Terminal Cover, Line or Load, 201...251A Devices (1 piece)

150TC3 IEC Terminal Cover, Line or Load, 317…480A Devices (1 piece)

SMCTM Flex Optional Accessories

[email protected] 446 226

Page 3: Smart Motor Controllers - SMCTM-3, SMCTM Flex Soft · PDF file150-F251NBD 251 222 182 141 560 x 225 x 253.8 (30.4kg) ... LCD display, IP66, Remote Door Mount 150-TC1 SMCTM-Flex terminal

[email protected] | [email protected]

SMCTM Flex Optional Accessories

20COMMER Dual-port EtherNet/IP Adapter Communications Module

20COMME EtherNet/IP Communication Adapter

20COMMP Profibus Communication Adapter

20COMMC ControlNet Communication Adapter

20COMMD DeviceNet Communication Adapter

4139145401S1FX Replacement Control Module, Standard 240VAC

4139145402S2FX Replacement Control Module, Standard 24VDC

20-HIM-C3S SMCTM-Flex, HIM, LCD display, IP66, Remote Door Mount

150-TC1 SMCTM-Flex terminal cover to suit 150-F108...135 (Two required)

150-TC2 SMCTM-Flex terminal cover to suit 150-F201...251 (Two required)

150-TC3 SMCTM-Flex terminal cover to suit 150-F317...480 (Two required)

Product Selection

Soft starter ratings are strongly influenced by the starting time and starting current characteristics of the driven machine. The following table, when used in conjunction with the ratings tables provided, ensures accurate soft starter selection.

Application Duty Application Duty

Agitator Heavy Fan - High pressure

Severe

Atomiser Heavy Grinder Medium

Bottle washer Light Hydraulic power pack

Medium

Centrifuge Severe Mill Severe

Chipper Severe Mill - Ball Severe

Compressor - Recip (Loaded) Severe Mill - Hammer Severe

Compressor - Recip (Unloaded) Heavy Mill - Roller Severe

Compressor - Screw (Loaded) Severe Mixer Severe

Compressor - Screw (Unloaded) Heavy Palletiser Severe

Conveyor - Belt Severe Planer Medium

Conveyor - Roller Medium Press Medium

Conveyor - Screw Heavy Pump - Bore Light

Crusher - Cone Medium Pump - Centrifugal

Medium

Crusher - Jaw Severe Pump - Positive displacement

Heavy

Crusher - Rotary Medium Pump - Slurry Severe

Crusher - Vertical impact Medium Re-pulper Severe

Debraker Medium Rotary table Heavy

Dryer Severe Sander Heavy

Dust collector Medium Saw - Bandsaw Severe

Edger Medium Saw - Circular Medium

Fan - Axial (Damped) Medium Separator Severe

Fan - Axial (Un-damped) Severe Shredder Severe

Fan - Centrifugal (Damped) Medium Slicer Light

Fan - Centrifugal (Un-damped) Severe Tumbler Heavy

SMCTM-3 SMCTM Flex

Motor Overload Ѵ Ѵ

Temperature Protection Ѵ Ѵ

Current Protection Ѵ Ѵ

Voltage Protection Ѵ

Communication capable Ѵ

Protection and Diagnosis

The above table is intended as a guide only. Individual machine and motor characteristics will determine the actual start current and start time requirements. Notes: Light duty rating - 300% FLC, 10 second startMedium (normal) duty rating - 350% FLC, 15 second startHeavy duty rating - 400% FLC, 20 second startSevere duty rating- 450% FLC, 30 second start

SMCTM-3 SMCTM Flex

Fan Module Ѵ Ѵ

Current Range Ѵ Ѵ

Modularity Ѵ Ѵ

Network Capabilities Ѵ Ѵ

LCD, Multi-lingual Display Ѵ Ѵ

Advanced Control Modes Ѵ Ѵ

Normal & heavy-duty Ratings Ѵ

Option Mondules Ѵ

Patented Control Modules Ѵ

Multiple Setup Options Ѵ

All Operating Modes in One Control Module

Ѵ

Scalability

Usability

SMCTM-3 SMCTM Flex

Easy Setup Ѵ Ѵ

LED Display Ѵ Ѵ

Built-in Test/reset button Ѵ Ѵ

Built-in LCD, Multi-lingual Display

Ѵ

Advanced Performance & Diagnosis

Ѵ

Network Capabilities Ѵ

Modularity Ѵ