Tyco Electronics introduces a quick and easy
way to protect secondary network cables – the
Smart Limiter cable protector. To many utilities,
a network system is the most attractive option
for customers seeking steadfast reliability.
The Smart Limiter cable protector will assist
companies in restoring their network system to
its most reliable state and when limiters operate,
they will be easily identified and replaced.
• Increases reliability by protecting cable
insulation from damage due to fault current
• Quick visual identification of blown limiters
reduces the time needed to find faulted limiters
• Fast installation in compact spaces through
the use of the ShearBolt connector. No special
tools are required for installation, only 11/16"
socket for installation and 1/2" for removal.
Connection is repeatable to the same standard
with every installation. No changing of die or
using crimping tools that require calibration.
• Easily repeatable installation regardless of
installer experience
• Sealing and mechanical protection are built in,
eliminating the need for additional components
• The limiter will only blow on secondary faults
and effortlessly coordinate with network
protector fuses.
• Minimal exposure to energized parts. Only the
conductor being inserted into the limiter needs
to be exposed making it very safe
• Fuse blowing activity is entirely contained in a
ballistic enclosure
• 100% submersible
• Gel-port cable entries will quench any arc when
“live” connections are made; making picking up
load safer
• Hinged bolt caps allow entry to enable voltage
measurements as required as these caps
are re-enterable
• Available, 100% submersible copper buses
(crab joints) make installing limiters in one
compact place convenient and trouble-free.
Available in 3W, 5W and 7W configurations
• Modular design allows circuits to be added or
subtracted without cutting cables
• No parts to move, slide or park when installing
or removing the limiter
• Tyco Electronics Smart Limiter cable protectors
have tested fault duty of 25kA per limiter
• Designed specifically for 208Y/120V systems
Energy Division
Smart LimiterCable Protector
© 2007 Tyco Electronics Corporation. All rights reserved.6-1773448-0 E288.05/08
Tyco Electronics Corporation8000 Purfoy RoadFuquay Varina, NC 27526-9349Tel: 800.327.6996Fax: 800.527.8350E-mail: [email protected]://energy.tycoelectronics.comwww.tycoelectronics.com
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the bestof our knowledge and belief correct and reliable. Users, however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such anassurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these productsis set forth in our standard terms and conditions of sale. Smart Limiter, ShearBolt, TE Logo and Tyco Electronics are trademarks.
Energy Division – a pioneer in the development of economical solutions for the electrical power industry. Our product range includes:Cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement andsurge arresters.
Ordering Information
Smart Limiter Cable Protector Part Number Description Per BoxSL-750-120V-F-FT(B1) Fused limiter for 750 kcmil cable 1SL-750-120V-NF-FT(B1) Non-Fused splice for 750 kcmil cable 1SL-500-120V-F-FT(B1) Fused limiter for 500 kcmil cable 1SL-500-120V-NF-FT(B1) Non-Fused splice for 500 kcmil cable 1SL-350-120V-F-FT(B1) Fused limiter for 350 kcmil cable 1SL-350-120V-NF-FT(B1) Non-Fused splice for 350 kcmil cable 1SL-250-120V-F-FT(B1) Fused limiter for 250 kcmil cable 1SL-250-120V-NF-FT(B1) Non-Fused splice for 250 kcmil cable 1SL-4/0-120V-F-FT(B1) Fused limiter for 4/0 cable 1SL-4/0-120V-NF-FT(B1) Non-Fused splice for 4/0 cable 1
Crab JointPart Number Description Per BoxCJ-4/0-3W3W-CU-FT-B1 3 way/3 way copper crab joint with
4/0 conductors 1CJ-4/0-5W5W-CU-FT-B1 5 way/5 way copper crab joint with
4/0 conductors 1CJ-4/0-7W7W-CU-FT-B1 7 way/7 way copper crab joint with
4/0 conductors 1CJ-250-3W3W-CU-FT-B1 3 way/3 way copper crab joint with
250 kcmil conductors 1CJ-250-5W5W-CU-FT-B1 5 way/5 way copper crab joint with
250 kcmil conductors 1CJ-250-7W7W-CU-FT-B1 7 way/7 way copper crab joint with
250 kcmil conductors 1CJ-350-3W3W-CU-FT-B1 3 way/3 way copper crab joint with
350 kcmil conductors 1CJ-350-5W5W-CU-FT-B1 5 way/5 way copper crab joint with
350 kcmil conductors 1CJ-350-7W7W-CU-FT-B1 7 way/7 way copper crab joint with
350 kcmil conductors 1CJ-500-3W3W-CU-FT-B1 3 way/3 way copper crab joint with
500 Kcmil conductors 1CJ-500-5W5W-CU-FT-B1 5 way/5 way copper crab joint with
500 kcmil conductors 1CJ-500-7W7W-CU-FT-B1 7 way/7 way copper crab joint with
500 kcmil conductors 1CJ-750-3W3W-CU-FT-B1 3 way/3 way copper crab joint with
750 kcmil conductors 1CJ-750-5W5W-CU-FT-B1 5 way/5 way copper crab joint with
750 kcmil conductors 1CJ-750-7W7W-CU-FT-B1 7 way/7 way copper crab joint with
750 kcmil conductors 1
Related test reports: EDR-5445, EDR-5446, EDR-5450, EDR-5452, 502-47332, 502-47339,502-47348.
Blown fuse after operation