Smart Lab Overview For Green Campus Interns 11 17 2010
Transcript of Smart Lab Overview For Green Campus Interns 11 17 2010
Smart Lab BuildingsSmart Lab Buildings
Marc Gomez, CIH, CSP, ARM, Interim Assistant Vice Marc Gomez, CIH, CSP, ARM, Interim Assistant Vice Chancellor, Facilities Management / Environmental Chancellor, Facilities Management / Environmental
Health & Safety Health & Safety Matt Gudorf Interim Campus Energy Manager, Energy Matt Gudorf Interim Campus Energy Manager, Energy
Project ManagerProject Manager
University of California, University of California, IrvineIrvine
Large research universityLarge research university$16M annual utilities budget$16M annual utilities budget
Lab buildings consume 2/3 of campus energyLab buildings consume 2/3 of campus energyMany energy initiatives to reduce carbon Many energy initiatives to reduce carbon
footprintfootprint
Campus Energy $avingsCampus Energy $avingsTeam SynergyTeam Synergy
SafetyManageme
nt
Visionary & Supportive
UpperManagement
Engineers
FacilityManager
s
Patience
Supportive Users/Researchers
AgendaAgenda
Smart Lab Overview Smart Lab Overview Centralized Demand Controlled Centralized Demand Controlled
VentilationVentilation Low Flow Fume HoodsLow Flow Fume Hoods Exhaust System OptimizationExhaust System Optimization Laboratory Smart Lighting ControlsLaboratory Smart Lighting Controls Smart Lab Case Study: Gross HallSmart Lab Case Study: Gross Hall
Balancing Lab Balancing Lab Safety & Safety &
Climate SafetyClimate Safety Create lab buildings that out perform Create lab buildings that out perform
ASHRAE 90.1 / CA Title 24 by 50%ASHRAE 90.1 / CA Title 24 by 50%
Combine energy initiatives such asCombine energy initiatives such as Centralized demand controlled ventilation Centralized demand controlled ventilation
(CDCV)(CDCV) Low flow (high performance) fume hoodsLow flow (high performance) fume hoods Reduced building exhaust stack airspeedsReduced building exhaust stack airspeeds Energy-efficient lightingEnergy-efficient lighting
Labs w/CDCVreal time lab air monitoring4 ach occupied2 ach unoccupied
Energy efficientlighting
Labs with low flow fume hoods(as appropriate)
Smart Lab Building Smart Lab Building ConceptConcept
Building Exhaust System
Smart Lab Smart Lab ParametersParameters
Current Best Practice Smart Lab Parameters
Air-handler/filtration airspeeds 400 ft/min. max 350 ft/min. max
Total system (supply + exhaust) pressure-drop 6 in. w.g. <5 in. w.g. (incl. dirty filter allow.)
Duct noise attenuators Few None
Occupied lab air-changes/hr. (ACH) 6 ACH 4 ACH w/contaminant sensing
Night air-change setback (unoccupied) No setback 2 ACH w/occupancy + contaminant sensing
+ no thermal inputs during setbacks
Low-flow/high-performance fume hoods No Yes, where hood density warrants
Fume hood face-velocities 100 FPM 70 FPM (low-flow hoods)
Fume hood face-velocities (unoccupied) 100 FPM 40 FPM (low-flow hoods)
Fume hood auto-closers None Where hood density high
Exhaust stack discharge velocity ~3,500 FPM Reduce or eliminate bypass air,
wind responsive controls
Lab illumination power-density 0.9 watt/SF 0.6 watt/SF w/LED task lighting
Fixtures near windows on daylight sensors No Yes
Energy Star freezers & refrigerators No Yes
Out-perform CA Title 24 20-25% 50%
AgendaAgenda
Smart Lab Overview Smart Lab Overview Centralized Demand Controlled Centralized Demand Controlled
VentilationVentilation Low Flow Fume HoodsLow Flow Fume Hoods Exhaust System OptimizationExhaust System Optimization Laboratory Smart Lighting ControlsLaboratory Smart Lighting Controls Smart Lab Case Study: Gross HallSmart Lab Case Study: Gross Hall
CDCV & Energy $avingsCDCV & Energy $avings Monitor Air Monitor Air
ContaminantsContaminants
ReduceReduce air changes per hour air changes per hour (ACH) (ACH)
if no contaminants detectedif no contaminants detected
IncreaseIncrease air changes per hour air changes per hour (ACH) (ACH)
when contaminants detectedwhen contaminants detected
Question: Is Increased Question: Is Increased ACH Safer?ACH Safer?
““Specification of Airflow Rates in Specification of Airflow Rates in Laboratories” by Tom Smith, Exposure Laboratories” by Tom Smith, Exposure Control TechnologiesControl Technologies
Conclusions: Conclusions: ACH as a metric for dilution is “too simplistic”ACH as a metric for dilution is “too simplistic” Need to take into account other factors that Need to take into account other factors that
lead to exposure, including contaminant lead to exposure, including contaminant generation rate, air mixing, etc.generation rate, air mixing, etc.
““Increased airflow may increase contaminant Increased airflow may increase contaminant generation and distribution throughout the generation and distribution throughout the space”space”
May lead to “false sense of safety”May lead to “false sense of safety”
Answer: Not NecessarilyAnswer: Not Necessarily
Alternatives to simply Alternatives to simply increasing ACH: increasing ACH:
Base air exchange rate on Base air exchange rate on contaminant generation contaminant generation
Review lab practices Review lab practices Attain proper air mix ratios Attain proper air mix ratios Reduce overall ACH to save Reduce overall ACH to save
energy and increase ACH as energy and increase ACH as needed via “smart controls”needed via “smart controls”
CA Ventilation Code CA Ventilation Code Requirements:Requirements:
Effective 1/2008Effective 1/2008 Refers to ASHRAE Refers to ASHRAE 62.1-200462.1-2004 New constructionNew construction No category for No category for university research university research labs labs
B “Research” Labs:B “Research” Labs: 0.43cfm/sf0.43cfm/sf Therefore: Therefore: 12 ft ceiling = 2.15 ACH12 ft ceiling = 2.15 ACH10 ft ceiling = 2.58 ACH10 ft ceiling = 2.58 ACH8 ft ceiling = 3.23 ACH8 ft ceiling = 3.23 ACH
B“Science Classroom”/L B“Science Classroom”/L (H-8): (H-8): 1 cfm/sf 1 cfm/sf
California California MechanicalMechanical
Code 2007Code 2007
In effect through In effect through December 2007December 2007Existing Existing constructionconstruction
B Labs:B Labs: 6 ACH 6 ACH H-8 LabsH-8 Labs: 1 cfm/sf: 1 cfm/sf Therefore:Therefore:12 ft ceiling = 5 ACH12 ft ceiling = 5 ACH10 ft ceiling = 6 ACH10 ft ceiling = 6 ACH8 ft ceiling = 7.5 ACH8 ft ceiling = 7.5 ACH
California Building California Building Code 2001Code 2001
CommentsCommentsVentilation Requirements Ventilation Requirements Code in Effect Code in Effect
Need “Alternative Means of Protection” from CA State Fire Marshal
for Less Than Minimum Required Ventilation
AgendaAgenda
Smart Lab Overview Smart Lab Overview Centralized Demand Controlled Centralized Demand Controlled
VentilationVentilation Low Flow Fume HoodsLow Flow Fume Hoods Exhaust System OptimizationExhaust System Optimization Laboratory Smart Lighting ControlsLaboratory Smart Lighting Controls Smart Lab Case Study: Gross HallSmart Lab Case Study: Gross Hall
Sash
AirfoilWork
Surface
Exhaust Plenum
Baffle
Increased Hood Depth
Operate safely at lower face velocities (i.e. 70 FPM rather than 100 FPM)
Low Flow (high performance) Low Flow (high performance) Fume HoodsFume Hoods
Benefits of Low Flow Fume Benefits of Low Flow Fume Hoods – UCI Study 2008Hoods – UCI Study 2008
Both traditional and low flow fume hoods Both traditional and low flow fume hoods UC Irvine subjected to 168 ASHRAE 110 UC Irvine subjected to 168 ASHRAE 110 teststests
Low flow hoods performed better than Low flow hoods performed better than standard hood at 80 & 100 fpm with fully standard hood at 80 & 100 fpm with fully open sash and at 18” open sashopen sash and at 18” open sash Tracer gas results were well under 0.1ppm “as Tracer gas results were well under 0.1ppm “as
used” ASHRAE criteriaused” ASHRAE criteria Low flow hoods save significant energy, Low flow hoods save significant energy,
particularly in constant volume systemsparticularly in constant volume systems Low flow hoods may be a good solution in Low flow hoods may be a good solution in
buildings with limited HVAC capacitybuildings with limited HVAC capacity
Flow & Cost ComparisonFlow & Cost ComparisonHVAC System HVAC System Type and Type and Fume Hood Fume Hood EquipmentEquipment
Flow at 100 fpm Flow at 100 fpm nominal face velocity nominal face velocity Annual Cost at $5 per Annual Cost at $5 per CFMCFM
Flow at 80 fpm Flow at 80 fpm nominal face velocity nominal face velocity Annual Cost at $5 per Annual Cost at $5 per CFMCFM
Flow at 70 fpm Flow at 70 fpm nominal face velocity nominal face velocity
Annual Cost at $5 per Annual Cost at $5 per CFMCFM
Constant Air Constant Air VolumeVolume
900 CFM900 CFM
$4500$4500720 CFM720 CFM
$3600$3600630 CFM630 CFM
$3150$3150
Variable Air Variable Air Volume (VAV)Volume (VAV)
Good: 682 CFM/$3410Good: 682 CFM/$3410
Poor: 851 CFM/$4255Poor: 851 CFM/$4255Good: 568 CFM/$2840Good: 568 CFM/$2840
Poor: 686 CFM/$3430Poor: 686 CFM/$3430Good: 511 CFM/$2555Good: 511 CFM/$2555
Poor: 604 CFM/$3020Poor: 604 CFM/$3020
VAV with ZPSVAV with ZPS Good: 492 CFM/$2460Good: 492 CFM/$2460
Poor: 558 CFM/$2790Poor: 558 CFM/$2790Good: 470 CFM/$2350Good: 470 CFM/$2350
Poor: 539 CFM/$2695Poor: 539 CFM/$2695Good: 462 CFM/$2310Good: 462 CFM/$2310
Poor: 530 CFM/$2650Poor: 530 CFM/$2650
VAV with ASCVAV with ASC 361 CFM361 CFM
$1,805$1,805343 CFM343 CFM
$1,715$1,715335 CFM335 CFM
$1,675$1,675
VAV with VAV with Perfect Sash Perfect Sash ManagementManagement
343 CFM343 CFM
$1,715$1,715331 CFM331 CFM
$1,655$1,655325 CFM325 CFM
$1,625$1,625
AgendaAgenda
Smart Lab Overview Smart Lab Overview Centralized Demand Controlled Centralized Demand Controlled
VentilationVentilation Low Flow Fume HoodsLow Flow Fume Hoods Exhaust System OptimizationExhaust System Optimization Laboratory Smart Lighting ControlsLaboratory Smart Lighting Controls Smart Lab Case Study: Gross HallSmart Lab Case Study: Gross Hall
Lab Building ExhaustLab Building Exhaust
Wind
Exhaust Fan Bypass Damper
Plenum
Fume Hood
Supply Fan Duct
Balcony
Re-Entrainment of Contaminated Air
Wind Tunnel TestingWind Tunnel TestingChallenge Conservative Challenge Conservative
AssumptionsAssumptions
Wind Tunnel TestingWind Tunnel Testing
Build model of Build model of campuscampus
Install model stacksInstall model stacks An abundance of air An abundance of air
sampling point sampling point receptorsreceptors
Slightly higher stacks, 4-5 feet
Variable speed fans (reduce exhaust fan flows)Install wind responsive equipment (if needed)
Reduce or eliminate bypass air
Exhaust Energy Reduction Exhaust Energy Reduction SolutionsSolutions
Original Stack Height
New Stack Height
Croul HallCroul Hall
Install variable Install variable frequency drives frequency drives (VFD)(VFD)
8’ Stack 8’ Stack ExtensionsExtensions
Static Pressure Static Pressure ResetReset
Energy Savings: Energy Savings: 344,000 kWh344,000 kWh
AgendaAgenda
Smart Lab Overview Smart Lab Overview Centralized Demand Controlled Centralized Demand Controlled
VentilationVentilation Low Flow Fume HoodsLow Flow Fume Hoods Exhaust System OptimizationExhaust System Optimization Laboratory Smart Lighting Laboratory Smart Lighting
ControlsControls Smart Lab Case Study: Gross HallSmart Lab Case Study: Gross Hall
Lab Area LPD from 1.1 to 0.6
Lab Prep LPD
from 1.0 to 0.4
Prep Room LPD from 2.0 to 1.0
Corridor LPD from 0.6 to 0.3
Lighting Controls Lighting Controls Reduce Power Density by Reduce Power Density by
50%50%
Lamp and BallastLamp and Ballast Replace existing 32 watt T8 lamps Replace existing 32 watt T8 lamps
with 25 watt T8 lampswith 25 watt T8 lamps Replace existing NLO instant start Replace existing NLO instant start
ballast with RLO program start ballast with RLO program start ballastballast In renovation projects, use reduced light In renovation projects, use reduced light
output (RLO) electronic ballasts in output (RLO) electronic ballasts in building spaces lighted with fluorescent building spaces lighted with fluorescent lamps where slightly lower light levels lamps where slightly lower light levels will suffice. RLO ballasts produce will suffice. RLO ballasts produce approximately 75% of rated light output approximately 75% of rated light output and use 12% to 20% less power than and use 12% to 20% less power than standard NLO ballasts. standard NLO ballasts.
Lower Blinds Lower Blinds to Allow for to Allow for
DaylightingDaylighting
Fixture Closest to the Fixture Closest to the Window is OFFWindow is OFF
Manual Switch Manual Switch to Occupancy to Occupancy
SensorSensor
50% Auto On - Manual to 50% Auto On - Manual to 100% 100%
A-B CIRCUITING
Auto on to 50% Light Auto on to 50% Light LevelLevel
Gross Hall Perforated Gross Hall Perforated BlindsBlinds
High performance High performance glazingglazing
Perforated blinds Perforated blinds allow diffuse light allow diffuse light to enter the space to enter the space when closedwhen closed
Reduced glareReduced glare Increased Increased
occupant controloccupant control
AgendaAgenda
Smart Lab Overview Smart Lab Overview Centralized Demand Controlled Centralized Demand Controlled
VentilationVentilation Low Flow Fume HoodsLow Flow Fume Hoods Exhaust System OptimizationExhaust System Optimization Laboratory Smart Lighting ControlsLaboratory Smart Lighting Controls Smart Lab Case Study: Gross Smart Lab Case Study: Gross
HallHall
Bill & Sue Gross HallBill & Sue Gross HallA Smart & Sustainable A Smart & Sustainable
DesignDesign
Gross Hall FeaturesGross Hall Features Centralized Demand Controlled Ventilation - Centralized Demand Controlled Ventilation - real-real-
time indoor air quality monitoring, varies the ventilation time indoor air quality monitoring, varies the ventilation raterate
Occupancy Based Controls -Occupancy Based Controls - controls both ventilation controls both ventilation system & lightingsystem & lighting
Natural VentilationNatural Ventilation -- operable windows linked with operable windows linked with mechanical ventilationmechanical ventilation
Smart Lighting Controls - Smart Lighting Controls - daylighting sensors used with daylighting sensors used with perforated blinds perforated blinds
Energy Star Equipment - Energy Star Equipment - freezers, refrigerators, ice freezers, refrigerators, ice machines & copiersmachines & copiers
Air Handling System - Air Handling System - larger components allow a low larger components allow a low velocity system, reducing pressure drops throughout the velocity system, reducing pressure drops throughout the system.system.
Building Exhaust - Building Exhaust - right sized exhaust system eliminates right sized exhaust system eliminates bypass airbypass air
Right Sized Air Handlers & Right Sized Air Handlers & ExhaustExhaust
Operable Windows Operable Windows Interlocked with HVAC Interlocked with HVAC
SystemSystem
Smart Lab “Safety Net”Smart Lab “Safety Net”
Phoenix Controls Phoenix Controls Celeris® Display Celeris® Display PanelsPanels Currently in use Currently in use
at Gross Hallat Gross Hall Programmed to Programmed to
display ACH, display ACH, occupancy status occupancy status and ventilation and ventilation offset offset information information within labwithin lab
Smart Lab “Safety Net”Smart Lab “Safety Net” Emergency General Emergency General
Ventilation Purge Ventilation Purge “Red Button”“Red Button” Fully opens general Fully opens general
exhaust ventilation exhaust ventilation valvesvalves
Response within Response within minutesminutes
Integrated alarm Integrated alarm systemsystem
Deactivates when Deactivates when button is pulled outbutton is pulled out
Smart Lab “Safety Net”Smart Lab “Safety Net”
Occupant TrainingOccupant Training Occupant welcome Occupant welcome
brochurebrochure ““Red Button” Red Button”
signagesignage
Estimated annual energy savings:• 890,080 kWh electrical with 193 kW demand
reduction• 22,464 therms of natural gas
Estimated annual energy cost savings:• $110,980 at $0.105/kWh and $0.78/therm
Savings by Design payment of $397,836 Exceeding Title 24 by 50%
Bid as a LEED New Construction (NC) Silver Design Build contractor proposed to increase the sustainable features to achieve LEED NC
Gold certification
Smart Labs Smart Labs Considerations/ChallengesConsiderations/Challenges
MaintenanceMaintenance Mechanical Repairs to Phoenix Mechanical Repairs to Phoenix
system (poppets, valves, etc)system (poppets, valves, etc) Software updates/adjustments to Software updates/adjustments to
Johnson ControlsJohnson Controls Sensor calibration/replacementSensor calibration/replacement Calibration of sash sensors, zone Calibration of sash sensors, zone
presence sensors, etc.presence sensors, etc.
Smart Labs Smart Labs Considerations/ChallengesConsiderations/Challenges
ConsiderationsConsiderations Lack of “universal” CDCV sensor for Lack of “universal” CDCV sensor for
all chemicals all chemicals CA requires variance from Cal/OSHA CA requires variance from Cal/OSHA
to allow use of low flow hoodsto allow use of low flow hoods Risk Assessment of lab operations Risk Assessment of lab operations
needed to select the appropriate needed to select the appropriate smart controlssmart controls
Life cycle cost/payback analysis Life cycle cost/payback analysis needed!needed!
Questions?Questions?
Information Presented Information Presented TodayToday
UC Irvine’s Smart Lab Retrofit GuideUC Irvine’s Smart Lab Retrofit Guide http://slidesha.re/cXtEOzhttp://slidesha.re/cXtEOz
Smart Lab Buildings PresentationSmart Lab Buildings Presentation http://slidesha.re/c9o9cfhttp://slidesha.re/c9o9cf
CDCV CDCV The Commissioning, Lab The Commissioning, Lab Safety, and Energy Savings ToolSafety, and Energy Savings Tool http://slidesha.re/ccmIPDhttp://slidesha.re/ccmIPD
Thank You!Thank You!