RECORD OF FIRE SAFETY RISK ASSESSMENT
Building Name & Use:
Address:
Postcode:
Printing works and warehouse area
Press Lane, 21 Ink Street, Presstown. PR3 3SS
Name of person(s) with fire safety duties: Mr T Jones (Managing Director)
Name and contact details of assessor: Mr T Jones (Managing Director) as above
Date ofAssessment:
3rd April 2011Assessorsignature:
STEP 1 IDENTIFY FIRE HAZARDS
Refer to Part One of the relevant Fire Safety Risk Assessment guide (see list on back page)
Sources of ignition, e.g. electrical fittings, smoking, heating, open flames
Electrical appliances, printing machinery, dryers.Gas heating system (covered by maintenance contract).LPG powered forklift truck (covered by maintenance contract).Hot works.Smoking.Deliberate fire setting.
Sources of fuel, eg, furniture, textiles and fabrics
Large quantities of paper and flammable liquids.
Sources of oxygen, eg, ventilation
Normal ventilation in office area.Roller shutter door in warehouse area.
YES NOAction required (Please tick)If you answered YES, record Action Points at STEP 4
STEP 2 IDENTIFY PEOPLE AT RISK
Refer to Part One of the relevant Fire Safety Risk Assessment guide
List all persons potentially at risk from fire, including employees, tenants, visitors and contractors
At time of assessment 18 employees, 12 in warehouse and 6 in office.Working hours from 0800 to 1800. (Occasionally requirement to work late).All employees familiar with the area, none have any impairments that need any special consideration inrelation to this assessment.
Occasionally contractors and maintenance staff would carry out inspections and maintenance.
YES NOAction required (Please tick)If you answered YES, record Action Points at STEP 4
-
7/28/2019 Small Factory example.pdf
2/7
2 of 7
STEP 3 EVALUATE, REMOVE, REDUCE AND PROTECT FROM RISK
Refer to Part One of the relevant Fire Safety Risk Assessment guideLikelihood of a fire starting
Printing machinery can become very hot during high production times.
Lack of maintenance to dryers could lead to increased fire risk.Flammable liquids stored in lockable cabinet. Only small amounts used at a time, although soaked ragskept beside machinery are not being disposed of properly.Some hot works carried out by contractors on an intermittent basis, no procedures in place to manage thiswork.
Evaluate the risk to people
Some pallets awaiting uplift were partially blocking the rear fire exit.Areas at bottom of fire escape stairs being used to store paper and cardboard boxes.Some local knowledge of deliberate fire setting in area. Site has uncovered skips but as they are situated
well away from the building, reduces potential for fire spread.
YES NOAction required (Please tick)If you answered YES, record Action Points at STEP 4
STEP 4 RECORD, PLAN, INFORM, INSTRUCT AND TRAIN
Refer to Part One of the relevant Fire Safety Risk Assessment guideFire Safety Policy (Further guidance on Fire Safety Policy in Part Two of guide)
No fire management policy.
A No smoking policy in place. Smoking shelter approx 10 metres from building.
Emergency fire action plan
Staff fire evacuation procedures are in place but no record of last fire drill was evident.
Fire safety information and training
Staff given general fire safety training on induction, but no refresher training being carried out.Staff not trained in use of extinguishers.
YES NOAction required (Please tick)If you answered YES, record Action Points at STEP 4
-
7/28/2019 Small Factory example.pdf
3/7
3 of 7
STEP 4 RECORD, PLAN, INFORM, INSTRUCT AND TRAIN (continued)
Refer to Part One of the relevant Fire Safety Risk Assessment guideFire Drills
No records of staff evacuation drills are being kept.
Maintenance of safety measures (For further guidance see Appendix A of relevant Risk Assessmentguide)
Fire alarm system installed but no records of testing and maintenance.Fire exit routes not clearly indicated with signs.
Sufficient provision of fire extinguishers but some not wall mounted or on suitable stands.Emergency lighting not provided in rear fire escape stairway.Spare LPG cylinder kept in external locked cage.Sufficient provision of escape routes, however two existing doors opening into main fire escape staircaseare not fire resisting.
Recording information and keeping records
All electrical appliances inspected and tested in 2010.Records kept and available for heating system maintenance.Records kept and available for forklift maintenance.
Records kept and available for maintenance of printers and dryers.Staff training records available for induction but none available for refresher training.No evidence of fire evacuation drills.
YES NOAction required (Please tick)If you answered YES, record Action Points at STEP 4
-
7/28/2019 Small Factory example.pdf
4/7
4 of 7
The assessor completing the following section should prioritise remedial measures, based on the level ofrisk.
Priority ratings and suggested timescales:
Low (L) 3 6 months Medium (M) Up to 3 months High (H) As soon as possible
STEP 4 ACTION POINTS
PriorityPerson
responsibleCompletion date
Note: Please print additional sheet if required
Introduce system for hot working bycontractors. Consider hot workpermit system.
Fit two fire resisting doors with selfclosures.
A Fire Management policy isrequired to identify persons withresponsibilities.
Review storage of flammableliquids & disposal of soaked rags.
Clear any pallets, paper &cardboard from fire exits and keeparea clear at all times.
Implement inspection andmaintenance programme fordryers.
Provide emergency lighting asrequired to rear escape stairway.
High May 2011ProductionManager
High
May 2011ProductionManagerHigh
May 2011ProductionManager
High
May 2011
High ManagingDirector
ProductionManager
May 2011
July 2011ProductionManager
Medium
-
7/28/2019 Small Factory example.pdf
5/7
5 of 7
The assessor completing the following section should prioritise remedial measures, based on the level ofrisk.
Priority ratings and suggested timescales:
Low (L) 3 6 months Medium (M) Up to 3 months High (H) As soon as possible
STEP 4 ACTION POINTS
PriorityPerson
responsibleCompletion date
Note: Please print additional sheet if required
Provide fire exit signage to clearly
identify exit routes.
Provide wall mounts or suitable
stands for fire extinguishers.
Provide refresher training to all staffto bring to their attention the fireprecautions and evacuationprocedures for the premises. Keeprecords of training.
Carry out and record details of fireevacuation drills to determine
suitability of arrangements.
Carry out and record details ofregular tests of fire alarm.
Consider training some employeesin the use of fire extinguishers.
Medium July 2011ManagingDirector
High
May 2011ProductionManagerHigh
May 2011ProductionManager
High
May 2011
Medium ProductionManager
ManagingDirector
July 2011
July 2011ManagingDirector
Medium
-
7/28/2019 Small Factory example.pdf
6/7
6 of 7
Review the fire risk assessment if there is a reason to suspect it is no longer valid or if there hasbeen a significant change in the matters to which it relates.
Reference Part One of the relevant sector specific, fire safety risk assessment guide
STEP 5 ASSESSMENT REVIEW
Review date April 2012 Review by
Reason for review: Annual review.
Outcomes of review
-
7/28/2019 Small Factory example.pdf
7/7
7 of 7
FIRE SAFETY RISK ASSESSMENT GUIDES
The following premises guides are available from Northern Ireland Fire & Rescue websitewww.nifrs.org. Follow the Make sure youre Fire Safe link and go to GuidanceDocuments. These can be downloaded from the Communities and Local Government
section.
1 Offices and Shops;
2 Factories and Warehouses;
3 Sleeping Accommodation;
4 Residential Care Premises;
5 Educational Premises;
6 Small and Medium Places of Assembly;
7 Large Places of Assembly;
8 Theatres, Cinemas and Similar Premises;
9 Open Air Events and Venues;
10 Healthcare Premises;
11 Transport Premises and Facilities;
12 Animal Premises and Stables;
13 Means of Escape for Disabled People (Supplementary Code); and
14 Reducing the Number of False Alarms from Detection and Alarm Systems.
Adapted from original materials created by the Scottish Centre for HealthyWorking Lives and the Scottish Fire and Rescue Services