Sistemas de Osmosis Inversa

download Sistemas de Osmosis Inversa

of 64

Transcript of Sistemas de Osmosis Inversa

  • 7/27/2019 Sistemas de Osmosis Inversa

    1/64

    Dulcosmose reverse osmosis system

    ecoPRO series

    Assembly and operating instructions

    BA_PMA_UO_0018_SW

    ecoPRO__ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __

    Please enter the identity code of the device here

    Original Operating Instructions (2006/42/EC)Part no. 986821 BA UO 012 02/13 EN

    Please carefully read these operating instructions before use! Do not discard!The operator shall be liable for any damage caused by installation or operating errors!Technical changes reserved.

  • 7/27/2019 Sistemas de Osmosis Inversa

    2/64

    Table of contents1 About this System ................................................................ 4

    1.1 Correct and proper use ................................................ 4

    1.2 Switching off in emergencies ....................................... 4

    2 Safety Chapter...................................................................... 52.1 Explanation of the safety information............................ 52.2 Users' qualifications...................................................... 7

    2.3 Dulcosmose safety instructions ................................. 8

    3 Storage and Transport ....................................................... 104 System Overview and Description of Function .................. 115 Assembly and Installation .................................................. 13

    5.1 Preconditions for assembly ........................................ 13

    5.2 Assembly ................................................................... 14

    5.3 Installation .................................................................. 14

    5.3.1 Systems with cleaning system ................................ 14

    5.3.2 Systems without cleaning system ........................... 156 Control Elements ............................................................... 166.1 Arrangement of control elements ............................... 16

    6.2 Function ..................................................................... 17

    6.3 Optional chemical cleaning ........................................ 17

    6.4 Display ....................................................................... 18

    6.5 Operating status display and parameter settings .. ... . 19

    6.5.1 Change access code .............................................. 21

    6.5.2 Set the language ..................................................... 21

    6.5.3 Set level control of permeate tank .......................... 22

    6.5.4 Set cell-constant conductivity sensor ...................... 22

    6.5.5 Set the temperature compensation of the conductivity measurement .................................................. 22

    6.5.6 Set compensation constant (Cal.-factor) ................ 22

    6.5.7 Set maximum conductivity ...................................... 22

    6.5.8 Wait time and maximum number of attempts incase of water shortage ........................................... 23

    6.5.9 Set rinse time of system start ................................. 23

    6.5.10 Set start-up time of high pressure pump ............... 24

    6.5.11 Set maximum flushing time ................................... 24

    6.5.12 Set maximum filling time of cleaning tank ............. 24

    6.5.13 Set frequency and duration of raw water rinse inoperation . ............................................................. 24

    6.5.14 Raw water rinsing at end of operation .................. 25

    6.5.15 Permeate rinse, set rinse time .............................. 25

    6.5.16 Cleaning pump for chemical cleaning ................... 25

    6.5.17 Set maximum idle time ......................................... 25

    6.5.18 Set interval operating time .................................... 25

    6.5.19 Set analogue output .............................................. 26

    6.5.20 Pause function ...................................................... 26

    6.5.21 Set minimum mains voltage .................................. 26

    6.5.22 Set mains voltage fault acknowledgement ....... .... 26

    6.6 "Fault" switching input ................................................ 266.7 "Metering pump" control output ................................. 26

    6.8 Alarm signal relay ...................................................... 27

    Table of contents

    2

  • 7/27/2019 Sistemas de Osmosis Inversa

    3/64

    6.9 Chemical cleaning ..................................................... 27

    7 Commissioning .................................................................. 288 Maintenance ...................................................................... 30

    8.1 Regular maintenance ................................................. 31

    8.2 Replace filter cartridge or bag .................................... 31

    8.3 Chemical cleaning and disinfection ........................... 32

    8.3.1 Cleaning .................................................................. 34

    8.3.2 Disinfection ............................................................. 36

    9 Troubleshooting ................................................................. 399.1 Direct fault in the system ........................................... 39

    9.2 Fault messages at the controller ................................ 39

    9.2.1 Fault alert: Water pressure too low ......................... 39

    9.2.2 Fault alert: Water pressure filter? ........................... 40

    9.2.3 Fault alert: Other fault ............................................. 40

    9.2.4 Fault alert: High pressure pump, cleaning pump ... . 40

    9.2.5 Fault alert: Rinse free time expired ......................... 41

    9.2.6 Fault alert: Filling time exceeded ............................ 419.2.7 Fault alert: Temperature measurement .................. 41

    9.2.8 Fault alert: Voltage supply too low .......................... 41

    9.2.9 Fault alert: Level switch .......................................... 42

    9.2.10 Fault alert: Memory error ...................................... 42

    9.2.11 Fault alert: Default setting ..................................... 42

    9.2.12 Warning message: Cleaning tank empty .............. 42

    9.2.13 Warning message: Water pressure too low .......... 42

    10 Decommissioning ............................................................... 4310.1 System anti-corrosion measures prior to shutdown

    with cleaning system ................................................ 43

    10.2 System anti-corrosion measures prior to shutdownwithout cleaning system ........................................... 44

    10.3 Disposal ................................................................... 45

    11 Technical Data ................................................................... 4612 Spare Parts List.................................................................. 4813 Appendix............................................................................. 50

    13.1 Checklist 1 ............................................................... 50

    13.2 Checklist 2 ............................................................... 51

    13.3 Default setting of Dulcosmose controller ............... 52

    13.4 Terminal wiring diagram .......................................... 55

    13.5 Terminal arrangement of Dulcosmose controller .. . 56

    13.6 Circuit diagram of Dulcosmose controller .............. 57

    13.7 Switching inputs Dulcosmose controller ................ 58

    13.8 Control outputs of Dulcosmose controller .............. 58

    13.9 Alarm output of Dulcosmose controller .................. 59

    13.10 EC Declaration of Conformity................................. 59

    14 Index................................................................................... 60

    Table of contents

    3

  • 7/27/2019 Sistemas de Osmosis Inversa

    4/64

    1 About this SystemThe ecoPRO 100-550 and ecoPRO 600-2700 series require feedwater with the following values/properties:

    ecoPRO 100-550 ecoPRO 600-2700Max. salt content 650mg/l* Max. salt content 1000mg/l*

    pH value 3-10 pH value 3-10

    Blocking index < 3 Blocking index < 3

    Free chlorine < 0.1 mg/l Free chlorine < 0.1 mg/l

    Sum Fe, Mn < 0.2 mg/l Sum Fe, Mn < 0.2 mg/l

    Total hardness < 0.1 dH Total hardness < 0.1 dH

    Bacterial count < 100 KBE/ml Bacterial count < 100 KBE/ml

    Turbidity < 0.5 NTU Turbidity < 0.5 NTU

    CSB < 5 mg/l as O2 CSB < 5 mg/l as O2

    * Different salt content influences the performance data accordinglyThe systems are fitted with a ProMaqua Dulcosmose controller.The controller can be used for manual or level-controlled operation.

    1.1 Correct and proper usen A reverse osmosis system from the ecoPRO series is solely

    intended for making pure water from drinking water. This is no

    longer suitable for human consumption.n All other uses or retrofits are only permissible after consultation

    with ProMaqua GmbH Heidelberg.

    n You are obliged to make sure the information in the operatinginstructions relating to the different phases of the unit's servicelife is observed!

    1.2 Switching off in emergenciesIn emergencies, switch off the device with the main switch on thecontroller or using the emergency stop switch to be installed by theoperator.

    About this System

    4

  • 7/27/2019 Sistemas de Osmosis Inversa

    5/64

    2 Safety ChapterNon-observance of the safety information

    n Non-observance of the safety information can result in dangerto persons as well as harm to the environment and damage tothe system. Failure to observe the safety information can leadto the loss of any rights to claim for damages. Moreover, failure

    to observe the information can lead to the following hazards: Failure of important system functions

    Failure of prescribed methods for maintenance and repairs

    Danger to persons due to electrical and mechanical effects

    Please observe the relevant national regulations and guidelines atevery phase of the device's service life!

    2.1 Explanation of the safety informationThese operating instructions provide information on the technical

    data and functions of the product. These operating instructions provide detailed safety information and are provided as clear step-by-step instructions.

    The safety information and notes are categorised according to thefollowing scheme. A number of different symbols are used todenote different situations. The symbols shown here serve only asexamples.

    DANGER!Nature and source of the dangerConsequence: Fatal or very serious injuries.

    Measure to be taken to avoid this dangerDanger!

    Denotes an immediate threatening danger. If this isdisregarded, it will result in fatal or very seriousinjuries.

    WARNING!Nature and source of the dangerPossible consequence: Fatal or very serious injuries.

    Measure to be taken to avoid this danger

    Warning!

    Denotes a possibly hazardous situation. If this isdisregarded, it could result in fatal or very seriousinjuries.

    Introduction

    Safety Chapter

    5

  • 7/27/2019 Sistemas de Osmosis Inversa

    6/64

    CAUTION!Nature and source of the dangerPossible consequence: Slight or minor injuries, material damage.

    Measure to be taken to avoid this danger

    Caution! Denotes a possibly hazardous situation. If this is

    disregarded, it could result in slight or minor injuries. May also be used as a warning about materialdamage.

    NOTICE!Nature and source of the dangerDamage to the product or its surroundings

    Measure to be taken to avoid this danger

    Note!

    Denotes a possibly damaging situation. If this isdisregarded, the product or an object in its vicinitycould be damaged.

    Type of informationHints on use and additional information

    Source of the information, additional measures

    Information!

    Denotes hints on use and other useful information.It does not indicate a hazardous or damaging situation.

    Safety Chapter

    6

  • 7/27/2019 Sistemas de Osmosis Inversa

    7/64

    2.2 Users' qualificationsWARNING!Danger of injury with inadequately qualified personnel!The operator of the plant / device is responsible forensuring that the qualifications are fulfilled.If inadequately qualified personnel work on the unit orloiter in the hazard zone of the unit, this could result indangers that could cause serious injuries and materialdamage.

    All work on the unit should therefore only be conducted by qualified personnel.

    Unqualified personnel should be kept away fromthe hazard zone

    Training DefinitionInstructed personnel An instructed person is deemed to be a person who has been instructed and,

    if required, trained in the tasks assigned to him/her and possible dangers thatcould result from improper behaviour, as well as having been instructed in therequired protective equipment and protective measures.

    Trained user A trained user is a person who fulfils the requirements made of an instructedperson and who has also received additional training specific to the systemfrom ProMinent or another authorised distribution partner.

    Trained qualified personnel

    A qualified employee is deemed to be a person who is able to assess thetasks assigned to him and recognize possible hazards based on his/hertraining, knowledge and experience, as well as knowledge of pertinent regulations. The assessment of a person's technical training can also be based onseveral years of work in the relevant field.

    Electrician Electricians are deemed to be people, who are able to complete work on electrical systems and recognize and avoid possible hazards independently basedon his/her technical training and experience, as well as knowledge of pertinentstandards and regulations.

    Electricians should be specifically trained for the working environment inwhich the are employed and know the relevant standards and regulations.

    Electricians must comply with the provisions of the applicable statutory directives on accident prevention.

    Customer Service department

    Customer Service department refers to service technicians, who havereceived proven training and have been authorised by ProMinent to work onthe system.

    Note for the system operatorThe pertinent accident prevention regulations, as wellas all other generally acknowledged safety regulations,must be adhered to!

    Safety Chapter

    7

  • 7/27/2019 Sistemas de Osmosis Inversa

    8/64

    2.3 Dulcosmose safety instructionsWARNING!Risk and Safety StatementsPossible consequence: Fatal or very serious injuries

    Observe the safety data sheets

    When handling the chemicals required for thesystem, we specifically refer you to the Risk andSafety Statements (R/S statements)

    Detailed information on this is contained in thesafety data sheets of the chemicals used

    The system operator must ensure that these safetydata sheets are available and that they are kept upto date

    WARNING!Unauthorised access!Possible consequence: Fatal or very serious injuries

    Measure: Ensure that there can be no unauthorised access to the unit

    WARNING!Operating errors!Possible consequence: Fatal or very serious injuries

    The unit should only be operated by adequatelyqualified and technically expert personnel

    Please also observe the operating instructions forcontrollers and fittings and any other componentgroups, such as sensors, sample water pumps ...

    The operator is responsible for ensuring that personnel are qualified

    WARNING!Live parts!Possible consequence: Fatal or very serious injuries

    Measure: The device must be disconnected from

    the power supply before it is opened Disconnect damaged, defective or manipulated

    devices from the power supply

    Safety Chapter

    8

  • 7/27/2019 Sistemas de Osmosis Inversa

    9/64

    CAUTION!Operating manual/spare partsPossible consequence: Slight or minor injuries, material damage

    The operating safety of the system delivered canonly be only guaranteed if the assembly and operating instructions are used compliant with theintended use described

    The limit values stipulated in the technical datamust never be exceeded in any circumstances

    The system must not be operated outside of theconditions described in the technical data

    Use original spare parts and accessories authorised by the manufacturer to increase safety Use ofother parts nullifies all liability for any consequences arising therefrom

    Safety Chapter

    9

  • 7/27/2019 Sistemas de Osmosis Inversa

    10/64

    3 Storage and Transportn Users' qualification: Instructed person, see Chapter 2.2

    Users' qualifications on page 7

    NOTICE!Storage > 3 monthsDamage to the product or its surroundings

    If the system is stored for more than 3 months afterdelivery then this may have a negative effect on thereverse osmosis membranes. The permeate output,rate of yield and salt retention rate may all be worsened in consequence. Anti-corrosion measures prior toshutdown should therefore be performed in accordance to the instructions for storage periods > 3months.

    n The system may only be packaged and transported uprightn Store and transport the system it its original packaging

    n The system must not be stored in the open or at temperaturesbelow 5 C or above 45 C .

    Storage and Transport

    10

  • 7/27/2019 Sistemas de Osmosis Inversa

    11/64

    4 System Overview and Description of Function

    I.

    II.

    III.

    BA_PMA_UO_0010_SW

    Fig. 1: Flow diagram of an ecoPRO system without cleaning systemII.

    III.

    I.

    BA_PMA_UO_0011_SW

    Fig. 2: Flow diagram of an ecoPRO system with cleaning system

    I. Raw water (drinking water)II. Permeate (ultra-pure water)III. Concentrate (concentrated water)1 Particle filter

    2 Manometer for differential pressure3 Solenoid valve, inlet valve4 Pressure switch6 High pressure pump8 Manometer for operating pressure9 Pressure pipe10 Spiral winding module11 Conductivity sensor12 Dulcosmose controller

    13 Flow meter for permeate14 3-way ball valve15 Ball valve16 Flow meter for concentrate

    17 3-way ball valve18 Ball valve19 PE cleaning tank20 Drain ball valve21 Cleaning pump22 Ball retaining valve26 Laboratory ball valve27 Angled retaining valve

    1. The raw water entering the system flows through a particlefilter (1) with a pore size of 5m to remove physical impurities(particles)

    The pressure drop at the filter can be determined by the

    upstream and downstream manometers (2), which thenallows conclusions to be drawn on the degree of foulingto the filter.

    System overview

    Functional description

    System Overview and Description of Function

    11

  • 7/27/2019 Sistemas de Osmosis Inversa

    12/64

    2. The downstream solenoid valve (3) is closed when thesystem is switched off

    This is necessary because otherwise permeate would beproduced by the pressure of feed water, even when thesystem is switched off. The system would then be "operated" at an incorrect operating point, resulting in poorpermeate quality.

    3. The pressure switch (4) continuously checks the feed waterpressure because if the inlet pressure is too low then thiswould negatively affect the performance of the system

    If the pressure drops below a preset minimum then thesystem is switched off.

    4. The high pressure pump (6) feeds the raw water at a correspondingly high pressure to the spiral winding modules in thepressure pipes (9,10); a partial flow (ultra-pure water, permeate) flows over the membrane and a second partial flow(concentrated water, concentrate) is fed to the drain or isrecirculated

    5. The angled retaining valve (27) thereby prevents counterpressure at the concentrate outlet by means of a high pressure pump

    6. The permeate and the flow volume of the concentrate can beset using control valves (15,18)

    7. The partial flows can be read off at the flow meter (13,16)8. The microprocessor controller (12) monitors function and dis

    plays malfunctions

    9. The controller calculates the quality (salt content) of the purewater using a conductivity measuring cell (11)

    It thereby continuously checks the salt content of the per

    meate and stops the system if a limit value is exceeded

    System Overview and Description of Function

    12

  • 7/27/2019 Sistemas de Osmosis Inversa

    13/64

    5 Assembly and Installationn User qualification, mechanical assembly: trained qualified per

    sonnel, see Chapter 2.2 Users' qualifications on page 7

    n User qualification, electrical installation: Qualified electrician,see Chapter 2.2 Users' qualifications on page 7

    n During assembly and installation of the system, the local instal

    lation regulations, general regulations and the technical data ofthe system must be observed.

    The position numbers refer to the flow diagram inChapter System overview on page 11

    5.1 Preconditions for assemblyNOTICE!Preconditions for assembly The location of the system must be dry and free of

    frost and the protection of the system from chemicals, dyes, vapours and weather conditions mustbe guaranteed. The ambient temperature must notexceed 45 C, even before start-up. Immediateheat sources, e.g. radiant heaters, as well as directsunlight, must be avoided

    The minimum raw water pressure must be at least

    3 bar and the maximum pressure must not exceed6 bar. Pressure fluctuations of more than +/- 0.5bar are not permitted. It might therefore be necessary to install a pressure reducer in the supply lineof the reverse osmosis system

    A sewer junction must be available to drain off theconcentrate. This must be acid and alkali resistantand large enough to allow the respective volumeflow of concentrate to drain off freely

    The power supply must have sufficient output

    Assembly and Installation

    13

  • 7/27/2019 Sistemas de Osmosis Inversa

    14/64

    5.2 AssemblyCAUTION!Possible consequence: Slight or minor injuries, material damage.

    The reverse osmosis system must be placed onto

    a solid, even surface . The bearing capacity of the surface must be at

    least the weight of the system + the weight ofthe water

    The system must be fixed to the ground at itsinstallation location

    A shut-off valve must be mounted between thesystem and the water supply

    NOTICE! Place the system near to a water connection and

    sewer junction To reduce the switching rate of the system to a

    minimum during irregular permeate consumption,and to fully exploit the total power (daily output) ofthe system, we recommend installation of a permeate storage tank

    5.3 InstallationWARNING!The electrical connection as well as all other electricalwork must be carried out by a qualified electrician.

    n Connect the system to the water line

    n Connect the system to the power supply Terminal arrangement 230 volt version (No. 1004192): on page 55accordingto the terminal plan

    5.3.1 Systems with cleaning systemCAUTION!The system is designed so that when in operation, thepermeate flows off freely into a permeate tank. If aconsumer is directly connected to the system thenmake sure that no counterpressure can build up in thepermeate line when stopping the system. This woulddestroy the membranes. We recommend you install areturn valve in the line.

    1. Connect the permeate outlet with the permeate tank or consumer2. If installed, connect the level switch of the permeate tank tothe controller

    Assembly and Installation

    14

  • 7/27/2019 Sistemas de Osmosis Inversa

    15/64

    3. Connect the concentrate connection to the drain4. Establish the power supply5. Set the 3-way valve (14) Fig. 2 at the permeate outlet to the

    "cleaning tank" position

    6. Set the 3-way valve (17) Fig. 2 at the concentrate outlet tothe "drain" position

    7. Connect the drain valve (21) Fig. 2 of the cleaning tank to thedrain by a hose and then open it

    5.3.2 Systems without cleaning system1. Provisionally connect the concentrate outlet to the drain2. If installed, connect the level switch of the permeate tank to

    the controller (see terminal plan Terminal arrangement230 volt version (No. 1004192): on page 55)

    3. Connect the concentrate connection to the drain4. Establish the power supply

    Assembly and Installation

    15

  • 7/27/2019 Sistemas de Osmosis Inversa

    16/64

    6 Control ElementsThe position numbers refer to the flow diagram inChapter System overview on page 11

    6.1 Arrangement of control elements

    1

    2

    3

    4

    69,10

    11

    12

    1315

    16

    18

    279

    ecoPRO 100/200

    1

    2

    34

    6

    9,10

    11

    12

    1315

    16

    18

    27 29

    ecoPRO 300/550 BA_PMA_UO_0012_SW

    Fig. 3: ecoPRO 100/200/300/550

    1

    2

    3

    4

    6

    9,10

    11

    1213

    15

    16

    18

    26

    27 29

    ecoPRO 600 - 1500

    1

    22

    34

    68

    9, 10

    11

    12

    13

    15

    16

    1826

    27

    ecoPRO 1800 - 2700BA_PMA_UO_0013_SW

    Fig. 4: ecoPRO 600/900/1200/1500/1800/2400/2700 without cleaning station

    Control Elements

    16

  • 7/27/2019 Sistemas de Osmosis Inversa

    17/64

    1

    22

    3

    4

    5

    6

    8

    20

    21

    22

    2315

    16

    17

    18

    19

    11

    13

    14

    27 12

    9

    10

    A

    B

    C

    1

    2

    3

    4

    6 8

    9, 10

    11

    1213

    14

    15

    1617

    18

    23

    26

    27 29

    ecoPRO 600 - 1500 CS ecoPRO 1800 - 2700 CSBA_PMA_UO_0019_SW

    Fig. 5: ecoPRO 600/900/1200/1500/1800/2400/2700 with cleaning station

    6.2 FunctionIn manual operating mode, the Dulcosmose

    reverse osmosis system starts running immediately after beingswitched on and can be switched off with the STOPSTART key.

    The level-controlled operating mode with 2 level switches is usedfor automatic filling of a permeate tank. The system only starts upafter the permeate level in the permeate tank has dropped belowthe minimum level. If the upper level is reached when filling then

    the Dulcosmose switches off. The system can be externallylocked by a pause contact.

    The raw water pressure is checked before system start. If the rawwater pressure is insufficient then the system goes into fault mode.After expiration of a waiting time, the raw water pressure isrechecked. If there is still insufficient raw water pressure after themaximum permissible number of checks then no additionalattempts are made.

    If there is sufficient raw water pressure then the solenoid valveopens and the high pressure pump starts. Permeate is generated.The permeate conductivity is monitored during operation. If thepermeate conductivity does not drop below the maximum permissible conductivity within a maximum flushing time then the systemgoes into fault mode.

    6.3 Optional chemical cleaningAn optional cleaning station is available for system sizes ecoPRO600 to 2700. The cleaning module can be retrofitted for system

    sizes ecoPRO 600 to 1500. The module is installed as shown onFig. 5. The cleaning module is integral to the system for systemsizes ecoPRO 1800 to 2700.

    Control Elements

    17

  • 7/27/2019 Sistemas de Osmosis Inversa

    18/64

    Chemical cleaning of the reverse osmosis module is required atregular intervals and is supported by the controller. Chemicalcleaning is started manually after filling the cleaning tank withcleaning agent. The flushing pump starts. Chemical cleaning isstopped by manual switch-off. All valves are closed manually. Thecleaning pump is switched off.

    6.4 DisplayNOTICE!After switching on the mains supply, the controllerstarts in "system OFF" mode or in the last active operating mode. If the contact for the external pause or thepermeate tank full level switch is activated at switch-on then the system starts in "idle" mode.

    Pressing the STOPSTART key during raw water or permeaterinsing stops the rinse procedures. The system

    switches off immediately.To do this, press the STOPSTART key for at least 2 seconds.

    STOP

    START

    2

    3

    4

    5

    8

    6

    7

    1

    XXXXXX

    Fig. 6: Control elements

    Position number key Function1 Respective measured variable ......here UO

    2 Display

    5 UP keyTo increase a displayed numerical value and to change the variables(flashing display).

    Control Elements

    18

  • 7/27/2019 Sistemas de Osmosis Inversa

    19/64

    Position number key Function7 BACK key

    Returns to permanent display or to the start of the respective settingmenu.

    6 DOWN key

    To decrease a displayed numerical value and to change the variables(flashing display).

    8 CHANGE key

    To move within a menu level and to change from a variable value toanother value within a menu item.

    3STOPSTART

    START/STOP key

    Start/Stop the control and metering function.

    4 INPUT key

    To accept, confirm or save a displayed value or condition. To acknowl

    edge an alarm.

    6.5 Operating status display and parameter settingsThe set parameters can be requested during running operation bypressing the key.

    Control Elements

    19

  • 7/27/2019 Sistemas de Osmosis Inversa

    20/64

  • 7/27/2019 Sistemas de Osmosis Inversa

    21/64

    (adjustable numbers/

    settings flash)Memory display

    1 secB

    (Request

    validation code)

    Validation code incorrect Changes are not saved Changes are saved

    Back to

    display window

    Fig. 8: Programming setting of access code (validation code)

    Operating status display textsThe text headings in the following chapters correspondto the texts in the displays of the operating status display.

    6.5.1 Change access codeNOTICE!Note access codeNote down the access code! Parameters can only beset once the correct access code has been entered.The default access code (5000) does not guaranteeany protection from unauthorised changes.

    New validation code

    xxxx

    Memory display1 sec

    (Request

    validation code)

    Changes are saved

    Confirm

    validation code

    xxxx

    Validation code incorrect Changes are not saved

    B

    Back to request

    "Change

    validation code"

    Fig. 9: Change access code (validation code)

    To protect against unauthorised changes of the settings, thesystem controller has an access code for the programming mode.It can be freely selected by the operator. The programming modeis still disabled after a change of the access code. It is only enabled when the new access code is entered.

    6.5.2 Set the languageIt is possible to select between different languages: German, English, French, Spanish, Italian.

    Language

    Control Elements

    21

  • 7/27/2019 Sistemas de Osmosis Inversa

    22/64

    6.5.3 Set level control of permeate tankLevel-controlled operating mode: The level-control with 2 levelswitches allows a permeate tank to be automatically filled. When

    the level control is enabled, the Dulcosmose system only starts upon switching on after the permeate level in the permeate tank hasdropped below the minimum level The system switches off automatically once the upper permeate level is reached.

    Manual operating mode: In manual operating mode, theDulcosmose system starts running immediately after beingswitched on and can be switched off with the STOPSTART key.

    6.5.4 Set cell-constant conductivity sensorCAUTION!Incorrect cell constantAn incorrect cell constant results in an incorrect con

    ductivity measurement.

    The cell constant of the conductivity sensor used must be entered.The entry is made in steps of 0.01.

    6.5.5 Set the temperature compensation of the conductivity measurementConductivity is a temperature-dependent variable. The controllercan compensate for the influence of the temperature on the conductivity in two ways. The simplest method is temperature compensation using a Pt 100 temperature sensor. If no temperature sensoris installed, the permeate temperature can be entered manually. Ifthe temperature is entered manually then no temperature is displayed in the standard display.

    6.5.6 Set compensation constant (Cal.-factor)CAUTION!Incorrect compensation constantAn incorrect compensation constant or temperature

    setting results in an incorrect conductivity measurement.

    The compensation factor (Cal.-factor) can be selected. In mostcases, a temperature compensation of 1 % / Kelvin is used. Thecompensation constant can be adjusted during operation to calibrate the conductivity display.

    6.5.7 Set maximum conductivityIn conjunction with the permeate valve (optional) the monitoring cir

    cuit for the conductivity ensures that only permeate with therequired conductivity reaches the consumer. The system is startedup with the permeate valve opened. As soon as the permeate conductivity drops below the maximum permissible conductivity, the

    Permeate tank level control

    Cell-constant conductivity sensor

    Pt 100 present Yes/No

    Cal.-factor conductivity measurement

    Maximum conductivity

    Control Elements

    22

  • 7/27/2019 Sistemas de Osmosis Inversa

    23/64

    permeate vale closes in systems that have no permeate rinsingand the water us then fed to the consumer. In systems with permeate rinsing, the permeate valve only closes after the cleaningtank is full. If the maximum permissible conductivity is not undershot during the flushing time then the system goes into fault mode.The permeate conductivity continues to be monitored during operation. As soon as the conductivity exceeds the maximum permissible value, the permeate valve opens. If the conductivity once

    more drops below the maximum permissible conductivity then thepermeate valve closes. Otherwise, the system goes into fault modeafter the maximum flushing time has expired. The permeate conductivity is not monitored during all rinsing procedures The permeate valve is opened. The function of the conductivity sensor isnot monitored by the controller. If conductivity value "0 S/cm" isdisplayed then the conductivity sensor must be checked.

    6.5.8 Wait time and maximum number of attempts in case of water shortage

    After switching on the Dulcosmose system manually or after thelower level in the permeate tank is undershot, the inlet valveopens. The water pressure is checked. If there is sufficient waterpressure then a system start rinsing procedure is run.

    If there is not enough water pressure then the inlet valve closesagain The system goes into fault mode. The water pressure is re-checked after expiration of a wait time If there is still not enoughwater pressure after the maximum number of attempts then nomore attempts are made.

    If the water pressure breaks down after expiration of the pantrinsing time while the high pressure pump is starting up then thepump is switched off. A second pump start-up commences a shorttime after this If the water pressure again breaks down then thesystem goes into fault mode. No additional attempts are made.

    The water pressure continues to be monitored while the system isrunning. If the water pressure drops while the system is runningthen the system is immediately switched off. As previouslydescribed, the water pressure is then checked several times andthe system restarts if there is enough water pressure . If there isstill insufficient water pressure after the maximum permissiblenumber of attempts then no more attempts are made and thesystem goes into fault mode The operation relay of the controlleronly drops off if the system goes into fault mode.

    6.5.9 Set rinse time of system startNOTICE!Rinse time of system startThe rinse time of the system start-up must be set so

    that after expiration of the rinsing time, the motor valveis fully opened and the metered chemicals are distributed within the complete system.

    Wait time in case of water shortage3 attempts maximum in case of watershortage

    Water pressure too low

    Water pressure breaks down

    Water pressure drops

    Rinse time of system start

    Control Elements

    23

  • 7/27/2019 Sistemas de Osmosis Inversa

    24/64

    Open the inlet and rinse valve (optional) for system start rinsing;the high pressure pump remains switched off. In case of systemswhere agents are added to stabilise hardness, the system startrinse serves to ensure there is an even distribution of the metered

    chemicals on the raw water side of the Dulcosmose systembefore starting up the high pressure pump. In case of Dulcosmose

    systems fitted with slow-opening motor-driven valves, the systemstart rinse also serves to completely open the valve before the

    pump starts up

    6.5.10 Set start-up time of high pressure pumpCAUTION!Maximum start-up timeIf the start-up time is too long then may result indamage to the pump. Exact specifications are contained in the operating manual of the pump.

    The water pressure is not monitored during the pump start-up time.A longer pump start-up time is especially required for larger systems to prevent incorrect switch-off due to a supposed watershortage during the pump start-up time.

    6.5.11 Set maximum flushing timeIf the permeate conductivity does not drop below the maximumconductivity during the maximum flushing time then theDulcosmose system switches off and the pant goes into fault

    mode.

    6.5.12 Set maximum filling time of cleaning tankDulcosmose systems with the "permeate rinsing" option have 2level switches in the cleaning tank whose contacts close as thelevel increases. The top level switch ends the filling procedure ifflushing has already completed. After removal, the cleaning tank isfilled automatically by the permeate valve the next time the

    Dulcosmose system is started. The lower level switch serves asdry-run protector for the cleaning pump If the cleaning tank is not

    filled within the maximum filling time then the Dulcosmose

    systemswitches off and the Dulcosmose system goes into fault mode.

    6.5.13 Set frequency and duration of raw water rinse in operation .

    The raw water is rinsed at regular intervals during operation of theDulcosmose system. To do this, the rinse valve (optional) openswhile the system is running and the permeate valve opens duringthe rinsing time. Any coating that might have formed on the mem

    brane is removed and rinsed off . This function is switched off byentering "0 hours" for the wait time . Raw water rinsing during operation is always carried out by the high pressure pump.

    start-up time of high pressure pump

    Fault, flushing time has expired

    Maximum filling time of cleaning tank

    Rinsing in operation, rinsing time 2minRinsing in operation every 0 h

    Control Elements

    24

  • 7/27/2019 Sistemas de Osmosis Inversa

    25/64

    6.5.14 Raw water rinsing at end of operation

    For raw water rinsing, the rinse valve (optional) opens for the duration of the rinsing time after switching off the system. The concen

    trate is thereby rinsed off at the raw water side of the Dulcosmose

    system. The inlet valve remains open. Normally, the raw waterrinsing is carried out with the high pressure pump switched off.However, depending on the configuration of the system, rinsingmay also be necessary when the high pressure pump is switchedon. If no rinse valve is installed then "concentrate suppression" canbe carried out. This is always done with the high pressure pumpswitched on.

    6.5.15 Permeate rinse, set rinse timeDuring permeate rinsing (optional), the raw water side of the

    Dulcosmose system is rinsed out of the rinsing tank with per

    meate for the rinsing time. The cleaning tank is automatically filledthe next time the system is started up. If the minimum level isreached in the tank during permeate rinsing then the cleaningpump switches off. The warning message "dry run" is displayed.The "dry run" message goes out after completion of the rinsingtime. No error message is issued.

    6.5.16 Cleaning pump for chemical cleaningChemical cleaning of the reverse osmosis module is required atregular intervals and is supported by the controller. A cleaning

    system may or may not be installed, depending on the configuration of the Dulcosmose system .

    6.5.17 Set maximum idle timeWhen the level controller is switched on, the Dulcosmose systemautomatically goes back into operation for the interval operationtime as soon as the maximum idle time is overshot and no pauselock is enabled. This automatic restart significantly reduces themicrobial contamination during idle as well as biological fouling ofthe membrane elements. This function is switched off by setting

    the idle time to "0 h".

    6.5.18 Set interval operating timeCAUTION!Permeate tank overflowThe permeate tank might overflow during interval operation. A suitable level drain must be installed in thepermeate tank.

    Raw water rinsing, rinsing time 2minutesHigh pressure pump during raw waterrinsing OFF

    Permeate rinsing, rinse time

    Cleaning pump installed

    Maximum idle time

    interval operating time

    Control Elements

    25

  • 7/27/2019 Sistemas de Osmosis Inversa

    26/64

    When the level controller is switched on, the Dulcosmose systemautomatically goes back into operation for the interval operationtime as soon as the maximum idle time is overshot and there is noexternal pause lock.

    6.5.19 Set analogue outputThe permeate conductivity can also be written with a recorder fordocumentation purposes. To do so, connect the recorder to thestandard output of the controller. It is possible to choose from a 0to 20 mA and 4 to 20 mA standard signal: 0 or 4 mA correspondsto the conductivity; 0 S/cm, 20 mA ca be assigned to any conductivity.

    6.5.20 Pause functionThe Dulcosmose system can be switched on and off by opening

    and closing an external contact connected to the Pause input ofthe controller. It is possible to select whether the Dulcosmose

    system starts up with an open or closed pause contact. If theDulcosmose system is switched off by a pause contact, then rawwater rinsing or permeate rinsing may occur. If there is a watershortage during this then the permeate rinse is immediatelyskipped.

    6.5.21 Set minimum mains voltagen The minimum mains voltage that can be tolerated by the con

    troller can be set in this menu. Permissible range: 79 - 108 %

    Default setting: 90 %

    100 % corresponds to 230 volt

    6.5.22 Set mains voltage fault acknowledgementIn this menu you can set whether the fault message "mains voltagetoo low" has to be acknowledged (setting: yes) or not (setting: no).Default setting: no.

    6.6 "Fault" switching inputAn external fault signaling device, such as a flow rate monitor, canbe connected to the "fault" switching input. The input must bebridged when no external fault message is connected.

    6.7 "Metering pump" control outputThe "metering pump" control output is used to control a metering

    pump if the feed water of the Dulcosmose system is also fed withhardness stabilisers or other chemicals. A metering pump can bedirectly connected to the controller. There is also a floating contact .

    Analogue output

    Pause with pause contact

    Minimum mains voltage

    Mains voltage fault acknowledgement

    Control Elements

    26

  • 7/27/2019 Sistemas de Osmosis Inversa

    27/64

    6.8 Alarm signal relayA signal device can be connected to the "Alarm" signal relay of the

    controller. If the Dulcosmose system is switched off or there is afault or power failure then the relay drops off (NOC).

    6.9 Chemical cleaningWARNING!Chemical cleaningPossible consequence: Fatal or very serious injuries.

    For chemical cleaning, observe the instructions in themaintenance chapter and observe the safety datasheets for the chemicals used!

    For chemical cleaning, select the chemical cleaning window with

    the key . The system must be switched off for this.

    Chemical cleaning is started by pressing the key. The cleaningpump starts up. After sufficient rinsing time with the cleaning solution, cancel chemical cleaning by pressing the STOPSTART key (for 2 seconds) If a level switch is installed in the cleaning tank for the lowerlevel then the cleaning pump is protected against a dry run. If nolevel switch is installed then this contact must be bridged.

    Chemical cleaning - startChemical cleaning 10:00 min:sec

    Control Elements

    27

  • 7/27/2019 Sistemas de Osmosis Inversa

    28/64

    7 Commissioningn Users' qualification: technical expert, see Chapter 2.2

    Users' qualifications on page 7

    CAUTION!Preservative agent sodium hydrogen sulphate(NaHSO 3 )Possible consequence: Slight or minor injuries, material damage.

    The systems are filled with preservative agent on delivery. Tomake sure that these chemicals are not fed to the consumers, thesystem must be rinsed for at least 30 mins before connection to theconsumers. To do this, please observe the on page 13installation instructions!

    The position numbers refer to the flow diagram inChapter System overview on page 11

    1. Set the solenoid valve (3) to the "manual" position using ascrewdriver

    2. Completely open ball valves (15) and (18)3. Open the raw water shut-off valve. The raw water flushes the

    system

    4. Rinse the system approx. 30 minutes in this state5. Set the solenoid valve (3) back to the "automatic" position6. Switch on the power supply7. Switch on the system with the STOPSTART key (keep closed approx. 2

    s) and check the rotational direction of the high pressurepump (for AC motors)

    If necessary, reverse polarity of the cable otherwise thepump may only build up insufficient pressure and will bedamaged.

    8. Using ball valves(15) and (18), flow meter (16) and flowmeter (13), set according to the specification for the system

    For system specifications, see Table on page 4

    Rinse system

    Commissioning

    28

  • 7/27/2019 Sistemas de Osmosis Inversa

    29/64

    9.CAUTION!Maximum permeate outputPossible consequence: Slight or minor injuries,material damage.

    The yield corresponds to the permeate outputrelative to the consumption of raw water.

    Permeate outputs compliant to the specifications must never be increased in any circumstances

    This damages the membrane and resultsin degradation in the quality of the permeate

    If the permeate output is exceeded then theoperating pressure must be reduced

    This is done by increasing the recirculation of concentrate at the ball valve (18)

    If conductivity is higher than required then lower the yield, i.e.discard more concentrate. To do this, slowly open the ballvalve (15) until the required conductivity is reached.

    10. Set 3-way ball valve (14) for permeate to the permeatetank position

    NOTICE!Fill out checklists 1 and 2 every week. These must besupplied on request in case of a fault.

    11. Close the drain ball valve (21) of the cleaning tank The system is now in operation. Fill out checklists 1 and 2

    ausfllen (see Appendix Chapter 13.1 Checklist 1 on page 50).

    12. Switch off the system with the STOPSTART key13. Connect the permeate connection to the permeate tank or

    the consumer

    14. Switch the system back on The system is now in operation. Fill out checklists 1 and 2

    (see Appendix Chapter 13.1 Checklist 1 on page 50).

    For systems with cleaning system

    Systems without cleaning system

    Commissioning

    29

  • 7/27/2019 Sistemas de Osmosis Inversa

    30/64

    8 Maintenancen Users' qualification: Instructed person, see Chapter 2.2

    Users' qualifications on page 7

    WARNING!Instructions on handling chemicalsPossible consequence: Fatal or very serious injuries

    When handling chemicals, we expressly draw yourattention to the danger and safety notices (R Snotices). Detailed information on this is contained inthe safety datasheets of the chemicals used

    WARNING!Instructions for cleaning chemicalsPossible consequence: Fatal or very serious injuries. When using acid-based cleaning chemicals (max.

    30% hydrochloric acid) or alkali-based cleaningchemicals (max. 30% sodium hydroxide), you mustwear protective goggles and gloves

    If the chemical touches your skin then immediatelyrinse off with lots of water and contact a doctor

    CAUTION!Instructions on disinfectionPossible consequence: Slight or minor injuries, material damage.

    When using an approx. 0.2% peracatic acid solution for disinfection (max. 15% peracetic acid) youmust wear protective goggles and gloves

    If the chemical touches your skin then immediatelyrinse it off with lots of water

    CAUTION!Instructions for anti-corrosion measures prior to shutdown using sodium hydrogen sulphatePossible consequence: Slight or minor injuries, material damage.

    When using an approx. 1% sodium hydrogen sulphate solution for anti-corrosion meaures prior toshutdown (max. 39% sodium hydrogen sulphatepowder) you must wear protective goggles andgloves

    If the chemical touches your skin then immediatelyrinse off with lots of water

    Maintenance

    30

  • 7/27/2019 Sistemas de Osmosis Inversa

    31/64

    8.1 Regular maintenanceMaintenance interval / checks

    n Weekly

    Visual inspection of the complete system for tightness

    Check differential pressure of filter: If there is a pressuredrop of approx. 0.8 bar over the filter (1) (difference

    between the manometers (2) before and after the filter)then replace the filter compliant to the instructions. Replaceevery 5 months at the latest

    Check membrane: If the standardised permeate outputdrops by 10 % or the conductivity rises by 10 % (relative tothe data in the start-up protocol) then the membrane element must be cleaned compliant to Chapter 8.3 Chemical cleaning and disinfection on page 32(chemicalcleaning)

    n 3 months

    Check pressure switch / solenoid valve: Close the rawwater shut-off valve when the system is in operation. If thepressure switch is OK then the system switches off. The

    controller display must show this as a fault. Re-establishthe raw water supply. The system goes back into operationwith a time delay

    n 6 months

    Check conductivity sensor: The sensor function must bechecked regularly or the sensor must be calibrated. Thegap between the measuring electrodes must be regularlychecked for soiling. Any dirt clinging to it can be removedusing a light stream of water, by immersing for 2 - 3minutes in diluted ( 1 %) acids or by rubbing with a cloth ora soft brush .

    Chemical cleaning: Carry out prophylactic cleaning every 6months compliant to Chapter 8.3 Chemical cleaning and

    disinfection on page 32.

    8.2 Replace filter cartridge or bagReplace the filter cartridges if there is a pressure drop of 0.8 bar atthe particle filter, but every 6 months at the latest.

    1. Shut off the raw water supply The system switches off.

    2. Open the vent plug of the filter unit to reduce the pressure3. Open the filter housing4. Insert a new filter cartridge (5 m) or bag and close the

    housing

    5. Close the vent plug6. Re-establish the raw water supply.

    The system switches back on automatically (time-delayed).

    Replace filter cartridge

    Maintenance

    31

  • 7/27/2019 Sistemas de Osmosis Inversa

    32/64

    8.3 Chemical cleaning and disinfectionCAUTION!Possible consequence: Slight or minor injuries, material damage.

    Also carry out immediate cleaning if the conduc

    tivity rises and the permeate output drops in constant conditions (raw water quality and temperature)

    To increase the lifetime of the modules, carry outtwo prophylactic cleanings with acid and one withalkali every year

    When operating reverse osmosis systems, deposits form on themembrane surface after a while. These deposits can either be inorganic (e.g. lime, plaster, iron, manganese), or organic (bacteria,germs). Depending on the type of deposits, this results in adecrease in permeate quality and/or a reduction in the flow of permeate.

    Chemical cleaning allows the majority of deposits to be removedeasily.

    The modules must be cleaned according to instructions. Theapproximate amount of cleaning fluid required for this, or its composition, is contained in the following table.

    WARNING!DisinfectionPossible consequence: Fatal or very serious injuries.

    Observe the safety data sheet

    Wear protective goggles and gloves. If the chemical touches your skin then immediately rinse offwith lots of water and contact a doctor.

    Peracetic acid is injurious when breathed inand can result in serious burns.

    Danger of fire if acid comes into contact withflammable substances.

    CAUTION!Specifications for metering quantity of chemicalsPossible consequence: material damage.The specifications for the metering quantity of chemicals depends significantly on the water used to manufacture the cleaning fluid and can therefore only serveas an estimated value.

    The acidic cleaning fluid should have apH value of 3

    It must never drop below a pH value of 2

    The alkaline cleaning fluid should have apH value of 11

    Maintenance

    32

  • 7/27/2019 Sistemas de Osmosis Inversa

    33/64

    Estimated values for compiling the cleaning fluid

    System type cleaning fluidAcidic cleaning Alkaline cleaning30% hydrochloric acid 30% sodiumhydroxide 30% sodiumhydroxide 30% hydrochloric acidFor cleaning For neutralising For cleaning For neutralising

    ecoPRO100 5 l 4 ml 3.5 ml 2.3 ml 1 ml

    ecoPRO200

    ecoPRO300

    10 l 8 ml 7 ml 4.5 ml 2 ml

    ecoPRO550

    ecoPRO600

    20 l 16 ml 14 ml 9 ml 4 ml

    ecoPRO900

    ecoPRO1200

    30 l 32 ml 28 ml 23 ml 8 ml

    ecoPRO1500 35 l 40 ml 35 ml 27 ml 10 ml

    ecoPRO1800 45 l 48 ml 42 ml 31.5 ml 12 mlecoPRO2400 60 l 64 ml 56 ml 40.5 ml 16 ml

    ecoPRO2700 90 l 72 ml 63 ml 45 ml 18 ml

    Estimated values for compiling the disinfection liquidSystem type Required 15% peracetic acid approx. ml

    amount of permeate for disinfectionecoPRO100 5 l 12.5 ml

    ecoPRO200

    ecoPRO300

    10 l 25 ml

    ecoPRO550

    ecoPRO600

    20 l 50 ml

    ecoPRO900

    ecoPRO1200

    30 l 100 ml

    ecoPRO1500 35 l 115 ml

    ecoPRO1800 45 l 140 ml

    ecoPRO2400 60 l 200 mlecoPRO2700 90 l 300 ml

    NOTICE!Position numbersAll position numbers in the text refer to the flow diagram Chapter 4 System Overview and Descriptionof Function on page 11

    Maintenance

    33

  • 7/27/2019 Sistemas de Osmosis Inversa

    34/64

    8.3.1 CleaningWARNING!Wear protective goggles and glovesPossible consequence: Fatal or very serious injuries.

    If the chemical touches your skin then immediately

    rinse off with lots of water and contact a doctor.

    NOTICE!If the results after cleaning are not satisfactory thenrepeat the cleaning.

    8.3.1.1 For systems with cleaning system1. Fill cleaning tank with permeate using 3-way ball valve (14)

    compliant to table Estimated values for compiling thecleaning fluid Table on page 33.

    2. Close the raw water inlet The system switches off.

    3. Add the appropriate chemicals compliant to table Estimated values for compiling the cleaning fluid Tableon page 33stirring constantly

    4. Set 3-way ball valve (17) for concentrate to the tank position

    5. Switch off the system at the controller with the STOPSTART key6. Open the ball valve (15)7. Close the ball valve (18) for recirculation of concentrate8. With the key, move to the "chemical cleaning" menu9. Start cleaning with the key and allow the solution to recir

    culate for 30-60 minutes.

    10.CAUTION!Check that the temperature does not exceed 30C. If necessary, empty some of the solution,refill with tap water, add the appropriate amount

    of chemicals and check the pH value Excessivetemperature may result in destruction of themembrane

    If the ph rises and the solution is heavily discoloured (visibleat the flow meter (16) and in the cleaning tank) then discardsome of the cleaning solution (drain ball valve (21)) and addsolution

    11. Switch off the system after rinsing12. Add appropriate chemicals to the tank compliant to table

    Estimated values for compiling the cleaning fluid Tableon page 33for neutralisation

    13. Empty the neutralised content of tank via ball valve (21)

    Maintenance

    34

  • 7/27/2019 Sistemas de Osmosis Inversa

    35/64

    14. Fill the cleaning tank with permeate or completely desalinated water

    15. Allow the system to recirculate again for approx. 5 minutes16. Empty the neutralised content of tank (as required) via ball

    valve (21). Repeat the rinsing procedure a second time asdescribed in steps 14 and 15.

    17. Open the raw water inlet after emptying the cleaning tank18. Switch system on for normal operation19. Open the ball valve (18) for recirculation of concentrate20. Rinse the system for at least 15 minutes21. Set the system compliant to the specifications22. Set 3-way ball valve (14) for permeate to the "pure water

    tank" position and the valve for concentrate (17) to the "drain"position" then close the drain ball valve (21)

    The system is now in normal operating mode. Fill outchecklists 1 and 2.

    8.3.1.2 Systems without cleaning systemNOTICE!Clean without cleaning system Chemical cleaning of the system is also possible

    without an installed cleaning system.

    However, in this case we do not accept any liability for damages to systems and/or persons!

    We therefore expressly recommend you use a

    cleaning system offered by us.

    Independent configuration and assembly of the cleaning system

    n To independently configure and assemble the cleaning systemyou need:

    Cleaning pump V ~ 1.5 2 m3/h, p max = 4 bar, acid and

    alkali resistant, for system sizes ecoPRO 2400 - 2700

    Cleaning pump V ~ 1.5 2 m3/h, p max = 2.4 bar, acid and

    alkali resistant, for system sizes ecoPRO 600 - 1800

    Container for cleaning fluid, acid and alkali resistant

    Various connection material (hoses, etc.)

    1. Fill a suitable cleaning container with the amount of permeatelisted in table Estimated values for compiling the cleaningfluid Table on page 33and add the appropriate chemicalsas per the table, stirring constantly

    2. Close the raw water inlet The system stops.

    3. At the controller, switch the system to system off4. Connect the permeate and concentrate line to the cleaning

    container

    5. Connect the pressure end of a suitable cleaning pump to thesuction end of the ball valve (29) and then connect thecleaning tank

    For systems without cleaning system

    Maintenance

    35

  • 7/27/2019 Sistemas de Osmosis Inversa

    36/64

    6. Open the ball valve (15). Close the ball valve (18) for recirculation of concentrate

    7. Start the cleaning pump8. Recirculate the solution for 30-60 minutes9.

    CAUTION!Check that the temperature does not exceed 30C. If necessary, empty some of the solution,refill with tap water, add the appropriate amountof chemicals and check the pH value Excessivetemperature may result in destruction of themembrane

    If the ph rises and the solution is heavily discoloured (visibleat the flow meter (16) and in the cleaning tank) then discardsome of the cleaning solution (drain ball valve (21)) and addsolution

    10. Switch off the cleaning pump at the end of the rinsing time11. Add appropriate chemicals to the tank compliant to table

    Estimated values for compiling the cleaning fluid Tableon page 33for neutralisation

    12. Empty the neutralised content of tank via ball valve (21)13. Fill the cleaning tank with permeate or completely desali

    nated water

    14. As described in steps 7 and 8, allow the system to once morerecirculate for approx. 5 minutes

    15. Empty the neutralised content of tank (as required) via ballvalve (21). Repeat the rinsing procedure a second time asdescribed in steps 13 and 14.

    16. Empty the cleaning container17. Re-connect the concentrate line to the sewer (drain)18. Connect the permeate line to the sewer for rinsing19. Open the raw water inlet20. Switch on the system and allow to run for approx. 15 minutes21. Re-connect the permeate line to the permeate tank or the

    consumer

    The system is now in normal operating mode. Fill outchecklists 1 and 2.

    8.3.2 DisinfectionNOTICE!If the results after disinfection are not satisfactory thenrepeat the disinfection.

    Maintenance

    36

  • 7/27/2019 Sistemas de Osmosis Inversa

    37/64

    8.3.2.1 For systems with cleaning system1. Fill cleaning tank with permeate using 3-way ball valve (14)

    compliant to table Estimated values for compiling the disinfection liquid Table on page 33.

    2. Close the raw water inlet The system switches off.

    3. Add the appropriate chemicals compliant to table Estimated values for compiling the disinfection liquid Tableon page 33stirring constantly

    4. Set 3-way ball valve (17) for concentrate to the tank position

    5. Switch off the system at the controller with the STOPSTART key6. Open ball valve (15) and close ball valve (18) for recirculation

    of concentrate

    7. With the key, move to the "chemical cleaning" menu8. Start cleaning with the and allow the solution to recirculate

    for 60 minutes9. Switch off the system after rinsing10. Open drain ball valve (21)

    Switch off the cleaning pump after emptying the tank

    11. Open the raw water inlet12. Switch system on for normal operation13. Open the ball valve (18) for recirculation of concentrate14. Rinse the system for at least 30 minutes15. Check permeate for P.E.S. using lead acetate paper and

    repeat rinsing if necessary16. Set system to normal (original) operating data17. Set 3-way ball valve (14) for permeate to the pure water

    tank position and the valve for concentrate (17) to the"sewer" position" then close the drain ball valve (21)

    The system is now in normal operating mode. Fill outchecklists 1 and 2.

    8.3.2.2 For systems without cleaning system1. Fill a suitable cleaning container with the amount of permeate

    listed in the Estimated values for compiling the disinfection liquid Table on page 33table .

    2. Add the appropriate chemicals compliant to table Estimated values for compiling the disinfection liquid Tableon page 33stirring constantly

    3. Switch off the system4. Connect the permeate and concentrate line to the cleaning

    container

    5. Connect the pressure end of the cleaning pump to the suction end of the ball valve (29) and then connect the cleaning

    tank6. Open ball valve (15) and close ball valve (18) for recirculationof concentrate

    Maintenance

    37

  • 7/27/2019 Sistemas de Osmosis Inversa

    38/64

    7. Start the cleaning pump8. Recirculate the solution for 60 minutes9. Switch off the cleaning pump at the end of the rinsing time10. Empty the cleaning container11. Re-connect the concentrate line to the sewer12. Connect the permeate line to the sewer for rinsing13. Open the raw water inlet14. Switch on the system15. Set the system compliant to the specifications (see Commis

    sioning) and allow to run for approx. 30 minutes

    16. Check permeate for P.E.S. using lead acetate paper andrepeat rinsing if necessary

    17. Re-connect the permeate line to the permeate tank or theconsumer

    The system is now in normal operating mode. Fill out

    checklists 1 and 2.

    Maintenance

    38

  • 7/27/2019 Sistemas de Osmosis Inversa

    39/64

    9 Troubleshootingn Users' qualification: trained user, see Chapter 2.2 Users'

    qualifications on page 7

    9.1 Direct fault in the systemFault / Malfunction Cause RemedyConductivity too high Deterioration of raw water Reduce yield

    Yield too high Reduce yield

    Pressure too low Increase pressure

    Module blocked Carry out acid rinse* and reduceyield

    Pump defective Replace

    Module defective ReplacePermeate output drops Temperature too low Increase pressure or temperature

    Module blocked Carry out acid rinse* and reduceyield

    Module defective Replace

    Malfunction / insufficient pressure Filter cartridges blocked Replace

    Primary pressure too low Increase

    Solenoid valve defective Replace

    * Rinse with alkali after every acid rinse compliant to the operating instructions if the results are not satisfactory.

    If the results are still unsatisfactory then contact your contractualpartner or ProMaqua GmbH Kontakt.

    9.2 Fault messages at the controllerOperating status display textsThe text headings in the following chapters correspondto the texts in the displays of the operating status dis

    play.

    9.2.1 Fault alert: Water pressure too lowCause: Water pressure determined too low after opening the inletvalve

    Remedy: Eliminate cause for too low water pressure

    If the maximum number of attempts is not exceeded, the

    Dulcosmose system starts up again automatically if

    there is sufficient water pressure after expiration of thewaiting time. To restart without waiting time, press thekey. If the maximum number of attempts is exceededthen the system only restarts after pressing the key.

    Troubleshooting

    39

  • 7/27/2019 Sistemas de Osmosis Inversa

    40/64

    9.2.2 Fault alert: Water pressure filter?When starting up the high pressure pump, it has been repeatedlydetermined that the water pressure is too low

    Remedy: Eliminate cause for too low water pressure

    NOTICE!Confirm the fault by pressing the key.

    NOTICE!The cause of this fault is often a dirty primaryfilter.

    Clean or replace the filter.

    9.2.3 Fault alert: Other faultPossible cause External fault signal triggered

    Remedy: Eliminate the cause of the fault

    Possible cause: No external safety equipment is connected andthe contacts are not bridged.

    Remedy: Bridge the contacts

    NOTICE!The message clears automatically after eliminating thefault.

    9.2.4 Fault alert: High pressure pump, cleaning pumpCause: The motor protection of the high pressure pump or thecleaning pump has triggered.

    Remedy: Eliminate cause of fault (see operating instructionsof the high pressure pump)

    NOTICE!Confirm the fault by pressing the key. No rawwater or permeate rinse is made.

    Troubleshooting

    40

  • 7/27/2019 Sistemas de Osmosis Inversa

    41/64

    9.2.5 Fault alert: Rinse free time expiredCause: The maximum rinse free time (flushing time) has expiredwithout the maximum conductivity being undershot.

    Remedy: Eliminate cause of fault (see operating instructions

    of the Dulcosmose system)

    NOTICE!Confirm the fault by pressing the key.

    9.2.6 Fault alert: Filling time exceededCause: The maximum filling time has been exceeded without thecleaning tank being filled.

    Remedy: Eliminate cause of fault (see operating instructions

    of the Dulcosmose

    system)

    NOTICE!Confirm the fault by pressing the key.

    9.2.7 Fault alert: Temperature measurementCause: Incorrect temperature measurement.

    Remedy: Check temperature sensor

    NOTICE!Confirm the fault by pressing the key.

    9.2.8 Fault alert: Voltage supply too lowCause: The voltage supply is lower than the minimum permissible

    voltage supply.Remedy: Check supply voltage

    NOTICE!The system restarts automatically as soon as theminimum permissible mains voltage is exceeded

    Troubleshooting

    41

  • 7/27/2019 Sistemas de Osmosis Inversa

    42/64

    9.2.9 Fault alert: Level switchCause: An invalid switching of the level switch has been detectedin the permeate tank.

    1. Remedy: Replace level switch2. Switch mains supply on and off

    Controller restarts.

    9.2.10 Fault alert: Memory errorCause: During self-testing, the controller has detected an error inthe memory

    Remedy: Replace the controller (only an electrical engineeris authorised to do so!)

    NOTICE!If the fault is triggered by a fault in the levelswitch then the fault message can be remediedby switching the mains supply off and back onand replacing the level switch

    9.2.11 Fault alert: Default settingCause: During self-testing, the controller has detected an error.Reset the program to its original state.

    Remedy: Replace the controller (only an electrical engineer

    is authorised to do so!)

    9.2.12 Warning message: Cleaning tank emptyCause: The lower level of the cleaning tank has been reachedduring permeate rinsing and chemical cleaning.

    The cleaning pump is stopped. No fault message is issued. Themessage clears during permeate rinsing after expiration of therinse time.

    1. See operating instructions of the Dulcosmose system.2. Check the filling procedure of the cleaning container.3. Adjust the rinsing time if necessary.

    9.2.13 Warning message: Water pressure too lowCause: The water pressure has dropped below the minimum permissible value during system start or in operation.

    The maximum permissible number of start attempts has not beenreached. A fault message is not yet issued.

    See troubleshooting Fault message: Water pressure too low on page 39

    Troubleshooting

    42

  • 7/27/2019 Sistemas de Osmosis Inversa

    43/64

    10 Decommissioningn Users' qualification: Instructed person, see Chapter 2.2

    Users' qualifications on page 7

    CAUTION!Wear protective goggles and glovesWear protective goggles and gloves. If the chemicaltouches your skin then immediately rinse off with lotsof water and contact a doctor.

    When unused for a longer period of time (longer ~1 week), thesystem must be filled with a anti-corrosion agent to protect itagainst biological infestation and to protect the membranes fromdrying up.

    Estimated values for compiling the shutdown anti-corrosion solutionAnti-corrosion measures prior to shutdownSystem type Required amount of permeate Sodium hydrosulphide approx.ecoPRO100 5 l 0.125 l

    ecoPRO200

    ecoPRO300

    10 l 0.25 l

    ecoPRO550

    ecoPRO600

    20 l 0.5 l

    ecoPRO900ecoPRO1200

    30 l 0.75 l

    ecoPRO1500 35 l 1.0 l

    ecoPRO1800 45 l 1.25 l

    ecoPRO2400 60 l 1.5 l

    ecoPRO2700 90 l 2.25 l

    10.1 System anti-corrosion measures prior to shutdown with cleaning systemThe position numbers refer to the flow diagram inChapter System overview on page 11

    1. Fill cleaning tank with permeate using 3-way ball valve (14)compliant to table Estimated values for compiling theshutdown anti-corrosion solution Table on page 43.

    2. Close the shut-off valve for drinking water The system switches off.

    3. Add the appropriate chemicals compliant to table Estimated values for compiling the shutdown anti-corrosion solution Table on page 43stirring constantly

    Ant-corrosion measures prior to shutdown

    Decommissioning

    43

  • 7/27/2019 Sistemas de Osmosis Inversa

    44/64

    4. Set 3-way ball valve (17) to the "cleaning tank" position5. At the controller, switch the system to "system off"6. With the key, move to the "chemical cleaning" menu7. Start cleaning with the key and allow the solution to recir

    culate for 15 minutes

    8. Switch off the system9. Switch off the main switch or pull the mains plug10. Attach a sign to the system - "Attention: anti-corrosoion solu

    tion" (with date of the last anti-corrosion measure as well ofwhen anti-corrosion agent is to be repeated)

    11. Close the ball valve (22) and empty the cleaning tank12. When putting back into operation, proceed as for commis

    sioning Chapter 7 Commissioning on page 28.

    10.2 System anti-corrosion measures prior to shutdown without cleaning systemThe position numbers refer to the flow diagram inChapter System overview on page 11

    1. Full a suitable cleaning container with permeate compliant to Estimated values for compiling the shutdown anti-corrosion solution Table on page 43.

    2. Close the shut-off valve for drinking water The system switches off.

    3. Add the appropriate chemicals compliant to table Estimated values for compiling the shutdown anti-corrosion solution Table on page 43stirring constantly

    4. At the controller, switch the system to "system off"5. Connect the permeate and concentrate line to the cleaning

    container

    6. Connect the pressure end of the cleaning pump to the suction end of the ball valve (29) and then connect the cleaningtank

    7. Open ball valve (15) and close ball valve (18) for recirculationof concentrate

    8. Start the cleaning pump9. Allow the solution to recirculate for 15 minutes10. Switch off the cleaning pump at the end of the rinsing time11. Empty the cleaning container12. Switch off the system13. Switch off the main switch or pull the mains plug14. Attach a sign to the system - "Attention: anti-corrosion solu

    tion" (with date of the last anti-corrosoin measure as well ofwhen anti-corrosion is to be repeated)

    15. Close the ball valve (22) and empty the cleaning tank16. When putting back into operation, proceed as for commis

    sioning Chapter 7 Commissioning on page 28.

    Decommissioning

    44

  • 7/27/2019 Sistemas de Osmosis Inversa

    45/64

    10.3 DisposalNOTICE!Regulations governing disposal of used parts Note the current national regulations and legal

    standards which apply in your country

    ProMaqua GmbH, Heidelberg//Germany is prepared to take backclean used parts.

    Decommissioning

    45

  • 7/27/2019 Sistemas de Osmosis Inversa

    46/64

    11 Technical DataSystem type ecoPRO

    Type 100 200 300 550Permeate output 100 l/h 200 l/h

    Concentrate output 100 l/h 100 l/h 100 l/h 150 l/hRaw water pressure 3 - 6 bar 3 - 6 bar 3 - 6 bar 3 - 6 bar

    Salt retention rate 90 -- 95 % 90 -- 95 % 90 -- 95 % 90 -- 95 %

    Yield approx. 50 % approx. 65 % approx. 75 % approx. 75 %

    Voltage supply 1~, 230 V, 50 Hz 1~, 230 V, 50 Hz 1~, 230 V, 50 Hz 1~, 230 V, 50 Hz

    Connection value 0.37 kW 0.55 kW 1.10 kW 1.10 kW

    Raw water connection DN 15 DN 15 DN 15 DN 15

    Permeate connection DN 10 DN 10 DN 15 DN 15

    Concentrate connection DN 10 DN 10 DN 15 DN 15Dimensions

    HxWxD [mm]

    without cleaning system

    1400x500x320 1400x500x320 1500x600x400 1500x600x400

    Dimensions

    HxWxD [mm]

    with cleaning system

    - - - -

    Type 600 900 1200 1500Permeate output 600 l/h 900 l/h 1200 l/h 1500 l/h

    Concentrate output 200 l/h 300 l/h 400 l/h 500 l/h

    Raw water pressure 3 - 6 bar 3 - 6 bar 3 - 6 bar 3 - 6 bar

    Salt retention rate 90 -- 95 % 90 -- 95 % 90 -- 95 % 90 -- 95 %

    Yield approx. 75 % approx. 75 % approx. 75 % approx. 75 %

    Voltage supply 400 V, 50 Hz 400 V, 50 Hz 400 V, 50 Hz 400 V, 50 Hz

    Connection value 1.50 kW 2.20 kW 2.20 kW 2.20 kW

    Raw water connection DN 20 DN 20 DN 20 DN 20

    Permeate connection DN 15 DN 15 DN 15 DN 15

    Concentrate connection DN 15 DN 15 DN 15 DN 15

    Dimensions

    HxWxD [mm]

    without cleaning system

    1650x720x700 1650x720x700 1650x720x700 1650x720x700

    Dimensions

    HxWxD [mm]

    with cleaning system

    1650x1120x700 1650x1120x700 1650x1120x700 1650x1120x700

    Technical Data

    46

  • 7/27/2019 Sistemas de Osmosis Inversa

    47/64

    Type 1800 2400 2700Permeate output 1800 l/h 2400 l/h 2700 l/h

    Concentrate output 600 l/h 800 l/h 900 l/h

    Raw water pressure 3 - 6 bar 3 - 6 bar 3 - 6 bar Salt retention rate 90 -- 95 % 90 -- 95 % 90 -- 95 %

    Yield approx. 75 % approx. 75 % approx. 75 %

    Voltage supply 400 V, 50 Hz 400 V, 50 Hz 400 V, 50 Hz

    Connection value 2.20 kW 3.00 kW 3.00 kW

    Raw water connection DN 25 DN 25 DN 25

    Permeate connection DN 20 DN 20 DN 20

    Concentrate connection DN 20 DN 20 DN 20

    DimensionsHxWxD [mm]

    without cleaning system

    1750x2600x750 1750x2600x750 1750x3500x750

    Dimensions

    HxWxD [mm]

    with cleaning system

    1800x2600x750 1800x2600x750 1800x3500x750

    Technical Data

    47

  • 7/27/2019 Sistemas de Osmosis Inversa

    48/64

    12 Spare Parts ListThe position numbers (Pos. No.) refer to the flow diagram in Chapter System overview on page 11

    Primary filterPos. No. Part no. Description Type Used in:1 1003110 Cartridge filter 5" ecoPRO 100 - 550

    1 1003111 Cartridge filter 10" ecoPRO 600 - 1500

    1 1003112 Cartridge filter 20" ecoPRO 1800 - 2700

    1 1003107 Filter cartridge 5" ecoPRO 100 - 550

    1 1003108 Filter cartridge 10" ecoPRO 600 - 15001 1003109 Filter cartridge 20" ecoPRO 1800 - 2700

    High-pressure pumpPos. No. Part no. Description Type Used in:6 1009371 High-pressure

    pump- ecoPRO 100

    6 1025440 High-pressurepump

    - ecoPRO 200

    6 1025442 High-pressurepump

    - ecoPRO 300/550

    6 1025443 High-pressurepump

    - ecoPRO 600

    6 1025464 High-pressurepump

    - ecoPRO 900

    6 1025465 High-pressurepump

    - ecoPRO 1200

    6 1025466 High-pressurepump

    - ecoPRO 1500/1800

    6 1037531 High-pressurepump

    - ecoPRO 2400 / 2700

    Pressure pipePos. No. Part no. Description Type Used in:9 1030785 Pressure pipe 1 module 2.5" ecoPRO 100/200

    9 1006354 Pressure pipe 1 module 4" ecoPRO 300 - 1500

    9 1006355 Pressure pipe 2 modules 4" ecoPRO 1800 - 2400

    9 1006356 Pressure pipe 3 modules 4" ecoPRO 2700

    ecoPRO spare parts list

    Spare Parts List

    48

  • 7/27/2019 Sistemas de Osmosis Inversa

    49/64

    Accessories for pressure pipesPos. No. Part no. Description Contents Used in:---- 1036079 O-ring set 2 pieces, membranes

    2 pieces, end cap

    Pressure pipe 2.5"

    ---- 1029624 Adapter set Pressure pipe 4.0"

    ---- on request O-ring set 2 pieces, membranes, Knappe

    OR 18x3

    2 pieces, end cap, Knappe OR18x3

    Pressure pipe 4.0"

    ModulePos. No. Part no. Description Type Used in:10 1003187 Module 2.5" ecoPRO 100/200

    10 1025439 Module 4" ecoPRO 300 - 2700

    ControlPos. No. Part no. Description Type Used in:12 1004192 Control UO-AS 230 V AC ecoPRO 100 - 2700

    Conductivity sensorPos. No. Part no. Description Type Used in:11 1001374 Conductivity

    sensorLFT 1 FE ecoPRO 100 - 2700

    Cleaning pumpPos. No. Part no. Description Type Used in:22 1025468 Centrifugal pump - ecoPRO 100 - 1800

    22 1034020 Centrifugal pump - ecoPRO 2400 / 2700

    Cleaning tankPos. No. Part no. Description Type Used in:20 791993 PE tank 35 l Chemical tank PE

    naturalecoPRO 600 - 1500

    20 791994 PE tank 60 l Chemical tank PEnatural

    ecoPRO 1800 - 2400

    20 1001490 PE tank 100 l Chemical tank PEnatural

    ecoPRO 2700

    Spare Parts List

    49

  • 7/27/2019 Sistemas de Osmosis Inversa

    50/64

    13 Appendix13.1 Checklist 1Checklist 1Date Permeateoutput

    [m3/h]Operatingpressure[bar]

    water temp[C]

    Concentrateto sewer[m3/h]

    Permeateconductivity[s/cm]

    Comment

    Appendix

    50

  • 7/27/2019 Sistemas de Osmosis Inversa

    51/64

    13.2 Checklist 2Checklist 2Date Raw water

    Pressure [bar] Conductivity [s/cm] Acid/alkali rinse, anti-corrosion,disinfection, closedown

    Appendix

    51

  • 7/27/2019 Sistemas de Osmosis Inversa

    52/64

    13.3 Default setting of Dulcosmose controllerDefault settingsAccess code c 5000*

    c .......................... Range 0 - 9999

    Language c German *

    c English

    c French

    c Spanish

    c Italian

    c ..........................

    Level controlPermeate tank

    c off *

    c on

    Cell constant

    Conductivity sensor

    c 1 *

    c .......................... Range 0.09 - 11.00

    Pt 100 present? c yes *

    c no

    c Permeate temperature ...........C

    Range 1 - 70 C

    Cal.-factor

    Conductivity measurement

    c 1 % / Kelvin *

    c ....... % / Kelvin Range 0.01 - 3.00 % / Kelvin

    Waiting time after water shortage c 5 min *

    c ............. min Range 1 - 15 min

    Maximum attempts

    after water shortage

    c 3 pieces *

    c ............ each Range 0 - 10 piece

    Rinse time of system start-up c 1 min *

    c .............. min Range 0 - 10 min

    Start-up time of high pressurepump

    c 5 sec*

    c .............. sec Range 1 - 30 sec

    Note: Values marked with an asterisk * are the values set when producing the controller.

    Appendix

    52

  • 7/27/2019 Sistemas de Osmosis Inversa

    53/64

    Default settings

    Maximum time rinse free c 5 min *

    c .............. min Range 0 - 15 min

    Maximum filling time of cleaningtank

    c 20 min *

    c .............. min Range 0 - 90 min

    Rinsing during operation, rinsetime

    c 2 min *

    c .............. min Range 0 - 15 min

    Rinsing during operation, every c 0 h * c .............. h Range 0 - 24 h

    Raw water rinse, rinse time c 2 min *

    c .............. min Range 0 - 15 min

    High pressure pump during

    raw water rinsing

    c off *

    c on

    Permeate rinsing, rinse time c 1 min *

    c .............. min Range 0 - 15 min

    Cleaning pump installed c no *

    c yes

    Maximum idle time c 12 h *

    c .............. h Range 0 - 48 h

    Interval operating time c 20 min *

    c .............. min Range 0 - 99 min

    Analogue output c 0 S/cm = 0 mA *

    c 0 S/cm = 4 mA

    c 1000 S/cm = 20 mA *

    c .............. S/cm = 20 mA Range 5 - 1500 S/cm

    Note: Values marked with an asterisk * are the values set when producing the controller.

    Appendix

    53

  • 7/27/2019 Sistemas de Osmosis Inversa

    54/64

    Default settings

    Pause with pause contact c closed *

    c open

    Minimum mains voltage c 90 %*

    c ... %

    Confirmation

    Mains supply fault

    c no *

    c yes

    Note: Values marked with an asterisk * are the values set when producing the controller.

    Appendix

    54

  • 7/27/2019 Sistemas de Osmosis Inversa

    55/64

    13.4 Terminal wiring diagram

    BA_PMA_UO_0015_SW

    Fig. 10: Terminal arrangement 230 volt version (No. 1004192)

    Terminal arrangement 230 volt version (No. 1004192):

    Appendix

    55

  • 7/27/2019 Sistemas de Osmosis Inversa

    56/64

    13.5 Terminal arrangement of Dulcosmose controller

    Hochdruckpumpe

    high-pressure pump

    Reinigungspumpe

    cleaning pump

    Eingangsventil

    input valve

    Permeatventilpermeat valve

    Splventilflushing valve

    Dosierpumpedosing pump

    Feh

    ler

    Mo

    tor

    Erro

    rmo

    tor

    Druc

    kw

    c

    hter

    pressurecon

    tro

    ller

    Ex

    terne

    Strung

    ex

    terna

    l

    disturbance

    Pause

    pause

    Le

    itfhigke

    it

    con

    duc

    tiv

    ity

    4-2

    0m

    A

    RS485

    (nichtverf

    g

    bar)

    (no

    tava

    ila

    ble)

    Zusc

    ha

    ltfu

    nktion

    Dos

    ierpum

    pe

    dos

    ingpu

    mp

    Connectin

    gfunc

    tion

    Me

    ldere

    lais

    Alarm

    (Alarmzus

    tan

    d)

    Signa

    lre

    lay

    alarm

    (alarm

    con

    dition

    )

    Re

    inigungs

    be

    hlter

    clean

    ing

    tan

    k

    Permea

    tbe

    hlter

    permea

    ttan

    k

    BA_PMA_UO_0016_SW

    Fig. 11: Terminal arrangement of Dulcosmosecontroller, 230 V AC

    Pause function configured by menu:1. Pause with pause contact open2. Pause with pause contact closed

    Terminal arrangement of Dulcosmose controller, 230 V AC

    Appendix

    56

  • 7/27/2019 Sistemas de Osmosis Inversa

    57/64

    13.6 Circuit diagram of Dulcosmose controller

    L

    N

    P E

    P E

    P E

    P E

    XR1

    XP1

    XP2

    XR2

    XR3

    XR4

    XR5

    XR6

    XR

    7

    X7

    X7

    X8

    X8

    X2

    X2

    X3

    X3

    X4

    X4

    X5

    X5

    X6

    1

    2

    3

    Hochdruckpumpehigh-pressure pump

    Netz 230 VAC, 50/60 Hzgrid 230 VAC, 50/60 Hz

    Reinigungspumpecleaning pump

    Eingangsventilinput valve

    Permeatventilpermeat valve

    Splventilflushing valve

    Dosierpumpedosing pump

    Melderelais Alarm

    signal relay alarm230 VAC, 100 VA

    Zuschaltfunktion DosierpumpeConnecting function dosing pump

    24 V, 100 mA

    Gesamtbelastungtotal loadmax. 230 VAC, 230 VA

    Normausgang Leitfhigkeit

    0/4 - 20 mA

    Messeingang Temperatur (Pt 100)Measuring input temperature (Pt 100)

    Messeingang LeitfhigkeitMeasuring input conductivity

    Schalteingang DruckwchterSwitching input pressure controller

    Schalteingang Fehler MotorSwitching input error motor

    Schalteingang StrungSwitching input disturbance

    Schalteingang PauseSwitching input pause

    Schalteingang Niveau Max. PermeatbehlterSwitching input level max. permeat tank

    F2/1

    .6AT

    F1/0

    ,16A

    T

    1

    1

    1

    1

    1

    1

    1

    2

    2

    2

    2

    2

    2

    3

    4

    1(-)

    1

    1

    1

    1

    1

    3

    3

    3

    3

    3

    2

    3

    2(+)

    2

    2

    2

    2

    2

    4

    4

    4

    4

    4

    standard output conductivity

    230 VAC, 100 VA

    230 VAC, 100 VA

    230 VAC, 100 VA

    230 VAC, 100 VA

    230 VAC, 100 VA

    230 VAC, 1.1 kW

    Schalteingang Niveau Min. PermeatbehlterSwitching input level min. permeat tank

    Schalteingang Niveau Min. ReinigungsbehlterSwitching input level min. cleaning tank

    Schalteingang Niveau Max. ReinigungsbehlterSwitching input level max. cleaning tank

    Ausg

    nge

    ou

    tpu

    ts

    Eing

    nge

    intpu

    ts

    BA_PMA_UO_0017_SW

    Fig. 12: Circuit diagram Dulcosmosecontroller 230 V AC, 50/60 Hz (Order No. 1004192)

    Circuit diagram Dulcosmose controller 230 V AC, 50/60 Hz (Order No.1004192)

    Appendix

    57

  • 7/27/2019 Sistemas de Osmosis Inversa

    58/64

    13.7 Switching inputs Dulcosmose controllerSwitching inputs Dulcosmose controllerTerminal Switching input Type Input open Input closedX2/1,2 Pressure controller NCC Pressure too low Pressure sufficient

    X2/3.4 Fault motor NCC Fault motor Motor OK

    X3/1,2 Fault NCC Fault active No fault

    X3/3.4 Pause

    Menu: Pause withpause contact open

    NCC Pause active Pause inactive

    Menu: Pause withpause contactclosed

    NOC Pause inactive Pause active

    X4/1,2 Level max. permeate container