Power Transmission and Distribution Medium voltage – cleverly switched Gas-insulated switchgear: Compact, maintenance-free and climate-independent

Transcript of Siemens MV Gas Insulated Switch Gear

Page 1: Siemens MV Gas Insulated Switch Gear

Power Transmission and Distribution

Medium voltage – cleverly switched Gas-insulated switchgear: Compact, maintenance-free and climate-independent

Page 2: Siemens MV Gas Insulated Switch Gear

There is one thing you just have to rely on: Smooth and safe operation of your system. Around the clock. Here, switch-gear assemblies as points of intersection play a decisive role – and switchgear con-cepts from Siemens offer the best solu-tion with no doubt.

As a pioneer for gas-insulated switchgear we bring along �5 years of know-how, so that you can take full advantage of this technology – with a compact, main-tenance-free and climate-independent design. For lower ratings we also offer air-insulated switchgear type SIMOSEC with SF6 switch-disconnectors. The only decisive factor are your requirements.

With Siemens you are always on the safe side. Whether for secondary or for primary distribution switchgear – all our switchgear is already type-tested today for indoor installation according to IEC 6��71-�00 (in main aspects also according to ANSI C37.�0). In this way you profit from our leading position as regards fulfillment of this new standard. Regardless of the fact that Siemens switchgear has been a synonym for maxi-mum personal and operational safety.

We take care that you can “switch cleverly”. Combining innovation and experience. With comprehensive know-how, world-wide service – and profound understand-ing of your markets. Go and see for yourself!

For perfect operation of your system:

Page 3: Siemens MV Gas Insulated Switch Gear

High demands – in practical imple-mentation: The 3D CAD procedure

�D CAD design tools provide for the precise implementation of quality and reliability for our switchgear in develop-ment and production. The technical data of your switchgear is transferred directly from the purchase order to the produc-tion department via the design depart-ment with mathematical precision. Using innovative technologies we can offer a maximum of quality and flexibility in production – with short delivery times.

Everything tailor-made:The laser cutting system

The use of CNC-controlled laser cutting systems guarantees the manufacture of precise, exact parts with a surface free of scratches – at a high cutting speed. Maximum material utilization is ensured by the programs generated by the NC nesting processor.

For surge-proof operation:Cast-resin part manufacture

Insulating parts made of cast resin guarantee the dielectric strength of high-voltage phases to earth. The complete production process of such parts – which are essential for switch-gear – is integrated in our production. The quality of these components is 100% routine-tested by means of X-ray, tightness, high-voltage and partial discharge tests.

Systematic quality – by innovative procedures, technologies and production processes

With six product families for the primaryand secondary distribution level, theSwitchgear Factory Frankfurt/Main has a top position on the world market for gas-insulated switchgear.

The reason is a distinct understanding of quality, reaching far beyond the certifica-tion according to DIN EN ISO 9001 and 14001. Thousands of switchgear assem-blies running reliably all over the world are an impressive proof for this.

Decades of experience in development,manufacture, quality and environmental management as well as in service sup-port the leading position of the factory – as a worldwide center of competence and leading production for medium-volt-age switchgear from Siemens.

Page 4: Siemens MV Gas Insulated Switch Gear

� 4

Strict eyes: Type and routine tests as an integral part of quality assurance

Very modern testing laboratories ensurethe high quality of our products. Here, type and routine tests for the different switchgear types as well as continuous process-accompanying quality assurance according to ISO 9001 and 14001 are performed. Our accredited testing labo-ratories in Frankfurt/Main and Berlin are among the largest in the world.

Being associated with PEHLA, they have the status of independent test insti-tutes. Furthermore, our type tests are internationally accepted. For example, we take over the testing and certifica-tion of packaged substations from other manufacturers who do not have a test-ing laboratory of their own.

With standards to success:Assembly

Standards play an important part at the Switchgear Factory Frankfurt/Main. The sequence of a process is document-ed in a reproducible way – to guarantee that the quality level the customer ex-pects is reached in a fast, safe and re-producible way. For example, assembly: It is divided into clearly defined opera-tions and organized following the one-piece-flow principle.

Necessary tools are always ready to hand, parts and materials are supplied to the workplace – all this saves en-ergy, time and supports precision. Ac-cording to the push-pull principle, the subsequent process always controls the preceding process: For example, by the information that an operation has been completed or that material is required.

More precise, faster, tighter:The laser welding equipment

The application of laser welding tech-nology leads to maximum precision, fast throughput times and gas tight-ness. The electrical bushings of the stainless-steel vessels are welded in without seals – as well as the metal bellows for transmission of the operat-ing energies from outside the vessel to the switching devices located inside.

Everything tight, everything all right: Integral leakage detection system

“Sealed for life” is the target for each and every switchgear vessel. For this purpose, the vessel is evacuated to-gether with the test chamber and then filled separately with helium, which has a smaller molecular structure than SF6. If no escaping helium is detected, gas tightness is guaranteed for life. The helium gas is absorbed again, the switchgear vessel is refilled with SF6, and the filling socket is welded tight.

Page 5: Siemens MV Gas Insulated Switch Gear

5

Quality inmedium-voltage switchgearYour requirements – and the suitable so-lution from Siemens. For every distribu-tion level, every rating, every application and every switchgear type. According to the different criteria, you can easily find out on which page of this brochure the medium-voltage switchgear you need is described. Just leave this page unfolded.

Selection matrix

Secondarydistribution level

Gas insulation

Air insulation

Cubicle-type & metal-clad

Metal-clad

Metal- enclosed

Single

SIMOSEC

8DH10

8DJ

NXPLUS C

Primarydistribution level

Gas insulation

Air insulation

Cubicle-type & metal-clad

Metal-clad Single

SIMOSEC

8DH10

NXPLUS C

Single

NXPLUS

8DB10

NXPLUS C

NXPLUS

8DA10

Single

Double

Switchgear type

Busbar system

Enclosure/Partitions

InsulationDistributionlevel

Contents

17.5 �5 630 630 �4 �0 630 630

17.5 �5 1�50 630 �4 �0 1�50 630

15 31.5 �500 �500 �4 �5 �500 �000

17.5 �5 1�50 1�50 �4 �0 1�50 1�50

Page 6 – 7

Page 8

Page 9

Page 12

17.5 �5 1�50 630 �4 �0 1�50 630

15 31.5 �500 �500 �4 �5 �500 �000

17.5 �5 1�50 1�50 �4 �0 1�50 1�50

Page 8

Page 9

Page 12

36 31.5 �500 �500

40.5 40 4000 �500

�4 �5 �000 1�50

40.5 31.5 �500 �500

40.5 40 4000 �500 Page 10

Page 11

Page 9

Page 10

Page 11

Ibusbar

[A]

Ur

[kV]

IK

[kA]

Ifeeder

[A]

Electrical data (max.)

Generation leveland high-voltage system

Low voltage

Primary distribution level

Secondary distribution level

Page 6: Siemens MV Gas Insulated Switch Gear

6

8DJ10 switchgear for secondary distribution systems up to 24 kV

Ring-main feeder Transformer feeder

Scheme 10 Scheme 71 Scheme 6�

8DJ10 switchgear

Technical features Up to 17.5 kV, �5 kA, 1 s

Up to �4 kV, �0 kA, 3 s

Busbar up to 630 A

Feeders up to 630 A

Metal-enclosed

Gas-insulated

Block-type construction

Ring-main feeders, transformer feeders

Factory-assembled, type-testedswitchgear according to IEC 6��71-�00

Classification according to IEC 62271-200

Partition class PM

Loss of service continuity category

Switchgear with HV HRC fuses:

LSC �A

Accessibility to compartments

Busbar compartment: non-accessible

Switching-device compartment:

non-accessible

Cable compartment: interlock-controlled

Internal arcclassification (option)

Wall-standing arrangement:

IAC A FL �1 kA, 1 s

Dimensions

Switchgear height 1360 mm and 1650 mm

Switchgear depth 775 mm

Switchgear width 710 mm, 1060 mm, 1410 mm

Your advantages:Independent of environment and climateCompact Maintenance-free Safe for operatorsReliable and safe operationEcologicalCost-efficient

Product range

Page 7: Siemens MV Gas Insulated Switch Gear

7

8DJ20 switchgearfor secondary distribution systems up to 24 kV

Ring-main feeder Transformer feeder

Your advantages:Independent of environment and climateCompact Maintenance-freeSafe for operatorsReliable and safe operationEcologicalCost-efficient

Product range (in extracts)

Scheme 01 Scheme �1 Scheme 10 Scheme 71 Scheme 10 LST Scheme �1 LST

Ring-main feeder Circuit-breaker feeder

Switchgear with HV HRC fuses Switchgear with circuit-breaker feeder

8DJ20 switchgear

Technical features Up to 17.5 kV, �5 kA, 1 s

Up to �4 kV, �0 kA, 3 s

Busbar up to 630 A

Feeders up to 630 A

Metal-enclosed

Gas-insulated

Block-type construction

Ring-main feeders, transformer feeders,circuit-breaker feeders

Factory-assembled, type-testedswitchgear according to IEC 6��71-�00

Classification according to IEC 62271-200

Partition class PM

Loss of service continuity category

Switchgear without HV HRC fuses:

LSC �B

Switchgear with HV HRC fuses:

LSC �A

Accessibility to compartments

Busbar compartment: non-accessible

Switching-device compartment:

non-accessible

Low-voltage compartment:

tool-based

Cable compartment: interlock-controlled

Internal arc classification (option)

Wall-standing arrangement:

IAC A FL �1 kA, 1 s

Dimensions

Switchgear height 1�00 mm, 1400 mm or 1760 mm

Switchgear depth 775 mm

Switchgear width 510 mm, 710 mm, 1060 mm, 1410 mm, 1760 mm

Page 8: Siemens MV Gas Insulated Switch Gear

8

8DH10 switchgear for secondaryand primary distribution systems up to 24 kV

8DH10 switchgear

Technical features Up to 17.5 kV, �5 kA, 1 s

Up to �4 kV, �0 kA, 3 s

Busbar up to 1�50 A

Feeders up to 630 A

Metal-enclosed

Single busbar

Gas-insulated

Modular and extendable as individual panel or as panel block

Factory-assembled, type-testedswitchgear according to IEC 6��71-�00

Classification according to IEC 62271-200

Partition class PM

Loss of service continuity category

Panels without HV HRC fuses: LSC �B

Panels with HV HRC fuses: LSC �A

Accessibility to compartments

Busbar compartment: tool-based

Switching-device compartment:

non-accessible

Low-voltage compartment: tool-based

Cable compartment• with HV HRC fuses:• without HV HRC fuses:• panel type K:

interlock-controlledinterlock-controlledtool-based

Internal arcclassification (option)

Wall-standing arrangement: IAC A FL �1 kA, 1 s

Free-standing arrangement: IAC A FLR �1 kA, 1 s

Dimensions

Switchgear height 1400 mm, �000 mm with low-voltage compartment

Switchgear depth 775 mm

Panel widths 350 mm and 500 mm, metering panels 600 mm or 850 mm

Product range (in extracts)

Your advantages:Independent of environment and climateCompact Maintenance-freeSafe for operatorsReliable and safe operationEcologicalCost-efficient

Ring-main paneltype RK

Transformer paneltype TR

Circuit-breaker paneltype LS1

Bus sectionalizer type LT1

Circuit-breaker panel type LST1

Billing metering paneltype ME1

Page 9: Siemens MV Gas Insulated Switch Gear

9

NXPLUS C switchgear for secondaryand primary distribution systems up to 24 kV

NXPLUS C switchgear

Technical features Up to 15 kV, 31.5 kA, 3 s

Up to �4 kV, �5 kA, 3 s

Busbar up to �500 A

Feeders up to �500 A

Metal-enclosed

Single and double busbar

Gas-insulated

Hermetically sealed

Factory-assembled, type-testedswitchgear according to IEC 6��71-�00

Classification according to IEC 62271-200

Partition class PM

Loss of service continuity category

Panels without HV HRC fuses:

LSC �B

Panels with HV HRC fuses:

LSC �A

Accessibility to compartments

Busbar compartment: tool-based

Switching-device compartment:

non-accessible

Low-voltage compartment:

tool-based

Cable compartment• with HV HRC fuses:• without HV HRC fuses:

interlock-controlled tool-based

Internal arc classification

7.� kV up to 15 kV: IAC A FLR 31.5 kA, 1 s

17.5 kV up to �4 kV: IAC A FLR �5 kA, 1 s

Dimensions

Switchgear height ��50 mm

Switchgear depth 1�50 mm

Panel widths 600 mm, 1�00 mm at �000 A and �500 AProduct range (in extracts)

Circuit-breaker panel Disconnector panel Bus sectionalizer Switch-disconnector panel

Contactor panel Metering panel

Your advantages:Independent of environment and climateCompactMaintenance-freeSafe for operatorsReliable and safe operationEcologicalCost-efficient

Page 10: Siemens MV Gas Insulated Switch Gear

10

8DA/B10 switchgearfor primary distribution systems up to 40.5 kV

8DA/B10 switchgear

Technical features Up to 40.5 kV, 40 kA, 3 s

Busbar up to 4000 A

Feeders up to �500 A

Metal-enclosed

Single and double busbar

Gas-insulated

Sealed

Factory-assembled, type-testedswitchgear according to IEC 6��71-�00

Classification according to IEC 62271-200

Partition class PM

Loss of service continuity category LSC �B

Accessibility to compartments

Busbar compartment: tool-based

Switching-device compartment:

tool-based

Low-voltage compartment:

tool-based

Cable compartment: tool-based

Internal arc classification

IAC A FL 40 kA, 1 s

Dimensions

Switchgear height �350 mm (standard), �700 mm (option)

Switchgear depth SBB 3-pole: 1675 mm, SBB �-pole: 1�65 mm, SBB 1-pole: 915 mm DBB 3-pole: �710 mm

Panel width 600 mm

Product range (in extracts)

Circuit-breaker panel

SBB

8DA10 3-pole

Disconnector panel

SBB

8DA11 1-pole

Bus sectionalizer

SBB

Circuit-breaker panel

DBB

8DA12 2-pole

Bus coupler

DBB

Bus sectionalizer

DBB

8DB10 3-pole

Your advantages:Independent of environment and climateCompact Low-maintenanceSafe for operatorsReliable and safe operationEcologicalCost-efficient

Page 11: Siemens MV Gas Insulated Switch Gear

11

NXPLUS switchgearfor primary distribution systems up to 40.5 kV

NXPLUS switchgear

Technical features Up to 40.5 kV, 31.5 kA, 3 s

Busbar up to �500 A

Feeders up to �500 A

Metal-enclosed

Single and double busbar

Gas-insulated

Hermetically sealed

Factory-assembled, type-testedswitchgear according to IEC 6��71-�00

Classification according to IEC 62271-200

Partition class PM

Loss of service continuity category

LSC �B

Accessibility to compartments

Busbar compartment: tool-based

Switching-device compartment:

non-accessible

Low-voltage compartment:

tool-based

Cable compartment: tool-based

Internal arc classification

IAC A FLR 31.5 kA, 1 s

Dimensions

Switchgear height SBB �450 mm, DBB �600 mm

Switchgear depth SBB 1600 mm, DBB 1840 mm

Panel width 600 mm

Product range (in extracts)

Bus coupler

DBB

Bus sectionalizer

DBB

Circuit-breaker panel

IC DBB

Bus sectionalizer

SBB

Circuit-breaker panel

IC SBB

Circuit-breaker panel

OC SBB

Your advantages:Independent of environment and climateCompactMaintenance-freeSafe for operatorsReliable and safe operationEcologicalCost-efficient

Page 12: Siemens MV Gas Insulated Switch Gear

1�

SIMOSEC switchgear

Technical features Up to 17.5 kV, �5 kA, 1 s

Up to �4 kV, �0 kA, 3 s

Busbar and feeders up to 1�50 A

Metal-enclosed

Single busbar

Air-insulated

Hermetically sealed switchgear vessel

Factory-assembled, type-tested switchgear according to IEC 6��71-�00

Classification according to IEC 62271-200

Partition class PM

Loss of service continuity category

Panels without HV HRC fuses, as well as panel types without removable circuit-breaker type 3AH6: LSC �B

Panels with HV HRC fuses, as well as panel types with 3AH6: LSC �A

Accessibility to compartments

Busbar compartment: tool-based

Switching-device compartment:

non-accessible

Switching-device compartment with 3AH6:

accessible, interlock-controlled

Low-voltage compartment: tool-based

Cable compartment• without HV HRC fuses:• with HV HRC fuses:

tool-basedinterlock-controlled,tool-based

Internal arc classification (option)

Wall-standing arrangement: IAC A FL �0 kA, 1 s

Free-standing arrangement: IAC A FLR �0 kA, 1 s

Dimensions

Switchgear height 1750 mm (standard), �100 mm (option)

Switchgear depth 1�30 mm

Panel widths 375 mm, 500 mm, 750 mm

Ring-main panel RK

Metering panel ME1

Circuit-breaker panel LS1 with 3AH5

Transformer panelTR

Circuit-breaker panel LS11 with 3AH6

Your advantages:CompactSafe for operatorsReliable and safe operationEcologicalCost-efficient

This switchgear is also available as SIMOSEC ANSI, and it is type-tested and UL-listed according to the standard ANSI/IEEE C37.

Product range (in extracts)

SIMOSEC switchgear for secondaryand primary distribution systems up to 24 kV

Page 13: Siemens MV Gas Insulated Switch Gear

13

25 years of gas-insulated medium- voltage switchgear from Siemens

In 198� Siemens introduced a world nov-elty to the market: The first gas-insulated switchgear for medium voltage. Right from the beginning, this innovation has written a success story.

For us, this is a commitment for con- tinuous development: As a leader in technology we have been permanently redefining performance and economic efficiency for a quarter century – a process you, as the customer, benefit from. Even tomorrow and the day after tomorrow.

Innovationby tradition

Milestones from a quarter century 1977Siemens brings the first vacuum circuit-breaker to market, setting new standards regarding the reachable number of op-erating cycles, necessary maintenance, small dimensions, reliability and environ-mental independence.

1982The first gas-insulated switchgear for the primary distribution level is available with the type designation 8DA10 and 8DB10. And for the secondary distribution level, Siemens offers the type 8DJ10 as the first hermetically welded, maintenance-free gas-insulated switchgear worldwide. This is the first switchgear that is extremely compact and climate-independent.

1985With 7SA50�, Siemens was the first worldwide provider to introduce a micro-processor-based multifunction protection relay to the market, thus initiating the age of numerical protection and control systems.

1993As the first switchgear of its kind, 8DH10 switchgear for the secondary distribution level combines hermetically welded tech-nology and maintenance-free design with simple extensibility. In the same year, the first maintenance-free, hermetically welded switchgear appears on the prima-ry distribution level: NXPLUS C. Gas work for installation and extension is therefore a thing of the past.

2000Siemens offers sealed systems for the complete medium-voltage range – up to 40.5 kV, 40 kA, 4500 A.

2006Every gas-insulated switchgear from Siemens complies with the new switch-gear standards IEC 6��71-100 and -�00.

First gas-insulated switchgear forsecondary distribution levels8DJ10 – Stadtwerke Lambrecht (Pfalz) GmbH, Germany

First gas-insulated switchgear forprimary distribution levels8DA10 – BELG (today, E.ON Bayern AG),Station Kulmbach Mitte, Germany

Page 14: Siemens MV Gas Insulated Switch Gear

14

Subject to change without prior noticeOrder no. E50001-U��9-A310-X-7600Printed in GermanyDispo 30403GB 0700�1 10��81 WS 0�076.

The information in this document contains general descriptions of the technical features, which may not always be available.An obligation to provide the respective performance feature shall exist only if expressly agreed in the terms of contract.

Siemens AGPower Transmission and DistributionMedium Voltage DivisionMozartstr. 31 c9105� ErlangenGermany

www.siemens.com/energy

For questions on power transmission anddistribution, please contact our CustomerSupport Center, �4 hours a day.

Tel.: +49 180 / 5�4 70 00Fax: +49 180 / 5�4 �4 71(Subject to charge: e.g. 1� ct/min)

E-mail: [email protected]/energy-support