Short Circuit 2011 2

download Short Circuit 2011 2

of 65

Transcript of Short Circuit 2011 2

  • 8/3/2019 Short Circuit 2011 2

    1/65

    POWER SYSTEMFAULTS

  • 8/3/2019 Short Circuit 2011 2

    2/65

  • 8/3/2019 Short Circuit 2011 2

    3/65

    POWER SYSTEM FAULTS

    Power substations as a target of study consists of someelements like Transmission Lines, Bus Bars, PowerTransformers, Outgoing Feeders, and Bus Couplers.

    Regardless of the design and the systematic preventivemaintenance procedures instituted, failures due toabnormal or fault conditions do occur

    Fault are intolerable power conditions (other thansteady-state or rated ones) to which the power system orrequirement are subjected.

  • 8/3/2019 Short Circuit 2011 2

    4/65

    General causes of power system

    faults

    1- Fault Current

    Healthy insulation in the equipment is subjected to either transientover voltages of small time duration due to switching and lightningstrokes, direct or indirect. Failure of insulation may be happened,resulting in very high fault current. This current may be more than10 times the rated or nominal current of the equipment.

    2- Insulation Aging

    Aging of power equipments may cause breakdown of its insulationeven at normal power frequency voltage.

  • 8/3/2019 Short Circuit 2011 2

    5/65

    General cause of power system

    faults (contd)

    3- External Causes

    External object such as bird, kite, or tree branch areconsidered as external cause of fault. These objectsmay span one conductor and ground causing singleline to ground fault (phase-earth) or span twoconductors causing phase-phase fault

  • 8/3/2019 Short Circuit 2011 2

    6/65

    Fault Effects

    The fault must be cleared as fast as possible. Manyequipments may be destroyed if the fault is not cleared

    rapidly. The dangerous of the faults depends on thetype of the fault, as example the three phase shortcircuit is the most dangerous fault because the shortcircuit current is maximum. Some of the effects of short

    circuit current are listed here under.

  • 8/3/2019 Short Circuit 2011 2

    7/65

    Fault Effects

    1- Due to overheating and the mechanical forcesdeveloped by faults, electrical equipments such as bus

    bars, generators, transformers will be damaged

    2- Negative sequence current arises fromunsymmetrical faults will lead to overheating.

    3- Voltage profiles may be reduced to unacceptable

    limits as a result of faults. A frequency drop may leadto instability

  • 8/3/2019 Short Circuit 2011 2

    8/65

    Fault Types

    Fault can be classified due t as:

    1- Permanent

    2- Transient

    Or due to PARTICIPATED PHASES as

    1- Phase-Earth

    2- Phase-Phase3- Phase-Phase-Earth

    4- Three-Phase or Three-Phase-Earth

  • 8/3/2019 Short Circuit 2011 2

    9/65

    Broad categorization of Fault Types

    Fault may be categorized broadly into 2 types:

    Symmetrical or balanced faults

    Asymmetrical or unbalanced faults

  • 8/3/2019 Short Circuit 2011 2

    10/65

  • 8/3/2019 Short Circuit 2011 2

    11/65

    Broad categorization of Fault Types

    3 FAULTS MAY BE REPRESENTED BY 1 CIRCUIT

    This is valid because system is maintained in a BALANCED state

    during the faultVoltages equal and 120 apart

    Currents equal and 120 apart

    Power System Plant Symmetrical

    Phase Impedances EqualMutual Impedances Equal

    Shunt Admittances Equal

  • 8/3/2019 Short Circuit 2011 2

    12/65

    Broad categorization of Fault Types

    Unbalanced FaultsUnbalanced Faults may be classified into

    SHUNT FAULTS and SERIES FAULTS.

    SHUNT FAULTS:

    Line to Ground

    Line to Line Line to Line to Ground

  • 8/3/2019 Short Circuit 2011 2

    13/65

    Broad categorization of Fault Types

  • 8/3/2019 Short Circuit 2011 2

    14/65

    Broad categorization of Fault Types

    Causes :

    1) Insulation Breakdown

    2) Lightning Discharges and other Overvoltages

    3) Mechanical Damage

    During unbalanced faults, symmetry of system Is

    lost therefore single phase representation is nolonger Valid

  • 8/3/2019 Short Circuit 2011 2

    15/65

    Broad categorization of Fault Types

    SERIES FAULTS OR OPEN CIRCUIT:

    Single Phase Open Circuit

    Double Phase Open Circuit

    Causes:

    1) Broken Conductor

    2) Operation of Fuses3) Maloperation of Single Phase Circuit Breakers

  • 8/3/2019 Short Circuit 2011 2

    16/65

    Characteristics of Faults

    A fault is characterized by:

    Magnitude of the fault current

    Power factor or phase angle of the fault current

    The magnitude of the fault current depends upon:

    The capacity and magnitude of the generating sources

    feeding into the fault

  • 8/3/2019 Short Circuit 2011 2

    17/65

    Characteristics of Faults

    The system impedance up to the point of fault orsource impedance behind the fault

    Type of fault

    System grounding, number and size of overheadground wires

    Fault resistance or resistance of the earth in the caseof ground faults and arc

    resistance in the case of both phase and ground faults

  • 8/3/2019 Short Circuit 2011 2

    18/65

    Characteristics of Faults

    The phase angle of the fault current is dependent upon:

    For phase faults: - the nature of the source andconnected circuits up to the fault location and

    For ground faults: - the type of system grounding inaddition to above.

  • 8/3/2019 Short Circuit 2011 2

    19/65

    Necessity for fault calculations

    Fault calculations are done primarily for the following:

    To determine the maximum fault current at the point ofinstallation of a circuit breaker and to choose a

    standard rating for the circuit breaker (rupturing)

    To select the type of circuit breaker depending uponthe nature and type of fault.

  • 8/3/2019 Short Circuit 2011 2

    20/65

  • 8/3/2019 Short Circuit 2011 2

    21/65

    Necessity for fault calculations

    The calculation is not only limited to present system

    requirements but also meet:

    The future expansion schemes of the system such asaddition of new generating units

    Construction of new transmission lines to evacuatepower.

    Construction of new lines to meet the load growth andor Construction of interconnecting tie lines

  • 8/3/2019 Short Circuit 2011 2

    22/65

    Necessity for fault calculations

    Basically, there are two approaches to faultcalculations. These are:

    (a) Actual reactance or impedance method

    (b) Percentage reactance or impedance method or perunit (p.u) reactance or impedance method.

    Machine and Transformer impedance or reactance arealways noted in percentage values on the nameplate.Hence the latter method is considered for ourcalculation.

  • 8/3/2019 Short Circuit 2011 2

    23/65

  • 8/3/2019 Short Circuit 2011 2

    24/65

  • 8/3/2019 Short Circuit 2011 2

    25/65

  • 8/3/2019 Short Circuit 2011 2

    26/65

  • 8/3/2019 Short Circuit 2011 2

    27/65

  • 8/3/2019 Short Circuit 2011 2

    28/65

  • 8/3/2019 Short Circuit 2011 2

    29/65

    Per Unit System

    Power system quantities such as voltage,current and impedance are often expressed inper unit or percent of specified values.

    Per unit quantities are calculated as:

    ValueBaseValueActualValuePer Unit

  • 8/3/2019 Short Circuit 2011 2

    30/65

    Per Unit Values

    base

    puSS

    S

    basepu

    II

    I

    base

    puVV

    V

    base

    puZZ

    Z

    ZZ

    2

    base

    base

    base

    puV

    S

    ZZ

    pu

    base

    2

    base

    pubase ZS

    VZZ Z

    Conversion of Per Unit Values

    Per Unit System

  • 8/3/2019 Short Circuit 2011 2

    31/65

    Per Unit System

    Usually, the nominal apparent power (S) andnominal voltage (V) are taken as the base values forpower (Sbase) and voltage (Vbase).

    The base values for the current (Ibase) andimpedance (Zbase) can be calculated based on thefirst two base values.

  • 8/3/2019 Short Circuit 2011 2

    32/65

    100%Z

    base

    actual

    %

    Z

    Z

    The percent impedance e.g. in a synchronous generator with 13.8

    kV as its nominal voltage, instead ofsaying the voltage is 12.42 kV, we say thevoltage is 0.9 p.u.

  • 8/3/2019 Short Circuit 2011 2

    33/65

    Simplified: Concerns about using phase or line voltages are

    removed in the per-unit system

    Actual values of R, XC and XL for lines, cables, and

    other electrical equipment typically phase values. It is convenient to work in terms of base VA (base

    volt-amperes)

  • 8/3/2019 Short Circuit 2011 2

    34/65

    ,3

    3

    B

    BB

    BBB

    VSI

    IVS

    B

    B

    B

    BB

    BBB

    SV

    IVZ

    ZIV

    2

    3/

    3

    Usually, the 3-phase SB or MVAB and line-to-line VB or kVB

    are selected

    IB and ZB dependent on SB and VB

  • 8/3/2019 Short Circuit 2011 2

    35/65

    The impedance of individual generators &transformer, are generally in terms ofpercent/per unit based on their own ratings.

    Impedance of transmission line in ohmicvalue

    When pieces of equipment with variousdifferent ratings are connected to a system, itis necessary to convert their impedances to aper unit value expressed on the same base.

  • 8/3/2019 Short Circuit 2011 2

    36/65

    ZV

    S

    Z

    ZZ old

    B

    old

    Bold

    B

    oldpu 2

    Z

    V

    S

    Z

    ZZ

    new

    B

    new

    B

    new

    B

    new

    pu 2

    new

    B

    new

    B

    Vbasevoltagenew&

    Sbasepowernewon theimpedanceunitpernewthebenew

    puZ

    old

    B

    old

    B

    Vbasevoltage&

    Sbasepoweron theimpedanceunitperthebeold

    puZ

    1

    2

    Change of Base

  • 8/3/2019 Short Circuit 2011 2

    37/65

    2

    new

    B

    old

    B

    old

    B

    new

    Bold

    pu

    new

    puVV

    SSZZ

    old

    B

    new

    Bold

    pu

    new

    puS

    SZZ

    From (1) and (2), the relationship between the old

    and the new per unit value

    If the voltage base are the same,

    Change of Base

  • 8/3/2019 Short Circuit 2011 2

    38/65

    2

    )(

    2

    )(

    )(

    )(

    )()(**

    newbase

    oldbase

    oldbase

    newbase

    oldpunewpu

    KV

    KV

    MVA

    MVAZZ

  • 8/3/2019 Short Circuit 2011 2

    39/65

    Other base quantites :-

    kAinkV.3

    MVACurrentBase

    OhmsinMVA

    )(kVZImpedanceBase

    b

    bb

    b

    2b

    b

  • 8/3/2019 Short Circuit 2011 2

    40/65

  • 8/3/2019 Short Circuit 2011 2

    41/65

  • 8/3/2019 Short Circuit 2011 2

    42/65

  • 8/3/2019 Short Circuit 2011 2

    43/65

  • 8/3/2019 Short Circuit 2011 2

    44/65

  • 8/3/2019 Short Circuit 2011 2

    45/65

  • 8/3/2019 Short Circuit 2011 2

    46/65

  • 8/3/2019 Short Circuit 2011 2

    47/65

  • 8/3/2019 Short Circuit 2011 2

    48/65

  • 8/3/2019 Short Circuit 2011 2

    49/65

  • 8/3/2019 Short Circuit 2011 2

    50/65

  • 8/3/2019 Short Circuit 2011 2

    51/65

  • 8/3/2019 Short Circuit 2011 2

    52/65

  • 8/3/2019 Short Circuit 2011 2

    53/65

  • 8/3/2019 Short Circuit 2011 2

    54/65

  • 8/3/2019 Short Circuit 2011 2

    55/65

    (1) To calculate the p.u impedance and % impedanceof a transmission line at 100 MVA

    base Line voltage 330 KV

    Line length 200 Kms

    Line resistance /Km = 0.06 ohms/KmLine reactance /Km = 0.4 ohms/Km

  • 8/3/2019 Short Circuit 2011 2

    56/65

    Z = R + jXFor the 200kms line length

    Z = 200 (0.06 + j 0.4)

    = 12 + j 80

    |Z| =[(12)2+ (80)2] = 80.895 ohms

  • 8/3/2019 Short Circuit 2011 2

    57/65

    Zp.u = Z x MVA base

    (KV)2base

    = 80.895 x 100

    (330)2

    = 0.0743 p.u

    %Z = 0.074 x 100

    = 7.43

    (2)T l l h i d 100 MVA b

  • 8/3/2019 Short Circuit 2011 2

    58/65

    (2)To calculate the p.u impedance to a 100 MVA base

    Given four generators; 90MVA, 11KV of 15%impedance each connected to step up transformers

    of 90MVA 11KV/330KV of 14% impedance. Calculatethe fault current at F.

    A d MVA 100

  • 8/3/2019 Short Circuit 2011 2

    59/65

    Assumed MVA = 100

    %Z generators = 15 on 90 MVA base

    or Zg p.u = 0.15 on 90 MVA base

    Zg p.u on 100 MVA base will be:

    (Zg p.u) base2 = (Zg p.u) base1 x MVA base2

    MVA base1

    (Zg p.u) 100 = 0.15 x 100

    90

    = 0.167

    %Z transformers = 14 on 90 MVA base

  • 8/3/2019 Short Circuit 2011 2

    60/65

    % t a s o e s o 90 base

    or Zt p.u = 0.14 on 90 MVA base

    Zt p.u on 100 MVA base will be:(Zt p.u) base2 = (Zt p.u) base1 x MVA base2

    MVA base1

    (Zt p.u) 100 = 0.14 x 100

    90= 0.156

  • 8/3/2019 Short Circuit 2011 2

    61/65

    The system reduces as follows

  • 8/3/2019 Short Circuit 2011 2

    62/65

    Ztotal = 0.323

    4

    = 0.08075

    Total p.u impedance at F = 0.08075 = Ztotal

    Fault MVA at F = Base MVA

    Ztotal

    = 100 MVA0.08075

    = 1238.4 MVA

  • 8/3/2019 Short Circuit 2011 2

    63/65

  • 8/3/2019 Short Circuit 2011 2

    64/65

    MORE EXAMPLES IN YOUR LECTURE BOOK,PLEASE.

  • 8/3/2019 Short Circuit 2011 2

    65/65