A Case Study on an Unusual Site with Shop-Fabricated Tanks.
by: John Cornell, Senior Tank Specialist
![Page 2: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/2.jpg)
Mr. John R. Cornell
21 Years Storage Tank Experience Around The Globe
Senior Tank Specialist for H.I.R. Technical Services
API-653 and STI-SP001 Certified Tank Inspector
Current job
Official Contracted Training Provider for API on Both
Introductory and Advanced Level Tank Training
Programs.
Exclusive Training Provider for PHSMA, DOT Part
195, Breakout Tanks.
H.I.R. Technical Serviceswww.storagetanks.info
![Page 3: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/3.jpg)
The Right Approach
Purpose of Presentation
Relate experience to new inspectors .
Challenge inspectors to bridge the gap between
standards.
Can we only use one inspection standard?
Help the tank owner.
Sources
API 653.
STI SP001.
API- 575 and others.
![Page 4: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/4.jpg)
![Page 5: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/5.jpg)
The Inspection Doesn’t Start Here…
![Page 6: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/6.jpg)
It starts here…
How old is the tank?
What has been or is
currently being stored in
the tank?
What construction code
was the tank built to?
Internal or External
inspection required?
Radiation
Fire hazards
Etc..
![Page 7: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/7.jpg)
What is the tank configuration?
Horizontal or Vertical axis?
What kind of roof?
Cone roof, Formed head, …
What type of roof access is available?
Vertical ladder, Spiral stairway, none?
Other questions…
![Page 8: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/8.jpg)
Is the tank clean?
Other questions…
![Page 9: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/9.jpg)
Choosing the inspection standard
I could keep going & going & going…
![Page 10: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/10.jpg)
Choosing the inspection standard
API-653 works for:
![Page 11: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/11.jpg)
Choosing the inspection standard
API-653 and STI-SP001 works for:
![Page 12: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/12.jpg)
Choosing the inspection standard
Don’t use API-653 for these, unless you
want to.
![Page 13: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/13.jpg)
Case Study: The Ugly Tank
Age: Unknown.
Operating Temp: >200° F.
Design Standard: Unknown.
Bottom: Cone down.
Bottom: Unsupported.
![Page 14: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/14.jpg)
Should we use API-653
API-653:
Temp: Up to 500° F
(260°C).
Bottom must be uniformly
supported.
Covers tanks built to API 650 and API 12C..
may apply to any steel tank constructed in
accordance with a tank specification.
![Page 15: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/15.jpg)
Can we use API-653
“API 653 was intended to inspect tanks constructed in
accordance with API 650 or API 620 as well as other
large field-erected tanks, while API 12R1 was
designed for production tanks.”
Phil Myers, P.E.
The New STI SP001 Tank Inspection Standard and
Compliance with The New EPA SPCC Rule for
Petroleum Storage Tanks, July 22, 2004
API-620: Does permit bottoms to be
sloped.
Question: Can API-653 inspector,
inspect API-620 tanks. Yes, under
limited conditions.
![Page 16: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/16.jpg)
Should we use STI-SP001
STI-SP001:
Temp < 200° F (93.3°C).
Tank may be on legs.
ELEVATED AST – an AST which is not in
contact with the ground.. Examples of
elevated tanks are tanks constructed on
grillage or grating, or tanks on supports.
![Page 17: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/17.jpg)
The inspection started at the bottom
![Page 18: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/18.jpg)
API-653 approach
Remember, API -
653 minimums are
based on a fully
supported bottoms.
![Page 19: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/19.jpg)
API-653 approach
Remember, API - 653 minimums are
based on a fully supported bottoms.
API-653, Table 4.4…..050”
API-653, 4.3.2.1(old “t” =/> 60%)
Take-away: The thickness of corroded
(Shell / Wall) may be reduced by 40%.
.375” x .60% = .225”
API-650 calls it a shell, API-620 calls
everything a wall..
![Page 20: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/20.jpg)
STI SP001 approach
Category 1 ASTs - The remaining AST
shell thickness shall not be less than
25% of the original “t”.
.375” x 25% = .0938”
![Page 21: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/21.jpg)
How thick should the cone be?
API-653, Table 4.4…..050”
653, 4.3.2.1(old “t” =/> 60%)
Plates may be reduced by 40%.
.375” x .60% = .225”
STI-SP001 - The remaining AST shell
“t” shall not be less than 25% of the
original “t”.
.375” x 25% = .0938”
![Page 22: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/22.jpg)
Required Floor / Cone Thickness
So for the floor
portion of the tank
inspection, we
instructed the
inspector to follow
the perceived
requirements of
API-653.
![Page 23: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/23.jpg)
Floor welds need to be inspected
STI-SP001, 8.3.2
Inspect the welds
for cracking by
visual inspection or
other means.
API-653, 4.3.8
Deterioration of
welds… must be
evaluated …
![Page 24: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/24.jpg)
Lessons learned - Coned Tanks
Both API-653 and STI-SP001 have
limits.
Use all available standards as tools..
Think about this..
Are you trying to pass the tank
or
Are you trying to fail the tank
![Page 25: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/25.jpg)
Now onto the shell
![Page 26: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/26.jpg)
Ultrasonic Thickness Readings
API-653:
Insulated tanks need to have insulation
removed only to the extent necessary to
determine the condition of the exterior
wall of the tank or the roof.
No particular guidance was given to our
inspector…
![Page 27: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/27.jpg)
Ultrasonic Thickness Readings
STI-SP001:
Readings must be concentrated in areas
where corrosion is likely to occur.
Direct guidance for the inspector to seek out
and find the areas at which accelerated
corrosion may be located.
![Page 28: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/28.jpg)
Ultrasonic Thickness Readings
API-653 / STI-SP001 Hybrid
Combination:
Remove the insulation as required to
determine the condition of the tank’s
exterior and take additional readings in
areas where internal corrosion is likely to
occur.
There was already enough insulation missing
on this tank that no addition insulation needed
to be removed.
![Page 29: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/29.jpg)
Shell Inspection Results
![Page 30: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/30.jpg)
Shell Inspection Results
14,000
Gallon
![Page 31: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/31.jpg)
Roof Hazards – Falling over
Fact: Many tank inspectors do not have
training in fall protection.
www.api-u.org/eLearning/FallProtectionIntro.html
![Page 32: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/32.jpg)
Roof Hazards – Falling over
A man was killed when he
fell from the top of a storage
tank.
There were no guardrails or
other safety devices on the
tops of the tanks,
the victim was not using
any fall protection
equipment.
![Page 33: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/33.jpg)
Roof Hazards – Falling overEmployers should follow the OSHA
guidelines for personal protective
equipment.
Owners, consider devices such as
nonskid surfaces and railings on top of
the tanks, and the
surfaces on top
should be kept free
of oily residue.
![Page 34: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/34.jpg)
Roof Hazards – Unsafe Ladders
Check the ladder and stairways for loose
treads or missing bolts and etc..
![Page 35: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/35.jpg)
Roof Hazards – Unsafe Treads
Check the ladder and stairways for loose
treads or missing bolts and etc..
![Page 36: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/36.jpg)
Topside Corrosion
API-575, 7.2.9 Tank Roof Inspection
Hammer testing is not a recommended
method of establishing roof plate integrity for
personnel loading.
![Page 37: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/37.jpg)
Check for corrosion as you go.
API Document 1972, Pre-653
1) All roofs should be hammer tested.
2) Regardless of the external appearance of
the roof.
3)The hammer testing should be done with a
full swing of the arm.
![Page 38: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/38.jpg)
Underside Roof Corrosion
STI SP001:..It may be necessary to check the
plate thickness with a hammer test to verify its
adequacy.
![Page 39: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/39.jpg)
Check for corrosion as you go.
API-653 permits any area on a tank roof
to corrode to a average thickness of not
less than .09” thickness in any 100
square inch area.
Experience shows that there can be
isolated thin spots.
![Page 40: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/40.jpg)
Check for corrosion as you go.
Experience shows that there can be isolated
thin spots.
![Page 41: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/41.jpg)
Floating Roof Inspection Hazards
This session will discuss approaching the inspection with safety in mind by reviewing:
Both Internal and External floating roofs.
and
How various designs will alter the inspections report.
![Page 42: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/42.jpg)
Entry into confined space occurs
when the vertical plane of a shell
manhole is broken.
Are you trained to be in here?
![Page 43: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/43.jpg)
Shows a floating roof from the top of
the cone roof looking in thru the roof
hatch.
![Page 44: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/44.jpg)
External Floating Roof Access
![Page 45: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/45.jpg)
Need more tank training?
Go to: www.api-u.org
Inspection of Fiberglass and Plastic Tanks.
Introduction to API 620, 650 and 653.
Advanced Tank Training.
API-12F and 12R1.
![Page 46: Shop-fabricated Tanks](https://reader036.fdocuments.net/reader036/viewer/2022081718/5530f82a4a7959f72d8b4923/html5/thumbnails/46.jpg)