Damage Evolution of Concrete Piles Mixed with Admixtures ...
Shake Table Test on a Low- Damage Concrete Wall Building
Transcript of Shake Table Test on a Low- Damage Concrete Wall Building
![Page 1: Shake Table Test on a Low- Damage Concrete Wall Building](https://reader030.fdocuments.net/reader030/viewer/2022020620/61e51c4ffb190f785b63bb2a/html5/thumbnails/1.jpg)
Shake Table Test on a Low-Damage Concrete Wall Building
2017-7-25
![Page 2: Shake Table Test on a Low- Damage Concrete Wall Building](https://reader030.fdocuments.net/reader030/viewer/2022020620/61e51c4ffb190f785b63bb2a/html5/thumbnails/2.jpg)
ILEE Project
NZ invited to propose an ILEE test for 2017 at Tongji University, China
Focus:
Shake-tables
System level verification
Low-damage concrete systems
![Page 3: Shake Table Test on a Low- Damage Concrete Wall Building](https://reader030.fdocuments.net/reader030/viewer/2022020620/61e51c4ffb190f785b63bb2a/html5/thumbnails/3.jpg)
Objectives for Test
Verify seismic response of low-damage concrete wall building implementing state-of-art concepts
Verify practical construction details used in low-damage buildings
Investigate interaction of the structural components (gravity and lateral systems)
Sub objectives:
1. Compare alternative wall-to-floor connection details
2. Compare alternative dissipating devices
3. Torsional / bi-directional response
4. Diaphragm design / load paths
5. PT walls with conventional walls
![Page 4: Shake Table Test on a Low- Damage Concrete Wall Building](https://reader030.fdocuments.net/reader030/viewer/2022020620/61e51c4ffb190f785b63bb2a/html5/thumbnails/4.jpg)
Update
Preliminary design finalized
Detailed design Component design (wall, frame, damper)
Connection detailing design (wall-to-floor, wall-to-foundation, column-to-foundation, damper connections)
![Page 5: Shake Table Test on a Low- Damage Concrete Wall Building](https://reader030.fdocuments.net/reader030/viewer/2022020620/61e51c4ffb190f785b63bb2a/html5/thumbnails/5.jpg)
Table capacity
Table dimension 10 x 6m
140t payload
500t-m weak direction, 800t-m strong axis
Crane capacity = 50t
Crane height = 18m
Gate 9x9m
Large area concrete and cutting not allowed
Minor grouting is permitted
![Page 6: Shake Table Test on a Low- Damage Concrete Wall Building](https://reader030.fdocuments.net/reader030/viewer/2022020620/61e51c4ffb190f785b63bb2a/html5/thumbnails/6.jpg)
Review of previous design
- Use different floor system and configurations on each level - Mixture of precast and composite floor - Link slab on one side of double-tee - Tongue slotted device at center - Flexible floor slabs for rib and timber and comslab levels - Torsion induced
- Too many variables, irregularity, too complex. Torsion can still be introduced by other ways.
- 140t payload, 500 t-m overturning moment
- Brace hard to design, difficult to adjust stiffness at short direction
![Page 7: Shake Table Test on a Low- Damage Concrete Wall Building](https://reader030.fdocuments.net/reader030/viewer/2022020620/61e51c4ffb190f785b63bb2a/html5/thumbnails/7.jpg)
Proposed Test Building
2 storeys (@ full scale)
Fit onto 2 tables joined (10 × 6m)
Post-tensioned wall system
Gravity load resisting frames/columns
F1 double-tee; F2 composite floor
Interchangeable connections (wall-to-floor, beam-to-
column, wall-to-foundation dissipaters)
Flexible connection
Isolated connection
![Page 8: Shake Table Test on a Low- Damage Concrete Wall Building](https://reader030.fdocuments.net/reader030/viewer/2022020620/61e51c4ffb190f785b63bb2a/html5/thumbnails/8.jpg)
Plan – level 1
![Page 9: Shake Table Test on a Low- Damage Concrete Wall Building](https://reader030.fdocuments.net/reader030/viewer/2022020620/61e51c4ffb190f785b63bb2a/html5/thumbnails/9.jpg)
Plan – level 2
![Page 10: Shake Table Test on a Low- Damage Concrete Wall Building](https://reader030.fdocuments.net/reader030/viewer/2022020620/61e51c4ffb190f785b63bb2a/html5/thumbnails/10.jpg)
Proposed Test Building
2 storeys
Weight 135.7 t
Height 8 m
Design moment 328 t-m
800 t-m
? t-m ? t-m
(500 t-m)
![Page 11: Shake Table Test on a Low- Damage Concrete Wall Building](https://reader030.fdocuments.net/reader030/viewer/2022020620/61e51c4ffb190f785b63bb2a/html5/thumbnails/11.jpg)
Dimension and weight
Member Size (mm)
Columns in all levels 400 x 400
Beams in all levels 400 x 300
Walls at x direction 150 x 2500
Walls at y direction 150 x 2000
Double-Tee floor 300TT
Composite floor Ultra-span 130
Level Self - Weight (t) Added mass
(t) Total (t)
Wall Column Beam Floor Total
Foundation 41.20
Level 1 12.96 6.14 7.08 17.32 43.50 7
Level 2 12.96 6.14 7.78 10.07 36.95 7
Total 25.92 12.28 14.86 26.49 121.7 14 135.7
![Page 12: Shake Table Test on a Low- Damage Concrete Wall Building](https://reader030.fdocuments.net/reader030/viewer/2022020620/61e51c4ffb190f785b63bb2a/html5/thumbnails/12.jpg)
Construction method
41 t 44 t
37 t
Crane capacity = 50t
Gate 9x9m
Large area concrete and cutting not allowed
Minor grouting is permitted
![Page 13: Shake Table Test on a Low- Damage Concrete Wall Building](https://reader030.fdocuments.net/reader030/viewer/2022020620/61e51c4ffb190f785b63bb2a/html5/thumbnails/13.jpg)
Frame – column joints
![Page 14: Shake Table Test on a Low- Damage Concrete Wall Building](https://reader030.fdocuments.net/reader030/viewer/2022020620/61e51c4ffb190f785b63bb2a/html5/thumbnails/14.jpg)
Test variations
Drift = 2% & 1%, damping 5%
Drift = 1%, damping 10-12%
Design
case
Test
Variatio
n
Desig
n drift
Energy dissipating device
Deliberate
torsion Wall base
Beam-column
joints
I #1 2% Steel fuse N/A No
II #2 1% Steel fuse N/A No
III
#3 1% Steel fuse Steel fuse No
#4 1% Viscous
damper Steel fuse No
#5 1% Viscous
damper HF2V No
#6 1% Viscous
damper HF2V Yes
#7 1% Viscous
damper HF2V Yes
![Page 15: Shake Table Test on a Low- Damage Concrete Wall Building](https://reader030.fdocuments.net/reader030/viewer/2022020620/61e51c4ffb190f785b63bb2a/html5/thumbnails/15.jpg)
Frame – slotted beam joints
- With energy dissipation devices - Without energy dissipation devices
![Page 16: Shake Table Test on a Low- Damage Concrete Wall Building](https://reader030.fdocuments.net/reader030/viewer/2022020620/61e51c4ffb190f785b63bb2a/html5/thumbnails/16.jpg)
Level I
Wall-to-floor connection - Isolated
![Page 17: Shake Table Test on a Low- Damage Concrete Wall Building](https://reader030.fdocuments.net/reader030/viewer/2022020620/61e51c4ffb190f785b63bb2a/html5/thumbnails/17.jpg)
Level I
Wall-to-floor connection - Link slab flexible
![Page 18: Shake Table Test on a Low- Damage Concrete Wall Building](https://reader030.fdocuments.net/reader030/viewer/2022020620/61e51c4ffb190f785b63bb2a/html5/thumbnails/18.jpg)
THANK YOU! QUESTIONS?