20
FILE No. A90-9611 SERVICE MANUAL AIR CONDITIONER SPLIT TYPE 2 WAY CASSETTE TYPE, HEATPUMP RAV-103TUH-PE RAV-133TUH-PE/RAV-132AH-PE RAV-163TUH-PE/RAV-162AH-PE Printed in UK Dec 1996 s Heronhill - for all your Toshiba requirements Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Transcript of SERVICE MANUAL AIR CONDITIONER SPLIT · PDF fileSERVICE MANUAL AIR CONDITIONER SPLIT TYPE 2...

Page 1: SERVICE MANUAL AIR CONDITIONER SPLIT · PDF fileSERVICE MANUAL AIR CONDITIONER SPLIT TYPE 2 WAY CASSETTE TYPE, ... WIRING DIAGRAM ... 07 Relay 52C Magnetic Contactor 63H High Pressure

FILE No. A90-9611

SERVICE MANUAL

AIR CONDITIONER SPLIT TYPE

2 WAY CASSETTE TYPE, HEATPUMPRAV-103TUH-PERAV-133TUH-PE/RAV-132AH-PERAV-163TUH-PE/RAV-162AH-PE

Printed in UK Dec 1996 s

Heronhill - for all your Toshiba requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Page 2: SERVICE MANUAL AIR CONDITIONER SPLIT · PDF fileSERVICE MANUAL AIR CONDITIONER SPLIT TYPE 2 WAY CASSETTE TYPE, ... WIRING DIAGRAM ... 07 Relay 52C Magnetic Contactor 63H High Pressure

-2-

• Operating conditions of units are as follows:

Note 1 : Cooling Capacity is based on the following temperature conditions:Indoor air inlet temperature 27°C DB, 19°C WB.Outdoor air inlet temperature 35°C DB.

Note 2: Heating Capacity is based on the following temperature conditions:Indoor air inlet temperature 20°C DB.Outdoor air inlet temperature 7°C DB, 6°C WB.

Note 3: For details on the Remote Controller and Control Circuitsrefer to Service Manual A90-9503.

OUTDOOR TEMPERATURE -2 TO 43°C (COOL)

-10 TO 21°C (HEAT)

ROOM TEMPERATURE 18 TO 32°C (COOL)

15 TO 29°C (HEAT)

ROOM HUMIDITY LESS THAN 80% (COOL)

CONTENTS

1. SPECIFICATION....................................................................................................................................................3

2. CONSTRUCTION VIEWS......................................................................................................................................6

3. WIRING DIAGRAM................................................................................................................................................8

4. SPECIFICATIONS OF ELECTRICAL PARTS........................................................................................................10

5. INTERFACE PCB.................................................................................................................................................12

6. REFRIGERANT PIPING DIAGRAM......................................................................................................................13

7. PERFORMANCE CHARACTER............................................................................................................................15

8. EXPLODED VIEWS AND PARTS LISTS...............................................................................................................17

SUMMARY

• The units referred to within this manual conform with the protection requirements of Directives 89/336/EECElectromagnetic Compatibility and 73/23/EEC Low Voltage.

Heronhill - for all your Toshiba requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Page 3: SERVICE MANUAL AIR CONDITIONER SPLIT · PDF fileSERVICE MANUAL AIR CONDITIONER SPLIT TYPE 2 WAY CASSETTE TYPE, ... WIRING DIAGRAM ... 07 Relay 52C Magnetic Contactor 63H High Pressure

-3-

MODEL

Power source

ITEM

Starting current

Power consumption

Running current

Power factor

Operating noise (SPL) (High, Med, Low)

Refrigerant

Phase

Hz

V

kW

%

A

A

dB(A)

Name of refrigerant

Interconnectionpipe

Larger side size

Coupler style

Smaller side size

Coupler style

mm

mm

Condensate drain pipe diameter

Appearance colour

Dimensions

Net weight

Heat exchanger type

Indoor fan type

Air volume

Fan motor output

Appearance colour

CEILING PANEL Model

Height

Width

Depth

mm

mm

mm

kg

m3/h

Net weight

Height

Depth

mm

mm

mm

kg

Dimensions Width

Air filter

Specifications are subject to change without notice.

RAV-103TUH-PE

1

220-240

50

0.07

93

0.33

0.6

R-22

Ø12.7

Flare

Ø6.4

Flare

Ø25.5(OD)mm

Grey (zinc galvanized steel+ Thermal insulator)

RBC-U133PG(W)-PE

Silky white (Munsell 2.9Y8.9/0.8)

25

1050

550

4.5

Washable

Finned tube

Transverse flow fan

550

7 x 2

190

910

480

23

W

40/36/34

1.SPECIFICATION

Heronhill - for all your Toshiba requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Page 4: SERVICE MANUAL AIR CONDITIONER SPLIT · PDF fileSERVICE MANUAL AIR CONDITIONER SPLIT TYPE 2 WAY CASSETTE TYPE, ... WIRING DIAGRAM ... 07 Relay 52C Magnetic Contactor 63H High Pressure

-4-

MODELITEM RAV-133TUH-PE

3.6kW

kW 4.2Heating capacity

Cooling capacity

1

50

HEATINGCOOLING

2.1 2.2

Power source

Power consumption

Power factor 89 89

Running current 10.3 10.7

Starting current

Operating noise (SPL)

Refrigerant

60

40/36/34

R-22

1.235

Refrigerant control

Interconnection pipe

Ø12.7

Flare

Ø 6.4

Flare7.5

Hz

Phase

kW

%

A

A

dB(A)dB(A)

kg

g/m

mm

m

Indoor unit (High, Med, Low)

Outdoor unit

Name of refrigerant

Charge volume

Add. volume (20-30m)

Larger side size

Coupler style

Smaller side size

Coupler styleStandard length

Maximum length(of one way) *1 m

30

If indoor unit higher m 15

If outdoor unit higher m 30

Condensate drain pipe diameter mmINDOOR UNIT Model RAV-133TUH-PE

Appearance colour Grey (zinc galvanized steel + thermal insulator)

Capillary tube & Expansion valve

50

Dimensions

Height mm 190

910Width mm

Depth mm 480

Net weight kg 23

Heat exchanger type Finned tubeIndoor fan type Transverse flow fan

Air volume m3/h 700Fan motor output W 7 x 2Air filter Washable

OUTDOOR UNIT Model RAV-132AH-PEAppearance colour Bronze white (Munsell 6Y7.5/1)

Dimensions Width mm

Depth mm

Height mm 740

880

310

Net weight kg 61

Ø 25.5 (OD)

Outdoor fan type Propeller fan

Air flow volume m3/h 2,700

Fan motor output W 39

PH230X3-4LSCompressor

Model

1.5

Protective device High pressure switch, Fuse, Crankcase heater, Overload relay, Bimetal thermostat

mm

220-240

Finned tube

Appearance colour Silky white (Munsell 2.9Y8.9/0.8)

Dimensions Width mm

Depth mm

Height mm 25

1050

550

Net weight kg 4.5

Washable

CEILING PANEL Model

Air filter

Specifications are subject to change without notice.

* Note 1 : These mean actual length.

RBC-U133PG(W)-PE

Heat exchanger type

Output kW

V

Maximum height difference

Heronhill - for all your Toshiba requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Page 5: SERVICE MANUAL AIR CONDITIONER SPLIT · PDF fileSERVICE MANUAL AIR CONDITIONER SPLIT TYPE 2 WAY CASSETTE TYPE, ... WIRING DIAGRAM ... 07 Relay 52C Magnetic Contactor 63H High Pressure

-5-

ITEM MODEL

Cooling capacity kW

kW

4.5

5.0

Power source V

50

Power consumption kW

Power factor %

Running current A

Starting current

Operatingnoise (SPL)

Indoor unit (high/med/low) 41/37/35

50

R-22

35

Outdoor unit

Refrigerant

Name of refrigerant

Charge volume kg

Add. volume (20-30m) g/m

Capillary tube & Expansion valve

Interconnectionpipe

Larger side size mm ø 12.7

Flare

mm ø 6.4

Coupler style FlareStandard length m 7.5

Maximum length(of one way) *1 m 30

15m

m 30

Condensate drain pipe diameter ø 25.5(OD)

RAV-163TUH-PE

Appearance colour Grey (zinc galvanized steel + thermal insulator)

Dimensions

Height

mm

mm 190

Width mm 910

Depth mm 480

Net weight kg 23Heat exchanger type Finned tube

Transverse flow fan

750

Fan motor output 7 x 2

Air filter

Refrigerant control

880

310

61Finned tubePropeller fan

2,700

39

Dimensions

Height mm

Width mm

Depth mm

Heat exchanger type

Net weight

Outdoor fan type

Air flow volume

Fan motor output

CompressorModel

Output

A

kg

m3/h

kW

W

Hz

Bronze white (Munsell 6Y7.5/1)

740

INDOOR UNIT Model

Heating capacity

Smaller side size

Coupler style

Phase

Indoor fan typeAir volume

OUTDOOR UNIT Model

Appearance colour

W

m3/h

Washable

1.6

RAV-163TUH-PE

1

220-240

COOLING

90

11.1

2.3

HEATING2.2

90

10.6

60

RAV-162AH-PE

PH250X3-4LS

1.5

Protective device

CEILING PANEL Model

Appearance colour

Dimensions Height

Width

Depth

mm

mm

mm

Net weight

Air filter

Specifications are subject to change without notice.

* Note 1 : These mean actual length.

High pressure switch, Fuse, Crankcase heater, Overload relay, Bimetal thermostat

RBC-U133PG(W)-PE

Silky white (Munsell 2.9Y8.9/0.8)

25

550

Washable

4.5

1050

If outdoor unit higher

If indoor unit higher

Maximum height difference

kg

dB (A)

dB (A)

Heronhill - for all your Toshiba requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Page 6: SERVICE MANUAL AIR CONDITIONER SPLIT · PDF fileSERVICE MANUAL AIR CONDITIONER SPLIT TYPE 2 WAY CASSETTE TYPE, ... WIRING DIAGRAM ... 07 Relay 52C Magnetic Contactor 63H High Pressure

-6-

2. CONSTRUCTION VIEWS

2.1 Indoor unitRAV-103TUH-PERAV-133TUH-PERAV-163TUH-PE

Spa

ce r

equi

red

for

serv

ice

and

inst

alla

tion

(Unit: mm)

550

Vie

w A

20

0

Ceiling opening 510

Panel outer dimension 550

Hang bolt pitch 480

41020 40

40

Han

g bo

lt pi

tch

930

Cei

ling

open

ing

1010

Pan

el o

uter

dim

ensi

on 1

050

73

131

96

186

26

717

0

156

140

190

1050

84

013

04

80

190Lo

ng h

ole

Re

mo

te c

on

tro

ller

60

0

Min

imum

Min

imum

60

0

Min

imum

70

70R

efrig

eran

t pi

ping

joi

nt

(

Gas

∅ 1

2.7)

Wiri

ng c

onne

ctio

n

84

011

0

90

66

20

40

60

29

0

Han

ger

bolt

(4-

M10

)R

efrig

eran

t pi

ping

joi

nt

( L

iqui

d ∅

6.4

)

256

00

A

12.5

83.5

2-4.

5 x

9L 120

Dra

in p

ipe

join

t

(out

er ∅

25.

5)

Heronhill - for all your Toshiba requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Page 7: SERVICE MANUAL AIR CONDITIONER SPLIT · PDF fileSERVICE MANUAL AIR CONDITIONER SPLIT TYPE 2 WAY CASSETTE TYPE, ... WIRING DIAGRAM ... 07 Relay 52C Magnetic Contactor 63H High Pressure

-7-

2.2 Outdoor unitRAV-132AH-PERAV-162AH-PE

(2-(20 x 60) slots)

Hole for drain

(2-ø19 hole)

(Liquid side ∅ 6.4)

(Gas side ∅ 12.7)Refrigerant piping joint

Anchor bolt hole

Blow out guidemounting hole

(4-ø3 embosses)

(Space for wiringand piping)

Outlet

(Space for wiringand piping)

Space required for service

When installed with theoutlet faced to the wall side

When installed with theinlet faced to the wall side

(Unit: mm)

(4-(12x18)slots) Air outlet

(Both sides)

Carrying handleElectric partsbox Terminal cover

Refrigerant piping joint

Knock - out hole for drain

Earth screw (M6)

Heronhill - for all your Toshiba requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Page 8: SERVICE MANUAL AIR CONDITIONER SPLIT · PDF fileSERVICE MANUAL AIR CONDITIONER SPLIT TYPE 2 WAY CASSETTE TYPE, ... WIRING DIAGRAM ... 07 Relay 52C Magnetic Contactor 63H High Pressure

-8-

S

how

s te

rmin

al b

lock

and

figu

res

show

term

inal

num

bers

.

Bro

ken

lines

sho

w w

iring

at s

ite.

Do

not o

pera

te th

e un

its w

ith m

agne

tic c

onta

ctor

pus

hed

in.

Sym

bol

Nam

e

S

ymbo

l

N

ame

FM

Fan

mot

or

43

Rel

ay

RC

R

unni

ng c

apac

itor

RY

01~

RY

14 R

elay

T

R

T

rans

form

er

S

M01

,02

S

tepp

er m

otor

TA

Sen

sor

C

S

Flo

at s

witc

h

T

C

S

enso

r

DM

D

rain

mot

or

F

Fus

e (P

CB

)

F3

Fus

e (I

nter

face

PC

B)

3.1 RAV-103TUH-PE RAV-133TUH-PE RAV-163TUH-PE

(

)R

Y01

outp

ut

Ear

thS

crew

F2

Indo

or u

nit

Out

door

uni

t (1 P

hase

mod

el)

Rem

ote

Con

trol

ler

CS

43C

N10

(PU

MP

)

TR

RY

01

RY

14

CN

01(T

RA

NS

)

CN

12

RE

MO

CO

N

UL

L

M

H

TA

CN

04(T

A)

CN

05(T

C)

CN

07(F

AN

)T

C

RY

11

WHI

FM

CN

09(L

OU

VE

R)

(L1)

(N) CN

03(S

ER

IAL)

CN

11(F

LOAT

)

43

DM

FP

ower

Sup

ply

220/

240V

5

0Hz

Spa

rkK

iller

FM 01

02

BLU

BLU

OR

N

WHI

RED

RC02

RC01

SM

SM01 02

TR

INT

ER

FAC

EP

CB

3. WIRING DIAGRAM

OR

NB

LKB

LK

RE

DWH

IW

HI

YEL

YELRED

YEL

BLU

OR

N B

LK

RE

D

F3

RY

04

RY

03

RY

02

Heronhill - for all your Toshiba requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Page 9: SERVICE MANUAL AIR CONDITIONER SPLIT · PDF fileSERVICE MANUAL AIR CONDITIONER SPLIT TYPE 2 WAY CASSETTE TYPE, ... WIRING DIAGRAM ... 07 Relay 52C Magnetic Contactor 63H High Pressure

-9-

TR

3.2 RAV-132AH-PE RAV-162AH-PE

Power Supply 220/240V 50HzCH

EarthScrew

Earth

RY07

F

1. Shows terminal block and figures show terminal numbers.Broken lines show wiring at site.

Don't operate the units with magnetic contactor pushed.

CMRCC52C

TE

TL

BLK

TD

BLK

WHI

63H

52C

F2

Indoor unit

Outdoor unit

26HD

WaveControlCircuit

20SR20SF

Symbol Name Symbo Name Symbol Name

20SF Solenoid Coil (4 Way Valve) CM Compressor F2 Fuse (T5A)

RY05, 07 Relay 52C Magnetic Contactor 63H High Pressure Switch

51C Overload Relay FMo Fan Motor (Out door) CH Crank Case Heater

20SR Solenoid Coil (2 Way Valve) TL Sensor F Fuse (on PCB)

RCc Running Capacitor (Compressor) TE Sensor TR Transformer

RCo Running Capacitor (Fan motor) 26HD Bimetal Thermostat TD Sensor

WHI FM0

RED

BLK

RED

BLU

BLK WHI WHI

RY05

RED

GRY

RED

RCO

51C

Heronhill - for all your Toshiba requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Page 10: SERVICE MANUAL AIR CONDITIONER SPLIT · PDF fileSERVICE MANUAL AIR CONDITIONER SPLIT TYPE 2 WAY CASSETTE TYPE, ... WIRING DIAGRAM ... 07 Relay 52C Magnetic Contactor 63H High Pressure

-10-

4.2. RAV-163TUH-PE

No. PARTS NAME TYPE SPECIFICATIONS

1 Indoor unit fan motor (x2) PAF-230-7-4 Output (Rated) 7W, 4 pole, 1 phase, 230V, 50Hz

2Running capacitor forindoor fan motor (x2)

EVM45M504UF AC 450V, 0.5µF

3 Transformer (Indoor unit) ST-9586 AC187~264V

4 Stepper motor (x2) MP35EA2 DC12V, 80mNm

5 Relay LY2F AC 240V, 2ab

6 Drain pump PCD-4N230TF-7 AC230V, 0.2A

7 Float switch FS-085-003E AC230V, 0.5A

8Sensor for roomtemperature

Maximum input38mA

°C 15 20 25 30 40

16.1 12.6 10.0 8.0 5.2

9Indoor unit sensor forheat- exchangertemperature.

DTN-C103J40Maximum input34mA

°C –12 0 25 50

62.29 32.82 10.0 3.59

4.1 RAV-103TUH-PE, RAV-133TUH-PE

No. PARTS NAME TYPE SPECIFICATIONS

1 Indoor unit fan motor (x2) PAF-230-7-4 Output (Rated) 7W, 4 pole, 1 phase, 230V, 50Hz

2Running capacitor for indoorfan motor (x2)

EEP2H105HQA105 AC 500V, 1.0µF

3 Transformer (Indoor unit) ST-9586 AC187~264V

4 Stepper motor (x2) MP35EA2 DC12V, 80mNm

5 Relay LY2F AC 240V, 2ab

6 Drain pump PCD-4N230TF-7 AC230V, 0.2A

7 Float switch FS-085-003E AC230V, 0.5A

8 Sensor for room temperatureMaximum input38mA

°C 15 20 25 30 40

16.1 12.6 10.0 8.0 5.2

9Indoor unit sensor for heat-exchanger temperature.

DTN-C103J40Maximum input34mA

°C –12 0 25 50

62.29 32.82 10.0 3.59

4. SPECIFICATION OF ELECTRICAL PARTS

Heronhill - for all your Toshiba requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Page 11: SERVICE MANUAL AIR CONDITIONER SPLIT · PDF fileSERVICE MANUAL AIR CONDITIONER SPLIT TYPE 2 WAY CASSETTE TYPE, ... WIRING DIAGRAM ... 07 Relay 52C Magnetic Contactor 63H High Pressure

-11-

No. PARTS NAME TYPE SPECIFICATIONS

1 Compressor PH250X3-4LS Output (Rated) 1.5 kW, 2 pole, 220/240V, 1 phase, 50Hz

2 Outdoor unit fan motor SMF-230-39N-2 Output (Rated) 39W, 6 pole, 230V, 1 phase, 50Hz

3Running capacitor for outdoorfan motor

EEP2G405HQA114 AC 400V, 4 µF

4 Magnetic contactor FMca-1S AC 220-240V, 50Hz

5 High pressure switch ACB-2TBO4WTripping pressure 30kg/cm²GResetting pressure 23kg/cm²G

6 Solenoid coil for four-way valve CHV-AC240V AC 220-240V

7 Crankcase heater AC 240V, 28W

8 Sensor for defrostingMaximum input15.5mA

°C –12 10

67.5 21.3

9 Fuse T5A

10Sensor for cooling operation in lowambient temperature

Maximum input15.5mA

°C –12 10

67.5 21.3

11 Solenoid coil for two-way valve NEV AC 240V AC 220-240V, 50Hz

12 Running capacitor for compressor MT-44MP456W AC 440V 45µF

13Transformer(Outdoor unit)

FT-67 AC 187-264V

14 Overload relay OL-177GM15 AC 240V, Tripping temp: 165°C, Resetting temp: 80°C

15 Bimetal thermostat CS-7 Tripping temp: 110°C, Resetting temp 90°C

4.3 RAV-132AH-PE

No. PARTS NAME TYPE SPECIFICATIONS

1 Compressor PH230X3-4LS Output (Rated) 1.5 kW, 2 pole, 220/240V, 1 phase, 50Hz

2 Outdoor unit fan motor SMF-230-39N-2 Output (Rated) 39W, 6 pole, 230V, 1 phase, 50Hz

3Running capacitor for outdoorfan motor

EEP2G405HQA114 AC 400V, 4 µF

4 Magnetic contactor FMca-1S AC 220-240V, 50Hz

5 High pressure switch ACB-2TBO4WTripping pressure 30kg/cm²GResetting pressure 23kg/cm²G

6 Solenoid coil for four-way valve CHV-AC240V AC 220-240V

7 Crankcase heater AC 240V, 28W

8 Sensor for defrostingMaximum input15.5mA

°C –12 10

67.5 21.3

9 Fuse T5A

10Sensor for cooling operation in lowambient temperature

Maximum input15.5mA

°C –12 10

67.5 21.3

11 Solenoid coil for two-way valve NEV AC 240V AC 220-240V, 50Hz

12 Running capacitor for compressor MT-44MP456W AC 440V 45µF

13Transformer(Outdoor unit)

FT-67 AC 187-264V

14 Overload relay OL-177GM15 AC 240V, Tripping temp: 165°C, Resetting temp: 80°C

15 Bimetal thermostat CS-7 Tripping temp: 110°C, Resetting temp 90°C

4.4 RAV-162AH-PE

Heronhill - for all your Toshiba requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Page 12: SERVICE MANUAL AIR CONDITIONER SPLIT · PDF fileSERVICE MANUAL AIR CONDITIONER SPLIT TYPE 2 WAY CASSETTE TYPE, ... WIRING DIAGRAM ... 07 Relay 52C Magnetic Contactor 63H High Pressure

-12-

5. INTERFACE PCB FOR LOUVER OPERATION

An additional PCB, referred to as the Interface PCB, is fitted to this unit to operate the dc stepper motors,which drive the louvers. The power supply to the interface PCB is via relay RY11 on the indoor PCB.

Heronhill - for all your Toshiba requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Page 13: SERVICE MANUAL AIR CONDITIONER SPLIT · PDF fileSERVICE MANUAL AIR CONDITIONER SPLIT TYPE 2 WAY CASSETTE TYPE, ... WIRING DIAGRAM ... 07 Relay 52C Magnetic Contactor 63H High Pressure

-13-

Cooling

Heating

6. REFRIGERANT PIPING DIAGRAM

Refrigerant pipe (Smaller side)ø6.4mm (1/4")

Strainer

Heat exchanger

Indoor unit

Distributor strainercapillary tubeIDø1.5 x 300 l x 2P

Refrigerant pipe (Larger side)ø12.7mm (1/2")

6.1 Indoor unitRAV-103TUH-PE

Heronhill - for all your Toshiba requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Page 14: SERVICE MANUAL AIR CONDITIONER SPLIT · PDF fileSERVICE MANUAL AIR CONDITIONER SPLIT TYPE 2 WAY CASSETTE TYPE, ... WIRING DIAGRAM ... 07 Relay 52C Magnetic Contactor 63H High Pressure

-14-

Cooling

Heating

Packed valvePacked valve

Strainer

Capillary tubeø2.4 x 500L x 1P

Check valve

Refrigerant pipe (Smaller side)ø6.4mm (1/4")

Strainer

Heat exchanger

Indoor unit

Distributor

Strainer

Refrigerant pipe (Larger side)ø12.7mm (1/2")

6.2 Indoor unitRAV-133TUH-PERAV-163TUH-PE

Distributor strainercapillary tube

Low pressure High pressure

P1

P2

Cooling HeatingHigh pressure Low pressure

Line Pressure

RAV-133TUH-PRAV-163TUH-P

IDφ 2.2x200 L x2PIDφ 1.5x200 L x2P

RAV-132AH-PERAV-162AH-PE

BYPASSCAPILLARY

INDOOR UNIT OUTDOOR UNIT

MODEL CAPILLARY MODEL MAINCAPILLARY

IDφ 2.4x500 L x1P IDφ 0.8x1000 L x1P

CompressorAccumulator

2-wayvalve

Expansionvalve

Dryer

Check jointTE sensor

TL sensor Heat exchanger

Four-way valve

High pressure switch

Outdoor unit

Bypass Capillary tubeø0.8 x 1000L x 1P

Outdoor unitRAV-132AH-PERAV-162AH-PE

Heronhill - for all your Toshiba requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Page 15: SERVICE MANUAL AIR CONDITIONER SPLIT · PDF fileSERVICE MANUAL AIR CONDITIONER SPLIT TYPE 2 WAY CASSETTE TYPE, ... WIRING DIAGRAM ... 07 Relay 52C Magnetic Contactor 63H High Pressure

-15-

Am

bien

t Tem

p. (

Dry

Bul

b) (

o C)

Capacity Ratio (%)

Am

bien

t Tem

p. (

Wet

Bul

b) (

o C)

Room Temp. (Wet Bulb) (oC)

Room Temp. (Dry Bulb) (oC)

7. PERFORMANCE CHARACTER

7.1 Cooling capacity

7.2 Heating capacity

-2 ~

Capacity Ratio (%)

RAV-132AH-PE

2.883.063.243.423.603.783.964.144.32

RAV-162AH-PE

3.603.824.054.284.504.734.955.185.40

RAV-132AH-PE

5.044.834.624.414.203.993.783.573.363.152.942.732.522.31

RAV-162AH-PE

6.005.755.505.255.004.754.504.254.003.753.503.253.002.75

(KW)

(KW)

Heronhill - for all your Toshiba requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Page 16: SERVICE MANUAL AIR CONDITIONER SPLIT · PDF fileSERVICE MANUAL AIR CONDITIONER SPLIT TYPE 2 WAY CASSETTE TYPE, ... WIRING DIAGRAM ... 07 Relay 52C Magnetic Contactor 63H High Pressure

-16-

7.3 Cooling capacityRAV-132AH-PERAV-162AH-PE

Indoor Unit

Outdoor Unit

Heating Capacity Ratio

Piping Length (m)

Cooling Capacity Ratio

Piping Length (m)

Out

door

Uni

t Hei

ght H

(m

)

Out

door

Uni

t Hei

ght H

(m

)

7.4 Piping length/additional refrigerant volume

45 5

0.95

Recharge quantity (kg)

30

1.55

25

1.35

Additional amount of refrigerantat installation site (kg)

40 50 20

1.20

20

Filled atfactory

Piping lengthless than (m)

Model

3030

RAV-132AH-PE

l The amount of refrigerant put into the outdoor unit at the factory is equivalent to that which fills up 20m length of refrigerant pipe.

l If the length of refrigerant pipe is 20m or less, addition of refrigerant at the installation site is unnecessary. If the length of the pipeexceeds 20m, add the refrigerant R-22.

l Overcharge or undercharge of refrigerant in the outdoor unit will cause malfunction of the compressor. The prescribed amount ofthe replenishment of the refrigerant is shown in the table above.The permissible amount of refrigerant is the prescribed amount ±50g.

Filled atfactory

RAV-162AH-PE

3530

0.35

25

0.15

0.15 0.35

10

1.05

15

1.10

1.35 1.45 1.50 1.60 1.75 1.95

Heronhill - for all your Toshiba requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Page 17: SERVICE MANUAL AIR CONDITIONER SPLIT · PDF fileSERVICE MANUAL AIR CONDITIONER SPLIT TYPE 2 WAY CASSETTE TYPE, ... WIRING DIAGRAM ... 07 Relay 52C Magnetic Contactor 63H High Pressure

LocationPart No Description

No

214 43039240 Canoe Clip

215 43A72001 Drain Pan

216 43A88004 Manual

217 43155086 Spark Killer

218 43A69008 Interface PC Board

219 37555721 Capacitor, Metal Film (RAV-103/133TUH-PE)

219 43155100 Capacitor, Metal Film (RAV-163TUH-PE)

220 43A69002 PC Board

221 43A58002 Transformer

222 43154141 Relay

223 43A62001 Cover, Remote Controller

224 43A69004 Remote Controller

225 43A50002 Sensor (TC)

226 43150118 Sensor (TA)

-17-

LocationPart No Description

No

201 43A22001 Casing Assembly

202 43020288 Fan

203 43151217 Float Switch

204 43A70003 Pump Assembly

205 43020253 Bearing

206 43071019 Drain Connection

207 43070164 Drain Hose

208 43A60002 3 P Terminal

209 43A60001 4 P Terminal

210 43A21014 Fan Motor

211 43019604 Sensor Fix Plate

212 43A22002 Casing Outlet

213 43A44012 Heat Exchanger (RAV-103TUH-PE)

213 43A44010 Heat Exchanger (RAV-133TUH-PE)

213 43A44011 Heat Exchanger (RAV-163TUH-PE)

8. EXPLODED VIEWS AND PARTS LIST

8.1 Indoor unitRAV-103TUH-PERAV-133TUH-PERAV-163TUH-PE

Heronhill - for all your Toshiba requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Page 18: SERVICE MANUAL AIR CONDITIONER SPLIT · PDF fileSERVICE MANUAL AIR CONDITIONER SPLIT TYPE 2 WAY CASSETTE TYPE, ... WIRING DIAGRAM ... 07 Relay 52C Magnetic Contactor 63H High Pressure

-18-

8.2 CEILING PANELRBC-U133PG(W)-PE

Location Part Description number Number

1 43080392 Filter2 43007108 Plate connect (long)3 43009504 ASM-Grille-Out4 43007107 Bushing5 43007109 Plate connect (short)

Location Part Description number Number

6 43009503 Grille-L-R7 43007124 Support plate8 43009499 ASM-Grille-Out9 43A26001 ASM-Motor

10 43007125 Support plate

1

1

3

10

54

7

6

47

9

55

2

2

74

28

2

8

4

Heronhill - for all your Toshiba requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Page 19: SERVICE MANUAL AIR CONDITIONER SPLIT · PDF fileSERVICE MANUAL AIR CONDITIONER SPLIT TYPE 2 WAY CASSETTE TYPE, ... WIRING DIAGRAM ... 07 Relay 52C Magnetic Contactor 63H High Pressure

-19-

8.3 Outdoor unitRAV-132AH-PERAV-162AH-PE

LocationNo.

Part No. Description

25 43041837 Compressor, AC220/240V,

50Hz, PH230X3-4LS (RAV-132AH-PE)

25 43041845 Compressor, AC220/240V,

50Hz, PH250X3-4LS (RAV-162AH-PE)26 43146454 Packed Valve (1/4")

27 43146406 Packed Valve (1/2")

28 43147321 Check Joint

29 43146424 Expansion Valve

30 43046198 Coil, 2-Way Valve

31 43146283 1-Way Valve

33 43A58003 Transformer, Power

34 43046151 Valve, 2-Way

35 43193043 Spring

36 43A50001 Sensor, Cond. Out (TL)

37 43150196 Sensor, Heat Exch. (TE)

38 43146418 Valve 4-Way

39 43157167 Heater, Crankcase

41 43146459 Capillary Tube

42 44246235 Capillary Tube

43 43150122 Thermostat, Bimetal

44 43107215 Holder, Sensor (TL)

LocationNo.

Part No. Description

1 43120156 Fan, Propeller2 43A21003 Motor, Fan, AC230V, 50Hz

3 43A43001 Condenser

4 43149212 Base, Spring, A

5 43149198 Spring, Buffer

6 43049132 Base, Spring, B

7 43A69003 PC Board

8 43A49001 Switch, High-Pressure

9 43060479 Terminal, 4P

10 43A60003 Terminal, 2P

11 43A60001 Terminal, 4P

12 43152334 Magnetic Contactor

13 43054286 Relay, Overload

14 43A19001 Guard, Fan

15 43119368 Hanger

16 43A46004 Solenoid Coil

17 43162027 Cover, Electric Parts

18 43155115 Capacitor, Plastic Film, 45MFD, 440V

20 43107215 Holder, Sensor (TE)

22 43148105 Accumulator

23 43145082 Dryer

24 43155080 Capacitor, Electrolytic