Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage...

43
Self-reclosing overload and earth leakage protection Unit 6/22 Moselle Ave, Henderson, Auckland, New Zealand PO Box 21-872, Henderson, Auckland, New Zealand Phone:+64 9 833 5749 Email:[email protected] Web: www.LPINZ.co.nz NEW ZEALAND WWW.LPINZ.CO.NZ

Transcript of Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage...

Page 1: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

Self-reclosing overload and earth leakage protection

Unit 6/22 Moselle Ave, Henderson, Auckland, New Zealand PO Box 21-872, Henderson, Auckland, New Zealand

Phone:+64 9 833 5749Email:[email protected]

Web: www.LPINZ.co.nzNEW ZEALANDWWW.LPINZ.CO.NZ

Page 2: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-2

P2- Self-reclosing overload and earth leakage protection

REC2Self-reclosing earth leakage relay · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · P2-5

WRU RAEarth leakage relay with built-in transformer · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · P2-7

WRU-10 RALDifferential relay with built-in transformer and display (type A) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · P2-9

RGU-10 RALEarth protection Relay WG Series · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · P2-11

CBS-4 RA / RALEarth leakage relay station WG / WGC Series · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · P2-13

CBS-8Earth leakage monitoring and signaling unit of the external transformer of the WG / WGP / WGC Series · · · · · · · · · · · · · · · · · · · · · · P2-15

WRKRT-25Earth leakage relay with built-in transformer · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · P2-17

MCBMCB Series Circuit-Breaker · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · P2-19

WRU-25 RA-MTEarth leakage relay with built-in transformer · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · P2-21

WRT-6Earth leakage relay with built-in transformer · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · P2-23

WRU-10 MTEarth leakage relay with built-in transformer and display (type A) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · P2-25tRGU-10 MTEarth leakage Relay WG + MT Series · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · P2-27

RGMTEarth leakage Relay WG + MT Series · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · P2-29

RECmax MPMotorized circuit breaker (up to 63 A) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · P2-31

MTMotorized circuit breaker (up to 63 A) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · P2-33

MT-FDEMotorized circuit-breaker (from 63 A) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · P2-35

Page 3: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-3

WRGMTComplete overload and earth leakage protection and reclosure equipment · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · P2-37

RECmax PSelf-reclosing motorized circuit breaker (up to 63 A) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · P2-38

RRMOverload reclosing relay · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · P2-40

Page 4: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-4

Product selection table

Equipment Protection Reclosure Associated circuit breaker External toroidal Page

REC

2

Earth Leakage Earth Leakage Earth leakage switch -- P2-5

WR

U R

A

Earth Leakage Earth Leakage

Contactor

-- P2-7

WR

U-1

0 R

AL

Earth Leakage Earth Leakage

Contactor

-- P2-9

RG

U-1

0 R

AL

Earth Leakage Earth Leakage

Contactor

Tipo WG / WGC

P2-11

CB

S-4

RA

Earth Leakage Earth Leakage

Contactor

Tipo WG / WGC

P2-13

CB

S-8

Earth Leakage Earth Leakage

Contactor

Tipo WG / WGP / WGC

P2-15

WR

KR

T-25

Earth Leakage + circuit breaker Earth Leakage

Circuit-breaker MCB-T / MCB-P

-- P2-17

WR

U-2

5 R

A-M

T

Earth Leakage + circuit breaker

Earth Leakage + circuit breaker

Circuit breaker MT Type WG

P2-21

WR

T-6

Earth Leakage + circuit breaker

Earth Leakage + circuit breaker

Circuit breaker MT

-- P2-23

WR

U-1

0 M

T

Earth Leakage + circuit breaker

Earth Leakage + circuit breaker

Circuit breaker MT

-- P2-25

RG

U-1

0 M

T

Earth Leakage + circuit breaker

Earth Leakage + circuit breaker

Circuit breaker MT Tipo WG / WGC

P2-27

RG

MT Earth Leakage

+ circuit breakerEarth Leakage

+ circuit breakerCircuit breaker MT

-- P2-29

WR

G-M

T

Earth Leakage + circuit breaker

Earth Leakage + circuit breaker

Circuit breaker MT

-- P2-37

RR

M

Circuit breaker Circuit breaker

Circuit breaker MT

-- P2-40

Page 5: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-5

Self-reclosing earth leakage relayREC2

FeaturesDescription

REC2 is a 2 or 4-pole earth leakage switch associated to a compact motor and control set that enables the automatic and safe re-closure of the installation, provided that the leakage is not permanent. Output contact available in REC2C model

The earth leakage switch is reclosed auto-matically, in accordance with the work mode selected (switch on the front):

}} Time sequence mode: after a switch trip, REC2 will make 6 reclosing attempts, with a timer set at 10, 20, 30, 60, 120 and 600 s. If the set can not be reclosed, it will be blocked in a trip status until it is reset manually.}} Insulation monitoring mode: after the

switch trip, REC2 repeats the previous se-quence, but it measures the presence of leak-age current in the installation before carrying out the reset. REC2 will only reclose when the insulation measurements are correct.

There are LEDs on the front part of the con-trol module to indicate the operation status:

}} Manual or automatic reclosure}} Reclosure mode selected}} Reclosing status}} Lock status

Drop-down window to activate/deactivate the automatic reclosure of the earth leakage switch.

Protection Earth Leakage

Class Electromechanical, Class A

Measurement Instantaneous value

Sensitivity IDn 30 mA or 300 mA (depending on the type)

Delay Fixed at 20 ms

Test With built-in button

Reset Manual (front cover)

Associated circuit breaker Built-in

In and no. of poles In 40 A or 63 A, Poles 2 or 4 (depending on the type)

Circuit breaker control Electromechanical relay

Reclosure Earth Leakage

No. of reclosures 6

Time between reclosures 10, 20, 30, 60, 120, 600 s

Partial counter reset time 600 s (reset time after 30 s)

Reclosure cancellation With the front cover

Features

Nominal voltage 2 poles: 230 Vac 4 poles: 230 / 400 Vac

Auxiliary power supply 230 Vac, 50 ... 60 Hz

Operating temperature -25 ... +55 ºC

Hose features (only REC2C)

Connector JST BHR-02VS-1

Hose YY 2x0.22, PVC 80 -300 V

Length 750 mm

Build features

Fixing DIN rail

Dimensions 2 poles: 5 modules (90 x 90 mm) 4 poles: 7 modules (125 x 90 mm)

Weight 2 poles: 560 g / 4 poles: 693 g

Degree of protection IP 40

Standards

IEC 61008-1, IEC 255-5

Earth leakage protection and self-reclosingRCCB with Self-reclosing system

Page 6: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-6

Self-reclosing earth leakage deviceREC2

References

Earth leakage protection and self-reclosingSelf-reclosing earth leakage switch

With output contact

Class Poles In (A) Sensitivity Type Code Type Code

A 2 40 30 mA REC2-2P-40-30 P26411 REC2C-2P-40-30 P26611

A 2 40 300 mA REC2-2P-40-300 P26321 REC2C-2P-40-300 P26521

A 2 63 30 mA REC2-2P-63-30 P26414 REC2C-2P-63-30 P26614

A 2 63 300 mA REC2-2P-63-300 P26324 REC2C-2P-63-300 P26524

A 4 40 30 mA REC2-4P-40-30 P26412 REC2C-4P-40-30 P26612

A 4 40 300 mA REC2-4P-40-300 P26322 REC2C-4P-40-300 P26522

A 4 63 30 mA REC2-4P-63-30 P26415 REC2C-4P-63-30 P26615

A 4 63 300 mA REC2-4P-63-300 P26325 REC2C-4P-63-300 P26525

Connections

REC2

REC2C - output contact

REC2 - 4 polesREC2 - 2 poles

2 N

N1

230 Vac - 50 Hz

CARGA

13 mm MAX.

16-25 mm2.

FN

2 N

N1

MotorReconexionAutomatica

230 Vac - 50 Hz

CARGA / LOAD

13 mm MAX.

16-25 mm2.

FN

Contacto auxiliar

Contacto auxiliarAuxiliary contact

Dimensions

Page 7: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-7

Protection Earth Leakage

Class A superimmunized

Measurement True root mean square (TRMS)

Sensitivity Adjustable from 30 mA ... 3 A

Delay Adjustable from 20 ms ... 1 s

Earth leakage transformer Built-in

Test and Reset With built-in button

Associated circuit breaker Contactor

In and no. of poles Defined by the contactor used

Circuit breaker control With switched relay

Reclosure Earth Leakage

No. of reclosures 6

Time between reclosures 8, 16, 30, 59, 115, 224, s

Partial counter reset time 15 min

Relay signaling

LED• Presence of voltage• Leakage current level• Triggered relay

Remote signaling (outputs) Leakage control signal (mVac / mA)

Remote Control (inputs) External test with button

Features

Auxiliary power supply 230 Vac (± 20 %) 50 / 60 Hz

Output contacts 250 Vac, 6 A

Operating temperature -10 ... +50 ºC

Construction features

Fixing DIN rail

Dimensions 4 modules (WRU-25 RA) / 6 modules (WRU-35 RA)

Weight 236 g (WRU-25 RA) / 415 g (WRU-35 RA)

Degree of protection IP 20 Terminals, IP 41 back panel

Standards

IEC 61008-1, IEC 755, IEC 255-5

Application

Said relays are connected to a contactor or similar element to guarantee the level of self-reclosing earth leakage protection after a trigger. It is very easy to install, so that it is the adequate solution for installations that require the use of earth leakage protection systems as a result of their location or posi-tion in a determined site, which makes them hard to supervise or access: lighting panels, telephony installations, television repeaters, refrigeration chambers, etc.

FeaturesDescription

}} Self-reclosing electronic earth leakage protection relay with built-in transformer, a diameter of Ø 25 or Ø 35 mm (depending on the type), with earth leakage trigger}} It is connected to a contactor or similar

element as a circuit breaker}} Type A relay, with high-frequency current

filtering and high immunity. Monitoring in true root mean square (TRMS)}} Adjustable sensitivity and trigger timer.}} Number of reclosures and time between

them, depending on the relay type}} Leakage level trigger indicator LED (%

sensitivity):}y 1 flash every 2 s: between 25 and 50 %}y 1 flash every 1 s: between 50 and 75 %}y 1 flash every 0.5 s: between 75 and 90%}y Permanent: Earth leakage protection tri-

gger}} Adjustable to the DIN profile 46277

(EN -50022)

Earth leakage relay with built-in transformerWRU RAEarth leakage protection and self-reclosingEarth leakage relay + contactor

Page 8: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-8

Use

ful

diam

eter

Ø

(mm

)

I n (A

)

Del

ay (s

) (*)

Num

ber

of

recl

osur

es

Tim

e be

twee

n re

clos

ures

(s)

Con

trol

of

the

circ

uit

brea

ker

Rem

ote

sign

alin

g (o

utpu

ts)

Type Code

25 0,03 ... 3 0,02 ... 1 6 8,16,30,59,115,224

Switched relay

mV ac proportional to the leakage current

WRU-25 RA P24211

35 0,03 ... 3 0,02 ... 1 6 8,16,30,59,115,224

Switched relay

mV ac proportional to the leakage current

WRU-35 RA P24221

Other earth leakage relays

25 0,03 ... 3 0,02 ... 1 3020 s, 40 s and the rest every 5 min

Switched relay

mV ac proportional to the leakage current

WRU-RM P24231

25 0,03 ... 3 0,02 ... 1 3020 s, 40 s and the rest every 5 min

Simple relay, NO, positive safety

Alarm relay: 1 simple relay NO-SP

WRU-RT P24431

25 0,03 ... 1 0,02 31

2 min, 4 min and the rest every 6 min

Simple relay NO

Alarm relay: 1 simple relay NO WRU-25-2R P24412

(*) The delay is cancelled in all relays with a sensitivity adjustment of 0.03 A.

References

Dimensions

Earth leakage relay with built-in transformerWRU RA

Earth leakage protection and self-reclosingEarth leakage relay + contactor

WRU-25 RA / WRU-RM / WRU-RT / WRU-25-2R

WRU-35 RA

Page 9: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-9

Protection Earth Leakage

Class A superimmunized

Measurement True root mean square (TRMS)

PROGRAMMABLE sensitivity 0.03...3A, extendible to 30 A using SETUP

PROGRAMMABLE delay Time setting: 0.02...1 s, up to 10s using SETUP.Inverse curve: INStantaneous/ SELective. IEC 60947-2

Test and Reset By built-in buttons, T & R

Associated circuit breaker CONTACTOR, defines the number of poles and the In

Circuit breaker control Switched NO/NC contact relay

Reclosure Earth Leakage

No. of reclosures

ProgrammableTime between reclosures

Reclosure time counter

Relay signaling

LED INDICATORS/BACK-LIT DISPLAY

• Power supply • Leakage trigger• Pre-alarm• Locking

• Protection settings• Leakage current/trigger reading• TEST and external status• Sequences/reclosure number

Remote Control External TEST possible, triggering by voltage input

Features

Auxiliary power supply 230 Vac (± 30%) 50 / 60 Hz

Output contacts 250 V ac, 5 A / 230 V ac, 250 mA

Operating temperature -20 ... + 70 ºC

Construction features

Fixing DIN rail

Dimensions 3 modules

Weight 275 g

Degree of protection IP 20, trans-cabinet IP 41

Standards

IEC 60947-2, IEC 60755, IEC 62020, IEC 61008

Application

The WRU-10 RAL relays combined with a CONTACTOR provide automatic reclosure fo-llowing an event and provide a suitable solution for public lighting, automatic cash machines, cold rooms, traffic lights, etc. Its characteris-tics have been designed to provide maximum safety and continuity of the electrical service, avoiding untimely triggers.

FeaturesDescription

}} Electronic differential protection relay with au-tomatic reclosing with built-in 28 mm transformer, constituting one unit.}} Superimmunized Type A , with high-frequency

current filter and high insulation. Measurement in true root mean square (TRMS) value}} Display with leds and back-lit display:

- Differential protection/reclosing settings- protection trigger current.- number of reclosures- protection status messages, etc.}} Unit with three output contact relays

one switched and two simple relays, all program-mable. The main relay provides the protection as-sociated with the contactor, one is for the pre-alarm and the other for locking once the maximum num-ber of reclosures is reached.}} There is a voltage input for

external triggering and reclosing}} Fitting: DIN 46277 (EN-50022) profile}} Reduced three-module size.}} Connection by pluggable terminals

Differential relay with built-in transformer and display (type A)

WRU-10 RALDifferential protection and reclosingDifferential relay with integrated toroidal transformer + contactor

Page 10: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-10

Connections

N reclosuresTime between reclosures

Net section (mm) In (A) Delay Type Code

Programmable Ǿ 28 0.03 ... 3 A extendible to 30 A

0.02 ... 1 s extendible to 10sInverse curve: INS/SEL WRU-10 RAL P24453

References‏

Dimensions

Differential relay with built-in transformer and display (type A)

WRU-10 RAL

Differential protection and reclosingDifferential relay with integrated toroidal transformer + contactor

Programmable Reclosure

Page 11: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-11

Protection Earth Leakage

Class A superimmunized

Measurement True root mean square (TRMS)

Sensitivity Programmable from 30 mA ... 30 A

Delay Programmable from 20 ms ... 10 sInverse curve: instantaneous or selective

Earth leakage transformer External, WG Series (WG / WGS / WGC)

Test and Reset With built-in button

Associated circuit breaker Contactor

In and no. of poles Defined by the contactor used

Circuit breaker control With a switched relay

Reclosure Earth Leakage

No. of reclosures Programmable: Depending on the reclosing sequence

Time between reclosures Programmable: 1 ... 900 s

Partial counter reset time Programmable

Relay signaling

LED• Presence of voltage• Leakage trip• Interlocking / reclosing status

Display Backlit LCD

Remote signaling (outputs) Lock status indicator relay

Remote Control (inputs) ON / OFF

Features

Auxiliary power supply 230 Vac (± 20 %) 50 / 60 Hz

Output contacts 250 Vac, 6 A

Operating temperature -10 ... +50 ºC

Construction features

Fixing DIN rail

Dimensions 3 modules

Weight 236 g

Degree of protection IP 20 Terminals, IP 41 back panel

Standards

IEC 61008-1, IEC 755, IEC 255-5

Application

The RGU-10 RAL relays associated to a meter allow the automatic reclosing after a trigger, thus offering the most adequate so-lution for public lighting, cash machines, refrig-eration chambers, traffic lights, etc. Its design characteristics guarantee maximum security and continuity of the electrical service, avoid-ing unwanted tripping.

FeaturesDescription

Electronic earth leakage protection relay, used to connect the external toroidal trans-formers of the WG / WGS / WGC Series

}} Self-reclosing with a programmable earth leakage trip}} Superimmunized type A Relay, with high

frequency current filtering and high immunity. Monitoring in true RMS }} The backlight display shows the following

information:}y Adjustment values}y Instantaneous leakage current}} It has two independent outputs:}y Trip relay}y End-of-reclosing-sequence interlocking

relay}} External input for remote control functions

(230 Vac)}} Automatic test of the connection and ex-

ternal transformer status }} Optional RS-485 Communications: type

RGU-10C RAL}} Reduced dimensions: 3 modules}} Assembly on DIN rail 46277 (EN-50022).}} Optional assembly on 72 x 72 panel with

accessory M5ZZF1.

Earth protection Relay WG SeriesRGU-10 RALEarth leakage protection and self-reclosingEarth protection relay + contactor + external transformer

Page 12: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-12

Reclosing element Communications In (A) Delay (s) Type Code

Contactor - 0,03 ... 30 0,02 ... 10 RGU-10 RAL P24622

Contactor RS-485 0,03 ... 30 0,02 ... 10 RGU-10 C RAL P24662

References

Dimensions

Connections

Earth protection Relay WG SeriesRGU-10 RAL

Earth leakage protection and self-reclosingEarth protection relay + contactor + external transformer

Page 13: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-13

Earth leakage relay station WG / WGC SeriesCBS-4 RA / RAL

Protection Earth Leakage

Class A superimmunized

Measurement True root mean square (TRMS)

Sensitivity IDn 0.03 A ... 30 A

Delay Programmable: 0.20 ms ... 10 sInverse curve: instantaneous or selective

Earth leakage transformer External, WG Series (WG / WGS / WGC)

Test and Reset With built-in button

Associated circuit breaker Contactor

In and no. of poles Defined by the contactor used

Reclosure Earth Leakage

No. of reclosures Programmable

Time between reclosures Programmable

Partial counter reset time Programmable

Features

Auxiliary power supply 230 Vac (± 20 %) 50 ... 60 Hz

Contacts with 4 earth leakage outputs 250 Vac, 5 A

Operating temperature -10 ... +50 ºC

Construction features

Fixing DIN rail

Dimensions 3 modules

Weight 236 g

Degree of protection IP 20 Terminals, IP 41 back panel

Standards

IEC 61008-1, IEC 755, IEC 255-5

Application

CBS-4 RA or CBS-4 RAL allow an intelligent earth leakage protection, with greatly reduced dimensions. A contactor is available per chan-nel, enabling the automatic reclosure after a

FeaturesDescription

}} Unit equivalent to 4 earth leakage protec-tion relays. 4 independent programmable re-lays available}} 4 inputs to connect the external toroidal

transformers of the WG / WGS / WGC}} Self-reclosing with programmable earth

leakage trip in each channel}} Superimmunized Type A relay with high

frequency current filtering and high immunity. Monitoring in true root mean square (TRMS) }} Reduced size: 3 modules}} 5 independent programmable outputs:}y 4 earth leakage trip outputs}y 1 end-of-reclosing-sequence interlocking

output}} Backlight display to show the information

of the 4 channels:}y Adjustment values}y Instantaneous leakage current}} Trip/external reset input}} Automatic test of the connection and sta-

tus of each external transformer }} Optional RS-485 Communications: type

CBS-4C RA and CBS-4C RAL}} Assembly on DIN rail 46277 (EN-50022)}} Optional assembly on 72 x 72 panel with

accessory M5ZZF1.

Earth leakage protection and self-reclosingEarth leakage station + contactor + external transformer

trip, thus offering the most adequate solution for public lighting, cash machines, refrigeration chambers, traffic lights, etc. In addition, ver-sion CBS-4 C, with RS-485 communications,

is used with the PowerStudio software and it adds the centralised supervision in real-time, as well as a record log that can be analysed later on.

Page 14: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-14

Size Communications No. of Relays No. of reclosures Type Code

3 modules - 4 / NO Programmable CBS-4 RA P24911

3 modules RS-485 4 / NO Programmable CBS-4 C RA P24912

3 modules - 4 / NC Programmable CBS-4 RAL P24A11

3 modules RS-485 4 / NC Programmable CBS-4 C RAL P24A12

References

Dimensions

Connections

Earth leakage relay unit WG / WGC SeriesCBS-4 RA / RAL

Earth leakage protection and self-reclosingEarth leakage station + contactor + external transformer

Page 15: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-15

Earth leakage monitoring and signaling unit of the external transformer of the WG / WGP / WGC Series

CBS-8

Protection

No. of protections 8

Class A superimmunized

Measurement True root mean square (TRMS)

Sensitivity 0.03 A ... 6.3 A external transformers WG/WGS0.03 A ... 63 A external transformers WGP/WGSP

Delay Time defined: 0,02 ... 10 sInverse curve: instantaneous or selective

Earth leakage transformer External, TRANSFORMERS WG / WGP / WGC

Test and Reset With built-in buttons, T & R

Associated circuit breaker Contactor or circuit breaker + trigger coil

Automatic reclosing

No. of reclosures 0 Programming option ... 10

Time between reclosures 0 Programming option ... 900 s

Partial counter reset time Double the reclosing time

LED indicator

• Power supply voltage• Leakage trip• Pre-alarm• Interlocked earth leakage reclosing• Automatic reclosure enabled

Display View• Instantaneous leak level indicator in each channel• Parameter programming• Reclosure status

Features

Auxiliary power supply 230 Vac (± 20 %) 50 ... 60 Hz

Output contacts 250 Vac, 5 A

Operating temperature -10 ... +50 ºC

Construction features

Fixing DIN Rail 46277 (EN 50022)

Dimensions 8 modules

Weight 609 g

Degree of protection IP 20 Terminals, IP 41 back panel

Standards

IEC 664, VDE 0110, IEC 801, UL 94, IEC 348, IEC 571-1, EN 61000-6-3, 61000-6-1, 61010-1

Application

FeaturesDescription

}} Unit equivalent to 8 earth leakage protec-tion networks. 8 independent programmable relays available}} 8 inputs to connect the external toroidal

transformers of the WG / WGP / WGC}} Superimmunized Type A relay with high

frequency current filtering and high immunity. Monitoring in true root mean square (TRMS)}} Reduced size, with 8 modules}} 9 independent programmable outputs

(8 earth leakage trip relays and 1 pre-alarm trip).

The CBS-8 earth leakage station associ-ated to the transformers of the WG / WGP / WGC Series allows an intelligent earth leak-age protection. Its design features guarantee maximum security and continuity of the elec-trical service, avoiding unwanted tripping.

Showing the value of the leak instantane-ously on the display with the pre-alarm in-dications provides the information about the state of lines being protected, thus allowing the implementation of an adequate preven-tive maintenance approach.

In addition, RS-485 communications are used with the PowerStudio software, which allows the centralised supervision of the sys-tem in real time, with a record log that can be analysed later on.

Earth leakage protection and self-reclosingEarth leakage station + contactor + external transformer

Page 16: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-16

References

Dimensions

Connections

Earth leakage monitoring and signaling unit of the external transformer of the WG / WGP / WGC Series

CBS-8

CBS-8

45

110

140 70

Size Communications No. of Relays In (A) Type Code

8 modules RS-485 8 0,03 ... 63 CBS-8 (*) P12811

(*) In the case of the 0.3 ... 63 A scale, use earth leakage transformers of the WGP / WGSP(*) In the case of the 0.03 ... 6.3 A scale, use earth leakage transformers of the WG / WGS

Earth leakage protection and self-reclosingEarth leakage station + contactor + external transformer

Page 17: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-17

Protection Earth Leakage

Class A superimmunized

Measurement True root mean square (TRMS)

Sensitivity Programmable from 30 mA ... 3 A

Delay Programmable from 20 ms ... 1 s

Earth leakage transformer Incorporated, Ø 25 mm

Test and Reset With built-in button

Associated circuit breaker Circuit-breaker MCB-T (WRKRT-25 T) and MCB-P (WRKRT-25 N)

In, No. of poles, thermal curve and cut-out power Defined by the circuit-breaker used, up to 63 A

Reclosure Earth Leakage

No. of reclosures 30 (WRKRT-25 T) and 6 (WRKRT-25 N)

Time between reclosures 20 s, 40 s, the remaining 28 every 5 min

Partial counter reset time 15 min

Relay signaling

LED

• Voltage presence indicator• Interlocked reclosure• Indicates the presence of leakage current that does not reach the trip point

Control input (R1-R2)WRKRT-25 T: External resetWRKRT-25 N: Connection/disconnection order of the associated MCB-P

Features

Auxiliary power supply 230 Vac (± 20 %) 50 / 60 Hz

Breaking element control contacts Maximum current 3 Aac

Operating temperature -10 ... +50 ºC

Construction features

Fixing DIN rail

Dimensions 4 modules

Weight 235 g

Degree of protection IP 20 Terminals, IP 41 Embedded relay

Standards

IEC 61008-1, IEC 755, IEC 255-5, IEC 947-2

Application

The WRKRT-25 Relays connected to an MCB circuit-breaker guarantee self-reclosing earth leakage and overload protection, with an automatic reclosure after an earth leakage trip. It is a very good solution in installations in special locations that are hard to monitor and guard: telephony installations, television repeaters, refrigeration chambers, etc.

FeaturesDescription

}} Self-reclosing earth leakage protection re-lay with a built-in transformer, with a diameter of Ø 25 mm, with automatic reclosure in case of a trip.}} Its operation is always associated to an

MCB circuit-breaker. Therefore, other mod-els can not be used}} The WRKRT-25 relay is used with the

MCB to guarantee the self-reclosing earth leakage and overload protection, with an au-tomatic reclosure after an earth leakage trip}} Type A relay with high frequency current

filtering and high immunity. Monitoring in true root mean square (TRMS)}} Adjustable sensitivity and timer.

Earth leakage relay with built-in transformerWRKRT-25Overcurrent and earth leakage protection and self-reclosingEarth leakage relay + MCB circuit-breaker

Page 18: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-18

No. of rec. Time between reclosures In (A)

Delay (s) (*1)

Associated circuit breaker Type Code

30 20s, 40 s and the rest every 5 min 0,03 ... 3 0,02 ... 1 Circuit-breaker MCB-T WRKRT-25 T P23111

6 0.5/1/2/4/8/16 min 0,03 ... 3 0,02 ... 1 Circuit-breaker MCB-P WRKRT-25 N (*2) P23121

Up to 63 A and 2 and 3+N poles(*1) The delay is cancelled in all relays with a sensitivity adjustment of 0.03 A.(*2) Only valid for overload relays of the MCB-P Series. External contactor input.

References

Dimensions

Connections

WRKRT-25 T WRKRT-25 N

Earth leakage relay with built-in transformerWRKRT-25

Overcurrent and earth leakage protection and self-reclosingEarth leakage relay + MCB circuit-breaker

WRKRT-25 T / WRKRT-25 N

CONTROL INPUT

LOADLOAD

Leakage control

Externalreset

Auxiliary contacts(white) Common(brown) Circuit breaker status(green) Earth leakage status

Page 19: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-19

Circuit-breaker

Gauges In (A) 6 - 10 - 16 - 20 - 25 - 32 - 40 - 50 - 63

Nominal cut-out power (EN 60898) 6 ... 63 A: 10 kA

Nominal cut-out power (EN 60947-2) 6 ... 16 A: 20 kA20 ... 63 A: 15 kA

Typical curve C or D, depending on the type

Nominal working voltage 230 / 400 Vac

Work frequency range 50 ... 60 Hz

Operating temperature -25 ... +55 ºC

Storage temperature -40 ... +70 ºC

Remote Control

Nominal voltage 230 Vac

Activation impulse 20 ms

Deactivation impulse 20 ms

Construction features

Fixing DIN rail

Dimensions 2 poles: 3 modules4 poles: 5 modules

Mechanical working life 20,000 operations

Weight 2 poles: 375 g4 poles: 615 g

Degree of protection IP 20 (DIN 40050)

Standards

IEC 60898, EN 60947, EN 60898, IEC 60947-2

Application

MCB are the perfect elements to guaran-tee self-reclosing earth leakage and over-load protection applications, connected to WRKRT-25 relays.

FeaturesDescription

MCB-P or MCB-T are circuit-breakers that combine the functions of a circuit breaker (overload and short-circuit protection) and those of a contactor on the same element.

There are two options with MCB:

}} Closed circuit-breaker: Allows remote control functions (contactor function). It can be disconnected and reconnected electrically with the adequate signal.}} Circuit-breaker opened by an overload or

short-circuit trip or by manual disconnection: remote control reset is not allowed, only ma-nually.

The remote control function works on the same contacts as those of the circuit break-er, guaranteeing the disconnection in each case.

The MCB-T type includes a remote con-trol module with two auxiliary, potential free (three-wire) contacts that indicate the status of the MCB at the input of the remote con-trol (contactor function) and/or the circuit breaker.

MCB Series Circuit-BreakerMCBOvercurrent and earth leakage protection and self-reclosing

Page 20: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-20

2 poles 4 poles

In (A)

MCB-P MCB-T MCB-P MCB-T

Type Code Type Code Type Code Type Code

6 MCB-P C-2p-6A P20210 MCB-T C-2p-6A P20310 - - - -

10 MCB-P C-2p-10A P20211 MCB-T C-2p-10A P20311 MCB-P C-4p-10A P20221 MCB-T C-4p-10A P20321

16 MCB-P C-2p-16A P20213 MCB-T C-2p-16A P20313 MCB-P C-4p-16A P20223 MCB-T C-4p-16A P20323

20 MCB-P C-2p-20A P20214 MCB-T C-2p-20A P20314 MCB-P C-4p-20A P20224 MCB-T C-4p-20A P20324

25 MCB-P C-2p-25A P20215 MCB-T C-2p-25A P20315 MCB-P C-4p-25A P20225 MCB-T C-4p-25A P20325

32 MCB-P C-2p-32A P20216 MCB-T C-2p-32A P20316 MCB-P C-4p-32A P20226 MCB-T C-4p-32A P20326

40 MCB-P C-2p-40A P20217 MCB-T C-2p-40A P20317 MCB-P C-4p-40A P20227 MCB-T C-4p-40A P20327

50 MCB-P C-2p-50A P20218 MCB-T C-2p-50A P20318 MCB-P C-4p-50A P20228 MCB-T C-4p-50A P20328

63 MCB-P C-2p-63A P20219 MCB-T C-2p-63A P20319 MCB-P C-4p-63A P20229 MCB-T C-4p-63A P20329

References

Dimensions

MCB Series Circuit-BreakerMCB

Overcurrent and earth leakage protection and self-reclosing

MCB-P / MCB-T

Connections

N

1 2

ON OFF

3L

MCB control module230 V ac

LOAD

RELAYK SERIE

Page 21: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-21

Protection Earth leakage and circuit breaker

Class A superimmunized

Measurement True root mean square (TRMS)

Sensitivity Programmable from 30 mA ... 3 A

Delay Programmable from 20 ms ... 1 s

Earth leakage transformer Built-in Ø 25 mm

Test and Reset With built-in button

Associated circuit breaker Motorized circuit-breaker MT

In and no. of poles Defined by the circuit breaker used

Circuit breaker control With a switched relay

Reclosure Earth leakage and circuit breaker

No. of reclosures 6

Time between reclosures 1 min

Partial counter reset time 15 min

Safety interlocking In the earth leakage protection device. With disconnection lever

Relay signaling

LED • Voltage presence indicator• Earth and/or short-circuit overload fault indicator

Remote signaling (outputs) Leakage control signal (proportional alternating voltage)

Features

Auxiliary power supply 230 Vac (± 20 %) 50 / 60 Hz

Circuit breaker control contacts 250 Vac, 8 Aac

Output contacts Maximum current 3 A

Operating temperature -10 ... +50 ºC

Construction features

Fixing DIN rail

Dimensions 4 modules

Weight 234 g

Degree of protection IP 20 Terminals, IP 41 back panel

Standards

IEC 61008-1, IEC 755, IEC 255-5

Application

The WRU-25 RA-MT relays connected to an MT or similar circuit breaker guarantee the self-reclosing earth leakage and overload protection of a system after a trip, with both earth leakage and overload protection sys-tems. It is a very good solution in installations in special locations that are hard to monitor and guard: telephony installations, television repeaters, refrigeration chambers, etc.

FeaturesDescription

}} Self-reclosing earth leakage protection re-lay with a built-in transformer, with a diameter of Ø 25 mm, with automatic reclosure in case of a trip.}} It is connected to a motorized circuit

breaker of the MT or similar series as the overload protection or circuit breaker ele-ment.}} Self-reclosing system after an overload

and/or earth leakage trip.}} Type A relay, with high current filtering and

high immunity. Monitoring in true root mean square (TRMS).}} The functions of the WRU-25 RA-MT are:}y Earth leakage protection and self-reclos-

ing}y Overload reclosing}} Leakage level trigger indicator LED (%

sensitivity):}y 1 flash every 2 s: between 25 and 50 %}y 1 flash every 1 s: between 50 and 75 %}y 1 flash every 0.5 s: >75 and <90%}y Permanent: Earth leakage protection

trigger

Earth leakage relay with built-in transformerWRU-25 RA-MTOvercurrent and earth leakage protection and self-reclosingEarth leakage relay + circuit breaker

Page 22: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-22

No. of reclosures

Useful diameter Ø (mm) In (A)

Delay (s) (*)

Time between reclosures

Associated circuit breaker Type Code

6 25 0,03 ... 3 0,02 ... 1 1 min SwitchMT WRU-25 RA-MT P24241

(*) The delay is cancelled in all relays with a sensitivity adjustment of 0.03 A.

References

Dimensions

Connections

Earth leakage relay with built-in transformerWRU-25 RA-MT

Overcurrent and earth leakage protection and self-reclosingEarth leakage relay + circuit breaker

WRU-25 RA-MT (self-reclosing earth leakage and overload protection)

WRU-25 RA-MT (self-reclosing, only earth leakage)

RED

A1/Y2

LOAD

R SPOWER

TE

T

ER

ST

Un 230VAC

ET

type WRU25

A1

Z1 Z2 A215

Y1 1618

NL1L2L3

HM On I

N

Off 0

1 3 5 7 12 14

118642

L

MT

MV

A1/Y2

LOAD

R SPOWER

TE

T

ER

ST

Un 230VAC

ET

type WRU25

A1

Z1 Z2 A215

Y1 1618

NL1L2L3

HM On I

N

Off 0

1 3 5 7 12 14

118642

L

MT

MV

RED

A1/Y2

LOAD

R SPOWER

TE

T

ER

ST

Un 230VAC

ET

type WRU25

A1

Z1 Z2 A215

Y1 1618

NL1L2L3

HM On I

N

Off 0

1 3 5 7 12 14

118642

L

MT

MV

A1/Y2

LOAD

R SPOWER

TE

T

ER

ST

Un 230VAC

ET

type WRU25

A1

Z1 Z2 A215

Y1 1618

NL1L2L3

HM On I

N

Off 0

1 3 5 7 12 14

118642

L

MT

MV

Page 23: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-23

Application

The WRT-6 relays connected to an MT or similar circuit breaker guarantee the self-reclosing earth leakage and overload protec-tion of a system after a trip, with both earth leakage and overload protection systems. It is a very good solution in installations in special locations that are hard to monitor and guard: telephony installations, television re-peaters, refrigeration chambers, etc.

FeaturesDescription

}} Self-reclosing protection relay with a built-in transformer, with a diameter of Ø 25 mm, with automatic reclosure in case of a trip.}} It is connected to a motorized circuit

breaker of the MT or similar series, acting as the earth leakage protection element or cir-cuit breaker}} Self-reclosing earth leakage and/or over-

load trigger}} Type A relay, with high frequency current

filtering and high immunity. Monitoring in true root mean square (TRMS)}} The WRT-6 has the following functions: }y Earth leakage protection and self-reclos-

ing }y Overload reclosing}} Visualisation of the following on the LED

display:}y instantaneous leakage current value}y total reclosing no. meter}} One output (potential free) to indicate the

reclosing interlocking.

Earth leakage relay with built-in transformerWRT-6Overcurrent and earth leakage protection and self-reclosingEarth leakage relay + circuit breaker

Protection Earth leakage and circuit breaker

Class A superimmunized

Measurement True root mean square (TRMS)

Sensitivity Fixed 30 mA or 300 mA (depending on the type)

Delay Fixed 20 ms

Earth leakage transformer Built-in Ø 25 mm

Test and Reset With built-in button

Associated circuit breaker Motorized circuit-breaker MT

In and no. of poles Defined by the circuit breaker used

Circuit breaker control With ON / OFF Relay

Reclosure Earth leakage and circuit breaker

No. of reclosures 2 circuit breaker and 10 earth leakage

Time between reclosures 1 min

Partial counter reset time 30 min

Safety interlocking In the earth leakage protection device. With disconnection lever

Features

Auxiliary power supply 230 Vac (± 20 %) 50 / 60 Hz

Circuit breaker control contacts 250 Vac, 8 Aac

Output contacts 250 Vac, 8 Aac

Operating temperature -10 ... +50 ºC

Construction features

Fixing DIN rail

Dimensions 6 modules

Weight 425 g

Degree of protection IP 20 Terminals, IP 41 Embedded relay

Standards

IEC 61008-1, IEC 755, IEC 255-5

Page 24: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-24

No. of reclosures

Useful diameter Ø (mm) In (A)

Delay (s) (*) Poles

Control of the circuit breaker Type Code

2 circuit breaker 10 earth leakage 25 0,03 0,02 in accordance

with MTON / OFF Relay WRT-6-25 0.03 P21121

2 circuit breaker 10 earth leakage 25 0,3 0,02 in accordance

with MTON / OFF Relay WRT-6-25 0.3 P21122

(*) The delay is cancelled in all relays with a sensitivity adjustment of 0.03 A.

References

Dimensions

Connections

Earth leakage relay with built-in transformerWRT-6

Overcurrent and earth leakage protection and self-reclosingEarth leakage relay + circuit breaker

LOAD

SEALSIGNAL

Page 25: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-25

Aplicación

WRU-10 MT relays associated with a motori-zed circuit breaker allow automatic reclosing after tripping, thus offering the most adequate solution for public lighting, ATM machines, re-frigerating chambers, traffic lights, etc. Their design features guarantee maximum security and continuity of the electrical service, avoiding unwanted tripping.

FeaturesDescription

}} Electronic earth leakage protection relay with automatic reclosing with built-in 28 mm transformer, forming a single unit.}} Superimmunized type A , with high-frequen-

cy current filter and high immunity. True root mean square measure (TRMS)}} Display with LEDs and backlight display:

- Earth leakage reclosing / protection parame-ters- Protection trip current- Number of reclosures- Protection status messages, etc.}} Unit with three contact output relays

one switched and two simple relays, all pro-grammable. The main relay provides the pro-tection associated with the contact, one is for the prealarm and the other for locking once the maximum number of reclosures is reached.}} It includes a voltage-free input for

external tripping and reclosing}} Fitting on DIN 46277 rail (EN-50022)}} Reduced three-module size}} Connection by pluggable terminals

Earth leakage relay with built-intransformer and display (type A)

WRU-10 MTOvercurrent and earth leakage protection and self-reclosingRelé diferencial con toroidal integrado + magnetotérmico motorizado

Protection Earth leakage

Class A superimmunized

Measurement True root mean square (TRMS)

PROGRAMMABLE sensitivity 0.03 to 3 A, amplifiable to 30 A using SETUP

PROGRAMMABLE delay

Time defined: 0.02 to 1 s, amplifiable to 10 s using SETUP.Inverse curve: INStantaneous / SELective. (IEC 60947-2)

Test and Reset Using buttons T & R

Associated circuit breaker Circuit breaker defining the number of poles and the In

Circuit breaker control Switched NO/NC contact relay

Reclosure Earth leakage and circuit breaker

No. of reclosures

ProgrammableTime between reclosures

Reclosure counter reset time

Relay signalling

LED indicators / backlight DISPLAY

• Power supply voltage • Leakage trigger• Prealarm• Locking

• Protection settings• Leakage current/

trip reading• TEST statuses and

external trip• Sequences / Number

of reclosures

Remote Control External TEST possible, tripping by voltage-free input

Electrical features

Auxiliary power supply 230 V ac (± 30%) 50 / 60 Hz

Output contacts 250 V ac, 5 A / 230 V ac, 250 mA

Operating temperature -20 ... + 70 ºC

Mechanical features

Attachment DIN rail 46722 (EN 50022)

Dimensions 3 modules

Weight 275 g

Protection degree IP 20, trans-cabinet IP 41

Standards

IEC 60947-2, IEC 60755, IEC 62020, IEC 61008

Page 26: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-26

Connections

References

Dimensions

Earth leakage relay with built-intransformer and display (type A)

WRU-10 MT

Overcurrent and earth leakage protection and self-reclosingRelé diferencial con toroidal integrado + magnetotérmico motorizado

MENU SETUP

NL1 L2 L3

M

N L

O I 12

11

Reset

Test

WRU-10 MT

4 5 6 3

9 10 11

1

1

�TILI���ION

R

MT��������2�������

O�����e�te���

23�����

MENU SETUP

NL1 L2 L3

M

N L

O I 12

11

Reset

Test

WRU-10 MT

4 5 6 3

9 10 11

1

1

�TILI���ION

RI�

MT��������2���

O�����e�te��� ������s

23�����

�1

�2

������

��

���te��������T��TRI����Re���e����

���te�����Re���e����

45

44

52,5

n2827

,25

73

1022,75

75

85

No. of reclosuresTime between reclosures

Net section (mm) In (A) Delay Type Code

Programmable Ǿ 28 0.03 to 3 A amplifiable to 30 A

0.02 to 1 s amplifiable to 10 sInverse curve: INS/SEL

WRU-10 MT P24275

Page 27: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-27

Protection Earth leakage and Circuit breaker

Class A superimmunized

Measurement True root mean square (TRMS)

Sensitivity Programmable from 30 mA ... 30 A

Delay Programmable from 20 ms ... 10 sInverse curve: instantaneous or selective

Earth leakage transformer External, WG / WGS / WGC

Test and Reset With built-in button

Associated circuit breaker Motorized circuit breaker MT Series, MT-FDE

In and no. of poles Defined by the circuit breaker used

Circuit breaker control Simple relay ON / OFF

Reclosure Earth leakage and Circuit breaker

No. of reclosures Programmable

Time between reclosures Programmable

Partial counter reset time Programmable

Relay signaling

LED

• Presence of voltage• Leak trip• Reclosing activation• Interlocking status

Display LCD

Remote signaling (outputs) Lock status indicator relay

Remote Control (inputs) ON / OFF

Features

Auxiliary power supply 230 Vac (± 20 %) 50 / 60 Hz

Output contacts Current 5 Aac

Operating temperature -10 ... +50 ºC

Construction features

Fixing DIN rail

Dimensions 3 modules

Weight 236 g

Degree of protection IP 20 Terminals, IP 41 back panel

Standards

IEC 61008-1, IEC 755, IEC 255-5

Application

The RGU-10 MT relays associated to the transformers of the WG Series allow an in-telligent earth leakage protection. These are used jointly with an MT or similar circuit breaker to enable the self-reclosure after a trip (overload and earth leakage reclosing), offering a very good solution for public light-ing, cash machines, refrigeration chambers, etc. Their design characteristics guarantee maximum security and continuity of the elec-trical service, avoiding unwanted tripping.

FeaturesDescription

}} Self-reclosing, electronic earth leakage protection relay}} Associated to an external toroidal trans-

former of the WG / WGS / WGC Series. It is connected to a motorized circuit breaker of the MT or similar series as the circuit breaker}} The self-reclosing earth leakage and/or

overload trip is programmable}} Superimmunized Type A relay with high

frequency current filtering and high immunity. Monitoring in true root mean square}} Backlight display }} Two independent outputs: trigger/reset re-

lay and end-of-reclosing-sequence interlock-ing relay}} External input for remote control func-

tions}} Automatic test of the connection and sta-

tus of the external transformer with an induc-tive test

Earth leakage Relay WG + MT Series

RGU-10 MTOvercurrent and earth leakage protection and self-reclosingEarth leakage relay + circuit breaker + transformer

Page 28: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-28

Reclosing element Communications In (A) Delay (s) (*) Type Code

Circuit-breaker - 0,03 ... 30 0,02 ... 10 RGU-10 MT P24642

Circuit-breaker RS-485 0,03 ... 30 0,02 ... 10 RGU-10 C MT P24652

(*) The delay is cancelled in all relays with a sensitivity adjustment of 0.03 A.

References

Dimensions

Connections

RGU-10 MT / RGU-10C MT RGU-10 MT with coil / RGU-10C MT with coil

Earth leakage Relay WG / WGC + MT SeriesRGU-10 MT

Overcurrent and earth leakage protection and self-reclosingEarth leakage relay + circuit breaker + transformer

MT

WG

MT

WG

SUPPLY A.C. 230 V

CARGALOAD

NL1 L2 L3

MU>

N LC1

C2 O I 12

11

1S1

1S2

Type

WG

1S11

S2

ON

/ O

FF e

xter

noE

xter

nal O

N/O

FF

Disparo por BOBINA Trip by TRIP COIL.

7 81 2 4 5 6

10 11 13 14 15

Reset

TestRGU-10 MT

12

3 9 CARGALOAD

NL1 L2 L3

M

N L

O I 12

11

T ype

WG

1 S11

S2

ON

/ O

FF e

xter

noE

xter

nal O

N/O

FF

Disparo por MOTOR OFFTrip by OFF MOTOR.

7 81 2 4 5 6

10 11 13 14 15

Reset

TestRGU-10 MT

12

3 9

1S1

1S2

MT

- C- 6

2/64

MT

- C- 6

2/64

SUPPLY A.C. 230 V

SETTING SETUPTRIP: SEC.T: St (in case of shunt coil)

Pt (in case of undervoltage coil)

SETTING SETUPTRIP:

SUPPLY A.C. 230 V

CARGALOAD

NL1 L2 L3

MU>

N LC1

C2 O I 12

11

1S1

1S2

Type

WG

1S11

S2

ON

/ O

FF e

xter

noE

xter

nal O

N/O

FF

Disparo por BOBINA Trip by TRIP COIL.

7 81 2 4 5 6

10 11 13 14 15

Reset

TestRGU-10 MT

12

3 9 CARGALOAD

NL1 L2 L3

M

N L

O I 12

11

T ype

WG

1 S11

S2

ON

/ O

FF e

xter

noE

xter

nal O

N/O

FF

Disparo por MOTOR OFFTrip by OFF MOTOR.

7 81 2 4 5 6

10 11 13 14 15

Reset

TestRGU-10 MT

12

3 9

1S1

1S2

MT

- C- 6

2/64

MT

- C- 6

2/64

SUPPLY A.C. 230 V

SETTING SETUPTRIP: SEC.T: St (in case of shunt coil)

Pt (in case of undervoltage coil)

SETTING SETUPTRIP:

Page 29: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-29

Protection Earth leakage and circuit breaker

Class A superimmunized

Measurement True root mean square (TRMS)

Sensitivity 0.03 / 3 A

Delay Fixed 20 ms

Earth leakage transformer External, WG / WGS / WGC

Test and Reset With built-in button

Associated circuit breaker Motorized circuit-breaker MT

In, No. of poles, thermal curve and cut-out power Defined by the circuit breaker used

Reclosure Earth leakage and circuit breaker

No. of reclosures 2 circuit breaker and 10 earth leakage

Time between reclosures 3 min

Partial counter reset time 30 min

Safety interlocking In the circuit breaker. With disconnection lever

Features

Auxiliary power supply 230 Vac (± 20 %) 50 / 60 Hz

Circuit breaker control contacts 250 Vac, 8 A

Output contacts 250 Vac, 8 A

Operating temperature -10 ... +50 ºC

Construction features

Fixing DIN rail

Dimensions 6 modules

Weight 350 g

Degree of protection Terminals: IP 20Embedded: IP 41

Standards

IEC 61008-1, IEC 755, IEC 255-5, IEC 947-2, IEC 60898

Application

The RGMT relays associated to WG, trans-formers, connected to an MT or similar circuit breaker guarantee the self-reclosing earth leakage and overload protection of a sys-tem after a trip, with both earth leakage and overload protection systems. It is the ideal solution for telephony installations, television repeaters, etc.

FeaturesDescription

}} Self-reclosing electronic earth leakage protection relay, associated to an external toroidal transformer of the WG / WGS / WGC}} It is connected to a motorized circuit break-

er of the MT or similar series as the overload protection or circuit breaker element.}} Type A relay with high frequency current

filtering and high immunity. Monitoring in true root mean square (TRMS).}} The RGMT has the following functions:}y Earth leakage protection and self-reclos-

ing}y Overload reclosing.}} Display of:}y Relay status}y Total reclosure no. meter}} Two remote control inputs:}y Remote trip/reset of the group}y Activate/Deactivate the overload reclos-

ure process.

Earth leakage Relay WG + MT SeriesRGMTOvercurrent and earth leakage protection and self-reclosingEarth leakage relay + circuit breaker + transformer

Page 30: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-30

Useful diameter Ø mm Poles In (A) No. of reclosures

Control of the circuit breaker

Delay (s) (*) Type Code

In accordance with WG

In accordance with MT 0,03 / 3 circuit breaker: 2

earth leakage: 10Relay ON / OFF 02 RGMT P21130

(*) The delay is cancelled in all relays with a sensitivity adjustment of 0.03 A.

References

Dimensions

Connections

Earth leakage Relay WG + MT SeriesRGMT

Overcurrent and earth leakage protection and self-reclosingEarth leakage relay + circuit breaker + transformer

Page 31: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-31

Application

The RECmax MP series are motorized circuit breakers that can be controlled remotely, apt for any application in which remote connec-tion/disconnection control is required.

They are also used as circuit breakers linked to CIRCUTOR self-reclosing relays.

They are an essential accessory for protec-tion and automatic circuit breaker and earth leakage reclosing system

FeaturesDescription

The RECmax MP series are motorized circuit breakers that can be linked remotely.

They function as protection against short-circuit and overload, and can also be used as a circuit breaker.

After a disconnection caused by a circuit breaker, the switch can be reconnected through an external order. It has two inputs that act through voltage-free external signals, ordering the opening (input O) and subse-quent closing (reclosing system) of the auto-matic switch (input I) . It also has two single-contacts outputs for signalling the status and the cause of the opening and closing of the automatic switch (trip, manual/Test).

Motorized circuit breaker (up to 63 A)RECmax MPOvercurrent and earth leakage protection and self-reclosing

Circuit-breaker

Gauges In (A) 6-10-16-20-25-32-40-50-63

Nominal cut-out power (IEC 947-2) 6 kA, in accordance with EN 6089810 kA, in accordance with EN 60947-2

Typical curve C or D, depending on the type

Nominal working voltage 240 / 415 Vac

Work frequency range 50 ... 60 Hz

Operating temperature -25 ... +55 ºC

Storage temperature -55 ... +55 ºC

Motor

Nominal voltage 230 Vac, ± 10 %

Opening impulse > 50 ms

Closing impulse > 50 ms

Construction features

Fixing DIN rail

Dimensions 2 poles: 5.5 modules4 poles: 7.5 modules

Mechanical working life > 20,000 operations

Weight 2 poles: 645 g4 poles: 890 g

Degree of protection IP 40 (DIN 40050)

Standards

IEC 947-2, IEC 60898

Page 32: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-32

Motorized circuit breaker (up to 63 A)RECmax MP

Overcurrent and earth leakage protection and self-reclosing

References

2 poles 4 poles

In (A)

C Curve D Curve C Curve D Curve

Type Code Type Code Type Code Type Code

6 RECmax MP-C2-6 P27110 RECmax MP-D2-6 P27130 RECmax MP-C4-6 P27120 RECmax MP-D4-6 P27140

10 RECmax MP-C2-10 P27111 RECmax MP-D2-10 P27131 RECmax MP-C4-10 P27121 RECmax MP-D4-10 P27141

16 RECmax MP-C2-16 P27112 RECmax MP-D2-16 P27132 RECmax MP-C4-16 P27122 RECmax MP-D4-16 P27142

20 RECmax MP-C2-20 P27113 RECmax MP-D2-20 P27133 RECmax MP-C4-20 P27123 RECmax MP-D4-20 P27143

25 RECmax MP-C2-25 P27114 RECmax MP-D2-25 P27134 RECmax MP-C4-25 P27124 RECmax MP-D4-25 P27144

32 RECmax MP-C2-32 P27115 RECmax MP-D2-32 P27135 RECmax MP-C4-32 P27125 RECmax MP-D4-32 P27145

40 RECmax MP-C2-40 P27116 RECmax MP-D2-40 P27136 RECmax MP-C4-40 P27126 RECmax MP-D4-40 P27146

50 RECmax MP-C2-50 P27117 RECmax MP-D2-50 P27137 RECmax MP-C4-50 P27127 RECmax MP-D4-50 P27147

63 RECmax MP-C2-63 P27118 RECmax MP-D2-63 P27138 RECmax MP-C4-63 P27128 RECmax MP-D4-63 P27148

79

4586 90 110 110

115

90 45

33

83

50

35

Dimensions

NL1 L2 L3

M

N L

O I

DISCONNECTIONEXTERNAL

C

RECONNECTIONEXTERNAL

14 9

15 10

Reset Test

TRIP

ON

/ O

FF

!

1 2 3 4 5 6 7 8

N LPOWER

230 V 30%50-60 Hz ; 5 VA

ac

CONTACT NC CONTACT NO

TRIP ON/OFF

230 V ; 0,25 Aac230 V ; 0,25 AacM !

ON

OFF

TEST

O C I

MP

9 10 11 12 13 1514

1 2 3N L

TRIP ON/OFFO C I

9 10 11 12 13 1514

POWER

4 5 6 7 8

Connections

Page 33: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-33

Application

The MT Series is composed of motorized cir-cuit breakers that can be activated remotely and can be used in any application that uses a connection/disconnection remote control. They are also used as the circuit breakers associated to the self-reclosing relays.

They are a vital accessory in the self-reclos-ing overload and earth leakage protection process.

FeaturesDescription

The motorized circuit breakers of the MT Se-ries can be associated remotely. They protect against short-circuits and overloads, but are also used as a circuit breaker.

Includes auxiliary contacts to indicate the sta-tus of the circuit breaker.

The switch can be connected again after a manual or circuit breaker disconnection with an electric order following the "DISCONNEC-TION (0) - CONNECTION (1)" sequence.

Motorized circuit breaker (up to 63 A)MTOvercurrent and earth leakage protection and self-reclosing

Circuit-breaker

Gauges In (A) 6-10-16-20-25-32-40-50-63

Nominal cut-out power (IEC 947-2) 6 kA, in accordance with EN 6089810 kA, in accordance with EN 60947-2

Typical curve C or D, depending on the type

Nominal working voltage 240 / 415 Vac

Work frequency range 50 ... 60 Hz

Operating temperature -25 ... +55 ºC

Storage temperature -55 ... +55 ºC

Motor

Nominal voltage 230 Vac, ± 10 %

Opening impulse > 50 ms

Closing impulse > 50 ms

Construction features

Fixing DIN rail

Dimensions 2 poles: 5.5 modules4 poles: 7.5 modules

Mechanical working life > 20,000 operations

Weight 2 poles: 645 g4 poles: 890 g

Degree of protection IP 40 (DIN 40050)

Standards

IEC 947-2, IEC 60898

Page 34: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-34

Motorized circuit breaker (up to 63 A)MT

Overcurrent and earth leakage protection and self-reclosing

References

Dimensions

2 poles 4 poles

In (A)

C Curve D Curve C Curve D Curve

Type Code Type Code Type Code Type Code

6 MT-C-E62-6A P20110 MT-D-E62-6A P20130 MT-C-E64-6A P20120 MT-D-E64-6A P20140

10 MT-C-E62-10A P20111 MT-D-E62-10A P20131 MT-C-E64-10A P20121 MT-D-E64-10A P20141

16 MT-C-E62-16A P20112 MT-D-E62-16A P20132 MT-C-E64-16A P20122 MT-D-E64-16A P20142

20 MT-C-E62-20A P20113 MT-D-E62-20A P20133 MT-C-E64-20A P20123 MT-D-E64-20A P20143

25 MT-C-E62-25A P20114 MT-D-E62-25A P20134 MT-C-E64-25A P20124 MT-D-E64-25A P20144

32 MT-C-E62-32A P20115 MT-D-E62-32A P20135 MT-C-E64-32A P20125 MT-D-E64-32A P20145

40 MT-C-E62-40A P20116 MT-D-E62-40A P20136 MT-C-E64-40A P20126 MT-D-E64-40A P20146

50 MT-C-E62-50A P20117 MT-D-E62-50A P20137 MT-C-E64-50A P20127 MT-D-E64-50A P20147

63 MT-C-E62-63A P20118 MT-D-E62-63A P20138 MT-C-E64-63A P20128 MT-D-E64-63A P20148

Accessory - Trip coil F6 P29101

2 poles

4 poles

Connections

LN

External connection signal

External disconnection signal

H HM

LN

I

2 4 12 2214 24

11 2131

0

LNLOAD

Conexionado Motor MT

LN

Orden conexión externa

Orden desconexión externa

H HM

LN

I

2 4 12 2214 24

11 2131

0

LNCARGA

Page 35: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-35

Application

The MT-FDE Series is composed of motor-ized circuit breakers that can be activated remotely and can be used in any application that uses a connection/disconnection remote control.

They are also used as circuit breakers as-sociated to the self-reclosing relays, for ex-ample, RGU-10 MT orRRM. They are a vital accessory in the self-reclosing overload and earth leakage protection process.

FeaturesDescription

Automatic switch with remote control of the MT-FDE Series, for currents of 80 to 250 A, 3 and 4 poles.

Responsible for the protection against short-circuits and overloads, but also used as a circuit breaker.

The switch can be reclosed with two me-thods, depending on the adjustment of the motor group in the operations mode:

}} “MANU”: executed manually with the same switch, following the OFF and ON se-quence.}} “AUTO”: carried out with an electrical im-

pulse, following the OFF and ON sequence.

Motorized circuit-breaker (from 63 A)MT-FDEOvercurrent and earth leakage protection and self-reclosing

Circuit-breaker

Gauges In (A) MT-FDE: 80-100-125-160MT-FEE: 250

No. of poles 3 or 4, depending on the type

Nominal cut-out power (IEC 947-2) MT-FDE: 25 kA, in accordance with IEC 60947-2MT-FEE: 36 kA

Typical curve C or D, depending on the type

Nominal working voltage 240 / 415 Vac

Work frequency range 50 ... 60 Hz

Operating temperature -25 ... +55 ºC

Storage temperature -55 ... +55 ºC

Motor

Nominal voltage 230 Vac

Minimum voltage 210 Vac

Activation impulse 50 ms

Deactivation impulse 50 ms

Construction features

Fixing Panel (base + plug-in socket)

Dimensions 3 poles: 81 x 130 x 185 mm4 poles: 108 x 130 x 185 mm

Weight Depending on the type

Degree of protection IP 40 (DIN 40050)

Standards

IEC 60947-2

Page 36: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-36

References

Motorized circuit-breaker (from 63 A)MT-FDE

Overcurrent and earth leakage protection and self-reclosing

3 poles 4 poles

Type Weight (kg) Code Type Weight (kg) Code

80 MT-FDE-80A 2,9 P20D60 MT-FDE-80A 3,4 P20D70

100 MT-FDE-100A 2,9 P20D61 MT-FDE-100A 3,4 P20D71

125 MT-FDE-125A 2,9 P20D62 MT-FDE-125A 3,4 P20D72

160 MT-FDE-160A 2,9 P20D63 MT-FDE-160A 3,4 P20D73

250 MT-FEE-250A 3,8 P20D64 MT-FEE-250A 4,6 P20D74

Connections

Dimensions

3 poles

4 poles

N L1 L2 L3

N L1 L2 L3

F1

N

A111

A4A212

N

8642

7531

Off

On

ED

EC

1

MANUAL

OffOn

N L1 L2 L3

N L1 L2 L3

LOAD

F1

N

A111

A4A212

N

8642

7531

Off

On

ED

EC

1 FDE

MANUAL

OffOn

Page 37: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-37

Application

The WRGMT groups can be used to make safety compatible with the continuity of the service in remote installations or installations that do not have the usual maintenance staff. They guarantee the overload and earth leak-age protection with a self-reclosing system after a trigger, both in the case of an earth leakage and overload trip.

It is a very good solution in installations in special locations that are hard to monitor and guard: telephony installations, television re-peaters, refrigeration chambers, etc.

Description

The WRGMT group acts as an overload (overload + short-circuit) and earth leakage protection system with earth leakage and overload reclosure.

The nominal current of the overload protec-tion is determined by the type of MT (up to 63 A) or MT-FDE used.

The group is composed of the following ele-ments:

}} RGMT relay (earth leakage protection)}} Motorized automatic switch of the MT-

FDE Series or motorized circuit breaker of the MT Series, with overload protection and circuit breaker functions}} Earth leakage transformer, WG

Complete overload and earth leakage protection and reclosure equipment

WRGMTOvercurrent and earth leakage protection and self-reclosing

References

Dimensions

WRGMT, 2 poles

2 poles 4 poles

IDn (A) Type Code Type Code

6 WRGMT-C-2-6 A P21210 -- --

10 WRGMT-C-2-10 A P21211 WRGMT-C-4-10 A P21221

16 WRGMT-C-2-16 A P21212 WRGMT-C-4-16 A P21222

20 WRGMT-C-2-20 A P21213 WRGMT-C-4-20 A P21223

25 WRGMT-C-2-25 A P21214 WRGMT-C-4-25 A P21224

32 WRGMT-C-2-32 A P21215 WRGMT-C-4-32 A P21225

40 WRGMT-C-2-40 A P21216 WRGMT-C-4-40 A P21226

50 WRGMT-C-2-50 A P21217 WRGMT-C-4-50 A P21227

63 WRGMT-C-2-63 A P21218 WRGMT-C-4-63 A P21228

Other currents, on demand

WRGMT, 4 poles

Page 38: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-38

Application

The RECmax MP series are motorized circuit breakers that can be reset automatically or controlled remotely, apt for any application in which remote connection/disconnection con-trol is required.

They are an essential accessory for protec-tion and automatic circuit breaker and earth leakage reclosing system, and for external connection/disconnection control.

Features

Description

The RECmax P series are 2- and 4-pole cir-cuit breakers connected to a compact motor and internal control unit that enables auto-matic reclosing system.

After triggering, the switch reconnects follow-ing a sequence of 3 reconnections, with 3 minutes between resets. If the unit is not able to reconnect after 3 attempts, it remains trig-gered until a manual or remote reset is made.

They can also be connected remotely to an external control. It has two inputs that through voltage-free external signals, order the open-ing (input O) and subsequent closing (reclos-ing system) of the automatic switch (input I) .

They function as protection against short-circuit and overload, and can also be used as a remote circuit breaker.

The switch status is indicated by LED signals on the device’s front panel. An green ON LED indicates that the device is in service; a red OFF LED indicates that the device is triggered.

A TEST/RESET of the device can be per-formed by pressing a button to check the trig-gering and then reset the device.

It also has two single-contact outputs for sig-nalling the status and the cause of the open-ing and closing of the automatic switch (trig-ger, manual/Test).

Self-reclosing motorized circuit breaker (up to 63 A)

RECmax POvercurrent self-reclosing

Circuit-breaker

Gauges In (A) 6-10-16-20-25-32-40-50-63

Nominal cut-out power (IEC 947-2) 6 kA, in accordance with EN 6089810 kA, in accordance with EN 60947-2

Typical curve C or D, depending on the type

Nominal working voltage 240 / 415 Vac

Work frequency range 50 ... 60 Hz

Operating temperature -25 ... +55 ºC

Storage temperature -55 ... +55 ºC

Motor

Nominal voltage 230 Vac, ± 10 %

Opening impulse > 50 ms

Closing impulse > 50 ms

Construction features

Fixing DIN rail

Dimensions 2 poles: 5.5 modules4 poles: 7.5 modules

Mechanical working life > 20,000 operations

Weight 2 poles: 645 g4 poles: 890 g

Degree of protection IP 40 (DIN 40050)

Standards

IEC 947-2, IEC 60898

Page 39: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-39

Self-reclosing motorized circuit breaker (up to 63 A)

RECmax P

Overcurrent self-reclosing

References

79

4586 90 110 110

115

90 45

33

83

50

35

Dimensions

Connections

NL1 L2 L3

M

N L

O I

DISCONNECTIONEXTERNAL

C

RECONNECTIONEXTERNAL

14 9

15 10

Reset Test

TRIP

ON

/ O

FF

!

2 poles 4 poles

In (A)

C Curve D Curve C Curve D Curve

Type Code Type Code Type Code Type Code

6 RECmax P-C2-6 P28110 RECmax P-D2-6 P28130 RECmax P-C4-6 P28120 RECmax P-D4-6 P28140

10 RECmax P-C2-10 P28111 RECmax P-D2-10 P28131 RECmax P-C4-10 P28121 RECmax P-D4-10 P28141

16 RECmax P-C2-16 P28112 RECmax P-D2-16 P28132 RECmax P-C4-16 P28122 RECmax P-D4-16 P28142

20 RECmax P-C2-20 P28113 RECmax P-D2-20 P28133 RECmax P-C4-20 P28123 RECmax P-D4-20 P28143

25 RECmax P-C2-25 P28114 RECmax P-D2-25 P28134 RECmax P-C4-25 P28124 RECmax P-D4-25 P28144

32 RECmax P-C2-32 P28115 RECmax P-D2-32 P28135 RECmax P-C4-32 P28125 RECmax P-D4-32 P28145

40 RECmax P-C2-40 P28116 RECmax P-D2-40 P28136 RECmax P-C4-40 P28126 RECmax P-D4-40 P28146

50 RECmax P-C2-50 P28117 RECmax P-D2-50 P28137 RECmax P-C4-50 P28127 RECmax P-D4-50 P28147

63 RECmax P-C2-63 P28118 RECmax P-D2-63 P28138 RECmax P-C4-63 P28128 RECmax P-D4-63 P28148

1 2 3 4 5 6 7 8

N LPOWER

230 V 30%50-60 Hz ; 5 VA

ac

CONTACT NC CONTACT NO

TRIP ON/OFF

230 V ; 0,25 Aac230 V ; 0,25 AacM !

ON

OFF

TEST

O C I

MP

9 10 11 12 13 1514

1 2 3N L

TRIP ON/OFFO C I

9 10 11 12 13 1514

POWER

4 5 6 7 8

Page 40: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-40

Protection Circuit breaker

Associated circuit breaker Motorized circuit breaker MT or MT-FDE

In, No. of poles, thermal curve and cut-out power Defined by the circuit breaker used

Circuit breaker control Motor control contactor

Reclosure Circuit breaker

No. of reclosures Programmable: 0, 1, 2, 4, 6, 8 times

Time between reclosures Programmable: 0.5, 1, 2, 3, 4, 5 min

Partial counter reset time 30 min

Safety interlocking In the circuit breaker. With disconnection lever

Relay signaling

LED

• Presence of voltage and no circuit breaker trigger• Trigger set off by external order• Interlocking after the end of reclosures• Reclosing

Remote signaling (outputs) RRM-P: Interlocking relayRRM-C: RS-485 Communications

Remote Control (inputs) ON/OFF Potential free input of the circuit breaker (non-reclosing external OFF)

Features

Auxiliary power supply 230 Vac (± 20 %) 50 / 60 Hz

Output contacts 250 Vac, 1 A

Operating temperature -10 ... +50 ºC

Construction features

Fixing DIN rail

Dimensions 1 modules

Weight 88 g

Degree of protection IP 20 Terminals, IP 41 back panel

Standards

IEC 947-2

Application

The RRM relays can be used in all applica-tions that require a self-reclosing motorized circuit breaker after a trigger or with the use of remote control systems. It has been specially designed to work with the circuit breakers of the MT or MT-FDE Series.

FeaturesDescription

Self-reclosing electronic relay of motorized circuit breakers.

The relays of the RRM series can be used to control, send remote signals and for the remote control of the associated motorized circuit breaker (MT or MT-FDE Series).

The RRM relay has the following functions:

}} Motorized circuit breaker control:}y Automatic reclosing}y Remote connection/disconnection (non-

reclosing)}} Signalling:}y Local, with LEDs}y Remote signalling with relay of the re-

closing lock (in RRM-P)}y RS-485 Communications (in RRM-C)}} Remote control of the automatic switch

The complete reclosing group is composed of the following elements:

}} Motorized circuit breaker of the MT or MT-FDE Series (2 or 4 poles)}} Control relay RRM.

Overload reclosing relayRRMOverload reclosure and protectionOverload + reclosing relay

Page 41: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-41

Reclosing element Communications

Number of reclosures

Time between reclosures Type Code

Circuit-breaker - 0, 1, 2, 4, 6, 8 0.5, 1, 2, 3, 4, 5 min RRM-P P25130

Circuit-breaker RS-485 0, 1, 2, 4, 6, 8 0.5, 1, 2, 3, 4, 5 min RRM-C P25131

References

Dimensions

Connections

RRM-P RRM-C

Overload reclosing relayRRM

Overload reclosingOverload + reclosing relay

LOADEXTERNAL TRIP

LOADEXTERNAL TRIP

SEALED RELAY

Page 42: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-42

Relation between products and accessories

Adaptor panel Contactor MCB MT MT-FDE WG / WGS

Adaptor for 72 x 72 panel Contactor Circuit breaker Motorized circuit breaker Motorized circuit

breakerEarth leakage transformers

M5ZZF1 -- See page 56 See page 66 See page 68 See P.1

REC

2

-- -- -- -- -- --

RG

U-1

0 R

AL

-- -- --

CB

S-4

RA

-- -- --

CB

S-8

-- -- -- --

WR

KR

T-25

-- -- -- -- --

WR

U-2

5 R

A-M

T

-- -- -- --

WR

U-1

0 M

T

-- -- -- --

RG

U-1

0 M

T

-- --

RG

MT

-- -- --

WR

GM

T

-- -- -- --

RR

M

-- -- -- --

Page 43: Self-reclosing overload and earth leakage protection · Self-reclosing overload and earth leakage protection ... The WRU-10 RAL relays combined with a ... Self-reclosing overload

Self-reclosing overload and earth leakage protection

P2-43