Self-Gatekeeping Checklist for Commercial Permitting and Plan Review
Mecklenburg County Code Enforcement 2145 Suttle Avenue, Charlotte, NC 28208 Questions? Contact Customer Service at (980) 314-CODE (2633)
www.meckpermit.com
Date Submitted Date to be Reviewed Date Accepted
Incoming Commercial Plans
Project Name Project Number
Project Address
Contact Person Cell Number
Fax NumberPhone Number Email
I certify, to the best of my professional belief, this submission meets all minimum submittal requirements required by Mecklenburg County Code Enforcement and the Plans Submittal Guidelines.
Signature of Seal holder / Designer License #
This form is intended to be used with OnSchedule, Express Review, Rehab and CTAC (Commercial Technical Assistance Center) plan submittals only. It is not intended to be used with Mega plan submittals.
InstructionsEach item should be evaluated and then indicate Included or N/A for each item as applicable. Every project is different and will require different items. This form should be completed by the Seal holder responsible for the submittal package. If a seal holder is not required, it should be completed by the designer responsible for the submittal package. If items are missing from the submittal package that require the review to be stopped, the review will be disapproved and the disapproval will be counted against the A/E Pass Rate. This form must be submitted with the submittal package.
General RequirementsItem # Item
Drawings Packaged per Packaging GuidelinesG1 Included N/A
2012 Appendix B - (Including Schedule of Special Inspection Services) must be reproduced on the plansIncluded N/AG2Completed Permit Application with Estimated Project Cost and Address Verification (one application per building or unit address)Included N/AG3
Plans that are submitted to our office, if they are marked, must be marked "For Construction Only". Cannot be marked as Bid Only, Permit Only, or 80% complete, only.Included N/AG4
A key plan is required to show location for upfit, renovations, and alterations onlyIncluded N/AG5
Estimated Permit Fees are required for OnSchedule, Express Review, RTAP's, and Rehab project submittalsIncluded N/AG6
Zoning Approval from Towns (Huntersville, Cornelius, Davidson) if applicableIncluded N/AG7
Planning Commission Approval as requiredIncluded N/AG8
Professional Seals signed and dated as requiredIncluded N/AG9All plan sheets are required to be "authored". Need name, address, phone, and signature of individual responsible for each plan sheet when not done by licensed professional.Included N/AG10
CTAC General RequirementsDrawings Packaged per Packaging Guidelines contained in one file (all trades) including a table of contentsG11 Included N/A
2012 Appendix B - (Including Schedule of Special Inspection Services) must be reproduced on the plansIncluded N/AG12Completed Permit Application submitted by contractor online, including Lien Agent (one application per building or unit address) Identify projects that involve multiple building permitsIncluded N/AG13
A key plan is required to show location for upfit, renovations, and alterations onlyIncluded N/AG14
Revisions to Approved Plans (RTAP)Only the revised sheets from the original drawings needs to be uploaded and listed on the Sheet Index with appropriate dates and revision numbersIncluded N/AG20
If the original approved plans were electronic plans from the old system (pre Feb. 1, 2012) upload the original plans as reference plansIncluded N/AG21
If the original approved plans were electronic plans in the new system (post Feb. 1, 2012) no reference plans are necessary to be uploaded, but will be accessed internally by our staff.Included N/AG22
a: Special Inspections checklist completed on Appendix BIncluded N/AG23
Special Inspection (Chapter 17, www.meck-si.com ) Plan Sheet when Special Inspections are required
c: IT categories 1-19 must be reproduced on the plans with the appropriate items indicated that are required for this project. This information is consistent with Appendix B - see www.meck-si.comIncluded N/AG25
b: Statement of Special Inspections (DPIRC) must be reproduced on the plans - see www.meck-si.comIncluded N/AG24
a: Upload modified Sheet IndexIncluded N/AG26
b: Modified Drawing FilesIncluded N/AG27
c: Written and signed response letter to Reviewers comments and uploaded as fileIncluded N/AG28
Re- submittals - Disapproved plans
Civil / Site PlanType of Occupancy and Land UseN/AIncludedC1
C2 N/AIncluded Vicinity Map / Key Map
C3 N/AIncluded North Arrow and Map Scale
C4 N/AIncluded Property and Street Right of Way Lines with Dimensions
C5 N/AIncluded Existing and Proposed Driveway Connections
C6 N/AIncluded Show All Easements and Right of Ways
Shell with CoreG19 Included N/A
ShellIncluded N/AG18
Structural FrameIncluded N/AG17
Footing / FoundationIncluded N/AG16
Phased Construction (see Plans Submittal Document for additional information)
CTAC: Modified drawing files should include the disapproved plan set with the revised sheets at the back of the plan set and amended table of contentsIncluded N/AG29
Construction Phasing Plan with detailed information on the scope of work for each phase along with the appropriate number of permit applications for each phase if applicableIncluded N/AG15
Locations of All Existing and Proposed Structures with Dimensions from Property Lines
Site Lighting PlanIncluded N/AC11
Accessible Curb CutsIncluded N/AC10
Parking Plan, including Accessible Parking, with CalculationsIncluded N/AC9
Locations of All Other Existing and Proposed Site ImprovementsIncluded N/AC8
Included N/AC7
Screening and BuffersIncluded N/AC12
Location, Type and Size of Public/Private Water Lines, Meters and Backflows
Person Responsible for Plan ( Name, Address and Contact Information)Included N/AC19
Owners Name, Address, and Contact InformationIncluded N/AC18
Adjoining Property Owners Names and Land UsesIncluded N/AC17
Storm Drainage / Topography / GradingIncluded N/AC16
Location of Sewer LinesIncluded N/AC15
Fire Hydrants - Public and PrivateIncluded N/AC14
Included N/AC13
Ramps (slope)Included N/AA17
Interior Finish Schedule/ Type MaterialIncluded N/AA20
Door Schedule Including HardwareIncluded N/AA21
Sections through Building (Detailed Wall Sections)Included N/AA22
Firestopping and Draftstopping Included N/AA19
Show toilet room layouts at sufficient scale for dimensions and details to verify for accessibility complianceIncluded N/AA14
Seating Layout - Furniture PlansIncluded N/AA12
Partition Layout/ Fire Ratings with UL/FM #Included N/AA11
Foundation PlanIncluded N/AA4
Floor/ Wall/ Roof PlanIncluded N/AA7
Elevations of building with dimensions (building height, floor to floor, height to ridge and eave)Included N/AA8
Footing Details (sizes & steps)Included N/AA3
Soil Reports or Load Capacity when requiredIncluded N/AA1
Design LoadsIncluded N/AA2
Architectural / Structural / Fire
Rehab Code expenditure log information shown on plans if applicableIncluded N/AA16
NCSBC Chapter 3411.7 Compliance shown on plans if applicableIncluded N/AA15
Show foundation slab details including vapor barrierIncluded N/AA5
Provide basement percentage below grade calculationsIncluded N/AA6
Identify the names and uses of each roomIncluded N/AA9
All penetration details for fire-rated construction including approved agency system informationIncluded N/AA10
Calculations for means of egress widths for occupancy loadsIncluded N/AA13
Wall bracing detailsIncluded N/AA23
Stair Details (risers/treads/handrails)Included N/AA18
Insulation/Energy Form - Comcheck information must be included on plan sheets if usedIncluded N/AA24
Chimney/ Fireplace DetailsIncluded N/AA26
Glass Type - Safety Glass as RequiredIncluded N/AA25
Construction TypeIncluded N/AA28
Gross and Net Floor AreaIncluded N/AA27
Occupancy Category
Fixed Extinguishing Systems (halon/foam)Included N/AA34
Attic ventilation details including overall ventilation calculationsIncluded N/AA33
I-2 occupancy color coded life safety drawings from NC (DHSR)Included N/AA32
High Piled StorageIncluded N/AA31
Hazardous Materials Storage or UseIncluded N/AA30
Included N/AA29
Window Schedule
Details for fabric awnings and canopies including fire-resistance informationIncludedA37
Pre-Engineered Metal Building Details - Option A or B - see Department policy Included N/AA36
Included N/AA35
N/A
Upfits of Multi-Tenant BuildingsIncluded N/AE18
Require Electrical Shell Drawing of BuildingIncluded N/AE19
Lighting Fixtures/ Outlet LayoutIncluded N/AE17
Smoke DetectorsIncluded N/AE16
Exit LightsIncluded N/AE15
Emergency Systems/ LightsIncluded N/AE14
SignsIncluded N/AE13
Hazardous Areas - Show classification of hazardous areas and define all boundaries.Included N/AE12
Fixed Electric HeatIncluded N/AE11
Separately Derived Systems GroundIncluded N/AE10
Ground Fault ProtectionIncluded N/AE9
Transformer Overcurrent ProtectionIncluded N/AE7
Feeder Overcurrent ProtectionIncluded N/AE6
Panel Overcurrent ProtectionIncluded N/AE5
Service Overcurrent Protection - Identify service mains, ratings and characteristicsIncluded N/AE4
Grounding Electrode ConductorIncluded N/AE3
Riser DiagramIncluded N/AE2
Number of Services and Equipment Physical LocationsIncluded N/AE1
Electrical
MechanicalEquipment (types, sizes, & location)Included N/AM1
Fuel-Vent or Chimney Size and LocationIncluded N/AM2
Combustion/ Ventilation, Air, Size and Location with CalculationsIncluded N/AM3
Ductwork (sizing, locations & insulation)Included N/AM4
Supply & Return Air Outlet, Inlet Locations, and Exhaust TerminationsIncluded N/AM5
Type of Duct MaterialsIncluded N/AM6
Fire Alarm Devices, Riser Diagram and Sequence of OperationsIncluded N/AE20
Included N/AE8 Panel Schedules with NEC 220 load summary for all new and/or affected panels and services
Exhaust Fans (CFM's)Included N/AM8
Show all fire-rated and smoke-rated walls (both existing and new) with their ratings on the Mechanical PlansIncluded N/AM7
Smoke Detection for Return Air
Kitchen Hood IncludedM11
Fire Dampers with applicable type noted; Static or DynamicIncludedM10
IncludedM9 N/A
N/A
N/A
HVAC Condensation Drain and termination / discharge location
BTU's/ CFM/ Tons of EquipmentIncluded N/AM18
Accessibility of EquipmentIncluded N/AM17
Structural Support Detail for RTU's > 500 lbsIncluded N/AM16
Rooftop Equipment DetailIncluded N/AM15
Gas Piping Detail Material, Size, Loads (Existing & New) and Total Equivalent Pipe LengthIncluded N/AM14
Energy Form (2012 NCECC 506 Requirements)Included N/AM13
Included N/AM12
Type System (wet, dry, etc.)Included N/AS5
Pipe Schedule or Hydraulic Included N/AS6
Total Flow & Pressure DemandIncluded N/AS7
Size, Location, & Main Risers and FDCIncluded N/AS8
Location of Private MainsIncluded N/AS9
If Hydraulic Design provide: a) Design/ Density/ AreaN/AIncludedS11
If Hydraulic Design provide: b) Type & Model SprinklerS12 Included N/A
System Standard (NFPA 13, 13R, 231 etc)Included N/AS1
Location of Water ConnectionS2 Included N/A
Test Data (Static, Residual, Flow)S3 Included N/A
Fire Pump DataIncluded N/AS4
SprinklerMinimum Facilities with calculationsIncluded N/AP14
Interceptors - sizing and calculationsIncluded N/AP13
PlumbingFixture (location)Included N/AP1
Drainage, Waste and Vent System Pipe Diagram Sizes (isometric & floor plans) and MaterialsIncluded N/AP2
TrapsIncluded N/AP3
CleanoutsIncluded N/AP4
Water Distribution Diagram and Piping MaterialsIncluded N/AP5
Pressure Reducing ValvesIncluded N/AP6
Backflow Preventers (Fixtures and Appliances)Included N/AP7
Equipment AccessibilityIncluded N/AP8
Leaders and Storm Drains with storm sizing calculations and design criteriaIncluded N/AP9
Connector to City Water/ SewerIncluded N/AP10
Connection to Private Well/ Septic TankIncluded N/AP11
Water Heater Details and LocationIncluded N/AP12
Note Any Unprotected AreasIncluded N/AS10
If Hydraulic Design provide: c) Discharge Constant (X)Included N/AS13
If Hydraulic Design provide: d) Hazen-Williams C. FactorIncluded N/AS14
Evacuation AlarmIncluded N/AS15
Electrical Connection to Central StationIncluded N/AS16
Sprinkler Riser DetailIncluded N/AS17
Sprinkler Information (alterations, renovations, and upfits- Reflective ceiling plan head locations)Included N/AS18