SELECTABLE-RANGE AC CURRENT TRANSDUCER Model CTS-150 · selectable-range ac current transducer...
Transcript of SELECTABLE-RANGE AC CURRENT TRANSDUCER Model CTS-150 · selectable-range ac current transducer...
Single unit offers:
Inputs from 0 to 50, 100 & 150 Amps
Outputs from 0 to 1, 5 or 10 Volts
Field selectable
Switch-Selectable Input and Output Ranges n One model serves a variety of applications
n Accommodates changes in load conditions without replacement
n Minimizes spare parts inventory
Faster, Simpler Installation n Clamped, split-core design for fast, non-interrupting installation
n Flying leads to minimize wiring and installation time
n Compact size to fit in tight spaces
n Self-powered to minimize installation complexity
Building Automation
Data Loggers
Panel Meters
Remote Monitoring
Load Monitoring
Branch Monitoring
Process Automation
Control Systems
Potential Applications
Accuracy and Durability n 1.0% of full scale accuracy on any range
n Average measurement with RMS calibration
n 4X over-range capability
n 600 volt isolation, tested to 3,500 volts
SELECTABLE-RANGE AC CURRENT TRANSDUCER Model CTS-150
4242 REYNOLDS DRIVE • HILLIARD, OHIO • 43026-1264 PHONE: (614) 777-1005 • FAX: (614) 777-4511 WWW.OHIOSEMITRONICS.COM • 1-800-537-6732
08/2016
Input Range (selectable)
Over-range (10 seconds)
Frequency Range
Output Signal (selectable)
Response Time (to 90% of FS)
Ripple (Vpp)
Output Loading
Accuracy
Temp Effect (-40 to 70 ˚C)
Operating RH
Insulation Class
Withstand Voltage
Sensing Aperture
Storage Range
Case
Compliance
Weight
50, 100, or 150 amps
4 X
50-60 Hertz
0 to 1, 5 or 10 volts
<200 mSec
<1.0% FS
>1 Megohm, min
1.0% of Full Scale (FS)
0.006% / ˚C typical
0-95%, non-condensing
600 VAC
3500 VAC for 1 minute
1.00 X 0.91 inches
-40 to 85 ˚C
UL94 V-0
RoHS
0.5 lbs
SPECIFICATIONS TABLECONNECTIONS & DIMENSIONS
1.66 [42.16]
0.88 [22.35]
1.84 [46.74]
1.44 [36.58]APPROXIMATELY 72”
(-) BLK(+)WHT
(-) BLK(+)WHT
OUTPUT
0.44 [11.18]
0.91 [23.10]
3.12 [79.32]
1.87 [47.45]
0.49 [12.45]
1.00 [25.40]
SELECTABLE-RANGE AC CURRENT TRANSDUCER
INPUT & OUTPUT RANGE SELECTION
0-50Aac Input
0-100Aac Input
0-150Aac Input
0-1Vdc Output 0-5Vdc Output 0-10Vdc Output
DIP-SWITCH SETTINGS
1 2 3 4 5 6
OPEN
1 2 3 4 5 6
OPEN
1 2 3 4 5 6
OPEN
1 2 3 4 5 6
OPEN
1 2 3 4 5 6
OPEN
1 2 3 4 5 6
OPEN
1 2 3 4 5 6
OPEN
1 2 3 4 5 6
OPEN
N/A
4242 REYNOLDS DRIVE • HILLIARD, OHIO • 43026-1264 PHONE: (614) 777-1005 • FAX: (614) 777-4511 WWW.OHIOSEMITRONICS.COM • 1-800-537-6732
Bottom view withDip-Switch identification
Model CTS-150
08/2016