SEISMIC PERFORMANCE OF RC WALL WITH TRUSS TYPE DETAILING … · SEISMIC PERFORMANCE OF RC WALL WITH...
Transcript of SEISMIC PERFORMANCE OF RC WALL WITH TRUSS TYPE DETAILING … · SEISMIC PERFORMANCE OF RC WALL WITH...
SEISMIC PERFORMANCE OF RC WALL WITH TRUSS TYPE DETAILING
R. Deepak Kumar,1 T. J. Vijay2 and Mr. K. Rajeshkumar3 1PG Student,
2,3 Assistant Professor, PSNA College of Engineering and Technology, Dindigul, Tamil Nadu,
India.
ABSTRACT
This paper presents experimental investigations of
seismic behavior of RCC shear walls reinforced with
steel Truss type detailing. In this experimental study,
wall specimens consisting of X bracing in vertical
direction and these specimens were tested under
medium cyclic load reversals and constant axial load
with the help of hydraulic actuator to examine the
influences of embedded truss detailing on the overall
seismic behavior of the specimens. Totally three shear
walls are casted, from that one is kept as standard
reinforcement and other two walls are strengthened by
using additional truss type detailing. The performance
of the wall specimens in terms of load–deformation
response and cracking patterns are evaluated. Based
on those results, detailed discussion of the influence of
different configurations on the seismic performance of
shear walls with different type of truss type detailing is
observed
Key words: truss type detailing, shear wall, cyclic
loading.
1. Introduction
Load bearing masonry consists of materials which
having the brittle nature. The earthquake causes
different kinds of stresses in a structure such as shear,
tension, torsion, etc., The conventional unreinforced
brick masonry collapses instantly during the sudden
earthquakes. It causes death of people and major
economic losses. To overcome these drawbacks,
reinforced concrete shear walls are adopted. The
designing of shear wall structures are not only for
stable, but also comparatively quite ductile. In safety
terms it means that, during very severe earthquakes
they will not suddenly collapse. They give enough
indicative warnings such as widening structural cracks,
yielding rods, etc., that offers most precious moments
for people to run out of structures, before they totally
collapse. For structural purposes, we consider the
exterior walls as shear-resisting walls. Forces from the
ceiling and roof diaphragms make their way to the
outside along assumed paths, enter the walls, and exit at
the foundation. Reinforced concrete (RC) shear walls
have been widely used in high-rise buildings located in
seismic regions to provide sufficient lateral strength
and stiffness to limit nonlinear responses at service
level earthquakes and to ensure adequate nonlinear
deformation capacity during the design of maximum
considered earthquakes. However the energy
dissipating capacity of the RC shear wall depends on
the detailing of the reinforcement in it. To increase the
energy dissipating capacity the additional arrangement
of truss type detailing is to be provided.
Owing to the combination of advantages of
reinforced concrete structural walls have demon- started
superiorities in strength stiffness and ductility.
Which make them favorable worldwide, Especially in
the high seismic regions the sapling of concrete and
tensile cracks can be effectively reduced according to
the experiment from of diagonal bracings can be
introduced in shear walls as an effective approach to
withstand shear force and improve the energy
dissipation capacity by adding inclined bracings in the
RC walls.
In order to supplement the insufficient ongoing
research on RC structural walls with bracings, especially
that on inelastic behavior under reversed cyclic
loadings, tested five specimens consisting of one steel–
concrete composite structural walls for control and other
four ones with bracings. This paper covers a
comprehensive research involving experimental
investigations. Their test specimens demonstrated
excellent ductility and energy dissipation characteristics,
exhibiting stable behavior at very large deformations
even after many load cycles. However, there were
hardly any experiments on steel–concrete composite
structural walls with bracings. Furthermore, most of
research in the literature just gave general comments on
the performance of steel composite shear walls, without
deeper explorations about the effect of individual
parameters.
2. Test program
2.1. Details of specimens
The experimental program included a total of three
specimens named Control and 4VX, which represented
a series of one fourth scale RC shear walls of common
building. All specimens had the exact same dimension
as illustrated in Fig. 1. The specimen was designed and
constructed following the code provisions of ductile
detailing, as per the code IS: 13920:1993. A size of 600
mm × 60 mm × 1100 mm was adopted for the wall,
which was connected to a concrete head with the
dimension of 800mm × 100mm×100mm and 1000 x
250 x 150 mm of base beam size. The differences
between each specimen were the transverse
reinforcement of the embedded 2vx bracings and the
details of detailing is given in table 2.
Table 1. Materials Properties
S.No Material property Results
1 Compressive strength of concrete 26.8 N/mm2
2 Yield strength of steel 458.2 N/mm2
3 Young’s modulus of steel 215462 N/mm2
4 Young’s modulus of Concrete 23846 N/mm2
Table 2 Details of Specimen
Specimens Element Description of detailing
Common for Control specimen
and 4VX specimens
Vertical portion of wall 4nos of 6mm Diameter
Boundary element 4 No. of 6 mm diameter as main bars and 6
mm diameter of 100 mm c/c in shear
Top beam portion 4 No. of 8 mm diameter as main bars and 6
mm diameter of 100 mm c/c in shear
Bottom beam portion 6 No. of 10 mm diameter as main bars and
6 mm diameter of 100 mm c/c in shear
Control specimen Horizontal portion of wall 7nos of 6mm Diameter
4VX specimen Horizontal portion of wall Four Vertical X bracings
Figure 1. Detailing of Control Specimen
Figure 2. Detailing of 4VX Specimen
2.2 Test setup
Each of the test specimens was subjected to axial
loads and cyclic load reversals to simulate an
earthquake scenario by a double acting 100 kN
capacity electro hydraulic actuator.. A constant axial
load of 20 kN (0.1Agf′c) will be applied by one
hydraulic jack of 100 kN loading capacity with its
end connecting to the concrete head. A load cell will
be attached to the jack to measure reaction force
(Figure 3). This setup is designed to ensure uniform
axial load distribution on the wall cross section area,
and more importantly, to accommodate the horizontal
movement of wall specimens due to lateral
displacements.
The first stage aiming to determine the cracking
displacement Δcr increases by the step of 1 mm for
the first 14 cycles and 2 mm for the after cycles.
After cracking happening in both directions, the cycle
Continues by the same size of step until the yielding
of steel is monitored.
The bottom of the wall was connected to laboratory
strong floor by pre-stressing rods, which aimed to
prevent horizontal movement between wall base and
the strong floor as well as the overturning movement.
One end of actuator was fixed to the reaction walls of
lab. All specimens share the same loading apparatus.
Figure 3. Test Setup
3. Experimental observations and results
3.1. Load–deformation response
Figure 4 and 5 shows the shear force versus lateral
displacement of hysteresis loop of control specimen
and 4VX specimens. Figure 6 shows the skeleton
curve of both control specimen and 4VX specimen.
From the figures 4 and 5, the hysteresis capacity of
the 4VX specimen is behaved high when compare
to control specimen. The ultimate load
Figure 4.Load Deflection Curve of Control Specimen
Figure 5.Load Deflection Curve of 4VX Specimen
Figure 6.Skeleton Curve for various Specimens
was observed as 25.46KN to fail the control
specimen and for 4VX specimens required
30.32KN in the positive loading cycles and at the
negative loading cycles control specimen took 27.5
KN and 4VX specimen took about 30.317 kN, at
same time the ductility behavior of the 4VX
specimen is higher. It deflects up to 9.1 mm but
control specimen deflected only 8.4 mm at the stage
-40
-30
-20
-10
0
10
20
30
-2.00E+01 0.00E+00 2.00E+01 4.00E+01
LOA
D in
kN
DEFLECTION in mm
Control Specimen
-40
-30
-20
-10
0
10
20
30
-1.00E+01 -5.00E+00 0.00E+00 5.00E+00 1.00E+01
LOA
D i
n k
N
DEFLECTION in mm
4VX
-40
-20
0
20
40
-20 -10 0 10 20
LOA
D in
KN
DEFLECTION in mm
SKELETON CURVE
4VX
CONTROL
of failure. The permanent drift at the top the wall
was observed as 4.8 mm for the 4VX specimen and
the 5.2 mm for the Control specimen. It shows that
the permanent deformation of the control specimen
is high when comparing to the 4VX specimen.
Energy absorption Characteristics of the control
specimen at the earlier cycles of the loading, up to
the 8 cycle it shown good and the consecutive
cycles it gets reduced, But compare to 4VX
specimen up to 12 cycles it shown good and the
consecutive cycles it gets reduced. The stiffness of
the specimen were decreased when the 8th
cycle in
the control specimen and for 12th
cycle for the 4VX
specimen. The control specimen took 15 cycles for
the failure where 4VX specimen took 19 cycles for
the failure.
3.2. Cracking pattern
Figure 8 and 9 shows the crack pattern of the
control specimen and the 4VX specimen
accordingly. The crack was observed at the 8th
cycle for the control specimen and the 12th
cycle for
the 4VX specimen. The ultimate width of the
cracks for the control specimen is 3.2 mm and 2.8
mm for the 4VX specimen at the stage of the failure
cycles. The cracks where observed by the means of
crack width microscope. Starting from the crack
propagation itself that same crack is monitored and
the behavior of that crack was studied. The Control
specimens show the crack of 0.2mm at the 8th
cycle
and it is increased with the increased cycle. The
4VX specimens show the crack of 0.1mm at the
starting stage and it is increased with the increased
cycle. The diagonal cracks were observed at the last
three cycles for the control specimen where no
control cracks were observed in 4VX specimen.
The large no of primary and secondary cracks were
observed in the control specimen when compare to
the 4VX specimen.
4. Conclusions
The seismic behavior of the RC shear wall with
truss type detailing was investigated
experimentally. Based on the observation and the
results the following conclusion can be drawn. The
experimental observation showed that 4VX steel
truss type detailing had a beneficial effect on the
shear wall capacity and energy dissipating capacity
of RC shear wall. By adding X shaped bracing in
the vertical direction of this unconventional
detailing model was able to withstand more shear
force under cyclic loading and low amount of the
crack propagation and thereby trending the failure
mode to the flexural failure.
Figure 7. Crack pattern of Control specimen
Figure 8. Crack pattern of 4VX specimen
References
1. Hui Wen Tian, Yuan QiLi and Cheng Yu
(2015), ‘Testing of steel sheathed cold-formed steel
trussed shear walls’, Thin-Walled Structures,
vol.94, No.4, pp.280–292.
10. IS 456 (2000), ‘Plain and Reinforced
Concrete-Code of Practice’, Bureau of Indian
Standards, New Delhi.
2. Omar A. El Azizy, Marwan T. Shedid ,
Wael W. El Dakhakhni and Robert G. Drysdale
(2015), ‘Experimental evaluation of the seismic
performance of reinforced concrete structural walls
with different end configurations’, Engineering
Structures, vol.101, No.3, pp.246-263.
3. Konstantinos I. Christidis, Emmanouil
Vougioukas and Konstantinos G. Trezos (2016),
‘Strengthening of non-conforming RC shear walls
using different steel configurations’, Engineering
Structures, vol.124, No.5, pp.258–268.
4. Wenwu Lan, Jiaxing Ma , Bing Li (2015),
‘Seismic performance of steel–concrete composite
structural walls with internal bracings’, Journal of
Constructional Steel Research Vol.110, No.2,
pp.76–89.
5. Omar A. El Azizy, Marwan T. Shedid ,
Wael W. El Dakhakhni , Robert G. Drysdale
(2015), ‘Experimental evaluation of the seismic
performance of reinforced concrete structural walls
with different end configurations’, Engineering
Structures, Vol.101, No.4, pp.246-263.
6. Xiaodong Ji, Tongseng Leong, Jiaru Qian,
Wuhui Qi, Weibiao Yang (2016), Cyclic shear
behavior of composite walls with encased steel
braces, Engineering Structures, Vol.127, No.3,
pp.117-128.
7. Yuntian Wua, Wei Yang, Yan Xiao, F.
ASCE, F. ACI (2016), ‘Seismic behavior of high
strength concrete composite walls with embedded
steel truss’, Journal of Constructional Steel
Research, Vol.118, No.5, pp.180–193.
8. Yuntian Wu, Dao-yang Kang, Yeong Bin
Yang (2016), ‘Seismic performance of steel and
concrete composite shear walls with embedded
steel truss for use in high-rise buildings’,
Engineering Structures, Vol.125, No.2, pp.39–53.
9. IS 13920 (1993), ‘ Ductile detailing of
reinforced concrete structures subjected to seismic
forces’ Bureau of Indian Standards, New Delhi.