Seismic Analysis and Design of Hospital Building-libre

download Seismic Analysis and Design of Hospital Building-libre

of 29

Transcript of Seismic Analysis and Design of Hospital Building-libre

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    1/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    1

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED

    HOSPITAL BUILDING

    Submitted at the end of final semester by

    K.Aslam

    [Reg.No.11609103006]

    In partial fulfillment for the award of the degree of

    BACHELOR OF ENGINEERING

    IN

    CIVIL ENGINEERING

    SRI VENKATESHWARA COLLEGE OF ENGINEERING & TECHNOLOGY

    THIRUVALLUR

    ANNA UNIVERSITY: CHENNAI 600 025

    APRIL 2012

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    2/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    2

    CERTIFICATE

    This is to certify that the project report entitled

    “SEISMIC ANALYSIS AND DESIGN OF MULTI STROREYED HOSPITAL

     BUILDING” is t he bonafied project work done by K.ASLAM (Reg.No.11609103006) in

    partial fulfillment of the requirement for the award of Bachelor of Engineering Degree in

    Civil Engineering under Sri Venkateswara College of Engineering & Technology during

    the year 2011-2012.

    Internal Guide

    S.SANTHANA RAMAN,M.E,C.A.R(CSU)USA Mrs.GAYATRI PADHY,B.E

    Dean& Project Guide Head of the Department Department of Civil Engineering. Department of Civil Engineering 

    S.V.C.E.T. . S.V.C.E.T.

    External Guide

    Dr.S.JUSTIN

    Engineering Manager

    SDDH,

    EDRC, Larsen & Toubro,

    Chennai.

    Mr.UP.VIJAY Mr.M.RAMPRATHAP

    Assistant Engineering Manager, Assistant Engineering Manager,

    EDRC, Larsen & Toubro, EDRC, Larsen & Toubro,

    Chennai. Chennai. 

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    3/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    3

    ACKNOWLEDGEMENT

    I take this oppurtunity to thank Mr.Bikram K.Naik [HR Manager, EDRC Division] and

    Mr.Mukesh Kumar Singh [HR Manager P&OD] for giving me the oppurtunity to work with

    Larsen & Toubro.

    I thank Dr.S.Justin [Engineer Manager (SDDH),EDRC], Mr.UP.Vijay [Assitant Engineering

    Manager] and Mr.M.Ramprathap [Assistant Engineering Manager] without them this project

    would not have been possible. Their feedback, comments and suggestions were helpful

    throughout the entire work.

    I also thank all other Engineers of the Health and Leisure Division of B&F, L&T for guiding

    me throughtout the program.

    I thank Dr.Suresh Mohan Kumar M.Tech,Ph.D our Principal, for giving me the oppurtunity

    to work with Larsen & Toubro Limited and I thank Mr.S.Santhanaraman M.E,C.A.R (CSU)

    USA and Mrs.Gayatri Padhy,B.E. without them this project would not have been possible

    throughout the entire work.

    Last but not the least I thank my friends and family for their whole hearted support and

    cooperation.

    K.ASLAM

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    4/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    4

    ABSTRACT

    Industrial training is an essential in the development of the practical and professional skills

    required of an Engineer and as an aid to prospective employment undertaking the training in

    a reputed firm adds to the advantage. The training was done with Larsen & Toubro, Chennai.

    The work allotted during the Indutrial Training period was the Seismic Analysis and Design

    of multistoryed New Teaching Hospital block at Agartala one of the projects undertaken by

    L&T.

    Earthquake Engineering was developed a lot from the early days and seismically analysing

    the structures requires specialized explicit finite element analysis software,which divides the

    element into very small slices and models the actual physics. The seismic analysis of the

    proposed building was done in the software ETABS, version- 9.7, which is one of the most

    advanced software in the structural design field. The loads applied on the structure was based

    on IS:875(part I)-1987[dead load],IS:875(part II)-1987[live load], IS:875(part III)-1987[wind

    load], IS:1893-2000 [Earthquake load]. Scale factor is calculated from the design base shear

    (Vb) to the base shear calculated using fundamental time period (Ta).

    Once the analysis was completed all the structural components were designed according to

    Indian standard code IS:456-2000. Footing, columns, beams, slab, staircase and shear wallwere designed. Ductile detailing of the structural elements were done as per code IS:13920-

    1993.

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    5/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    5

    LIST OF CONTENTS PAGE NO.

    1.0 INTRODUCTION 1

    1.1 New Teaching Hospital Building 1

    1.2 Larsen & Toubro 2

    1.2.1 Vision and Mission 2

    2.0 FEATURES OF PROJECT 2

    3.0 INTRODUCTION TO ETABS 3

    3.1 Modeling Features 3

    3.2 Analysis Features 4

    4.0 LOAD CALCULATION 5

    4.1 General data 5

    4.2 Dead load 5

    4.2.1 Typical Floor slab 5

    4.2.2 Terrace Floor slab 5

    4.3 Live load 5

    4.4 Wall load 6

    4.4.1 Member load due to 230mm thick exterior wall 6

    4.4.2 Member load due to 100mm thick interior wall 6

    4.5 Static check for load combintion 6

    4.5.1 Plinth level 6

    4.5.2 Floor level 7

    4.5.3 Static check for dead and live load combination. 8

    4.6 Wind load calculation 9

    4.6.1 Basic wind speed 9

    4.6.2 Design wind speed 9

    4.6.3 Design wind pressure 9

    4.6.4 Wind force 10

    4.7 Seismic load calculation 13

    4.7.1 Zone factor 14

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    6/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    6

    4.7.2 Response reduction factor 14

    4.7.3 Importance factor 14

    4.7.4 Seismic weight 14

    4.7.5 Soil classification 15

    4.7.6 Seismic base shear calculation 16

    4.7.8 Analysis 17

    4.7.9 Scale factor calculation 18

    5.0 MODELLING AND ANALYSIS OF THE BUILDING 23

    5.1 Basic Grid system 23

    5.2 Define Geometry 23

    5.3 Define material Property 24

    5.4 Define frame section 24

    5.5 Define Wall or Slab section 25

    5.6 Define Diaphram 26

    5.7 Define Response Spectrum Function 26

    5.8 Response Spectrum Function 26

    5.9 Define Static load cases 26

    5.10 Define load combination 28

    5.11 Output 30

    6.0 DESIGN OF FOUNDATION 36

    6.1 General 36

    6.2 Design of Isolated footing 36

    6.3 Design of typical isolated footing 37

    6.3.1 Design Parameters 37

    6.3.2 Bending moment in X direction 38

    6.3.3 Bending moment in Y direction 39

    6.3.4 Check for one way shear 39

    6.3.5 Check for two way shear 39

    6.3.6 Transfer of forces at column base 40

    6.4 Foundation detailing 40

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    7/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    7

    7.0 COLUMN DESIGN 41

    7.1 General 41

    7.2 Column design 42

    7.2.1 Design Parameters 42

    7.2.2 Design of bending moment 42

    7.2.3 Reinforcement provided 43

    7.2.4 Design Parameters 43

    7.2.5 Design of bending moment 44

    7.2.6 Calculation of reinforcement 44

    7.3 Column detailing 45

    8.0 BEAM DESIGN 46

    8.1 General 46

    8.2 Beam design 47

    8.2.1 Design Parameters 47

    8.2.2 Bending moment calculation 47

    8.2.3 Shear Reinforcement 48

    8.2.4 Shear Reinforcement at mid span 48

    8.2.5 Design of Hanger bars 49

    8.2.6 Development Length 49

    8.2.7 Check for deflection 49

    8.3 Beam Detailing 50

    9.0 DESIGN OF SLAB 51

    9.1 Design of one way and two way slab 51

    9.2 Design of typical two way slab 53

    9.2.1 Design parameters 53

    9.2.2 Design of moments 53

    9.2.3 Reinforcement calculation 54

    9.2.4 Check for depth 54

    9.2.5 Check for shear 54

    9.2.6 Check for deflection 55

    9.3 Reinforcement details 55

    9.4 Slab detailing 56

    10. DESIGN OF STAIRCASE 57

    10.1 General 57

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    8/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    8

    10.2 Design parameters 59

    10.3 Load acting on stairs 59

    10.4 Design of waist slab type staircase 59

    10.5 Reinforcement provided 60

    10.6 Staircase detailing 60

    11. DESIGN OF SHEARWALL 61

    11.1 General 61

    11.2 Wall dimensions 61

    11.3 Check for boundary element 62

    11.4 Fixing boundary element 62

    11.5 Determination of minimum steel 62

    11.6 Shear reinforcement 63

    11.7 Flexural strength 63

    11.8 Transverse reinforcement 64

    11.9 Shear wall detailing 64

    12. Conclusion 65

    13. References 66

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    9/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    9

    LIST OF SYMBOLS

    Asc = Area of Compression Steel

    Ast  = Area of tension steel

    A sv = Area of shear reinforcement

    Ag = Gross area of concrete

    b = Breadth of the section

    B.M = Bending Moment

    C/C = Center to Center

    d = Effective depth

    d’  = Depth of compression reinforcement.

    DL = Dead load

    D = Over all depth

    Df   = Depth of flange

    EL = Earthquake load

    f ck   = Characteristic Strength of concrete

    f y  = Characteristic Strength of steel

    I = Importance Factor (IS: 1893-1987)

    L = Clear Span

    L.L = Live Load

    k 1  = Modification Factor (IS: 456-2000)

    K1  = Risk Factor (IS 875:-1987) part III

    K2  = Topography factor (IS 875-1987) part III

    Ld  = Development Length

    Leff   = Effective length

    Lx = Length of span in x direction

    Ly  = Length of span in x direction

    M.F = Modification factor

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    10/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    10

    M.R = Moment of Resistance

    Mu = Ultimate Moment

    Mu limit = Limiting moment of reinforcement of a section

    Pu  = Axial load on a compression member

    Pt  = Percentage of reinforcement

    R.C.C = Reinforcement cement concrete

    R = Response Reduction factor (IS: 1893-1987) part-III

    S = Spacing of reinforcement

    S.F = Shear force

    T = Torsion moment

    Vu = Shear force

    WL = Wind load

    Zp  = Plastic section modulus (IS: 456-2000)

    Z = Zone factor (IS: 1893-1987)-part III

    τc  = Critical shear stress in concrete

    τv  = Nominal shear stress in concrete

    φ  = Nominal diameter of bars 

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    11/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    11

    LIST OF TABLES PAGE NO.

    1.  Value of Topography Factor K2  11 

    2.  Wind load calculation 11

    3.  Wind forces from Analysis (X Direction) 12

    4.  Wind forces from Analysis (Y Direction) 12

    5.  Seismic zone 14

    6.  Base shear in X-direction using ETABS model 17

    7.  Base shear in Y-direction using ETABS model 18

    8.  Base shear in X-direction using ETABS model 19

    9.  Base shear in Y-direction using ETABS model 20

    10. Period Vs Sa/g 20

    11. Seismic weight output 22

    12. Load combination 28

    13. Moment coefficients 54

    14. Reinforcement provided 54

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    12/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    12

    LIST OF FIGURES PAGE NO.

    1.  Location map 01

    2.  Panel drawing 07

    3.  Axial load from Analysis 09

    4.  Plan & Elevation 10

    5.  Soil classification 15

    6.  Response spectra for soft soil 22

    7.  The new model initialization form. 23

    8.  Building Plan Grid System and Storey Data Definition 23

    9.  Material property data form 24

    10. Define Frame Properties form 24

    11.  Section properties and Reinforcement details. 25

    12. Define wall or slab section 25

    13. Define Diaphragms 26

    14. Define response spectrum function. 26

    15. Response spectrum function graph 27

    16. Define static load case 27

    17. 

    Define load combinations 28

    18. Model output 30

    19. Bending moment diagram from Analysis 31

    20. Shear force diagram from Analysis 32

    21. Diaphragm 33

    22. 

    Plan showing slab details 34

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    13/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    13

    23. Plan showing beam and column ID 35

    24. Types of footing 36

    25. Pressure diagram 38

    26. Footing detailing 40

    27. Types of column 41

    28. Column detailing 45

    29. Beam detailing 50

    30. 

    Types of Slab 51

    31. Load distribution in two way slab 53

    32. R.C Details of Slabs 55

    33. Slab detailing 56

    34. Types of staircase 58

    35. 

    Detailing of staircase 60

    36. Shear wall diagram 61

    37. Shear wall detailing. 64

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    14/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    14

    1.0 INTRODUCTION 

    1.1 NEW TEACHING HOSPITAL BUILDING:

    Figure1-location map

    The New teaching hospital block located at Agartala. The total build up area of the hospital

    building is 12596.67 square meter and having five floors (G+5). The Hospital building

    consists of various divisions like Ortho ward,Orthopedic ward, Opthamal ward, ENT ward,

    major and minor operation theaters, out patient ward, seminar halls for medical students,

    scanning and X-ray centre and medicine store room etc. The building located at seismic

    prone zone (zone factor V). The building has designed according to the Earthquake resistant

    considerations.

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    15/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    15

    1.2 LARSEN & TOUBRO LIMITED

    1.2.1 Vision and Mission

    The design and execution of New teaching hospital block were awarded to Larsen & Toubro

    Limited (L&T) is an Indian multinational conglomerate company headquarted in Mumbai,

    India. The company has four main sectors; Technology, Engineering, Construction and

    Manufacturing. L&T has an international presence with a global spread of office and

    factories further, supplemented by a comprehensive marketing and distribution network. The

    firm has more than 60 units in 25 countries. Domestic business with in India dominates, but

    the company steadily growing it’s global operations with a focus on China and Middle East.The company was founded in Mumbai in 1938 by Danish Engineers, Mr.Henning Hlock-

    Larsen and Seren Kristian Toubro. In 1944 ECC was incorporated by the partners; presently

    ECC(Engineering Construction & Contracts Division of L&T) is the largest contruction

    organization. L&T covers various disciplines of construction- Civil, Mechanical,

    Instrumentation and Electrical.

    The design wing of L&T, EDRC division provides consultancy design and total Engineering

    solutions to customers. It carries out both residential and commercial projects. The training

    work was carried out in the EDRC division of L&T.

    2.0 FEATURES OF PROJECT

    The project consists of Seismic Analysis and Design of New Teaching Hospital block (NTH)

    located at Agartala. The architectural drawings of NTH were done in the Auto CAD 2010 and

    the structural modeling was done by using ETABS software. The concrete mix used for all

    the structural member is M 30 and steel is Fe 500. The load combination were taken to obtain

    the maximum design loads, bending moments and shear forces. The structural element

    designs were carried as per IS:456-2000 for the load combinations. Earthquake resistant

    design detailing of the structure was done as per IS:13920-1993.

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    16/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    16

    3.0 INTRODUCTION TO ETABS:

    ETABS is sophisticated software for analysis and design program developed specifically for

    buildings systems. ETABS version-9.7 features an in intuitive and powerful graphical

    interface coupled with unmatched modeling, analytical, and design procedures, all integrated

    using common database. Although quick and easy for simple structures, ETABS can also

    handle the largest and most complex building models, including a wide range of nonlinear

    behaviors, making it the tool of choice for structural engineers in the building industry.

    3.1 MODELING FEATURES

    The ETABS building is idealized as an assemblage of area, line and point objects. Those

    objects are used to represent wall, floor, column, beam, brace and link / spring physical

    members. The basic frame geometry is defined with reference to a simple three-dimensional

    grid system. With relatively simple modeling techniques, very complex framing situations

    may be considered.

    The building may be unsymmetrical and non-regulator in plan, Torsional behavior of the

    floors and understory compatibility of the floors are accurately reflected in the results. Thesolution enforces complete three-dimensional displacement compatibility, making it possible

    to capture tubular effects associated with the behavior of tall structures having relatively

    closely spaced columns.

    Semi-rigid floor diaphragms may be modeled to capture the effects of in plane floor

    deformations. Floor objective may span between adjacent levels to create sloped floors

    (ramps), which can be useful for modeling parking garage structures.

    3.2 ANALYSIS FEATURES

    Static analysis for user specified vertical and lateral floor on story loads are possible. If floor

    elements with plate bending capability are modeled, vertical uniform loads on the floor are

    transferred to the beams and columns through bending of the floor elements.

    The program can automatically generate lateral wind and seismic load patterns to meet the

    requirements of various building codes. Three dimensional mode shapes and frequencies,

    model participation factors, direction factors and participating mass percentage are evaluated

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    17/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    17

    using Eigen vector or Ritz-vector analysis-Delta analysis effects may be included with static

    or dynamic analysis.

    Response spectrum analysis, linear time history analysis, nonlinear analysis and static

    nonlinear analysis are possible. The static nonlinear capabilities also allow you to perform

    incremental construction analysis, so that forces that arise as a result of construction sequence

    are included. Results from the various static load cases may be combined with each other or

    with the results from the dynamic response dynamic response spectrum or time history

    method.

    Output may be viewed graphically, displayed in tabular output, the types of output include

    reactions, member forces, mode shapes, participation factors, static and dynamic story

    displacements and story shears inter story drifts and joint displacements, time history traces

    and more.

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    18/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    18

    4.0 LOAD CALCULATIONS 

    4.1 GENERAL DATA

    Structure = G + 5

    Floor height ( First Floor to Fifth Floor) = 4.0 m

    Grade of concrete (for all structural elements) = M 30

    Unit weight of concrete = 25kN/m3 

    Unit weight of cement mortar = 24kN/m3

     

    Unit weight of water = 10kN/m3

    Unit weight of Brick = 20kN/m3

    4.2 DEAD LOAD (As per IS 875 part I) 

    4.2.1 TYPICAL FLOOR SLAB:

    Self-weight of slab (150mm thick) = 3.75 kN/m2 

    Floor Finish = 1.5 kN/m2 

    Total Load = 5.25 kN/m2 

    4.2.2 TERRACE FLOOR SLAB:

    Self-weight of slab (150mm thick) = 3.75 kN/m2 

    Terrace (Roof finish + Water proofing) = 3.20 kN/m2 

    Total Load = 6.95 kN/ m2 

    4.3 LIVE LOAD (As per IS 875 part II)

    Living room, Toilet & Bath room = 3.00 kN/m2 

    Recreation Room and Pantry = 3.00 kN/m2 

    Store and Laundry = 4.00 kN/m2 

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    19/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    19

    Corridors & stair case = 4.00 kN/m2

    Terrace Floor = 1.5 kN/m2 

    ICU = 3.00 kN/m2 

    Lounge = 3.00 kN/m2 

    Nurse station = 3.00 kN/m2 

    Operation Theatres = 3.00 kN/m2 

    Dining room = 4.00 kN/m2 

    Waiting room = 4.00 kN/m2

     

    4.4 WALL LOAD

    4.4.1 Member load due to 230mm thick exterior wall

    Wall thickness = 230 mm

    Floor Height = 4000 mm

    Beam Depth = 750 mm

    (0.23 × (4-0.75) × 20) = 15kN/m

    4.4.2 Member load due to 230mm thick interior wall

    Wall thickness = 115 mm

    Floor Height = 4000 mm

    Beam Depth = 750 mm

    (0.115 × (4-0.75) × 20 = 7.5 kN/m

    4.5 STATIC CHECK FOR LOAD COMBINATION (D.L + L.L)

    4.5.1 PLINTH LEVEL

    Beam size = 300×750mm

    Self-weight of beam (B1) = 25×0.75 ×0.3×3.42

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    20/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    20

    = 19.24kN/m

    Self-weight of beam (B2) = 25× 0.75 ×0.3×4.28

    = 24.08kN/m

    Self-weight of beam (B3) = 25× 0.75 ×0.3×3.60

    = 20.25kN/m

    Self-weight of beam (B4) = 25× 0.75 ×0.3×4.95

    = 27.85kN/m

    Wall load on beam (B2, B3 & B4) = (0.115×(4-0.75)×20

    = 7.5kN/m

    Column size = 750×750mm

    Self-weight of column C1 =25× (4-0.75) ×0.75×0.75

    = 45.70kN

    Total Load at Plinth level = 159.62 kN/m

    .

    Figure 2-Panel drawing

    4.5.2 FLOOR LEVEL

    Beam size = 300×750mm

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    21/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    21

    Self-weight of beam (B1) = 25× 0.75 ×0.3×3.42

    = 19.24kN/m

    Self-weight of beam (B2) = 25× 0.75×0.3×4.28

    = 24.08kN/m

    Self-weight of beam (B3) = 25× 0.75 ×0.3×3.60

    = 20.25kN/m

    Self-weight of beam (B4) = 25× 0.75 ×0.3×4.95

    = 27.85kN/m

    Self-weight of Slab = 25× 0.15×9.23×7.02

    = 242.98kN/m

    Column size = 750×750mm

    Self-weight of column =25× (4-0.75) ×0.75×0.75

    = 45.70kN

    Wall load on beam (B2, B3 & B4) = 0.115×(4-0.75) ×20

    = 7.5kN/m

    Live load on Slab = 5.5×9.23×7.02

    = 356.37kN/m2 

    4.5.3 STATIC CHECK FOR DEAD AND LIVE LOAD COMBINATION

    Total dead load = 2417.72kN/m

    Total dead Imposed load = 157.50kN/m

    Total live load (Floors+ Terrace) = 2138.22kN/m

    Total load = 4713.44 kN/m

    Axial load from Analysis = 4737.58 kN/m

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    22/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    22

    Figure 3- Axial load from software

    4.6 WIND LOAD CALCULATION

    Wind is air in motion relative to the surface of the earth. The primary cause of wind is traced

    to earth’s rotation and differences in terrestrial radiation. The radiation effects are primarily

    responsible for convection either upwards or downwards. The wind generally blows

    horizontal to the ground at high wind speeds. Since vertical components of atmospheric

    motion are relatively small, the term ‘wind’ denotes almost exclusively the horizontal wind,

    vertical winds are always identified as such. The wind speed is assessed with the aid of

    anemometers or anemographs.

    4.6.1BASIC WIND SPEED:

    Basic wind speed is based on peak gust velocity averaged over a short time interval of about

    three seconds and corresponds to mean heights above ground level in an open terrain. Basic

    wind speed given in figure1 in IS 875(part):1987.

    4.6.2 DESIGN WIND SPEED:

    The basic wind speed for any site is obtained from figure and shall be modified to include the

    following effects to get design wind velocity at any height shall be modified to include the

    following effects to get design wind velocity at any height(Vz) for the chosen structure:

    Vz = Vb× k 1×k 2× k 3 

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    23/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    23

    The suggested life period to be assumed in design and the corresponding k 1  factors for

    different structures for different class of structures given in table 1, IS 875(part):1987. k 2 is

    the terrain, Height and structure size factor given in table 2, IS 875(part):1987. k 3 is the

    topography factor given in table 3, IS 875(part):1987.

    4.6.3 DESIGN WIND PRESSURE:

    The design wind pressure at any height above mean ground level shall be obtained by the

    following relationship between wind pressure and wind velocity

    Pz = 0.6×Vz2 

    4.6.4 WIND FORCES:

    The value of force coefficient apply to the building or structure as a whole and multiplied by

    effective frontal area of the building by design wind pressure, Pz gives the total wind load on

    that particular building or structure. The force coefficients are given in two mutually

    perpendicular directions relative to reference axis of the structural member. They are

    designed as Cpn and Cpt, give the normal and transverse, respectively to the reference plane.

    Fn = Cpn× Pz×l×b

    Ft= Cpt × Pz× l×b

    Basic wind speed at Agartala (As per IS 875-1987) = 50km/s (Vb)

    Terrain category (clause 5.3.2.1) = 2

    Building class (B=36m, W=53.0) (clause 5.3.2.2) = C

    Risk coefficient (K1) (Assume 100 years Life period) = 1.08

    Topography factor (K3)(clause 5.3.2.3) = 1

    a=53.0m a=53.0m

    b=36m h=28.0m

    Fig4.A- Plan Fig 4.B- Elevation

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    24/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    24

    In X-direction (a/b) = 1.47 In Y-direction (b/a) = 0.68

    In X-direction (h/b) = 0.78 In Y-direction (h/a) = 0.53

    Width of building in X-direction = 53.0m

    Width of building in Y-direction = 36m

    1. Value of Topography Factor (k 2) - Table 1

    Force coefficient in X-direction = 1.075(from code IS 875-1987(part3))

    Force coefficient in Y-direction = 1.20(from code IS 875-1987(part 3))

    Design speed Vz = Vb× K1 × K2 × K3 

    2. Wind load calculation-Table 2

    Story Height(m) K 2  Vz(km/s) Pz=0.6Vz2(kN)

    Load X in

    direction(kN)

    Load in Y

    direction(kN)

    FIRST 4.0 0.930 50.22 1.513 351.32 577.36

    SECOND 8.0 0.930 50.22 1.513 234.21 384.91

    THIRD 12.0 0.950 51.30 1.579 244.43 401.69

    FOURTH 16.0 0.979 52.87 1.677 259.60 426.63

    FIFTH 20.0 1.000 54.00 1.749 270.75 444.95

    TERRACE 24.0 1.016 54.86 1.805 139.71 229.60

    Total 1500.02 2465.14

    Height(m) K2 

    10 0.93

    15 0.9720 1.00

    30 1.04

    50 1.10

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    25/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    25

    3. Wind forces from Analysis – Table 3

    Story Point Load FX

    (kN)

    FY

    (kN)

    FZ

    (kN)

    MX

    (kN-m)

    MY

    (kN-m)

    MZ

    (kN-m)

    BASE 1 WINDPX -3.94 -0.36 -11.44 0.304 -15.199 0.071

    BASE 3 WINDPX -5.17 0.35 1.63 -1.013 -16.898 -0.036

    BASE 58 WINDPX -0.22 -7.95 -30.13 0.341 -0.544 0.041

    BASE 59 WINDPX -0.35 10.82 42.97 -0.494 -0.649 0.05

    BASE 96 WINDPX -6.44 -0.43 119.41 1.174 -18.245 0.121

    BASE 115 WINDPX -6.22 0.15 -13.46 -0.426 -19.163 -0.216

    BASE 379 WINDPX -27.28 -0.03 -107.35 0.097 -2.789 0

    BASE 380 WINDPX -27.92 0 -33.24 0.012 -2.75 0

    BASE 184 WINDPX -4.39 -0.13 -1.19 0.179 -0.241 -0.001

    BASE 191 WINDPX 3.41 -0.67 -16.6 0.358 -0.051 0.007

    BASE 200 WINDPX -3.12 0.06 -2.57 0.054 -0.102 0.002

    BASE 201 WINDPX 4.55 -0.78 23.06 0.423 -0.029 -0.007

    Summation WINDPX 1500.02

    4. Wind forces from software-Table 4

    Story Point Load FX

    (kN)

    FY

    (kN)

    FZ

    (kN)

    MX

    (kN-m)

    MY

    (kN-m)

    MZ

    (kN-m)

    BASE 1 WINDPY -1.01 -6.36 -33.52 23.774 -3.106 -0.198

    BASE 3 WINDPY -1.36 -9.92 -34.13 31.666 -3.66 -0.205

    BASE 5 WINDPY -1.94 -6.61 -39.98 25.27 -4.641 -0.171

    BASE 73 WINDPY -18.29 -0.3 -62.8 0.695 -0.976 -0.097

    BASE 74 WINDPY 5.39 -65.76 -255.22 6.363 -0.504 0.21

    BASE 117 WINDPY -0.6 -2.1 -224.58 0 0 0

    BASE 119 WINDPY 0.75 -2.38 -229.76 0 0 0

    BASE 374 WINDPY 20.31 -0.44 94.16 1.313 1.667 0

    BASE 375 WINDPY 20.38 -0.46 105.38 1.36 1.582 0.001

    BASE 197 WINDPY 2.35 0.3 -4.6 0.196 0.157 -0.002

    BASE 199 WINDPY -19.47 -1.77 31.28 0.924 -0.613 0.034

    BASE 200 WINDPY -3.02 0.32 -5.15 0.212 -0.177 0.003

    BASE 201 WINDPY 14.03 -2.17 77.89 1.349 0.306 -0.02

    Summation WINDPY 2465.14

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    26/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    26

    4.7 SEISMIC LOAD CALCULATION (Based on code IS 1893-2002)

    During an earthquake, ground motions develop in a random manner both horizontally and

    vertically in all directions radiating from the epicenter. The ground motions develop

    vibrations in the structure inducing inertial forces on them. Hence structures located in

    seismic zones should be suitably designed and detailed to ensure strength, serviceability and

    stability with acceptable levels of safety under seismic forces.

    The satisfactory performance of a large number of reinforced concrete structures subject to

    severe earthquake in various parts of the world has demonstrated that it is possible to design

    structures to successfully withstand the destructive effects of major earthquakes.

    The Indian standard codes IS: 1893-1984 and IS: 13920-1993 have specified the minimum

    design requirements of earthquake resistant design probability of occurrence of earthquakes,

    the characteristics of the structure and the foundation and the acceptable magnitude of

    damage.

    Determination of design earthquake forces is computed by the following methods,

    1)  Equivalent static lateral loading.

    2) 

    Dynamic Analysis.

    In the first method, different partial safety factors are applied to dead, live, wind earthquake

    forces to arrive at the design ultimate load. In the IS: 456-2000 code, while considering

    earthquake effects, wind loads assuming that both severe wind and earthquake do not act

    simultaneously. The American and Australian code recommendations are similar but with

    different partial safety factors.

    The dynamic analysis involves the rigorous analysis of the structural system by studying the

    dynamic response of the structure by considering the total response in terms of component

    modal responses.

    4.7.1 ZONE FACTOR (Z):

      The values of peak ground acceleration given in units ‘g’ for the maximum

    considered earthquake.

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    27/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    27

      The value of (Z/2) corresponds to design basis earthquake damage control in limit

    state.

      Based on history of seismic activities seism tectonic understanding the entire country

    has been divided in to four zones. The zone factor from table 2(IS 1893:2002)

    Seismic zone II III IV V

    Seismic Intensity Low Moderate Severe Very severe

    Z 0.10 0.16 0.24 0.36

    Zone factor values- Table 5 

    4.7.2 RESPONSE REDUCTION FACTOR (R):

      R is the response reduction factor and controls the permitted damage in design basis

    earthquake.

      The minimum value of R is 3 and maximum is 5 however to use higher values of R

    special ductile detailing requirements are must and the designer is accepting more

    damages but in the controlled manner. The Response reduction factor from table 7(IS

    1893:2002)

    4.7.3 IMPORTANCE FACTOR (I):

      I is the importance factor and permitted damage could be reduced by setting the value

    of I more than ‘1’. 

      For the buildings like ‘HOSPITALS’, communication and community buildings the

    value is 1.5 from table 6 (IS 1893:2002).

    4.7.4 SEISMIC WEIGHT (W): 

      Seismic weight of the building is measured in Newton. Seismic weight includes the

    dead loads (that of floor, slabs, finishes, columns, beams, water tanks, permanent

    machines etc.

      Seismic weight includes only a part of Imposed loads, for example 25% to 50% of

    imposed loads for buildings from table 8 (IS 1893:2002).

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    28/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    28

    4.7.5 SOIL CLASSIFICATION:

      Sa/g is the lateral acceleration to be established in m/s2. For 5 present of damping

    three different types of curves are recommended in IS 1893:2002 for different

    stiffness of supporting media-Rock, Medium soil and Soft soil.

      The classification of soil is based on the average shear velocity for 30m of rock or soil

    layers or based on average Standard Penetration Test (SPT) values for top 30m.

    Fi

    Figure 5- soil classification graph

    Zone factor of the building (Z) = 0.36 (Zone V)

    Importance of the building (I) = 1.5 (Post Earth quake service needed)

    Response reduction factor (R) = 5 (Ductile shear walls with SMRF system)

    Soil type = Soft soil

    Width of building in X-direction = 53.0m

    Width of building in Y-direction = 36m

    Height of the building = 28m

    Seismic weight of the building = 177309kN

    0

    0.5

    1

    1.5

    2

    2.5

    3

    0 0.5 1 1.5 2 2.5 3 3.5 4

    Period (s)

       S  p  e  c   t  r  a   l   A  c  c  e   l  e  r  a   t   i  o  n   C  o  e   f   f   i  c   i

      e  n   t   (   S  a   /  g   )

     

    Type I (Rock, or Hard Soil) 

    Type II (Medium Soil) 

    Type III (Soft Soil) 

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    29/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    29

    4.7.6 SEISMIC BASESHEAR CALCULATION:

    The design base shear is the sum of lateral forces applied at all levels that are finally

    transferred to the ground.

    Vb = Ah× W

    Ah  = (ZI/2R)(Sa/ g)

    Fundamental Natural Time period (without infill)

    Ta = 0.075(h) 0.75

     

    Ta (X-Direction) = 0.913

    Ta (Y-Direction) = 0.913

    Sa/g = 1.67/T = 1.83

    Ah (X-Direction) = 0.099

    Ah (Y-Direction) = 0.099

    Fundamental Natural Time period (with infill)

    Ta = (0.09×h)/√d 

    Ta (X-Direction) = 0.420 & Ta (Y-Direction) = 0.346

    Sa/g = 2.5

    Ah (X-Direction) = 0.135 &Ah (Y-Direction) = 0.135

    Base shear (without infill)

    Base shear (X direction) (Ah×W) = 17554kN

    Base shear (Y direction) (Ah×W) = 17554kN

    Base shear (with infill)

    Base shear (X direction) (Ah×W) = 23937kN

    Base shear (Y direction)(Ah×W) = 23937kN

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    30/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    30

    Average base shear

    Base shear in X-direction using Code = 20746kN

    Base shear in Y-direction using Code = 20746kN

    Base shear in X-direction using ETABS model = 6760kN

    Base shear in Y-direction using ETABS model = 6173.94kN

    4.7.7 ANALYSIS 

    Analysis options are set before the analysis, the analysis is performed with a scale factor 1.

    The number of modes is initially set as 1.5 after anlysis. If the cumulative mass participation

    factor is less than 95 percentage, then it is modified accordingly with base shear values

    obtained for the earth quake load case the new scale factor is calculated and again the model

    is analysed for the new scale factor. It can be observed that the base shear value calculated

    from the code and by the software with the new scale factor are the same.

    6. Base shear in X-direction using ETABS model- Table 6

    Story Point Load FX

    (kN) 

    FY

    (kN) 

    FZ

    (kN) 

    MX

    (kN-m) 

    MY

    (kN-m) 

    MZ

    (kN-m) 

    BASE 1 SPECX 21.12 6.06 51.23 23.359 78.266 0.911

    BASE 3 SPECX 26.97 8.54 30.56 25.089 86.532 1.435

    BASE 5 SPECX 29.62 3.71 63.14 11.368 90.891 1.676

    BASE 7 SPECX 161.37 34.86 772.61 1.607 14.971 0.587

    BASE 8 SPECX 190.16 4.52 19.77 0.66 20.901 0.464

    BASE 9 SPECX 161.54 29.35 759.54 1.607 15.034 0.604

    BASE 62 SPECX 36.09 4.51 13.19 12.545 100.706 1.788

    BASE 66 SPECX 10.92 1.08 12.92 0 0 0

    BASE 115 SPECX 26.77 4.34 63.2 12.201 80.561 2.515

    BASE 1591 SPECX 0.11 6.7 0.93 0 0 0

    BASE 1592 SPECX 0.82 6.79 5.12 0 0 0

    BASE 1594 SPECX 2.23 7.86 15.27 0 0 0

    BASE 1595 SPECX 0.08 5.91 11.84 0 0 0

    Sum 6760

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    31/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    31

    7.Base shear in Y-direction using ETABS model- Table 7

    Story Point Load FX

    (kN) 

    FY

    (kN) 

    FZ

    (kN) 

    MX

    (kN-m) 

    MY

    (kN-m) 

    MZ

    (kN-m) 

    BASE 1 SPECY 5.67 14.41 91.79 52.89 17.692 1.018

    BASE 3 SPECY 6.92 25.76 92.27 77.876 19.551 2.137

    BASE 5 SPECY 8.2 18.87 118.39 65.448 21.629 1.569

    BASE 7 SPECY 66.6 69.75 520.95 6.717 4.599 0.125

    BASE 159 SPECY 0.34 39.45 118.78 5.311 0.793 0.009

    BASE 160 SPECY 0.15 68.93 307.44 6.871 0.433 0.001

    BASE 172 SPECY 11.22 0.16 77.79 0 0 0

    BASE 174 SPECY 60.13 0.3 402.37 0 0 0

    BASE 1587 SPECY 0.19 105.15 76.18 0 0 0

    BASE 1588 SPECY 0.1 107.69 219.67 0 0 0

    BASE 1591 SPECY 0.01 54.74 65.87 0 0 0

    BASE 1592 SPECY 0.2 65.62 205.77 0 0 0

    BASE 1594 SPECY 0.47 98.15 299.42 0 0 0

    BASE 1595 SPECY 0.03 46.88 222.45 0 0 0

    Sum 6173.94

    4.7.8 SCALE FACTOR CALCULATION

    Summation of support reaction gives the seismic weight of the building. Base shear in

    X direction calculated as per the code. ETABS did the dynamic analysis and total base shear

    in X and Y direction are found from results. The ratio of base shear obtained from code to

    that obtained from dynamic analysis gives the shear force in X and Y direction. Since thespectra value for different time period is calculated manually the base shear values might not

    be the same values obtained from manual calculations. Thus the new scale factor is calculated

    and the structure reanalyzed to obtain the new base shear values.

    Base shear (from Analysis)

    Base shear in X-direction using Code = 20746kN

    Base shear in Y-direction using Code = 20746kN

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    32/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    32

    Base shear in X-direction using ETABS model = 6760kN

    Base shear in Y-direction using ETABS model = 6173.94kN

    Scale Factor (Vbx/ Vbx') = 3.07

    Scale Factor (Vby/ Vby') = 3.36

    8. Base shear in X-direction using ETABS model-Table 8 

    Story Point Load FX

    (kN) 

    FY

    (kN) 

    FZ

    (kN) 

    MX

    (kN-m) 

    MY

    (kN-m) 

    MZ

    (kN-m) 

    BASE 1 SPECX 64.85 18.61 157.27 71.713 240.277 2.796

    BASE 3 SPECX 82.81 26.2 93.83 77.024 265.653 4.404

    BASE 5 SPECX 90.92 11.39 193.85 34.901 279.036 5.146

    BASE 7 SPECX 495.42 107.03 2371.91 4.934 45.96 1.803

    BASE 115 SPECX 82.19 13.33 194.02 37.458 247.321 7.72

    BASE 117 SPECX 21.32 6.37 714.21 0 0 0

    BASE 119 SPECX 23.94 6.78 724.44 0 0 0

    BASE 121 SPECX 13.81 5.94 40.5 0 0 0

    BASE 442 SPECX 340.62 9.65 1323.44 8.414 34.379 0.113

    BASE 1587 SPECX 0.81 99.15 997.9 0 0 0

    BASE 1588 SPECX 0.68 87.3 1162.35 0 0 0

    BASE 1591 SPECX 0.32 20.57 2.86 0 0 0

    BASE 1592 SPECX 2.52 20.84 15.73 0 0 0

    BASE 1594 SPECX 6.84 24.14 46.89 0 0 0

    BASE 1595 SPECX 0.26 18.13 36.35 0 0 0

    Sum 20753.07

    9. Base shear in Y-direction using ETABS model-Table 9

    Story Point Load FX

    (kN)

    FY

    (kN)

    FZ

    (kN)

    MX

    (kN-m)

    MY

    (kN-m)

    MZ

    (kN-m)

    BASE 1 SPECY 19.05 48.43 308.4 177.711 59.445 3.419

    BASE 3 SPECY 23.25 86.57 310.02 261.662 65.691 7.179

    BASE 5 SPECY 27.56 63.42 397.8 219.907 72.672 5.271

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    33/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    33

    BASE 7 SPECY 223.79 234.38 1750.39 22.57 15.453 0.422

    BASE 119 SPECY 10.08 20.21 2062.4 0 0 0

    BASE 121 SPECY 4.34 22.2 24.92 0 0 0

    BASE 123 SPECY 2.91 62.47 11.13 156.838 5.821 0.665

    BASE 440 SPECY 210.17 7.31 1056.86 14.678 17.001 0.01

    BASE 442 SPECY 216.26 17.22 1617.36 21.921 16.802 0.136

    BASE 1592 SPECY 0.67 220.5 691.38 0 0 0

    BASE 1594 SPECY 1.58 329.78 1006.05 0 0 0

    BASE 1595 SPECY 0.09 157.52 747.42 0 0 0

    Sum 20744.37

    Base shear in X-direction using Code = 20746 kN

    Base shear in Y-direction using Code = 20746 kN

    Base shear in X-direction using ETABS model = 20753.07 kN

    Base shear in Y-direction using ETABS model = 20744.37 kN

    10. Period Vs Sa/g- Table 10 

    Period

    (seconds) Sa /g

    Acceleration

    (m2 /s)

    0 1.000 0.530

    0.1 2.500 1.324

    0.2 2.500 1.324

    0.3 2.500 1.324

    0.4 4.175 2.212

    0.5 3.340 1.769

    0.6 2.783 1.474

    0.7 2.386 1.264

    0.8 2.088 1.106

    0.9 1.856 0.983

    1 1.670 0.885

    1.1 1.518 0.804

    1.2 1.392 0.737

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    34/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    34

    1.3 1.285 0.681

    1.4 1.193 0.632

    1.5 1.113 0.590

    1.6 1.044 0.5531.7 0.982 0.520

    1.8 0.928 0.491

    1.9 0.879 0.466

    2 0.835 0.442

    2.1 0.795 0.421

    2.2 0.759 0.402

    2.3 0.726 0.3852.4 0.696 0.369

    2.5 0.668 0.354

    2.6 0.642 0.340

    2.7 0.619 0.328

    2.8 0.596 0.316

    2.9 0.576 0.305

    3 0.557 0.2953.1 0.539 0.285

    3.2 0.522 0.276

    3.3 0.506 0.268

    3.4 0.491 0.260

    3.5 0.477 0.253

    3.6 0.464 0.246

    3.7 0.451 0.2393.8 0.439 0.233

    3.9 0.428 0.227

    4 0.418 0.221

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    35/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    35

    Figure 6-Response spectra for Soft soil sites

    11. Seismic weight output-Table 11

    Story Point Load FX

    (kN)

    FY

    (kN)

    FZ

    (kN)

    MX

    (kN-m)

    MY

    (kN-m)

    MZ

    (kN-m)

    BASE 1 SISWT 27.65 21.32 2497.5 -34.428 42.726 0.476

    BASE 3 SISWT 6.31 19.1 4190.33 -33.679 12.518 -0.08

    BASE 5 SISWT 0.11 19.9 3577.2 -33.288 3.005 0.052

    BASE 72 SISWT -17.8 -13.2 2293.75 19.13 -29.645 -0.359

    BASE 73 SISWT 55.84 -1.31 243.8 1.129 2.512 -0.173

    BASE 74 SISWT -57.53 62.27 545.42 -4.294 -3.983 0.017

    BASE 148 SISWT -13.74 -31.27 3478.73 54.117 -21.508 0.292

    BASE 149 SISWT -15.04 -14.49 1985.17 20.963 -23.614 0.588

    BASE 410 SISWT 21.85 53.21 477.07 -2.793 2.787 -0.171

    BASE 416 SISWT -0.1 22.94 277.04 1.069 0.413 -0.059

    BASE 198 SISWT 34.07 -1.58 56.5 0.839 1.065 -0.028

    BASE 199 SISWT -33.99 -1.54 56.36 0.832 -1.057 0.028

    BASE 200 SISWT -7.72 0.22 -8.62 0.142 -0.455 0

    Sum 177309.1

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    36/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    36

    5.0 MODELING AND ANALYSIS OF THE BUILDING

    The primary purpose of structural analysis in building structure is to establish the distribution

    of internal forces and moment over the whole or part of the structure and to identify the

    critical design conditions at all sections the geometry is commonly idealised by considering

    the structure to make up of linear elements. Here the structural analysis is carried out by

    ETABS

    5.1 BASIC GRID SYSTEM:

    Begin creating the grid system by clicking the File menu > New model command or the New

    model icon. The form shown in figure below wil display. Select the No option on that form

    the next figure will display.

    Figure 7-The new model initialization form.

    5.2 DEFINE GEOMETRY:

    The Building Plan Grid System and Storey Data form is used to specify horizontal and

    vertical grid line spacing, storey data, storey elevation and units. They automatically add the

    structural objects with appropriate properties to the model.

    Figure 8- Building Plan Grid System and Storey Data Definition

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    37/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    37

    5.3 DEFINE MATERIAL PROPERTY:

    The material properties of each object in the model is specified in the appropriate form. The

    material used is concrete, the grade of concrete, the properties of concrete such as Mass per

    unit volume, Modulus of Elasticity of concrete,Poisson ratio are specified and for steel yield

    strength is specified.

    Figure 9- Material property data form.

    5.4 DEFINE FRAME SECTION:

    Assign the frame section such as Column and Beam. Select the section property as Rectangle

    and define the depth,width and reinfprcement details,cover provisions.similarly for various

    sections like circular,pipe, steel joist sections aiso assigned with suitable data.

    Figure 10- Define Frame Properties form.

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    38/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    38

    Figure 11- Section properties and Reinforcement details.

    5.5 DEFINE WALL OR SLAB SECTION:

    Assign the slab or wall section then assign the section name,thickness,material used,type and

    reinforcement details.

    Figure 12- Define wall or slab section

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    39/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    39

    5.6 DEFINE DIAPHRAM: 

    The lateral loads can be in the form of wind or seismic loads, the loads are automatically

    calculated from the dimensions and properties of the structure based on built-in options for a

    variety of building codes. For Rigid diaphragm systems, the wind loads applied at the

    geometric centers of each rigid floor diaphragm.

    Figure 13-Define Diaphragms

    5.7 DEFINE RESPONSE SPECTRUM FUNCTION:

    Functions are defined to describe how a load varies as a function of period, time or

    frequency.

    Figure 14- Define response spectrum function.

    5.8 RESPONSE SPECTRUM FUNCTIONS

    Response spectrum functions are pseudo spectral acceleration versus period functions for usein response spectrum analysis. In this program the acceleration values to be normalized; that

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    40/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    40

    is, the functions themselves are not assumed to have units. Instead, the units are associated

    with a scale factor that multiplies the function and is specified when we define the response

    spectrum case.

    Figure 15- Response spectrum function graph

    5.9 STATIC LOAD CASES:

    Loads represent the actions upon the structure, such as force, pressure, support displacement,

    thermal effects and others. A spatial distribution of loads upon the structure is called static

    load case. Define as many load cases as needed. Typically separate load case definitions

    would be used for dead load, live load, static earthquake load, wind load, snow load, and

    Thermal load.

    Figure 16- Define static load case

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    41/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    41

    5.9 DEFINE LOAD COMBINATIONS:

    Define the load combinations in the appropriate form; Select the Add new combo option,

    then enter the load combination name, assign the loads with suitable scale factor. When the

    combination is defined, it applies to the results for every object in the model.

    Figure 17- Define load combinations

    12. Load combination -Table 12

    COMB DEAD LOAD LIVELOAD3 WIND/ E.QLOAD

    COMB01 1.5 DEADLOAD + 1.5LIVELOAD + 1.5 LIVELOAD

    COMB02 1.2 DEADLOAD + 0.6LIVELOAD + 0.3 LIVELOAD +1.2 E.Q.LOADX

    COMB03 1.2 DEADLOAD + 0.6 LIVELOAD + 0.3 LIVELOAD +1.2 E.Q.LOADY

    COMB04 1.5 DEADLOAD + +1.5 E.Q.LOADX

    COMB05 1.5 DEADLOAD + +1.5 E.Q.LOADY

    COMB06 0.9 DEADLOAD + -1.5 E.Q.LOADX

    COMB07 0.9 DEADLOAD + -1.5 E.Q.LOADY

    COMB08 1.2 DEADLOAD + 1.2 LIVELOAD + 1.2 LIVELOAD +1.2WINDLOADX

    COMB09 1.2 DEADLOAD + 1.2 LIVELOAD + 1.2 LIVELOAD -1.2WINDLOADX

    COMB10 1.2 DEADLOAD + 1.2 LIVELOAD + 1.2 LIVELOAD +1.2WINDLOADY

    COMB11 1.2 DEADLOAD + 1.2 LIVELOAD + 1.2 LIVELOAD -1.2WINDLOADY

    COMB12 1.5 DEADLOAD + +1.5WINDLOADX

    COMB13 1.5 DEADLOAD + -1.5 WINDLOADX

    COMB14 1.5 DEADLOAD + +1.5WINDLOADY

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    42/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    42

    COMB15 1.5 DEADLOAD + -1.5 WINDLOADY

    COMB16 0.9 DEADLOAD + +1.5WINDLOADX

    COMB17 0.9 DEADLOAD + -1.5 WINDLOADX

    COMB18 0.9 DEADLOAD + +1.5WINDLOADY

    COMB19 0.9 DEADLOAD + -1.5 WINDLOADY

    UNFACTORED COMBINATION

    COMB 20 1 DEADLOAD + 1 LIVELOAD + 1 LIVELOAD

    COMB 21 1 DEADLOAD + 0.5 LIVELOAD + 0.25LIVELOAD +1 E.Q.LOADX

    COMB 22 1 DEADLOAD + 0.5 LIVELOAD + 0.25LIVELOAD +1 E.Q.LOADY

    COMB 23 1 DEADLOAD + -1 E.Q.LOADX

    COMB 24 1 DEADLOAD + -1 E.Q.LOADY

    COMB 25 1 DEADLOAD + 1 LIVELOAD + 1 LIVELOAD +1 WINDLOADXCOMB 26 1 DEADLOAD + 1 LIVELOAD + 1 LIVELOAD -1 WINDLOADX

    COMB 27 1 DEADLOAD + 1 LIVELOAD + 1 LIVELOAD +1 WINDLOADY

    COMB 28 1 DEADLOAD + 1 LIVELOAD + 1 LIVELOAD -1 WINDLOADY

    COMB 29 1 DEADLOAD + +1 WINDLOADX

    COMB 30 1 DEADLOAD + -1 WINDLOADX

    COMB 31 1 DEADLOAD + +1 WINDLOADY

    COMB 32 1 DEADLOAD + -1 WINDLOADY

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    43/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    43

    5.11 MODEL OUTPUT

    A) OUTPUT: 3D-MODEL OF A RC FRAME

    Figure.18-3D model of RC frame

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    44/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    44

    B) BENDING MOMENT DIAGRAM FROM ANALYSIS

    Figure 19- Bending Moment from analysis.

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    45/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    45

    C) SHEAR FORCE FROM ANALYSIS

    Figure 20- Shear Force from analysis.

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    46/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    46

    D) DIAPHRAGM

    Figure 21-Diaphram output from analysis.

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    47/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    47

    E) PLAN SHOWING SLAB ID

    Figure 22- Plan showing slab ID

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    48/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    48

    E) PLAN SHOWING BEAM ID

    Figure 23- Plan showing Beam ID

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    49/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    49

    6.0 DESIGN OF FOUNDATION

    6.1GENERAL 

    In a typical structure built on a ground, that part of structure which is located above the

    ground is generally referred to as the superstructure and the part which lies below ground is

    referred to as substructure or foundation. The purpose of the foundation is to effectively

    support the superstructure by

      Transmitting the applied load effects to the soil below without exceeding the safe

    bearing capacity of soil.

      Ensuring that the settlement of the structure is within the tolerable limits, and as

    uniform as possible.

    Further the foundation should provide adequate safety against possible instability due to

    overturning or sliding and possible pullout.

    Footings belong to the category of shallow foundation, types of footings are Isolated footing,

    Combined footing and Wall footing.

    In some cases it may be inconvenient to provide separate isolated footings for columns (or

    walls) on account of inadequate areas available in plan. This may occur when two or more

    columns are located close to each other or if they are relatively heavily loaded and rest on soil

    with low safe bearing capacity resulting in an overlap of areas if isolated footings are

    attempted. In such cases it is advantageous to provide a single footing for the column.

    Isolated footing

    Figure 24-Types of footing

    6.2 DESIGN OF ISOLATED FOOTING

    For ordinary structures located on reasonably firm soil, it usually suffices to provide a

    separate footing is also called an isolated column. It is generally square or rectangular in plan

    other shapes are resorted to under special circumstances. The footing basically comprises a

    thick slab which may be flat, stepped or sloped.

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    50/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    50

    6.3 DESIGN OF TYPICAL ISOLATED FOOTING

    6.3.1 DESIGN PARAMETERS:

    Grade of concrete using (f ck ) = 30N/mm2 

    Grade of steel using (fy) = 500 N/mm

    2

     Load combination considered (COMBO 5) = 1.5D.L+1.5E.L

    Axial load = 1584.89 kN

    Moment in X direction (Mux) = 18.26 kNm

    Moment in X direction (Muy) = 16.13 kNm

    Safe bearing capacity of soil = 100 kN/ m2 

    Unit weight of concrete = 25kN/m3 

    Shape of the footing = Square footing

    Type of the footing = Flat

    Assume self-weight of footing as 15% = 1.15×1584.89 kN

    Total weight = 1822.62 kN(unfactored)

    [P/A] ± [Mx /Z] ± [My] ≤ q (SBC of soil) 

    [1822.62/B.L] + [18.26×6/B.L2

    ] + [18.26×6/B.L2

    ] = 100 kN/ m2

     

    Assume L/B ratio =1 (L=B)

    Solve the above equation, Size of the footing = 4.4m×4.4 m

    [P/A] + [Mx /Z] + [My] P1  = 96.01 kN/ m2 

    [P/A] +[Mx /Z] - [My] P2  = 93.73 kN/ m2 

    [P/A] - [Mx /Z] + [My] P3  = 94.55 kN/ m2 

    [P/A] - [Mx /Z] - [My] P4  = 92.27 kN/ m2 

    Assume depth of footing = 700 mm

    Downward pressure due to base slab (0.7×25) = 17.5 kN/ m2 

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    51/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    51

    Figure 25-Pressure diagram 

    6.3.2 BENDING MOMENT IN X DIRECTION

    Cantilever projection along X = 1.825 m

    Mx [94.22×0.5×1.8252]+[.5×1.825×1.945×.67×1.825]-[17.5×0.5×1.825

    2] =129.91kNm

    Steel required along X direction

    Mu lim = 0.138×f ck ×b×d2 

    Depth required = 178mm

    Depth provided [700-50-(25/2)] = 637mm

    Mu/b.d2 = [1.5×129.91×10

    6] / [1000×637

    2] = 0.48

    Percentage of steel = 0.117

    Provide percentage of steel = 0.75

    Provide 25mm diameter bars and spacing [.785×252×1000]/4400 =111.50

    Provide 25mm diameter bars at spacing of 100mm c/c.

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    52/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    52

    6.3.3 BENDING MOMENT IN Y DIRECTION:

    Cantilever projection along Y = 1.825 m

    My[94.22×0.5×1.8252]+[.5×1.825×1.945×.67×1.825]-[17.5×0.5×1.825

    2]=129.91kNm

    Steel required along Y direction

    Mu lim  = 0.138×f ck ×b×d2 

    Depth required = 178mm

    Depth provided [700-50-(25/2)] = 637mm

    Mu/b.d2 = [1.5×129.91×10

    6] / [1000×637

    2] = 0.48

    Percentage of steel = 0.117

    Provide percentage of steel = 0.75

    Provide 25mm diameter bars and spacing [0.785×252×1000]/4400 =111.50

    Provide 25mm diameter bars at spacing of 100mm c/c.

    6.3.4 CHECK FOR ONE WAY SHEAR:

    Critical section located a distance of ‘d’ from the face of the column.

    Average pressure (95.187+94.215)/2 = 94.70 kN/ m2 

    Shear force at critical section (94.70-15)×(1.825-.637) = 94.60

    Nominal shear stress τv = (Vu×1.5)/b.d = 0.22N/ mm2 

    From IS: 456-2000, table 19 Percentage of reinforcement = 0.59N/ mm2 

    Safe in one way shear. τv  < τc 

    6.3.5 CHECK FOR TWO WAY SHEAR:

    Average pressure (94.345+94.14)/2 = 94.24 kN/ m2 

    Vu = 94.24× [(4.4×4.4)-(0.75+0.637)(0.75+0.637)] =1563.06kN

    Nominal shear stress τv = (Vu×1.5)/b.d = 0.66 N/ mm2 

    τc = 0.25×√(f ck ) = 1.37 N/ mm2 

    τv < τc  Hence safe in two way shear.

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    53/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    53

    6.3.6 TRANSFER OF FORCES AT COLUMN BASE:

    As some bars are in tension, no transfer of forces is possible through bearing at the column

    footing interface. So, these bars may be extended into the footing.

    Development length required for 32mm diameter bars (In tension)

    Ld = (φ×fy×0.87)/ (4×1.6×1.8) = 38φ 

    Ld = 38 ×32 = 1216mm

    Length available = 750-50-25-16+(8×32) = 915mm

    The balance length = 301mm adopt = 350mm

    Need to be provided beyond the bend point.

    6.4 DETAILING OF FOOTING

    Figure 26-RC detailing of footing detailing

    Y 25 AT 100 mm C/C = 25mm dia bars at 100mm c/c

    Y 25 AT 100 mm C/C = 25mm dia bars at 100mm c/c

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    54/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    54

    7.0 COLUMN DESIGN

    7.1 GENERAL

    The column is a compression member which is subjected (predominantly) to axial forces. The

    IS 456:2000 code (clause 25.1.1) defines the column as a ‘compression member’ the effective

    length of which exceeds three times the least lateral dimension. The term ‘pedestal’ is used to

    describe a vertical compression member whose effective length is less than three times to

    least lateral dimension.

    Classification of columns

    Based on type of Reinforcement:

    1)  Tied columns

    2)  Spiral columns

    3)  Composite columns

    Figure 27-Types of column

    Based on type of loading

    1)  Axially loaded column

    2)  Columns with uniaxial eccentric loading

    3)  Columns with biaxial eccentric loading

    Based on Slenderness Ratio

    1)  Short columns

    2) 

    Slender or long columns

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    55/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    55

    7.2 COLUMN DESIGN

    7.2.1 DEIGN PARAMETERS:

    Terrace level: C-1

    Grade of concrete using (f ck ) = 30N/mm2 

    Grade of steel using (fy) = 500 N/mm2 

    Load combination considered (COMBO 5) = 1.5D.L+1.5E.L

    Axial load = 316.44kN

    Moment in X direction (Mux) = 235.84kNm

    Moment in X direction (Muy) = 128.0 kNm

    Size of the column = 750×750mm

    d' = 60mm

    Ratio of d’/D  = 60/750= 0.08

    Pt / f ck = 1.0/ 30= 0.03

    Pu / f ck  bd =(316×103)/(30×750×750) = 0.018

    Mu / f ck  bd2[From the code IS 456- 1978 chart 48] = 0.08

    Mux1  =0.08×30×750×7502 

    =1012.50kNm

    Ratio of d’/D  =60/750= 0.08

    Pt / f ck = 1.0/ 30 =0.03

    Pu / f ck  bd =(1586×103)/(30×750×750) = 0.018

    Mu / f ck  bd2[From the code IS 456- 1978 chart 48] = 0.08

    Muy1  =0.08×30×750×7502 

    =1012.50kNm

    Percentage of reinforcement = 1.0

    Puz / Ag  [From the code IS 456- 1978 chart 63] = 17

    = 17×750×750

    = 9562 kN/m2 

    7.2.2 BENDING MOMENT CALCULATION: 

    [Mux / Mux1] αn

     + [Muy / Muy1] αn≤ 1 

    [Pu /Puz] = (316.44/ 9562)

    = 0.03

    [Pu /Puz]≤0.2 so αn  =1

    [235.84/ 1012.50] +[128/1012.50] = 0.36

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    56/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    56

    0.36 ≤ 1 

    [Muy / Muy1] αn

      [From the code IS 456- 1978 chart 64] = 0.80 > 0.0.13

    7.2.3 REINFORCEMENT PROVIDED:Pt = 1.0

    Ast  = (1.0×750× 750)/ 100

    Ast  =5625mm2

    Provide 20 numbers of 20 mm diameter bars. (Ast=6280mm2)

    Transverse reinforcement

    Tie diameter φt  = φ long/4

    25/4 = 6.25mmProvide 8 mm diameter tie bars

    Tie spacing St < or = 16 φ 

    =16×25= 517mm

    Spacing of ties should not greater than 300mm.

    As per IS13920:1993

    Spacing of hoops should not greater than = (1/4 of least lateral dimension)

    (1/4)×750=187.5mmProvide 8 mm bars at spacing 190mm c/c as a transverse reinforcement

    7.2.4 DESIGN PARAMETERS:

    Fifth floor level

    Grade of concrete using (f ck ) =30N/mm2 

    Grade of steel using (fy) = 500 N/mm2

    Load combination considered (COMBO 5) = 1.5D.L+1.5E.L

    Axial load = 659.88kN/mm2 

    Mux = 122.65kNm

    Muy = 59.10kNm

    Size of the column = 750×750mm

    d' = 60mm

    Ratio of d’/D  = 60/750= 0.08

    Pt / f ck = 1.0/ 30= 0.03

    Pu / f ck  bd (659.88×103)/(30×750×750) = 0.04

    Mu / f ck  bd2  [From the code IS 456- 1978 chart 48] = 0.08

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    57/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    57

    Mux1  =0.08×30×750×7502 

    =1012.50kNm

    Ratio of d’/D  =60/75= 0.08

    Pt / f ck = 1.0/ 30=0.03

    Pu / f ck  bd (659.88×103)/(30×750×750) = 0.04

    Mu / f ck  bd2  [From the code IS 456- 1978 chart 48] = 0.08

    Muy1  =0.08×30×750×7502 

    =1012.50kNm

    Percentage of reinforcement = 1.0

    Puz / Ag  [From the code IS 456- 1978 chart 63] = 17

    = 17×750×750

    = 9562 kN/m2 

    7.2.5 BENDING MOMENT CALCULATION:

    [Mux / Mux1] αn

     + [Muy / Muy1] αn≤ 1 

    [Pu /Puz] = (659.88 / 9562.5) = 0.07

    [Pu /Puz]≤0.2 so αn  =1

    [122.16/ 1012.5] + [59.10/1012.5] = 0.18

    0.18 ≤ 1 

    [Muy / Muy1] αn

    [From the code IS 456- 1978 chart 64] =0.80> 0.05(calculated).

    7.2.6 REINFORCEMENT DETAILS:

    Pt = 1.0

    Ast  = (1.0×750× 750)/ 100

    Ast  =5625mm2

    Provide 20 numbers of 20 mm diameter bars 4 on each face (6280 mm2)

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    58/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    58

    7.3 COLUMN DETAILING:

    Figure 28.a-Longitudinal section

    Figure 28.b-Cross section 

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    59/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    59

    8.0 BEAM DESIGN

    8.1 GENERAL:

      A reinforced concrete flexure member should be able to resist tensile, compressive

    and shear stresses induced in it by loads acting on the member.

      Concrete is fairly strong in compression but week in tension.

      Thus the tensile weakness of concrete is overcome by the provision of reinforcing

    steel in the tension zone.

      A flexure member may be Beam, slab, Wall or Component of foundation.

    There are three types of reinforced concrete beams:

    1. Singly reinforced beams

    2. Doubly reinforced beams

    3. Singly or doubly reinforced flanged beams

    Singly Reinforced Beams.

      In Singly reinforced simply supported beams or slabs reinforcing steel bars are placed

    near the bottom of beam or slabs where they are most effective in resisting the tensile

    stresses.

      In the case of cantilever beams or slabs reinforcing steel bars are placed near the top

    of the beam or slabs for the same reason.

    Doubly Reinforced Beams.

    A doubly reinforced concrete section is reinforced in both compression and tension regions.

    The section of the beam or slab may be rectangle, T and L section. The necessity of usingsteel in compression region arises due to two main reasons:

      When depth of the section is restricted, the strength available from singly reinforced

    section is in adequate.

      At a support of a continuous beam or slab where bending moment changes sign. Such

    a situation may also arise in the design of a beam circular in plan.

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    60/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    60

    Flanged beams: 

    When a reinforced concrete slab is cast monolithically with the beam as in the case of

    beam supported floor slab system, the beams can be considered as flanged beams with

    slab acting as an effective flange on compression side.

      Minimum reinforcement  –  The minimum area of tension reinforcement shall not be

    less than that given by the following:

    Ast min=0.85bd/ fy

      The maximum area of compression reinforcement shall not exceed 0.04 bD.

    Compression reinforcement shall be enclosed by stirrups for effective restraint. The

    anchorage length of straight bars in compression shall be equal to the development

    length of bars in compression.

      Where the depth of the web in a beam exceeds 750 mm side face reinforcement shall

    be provided along the two faces. The total area of such reinforcement shall be not less

    than 0.1 percent of the web area and shall be distributed equally on two faces at a

    spacing not exceeding 300 mm or web thickness whichever is less.

    8.2 DESIGN OF TYPICAL BEAM

    8.2.1 DESIGN PARAMETERS

    Grade of concrete using (f ck ) = 30N/mm2 

    Grade of steel using (fy) = 500 N/mm2 

    Length of the beam = 8.20m

    Size of the beam = 300×750mm

    Load combination considered Envelope of factored loads.

    8.2.2 BENDING MOMENT CALCULATION:

    Maximum positive moment [Mmax] = 124.61kNm

    Mu / b.d2 = (124.61×10

    6)/ 300×690

    2  = 0.87

    Mulim = 3.99 > 0.87, Beam section is designed as singly reinforced.

    [From table 4 of SP:16] Pt = 0.215

    Ast = (Pt×bd)/100 = 438.84mm2 

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    61/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    61

    Minimum Ast = (0.85/f y)= Ast/bd = 360.16 mm2 

    Provide 3 numbers of 16mm dia bars

    Maximum negative moment [Mmax] = 300.20kNm

    Mu / b.d2= (300.20×10

    6)/ 300×690

    2  = 2.10

    [From table 4 of SP:16] Pt = 1097.10mm2 

    Ast = (Pt×bd)/100 = 1097.10mm2 

    3 numbers of 16mm dia bars, 2 numbers of 12mm dia bars.

    8.2.3 SHEAR REINFORCEMENT AT SUPPORT:τv = Vu/ b.d =134×10

    3 /300×690 = 0.64

    Pt (100×1097.10/690×300) = 0.50

    τc = 0.50

    τc < τv 

    Hence the beam is unsafe against shear so shear reinforcement is required.

    Vs  = Vu- (τc × b×d)

    (134-(0.5×300×690×10-3

    ) = 30.5kN

    Sv = (0.87×500×2×113×690)/ (30.5×103) = 222mm

    As per ductile detailing should be greater than (d/4) = (690/4) =172.50mm

    Adopt stirrup spacing 200mm c/c for a distance 2d = 2×690 =1.5m from the face of the

    support.

    8.2.4 SHEAR REINFORCEMENT AT MID SPAN:

    τv = Vu/ b.d = 70.5×103 /300×690 = 0.34

    Pt (100×1097.10/750×300) = 0.5

    τc = 0.5

    τc > τv 

    Minimum shear reinforcement is to be provided.

    Asv / b.Sv = 0.4/ 0.87× f y 

    0.785×82 / 300×Sv  = 0.4/ 300×500

    Sv  = 182mm

    < 0.75×d = 517.5mm

    < Least lateral dimension = 300 mm

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    62/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    62

    < 300mm

    So provide 8mm dia 2 legged stirrups at 100 mm c/c for a distance of L-4d = 8.20- 2.76 =

    5.44m

    8.2.5 DESIGN OF HANGER BARS:

    Maximum shear due to secondary beam Vu = 61.19kN

    For single bar or single group of parallel bars all bent up to the same cross section.

    Vus  = 0.87×f y×Asv ×Sin α×2 

    0.87×500×.785×122×Sin60 ×2 = 170.34kN

    So provide 2 numbers of bars 12 mm diameters at an angle of 60’ 

    8.2.6 DEVELOPMENT LENGTH

    Ld = (φ×fy×0.87)/ (4×1.6×1.8)  = 1.2

    For ductile detailing

    Development length = Ld + 10d- allowance for 90’ bent.

    1.2+(10×.032×)-(8×.032) = 1.7m

    8.2.7 CHECK FOR DEFLECTION:

    Deflection actual = 8250 / 690 = 11.96 mm

    Deflection allowable for continuous beam = 26 mm

    Stress in steel f s = 0.58×fy×[Ast required/ Ast provided] =0.58(438.82/452.16)500

    f s (Permissible stress in steel) = 281 N/mm2 

    Find k1 (From IS 456-2000figure 4 modification factor chart)

    Pt =(100×452.16)/ bd = 0.22

    k1 = 0.95

    Find k2

    Pt =(100×1205.86)/ bd = 0.58

    K2 = 0.9

    Deflection allowable = k1×k2×26

    Deflection allowable = 0.95×0.9×26

    = 22.23mm

    11.26 < 22.23 Safe in deflection

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    63/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    63

    8.3 BEAM DETAILING

    Figure 29-Longitudinal section of beam

    3a -Y16 = 3 numbers of 16mm dia bars (top layer-1)

    2b -Y12 = 2 numbers of 12mm dia bars (top layer-2)

    3c- Y16 = 3 numbers of 16mm dia bars (bottom layer-1)

    Shear reinforcement =2×d = 1500mm stirrup spacing 200mm c/c for a distance 2d = 2×750

    =1.5m from the face of the support.

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    64/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    64

    9.0 DESIGN OF SLAB

    9.1 ONE WAY AND TWO WAY SLAB

    The most common type of structural element used to cover floors and roofs of buildings are

    reinforced concrete slabs of different types. One way slabs are those supported on the two

    opposite sides so that the loads are carried along one direction only. A common example of

    one way slab is the verandah slab spanning in the shorter direction with main reinforcements

    and distribution reinforcements in the transverse direction.

    ONE -WAY SLAB

    Reinforced concrete slabs supported on two opposite sides with their longer dimension

    exceeding two times the shorter dimension are referred to as one- way slabs.[ Ly /Lx >2 ]

    TWO WAY SLAB

    Reinforced concrete slabs supported on all the four sides with their effective span in the

    longer direction not exceeding two times the effective span in the shorter direction are

    designed as two way slabs. Two- way slabs bending moments are maximum at the centre of

    the slab and the larger moment invariably develops along the short span. [Ly /Lx ≤2]

    Figure 30-Types of slab

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    65/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    65

      Shorter of the two spans should be used for calculating the span to effective

    depth ratios.

      For two way slab of shorter span- up to 3.5m with fy=250, the span to overall

    depth ratios given below & vertical deflection limits up to 3 kN per squaremeter.

    1.  f y = 500, values given below should be multiplied to 0.8.

    2.  Simply Supported slabs = 35

    3.  Continuous slabs =40

      Span to effective depth ratios for spans up to 10m

    i.  Cantilever =7

    ii.  Simply supported =20

    iii.  Continuous = 26

      Spans above 10m- value may be multiplied by 10/span in m.

    Effective span

      Simply Supported slab & Continuous slab(width of the support is less than

    1/12 of clear span)

    the least of,

    1.  Clear span + effective Depth

    2.  Centre to Centre of supports

    3.  Continuous slab-(width of the support are wider than 1/12 of clear

    span or 600mm whichever is less)

      One end fixed and other continuous- clear span bet’ support. 

      One end free and other continuous- the least one,

    1.  clear span+1/2x eff. Depth of slab

    2.  Clear span+1/2x width of the discontinuous support.

      Roller or rocket bearing- distance bet’ the Centre of bearing. 

    i.  Cantilever-Face of the support +1/2 eff. Depth.

    ii.  Frame : (continuous frame )c/c distance

      Slabs spanning in two directions at right angles

    1.  The most commonly used limit state of collapse method is based on

    yield-line theory.

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    66/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    66

    Figure 31- load distribution in two way slab

    9.2 DESIGN OF TYPICAL TWOWAY SLAB

    9.2.1 DESIGN PARAMETERS:

    Length of slab in X-direction (L×) = 3.60m

    Length of slab in Y direction (Ly)  =4.55m

    Grade of concrete using (f ck ) =30N/mm2 

    Grade of steel using (fy) = 500 N/mm2 

    Ly /L×  = 4.55/3.60

    = 1.2 < 2 (two way slab)

    Basic value of L/D ratio = 3600/28

    Effective depth = 130mmOverall depth = 150mm

    Effective span =clearspan+eff.depth

    = 3.6+0.130

    = 3.73m

    Self-weight of the slab = 1× 25× 0.150

    = 3.75kN/m2 

    Live load = 4kN/m2 

    Floor Finish = 24×1×0.06 = 1.5kN/m2 

    Total Load =9.25kN/m2 

    Ultimate load = 9.25×1.5

    =13.875kN/m2 

    9.2.2 DESIGN OF BENDING MOMENT:

    Two adjacent edges discontinuous (from code IS456:2000 table 26)

    Ly /L×  = 1.2

    Mxe  = α×e× W × L×2 

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    67/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    67

    13. Moment calculation Table-13

    Moment coefficients Ultimate load(W) in

    kN

    Length (Lx) in m M= α×e×W× L× (kNm)

    α×e

    =0.065 (Edge) 13.875 3.73 12.54

    α×m=0.049 (Span) 13.875 3.73 9.45

    αye =0.047 (Edge) 13.875 3.73 9.07

    αym=0.035 (Span) 13.875 3.73 6.75

    9.2.3 REINFORCEMENT CALCULATION: TABLE-14

    Moment

    (kN-m)

    Ast calculation Ast  No .of bars with

    diameter.

    Spacing

    12.54 87×500 × Ast ×130(1  –  

    500×Ast /30×1000 ×130)

    230 mm Provide 10mm dia bars 300mm

    9.45 87×500 × Ast ×130(1  –  

    500×Ast /30×1000 ×130)

    171mm Provide 10mm dia bars 300mm

    9.07 87×500 × Ast ×130(1  –  

    500×Ast /30×1000 ×130)

    164mm Provide 10mm dia bars 300mm

    6.75 87×500 × Ast ×130(1  –  

    500×Ast /30×1000 ×130)

    122mm Provide 10mm dia bars 300mm

    9.2.4 CHECK FOR DEPTH:

    Max. B.M in the slab = 12.68 kN/m2 

    M.R = 0.138 × f ck × b × d2

    12.68 kNm = 0.138 ×30×1000× d2 

    Depth = 55.34 < 130 mm

    9.2.5 CHECK FOR SHEAR:

    V ux  = 0.5×13.875×3.73

    = 25.88kN

    Max. S.F. of support, Vu  =(25.88×103)/(1000×150)

    Nominal shear stress τv  = 0.17 N/mm2 

    100Ast / bd = 0.15

    Critical shear τc  = 0.29 N/mm2 

    Hence the slab is safe against shear.  τc  > τv 

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    68/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    68

    9.2.6 CHECK FOR DEFLECTION:

    Deflection actual = 3730/ 130 = 28mm

    Stress in steel f s  = 0.58 × (230/304) × 500

    f s(From IS 456-2000 figure 4 ) modification factor) = 220 N/mm2 

    Modification factor (k 1) = 1.8

    Deflection allowable = 1.8×20×1×1 = 36mm

    [28mm < 36mm] The slab having the sufficient stiffness and the deflection will be within the

    permissible value.

    9.3 REINFORCEMENT DETAILS

    Figure 32- R.C.Slab details

      Tension reinforcement;(lower part of the slab)

    1.  0.25L-continuous edge

    2.  0.15L-discontinuous edge

      Continuous edges of middle strip, the tension reinforcement. Shall extend in the upper part of

    the slab a distance 0.15L from the support and at least 50 % shall extend a distance of 0.3L.

    1.  Negative moments at discontinuous edge- 0.1L

    2.  Torsion reinforcement shall be provided at any corner

      Minimum distance- 1/5 x shorter span

      Area of reinforcement-3/4 x area required for the max. Mid-span

    meters in the slab.

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    69/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    69

      Spacing

    1.  main steel- ≠ > 3d or 300mm whichever is smaller  

    2.  Distribution steel- ≠> 5d or 450mm whichever is smaller  

      Minimum reinforcement: ≠< 0.15 % of the total cross sectional

    area for f y=250 and 0.12% when f y=415 bars are used

      Maximum diameter of bars : ≠> 1/8 x D

      Cover: should not be less then15mm nor < dia. of bar whichever is higher

    Figure 33-Slab detailing

    1- 10mm dia bars at 300mm spacing 3,4-10mm dia bars at 300mm spacing

    2,3-10mm dia bars at 300mm spacing 5,6-10mm dia bars at 300mm spacing

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    70/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    70

    10.0 DESIGN OF STAIRCASE

    10.1 GENERAL:

    Functionally the staircase is an important component of building, and often the only means of

    access between the various floors in the building. It consists of a flight of steps, usually with

    one or more intermediate landings provided between floor levels. Following are the structural

    components of staircase.

    A) Thread: The horizontal portion of a step where the foot rests is referred to as tread.

    The typical dimension of a tread is 250mm to 300mm.

    B) Riser: Riser is the vertical distance between the adjacent treads or the vertical

    projection of one step with value of the step 150 to 190mm depending upon the type of

    building. The width of stairs is generally 1 to 1.5m and in case not less than 850mm. Public

    buildings should be provided with larger widths to facilitate free passage to users and prevent

    overcrowding.

    C) Going: Going is the horizontal projection (plan) of an inclined flight of steps

    between the first and last riser. A typical flight comprises two landings and one going. To

    break the monotony of climbing, the number of steps in a flight should not exceed 10 to12.

    The tread riser combination can be provided in conjunction with

    1)  Waist slab type

    2)  Tread riser type

    3)  Isolated cantilever type

    4) 

    Double cantilever precast tread slab with a central inclined beam.

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    71/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    71

    Figure 34-Types of staircases

    Types of staircases

    The various types of staircases adopted in different types of buildings can be grouped under

    geometrical and structural classifications depending upon their shape and plan pattern and

    their structural behavior under loads. Types of staircases based on geometrical classification.

    1)  Straight stairs (with or without landing)

    2)  Quarter-turn stairs

    3) 

    Dog-legged stairs

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    72/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    72

    4)  Open well stairs

    5)  Spiral stairs

    6)  Helical stairs

    10.2 DESIGN PARAMTERS

    Type of staircase = Waist slab type

    Number of steps in flight = 12

    Tread (T) =300mm

    Riser (R) =150mm

    Width of landing beams =600mm

    Grade of concrete using (f ck ) =30N/mm2

     

    Grade of steel using (fy) = 500 N/mm2 

    Effective span (L) = [(12×300) +600] = 4200mm

    Thickness of waist slab = [4200/20]

    = 210mm

    10.3 LOAD ACTING ON STAIRS

    Dead load of slab (on slope) (Ws) = (0.21×1×25) = 5.25kN/m

    Dead load of slab on horizontal span [Ws√R 

    2

    +T

    2

     / T] = 5.59kN/mDead of one step (0.5×0.15×0.3×25) = 0.56kN/m

    Load of steps/m length = [0.56×(1000/300)] =1.86kN/m

    Floor finishes = 1.5kN/m

    Total dead = 8.95kN/m

    Live load (overcrowding) per meter = 5kN/m

    Total service load =13.95kN/m

    Total ultimate load = (1.5×13.95)

    =20.93kN/m

    10.4 DESIGN OF WAIST SLAB TYPE STAIRCASE

    Maximum bending moment (0.125×20.93×4.22) = 46.15kNm

    Check for depth of waist slab(d)=√46.15×106 /(0.138×30×1000) = 106mm

    Assume a cover of 20mm and using 12mm dia bars [210-20-6] = 184mm

    Effective depth provided is greater than the required depth (184 >106)

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    73/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    73

    10.5 REINFORCEMENT PROVIDED

    Using table 2 from SP: 16

    [Mu/ b×d2] = [46.15×106 /1000×184

    2] = 1.35 

    Pt = [Ast×100/b×d] =0.329

    Ast =606mm2 

    Provide 12mm diameter bars at 200mm spacing (Ast=678mm2) as main reinforcement.

    Distribution reinforcement (0.0012×1000×210)=252mm2

    Provide 8mm diameter bars at 200mm spacing (Ast=252mm2) as distribution reinforcement.

    10.6 STAIRCASE DETAILING

    Figure 35-Detailing of staircases

    Longitudinal reinforcement: Y 12 AT 200 c/c

    Distribution reinforcement: Y 8 at 200 c/c

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    74/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    74

    11.0 DESIGN OF SHEAR WALL

    11.1 GENERAL

    Lateral force resisting system in the building is a dual system consisting of SMRF and shear

    walls. In general, the shear walls will resist all the lateral force being a relatively stiff

    element.

    The design of shear wall is based on the assumption that it will be the part of the lateral force

    resisting system of the structure.

    The shear wall is provided in between the middle two columns of the exterior frames. These

    columns will act as a flange element or boundary elements for the shear wall. Therefore,

    there is no need for further thickening of shear wall at the end or boundary regions.

    Calculated reinforcement in horizontal and vertical direction is greater than the minimum

    prescribed reinforcement provided reinforcement is uniformly distributed in both the

    directions.

    Figure 36-Shear Wall

    11.2 WALL DIMENSIONS:

    Length of the wall = 7.2m

    Thickness of wall = 230mm

    Height of the wall = 4.0m

    Load combinations considered = 1.5DL + 1.5 EQL

    = 0.9DL + 1.5 EQL

    P1 Axial load (1.5DL + 1.5 EQL) = 3349 kN

    Shear force = 7532.98 kN

    Bending moment = 33781.95

    P2 Axial load = 2197 kN

    Shear force = 7529.02 kN

  • 8/20/2019 Seismic Analysis and Design of Hospital Building-libre

    75/79

    SEISMIC ANALYSIS AND DESIGN OF MULTI STOREYED HOSPITAL BUILDING 

    75

    Bending moment = 33756 kNm

    Grade of concrete using (f ck ) =30N/mm2 

    Grade of steel using (fy) = 500 N/mm2 

    11.3 CHECK FOR BOUNDARY ELEMENT:

    Moment of inertia I= (t ×L3)/ 12 = (230 ×7.2

    3)/ 12

    = 7.15 ×1012

     mm4 

    Area= t×L = 230×7200

    =1656×103 mm

    f c= (P/A)±( Mt ×L/ I) =2.02 ± 17.03

    = 19.05 and -15.01kN/ m2 

    11.4 FIXING BOUNDARY ELEMENT:

    Assume width of flange (Wf) = 230 mm

    Length of flange (Lf) = (0.1×L) = 0.1×7200

    = 720mm

    Provide 750×250mm boundary element.

    Lw = 7200-(2×750) = 5700

    c/c = 7200-750 = 6450

    Wall thickness is 230mm so provide two layers of steel.

    11.5 DETERMINATION OF MINIMUM STEEL:

    1) VERTICAL REINFORCEMENT = 0.0025×Ag

    0.0025×1000×230 = 575 mm2 

    Provide area of steel is 1% of gross area. That is 0.5% in each layer.

    Area of steel in each layer (Ast) = (0.575×1000×230)/100

    = 1322.5mm2 

    Diameter of b