SEG / SEG PLUS€¦ · Instructions of deflector installation in SEG boilers (14kW, 17kW, 28kW,...
Transcript of SEG / SEG PLUS€¦ · Instructions of deflector installation in SEG boilers (14kW, 17kW, 28kW,...
ENGLISH
SEG / SEG PLUSOPERATION AND MAINTENANCE DOCUMENTATION
TRANSLATION OF THE ORIGINAL MANUAL
ISSUE II 2019/06/01
1
INTRODUCTION
Dear User, Thank you for choosing the heating boiler from Metal-Fach. We hope that the device will meet your requirements and bring much satisfaction. The heating boiler was designed and
manufactured according to the most important, current norms and standards, guaranteeing safety and dependable use. Using the device in accordance with the provided manual ensures effective and
dependable operation. The boiler is not meant to be operated by persons of lowered mental or physical independence or by persons with no experience or limited knowledge about the product if they are not supervised or
instructed by the person responsible for their safety. Operation by children is prohibited.
2
Table of Contents 1. Initial activities ............................................................................................................................. 3 2. Applied symbols .......................................................................................................................... 3 3. Definitions of terms in the manual ........................................................................................... 3 4. General information ................................................................................................................... 3 5. Boiler equipment ........................................................................................................................ 3 6. Use ................................................................................................................................................ 4 7. Basic elements of the boiler ....................................................................................................... 5 8. Basic dimentions of the boiler SEG/SEG PLUS ......................................................................... 6 9. Technical specifications SEG/SEG PLUS .................................................................................... 7 10. Control and safety ....................................................................................................................... 8 11. Fuel ............................................................................................................................................... 8 12. Requirements for the boiler room and boiler installation ...................................................... 8 13. Instructions of deflector installation in SEG boilers (14kW, 17kW, 28kW, 38kW) ............... 10 14. Boiler installation ...................................................................................................................... 10 15. Connecting the boiler to the heating system ......................................................................... 11 16. Connection of boiler to heating installation in closed-loop system (additional option) .... 14 17. Requirements for the expansion vessel ................................................................................. 15 18. Connecting the boiler to the power supply ............................................................................ 15 19. Connecting the boiler to the chimney ..................................................................................... 18 20. Boiler start-up ............................................................................................................................ 18 21. Recommended boiler power settings ..................................................................................... 22 22. Tips when using the boiler ....................................................................................................... 23 23. Boiler maintenece and cleaning .............................................................................................. 23 24. Istruction for utilising the boiler .............................................................................................. 23 25. Spare parts list ........................................................................................................................... 23 26. Possible faults and malfunctions ............................................................................................. 24 27. Operating requirements ........................................................................................................... 28 28. Installing the feeder in the boiler and start-up ...................................................................... 28 29. Installation and replacing the overload clutch arrester ........................................................ 28 30. Feeder operations ..................................................................................................................... 30 31. Feeder operation manual ......................................................................................................... 30 32. Feeder mantenance .................................................................................................................. 30 33. Replacing the ignition ............................................................................................................... 30 34. Disposal of EkoEnergia burner after its lifespan .................................................................... 31 35. Possible disruptions in work of ekoenergia burner .............................................................. 32
Warranty conditions ................................................................................................................. 33 Confirmation of performance of inspection, guarantee repair, maintenance service: ..... 35 Conformity declaration WE/UE ................................................................................................ 37 Warranty Card for the steel boilers, central heating water boilers ...................................... 39 Warranty claim .......................................................................................................................... 41 Start-up report ........................................................................................................................... 43 Start-up report ........................................................................................................................... 45
List of tables Tab. 5.1 Boiler equipment ................................................................................................................... 4 Tab. 8.1 Boiler dimentions (mm) SEG/SEG PLUS ............................................................................... 6 Tab. 9.1 Technical specifications SEG/SEG PLUS ............................................................................... 7 Tab. 14.1 Flammability of construction products: ........................................................................... 11 Tab. 15.1 Symbols applied in the schematics .................................................................................. 12 Tab. 15.2 Symbols applied in the schematics .................................................................................. 12 Tab. 21.1 Suggested settings of GOLD II and PLATINUM controller for work with ekoenergia
burner – ecopea fuel ......................................................................................................... 22 Tab. 25.1 Spare parts ......................................................................................................................... 23 Tab. 35.1 Examples of ekoenergia burner failures ......................................................................... 32
Description of schematics Schematic 1.1 Serial plate .................................................................................................................... 3 Schematic 7.1 Basic elements of the boiler SEG 14-38 kW ............................................................... 5 Schematic 8.1 Boiler dimentions SEG/SEG PLUS ............................................................................... 6 Schematic 12.1 Minimal requirements for the boiler room ............................................................. 9 Schematic 13.1 Deflector's position above burner’s furnace. ........................................................ 10 Schematic 15.1 Connecting the boiler to the heating system diagram ........................................ 12 Schematic 15.2 Connecting boilers to the heating system diagram ............................................. 12 Schematic 15.3 Connecting the boiler to the heating system ........................................................ 13 Schematic 15.4 Connecting the boiler to the heating system with Laddomat and buffer .......... 13 Schematic 16.1 Safety schematics of the boiler with the cooling coil and thermal protection .. 14 Schematic 16.2 BVTS Valve ................................................................................................................ 15 Schematic 18.1 Electrical schematics for connecting the boiler– controllerPLATINUM. ............. 16 Schematic 18.2 Electrical schematics for connecting the boiler – additional B MODULE. .......... 17 Schematic 20.1 Automatic boiler start-up; PLATINUM controller: ................................................. 18
3
1. Initial activities (USER)
Procedure to follow on delivery of the METAL-FACH boiler
check if the boiler is complete (tab 5.1) and if it has not been damaged during delivery
confront your order with the data plate, that is placed on the left or right on the boiler body
read the user's manual carefully as it contains all the information required for safe
operation of the boiler
If you happen to encounter any problems, please contact our service department or dedicated
METAL- FACH service centre. The staff are trained and certified and have access to the original
parts which ensure proper servicing and boiler installation.
Schematic 1.1 Serial plate
2. Applied symbols (USER/INSTALLER)
ATTENTION!
Very important piece of information that needs to be read
TIP!
Information that should be read to make operation easier.
3. Definitions of terms in the manual (USER/INSTALLER)
Central heating boiler is a device intended to burn solid fuels in order to heat up the heat
carrier (usually water) that circulates in the heating system.
Burner - a technical device enabling burning of pellet fuels (BIO burner), coal in the form of
eco peas (cast iron burner).
Feeder is a part or set of devices designed for delivering various fuels to the boiler.
Biomass - in energy production terms, it is a source of primeval energy consisting of different
plant or animal substances which have been biodegraded. Its use is not limited within the legal
system.
Pellet is a burning material that comes from the pressed wood waste, mainly wood dust,chip,
woodwork or lumbermill waste. It can also be produced from bark, straw,sunflower or other
organic materials. Pellet is delivered in the form of granules or rolls
4. General information (USER)
The maintenance and operation documentation is a part of the product that comes with the
delivered boiler. The Operation and Maintenance Documentation contains data concerning the
design, installation and method of using SEG/SEG PLUS series boilers with an EkoEnergia burner
(cast iron, retort burner). A thorough study of the manual enables a proper and safe operation of
the boiler.
ATTENTION!
The user is advised to follow all guidelines concerning the appliance given in this
Operation and Maintenance Documentation, Guarantee Terms as well as in
generally applicable law.
Our boilers are shipped assembled. They are tightly attached to a pallet. Some other forms of
securing the boiler are used e.g. foil wrapping.
During the shipping, the boiler should be tightly secured (e.g.with transport belts) so that it
does not turn or move. The delivery should meet the requirements set in the general rules for
transporting materials. The loading and unloading of the boilers should be carried out using lifting
devices (fork lift truck) of lifting capacity over 1000kg.
5. Boiler equipment (USER)
The delivery includes basic as well as additional elements depending on the type of order. On
receiving the boiler you should carefully inspect the boiler to ensure that it has been delivered
undamaged and complete. The additional and basic elements are listed below (Tab 5.1).
4
Tab. 5.1 Boiler equipment
Basic equipment Unit Number
of items
Central heating boiler pcs. 1
Microprocessor regulator operates:
boiler temperature sensor
hot tap water temperature sensor
central heating feed and return temperature sensor C.H.1 and
C.H.2
return water temperature sensor
outside temperature sensor
fumes temperature sensor
burner temperature
pcs. 1
Blower fan pcs. 1
STB pcs. 1
Fuel feeding system with burner set 1
Fuel bin pcs. 1
Boiler cleaning equipment
poker
brush
pcs. 1
Adjustable screws pcs. 4
Additional equipment Unit Number
of items
LAMBDA SENSOR module pcs. 1
Cooling coil for closed system with valve pcs. 1
Documentation Unit Number
of items
Boiler maintenance and operation documentation pcs. 1
Controller user's manual and warranty card pcs. 1
Blower fan user's manual and warranty card pcs. 1
Screw motoreducer user's manual pcs. 1
EKOENERGIA feeder maintenance and operation manual pcs. 1
ATTENTION!
Every user should familirise themselves with the operation manual for the regulator,
blower fan and EKOENERGIA feeder
ATTENTION!
METAL-FACH reserves the right to implement changes to the parametres, equipment
and specification of the offered products without prior notice.
6. Use (USER/INSTALLER)
Boilers intended for heating of residential buildings like: single-family and multi-family homes,
utility buildings, public buildings are equipped with an automatic furnace chamber filling system.
Thanks to the newest construction solutions, the SEG and SEG PLUS boilers can reach the capacity
of 90%. The proper operation and highest performance of the boiler depends on the quality of
installation, right flue and appropriate service and maintenance.
ATTENTION!
The boilers are designed to operate only with open system water installations with
gravitional or forced circulation which are secured in accordance with PN-EN 13384-
1:2004/ A1:2007 Heating and Calorifics
5
7. Basic elements of the boiler (USER/INSTALLER)
The water chassis is a construction made from welded certified steel sheets of 6 mm thickness
P265GH (for fumes interacting elements) and 4 mm (for other elements) S235JR+N.
Schematic 7.1 Basic elements of the boiler SEG 14-38 kW
Schematics description
1. Exchanger
2. Fuel bin
3. Feeder
4. Motoreducer
5. Burner
6. Feeder cover
7. Extinguishing unit
8. Cleaning door
9. Observation door
10. Ash door
11. Infeed stub
12. Return stub
13. Discharge stub
14. Adjustable screw
15. Flue
16. Upper cleaning hatch
17. Ash pan cleanout
18. Cooling coil (optional)
19. Sleeve of STB sensor
20. Sleeve of boiler temp. sensor
21. Sleeve of flue gas temp. sensor
22. Lambda sensor case
23. Pressure equalization conduit
24. Ventilator
25. Sleeve of Feeder temp. sensor
26. Ash drawer
27. Deflector
28. Swirlers
30. Control module
31. Display
32. Switch
33. Fuse
34. STB
35. Ventilator electrical connection
36. Feeder electrical connection
37. Ignition electrical connection
38. Feeder temperature sensor
39. Sensor of mixer 2
40. Hot Tap Water Sensor
41. Fumes sensor
42. Hot tap water pump (CWU)
43. Mixer pump 2
44. Mixer pump 1
45. Boiler socket
46. Mixer 1
47. Mixer 2
48. Central heating pump (CO)
49. Circulation pump
50. Return sensor
51. Weather sensor
52. Sensor of mixer 1
6
8. Basic dimentions of the boiler SEG/SEG
PLUS (USER/INSTALLER)
ATTENTION!
Feet are present on boilers:
- from SEG 14 to SEG 38
- from SEG PLUS 14 to SEG PLUS 38.
Their height is 30 mm.
Schematic 8.1 Boiler dimentions SEG/SEG PLUS
Tab. 8.1 Boiler dimentions (mm) SEG/SEG PLUS
TYPE SEG/
SEG PLUS - 14
SEG/
SEG PLUS - 17
SEG/
SEG PLUS - 28 SEG - 38 SEG - 50 SEG - 75
A 1250 1250 1250 1290 1443 1505
B 535 535 535 585 681 793
C 1225 1420 1480 1480 1490 1440
D 758 793 845 845 1060 1175
E 910 1105 1160 1160 1110 1115
F 347 356 409 409 536 545
G 1 1/2” 1 1/2” 1 1/2” 1 1/2” 1 1/2” 1 1/2”
H 3/4'' 3/4'' 3/4'' 3/4'' 3/4'' 3/4''
I 180 180 180 180 220 220
J 1 1/2” 1 1/2” 1 1/2” 1 1/2” 1 1/2” 1 1/2”
K 213 247 245 245 337 350
L 213 207 205 205 190 175
M 680 680 680 680 680 680
N 693 716 765 765 850 850
O 125 125 125 125 175 220
P 865 905 954 954 1218 1413
R - - - - - -
S - - - - - -
T - - - - - -
U 338x158 338x198 338x198 388x198 488x198 600x264
7
9. Technical specifications SEG/SEG PLUS (USER/INSTALLER)
Tab. 9.1 Technical specifications SEG/SEG PLUS
PARAMETERS UNIT
TYPE OF BOILERS
SEG/
SEG PLUS – 14
SEG/
SEG PLUS – 17
SEG/
SEG PLUS – 28 SEG – 38 SEG – 50 SEG – 75
Nominal thermal output (coal) [kW] 14 17 28 38 50 75
Boiler power range [kW] 4,2-14 5,1-17 8,4-28 10,5-38 15-50 22,5-75
Heating surface [m2] 2,1 2,54 2,85 3,11 5,41 6,75
Boiler water capacity [L] 60 68 73 95 120 173
Maximum working pressure [bar] 3 3 3 3 3 3
Maximum working temperature [°C] 95 95 95 95 95 95
Test pressure [bar] 4,5 4,5 4,5 4,5 4,5 4,5
Boiler class [-] 5 5 5 5 5 5
Boiler efficiency [%] ≤90 ≤90 ≤90 ≤90 ≤90 ≤90
Single fuel load [L] 190 290 350 350 400 520
Fuel [-] eco-pea coal
Power supply [-] ~230V; 50Hz
Electrical power consumption during boiler work at
nominal power [W] 350 350 350 350 400 400
Electric- power consumption (temporarily
maximum) [W] 1050 1050 1050 - - -
Temperature controller setting range [°C] 60-85 (1 at a time)
Required chimney flue [pa] [Pa] 20 23 23 35 38 40
Flow resistance δT [10k] [mbar] 5,47 7,03 12,33 29,83 60,88 136,98
Flow resistance δT[20k] [mbar] 1,19 1,75 3,8 7,45 15,47 34,24
Boiler weight [kg] [kg] 448 510 535 551 785 935
8
10. Control and safety (USER/INSTALLER)
1) Automatic control of the boiler can adjust:
boiler temperature
temperatury w obiegu centralnego ogrzewania C.O.1,C.O.2 ;
hot water temperature
room temperature
temperature of return water from central heating (boiler exchanger protective feature)
ignition time (depending on type of fuel)
fuel feeder operation time
feeder and vent manual control time
automatic burner power modulation (fuzzy logic)
automatic air feed (lambda sensor module)
2) Temperature sensor
The STB mechanical protection is situated inside the boiler and prevent the heating system
from overheating. it is set by default at 95oC. if temperature exceeds 95, the vent is turned off. at
the same time central heating hot water pumps come on and the mixer valve opens.
3) Fuzzy Logic control (advantages):
advanced algorithm
reduces fuel consuption and lowers the amount of sooth and contamination in the boiler
enhanced boiler working temperature stability- eliminates condensation in the boiler
(sweating of the boiler)
combustion chamber temperature is high and stable which lowers carbon oxides
emission.
4) Lambda sensor
The sensor continiously adjusts the amount of air in order to provide the most efficient
operation of the boiler and minimise the carbon oxide emission under the given boiler load, fuel
type and weather conditions.
5) Fumes temperature sensor
The sensor is situated in the boiler flue. it allows to control the fumes temperature. if the
temperature exceeds 250 oC, the vent automatically shuts down until the combustion
temperature drops.
6) Mixing valve acutator x2
With this device you can adjust the set heating circle temperature in the central heating
system, keeping the constant boiler temperature. The temperature is calculated from the heating
curve in relation to the outside temperature
11. Fuel (USER)
The default fuel of boilers equipped with a screw feeder or retort or BIO burner is:
1) Grade II class a1 hard coal compliant with section 5.3 (Table 7) of standard PN EN 303-
5:2012 calorific value: > 26MJ/kg; moisture: 11% in working condition;
ash content: 2 - 7 % in working condition of mass in dry state;
volatile element content: 15 -30% in working condition of mass in dry state;
The fuel should be clean and not contain rocks, pieces of wood etc.
12. Requirements for the boiler room and
boiler installation (USER/INSTALLER)
In Poland, all the soild fuels boilers should be made in accordance with PN- 87/B-02411 Norm
„Soild fuels boilers”. The have been divided into two categories.
1) For small boilers under 25 kW, the following requirements should be met:
the boiler should be placed in the central position to the heated rooms and in a seperate
room.
the floor surface should be inflammable. If the floor is flammable, it should be covered
with steel metal sheet of 0,7 mm thickness and exceed the boiler contour by at least 50
cm. the boiler should be placed on inflammable base of 0,05 m above the floor and
secured by steel angles.
the boiler room can be lit naturally as well as artificially.
the location of the boiler in the room should enable free access to the boiler during
cleaning and maintenance works. The distance between the back of the boiler and a wall
should be at least 70 cm, the side of the boiler and a wall should be at least 100 cm and
the front of the boiler and a wall opposite should be at least 200 cm;
the height in a new building should be at least 220 cm. in old buildings the the boiler room
should be at least 190 cm high as long as the ventilation inside is sufficient (supply-
exhaust ventilation)
supply ventilation should be provided by an open slot of 200 cm2 in diameter and placed
up to 100 cm over the floor surface.
the exhaust ventilation should be provided by an exhaust duct of 14 x 14 diameter and
made from noncombustible material. Its outlet should be installed under the ceiling of the
boiler room. The exhaust duct should lead out over the roof and placed in the close vicinity
of the chimney. No shut down equipment can be installed on the duct.
2) Boiler rooms of heating power greater than 25kW should meet extra requirements, such
as:
the distance to the far-most chimney, at gravitional draught, cannot exceed 50 cm of the
chimney height.
9
the fuel and slag store should be located by the boiler room. The storing height up to 220
cm with a 50 cm free space above it.
the equipment for vertical and horizontal delivery of the fuel and slag should be
considered.
the fuel store should be equipped with natural ventilation that allows for full airing once an
hour in the fuel store and three airing circles an hour in the slag store.
the entrance door to the boiler room should be fire- resistant (0,5 class of fire resistance),
the minimum width 80cm and should open outside. the door should have a handle- free
system when opened from the inside and have a door handle when coming inside
the requirements for the ventilation are the same as those for the boiler rooms of lower
power; additionaly, in the boiler rooms of power greater than 400 kW, the supply exhaust
ventilation should be accompanied by mechanical ventilation that can be periodically
activated when feeding the fuel and removing slag. it must also be able to provide 10 airing
circles an hour
natural lightning which can light the front of the boiler should be considered in the room.
the total surface of the windows should equal at least 1/15 of the floor surface; half of the
windows in the room should open; the electrical lightining and electrical socket of max. 24
V should also be located in the room
inspection chamber that will allow cooling water should be located in the floor; its capacity
should equal the water capacity of the biggest boiler but not exceed 2m3
in the boiler room all the heating pipes should be insulated
The placing of the boiler together with the minimum distance requirements is presented in
the boiler room (Schematic 12.1)
ATTENTION!
The mechanical exhaust ventilation should not be used in the boiler room
ATTENTION!
Correct fresh air infeed to the boiler room will ensure efficient fuel burn.
ATTENTION!
Ensure that the carbon dioxide level in the room is not too high.
ATTENTION!
For more information on boiler room construction, refer to the 12.03.2009 Minister
of Infrastructure Law.
TIP!
The rules included in the law serve only as guidelines which must be verified as the
law is amended.
Schematic 12.1 Minimal requirements for the boiler room
10
13. Instructions of deflector installation in
SEG boilers (14kW, 17kW, 28kW, 38kW) (USER/INSTALLER)
1. Insert the support rods into the boiler by resting them on the brackets situated on the boiler’s
interior side walls.
2. Place the deflector’s ceramic elements on them in such a manner that the oval recesses rest
on these rods.
3. Position the entirety directly above the burner's furnace
Schematic 13.1 Deflector's position above burner’s furnace.
14. Boiler installation (USER/INSTALLER)
The important element of installation is correct setting and levelling of the SEG and SEG PLUS
boilers. The boilers do not require special base and need to be leveled with adjustable feet. The
boiler must be set in the vertical position.
1. Check that four adjustable feet have been provided
2. Level the boiler in relation to the floor (if the position of
the boiler is level, there is no need for the feet)
3. Place the feet into the dedicated slots.
4. Level the position of the boiler.
ATTENTION!
If the boiler is not levelled properly it can be damaged.
ATTENTION!
The boiler must not be placed in a damp and wet room as the enhanced corrosion
process will shortly damage the boiler.
ATTENTION!
The adjustable screws in the boilers are:
SEG 14 - 38
SEG PLUS 14 - 38
11
The boiler must be placed on a flameproof pad that exceeds the boiler outline by 2 cm. if the
boiler is located in the basement, it is recommended that it is placed on a base of at least 5 cm
thick. The bearing of the floor and the fire hazard conditions are the key elements of choosing the
right location for the boiler i.e:
• 20 cm - from any flammable materials
• 40 cm - from any flammable materials of C3 flammability
• 40 cm - from any flammable materials of unknown flammability
Tab. 14.1 Flammability of construction products:
Flammability of construction
products: Construction products
A - noncombustible Sandstone, concrete, bricks, fire-resistant plaster,
(concrete/ cement) mortar, tiles, granite
B - difficult to ignite Wood- cement boards/beams, fibreglass, mineral
insulation
C1 - difficult to ignite Beech wood, oak wood, plywood
C2 - normal combustibility Pine, larch and spruce wood, corck, plank boards,
rubber floorings
C3 - Easily ignited Asphalt plywood, celluloid compound, polyurethane,
polystyrene, polyethylene, plastics, PVC
15. Connecting the boiler to the heating
system (INSTALLER)
The connecting of the boiler to the central heating system should be contracted to a producer-
certified company. This procedure should be confirmed in the warranty card which is attached to
this manual. The boiler must be connected according to the manufacturer’s guidelines and this
manual.
ATTENTION!
It is recommended for first start-up of the boiler to be performed according to
the guidelines given in the Operation and Maintenance Documentation, by a person
holding a valid license - (Information concerning persons licensed to start up the
boiler is available from the Manufacturer - tel. +48 85 711 94 56).
ATTENTION!
The temperature of the return water from the central heating boiler should not be
lower than 45C.
ATTENTION!
It is required that the boiler is connected to the heating installation by a four- way
valve.
The schematics of the connecting the boiler to the heating installation meet the PN- 91/B-
02420 requirements.
12
Schematic 15.1 Connecting the boiler to the heating system diagram
Tab. 15.1 Symbols applied in the schematics
Designation Key
RO Deaeration pipe
RW Expansion pipe
RS Signal pipe
RP Spill pipe
RB Safety pipe
T1 Temperature
P1 Pressure
Schematic 15.2 Connecting boilers to the heating system diagram
Tab. 15.2 Symbols applied in the schematics
Designation Key
T Temperature sensor
Tk Boiler temperature sensor
Tz Outside temperature sensor
Tcw Hot tap water temperature sensor
Tco Central heating temperature sensor
Tpw Return water temperature
Tpod Feeder temperature sensor
13
Schematic 15.3 Connecting the boiler to the heating system
Figure description:
1. Outside the building
2. Expansion vessel
3. Room regulator
4. Mixer
5. Heater
6. Heating circle
7. Floor heating
Schematic 15.4 Connecting the boiler to the heating system with Laddomat and buffer
8. Central heating pump (CO)
9. Hot tap water pump (CWU)
10. Circulation pump
11. Additional pump P3
12. Block
13. Laddomat
14. 1,2,3,4 heating circle pumps
15. Thermostat mixing valve
14
16. Connection of boiler to heating
installation in closed-loop system
(additional option) (INSTALLER)
ATTENTION!
The central heating system in the open system must meet the requirements set in
the PN-EN 12828:2006 norm- Heating systems in buildings and the PN-EN 303-
5:2012 Solid fuel boilers with manual and automatic feeding.
When installing the boiler in the closed system, it is important to use elements that prevent
overheating, excessive increase of pressure and use the controller of temperature during burning
process.
In the SEG and SEG PLUS boilers, there is a copper coil that is installed inside the boiler
exchanger. The coil is made from ribbed copper pipe.
Schematic 16.1 Safety schematics of the boiler with the cooling coil and thermal protection
Tab. 16.1 Examples of devices enabling heating systems protection
Part Description
STB Safety temperature stop with manual return to start position
Cooling coil Cooling coil cools the system when the temperature exceeds
97C
BVTS Valve
BVTS valve prevents the flame from returning back into the
solid fuel feeder through flooding the fuel in heightened
temperature situation.
Pressure expansion tank Preventing heightened pressure
Safetly fixtures It includes safety valve, manometer and deaerator
ATTENTION
The boiler installed in the closed system must be equipped with all the safety
devices listed in Tab. 16..
ATTENTION!
The cooling coil should be connected to the water system. The power supply cannot
be the pressure tank unit because it needs power supply for its operation.
The exchanger that is installed in the water coat is connected to the cold water cable, that
flows through it only when the thermal valve opens up when it exceeds the given temperature.
The water goes through the exchanger and receives the heat from boiler water coat and then is
led to the sewage system as hot water might damage it.
The exchanger is able to lower the temperature in the water coat by few degrees within
several seconds. If the temperature in the boiler coat drops below the set temperature then the
valve cuts off the water to the exchanger. In this solution, the high quality of the exchanger and
valve allows several consecutive switch off and on of the protection
In the solution with a built in safety coil e.g thermal protection is used.
The solid fuel boilers with an automatic feeding feature carry very little risk of an uncontrolled
rise in central heating temperature as the amount of the fed fuel is small. Moreover, in case of a
sudden temperature rise, the safety procedure will activate without the user.
If anything goes wrong, the controller will switch off the feeder for 30 sec in order to remove
the ember. If after 2 min from the ember removal, the feeder temperature does not drop, the
controller will try again. After four consecutive trials to reach 85oC the controller fails to lower the
feeder temperature, the boiler stops and emergency extinguishing will start.
15
Schematic 16.2 BVTS Valve
The emergency extinguisher, that prevents from combustion of fuel in the tank. Can also be
connected to the water system. In case the set temperature is exceeded, the extinguisher opens
the water valve and activated regardless of the power supply.
Thanks to the special design of SEG and SEG PLUS series boilers, the risk of flame penetrating
into the fuel dispenser is negligible and is counteracted by:
hermetic design/limit switch protection of the fuel dispenser;
device equalizing pressure between the furnace chamber and fuel dispenser
ATTENTION!
The gas pressure in the expansion vessel should be checked before use and
properly adjusted. The vessel should be inspected once a year.
ATTENTION!
The safety valve should be installed in the heat source or its closest vicinity e.g
power cable to the system in an easily accessible spot.
ATTENTION!
The safety valve should prevent the max excessing of work pressure no more than
10%
17. Requirements for the expansion vessel (INSTALLER)
Every open water heating installation should be equipped with an expansion vessel, which
receives excess water volume and deaerates the installation. The vessel should be installed in the
top-most point of the installation, and if possible, vertically above the boiler (boilers).
The capacity of the vessel should be calculated using the unit capacity for every kW of power at
1-2 dm 3.
The expansion vessel is equipped in stubs to connect a riser safety tube, safety downpipe, and
a spill pipe and - connected to it - deaeration.
The diameter of the deaeration and spill pipe should be at least
[MM]
- Boiler efficiency [kW]
The most important requirements on the operation of the device are the following:
The expansion vessel should be about 3.5% of the total water volume in the water heating
installation and boiler.
Each boiler must have a safety tube and spill-pipe.
Installation should be equipped with a signal pipe and expansion pipe, and a stub for
deaerating the expansion vessel.
In the case of several boilers, each should have its own safety pipe in accordance with the
guidelines in PN-91/B-02413. Safety and spill pipes should not have any closing valves, and the
pipes and vessel should be protected from freezing.
18. Connecting the boiler to the power supply (INSTALLER)
The boiler is designed for 230V/50 Hz voltage. Such connection should be carried out by a
certified specialist. The 230V/10A connection socket with grounding should be easily accessible.
The power supply to the boiler and room lighting should have own circuit.
The finishing and heating test should be noted in the Warranty Card. the Warranty Card
should then be sent over to the manufacturer in order for the user to be registered in the
company system.
ATTENTION!
First start-up of the boiler must be performed solely by service personnel trained by
the manufacturer, holding a current Authorized Service Technician or Distributor
certificate issued by METAL-FACH, or by a person holding an Electrician's license up
to 1.5 kW.
ATTENTION!
All the pumps, mixers, transmitters, ignition etc. are not parts of the controller
equipment.
16
Schematic 18.1 Electrical schematics for connecting the boiler– controllerPLATINUM.
Electrical connection diagram of regulator:
Panel - control panel, and additionally, ecoSTER200/ecoSTER TOUCH room panel, λ - Lambda sensor module, B - module for support of additional heating circulations, BT – CT4 boiler temperature sensor, FS
– CT4 fuel feeder temperature sensor, CWU – domestic hot water temp. sensor, RS - CT4 return water temp. sensor, M1/M2 – CT4 temp. sensor of regulated mixer’s circulation, BH- upper CT4 buffer temp.
sensor, BL- lower CT4 buffer temp. sensor, WS- CT6-P weather temperature sensor, FT- CT2S flue gas temp. sensor, TR- universal thermostat of mixer (open-close), H- outlet for control of back-up boiler or
signaling of alarms, RE- relay (12V, max 80mA) for connection of back-up boiler/alarm, DS- inlet to fuel dispenser cover flap or door opening sensor, RMP- inlet of RPM sensor, L N PE- 230V~ grid power
supply, GR – earthing strip, STB – inlet to safety temp. limiter, PO – main feeder, W- fan, PM- domestic hot water circulating pump, PCO- boiler pump charging the buffer, IG- igniter, PCW- domestic hot water
pump, SM1/SM2- mixer’s actuator, PM1/PM2- mixer’s pump, CPU- control
17
Schematic 18.2 Electrical schematics for connecting the boiler – additional B MODULE.
Schematics of electric connections – additional B MODULE,
where
M3- regulated circuit temperature sensor (mixer 3) CT4 type
M4- regulated circuit temperature sensor (mixer 4) CT4 type
RM3- mixer 3 room thermostat
RM4- mixer 4 room thermostat
FS- BU feeder fuel level sensor
H2- outlet to the back-up boiler control or alarm or hot tap water
circulation pump
Relay
L N PE- power supply 230V~
P/M ¾ - mixer pump
SM ¾ - mixer servo
BU - The fuel tank from the bunker to the tank in the boiler
CPU- control
A - ecoMAX 860P2-T controller, module A
18
19. Connecting the boiler to the chimney (INSTALLER)
Smoke flue
The flue pipes extract the fumes outside and intake air used for burning fuel. The necessary
draught depends on:
the temperature difference between the hot fumes and cold air
proper chimney height
the chimney diameter should be no less than 20 x 20 cm
chimney properties (smooth surfaces inside and outside) grout tightness
The effective height of the chimney is the difference between the highest grate and the flue
outlet. The effective height of the individual chimneys must be at least 4 m and of collective
chimneys for solid and liquid fuels should be at least 5 m. the difference between the two grates
can’t be greater than 6,5 m.
In case of sloping roofs, the chimneys should end at the ridge, in the area of free wind. It
prevents any draught brakes. Pay attention to the location of the building in relation to the
buildings around.
Choosing chimney
In most cases, choosing the right chimney is done by using an approximation method or
according to manufacturer’s recommendations. In special cases (bad pressure conditions, large
volume of fumes) the chimneys are chosen according to the PN-EN 13384-1+A2:2008 Norm.
Chimneys for solid fuels boilers
It must be noted that the solid fuel grates of nominal thermal power of >20 kW and without
vent require separate chimney.For the solid fuel grates, single-layer brick chimneys can be used.
Today, three-layer chimneys of smooth surface and good thermal insualtion are commonly used.
Flue
The boiler is connected to the chimney with a flue and smoke flue. The smoke flue consists of
pipes and fittings which are set in rooms. The smoke flues meet the requirements set in the
chimney fire hazard regulations and are often made from the same material as the main chimney.
The smoke flues should be made from non-flammable materials. The smoke flues or their
housings should meet the requirements set in the small chimneys fire test Polish Norm. It is
allowed to build the housing from solid bricks of 12 cm thickness. The bricks should be set on the
cement- plaster mortar with outer plaster or binder. The connections should be kept as short as
possible and set in the upright direction to the chimney in order to avoid heat losses and
additional resistance. They cannot be set to other rooms. The fumes pipes should not be set in
rooms where furnaces cannot be installed, moreover, they cannot installed in walls and ceilings.
Due to low fumes temperature, in order to protect the chimney from dampness and draught limit,
use the acid- resistant or ceramic chimney liners with condensate discharge to the waste drain.
The distance between the chimney and the closest tree top line should be at least 6m.
20. Boiler start-up (USER/INSTALLER)
SEG/ SEG PLUS boilers have a single combustion chamber - at the bottom with a built-in
furnace.
Schematic 20.1 Automatic boiler start-up; PLATINUM controller:
1. The first step is to switch the boiler on until “contact”
2. Controller display. The red
boiler feed switch is found in the
upper left corner, and an 8.2A fuse
is located under the switch.
3. Starting boiler feed.
To start feed to the boiler, press the red button in the “I” position, as illustrated in the drawing
above
19
If this is performed correctly, the
display will activate as in the
drawing shown here.
4. The main menu is presented
in the picture shown here.
The controller has a touch screen and is operated using a finger.
5. Manual Work Menu
After connecting all devices to the boiler (pumps, actuators, valves, etc.), it is possible to check
their work. The “Manual work” menu is used for this purpose. To enter the manual work menu,
select the manual work icon and confirm.
After following these instructions,
the menu will be displayed as in
the drawings shown here.
6. Starting the boiler
The boiler needs a dose of fuel to work. When the boiler is new, the first thing to do is to fill the
dispenser with the proper type of fuel. The feeder in Sokół boilers is a wormscrew feeder (the
worm is responsible for transporting fuel to the burner). For problem-free start-up, first “feed” the
starting dose fo fuel to the boiler's burner.
20
To do this, select the feeder in the
“Manual work” menu and press
ENTER to start it (OFF will change
to ON).
a) EkoEnergia burner
The picture shown here shows an
empty feeder (no starting fuel
dose)
When the feeder is set to ON in the Manual work menu, fuel will begin to arrive at the burner.
The picture shown here shows a
correct “heap” of fuel enabling
boiler start-up. Exit the manual
work menu when such a heap is
obtained.
7. Switching on the boiler
To switch on the boiler’s
controller, return to the main
menu. The next step is to press
the red button in order to start the
controller..
21
If this is performed correctly,
“FIRING UP” should replace “OFF”
in the upper left corner.
8. Firing up process.
The firing up process takes place as follows:
Feed time - the feeder supplies the starting dose of fuel;
Ignition test time - fan and feeder work to raise a flame from embers;
Firing up time - blower works together with igniter;
The firing up cycle has 3 attempts, and if the boiler is not fired up, “Firing up failed” will be
displayed on the screen.
The igniter’s work is illustrated by
the flame visible in the picture
shown here.
The boiler is recognized as having
been fired up successfully at the
instant when flue gas temperature
exceeds the boiler's temperature
by 10 degrees. To check the flue
gas temperature at any given time,
enter the information menu.
In the figure shown here, we see
that the flue gas temperature is
not 10 degrees greater than the
boiler's temperature, so the boiler
is working in “FIRING UP” mode.
If the flue gas temperature is 10
degrees greater than the boiler’s
temperature, the boiler enters
normal work mode, as illustrated
in the pictures shown here.
22
c) First boiler start-up.
If all of the above steps have been performed correctly, first boiler start-up can be
commenced.
Extinguishing the boiler
If you plan a longer idle period for the boiler, set the control panel in the „OFF” mode.
Re-commencing the boiler if the boiler had been stopped due to lack of fuel.
remove the carbon deposit from the burner
feed the fuel into the bin
on the control panel, set the „OFF” mode
feed the fuel into the burner with the „TEST” manual fuel stoking feature,
feed the fuel until granulate is visible at the top of the burner
set the „ON” mode on the control panel, flame should appear after few minutes
if there is no ignition, set fire by using traditional grill ignition or wood
set the blower to „TEST”
after starting fire, set the „ON” mode on the control panel.
Automatic commencing the boiler after replacing the safety clutch fuse:
remove the carbon deposit from the burner
turn the screw left and right and check if there are no „foreign bodies” e.g. stone, metal
rod. If such are present, rmove them and put on the pin
feed the fuel into the bin
on the control panel, set the „OFF” mode
feed the fuel into the burner with the „TEST” manual fuel stoking feature,
feed the fuel until granulate is visible at the top of the burner
set the „ON” mode on the control panel, flame should appear after few minutes
if there is no ignition, set fire by using traditional grill ignition or wood
set the blower to „TEST”
after starting fire, set the „ON” mode on the control panel.
ATTENTION!
Remember to close the feeder cover tightly.
ATTENTION!
Do not stand in front of the boiler when opening the boiler door as you may run the
risk of getting burn.
ATTENTION!
If the boiler is equipped with a Lambda sensor, set its parameters with a fumes
analyser during setting the blower for the following boiler powers.
21. Recommended boiler power settings (USER)
To obtain the correct, fault-free and efficient operation of the boiler, the boiler should operate
at 80% of its nominal power and temperature of 60C. It is also suggested to install a mixing valve.
Tab. 21.1 Suggested settings of GOLD II and PLATINUM controller for work with ekoenergia
burner – ecopea fuel
Power 14 17 25 35 50 75
Parameter
Burn out 20 20 20 20 20 20
Blow 15 15 15 15 15 15
Blow 100% 30 30 30 30 30 30
Feeder cycle (ON+OFF) 20 20 20 20 20 20
Feeding in cycle-ON 13 16 20 25 20 25
Initial stoking 10 10 10 20 10 10
Ignition 0 0 0 0 0 0
Blower+ Ignitor 5 5 5 0 0 0
Fire test 3 3 3 4 4 4
Initial power 60 60 60 60 60 60
Burn out 2 2 2 2 2 2
Boiler power (kW) 14 17 25 35 50 75
Blower 100% 22 22 22 25 35 40
Blower 80% 20 20 20 22 30 37
Blower 60% 18 18 18 20 25 34
Blower 40% 16 16 16 18 20 31
Blower 20% 14 14 12 16 15 28
Starting power 9 9 9 9 9 9
Burn out 12 12 12 12 12 12
Sustain power 12 12 12 12 12 12
ATTENTION!
The controller settings can be regulated depending on the variety of the existing
central heating systems, heating requirements of the bulding and calorific value of
the fuel. The boiler parameters are set by the user and it is not serviced by the
company.
23
22. Tips when using the boiler (USER)
the boiler can be operated by two adults who have familiried themselves with the manual
the presence of unsupervised children in the boiler room, or allowing them to operate the
boiler is forbidden.
ensure that the boiler is switched off during any works with flammable materials that
emimt flammable gases or fumes e.g glueing, painting etc.)
turn off the boiler before clearing out the exhaust carbon from the retort, gutter etc.( „OFF”
position)
turn off the boiler before stoking the boiler („OFF position)
do not use flammable liquids for igniting the boiler, the boiler ignites automatically
(ignition)
turn off the boiler before cleaning
do not overheat the boiler
do not place any flammable material in the close vicinity of the boiler
during ash removal, any flammable materials should be kept at a distance of 150 cm from
the boiler
the ash should be placed in heat resistant containers with a lid
if the boiler operates at the temperature lower that 60C, the steel exchanger may „sweat”
and cause corrosion that shorten the boiler life span. That is why the minimum operation
temperature of the boiler should be 60C
after the heating season is over, the boiler and the smoke duct must be thoroughly
cleaned
the boiler room should be kept tidy and dry
ATTENTION!
The boiler is not meant to be operated by persons of lowered mental or physical
independence or by persons with no experience or limited knowledge about the
product if they are not supervised or instructed by the person responsible for their
safety.
ATTENTION!
Any tampering with the boiler electronic system or boiler construction is forbidden.
23. Boiler maintenece and cleaning (USER)
ATTENTION!
Clean the boiler only when it is disconnected from the power supply.
In order to save fuel, the burner chamber as well as the convection channels must be kept
clean. The walls and the grates in the burner chamber should be cleaned through the charger and
burner doors. The boiler exchanger should also be cleaned regularly.
The convection channels and the flue should be cleaned through cleaning hatch on the boiler
flue or at the bottom in the side wall. It should be carried out with expendable metal brushes. The
boiler should be cleaned during the idle period, preferably every 100 hours. A thorough cleaning
of the boiler should be done monthly.
If the fuel is of low quality, cleaning should be done more often.
24. Istruction for utilising the boiler (USER)
Before scrapping the boiler, all the electronic elements should be removed. They should be
disposed of according to the 2002/96/WE Electric and Electronic Equipment. In order to dispose of
the electronic elements you should contact the manufacturer.
The steel elements the boiler is made from should be scrapped in the dedicated locations
(scrap yards).
ATTENTION!
The boiler and its elements should not be disposed of together with other waste.
25. Spare parts list (USER/INSTALLER)
Tab. 25.1 Spare parts
Spare parts Article
Sensors Sensors
Temperature sensors for GOLD
Boiler sensor
Feeder sensor
Return sensor
Central Heating Sensor
Hot Tap Water Sensor
Outside sensor
Fumes sensor
Photo sensor
24
Spare parts Article
Temperature sensor for PLATINUM
Boiler sensor
Feeder sensor
Return sensor
Central Heating sensor
Controllers GOLD Regulator
PLATINUM Regulator
STB Thermal protection
Ignition Ignition 700W
Sensor Lambda sensor set
Lambda sensor case
Fan RMS-108 Fan
RMS-120 Fan
Feeder Motoreducer with engine 1 rpm
Motoreducer with engine 3 rpm
Motoreducer with engine 1 rpm
Motoreducer with engine 1 rpm EkoEnergia
Motoreducer with engine 2 rpm EkoEnergia
Feeder motor 0,09 kw
Feeder motor 0,18 kw
Feeder motor 0,09 kw EkoEnergia
Feeder motor 0,18 kw EkoEnergia
Feeder screw 800 mm
Feeder screw 890 mm
Feeder screw- other size
Feeder screw EkoEnergia 25 kw
Feeder screw EkoEnergia 35 kw
Feeder screw EkoEnergia 50 kw
Feeder screw EkoEnergia 75 kw
Burner safety pin M5x60, class 8,8
25 kw EkoEnergia boiler feeder
35 kw EkoEnergia boiler feeder
50 kw EkoEnergia boiler feeder
75 kw EkoEnergia boiler feeder
Oprzyrządowanie Capillary for fumes sensor
Electric bundle
Ventilator, feeder, ignitor socket
Rubber loop
Power switch
Fuse nest
Fuse
Interface transmitter
Bin sealing
Spare parts Article
Eye-hole sealing
Door sealing
Feeder sealing
Door handle
Side sheet metal 1 pc.
Top shhet metal 1 pc.
Door 1 pc.
26. Possible faults and malfunctions (USER)
Before calling the helpline read the FAQ section of the manual.
ATTENTION!
Please remember that in the case of unnecessary customer support, the customer
covers the costs of calling and work of the support unit (price list available at
www.metalfachtg.com.pl).
You can also report problems online: www.metalfachtg.com.pl/zglos-problem-online.
Infoline: Paweł Czepiel
(Russian, English)
mobile +48 663 453 222
e-mail: [email protected]
25
Question Answer Explanation
How long can the boiler
operate on full tank?
There is no simple answer. It can be assumed that the boiler
can operate for 3-4 days.
The continuous burn time depends on:
fuel calorific value
heating insulation of the building
kind of installation i.e. floor heating, radiators, boiler
boiler exchanger cleanliness, amount of ash in the ash tray
outside temperature
inside temperature
combustion quality
What is the lowest
temperature of the boiler?
The higher the temperature the better but the lowest
temperature should not fall below 60oC.
The boiler should be adjusted in the way so that when the boiler temperature is 60oC, the fumes
temperature is 140oC. It ensures the best efficiency of the boiler. At such temperatures, the boiler will not
„sweat” and get wet as there is no fumes gas condensation
What is the minimum return
temperature?
The recommended return temperature is 10oC lower than
the feeding temperature.
In practice, without any mixing valves or other mixing devices it is impossible. It is recommended to install a
four-way valve to make the boiler operate on short circulation at high temperature and the installation on
any set temperature. The protection of the boiler is still in place and equals the boiler feeding temperature.
How is the boiler protected
against freezing?
The boiler is protected against freezing with the controller
software.
At the temperature below 8oC, the controller opens up the mixing valve and turns on the central heating
pump in order to prevent the water in the installation from freezing. Additionally, all the pipes that are
exposed to heat loss should be extra insulated. Check if all the windows in the vicinity of the piping are
complete and shut and there are no holes in the walls etc.
What are the GOLD controllers
working modes?
The GOLD controllers have three working modes. Summer- heating up the tap water.
Manual- heating up the tap water and feeding the central heating. In this mode, set the temperature on the
boiler and the heating circulation.
Weather- heating up the tap water and the central heating. In this mode, the controller calculates the set
temperature for the boiler and heating circulation.
Why is there grime in the
boiler?
There are few conditions in which grime collects in the boiler
e.g. wet fuel, bad combustion conditions, oversized boiler,
low boiler temperature.
In the first case, the wet fuel produces low fumes temperature causing fumes condensation. In such case,
not only does the boiler get dirty but the chimney as well.
In the second case, it is usually caused by insufficient amount of air in the combustion chamber. It is
enough to let in some more air and the flame with gases will burn completely.
In the case of an oversized boiler, the temperature is reached very quickly making the boiler idle and the
fumes gases burn out causing grime collection. The worst scenario is when the temperature is too low. If
the boiler is not connected properly, it becomes a thermostat, which means that if you want to lower the
temperature in your house, you need to lower the boiler temperature. It is recommended to install mixing
valves.
What to do when the water in
the boiler boils?
Do not panic. Nothing serious usually happens. The reason
for that might be lack of heat reception, open ash tray door,
feeding easily burnt materials e.g. paper.
In such case, when the temperature exceeds 90oC, the controller activates all the pumps (even the ones
that are switched off) and opens up the mixing valve in order to cool down the boiler. If the door is open
please close it. It is essential not to let cold water into the installation as it may cause an explosion.
What is a heating curve? Heating curve is an outside temperature graph in relation to
the central heating water temperature. The heating curve is a
calculated heating temperature in relation to the outside
temperature.
The heating curve graph is included in the controller manual.
The blower fan is not working? The blower fan is not working because it might be unplugged.
The boiler has overheated and STB protection has
intervened.
Put the blower plug back in. After the boiler has cooled down, press the STB button.
26
Question Answer Explanation
Is it allowed to fill up the
installation with water while
the boiler is working?
Filling up the installation while the boiler is working is
absolutely forbidden.
Letting water into the boiler runs the risk of unsealing the boiler and installation. If the boiler is overly
heated it may unseal and crack.
In the case of an oversized boiler, the temperature is reached very quickly making the boiler idle and the
fumes gases burn out causing grime collection. The worst scenario is when the temperature is too low. If
the boiler is not connected properly, it becomes a thermostat, which means that if you want to lower the
temperature in your house, you need to lower the boiler temperature. It is recommended to install mixing
valves.
Is it advisable to install a four-
way valve?
Yes, it is advisable to install a four-way valve. A four- way valve is a very useful device which:
protects the boiler against low temperature corrosion, mixes the infeed water with return so as to
achieve a stable agent for the central and floor heating
enables smooth temperature control by an actuator, saves fuel, protects the boiler from corrosion and
prolongs boiler life span.
What is central tap water
priority?
The central hot tap water priority is a controller feature that
heats up the hot tap water vessel and then activates the
central heating.
The feature is used in hot tap water consumpiton conditions.
What is hot tap water
decontamination?
It is a feature of the controller that heats up the tap water
tank to 70oC in order to decontaminate it.
The feature kills the Lagionaella bacteria in the central tap water circuit. If the water in the tank is kept
below 50oC, the bacteria settles. The situation is possible to take place when the tank temperature is kept
below 50oC or when the taps are rarely open.
What is the anti-lock? Antilock feature works only with pellet. The main purpose of the device is to keep the heat in the furnace. If the boiler shuts off after reaching the
required temperature then, provided the temperature does not fall, the antilock ativates for 5-10 seconds
every 20 minutes. The antilock can be set according to the preferences and boiler power. Usually, it is set
for 5 seconds.
The feeder engine is working
but not stoking.
The engine is working but not stoking because the pin is off
or the feeding screw is worn off.
Replace the pin.
Replace the feeding screw.
What fuel can I use in boilers
with a gutter feeder?
You can use different fuels thanks to three working modes. Mode 1- eco- pea.
Mode 2- pellet as well as grain, seeds or fine wood chips of low granulation.
Mode 3- grate- wood and coal. If you use eco-pea or pellet, you can simultaniously use the upper grate by
gradually adding wood or coal.
The feeder does not work and
the engine is humming.
The feeder does not work and the engine is humming
because it is probably blocked and the pin is off. Another
reason might be that the engine capacitor is worn off.
Open the cleaning hatch door, remove the „foreign body” e.g. a stone.
Replace the engine capacitor.
The feeder engine is
overheating.
The feeder engine is overheating because the capacitor is
worn off.
Replace the engine capacitor.
Why is the pin off? The pin is off because the pellet granulation is different than
recommended, there are too much saw dust in pellet. The
fuel might be wet or there is sinter in the burner.
Change pellet.
Dry off the fuel.
Clean the burner.
Why is the fuel burning in the
boilers with automatic
feeding?
It is due to bad feeding times. Blower settings are wrong. Adjust fuel feeding and/or the blower (see the setting table).
Call the helpline.
Why is there sinter on the
burner?
Sinter is made by excessive air infeed. Regulate the blower operation.
What does alarm mean –
excessive flue gas temp. ?
Clean boiler means that the boiler's exchanger may be dirty.
Flue gas temperature greater than 280oC.
Clean the boiler's exchanger.
Reduce fuel feed
27
Question Answer Explanation
Why does the unburnt pellet
fall into the ash tray?
Because the pellet feeing rate or ventilation are too big. Lower the feeding by 2-3% and check for improvement, if necessary, repeat the procedure.
Lower the ventilation by 2-3% and check for improvement, if necessary, repeat the procedure.
What does the „feeder
overheat” mean?
The overheated feeder can mean that the fuel bin door is
open.
The seal under the bin is broken.
The cleaning hatch seal is broken.
The seal between the burner and feeder pipe is broken.
Loose screws on the connections of the basket between the
feeder and burner.
Close the fuel bin door
Replace the seal under the bin door.
Replace the seal under the basket.
Replace the seal.
Tighten all the screws.
What does the „boiler
overheat” alarm mean?
The boiler overheats when the temperature exceeds 90oC
(usually when the upper grate is in operation).
The hold time is too short.
Cool down the boiler, remove the fuel if necessary.
Increase the hold time.
What does the „fumes sensor
damaged” alarm mean?
It means that the fumes temperature has exceeded 250oC.
The fumes temperature sensor is broken.
Lower the fuel feeding. If the fuel is burnt on the burner and grate simultaniously, feed less fuel to the
grate.
Replace the fumes temperature sensor.
Smoke coming from the boiler
door.
It means that there is no draught. Tighten wall in the connection between the flue pipe and the chimney.
Check if the patency of the chimney, and its parameters are as recommended by the manufacturer.
Seal the outlet of the boiler to the chimney vent, preventing the suction of cool air.
If the chimney diameter is too small, you can install an extraction fan.
There is water coming from
the convection channels.
The fuel used is wrong or the humidity is too high.
Combustion temperature is too low.
Too little air feed.
Fumes throttle is closed.
Controller is set incorrectly.
Use fuel of proper energy value and humidity.
Open the air throttle.
Open the fumes throttle.
Set the controller right.
During the initial start-ups the
boiler „sweats”.
It is due to condensation. Heat the boiler above 80oC and keep this temperature for at least 6 hours. If necessary, repeat.
Why is the fuel combustion so
rapid?
The chimney diameter is too big.
Air flow is too high.
Controller set is incorrect.
Close the throttle on the flue.
Check the sealant on the door.
Regulate the airflow.
Regulate the controller or call the helpline.
What features does the
microprocessor regulator
have?
The controller provides:
automatic ignition
weather control
room control (room temperature)
central tap water pump regulation
clock regulation of the circulation pump, additional
pump, burner (boiler operation time)
extinguishing
control via Lambda sensor.
28
27. Operating requirements (USER)
The assembly and disassembly of the feeder and its elements should not be forced. No
pressure and vibrations are allowed and the whole unit should be carefully levelled. The
connecting surfaces should be smooth and clean. A long-lasting overload, which is prevented by
the pin, is not allowed. The feeder must be disconnected from the power line before performing
any maintainance and cleaning.
TIP!
The fuel feeder room should be well ventilated and free of intensive heat sources
(radiators, electric fires etc.) in its vicinity. The temperature in the room should not
be lower than 0C and not exceed 40C.
28. Installing the feeder in the boiler and
start-up (INSTALLER)
ATTENTION
The installation of the feeder should be performed only by a certified company
specialising in assemby and maintenance of electric systems. Any installation works
performed by an unauthorised persons releases the manufacturer from lability and
warranty.
During connecting the feeder to the boiler, ensure that:
the screw shaft is well-levelled
all the screws are tightened to prevent any loosing-up
put the plug into the socket located at the bottom of the boiler
during installing the multi-fuel burner, secure the mounting plate with heat- resistant
silicone of resistance of 1250C.
29. Installation and replacing the overload
clutch arrester (USER/INSTALLER)
The EkoEnergia burner does not require any specialist operation. It is a self-operating device
which feeds the fuel to the burning area. In case of fuel of too big grains or containing too much
unwanted waste the 125 Nm torque limiting screw might fall off and damage the motoreducer. In
such case the warranty is void.
ATTENTION!
Replacing the pin does not fall under the warranty and can be performed by the
user following the manual. Replacing the pin does not make the warranty void.
Before replacing the pin make sure that the boiler is disconnected from the power
line and all the works must be done carefully and precisely.
The arrester for the overload clutch that limits the torque to 125Nm is a screw with cylindrical
head and DIN 6912 M5 X 50 hexagonal nest of 5.8 mechanical properities class. There are 3 pins
delivered with the motoreducer.
Protection element (locking screw)
1. Remove the plastic cover from the mechanism
29
2. Remove the protection element from the
motoreducer
3. Clean the element from any dirt and residues left
by the locking screw
4. Insert a new protection element
5. Secure the screw with a nut
6. The protection element has been installed
correctly
7. Put the plastic cover back on
30
30. Feeder operations (USER)
ATTENTION!
The settings must not be corrected more than 5-10% at a time in order not to spoil
the correct settings.
During the feeder operation, pay special attention to:
-the amount of air that is supplied by the blower should be correlated with the fuel
combustion rate
-monitoring the condition and look of the fire in the furnace:
o red, smokey flame means that the air infeed is too low
o bright, white flame means that the air infeed is too high
o the correct flame should be clean of bright yellow colour
31. Feeder operation manual (USER/INSTALLER)
The weekly activities that should be performed on the feeder
open the inspection door to check on the flame
from time to time, remove ash. If ash settles excessively too often you need to correct the
proportion of the fuel mass to the air infeed. If correction does not work, check if the type
of the fuel you use has right properties
check the fuel level in the feeding chamber
clean out the pipe of any pellet or biomass, empty the bin, clean the funace, blow through
the burner, unscrew the blower, remove the ash
dismount the motoreducer with the screw by removing the safety pin to disconnect the
screw from the motoreducer
to prevent the elements mentioned above from seizure, grease the screw pivot and the
motoreducer sleeve with some bearing gease.
During any works with the feeder, remember that there are particularly dangerous spots
such as the chamber under the bin and rotary screw shaft by the reducer.
ATTENTION
You may hurt yourself seriously if you do not operate the feeder properly.
ATTENTION
If the feeder is not disconnected from the power supply, during weekly activities, it
may activate itself automatically.
32. Feeder mantenance (USER)
You should periodically clean the feeder from dust, fuel remains or ash. Clean the engine
chassis regularly. The reducers are filled with synthetic oil that ensures their performance during
the operation period so you need to clean it on the outside.
ATTENTION
Do not use any solvents when cleaning as they may damage the seals and ring
gaskets. Any maintenance works on the engine should be performed according to
the Operation and Maintenance Documentation guidelines.
33. Replacing the ignition (USER/INSTALLER)
ATTENTION
Before replacing the ingnitor disconnect the boiler from power outlet by unplugging
it from the socket.
1. Disconnect the ignition power cabel.
2. Unscrew the lock nut.
31
3. Unscrew the ignition mounting screws.
4. Carefully remove the broken ignition.
5. Install the new ignition.
6. Tighten all the screws and connect the power cable.
Check if the device works.
34. Disposal of EkoEnergia burner after its
lifespan (USER)
All the information about the disposal of the trough burner after its lifespan is included in the
chapter „Disposing the trough burner after its lifespan”.
32
35. Possible disruptions in work of ekoenergia
burner (USER)
Tab. 35.1 Examples of ekoenergia burner failures
Failure Possible cause Method of repair
Burner does not activate
No power or boiler controller
switched off
Check the power feed and
master switch of the electronic
controller
Motoreducer’s fuse activated Check and replace if necessary
Overload relay tripped Reset overload relay
Motor’s thermal breaker
switch activated
Check the breaker switch and
determine the cause of its
activation
Worm feeder is empty (no
fuel)
Overload relay tripped Reset overload relay
No fuel in dispenser or fuel
suspended above feeder
Check level of fuel in dispenser
and above holes for fuel
intake
Worm coupling decoupled
from motoreducer
Replace coupling insert and
recouple the coupling
The feeder's worm does not
turn in the burner despite
work of motoreducer
Motoreducer’s fuse activated Check and replace if necessary
Worm coupling decoupled
from motoreducer
Replace coupling insert and
recouple the coupling
Worm not cleaned before end
of boiler work
Remove the worm, clean it,
notify the manufacturer
Frequent shearing of wedge
securing the worm occurs
Unstable fastening of
motoreducer’s bracket to
substrate
Correct this and ensure
permanent fastening
Poorly centered motoreducer
bracket relative to worm
Check axiality of installation
and center if necessary
Smoke is rising from the
dispenser
A leak of the entire system is
present
Check whether the feeder's
cover flap is closed tightly,
Check the seals and bolts of
the feeder and the burner,
tighten loose elements if
necessary
Singed end of worm in retort Improper combustion
regulation
Adjust to correct burning in
the boiler according to boiler's
instruction manual
ATTENTION!
Following these instructions extends the time of reliable feeder work. Information
about potential factory defects must sent immediately after their detection,
preferably in writing.
ATTENTION!
The manufacturer reserves the right to implement any construction changes during
modernisation of the product.
33
Warranty conditions
(USER) User’s Declaration: I hereby declare that the boiler (hereinafter also referred to as the “appliance”) has been delivered
to me as per my order, new and complete. The Seller has familiarized me with the appliance’s operation and provided a complete set of documentation (including, in particular: Operation and Maintenance Documentation including, among other things, instructions for installation and use of the appliance, guarantee terms). I take note of the manufacturer’s recommendation to conduct annual technical inspections of the appliance, which are to be confirmed on the guarantee card.
……………………………………………………………. Date and legible signature of the User
Scope of the guarantee: 1. Liability arising from the guarantee covers only defects resulting from causes present in the
appliance at the time of its issue to the User. 2. A guarantee on the appliance is granted by the manufacturer (also referred to as the
"Guarantor”): Jacek Kucharewicz, conducting economic activity under the company name Metal Fach Jacek Kucharewicz, 16-100 Sokółka, ul. Sikorskiego 66, NIP (Taxpayer Identification Number): 545-100-10-62, REGON 050073833, telephone +48 85 711 94 56).
3. Under the guarantee, the User obtains the right to free repair of the appliance if defects of the appliance are revealed during the guarantee period. In the event where the Guarantor determines that it is impossible to repair the appliance or part thereof, the Guarantor reserves the right to replace the appliance or part thereof with a new one.
Guarantee period: On the appliance (boiler) – 2 years from the date of sale, but no longer than 36 months from the
date of its production, with the exception of: a) the exchanger – the guarantee on which has a duration of 5 years from the date of sale; b) moving parts, cast iron, mechanical parts, parts of the worm, igniter – the guarantee on which
has a duration of 1 year from the date of sale; c) consumables (e.g. sealing cord, seals, vermiculite, chamotte), electrical components, bolt
securing the worm’s clutch, pins – which are not covered by the guarantee. Terms of exercising rights under the guarantee: 1. Installation of the appliance according to the Operation and Maintenance Documentation
(particularly connection of the boiler to a properly built installation, performance of first start-up according to the guidelines of the appliance’s manufacturer, application of devices protecting the boiler against return of cold water (four-way valve with actuator, laddomat, etc.)
2. Sending a copy of the guarantee card, properly filled out, signed and sealed by the Seller, to the Manufacturer’s address within 30 days from the date of the appliance’s sale
3. Presentation of the guarantee card, properly filled out (signed and sealed by the seller), at the time of filing a claim, along with proof of the appliance's purchase (e.g. receipt, invoice). In the event of the User’s loss of the guarantee card, a duplicate will not be issued.
4. Adherence by the User to the guidelines given in the appliance’s Operation and Maintenance Documentation.
5. Performance of first boiler start-up within 6 months from the date of the appliance’s installation by the fitter in accordance with the guidelines given in the Operation and Maintenance Documentation, by a person holding a valid license to do so (Information concerning persons licensed to start up the boiler is available from the Guarantor - +48 85 711 94 56), confirmation of this fact in the guarantee card, and submission of a start-up report to the Guarantor. First boiler start-up is a paid service, and its cost is covered by the User.
6. Performance of annual inspections of the appliance according to the guidelines given in the Operation and Maintenance Documentation, by specialized companies holding the relevant licenses (a list of examples of specialized companies is available from the Manufacturer - telephone number
7. +48 85 711 94 56), and recording of their performance on the guarantee card. Inspection of the appliance is a paid service.
8. Performance of maintenance of the appliance (e.g. adjustment, cleaning, measurement of the appliance, analysis of flue gas) by specialized companies holding the relevant licenses (a list of examples of specialized companies is available from the Manufacturer – telephone number +48 85 711 94 56), according to the guidelines given in the Operation and Maintenance Documentation, and recording of maintenance services on the guarantee card. The User may report a need for intervention by service technicians to the Guarantor (Infoline +48 858 880011, www.metalfachtg.pl/zglos-problem-online). The maintenance service is a paid service.
9. Performance of guarantee repairs solely by specialized companies holding the relevant licenses (a list of specialized companies is available from the Guarantor - tel. +48 85 711 94 56), and recording of their performance on the guarantee card.
10. Use of spare parts and consumables meeting the manufacturer’s specifications. It is recommended to use original spare parts.
11. The guarantee covers the territory of the Republic of Poland. The guarantee does not cover defects of the appliance arising from: 1. Failure by the User to adhere to the conditions specified in the Operation and Maintenance
Documentation and the instructions given therein concerning transportation, installation, operation, use and maintenance of the appliance;
2. Improper storage and transportation by the User; 3. Damage to subassemblies of the appliance due to the application of improper electrical voltage
by the User. In the case of direct or indirect power supply to the appliance from power generators, UPS systems or devices, the User should consult the specifications of power supply devices with the manufacturer;
4. Defects of the appliance caused by a defective heating installation connected to the appliance; 5. Overheating of the boiler by the User; 6. Connection, by the User, of the boiler to a closed-loop system without the application of the
appropriate cooling device. 7. Application by the User of improper fuel or fuel of poor quality; 8. Independent modification of the appliance by the User.
34
Claim procedure:
1. In the event where improper work of the appliance is detected, prior to filing a claim, make sure that all steps were taken according to the Operation and Maintenance Documentation.
2. The User should report the need to repair the appliance under the guarantee without delay, preferably within 7 days from the date on which the defect is detected. A claim may be filed directly to the Seller or Guarantor (Infoline +48 858 880011, www.metalfachtg.pl/zglos-problem-online).
3. It is recommended to cease use of a defective appliance. 4. The User is obligated to provide free access to the appliance (particularly in a manner enabling
removal of the appliance’s housing, access to valves). 5. Guarantee repairs will be performed by the Guarantor or by a specialized company indicated by
the Guarantor. 6. Performance of the obligations arising from the guarantee will occur within 14 work days,
counting from the date on which the appliance is made available (at the place of its installation) by the User.
7. The User arranges the date on which the appliance is to be made available with the Guarantor. 8. Depending on the scope of repair, it may be performed at the User’s location, at the place
where the appliance is installed, or at the establishment of the Guarantor or specialized company performing activities in the Guarantor’s name.
9. Repair performed under the guarantee is to be confirmed on the guarantee card. 10. The guarantee is extended by the time during which the user was unable to use the appliance
due to a defect of the appliance covered by the guarantee. 11. The guarantee does not exclude, limit or suspend the buyer’s rights arising from laws
concerning guarantees on defects of a sold object.
35
Confirmation of performance of inspection, guarantee repair, maintenance service:
Item no.
Date of performance Description of performed activities Contractor’s signature and seal
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
37
Conformity declaration WE/UE
1. Manufacturer: METAL-FACH Jacek Kucharewicz Ul. Sikorskiego 66 16-100 Sokółka NIP 545-100-10-62
2. Product name and intended use Solid fuel steel central heating boiler with automatic feeder. Type SEG / SEG PLUS…………………………………………. Manufacturer’s number……………………..………………………………. Year of production 20………………………………………………………….
Relevant documents: 1. Act of 19 April 2016 on conformity assessment and market monitoring systems (Journal of Laws item 542).
Electromagnetic compatibility directive -2014/30/UE 2. Regulation of the Polish Minister of Economy of 21.10.2008 on the essential requirements of mechanical devices ( Polish Journal of Laws no. 199 item 1228) with change published in Polish Journal of Laws 2011
no. 124 item 701. Directive 2006/42/WE Machinery.
Technical documentation: 1. Norm PN-EN 303-5:2012: Heating boilers for solid fuels, hand and automatically stocked of nominal power of 500 kW. 2. Norm PN EN ISO 12100:2012 Safety of machinery –Basic concepts, principles for design – part 1: Basic terminology, Methodology. 3. Norm PN EN 1708-1:2010 Welding — Basic welded joint details in steel Part 1: Pressurized components 4. Norm PN EN ISO 9606-1:2014-02 Welder Approval Testing.Steel 5. Norm PN-EN 60335-2-102 Household and similar electrical appliances. Safety. General requirements 6. Norm PN EN 60335-2-102:2006/A1:2010 Household and similar electrical appliances. Safety. General requirements of gas, oil and solid fuel burning devices with electrical connections. 7. Norm PN EN 61000-6-2:2008 on electromagnetic compatibility (EMC)-Part 6-3 General norms- Reistance in industrial environments 8. Norm PN EN 61000-6-3:2008/A1:2012 on electromagnetic compatibility (EMC)-Part 6-3 General norms-Emission norms in environments: habitated, retail and of low industry
The product has the marks
Person approving the documentation: Location: Sokółka Date 12.2015 Włodzimierz Lewko (Name, Surname, Signature)
Location: Sokółka Date 12.2015 Jacek Kucharewicz
(Name, Surname, Signature)
39
Warranty Card for the steel boilers, central heating water boilers
Power: ……………………………………….……………. [kW]
Type: ……………………………………………………………. Number: ……………………………………………………………….
Production date: ……………………………………….……………………………………….……………………………………….………………………………………………………………………………………………..………. Purchase date: ……………………………………….……………………………………….……………………………………….…………………………………………………………………………………………………..……... Buyer’s name: ………………………..……………………………………….……………………………………….……………………………………….………………………………………………………………………………… Address: ……………………………………….……………………………………….……………………………………….……………………………………….……………………………………………………………………
………………………………………. Date of purchase and seal
………………………………………. I agree to the warranty conditions
Buyer’s signature
Personal data given in this form are processed by Jacek Kucharewicz, conducting economic activity under the company name Metal Fach Jacek Kucharewicz, 16-100 Sokółka, ul. Sikorskiego 66, NIP (Taxpayer Identification Number): 545-100-10-62, telephone number +48 85 711 94 for the purpose of performing the provisions set forth in the guarantee terms - pursuant to the act of 29 August 1997 on personal data protection (consolidated text: Journal of Laws of 2014, item 1182). The User has the right to access their personal data, correct them, demand cessation of processing of their personal data, as well as to raise an objection against processing of data in cases specified by the law. Any correspondence concerning processing of personal data is to be addressed to: Metal Fach Jacek Kucharewicz, 16-100 Sokółka, ul. Sikorskiego 66. Providing personal data is voluntary. Pursuant to the act of 29 August 1997 on personal data protection (consolidated text: Journal of Laws of 2014, item 1182), we hereby inform that the personal data given in this form will be subject to protection against access by unauthorized persons.
41
Warranty claim
Client's details: ………………………………………………………………………………… ………………………………………………………………………………….………………
(first name, second name, address, contact number) Purchase document number: date: …………………………………………………………… Payment document number: ………..……….………………………………………………. Seller’s signature: …………………………………………………………………………
Batch and product number: …………………………………….………………………… ………………………………….………….……………………………………………… Name of the product under warranty: ……………………………………………… …………………………………………………………………………………………………. Warranty period:: valid invalid Detailed description of the fault: ………………………………………………………………….. …………………………………………………………………………………………………. ………………………………………………………………………………………………….
Warranty comencement conditions: 1. Payment confirmation from the point of sale is the condition of warranty procedure comencement. 2. The warranty card is the only condition for free repair. 3. A person filing a claim assumes the obligation to reimburse expenses incurred by METAL FACH Jacek Kucharewicz in the event of an unjustified call of the service team or failure to meet the conditions specified
in points 1 or 2 (net cost of every commenced hour of one service technician’s work - PLN 70, net travel cost PLN 1/km in both directions). 4. Legible signature of the Purchaser to confirm the familiarisation with the warranty procedure conditions
………………………………………………………………………… ………………………………………………………………………… (legible signature of Purchaser) (Warrant's signature)
I declare, that I have read and understood the Warranty Conditions under which I am claiming warranty and I allow my personal data to be processed for the purpose of warranty, in accordance with the Personal
Data Protection Act dated 29/08/1997 (Dz. Ust. No. 133, item 883).
………………………………………………………………………… (legible signature of Purchaser)
The Producer is obligated to take warranty actions within 14 days from receiving the claim in writing on the producer’s form. Personal data given in this form are processed by Jacek Kucharewicz, conducting economic activity under the company name Metal Fach Jacek Kucharewicz, 16-100 Sokółka, ul. Sikorskiego 66, NIP (Taxpayer
Identification Number): 545-100-10-62, telephone number +48 85 711 94 for the purpose of performing the provisions set forth in the guarantee terms - pursuant to the act of 29 August 1997 on personal data protection (consolidated text: Journal of Laws of 2014, item 1182). The User has the right to access their personal data, correct them, demand cessation of processing of their personal data, as well as to raise an objection against processing of data in cases specified by the law. Any correspondence concerning processing of personal data is to be addressed to: Metal Fach Jacek Kucharewicz, 16-100 Sokółka, ul. Sikorskiego 66. Providing personal data is voluntary. Pursuant to the act of 29 August 1997 on personal data protection (consolidated text: Journal of Laws of 2014, item 1182), we hereby inform that the personal data given in this form will be subject to protection against access by unauthorized persons.
43
Start-up report
(Owner’s copy)
In order to verify your purchase and warranty validity please send the report on the start-up within 30 days. You can do it by:
1. E- mailing the scan or photo of the report. 2. Sending a letter with the copy of the report, the company's address can be found at the
end of the manual.
Boilre room Valid Invalid Comments
In compliance with the conditions of chapter 12. Boiler room and boiler installation requirements
In compliance with the conditions of chapter 19. Connecting the boiler to the chimney
Central heating system Valid Invalid Comments
In compliance with the conditions of chapter 15 Connecting the boiler to the heating system
In compliance with the conditions of chapter 17. Expansion vessel requirements
There is no other heating source. If there is, how does it affect the operation of the boiler?
Anti-freeze protection of the boiler
Connecting the components to the electrical system
Valid Invalid Comments
The conditions are in accordance with the Operation and Mainteneance Documentation in the chapter: 18. Connecting the components to the electrical system.
Components test Valid Invalid Comments
The sensors are placed in the correct places.
The readings are in accordance with the actual state.
The fan rotation is correct.
Opening the blower door with blow power.
The screw rotation is correct.
Boiler start-up Valid Invalid Comments
The hydraulic connection to the system is tight.
Fireman/Strażak system test (if installed)
Checking the connection between the fuel feeder and boiler.
Stoking fuel to the fuel bin.
Checking the coal feed by the feeder
Boiler start-up in accordance with chapter 21. Boiler start-up
20
Initial regulation of the boiler parameters settings.
Final regulation of the boiler parameters settings.
Personal data given in this form are processed by Jacek Kucharewicz, conducting economic activity
under the company name Metal Fach Jacek Kucharewicz, 16-100 Sokółka, ul. Sikorskiego 66, NIP (Taxpayer Identification Number): 545-100-10-62, telephone number +48 85 711 94 for the purpose of performing the provisions set forth in the guarantee terms - pursuant to the act of 29 August 1997 on personal data protection (consolidated text: Journal of Laws of 2014, item 1182). The User has the right to access their personal data, correct them, demand cessation of processing of their personal data, as well as to raise an objection against processing of data in cases specified by the law. Any correspondence concerning processing of personal data is to be addressed to: Metal Fach Jacek Kucharewicz, 16-100 Sokółka, ul. Sikorskiego 66. Providing personal data is voluntary. Pursuant to the act of 29 August 1997 on personal data protection (consolidated text: Journal of Laws of 2014, item 1182), we hereby inform that the personal data given in this form will be subject to protection against access by unauthorized persons.
44
The set parameters of the boiler parameters (chapter 23. Recommended settings of the boiler power)
Boiler: Boiler operation mode: Required temperature: Boiler hysthesis:
System password:
Burner: Fuel:: Stand-by maintaining: Operation maintaining: Blower outlet: Antilock: Test mode power: Feeding 100%: Initial stoking: Ignition: Blower+ Ignitor: Fire test: Initial power: Burn out:
Blow: Blow 100%: Blow 80%: Blow 60%: Blow 40%: Blow 20%: Starting power: Sustain power:
User's training certificate on YES NO Comments
Start-up date
………………………..
Boiler name
………………………..
Boiler power (kW)
………………………..
Serial number
………………………..
Training on safe operation of the boiler is included in chapter 22. When operating the boiler you should remember
……………………………………………………. (TECHNICIAN’S NAME)
……………………………………………………. (ADDRESS)
……………………………………………………. (COMPANY SEAL)
……………………………………………………. (OWNER’S NAME)
……………………………………………………. (ADDRESS)
……………………………………………………. CONTACT NUMBER
Training on boiler regulator and combustion control.
Blower rpm
Boiler maintenance chapter 23. Cleaning and maintenance of the boiler
Required fuel quality chapter 11. Fuel
……………………………………………………. (SIGNATURE)
……………………………………………………. (SIGNATURE)
Procedure to follow in emergency situation 26. Examples of device faults and malfunctions
45
Start-up report
(METAL FACH Jacek Kucharewicz company's copy)
In order to verify your purchase and warranty validity please send the report on the start-up within 30 days. You can do it by:
1. E- mailing the scan or photo of the report. 2. Sending a letter with the copy of the report, the company's address can be found at the
end of the manual.
Boilre room Valid Invalid Comments
In compliance with the conditions of chapter 12. Boiler room and boiler installation requirements
In compliance with the conditions of chapter 19. Connecting the boiler to the chimney
Central heating system Valid Invalid Comments
In compliance with the conditions of chapter 15 Connecting the boiler to the heating system
In compliance with the conditions of chapter 17. Expansion vessel requirements
There is no other heating source. If there is, how does it affect the operation of the boiler?
Anti-freeze protection of the boiler
Connecting the components to the electrical system
Valid Invalid Comments
The conditions are in accordance with the Operation and Mainteneance Documentation in the chapter: 18. Connecting the components to the electrical system.
Components test Valid Invalid Comments
The sensors are placed in the correct places.
The readings are in accordance with the actual state.
The fan rotation is correct.
Opening the blower door with blow power.
The screw rotation is correct.
Boiler start-up Valid Invalid Comments
The hydraulic connection to the system is tight.
Fireman/Strażak system test (if installed)
Checking the connection between the fuel feeder and boiler.
Stoking fuel to the fuel bin.
Checking the coal feed by the feeder
Boiler start-up in accordance with chapter 21. Boiler start-up
20
Initial regulation of the boiler parameters settings.
Final regulation of the boiler parameters settings.
Personal data given in this form are processed by Jacek Kucharewicz, conducting economic activity
under the company name Metal Fach Jacek Kucharewicz, 16-100 Sokółka, ul. Sikorskiego 66, NIP (Taxpayer Identification Number): 545-100-10-62, telephone number +48 85 711 94 for the purpose of performing the provisions set forth in the guarantee terms - pursuant to the act of 29 August 1997 on personal data protection (consolidated text: Journal of Laws of 2014, item 1182). The User has the right to access their personal data, correct them, demand cessation of processing of their personal data, as well as to raise an objection against processing of data in cases specified by the law. Any correspondence concerning processing of personal data is to be addressed to: Metal Fach Jacek Kucharewicz, 16-100 Sokółka, ul. Sikorskiego 66. Providing personal data is voluntary. Pursuant to the act of 29 August 1997 on personal data protection (consolidated text: Journal of Laws of 2014, item 1182), we hereby inform that the personal data given in this form will be subject to protection against access by unauthorized persons.
46
The set parameters of the boiler parameters (chapter 23. Recommended settings of the boiler power)
Boiler: Boiler operation mode: Required temperature: Boiler hysthesis:
System password:
Burner: Fuel:: Stand-by maintaining: Operation maintaining: Blower outlet: Antilock: Test mode power: Feeding 100%: Initial stoking: Ignition: Blower+ Ignitor: Fire test: Initial power: Burn out:
Blow: Blow 100%: Blow 80%: Blow 60%: Blow 40%: Blow 20%: Starting power: Sustain power:
User's training certificate on YES NO Comments
Start-up date
………………………..
Boiler name
………………………..
Boiler power (kW)
………………………..
Serial number
………………………..
Training on safe operation of the boiler is included in chapter 23. When operating the boiler you should remember
……………………………………………………. (TECHNICIAN’S NAME)
……………………………………………………. (ADDRESS)
……………………………………………………. (COMPANY SEAL)
……………………………………………………. (OWNER’S NAME)
……………………………………………………. (ADDRESS)
……………………………………………………. CONTACT NUMBER
Training on boiler regulator and combustion control.
Blower rpm
Boiler maintenance chapter 24. Cleaning and maintenance of the boiler
Required fuel quality chapter 13 Fuel
……………………………………………………. (SIGNATURE)
……………………………………………………. (SIGNATURE)
Procedure to follow in emergency situation 27. Examples of device faults and malfunctions
METAL-FACH JACEK KUCHAREWICZ
UL. SIKORSKIEGO 66, 16-100 SOKÓŁKA
TEL. +48 85 711 94 54
WWW.METALFACH.COM.PL
SERVICE INFOLINECALL US
+48 663 453 222
WRITE TO [email protected]